ESBD_393688_1738703430357_HHS0015184 Attachment H-3c.pdf

PDF 7 MB Posted

Attached to
Project 24-207-SAH, Alamo Hall Geriatric MSU Renovations, San Antonio, TX
Solicitation number
HHS0015184
Issued by
Texas

About this file

This file contains electrical construction documents from Moose Engineers for renovations at Alamo Hall and the Seidel Building at San Antonio State Hospital. The drawings include detailed electrical demolition plans, lighting floor plans, power floor plans, special systems floor plans, and electrical panel schedules for both buildings. The plans show existing electrical infrastructure to be demolished or modified as well as new electrical work to be installed as part of the renovation project.

The drawings provide comprehensive technical details including location of electrical panels, lighting fixtures, power outlets, special systems, and associated conduit/wiring. Key elements include modifications to lighting systems, power distribution, fire alarm systems, and other low voltage systems throughout both facilities. The electrical panel schedules specify circuit loads, branch circuits, and power requirements. The plans indicate close coordination required between electrical demolition and new work to maintain essential building systems during construction. Multiple drawing sheets show both floor levels of Alamo Hall as well as the Seidel Building, with detailed notes and specifications for electrical contractors to follow during implementation.

View the file

Other files

File Type Posted
ESBD_393688_1738699998320_HHS0015184 Attachment H-1f.pdf PDF
ESBD_393688_1738702541104_HHS0015184 Attachment H-2d.pdf PDF
ESBD_393688_1738699995334_HHS0015184 Attachment H-1g.pdf PDF
ESBD_393688_1738699992490_HHS0015184 Attachment H-1c.pdf PDF
ESBD_393688_1738699993254_HHS0015184 Attachment H-1a.pdf PDF
ESBD_393688_1738702536322_HHS0015184 Attachment H-2e.pdf PDF
ESBD_393688_1738699999440_HHS0015184 Attachment H-1e.pdf PDF
ESBD_393688_1738698135480_HHS0015184 Attachments.zip ZIP file
ESBD_393688_1738699994376_HHS0015184 Attachment H-1d.pdf PDF
ESBD_393688_1738699996382_HHS0015184 Attachment H-1i.pdf PDF
ESBD_393688_1738702539922_HHS0015184 Attachment H-2b.pdf PDF
ESBD_393688_1738702537792_HHS0015184 Attachment H-2g.pdf PDF
ESBD_393688_1738698012370_HHS0015184 RFP final.pdf PDF
ESBD_393688_1738699997302_HHS0015184 Attachment H-1h.pdf PDF
ESBD_393688_1738698053000_HHS0015184 Exhibits.zip ZIP file
ESBD_393688_1738702537061_HHS0015184 Attachment H-2f.pdf PDF
ESBD_393688_1738703429313_HHS0015184 Attachment H-3a.pdf PDF
ESBD_393688_1738699991716_HHS0015184 Attachment H-1b.pdf PDF
ESBD_393688_1738702542122_HHS0015184 Attachment H-2c.pdf PDF
ESBD_393688_1738703428621_HHS0015184 Attachment H-3b.pdf PDF
ESBD_393688_1738702538751_HHS0015184 Attachment H-2a.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

DN

C

SERVICE

DISCONNECT

SWITCH

AP/AT

PP

PP

PP

PP

PP

PP

DIP POLE

EXISTING

ELECTRICAL

GEAR TO

REMAIN

AP/ATAP/ATAP/AT

AP

AP

AP

AP AP

EXISTING

SERVICE

XFMR

"T3"

UP

DIP POLE

UP

AS/AT

TP

TP

TP

TP

TP TP

AT

ATATATAT

AT

AT

AT

AT

AT

AT

AT

AT

2 1

1 2

EXISTING

GENERATOR

SHALL BE

SALVAGED

ALAMO HALL BUILDING 521

SEIDEL BUILDING 598

EXISTING

MDP-3

SEC.1

EXISTING

MDP-3

SEC.2

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :0

P

M

ED0.1

ELECTRICAL SITE PLAN -

DEMOLITION

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1" = 20'-0"ED0.1

1 ELECTRICAL SITE PLAN - DEMOLITION

0' 10' 20' 40' 80'

SCALE: 1" = 20'-0"

EXISTING POWER/TELECOM LINES TO REMAIN.

EXISTING POLE TO REMAIN.

EXISTING POLE MOUNTED TRANSFORMERS TO REMAIN.

REMOVE EXISTING GENERATOR AND ASSOCIATED EQUIPMENT. REFER TO SHEET E4.1 FOR

MORE INFORMATION. RETURN TO OWNER FOR SALVAGE.

DEMOLISH EXISTING FEEDERS FROM GENERATOR TO ATS. LINE IS SCHEMATIC IN NATURE,

FIELD VERIFY. COORDINATE WITH OWNER FOR SALVAGE OF ATS. REFER TO E4.1 FOR MORE

INFORMATION.

DEMOLISH EXISTING FEEDERS FROM TRANSFORMER T3 TO MDP-3. REFER TO E4.2 FOR MORE

INFORMATION.

EXISTING AERIAL SECONDARY FEEDERS AND WEATHERHEAD TO BE DEMOLISHED. EXISTING

SERVICE RATED DISCONNECT SWITCH TO BE DEMOLISHED. REFER TO SHEET E4.1 FOR MORE

INFORMATION.

EXISTING AERIAL TELECOM TO REMAIN. PROTECT DURING ELECTRICAL REWORK.

DEMOLITION KEYED NOTES:

GENERAL DEMOLITION NOTES: (APPLIES TO ALL DEMOLITION SHEETS)

1. SEE OTHER SHEETS FOR ADDITIONAL DEVICES

2. GENERAL: EXCEPT FOR ITEMS OR MATERIALS INDICATED TO BE REUSED, SALVAGED, REINSTALLED, OR OTHERWISE INDICATED TO REMAIN OWNER'S PROPERTY, REMOVE DEMOLISHED MATERIALS FROM PROJECT SITE AND LEGALLY DISPOSE OF THEM IN AN EPA-APPROVED LANDFILL. DO NOT ALLOW DEMOLISHED MATERIALS TO ACCUMULATE ON-SITE REMOVE FROM OWNER OCCUPIED AREAS DAILY. REMOVE AND TRANSPORT DEBRIS IN

A MANNER THAT WILL PREVENT SPILLAGE ON ADJACENT SURFACES AND AREAS.

3. TRACE CIRCUITS FEEDING EXISTING TO-REMAIN PORTIONS OF THE BUILDING. DO NOT DEMOLISH CIRCUITS IN THESE AREAS. IF CIRCUITS ARE IN BOTH "TO REMAIN" AND "TO BE REMOVED" AREAS, DEMOLISH BACK TO

NEAREST TO-REMAIN J-BOX.

4. DEMOLISH AND REMOVE EXISTING CONSTRUCTION ONLY TO THE EXTENT REQUIRED BY NEW CONSTRUCTION AND AS INDICATED. COMPLETE SELECTIVE DEMOLITION OPERATIONS ABOVE EACH FLOOR OR TIER BEFORE

DISTURBING SUPPORTING MEMBERS ON THE NEXT LOWER LEVEL.

5. REMOVED AND SALVAGED ITEMS: CLEAN SALVAGED ITEMS, PACK OR CRATE ITEMS AFTER CLEANING.

IDENTIFY CONTENTS OF CONTAINERS. STORE ITEMS IN A SECURE AREA UNTIL DELIVERY TO OWNER.

TRANSPORT ITEMS TO OWNER'S STORAGE AREA DESIGNATED BY OWNER. PROTECT ITEMS FROM DAMAGE

DURING TRANSPORT AND STORAGE.

6. REMOVED AND REINSTALLED ITEMS: CLEAN AND REPAIR ITEMS TO FUNCTIONAL CONDITION ADEQUATE FOR INTENDED REUSE. PAINT EQUIPMENT TO MATCH NEW EQUIPMENT. PACK OR CRATE ITEMS AFTER CLEANING AND REPAIRING. IDENTIFY CONTENTS OF CONTAINERS. PROTECT ITEMS FROM DAMAGE DURING TRANSPORT AND STORAGE. REINSTALL ITEMS IN LOCATIONS INDICATED. COMPLY WITH INSTALLATION REQUIREMENTS FOR NEW MATERIALS AND EQUIPMENT. PROVIDE CONNECTIONS, SUPPORTS, AND MISCELLANEOUS MATERIALS

NECESSARY TO MAKE ITEM FUNCTIONAL FOR USE INDICATED.

7. EXISTING ITEMS TO REMAIN: PROTECT CONSTRUCTION INDICATED TO REMAIN AGAINST DAMAGE AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY ARCHITECT, ITEMS MAY BE REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND REINSTALLED IN THEIR ORIGINAL

LOCATIONS AFTER SELECTIVE DEMOLITION OPERATIONS ARE COMPLETE.

8. COORDINATE ALL DEMO ACTIVITIES WITH OWNER AND ARCHITECT AND PROVIDE 10 DAYS NOTICE FOR ANY

POWER OUTAGES.

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

01/29/2025

V

V

V

V

AV

F

AV

AV

V

V V

AV

V

AV

AV

V

V

V

AV

AV

AVAV

AV

AV

F

SD F

F

HD

V

AV

V V

AV

AV

V

AV

V

AV

V

SD

F

F F

F

F

AVAV

AV AV

AV

F

V

AV

AV

F

HD

V

AV

V

F

F

AV

AV AV

AV

SD

SD

FACP

A

FA ANNFA ANN

A

TS

FS

A

TS

FS

A

FSD

DSD

WP

WP

WP

EXISTING

NAC

MECH RM

D

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :0

P

M

ED3.3

SPECIAL SYSTEMS DEMO

FLOOR PLAN - SEIDEL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1/8" = 1'-0"ED3.3

1 SPECIAL SYSTEMS DEMOLITION FLOOR PLAN - SEIDEL

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

EXISTING FIRE ALARM DEVICE TO REMAIN.

REMOVE EXISTING FIRE ALARM DEVICE.

ALTERNATE: EXISTING CEILING TO BE REPLACED. BAG, COIL, AND SECURE

EXISTING DEVICE. DEVICE TO BE REINSTALLED IN SAME LOCATION IN NEW

WORK.

EXISTING FIRE ALARM EQUIPMENT TO REMAIN.

