ES-Plan_Sheets.pdf

PDF 4 MB Posted

Attached to
General Aviation Terminal Building
Solicitation number
25-011P
Issued by
Flagler County, Florida

About this file

The provided document is a set of electrical systems plan sheets (ES000-ES401) prepared by Joseph Lawrence & Co. Space Coast Consulting Engineers for a new General Aviation Terminal Building project at Flagler Executive Airport in Florida. The electrical systems drawings comprehensively detail the design for security, communications, access control, and infrastructure systems, including floor plans, one-line diagrams, riser diagrams, and detailed installation specifications across two building floors. The plans cover multiple technical systems, including IP CCTV, intrusion detection, network infrastructure, door access controls, and comprehensive cabling and conduit routing.

The electrical design incorporates sophisticated technology infrastructure, with specific provisions for communication rooms, service entrance conduits, ground busbar systems, and extensive networking equipment placement. Key design elements include multiple communication rooms (COMM 134 and COMM 116), provisions for local exchange carrier and facility communication services, cable trays, plywood backboards, and integrated systems for video management, access control, and security monitoring. The design emphasizes compliance with national electrical codes, proper grounding and bonding practices, and detailed specifications for cable installation, conduit routing, and equipment mounting. The plans demonstrate a comprehensive approach to technological infrastructure that supports the functional requirements of a modern general aviation terminal facility.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ES000

vo ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

1. ALL CONDUIT ABOVE GRADE SHALL BE NMC OR EMT, ALL CONDUIT BELOW

GRADE SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.

2. PRODUCTS SHALL BE RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO

BE INSTALLED.

3. WORKING CLEARANCES AROUND ELECTRICAL EQUIPMENT SHALL BE

MAINTAINED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE

ARTICLE 110, COORDINATE EQUIPMENT INSTALLATION TO MAINTAIN

REQUIRED CLEARANCES.

4. IF AN OUTLET BOX IS REQUIRED TO BE LOCATED IN AN ASSEMBLY OR

PARTITION RATED AS 'FIRE / SMOKE' OR 'SMOKE' OR IDENTIFIED AS EITHER

'FIRE / SMOKE' OR 'SMOKE' THEN ALL OF THE FOLLOWING CONDITIONS SHALL

BE MET:

4.1. THE OUTLET BOX SHALL BE METALLIC.

4.2. THE OUTLET BOX OPENINGS SHALL OCCUR ONLY ON ONE SIDE OF THE

FRAMING SPACE.

4.3. THE OUTLET BOX OPENINGS SHALL NOT EXCEED 16 SQUARE INCHES.

4.4. ALL CLEARANCES BETWEEN THE OUTLET BOX AND THE WALL BOARD

MATERIAL SHALL BE COMPLETELY SEALED WITH APPROVED MATERIALS

IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS FOR

THE PROJECT.

4.5. PROVIDE A SUPPLEMENTAL BARRIER AROUND OUTLETS LARGER THAN

16 INCHES SO THAT THE ORIGINAL RATING OF THE PENETRATION IS

MAINTAINED.

4.6. THE TOTAL AGGREGATE SURFACE AREA OF ALL PENETRATIONS SHALL

NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.

4.7. THE OUTLET BOX SHALL BE SEPARATED FROM OPENINGS ON THE

OPPOSITE SIDE OF THE RATED PARTITION BY A MINIMUM HORIZONTAL

DISTANCE OF 24 INCHES.

4.8. THE ANNULAR SPACE SHALL NOT EXCEED 1/8" INCH BETWEEN THE

EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.

5. THE OUTLET BOX SHALL BE SECURELY FASTENED TO A PARTITION FRAMING

MEMBER BY MEANS OF AN APPROVED ATTACHMENT METHOD.

6. LOCATIONS OF EQUIPMENT SHOWN ON THE DRAWINGS ARE APPROXIMATE.

COORDINATE EXACT EQUIPMENT LOCATION AND CONNECTION

REQUIREMENTS IN THE FIELD PRIOR TO INSTALLATION.

7. FOR EXACT LOCATION OF CEILING MOUNTED EQUIPMENT REFER TO THE

ARCHITECTURAL REFLECTED CEILING PLAN. LOCATIONS OF EQUIPMENT NOT

INCLUDED ON THE REFLECTED CEILING PLAN SHALL BE COORDINATED WITH

THOSE ITEMS SHOWN. COORDINATION OF CEILING MOUNTED EQUIPMENT

SHALL BE DONE PRIOR TO ANY ROUGH-IN. NOTIFY ENGINEER OF ANY

DISCREPANCY.

