This is a technical specifications document outlining detailed requirements for doors, frames, hardware and related components for a secure healthcare facility. The specifications cover multiple door types including hollow metal doors, wood doors, aluminum entrances, security windows, coiling counter doors, and overhead coiling doors, along with associated hardware like hinges, locks, closers and other accessories. Key requirements include anti-ligature hardware, tamper-resistant fasteners, security screws, and controlled access/egress features appropriate for a secure healthcare environment.
The specifications emphasize security, durability and safety with requirements for fire ratings, smoke containment, accessibility compliance, and integration with existing security systems. Specific products are identified as facility standards, including Best patented key systems and Best anti-ligature hardware with no substitutions allowed. The documents include detailed requirements for materials, fabrication, installation, testing, warranties and maintenance. While pricing is not specifically addressed, the specifications require high-quality institutional grade products suitable for a secure healthcare setting with warranties ranging from 2-5 years depending on the component.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HOLLOW METAL DOORS AND FRAMES 081113 - 3
d. Edge Construction: Model 1, Full Flush.
e. Core: Manufacturer's standard.
3. Frames:
a. Materials: Metallic-coated, cold-rolled steel sheet, minimum thickness of 0.0625 inch (1.59 mm).
b. Sidelite Frames: Fabricated from same thickness material as adjacent door frame.
c. Construction: Face welded.
4. Exposed Finish: Prime Factory.
2.5 BORROWED LITES
A. Fabricate of metallic-coated steel sheet, minimum thickness of 0.0625 inch (1.59mm).
B. Construction: Full profile welded.
C. Fabricate in one piece except where handling and shipping limitations require multiple sections.
Where frames are fabricated in sections due to shipping or handling limitations, provide alignment plates or angles at each join, fabricated of metal of same or greater thickness as metal as frames.
D. Provide countersunk, Tamper Resistant flat-or oval-head exposed screws and bolts for exposed fasteners unless otherwise indicate.
2.6 EXTERIOR HOLLOW-METAL DOORS AND FRAMES
A. Heavy-Duty Doors and Frames: SDI A250.8, Level 2. At locations indicated in the Door and
Frame Schedule.
1. Physical Performance: Level B according to SDI A250.4.
2. Doors:
a. Type: As indicated in the Door and Frame Schedule.
b. Thickness: 1-3/4 inches (44.5 mm).
c. Face: Metallic-coated steel sheet, minimum thickness of 0.0625 inch (1.590 mm), with minimum A40 (ZF120) coating.
d. Edge Construction: Model 1, Full Flush.
e. Core: Manufacturer's standard insulation material.
3. Thermal-Rated Doors: Provide doors fabricated with thermal-resistance value (R-value) of not less than [2.1 deg F x h x sq. ft./Btu (0.370 K x sq. m/W) when tested according to
ASTM C 1363.
4. Frames:
a. Materials: Metallic-coated steel sheet, minimum thickness of 0.625 inch (1.59 mm), with minimum A40 (ZF120) coating.
b. Construction: Face welded.
HOLLOW METAL DOORS AND FRAMES 081113 - 4
5. Exposed Finish: Prime Factory.
2.7 FRAME ANCHORS
A. Jamb Anchors:
1. Masonry Type: Adjustable strap-and-stirrup or T-shaped anchors to suit frame size, not less than 0.042 inch (1.0 mm) thick, with corrugated or perforated straps not less than 2 inches (51 mm) wide by 10 inches (254 mm) long; or wire anchors not less than 0.177 inch (4.5 mm) thick.
2. Stud-Wall Type: Designed to engage stud, welded to back of frames; not less than 0.042 inch (1.0 mm) thick.
3. Compression Type for Drywall Slip-on Frames: Adjustable compression anchors.
4. Postinstalled Expansion Type for In-Place Concrete or Masonry: Minimum 3/8-inch-
(9.5-mm-) diameter bolts with expansion shields or inserts. Provide pipe spacer from frame to wall, with throat reinforcement plate, welded to frame at each anchor location.
B. Floor Anchors: Formed from same material as frames, minimum thickness of 0.042 inch (1.0 mm), and as follows:
1. Monolithic Concrete Slabs: Clip-type anchors, with two holes to receive fasteners.
2. Separate Topping Concrete Slabs: Adjustable-type anchors with extension clips, allowing not less than 2-inch (51-mm) height adjustment. Terminate bottom of frames at finish floor surface.
2.8 MATERIALS
A. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B; suitable for exposed applications.
B. Hot-Rolled Steel Sheet: ASTM A 1011/A 1011M, Commercial Steel (CS), Type B; free of scale, pitting, or surface defects; pickled and oiled.
C. Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS), Type B.
D. Frame Anchors: ASTM A 879/A 879M, Commercial Steel (CS), 04Z (12G) coating designation; mill phosphatized.
1. For anchors built into exterior walls, steel sheet complying with ASTM A 1008/A 1008M or ASTM A 1011/A 1011M, hot-dip galvanized according to ASTM A 153/A 153M, Class B.
E. Inserts, Bolts, and Fasteners: Hot-dip galvanized according to ASTM A 153/A 153M.
F. Power-Actuated Fasteners in Concrete: From corrosion-resistant materials.
G. Grout: ASTM C 476, except with a maximum slump of 4 inches (102 mm), as measured according to ASTM C 143/C 143M.
H. Mineral-Fiber Insulation: ASTM C 665, Type I (blankets without membrane facing).
HOLLOW METAL DOORS AND FRAMES 081113 - 5
I. Glazing: Section 088000 "Glazing."
J. Bituminous Coating: Cold-applied asphalt mastic, compounded for 15-mil (0.4-mm) dry film thickness per coat.
2.9 FABRICATION
A. Fabricate hollow-metal work to be rigid and free of defects, warp, or buckle. Accurately form metal to required sizes and profiles, with minimum radius for metal thickness. Where practical, fit and assemble units in manufacturer's plant. To ensure proper assembly at Project site, clearly identify work that cannot be permanently factory assembled before shipment.