DEMOLITION SPECIAL SYSTEMS KEYED NOTES:

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

01/29/2025

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

UP

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

CONSULT 1

DOCTOR'S

OFFICE

DOCTOR'S

OFFICE

CONSULT 2

STAFF TOILET

EXAM TOILET

MECH. ROOM

ELEV. MACH.

ROOM

NEW ELEVATOR

EVS SUPPLY

MECH ROOM

IT / SERVER

SERVERY/

NOURISHMENT

TREATMENT

PLANNING &

TELEHEALTH

CONFERENCE

PSYCHOLOGISTS

INCENTIVE

THERAPY

PNA OFFICE

EXAM ROOM

ADMIN OFFICE

MECH ROOM

ELEC. ROOM

COMFORT ROOM

STOR.

STAFF T/R

PROGRAM

COORDINATOR

STORAGE

SECURE

RECEIVING

FIRE RISER

ROOM

PATIENT

CORRIDOR

PATIENT

CORRIDOR

STAFF

CORRIDOR

OFFICE

SOCIAL OFFICE

STORAGE

EMRG. ELEC.

LOBBY/SCREENING

STAIRS S2

STAIRS

120B

STAIRS

GROUP

STAIRS

STAIRS

VESTIBULE

INCENTIVE

THERAPY

NOISY / DINING

STORAGE

SUPPLY

STORAGE ROOM

CLEAN LINEN

ELEVATOR

SCREEN/

RECEIVING

QUIET ACTIVITY

ADA PATIENT

TOILET

STAFF TLT.

GROUP

STAFF

ELOPEMENT

EAST PORCH

NURSE

MANAGER

FRONT PORCH

100A

EVS

STAFF STATION

MED ROOM

CONSULT 3

STAFF OFFICE

ADA PATIENT

TLT.

STAFF

ELOPEMENT

STAFF

CORRIDOR

R-A1

R-A1

A

R-B

R-B

R-B

R-C2

R-A1

R-A1 D

R-A1

R-A1

B B B

G

G

R-B R-B

R-B

SC

SC

R-A1R-A1

X

X

X

X

R-A15

6 5

SC1

WP

R-BR-B

R-B

R-A1

R-A1

R-A1

R-A1

R-A1

G

R-A1

R-A1

R-A1

R-B R-B

R-BR-B

R-B R-B R-B

X

X

X 6

X

X X

X

X

X

X

VS

SC1

SC1

X X

VS

J J J

J J

VS

VS

VS

VS

J

J

J

R-A1

J

J J

J

J J

J J

J

J

J

J

J

J J

J

J

J

J J J

J

J

J J J

J

J J

K

K

LS1-14(S.C.)

L1B-22

L1B-15

STOR.

J

J

J

J

J

6 6

J

R-A1

J J

R-A1

J

R-A1

J

J

G

G

J

WHEELCHAIR

STORAGE

100D

R-A1

J

C

C

R-A1

J

VS

f f f f a f a a a a a a a a a a a

3b a b b bb b b

3bc a a a a a g g g g g c c c c c c c c c c c c cc c c h h h h h

J

J m m m m m m m q q q

J

J

J

J

J

J

J

J

J

J

X 6

X

J

X

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :2

P

M

E1.1

LIGHTING FIRST FLOOR

PLAN - ALAMO HALL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1/8" = 1'-0"E1.1

1 LIGHTING FIRST FLOOR PLAN - ALAMO HALL

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

CONNECT TO EXISTING LIGHTING CIRCUIT SERVING FIXTURE INDICATED.

EXISTING LIGHTING IN ELEVATOR SHAFT TO REMAIN.

REFER TO DETAIL 2, SHEET E6.1 FOR LIGHTING IN ELEVATOR SHAFT.

PROVIDE NEW LIGHTING CONTROLS TO CONTROL EXISTING LIGHTS IN SPACE.

EGRESS LIGHT. FIXTURE SHALL BE CONTROLLED VIA SWITCHING OF NORMAL LIGHTS IN SPACE. PROVIDE UL-924 DEVICE TO FULLY ILLUMINATE FIXTURE UPON LOSS OF NORMAL POWER, REGARDLESS OF SWITCH POSITION. CONNECT TO EXISTING LIFE SAFETY

LIGHTING BRANCH CIRCUIT IN AREA.

FIXTURE SHALL BE ALWAYS ON AND CONNECTED TO EXISTING UNSWITCHED LIFE SAFETY LIGHTING BRANCH CIRCUIT IN AREA.

EXTERIOR LIGHTS SHALL BE CONNECTED TO EXISTING WALL PACK LIGHTING CIRCUIT AND CONTROLLED THRU EXISTING TIMECLOCK

AND PHOTOCELL.

CONNECT EXISTING LIGHT FIXTURE TO NEW CIRCUIT INDICATED.

EGRESS LIGHT CIRCUIT FOR EXISTING LIGHT. EXISTING FIXTURE SHALL BE CONTROLLED VIA SWITCHING OF NORMAL LIGHTS IN SPACE.

PROVIDE UL-924 DEVICE TO FULLY ILLUMINATE FIXTURE UPON LOSS OF NORMAL POWER, REGARDLESS OF SWITCH POSITION.

CONNECT TO EXISTING LIFE SAFETY LIGHTING BRANCH CIRCUIT IN AREA.

ELECTRICAL LIGHTING KEYED NOTES:

GENERAL NOTES LIGHTING SHEETS: (APPLIES TO ALL LIGHTING SHEETS)

1. DEVICE LOCATION GUIDELINES: LOCATE DEVICES ADJACENT TO THE DOOR FRAMES 4 INCHES TO THE EDGE OF THE DEVICES AT ADA HEIGHT GUIDELINES. CO-LOCATE SIMILAR DEVICES UNDER A COMMON FACEPLACE (EXAMPLE - MULTIPLE LIGHT SWITCHES). LOCATE ADDITIONAL DEVICES HORIZONTALLY ADJACENT TO EACH OTHER. COORDINATE SWITCH LOCATIONS IN ROOMS WITH ARCHITECT AND OTHER DEVICES (THERMOSTATS, FIRE ALARM, AND CALL BUTTONS). DO NOT STAGGER DEVICES. ONLY WHEN HORIZONTAL SPACE DOES NOT PERMIT, STACK DEVICES VERTICALLY WITH TWO INCHES BETWEEN FACEPLATES TO NO MORE THAN 72 INCHES AFF TO THE TOP OF THE FACEPLATE.

COORDINATE LOCATIONS WITH ARCHITECTURAL ELEVATIONS. DEVICES SHALL BE MOUNTED AT SPECIFIC DEVICE MOUNTING HEIGHTS AS LISTED

PER SPECIFICATIONS.

2. SWITCHES SHALL BE PROVIDED FOR EACH ROOM.

3. MINIMUM CIRCUIT SIZE IS 2 #12 AND 1 #12 GROUND IN ½” CONDUIT. MAXIMUM FIXTURE WHIP LENGTH FROM ANY J-BOX 6 FEET. LIGHTING CIRCUITS JOINTS SHALL BE MADE UP IN OVERHEAD J-BOXES SECURED TO STRUCTURE WITH LIGHTING WHIPS FROM THE J-BOXES. FIXTURES

DESIGNED TO BE QUICK-CLIPPED TOGETHER SHALL BE CONNECTED AS PER MANUFACTURER.

4. COORDINATE LIGHT LOCATIONS WITH OTHER CEILING ITEMS OR JOIST ITEMS PRIOR TO INSTALLATION. LIGHT LOCATIONS TAKE PRECEDENCE

OVER AIR DEVICES.

5. PROVIDE SECONDARY SUPPORT WIRES FROM ALL FOUR (4) CORNERS OF THE LAY-IN FIXTURES TO THE STRUCTURE ABOVE. DO NOT SUPPORT FIXTURES FROM CEILING GRID WIRE SUPPORTS, PIPING, CONDUIT, SIDE WALLS, OR MECHANICAL EQUIPMENT. CEILING SPECIFICATIONS DO NOT

SUPERCEDE THIS REQUIREMENT.

6. HATCHED FIXTURES ARE UNSWITCHED.

7. FIXTURES WITH “E” SUFFIX ARE CONNECTED TO GENERATOR BACKED LIFE SAFETY BRANCH.

8. FIRESTOP ALL CONDUIT PENETRATIONS IN RATED WALLS. SEE ARCHITECTURAL FOR WALL RATINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE TO SHEET ROCK AND REPAIR. PROVIDE FIRE RATED SLEEVES IN ALL FLOOR PENETRATIONS.

9. CONTRACTOR TO VERIFY FIXTURE VOLTAGE PRIOR TO INSTALLING ANY RELOCATED FIXTURE. COORDINATE WITH RCP FOR FIXTURE

LOCATIONS.

10. ALL RELOCATED FIXTURES SHALL BE CLEANED AND TESTED. IF DAMAGED DURING CONSTRUCTION, CONTRACTOR SHALL REPLACE FIXTURE

AT NO CHARGE TO OWNER.

11. ALL SWITCH WALLPLATES IN PATIENT CARE SPACES SHALL BE STEEL WITH TORX HEAD W/ CENTER PIN FASTENERS.

KENALL #WSP-A-6-S-1 OR EQUAL.

12. ALL FASTENERS ASSOCIATED WITH LIGATURE RESISTANT LIGHTING FIXTURES SHALL BE TORX HEX SCREWS.

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

D W

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

MECH ROOM

ADA PATIENT

BED 6

ADA PATIENT

BED 5

PATIENT BED 3

PATIENT BED 2

PATIENT BED 7

NEW ELEVATOR

STAFF STATION

ELECT. ROOM

SECLUSION ANTE

ANTE ROOM T/R

SECLUSION

ROOM

ADA TLT /

SHWR 2

CLN

PATIENT BED 17

PAT TLT. 6

STOR.

EXAM ROOM

STOR.