8. PROVIDE FINAL CONNECTIONS TO OWNER PROVIDED EQUIPMENT WHERE

INDICATED ON THE DRAWINGS AND SPECIFICATIONS.

9. PRIOR TO ROUGH-IN AND INSTALLATION OF ANY FLOOR MOUNTED DEVICE,

VERIFY LOCATION WITH THE OWNER AND ARCHITECT.

10. VERIFY AND COORDINATE THE LOCATION OF REQUIRED DIVISION 28 OUTLETS

WITH OTHER TRADE DRAWINGS AND OWNER PROVIDED EQUIPMENT.

11. EACH TELEVISION OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG

OUTLET BOX WITH A SINGLE GANG PLASTER RING AND (1) ONE INCH CONDUIT

STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING OR

TO AN ACCESSIBLE CABLE TRAY WHERE PROVIDED.

12. THE DESIGNATION 'N.I.C.' SHALL DENOTE ITEMS WHICH ARE 'NOT IN

CONTRACT'.

13. THE DESIGNATION 'U.S.C.' SHALL DENOTE ITEMS WHICH ARE 'UNDER

SEPARATE CONTRACT'.

14. THE DESIGNATION 'F.B.O.' SHALL DENOTE ITEMS WHICH ARE 'FURNISHED BY

OTHERS'.

15. THE DESIGNATION 'O.F.E.' SHALL DENOTE ITEMS WHICH ARE 'OWNER

FURNISHED EQUIPMENT'.

16. ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE

DIVISION 27 AND 28 EQUIPMENT SHALL BE PROVIDED UNDER THIS CONTRACT.

PROVIDE COORDINATION FOR THE INSTALLATION OF THIS RACEWAY WITH

THE ELECTRICAL CONTRACTOR.

17. THE SYMBOL LEGENDS SHOWN ON THIS SHEET ARE ALL INCLUSIVE,

SYMBOLS INCLUDED IN THE LEGEND MAY OR MAY NOT BE USED FOR THIS

PROJECT.

18. THE FLOOR MOUNTED VOICE / DATA OUTLET SHALL HAVE A SINGLE GANG

SPACE WITHIN THE FLOOR BOX AND A (1) 1" CONDUIT CONCEALED IN SLAB

THAT IS STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED

CEILING OR TO AN ACCESSIBLE CABLE TRAY WHERE PROVIDED. RACEWAY

INSTALLATION BY ELECTRICAL CONTRACTOR.

19. ALL BONDING AND GROUNDING ELEMENTS UTILIZED FOR THE TECHNOLOGY

SYSTEM CABLING SYSTEM SHALL BE IN COMPLIANCE WITH SPECIFICATIONS.

20. PROVIDE ALL SLEEVES AS REQUIRED FOR ALL LOW VOLTAGE CABLE

PATHWAYS. RESTORE THE FIRE RATING OF THE SURFACE, ONCE SLEEVES

ARE INSTALLED. SLEEVE ASSEMBLIES SHALL BE LISTED FOR THE MEDIUM

BEING PENETRATED.

21. CABLE UNDER SLAB SHALL USE INDOOR / OUTDOOR JACKET.

22. ALL REQUIRED JUNCTION BOXES ARE NOT SHOWN ON FLOOR PLANS.

PROVIDE JUNCTION BOXES AS REQUIRED PER SPECIFICATIONS.

23. ALL RACEWAYS SHOWN ON THESE DRAWINGS ARE ONLY FOR TECHNOLOGY

SYSTEMS. FOR ELECTRICAL RACEWAYS, SEE ELECTRICAL DRAWINGS.

GENERAL SYSTEM NOTES

1. ALL DOUBLE DOORS ARE TO RECEIVE (1) DOOR POSITION SWITCH ON EACH

DOOR LEAF AND SHALL REPORT AS ONE ALARM POINT.

2. ALL 120V POWER WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT.

3. ALL CONDUIT ABOVE GRADE SHALL BE METALLIC, ALL CONDUIT BELOW

GRADE SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.

