ESBD_484259_1770149331704_EXHIBIT B - Burnet Annex on the Square_MEP_R1.pdf

PDF 8 MB Posted

Attached to
RE-BID LIFT INSTALLATION
Solicitation number
26-4090-05
Issued by
Brazos County, Texas

About this file

This is an electrical design and specifications document for the Burnet County Annex renovation project located at 127 E. Jackson Street, Burnet, Texas 78611, prepared by Capital Consulting Engineers and Levy Dykema. The document serves as Exhibit B to the project bid package and provides comprehensive mechanical, electrical, plumbing (MEP), and related systems specifications and design plans. The scope encompasses the complete electrical installation for a two-story county office building, including main service equipment rated at 400 amperes at 208/120 volts, three-phase power distribution through panelboards P1 (400A), P2 (200A), and PG (100A), lighting systems with LED fixtures and occupancy sensors, fire alarm and detection systems (Simplex manufacturer), communications infrastructure with Category 6 cabling and fiber backbone, security and access control systems, HVAC equipment power and controls, emergency power generation capabilities via a 25-kilowatt Generac generator with automatic transfer switch, elevator machinery room systems, and associated branch circuit wiring and controls. The document includes detailed schedules, legends, symbols, one-line diagrams, lighting plans for both floors, power plans, HVAC power plans, grounding electrode systems, conduit routing specifications, and typical installation details addressing code compliance with the 2020 National Electrical Code, local amendments adopted by the City of Burnet and State of Texas, and standards from NFPA, IEEE, UL, NEMA, and ASTM.

The specifications establish mandatory compliance with all local, state, and national electrical codes and industry standards, require all work to be performed by skilled craftsmen in a workmanlike manner, and stipulate that the electrical contractor shall provide all labor, materials, equipment, permits, and licenses necessary for complete system installation. The contractor is responsible for field verification of conditions, coordination with all other trades, protection of existing systems, and delivery of as-built documentation and three-copy maintenance manuals upon project completion. All electrical equipment must be new, UL-listed, and properly labeled; conductors must be copper THWN-2 with minimum #12 AWG for light and power circuits and #14 AWG for control wiring; and all work is guaranteed against defective materials and workmanship for a minimum of one year from the date of substantial completion. The document does not specify pricing, funding sources, set-asides, incumbent vendors, or contract award dates, as it functions as a technical design and specification guide rather than a procurement document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FINISHED CEILING

FINISHED FLOOR

BOD

BOD

BOD

COD

COD

AC = ABOVE COUNTER,

MINIMUM 4" ABOVE

BACKSPLASH TO BOTTOM OF

DEVICE.

48" TOD IS ACCEPTABLE FOR

CMU BLOCK CONSTRUCTION.

M

IN

IM

U

M T

O B

O T

T O

M O

F D

E V

IC

E

M O

U N

T

A

B O

V E

D O

O R

F R

A M

E

T O

T O

P O

F T

R

IM

M

IN

IN

H A

Z A

R D

O U

S L O

C A

T

IO

N S

-T O

B O

T T

O M

O F

C A

N 8

A F

F T

O B

O T

T O

M O

F D

E V

IC

E

O R

B E

L O

W C

E

IL

IN

G

T O

T O

P O

F D

E V

IC

E

W H

IC

H

E V

E R

I S

L O

W E

R

FIR

E

FIR

E

C S F F F

FIRE

F KPS

D

ADDITIONAL MOUNTING HEIGHTS

44" COD.CB

EPB

EPC

PANEL

BOARD

44" COD.

44" COD.

44" COD.

44" COD.

W

T CO₂

INTERIOR BOX MOUNTING HEIGHTS

ABOVE COUNTER, 4" BACK SPLASHAC

AUTOMATIC TRANSFER SWITCHATS

ABOVE FINISHED GRADEAFG

ABOVE FINISHED FLOORAFF

BELOW GRADEBLG

BOTTOM OF DEVICEBOD

CONDUITC

STROBE (NUMBER INDICATES CANDELA RATING)

SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING)

SPEAKER

MANUAL PULLSTATION

IPS INDOOR PROTECTIVE SHIELD

MAGNETIC DOOR HOLDER, BY DIV 28

FIRE/SMOKE DAMPER

SMOKE DETECTOR, SMOKE DETECTOR WALL MOUNTED

HEAT DETECTOR, HEAT DETECTOR WALL MOUNTED

CONNECTION TO TAMPER SWITCH, SWITCH BY OTHERS

CONNECTION TO FLOW SWITCH, SWITCH BY OTHERS

CONNECTION TO PRESSURE SWITCH, SWITCH BY OTHERS

BEAM DETECTOR TRANSMITTER

BEAM DETECTOR RECEIVER

DUCT SMOKE DETECTOR

FIRE ALARM REMOTE ANNUNICATOR

FIRE ALARM CONTROL PANEL

M

F

F

F

F

FSD

SD SD

HD HD

TS

FS

PS

BD

BD

SD

FARA

FACP

SYMBOL DESCRIPTION

LAY-IN OR RECESSED FIXTURE, SIZE ON PLANS

WALL MOUNTED FIXTURE, SIZE ON PLANS

SURFACE MOUNTED FIXTURE, SIZE ON PLANS

PENDANT OR SURFACE MOUNTED FIXTURE, SIZE ON PLANS

RECESSED DOWNLIGHT FIXTURE

SURFACE MOUNTED FIXTURE

WALL MOUNTED FIXTURE

CEILING MOUNTED, WALL MOUNTED EXIT

LIGHT (W/ DIRECTIONAL ARROWS)

ROUND POLE MOUNTED FIXTURE, EXTERIOR

DIRECTIONAL INGROUND FIXTURE, EXTERIOR

PENDANT MOUNTED FIXTURE, SIZE ON PLANS

SHADED FIXTURE INDICATES FIXTURE IS UNSWITCHED

AND ALSO INDICATES EMERGENCY POWER.

WALL WASH OR DIRECTIONAL FIXTURE

WALL SCONCE FIXTURE

TRACK FIXTURE, SEE PLAN FOR SIZE AND HEADS

CEILING FAN FIXTURE

1 HEAD REMOTE EMERGENCY LIGHT

2 HEAD EMERGENCY LIGHT BATTERY PACK

1 HEAD REMOTE EMERGENCY LIGHT BATTERY PACK

2 HEAD LIGHT WITH MOTION SENSOR

SQUARE POLE MOUNTED FIXTURE, EXTERIOR

POST TOP FIXTURE, EXTERIOR

BOLLARD FIXTURE, EXTERIOR

CATV JACK, WALL MOUNTED

MICROPHONE OUTLET

SPEAKER, SPEAKER WALL MOUNTED

CLOCK HANGER RECEPTACLE

VOICE OUTLET - WALL MOUNTED

VOICE/DATA OUTLET MOUNTED IN FLOORBOX - SUBSCRIPT

INDICATES NUMBER OF CABLES/JACKS - NO SUBSCRIPT

INDICATES 2 CABLES/JACKS

C

SS

E

VOICE/DATA OUTLET - SUBSCRIPT INDICATES NUMBER OF

CABLES/JACKS - NO SUBSCRIPT INDICATES 2 CABLES/JACKS

EXISTING VOICE/DATA OUTLET

W

DATA RACK

F SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING),

CEILING MOUNTED

FIRE ALARM SIGNAL EXTENDER PANELFASP

CARD ACCESS SYSTEMCAS

CLOSED CIRCUIT TVCCTV

CEILINGCLG

CENTER OF DEVICECOD

COPPERCU

DIGITAL VIDEO RECORDERDVR

EXISTING(E)

ELECTRICAL CONTRACTOREC

EXHAUST FANEF

GENERAL CONTRACTORGC

GROUNDGND

FIELD ADJUSTABLE LONG TIME, SHORT TIME AND

INSTANTANEOUS

LSI

FIELD ADJUSTABLE LONG TIME, SHORT TIME,

INSTANTANEOUS AND GROUND FAULT

LSIG

MECHANICAL CONTRACTORMC

NEW(N)

NIGHT LIGHTNL

PAN-TILT-ZOOMPTZ

QUANTITYQTY

RELOCATED(R)

SURFACESF

TELECOMMUNICATIONS MAIN GROUNDING BUS BARTMGB

TELECOMMUNICATIONS BONDING BACKBONETBB

TEMPERATURE CONTROL CONTRACTORTC

TELEPHONE TERMINAL BOARDTTB

TYPICALTYP

UNDERGROUNDUG

UNLESS OTHERWISE NOTEDUON

WITHW/

WIRE MOLDWM

WEATHER PROOF (WHILE IN USE)WP

TRANSFORMERXFMR

SWITCH DESIGNATIONa,b,c etc

CIRCUIT DESIGNATION, PANEL BN1L, CIRCUITS 2,4,6BN1L-2,4,6

INDICATES DETAIL 1 ON SHEET E5011/E501

1 SHEET WORK NOTE

HOME RUN TO PANEL

CONDUIT CONCEALED IN CEILING OR WALL

CONDUIT CONCEALED UNDER FLOOR

LOW VOLTAGE CIRCUIT

FIBER OPTIC CABLE

CABLE TRAY

CIRCUIT, NUMBER OF HASH MARKS INDICATES NUMBER OF

CONDUCTORS IN CABLE/RACEWAY. GROUND WIRE IS NOT

SHOWN BUT SHALL BE INCLUDED. NO HASH MARKS

INDICATES 2 CONDUCTORS PLUS GROUND.