B. Hollow-Metal Doors:
1. Exterior Doors: Provide weep-hole openings in bottoms of exterior doors to permit moisture to escape. Seal joints in top edges of doors against water penetration.
2. Astragals: Provide overlapping astragal on one leaf of pairs of doors where required by
NFPA 80 for fire-performance rating or where indicated.
C. Hollow-Metal Frames: Where frames are fabricated in sections due to shipping or handling limitations, provide alignment plates or angles at each joint, fabricated of same thickness metal as frames.
1. Sidelite Frames: Provide closed tubular members with no visible face seams or joints, fabricated from same material as door frame. Fasten members at crossings and to jambs by butt welding.
2. Provide countersunk, flat- or oval-head exposed screws and bolts for exposed fasteners unless otherwise indicated.
3. Grout Guards: Weld guards to frame at back of hardware mortises in frames to be grouted.
4. Floor Anchors: Weld anchors to bottoms of jambs with at least four spot welds per anchor; however, for slip-on drywall frames, provide anchor clips or countersunk holes at bottoms of jambs.
5. Jamb Anchors: Provide number and spacing of anchors as follows:
a. Masonry Type: Locate anchors not more than 16 inches (406 mm) from top and bottom of frame. Space anchors not more than 32 inches (813 mm) o.c., to match coursing, and as follows:
1) Two anchors per jamb up to 60 inches (1524 mm) high.
2) Three anchors per jamb from 60 to 90 inches (1524 to 2286 mm) high.
3) Four anchors per jamb from 90 to 120 inches (2286 to 3048 mm) high.
4) Four anchors per jamb plus one additional anchor per jamb for each 24 inches (610 mm) or fraction thereof above 120 inches (3048 mm) high.
b. Stud-Wall Type: Locate anchors not more than 18 inches (457 mm) from top and bottom of frame. Space anchors not more than 32 inches (813 mm) o.c. and as follows:
1) Three anchors per jamb up to 60 inches (1524 mm) high.
HOLLOW METAL DOORS AND FRAMES 081113 - 6
2) Four anchors per jamb from 60 to 90 inches (1524 to 2286 mm) high.
3) Five anchors per jamb from 90 to 96 inches (2286 to 2438 mm) high.
4) Five anchors per jamb plus one additional anchor per jamb for each 24 inches (610 mm) or fraction thereof above 96 inches (2438 mm) high.
c. Compression Type: Not less than two anchors in each frame.
d. Postinstalled Expansion Type: Locate anchors not more than 6 inches (152 mm) from top and bottom of frame. Space anchors not more than 26 inches (660 mm) o.c.
6. Door Silencers: Except on weather-stripped frames, drill stops to receive door silencers.
a. Single-Door Frames: Drill stop in strike jamb to receive three door silencers.
b. Double-Door Frames: Drill stop in head jamb to receive two door silencers.
D. Hardware Preparation: Factory prepare hollow-metal work to receive templated mortised hardware; include cutouts, reinforcement, mortising, drilling, and tapping according to
SDI A250.6, the Door Hardware Schedule, and templates.
1. Reinforce doors and frames to receive nontemplated, mortised, and surface-mounted door hardware.
2. Comply with applicable requirements in SDI A250.6 and BHMA A156.115 for preparation of hollow-metal work for hardware.
E. Stops and Moldings: Provide stops and moldings around glazed lites and louvers where indicated. Form corners of stops and moldings with mitered hairline joints.
1. Single Glazed Lites: Provide fixed stops and moldings welded on secure side of hollow-metal work.
2. Multiple Glazed Lites: Provide fixed and removable stops and moldings so that each glazed lite is capable of being removed independently.
3. Provide fixed frame moldings on outside of exterior and on secure side of interior doors and frames.
4. Provide loose stops and moldings on inside of hollow-metal work.
5. Coordinate rabbet width between fixed and removable stops with glazing and installation types indicated.
2.10 STEEL FINISHES
A. Prime Finish: Clean, pretreat, and apply manufacturer's standard primer.
1. Shop Primer: SDI A250.10.
B. Factory Finish: SDI A250.3.
1. Color and Gloss: As selected by Architect from manufacturer's full range.
2.11 ACCESSORIES
A. Grout Guards: Formed from same material as frames, not less than 0.016 inch (0.4 mm) thick.
HOLLOW METAL DOORS AND FRAMES 081113 - 7
PART 3 - EXECUTION
3.1 INSTALLATION
A. Hollow-Metal Frames: Install hollow-metal frames for doors, transoms, sidelites, borrowed lites, and other openings, of size and profile indicated. Comply with SDI A250.11 or NAAMM-
HMMA 840 as required by standards specified.
1. Set frames accurately in position; plumbed, aligned, and braced securely until permanent anchors are set. After wall construction is complete, remove temporary braces, leaving surfaces smooth and undamaged.
a. At fire-rated openings, install frames according to NFPA 80.
b. Where frames are fabricated in sections because of shipping or handling limitations, field splice at approved locations by welding face joint continuously;
grind, fill, dress, and make splice smooth, flush, and invisible on exposed faces.
c. Install frames with removable stops located on secure side of opening.
d. Install door silencers in frames before grouting.
e. Remove temporary braces necessary for installation only after frames have been properly set and secured.
f. Check plumb, square, and twist of frames as walls are constructed. Shim as necessary to comply with installation tolerances.
g. Field apply bituminous coating to backs of frames that will be filled with grout containing antifreezing agents.
2. Floor Anchors: Provide floor anchors for each jamb and mullion that extends to floor, and secure with postinstalled expansion anchors.
a. Floor anchors may be set with power-actuated fasteners instead of postinstalled expansion anchors if so indicated and approved on Shop Drawings.
3. Metal-Stud Partitions: Solidly pack mineral-fiber insulation inside frames.
4. Masonry Walls: Coordinate installation of frames to allow for solidly filling space between frames and masonry with grout.
