ESBD_484259_1770149331704_EXHIBIT B - Burnet Annex on the Square_MEP_R1.pdf
PDF 8 MB Posted
- Attached to
- RE-BID LIFT INSTALLATION
- Solicitation number
- 26-4090-05
- Issued by
- Brazos County, Texas
About this file
This is an electrical design and specifications document for the Burnet County Annex renovation project located at 127 E. Jackson Street, Burnet, Texas 78611, prepared by Capital Consulting Engineers and Levy Dykema. The document serves as Exhibit B to the project bid package and provides comprehensive mechanical, electrical, plumbing (MEP), and related systems specifications and design plans. The scope encompasses the complete electrical installation for a two-story county office building, including main service equipment rated at 400 amperes at 208/120 volts, three-phase power distribution through panelboards P1 (400A), P2 (200A), and PG (100A), lighting systems with LED fixtures and occupancy sensors, fire alarm and detection systems (Simplex manufacturer), communications infrastructure with Category 6 cabling and fiber backbone, security and access control systems, HVAC equipment power and controls, emergency power generation capabilities via a 25-kilowatt Generac generator with automatic transfer switch, elevator machinery room systems, and associated branch circuit wiring and controls. The document includes detailed schedules, legends, symbols, one-line diagrams, lighting plans for both floors, power plans, HVAC power plans, grounding electrode systems, conduit routing specifications, and typical installation details addressing code compliance with the 2020 National Electrical Code, local amendments adopted by the City of Burnet and State of Texas, and standards from NFPA, IEEE, UL, NEMA, and ASTM.
The specifications establish mandatory compliance with all local, state, and national electrical codes and industry standards, require all work to be performed by skilled craftsmen in a workmanlike manner, and stipulate that the electrical contractor shall provide all labor, materials, equipment, permits, and licenses necessary for complete system installation. The contractor is responsible for field verification of conditions, coordination with all other trades, protection of existing systems, and delivery of as-built documentation and three-copy maintenance manuals upon project completion. All electrical equipment must be new, UL-listed, and properly labeled; conductors must be copper THWN-2 with minimum #12 AWG for light and power circuits and #14 AWG for control wiring; and all work is guaranteed against defective materials and workmanship for a minimum of one year from the date of substantial completion. The document does not specify pricing, funding sources, set-asides, incumbent vendors, or contract award dates, as it functions as a technical design and specification guide rather than a procurement document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FINISHED CEILING
FINISHED FLOOR
BOD
BOD
BOD
COD
COD
AC = ABOVE COUNTER,
MINIMUM 4" ABOVE
BACKSPLASH TO BOTTOM OF
DEVICE.
48" TOD IS ACCEPTABLE FOR
CMU BLOCK CONSTRUCTION.
M
IN
IM
U
M T
O B
O T
T O
M O
F D
E V
IC
E
M O
U N
T
A
B O
V E
D O
O R
F R
A M
E
T O
T O
P O
F T
R
IM
M
IN
IN
H A
Z A
R D
O U
S L O
C A
T
IO
N S
-T O
B O
T T
O M
O F
C A
N 8
A F
F T
O B
O T
T O
M O
F D
E V
IC
E
O R
B E
L O
W C
E
IL
IN
G
T O
T O
P O
F D
E V
IC
E
W H
IC
H
E V
E R
I S
L O
W E
R
FIR
E
FIR
E
C S F F F
FIRE
F KPS
D
ADDITIONAL MOUNTING HEIGHTS
44" COD.CB
EPB
EPC
PANEL
BOARD
44" COD.
44" COD.
44" COD.
44" COD.
W
T CO₂
INTERIOR BOX MOUNTING HEIGHTS
ABOVE COUNTER, 4" BACK SPLASHAC
AUTOMATIC TRANSFER SWITCHATS
ABOVE FINISHED GRADEAFG
ABOVE FINISHED FLOORAFF
BELOW GRADEBLG
BOTTOM OF DEVICEBOD
CONDUITC
STROBE (NUMBER INDICATES CANDELA RATING)
SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING)
SPEAKER
MANUAL PULLSTATION
IPS INDOOR PROTECTIVE SHIELD
MAGNETIC DOOR HOLDER, BY DIV 28
FIRE/SMOKE DAMPER
SMOKE DETECTOR, SMOKE DETECTOR WALL MOUNTED
HEAT DETECTOR, HEAT DETECTOR WALL MOUNTED
CONNECTION TO TAMPER SWITCH, SWITCH BY OTHERS
CONNECTION TO FLOW SWITCH, SWITCH BY OTHERS
CONNECTION TO PRESSURE SWITCH, SWITCH BY OTHERS
BEAM DETECTOR TRANSMITTER
BEAM DETECTOR RECEIVER
DUCT SMOKE DETECTOR
FIRE ALARM REMOTE ANNUNICATOR
FIRE ALARM CONTROL PANEL
M
F
F
F
F
FSD
SD SD
HD HD
TS
FS
PS
BD
BD
SD
FARA
FACP
SYMBOL DESCRIPTION
LAY-IN OR RECESSED FIXTURE, SIZE ON PLANS
WALL MOUNTED FIXTURE, SIZE ON PLANS
SURFACE MOUNTED FIXTURE, SIZE ON PLANS
PENDANT OR SURFACE MOUNTED FIXTURE, SIZE ON PLANS
RECESSED DOWNLIGHT FIXTURE
SURFACE MOUNTED FIXTURE
WALL MOUNTED FIXTURE
CEILING MOUNTED, WALL MOUNTED EXIT
LIGHT (W/ DIRECTIONAL ARROWS)
ROUND POLE MOUNTED FIXTURE, EXTERIOR
DIRECTIONAL INGROUND FIXTURE, EXTERIOR
PENDANT MOUNTED FIXTURE, SIZE ON PLANS
SHADED FIXTURE INDICATES FIXTURE IS UNSWITCHED
AND ALSO INDICATES EMERGENCY POWER.
WALL WASH OR DIRECTIONAL FIXTURE
WALL SCONCE FIXTURE
TRACK FIXTURE, SEE PLAN FOR SIZE AND HEADS
CEILING FAN FIXTURE
1 HEAD REMOTE EMERGENCY LIGHT
2 HEAD EMERGENCY LIGHT BATTERY PACK
1 HEAD REMOTE EMERGENCY LIGHT BATTERY PACK
2 HEAD LIGHT WITH MOTION SENSOR
SQUARE POLE MOUNTED FIXTURE, EXTERIOR
POST TOP FIXTURE, EXTERIOR
BOLLARD FIXTURE, EXTERIOR
CATV JACK, WALL MOUNTED
MICROPHONE OUTLET
SPEAKER, SPEAKER WALL MOUNTED
CLOCK HANGER RECEPTACLE
VOICE OUTLET - WALL MOUNTED
VOICE/DATA OUTLET MOUNTED IN FLOORBOX - SUBSCRIPT
INDICATES NUMBER OF CABLES/JACKS - NO SUBSCRIPT
INDICATES 2 CABLES/JACKS
C
SS
E
VOICE/DATA OUTLET - SUBSCRIPT INDICATES NUMBER OF
CABLES/JACKS - NO SUBSCRIPT INDICATES 2 CABLES/JACKS
EXISTING VOICE/DATA OUTLET
W
DATA RACK
F SPEAKER/STROBE (NUMBER INDICATES CANDELA RATING),
CEILING MOUNTED
FIRE ALARM SIGNAL EXTENDER PANELFASP
CARD ACCESS SYSTEMCAS
CLOSED CIRCUIT TVCCTV
CEILINGCLG
CENTER OF DEVICECOD
COPPERCU
DIGITAL VIDEO RECORDERDVR
EXISTING(E)
ELECTRICAL CONTRACTOREC
EXHAUST FANEF
GENERAL CONTRACTORGC
GROUNDGND
FIELD ADJUSTABLE LONG TIME, SHORT TIME AND
INSTANTANEOUS
LSI
FIELD ADJUSTABLE LONG TIME, SHORT TIME,
INSTANTANEOUS AND GROUND FAULT
LSIG
MECHANICAL CONTRACTORMC
NEW(N)
NIGHT LIGHTNL
PAN-TILT-ZOOMPTZ
QUANTITYQTY
RELOCATED(R)
SURFACESF
TELECOMMUNICATIONS MAIN GROUNDING BUS BARTMGB
TELECOMMUNICATIONS BONDING BACKBONETBB
TEMPERATURE CONTROL CONTRACTORTC
TELEPHONE TERMINAL BOARDTTB
TYPICALTYP
UNDERGROUNDUG
UNLESS OTHERWISE NOTEDUON
WITHW/
WIRE MOLDWM
WEATHER PROOF (WHILE IN USE)WP
TRANSFORMERXFMR
SWITCH DESIGNATIONa,b,c etc
CIRCUIT DESIGNATION, PANEL BN1L, CIRCUITS 2,4,6BN1L-2,4,6
INDICATES DETAIL 1 ON SHEET E5011/E501
1 SHEET WORK NOTE
HOME RUN TO PANEL
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT CONCEALED UNDER FLOOR
LOW VOLTAGE CIRCUIT
FIBER OPTIC CABLE
CABLE TRAY
CIRCUIT, NUMBER OF HASH MARKS INDICATES NUMBER OF
CONDUCTORS IN CABLE/RACEWAY. GROUND WIRE IS NOT
SHOWN BUT SHALL BE INCLUDED. NO HASH MARKS
INDICATES 2 CONDUCTORS PLUS GROUND.