4. ALL CARD READERS AND KEYPADS DEDICATED FOR ELEVATOR FLOOR

CONTROL ARE SHOWN INSIDE THE ELEVATOR CAB ON THE LOWEST LEVEL

FLOOR PLAN TO WHICH THE ELEVATOR TRAVELS.

5. ALL CONDUIT, WIRING AND ASSOCIATED BACK BOXES SHALL BE FULLY

CONCEALED WITHIN WALLS, FLOORS AND CEILINGS.

6. INSTALLATION OF BALANCE TWISTED PAIR CABLE SHALL BE IN ACCORDANCE

WITH SPECIFICATION SECTION 271000 GUIDELINES, CABLE INSTALLATION AND

TERMINATIONS THAT DO NOT COMPLY SHALL BE REPLACED BY THE

CONTRACTOR AT NO ADDITIONAL COST.

6.1. THE MAXIMUM PULLING TENSION SHALL NOT EXCEED 25 POUNDS TO

AVOID STRETCHING THE CONDUCTORS.

6.2. THE MINIMUM BEND RADIUS OF THE CABLE SHALL NOT BE LESS THAN

FOUR TIMES THE OUTSIDE DIAMETER OF THE CABLE.

6.3. THE CABLE SHALL BE INSTALLED WITHOUT KINKS OR TWISTS. THE

APPLICATION OF CABLE TIES SHALL NOT DEFORM THE CABLE BUNDLE.

6.4. STRIP BACK ONLY AS MUCH CABLE JACKET AS REQUIRED TO TERMINATE

THE CABLE. CABLE PAIRS SHALL NOT BE UNTWISTED MORE THAN 1/2".

7. INSTALLATION OF FIBER OPTIC CABLES SHALL BE IN ACCORDANCE WITH

SPECIFICATION SECTION 271000. CABLE INSTALLATION AND TERMINATIONS

THAT DO NOT COMPLY SHALL BE REPLACED BY THE CONTRACTOR AT NO

ADDITIONAL COST.

7.1. THE BEND RADIUS FOR HORIZONTAL FIBER OPTIC CABLE SHALL NOT BE

LESS THAN 1 INCH UNDER NO-LOAD CONDITIONS. WHEN UNDER A

MAXIMUM TENSILE LOAD OF 50 LBF, THE BEND RADIUS SHALL NOT BE

LESS THAN 2 INCHES.

7.2. THE BEND RADIUS FOR INTRABUILDING OPTICAL FIBER BACKBONE

SHALL NOT BE LESS THAN THAT RECOMMENDED BY THE

MANUFACTURER IF NO RECOMMENDATION IS KNOWN, THEN THE

APPLIED BEND RADIUS SHALL NOT BE LESS THAN 10 TIMES THE CABLE

OUTSIDE DIAMETER UNDER NO-LOAD CONDITIONS AND NOT LESS THAN

15 TIMES THE CABLE OUTSIDE DIAMETER WHEN THE CABLE IS UNDER

TENSILE LOAD.

8. COORDINATE LOCATION OF ALL FIRE RATED PENETRATIONS PRIOR TO

PROCEEDING WITH INSTALLATION. ALL PENETRATIONS THROUGH FIRE

RATED BARRIERS SHALL BE COMPLETELY SEALED WITH A LISTED FIRE STOP

SYSTEM IN ACCORDANCE WITH NFPA AND THE AUTHORITY HAVING

JURISDICTION.

9. THE DESIGNATION 'D.H.C.' SHALL DENOTE ITEMS WHICH ARE 'DOOR

HARDWARE CONTRACTOR'.

SECURITY SYSTEM NOTESBASIC MATERIALS

DESCRIPTIONSYMBOL

JUNCTION BOX (LABEL COVER WITH PERMANENT MARKER.

BOX WITH NO NUMBER IS NOT REFERENCED FROM OTHER

SHEETS)

JUNCTION BOX - FLOOR MOUNTED

JUNCTION BOX - PEDESTAL MOUNTED

PB IN-GROUND PULLBOX

CONDUIT CONCEALED ABOVE CEILING OR IN WALL.

