ESBD_393688_1738699998320_HHS0015184 Attachment H-1f.pdf

PDF 9 MB Posted

Attached to
Project 24-207-SAH, Alamo Hall Geriatric MSU Renovations, San Antonio, TX
Solicitation number
HHS0015184
Issued by
Texas

About this file

This file contains mechanical and electrical construction drawings and specifications from Moose Engineers for renovations to Alamo Hall Geriatric MSU and Seidel Building at the San Antonio State Hospital for the Texas State Health and Human Services Commission. The drawings include detailed mechanical floor plans, demolition plans, lighting plans, and electrical systems for both buildings. The documents appear to be final construction documents dated November 2024.

The drawings include comprehensive mechanical and electrical specifications including HVAC systems, lighting fixture schedules, power distribution plans, and fire alarm systems. Key elements shown include new generators, automatic transfer switches, lighting control systems, and mechanical equipment like fan coil units and air handling units. The drawings provide detailed technical information through floor plans, schedules, and keyed notes to guide construction and installation. There is also an alternate pricing option shown for corridor work in the Seidel building. All drawings include professional engineering stamps indicating they are signed and sealed construction documents.

View the file

Other files

File Type Posted
ESBD_393688_1738702541104_HHS0015184 Attachment H-2d.pdf PDF
ESBD_393688_1738703430357_HHS0015184 Attachment H-3c.pdf PDF
ESBD_393688_1738699995334_HHS0015184 Attachment H-1g.pdf PDF
ESBD_393688_1738699992490_HHS0015184 Attachment H-1c.pdf PDF
ESBD_393688_1738699993254_HHS0015184 Attachment H-1a.pdf PDF
ESBD_393688_1738702536322_HHS0015184 Attachment H-2e.pdf PDF
ESBD_393688_1738699999440_HHS0015184 Attachment H-1e.pdf PDF
ESBD_393688_1738698135480_HHS0015184 Attachments.zip ZIP file
ESBD_393688_1738699994376_HHS0015184 Attachment H-1d.pdf PDF
ESBD_393688_1738699996382_HHS0015184 Attachment H-1i.pdf PDF
ESBD_393688_1738702539922_HHS0015184 Attachment H-2b.pdf PDF
ESBD_393688_1738702537792_HHS0015184 Attachment H-2g.pdf PDF
ESBD_393688_1738698012370_HHS0015184 RFP final.pdf PDF
ESBD_393688_1738699997302_HHS0015184 Attachment H-1h.pdf PDF
ESBD_393688_1738698053000_HHS0015184 Exhibits.zip ZIP file
ESBD_393688_1738702537061_HHS0015184 Attachment H-2f.pdf PDF
ESBD_393688_1738703429313_HHS0015184 Attachment H-3a.pdf PDF
ESBD_393688_1738699991716_HHS0015184 Attachment H-1b.pdf PDF
ESBD_393688_1738702542122_HHS0015184 Attachment H-2c.pdf PDF
ESBD_393688_1738703428621_HHS0015184 Attachment H-3b.pdf PDF
ESBD_393688_1738702538751_HHS0015184 Attachment H-2a.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D W

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

D

D

16 16

MECH ROOM

ADA PATIENT

BED 6

ADA PATIENT

BED 5

PATIENT BED 3

PATIENT BED 2

PATIENT BED 7

NEW ELEVATOR

STAFF STATION

ELECT. ROOM

SECLUSION ANTE

ANTE ROOM T/R

SECLUSION

ROOM

ADA TLT /

SHWR 2

CLN

PATIENT BED 17

PAT TLT. 6

STOR.

EXAM ROOM

STOR.

PATIENT BED 1

PATIENT BED 4

PAT TLT. 2

STAFF

OBSERVATION

SOILED

PATIENT SHWR 2

ELOPEMENT

CONSULT 4

ADA PATIENT

BED 15

PAT TLT / TUB

SHWR 3

PATIENT BED 19

PATIENT BED 20

MECH. ROOM

PAT TLT. 5

MECH ROOM

PAT TLT

PATIENT

CORRIDOR

219 PATIENT

CORRIDOR

ADA TLT / SHWR

206 EVS

CLN

IDF ROOM

LAUNDRY

PATIENT BED 18

EXISTING STAIRS

INCENTIVE

THERAPY

STAIRS

ELEVATOR

PATIENT BED 16

PATIENT BED

PATIENT BED

PATIENT BED

PAT TLT. 3

PATIENT BED

PAT. TLT. 4

PATIENT BED

ADA PATIENT

BED 14

PATIENT

SHOWER 1

PAT TLT. 1

PATIENT BED

STOR.

STOR.

PATIENT

CORRIDOR

FCU-45

FCU-48

FCU-39

FCU-40

3/4" D

3/4" CHWR

3/4" CHWS

3/4" D

3/4" D

3/4" D

3/4" CHWS

3/4" CHWR

1" CHWS 1" CHWR

3/4" D

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :5

A

M

MD2.2

MECHANICAL HYDRONICS

DEMO - ALAMO HALL 521 -

LEVEL 2

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

DEMOLISH PIPING BACK TO MAIN. CAP FOR RECONNECTION IN NEW WORK

PHASE.

DEMOLISH PIPING BACK TO APPROXIMATE LOCATION. CAP FOR RECONNECTION

IN NEW WORK PHASE.

DEMOLISH PIPING IN ITS ENTIRETY FROM TAILPIECE OF SINK TO UNIT.

MECHANICAL KEYED NOTES:

1. PIPING DEMOLITION TO INCLUDE ANY ASSOCIATED HANGERS, SUPPORS AND

INSUALTION.

2. THE "EXISTING" MECHANICAL LAYOUTS INDICATED ON THESE DOCUMENTS

ARE BASED ON THE INFORMATION AVAILABLE AND MAY BE INCOMPLETE AND

INACCURATE. IT SHOULD BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY

ACTUAL CONDITIONS AND MAKE SUITABLE ADJUSTMENTS AS NECESSARY, TO

ACCOMMODATED NEW WORK, AT NO EXTRA COST TO THE OWNER.

CONDITIONS DIFFERENT TO THOSE INDICATED SHALL BE INCORPORATED INTO

THE CONSTRUCTION DOCUMENTS. NOTE THAT ANY UNCOVERED SYSTEMS

MUST BE CAREFULLY IDENTIFIED PRIOR TO MODIFICATIONS.

3. CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES AND

INCLUDE ANY MODIFICATIONS NEEDED TO ACCOMMODATE THEIR WORK.

4. IF AT ANY TIME DURING DEMOLITION OR CONSTRUCTION THE CONTRACTOR

ENCOUNTERS SUSPECTED HAZARDOUS MATERIALS THE CONTRACTOR SHALL

NOT DISTURB THESE SUSPECT MATERIALS IN ANY WAY. IMMEDIATELY NOTIFY

OWNERS REPRESENTATIVE. AN ASBESTOS SURVEY IS AVAILABLE FOR THIS

PROJECT THAT IDENTIFIES AREAS AND SYSTEMS WHERE ABATEMENT WILL BE

REQUIRED. THE SURVEY IS INTENDED TO COVER POTENTIAL ITEMS IN THE

CONSTRUCTION AREA. HOWEVER, THE CONTRACTOR SHALL USE CAUTION

SINCE ADDITIONAL HAZARDOUS MATERIALS MAY BE UNCOVERED THAT ARE

NOT IDENTIFIED IN THE SURVEY.

MECHANICAL GENERAL NOTES:

1/8" = 1'-0"MD2.2

SECOND FLOOR PLAN DEMO - MECHANICAL

HYDRONICS

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

L

R

DN

UP

X XX X X X X

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

QUIET ACTIVITY

FCU-14

FCU-15

FCU-16

FCU-5

SB

FCU-11

20"x12"

12"x8"

8"x8"

8"x8"

8"x10"

EA

SA

SA

SB

RA

SB

SB

EA

SB

SB

SB

EA

EA

EA

SCREEN/

RECEIVING

236 SF

SB

1 FCU-20

SB

SB

SA

SA

SA

STAFF STATION

MED ROOM

EVS

SB

18"x10"

SA

SC

SERVERY/

NOURISHMENT

195 SF

SB

FCU-63

T

T

T

T

T

SC

SC

SA

STORAGE ROOM

CLEAN LINEN

STORAGE

SUPPLY

SA

EA

SA

RA

RA

SE

RB

SE

EX

EX

SE

RB

6"x10"

14"x8"

10"x12"

6"x10"

8"x12"

10"x10"

RA

10"x10"

6"x6" 6"x6"

RB

10"x10"

RA

10"x10"

RA

10"x10"

RA

RB

6"x6"

EA

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :5

A

M

M1.1

MECHANICAL FLOOR PLAN

- ALAMO HALL 521 - LEVEL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

RELOCATE FCU TO APPROXIMATE LOCATION. SUSPEND UNIT WITH ALL-THREAD

AND SPRING ISOLATORS. TRANSITION SUPPLY AND RETURN DUCTWORK AS

NECESSARY TO CONNECT TO UNIT.