5. Concrete Walls: Solidly fill space between frames and concrete with mineral-fiber insulation.
6. In-Place Concrete or Masonry Construction: Secure frames in place with postinstalled expansion anchors. Countersink anchors, and fill and make smooth, flush, and invisible on exposed faces.
7. In-Place Metal or Wood-Stud Partitions: Secure slip-on drywall frames in place according to manufacturer's written instructions.
8. Installation Tolerances: Adjust hollow-metal door frames for squareness, alignment, twist, and plumb to the following tolerances:
a. Squareness: Plus or minus 1/16 inch (1.6 mm), measured at door rabbet on a line
90 degrees from jamb perpendicular to frame head.
b. Alignment: Plus or minus 1/16 inch (1.6 mm), measured at jambs on a horizontal line parallel to plane of wall.
c. Twist: Plus or minus 1/16 inch (1.6 mm), measured at opposite face corners of jambs on parallel lines, and perpendicular to plane of wall.
HOLLOW METAL DOORS AND FRAMES 081113 - 8
d. Plumbness: Plus or minus 1/16 inch (1.6 mm), measured at jambs at floor.
B. Hollow-Metal Doors: Fit hollow-metal doors accurately in frames, within clearances specified below. Shim as necessary.
1. Non-Fire-Rated Steel Doors:
a. Between Door and Frame Jambs and Head: 1/8 inch (3.2 mm) plus or minus 1/32 inch (0.8 mm).
b. Between Edges of Pairs of Doors: 1/8 inch (3.2 mm) to 1/4 inch (6.3 mm) plus or minus 1/32 inch (0.8 mm).
c. At Bottom of Door: 3/4 inch (19.1 mm) plus or minus 1/32 inch (0.8 mm).
d. Between Door Face and Stop: 1/16 inch (1.6 mm) to 1/8 inch (3.2 mm) plus or minus 1/32 inch (0.8 mm).
2. Fire-Rated Doors: Install doors with clearances according to NFPA 80.
3. Smoke-Control Doors: Install doors and gaskets according to NFPA 105.
C. Glazing: Comply with installation requirements in Section 088000 "Glazing" and with hollow-metal manufacturer's written instructions.
1. Secure stops with countersunk flat- or oval-head machine screws spaced uniformly not more than 9 inches (230 mm) o.c. and not more than 2 inches (51 mm) o.c. from each corner.
3.2 ADJUSTING AND CLEANING
A. Final Adjustments: Check and readjust operating hardware items immediately before final inspection. Leave work in complete and proper operating condition. Remove and replace defective work, including hollow-metal work that is warped, bowed, or otherwise unacceptable.
B. Remove grout and other bonding material from hollow-metal work immediately after installation.
C. Prime-Coat Touchup: Immediately after erection, sand smooth rusted or damaged areas of prime coat and apply touchup of compatible air-drying, rust-inhibitive primer.
D. Metallic-Coated Surface Touchup: Clean abraded areas and repair with galvanizing repair paint according to manufacturer's written instructions.
E. Touchup Painting: Cleaning and touchup painting of abraded areas of paint are specified in painting Sections.
END OF SECTION 081113
WOOD DOORS 081416 - 1
SECTION 081416 - FLUSH WOOD DOORS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Factory finishing flush wood doors.
B. Related Sections:
1. Division 08 - Hollow Metal Door Frames.
1.3 SUBMITTALS
A. Product Data: For each type of door indicated. Include details of core and edge construction, louvers, and trim for openings. Include factory-finishing specifications.
B. Shop Drawings: Indicate location, size, and hand of each door; elevation of each kind of door;
construction details not covered in Product Data; location and extent of hardware blocking; and other pertinent data.
1. Indicate dimensions and locations of mortises and holes for hardware.
2. Indicate dimensions and locations of cutouts.
3. Indicate requirements for veneer matching.
4. Indicate doors to be factory finished and finish requirements.
5. Indicate fire-protection ratings for fire-rated doors.
C. Samples for Initial Selection: For factory-finished doors. .
D. Samples for Verification:
1. Factory finishes applied to actual door face materials, approximately 8 by 10 inches (200 by 250 mm), for each material and finish. For each wood species and transparent finish, provide set of three (3) samples showing typical range of color and grain to be expected in the finished work.
2. Corner section of doors, approximately 8 by 10 inches (200 by 250 mm), with door faces and edges representing actual materials to be used.
a. Provide samples for each species of veneer and solid lumber required.
b. Provide samples for each color, texture, and pattern of plastic laminate required.
c. Finish veneer-faced door samples with same materials proposed for factory-finished doors.
3. Frames for light openings, 6 inches (150 mm) long, for each material, type, and finish required.
WOOD DOORS 081416 - 2
E. Warranty: Sample of special warranty.
1.4 QUALITY ASSURANCE
A. Source Limitations: Obtain flush wood doors from single manufacturer wherever possible.
B. Quality Standard: In addition to requirements specified, comply with WDMA I.S.1-A, latest edition, "Architectural Wood Flush Doors."
C. Fire-Rated Wood Doors: Doors complying with NFPA 80 that are listed and labeled by a qualified testing agency, for fire-protection ratings indicated, based on testing at positive pressure according to UBC Standard 7-2.
1. Oversize Fire-Rated Door Assemblies: For units exceeding sizes of tested assemblies, provide certification by a qualified testing agency that doors comply with standard construction requirements for tested and labelled fire-rated door assemblies except for size. .
2. Temperature-Rise Limit: At vertical exit enclosures and exit passageways, provide doors that have a maximum transmitted temperature end point of not more than 450 Degrees F
(250 Degrees C) above ambient after thirty (30) minutes of standard fire-test exposure.
D. Preinstallation Conference: Conduct conference at Project site.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Comply with requirements of referenced standard and manufacturer's written instructions.
B. Package doors individually in cardboard cartons and wrap bundles of doors in plastic sheeting.
C. Mark each door on top and bottom rail with opening number used on Shop Drawings.
1.6 PROJECT CONDITIONS
A. Environmental Limitations: Do not deliver or install doors until spaces are enclosed and weathertight, wet work in spaces is complete and dry, and HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.
B. Environmental Limitations: Do not deliver or install doors until spaces are enclosed and weathertight, wet work in spaces is complete and dry, and HVAC system is operating and maintaining ambient temperature between 60 and 90 Degrees F (16 and 32 Degrees C) and relative humidity between 25 and 55 percent during the remainder of the construction period.
1.7 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace doors that fail in materials or workmanship within specified warranty period.
WOOD DOORS 081416 - 3
1. Failures include, but are not limited to, the following:
a. Warping (bow, cup, or twist) more than 1/4 inch (6.4 mm) in a 42-by-84-inch
(1067-by-2134-mm) section.
b. Telegraphing of core construction in face veneer exceeding 0.01 inch in a 3-inch
(0.25 mm in a 76.2-mm) span.
2. Warranty shall also include installation and finishing that may be required due to repair or replacement of defective doors.
3. Warranty Period for Solid-Core Interior Doors: Life of installation.
PART 2 - PRODUCTS
2.1 MANUFACTURES
A. Manufacturer’s: Subject to compliance with requirements, provide products by one of the following:
1. Mohawk
2. VT Industries.
3. Eggers Industries.
2.2 DOOR CONSTRUCTION, GENERAL
A. Low-Emitting Materials: Provide doors made with adhesive and composite wood products that do not contain urea formaldehyde and Green Guard Certified.
B. WDMA I.S.1-A Performance Grade: Standard Duty.
C. Solid Lumber Core Doors:
1. Solid Lumber: WDMA I.S.10.
a. Screw Withdrawal, Face: 700 LBf (3100n).
b. Screw Withdrawal, Face: 400 LBf (1780n).
2. Blocking: Provide wood blocking as follows:
a. 6-inch (125-mm) top-rail blocking, in doors indicated to have closers.
b. 6-inch (125-mm) bottom-rail blocking, in doors indicated to have kick, mop, or armor plates.
c. 6-inch (125-mm) midrail blocking, in doors indicated to have exit devices.
D. Fire-Protection-Rated Doors: Provide core specified as needed to provide fire-protection rating indicated.
1. Edge Construction: Provide edge construction with intumescent seals concealed by outer stile. Comply with specified requirements for exposed edges.
2. Pairs: Provide fire-retardant stiles that are listed and labeled for applications indicated without formed-steel edges and astragals. Provide stiles with concealed intumescent seals. Comply with specified requirements for exposed edges.
WOOD DOORS 081416 - 4
3. Pairs: Provide formed-steel edges and astragals with intumescent seals.
a. Finish steel edges and astragals with baked enamel same color as doors.
2.3 VENEERED-FACED DOORS FOR TRANSPARENT FINISH
A. Interior Solid-Core Doors:
1. Grade: AWA Premium Grade, with Grade A faces.
2. Species: Select Cherry-stained Dark Brown.
3. Cut: Plain Sliced.
4. Match between Veneer Leaves: Book Center balanced match.
5. Assembly of Veneer Leaves on Door Faces: Book Center balanced match.
6. Pair and Set Match: Provide for doors pair matched.
7. Vertical Edges: Same species.
8. Core: Particleboard LD2.
9. Construction: Five plies. Stiles and rails are bonded to core, then entire unit abrasive planed before veneering. Faces are bonded to core using a hot press.
10. WDMA I.S.1.-A Performance Grade: Super heavy duty.
2.4 FABRICATION
A. Where required, factory fit doors to suit frame-opening sizes indicated. Comply with clearance requirements of referenced quality standard for fitting unless otherwise indicated.
1. Comply with requirements in NFPA 80 for fire-rated doors.
B. Factory machine doors for hardware that is not surface applied. Locate hardware to comply with DHI-WDHS-3. Comply with final hardware schedules, door frame Shop Drawings, DHI A115-W series standards, and hardware templates.
1. Coordinate with hardware mortises in metal frames to verify dimensions and alignment before factory machining.
2. Metal Astragals: Factory machine astragals and formed-steel edges for hardware for pairs of fire-rated doors.
C. Openings: Cut and trim openings through doors in factory.
1. Light Openings: Trim openings with moldings of material and profile indicated.
2. Glazing: Factory install glazing in doors indicated to be factory finished. Comply with applicable requirements in Division 08 Section “Glazing”.
3. Louvers: Factory install louvers in prepared openings.
D. Fasteners: All exposed fasteners must be tamper -resistant.
WOOD DOORS 081416 - 5
2.5 FACTORY FINISHING
A. General: Comply with referenced quality standard for factory finishing. Complete fabrication, including fitting doors for openings and machining for hardware that is not surface applied, before finishing.
1. Finish faces, all four edges, edges of cutouts, and mortises. Stains and fillers may be omitted on top and bottom edges, edges of cutouts, and mortises.
2. Finish doors at factory.
3. Transparent Finish:
a. Grade: Premium.
b. Finish: WDMA TR-6 catalyzed polyurethane.
c. Staining: Match Architect’s.
d. Effect: Filled finish.
e. Sheen: Satin.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine doors and installed door frames before hanging doors.
1. Verify that frames comply with indicated requirements for type, size, location, and swing characteristics and have been installed with level heads and plumb jambs.
2. Reject doors with defects.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Hardware: For installation, see Division 8 Section "Door Hardware."
B. Installation Instructions: Install doors to comply with manufacturer's written instructions and the referenced quality standard, and as indicated.
1. Install fire-rated doors in corresponding fire-rated frames according to NFPA 80.
C. Job-Fitted Doors: Align and fit doors in frames with uniform clearances and bevels as indicated below; do not trim stiles and rails in excess of limits set by manufacturer or permitted for fire-rated doors. Machine doors for hardware. Seal edges of doors, edges of cutouts, and mortises after fitting and machining.
1. Clearances: Provide 1/8 inch (3.2 mm) at heads, jambs, and between pairs of doors.
Provide 1/8 inch (3.2 mm) from bottom of door to top of decorative floor finish or covering unless otherwise indicated. Where threshold is shown or scheduled, provide 1/4 inch (6.4 mm) form bottom of door to top of threshold unless otherwise indicated.
a. Comply with NFPA 80 for fire-rated doors.
WOOD DOORS 081416 - 6
2. Bevel fire-rated doors 1/8 inch in 2 inches (3-1/2 degrees) at lock edge; trim stiles and rails only to extent permitted by labeling agency.
D. Factory-Fitted Doors: Align in frames for uniform clearance at each edge.
E. Factory-Finished Doors: Restore finish before installation if fitting or machining is required at
Project site.
3.3 ADJUSTING
A. Operation: Re-hang or replace doors that do not swing or operate freely.
B. Finished Doors: Replace doors that are damaged or that do not comply with requirements.
Doors may be repaired or refinished if work complies with requirements and shows no evidence of repair or refinishing.
END OF SECTION 081416
COILING COUNTER DOORS 083313 - 1
SECTION 083313 - COILING COUNTER DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Counter door assemblies.
B. Related Requirements:
1. Section 055000 "Metal Fabrications" for door-opening framing and corner guards.
1.2 ACTION SUBMITTALS
A. Product Data: For each type and size of coiling counter door and accessory.
B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data.
1. Include points of attachment and their corresponding static and dynamic loads imposed on structure.
2. Show locations of locking devices and other accessories.
1.3 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.4 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer for both installation and maintenance of units required for this
Project.
PART 2 - PRODUCTS
2.1 COUNTER DOOR ASSEMBLY
A. Counter Door: Coiling counter door formed with curtain of interlocking metal slats.
1. Basis of Design: Overhead Door Corporation Model 657 with integral frame of approved equal.
http://www.specagent.com/LookUp/?ulid=21&mf=&src=wd
COILING COUNTER DOORS 083313 - 2
B. Operation Cycles: Door components and operators capable of operating for not less than
20,000.
C. Size: Refer to architectural drawings.
D. Door Curtain Material: Stainless steel.
E. Door Curtain Slats: Flat profile slats of 1-1/4-inch (32-mm) center-to-center height.
F. Bottom Bar: Manufacturer's standard continuous channel or tubular shape, fabricated stainless steel finished to match door.
G. Curtain Jamb Guides: Stainless steel with exposed finish matching curtain slats. Provide continuous integral wear strips to prevent metal-to-metal contact and to minimize operational noise.
H. Hood: Stainless steel.
1. Mounting: Face of Wall
I. Integral Frame, Hood, and Fascia: Stainless steel.
1. Mounting: Face of Wall
J. Sill Configuration: Integral metal sill.
K. Locking Devices: Equip door with locking device assembly and chain lock keeper.
1. Locking Device Assembly: Cremone-type, both jamb sides locking bars, operable from inside with thumbturn.
L. Manual Door Operator: Manufacturer's standard crank operator.
M. Curtain Accessories: Equip door with smoke seals, push/pull handles and pull-down strap.
N. Door Finish:
1. Stainless Steel Finish: ASTM A480/A480M No. 4 (polished directional satin).
2. Interior Curtain-Slat Facing: Match finish of exterior curtain-slat face.
2.2 MATERIALS, GENERAL
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2.3 DOOR CURTAIN MATERIALS AND FABRICATION
A. Door Curtains: Fabricate coiling counter door curtain of interlocking metal slats in a continuous length for width of door without splices. Unless otherwise indicated, provide slats of thickness and mechanical properties recommended by door manufacturer for performance, size, and type of door indicated, and as follows:
COILING COUNTER DOORS 083313 - 3
B. Curtain Jamb Guides: Manufacturer's standard angles or channels and angles of same material and finish as curtain slats unless otherwise indicated, with sufficient depth and strength to retain curtain, to allow curtain to operate smoothly, and to withstand loading. Slot bolt holes for guide adjustment. Provide removable stops on guides to prevent overtravel of curtain.
2.4 HOODS
A. General: Form sheet metal hood to entirely enclose coiled curtain and operating mechanism at opening head. Contour to fit end brackets to which hood is attached. Roll and reinforce top and bottom edges for stiffness. Form closed ends for surface-mounted hoods and fascia for any portion of between-jamb mounting that projects beyond wall face. Equip hood with intermediate support brackets as required to prevent sagging.
B. Integral Frame, Hood, and Fascia: Welded sheet metal assembly of the following sheet metal(s):
1. Stainless Steel.
2.5 LOCKING DEVICES
A. Slide Bolt: Fabricate with side-locking bolts to engage through slots in tracks for locking by padlock, located on both left and right jamb sides, operable from coil side.
B. Chain Lock Keeper: Suitable for padlock.
2.6 CURTAIN ACCESSORIES
A. Smoke Seals: Equip each fire-rated door with replaceable smoke-seal perimeter gaskets or brushes for smoke and draft control as required for door listing and labeling by a qualified testing agency.
B. Push/Pull Handles: Equip each push-up-operated or emergency-operated door with lifting handles on each side of door, finished to match door.
C. Pull-Down Strap: Provide pull-down straps for doors more than 84 inches (2130 mm) high.
2.7 COUNTER DOOR ACCESSORIES
A. Integral Metal Sill: Fabricate sills as integral part of frame assembly of Type 304 stainless steel in manufacturer's standard thickness with ASTM A480/A480M No. 4 finish.
2.8 COUNTERBALANCE MECHANISM
A. General: Counterbalance doors by means of manufacturer's standard mechanism with an adjustable-tension, steel helical torsion spring mounted around a steel shaft and contained in a spring barrel connected to top of curtain with barrel rings. Use grease-sealed bearings or self-lubricating graphite bearings for rotating members.
COILING COUNTER DOORS 083313 - 4
B. Brackets: Manufacturer's standard mounting brackets of either cast iron or cold-rolled steel plate.
2.9 MANUAL DOOR OPERATORS
A. General: Equip door with manual door operator by door manufacturer.
B. Push-up Door Operation: Design counterbalance mechanism so that required lift or pull for door operation does not exceed 25 lbf (111 N).
C. Crank Operator: Consisting of crank and crank gearbox, steel crank drive shaft, and gear-reduction unit, of type indicated. Size gears to require not more than 25-lbf (111-N) force to turn crank. Fabricate gearbox to be oiltight and to completely enclose operating mechanism.
Provide manufacturer's standard crank-locking device.
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Install coiling counter doors and operating equipment complete with necessary hardware, anchors, inserts, hangers, and equipment supports; according to manufacturer's written instructions and as specified.
3.2 FIELD QUALITY CONTROL
A. Repair or remove and replace installations where inspections indicate that they do not comply with specified requirements.
B. Reinspect repaired or replaced installations to determine if replaced or repaired door assembly installations comply with specified requirements.
3.3 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain coiling counter doors.
END OF SECTION 083313
OVERHEAD COILING DOORS 083323 - 1
SECTION 083323 - OVERHEAD COILING DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Service doors.
2. Insulated service doors.
3. Locking Devices
4. Curtain Accessories
5. Manual Door Operators
6. Electric Door Operators.
B. Related Requirements:
1. Section 055000 "Metal Fabrications" for miscellaneous steel supports, door-opening framing, corner guards, and bollards.
1.2 ACTION SUBMITTALS
A. Product Data: For each type and size of overhead coiling door and accessory.
B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data.
1. Include points of attachment and their corresponding static and dynamic loads imposed on structure.
2. Include diagrams for power, signal, and control wiring.
C. Samples: For each color and texture specified.
1.3 INFORMATIONAL SUBMITTALS
A. Sample warranty.
1.4 CLOSEOUT SUBMITTALS
A. Special warranty.
B. Maintenance data.
C. Record Documents: For fire-rated doors, list of door numbers and applicable room name and number to which door accesses.
OVERHEAD COILING DOORS 083323 - 2
1.5 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer for both installation and maintenance of units required for this
Project.
1.6 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of doors that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Two years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Structural Performance, Exterior Doors: Capable of withstanding the following design wind loads:
1. Design Wind Load: Uniform pressure (velocity pressure) of 20 lbf/sq. ft. (960 Pa), acting inward and outward.
2.2 DOOR ASSEMBLY SEIDEL HALL (Non-Insulated Door)
A. Service Door: Overhead coiling door formed with curtain of interlocking metal slats.
1. Basis of Design: Overhead Door Company Model 620 or Approved Equal.
B. Operation Cycles: Door components and operators capable of operating for not less than
20,000.
C. Door Curtain Material: Galvanized steel.
D. Door Curtain Slats: Flat profile slats of 2-5/8-inch (67-mm) center-to-center height.
E. Bottom Bar: Two angles, each not less than 1-1/2 by 1-1/2 by 1/8 inch (38 by 38 by 3 mm) thick; fabricated from hot-dip galvanized steel and finished to match door.
F. Curtain Jamb Guides: Galvanized steel with exposed finish matching curtain slats.
G. Hood: Match curtain material and finish.
1. Mounting: Face of wall.
H. Locking Devices: Equip door with locking device assembly.
http://www.specagent.com/LookUp/?ulid=7627&mf=&src=wd
OVERHEAD COILING DOORS 083323 - 3
1. Locking Device Assembly: Single-jamb side locking bars, operable from inside and outside with cylinders.
I. Electric Door Operator:
1. Usage Classification: Standard duty, up to 25 cycles per hour and up to 90 cycles per day.
2. Safety: Listed according to UL 325 by a qualified testing agency for commercial or industrial use.
3. Motor Exposure: Exterior, wet, and humid.
4. Motor Electrical Characteristics:
a. Horsepower: as recommended by Overhead Coiling Door Manufacturer.
b. Voltage: 208 V ac, three phase, 60 Hz
5. Emergency Manual Operation: Chain type.
6. Obstruction-Detection Device: Automatic electric sensor edge on bottom bar.
7. Control Station(s): Exterior mounted
8. Other Equipment: Audible and visual signals and Portable radio-control system.
J. Curtain Accessories: Equip door with push/pull handles, pull-down strap, and automatic-closing device.
K. Door Finish:
1. Baked-Enamel or Powder-Coated Finish: Color as selected by Architect from manufacturer's standard range.
2.3 MATERIALS, GENERAL
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2.4 DOOR CURTAIN MATERIALS AND CONSTRUCTION
A. Door Curtains: Fabricate overhead coiling-door curtain of interlocking metal slats, designed to withstand wind loading indicated, in a continuous length for width of door without splices.
Unless otherwise indicated, provide slats of thickness and mechanical properties recommended by door manufacturer for performance, size, and type of door indicated, and as follows:
1. Insulation: Fill slats for insulated doors with manufacturer's standard thermal insulation complying with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, according to ASTM E84 or UL 723. Enclose insulation completely within slat faces.
2. Metal Interior Curtain-Slat Facing: Match metal of exterior curtain-slat face, with minimum steel thickness of 24 gauge.
B. Curtain Jamb Guides: Manufacturer's standard angles or channels and angles of same material and finish as curtain slats unless otherwise indicated, with sufficient depth and strength to retain curtain, to allow curtain to operate smoothly, and to withstand loading. Slot bolt holes for guide adjustment. Provide removable stops on guides to prevent overtravel of curtain.
OVERHEAD COILING DOORS 083323 - 4
2.5 HOODS
A. General: Form sheet metal hood to entirely enclose coiled curtain and operating mechanism at opening head. Contour to fit end brackets to which hood is attached. Roll and reinforce top and bottom edges for stiffness. Form closed ends for surface-mounted hoods and fascia for any portion of between-jamb mounting that projects beyond wall face. Equip hood with intermediate support brackets as required to prevent sagging.
1. Exterior-Mounted Doors: Fabricate hood to act as weather protection and with a perimeter sealant-joint-bead profile for applying joint sealant.
2.6 LOCKING DEVICES
A. Slide Bolt: Fabricate with side-locking bolts to engage through slots in tracks for locking by padlock, located on both left and right jamb sides, operable from coil side.
B. Locking Device Assembly: Fabricate with cylinder lock, spring-loaded dead bolt, operating handle, cam plate, and adjustable locking bars to engage through slots in tracks.
1. Lock Cylinders: As standard with manufacturer and keyed to building keying system.
2. Keys: Two for each cylinder.
C. Safety Interlock Switch: Equip power-operated doors with safety interlock switch to disengage power supply when door is locked.
2.7 CURTAIN ACCESSORIES
A. Weatherseals for Exterior Doors: Equip each exterior door with weather-stripping gaskets fitted to entire exterior perimeter of door for a weather-resistant installation unless otherwise indicated.
B. Push/Pull Handles: Equip each push-up-operated or emergency-operated door with lifting handles on each side of door, finished to match door for doors less than 84 inches (2130 mm) high.
C. Pull-Down Strap: Provide pull-down straps for doors more than 84 inches (2130 mm) high.
2.8 COUNTERBALANCE MECHANISM
A. General: Counterbalance doors by means of manufacturer's standard mechanism with an adjustable-tension, steel helical torsion spring mounted around a steel shaft and contained in a spring barrel connected to top of curtain with barrel rings. Use grease-sealed bearings or self-lubricating graphite bearings for rotating members.
B. Brackets: Manufacturer's standard mounting brackets of either cast iron or cold-rolled steel plate.
OVERHEAD COILING DOORS 083323 - 5
2.9 ELECTRIC DOOR OPERATORS
A. General: Electric door operator assembly of size and capacity recommended and provided by door manufacturer for door and operation-cycles requirement specified, with electric motor and factory-prewired motor controls, starter, gear-reduction unit, solenoid-operated brake, clutch, control stations, control devices, integral gearing for locking door, and accessories required for proper operation.
1. Comply with NFPA 70.
2. Control equipment complying with NEMA ICS 1, NEMA ICS 2, and NEMA ICS 6, with
NFPA 70 Class 2 control circuit, maximum 24-V ac or dc.
B. Usage Classification: Electric operator and components capable of operating for not less than number of cycles per hour indicated for each door.
C. Motors: Reversible-type motor, with controller (disconnect switch) for motor exposure indicated for each door assembly.
1. Electrical Characteristics: Minimum as indicated for each door assembly. If not indicated, large enough to start, accelerate, and operate door in either direction from any position, at a speed not less than 8 in./sec. (203 mm/s) and not more than 12 in./sec. (305 mm/s), without exceeding nameplate ratings or service factor.
2. Operating Controls, Controllers, Disconnect Switches, Wiring Devices, and Wiring:
Manufacturer's standard unless otherwise indicated.
D. Obstruction-Detection Devices: External entrapment protection consisting of indicated automatic safety sensor capable of protecting full width of door opening. For non-fire-rated doors, activation of device immediately stops and reverses downward door travel.
1. Electric Sensor Edge: Automatic safety sensor edge, located within astragal or weather stripping mounted to bottom bar. Contact with sensor activates device. Connect to control circuit using manufacturer's standard take-up reel or self-coiling cable.
E. Control Station: Three-button control station in fixed location with momentary-contact push-button controls labeled "Open" and "Stop" and sustained- or constant-pressure push-button control labeled "Close."
1. Exterior-Mounted Units: Full-guarded, standard-duty, surface-mounted, weatherproof type, NEMA ICS 6, Type 4 enclosure, key operated.
F. Emergency Manual Operation: Equip each electrically powered door with capability for emergency manual operation. Design manual mechanism so required force for door operation does not exceed 25 lbf (111 N).
G. Emergency Operation Disconnect Device: Equip operator with hand-operated disconnect mechanism for automatically engaging manual operator and releasing brake for emergency manual operation while disconnecting motor without affecting timing of limit switch. Mount mechanism so it is accessible from floor level. Include interlock device to automatically prevent motor from operating when emergency operator is engaged.
H. Motor Removal: Design operator so motor may be removed without disturbing limit-switch adjustment and without affecting emergency manual operation.
OVERHEAD COILING DOORS 083323 - 6
I. Audible and Visual Signals: Audible alarm and visual indicator lights in compliance with the accessibility standard.
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Install overhead coiling doors and operating equipment complete with necessary hardware, anchors, inserts, hangers, and equipment supports; according to manufacturer's written instructions and as specified.
B. Power-Operated Doors: Install automatic garage doors openers according to UL 325.
3.2 FIELD QUALITY CONTROL
A. Perform the following tests and inspections with the assistance of a factory-authorized service representative:
1. Test door release, closing, and alarm operations when activated by smoke detector or building's fire-alarm system. Test manual operation of closed door. Reset door-closing mechanism after successful test.
2. Fire-Rated Door Inspections: Inspect each fire-rated door in accordance with NFPA 80, Section 5.2.
B. Repair or remove and replace installations where inspections indicate that they do not comply with specified requirements.
C. Reinspect repaired or replaced installations to determine if replaced or repaired door assembly installations comply with specified requirements.
3.3 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain overhead coiling doors.
END OF SECTION 083323
SPECIAL FUNCTION DOORS 083400 - 1
SECTION 083400 – SPECIAL FUNCTION DOORS
PART 1 - GENERAL
1.1 GENERAL REQUIREMENTS
A. Work of this Section, as shown or specified, shall be in accordance with the requirements of the Contract Documents.
1.2 SECTION INCLUDES
A. Work of this Section includes all labor, materials, equipment, and services necessary to complete the special function doors as shown on the drawings and/or specified herein, including, but not necessarily limited to, the following:
1. Barricade resistant door assemblies
1.3 RELATED SECTIONS
A. Flush Wood Doors – Section 081416
B. Hollow Metal Doors & Frames – Section 081113
C. Door Hardware – Section 087100
1.4 QUALITY ASSURANCE
A. Provide assembly compliant to UL-1784 Standard for Air Leakage Tests of Door Assemblies and Other Opening Protectives.
B. Doors to be pre-assembled with all hardware prior to arriving onsite.
1.5 SUBMITTALS
A. Product Data – Submit:
1. Materials list of items proposed to be provided under this Section.
2. Manufacturer’s specifications, cut sheets and other data needed to prove compliance with the specified requirements.
B. Shop Drawings: Provide shop drawings in sufficient detail to show fabrication, installation, anchorage, and interface of the work of this Section with the work of adjacent trades.
C. Manufacturer's recommended installation procedures.
1.6 PRODUCT HANDLING
A. Protection: Use all means necessary to protect the materials of this Section before, during, and after installation, and to protect the installed work and materials of all other trades.
B. Replacements: In the event of damage, immediately make all repairs and replacements necessary.
C. Provide 1-year warranty on complete door assembly.
SPECIAL FUNCTION DOORS 083400 - 2
PART 2 PRODUCTS
2.1 BARRICADE RESISTANT DOOR ASSEMBLIES
A. SWING Anti-Barricade Doorset by Kingsway Group, Inc. 1521 E. Avis Dr, Madison Heights MI
48071.
1. Complete doorset delivered in three sections: door assembly, frame assembly, and emergency stop assembly.
2. Door assembly consisting of solid core wood door, ligature resistant mortise lockset, double acting hinge with 105-degree opening, and privacy vision panel operated by oval-drive staff key which also operates anti-barricade stop.
3. Frame assembly to be constructed of minimum 14-gauge mild steel, having single-rabbet strike jamb to coordinate with anti-barricade stop, flush hinge jamb, and flush header.
4. Emergency stop assembly to consist of hinged stop with two locking points on jamb, operated by oval drive staff key.
5. Hardware:
a. Double acting continuous hinge: KG202 SwingHinge double acting continuous hinge by
Kingsway Group
b. Ligature Resistant Mortise Lockset: Refer to Door Hardware Schedule
c. Privacy Vision Panel: Cut out to be provided for existing Duralux by Kingsway group to be installed by contractor.
d. Anti-barricade Stop: Kingsway SwingStop anti-barricade wood or aluminum stop with two locking points by Kingsway Group
e. Concealed Closer: KG35 by Kingsway Group. Refer to Door Hardware Schedule
6. Construction: Door to be made having a solid core and hardwood stiles. Assembly to be completed with Torx Security Fasteners throughout.
7. Finish: As selected by architect from selections offered by Kingsway Group.
PART 3 EXECUTION
3.1 INSPECTION
A. Examine the areas and conditions where special function doors are to be installed and correct any conditions detrimental to the proper and timely completion of the work. Do not proceed with the work until unsatisfactory conditions are corrected to permit proper installation of the work.
3.2 INSTALLATION
A. Coordinate as required with other trades to ensure proper and adequate provision in the work of those trades for interface with the work of this Section.
SPECIAL FUNCTION DOORS 083400 - 3
B. Install the work of this Section in strict accordance with the original design, the approved Shop Drawings, pertinent requirements of governmental agencies having jurisdiction, and the manufacturer’s recommended installation procedures.
END OF SECTION
ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS 084113 - 1
SECTION 084113 - ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
1.1 SUMMARY
A. Section Includes:
1. Aluminum-framed entrance and storefront systems.
1.2 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.3 ACTION SUBMITTALS
A. Product data.
B. Shop Drawings:
1. Plans, elevations, sections, full-size details, and attachments to other work.
2. Connection to and continuity with adjacent thermal, weather, air, and vapor barriers.
3. Point-to-point wiring diagrams.
C. Samples: Manufacturer's standard color sheets, showing full range of available colors for each type of exposed finish.
D. Entrance Door Hardware Schedule: Prepared by or under supervision of supplier, detailing fabrication and assembly of entrance door hardware, as well as procedures and diagrams.
1.4 INFORMATIONAL SUBMITTALS
A. Energy Performance Certificates: NFRC-certified energy performance values from manufacturer.
B. Product test reports.
C. Source quality-control reports.
D. Field quality-control reports.
E. Sample warranties.
ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS 084113 - 2
1.5 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.6 QUALITY ASSURANCE
A. Installer Qualifications:
1. Authorized representative who is trained and approved by manufacturer.
B. Product Options: Information on Drawings and in Specifications establishes requirements for aesthetic effects and performance characteristics of assemblies. Aesthetic effects are indicated by dimensions, arrangements, alignment, and profiles of components and assemblies as they relate to sightlines, to one another, and to adjoining construction.
1. Do not change intended aesthetic effects, as judged solely by Architect, except with
Architect's approval. If changes are proposed, submit comprehensive explanatory data to
Architect for review.
1.7 WARRANTY
A. Special Warranty: Manufacturer and Installer agree to repair or replace components of aluminum-framed entrance and storefront systems that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Two years from date of Substantial Completion.
B. Special Finish Warranty, Anodized Finishes: Standard form in which manufacturer agrees to repair finishes or replace aluminum that shows evidence of deterioration of anodized finishes within specified warranty period.
1. Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. General Performance: Comply with performance requirements specified, as determined by testing of aluminum-framed entrance and storefront systems representing those indicated for this Project without failure due to defective manufacture, fabrication, installation, or other defects in construction.
1. Aluminum-framed entrance and storefront systems to withstand movements of supporting structure, including, but not limited to, twist, column shortening, long-term creep, and deflection from uniformly distributed and concentrated live loads.
2. Failure also includes the following:
a. Thermal stresses transferring to building structure.
b. Glass breakage.
ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS 084113 - 3
c. Noise or vibration created by wind and thermal and structural movements.
d. Loosening or weakening of fasteners, attachments, and other components.
e. Failure of operating units.
B. Structural Loads:
1. Design Wind Loads: Determine design wind loads applicable to Project from basic wind speed indicated in miles per hour (meters per second) at 33 feet (10 m) above grade, according to ASCE 7, Section 6.5, "Method 2-Analytical…