ALL CONDUITS ARE 1" UNLESS OTHERWISE LABELED

CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER

FLOOR. ALL CONDUITS ARE 1" UNLESS OTHERWISE NOTED

CONDUIT EXPOSED

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT STUB

CONDUIT CONTINUED

SLEEVE TURNING UP

SLEEVE TURNING DOWN

CABLE TRAY

WALL PENETRATION CONDUIT SLEEVE

SECURITY CAMERA POLE. POLE TO MATCH UTILITY PACKAGE

SPECIFICATIONS FOR LIGHTING POLES IN THE SAME AREA

DATA SYSTEM

DESCRIPTIONSYMBOL

COMMUNICATIONS OUTLET, MOUNTED AT RECEPTACLE HEIGHT

UNLESS OTHERWISE NOTED. MODULE AND FACEPLATE

DESCRIPTIONS AS INDICATED IN THE SPECIFICATIONS.

N = NUMBER OF 8P8C OUTLETS

X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE

WALL TELEPHONE OUTLET FOR WALL PHONE.

MOUNTED AT 48" ABOVE FINISHED FLOOR TO CENTER

CEILING MOUNTED WIRELESS ACCESS POINT OUTLET.

X = MOUNTING (F)LUSH, (S)URFACE, (C)EILING

N = NUMBER OF 8P8C JACKS.

TELEPHONE OUTLET IN ELEVATOR MACHINE ROOM.

(S)URFACE MOUNTED.

COMBINED VOICE / DATA, AUDIO / VIDEO AND POWER OUTLETS

IN FLOOR BOX. POWER RECEPTACLE IS SHOWN FOR

REFERENCE ONLY. CONDUIT, BOX AND POWER RECEPTACLE

PROVIDED BY DIV. 26. REFER TO DETAILS FOR FLOOR BOX

CONFIGURATION.

Y = NUMBER OF 8P8C JACKS

X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE

DIRECTIONAL MOTION DETECTOR

CR

KP

SECURITY SYSTEM

DESCRIPTIONSYMBOL

KEYPAD

CARD READER

MD

X

ALARM SIREN

WP: WEATHERPROOF

X

S

WP

ELECTRO MAGNETIC LOCK

ELECTRIC STRIKE FRAME

DOOR / WINDOW CONTACT

ES

DC

360° MOTION DETECTOR

FIXED CCTV CAMERA

x = 1, 2, 3....CAMERA TYPE

PAN / TILT / ZOOM CCTV CAMERA

x = 1, 2, 3....CAMERA TYPE

SECURITY PANEL

KEY SWITCH

REMOTE DOOR RELEASE BUTTON

DURESS BUTTON

X = TYPE

INTERCOM MASTER STATION

X = 1, 2, 3....TYPE

INTERCOM SUB-STATION

REQUEST TO EXIT MOTION SENSOR

PERSONAL COMPUTER WORKSTATION

REQUEST TO EXIT PUSH-BUTTON

CARD READER / KEYPAD

BIOMETRIC READER

ELECTRIC LOCK

DELAYED EGRESS LOCK

MD

CK

BR

ML

DE

SEC

KS

RR

IS

RS

RB

PC

D X

IM X

LADDER TRAY

TP

'X' DENOTES USE (P-PAGING OR S-SECURITY)

'Y' DENOTES FLOOR

'Z' DENOTES NUMBER

JJ X,Y,Z

JJ

JJ

X,N

W

S2

SYS

WAP

XN

X, Y, Z

ADAPTER, (P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH,

(PD) PEDESTAL, (L)FLOOR

ADAPTER, (P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH, (PD)

PEDESTAL, (L)FLOOR

Z = TYPE

EL

NEW TERMINAL BUILDING

AIRCRAFT PARKING

COMM.

COMM.

ES001

vo ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

GENERAL NOTES:

A. REFER TO SPECIFICATION.

B. REFER TO GENERAL NOTES.

C. DO NOT SCALE ELECTRICAL DRAWING FOR ANY DIMENSIONS.

D. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL

CODES.

E. PROVIDE GROUNDING AND BONDING PER NEC 250.

F. FIELD VERIFY EXACT LOCATION OF ALL CONDUITS AND COORDINATE WITH CIVIL PLANS PRIOR

TO ROUGH IN.

N

PLAN NORTH

KEY NOTES:

1. LOCAL EXCHANGE CARRIER SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN FOR

CONDUIT SIZE AND QUANTITY.

2. CATV PROVIDER SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN FOR CONDUIT SIZE

AND QUANTITY.

3. FACILITY COMMUNICATIONS CONDUITS. REFER TO FLOOR PLAN FOR CONDUIT SIZE AND

QUANTITY. STUB CONDUIT 5' OUT OF BUILDING.