EXISTING EXHAUST DUCTWORK DOWN FROM FLOOR ABOVE. CONNECT NEW

DUCT TO EXISTING MAIN.

TERMINATE FULLY INSULATED COPPER CONDENSATE AT MOP SINK WITH 1" AIR

GAP.

ROUND SUPPLY DUCT TO ELBOW UPWARDS TOWARD FLOOR ABOVE AND RUN

AS CLOSE AS POSSIBLE TO STRUCTURE TO AVOID OUTSIDE AIR DUCT.

MECHANICAL KEYED NOTES:

1/8" = 1'-0"M1.1

1 FIRST FLOOR PLAN - MECHANICAL

1. TEMPERATURE SENSORS TO BE CEILING MOUNTED. ROOMS TO HAVE 5

DEGREES OF ADJUSTABILITY.

2. FIELD VERIFY EXISTING SITE CONDITIONS PRIOR TO START OF WORK.

3. ACCESS PANELS TO BE INSTALLED DIRECTLY BELOW FCUS. REFER TO

ARCHITECT FOR LOCATIONS.

4. ALL DAMPERS LOCATED ABOVE GYPSUM CEILINGS ARE TO BE PROVIDED

WITH ANTI LIGATURE RATED REMOTE CABLE OPERATED DAMPERS.

MECHANICAL GENERAL NOTES:

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

D

D

16 16

MECH ROOM

ADA PATIENT

BED 6

ADA PATIENT

BED 5

PATIENT BED 3

PATIENT BED 2

PATIENT BED 7

NEW ELEVATOR

STAFF STATION

ELECT. ROOM

SECLUSION ANTE

ANTE ROOM T/R

SECLUSION

ROOM

ADA TLT /

SHWR 2

CLN

PATIENT BED 17

PAT TLT. 6

STOR.

EXAM ROOM

STOR.

PATIENT BED 1

PATIENT BED 4

PAT TLT. 2

STAFF

OBSERVATION

SOILED

PATIENT SHWR 2

ELOPEMENT

CONSULT 4

ADA PATIENT

BED 15

PAT TLT / TUB

SHWR 3

PATIENT BED 19

PATIENT BED 20

MECH. ROOM

PAT TLT. 5

MECH ROOM

PAT TLT

PATIENT

CORRIDOR

219 PATIENT

CORRIDOR

ADA TLT / SHWR

206 EVS

CLN

IDF ROOM

LAUNDRY

PATIENT BED 18

EXISTING STAIRS

INCENTIVE

THERAPY

STAIRS

ELEVATOR

PATIENT BED 16

PATIENT BED

PATIENT BED

PATIENT BED

PAT TLT. 3

PATIENT BED

PAT. TLT. 4

PATIENT BED

ADA PATIENT

BED 14

PATIENT

SHOWER 1

PAT TLT. 1

PATIENT BED

STOR.

STOR.

PATIENT

CORRIDOR

FCU-62

FCU-45

FCU-481

EF-27

ON ROOF

SA

FCU-39

SC

RA

8"x12"

SC

8"x12"

8"x12"

8"x12"

EA

6"x6"

EX

EX

EX

FCU-40

EX

SB

SB

EX

EA

SA

8"x12"

EX

10"x10"

RB

RA

RA

RA

EX

10"x10"

RA

SB

DN

UP

EX

50EX

12"x12" 8"x8"

RA

RA

10"x10"

RA

SA

RA

EA

SA

SB

RA

14"x12"

12"x10"

FCU-48

EX

115 1

SA

FCU-56

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :0

A

M

M1.2

MECHANICAL FLOOR PLAN

- ALAMO HALL 521 - LEVEL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1/8" = 1'-0"M1.2

1 SECOND FLOOR PLAN - MECHANICAL

RELOCATE FCU TO APPROXIMATE LOCATION. SUSPEND UNIT WITH ALL-THREAD

AND SPRING ISOLATORS.

EXHAUST DUCTWORK UP TO NEW FAN ON ROOF ABOVE. TRANSITION AS

NECESSARY TO CONNECT.

ROUTE 3/4" CONDENSATE DOWN TO TAIL PIECE OF SINK.

CONNECT 3/4" CONDENSATE TO EXISTING LINE CONNECTING TO TAILPIECE OF

SINK.

SUSPEND NEW FAN-COIL UNIT WITH ALL-THREAD AND SPRING ISOLATORS.

REBALANCE ROOF MOUNTED EXHAUST FAN EF-18 TO 140 CFM.

MECHANICAL KEYED NOTES:

1. TEMPERATURE SENSORS TO BE CEILING MOUNTED. ROOMS TO HAVE 5

DEGREES OF ADJUSTABILITY.

2. FIELD VERIFY EXISTING SITE CONDITIONS PRIOR TO START OF WORK.

3. ACCESS PANELS TO BE INSTALLED DIRECTLY BELOW FCUS. REFER TO

ARCHITECT FOR LOCATIONS.

4. ALL DAMPERS LOCATED ABOVE GYPSUM CEILINGS ARE TO BE PROVIDED

WITH ANTI LIGATURE RATED REMOTE CABLE OPERATED DAMPERS.

MECHANICAL GENERAL NOTES:

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

UP

M1.3

40"x16" 40"x14"

30"x12"

14"x12"

12"x8"

14"x12"

18"x12"20"x16"

20"x12"

12"x12"

EA

EA

26"x16"

12"x10"

10"x10"

VAV-1-1

VAV-1-2

VAV1-3

VAV-1-4

VAV-1-5

VAV-1-6

VAV-1-7

VAV-1-8

VAV-1-9 VAV-1-10

AHU-2

1 1

EF-4

ON ROOF

EF-5

ON ROOF

SA

SA

SA

SA

SA

50SA

50SC

SA

SA

SB

SB

SA

SB

SC

SC

SB

SB

SB

SB

SB

SB

SA

SA

SA

SA

SB

SB

SB

SB

SB

SC

SB

SB

SB

SA

SE

SE

T

T

T

T

T

T

TT

T

T

EA

EA

EA

RB

RB

RA

RA

RA

RA

RA

RA

RA

RB

100 RB

RB

SB

EA

EA

RB

RB

RA

RA

RB

RB

SS-1

10"/12"

14"x12"

12"x12"

T

T

8"x10"

12"x10"

12"x12"

16"x12"

8"x12"

8"x10"

10"x12" 12"x12"

20"x12"

RB

22"x10"

22"x10"

EA

12"x8"

RH-1

ON ROOF

9AHU-1

3/4" D

26"x16"

CU-1

ON ROOF

AFMS

RH-1

10"x18"

2" CHWS

2" CHWR

1 1/2" HWR

1 1/2" HWS

M

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :0

A

M

M1.3

MECHANICAL FLOOR PLAN

- SEIDEL BUILDING 598

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

SUSPEND VAV WITH ALL-THREAD AND SPRING

ISOLATORS. COORDINATE FINAL LOCATION WITH

ARCHITECTURAL RCP FOR ACCESS PANEL LOCATIONS.

CONNECT EXISTING CHILLED WATER AND HOT WATER

PIPING TO NEW VALVE PACKAGE.

EXHAUST DUCTWORK UP TO FAN ON ROOF. TRANSITION

AS NECESSARY TO CONNECT.

UNIT TO BE MOUNTED ABOVE DOOR.

TERMINATE FULLY INSULATED COPPER CONDENSATE AT

FLOOR DRAIN WITH 1" AIR GAP.

REFRIGEREANT PIPING UP TO CONDENSING UNIT ON

ROOF.

EXISTING CHILLED WATER TO TRAVEL OVER TOP OF AIR

HANDLING UNIT.

18"x10" OUTSIDE AIR DUCT UP TO ROOF HOOD. AIRFLOW

MEASURING STATION TO BE LOCATED IN VERTICAL

POSITION.

RELOCATE AHU-2 VFD AND BAS PANEL TO APPROXIMATE

LOCATION.

CONDENSATE DOWN TO TAILPIECE OF SINK.

MECHANICAL KEYED NOTES:

1. TEMPERATURE SENSORS TO BE CEILING MOUNTED.

ROOMS TO HAVE 5 DEGREES OF ADJUSTABILITY.

2. FIELD VERIFY EXISTING SITE CONDITIONS PRIOR TO

START OF WORK.

3. ACCESS PANELS TO BE INSTALLED DIRECTLY BELOW

VAVS. REFER TO ARCHITECT FOR LOCATIONS.

4. ALL DAMPERS LOCATED ABOVE GYPSUM CEILINGS

ARE TO BE PROVIDED WITH ANTI LIGATURE RATED

REMOTE CABLE OPERATED DAMPERS.

5. ALL DUCTWORK FROM UNIT OUTLET TO INLET OF VAV

BOX TO BE MEDIUM PRESSURE. ALL DUCTWORK FROM

VAV BOX TO AIR TERMINAL TO BE LOW PRESSURE.