PATIENT BED 1

PATIENT BED 4

PAT TLT. 2

STAFF

OBSERVATION

SOILED

PATIENT SHWR 2

ELOPEMENT

CONSULT 4

ADA PATIENT

BED 15

SHWR 3

PATIENT BED 19

PATIENT BED 20

MECH. ROOM

PAT TLT. 5

MECH ROOM

PAT TLT

ELOPEMENT

PATIENT

CORRIDOR

PATIENT

CORRIDOR

ADA TLT / SHWR

206 EVS

CLN

IDF ROOM

LAUNDRY

PATIENT BED 18

EXISTING STAIRS

INCENTIVE

THERAPY

STAIRS

ELEVATOR

PATIENT BED 16

PATIENT BED

PATIENT BED

PATIENT BED

PAT TLT. 3

PATIENT BED

PAT. TLT. 4

PATIENT BED

ADA PATIENT

BED 14

PATIENT

SHOWER 1

PAT TLT. 1

PATIENT BED

STOR.

STOR.

PATIENT

CORRIDOR

STOR.

PATIENT

CORRIDOR

PATIENT

CORRIDOR

MAIN MED RM

G

G

R-A1

G

R-A1R-A1

R-A1

R-A1

R-A1

A

A

A

R-A1

R-A1

R-A1

R-A1R-A1

R-A1

R-A1

C

C C

G G

C

VS

C

R-A2

R-A2

R-A2

STAIRS

C

X

X

X

X X

8 8

X X

X

X

X

X

X

X

X

X

X 8

SECONDARY

MED RM.

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

1 1

VS

VS

J

R-A1R-A1

R-A1

R-A1 R-A1

J J

R-A1

PAT TLT / TUB

J

J

R-A1

R-A1

J

J J J

STAFF

RESTROOM

J

J

J

X8 a a a a a a a a a a a a a a a a a a a a a ab b c3

3c c

NOISY ACTIVITY

200R-A1

J c c

JJ

J

A

9 J

VESTIBULE

231A

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :2

P

M

E1.2

LIGHTING SECOND FLOOR

PLAN - ALAMO HALL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1/8" = 1'-0"E1.2

1 LIGHTING SECOND FLOOR PLAN - ALAMO HALL

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

CONNECT TO EXISTING LIGHTING CIRCUIT SERVING FIXTURE INDICATED.

PROVIDE NEW LIGHTING CONTROLS TO CONTROL EXISTING LIGHTS IN SPACE.

REFER TO DETAIL 2, SHEET E6.1 FOR LIGHTING IN ELEVATOR SHAFT.

RELOCATED PATIENT ROOM NIGHTLIGHT FIXTURE. EXTEND EXISTING CIRCUIT TO NEW LOCATION. MATCH EXISTING CONDUIT AND

CONDUCTOR SIZE.

RELOCATED LIGHTING CONTROLS. EXTEND CIRCUIT TO LOCATION SHOWN. MATCH EXISTING CONDUIT AND CONDUCTOR SIZE.

RELOCATED LIGHT SWITCH FOR SECLUSION ROOM. EXTEND CIRCUIT TO LOCATION SHOWN. MATCH EXISTING CONDUIT AND

CONDUCTOR SIZE.

EGRESS LIGHT. FIXTURE SHALL BE CONTROLLED VIA SWITCHING OF NORMAL LIGHTS IN SPACE. PROVIDE UL-924 DEVICE TO FULLY ILLUMINATE FIXTURE UPON LOSS OF NORMAL POWER, REGARDLESS OF SWITCH POSITION. CONNECT TO EXISTING LIFE SAFETY

LIGHTING BRANCH CIRCUIT IN AREA.

FIXTURE SHALL BE ALWAYS ON AND CONNECTED TO UNSWITCHED CIRCUIT, CONNECT TO EXISTING UNSWITCHED LIFE SAFETY

LIGHTING BRANCH CIRCUIT IN AREA.

EGRESS LIGHT CIRCUIT FOR EXISTING LIGHT. EXISTING FIXTURE SHALL BE CONTROLLED VIA SWITCHING OF NORMAL LIGHTS IN SPACE.

PROVIDE UL-924 DEVICE TO FULLY ILLUMINATE FIXTURE UPON LOSS OF NORMAL POWER, REGARDLESS OF SWITCH POSITION.

CONNECT TO EXISTING LIFE SAFETY LIGHTING BRANCH CIRCUIT IN AREA.

ELECTRICAL LIGHTING KEYED NOTES:

ALTERNATE 3: PROVIDE NEW LIGHT FIXTURES IN EXISTING LOCATIONS FOR PATIENT ROOMS.

DISCONNECT AND RECONNECT EXISTING CIRCUIT FOR FIXTURE:

- WHERE EITHER EXISTING OR NEW 2X4 ARE SHOWN, PROVIDE TYPE "K" FIXTURE.

- WHERE EITHER EXISTING OR NEW 1X4 ARE SHOWN, PROVIDE TYPE "F" FIXTURE.

ALTERNATE LIGHTING GENERAL NOTE:

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

01/29/2025

Revision Schedule

UP

B

B

HHH

B

H

H

BBBBBB

B

F

F

X

X

X

X

X

X

X

X

X

B

B B

B B

C

PATIENT BLDG

STORAGE

S109

STAFF TLT

S110

LAW TLT

S125

LAW LOUNGE

S124

PAT TLT

S111

EVS

S108

BED BUG

S114

PUBLIC TLT

S106

TELEHEALTH

S116

SIT/PRIV

S107

TLT/ SHWR

S113

PATIENT

EVALUATION

S117

SECURITY IT

SERVERS

S121

ELOPEMENT

S122

OPEN VISIT

S105

CENTRAL

CONTROL

S118

SECURITY/

SCREENING

S103

OFFICE

S120

PUBLIC LOBBY/

WAIT

S100

STAFF

VESTIBULE

S104

SHELL

SHELL

ELOPEMENT

S122

ADMISSIONS/

SCREENING

AREA

S112

STAFF

BREAKROOM &

LOCKERS

S101

STAFF T/R

S102

CORR.

S123

STAFF OPEN

AREA

S119

MEDICATION

ROOM

S117A

B B B

B

B

B

B B

B

B

B

B

B

KKK

B

BB

B

B

K

K

K

K K

K K

K K

L

L

SA

SA

SA

SA

SA

SA

2 2

1 1

B

2 2

SB SB

3 3

SB

SC 3

K

K

K

K

K

SC

SC

F

F F

F

F

F

F K

H

SERVING

F

SC1

J

J

J J J J J JJ J J

J J J

J J

J

J

J J J

J J

J

J

J

J

J J J

J

J

J

J

J J

J

JJ

J

J

J J

J J

J J

J

JJ

J

J J

J

J

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

J

J

J J

J

B-2

B-4

B-6

B

B

NEW LTG

INV.

NEW

PANEL "B"

SC 3

INV-3

TC

OS

j j j j jj j j

INV-3

c c c c a a a a a a f f f f f b b b b g g g g g g g h h h h h h

J

J

NEW

"ATS-SB2"

NEW

GENERATOR

"G2"

EXISTING

SERVICE

XFMR

"T3"

EXISTING

MDP-3

SEC.2

h

EXISTING

PANEL

"P"

X 2

X

NEW

PANEL

"C"

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :2

P

M

E1.3

LIGHTING FLOOR PLAN -

SEIDEL BUILDING

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1/8" = 1'-0"E1.3

1 LIGHTING FLOOR PLAN - SEIDEL

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

1 EGRESS LIGHT. FIXTURE SHALL BE CONTROLLED VIA SWITCHING OF NORMAL LIGHTS IN SPACE. PROVIDE UL-924 DEVICE TO FULLY ILLUMINATE FIXTURE UPON LOSS OF NORMAL POWER, REGARDLESS OF SWITCH POSITION. CONNECT TO LIGHTING INVERTER CIRCUIT 1.

FIXTURE SHALL BE ALWAYS ON AND CONNECTED TO UNSWITCHED CIRCUIT, LIGHTING INVERTER CIRCUIT 2.

EXTERIOR LIGHTS SHALL BE CONTROLLED THRU NEW ASTRONOMICAL TIMECLOCK AND PHOTOCELL. CONNECT TO LIGHTING INVERTER CIRCUIT 3.

REFEED ANY EXISTING TO REMAIN LIGHTING BRANCH CIRCUITS BEING SERVED FROM DEMOLISHED PANEL "B" FROM PANEL "C". PRICE (1) 20A/1P

CIRCUIT REFEED. VERIFY VOLTAGE PRIOR TO REWORK.

ALTERNATE: PRICE NEW WORK OF THIS AREA AS ALTERNATE.

MOUNT FIXTURE ON RACK. PROVIDE WP SWITCH TO CONTROL FIXTURE. CONNECT TO 120V CIRCUIT SERVING RACK RECEPTACLE, CKT C-8. MOUNT

LIGHT AT TOP OF RACK TO ILLUMINATE GENERATOR AREA.

COORDINATE SWITCH LOCATIONS WITH OWNER PRIOR TO ROUGH-IN.

ELECTRICAL KEYED NOTES:

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

01/29/2025

UP

C

J

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

GFI

T-1 MSB

HM1

L1A

L1B

LS1 CR

NEW

GENERATOR

"G1"

NEW PAD

MOUNT

DOCKING

STATION

"DS1"

ATS-SB1

T

T TV

T

T

T

T TV

T

T

REF AC

GFI

ATS-E1

CONSULT 1

DOCTOR'S

OFFICE

DOCTOR'S

OFFICE

CONSULT 2

STAFF TOILET

EXAM TOILET

MECH. ROOM

ELEV. MACH.

ROOM

NEW ELEVATOR

EVS SUPPLY

CONSULT 3

MECH ROOM

IT / SERVER

SERVERY/

NOURISHMENT

STAFF

CORRIDOR

TREATMENT

PLANNING &

TELEHEALTH

CONFERENCE

PSYCHOLOGISTS

INCENTIVE

THERAPY

PNA OFFICE

EXAM ROOM

ADMIN OFFICE

MECH ROOM

ELEC. ROOM

COMFORT ROOM

STOR.

STAFF T/R

PROGRAM

COORDINATOR

STORAGE

SECURE

RECEIVING

FIRE RISER

ROOM

PATIENT

CORRIDOR

PATIENT

CORRIDOR

STAFF

CORRIDOR

OFFICE

SOCIAL OFFICE

STORAGE

EMRG. ELEC.

LOBBY/SCREENING

WEST PORCH

100B

FRONT PORCH

100A

STAIRS S2

STAIRS

120B

STAIRS

NORTH PORCH

STAIRS

ADA PATIENT

TLT.