4. COMMUNICATIONS CONDUITS BETWEEN COMMUNICATIONS ROOM. REFER TO FLOOR PLAN

FOR CONDUIT SIZE.

5. SPARE CONDUIT. REFER TO FLOOR PLAN FOR CONDUIT SIZE AND QUANTITY. STUB CONDUIT 5'

OUT OF BUILDING.

6. CAP AND MARK LOCATIONS OF CONDUITS.

N

E

S

W

L2 L2

WAP

C2

F2

F2

F2

F2

F2

F2

F2

F2

F2 F2

F2

F2

WAP

C2

WAP

C2

F2

F2 F2

WAP

F2

WAP

F2

F1

W

WAP

C2

WAP

C2

WAP

C2

WAP

C2

WAP

C2

WAP

C2

F2

F2

F2

TVTVF2 L2 L2F2

F2

F2

F1

F1

F2

L2 L2

F2

L2F2

F2

F2

F2

F2F2

F2

F2

CR DC

EL

DC EL

CR

CR DC

ELCR

CR

CR

DC EL DC EL

CR

DC EL DC EL

CR

DC EL

CR

DC EL

CR

DC EL

CR

CR

DC EL DC EL

OFFICE

FILE ROOM

CONFERENCE

ROOM

ASSISTANT TO

DIRECTOR

STAFF OFFICE

VENDING

DIRECTOR

ELECTRICAL

CLOSET

SERVING

AREA

EXECUTIVE

CONF. RM.

RECEPTION

LOBBY

FBO OFFICE

OPS OFFICE

BREAK RM

COMM

FUTURE TENANT

FUTURE TENANT

CREW LINE

COVERED

CANOPY

101A

1160 SF

PORTE

COCHERE

FUTURE TENANT

PERSONAL

BRK. RM.

PERSONAL

BRK. RM.

CREW LOUNGE

FLIGHT

PLANNING

MECH.

PERSONAL

BRK. RM.

CORR.

STOR.

JAN.

RESTROOM

117D

RESTROOM

117A 117B

117C

ELECT.

OFFICE

RESTROOM

124A CLOSET

124B

JAN.

RESTROOM

RESTROOM

CLOSET

CONTR.

LULA LIFT

101B

CORR.

CORR.

JAN.

MEN'S

WOMEN'S

MECHANICAL

COMM

FIRE R.

VEST

COVERED

CANOPY

CA-02

CA-09

CA-10CA-08

CA-11

CA-07

CA-06

CA-03 CA-14

CA-13

CA-21CA-12

CA-19

CA-05 CA-18

CA-04 CA-17

CA-16

CA-20

CA-15

CA-01

25 26 26

MDMDMD

MD

MD

KP

PC

TYP.

TV

L2

L2

L2

L2

MDMD

DCDCDC

W

DC

DC

DC

DC

F2

S

W P

ES101

KP

MD

TYP.

TYP.

MD

TYP.

CR

MD

MD

MDMD

DC

DC

DC

DC

TV 20

TYP.

MD

DC

ES101

TV

TV

TV

TV

F2

F2

F2 F2 F2

TV

F2F2

TV

TV

TV

TV

F2

F2 F2

F2

TV

F2

F2

F2 S2

TV

S2

COMM

5 16

SE

C

AC

S

COMM

SE

C

AC

S

12 18

ES101

vo ic e

7.

0.

w w w

.k m ad g.

ne t

AA

N

PLAN NORTH

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

A. REFER TO SPECIFICATION.

B. REFER TO GENERAL NOTES.

C. DO NOT SCALE ELECTRICAL DRAWINGS FOR ANY DIMENSIONS.

D. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL

CODES.

E. PROVIDE GROUNDING AND BONDING PER NEC 250.

F. FIELD VERIFY EXACT LOCATION OF ALL DEVICES AND EQUIPMENT PRIOR TO ROUGH IN.

KEY NOTES:

GENERAL NOTES:

1. 3

4" X 4' X 8' CLASS A/B RESISTANT PLYWOOD TERMINATION BACKBOARD. COAT BACKBOARD

WITH GRAY CLASS A FLAME SPREAD, FIRE RETARDANT PAINT. INSTALL BACKBOARD ON WALLS

AS INDICATED ON PLAN. BACKBOARD SHALL BE INSTALLED 4" AFF.