MECHANICAL GENERAL NOTES:

1/4" = 1'-0"M1.3

2 AHU-1 VIEW

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

UP

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

1 1

D

D

16 16

FCU-5

3/4" D

3/4" CHWS

3/4" CHWR

3/4" D 3/4" D

3/4" CHWR

3/4" CHWS

3/4" CHWR

3/4" CHWS

1" CHWS

1" CHWR

3/4" CHWS

3/4" CHWR

3/4" D

FCU-11

FCU-20

FCU-63

3/4" CHWS

3/4" CHWR

3/4" D

FCU-14

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :0

A

M

M2.1

MECHANICAL HYDRONICS

- ALAMO HALL 521 - LEVEL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1/8" = 1'-0"M2.1

1 FIRST FLOOR PLAN - MECHANICAL HYDRONICS

TERMINATE FULLY INSULATED COPPER CONDENSATE AT MOP SINK WITH 1" AIR

GAP.

CONNECT FULLY INSUALTED COPPER CONDENSATE FULL SIZE OF OUTLET TO

UNIT. TRAP PER DETAIL 6/M5.1.

MECHANICAL KEYED NOTES:

1. PROVIDE CONDENSATE CLEANOUTS AT ALL CHANGE IN DIRECTIONS.

2. FIELD VERIFY EXISTING SITE CONDITIONS PRIOR TO START OF WORK.

MECHANICAL GENERAL NOTES:

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

A.2

A.2

C.4

C.4

B.3

B.3

D.5

D.5

E

E

F

F

I

I

J

J

L

L

M

M

N

N

400400

100100

200200

300300

G

G

H

H

A1.1

A1.1

O

O

2 2

3 3

4 4 B

B

C

C

A

A

D

D

16 16

MECH ROOM

ADA PATIENT

BED 6

ADA PATIENT

BED 5

PATIENT BED 3

PATIENT BED 2

PATIENT BED 7

NEW ELEVATOR

STAFF STATION

ELECT. ROOM

SECLUSION ANTE

ANTE ROOM T/R

SECLUSION

ROOM

ADA TLT /

SHWR 2

CLN

PATIENT BED 17

PAT TLT. 6

STOR.

EXAM ROOM

STOR.

PATIENT BED 1

PATIENT BED 4

PAT TLT. 2

STAFF

OBSERVATION

SOILED

PATIENT SHWR 2

ELOPEMENT

CONSULT 4

ADA PATIENT

BED 15

PAT TLT / TUB

SHWR 3

PATIENT BED 19

PATIENT BED 20

MECH. ROOM

PAT TLT. 5

MECH ROOM

PAT TLT

PATIENT

CORRIDOR

219 PATIENT

CORRIDOR

ADA TLT / SHWR

206 EVS

CLN

IDF ROOM

LAUNDRY

PATIENT BED 18

EXISTING STAIRS

INCENTIVE

THERAPY

STAIRS

ELEVATOR

PATIENT BED 16

PATIENT BED

PATIENT BED

PATIENT BED

PAT TLT. 3

PATIENT BED

PAT. TLT. 4

PATIENT BED

ADA PATIENT

BED 14

PATIENT

SHOWER 1

PAT TLT. 1

PATIENT BED

STOR.

STOR.

PATIENT

CORRIDOR

FCU-62

FCU-45

FCU-48

FCU-39

FCU-40

3/4" D

3/4" CHWR

3/4" D

3/4" CHWS

3/4" D

1" CHWS

1" CHWR

3/4" D

3/4" D

3/4" D

3/4" D

3/4" CHWS

3/4" CHWR

STAFF

RESTROOM

3/4" CHWR

3/4" CHWS

3/4" D 3/4" D

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M2.2

MECHANICAL HYDRONICS

- ALAMO HALL 521 - LEVEL

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

1/8" = 1'-0"M2.2

1 SECOND FLOOR PLAN - MECHANICAL HYDRONICS

CONNECT NEW CONDENSATE LINE TO EXISTING AT SAME LOCATION IT WAS

PREVIOUSLY INSTALLED.

CONNECT FULLY INSUALTED COPPER CONDENSATE FULL SIZE OF OUTLET TO

UNIT. TRAP PER DETAIL 6/M5.1.

CONDENSATE DOWN TO TAILPIECE OF SINK. COORDINATE WITH PLUMBING

CONTRACTOR PRIOR TO START OF WORK.

MECHANICAL KEYED NOTES:

1. PROVIDE CONDENSATE CLEANOUTS AT ALL CHANGE IN DIRECTIONS.

2. FIELD VERIFY EXISTING SITE CONDITIONS PRIOR TO START OF WORK.

MECHANICAL GENERAL NOTES:

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

AIR HANDLING UNIT SCHEDULE

MARK

LOCATION

TOTAL CFM

O.A. CFM (MIN-MAX)

EXT. S.P. *

AMBIENT TEMP. (F)

FAN

TYPE

DRIVE

SIZE

FAN RPM

AIR MODULATION

MAX FAN BHP

FAN MOTOR (MIN. HP/V/PH) / # OF FANS

COOLING COIL

TYPE / # COILS

CFM

ENT AIR (DB/WB)

LEAVING AIR (DB/WB)

MAX FACE VEL (FPM)

MAX AIR S.P.D. (IN. WATER)

GPM 44 F/10 TEMP. RISE

MAX WATER PD (FT)

ROWS/FINS (PER IN)

TOTAL OUTPUT (MIN. MBH)

SENS. OUTPUT (MIN. MBH)

ACCESS SECTION

SIZE (MIN.)

DOOR REQUIRED

HEATING COIL

TYPE / # COILS

CFM

ENT. AIR (F)

LEAVING AIR (DB)

MAX FACE VEL (FPM)

MAX AIR S.P.D. (IN. WATER)

GPM 140 F/20 TEMP. DROP

MAX WATER PD (FT)

ROWS/FINS (PER IN)

OUTPUT (MIN. MBh)

ACCESS SECTION

SIZE (MIN.)

DOOR REQUIRED

FILTER MIXING BOX

MIXING BOX TYPE

FILTER TYPE

MERV

UNIT WEIGHT (lbs.)

REFERENCE

NOTES

* EXTERNAL STATIC PRESSURE INCLUDES SYSTEM LOSSES AND 0.25" DIRTY FILTER ALLOWANCE AND

EXCLUDES LOSSES DUE TO ITEMS IN UNIT ITSELF (COILS, CASING,

DAMPERS, CLEAN FILTERS, ETC.)

NOTES:

1. BRANCH PIPE INCLUDES PIPING BETWEEN MAIN AND EQUIPMENT, UNLESS INDICATED OTHERWISE.

2. PROVIDE WITH REMOTE VFD TO BE MOUNTED ON WALL OF MECHANICAL ROOM.

3. UNIT TO BE SHIPPED IN SECTIONS AND BE FIELD INSTALLED.

4. PROVIDE UNIT WITH VERTICAL DISCHARGE.

5. UNIT TO BE MOUNTED ON EXISTING PAD.

6. PROVIDE WITH 3-WAY VALVE.

AHU-1

MECH ROOM

1.5

PLENUM

DIRECT

17.71

VFD

5.11

5.3 / 460 / 3 / 1

CW / 1

5,210

77.1 / 62.8

55 / 54

0.74

28.9

5.7

4 / 10

18"

YES

HW / 1

2,500

62.2

0.05

13.0

1 / 11

18"

YES

FILTER MIXING

2" PLEATED

MERV 13

2,336

CAH012GDCC

1-6

MARK

SA

SB

SC

SD

SE

RA

RB

EA

* AT MAX. CFM

KEYED NOTES (AIR DEVICE SCHEDULE):

1. FIELD INSULATE PLENUM BOX OR BACKSIDE OF DIFFUSER.

2. O.B.D. REQUIRED AT DUCTED EXHAUST LOCATION WHERE AIR

DEVICE IS USED IN A GYP. CEILING.

3. 24x24" MODULE SIZE FOR LAY-IN CEILING INSTALLATION.

4. FIXTURE TO BE ANTI LIGATURE RATED

MODEL

SG-SD

SG-SD

SG-SD

271FL

SG-SD

SG-SD

SG-SD

SG-SD

SIZE

12"x12"

24"x24"

24"x24"

14"x8"

12"x8"

12"x12"

24"x10"

12"x12"

THROW (@ 100 FPM)

8-FT

14-FT

20-FT

11-FT

15-FT

AIR DEVICE SCHEDULE

CFM RANGE

0-100

0-200

50-300

0-300

0-300

0-400

0-1000

0-400

INLET

6"Ø

8"Ø

10"Ø

12"x6"

10"x8"

10"x10"

22"x8"

10"x10"

GENERAL NOTES (AIR DEVICE SCHEDULE):

1. ALL AIR DEVICES TO BE WHITE FINISH UNLESS NOTED OTHERWISE.

2. REFER TO REFLECTED CEILING PLANS FOR CEILING TYPES. ALL AIR DEVICES MOUNTED IN A

DRYWALL CEILING SHALL HAVE A MOUNTING FRAME.

