The document is an exhibit detailing utility connections for a VA project at the Palo Alto Health Care System (VAPAHCS). The exhibit provides technical specifications for infrastructure requirements, including drainage, water supply, and electrical connections for a site preparation project involving trash compactor modifications and a cart wash station installation.
Key technical details include provisions for a floor drain connection to sanitary sewer, a 1" water line supply for a steam machine, and electrical power requirements of 480V/3-Phase/100A and 120V/1-Phase/15A. The project involves coordinating power sources with multiple ongoing projects at the loading dock, with existing 30A, 480V trailer disconnects potentially available for repurposing. The related solicitation (36C26125R0089) is specifically for VISN 21 Multiple-Award Construction Contract (MACC) Group 2 contractors, with a mandatory site visit scheduled for October 2nd, 2025, at 9:00 AM PDT at Building 100 Lobby in Palo Alto, California.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AV PAHCS
Exhibit 06 - Utility Connections
Floor drain in utility space can potentially be tapped for drainage
Contractor to provide drain line from condensate tank w/ 2" flange to sanitary sewer.
Contractor to determine POC
Trench drain has conduits running above it.
Trench drain to sanitary sewer runs along loading dock.
external hose
Existing domestic cold water line in utility space feeds external hose. Could be split to provide water for steam machine.
1" water line supply required for steam machine.
Electrical Panels 100-NMCC00A and 100-QMCC00A located on the other side of concrete wall.
Contractor to coordinate power source with multiple ongoing projects at the loading dock.
(2) existing 30A, 480V trailer disconnects at side of loading dock fed from 100-QMCC00A.
May be able to repurpose.
480V/3-Phase/100A and 120V/1-Phase/15A required for steam machine and control panel.