2. MAIN SYSTEMS GROUND BUSBAR WITH #2/0 IN 1" CONDUIT TO 120 VOLT POWER SOURCE

GROUND.

3. SYSTEMS GROUND BUSBAR WITH #2/0 IN 1" CONDUIT TO MAIN SYSTEMS GROUND BUSBAR.

4. OVERHEAD 12" LADDER CABLE TRAY. BOND TO SYSTEMS GROUND BUSBAR.

5. COMMUNICATIONS 2 POST OPEN RACK. LOCATE VIDEO MANAGEMENT SERVER, ACCESS

CONTROL SERVER AND SECURITY NETWORK SWITCHES IN THIS COMMUNICATIONS RACK.

BOND TO SYSTEMS GROUND BUSBAR.

6. COMMUNICATIONS 2 POST OPEN RACK. LOCATE VIDEO AND SECURITY NETWORK SWITCHES IN

THIS COMMUNICATIONS RACK. BOND TO SYSTEMS GROUND BUSBAR.

7. ACCESS CONTROL SYSTEM (ACS) POWER SUPPLY AND DOOR CONTROLLER CABINET.

8. (2) 2" RIGID CONDUITS TO ROOF WITH GOOSE NECK AT ROOF TOP. BOND TO SYSTEMS GROUND

BUSBAR.

9. (2) 4" COMMUNICATIONS SERVICE ENTRANCE CONDUITS TO SERVICE ENTRANCE. COORDINATE

WITH SITE UTILITIES FOR ADDITIONAL INFORMATION. CONDUITS SHALL HAVE MINIMUM 36"

SWEEPS. BOND TO SYSTEMS GROUND BUSBAR.

10. (3) 2" CONDUITS TO COMM. ROOM 118.

11. (2) 4" COMMUNICATIONS CONDUIT SLEEVES FOR VOICE DATA CABLES. BOND TO SYSTEMS

GROUND BUSBAR.

12. (3) 2" CONDUITS FROM COMM. ROOM 134.

13. (1) 4" CONDUIT FOR FACILITY COMMUNICATIONS. COORDINATE WITH SITE UTILITIES FOR

ADDITIONAL INFORMATION. CONDUITS SHALL HAVE MINIMUM 36" SWEEPS. BOND TO SYSTEMS

GROUND BUSBAR.

14. (1) 3" CONDUIT FOR CATV SERVICE ENTRANCE CONDUITS TO SERVICE ENTRANCE.

COORDINATE WITH SITE UTILITIES FOR ADDITIONAL INFORMATION. CONDUITS SHALL HAVE

MINIMUM 36" SWEEPS. BOND TO SYSTEMS GROUND BUSBAR.

15. INTRUSION SECURITY SYSTEM CONTROL PANEL AND POWER SUPPLY.

16. OWNER PROVIDER COMMUNICATIONS RACK.

17. ACCESS CONTROL REMOTE CONTROL PANEL AND POWER SUPPLY.

18. INTRUSION SECURITY SYSTEM REMOTE CONTROL PANEL AND POWER SUPPLY.

19. SECURITY SYSTEMS DEDICATED WORKSTATION COMPUTER. COMPUTER SHALL INTEGRATE

WITH VIDEO MANAGEMENT SOFTWARE AND ACCESS CONTROL SYSTEM. PROVIDE DEDICATED

COMMUNICATIONS OUTLET WITH (2) GREEN CAT 6 PLENUM CABLE TO COMM. ROOM 134.

20. PROVIDE WALL MOUNTED TV OUTLET ADJACENT TO 120VAC DUPLEX RECEPTACLE.

COORDINATE MOUNTING HEIGHT WITH ELECTRICAL AND ARCHITECT DRAWINGS PRIOR TO

ROUGH IN. PROVIDE (1) CAT 6 UTP PLENUM RATED CABLE AND (1) RG-6 COAX PLENUM RATED

CABLE TO NEAREST COMM. ROOM.

21. WALL MOUNTED DATA OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO NEAREST COMM.

ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END WITH CAT 6

HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND TESTED. REFER TO

SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.

22. FLOOR BOX MOUNTED DATA OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO NEAREST

COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END WITH CAT

6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND TESTED. REFER

TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.

23. CEILING MOUNTED WIRELESS ACCESS POINT OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6

CABLES TO NEAREST COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT

EACH END WITH CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED

AND TESTED. REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.

24. WALL MOUNTED WIRELESS ACCESS POINT. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO

NEAREST COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END

WITH CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND

TESTED. REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.

25. WALL MOUNTED CAMERA ABOVE COVERED CANOPY AT APPROXIMATELY 15' AFF. COORDINATE

PRIOR TO ROUGH IN.

26. CEILING MOUNT CAMERA UNDER COVERED AREA. COORDINATE PRIOR TO ROUGH IN.

27. WALL MOUNT CAMERA AT APPROXIMATELY 15' AFF. COORDINATE PRIOR TO ROUGH IN.

N

E

S

W

OBSERV.MEZZ.

LULA LIFT

201A

CLOSET

F2

WAP

F2

F2

OBSERV. DECK

CA-22

DC

TYP.

DC

TV

TV

ES102

vo ic e

7.

0.

w w w

.k m ad g.

ne t

AA

N

PLAN NORTH

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

LAWRENCE M. STOFF

P.E. #78586

A. REFER TO SPECIFICATION.

B. REFER TO GENERAL NOTES.

C. DO NOT SCALE ELECTRICAL DRAWINGS FOR ANY DIMENSIONS.

D. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL

CODES.

E. PROVIDE GROUNDING AND BONDING PER NEC 250.

F. FIELD VERIFY EXACT LOCATION OF ALL DEVICES AND EQUIPMENT PRIOR TO ROUGH IN.

KEY NOTES:

GENERAL NOTES:

1. WALL MOUNTED DATA OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO NEAREST

COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END WITH

CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND TESTED.

REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.

2. WALL MOUNTED WIRELESS ACCESS POINT OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6

CABLES TO NEAREST COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED

AT EACH END WITH CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE

LABELED AND TESTED. REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.

ES200

ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

LAN/WAN

COMPOSITE

ACCESS CONTROL

CABLE (TYP.)

CAT 6 PATCH

CORD (TYP.)

RS485

ES201

ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

ETH

ER

N

ET N

ETW

O

R K

ES202

ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

ES203

ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

COMMUNICATION RISER DIAGRAM

1. REFER TO SHEET ES000 FOR SYMBOL LEGEND.

2. REFER TO SHEET ES000 FOR GENERAL NOTES.

3. REFER TO PROJECT MANUAL.

4. INSTALL BUSHINGS TO ALL RACEWAY TERMINATIONS.

GENERAL NOTES

REFERENCE NOTES

1. PLYWOOD BACKBOARD. REFER TO SPECIFICATIONS AND FLOOR PLANS FOR ADDITIONAL

REQUIREMENTS.

2. CABLE TRAY. INSTALL ABOVE EQUIPMENT RACKS AND/OR CABINETS. REFER TO FLOOR

PLANS FOR LAYOUT.

3. LOCAL EXCHANGE CARRIER SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN

FOR CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE PRIOR

TO ROUGH IN.

4. FACILITY COMMUNICATIONS SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN

FOR CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE PRIOR

TO ROUGH IN.

5. CATV PROVIDER SERVICE ENTRANCE CONDUITS. REFER TO SITE PLAN FOR CONDUIT

SIZE, QUANTITY AND CABLE REQUIREMENTS. COORDINATE PRIOR TO ROUGH IN.

6. COMMUNICATIONS CONDUITS BETWEEN COMMUNICATIONS ROOM. REFER TO FLOOR

PLAN FOR CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE

PRIOR TO ROUGH IN.

7. SPARE CONDUIT STUB OUT AND CAP 5' OUT OF BUILDING. COORDINATE PRIOR TO

ROUGH IN.

8. COMMUNICATIONS CONDUIT SLEEVES FOR VOICE DATA CABLES.

9. CONDUITS TO ROOF WITH GOOSE NECK AT ROOF TOP. REFER TO FLOOR PLAN FOR

CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE PRIOR TO

ROUGH IN.

SLAB

ROOF

COMM. 134 COMM. 118

8 8

2 2

1 1

ES400

ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

ES401

ic e

7.

0.

w w w

.k m ad g.

ne t

AA

JL

C&O

Joseph, Lawrence & Co

Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com

CA No. 28730

Space Coast

BLAKE LAWRENCE SUDDETH

P.E. #69060

File details come from the government source that posted it. Updated .