3. FOR 2-WAY DISCHARGE, THROWS LISTED REFLECT AIRFLOW IN A SINGLE DIRECTION.

4. P.D. ("WG) REFLECTS "TOTAL" PRESSURE (STATIC AND DYNAMIC).

5. REFER TO FLEX DUCT SCHEDULE FOR DUCT SIZES.

6. TRANSITION AS REQUIRED TO CONNECT DUCT TO AIR DEVICE.

# SLOTS

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

O.B.D. REQ'D. ?

NO

NO

NO

NO

NO

NOTE #2

NOTE #2

NOTE #2

P.D. ("WG) *

0.08

0.1

0.08

0.04

0.04

0.07

0.07

0.07

MAX. NC

REFERENCE

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

NOTES

1,4

1,4

1,4

1,4

2,4

2,4

2,4

SINGLE DUCT TERMINAL UNIT SCHEDULE

MARK

VAV-1-1

VAV-1-2

VAV-1-3

VAV-1-4

VAV-1-5

VAV-1-6

VAV-1-7

VAV-1-8

VAV-1-9

VAV-1-10

GENERAL NOTES (VAV BOX SCHEDULE):

1. ALL VAV BOXES SHALL HAVE T-STATS (SEE SPECS FOR CONTROL REQUIREMENTS).

2. MAX. PRESSURE DROP INCLUDES ELECTRIC HEATING COIL AND TERMINAL UNIT LOSSES.

3. INLET SIZE INDICATED IS AT BOX CONNECTION. PROVIDE MIN. OF 3 DUCT DIAMETERS OF STRAIGHT, RIGID, ROUND DUCT AHEAD OF CONNECTION.

4. FACTORY MOUNTED CONTROLS WITH MULTI-TAP STEP DOWN TRANSFORMER.

5. CONTROLS AND HEATING CONNECTIONS TO BE ON SAME HAND. REFERENCE DETAILS AND FLOOR PLAN.

MAX NC

DISCHARGE (.5" WG)

COOLING

CFM (MAX)

UNIT S.P. DROP

(MAX. "WG)

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

CASING

TYPE

INT. LINED

INT. LINED

INT. LINED

INT. LINED

INT. LINED

INT. LINED

INT. LINED

INT. LINED

INT. LINED

INT. LINED

INLET

SIZE (IN)

8ø

8ø

6ø

10ø

6ø

6ø

8ø

8ø

6ø

6ø

OUTLET SIZE

(APPROX)

12x10

12x10

12x8

14x12.5

12x8

12x8

12x10

12x10

12x8

12x8

REFERENCE

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

TITUS

MODEL

DESV

DESV

DESV

DESV

DESV

DESV

DESV

DESV

DESV

DESV

NOTES

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

1,2,3,4,5

DUCTLESS SPLIT SYSTEM SCHEDULE

MARK

SERVICE

TOTAL COOLING CAPACITY (MBH)

TOTAL HEATING CAPACITY (MBH)

SEER (AT ARI CONDITIONS)

REFRIGERANT

INDOOR UNIT

TYPE

COOLING EAT (DB/WB)

MAX AIRFLOW (CFM)

VOLTS / PHASE

MCA

MOCP

OUTDOOR UNIT

MARK

VOLTS / PHASE

MCA

MOCP

REFERENCE

MANUFACTURER INDOOR/OUTDOOR SECTION

INDOOR UNIT MODELNo.

OUTDOOR UNIT MODEL No.

NOTES

NOTES:

1. PROVIDE WITH CONDENSATE PUMP. CONDENSATE PUMP SHALL NOT REQUIRE AN ADDITIONAL ELECTRICAL CONNECTION.

2. MANUFACTURER TO SIZE REFRIGERANT LINES. LENGTH SHALL BE BASED ON DISTANCE

FROM INDOOR UNIT TO ROOF MOUNTED OUTDOOR UNIT.

3. PROVIDE MANUFACTURER'S STD. MOUNTING HARDWARE.

4. INDOOR UNIT TO BE POWERED BY OUTDOOR UNIT.

5. PROVIDE WITH MANUFACTURER'S STANDARD HAIL GUARD AND LOW AMBIENT KIT.

SS-1

IDF 126

24.0

19.0

R-410A

80 / 67

CU-1

208/1

13.4

DAIKIN

FTK24AXVJU

RK24AXVJU

1,2,3,4,5

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M3.1

MECHANICAL SCHEDULES

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

FAN SCHEDULE

MARK

EF-25

EF-4

EF-5

NOTES (FAN SCHEDULE):

1. PROVIDE MANUFACTURER'S STANDARD MOTOR-RATED SWITCH, 12-IN ROOF CURB WITH TRAY-MOUNTED GRAVITY BACKDRAFT DAMPER, AND BIRD SCREEN.

TYPE

DOWNBLAST

DOWNBLAST

DOWNBLAST

MANUFACTURER & MODEL

GREENHECK G-070-VG

GREENHECK G-090-VG

GREENHECK G-070-VG

SERVICE

ROOMS 232/233

NORTH SEIDEL

LOCKER ROOM

CFM

S.P. ("WG)

0.25

0.40

0.60

MAX. BHP

0.02

0.11

0.02

H.P.

0.07

0.17

0.07

V/PH

115/1

115/1

115/1

MAX. SONES

3.5

9.2

3.5

DRIVE

DIRECT

DIRECT

DIRECT

CONTROL

INTERLOCKED

INTERLOCKED

INTERLOCKED

NOTES

1,2

1,2

1,2

CHILLED WATER FAN COIL SCHEDULE

MARK

FCU-62

FCU-63

GENERAL NOTES (VAV BOX SCHEDULE):

1. PROVIDE FCU WITH THE FOLLOWING: COOLING COIL, DIRECT DRIVE FAN, AND 1" FILTER.

2. PROVIDE STAINLESS STEEL DRAIN PAN AND COIL CASING.

3. FCUS SHALL BE PROVIDED WITH 3/8" CLOSED CELL FOAM INSULATION.

4. PROVIDE FACTORY MOUNTED PIPING PACKAGE WITH 2 WAY POSITION CONTRL VALVE WITH FIXED FLOW CONTROL

5. 10.5" IS THE MAXIMUM ALLOWED HEIGHT FOR ALL FCUS

ENVIRO-TEC

MODEL

HLP

HLP

SIZE

SUPPLY AIR

(CFM)

OUTSIDE

AIR (CFM)

ESP

(IN W.C.)

0.32

0.34

SUPPLY AIR TEMP

(DEG, F, DB/WB)

55 / 54

55 / 54

RETURN AIR TEMP

(DEG, F, DB/WB)

75 / 68

75 / 68

FLOW

2.5

2.5

WPD

(FT HD)

4.1

4.1

HEAT TYPE

ELECTRIC

ELECTRIC

HEATING CAP

(KW)

1.5

VOLTAGE

(VOLT/PH)

277/1

277/1

EWT

(DEG F)

LWT

(DEG F)

54.3

MCA

(AMP)

5.14

7.4

MOCP

(AMP)

NOTES

ALL

ALL

ROOF HOOD SCHEDULE

MARK

RH-1

NOTES (RELIEF HOOD SCHEDULE):

1. PROVIDE WITH BIRDSCREEN AND MANUFACTURER'S STD. 18" ROOF CURB (GALVANIZED WITH NAILER).

2. PROVIDE DAMPER AND ACTUATOR ASSEMBLY IN ROOF CURB TRAY.

3. PROVIDE SECURITY BAR BARRIER WITH FRAME INSTALLED WITHIN ROOF CURB OPENING BELOW HOOD.

SERVES

AHU-1

THROAT SIZE

14"x18"

CFM

MAX. S.P. IN. H2O

0.05

DAMPER TYPE

MOTORIZED 24V

REFERENCE

FGI-14x18

WEIGHT

NOTES

1,2,3

EXISTING FAN COIL SCHEDULE - FOR REFERENCE ONLY

MARK

FCU-5

FCU-11

FCU-14

FCU-20

FCU-39

FCU-40

FCU-45

FCU-48

FCU-56

GENERAL NOTES (VAV BOX SCHEDULE):

1. VAV BOX IS EXISTING AND WILL ONLY BE RELOCATED. THIS SCHEDULE IS FOR REFERENCE ONLY.

ENVIRO-TEC

MODEL

HLP

HLP

HLP

HLP

HLP

HLP

HLP

HLP

HLP

SIZE

SUPPLY AIR

(CFM)

OUTSIDE

AIR (CFM)

ESP

(IN W.C.)