STAIRS

VESTIBULE

MED ROOM

INCENTIVE

THERAPY

NOISY / DINING

STORAGE

SUPPLY

STORAGE ROOM

CLEAN LINEN

ELEVATOR

SCREEN/

RECEIVING

QUIET ACTIVITY

ADA PATIENT

TOILET

EVS

STAFF TLT.

GROUP

STAFF

ELOPEMENT

STOR.

EAST PORCH

NURSE

MANAGER

STAFF

141 B

PRINTER ALCOVE

STAFF STATION

ADA PATIENT

TLT.

STAFF

ELOPEMENT

STAFF OFFICE

GFI

AC

GFI

T

AC

GFI

T

GFI

D.S. "E1P"

D.S. "E1S"

EPO

GEN

GEN ANN

FA ANN

T TV

T TV

TV

WP

GFI

WP

GFI

GFI

AC

GFI

LS1-14(S.C.)

L1A-2 L1C-7

L1C-16 L1C-18

L1C-12 L1C-14

L1C-6

CR-18

CR-5

CR-7

L1C-11

L1C-9

LS1-7

CR-23

CR-14

T

T

T

T

T

T

L1C-2

L1C-4

L1A-14

T

L1A-11

L1A-15

L1A-20

L1B-20

L1A-34

AC

L1C-10 L1C-8

T

TV

FB

T

T

GFI

GFI

GFI

T

NEW

PANEL

L1C

SBH

F.D.S.

"SDS"

F.D.S.

"E1"

FUEL

FILTER

"X1E1"

T

T

GFI

T

T

T

T

AC

GFI

T

AC

GFI

T

AC

GFI

T

T T

T

T

T

T

T

MSB-20,22,24

SBH-1,3,5

FB

ELEV 1

DISC.

SWITCH

CORR.

113A

WHEELCHAIR

STORAGE

100D

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :3

P

M

E2.1

POWER FIRST FLOOR

PLAN - ALAMO HALL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

1/8" = 1'-0"E2.1

1 POWER FIRST FLOOR PLAN - ALAMO HALL

NEW GENERATOR WITH 96 HOUR BELLY TANK. SEE SHEET E4.1 FOR MORE INFORMATION. FUEL INLET PORT SHALL BE LOCATED

CLOSEST TO SERVICE DRIVE. EXHAUST AIR SHALL VENT UP.

NEW ATS-SB1 AND PANEL "SBH". REWORK FEEDERS SERVING EXISTING PANEL "MSB". REF: E4.1.

NEW ATS-E1 DISTRIBUTION. COORDINATE LOCATION WITH WINDOWS.

NEW ELEVATOR POWER CONNECTION. REF DETAILS 1,2/E6.1. EXISTING RECEPTACLES, LIGHTING, SUMP PUMP IN SHAFT TO REMAIN.

POWERED DOOR HOLDER. CONNECT TO EXISTING 120V CIRCUIT SERVING EXISTING DOOR HOLDERS, CIRCUIT LS1-7. DOORS SHALL

BE INTERLOCKED WITH FIRE ALARM SYSTEM.

REMOTE EPO FOR GENERATOR. COORDINATE FINAL LOCATION WITH OWNER PRIOR TO ROUGH-IN.

RECEPTACLE DEDICATED FOR X-RAY MACHINE. COORDINATE FINAL LOCATION WITH OWNER PRIOR TO ROUGH-IN.

CONNECT TO EXISTING 120V RECEPTACLE CIRCUIT INDICATED. EXTEND TO NEW RECEPTACLE LOCATIONS, 2#12 AND #12GND IN 3/4"C.

REPLACE EXISTING RECEPTACLE WITH "T" RECEPTACLE.

POWER FOR ICEMAKER/WATER DISPENSER. COORDINATE MOUNTING HEIGHT AND CONNECTION WITH EQUIPMENT PROVIDED.

NEW ELEVATOR POWER CONNECTION. REF DETAILS 1,2/E6.1. NEW RECEPTACLES, LIGHTING, SUMP PUMP 120V CIRCUIT SHALL BE FED

FROM PANEL C-1,3,5.

FIELD COORDINATE LOCATION OF FUEL FILTER. REF: E4.1.

ELECTRICAL POWER KEYED NOTES:

GENERAL NOTES POWER SHEETS: (APPLIES TO ALL POWER SHEETS)

1. SEE ALL OTHER PLANS FOR ADDITIONAL DEVICES. SOME POWER CIRCUITING MAY BE ON OTHER PLANS. COORDINATE THE LOCATIONS OF

DATA/CATV JACKS WITH THE RECEPTACLES. MOUNT ADJACENT TO EACH OTHER.

2. WHEN LOCATING SYSTEMS NEXT TO DOORS FOLLOW DEVICE LOCATION GUIDELINES. MOUNT AT ADA HEIGHT. PROVIDE MULTI-GANG BOXES

FOR SIMILAR SYSTEMS. ALL DEVICE PLATES SHALL BE ORTHOGONAL WITH ADJACENT PLATES.

3. MINIMUM CIRCUIT SIZE IS 2 #12 AND 1 #12 GROUND IN 3/4” CONDUIT. ALL CONDUCTORS SHALL BE 75 DEGREE COPPER THHN INDOOR, THWN FOR EXTERIOR USAGE, COLOR CODED AS PER NEC AND LOCAL AMENDMENTS WITH SIZE, TEMPERATURE, AND VOLTAGE PERMANENTLY PRINTED ON THE JACKET. ALL JOINTS SHALL BE MADE UP USING SELF LOCKING, TWIST-ON, COLOR CODED, SQUARE WIRE SPRING GRAB, LONG SKIRT, WIRE CONNECTORS WITH SWEPT WINGS.

4. COORDINATE RECEPTACLE LOCATIONS WITH MILLWORK AND COUNTERS. DO NOT LOCATE RECEPTACLES BEHIND DRAWERS OR HIDDEN IN MILLWORK UNLESS SPECIFICALLY DIRECTED BY OWNER/ARCHITECT. REVIEW ARCHITECTURAL ELEVATIONS PRIOR TO RECEPTACLE ROUGH-INS.

SEE ARCH ELEVATIONS IN BREAKROOMS FOR APPLIANCES AND RECEPTACLE MOUNTING LOCATIONS.

5. ALL RECEPTACLES SHALL BE HOSPITAL GRADE, MINIMUM 20 AMP RATED. GFI RECEPTACLES SHALL HAVE TEST BUTTONS WITH INDICATOR LIGHTS. EXTERIOR RECEPTACLES SHALL BE LABELED WEATHER RESISTANT WITH WP COVERS CONFORMING TO WET LOCATION CORD CONNECTION, NEC 406. MOUNT RECEPTACLES 18” AFF, 6” ABOVE BACKSPLASH AT COUNTERS, 48” IN TOILET ROOMS, AT EQUIPMENT ROUGH-IN LOCATIONS FOR APPLIANCES, AND AS INDICATED FOR TV’S. PROVIDE GFI RECEPTACLES WITHIN SIX (6) FEET OF ALL SINKS, EXTERIOR RECEPTACLES, AND UNDERCOUNTER EQUIPMENT. OVERSIZED COVER PLATES ARE NOT ALLOWED. COORDINATE COLOR WITH OWNER/ARCHITECT. PROVIDE SPEC GRADE RECEPTACLES MOUNTED BEHIND WATER COOLERS WITH GFI CIRCUIT BREAKERS.

6. ALL EQUIPMENT SHALL HAVE AN INDIVIDUAL LOCAL DISCONNECTING MEANS, EITHER CORDED PLUG AND RECEPTACLE OR SWITCHED DISCONNECT. VERIFY FROM EQUIPMENT SUBMITTED OR RELOCATED IF DIRECT CONNECT OR RECEPTACLE. IF DIRECT CONNECT, PROVIDE SAFETY SWITCH LOCKABLE IN THE OPEN POSITION AS PER NEC. OTHERWISE PROVIDE RECEPTACLE CORD PLUG AS REQUIRED BY EQUIPMENT

SUBMITTAL.

7. ON CIRCUITS GREATER THAN 20A, FEEDING MULTIPLE PIECES OF EQUIPMENT, PROVIDE FUSED DISCONNECTS (SIZED FOR EQUIPMENT

PROTECTING).

8. PROVIDE INDIVIDUAL DISCONNECTS FOR ALL SMOKE FIRE DAMPERS AND VAV’S. NO EXCEPTIONS.

9. CONTRACTOR IS RESPONSIBLE FOR UPDATING THE CIRCUITING INFORMATION OF ELECTRICAL PANELS, HVAC CONTROLS, INTERCOM SWITCH BANKS, DATA/VOICE/VIDEO CABLING, AND ANY CIRCUITED SYSTEM INDICATING THE FINAL ROOM NUMBERING AND CIRCUIT NUMBER BASED UPON

THE ACTUAL INSTALLATION.

10. FIRESTOP ALL CONDUIT PENETRATIONS IN RATED WALLS. SEE ARCHITECTURAL FOR WALL RATINGS. CONTRACTOR SHALL BE RESPONSIBLE

FOR DAMAGE TO SHEET ROCK AND REPAIR.

11. PROVIDE FIRE RATED SLEEVES IN ALL FLOOR PENETRATIONS.

12. CONNECT NO MORE THAN 5 RECEPTACLES TO ANY CIRCUIT. VERIFY AND TRACE RECEPTACLE COUNT PRIOR TO CONNECTING TO EXISTING

CIRCUITS.

13. ALL WALLPLATES SHALL BE ENGRAVED WITH CIRCUIT NUMBER.

14. ALL WALL PLATES IN PATIENT AREAS SHALL BE SECURED ANTI-LIGATURE WITH TORX BIT HEAD W/ CENTER PIN.

15. ALL FEEDERS AND BRANCH CIRCUITS IN PROJECT SHALL BE IN METALLIC CONDUIT (EMT/IMC/RMC PER SPEC) WITH GREEN INSULATED

GROUND (EQUIPMENT GROUNDING CONDUCTOR).

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

GFI

S

HM2

L2A

45KVA

S

S

S

S

S

S

MECH ROOM

ADA PATIENT

BED 6

ADA PATIENT

BED 5

PATIENT BED 3

PATIENT BED 2

PATIENT BED 7

NEW ELEVATOR

STAFF STATION

ELECT. ROOM

SECLUSION ANTE

ANTE ROOM T/R

SECLUSION

ROOM

ADA TLT /

SHWR 2

CLN

PATIENT BED 17

PAT TLT. 6

STOR.