LV
1 SHEET DEMO WORK NOTE
CR CARD READER
DC
MRX
PS
CAMERA, CEILING AND WALL MOUNTED DOME, FIXED
CAMERA, CEILING AND WALL MOUNTED DOME, PTZ
CAMERA, CEILING MOUNTED, 360 DEGREE
CAMERA
DVR
SPS
DIGITAL VIDEO RECORDER
SURVEILLANCE POWER SUPPLY
M MONITOR
A
LX
PRX
ML
DPS
ES
EL
AO
FA
SPEAKER SIGNAL DEVICE
DOOR CONTROLLER
MOTION SENSOR REQUEST TO EXIT
POWER SUPPLY W/BATTERY, BY DIV 8, INSTALLED AND
CONNECTED BY DIV 27
CONNECTION TO REQUEST TO EXIT & LATCH BOLT
MONITORING
CONNECTION TO PANIC REQUEST TO EXIT
CONNECTION TO MAGNETIC DOOR LOCK
CONNECTION TO MAGNETIC DOOR POSITION SWITCH
CONNECTION TO ELECTRIC DOOR STRIKE
CONNECTION TO ELECTRIC LATCH
CONNECTION TO ELECTRIC AUTO OPENER
CONNECTION TO FIRE ALARM CONTACT
INDICATES SECURITY DOOR 1
PANEL
SCP SECURITY CONTROL PANEL
SDC SECURITY DOOR CONTROLLERS
KP KEYPAD
PT POWER TRANSFER SWITCH
SWITCH - SPST
2 SINGLE POLE, DOUBLE THROW
3 THREEWAY
4 FOURWAY
K KEY OPERATED
P PILOT LIGHT
WP WEATHERPROOF
OS OCCUPANCY SENSOR (DUAL TECHNOLOGY)
D DIMMER
MC SPOT-MOMENTARY CONTACT
LV LOW VOLTAGE
T TIMER SWITCH
TS TEST SWITCH
VS VACANCY SENSOR (DUAL TECHNOLOGY) WITH DIMMING
OCCUPANCY SENSOR SWITCH (CEILING) - SUBSCRIPT IS
TYPE
OS
RECEPTACLE - SIMPLEX
RECEPTACLE - DUPLEX
GFI RECEPTACLE - DUPLEX (GROUND FAULT INTERRUPT)
D DEVICE RECEPT W/2 USB PORTS
DC DROP CORD
WP WEATHERPROOF COVER & WEATHER
RESISTANT RECEPTACLE
TR TAMPER RESISTANT
S SURGE PROTECTED
IG ISOLATED GROUND
FILLED CENTER INDICATES HOSPITAL GRADE
EMERGENCY RECEPTACLE
RECEPTACLE - DOUBLE DUPLEX
GFI RECEPTACLE - DOUBLE DUPLEX
- SAME INDICATORS AS SHOWN FOR DUPLEX RECEPTACLE
RECEPTACLE - 208V
R RANGE - NEMA 14-50R
D DRYER - NEMA 10-30R
W WELDER - NEMA 14-50R
* NEMA CONFIGURATION AS NOTED
208V RECEPTACLE IN RECESSED FLOORBOX
DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX
DOUBLE DUPLEX RECEPTACLE/GFI IN RECESSED FLOORBOX
J-BOX - BOX INDICATES FLOOR MOUNTING -4"X4"X2-1/8" DEEP
UNLESS OTHERWISE NOTED
SPECIAL PURPOSE CONNECTION - BOX INDICATES FLOOR
MOUNTING - WORK AS NOTED
RECEPTACLE - DUPLEX, MOUNTING IN CEILING
MANUAL MOTOR DISCONNECT/STARTER SWITCH
COMBINATION STARTER/DISCONNECT SWITCH
DISCONNECT SWITCH
CONTACTOR
ELECTRIC MOTOR CONNECTION
EMERGENCY PUSHBUTTON
PC PHOTOCELL, PHOTOCELL WALL MOUNTEDPC
EXISTING PANELBOARD, SURFACE MOUNTED
EXISTING PANELBOARD, FLUSH MOUNTED
TIME CLOCK
M ELECTRIC METER, BUILDING MOUNTED
TRANSFORMER, INTERIOR
or
VARIABLE FREQUENCY DRIVE
J JJ
CLG
CO₂
THERMOSTAT/TEMPERATURE SENSOR BY MC OR TC, J-BOX
AND CONDUIT TO CEILING BY EC
CARBON MONOXIDE DETECTOR BY MC, J-BOX & CONDUIT TO
CEILING BY EC
PP POWER POLE
R RELAY
CIRCUIT BREAKER
CONTROL PANEL
LRP LIGHTING RELAY PANEL
TCP TEMPERATURE CONTROL PANEL
GAP GENERATOR ANNUNCIATOR PANEL
PACP PA CONTROL PANEL
MGA MED GAS ALARM PANEL
PANELBOARD, SURFACE MOUNTED
PANELBOARD, FLUSH MOUNTED
TRANSFORMER, EXTERIOR
CLG
GFI RECEPTACLE - DUPLEX, MOUNTING IN CEILING
M
T
TC
VFD
LIGHTING
ELECTRICAL LEGEND
SYMBOL DESCRIPTION
FIRE ALARM
SYMBOL DESCRIPTION
COMMUNICATIONS
SYMBOL DESCRIPTION
ABBREVIATIONS AND MISCELLANEOUS
SYMBOL DESCRIPTION
SURVEILLANCE SYSTEM
DESCRIPTION
SECURITY SYSTEM
SYMBOL
SYMBOL DESCRIPTION
DEVICES AND POWER
REX MANUAL REQUEST TO EXIT
DS DOOR SWITCH CONTACT
CATV JACK CEILING MOUNTEDCLG
WIRELESS ACCESS POINT, WIRELESS ACCESS POINT WALL
MOUNTED - 2 CABLES/JACKS
WAP WAP
SECURITY CAMERA
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
ALL WORK SHALL BE PERFORMED PER 2020 NEC, AND ALL WORK SHALL BE PERFORMED IN
COMPLIANCE WITH THE LATEST EDITION OF ALL LOCAL AMENDMENTS AND REGULATIONS AS
ADOPTED BY THE CITY OF BURNET AND THE STATE OF TEXAS, AND THE PUBLICATIONS AND
STANDARDS OF THE FOLLOWING AUTHORITIES, IN ADDITION TO THOSE SPECIFIED IN
RELATED SUPPLEMENTARY CONDITIONS, WHICH ARE REFERENCED IN ELECTRICAL
SPECIFICATIONS BY THE ABBREVIATIONS NOTED.
UNITED STATES OF AMERICA STANDARDS INSTITUTE - USASI INSTITUTE OF ELECTRICAL AND
ELECTRONIC ENGINEERS - IEEE NATIONAL ELECTRICAL CODE - NEC NATIONAL FIRE
PROTECTION ASSOCIATION - NFPA UNDERWRITER'S LABORATORIES - UL NATIONAL
ELECTRICAL MANUFACTURERS ASSOCIATION - NEMA AMERICAN SOCIETY OF TESTING
MATERIALS - ASTM OCCUPATIONAL SAFETY AND HEALTH ACT - OSHA
ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, PLANS AND
THE SPECIFICATIONS, AND SHALL BE PERFORMED WITH THE LATEST INDUSTRY ACCEPTED
STANDARDS.
THE INTENT OF THIS CONSTRUCTION PACKAGE IS TO ILLUSTRATE ALL THE WORK TO BE
ACCOMPLISHED TO PROVIDE AN ELECTRICAL INSTALLATION COMPLETE IN EVERY RESPECT.
CARE HAS BEEN TAKEN TO INDICATE THE COMPLETE SCOPE OF WORK REQUIRED FOR THIS
PROJECT, HOWEVER, IT IS NOT THE INTENT TO INDICATE EVERY CONFLICT WHICH MAY
ARISE, AND PROVIDE FOR SUCH ON THESE DOCUMENTS. NO ASSURANCE IS GIVEN THAT
THE PLANS COMPLETELY REFLECT ACTUAL JOB SITE CONDITIONS. IF IT IS DISCOVERED IN
THE FIELD THAT ACTUAL LOCATIONS OR CONDITIONS DIFFER GREATLY FROM THOSE
SHOWN, CONTRACTOR SHALL GET APPROVAL FROM OWNER PRIOR TO COMMENCING
WORK.
CONTRACTOR SHALL VISIT THE SITE AND FIELD VERIFY THE PROPOSED INSTALLATION
LOCATION AND ALL WORKING CONDITIONS SUCH AS STARTING TIME, NOISE LIMITATIONS,
CONFINED SPACE LIMITATIONS, OFFSETS AND ROUTING ADJUSTMENTS THAT MAY BE
REQUIRED, ETC., TO COMPLETE THE WORK. CONTRACTOR SHALL COORDINATE WITH THE
OWNER REGARDING OBSTRUCTION OF ROADWAY OR DRIVEWAY AREAS, ON SITE
MATERIALS AND EQUIPMENT STORAGE, AND BUILDING ACCESS. SITE INSPECTION SHALL
DETERMINE CONDITION OF EXISTING ELEMENTS TO REMAIN AND BE PROTECTED.
CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING ALL
WORK DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, AND
MISALIGNMENT ACCORDING TO APPLICABLE CODES, STANDARDS, AND GOOD
CONSTRUCTION PRACTICES. CONTRACTOR SHALL TAKE PROPER PRECAUTIONS TO
PROTECT ALL EXISTING OPERATIONS AND PROPERTY ADJACENT WITH WHICH WORK COMES
IN CONTACT, OR OVER OR UNDER WHICH HE MAY TRANSPORT, HOIST, OR MOVE
MATERIALS, EQUIPMENT, DEBRIS, ETC. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR
AND/OR REPLACEMENT IN KIND OF ALL INADVERTENT DAMAGE TO EXISTING SYSTEMS.
ALL NECESSARY PERMITS, LICENSES, CERTIFICATES, TESTS, ETC., SHALL BE PROCURED AND
PAID FOR BY THE CONTRACTOR.
THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION INSTALLATION DIMENSIONS.
ALL CONDUIT ROUTING ARE SHOWN IN APPROXIMATE LOCATIONS ONLY. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR FIELD VERIFICATION OF CONDITIONS, AND SHALL PERFORM
FIELD MEASUREMENTS PRIOR TO FABRICATION AND/OR PURCHASE OF ANY EQUIPMENT
AND MATERIAL. REFERENCE ALL DETAILS FOR ADDITIONAL CONSTRUCTION
REQUIREMENTS. DETAILS MAY NOT BE REFERENCED ON THE DRAWING(S), BUT ARE
INTENDED TO BE TYPICAL THROUGHOUT UNLESS OTHERWISE NOTED.
DO NOT BEGIN WORK IF ANY DISCREPANCIES OR CONFLICTS EXIST OR ARE DISCOVERED
BETWEEN SYSTEMS, UTILITIES, UNTIL THE DISCREPANCIES HAVE BEEN RESOLVED.
IMMEDIATELY CALL SUCH DISCREPANCIES OR CONFLICTS TO THE ATTENTION OF THE
OWNER'S CONSTRUCTION REPRESENTATIVE AND/OR ENGINEER. SHOULD ANY CONFLICTS
OR AMBIGUITIES EXIST IN THE DRAWINGS, NOTES, OR SPECIFICATIONS, BRING THESE TO
THE ATTENTION OF THE ENGINEER IMMEDIATELY BEFORE PROCEEDING WITH WORK.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING FULL COORDINATION WITH
ALLTRADES TO ACCOMPLISH THE WORK AS INDICATED AND NOTED IN CONTRACT
DOCUMENTS. COORDINATE WITH OWNER'S REPRESENTATIVE, AND MAINTAIN A SET OF ALL
CHANGES BETWEEN THE DRAWINGS AND THE ACTUAL CONSTRUCTION. CONFLICTS ARISING
DUE TO LACK OF COORDINATION SHALL BE THE RESPONSIBILITY OF, AND AT THE EXPENSE
OF, THE CONTRACTOR. FINAL AS-BUILT DRAWINGS ARE TO BE DELIVERED TO THE
OWNER/ENGINEER AND THE FINAL INVOICE FOR THE CONTRACT WILL NOT BE PAID UNTIL
THESE AS-BUILT DRAWINGS ARE RECEIVED.