0.31

0.14

0.32

0.28

0.34

0.28

0.31

0.29

0.3

SUPPLY AIR TEMP

(DEG, F, DB/WB)

55 / 54

55 / 54

55 / 54

55 / 54

55 / 54

55 / 54

55 / 54

55 / 54

55 / 54

RETURN AIR TEMP

(DEG, F, DB/WB)

75 / 68

75 / 68

75 / 68

75 / 68

75 / 68

75 / 68

75 / 68

75 / 68

75 / 68

FLOW

3.5

2.5

2.5

WPD

(FT HD)

6.8

4.3

4.1

6.8

10.2

6.2

3.6

3.6

HEAT TYPE

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

HEATING CAP

(KW)

1.5

1.5

VOLTAGE

(VOLT/PH)

277/1

277/1

277/1

277/1

277/1

277/1

277/1

277/1

277/1

EWT

(DEG F)

LWT

(DEG F)

53.1

53.7

53.9

53.1

54.3

53.8

54.3

52.8

MCA

(AMP)

5.14

14.79

5.76

5.14

8.03

5.76

10.23

5.14

7.4

MOCP

(AMP)

NOTES

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M3.2

MECHANICAL SCHEDULES

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

M4.1

T

SA

AI - Zone Temp

AI - Zone Setpoint Adjust

BI - Zone Override

BO - Return Air Damper

T

N.C.

N.O.

M

M

T

AI - Mixed Air Temp

T

AI - Return Air Temp

AO - Cooling Valve AO - Heating Valve

OA

BO - Supply Fan Status

M

CT

SF

CHWS

CHWR

M

HWS

HWR

M

RA

AI - Heating Supply Air Temp

VARIABLE VOLUME AHU SCHEMATIC

NOT TO SCALE

GENERAL CONTROLS NOTES:

1. ALL SPACE SENSORS (UNLESS NOTED OTHERWISE) TO BE SENSOR TYPE

WITH MANUAL OVERRIDE BUTTON. SENSOR TO HAVE SLIDER ADJUSTMENT

(WARM-COOL) WITH SPACE TEMPERATURE INDICATION. SPACE SENSORS TO

HAVE 5 DEGREE DEADBAND.

2. ALL WIRING TO BE RUN IN A NEAT AND WORKMANLIKE MANNER, PARALLEL

AND PERPENDICULAR TO BUILDING LINES. WIRING TO BE RUN ON J-HOOKS

IN ACCESSIBLE LOCATIONS, IN CONDUIT IN EXPOSED LOCATIONS, ABOVE

GYP CEILINGS, AND BELOW 8 FOOT (ALL WIRING WITHIN WALLS TO BE RUN

IN CONDUIT).

3. ALL DAMPERS AND SENSORS ARE TO BE LOW VOLTAGE (24V) POWERED BY

DDC CONTRACTOR.

AI - Return Air Humidity

H

DEVICE

Fan

Temp/Humidity Sensors/Misc. Sensors

Current Sensing Relay

Motorized Valves - Body

Motorized Valves - Actuator

Dampers (O/A / Misc)

Damper Actuators (O/A / Misc)

SUPPLIED BY

AHU Manufacturer

Controls Subcontractor

Controls Subcontractor

Controls Subcontractor

Controls Subcontractor

Controls Subcontractor

RESPONSIBILITY MATRIX

INSTALLED BY

Mechanical Subcontractor

Controls Subcontractor

Controls Subcontractor

Mechanical Subcontractor

Controls Subcontractor

Controls Subcontractor

WIRING BY CONTROLS

DDC panel to starter or VFD

DDC panel to sensors

DDC panel to CSR

N/A

DDC panel to actuator

N/A

DDC Panel to Actuator

WIRING BY ELECTRICAL

Electrical panel to starter/VFD

N/A

N/A

N/A

N/A

N/A

N/A

Mechanical Subcontractor Mechanical Subcontractor

Dampers (R/A)

Duct Smoke Detector

AHU Manufacturer

Electrical Subcontractor

Mechanical Subcontractor

Electrical Subcontractor

N/A

N/A

N/A

Fire Alarm Panel to Device

HL

BI - Dirty Filter Switch

Pre-FilterBO - Outside Air Damper

T

BI - Freezestat

T

VFD

BO - Start/Stop

SS

AI - Supply Air Temp

HWCHW

REFER TO SCHEDULE

FOR 2-WAY OR

3-WAY VALVE

BI - Return Air Smoke Detector

FREEZE PROTECTION:

INTERLOCK FREEZESTAT WITH FAN STARTER / VFD. ALARM INPUT (DRY CONTACTS) TO DDC, FORCE CW CONTROL VALVE TO 50% OPEN, HOT WATER HEAT TO 100%. OPEN RETURN AIR DAMPER, CLOSE OUTSIDE AIR

DAMPER. MANUAL RESET AT FREEZESTAT.

BI - Duct Static Pressure (2/3 Longest Run)

AI - Outside Airflow

SINGLE ZONE UNIT

RUN CONDITIONS - SCHEDULED:

THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING

MODES:

OCCUPIED MODE: THE UNIT SHALL MAINTAIN

- A 72°F (ADJ.) COOLING SETPOINT

- A 70°F (ADJ.) HEATING SETPOINT.

UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN

- A 85°F (ADJ.) COOLING SETPOINT.

- A 55°F (ADJ.) HEATING SETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

- HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY

A USER DEFINABLE AMOUNT (ADJ.).

- LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A

USER DEFINABLE AMOUNT (ADJ.).

ZONE SETPOINT ADJUST:

THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING

SETPOINTS AT THE ZONE SENSOR.

ZONE OPTIMAL START:

THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM

SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING

COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.

ZONE UNOCCUPIED OVERRIDE:

A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE

AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE

EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE

SCHEDULE.

EMERGENCY SHUTDOWN:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY

SHUTDOWN SIGNAL.

SUPPLY/RETURN AIR SMOKE DETECTION:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN AIR SMOKE

DETECTOR STATUS.

SUPPLY FAN:

THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.)

MINIMUM RUNTIME.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

- SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

- SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

COOLING COIL VALVE:

THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND MAINTAIN SETPOINT RESET

BASED ON ZONE COOLING REQUIREMENTS. THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE

RESET BASED ON ZONE COOLING REQUIREMENTS AS FOLLOWS:

- THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F (ADJ.)

- AS COOLING DEMAND DECREASES THE SETPOINT SHALL INCREMENTALLY RESET UP TO A

MAXIMUM OF 60°F (ADJ.) (RETURN AIR HUMIDITY TO OVERRIDE TEMP RESET SCHEDULE)

THE COOLING SHALL BE ENABLED WHENEVER:

- OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).

- AND THE ZONE TEMPERATURE IS ABOVE COOLING SETPOINT.

- AND THE SUPPLY FAN STATUS IS ON.

- AND THE HEATING IS NOT ACTIVE.

THE COOLING COIL VALVE SHALL OPEN TO 50% (ADJ.) WHENEVER THE FREEZESTAT (IF PRESENT) IS

ON.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

- HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).

- LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).

HEATING COIL VALVE:

THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE HEATING COIL

VALVE TO MAINTAIN ITS HEATING SETPOINT.

THE HEATING SHALL BE ENABLED WHENEVER:

- SPACE HUMIDITY EXCEEDS 60%RH (ADJ.)

- OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).

- AND THE ZONE TEMPERATURE IS BELOW HEATING SETPOINT.

- AND THE SUPPLY FAN STATUS IS ON.

- AND THE COOLING IS NOT ACTIVE.

THE HEATING COIL VALVE SHALL OPEN WHENEVER THE FREEZESTAT (IF PRESENT) IS ON.

OUTSIDE AIR VENTILATION:

WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL OPEN THE OUTSIDE AIR DAMPER AND

MAINTAIN STATUS UNTIL MODE CHANGE. UPON ENTERING UNOCCUPIED MODE, THE OUTSIDE AIR

DAMPER SHALL FULLY CLOSE.

DEHUMIDIFICATION:

THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND OVERRIDE THE COOLING

SEQUENCE TO MAINTAIN RETURN AIR HUMIDITY AT OR BELOW 60% RH (ADJ.). DEHUMIDIFICATION

SHALL BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON.

RETURN AIR HUMIDITY:

THE CONTROLLER SHALL MONITOR THE RETURN AIR HUMIDITY AND USE AS REQUIRED FOR

HUMIDITY CONTROL.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

- HIGH RETURN AIR HUMIDITY: IF THE RETURN AIR HUMIDITY IS GREATER THAN 70% (ADJ.).

- LOW RETURN AIR HUMIDITY: IF THE RETURN AIR HUMIDITY IS LESS THAN 35% (ADJ.).

RETURN AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE RETURN AIR TEMPERATURE.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

- HIGH RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).

- LOW RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).

CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY

ADDITIONAL CONTROL PANELS, INCLUDING POWER

REQUIREMENTS AND SHALL COORDINATE WITH ELECTRICAL

CONTRACTOR.