EXAM ROOM

STOR.

PATIENT BED 1

PATIENT BED 4

PAT TLT. 2

STAFF

OBSERVATION

SOILED

PATIENT SHWR 2

ELOPEMENT

CONSULT 4

ADA PATIENT

BED 15

PAT TLT / TUB

SHWR 3

PATIENT BED 19

PATIENT BED 20

MECH. ROOM

245PAT TLT. 5

MECH ROOM

PAT TLT

ELOPEMENT

PATIENT

CORRIDOR

PATIENT

CORRIDOR

ADA TLT / SHWR

EVS

CLN

IDF ROOM

LAUNDRY

PATIENT BED 18

EXISTING STAIRS

INCENTIVE

THERAPY

STAIRS

STAIRS

ELEVATOR

PATIENT BED 16

PATIENT BED

PATIENT BED

PATIENT BED

PAT TLT. 3

PATIENT BED

PAT. TLT. 4

PATIENT BED

ADA PATIENT

BED 14

PATIENT

SHOWER 1

PAT TLT. 1

PATIENT BED

STOR.

STOR.

PATIENT

CORRIDOR

STOR.

PATIENT

CORRIDOR

PATIENT

CORRIDOR

MAIN MED RM

STAFF

RESTROOM

SECONDARY

MED RM.

AC

GFI

T

CR2-3

CR2-1 CR2-5 CR2-7

CR2-9 CR2-11

CR2-15

CR2-13

T

VESTIBULE

VESTIBULE

231A

L2A-27

LS1-7

CR2-10

CR2-6

CR2-8

GEN ANN

T

S

3TAC

T

T

S

UC

REF

S

NEW

PANEL

CR2

CR2-2

+54"

GFI

S

S

CR2-19

CR2-4

S

+54"

GFI

CR2-17

REF

L2A-29

L2A-31

L5-30R

T

T

L2A-13

AC

GFI

F

F

F

F

F

F

F

F

F

F

S T

F

F

F

F

F

F

F

F

T

T

F

F

F

F

T a b c

T TV

L2A-23

AC

T

TV

ELEV 2

DISC.

SWITCH

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :3

P

M

E2.2

POWER SECOND FLOOR

PLAN - ALAMO HALL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"1/8" = 1'-0"E2.2

1 POWER SECOND FLOOR PLAN - ALAMO HALL

CONNECT TO EXISTING 120V RECEPTACLE CIRCUIT INDICATED. EXTEND TO NEW RECEPTACLE LOCATIONS, 2#12 AND #12GND IN 3/4"C.

POWERED DOOR HOLDER. CONNECT TO EXISTING 120V CIRCUIT SERVING EXISTING DOOR HOLDERS, CIRCUIT LS1-7. DOORS SHALL

BE INTERLOCKED WITH FIRE ALARM SYSTEM.

REPLACE EXISTING RECEPTACLE WITH "S" RECEPTACLE.

CONNECT TO EXISTING 120V RECEPTACLE CIRCUIT INDICATED. EXTEND TO NEW RECEPTACLE LOCATIONS, 2#12 AND #12GND IN 3/4"C.

REPLACE EXISTING RECEPTACLE WITH "T" RECEPTACLE.

SWITCH TO CONTROL RECEPTACLE IN ADA PATIENT ROOMS 6,14, AND 15. PROVIDE LABEL INDICATING WHICH ROOM IS CONTROLLED.

-SUBSCRIPT "a" CONTROLS CIRCUIT CR-2 -SUBSCRIPT "b" CONTROLS CIRCUIT CR-4 -SUBSCRIPT "c" CONTROLS CIRCUIT CR-6

COORDINATE RECEPTACLE HEIGHT WITH WALL MOUNTED MONITOR PROVIDED.

ELECTRICAL POWER KEYED NOTES:

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

MECH ROOM

ADA PATIENT

BED 6

ADA PATIENT

BED 5

PATIENT BED 3

PATIENT BED 2

PATIENT BED 7

NEW ELEVATOR

STAFF STATION

ELECT. ROOM

SECLUSION ANTE

ANTE ROOM T/R

SECLUSION

ROOM

ADA TLT /

SHWR 2

CLN

PATIENT BED 17

PAT TLT. 6

STOR.

EXAM ROOM

STOR.

PATIENT BED 1

PATIENT BED 4

PAT TLT. 2

STAFF

OBSERVATION

SOILED

PATIENT SHWR 2

ELOPEMENT

CONSULT 4

ADA PATIENT

BED 15

PAT TLT / TUB

SHWR 3

PATIENT BED 19

PATIENT BED 20

MECH. ROOM

245PAT TLT. 5

MECH ROOM

PAT TLT

ELOPEMENT

PATIENT

CORRIDOR

PATIENT

CORRIDOR

ADA TLT / SHWR

206 EVS

CLN

IDF ROOM

LAUNDRY

PATIENT BED 18

EXISTING STAIRS

INCENTIVE

THERAPY

STAIRS

STAIRS

ELEVATOR

PATIENT BED 16

PATIENT BED

PATIENT BED

PATIENT BED

PAT TLT. 3

PATIENT BED

PAT. TLT. 4

PATIENT BED

ADA PATIENT

BED 14

PATIENT

SHOWER 1

PAT TLT. 1

PATIENT BED

STOR.

STOR.

PATIENT

CORRIDOR

STOR.

PATIENT

CORRIDOR

PATIENT

CORRIDOR

MAIN MED RM

FCU-45

FCU-48

FCU-62 3

EF-27

ON ROOF

FCU-39

HM2-43

M

L2A-25

M

STAFF

RESTROOM

PATIENT

CORRIDOR

PATIENT

CORRIDOR

SECONDARY

MED RM.

NOISY ACTIVITY

VESTIBULE

231A

VESTIBULE

FCU-56

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :4

P

M

E2.2M

MECHANICAL POWER

SECOND FLOOR PLAN -

ALAMO HALL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

1/8" = 1'-0"E2.2M

MECHANICAL POWER SECOND FLOOR PLAN - ALAMO

HALL

NEW EXHAUST FAN. PROVIDE MOTOR RATED TOGGLE SWITCH ADJACENT TO MOTOR ON ROOF.

NEW FCU. PROVIDE POWER CONNECTION AS INDICATED. MOTOR RATED TOGGLE SWITCH LOCATED ADJACENT TO EQUIPMENT

SERVED. UTILIZE SPARE 20A/1P CB IN PANEL INDICATED.

RELOCATED FCU. EXTEND EXISTING BRANCH CIRCUIT SERVING DEVICE, MATCH EXISTING SIZE. REINSTALL MAINTAINED

DISCONNECT.

FLUSH VALVE SENSOR POWER CONNECTION. PROVIDE RECESSED JBOX, CONDUIT, AND CONDUCTORS REQUIRED. COORDINATE WITH PLUMBING TRADES FOR EQUIPMENT AND LOCATION. CONNECT TO MAINTAINED CONDUCTORS SERVING PREVIOUSLY DEMOLISHED SENSOR AND EXTEND TO NEW LOCATION AS REQUIRED. 2#12 AND #12GND IN 3/4"C. ALL WIRING SHALL BE IN

CONDUIT.

ELECTRICAL POWER KEYED NOTES:

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

AC

GFI

AC

GFI

GFI

WP

GFI

T

AC

GFI

T

AC

GFI

REF

REF

AC

GFI

AC

GFI FB

SHELL

EXISTING

PANEL "A"

EXISTING

PANEL

"SUB-A"

EXISTING

PANEL

"A3"

EXISTING

PANEL

"M"

EXISTING

XFMR

"TM"

EXISTING

PANEL

"N"

EXISTING

MDP-3

SEC.2

EXISTING

SERVICE

XFMR

"T3"

PP

RISER POLE

WP

GFI

T

EXISTING

PANEL

"P"

FACP

NEW

PANEL "B"

T

T

T

T

T TV

T

T

NEW

"ATS-SB2"

EXISTING

MDP-3

SEC.1

PATIENT BLDG

STORAGE

S109

STAFF TLT

S110

LAW TLT

S125

LAW LOUNGE

S124PAT TLT

S111

EVS

S108

BED BUG

S114

PUBLIC TLT

S106

TELEHEALTH

S116

SIT/PRIV

S107

TLT/ SHWR

S113

PATIENT

EVALUATION

S117

SECURITY IT

SERVERS

S121

ELOPEMENT

S122

OPEN VISIT

S105

CENTRAL

CONTROL

S118

SECURITY/

SCREENING

S103

OFFICE

S120PUBLIC LOBBY/

WAIT

S100

STAFF

VESTIBULE

S104

SHELL

SHELL

ELOPEMENT

S122

ADMISSIONS/

SCREENING

AREA

S112

STAFF

BREAKROOM &

LOCKERS

S101

STAFF T/R

S102

CORR.

S123

STAFF OPEN

AREA

S119

MEDICATION

ROOM

S117A

GFI

GFI

S

T

S

T T

T

T

EDF

WP

GFI

NEW LTG

INV.

C-9,11

C-8

UP

B-1

B-3

B-5

B-7

B-11

B-13

B-15

B-19

B-17

B-21

B-23

B-25

B-27

B-29

B-31

B-33

B-35

B-10

B-12

B-14

B-16

B-18

B-20

B-28

B-22

B-24

B-26

EXISTING

D.S. "P"

EXISTING

D.S. "M"

CHP-2A CHP-2B

B-37

NEW

GENERATOR

"G2"

L5-30R

GFI

AC

GFI

EPO

GEN

C-14,16,18

T

B-41B-39

T

+54"

+54"

B-9

GFI

GFI

GFI

TV

NEW

PANEL

"C"

FUEL

FILTER

CORR.

S130CORR.

S132

CORR.

S131

CORR.

S133

CORR.

S134

MOTOR

208/3PH

13A FLA

BOILER

MOTOR

208/3PH

13A FLA

BOILER HUT

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :4

P

M

E2.3

POWER FLOOR PLAN -

SEIDEL BUILDING

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1 NEW SECONDARY FEEDERS SERVING FROM BUILDING TRANSFORMER TO NEW "ATS-SB2". IN SAME TRENCH, ROUTE LOAD-SIDE FEEDER FROM "ATS-SB2" TO MAIN OVERCURRENT DEVICE AT "MDP-3". SAWCUT CONCRETE. SCAN SLAB PRIOR TO WORK AND FOLLOW ALL ARCHITECTURAL, CIVIL AND STRUCTURAL REQUIREMENTS. DO NOT DISTURB GUY WIRE SUPPORT. ROUTING IS SCHEMATIC IN NATURE.

NEW ELECTRICAL RACK TO MOUNT SERVICE RECEPTACLE, EPO, SWITCH, AND LIGHT. RACK SHALL BE 8'-HIGH .

NEW UNDERGROUND FEEDERS. REF E4.2.

PROVIDE 20A/1P GFI CB IN PANEL INDICATED.

ELECTRIC DRINKING FOUNTAIN. COORDINATE POWER ROUGH-IN AND CONNECTIONS REQUIRED WITH EQUIPMENT PROVIDED. PROVIDE 20A/1P

GFI CB IN PANEL INDICATED.

NEW FLOORBOX. SAWCUT CONCRETE. SCAN SLAB PRIOR TO WORK AND FOLLOW ALL ARCHITECTURAL AND STRUCTURAL REQUIREMENTS.

PROVIDE 25A/2P CB IN PANEL INDICATED. COORDINATE CB WITH INVERTER PROVIDED PER MANUFACTURER REQUIREMENTS.

COORDINATE EQUIPMENT IN AREA TO ENSURE 10' MIN. CLEARANCE IS PROVIDED BETWEEN EXISTING GATE AND NEW EQUIPMENT.

REFEED ANY EXISTING TO REMAIN RECEPTACLE BRANCH CIRCUITS BEING SERVED FROM DEMOLISHED PANEL "B" FROM PANEL "C". PRICE (3)

20A/1P CIRCUIT REFEED. CONFIRM WITH OWNER.

RECEPTACLE DEDICATED FOR BEDBUG ZAPPER. COORDINATE FINAL LOCATION WITH OWNER PRIOR TO ROUGH-IN.

RECEPTACLE DEDICATED FOR X-RAY MACHINE. COORDINATE FINAL LOCATION WITH OWNER PRIOR TO ROUGH-IN.

COORDINATE L5-30R RECEPTACLE LOCATION WITH IT EQUIPMENT INSTALLED AND OWNER DIRECTION. RECEPTACLE TO SERVE RACK 2.

MOTORIZED GATE. PROVIDE DISCONNECTING MEANS SUITABLE FOR VOLTAGE AND AMPACITY OF EQUIPMENT SERVED. PROVIDE 1"C FROM PEDESTAL OPENER TO MOTOR CONTROLLER. PROVIDE 3/4"C FROM MOTOR CONTROLLER TO LOCAL OPERATOR. COORDINATE VOLTAGE AND OVERCURRENT SIZE WITH EQUIPMENT PROVIDED. COORDINATE PEDESTAL LOCATION WITH OWNER. REFER TO TECH DRAWINGS FOR DATA

CONDUIT REQUIREMENTS.

FIELD COORDINATE LOCATION OF FUEL FILTER. REF: E4.2.

COORDINATE RECEPTACLE HEIGHT WITH WALL MOUNTED MONITOR PROVIDED.

PROVIDE CAST LOCKABLE WP WHILE-IN-USE COVER.

ELECTRICAL POWER KEYED NOTES:

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

1/8" = 1'-0"E2.3

1 POWER FLOOR PLAN - SEIDEL

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

UP

C

F

AV

AV

V

VAVVVAV

SD

AV

VAV

F F

F

SD SD

AV

V

F

AVAV

V

V

V

AV

SD

SD

SD SD

SD SD

SD

SD

HD

F

F

F

V

V

AV

V

AV

V AV

V

V

AV

V

V

V

V

AV

AV

AV

SD

SD

SD

SD

SD

AV

AV

VAV

SD V

SDSD

HD

V

V

SD

V

V

V

V

V

V

V

VV

V

V

V

V

V

V

AV

AV

F

AV

F

V

V

DH

DH

V

AV

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

EX. FACP

CONSULT 1

DOCTOR'S

OFFICE

DOCTOR'S

OFFICE

CONSULT 2

STAFF TOILET

107 EXAM TOILET

MECH. ROOM

ELEV. MACH.

ROOM

NEW ELEVATOR

EVS SUPPLY

CONSULT 3

MECH ROOM

IT / SERVER

SERVERY/

NOURISHMENT

STAFF

CORRIDOR

TREATMENT

PLANNING &

TELEHEALTH

CONFERENCE

PSYCHOLOGISTS

INCENTIVE

THERAPY

PNA OFFICE

EXAM ROOM

ADMIN OFFICE

MECH ROOM

ELEC. ROOM

COMFORT ROOM

STOR.

STAFF T/R

PROGRAM

COORDINATOR

110 STORAGE

SECURE

RECEIVING

FIRE RISER

ROOM

PATIENT

CORRIDOR

PATIENT

CORRIDOR

STAFF

CORRIDOR

OFFICE

SOCIAL OFFICE

STORAGE

EMRG. ELEC.

LOBBY/SCREENING

WEST PORCH

100B

FRONT PORCH

100A

STAIRS S2

STAIRS

120B

STAIRS

NORTH PORCH

GROUP

STAIRS

STAIRS

VESTIBULE

MED ROOM

INCENTIVE

THERAPY

NOISY / DINING

STORAGE

SUPPLY

STORAGE ROOM

CLEAN LINEN

ELEVATOR

CLEAN LINEN

SCREEN/

RECEIVING

QUIET ACTIVITY

ADA PATIENT

TOILET

EVS

STAFF TLT.

GROUP

STAFF

ELOPEMENT

STOR.

EAST PORCH

NURSE

MANAGER

STAFF

141 B

PRINTER ALCOVE

STAFF STATION

ADA PATIENT

TLT.

STAFF

ELOPEMENT

STAFF OFFICE

WP

ELEV

RECALL

ELEV

RECALL

FA ANN

GEN ANNFSD

DSD

FSD

DSD

1 1

WP

WHEELCHAIR

STORAGE

100D

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG. CLG. CLG.

CLG.

CLG.

CLG.CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

FSD

DSD

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :4

P

M

E3.1

SPECIAL SYSTEMS FIRST

FLOOR PLAN - ALAMO

HALL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

1/8" = 1'-0"E3.1

1 SPECIAL SYSTEMS FIRST FLOOR PLAN - ALAMO HALL

GENERAL NOTES SPECIAL SYSTEMS: (APPLIES TO ALL SPECIAL SYSTEMS SHEETS)

1. SEE ALL OTHER PLANS FOR ADDITIONAL DEVICES.

2. WHEN LOCATING SYSTEMS NEXT TO DOORS, FOLLOW DEVICE LOCATION GUIDELINES.

3. ALL CABLING SHALL BE IN CONDUIT IN EXPOSED SPACES REGARDLESS IF ALLOWED NOT TO BE IN CONDUIT BY OTHER SPECIFICATIONS UNLESS DIRECTED OTHERWISE BY THE ENGINEER. ALL CABLING TO BE SUPPORTED BY J-HOOKS WHEN NOT IN CONDUIT OR CABLE TRAY. DO NOT STRAP TO STRUCTURE. SEPARATE CABLING AND PROVIDE SEPARATE J-HOOKS FOR DATA, CONTROLS, PA, SECURITY, AND FIRE ALARM IF NOT IN CONDUIT. TIE WRAP CABLING TOGETHER EVERY 4-6 FEET. PROVIDE SERVICE LOOPS IN CABLING, TIE WRAPPED TOGETHER. SERVICE LOOP SHALL

BE 24” MINIMUM.

4. PROVIDE CONDUIT SLEEVES THROUGH WALLS. ALL CONDUITS SHALL HAVE NYLON BUSHINGS ON THE ENDS. PROVIDE PULL STRINGS IN ALL EMPTY CONDUITS UNDER TWO (2) INCHES. PROVIDE MULE TAPE IN ALL EMPTY CONDUITS TWO (2) INCHES AND LARGER OR ANY CONDUIT RUNS LONGER THAN 100 FEET WITHOUT INTERMEDIATE PULL BOXES. SLEEVES LESS THAN 36 INCHES DO NOT REQUIRE PULL STRINGS.

5. FIRESTOP ALL CONDUIT PENETRATIONS IN RATED WALLS. PROVIDE INTUMESCENT FILL IN WALL CONDUIT SLEEVES IN RATED WALLS. SEE ARCHITECTURAL FOR WALL RATINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE TO SHEET ROCK AND REPAIR.

6. PROVIDE FIRE RATED SLEEVES WITH INTUMESCENT FILL IN ALL FLOOR PENETRATIONS.

7. ALL CABLING SHALL BE PLENUM RATED. ALL UNDERGROUND CABLING SHALL BE OUTDOOR RATED AS WELL AS PLENUM RATED. NO

EXCEPTIONS.

8. PROVIDE TUBE TYPE DUCT SMOKE DETECTORS FOR ALL SMOKE FIRE DAMPERS. PROVIDE TUBE TYPE DUCT SMOKE DETECTORS IN EACH AIR HANDLING UNIT IN THE SUPPLY AND RETURN. ALL DUCT SMOKE DETECTORS SHALL HAVE THE FOLLOWING CHARACTERISTICS; MOUNTED IN THE DIRECTION OF AIR FLOW, ADDRESSABLE WITH SELF SENSITIVITY, RATED FOR THE AIR SPEED, AND HAVE REMOTE INDICATOR LIGHT TEST STATIONS. FIRE ALARM CONTRACTOR SHALL PROVIDE INTERFACE OF DUCT SMOKE DETECTORS AND FIRE ALARM PANEL. PROVIDE 24V POWER

FROM FIRE ALARM PANEL.

9. PROVIDE LEXAN COVERS FOR ALL FIRE ALARM PULL STATIONS.

10. SEE SPECIFICATIONS FOR ADDITIONAL FIRE ALARM DEVICES AND MOUNTING HEIGHTS. MOUNT DEVICES IN ACCORDANCE WITH NFPA 72.

11. ALL SMOKE AND HEAT DETECTORS SHALL BE POWERED BY THE FIRE ALARM PANEL.

12. THE FIRE ALARM CONTROL PANEL SHALL SHUNT ALL AIR HANDLERS AND CLOSE ALL SMOKE FIRE DAMPERS IN THE EVENT OF A FIRE ALARM.

PROVIDE RELAYS FOR ALL AIR HANDLERS AND SMOKE FIRE DAMPER CIRCUITS AND CONNECT TO FIRE ALARM SYSTEM.

13. DESIGN IS SCHEMATIC IN NATURE. CONTRACTOR SHALL PROVIDE CODE COMPLIANT DESIGN AND PROVIDE ALL DEVICES, NAC PANELS, WIRING

AND INFRASTRUCTURE REQUIRED FOR A COMPLETE INSTALLATION.

1 NEW/RELOCATED FIRE ALARM DEVICE. CONNECT TO EXISTING SYSTEM. PROVIDE NEW CABLING AND INTERCEPT POINTS AS REQUIRED

FOR A COMPLETE AND OPERATIONAL SYSTEM.

RELOCATED FIRE ALARM ANNUCIATOR PANEL. REWORK CABLING FOR OPERATIONAL SYSTEM.

DOOR HOLDER. PROVIDE RELAYS CONNECTED TO FIRE ALARM THAT SHALL CLOSE DOORS UPON ACTIVATION OF THE FIRE ALARM

SYSTEM.

FIRE SMOKE DAMPER/DUCT SMOKE DETECTOR. PROVIDE 120V CIRCUIT AND MOTOR RATED TOGGLE SWITCH FOR DISCONNECTING MEANS. PROVIDE DUCT SMOKE DETECTOR. COORDINATE LOCATIONS AND POWER CONNECTIONS WITH MECHANICAL TRADES. CONNECT NO MORE THAN 15 PER CIRCUIT TO EXISTING FIRE/SMOKE DAMPER CIRCUITS IN BUILDING "LS1-13,17,19" . FIELD VERIFY. REFER TO

MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITES.

ELECTRICAL SPECIAL SYSTEMS KEYED NOTES:

A. EXISTING FIRE ALARM SYSTEM FOR THIS BUILDING IS EDWARDS. ALL NEW DEVICES SHALL BE BY SAME SYSTEM/MANUFACTURER.

GENERAL NOTES (ALAMO HALL, SHEETS E3.1 AND 3.2):

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

01/29/2025

AV

V

V

SD

SD

AV

V

AV

V

AV

SD

SD

V

V

F

AV

SD

SD

AV

SD

SD

V SD

SD

SDSD

SD

SD

SDHD

V

V

AV

V

AV

SD

AV

SD

V

SD

SDHD

V

V

V

V

V

V

DH

DH

V SD

V

DH

DH

AV

VV

AV

D H

D H

V

V

SD

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

MECH ROOM

ADA PATIENT

BED 6

ADA PATIENT

BED 5

PATIENT BED 3

PATIENT BED 2

PATIENT BED 7

NEW ELEVATOR

STAFF STATION

ELECT. ROOM

SECLUSION ANTE

ANTE ROOM T/R

SECLUSION

ROOM

ADA TLT /

SHWR 2

CLN

PATIENT BED 17

PAT TLT. 6

STOR.

EXAM ROOM

STOR.

PATIENT BED 1

PATIENT BED 4

PAT TLT. 2

STAFF

OBSERVATION

SOILED

PATIENT SHWR 2

ELOPEMENT

CONSULT 4

ADA PATIENT

BED 15

PAT TLT / TUB

SHWR 3

PATIENT BED 19

PATIENT BED 20

MECH. ROOM

245PAT TLT. 5

MECH ROOM

PAT TLT

ELOPEMENT

PATIENT

CORRIDOR

PATIENT

CORRIDOR

ADA TLT / SHWR

EVS

CLN

IDF ROOM

LAUNDRY

PATIENT BED 18

EXISTING STAIRS

STAIRS

ELEVATOR

PATIENT BED 16

PATIENT BED

PATIENT BED

PATIENT BED

PAT TLT. 3

PATIENT BED

PAT. TLT. 4

PATIENT BED

ADA PATIENT

BED 14

PATIENT

SHOWER 1

PAT TLT. 1

PATIENT BED

STOR.

STOR.

PATIENT

CORRIDOR

STOR.

PATIENT

CORRIDOR

PATIENT

CORRIDOR

MAIN MED RM

ELEV

RECALL

FA ANN

NAC

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

SECONDARY

MED RM.

CLG.

CLG.

GEN ANN

CLG.

STAFF

RESTROOM

CLG.

CLG.

CLG.

CLG.

CLG.

NOISY ACTIVITY

PATIENT

CORRIDOR

PATIENT

CORRIDOR

VESTIBULE

231A FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

CLG.

CLG.

FSD

DSD

FSD

DSD

CLG.

CLG.

CLG.

FSD

DSD

FSD

DSD

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :4

P

M

E3.2

SPECIAL SYSTEMS

SECOND FLOOR PLAN -

ALAMO HALL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

1/8" = 1'-0"E3.2

1 SPECIAL SYSTEMS SECOND FLOOR PLAN - ALAMO HALL

1 NEW/RELOCATED FIRE ALARM DEVICE. CONNECT TO EXISTING SYSTEM. PROVIDE NEW CABLING AND INTERCEPT POINTS AS REQUIRED

FOR A COMPLETE AND OPERATIONAL SYSTEM.

NEW FIRE ALARM DEVICE. CONNECT THROUGH ELEVATOR CONTROLS AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.

DOOR HOLDER. PROVIDE RELAYS CONNECTED TO FIRE ALARM THAT SHALL CLOSE DOORS UPON ACTIVATION OF THE FIRE ALARM

SYSTEM.

CONNECT EXISTING FIRE ALARM DEVICES IN EXISTING SHAFT TO NEW ELEVATOR EQUIPMENT.

FIRE SMOKE DAMPER/DUCT SMOKE DETECTOR. PROVIDE 120V CIRCUIT AND MOTOR RATED TOGGLE SWITCH FOR DISCONNECTING MEANS. PROVIDE DUCT SMOKE DETECTOR. COORDINATE LOCATIONS AND POWER CONNECTIONS WITH MECHANICAL TRADES. CONNECT NO MORE THAN 15 PER CIRCUIT TO EXISTING FIRE/SMOKE DAMPER CIRCUITS IN BUILDING "LS1-13,17,19" . FIELD VERIFY. REFER TO

MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITES.

ELECTRICAL SPECIAL SYSTEMS KEYED NOTES:

Revision Schedule

No. Description Date

1 Addendum 01 01/29/25

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

01/29/2025

AV

AV

AV

AV

AV

F

F

HD

V

AV

V V

AV

AV

V

AV

V

AV

V

SD

F F

F

F

AVAV

AV AV

AV

F

V

AV

AV

F

HD

V

AV

V

F

F

AV

AV AV

AV

F

F

AV

AV V

V

AV

AV

V

AV

V

AV

V V

AV V

V

AV

V

AV

V

V

AV

AV

V

SD

SD

SD

SD

SD

SD

SD

SD

SD

V

V

V

SD

SD

SD

V

V

FACP

FA ANNFA ANN

TS

FS

A

TS

FS

A

DSD

WP

WP

WP

WP

NEW LTG

INV.

CLG.

CLG.

PATIENT BLDG

STORAGE

S109

STAFF TLT

S110

LAW TLT

S125

LAW LOUNGE

S124

PAT TLT

S111

EVS

S108

BED BUG

S114

PUBLIC TLT

S106

TELEHEALTH

S116

SIT/PRIV

S107

TLT/ SHWR

S113

PATIENT

EVALUATION

S117 SECURITY IT

SERVERS

S121

ELOPEMENT

S122

OPEN VISIT

S105

CENTRAL

CONTROL

S118

SECURITY/

SCREENING

S103

OFFICE

S120

PUBLIC LOBBY/

WAIT

S100

STAFF

VESTIBULE

S104

SHELL

SHELL

ELOPEMENT

S122

ADMISSIONS/

SCREENING

AREA

S112

STAFF

BREAKROOM &

LOCKERS

S101 STAFF T/R

S102

CORR.

S123

STAFF OPEN

AREA

S119

MEDICATION

ROOM

S117A

WP

WG

CLG.

CLG.

CLG.

CLG.

CLG.CLG.CLG.

CLG.CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

CLG.

WP

EXISTING

NAC

CLG.

CLG.

A

NEW

"ATS-SB2"

NEW

GENERATOR

"G2"

GEN ANN

CLG.

CLG.

FA ANN

D

D

MECH RM

AHU-1

AHU-2

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSDFSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

FSD

DSD

4 4

4 4 4

FSD

DSD

CLG.

CLG.

D

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/2

/2

:4 :5

P

M

E3.3

SPECIAL SYSTEMS FLOOR

PLAN - SEIDEL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

0' 4' 8' 16' 32'

SCALE: 1/8"=1'-0"

1/8" = 1'-0"E3.3

1 SPECIAL SYSTEMS FLOOR PLAN - SEIDEL

1 PROVIDE NEW FIRE ALARM DEVICE. CONNECT TO EXISTING FACP.

ALTERNATE: REINSTALL DEVICE IN NEW CEILING. PROVIDE NEW BACKBOX AND CONNECTIONS.

PROVIDE NEW FIRE ALARM ANNUNCIATOR CONNECTED TO EXISTING SYSTEM.

FIRE SMOKE DAMPER/DUCT SMOKE DETECTOR. PROVIDE 120V CIRCUIT AND MOTOR RATED TOGGLE SWITCH FOR DISCONNECTING MEANS.

PROVIDE DUCT SMOKE DETECTOR. COORDINATE LOCATIONS AND POWER CONNECTIONS WITH MECHANICAL TRADES. CONNECT NO MORE THAN 15 PER CIRCUIT TO CIRCUITS C-15,17,19. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITES.

ELECTRICAL KEYED NOTES:

A. EXISTING FIRE ALARM SYSTEM FOR THIS BUILDING IS SIEMENS. ALL NEW

DEVICES SHALL BE BY SAME SYSTEM/MANUFACTURER.

GENERAL NOTES (SEIDEL BUILDING, SHEET E3.3):

LORENZO L. SANCHEZ

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

152308

E OF T

IN

E E

XA

S

L

R

01/29/2025

Revision Schedule

TOTAL KVA: 145.11 PANEL DESIGN CURRENT: 167 AMPS

4 20/1 NEW - FCU-63 45 1,423 X 2,825 46 EXISTING EDH-3 20/3 4

4 20/1 EXISTING FCU-25 47 1,640 X 2,825 48 4

EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP

EXISTING PANEL HM1

LOCATION: ELEC. ROOM 116 VOLTAGE: 277/480 V KAIC: 22 BUSSING SHALL BE FULLY RATED

MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT

ENCLOSURE: NEMA 1 STYLE: EXISTING BUSSING: 250 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR

BRKR MTG: BOLT-ON (REF: SIEMENS) MCB: A ACCESSORIES: 48 SPACE

BREAKERS: SERIES RATED. 75 DEGREE TERMINALS MLO: A

PHASE A 17978 0 0 20268 1731 39977 40410 146

PHASE B 17978 0 0 20505 1731 40214 40647 147

PHASE C 17978 0 0 19730 1731 39439 39872 144

TOTAL 53934 0 0 60503 5193 119630 120928

PANEL DESIGN KVA: 120.93 PANEL SUBTOTAL: 145 AMPS

RESERVE CAPACITY KVA: 24.19 RESERVE CAPACITY: 22 AMPS

FED FROM CB IN "MSB"

CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE

4 20/1 EXISTING FCU-1 1 2,278 X 1,179 2 EXISTING FCU-13 20/1 4

4 20/1 EXISTING FCU-6 3 2,278 X 2,415 4 EXISTING FCU-14,15 20/1 4

4 20/1 EXISTING FCU-3,4 5 3,277 X 2,278 6 EXISTING FCU-16,17 20/1 4

4 20/1 EXISTING FCU-2,5 7 3,277 X 2,278 8 EXISTING FCU-18,20 20/1 4

3 20/3 EXISTING OAU-1,2 21 886 X 5,000 22 EXISTING EWH-1 30/3 0

3 23 886 X 5,000 24 0

7 25 1,731 X 5,000 26 0

7 20/3 EXISTING CHP-1 27 1,731 X 5,000 28 EXISTING EWH-2 30/3 0

7 29 1,731 X 5,000 30 0

6 31 1,731 X 4,986 32 0

6 20/3 EXISTING CHP-2 33 1,731 X 4,986 34 EXISTING HS-2 30/3 0

6 35 1,731 X 4,986 36 0

0 37 2,992 X 2,660 38 4

0 20/3 EXISTING HS-1 39 2,992 X 2,660 40 EXISTING EDH-5 20/3 4

0 41 2,992 X 2,660 42 4

4 20/1 EXISTING FCU-23,24 43 2,278 X 2,825 44 4

4 20/1 EXISTING FCU-7,9 9 2,278 X 2,278 10 EXISTING FCU-19 20/1 4

4 20/1 EXISTING FCU-8 11 2,278 X 2,779 12 EXISTING FCU-21,22 20/1 4

4 20/1 EXISTING FCU-10 13 3,277 X 4,433 14 3

4 20/1 EXISTING FCU-11 15 3,277 X 4,433 16 EXISTING AHU-1 20/3 3

4 20/1 EXISTING FCU-12 17 1,139 X 4,433 18 3

3 19 886 X 5,000 20 0

TOTAL KVA: 128.95 PANEL DESIGN CURRENT: 149 AMPS

EXISTING PANEL HM2

LOCATION: ELEC. ROOM 250 VOLTAGE: 277/480 V KAIC: 22 BUSSING SHALL BE FULLY RATED

MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT

ENCLOSURE: NEMA 1 STYLE: EXISTING BUSSING: 250 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR

BRKR MTG: BOLT-ON (REF: SIEMENS) MCB: A ACCESSORIES: GROUND BUS, 54 SPACE

BREAKERS: SERIES RATED. 75 DEGREE TERMINALS MLO: 150 A AGF: ARC/GROUND FAULT CB

20/1 EXISTING SPARE 45 X 6,011 46 EXISTING EDH-6 30/3 4

20/1 EXISTING SPARE 47 X 6,011 48 4

49 X 50 EXISTING BUSSED SPACE

30/3 EXISTING LOAD 51 X 52 EXISTING BUSSED SPACE

53 X 54 EXISTING BUSSED SPACE

EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP

PHASE A 7979 0 1363 25044 0 34386 34727 125

PHASE B 7979 0 1681 26236 0 35896 36316 131

PHASE C 7979 0 4151 23244 0 35374 36412 131

TOTAL 23937 0 7195 74524 0 105656 107454

PANEL DESIGN KVA: 107.45 PANEL SUBTOTAL: 129 AMPS

RESERVE CAPACITY KVA: 21.49 RESERVE CAPACITY: 19 AMPS

FED FROM CB IN "MSB"

CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE

4 20/1 EXISTING FCU-26,27 1 3,280 X 2,278 2 EXISTING FCU-46,47 20/1 4

4 20/1 EXISTING FCU-28,29 3 3,280 X 2,278 4 EXISTING FCU-45 20/1 4

4 20/1 EXISTING FCU-30,31 5 3,280 X 2,918 6 EXISTING FCU-48,49 20/1 4

4 20/1 EXISTING FCU-33,34 7 2,779 X 2,278 8 EXISTING FCU-32 20/1 4

0 20/3 EXISTING HS-3 33 2,992 X 2,327 34 EXISTING EDH-4 20/3 4

0 35 2,992 X 2,327 36 4

0 37 1,995 X 2,659 38 4

0 20/3 EXISTING HS-4 39 1,995 X 2,659 40 EXISTING EDH-5 20/3 4

0 41 1,995 X 2,659 42 4

4 20/1 NEW - FCU-62 43 1,423 X 6,011 44 4

3 20/3 EXISTING OUA-3,4,5 21 1,330 X 2,133 22 EXISTING FCU-61 20/1 4

3 23 1,330 X 2,245 24 EXISTING LTS - 2ND FLOOR CORRIDOR 20/1 2

2 20/1 EXISTING LTS - 2ND FLOOR NORTH 25 1,363 X 2,992 26 0

2 20/1 EXISTING LTS - 2ND FLOOR WEST 27 1,681 X 2,992 28 EXISTING HS-5 20/3 0

2 20/1 EXISTING LTS - 2ND FLOOR EAST 29 1,906 X 2,992 30 0

0 31 2,992 X 2,327 32 4

4 20/1 EXISTING FCU-35,36 9 3,280 X 2,278 10 EXISTING FCU-50 20/1 4

4 20/1 EXISTING FCU-37,38 11 2,393 X 3,280 12 EXISTING FCU-51,52 20/1 4

4 20/1 EXISTING FCU-39,40 13 3,056 X 2,278 14 EXISTING FCU-53,54 20/1 4

4 20/1 EXISTING FCU-41,42 15 3,391 X 3,280 16 EXISTING FCU-55,56 20/1 4

4 20/1 EXISTING FCU-43,44 17 2,779 X 2,278 18 EXISTING FCU-57,58 20/1 4

3 19 1,330 X 2,779 20 EXISTING FCU-59,60 20/1 4

EQPT VA RCPT VA LTG VA AC/HEAT VA MOTORS CONN VA FTL VA PANEL VA PHASE AMP

PHASE A 1176 6840 1009 0 0 9025 7534 63

PHASE B 800 7340 0 0 0 8140 6269 52

EXISTING PANEL L1A

LOCATION: ELEC. ROOM 116 VOLTAGE: 208/120 V KAIC: 22 BUSSING SHALL BE FULLY RATED

MOUNTING: SURFACE PHASE: 3 P / 4W CODES: 0=EQPT, 1=RCPT, 2=LTG, 3=A/C, 4=HEAT

ENCLOSURE: NEMA 1 STYLE: EXISTING BUSSING: 250 A 5=CONTINUOUS MOTORS, 6=LRGST MOTOR

BRKR MTG: BOLT-ON (REF: SIEMENS) MCB: 125 A ACCESSORIES: GROUND BUS, 42 SPACE

7 20/2 EXISTING DSCU-1-2 35 998 X 998 36 EXISTING DSCU-1-4 20/2 7

7 37 998 X 998 38 7

7 20/2 EXISTING DSCU-1-3 39 998 X 998 40 EXISTING DSCU-2-1 20/2 7

7 41 998 X 998 42 7

BREAKERS: SERIES RATED. 75 DEGREE TERMINALS MLO: A AGF: ARC/GROUND FAULT CB

CODE BRKR CIRCUIT USE CKT LOAD A B C LOAD CKT CIRCUIT USE BRKR CODE

1 20/1 EXISTING RCPTS - SOCIAL OFFICE 114 1 780 X 920 2 EXISTING RCPTS - PATIENT STORAGE 109 20/1 1

1 20/1 EXISTING RCPTS - DR OFFICE 113 3 1,080 X 660 4 EXISTING RCPTS - NURSE MGR 108 20/1 1

PHASE C 1730 6220 240 0 0 8190 6665 56

TOTAL 3706 20400 1249 0 0 25355 20467

PANEL DESIGN KVA: 20.47 PANEL SUBTOTAL: 57 AMPS

RESERVE CAPACITY KVA: 4.09 RESERVE CAPACITY: 9 AMPS

TOTAL KVA: 24.56 PANEL DESIGN CURRENT: 65 AMPS

25 X 1,009 26 EXISTING 1ST FLR LT A WING 20/1 2

100/3 NEW PANEL "L1C" 27 X 760 28 EXISTING RCPTS - LOBBY 100 20/1 1

29 X 500 30 EXISTING FOUNTAIN 20/1 0

7 20/2 EXISTING DSCU-1-1 31 998 X 32 EXISTING SPARE 20/1AGF

7 33 998 X 540 34 RECEPT - STORAGE 132, SERV/NOURISH 141 20/1 1

1 20/1 EXISTING RCPTS - DINING AREA 119 15 900 X 800 16 EXISTING RCPTS - FRIDGE 122 20/1 0

20/1AGF SPARE 17 X 1,200 18 EXISTING RCPTS - COUNTERTOP 122 20/1 1

20/1AGF SPARE 19 X 540 20 EXISTING RCPTS - VESTI., LOBBY, SUMP PUMP 20/1 1

1 20/1 EXISTING RCPTS - BK ROOM 122 21 400 X 22 SPARE 20/1

20/1 SPARE 23 X…