WORK AREAS ARE TO BE KEPT FREE OF DEBRIS AT ALL TIMES AND ARE TO BE LEFT BROOM
CLEAN AT THE END OF EACH WORKING DAY. THE CONTRACTOR SHALL DISPOSE OF OFF-
SITE, ALL MATERIALS REMOVED WHICH ARE NOT BE REINSTALLED OR SALVAGED ON THE
PROJECT, UNLESS DIRECTED OTHERWISE BY OWNER. DISPOSAL OF MATERIAL SHALL BE IN
ACCORDANCE WITH ACCEPTABLE METHODS APPROVED BY OWNER AND COORDINATED
THROUGH OWNER'S COORDINATOR.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE RATING OF ALL
PENETRATIONS THROUGH FIRE AND SMOKE RATED SURFACES. THE CONTRACTOR SHALL
COMPLY WITH UL LISTING INSTRUCTIONS FOR PENETRATIONS THROUGH RATED SURFACES.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR TRAINING OF HIS EMPLOYEES AND
SUBCONTRACTORS IN THE RECOGNITION AND AVOIDANCE OF UNSAFE CONDITIONS, AND IN
THE REGULATIONS AND HAZARDS WHICH APPLY TO THE AREA IN WHICH THE WORK WILL
TAKE PLACE. ALL SAFETY EXPOSURES OR VIOLATIONS BROUGHT TO THE ATTENTION OF
THE CONTRACTOR SHALL BE RECTIFIED IMMEDIATELY.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING PROTECTION OF PERSONS AND
PROPERTY, AND FOR PROVIDING SAFE WORKING CONDITIONS THROUGHOUT THE WORK
PROCESS. CONTRACTOR SHALL PROVIDE TEMPORARY COVERINGS FOR OPENINGS
THROUGH WALLS OR FLOORS, AND PROVIDE TEMPORARY BARRIERS, PARTITIONS AND OR
DUST BARRIERS WHERE REQUIRED TO MAINTAIN OSHA AND THE OWNER'S SAFETY
STANDARDS AND TO PREVENT DAMAGE TO PROPERTY. ALL AREAS ADJACENT TO THE
CONSTRUCTION AREA OR AFFECTED BY THE CONSTRUCTION MUST BE PROTECTED FROM
DAMAGE, CLEANED AND RESTORED TO THEIR ORIGINAL CONDITION AT THE END OF THE
PROJECT. WELDING BLANKETS SHALL BE UTILIZED FOR PROTECTION OF COMBUSTIBLE
MATERIALS IN AREA WHERE WELDING OR CUTTING WITH A TORCH IS CONDUCTED.
ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP
FOR A PERIOD OF NO LESS THAN ONE (1) YEAR AFTER THE DATE OF SUBSTANTIAL
COMPLETION OR ACCEPTANCE OF THE WORK. THE CONTRACTOR SHALL REPAIR OR
REPLACE, AT HIS OWN EXPENSE WHEN ORDERED TO DO SO, ALL WORK THAT MAY DEVELOP
DEFECTS IN MATERIAL OR WORKMANSHIP WITHIN SAID PERIOD OF TIME. ALL EQUIPMENT
SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS FOR
SERVICE INTENDED. AS INTERPRETED BY THE ENGINEER, THE INSTALLATION OF ALL
EQUIPMENT SHALL BE MADE BY EXPERIENCED CRAFTSMAN IN A NEAT, WORKMANLIKE
MANNER. ALL MATERIALS, TOOLS, COSTS, AND SERVICES NECESSARY TO COMPLETELY
INSTALL ALL ELECTRICAL WORK SHALL BE PROVIDED BY THE CONTRACTOR.
16.
17.
18.
19.
20.
21.
22.
23.
24.
ALL PROPOSED EQUIPMENT INSTALLED ON THIS PROJECT SHALL BE NEW AND UNUSED UNLESS
NOTED OTHERWISE. ALL EQUIPMENT SHALL BE LABELED AND LISTED FOR THE INTENDED USE.
THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL LABELS, DIRT, PAINT SPOTS, GREASE AND
STAINS FROM ALL ELECTRICAL EQUIPMENT AND SHALL CLEAN ALL EQUIPMENT AS NECESSARY.
NO LOOSE PARTS OR SCRAPS OF EQUIPMENT SHALL BE LEFT ON THE PREMISES. EQUIPMENT
LOCATION AND ROUTING IS APPROXIMATE AND SHALL BE PLACED TO PROVIDE PROPER
ACCESS AND CLEARANCE FROM OTHER TRADES AND EQUIPMENT.
ALL WIRING SHALL BE THWN/THHN, 98% CONDUCTIVITY COPPER, STANDARD CONDUCTOR, 600V
INSULATION. ALL WIRING SHALL BE INSTALLED IN RIGID CONDUIT AND CONTINUOUS (WITHOUT
SPLICES).
A GREEN GROUNDING CONDUCTOR SHALL BE PROVIDED WITH ALL BRANCH AND FEEDER
CIRCUITS. SIZE PER N.E.C. 250-122 UNLESS NOTED OTHERWISE. ALSO PROVIDE A SEPARATE
DEDICATED INSULATED AND ISOLATED GROUNDING CONDUCTOR FOR ISOLATED GROUND
CIRCUITS. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION
SHALL BE TESTED AND PROVED TO BE FREE OF UNWANTED GROUNDS AND OTHER DEFECTS.
ALL EXTERIOR CONDUIT SHALL BE RIGID GALVANIZED STEEL CONDUIT. FITTINGS SHALL BE
STEEL THREADED TYPE. MOUNT THE CONDUIT AS HIGH AS POSSIBLE AND RUN PARALLEL AND
PERPENDICULAR TO STRUCTURE. ALL OTHER CONDUIT SHALL BE EMT WITH STEEL
COMPRESSION OR STEEL SET SCREW FITTINGS, 3/4" MIN., UNLESS NOTED OTHERWISE.
KEEP RACEWAYS AT LEAST SIX INCHES AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR
HOT WATER PIPES. INSTALL HORIZONTAL RACEWAY RUNS ABOVE WATER AND STEAM PIPING.
ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL PULL WIRES IN EMPTY RACEWAYS.
USE NO. 14 AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINE HAVING NOT LESS THAN
200-LB TENSILE STRENGTH.
CHANNEL AND ANGLE SUPPORT SYSTEMS, HANGERS, ANCHORS, SLEEVES, AND FASTENERS
SHALL BE DESIGNED TO PROVIDE SECURE SUPPORT FROM THE BUILDING STRUCTURE FOR
ELECTRICAL COMPONENTS. SUPPORTING DEVICES SHALL BE HOT DIPPED GALVANIZED STEEL.
CONFORM TO MANUFACTURER'S RECOMMENDATIONS FOR SELECTING SUPPORTS. SUPPORT
PARALLEL RUNS OF HORIZONTAL RACEWAYS TOGETHER ON TRAPEZE OR BRACKET TYPE
HANGERS.
PULL BOXES SHALL BE GALVANIZED SHEET METAL WITH SCREW-ON COVERS AND WELDED
SEAMS, STAINLESS STEEL NUTS, BOLTS, SCREWS AND WASHERS. BOXES SHALL BE SIZED IN
ACCORDANCE WITH THE NEC.
UNLESS OTHERWISE NOTED ALL 120V SINGLE PHASE CIRCUITS WILL REQUIRE A INDIVIDUAL
NEUTRAL CONDUCTOR - INCLUDING MULTI-CIRCUITS COMBINED IN SINGLE CONDUIT RUNS.
CAPITAL CONSULTING ENGINEERS
CAPCONSULTINGENG.COM TX FIRM # 26531
BUCKLEY H. PARKS
DESNECIL
106223
R E
E
NI
GNELANOISSEF
O R
P
SA
XETFOETATS
Project Number:
C O
N G
R E S
S A
V E N
U E
S U
IT
E
A U
S T
IN
T X
(5
-9
W W
W .L
E V
Y D
Y K
E M
A .C
O M
© 2024 LEVY DYKEMA
08/21/2025
A u to d e sk
D o cs
/3 -1
B u rn e t
C o u n ty A n n e x/
B u rn e t
C o u n ty _E
LE
C
_R V
.r vt
B U
R N
E T
C O
U N
T Y
A N
N E X
E001
ELECTRICAL COVER
SHEET
33-1408
E
J A
C K
S O
N S
T
B U
R N
E T
T X
CONTROL EQUIPMENT SCHEDULE
UNIT
ITEMS BY OTHERS ITEMS BY ELECTRICAL CONTRACTOR
CONTROL DEVICES
INST.
BY
FURN.
BY
NOTES
DESCRIPTION VOLTAGE PHASE FLA
DISCONNECT
DESCRIPTION AMPS
NEMA
ENCLOSURE
CU-1-1 CONDENSING UNIT 208 V 1 36A NON-FUSED 60A NEMA 3R FCU-1-1 MC MC 4
CU-2-1 CONDENSING UNIT 208 V 1 32A NON-FUSED 60A NEMA 3R FCU-2-1 MC MC 4
CU-IT-MAIN CONDENSING UNIT 208 V 1 34.0 NON-FUSED 60A NEMA 3R FCU-IT-MAIN MC MC 1, 4
CU-LAB CONDENSING UNIT 208 V 1 22.0 NON-FUSED 30A NEMA 3R FCU-LAB MC MC 1, 4
EF-1-1 thru EF-1-3 EXHAUST FAN 120 V 1 1A MOTOR RATED 15A NEMA 1 OCCUPANCY SENSOR EC EC 2, 4
EF-2-1 & EF-2-2 EXHAUST FAN 120 V 1 1A MOTOR RATED 15A NEMA 1 OCCUPANCY SENSOR EC EC 2, 4
EWH-1 ELECTRIC WATER HEATER 208 V 1 12A MOTOR RATED 20A NEMA 1 --- -- -- 4
FCU-1-1 FAN COIL UNIT 208 V 1 25A NON-FUSED 30A NEMA 1 THERMOSTAT MC MC 3, 4
FCU-2-1 FAN COIL UNIT 208 V 1 25A NON-FUSED 30A NEMA 1 THERMOSTAT MC MC 3, 4
NOTES:
1. FCU POWERED BY CU. PROVIDE WIRE AND CONDUIT PER NEC.
2. INTERLOCK WITH OCCUPANCY SENSORS IN MEN'S AND WOMEN'S RESTROOMS.
3. UNIT PROVIDED WITH DUCT SMOKE DETECTOR, CONNECT TO FIRE ALARM SYSTEM.
4. ELECTRICAL CONTRACTOR TO MAKE FINAL CONNECTION AS NOTED IN PLANS.
# DATE ISSUE
1 08/21/2025 ADDENDUM 1
DIVISION 26 - ELECTRICAL
SCOPE
THE PROVISIONS, TERMS AND REQUIREMENTS OF DIVISION 1 AND 2, THE APPLICABLE DRAWINGS AND TECHNICAL
SPECIFICATIONS HEREIN SHALL APPLY TO WORK UNDER THIS DIVISION.
THIS WORK CONSISTS OF, BUT IS NOT NECESSARILY LIMITED TO, THE FURNISHING OF ALL LABOR, EQUIPMENT, APPLIANCES AND MATERIALS AND THE PERFORMANCE OF ALL OPERATIONS IN CONNECTION WITH THE INSTALLATION OF ALL ELECTRICAL WORK COMPLETED, IN STRICT ACCORDANCE WITH SPECIFICATIONS AND/OR DRAWINGS, APPLICABLE CODES, INCLUDING INCIDENTAL MATERIALS NECESSARY AND REQUIRED FOR THEIR
COMPLETION.
"PROVIDE" = FURNISHED AND INSTALLED COMPLETE. "OR EQUAL" = OR EQUAL AS APPROVED TO QUOTE BY
ENGINEER, 10 DAYS PRIOR TO BID.
260000 - COMMON WORK RESULTS
A. INTENT OF DRAWINGS: DRAWINGS ARE PARTLY DIAGRAMMATIC AND DO NOT SHOW EXACT LOCATION OF
CONDUIT UNLESS SPECIFICALLY DIMENSIONED.
B. WORKMANSHIP:
1. WORK SHALL BE ACCOMPLISHED BY WORKMEN SKILLED IN PARTICULAR TRADE, IN CONFORMANCE
WITH BEST PRACTICES AND ACCEPTED STANDARDS.
2. WORK SHALL CONTRIBUTE TO EFFICIENCY OF OPERATION, ACCESSIBILITY, MAINTENANCE AND
APPEARANCE. NO PART OF INSTALLATION SHALL INTERFERE WITH OPERATION OF ANY OTHER
SYSTEM OR PART OF BUILDING.
3. NON-SATISFACTORY WORK SHALL BE CORRECTED AT NO ADDITIONAL EXPENSE TO OWNER.
C. RESPONSIBILITY:
1. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF SATISFACTORY AND
COMPLETE WORK IN ACCORDANCE WITH THE INTENT OF DRAWINGS AND SPECIFICATIONS. PROVIDE, AT NO EXTRA COST, INCIDENTAL ITEMS REQUIRED FOR COMPLETION OF WORK EVEN THOUGH NOT
SPECIFICALLY MENTIONED OR INDICATED IN SPECIFICATIONS OR ON DRAWINGS.
2. IF, AT ANY TIME, AND IN ANY CASE, CHANGE IN LOCATION OF CONDUIT, OUTLETS, FIXTURES, SWITCHES, PANELS, ELECTRICAL EQUIPMENT OR ASSOCIATED COMPONENTS, ETC., BECOMES
NECESSARY DUE TO OBSTACLES OR INSTALLATION OF OTHER TRADES, SUCH REQUIRED CHANGES
SHALL BE MADE BY CONTRACTOR AT NO EXTRA COST.
3. CONFLICTS DISCOVERED DURING CONSTRUCTION SHALL BE IMMEDIATELY CALLED TO THE
ATTENTION OF THE ENGINEER FOR DECISION. DO NOT PROCEED WITH INSTALLATION IN AREA OF
QUESTION UNTIL CONFLICT HAS BEEN FULLY RESOLVED.
4. COORDINATE ALL ELECTRICAL WORK WITH OTHER TRADES TO PREVENT UNNECESSARY DELAYS IN
THE CONSTRUCTION SCHEDULE.
5. PROVIDE TEMPORARY ELECTRICAL POWER AND LIGHTING FOR ALL TRADES THAT REQUIRE SERVICE
DURING THE COURSE OF THIS PROJECT. PROVIDE TEMPORARY SERVICE AND DISTRIBUTION AS
REQUIRED. COMPLY WITH THE NFPA 70 AND OSHA REQUIREMENTS. (ENERGY COSTS BY GENERAL
CONTRACTOR.)
D. GUARANTEE-WARRANTY: THIS CONTRACTOR SHALL AND HEREBY DOES WARRANT AND GUARANTEE:
1. THAT ALL WORK EXECUTED UNDER THIS SECTION WILL BE FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THIS WORK.
2. THE CONTRACTOR AGREES TO, AT THE CONTRACTOR'S OWN EXPENSE, REPAIR AND REPLACE ALL
SUCH DEFECTIVE MATERIALS AND WORK AND ALL OTHER WORK DAMAGED THEREBY WHICH
BECOMES DEFECTIVE DURING THE TERM OF WARRANTY. AGREEMENT DOES NOT INCLUDE DAMAGES
DONE BY OWNER.
E. PERMITS, TESTS, CODES AND STANDARDS:
1. ELECTRICAL CONTRACTOR TO PAY FOR ALL PERMITS AND FEES IN CONNECTION WITH THIS WORK.
2. WORK SHALL BE IN ACCORCDANCE WITH THE MOST RECENT EDITIONS OF ADOPTED LOCAL, STATE
AND NATIONAL CODES AND ORDINANCES, THE STATE FIRE MARSHAL, AND UTILITY COMPANY
REGULATIONS.
3. ELECTRICAL WORK SHALL CONFORM TO NATIONAL ELECTRICAL CODES, LATEST EDITIONS, AS A
MINIMUM REQUIREMENT.
4. ALL MATERIAL TO CONFORM WITH APPLICABLE STANDARDS.
F. DISCREPANCIES: PRIOR TO SUBMITTING BID, CONTRACTOR SHALL REFER ANY APPARENT
DISCREPANCIES OR OMISSIONS TO ENGINEER FOR CLARIFICATION.
G. PRIOR APPROVALS: ALL PROPOSED SUBSTITUTIONS SHALL BE RECEIVED BY THE ENGINEER 10 DAYS
PRIOR TO BID. PRIORS RECEIVED AFTER 3 P.M. OF THE 10TH DAY WILL BE REJECTED. SUPPLY TECHNICAL DATA, PHOTOMETRICS AND DIMENSIONAL DRAWINGS SHOWING THAT SUBSTITUTES ARE
EQUAL TO PRODUCT SPECIFIED. FAXED PRIOR APPROVALS WILL NOT BE ACCEPTED.
H. SHOP DRAWING SUBMITTALS:
1. IN ADDITION TO DISTRIBUTION REQUIREMENTS FOR SUBMITTALS SPECIFIED IN DIVISION 1 SECTION "SUBMITTALS," SUBMIT DRAWINGS FOR FINAL AND OFFICIAL APPROVAL THROUGH THE GENERAL
CONTRACTOR AS LISTED BELOW. IF THE AUTHORITY HAVING JURISDICTION REQUIRES SHOP
DRAWINGS TO HAVE A REGISTERED ENGINEERS STAMP AFFIXED, THIS SHALL BE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR TO ACQUIRE SUCH STAMP AT CONTRACTOR'S COST.
A. ENGINEER - 2 COPIES.
B. GENERAL CONTRACTOR - 2 COPIES.
C. SUBCONTRACTOR - COPIES AS REQUIRED.
ADDITIONAL COPIES MAY BE REQUIRED BY INDIVIDUAL SECTIONS OF THESE SPECIFICATIONS.
COPIES OF PRICE LIST SHEETS ARE NOT ACCEPTABLE. MANUFACTURER'S NAME AND ADDRESS MUST
APPEAR ON EACH SHEET. ALL COPIES SHALL BE COMPLETELY LEGIBLE. FAX COPIES ARE
UNACCEPTABLE. ALL SHOP DRAWINGS NOT BOUND IN DUO-TANG, MEAD OR EQUIVALENT FOLDERS
WILL BE REJECTED.
2. SHOP DRAWINGS SHALL INCLUDE A COMPLETED SPECIFICATION SHEET OF ALL EQUIPMENT ALONG
WITH FABRICATION, INSTALLATION DRAWINGS, SETTING DIAGRAMS, SCHEDULES, PATTERNS,
TEMPLATES AND SIMILAR DRAWINGS. INSTALLATION DRAWINGS FOR FIRE ALARM SHALL BE DONE
WITH A COMPUTER CADD PROGRAM AND INCLUDE NO OTHER SYSTEM. A BASIC FLOOR PLAN IN
ELECTRONIC FORMAT CAN BE OBTAINED FROM THE PROJECT ENGINEER.
I. PROJECT CLOSE-OUT RECORD DOCUMENTS:
1. PROVIDE THREE FULL SIZE SETS, UNLESS MORE ARE CALLED FOR UNDER DIVISION 1 (ONE FOR ENGINEER AND ONE FOR OWNER). IN ADDITION TO REQUIREMENTS CALLED FOR UNDER DIVISION 1, INDICATE THE FOLLOWING INSTALLED CONDITIONS:
A. ACTUAL LOCATION OF ALL ELECTRICAL SERVICE GEAR/FEEDERS, PANEL/MOTOR/SPECIAL
EQUIPMENT FEEDERS, ALL MAJOR UNDERGROUND OR UNDERSLAB CONDUITS, ALL CONDUIT
STUBS FOR FUTURE USE, ANY CHANGE IN BRANCH CIRCUITRY FROM DRAWINGS, KEY JUNCTION
BOXES AND PULL BOXES NOT INDICATED ON DRAWINGS, ANY CONTROL LOCATIONS OR
INDICATOR LIGHTS NOT SHOWN ON DRAWINGS.
B. ADDENDUM ITEMS, CHANGE ORDER ITEMS AND ALL CHANGES MADE TO DRAWINGS FROM
BIDDING PHASE THROUGH TO PROJECT COMPLETION.
C. ACTUAL EQUIPMENT AND MATERIALS INSTALLED. WHERE MANUFACTURER AND CATALOG
NUMBER ARE INDICATED ON DRAWINGS, GENERALLY OR IN FIXTURE OR EQUIPMENT SCHEDULES, CHANGE TO REFLECT ACTUAL PRODUCTS INSTALLED.
D. CHANGE SERVICE PANEL AND BRANCH PANEL BREAKER LOCATIONS AND SCHEDULES TO
REFLECT ACTUAL INSTALLED CONDITIONS.
J. PROJECT CLOSE-OUT MAINTENANCE MANUALS:
1. PREPARE 3 COPIES, UNLESS MORE ARE CALLED FOR UNDER DIVISION 1 (ONE FOR ENGINEER, TWO FOR OWNER).IN ADDITION TO REQUIREMENTS UNDER DIVISION 1, PROVIDE HEAVY DUTY, DURABLE 3- RING VINYL COVERED LOOSE-LEAF BINDER FOR EACH MANUAL SIZED TO RECEIVE 8.5 INCH BY 11 INCH PAPER. PROVIDE A CLEAR PLASTIC SLEEVE ON THE SPINE TO HOLD LABELS AND POCKETS IN
THE COVER TO RECEIVE FOLDED SHEETS. IN MANUAL, INCLUDE ALL SHOP DRAWINGS,
INSTALLATION/OPERATION/MAINTENANCE DATA FURNISHED WITH ELECTRICAL EQUIPMENT,
VOICE/DATA TEST REPORTS, AND LETTERS FROM MANUFACTURER'S REPRESENTATIVES THAT THE
FIRE ALARM, HAS BEEN COMPLETED AND TESTED TO SATISFY REQUIREMENTS/CODES. LIST
PROJECT NAME, DATE, AND CONTRACTOR'S NAME, ADDRESS AND TELEPHONE NUMBER. INCLUDE
INDEX SHEET FOR EACH SPECIFICATION SECTION INDICATING EQUIPMENT, WITH SUPPLIER AND SUPPLIER'S TELEPHONE NUMBER. PROVIDE TABBED DIVIDERS INDICATING MAJOR GROUPINGS OF
EQUIPMENT.
2. TURN OVER TO OWNER ALL SPARE EQUIPMENT AND DEVICES SPECIFIED AND SHOWN.
K. SUPPORTING EQUIPMENT:
1. UNLESS OTHERWISE INDICATED, FASTEN ELECTRICAL ITEMS AND THEIR SUPPORTING HARDWARE SECURELY TO THE BUILDING STRUCTURE, INCLUDING CONDUITS, RACEWAYS, CABLES, CABLE TRAYS, BUSWAYS, CABINETS, PANELBOARDS, TRANSFORMERS, BOXES, DISCONNECT SWITCHES, AND
CONTROL COMPONENTS. FASTEN BY MEANS OF WOOD SCREWS OR SCREW-TYPE NAILS ON WOOD,
TOGGLE BOLTS ON HOLLOW MASONRY UNITS, CONCRETE INSERTS OR EXPANSION BOLTS ON
CONCRETE OR SOLID MASONRY, AND MACHINE SCREWS, WELDED THREADED STUDS, OR SPRING-
TENSION CLAMPS ON STEEL. THREADED STUDS DRIVEN BY A POWER CHARGE AND PROVIDED WITH
LOCK WASHERS AND NUTS MAY BE USED INSTEAD OF EXPANSION BOLTS AND MACHINE OR WOOD
SCREWS. DO NOT WELD CONDUIT, PIPE STRAPS, OR ITEMS OTHER THAN THREADED STUDS TO STEEL STRUCTURES. IN PARTITIONS OF LIGHT STEEL CONSTRUCTION, USE SHEET METAL SCREWS. ALL DEVICE BOXES IN SHEETROCK WALLS WILL BE TIGHT BEFORE, DURING AND AFTER INSTALLATION OF
SHEETROCK.
2. PROVIDE SUPPORTS FOR ELECTRICAL ITEMS IN ACCORDANCE WITH NFPA 70 AND ALL OTHER
APPLICABLE CODES.
3. CONTRACTOR RESPONSIBLE FOR PROVIDING WATERTIGHT CONDUIT PENETRATIONS AT ALL
WATERTIGHT WALLS, FLOORS ROOFS AND MEMBRANES. CONTRACTOR ALSO RESPONSIBLE TO
MAINTAIN FIRE RATING OF WALLS, FLOORS, ROOFS AND MEMBRANES PENETRATED.
4. WHEN APPLICABLE, CENTER WITHIN INSULATION ANY ELECTRICAL CONDUIT ROUTED IN ATTIC SPACE.
PROVIDE SEALING AS PER NFPA 70 300-7 FOR ALL CONDUITS EXPOSED TO DIFFERENT
TEMPERATURES.
L. ELECTRICAL IDENTIFICATION:
1. APPLY CIRCUIT/CONTROL/ITEM DESIGNATION LABELS OF ENGRAVED PLASTIC LAMINATE FOR DISCONNECT SWITCHES, BREAKERS, PUSHBUTTONS, PILOT LIGHTS, FA DUCT DETECTION, MOTOR
STARTERS, PANELBOARDS AND MAIN CONTROL PANEL AND SIMILAR SYSTEMS.
2. IDENTIFY ALL 120 VAC AND 208 VAC POWER RECEPTACLE COVER PLATES WITH PANEL AND CIRCUIT NUMBER UTILIZING A CLEAR LABEL WITH BLACK DESIGNATIONS. DESIGNATION EXAMPLE: L1-38.
260519 - CONDUCTORS AND CABLES
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. ALL CONDUCTORS SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA 70, NEMA, UL NETA ATS-1995, AND ALL OTHER APPLICABLE CODES. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM
CONDUCTORS SHALL NOT BE USED.
C. MINIMUM CONDUCTOR SIZE FOR LIGHT AND POWER SHALL BE #12 AWG COPPER. MINIMUM CONDUCTOR SIZE FOR CONTROL WIRING SHALL BE #14 AWG COPPER UNLESS NOTED OTHERWISE ON DRAWINGS. #10 AWG AND SMALLER SHALL BE SOLID WIRE AND #8 AWG AND LARGER SHALL BE STRANDED. PROVIDE
MINIMUM #10 AWG FOR EXTERIOR LIGHTING CIRCUITS.
D. MC CABLE ALLOWED, IN CONCEALED WALL AND CEILING SPACES.
E. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, INCLUDING SCREWS AND BOLTS, IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE TIGHTENING VALVES OR AS SPECIFIED IN UL CODES.
F. COLOR CODE SECONDARY SERVICE, FEEDER, AND BRANCH CIRCUIT CONDUCTORS WITH FACTORY
APPLIED COLOR AS FOLLOWS:
208Y/120 VOLTS PHASE 480Y/277 VOLTS
RED A BROWN
BLACK B YELLOW
BLUE C PURPLE
WHITE NEUTRAL GRAY
GREEN GROUND GREEN
262726 - WIRING DEVICES
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. ACCEPTABLE MANUFACTURERS: PASS & SEYMORE, BRYANT, GE, HUBBELL, LEVITON.
C. DEVICES:
1. GENERAL LIGHT SWITCHES SHALL BE 20 AMP, 120/277 VOLT AC RATED AND INDUSTRIAL GRADE.
2. GENERAL RECEPTACLES SHALL BE SELF GROUNDING 5-20R AND INDUSTRIAL GRADE. GFCI
RECEPTACLES SHALL BE 20 AMP FEED THROUGH TYPE WITH TWO UTILIZATION POINTS. DO NOT
CONNECT DOWNSTREAM DEVICES TO LOAD SIDE OF GFCI.
3. DIMMERS SHALL BE LUTRON NOVA SERIES, SIZED APPROPRIATELY FOR LOAD.
4. GENERAL DEVICE COLOR SHALL BE WHITE. EMERGENCY POWER DEVICE COLOR SHALL BE RED
ONLY.
D. DEVICE PLATES:
1. DEVICE PLATES SHALL HAVE OPENING FOR DEVICE INTENDED AND SHALL BE LEXAN. GENERAL
DEVICE COLOR SHALL BE WHITE.
2. ALL DEVICE PLATES SHALL HAVE A CLEAR LABEL WITH THE PANEL AND CIRCUIT NUMBER
DESIGNATION IN BLACK.
3. WEATHERPROOF RECEPTACLE COVERS SHALL BE A CORROSION RESISTANT DIE CAST METAL,
MINIMUM 3 INCH DEEP, FLIP COVER WITH LATCH AND WITH PAD LOCKING PROVISIONS.
M. IDENTIFICATION:
1. CABLE/WORKSTATION LABELS: USE A UNIQUE 5-SYLLABLE ALPHANUMERIC DESIGNATION. FIRST SYLLABLE IS TO IDENTIFY AND LOCATE THE WIRING CLOSET OR EQUIPMENT ROOM WHERE THE CABLE ORIGINATES. SECOND SYLLABLE IS TO IDENTIFY THE RACK NUMBER. THIRD SYLLABLE IS TO IDENTIFY THE PATCH PANEL OR TERMINAL BLOCKS TO WHICH THE CABLE TERMINATES. FOURTH AND FIFTH SYLLABLES ARE TO IDENTIFY THE PATCH PANEL PORT NUMBER.
EXAMPLE: J2A33 (WIRING CLOSET J, RACK 2, PATCH PANEL A, PORT NUMBER 33). LABEL CABLES WITHIN WORKSTATION OUTLET BOXES, WHERE ACCESSIBLE IN CABINETS OR JUNCTION BOXES, AT REAR OF PATCH PANELS, AT TERMINATION BLOCKS AND ELSEWHERE AS INDICATED. PLACE LABELS WITH 4 INCHES OF CABLE TERMINATION POINT. CABLE LABELS SHALL BE VINYL OR VINYL CLOTH, SELF ADHESIVE, WRAPAROUND MARKERS WITH PREPRINTED NUMBERS AND LETTERS. LABEL EACH WORKSTATION JACK ON WORKSTATION FACEPLATE UNDER CLEAR VIEW
COVERS WITH PREPRINTED LABEL.
2. PATCH PANEL LABELING: LABEL EACH WORKSTATION PANEL WITH SELF ADHESIVE PREPRINTED SINGLE LETTER DESIGNATION (A THROUGH Z). LABEL PATCH PANELS USED AS A PATCH TO TELEPHONE CROSS CONNECT BLOCKS AS "TELEPHONE PATCH." IF MORE THAN ONE TELEPHONE PATCH PANEL, INCLUDE LETTER DESIGNATION. EXAMPLE:
TELEPHONE PATCH A.
3. RACK LABELING: LABEL EACH RACK WITH ENGRAVED PLASTIC LAMINATE NUMBER DESIGNATION. EXAMPLE: RACK 1.
4. WIRING CLOSET/EQUIPMENT ROOM: LABEL WIRING CLOSET WITH ENGRAVED PLASTIC LAMINATE LETTER DESIGNATION.
PLACE LABEL MINIMUM 6 FEET ABOVE FINISHED FLOOR IN VISIBLE LOCATION WITH MINIMUM 2 INCH HIGH LETTERS.
EXAMPLE: WIRING CLOSET J.
5. CABLE SCHEDULE/MAP: POST AT A PROMINENT LOCATION IN EACH EQUIPMENT ROOM. LIST INCOMING AND OUTGOING CABLES AND THEIR DESIGNATIONS, ORIGINS, AND DESTINATIONS. PROTECT WITH A RIGID FRAME AND CLEAR PLASTIC COVER. OBTAIN PRINTED FLOOR PLAN FROM ENGINEER AND INDICATE EACH WORKSTATION JACK, RACK, AND CLOSET
DESIGNATIONS. SEND COPY TO ENGINEER AND INCLUDE WITH AS-BUILT MANUALS/DRAWINGS.
N. FIELD QUALITY CONTROL:
1. TESTING AGENCY: PROVIDE A QUALIFIED NRTL, BICSI CERTIFIED TESTING AGENCY TO PERFORM TESTS AND
INSPECTIONS.
2. PERFORM TESTS AND INSPECTIONS AS FOLLOWS:
A. VISUALLY INSPECT UTP AND OPTICAL FIBER CABLE JACKET MATERIALS FOR NRTL CERTIFICATION MARKINGS.
INSPECT CABLING TERMINATIONS IN COMMUNICATIONS EQUIPMENT ROOMS FOR COMPLIANCE WITH COLOR- CODING FOR PIN ASSIGNMENTS, AND INSPECT CABLING CONNECTIONS FOR COMPLIANCE WITH TIA/EIA-568-B.1.
B. VISUALLY CONFIRM CATEGORY 6, MARKING OF OUTLETS, COVER PLATES,OUTLET/CONNECTORS, AND PATCH
PANELS.
C. VISUALLY INSPECT CABLE PLACEMENT, CABLE TERMINATION, GROUNDING AND BONDING, EQUIPMENT AND PATCH CORDS, AND LABELING OF ALL COMPONENTS. UTP PERFORMANCE TESTS: TEST FOR EACH OUTLET AND MULTI- OUTLET ASSEMBLY. PERFORM THE FOLLOWING TESTS ACCORDING TO TIA/EIA-568-B.1 AND TIA/EIA-568-B.2:
1) WIRE MAP.
2) LENGTH (PHYSICAL VS. ELECTRICAL, AND LENGTH REQUIREMENTS).
3) INSERTION LOSS.
4) NEAR-END CROSSTALK (NEXT) LOSS.
5) POWER SUM NEAR-END CROSSTALK (PSNEXT) LOSS.
6) EQUAL-LEVEL FAR-END CROSSTALK (ELFEXT).
7) POWER SUM EQUAL-LEVEL FAR-END CROSSTALK (PSELFEXT).
8) RETURN LOSS.
9) PROPAGATION DELAY.
10) DELAY SKEW.
D. TEST UTP BACKBONE COPPER CABLING FOR DC LOOP RESISTANCE, SHORTS, OPENS, INTERMITTENT FAULTS, AND POLARITY BETWEEN CONDUCTORS. TEST OPERATION OF SHORTING BARS IN CONNECTION BLOCKS. TEST CABLES AFTER TERMINATION BUT NOT CROSS-CONNECTION. TEST INSTRUMENTS SHALL MEET OR EXCEED APPLICABLE REQUIREMENTS IN TIA/EIA-568-B.2. PERFORM TESTS WITH A TESTER THAT COMPLIES WITH PERFORMANCE REQUIREMENTS IN "TEST INSTRUMENTS (NORMATIVE)" ANNEX, COMPLYING WITH MEASUREMENT ACCURACY SPECIFIED IN "MEASUREMENT ACCURACY (INFORMATIVE)" ANNEX. USE ONLY TEST CORDS AND ADAPTERS THAT ARE QUALIFIED BY TEST EQUIPMENT MANUFACTURER FOR CHANNEL OR LINK TEST CONFIGURATION.
E. OPTICAL FIBER CABLE TESTS:
1) TEST INSTRUMENTS SHALL MEET OR EXCEED APPLICABLE REQUIREMENTS IN TIA/EIA-568-B.1. USE ONLY TEST CORDS AND ADAPTERS THAT ARE QUALIFIED BY TEST EQUIPMENT MANUFACTURER FOR CHANNEL OR LINK
TEST CONFIGURATION.
2) LINK END-TO-END ATTENUATION TESTS:
A) HORIZONTAL AND MULTIMODE BACKBONE LINK MEASUREMENTS: TEST AT 850 OR 1300 NM IN 1 DIRECTION
ACCORDING TO TIA/EIA-526-14-A, METHOD B, ONE REFERENCE JUMPER.
B) ATTENUATION TEST RESULTS FOR BACKBONE LINKS SHALL BE LESS THAN 2.0 DB. ATTENUATION TEST RESULTS SHALL BE LESS THAN THAT CALCULATED ACCORDING TO EQUATION IN TIA/EIA-568-B.1.
3) OPTICAL FIBER CABLE PERFORMANCE TESTS: PERFORM OPTICAL FIBER END-TO-END LINK TESTS ACCORDING
TO TIA/EIA-568-B.1 AND TIA/EIA-568-B.3.
3. RETESTING: CORRECT DEFICIENCIES INDICATED BY TESTS AND COMPLETELY RETEST WORK AFFECTED BY SUCH DEFICIENCIES. VERIFY THAT THE TOTAL SYSTEM MEETS THE SPECIFICATIONS AND COMPLIES WITH APPLICABLE STANDARDS. CONTRACTOR WILL BE REIMBURSED FOR REPLACEMENT OF EXISTING CABLE UPON APPROVAL OF
ENGINEER.
4. REPORT OF TESTS AND INSPECTIONS: PREPARE A WRITTEN RECORD OF INSPECTIONS, TESTS, AND DETAILED TEST
RESULTS IN THE FORM OF A TEST LOG.
5. TAG ALL CABLES, TERMINAL BLOCKS, OUTLETS, AND OTHER COMPONENTS FOR WHICH TESTS HAVE BEEN
SATISFACTORILY COMPLETED.
O. COMMISSIONING:
1. ACCEPTANCE: THIS IS TO BE A CERTIFIED EIA/TIA 568 CATEGORY 6 DATA SYSTEM. SUBMIT SYSTEM CERTIFICATES
PRIOR TO FINAL ACCEPTANCE.
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
283100 - FIRE DETECTION AND ALARM
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. MANUFACTURER: SIMPLEX.
C. COMPLIANCE: FIRE ALARM DESIGN SHALL BE COMPLIANCE WITH INTERNATIONAL BUILDING CODES, NFPA 72, NFPA 13 AND
NFPA 90A AND APPLICABLE GOVERNMENT AGENCY CODES.
D. CONTROL PANEL TO BE INTELLIGENT ADDRESSABLE, WITH 150 PERCENT POWER SUPPLY BATTERY BACKUP AND INTEGRAL
DACT DIALER. INSTALL SEMI-FLUSH.
E. MANUAL STATIONS: INTELLIGENT ADDRESSABLE NON-CODED DOUBLE ACTION. MOUNT SEMIFLUSH IN RECESSED BACK BOXES. SURFACE INSTALLATIONS SHALL UTILIZE SURFACE BOX PROVIDED BY FIRE ALARM MANUFACTURER AND WIREMOLD
700 RACEWAY. BOX BY WIREMOLD NOT ACCEPTABLE.
F. HORN/STROBE UNITS: COMBINATION FLUSH MOUNT TYPE WITH WHITE FINISH. STROBE UNITS TO BE XENON STROBE TYPE AND SHALL COMPLY WITH ADA REQUIREMENTS. INSTALL IN CEILING. STROBES SHALL BE SYNCHRONIZED. SURFACE INSTALLATIONS SHALL UTILIZE SURFACE BOX PROVIDED BY FIRE ALARM MANUFACTURER AND WIREMOLD 700. BOX BY
WIREMOLD NOT ACCEPTABLE.
G. PHOTOELECTRIC SMOKE DETECTORS: INTELLIGENT ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR TO EMPLOY LIGHT SCATTERING PRINCIPLE OF OPERATION. SMOKE DETECTOR SHALL ALARM WHEN SMOKE OBSCURATION LEVEL IN THE
DETECTION CHAMBER REACHES THE 3 PERCENT PER FOOT LEVEL. DO NOT MOUNT SMOKE DETECTORS ANY CLOSER THAN
60 INCHES FROM HVAC AIR DIFFUSERS.
H. HEAT DETECTORS: INTELLIGENT ADDRESSABLE.
1. FIXED TEMPERATURE TYPE, 135 DEG F.
2. RATE OF RISE TYPE, 135 DEG F.
I. DUCT DETECTION (INDUSTRIAL, COMMERCIAL, EDUCATIONAL AND RETAIL): INTELLIGENT ADDRESSABLE PHOTOELECTRIC WITH SAMPLING TUBES. (1) LOCATE IN SINGLE OR COMBINED RETURN AIR SYSTEMS GREATER THAN 2000 CFM UPSTREAM OF ANY FILTERS, AND (2) FOR RETURN SYSTEMS SERVING MORE THAN ONE FLOOR AND GREATER THAN 15,000 CFM, ALSO LOCATE IN RETURN AIR SYSTEM AT EACH STORY UPSTREAM OF THE CONNECTION BETWEEN THE RETURN AIR RISER AND ANY AIR DUCTS OR PLENUMS. COMPLY WITH IMC SECTION 606 FOR LOCATIONS; COMPLY WITH NFPA 72 FOR INSTALLATIONS.
PROVIDE REMOTE TEST STATION ON WALL ADJACENT EACH UNIT. PROVIDE FAN SHUTDOWN RELAY WITHIN 3 FEET OF AIR HANDLER STARTER INTEGRATED WITH FACP FOR SHUTDOWN OF AIR HANDLER UNDER GENERAL ALARM.
J. MAGNETIC DOOR HOLDERS SHALL BE FLOOR OR WALL MOUNTED AS INDICATED COMPLETE WITH MATCHING DOOR PLATE.
ELECTROMAGNET: REQUIRES NO MORE THAN 3 W TO DEVELOP 25 LBF HOLDING FORCE. RATING: 120 VAC.
K. MAIN VALVE SUPERVISORY SWITCHES SHALL BE FURNISHED BY OTHERS AND WIRED BY ELECTRICAL CONTRACTOR.
L. FLOW AND TAMPER SWITCHES SHALL BE FURNISHED AND INSTALLED BY OTHERS AND WIRED BY ELECTRICAL
CONTRACTOR.
M. NOTIFICATION CIRCUITS SHALL BE WIRED CLASS A. INITIATION CIRCUITS SHALL BE WIRED CLASS B. CONDUCTORS SHALL
BE MINIMUM #16 AWG FA CONDUCTOR ENCLOSED IN EMT.
N. PROVIDE A LETTER OF VERIFICATION THAT THE FIRE ALARM SYSTEM HAS BEEN COMPLETED AND TESTED IN ACCORDANCE WITH NFPA PROCEDURES BY MANUFACTURER'S REPRESENTATIVE WITH AN ATTACHED COPY OF THE AHJ'S ACCEPTANCE
REPORT. THE LETTER SHALL BE INCLUDED WITH AS-BUILT MANUALS.
O. TRAINING: TRAIN OWNER'S PERSONNEL A MINIMUM OF 4 HOURS. SCHEDULE ONE WEEK IN ADVANCE.
END OF SECTION
260526 - GROUNDING AND BONDING
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. INSTALL SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTORS FOR FEEDER AND BRANCH
CIRCUITS IN COMPLIANCE WITH NFPA 70 ARTICLE 250.
C. PROVIDE #6 AWG MINIMUM GREEN INSULATED COPPER CONDUCTOR IN RACEWAY FROM GROUNDING ELECTRODE SYSTEM TO EACH TELEPHONE, ALARM AND COMMUNICATIONS SYSTEM'S TERMINAL BOARD, CABINET OR EQUIPMENT LOCATION.
D. SYSTEM GROUND: PROPERLY BOND SYSTEM NEUTRAL TO SYSTEM GROUND IN THE MAIN SERVICE APPARATUS. ALL OTHER NEUTRAL BUSSES, BARS, ETC., MUST BE ISOLATED FROM GROUND. ESTABLISH THE SYSTEM GROUND AS THE GROUNDING BUS IN MAIN SERVICE APPARATUS BY PROVIDING THE PROPER
GROUND BUS IN THE MAIN SERVICE APPARATUS AND BY PROVIDING THE PROPER GROUNDING
CONDUCTOR, INSTALLED IN RIGID STEEL CONDUIT, BONDED TO THE GROUNDING BUS AND EXTENDED TO
THE GROUNDING POINT WHERE THE BOND SHALL BE MADE WITH THE PROPER COMBINATION
CONDUIT/CABLE GROUNDING CLAMP. UNLESS PROHIBITED BY LOCAL CODES, THE GROUNDING POINT SHALL BE ESTABLISHED ON THE INCOMING WATER MAIN, UFER GROUND AND STRUCTURAL STEEL.
BUILDING METALLIC WATER PIPING SYSTEM MUST BE BONDED, AS REQUIRED BY CODES, TO THE GROUNDING BUS IN THE MAIN SERVICE APPARATUS. CAREFULLY CHECK THE DRAWINGS FOR ADDITIONAL
GROUNDING REQUIREMENTS AND COMPLY WITH NFPA 70 AND ALL OTHER APPLICABLE
CODES/STANDARDS.
E. GROUNDING ELECTRODE: UFER GROUND FABRICATED ACCORDING TO NFPA 70, PARAGRAPH 250-52(A)(3), USING A MINIMUM OF 20 FEET OF BARE COPPER CONDUCTOR NOT SMALLER THAN NO. 4 AWG. BOND GROUNDING CONDUCTOR BY CADWELD PROCESS TO REINFORCE STEEL IN AT LEAST 4 LOCATIONS AND
TO ANCHOR BOLTS.
260533 - RACEWAYS AND BOXES
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS"
SECTION.
B. CONDUIT RACEWAY:
1. INDOORS, USE THE FOLLOWING, UNLESS OTHERWISE STATED:
A. CONCEALED: EMT OR MC CABLE.
B. EXPOSED: EMT, IMC OR RMC.
C. CONNECTION TO VIBRATING EQUIPMENT: FLEXIBLE METAL CONDUIT.
2. OUTDOORS, USE THE FOLLOWING, UNLESS OTHERWISE STATED:
A. CONCEALED: RMC OR IMC.
B. EXPOSED: RMC OR IMC.
C. UNDERGROUND: SCHEDULE 40 PVC WITH SCHEDULE 80 PVC FITTINGS.
D. CONNECTION TO VIBRATING EQUIPMENT: LIQUID TIGHT FLEXIBLE METAL CONDUIT.
3. ENT IS NOT ALLOWED.
4. CONCEAL CONDUIT AND CABLE, UNLESS OTHERWISE NOTED; CONDUIT IS PERMITTED TO BE
EXPOSED IN EQUIPMENT ROOMS. ALL CONDUITS SHALL HAVE INSULATED GROUND WIRE INSTALLED.
DO NOT INSTALL CONDUIT EMBEDDED IN SLABS. EMT FITTINGS SHALL BE STEEL, COMPRESSION OR
SET SCREW TYPE. ALL RACEWAYS SHALL BE INSTALLED AND SUPPORTED IN ACCORDANCE WITH
NFPA 70 AND APPLICABLE CODES.
C. OUTLET BOXES:
1. CONFORM TO UL 514A, "METALLIC BOXES, ELECTRICAL," AND UL 514B, "FITTINGS FOR CONDUIT AND OUTLET BOXES." OUTLET BOXES SHALL BE METALLIC AND INSTALLED FLUSH IN ALL AREAS, EXCEPT MECHANICAL ROOMS, ABOVE LAY-IN CEILINGS, OR AS OTHERWISE INDICATED. MINIMUM SIZE TO BE 4 INCHES SQUARE BY 2-1/8 INCHES DEEP. BOXES SHALL BE OF TYPE, SHAPE, SIZE AND DEPTH TO SUIT
EACH LOCATION AND APPLICATION. ALL FITTINGS SHALL BE STEEL.
D. PULL AND JUNCTION BOXES:
1. COMPLY WITH UL 50, "ELECTRICAL CABINETS AND BOXES," FOR BOXES OVER 100 CUBIC INCHES
VOLUME. BOXES SHALL HAVE SCREWED OR BOLT-ON COVERS, SHALL BE SUITABLE FOR THE
INTENDED APPLICATION AND SHALL BE LABELED.
E. ALL MATERIALS SHALL BE UL LISTED, APPROPRIATE FOR INTENDED APPLICATION. ENTIRE RACEWAY SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 70, ANSI, NEMA, UL, AND ALL OTHER APPLICABLE CODES.
262416 - PANELBOARDS
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. MANUFACTURER: SIEMENS, SQUARE-D, GE OR CUTLER HAMMER.
C. LOAD CENTERS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY NOTED.
D. PANELBOARDS SHALL HAVE ALUMINUM BUS INCLUDING NEUTRAL AND GROUND BARS. BREAKERS SHALL BE BOLT ON TYPE. ALL 3-POLE BREAKERS 30 AMP AND LARGER SHALL HAVE MINIMUM FEATURE OF A
THERMAL MAGNETIC ADJUSTMENT FEATURE.
E. PROVIDE TYPED CIRCUIT SCHEDULES FOR EXISTING PANELBOARDS WHERE LOADS HAVE CHANGED AND FRAMED,TYPED CIRCUIT SCHEDULES FOR ALL NEW PANELBOARDS WITH IDENTIFICATION OF ITEMS CONTROLLED BY EACH INDIVIDUAL BREAKER. INDICATE ROOM NUMBERS OF ITEMS CONTROLLED OR
ROOM NAME WHERE APPROPRIATE FOR OWNER'S CONVENIENCE.
262816 - CIRCUIT AND MOTOR DISCONNECTS
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS FOR ELECTRICAL"
SECTION.
B. MANUFACTURER: SAME AS PANELBOARD MANUFACTURER.
C. DISCONNECTS SHALL BE HEAVY DUTY TYPE WITH CLASS R REJECTION FEATURE WHEN REQUIRED TO BE FUSIBLE. VOLTAGE RATING SHALL BE AT OR GREATER THAN THE APPLICATION VOLTAGE. PROVIDE NEMA 3R ENCLOSURE FOR EXTERIOR LOCATIONS. SERVICE SWITCHES SHALL BE UL LISTED FOR USE AS
SERVICE EQUIPMENT.
262913 - MOTOR CONTROLLERS
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. MANUFACTURER: SAME AS PANELBOARD MANUFACTURER.
C. UNLESS SCHEDULED OTHERWISE, 3/4 HORSEPOWER OR LESS SINGLE-PHASE MOTORS SHALL HAVE 1 HP RATED MANUAL TOGGLE STARTERS WITH THERMAL OVERLOAD PROTECTION SIZED FOR THE MOTOR IN ACCORDANCE WITH NFPA 70. PROVIDE PILOT LIGHT FOR MANUAL STARTERS NOT IN SIGHT FROM MOTOR.
UNITS LOCATED AT THE EXTERIOR OF THE BUILDING SHALL BE NEMA 3R RATED.
D. STARTERS SHALL BE ACROSS-THE-LINE MAGNETIC TYPE, COMBINATION STARTER/DISCONNECT, FVNR, AND HP RATED, UNLESS OTHERWISE SCHEDULED. STARTER SHALL HAVE RESETABLE OVERLOAD
PROTECTION ON ALL PHASES, CONSTRUCTED OF ONE-PIECE CLASS 20 CONSTRUCTION. PROVIDE 120
VOLT CONTROL, H-O-A AND INTERLOCKS WHERE INDICATED ON SCHEDULES. PROVIDE TWO N/O
AUXILIARY CONTACTS. UNITS LOCATED AT THE BUILDING EXTERIOR SHALL BE NEMA 3R RATED.
E. ALL MOTOR CONTROLLERS SHALL BE UL LISTED AND INSTALLED IN ACCORDANCE WITH NFPA 70, NEMA, AND MANUFACTURER'S RECOMMENDATIONS.
265100 - LIGHTING
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. MANUFACTURER, MODEL, STYLE, COLOR, SIZE, ETC., AS SCHEDULED. IF NO COLOR HAS BEEN SELECTED, PROVIDE FIXTURE WITH THE STANDARD FINISH AS PUBLISHED BY THE MANUFACTURER. ALL FIXTURES TO BE SUPPLIED AS COMPLETE, HOUSING, SOCKETS, LAMP HOLDERS, INTERNAL WORKING, WIRE GUARDS, LENS GUARDS, DIFFUSING MATERIALS OR LENSES, PENDANTS, HANGERS, CANOPIES, ALIGNERS, END CAPS, BALLASTS AND EMERGENCY BATTERY PACKS, PLASTER FRAMES, RECESSING BOXES, HOLD DOWN CLIPS, ANCHOR BOLTS, ETC. INSTALL PLUMB AND TRUE, FREE OF LIGHT LEAKS, WARPS, DENTS AND
OTHER IRREGULARITIES.
C. SUPPORT FOR RECESSED AND SEMI-RECESSED GRID-TYPE FLUORESCENT FIXTURES:
1. ALL LIGHTING FIXTURES SHALL BE POSITIVELY ATTACHED TO THE SUSPENDED CEILING SYSTEM BY MECHANICAL MEANS AS SPECIFIED IN THE NATIONAL ELECTRIC CODE, SECTION 410-16 (C) UNLESS INDEPENDENTLY SUPPORTED. THE ATTACHMENT DEVICE, A MINIMUM OF TWO PER FIXTURE, SHALL HAVE A CAPACITY OF 100 PERCENT OF THE LIGHTING FIXTURE WEIGHT ACTING IN ANY DIRECTION.
2. PENDANT-HUNG LIGHTING FIXTURES SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE
USING NO. 9-GAGE WIRE OR AN APPROVED ALTERNATE SUPPORT WITHOUT USING THE CEILING
SUSPENSION SYSTEM FOR DIRECT SUPPORT.
3. LIGHTING FIXTURES WEIGHING LESS THAN 56 POUNDS SHALL HAVE, IN ADDITION TO THE
REQUIREMENTS OUTLINED ABOVE, TWO NO. 12-GAGE HANGERS CONNECTED FROM OPPOSITE
CORNERS OF THE FIXTURE HOUSING TO THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK.
4. LIGHTING FIXTURES WEIGHING 56 POUNDS OR MORE SHALL BE SUPPORTED DIRECTLY FROM THE
STRUCTURE ABOVE BY APPROVED HANGERS.
D. SUPPORT FOR SUSPENDED FIXTURES: BRACE PENDANTS AND RODS OVER 48 INCHES LONG TO LIMIT SWINGING. SUPPORT STEM-MOUNTED, SINGLE-UNIT, SUSPENDED FLUORESCENT FIXTURES WITH TWIN- STEM HANGERS. FOR CONTINUOUS ROWS, USE TUBING OR STEM FOR WIRING AT ONE POINT AND TUBING OR ROD FOR SUSPENSION FOR EACH UNIT LENGTH OF CHASSIS, INCLUDING ONE AT EACH END.
E. SURFACE-MOUNTED LIGHT FIXTURES ATTACHED TO A CEILING GRID SHALL BE ATTACHED WITH POSITIVE CLAMPING DEVICES THAT COMPLETELY SURROUND THE SUPPORTING MEMBERS. SAFETY WIRES SHALL BE ATTACHED BETWEEN THE CLAMPING DEVICE AND THE ADJACENT CEILING HANGER OR TO THE
STRUCTURE ABOVE.
DIVISION 27 - COMMUNICATIONS
270500 - TELE-DATA COMMUNICATIONS
A. SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE "COMMON WORK RESULTS" SECTION.
B. MANUFACTURERS: SIEMON, ICC, LEVITON, ORTRONICS, AMP, HUBBELL OR UNIPRISE.
C. STANDARDS: MATERIALS SHALL HAVE NRTL LISTING IN COMPLIANCE WITH UL910. COMPLY WITH TIA/EIA-569-A AND NFPA 70 FOR PATHWAYS AND SPACES, NECA 1, BICSI TDMM AND NFPA 70 FOR EQUIPMENT ROOM INSTALLATIONS, NECA 1, BICSI ITSIM CHAPTER 6 AND TIA/EIA-568 FOR CABLE INSTALLATIONS, TIA/EIA 568 FOR COPPER CONNECTING HARDWARE, TIA/EIA-568 AND TIA/EIA-604 FOR FIBER CONNECTING HARDWARE, TIA/EIA-J-STD-607A, BICSI TDMM AND NFPA 70 FOR GROUNDING, TIA/EIA-568B AND TIA/EIA 526-14-A FOR TESTING, TIA/EIA-606-A CLASS 2 LEVEL, UL 969 AND NFPA 70 FOR
LABELING.
D. TELEPHONE/DATA ROOMS: WHERE TERMINAL BOARDS ARE INDICATED ON THE CONSTRUCTION
DOCUMENTS, PROVIDE 3/4-INCH THICK INTERIOR GRADE PLYWOOD FROM FLOOR TO CEILING WITH FIRE RETARDANT PAINT ON ALL SIDES. COORDINATE CONDUIT FROM THE TELEPHONE TERMINAL BOARD (TTB) TO EXTERIOR OF BUILDING; SIZE AND ROUTE AS DICTATED BY SERVING UTILITY COMPANY. PROVIDE TTB COMMUNICATION GROUNDING BUS AS REQUIRED BY SERVING UTILITY, MINIMUM #6 AWG IN PVC CONDUIT, EXTENDED, SHORTEST AND MOST DIRECT ROUTE TO GROUND BAR AT MAIN SWITCH. TERMINATE IN GROUND BAR INSTALLED ON TTB. PROVIDE MINIMUM OF TWO QUAD-PLEX POWER RECEPTACLE 6 INCHES
ABOVE FINISHED FLOOR AND ADDITIONAL AS INDICATED ON DRAWINGS.
E. VOICE/DATA WORKSTATION ROUGH-INS: PROVIDE 4 INCH SQUARE, 2-1/8-INCH DEEP 1-GANG ROUGH-IN WITH 3/4-INCH CONDUIT STUBBED TO CEILING SPACE WITH A 90 DEGREE BEND AND INSULATED THROAT
BUSHING, UNLESS OTHERWISE STATED.
F. WORKSTATION OUTLET ASSEMBLIES: (MODULES SHALL BE COLOR CODED FOR SERVICE TYPE, FACEPLATE/JACK COLOR SAME AS SPECIFIED IN THE WIRING DEVICES SECTION).
1. WALL MOUNT TELEPHONE ASSEMBLY: STAINLESS STEEL WALL MOUNT PLATE WITH FLAT, CATEGORY
6, T568A/B, RJ45 MODULE.
2. VOICE ONLY WALL JACK ASSEMBLIES: (1) ANGLED CATEGORY 6, T568A/B, RJ45 MODULE AND (1)
BLANK MODULE IN A MODULAR STYLE FACEPLATE. FACEPLATE SHALL HAVE CLEAR VIEW LABEL
COVERS.
3. DATA ONLY WALL JACK ASSEMBLIES: (1) ANGLED CATEGORY 6, T568A/B, RJ45 MODULE AND (1) BLANK MODULE IN A MODULAR STYLE FACEPLATE. FACEPLATE SHALL HAVE CLEAR VIEW LABEL COVERS.
4. COMBINATION VOICE/DATA WALL JACK ASSEMBLIES: (3) ANGLED CATEGORY 6, T568A/B, RJ45
MODULES AND (3) BLANK MODULES IN A MODULAR STYLE FACEPLATE. FACEPLATE SHALL HAVE
CLEAR VIEW LABEL COVERS.
G. CABLES:
1. HORIZONTAL WORKSTATION CABLING: CATEGORY 6 UNSHIELDED TWISTED PAIR (UTP) CABLE, 4 PAIR, COLOR CODED, THERMOPLASTIC-INSULATED CONDUCTORS IN POLYVINYL CHLORIDE (PVC) JACKET.
USE PLENUM RATED CABLE IN SPACES USED FOR AIR HANDLING.
2. VERTICAL BACKBONE CABLING: CATEGORY 6 UNSHIELDED TWISTED PAIR (UTP) CABLE, 25 PAIR FOR
RUNS BETWEEN WIRING CLOSETS AND EQUIPMENT ROOMS.
3. FIBER OPTIC BACKBONE CABLING: FACTORY FABRICATED, JACKETED, LOW-LOSS, GLASS-TYPE, FIBER-OPTIC, MULTIMODE, GRADED INDEX, OPERATING AT 850 AND 1300 NANOMETERS. 12 STANDS PER CABLE, 62.5 MICRON CORE DIAMETER, 125 MICRON CLADDING, MAXIMUM ATTENUATION OF MINUS
3.75 DB/KM AT 850 NM AND 1.5 DB/KM AT 1300NM, MINIMUM MODAL BANDWIDTH OF 160 MHZ/KM AT 850 NM AND 500 MHZ/KM AT 1300 NM AND OPERATING TEMPERATURE RANGE OF MINUS 20 TO 70 DEG C.
H. WORKSTATION PATCH PANELS: WORKSTATION PATCH PANELS SHALL BE CATEGORY 6 IN 24 OR 48 PORT SIZES WITH REAR WIRE MANAGEMENT AND S110 TERMINATION BLOCKS. TELEPHONE PATCH PANELS SHALL BE CATEGORY 6 IN 24 OR 48 PORT SIZES WITH REAR WIRE MANAGEMENT AND S110
TERMINATION BLOCKS. ALL PATCH PANELS SHALL BE SEPARATED IN RACKS BY FRONT CABLE
MANAGERS (1.75 INCH FOR 24 PORT AND 3.5 INCH FOR 48 PORT). PROVIDE 110 STYLE, HINGED PUNCHDOWN BLOCKS AND 4-PAIR, CATEGORY 6 CABLES BETWEEN TELEPHONE PATCH PANEL AND 110 BLOCKS. CROSS CONNECTING BY TELEPHONE COMPANY. ALL EQUIPPED SHALL BE SELECTED AND
SIZED TO ACCOMMODATE INCOMING WORKSTATION CABLES PLUS 20 PERCENT SPARE CAPACITY.
I. FIBER BACKBONE PATCH PANELS: FIBER BACKBONE PATCH PANELS SHALL BE RACK MOUNTED PATCH PANELS IN 24 OR 48 PORT SIZES EQUIPPED TO ACCOMMODATE FIBER BACKBONE CABLES PLUS 20 PERCENT SPARE CAPACITY. PATCH PANELS SHALL HAVE QUICK-CONNECT, SIMPLEX AND DUPLEX TYPE SC COUPLERS WITH SELF-CENTERING, AXIAL ALIGNMENT MECHANISMS WITH INSERTION LOSS
NO MORE THAN .5 DB.
J. WORKSTATION PATCH CORDS (UTP): PROVIDE 4 PAIR CABLES IN APPROPRIATE LENGTHS FOR EACH WORKSTATION PATCH PANEL PORT (USED OR UNUSED), CATEGORY 6 RATED AND TERMINATED WITH
AN RJ-45 PLUG AT EACH END. CABLES TO BE ROUTED FROM WORKSTATION PATCH PANELS TO
TELEPHONE PATCH PANEL ABOVE OR OWNER'S HUB EQUIPMENT BELOW. LENGTH SHALL BE LONG
ENOUGH TO BE ROUTED FROM THE WORKSTATION PORT THROUGH THE FRONT CABLE MANAGER,
THROUGH THE SIDE CABLE MANAGER, THROUGH THE FRONT CABLE MANAGER TO THE TELEPHONE
PATCH PORT OR OWNER'S HUB PORT. ALSO, PROVIDE 6 FOOT, CATEGORY 6 RATED PATCH CORDS
FOR EACH WORKSTATION JACK AT THE USER END.
K. FIBER BACKBONE PATCH CORDS: PROVIDE DUAL FIBER CABLES IN 36 INCH OR 72 INCH LENGTHS FOR
EACH FIBER PATCH PANEL PORT.
L. WORKSTATION WIRING INSTALLATION:
1. INSTALL CABLE WITHOUT DAMAGING CONDUCTORS OR JACKET. DO NOT BEND CABLE TO A SMALLER
RADIUS THAN MINIMUM RECOMMENDED BY MANUFACTURER. DO NOT EXCEED MANUFACTURER'S
RECOMMENDED PULLING…