Hardware Points Software Points

Point Name AI AO BI BO LOOP Sched Trend Alarm Show On Graphic

Mixed Air Temp

Return Air Humidity

Return Air Temp

Supply Air Temp

Return Air Damper

Outside Air Damper

Supply Fan Status

Supply Fan Start/Stop

Supply Air Temp Setpoint

High Supply Air Temp

Low Supply Air Temp

High Mixed Air Temp

Low Mixed Air Temp

High Return Air Humidity

High Return Air Temp

Dirty Filter Switch (Verify quantity with equipment)

Freeze Stat Temp

Heating Valve Actuator

Cooling Valve Actuator

Heating Supply Air Temp

Supply Air Smoke Detector

Zone Temperature

Zone Setpoint Adjust

Zone Override

BI - Supply Air Smoke Detector

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M4.1

MECHANICAL CONTROLS

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

M402

H L

BI - HIGH STATIC SHUTDOWN

DIRTY FILTER SWITCH (VERIFY QUANTITY WITH EQUIPMENT)

HIGH WATER CUT-OFF

BI - High water Cut-Off Switch

AO - Heating Modulation

Strip Heat

T

SA

AI - Zone Temp

AI - Zone Setpoint Adjust

BI - Zone Override

T

H

AI - Return Air Humidity

BI - Supply Air Smoke Detector

N.O.M

T

AI - Mixed Air Temp

T

AI - Return Air Temp

AO - Cooling Valve

OA

CHW

BI - Supply Fan Status

M

CT

VFD

BI - Supply Fan VFD Fault

BO - Supply Fan Start/Stop

SF

CHWS

CHWR

M

RA

AI - Supply Air Temp

Single Zone Unit

Run Conditions - Scheduled:

The unit shall run according to a user definable time schedule in the following modes:

· Occupied Mode: The unit shall maintain o A 72°F (adj.) cooling setpoint o A 70°F (adj.) heating setpoint.

· Unoccupied Mode (night setback): The unit shall maintain o A 85°F (adj.) cooling setpoint.

o A 55°F (adj.) heating setpoint.

Alarms shall be provided as follows:

· High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

· Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).

Zone Setpoint Adjust:

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

Zone Optimal Start:

The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.

Zone Unoccupied Override:

A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.

Emergency Shutdown:

The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.

Supply Air Smoke Detection:

The unit shall shut down and generate an alarm upon receiving a supply air smoke detector status.

Supply Fan:

The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties.

To prevent short cycling, the supply fan shall have a user definable (adj.) minimum runtime.

Alarms shall be provided as follows:

· Supply Fan Failure: Commanded on, but the status is off.

· Supply Fan in Hand: Commanded off, but the status is on.

· Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).

Zone Temperature Control:

The controller shall measure the zone temperature and shall modulate the supply fan speed to maintain zone temperature setpoint. The fan speed shall increase as the zone temperature rises above cooling setpoint, or as the zone temperature drops below heating setpoint. The supply fan shall not turn down to a speed lower than required ventilation amount.

Cooling Coil Valve:

The controller shall measure the zone temperature and modulate the cooling coil valve to maintain its cooling setpoint.

The cooling shall be enabled whenever:

· Outside air temperature is greater than 60°F (adj.).

· AND the economizer (if present) is disabled or fully open.

· AND the zone temperature is above cooling setpoint.

· AND the supply fan status is on.

· AND the heating is not active.

Electric Heating:

The controller shall measure the zone temperature and energize the electric heat to maintain its heating setpoint.

The heating shall be enabled whenever:

· Outside air temperature is less than 65°F (adj.).

· AND the zone temperature is below heating setpoint.

· AND the supply fan status is on.

· AND the cooling is not active.

Dehumidification:

When in the occupied mode, DDC shall monitor the return air humidity. Upon return humidity exceeding 60% (adj.), leaving supply air temperature to reset to 52° (adj.) Duct heater shall modulate to maintain zone temperature setpoint. Reset to return to normal LAT once return air

Mixed Air Temperature:

The controller shall monitor the mixed air temperature and use as required for economizer control (if present) or preheating control (if present).

Alarms shall be provided as follows:

· High Mixed Air Temp: If the mixed air temperature is greater than 90°F (adj.).

· Low Mixed Air Temp: If the mixed air temperature is less than 45°F (adj.).

Return Air Humidity:

The controller shall monitor the return air humidity and use as required for economizer control (if present) or humidity control (if present).

Alarms shall be provided as follows:

· High Return Air Humidity: If the return air humidity is greater than 70% (adj.).

· Low Return Air Humidity: If the return air humidity is less than 35% (adj.).

Return Air Temperature:

The controller shall monitor the return air temperature and use as required for economizer control (if present).

Alarms shall be provided as follows:

· High return air temp: if the return air temperature is greater than 90°f (adj.).

· Low return air temp: if the return air temperature is less than 45°f (adj.).

Supply Air Temperature:

the controller shall monitor the supply air temperature.

Alarms shall be provided as follows:

· High supply air temp: if the supply air temperature is greater than 120°f (adj.).

· Low supply air temp: if the supply air temperature is less than 45°f (adj.).

CHW CONSTANT AIR VOLUME FCU W/ ELECTRIC REHEAT - SCHEMATIC

NOT TO SCALE

ELEC

Hardware Points Software Points Point Name

AI AO BI BO LOOP Sched Trend Alarm Show On Graphic

MIXED AIR TEMP

RETURN AIR HUMIDITY

RETURN AIR TEMP

SUPPLY AIR TEMP

RETURN AIR DAMPER

OUTSIDE AIR DAMPER (Min. OA)

HIGH STATIC SHUTDOWN

SUPPLY FAN STATUS

SUPPLY FAN START/STOP

DEVICE

FAN

TEMP/HUMIDITY SENSORS/MISC. SENSORS

CURRENT SENSING RELAY

MOTORIZED VALVES - BODY

MOTORIZED VALVES - ACTUATOR

FREEZSTAT

DAMPERS (O/A / R/A)

DAMPER ACTUATORS (O/A / R/A)

OUTSIDE AIR AFMS

SUPPLIED BY

AHU MANUFACTURER

CONTROLS SUBCONTRACTOR

RESPONSIBILITY MATRIX

INSTALLED BY WIRING BY CONTROLS

DDC PANEL TO STARTER OR VFD

DDC PANEL TO SENSORS

DDC PANEL TO CSR

N/A

DDC PANEL TO SENSORS

STARTER AND DDC PANEL INTERLOCK

N/A

DDC PANEL TO ACTUATOR

DDC PANEL TO VAV

WIRING BY ELECTRICAL

ELECTRICAL PANEL TO STARTER/VFD

N/A

N/A

N/A

N/A

N/A

N/A

N/A

ELECTRICAL PANEL TO AFMS

FAN VFD MECHANICAL CONTRACTOR DDC PANEL TO VFD ELECTRICAL PANEL TO VFD/FAN

DUCT SMOKE DETECTOR ELECTRICAL CONTRACTOR N/A FIRE ALARM PANEL TO DEVICE

CW VALVE POSITION

CW VALVE MODULATE

OUTSIDE AIRFLOW

CONTROLS SUBCONTRACTOR

CONTROLS SUBCONTRACTOR

CONTROLS SUBCONTRACTOR

CONTROLS SUBCONTRACTOR

AHU MANUFACTURER

CONTROLS SUBCONTRACTOR

MECHANICAL CONTRACTOR

MECHANICAL CONTRACTOR

MECHANICAL CONTRACTOR

CONTROLS SUBCONTRACTOR

CONTROLS SUBCONTRACTOR

MECHANICAL CONTRACTOR

CONTROLS SUBCONTRACTOR

CONTROLS SUBCONTRACTOR

MECHANICAL CONTRACTOR

ELECTRICAL CONTRACTOR

CONTROLS SUBCONTRACTOR

MECHANICAL CONTRACTOR

SUPPLY AIR SMOKE DETECTOR

H AI - Zone Humidity

AI - Zone Setpoint

BI - Zone Override

CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY

ADDITIONAL CONTROL PANELS, INCLUDING POWER

REQUIREMENTS AND SHALL COORDINATE WITH ELECTRICAL

CONTRACTOR.

RH has returned to 50% (adj.).

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M4.2

MECHANICAL CONTROLS

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

M4.3

M4.3

M4.3

IDF/MDF RN COOLING

NOT TO SCALE

T AI - Zone Temp

AI - Zone Setpoint Adjust*

BI - Zone Override

DASA

AI - Airflow

AO - Zone Damper

M

SA

M

T AI - Zone Temp

Manufacturer's provided stat TRun Conditions - Interlocked:

The fans shall be interlocked (as referenced on exhaust fan schedule) to run whenever the roof top unit is scheduled unless shutdown on safeties.

Fan:

The fan shall have a user definable (adj.) minimum runtime.

Fan Status:

The controller shall monitor the fan status.

Alarms shall be provided as follows:

EA

BO - Fan Start/Stop

M

CT

BI - Fan Status

Fan Failure: Command on, but the status is off.