LV

1 SHEET DEMO WORK NOTE

CR CARD READER

DC

MRX

PS

CAMERA, CEILING AND WALL MOUNTED DOME, FIXED

CAMERA, CEILING AND WALL MOUNTED DOME, PTZ

CAMERA, CEILING MOUNTED, 360 DEGREE

CAMERA

DVR

SPS

DIGITAL VIDEO RECORDER

SURVEILLANCE POWER SUPPLY

M MONITOR

A

LX

PRX

ML

DPS

ES

EL

AO

FA

SPEAKER SIGNAL DEVICE

DOOR CONTROLLER

MOTION SENSOR REQUEST TO EXIT

POWER SUPPLY W/BATTERY, BY DIV 8, INSTALLED AND

CONNECTED BY DIV 27

CONNECTION TO REQUEST TO EXIT & LATCH BOLT

MONITORING

CONNECTION TO PANIC REQUEST TO EXIT

CONNECTION TO MAGNETIC DOOR LOCK

CONNECTION TO MAGNETIC DOOR POSITION SWITCH

CONNECTION TO ELECTRIC DOOR STRIKE

CONNECTION TO ELECTRIC LATCH

CONNECTION TO ELECTRIC AUTO OPENER

CONNECTION TO FIRE ALARM CONTACT

INDICATES SECURITY DOOR 1

PANEL

SCP SECURITY CONTROL PANEL

SDC SECURITY DOOR CONTROLLERS

KP KEYPAD

PT POWER TRANSFER SWITCH

SWITCH - SPST

2 SINGLE POLE, DOUBLE THROW

3 THREEWAY

4 FOURWAY

K KEY OPERATED

P PILOT LIGHT

WP WEATHERPROOF

OS OCCUPANCY SENSOR (DUAL TECHNOLOGY)

D DIMMER

MC SPOT-MOMENTARY CONTACT

LV LOW VOLTAGE

T TIMER SWITCH

TS TEST SWITCH

VS VACANCY SENSOR (DUAL TECHNOLOGY) WITH DIMMING

OCCUPANCY SENSOR SWITCH (CEILING) - SUBSCRIPT IS

TYPE

OS

RECEPTACLE - SIMPLEX

RECEPTACLE - DUPLEX

GFI RECEPTACLE - DUPLEX (GROUND FAULT INTERRUPT)

D DEVICE RECEPT W/2 USB PORTS

DC DROP CORD

WP WEATHERPROOF COVER & WEATHER

RESISTANT RECEPTACLE

TR TAMPER RESISTANT

S SURGE PROTECTED

IG ISOLATED GROUND

FILLED CENTER INDICATES HOSPITAL GRADE

EMERGENCY RECEPTACLE

RECEPTACLE - DOUBLE DUPLEX

GFI RECEPTACLE - DOUBLE DUPLEX

- SAME INDICATORS AS SHOWN FOR DUPLEX RECEPTACLE

RECEPTACLE - 208V

R RANGE - NEMA 14-50R

D DRYER - NEMA 10-30R

W WELDER - NEMA 14-50R

* NEMA CONFIGURATION AS NOTED

208V RECEPTACLE IN RECESSED FLOORBOX

DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX

DOUBLE DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX

J-BOX - BOX INDICATES FLOOR MOUNTING -4"X4"X2-1/8" DEEP

UNLESS OTHERWISE NOTED

SPECIAL PURPOSE CONNECTION - BOX INDICATES FLOOR

MOUNTING - WORK AS NOTED

RECEPTACLE - DUPLEX, MOUNTING IN CEILING

MANUAL MOTOR DISCONNECT/STARTER SWITCH

COMBINATION STARTER/DISCONNECT SWITCH

DISCONNECT SWITCH

CONTACTOR

ELECTRIC MOTOR CONNECTION

EMERGENCY PUSHBUTTON

PC PHOTOCELL, PHOTOCELL WALL MOUNTEDPC

EXISTING PANELBOARD, SURFACE MOUNTED

EXISTING PANELBOARD, FLUSH MOUNTED

TIME CLOCK

M ELECTRIC METER, BUILDING MOUNTED

TRANSFORMER, INTERIOR

or

VARIABLE FREQUENCY DRIVE

J JJ

CLG

CO₂

THERMOSTAT/TEMPERATURE SENSOR BY MC OR TC, J-BOX

AND CONDUIT TO CEILING BY EC

CARBON MONOXIDE DETECTOR BY MC, J-BOX & CONDUIT TO

CEILING BY EC

PP POWER POLE

R RELAY

CIRCUIT BREAKER

CONTROL PANEL

LRP LIGHTING RELAY PANEL

TCP TEMPERATURE CONTROL PANEL

GAP GENERATOR ANNUNCIATOR PANEL

PACP PA CONTROL PANEL

MGA MED GAS ALARM PANEL

PANELBOARD, SURFACE MOUNTED

PANELBOARD, FLUSH MOUNTED

TRANSFORMER, EXTERIOR

CLG

GFI RECEPTACLE - DUPLEX, MOUNTING IN CEILING

M

T

TC

VFD

LIGHTING

ELECTRICAL LEGEND

SYMBOL DESCRIPTION

FIRE ALARM

SYMBOL DESCRIPTION

COMMUNICATIONS

SYMBOL DESCRIPTION

ABBREVIATIONS AND MISCELLANEOUS

SYMBOL DESCRIPTION

SURVEILLANCE SYSTEM

DESCRIPTION

SECURITY SYSTEM

SYMBOL

SYMBOL DESCRIPTION

DEVICES AND POWER

REX MANUAL REQUEST TO EXIT

DS DOOR SWITCH CONTACT

CATV JACK CEILING MOUNTEDCLG

WIRELESS ACCESS POINT, WIRELESS ACCESS POINT WALL

MOUNTED - 2 CABLES/JACKS

WAP WAP

SECURITY CAMERA

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

ALL WORK SHALL BE PERFORMED PER 2020 NEC, AND ALL WORK SHALL BE PERFORMED IN

COMPLIANCE WITH THE LATEST EDITION OF ALL LOCAL AMENDMENTS AND REGULATIONS AS

ADOPTED BY THE CITY OF BURNET AND THE STATE OF TEXAS, AND THE PUBLICATIONS AND

STANDARDS OF THE FOLLOWING AUTHORITIES, IN ADDITION TO THOSE SPECIFIED IN

RELATED SUPPLEMENTARY CONDITIONS, WHICH ARE REFERENCED IN ELECTRICAL

SPECIFICATIONS BY THE ABBREVIATIONS NOTED.

UNITED STATES OF AMERICA STANDARDS INSTITUTE - USASI INSTITUTE OF ELECTRICAL AND

ELECTRONIC ENGINEERS - IEEE NATIONAL ELECTRICAL CODE - NEC NATIONAL FIRE

PROTECTION ASSOCIATION - NFPA UNDERWRITER'S LABORATORIES - UL NATIONAL

ELECTRICAL MANUFACTURERS ASSOCIATION - NEMA AMERICAN SOCIETY OF TESTING

MATERIALS - ASTM OCCUPATIONAL SAFETY AND HEALTH ACT - OSHA

ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, PLANS AND

THE SPECIFICATIONS, AND SHALL BE PERFORMED WITH THE LATEST INDUSTRY ACCEPTED

STANDARDS.

THE INTENT OF THIS CONSTRUCTION PACKAGE IS TO ILLUSTRATE ALL THE WORK TO BE

ACCOMPLISHED TO PROVIDE AN ELECTRICAL INSTALLATION COMPLETE IN EVERY RESPECT.

CARE HAS BEEN TAKEN TO INDICATE THE COMPLETE SCOPE OF WORK REQUIRED FOR THIS

PROJECT, HOWEVER, IT IS NOT THE INTENT TO INDICATE EVERY CONFLICT WHICH MAY

ARISE, AND PROVIDE FOR SUCH ON THESE DOCUMENTS. NO ASSURANCE IS GIVEN THAT

THE PLANS COMPLETELY REFLECT ACTUAL JOB SITE CONDITIONS. IF IT IS DISCOVERED IN

THE FIELD THAT ACTUAL LOCATIONS OR CONDITIONS DIFFER GREATLY FROM THOSE

SHOWN, CONTRACTOR SHALL GET APPROVAL FROM OWNER PRIOR TO COMMENCING

WORK.

CONTRACTOR SHALL VISIT THE SITE AND FIELD VERIFY THE PROPOSED INSTALLATION

LOCATION AND ALL WORKING CONDITIONS SUCH AS STARTING TIME, NOISE LIMITATIONS,

CONFINED SPACE LIMITATIONS, OFFSETS AND ROUTING ADJUSTMENTS THAT MAY BE

REQUIRED, ETC., TO COMPLETE THE WORK. CONTRACTOR SHALL COORDINATE WITH THE

OWNER REGARDING OBSTRUCTION OF ROADWAY OR DRIVEWAY AREAS, ON SITE

MATERIALS AND EQUIPMENT STORAGE, AND BUILDING ACCESS. SITE INSPECTION SHALL

DETERMINE CONDITION OF EXISTING ELEMENTS TO REMAIN AND BE PROTECTED.

CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING ALL

WORK DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, AND

MISALIGNMENT ACCORDING TO APPLICABLE CODES, STANDARDS, AND GOOD

CONSTRUCTION PRACTICES. CONTRACTOR SHALL TAKE PROPER PRECAUTIONS TO

PROTECT ALL EXISTING OPERATIONS AND PROPERTY ADJACENT WITH WHICH WORK COMES

IN CONTACT, OR OVER OR UNDER WHICH HE MAY TRANSPORT, HOIST, OR MOVE

MATERIALS, EQUIPMENT, DEBRIS, ETC. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR

AND/OR REPLACEMENT IN KIND OF ALL INADVERTENT DAMAGE TO EXISTING SYSTEMS.

ALL NECESSARY PERMITS, LICENSES, CERTIFICATES, TESTS, ETC., SHALL BE PROCURED AND

PAID FOR BY THE CONTRACTOR.

THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION INSTALLATION DIMENSIONS.

ALL CONDUIT ROUTING ARE SHOWN IN APPROXIMATE LOCATIONS ONLY. THE CONTRACTOR

SHALL BE RESPONSIBLE FOR FIELD VERIFICATION OF CONDITIONS, AND SHALL PERFORM

FIELD MEASUREMENTS PRIOR TO FABRICATION AND/OR PURCHASE OF ANY EQUIPMENT

AND MATERIAL. REFERENCE ALL DETAILS FOR ADDITIONAL CONSTRUCTION

REQUIREMENTS. DETAILS MAY NOT BE REFERENCED ON THE DRAWING(S), BUT ARE

INTENDED TO BE TYPICAL THROUGHOUT UNLESS OTHERWISE NOTED.

DO NOT BEGIN WORK IF ANY DISCREPANCIES OR CONFLICTS EXIST OR ARE DISCOVERED

BETWEEN SYSTEMS, UTILITIES, UNTIL THE DISCREPANCIES HAVE BEEN RESOLVED.

IMMEDIATELY CALL SUCH DISCREPANCIES OR CONFLICTS TO THE ATTENTION OF THE

OWNER'S CONSTRUCTION REPRESENTATIVE AND/OR ENGINEER. SHOULD ANY CONFLICTS

OR AMBIGUITIES EXIST IN THE DRAWINGS, NOTES, OR SPECIFICATIONS, BRING THESE TO

THE ATTENTION OF THE ENGINEER IMMEDIATELY BEFORE PROCEEDING WITH WORK.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING FULL COORDINATION WITH

ALLTRADES TO ACCOMPLISH THE WORK AS INDICATED AND NOTED IN CONTRACT

DOCUMENTS. COORDINATE WITH OWNER'S REPRESENTATIVE, AND MAINTAIN A SET OF ALL

CHANGES BETWEEN THE DRAWINGS AND THE ACTUAL CONSTRUCTION. CONFLICTS ARISING

DUE TO LACK OF COORDINATION SHALL BE THE RESPONSIBILITY OF, AND AT THE EXPENSE

OF, THE CONTRACTOR. FINAL AS-BUILT DRAWINGS ARE TO BE DELIVERED TO THE

OWNER/ENGINEER AND THE FINAL INVOICE FOR THE CONTRACT WILL NOT BE PAID UNTIL

THESE AS-BUILT DRAWINGS ARE RECEIVED.

WORK AREAS ARE TO BE KEPT FREE OF DEBRIS AT ALL TIMES AND ARE TO BE LEFT BROOM

CLEAN AT THE END OF EACH WORKING DAY. THE CONTRACTOR SHALL DISPOSE OF OFF-

SITE, ALL MATERIALS REMOVED WHICH ARE NOT BE REINSTALLED OR SALVAGED ON THE

PROJECT, UNLESS DIRECTED OTHERWISE BY OWNER. DISPOSAL OF MATERIAL SHALL BE IN

ACCORDANCE WITH ACCEPTABLE METHODS APPROVED BY OWNER AND COORDINATED

THROUGH OWNER'S COORDINATOR.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE RATING OF ALL

PENETRATIONS THROUGH FIRE AND SMOKE RATED SURFACES. THE CONTRACTOR SHALL

COMPLY WITH UL LISTING INSTRUCTIONS FOR PENETRATIONS THROUGH RATED SURFACES.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR TRAINING OF HIS EMPLOYEES AND

SUBCONTRACTORS IN THE RECOGNITION AND AVOIDANCE OF UNSAFE CONDITIONS, AND IN

THE REGULATIONS AND HAZARDS WHICH APPLY TO THE AREA IN WHICH THE WORK WILL

TAKE PLACE. ALL SAFETY EXPOSURES OR VIOLATIONS BROUGHT TO THE ATTENTION OF

THE CONTRACTOR SHALL BE RECTIFIED IMMEDIATELY.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING PROTECTION OF PERSONS AND

PROPERTY, AND FOR PROVIDING SAFE WORKING CONDITIONS THROUGHOUT THE WORK

PROCESS. CONTRACTOR SHALL PROVIDE TEMPORARY COVERINGS FOR OPENINGS

THROUGH WALLS OR FLOORS, AND PROVIDE TEMPORARY BARRIERS, PARTITIONS AND OR

DUST BARRIERS WHERE REQUIRED TO MAINTAIN OSHA AND THE OWNER'S SAFETY

STANDARDS AND TO PREVENT DAMAGE TO PROPERTY. ALL AREAS ADJACENT TO THE

CONSTRUCTION AREA OR AFFECTED BY THE CONSTRUCTION MUST BE PROTECTED FROM

DAMAGE, CLEANED AND RESTORED TO THEIR ORIGINAL CONDITION AT THE END OF THE

PROJECT. WELDING BLANKETS SHALL BE UTILIZED FOR PROTECTION OF COMBUSTIBLE

MATERIALS IN AREA WHERE WELDING OR CUTTING WITH A TORCH IS CONDUCTED.

ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP

FOR A PERIOD OF NO LESS THAN ONE (1) YEAR AFTER THE DATE OF SUBSTANTIAL

COMPLETION OR ACCEPTANCE OF THE WORK. THE CONTRACTOR SHALL REPAIR OR

REPLACE, AT HIS OWN EXPENSE WHEN ORDERED TO DO SO, ALL WORK THAT MAY DEVELOP

DEFECTS IN MATERIAL OR WORKMANSHIP WITHIN SAID PERIOD OF TIME. ALL EQUIPMENT

SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS FOR

SERVICE INTENDED. AS INTERPRETED BY THE ENGINEER, THE INSTALLATION OF ALL

EQUIPMENT SHALL BE MADE BY EXPERIENCED CRAFTSMAN IN A NEAT, WORKMANLIKE

MANNER. ALL MATERIALS, TOOLS, COSTS, AND SERVICES NECESSARY TO COMPLETELY

INSTALL ALL ELECTRICAL WORK SHALL BE PROVIDED BY THE CONTRACTOR.

16.

17.

18.

19.

20.

21.

22.

23.

24.

ALL PROPOSED EQUIPMENT INSTALLED ON THIS PROJECT SHALL BE NEW AND UNUSED UNLESS

NOTED OTHERWISE. ALL EQUIPMENT SHALL BE LABELED AND LISTED FOR THE INTENDED USE.

THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL LABELS, DIRT, PAINT SPOTS, GREASE AND

STAINS FROM ALL ELECTRICAL EQUIPMENT AND SHALL CLEAN ALL EQUIPMENT AS NECESSARY.

NO LOOSE PARTS OR SCRAPS OF EQUIPMENT SHALL BE LEFT ON THE PREMISES. EQUIPMENT

LOCATION AND ROUTING IS APPROXIMATE AND SHALL BE PLACED TO PROVIDE PROPER

ACCESS AND CLEARANCE FROM OTHER TRADES AND EQUIPMENT.

ALL WIRING SHALL BE THWN/THHN, 98% CONDUCTIVITY COPPER, STANDARD CONDUCTOR, 600V

INSULATION. ALL WIRING SHALL BE INSTALLED IN RIGID CONDUIT AND CONTINUOUS (WITHOUT

SPLICES).

A GREEN GROUNDING CONDUCTOR SHALL BE PROVIDED WITH ALL BRANCH AND FEEDER

CIRCUITS. SIZE PER N.E.C. 250-122 UNLESS NOTED OTHERWISE. ALSO PROVIDE A SEPARATE

DEDICATED INSULATED AND ISOLATED GROUNDING CONDUCTOR FOR ISOLATED GROUND

CIRCUITS. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION

SHALL BE TESTED AND PROVED TO BE FREE OF UNWANTED GROUNDS AND OTHER DEFECTS.

ALL EXTERIOR CONDUIT SHALL BE RIGID GALVANIZED STEEL CONDUIT. FITTINGS SHALL BE

STEEL THREADED TYPE. MOUNT THE CONDUIT AS HIGH AS POSSIBLE AND RUN PARALLEL AND

PERPENDICULAR TO STRUCTURE. ALL OTHER CONDUIT SHALL BE EMT WITH STEEL

COMPRESSION OR STEEL SET SCREW FITTINGS, 3/4" MIN., UNLESS NOTED OTHERWISE.

KEEP RACEWAYS AT LEAST SIX INCHES AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR

HOT WATER PIPES. INSTALL HORIZONTAL RACEWAY RUNS ABOVE WATER AND STEAM PIPING.

ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL PULL WIRES IN EMPTY RACEWAYS.

USE NO. 14 AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINE HAVING NOT LESS THAN

200-LB TENSILE STRENGTH.

CHANNEL AND ANGLE SUPPORT SYSTEMS, HANGERS, ANCHORS, SLEEVES, AND FASTENERS

SHALL BE DESIGNED TO PROVIDE SECURE SUPPORT FROM THE BUILDING STRUCTURE FOR

ELECTRICAL COMPONENTS. SUPPORTING DEVICES SHALL BE HOT DIPPED GALVANIZED STEEL.

CONFORM TO MANUFACTURER'S RECOMMENDATIONS FOR SELECTING SUPPORTS. SUPPORT

PARALLEL RUNS OF HORIZONTAL RACEWAYS TOGETHER ON TRAPEZE OR BRACKET TYPE

HANGERS.

PULL BOXES SHALL BE GALVANIZED SHEET METAL WITH SCREW-ON COVERS AND WELDED

SEAMS, STAINLESS STEEL NUTS, BOLTS, SCREWS AND WASHERS. BOXES SHALL BE SIZED IN

ACCORDANCE WITH THE NEC.

UNLESS OTHERWISE NOTED ALL 120V SINGLE PHASE CIRCUITS WILL REQUIRE A INDIVIDUAL

NEUTRAL CONDUCTOR - INCLUDING MULTI-CIRCUITS COMBINED IN SINGLE CONDUIT RUNS.

CAPITAL CONSULTING ENGINEERS

CAPCONSULTINGENG.COM TX FIRM # 26531

BUCKLEY H. PARKS

DESNECIL

106223

R E

E

NI

GNELANOISSEF

O R

P

SA

XETFOETATS

Project Number:

C O

N G

R E S

S A

V E N

U E

S U

IT

E

A U

S T

IN

T X

(5

-9

W W

W .L

E V

Y D

Y K

E M

A .C

O M

© 2024 LEVY DYKEMA

08/21/2025

A u to d e sk

D o cs

/3 -1

B u rn e t

C o u n ty A n n e x/

B u rn e t

C o u n ty _E

LE

C

_R V

.r vt

B U

R N

E T

C O

U N

T Y

A N

N E X

E001

ELECTRICAL COVER

SHEET

33-1408

E

J A

C K

S O

N S

T

B U

R N

E T

T X

CONTROL EQUIPMENT SCHEDULE

UNIT

ITEMS BY OTHERS ITEMS BY ELECTRICAL CONTRACTOR

CONTROL DEVICES

INST.

BY

FURN.

BY

NOTES

DESCRIPTION VOLTAGE PHASE FLA

DISCONNECT

DESCRIPTION AMPS

NEMA

ENCLOSURE

CU-1-1 CONDENSING UNIT 208 V 1 36A NON-FUSED 60A NEMA 3R FCU-1-1 MC MC 4

CU-2-1 CONDENSING UNIT 208 V 1 32A NON-FUSED 60A NEMA 3R FCU-2-1 MC MC 4

CU-IT-MAIN CONDENSING UNIT 208 V 1 34.0 NON-FUSED 60A NEMA 3R FCU-IT-MAIN MC MC 1, 4

CU-LAB CONDENSING UNIT 208 V 1 22.0 NON-FUSED 30A NEMA 3R FCU-LAB MC MC 1, 4

EF-1-1 thru EF-1-3 EXHAUST FAN 120 V 1 1A MOTOR RATED 15A NEMA 1 OCCUPANCY SENSOR EC EC 2, 4

EF-2-1 & EF-2-2 EXHAUST FAN 120 V 1 1A MOTOR RATED 15A NEMA 1 OCCUPANCY SENSOR EC EC 2, 4

EWH-1 ELECTRIC WATER HEATER 208 V 1 12A MOTOR RATED 20A NEMA 1 --- -- -- 4

FCU-1-1 FAN COIL UNIT 208 V 1 25A NON-FUSED 30A NEMA 1 THERMOSTAT MC MC 3, 4

FCU-2-1 FAN COIL UNIT 208 V 1 25A NON-FUSED 30A NEMA 1 THERMOSTAT MC MC 3, 4

NOTES:

1. FCU POWERED BY CU. PROVIDE WIRE AND CONDUIT PER NEC.

2. INTERLOCK WITH OCCUPANCY SENSORS IN MEN'S AND WOMEN'S RESTROOMS.

3. UNIT PROVIDED WITH DUCT SMOKE DETECTOR, CONNECT TO FIRE ALARM SYSTEM.

4. ELECTRICAL CONTRACTOR TO MAKE FINAL CONNECTION AS NOTED IN PLANS.

# DATE ISSUE

1 08/21/2025 ADDENDUM 1

DIVISION 26 - ELECTRICAL

SCOPE

THE PROVISIONS, TERMS AND REQUIREMENTS OF DIVISION 1 AND 2, THE APPLICABLE DRAWINGS AND TECHNICAL

SPECIFICATIONS HEREIN SHALL APPLY TO WORK UNDER THIS DIVISION.

THIS WORK CONSISTS OF, BUT IS NOT NECESSARILY LIMITED TO, THE FURNISHING OF ALL LABOR, EQUIPMENT, APPLIANCES AND MATERIALS AND THE PERFORMANCE OF ALL OPERATIONS IN CONNECTION WITH THE INSTALLATION OF ALL ELECTRICAL WORK COMPLETED, IN STRICT ACCORDANCE WITH SPECIFICATIONS AND/OR DRAWINGS, APPLICABLE CODES, INCLUDING INCIDENTAL MATERIALS NECESSARY AND REQUIRED FOR THEIR

COMPLETION.

"PROVIDE" = FURNISHED AND INSTALLED COMPLETE. "OR EQUAL" = OR EQUAL AS APPROVED TO QUOTE BY

ENGINEER, 10 DAYS PRIOR TO BID.

260000 - COMMON WORK RESULTS

A. INTENT OF DRAWINGS: DRAWINGS ARE PARTLY DIAGRAMMATIC AND DO NOT SHOW EXACT LOCATION OF

CONDUIT UNLESS SPECIFICALLY DIMENSIONED.

B. WORKMANSHIP:

1. WORK SHALL BE ACCOMPLISHED BY WORKMEN SKILLED IN PARTICULAR TRADE, IN CONFORMANCE

WITH BEST PRACTICES AND ACCEPTED STANDARDS.

2. WORK SHALL CONTRIBUTE TO EFFICIENCY OF OPERATION, ACCESSIBILITY, MAINTENANCE AND

APPEARANCE. NO PART OF INSTALLATION SHALL INTERFERE WITH OPERATION OF ANY OTHER

SYSTEM OR PART OF BUILDING.

3. NON-SATISFACTORY WORK SHALL BE CORRECTED AT NO ADDITIONAL EXPENSE TO OWNER.

C. RESPONSIBILITY:

1. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF SATISFACTORY AND

COMPLETE WORK IN ACCORDANCE WITH THE INTENT OF DRAWINGS AND SPECIFICATIONS. PROVIDE, AT NO EXTRA COST, INCIDENTAL ITEMS REQUIRED FOR COMPLETION OF WORK EVEN THOUGH NOT

SPECIFICALLY MENTIONED OR INDICATED IN SPECIFICATIONS OR ON DRAWINGS.

2. IF, AT ANY TIME, AND IN ANY CASE, CHANGE IN LOCATION OF CONDUIT, OUTLETS, FIXTURES, SWITCHES, PANELS, ELECTRICAL EQUIPMENT OR ASSOCIATED COMPONENTS, ETC., BECOMES

NECESSARY DUE TO OBSTACLES OR INSTALLATION OF OTHER TRADES, SUCH REQUIRED CHANGES

SHALL BE MADE BY CONTRACTOR AT NO EXTRA COST.

3. CONFLICTS DISCOVERED DURING CONSTRUCTION SHALL BE IMMEDIATELY CALLED TO THE

ATTENTION OF THE ENGINEER FOR DECISION. DO NOT PROCEED WITH INSTALLATION IN AREA OF

QUESTION UNTIL CONFLICT HAS BEEN FULLY RESOLVED.

4. COORDINATE ALL ELECTRICAL WORK WITH OTHER TRADES TO PREVENT UNNECESSARY DELAYS IN

THE CONSTRUCTION SCHEDULE.

5. PROVIDE TEMPORARY ELECTRICAL POWER AND LIGHTING FOR ALL TRADES THAT REQUIRE SERVICE

DURING THE COURSE OF THIS PROJECT. PROVIDE TEMPORARY SERVICE AND DISTRIBUTION AS

REQUIRED. COMPLY WITH THE NFPA 70 AND OSHA REQUIREMENTS. (ENERGY COSTS BY GENERAL

CONTRACTOR.)

D. GUARANTEE-WARRANTY: THIS CONTRACTOR SHALL AND HEREBY DOES WARRANT AND GUARANTEE:

1. THAT ALL WORK EXECUTED UNDER THIS SECTION WILL BE FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THIS WORK.

2. THE CONTRACTOR AGREES TO, AT THE CONTRACTOR'S OWN EXPENSE, REPAIR AND REPLACE ALL

SUCH DEFECTIVE MATERIALS AND WORK AND ALL OTHER WORK DAMAGED THEREBY WHICH

BECOMES DEFECTIVE DURING THE TERM OF WARRANTY. AGREEMENT DOES NOT INCLUDE DAMAGES

DONE BY OWNER.

E. PERMITS, TESTS, CODES AND STANDARDS:

1. ELECTRICAL CONTRACTOR TO PAY FOR ALL PERMITS AND FEES IN CONNECTION WITH THIS WORK.

2. WORK SHALL BE IN ACCORCDANCE WITH THE MOST RECENT EDITIONS OF ADOPTED LOCAL, STATE

AND NATIONAL CODES AND ORDINANCES, THE STATE FIRE MARSHAL, AND UTILITY COMPANY

REGULATIONS.

3. ELECTRICAL WORK SHALL CONFORM TO NATIONAL ELECTRICAL CODES, LATEST EDITIONS, AS A

MINIMUM REQUIREMENT.

4. ALL MATERIAL TO CONFORM WITH APPLICABLE STANDARDS.

F. DISCREPANCIES: PRIOR TO SUBMITTING BID, CONTRACTOR SHALL REFER ANY APPARENT

DISCREPANCIES OR OMISSIONS TO ENGINEER FOR CLARIFICATION.

G. PRIOR APPROVALS: ALL PROPOSED SUBSTITUTIONS SHALL BE RECEIVED BY THE ENGINEER 10 DAYS

PRIOR TO BID. PRIORS RECEIVED AFTER 3 P.M. OF THE 10TH DAY WILL BE REJECTED. SUPPLY TECHNICAL DATA, PHOTOMETRICS AND DIMENSIONAL DRAWINGS SHOWING THAT SUBSTITUTES ARE

EQUAL TO PRODUCT SPECIFIED. FAXED PRIOR APPROVALS WILL NOT BE ACCEPTED.

H. SHOP DRAWING SUBMITTALS:

1. IN ADDITION TO DISTRIBUTION REQUIREMENTS FOR SUBMITTALS SPECIFIED IN DIVISION 1 SECTION "SUBMITTALS," SUBMIT DRAWINGS FOR FINAL AND OFFICIAL APPROVAL THROUGH THE GENERAL

CONTRACTOR AS LISTED BELOW. IF THE AUTHORITY HAVING JURISDICTION REQUIRES SHOP

DRAWINGS TO HAVE A REGISTERED ENGINEERS STAMP AFFIXED, THIS SHALL BE THE SOLE

RESPONSIBILITY OF THE CONTRACTOR TO ACQUIRE SUCH STAMP AT CONTRACTOR'S COST.

A. ENGINEER - 2 COPIES.

B. GENERAL CONTRACTOR - 2 COPIES.

C. SUBCONTRACTOR - COPIES AS REQUIRED.

ADDITIONAL COPIES MAY BE REQUIRED BY INDIVIDUAL SECTIONS OF THESE SPECIFICATIONS.

COPIES OF PRICE LIST SHEETS ARE NOT ACCEPTABLE. MANUFACTURER'S NAME AND ADDRESS MUST

APPEAR ON EACH SHEET. ALL COPIES SHALL BE COMPLETELY LEGIBLE. FAX COPIES ARE

UNACCEPTABLE. ALL SHOP DRAWINGS NOT BOUND IN DUO-TANG, MEAD OR EQUIVALENT FOLDERS

WILL BE REJECTED.

2. SHOP DRAWINGS SHALL INCLUDE A COMPLETED SPECIFICATION SHEET OF ALL EQUIPMENT ALONG

WITH FABRICATION, INSTALLATION DRAWINGS, SETTING DIAGRAMS, SCHEDULES, PATTERNS,

TEMPLATES AND SIMILAR DRAWINGS. INSTALLATION DRAWINGS FOR FIRE ALARM SHALL BE DONE

WITH A COMPUTER CADD PROGRAM AND INCLUDE NO OTHER SYSTEM. A BASIC FLOOR PLAN IN

ELECTRONIC FORMAT CAN BE OBTAINED FROM THE PROJECT ENGINEER.

I. PROJECT CLOSE-OUT RECORD DOCUMENTS:

1. PROVIDE THREE FULL SIZE SETS, UNLESS MORE ARE CALLED FOR UNDER DIVISION 1 (ONE FOR ENGINEER AND ONE FOR OWNER). IN ADDITION TO REQUIREMENTS CALLED FOR UNDER DIVISION 1, INDICATE THE FOLLOWING INSTALLED CONDITIONS:

A. ACTUAL LOCATION OF ALL ELECTRICAL SERVICE GEAR/FEEDERS, PANEL/MOTOR/SPECIAL

EQUIPMENT FEEDERS, ALL MAJOR UNDERGROUND OR UNDERSLAB CONDUITS, ALL CONDUIT

STUBS FOR FUTURE USE, ANY CHANGE IN BRANCH CIRCUITRY FROM DRAWINGS, KEY JUNCTION

BOXES AND PULL BOXES NOT INDICATED ON DRAWINGS, ANY CONTROL LOCATIONS OR

INDICATOR LIGHTS NOT SHOWN ON DRAWINGS.

B. ADDENDUM ITEMS, CHANGE ORDER ITEMS AND ALL CHANGES MADE TO DRAWINGS FROM

BIDDING PHASE THROUGH TO PROJECT COMPLETION.

C. ACTUAL EQUIPMENT AND MATERIALS INSTALLED. WHERE MANUFACTURER AND CATALOG

NUMBER ARE INDICATED ON DRAWINGS, GENERALLY OR IN FIXTURE OR EQUIPMENT SCHEDULES, CHANGE TO REFLECT ACTUAL PRODUCTS INSTALLED.

D. CHANGE SERVICE PANEL AND BRANCH PANEL BREAKER LOCATIONS AND SCHEDULES TO

REFLECT ACTUAL INSTALLED CONDITIONS.

J. PROJECT CLOSE-OUT MAINTENANCE MANUALS:

1. PREPARE 3 COPIES, UNLESS MORE ARE CALLED FOR UNDER DIVISION 1 (ONE FOR ENGINEER, TWO FOR OWNER).IN ADDITION TO REQUIREMENTS UNDER DIVISION 1, PROVIDE HEAVY DUTY, DURABLE 3- RING VINYL COVERED LOOSE-LEAF BINDER FOR EACH MANUAL SIZED TO RECEIVE 8.5 INCH BY 11 INCH PAPER. PROVIDE A CLEAR PLASTIC SLEEVE ON THE SPINE TO HOLD LABELS AND POCKETS IN

THE COVER TO RECEIVE FOLDED SHEETS. IN MANUAL, INCLUDE ALL SHOP DRAWINGS,

INSTALLATION/OPERATION/MAINTENANCE DATA FURNISHED WITH ELECTRICAL EQUIPMENT,

VOICE/DATA TEST REPORTS, AND LETTERS FROM MANUFACTURER'S REPRESENTATIVES THAT THE

FIRE ALARM, HAS BEEN COMPLETED AND TESTED TO SATISFY REQUIREMENTS/CODES. LIST

PROJECT NAME, DATE, AND CONTRACTOR'S NAME, ADDRESS AND TELEPHONE NUMBER. INCLUDE

INDEX SHEET FOR EACH SPECIFICATION SECTION INDICATING EQUIPMENT, WITH SUPPLIER AND SUPPLIER'S TELEPHONE NUMBER. PROVIDE TABBED DIVIDERS INDICATING MAJOR GROUPINGS OF

EQUIPMENT.

2. TURN OVER TO OWNER ALL SPARE EQUIPMENT AND DEVICES SPECIFIED AND SHOWN.

K. SUPPORTING EQUIPMENT:

1. UNLESS OTHERWISE INDICATED, FASTEN ELECTRICAL ITEMS AND THEIR SUPPORTING HARDWARE SECURELY TO THE BUILDING STRUCTURE, INCLUDING CONDUITS, RACEWAYS, CABLES, CABLE TRAYS, BUSWAYS, CABINETS, PANELBOARDS, TRANSFORMERS, BOXES, DISCONNECT SWITCHES, AND

CONTROL COMPONENTS. FASTEN BY MEANS OF WOOD SCREWS OR SCREW-TYPE NAILS ON WOOD,

TOGGLE BOLTS ON HOLLOW MASONRY UNITS, CONCRETE INSERTS OR EXPANSION BOLTS ON

CONCRETE OR SOLID MASONRY, AND MACHINE SCREWS, WELDED THREADED STUDS, OR SPRING-

TENSION CLAMPS ON STEEL. THREADED STUDS DRIVEN BY A POWER CHARGE AND PROVIDED WITH

LOCK WASHERS AND NUTS MAY BE USED INSTEAD OF EXPANSION BOLTS AND MACHINE OR WOOD

SCREWS. DO NOT WELD CONDUIT, PIPE STRAPS, OR ITEMS OTHER THAN THREADED STUDS TO STEEL STRUCTURES. IN PARTITIONS OF LIGHT STEEL CONSTRUCTION, USE SHEET METAL SCREWS. ALL DEVICE BOXES IN SHEETROCK WALLS WILL BE TIGHT BEFORE, DURING AND AFTER INSTALLATION OF

SHEETROCK.

2. PROVIDE SUPPORTS FOR ELECTRICAL ITEMS IN ACCORDANCE WITH NFPA 70 AND ALL OTHER

APPLICABLE CODES.

3. CONTRACTOR RESPONSIBLE FOR PROVIDING WATERTIGHT CONDUIT PENETRATIONS AT ALL

WATERTIGHT WALLS, FLOORS ROOFS AND MEMBRANES. CONTRACTOR ALSO RESPONSIBLE TO

MAINTAIN FIRE RATING OF WALLS, FLOORS, ROOFS AND MEMBRANES PENETRATED.

4. WHEN APPLICABLE, CENTER WITHIN INSULATION ANY ELECTRICAL CONDUIT ROUTED IN ATTIC SPACE.

PROVIDE SEALING AS PER NFPA 70 300-7 FOR ALL CONDUITS EXPOSED TO DIFFERENT

TEMPERATURES.

L. ELECTRICAL IDENTIFICATION:

1. APPLY CIRCUIT/CONTROL/ITEM DESIGNATION LABELS OF ENGRAVED PLASTIC LAMINATE FOR DISCONNECT SWITCHES, BREAKERS, PUSHBUTTONS, PILOT LIGHTS, FA DUCT DETECTION, MOTOR

STARTERS, PANELBOARDS AND MAIN CONTROL PANEL AND SIMILAR SYSTEMS.

2. IDENTIFY ALL 120 VAC AND 208 VAC POWER RECEPTACLE COVER PLATES WITH PANEL AND CIRCUIT NUMBER UTILIZING A CLEAR LABEL WITH BLACK DESIGNATIONS. DESIGNATION EXAMPLE: L1-38.

260519 - CONDUCTORS AND CABLES

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. ALL CONDUCTORS SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA 70, NEMA, UL NETA ATS-1995, AND ALL OTHER APPLICABLE CODES. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM

CONDUCTORS SHALL NOT BE USED.

C. MINIMUM CONDUCTOR SIZE FOR LIGHT AND POWER SHALL BE #12 AWG COPPER. MINIMUM CONDUCTOR SIZE FOR CONTROL WIRING SHALL BE #14 AWG COPPER UNLESS NOTED OTHERWISE ON DRAWINGS. #10 AWG AND SMALLER SHALL BE SOLID WIRE AND #8 AWG AND LARGER SHALL BE STRANDED. PROVIDE

MINIMUM #10 AWG FOR EXTERIOR LIGHTING CIRCUITS.

D. MC CABLE ALLOWED, IN CONCEALED WALL AND CEILING SPACES.

E. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, INCLUDING SCREWS AND BOLTS, IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE TIGHTENING VALVES OR AS SPECIFIED IN UL CODES.

F. COLOR CODE SECONDARY SERVICE, FEEDER, AND BRANCH CIRCUIT CONDUCTORS WITH FACTORY

APPLIED COLOR AS FOLLOWS:

208Y/120 VOLTS PHASE 480Y/277 VOLTS

RED A BROWN

BLACK B YELLOW

BLUE C PURPLE

WHITE NEUTRAL GRAY

GREEN GROUND GREEN

262726 - WIRING DEVICES

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. ACCEPTABLE MANUFACTURERS: PASS & SEYMORE, BRYANT, GE, HUBBELL, LEVITON.

C. DEVICES:

1. GENERAL LIGHT SWITCHES SHALL BE 20 AMP, 120/277 VOLT AC RATED AND INDUSTRIAL GRADE.

2. GENERAL RECEPTACLES SHALL BE SELF GROUNDING 5-20R AND INDUSTRIAL GRADE. GFCI

RECEPTACLES SHALL BE 20 AMP FEED THROUGH TYPE WITH TWO UTILIZATION POINTS. DO NOT

CONNECT DOWNSTREAM DEVICES TO LOAD SIDE OF GFCI.

3. DIMMERS SHALL BE LUTRON NOVA SERIES, SIZED APPROPRIATELY FOR LOAD.

4. GENERAL DEVICE COLOR SHALL BE WHITE. EMERGENCY POWER DEVICE COLOR SHALL BE RED

ONLY.

D. DEVICE PLATES:

1. DEVICE PLATES SHALL HAVE OPENING FOR DEVICE INTENDED AND SHALL BE LEXAN. GENERAL

DEVICE COLOR SHALL BE WHITE.

2. ALL DEVICE PLATES SHALL HAVE A CLEAR LABEL WITH THE PANEL AND CIRCUIT NUMBER

DESIGNATION IN BLACK.

3. WEATHERPROOF RECEPTACLE COVERS SHALL BE A CORROSION RESISTANT DIE CAST METAL,

MINIMUM 3 INCH DEEP, FLIP COVER WITH LATCH AND WITH PAD LOCKING PROVISIONS.

M. IDENTIFICATION:

1. CABLE/WORKSTATION LABELS: USE A UNIQUE 5-SYLLABLE ALPHANUMERIC DESIGNATION. FIRST SYLLABLE IS TO IDENTIFY AND LOCATE THE WIRING CLOSET OR EQUIPMENT ROOM WHERE THE CABLE ORIGINATES. SECOND SYLLABLE IS TO IDENTIFY THE RACK NUMBER. THIRD SYLLABLE IS TO IDENTIFY THE PATCH PANEL OR TERMINAL BLOCKS TO WHICH THE CABLE TERMINATES. FOURTH AND FIFTH SYLLABLES ARE TO IDENTIFY THE PATCH PANEL PORT NUMBER.

EXAMPLE: J2A33 (WIRING CLOSET J, RACK 2, PATCH PANEL A, PORT NUMBER 33). LABEL CABLES WITHIN WORKSTATION OUTLET BOXES, WHERE ACCESSIBLE IN CABINETS OR JUNCTION BOXES, AT REAR OF PATCH PANELS, AT TERMINATION BLOCKS AND ELSEWHERE AS INDICATED. PLACE LABELS WITH 4 INCHES OF CABLE TERMINATION POINT. CABLE LABELS SHALL BE VINYL OR VINYL CLOTH, SELF ADHESIVE, WRAPAROUND MARKERS WITH PREPRINTED NUMBERS AND LETTERS. LABEL EACH WORKSTATION JACK ON WORKSTATION FACEPLATE UNDER CLEAR VIEW

COVERS WITH PREPRINTED LABEL.

2. PATCH PANEL LABELING: LABEL EACH WORKSTATION PANEL WITH SELF ADHESIVE PREPRINTED SINGLE LETTER DESIGNATION (A THROUGH Z). LABEL PATCH PANELS USED AS A PATCH TO TELEPHONE CROSS CONNECT BLOCKS AS "TELEPHONE PATCH." IF MORE THAN ONE TELEPHONE PATCH PANEL, INCLUDE LETTER DESIGNATION. EXAMPLE:

TELEPHONE PATCH A.

3. RACK LABELING: LABEL EACH RACK WITH ENGRAVED PLASTIC LAMINATE NUMBER DESIGNATION. EXAMPLE: RACK 1.

4. WIRING CLOSET/EQUIPMENT ROOM: LABEL WIRING CLOSET WITH ENGRAVED PLASTIC LAMINATE LETTER DESIGNATION.

PLACE LABEL MINIMUM 6 FEET ABOVE FINISHED FLOOR IN VISIBLE LOCATION WITH MINIMUM 2 INCH HIGH LETTERS.

EXAMPLE: WIRING CLOSET J.

5. CABLE SCHEDULE/MAP: POST AT A PROMINENT LOCATION IN EACH EQUIPMENT ROOM. LIST INCOMING AND OUTGOING CABLES AND THEIR DESIGNATIONS, ORIGINS, AND DESTINATIONS. PROTECT WITH A RIGID FRAME AND CLEAR PLASTIC COVER. OBTAIN PRINTED FLOOR PLAN FROM ENGINEER AND INDICATE EACH WORKSTATION JACK, RACK, AND CLOSET

DESIGNATIONS. SEND COPY TO ENGINEER AND INCLUDE WITH AS-BUILT MANUALS/DRAWINGS.

N. FIELD QUALITY CONTROL:

1. TESTING AGENCY: PROVIDE A QUALIFIED NRTL, BICSI CERTIFIED TESTING AGENCY TO PERFORM TESTS AND

INSPECTIONS.

2. PERFORM TESTS AND INSPECTIONS AS FOLLOWS:

A. VISUALLY INSPECT UTP AND OPTICAL FIBER CABLE JACKET MATERIALS FOR NRTL CERTIFICATION MARKINGS.

INSPECT CABLING TERMINATIONS IN COMMUNICATIONS EQUIPMENT ROOMS FOR COMPLIANCE WITH COLOR- CODING FOR PIN ASSIGNMENTS, AND INSPECT CABLING CONNECTIONS FOR COMPLIANCE WITH TIA/EIA-568-B.1.

B. VISUALLY CONFIRM CATEGORY 6, MARKING OF OUTLETS, COVER PLATES,OUTLET/CONNECTORS, AND PATCH

PANELS.

C. VISUALLY INSPECT CABLE PLACEMENT, CABLE TERMINATION, GROUNDING AND BONDING, EQUIPMENT AND PATCH CORDS, AND LABELING OF ALL COMPONENTS. UTP PERFORMANCE TESTS: TEST FOR EACH OUTLET AND MULTI- OUTLET ASSEMBLY. PERFORM THE FOLLOWING TESTS ACCORDING TO TIA/EIA-568-B.1 AND TIA/EIA-568-B.2:

1) WIRE MAP.

2) LENGTH (PHYSICAL VS. ELECTRICAL, AND LENGTH REQUIREMENTS).

3) INSERTION LOSS.

4) NEAR-END CROSSTALK (NEXT) LOSS.

5) POWER SUM NEAR-END CROSSTALK (PSNEXT) LOSS.

6) EQUAL-LEVEL FAR-END CROSSTALK (ELFEXT).

7) POWER SUM EQUAL-LEVEL FAR-END CROSSTALK (PSELFEXT).

8) RETURN LOSS.

9) PROPAGATION DELAY.

10) DELAY SKEW.

D. TEST UTP BACKBONE COPPER CABLING FOR DC LOOP RESISTANCE, SHORTS, OPENS, INTERMITTENT FAULTS, AND POLARITY BETWEEN CONDUCTORS. TEST OPERATION OF SHORTING BARS IN CONNECTION BLOCKS. TEST CABLES AFTER TERMINATION BUT NOT CROSS-CONNECTION. TEST INSTRUMENTS SHALL MEET OR EXCEED APPLICABLE REQUIREMENTS IN TIA/EIA-568-B.2. PERFORM TESTS WITH A TESTER THAT COMPLIES WITH PERFORMANCE REQUIREMENTS IN "TEST INSTRUMENTS (NORMATIVE)" ANNEX, COMPLYING WITH MEASUREMENT ACCURACY SPECIFIED IN "MEASUREMENT ACCURACY (INFORMATIVE)" ANNEX. USE ONLY TEST CORDS AND ADAPTERS THAT ARE QUALIFIED BY TEST EQUIPMENT MANUFACTURER FOR CHANNEL OR LINK TEST CONFIGURATION.

E. OPTICAL FIBER CABLE TESTS:

1) TEST INSTRUMENTS SHALL MEET OR EXCEED APPLICABLE REQUIREMENTS IN TIA/EIA-568-B.1. USE ONLY TEST CORDS AND ADAPTERS THAT ARE QUALIFIED BY TEST EQUIPMENT MANUFACTURER FOR CHANNEL OR LINK

TEST CONFIGURATION.

2) LINK END-TO-END ATTENUATION TESTS:

A) HORIZONTAL AND MULTIMODE BACKBONE LINK MEASUREMENTS: TEST AT 850 OR 1300 NM IN 1 DIRECTION

ACCORDING TO TIA/EIA-526-14-A, METHOD B, ONE REFERENCE JUMPER.

B) ATTENUATION TEST RESULTS FOR BACKBONE LINKS SHALL BE LESS THAN 2.0 DB. ATTENUATION TEST RESULTS SHALL BE LESS THAN THAT CALCULATED ACCORDING TO EQUATION IN TIA/EIA-568-B.1.

3) OPTICAL FIBER CABLE PERFORMANCE TESTS: PERFORM OPTICAL FIBER END-TO-END LINK TESTS ACCORDING

TO TIA/EIA-568-B.1 AND TIA/EIA-568-B.3.

3. RETESTING: CORRECT DEFICIENCIES INDICATED BY TESTS AND COMPLETELY RETEST WORK AFFECTED BY SUCH DEFICIENCIES. VERIFY THAT THE TOTAL SYSTEM MEETS THE SPECIFICATIONS AND COMPLIES WITH APPLICABLE STANDARDS. CONTRACTOR WILL BE REIMBURSED FOR REPLACEMENT OF EXISTING CABLE UPON APPROVAL OF

ENGINEER.

4. REPORT OF TESTS AND INSPECTIONS: PREPARE A WRITTEN RECORD OF INSPECTIONS, TESTS, AND DETAILED TEST

RESULTS IN THE FORM OF A TEST LOG.

5. TAG ALL CABLES, TERMINAL BLOCKS, OUTLETS, AND OTHER COMPONENTS FOR WHICH TESTS HAVE BEEN

SATISFACTORILY COMPLETED.

O. COMMISSIONING:

1. ACCEPTANCE: THIS IS TO BE A CERTIFIED EIA/TIA 568 CATEGORY 6 DATA SYSTEM. SUBMIT SYSTEM CERTIFICATES

PRIOR TO FINAL ACCEPTANCE.

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

283100 - FIRE DETECTION AND ALARM

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. MANUFACTURER: SIMPLEX.

C. COMPLIANCE: FIRE ALARM DESIGN SHALL BE COMPLIANCE WITH INTERNATIONAL BUILDING CODES, NFPA 72, NFPA 13 AND

NFPA 90A AND APPLICABLE GOVERNMENT AGENCY CODES.

D. CONTROL PANEL TO BE INTELLIGENT ADDRESSABLE, WITH 150 PERCENT POWER SUPPLY BATTERY BACKUP AND INTEGRAL

DACT DIALER. INSTALL SEMI-FLUSH.

E. MANUAL STATIONS: INTELLIGENT ADDRESSABLE NON-CODED DOUBLE ACTION. MOUNT SEMIFLUSH IN RECESSED BACK BOXES. SURFACE INSTALLATIONS SHALL UTILIZE SURFACE BOX PROVIDED BY FIRE ALARM MANUFACTURER AND WIREMOLD

700 RACEWAY. BOX BY WIREMOLD NOT ACCEPTABLE.

F. HORN/STROBE UNITS: COMBINATION FLUSH MOUNT TYPE WITH WHITE FINISH. STROBE UNITS TO BE XENON STROBE TYPE AND SHALL COMPLY WITH ADA REQUIREMENTS. INSTALL IN CEILING. STROBES SHALL BE SYNCHRONIZED. SURFACE INSTALLATIONS SHALL UTILIZE SURFACE BOX PROVIDED BY FIRE ALARM MANUFACTURER AND WIREMOLD 700. BOX BY

WIREMOLD NOT ACCEPTABLE.

G. PHOTOELECTRIC SMOKE DETECTORS: INTELLIGENT ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR TO EMPLOY LIGHT SCATTERING PRINCIPLE OF OPERATION. SMOKE DETECTOR SHALL ALARM WHEN SMOKE OBSCURATION LEVEL IN THE

DETECTION CHAMBER REACHES THE 3 PERCENT PER FOOT LEVEL. DO NOT MOUNT SMOKE DETECTORS ANY CLOSER THAN

60 INCHES FROM HVAC AIR DIFFUSERS.

H. HEAT DETECTORS: INTELLIGENT ADDRESSABLE.

1. FIXED TEMPERATURE TYPE, 135 DEG F.

2. RATE OF RISE TYPE, 135 DEG F.

I. DUCT DETECTION (INDUSTRIAL, COMMERCIAL, EDUCATIONAL AND RETAIL): INTELLIGENT ADDRESSABLE PHOTOELECTRIC WITH SAMPLING TUBES. (1) LOCATE IN SINGLE OR COMBINED RETURN AIR SYSTEMS GREATER THAN 2000 CFM UPSTREAM OF ANY FILTERS, AND (2) FOR RETURN SYSTEMS SERVING MORE THAN ONE FLOOR AND GREATER THAN 15,000 CFM, ALSO LOCATE IN RETURN AIR SYSTEM AT EACH STORY UPSTREAM OF THE CONNECTION BETWEEN THE RETURN AIR RISER AND ANY AIR DUCTS OR PLENUMS. COMPLY WITH IMC SECTION 606 FOR LOCATIONS; COMPLY WITH NFPA 72 FOR INSTALLATIONS.

PROVIDE REMOTE TEST STATION ON WALL ADJACENT EACH UNIT. PROVIDE FAN SHUTDOWN RELAY WITHIN 3 FEET OF AIR HANDLER STARTER INTEGRATED WITH FACP FOR SHUTDOWN OF AIR HANDLER UNDER GENERAL ALARM.

J. MAGNETIC DOOR HOLDERS SHALL BE FLOOR OR WALL MOUNTED AS INDICATED COMPLETE WITH MATCHING DOOR PLATE.

ELECTROMAGNET: REQUIRES NO MORE THAN 3 W TO DEVELOP 25 LBF HOLDING FORCE. RATING: 120 VAC.

K. MAIN VALVE SUPERVISORY SWITCHES SHALL BE FURNISHED BY OTHERS AND WIRED BY ELECTRICAL CONTRACTOR.

L. FLOW AND TAMPER SWITCHES SHALL BE FURNISHED AND INSTALLED BY OTHERS AND WIRED BY ELECTRICAL

CONTRACTOR.

M. NOTIFICATION CIRCUITS SHALL BE WIRED CLASS A. INITIATION CIRCUITS SHALL BE WIRED CLASS B. CONDUCTORS SHALL

BE MINIMUM #16 AWG FA CONDUCTOR ENCLOSED IN EMT.

N. PROVIDE A LETTER OF VERIFICATION THAT THE FIRE ALARM SYSTEM HAS BEEN COMPLETED AND TESTED IN ACCORDANCE WITH NFPA PROCEDURES BY MANUFACTURER'S REPRESENTATIVE WITH AN ATTACHED COPY OF THE AHJ'S ACCEPTANCE

REPORT. THE LETTER SHALL BE INCLUDED WITH AS-BUILT MANUALS.

O. TRAINING: TRAIN OWNER'S PERSONNEL A MINIMUM OF 4 HOURS. SCHEDULE ONE WEEK IN ADVANCE.

END OF SECTION

260526 - GROUNDING AND BONDING

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. INSTALL SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTORS FOR FEEDER AND BRANCH

CIRCUITS IN COMPLIANCE WITH NFPA 70 ARTICLE 250.

C. PROVIDE #6 AWG MINIMUM GREEN INSULATED COPPER CONDUCTOR IN RACEWAY FROM GROUNDING ELECTRODE SYSTEM TO EACH TELEPHONE, ALARM AND COMMUNICATIONS SYSTEM'S TERMINAL BOARD, CABINET OR EQUIPMENT LOCATION.

D. SYSTEM GROUND: PROPERLY BOND SYSTEM NEUTRAL TO SYSTEM GROUND IN THE MAIN SERVICE APPARATUS. ALL OTHER NEUTRAL BUSSES, BARS, ETC., MUST BE ISOLATED FROM GROUND. ESTABLISH THE SYSTEM GROUND AS THE GROUNDING BUS IN MAIN SERVICE APPARATUS BY PROVIDING THE PROPER

GROUND BUS IN THE MAIN SERVICE APPARATUS AND BY PROVIDING THE PROPER GROUNDING

CONDUCTOR, INSTALLED IN RIGID STEEL CONDUIT, BONDED TO THE GROUNDING BUS AND EXTENDED TO

THE GROUNDING POINT WHERE THE BOND SHALL BE MADE WITH THE PROPER COMBINATION

CONDUIT/CABLE GROUNDING CLAMP. UNLESS PROHIBITED BY LOCAL CODES, THE GROUNDING POINT SHALL BE ESTABLISHED ON THE INCOMING WATER MAIN, UFER GROUND AND STRUCTURAL STEEL.

BUILDING METALLIC WATER PIPING SYSTEM MUST BE BONDED, AS REQUIRED BY CODES, TO THE GROUNDING BUS IN THE MAIN SERVICE APPARATUS. CAREFULLY CHECK THE DRAWINGS FOR ADDITIONAL

GROUNDING REQUIREMENTS AND COMPLY WITH NFPA 70 AND ALL OTHER APPLICABLE

CODES/STANDARDS.

E. GROUNDING ELECTRODE: UFER GROUND FABRICATED ACCORDING TO NFPA 70, PARAGRAPH 250-52(A)(3), USING A MINIMUM OF 20 FEET OF BARE COPPER CONDUCTOR NOT SMALLER THAN NO. 4 AWG. BOND GROUNDING CONDUCTOR BY CADWELD PROCESS TO REINFORCE STEEL IN AT LEAST 4 LOCATIONS AND

TO ANCHOR BOLTS.

260533 - RACEWAYS AND BOXES

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS"

SECTION.

B. CONDUIT RACEWAY:

1. INDOORS, USE THE FOLLOWING, UNLESS OTHERWISE STATED:

A. CONCEALED: EMT OR MC CABLE.

B. EXPOSED: EMT, IMC OR RMC.

C. CONNECTION TO VIBRATING EQUIPMENT: FLEXIBLE METAL CONDUIT.

2. OUTDOORS, USE THE FOLLOWING, UNLESS OTHERWISE STATED:

A. CONCEALED: RMC OR IMC.

B. EXPOSED: RMC OR IMC.

C. UNDERGROUND: SCHEDULE 40 PVC WITH SCHEDULE 80 PVC FITTINGS.

D. CONNECTION TO VIBRATING EQUIPMENT: LIQUID TIGHT FLEXIBLE METAL CONDUIT.

3. ENT IS NOT ALLOWED.

4. CONCEAL CONDUIT AND CABLE, UNLESS OTHERWISE NOTED; CONDUIT IS PERMITTED TO BE

EXPOSED IN EQUIPMENT ROOMS. ALL CONDUITS SHALL HAVE INSULATED GROUND WIRE INSTALLED.

DO NOT INSTALL CONDUIT EMBEDDED IN SLABS. EMT FITTINGS SHALL BE STEEL, COMPRESSION OR

SET SCREW TYPE. ALL RACEWAYS SHALL BE INSTALLED AND SUPPORTED IN ACCORDANCE WITH

NFPA 70 AND APPLICABLE CODES.

C. OUTLET BOXES:

1. CONFORM TO UL 514A, "METALLIC BOXES, ELECTRICAL," AND UL 514B, "FITTINGS FOR CONDUIT AND OUTLET BOXES." OUTLET BOXES SHALL BE METALLIC AND INSTALLED FLUSH IN ALL AREAS, EXCEPT MECHANICAL ROOMS, ABOVE LAY-IN CEILINGS, OR AS OTHERWISE INDICATED. MINIMUM SIZE TO BE 4 INCHES SQUARE BY 2-1/8 INCHES DEEP. BOXES SHALL BE OF TYPE, SHAPE, SIZE AND DEPTH TO SUIT

EACH LOCATION AND APPLICATION. ALL FITTINGS SHALL BE STEEL.

D. PULL AND JUNCTION BOXES:

1. COMPLY WITH UL 50, "ELECTRICAL CABINETS AND BOXES," FOR BOXES OVER 100 CUBIC INCHES

VOLUME. BOXES SHALL HAVE SCREWED OR BOLT-ON COVERS, SHALL BE SUITABLE FOR THE

INTENDED APPLICATION AND SHALL BE LABELED.

E. ALL MATERIALS SHALL BE UL LISTED, APPROPRIATE FOR INTENDED APPLICATION. ENTIRE RACEWAY SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 70, ANSI, NEMA, UL, AND ALL OTHER APPLICABLE CODES.

262416 - PANELBOARDS

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. MANUFACTURER: SIEMENS, SQUARE-D, GE OR CUTLER HAMMER.

C. LOAD CENTERS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY NOTED.

D. PANELBOARDS SHALL HAVE ALUMINUM BUS INCLUDING NEUTRAL AND GROUND BARS. BREAKERS SHALL BE BOLT ON TYPE. ALL 3-POLE BREAKERS 30 AMP AND LARGER SHALL HAVE MINIMUM FEATURE OF A

THERMAL MAGNETIC ADJUSTMENT FEATURE.

E. PROVIDE TYPED CIRCUIT SCHEDULES FOR EXISTING PANELBOARDS WHERE LOADS HAVE CHANGED AND FRAMED,TYPED CIRCUIT SCHEDULES FOR ALL NEW PANELBOARDS WITH IDENTIFICATION OF ITEMS CONTROLLED BY EACH INDIVIDUAL BREAKER. INDICATE ROOM NUMBERS OF ITEMS CONTROLLED OR

ROOM NAME WHERE APPROPRIATE FOR OWNER'S CONVENIENCE.

262816 - CIRCUIT AND MOTOR DISCONNECTS

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS FOR ELECTRICAL"

SECTION.

B. MANUFACTURER: SAME AS PANELBOARD MANUFACTURER.

C. DISCONNECTS SHALL BE HEAVY DUTY TYPE WITH CLASS R REJECTION FEATURE WHEN REQUIRED TO BE FUSIBLE. VOLTAGE RATING SHALL BE AT OR GREATER THAN THE APPLICATION VOLTAGE. PROVIDE NEMA 3R ENCLOSURE FOR EXTERIOR LOCATIONS. SERVICE SWITCHES SHALL BE UL LISTED FOR USE AS

SERVICE EQUIPMENT.

262913 - MOTOR CONTROLLERS

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. MANUFACTURER: SAME AS PANELBOARD MANUFACTURER.

C. UNLESS SCHEDULED OTHERWISE, 3/4 HORSEPOWER OR LESS SINGLE-PHASE MOTORS SHALL HAVE 1 HP RATED MANUAL TOGGLE STARTERS WITH THERMAL OVERLOAD PROTECTION SIZED FOR THE MOTOR IN ACCORDANCE WITH NFPA 70. PROVIDE PILOT LIGHT FOR MANUAL STARTERS NOT IN SIGHT FROM MOTOR.

UNITS LOCATED AT THE EXTERIOR OF THE BUILDING SHALL BE NEMA 3R RATED.

D. STARTERS SHALL BE ACROSS-THE-LINE MAGNETIC TYPE, COMBINATION STARTER/DISCONNECT, FVNR, AND HP RATED, UNLESS OTHERWISE SCHEDULED. STARTER SHALL HAVE RESETABLE OVERLOAD

PROTECTION ON ALL PHASES, CONSTRUCTED OF ONE-PIECE CLASS 20 CONSTRUCTION. PROVIDE 120

VOLT CONTROL, H-O-A AND INTERLOCKS WHERE INDICATED ON SCHEDULES. PROVIDE TWO N/O

AUXILIARY CONTACTS. UNITS LOCATED AT THE BUILDING EXTERIOR SHALL BE NEMA 3R RATED.

E. ALL MOTOR CONTROLLERS SHALL BE UL LISTED AND INSTALLED IN ACCORDANCE WITH NFPA 70, NEMA, AND MANUFACTURER'S RECOMMENDATIONS.

265100 - LIGHTING

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. MANUFACTURER, MODEL, STYLE, COLOR, SIZE, ETC., AS SCHEDULED. IF NO COLOR HAS BEEN SELECTED, PROVIDE FIXTURE WITH THE STANDARD FINISH AS PUBLISHED BY THE MANUFACTURER. ALL FIXTURES TO BE SUPPLIED AS COMPLETE, HOUSING, SOCKETS, LAMP HOLDERS, INTERNAL WORKING, WIRE GUARDS, LENS GUARDS, DIFFUSING MATERIALS OR LENSES, PENDANTS, HANGERS, CANOPIES, ALIGNERS, END CAPS, BALLASTS AND EMERGENCY BATTERY PACKS, PLASTER FRAMES, RECESSING BOXES, HOLD DOWN CLIPS, ANCHOR BOLTS, ETC. INSTALL PLUMB AND TRUE, FREE OF LIGHT LEAKS, WARPS, DENTS AND

OTHER IRREGULARITIES.

C. SUPPORT FOR RECESSED AND SEMI-RECESSED GRID-TYPE FLUORESCENT FIXTURES:

1. ALL LIGHTING FIXTURES SHALL BE POSITIVELY ATTACHED TO THE SUSPENDED CEILING SYSTEM BY MECHANICAL MEANS AS SPECIFIED IN THE NATIONAL ELECTRIC CODE, SECTION 410-16 (C) UNLESS INDEPENDENTLY SUPPORTED. THE ATTACHMENT DEVICE, A MINIMUM OF TWO PER FIXTURE, SHALL HAVE A CAPACITY OF 100 PERCENT OF THE LIGHTING FIXTURE WEIGHT ACTING IN ANY DIRECTION.

2. PENDANT-HUNG LIGHTING FIXTURES SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE

USING NO. 9-GAGE WIRE OR AN APPROVED ALTERNATE SUPPORT WITHOUT USING THE CEILING

SUSPENSION SYSTEM FOR DIRECT SUPPORT.

3. LIGHTING FIXTURES WEIGHING LESS THAN 56 POUNDS SHALL HAVE, IN ADDITION TO THE

REQUIREMENTS OUTLINED ABOVE, TWO NO. 12-GAGE HANGERS CONNECTED FROM OPPOSITE

CORNERS OF THE FIXTURE HOUSING TO THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK.

4. LIGHTING FIXTURES WEIGHING 56 POUNDS OR MORE SHALL BE SUPPORTED DIRECTLY FROM THE

STRUCTURE ABOVE BY APPROVED HANGERS.

D. SUPPORT FOR SUSPENDED FIXTURES: BRACE PENDANTS AND RODS OVER 48 INCHES LONG TO LIMIT SWINGING. SUPPORT STEM-MOUNTED, SINGLE-UNIT, SUSPENDED FLUORESCENT FIXTURES WITH TWIN- STEM HANGERS. FOR CONTINUOUS ROWS, USE TUBING OR STEM FOR WIRING AT ONE POINT AND TUBING OR ROD FOR SUSPENSION FOR EACH UNIT LENGTH OF CHASSIS, INCLUDING ONE AT EACH END.

E. SURFACE-MOUNTED LIGHT FIXTURES ATTACHED TO A CEILING GRID SHALL BE ATTACHED WITH POSITIVE CLAMPING DEVICES THAT COMPLETELY SURROUND THE SUPPORTING MEMBERS. SAFETY WIRES SHALL BE ATTACHED BETWEEN THE CLAMPING DEVICE AND THE ADJACENT CEILING HANGER OR TO THE

STRUCTURE ABOVE.

DIVISION 27 - COMMUNICATIONS

270500 - TELE-DATA COMMUNICATIONS

A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.

B. MANUFACTURERS: SIEMON, ICC, LEVITON, ORTRONICS, AMP, HUBBELL OR UNIPRISE.

C. STANDARDS: MATERIALS SHALL HAVE NRTL LISTING IN COMPLIANCE WITH UL910. COMPLY WITH TIA/EIA-569-A AND NFPA 70 FOR PATHWAYS AND SPACES, NECA 1, BICSI TDMM AND NFPA 70 FOR EQUIPMENT ROOM INSTALLATIONS, NECA 1, BICSI ITSIM CHAPTER 6 AND TIA/EIA-568 FOR CABLE INSTALLATIONS, TIA/EIA 568 FOR COPPER CONNECTING HARDWARE, TIA/EIA-568 AND TIA/EIA-604 FOR FIBER CONNECTING HARDWARE, TIA/EIA-J-STD-607A, BICSI TDMM AND NFPA 70 FOR GROUNDING, TIA/EIA-568B AND TIA/EIA 526-14-A FOR TESTING, TIA/EIA-606-A CLASS 2 LEVEL, UL 969 AND NFPA 70 FOR

LABELING.

D. TELEPHONE/DATA ROOMS: WHERE TERMINAL BOARDS ARE INDICATED ON THE CONSTRUCTION

DOCUMENTS, PROVIDE 3/4-INCH THICK INTERIOR GRADE PLYWOOD FROM FLOOR TO CEILING WITH FIRE RETARDANT PAINT ON ALL SIDES. COORDINATE CONDUIT FROM THE TELEPHONE TERMINAL BOARD (TTB) TO EXTERIOR OF BUILDING; SIZE AND ROUTE AS DICTATED BY SERVING UTILITY COMPANY. PROVIDE TTB COMMUNICATION GROUNDING BUS AS REQUIRED BY SERVING UTILITY, MINIMUM #6 AWG IN PVC CONDUIT, EXTENDED, SHORTEST AND MOST DIRECT ROUTE TO GROUND BAR AT MAIN SWITCH. TERMINATE IN GROUND BAR INSTALLED ON TTB. PROVIDE MINIMUM OF TWO QUAD-PLEX POWER RECEPTACLE 6 INCHES

ABOVE FINISHED FLOOR AND ADDITIONAL AS INDICATED ON DRAWINGS.

E. VOICE/DATA WORKSTATION ROUGH-INS: PROVIDE 4 INCH SQUARE, 2-1/8-INCH DEEP 1-GANG ROUGH-IN WITH 3/4-INCH CONDUIT STUBBED TO CEILING SPACE WITH A 90 DEGREE BEND AND INSULATED THROAT

BUSHING, UNLESS OTHERWISE STATED.

F. WORKSTATION OUTLET ASSEMBLIES: (MODULES SHALL BE COLOR CODED FOR SERVICE TYPE, FACEPLATE/JACK COLOR SAME AS SPECIFIED IN THE WIRING DEVICES SECTION).

1. WALL MOUNT TELEPHONE ASSEMBLY: STAINLESS STEEL WALL MOUNT PLATE WITH FLAT, CATEGORY

6, T568A/B, RJ45 MODULE.

2. VOICE ONLY WALL JACK ASSEMBLIES: (1) ANGLED CATEGORY 6, T568A/B, RJ45 MODULE AND (1)

BLANK MODULE IN A MODULAR STYLE FACEPLATE. FACEPLATE SHALL HAVE CLEAR VIEW LABEL

COVERS.

3. DATA ONLY WALL JACK ASSEMBLIES: (1) ANGLED CATEGORY 6, T568A/B, RJ45 MODULE AND (1) BLANK MODULE IN A MODULAR STYLE FACEPLATE. FACEPLATE SHALL HAVE CLEAR VIEW LABEL COVERS.

4. COMBINATION VOICE/DATA WALL JACK ASSEMBLIES: (3) ANGLED CATEGORY 6, T568A/B, RJ45

MODULES AND (3) BLANK MODULES IN A MODULAR STYLE FACEPLATE. FACEPLATE SHALL HAVE

CLEAR VIEW LABEL COVERS.

G. CABLES:

1. HORIZONTAL WORKSTATION CABLING: CATEGORY 6 UNSHIELDED TWISTED PAIR (UTP) CABLE, 4 PAIR, COLOR CODED, THERMOPLASTIC-INSULATED CONDUCTORS IN POLYVINYL CHLORIDE (PVC) JACKET.

USE PLENUM RATED CABLE IN SPACES USED FOR AIR HANDLING.

2. VERTICAL BACKBONE CABLING: CATEGORY 6 UNSHIELDED TWISTED PAIR (UTP) CABLE, 25 PAIR FOR

RUNS BETWEEN WIRING CLOSETS AND EQUIPMENT ROOMS.

3. FIBER OPTIC BACKBONE CABLING: FACTORY FABRICATED, JACKETED, LOW-LOSS, GLASS-TYPE, FIBER-OPTIC, MULTIMODE, GRADED INDEX, OPERATING AT 850 AND 1300 NANOMETERS. 12 STANDS PER CABLE, 62.5 MICRON CORE DIAMETER, 125 MICRON CLADDING, MAXIMUM ATTENUATION OF MINUS

3.75 DB/KM AT 850 NM AND 1.5 DB/KM AT 1300NM, MINIMUM MODAL BANDWIDTH OF 160 MHZ/KM AT 850 NM AND 500 MHZ/KM AT 1300 NM AND OPERATING TEMPERATURE RANGE OF MINUS 20 TO 70 DEG C.

H. WORKSTATION PATCH PANELS: WORKSTATION PATCH PANELS SHALL BE CATEGORY 6 IN 24 OR 48 PORT SIZES WITH REAR WIRE MANAGEMENT AND S110 TERMINATION BLOCKS. TELEPHONE PATCH PANELS SHALL BE CATEGORY 6 IN 24 OR 48 PORT SIZES WITH REAR WIRE MANAGEMENT AND S110

TERMINATION BLOCKS. ALL PATCH PANELS SHALL BE SEPARATED IN RACKS BY FRONT CABLE

MANAGERS (1.75 INCH FOR 24 PORT AND 3.5 INCH FOR 48 PORT). PROVIDE 110 STYLE, HINGED PUNCHDOWN BLOCKS AND 4-PAIR, CATEGORY 6 CABLES BETWEEN TELEPHONE PATCH PANEL AND 110 BLOCKS. CROSS CONNECTING BY TELEPHONE COMPANY. ALL EQUIPPED SHALL BE SELECTED AND

SIZED TO ACCOMMODATE INCOMING WORKSTATION CABLES PLUS 20 PERCENT SPARE CAPACITY.

I. FIBER BACKBONE PATCH PANELS: FIBER BACKBONE PATCH PANELS SHALL BE RACK MOUNTED PATCH PANELS IN 24 OR 48 PORT SIZES EQUIPPED TO ACCOMMODATE FIBER BACKBONE CABLES PLUS 20 PERCENT SPARE CAPACITY. PATCH PANELS SHALL HAVE QUICK-CONNECT, SIMPLEX AND DUPLEX TYPE SC COUPLERS WITH SELF-CENTERING, AXIAL ALIGNMENT MECHANISMS WITH INSERTION LOSS

NO MORE THAN .5 DB.

J. WORKSTATION PATCH CORDS (UTP): PROVIDE 4 PAIR CABLES IN APPROPRIATE LENGTHS FOR EACH WORKSTATION PATCH PANEL PORT (USED OR UNUSED), CATEGORY 6 RATED AND TERMINATED WITH

AN RJ-45 PLUG AT EACH END. CABLES TO BE ROUTED FROM WORKSTATION PATCH PANELS TO

TELEPHONE PATCH PANEL ABOVE OR OWNER'S HUB EQUIPMENT BELOW. LENGTH SHALL BE LONG

ENOUGH TO BE ROUTED FROM THE WORKSTATION PORT THROUGH THE FRONT CABLE MANAGER,

THROUGH THE SIDE CABLE MANAGER, THROUGH THE FRONT CABLE MANAGER TO THE TELEPHONE

PATCH PORT OR OWNER'S HUB PORT. ALSO, PROVIDE 6 FOOT, CATEGORY 6 RATED PATCH CORDS

FOR EACH WORKSTATION JACK AT THE USER END.

K. FIBER BACKBONE PATCH CORDS: PROVIDE DUAL FIBER CABLES IN 36 INCH OR 72 INCH LENGTHS FOR

EACH FIBER PATCH PANEL PORT.

L. WORKSTATION WIRING INSTALLATION:

1. INSTALL CABLE WITHOUT DAMAGING CONDUCTORS OR JACKET. DO NOT BEND CABLE TO A SMALLER

RADIUS THAN MINIMUM RECOMMENDED BY MANUFACTURER. DO NOT EXCEED MANUFACTURER'S

RECOMMENDED PULLING…