Fan In Hand: Command off, but the status is on.

M4.3

TYPICAL EXHAUST FAN SCHEMATIC (EF)

NOT TO SCALE

DEVICE

Room Temperature Sensors

Damper Actuator

Temp Sensor

Electric Heat Power

SUPPLIED BY

Controls Subcontractor

Controls Subcontractor

Controls Subcontractor

Electric Subcontractor

RESPONSIBILITY MATRIX

INSTALLED BY

Controls Subcontractor

Controls Subcontractor

Electric Subcontractor

WIRING BY CONTROLS

DDC Panel to Sensors

DDC Panel to Actuator

DDC Panel to Sensors

N/A

WIRING BY ELECTRICAL

Electrical to Rough-in Box

None

None

Velocity Sensor Air Terminal Manufacturer Mechanical Subcontractor None

Step-Down Transformer Air Terminal Manufacturer Mechanical Subcontractor Transformer to Devices Electrical Panel to Transformer

Controls Subcontractor

DDC Panel to Sensors

Electrical Panel to Air Terminal

VARIABLE AIR VOLUME - TERMINAL UNIT - ELECTRIC REHEAT

RUN CONDITIONS - SCHEDULED:

The unit shall run according to a user definable time schedule in the following modes:

- Occupied Mode: The unit shall maintain

- A 74°f (adj.) cooling setpoint

- A 70°f (adj.) heating setpoint.

- Unoccupied mode (night setback): the unit shall maintain

- A 85°f (adj.) cooling setpoint.

- A 55°f (adj.) heating setpoint.

Alarms shall be provided as follows:

- High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

- Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).

ZONE SETPOINT ADJUST:*

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

ZONE OPTIMAL START:

The unit shall use an optimal start algorithm for morning start-up. this algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.

ZONE UNOCCUPIED OVERRIDE:

A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for 1 hr (adj). At the expiration of this time, control of the unit shall automatically return to the schedule.

VARIABLE VOLUME TERMINAL UNIT - FLOW:

The unit shall maintain zone setpoints by controlling the airflow through one of the following:

Occupied:

- Unit's primary air damper shall remain fully closed until air handler's fan has started. At full cooling, primary air valve shall open to maximum flow (as scheduled) to maintain space cooling setpoint. As room temperature decreases, primary damper shall be modulated toward the closed position until air valves minimum air flow setpoint is reached.

Unoccupied:

- When the zone is unoccupied the zone damper shall control to its minimum scheduled cfm. If minimum and maximum cfm's are equal, air terminal to reduce to 50% airflow.

- When the zone temperature is greater than its cooling setpoint, the zone damper shall modulate between the minimum unoccupied airflow (adj.) and the maximum cooling airflow (adj.) until the zone is satisfied.

AIR TERMINAL SCHEMATIC

NOT TO SCALE (SINGLE DUCT - ELECTRIC REHEAT)

Split-System Air Conditioners:

Unit to run based on unit standard thermostat and controls. DDC temperature sensor to monitor space temperature and alarm if temperature exceeds 80°F (adj.).

INRUSH CURRENT LIMITING - ALAMO BUILDING4

A) BAS shall coordinate restarting of mechanical equipment on changeover from normal power to standby power to control momentary excessive power surges and to control air flow to avoid excessive pressure differential.

B) The BAS shall monitor the "normal power available" contact on the ATS. Upon loss of normal power for a duration of 2 second or longer, all equipment shall be commanded to stop by the BAS.

C) When emergency power is established, as indicated by ATS, and the generator is confirmed running for 15 seconds, BAS shall restart the system components based on the following prioritization. All equipment shall have a 10 second separation between starts.

1. Chilled Water Pumps.

2. Air Cooled Chiller

3. Air Handling Units

4. Fan Coil Units

5. Exhaust Fans

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M4.3

MECHANICAL CONTROLS

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

SIDE TAKE-OFF DETAILS

NOT TO SCALE

M5.1

ELBOW AND DUCT TAKE-OFF

NOT TO SCALE

M5.1

2 DUCT CROSS OVER DETAIL

NOT TO SCALE

M5.1

DUCT FLEXIBLE CONNECTION DETAILS

NOT TO SCALE

M5.1

DUCT TRANSITION DETAIL

NOT TO SCALE

M5.1

TYPICAL DRAIN TRAP DETAIL

NOT TO SCALE

M5.1

FLEX. DUCT (FLEXMASTER 8M OR

ENGINEER APPROVED EQUAL)

FLEX. DUCT (FLEXMASTER 8M OR

ENGINEER APPROVED EQUAL)

VOLUME DAMPER (MIN 18 GA BLADE) (BLADE

SHALL NOT EXTEND INTO TRUNK DUCT, IE NO

SCOOP)(FLEXMASTER MODEL STOD-B03 OR

APPROVED EQUAL)

CONICAL BELLMOUTH SIDE TAKE-OFF

BOOT SIDE TAKE-OFF

ALL SIDE TAKEOFF FITTINGS FOR AIR

DEVICES TO BE EITHER CONICAL

BELLMOUTH OR BOOT TYPE AS

SHOWN. IN APPLICATIONS WHERE

DUCT EDGE IS 1" OR LESS FROM

EDGE OF FITTING FLANGE, BOOT SIDE

TAKE OFF SHALL BE USED.

1-1/2" INSULATION

BUILD-OUT W/ LOCKING

HAND QUADRANT

VAPOR SEAL OUTER

SLEEVE TO DUCT

INSULATION.

1" OFFSET

REAR EDGE

FLEX. DUCT TO BE FULLY EXTENDED

W/ NO TURN LESS THAN A 2 DIA.

RADIUS.

LAP FLEX. DUCT INSULATION OVER DUCT BOOT, SEAL W/ MASTIC

AND SECURE WITH DUCT STRAP.

3/8" SQUARE AXLE IN NYLON BEARINGS

(FLEXMASTER-STOD OR STOCD)

INSULATED

DUCT

BOOT SIDE

TAKE-OFF TAP

FITTING

AIR

FLOW

(FLEXMASTER-SBMD)

LAP FLEX. DUCT INSULATION OVER DUCT

BOOT, SEAL W/ MASTIC AND SECURE WITH

DUCT STRAP.

3/8" SQUARE AXLE IN NYLON BEARINGS

ROLLED STIFFENER BEADS

FLEX. DUCT TO BE FULLY EXTENDED

W/ NO TURN LESS THAN A 2 DIA.

RADIUS.

VOLUME DAMPER (MIN 18 GA BLADE)

(BLADE SHALL NOT EXTEND INTO

TRUNK DUCT, IE NO SCOOP)

1-1/2" INSULATION BUILD-OUT W/

LOCKING HAND QUADRANT

VAPOR SEAL OUTER SLEEVE TO DUCT

INSULATION.

AIR

FLOW

INSULATED

DUCT

EXTENDED

CONICAL

TAP FITTING

ROLLED STIFFENER BEADS

HEAVY DUTY GALVANIZED

SUPPORT WIRE. SECURE TO

STRUCTURE.

4" GALVANIZED STEEL BAND

4" GALVANIZED STEEL BAND

HEAVY DUTY GALVANIZED

SUPPORT WIRE. SECURE TO

STRUCTURE.

SECURE FLEXIBLE DUCT TO TAP W/SS CLAMP AND

WORM SCREW FOR ADJUSTMENT. (FLEXMASTER LS)

SECURE FLEXIBLE DUCT TO TAP W/SS CLAMP AND

WORM SCREW FOR ADJUSTMENT. (FLEXMASTER LS)

W

W

TURNING VANES SHALL HAVE

TRAILING EDGES IF DUCT WIDTH

CHANGES AT THE ELBOW.

SINGLE BLADED TURNING VANES

AT ELBOWS OR 1.5 x C DIA.

RADIUS ELBOWS AS SHOWN ON

DRAWINGS.

INSULATION AS SPECIFIED OR

FIBROUS DUCT BOARD. (SEE

SPECS)

MAIN SUPPLY DUCT

VOLUME DAMPER

REQUIRED AT ALL

BRANCH TAKE-OFFS.

TO CEILING OR

SIDEWALL REGISTER

OR BRANCH DUCT.

1/4 x W BUT NO

LESS THAN 4"

INSULATION AS SPECIFIED OR

OR FIBROUS DUCT BOARD. (SEE

SPECS.)

MAIN SUPPLY

DUCT

AIR FLOW

NOTE:

BLANKET

INSULATION

AIR FLOW

SUPPLY AIR

DUCT

EXHAUST DUCT

AIR FLOW

DUCT-BOOT MOUNTED REGISTER

GALVANIZED DUCT

OPPOSED BLADE

FLEXIBLE MATERIAL AS

SPECIFIED

1-1/2" POCKET

SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1-1/2" MIN. TO 3" MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUT. MAX. 1/4"

SHEET METAL EDGE OFFSET.

1" FLANGE

BOLT ON 4" CENTERS

1"X1/8" BAND IRON

ALTERNATE POSITION OF BOLT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

SHEET METAL SCREWS ON

12" CENTERSDRAW BAND

1"x1/8"

RIVET ON 4"

CENTERS

DUCT

BOLT ON 4"

CENTERS

1-1/2" MIN. TO 3" MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUT. MAX. 1/4"

SHEET METAL EDGE OFFSET.

1-1/2" 1/2"1/2"

FLEXIBLE MATERIAL

AS SPECIFIED

FLANGED

CONNECTION

ON FAN SIDE

5/16"

FLANGE

TO BE INSTALLED AT ALL BUILDING EXPANSION JOINT LOCATIONS AND ALL HVAC UNIT

CONNECTIONS. CONTRACTOR IS RESPONSIBLE FOR LOCATION AND QUANTITY.

NOTE:

30° MAX

UNLESS OTHERWISE INDICATED ON

PLANS, MAXIMUM ANGLES SHOWN

ABOVE SHALL APPLY.

15° MAX

15° MAX

1"-2"

2"-3"

0"-1"

UNIT TOTAL STATIC PRESS.

2" 3"

2. LOCATE TRAP SO AS

TO BE ACCESSIBLE FOR

4"3"

CLEANING.

SEE SCHEDULE BELOW.

1. FOR DEPTH OF SEAL,

INSULATION

2" ba

1"

NOTES:

OPEN

DRAIN

DRAIN LINE SHALL BE AT LEAST THE SAME SIZE

AS THE NIPPLE OR OUTLET ON THE DRAIN PAN.

PROVIDE AT

EACH CHANGE

IN DIRECTION

(TYP.)

CLEANOUT

DRAIN

PITCH DOWN TOWARD

1" b a

PAN

DRAIN

C.O.

OPEN

UNION

UNION

3. ALL FITTING TO BE

DWV.

REFERENCE FINAL UNIT SUBMITTAL FOR UNIT

TOTAL STATIC PRESSURE.

3"-4" 5"4"

4"-5" 6"5"

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M5.1

MECHANICAL DETAILS

230905(m)

11/15/2024

Author

Checker

T E

X A

S S

T A

T E

H E

A L T

H A

N D

H U

M A

N S

E R

V

IC

E S

C O

M M

IS

S

IO

N

S

N

E W

B R

A U

N F

E L S

A V

E

S A

N A

N T

O N

IO

T E

X A

S

FINAL CONSTRUCTION DOCUMENTS

A

LA

M O

H A

LL

G

E R

IA

T

R

IC

M S

U R

E N

O V

A T

IO

N

S

Revision Schedule

No. Description Date

AUSTIN R. KACE

S

GS

IONAL EN

T

P R O F

E

S

T A

E

DICENSE

150421

E OF T

IN

E E

XA

S

A B C A B C

REFRIGERANT COIL PIPING DETAIL

NO SCALE

M5.2

AIR

SUPPLY

AIR

RETURN

CHWR

CHWS

DRAINCONDENSATE

OVERFLOW SWITCH

WITH RELAY

UNISTRUT

AIR HANDLER

AUXLIARY DRAIN PAN,

SUSPEND UNIT FROM

STRUCTURE W

ITH

ALL-THREAD AND

SPRING IS

OLATORS,

TYPICAL.

SUSPEND DRAIN PAN

FROM UNISTRUT W

ITH

APPROVED STRAP, T

YP.

MINIMUM 4" C

LEARANCE

AROUND AIR HANDLER,

ALL SIDES.

1/2" H

OSE BIB CONNECTION

DRAIN VALVE IN

PAN W

ITH

C W

S /H

W S

AIR FLOW

N.O.

N.C.

C W

R /H

W R

(TYP)

TEMPERATURE GAUGE

WALL MOUNTED MINISPLIT

NOT TO SCALE

M5.2

PIPING THRU WALL ABOVE GRADE

NOT TO SCALE

M5.2

4 PIPE OR CONDUIT DUCT THRU ROOF

NOT TO SCALE

M5.2

CHILLED OR HOT WATER COIL PIPING SCHEMATIC

NOT TO SCALE

M5.2

FLUSH MTD. MOTOR - RATED

DISCONNECT SWITCH

INSULATED REFRIGERANT

LINE IN WALLFLUSH MTD. MOTOR - RATED

DISCONNECT SWITCH

ELECTRICAL

IN WALL

T T

48" AFF

OPTIONAL CHOICE FOR

REFRIGERANT CONNECTION

LOCATION

INSULATED RS/RL

LINES IN WALL

(CEILING IF

APPLICABLE)

120V POWER FROM

CONDENSING UNIT.

COORDINATE REQUIREMENTS

WITH MANUFACTURER.

CONTROL CABLE TO BE

ROUTED WITH POWER

INTEGRAL COND. PUMP

(POWERED FROM UNIT)

BUILT IN CHECK VALVE

INSULATED COPPER

PUMPED CONDENSATE

DRAIN LINE IN WALL

DDC T-STAT FOR MONITORING

PURPOSES ONLY

MANUFACTURERS

STANDARD T-STAT

STUD PROTECTION

PLATES TO PROTECT

REFRIGERANT PIPE

PIPING CONNECTION TO UNIT

TO BE FULLY CONCEALED

BEHIND UNIT

A B

C

A

B

0" TO 3/8"

PIPE SLEEVE

SEALANT

PIPE

MATERIAL

BACK UP

PIPE

PIPE

SLEEVE

3/8"

ON INSULATION PER

AND RECOMMENDATIONS

OUTDOOR WEATHER RESISTANT

COATING SHALL BE APPLIED

MANUFACTURER'S PROCEDURES

3/8"

0" TO 1/4"

INSULATION

SEALANT

BACK UP

MATERIAL

PIPE/CONDUIT

SHEET METAL

FLASHING

COMPOUND

WATERPROOF

ENCLOSURE

18 GA. GALVANIZED

PIPE

BUILT-UP ROOFING

SEE FLOOR PLAN FOR

CONTINUATION OF PIPING

GASKET AROUND

STEEL ANGLE

JOIST

INSULATION

FLASHING TREATED WOOD

SECURE PIPE

COUNTER

BOARD

RIGID

TO STRUCTURE

NOTE:

DIAGRAM SHOWN FOR INFORMATION

PURPOSES, REFER TO ROOFING

CONSULTANT DETAILS

KEYED NOTES:

NOTE:

FULLY ACCESSIBLE.

MAINS ARE LOCATED BELOW COIL.

GIVEN FOR C , AND SHALL BE INSTALLED IN RETURN LINE.

AUTOMATIC AIR VENT PIPED TO FLOOR DRAIN. PROVIDE WHEN

2-WAY MODULATING VALVE IS REQUIRED WHEN NO VALUE IS

BALL OR BUTTERFLY ISOLATION VALVE DEPENDING ON SIZE.

1. THERMOMETER WELL AND PETES PLUG TO BE INSTALLED

FOR SIZES AND NOTES.

SEE COIL PIPING SIZE SCHEDULE

NOTE:

WELL (TYP)

DDC SENSOR

TEST PORT (TYP)

PRESSURE/TEMP

CONNECTION & CAP

3/4" HOSE DRAIN

BYPASS VALVE (BALANCING PURPOSE) BALL OR BUTTERFLY VALVE

DEPENDING ON SIZE. VALVE TO HAVE MEMORY STOP.

WYE STRAINER WITH 3/4"

HOSE DRAIN AND CAP

UNION (TYP)

CALIBRATED BALANCING

VALVE (RE:SCHEDULE FOR

GPM)

FULLY SIZE TEMPORARY BYPASS FOR FLUSHING

PURPOSES. REMOVE AFTER FLUSH COMPLETE. AHU

COIL/VALVE ASSEMBLY TO BE COMPLETELY ISOLATED

DURING FLUSH.

COILS

MARK

NO.

CHILL H20

SIZE SCHEDULE

FCU-62

FCU-63

3/4" 3/4" 1/2"

COILS

HOT H20

PLUGS PROVIDED WITH OTHER APPURTENANCES.

2. P/T PLUGS INDICATED ARE TO BE INDEPENDENT OF ANY

3/4" 3/4" 1/2"

AHU-1 2" 2" 1-1/2" 1-1/2 1-1/2 1-1/4"

JOB NO:

DATE:

DRAWN BY:

CHECKED BY:

2023 CHESNEY MORALES PARTNERS, INC.

ALL RIGHTS RESERVED. NO PART OF THIS

DOCUMENT MAY BE REPRODUCED OR UTILIZED

IN ANY FORM WITHOUT PRIOR WRITTEN AUTHORIZATION

OF CHESNEY MORALES PARTNERS, INC.

C

SHEET

P R

O J E

C T

N U

M B

E R

-2

-S

A H

A T

S A

N A

N T

O N

IO

S

T A

T E

H O

S P

IT

A

L

/1 /2

:3 :1

A

M

M5.2

ME…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .