ES-Plan_Sheets.pdf
PDF 4 MB Posted
- Attached to
- General Aviation Terminal Building
- Solicitation number
- 25-011P
- Issued by
- Flagler County, Florida
About this file
The provided document is a set of electrical systems plan sheets (ES000-ES401) prepared by Joseph Lawrence & Co. Space Coast Consulting Engineers for a new General Aviation Terminal Building project at Flagler Executive Airport in Florida. The electrical systems drawings comprehensively detail the design for security, communications, access control, and infrastructure systems, including floor plans, one-line diagrams, riser diagrams, and detailed installation specifications across two building floors. The plans cover multiple technical systems, including IP CCTV, intrusion detection, network infrastructure, door access controls, and comprehensive cabling and conduit routing.
The electrical design incorporates sophisticated technology infrastructure, with specific provisions for communication rooms, service entrance conduits, ground busbar systems, and extensive networking equipment placement. Key design elements include multiple communication rooms (COMM 134 and COMM 116), provisions for local exchange carrier and facility communication services, cable trays, plywood backboards, and integrated systems for video management, access control, and security monitoring. The design emphasizes compliance with national electrical codes, proper grounding and bonding practices, and detailed specifications for cable installation, conduit routing, and equipment mounting. The plans demonstrate a comprehensive approach to technological infrastructure that supports the functional requirements of a modern general aviation terminal facility.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ES000
vo ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
1. ALL CONDUIT ABOVE GRADE SHALL BE NMC OR EMT, ALL CONDUIT BELOW
GRADE SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.
2. PRODUCTS SHALL BE RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO
BE INSTALLED.
3. WORKING CLEARANCES AROUND ELECTRICAL EQUIPMENT SHALL BE
MAINTAINED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE
ARTICLE 110, COORDINATE EQUIPMENT INSTALLATION TO MAINTAIN
REQUIRED CLEARANCES.
4. IF AN OUTLET BOX IS REQUIRED TO BE LOCATED IN AN ASSEMBLY OR
PARTITION RATED AS 'FIRE / SMOKE' OR 'SMOKE' OR IDENTIFIED AS EITHER
'FIRE / SMOKE' OR 'SMOKE' THEN ALL OF THE FOLLOWING CONDITIONS SHALL
BE MET:
4.1. THE OUTLET BOX SHALL BE METALLIC.
4.2. THE OUTLET BOX OPENINGS SHALL OCCUR ONLY ON ONE SIDE OF THE
FRAMING SPACE.
4.3. THE OUTLET BOX OPENINGS SHALL NOT EXCEED 16 SQUARE INCHES.
4.4. ALL CLEARANCES BETWEEN THE OUTLET BOX AND THE WALL BOARD
MATERIAL SHALL BE COMPLETELY SEALED WITH APPROVED MATERIALS
IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS FOR
THE PROJECT.
4.5. PROVIDE A SUPPLEMENTAL BARRIER AROUND OUTLETS LARGER THAN
16 INCHES SO THAT THE ORIGINAL RATING OF THE PENETRATION IS
MAINTAINED.
4.6. THE TOTAL AGGREGATE SURFACE AREA OF ALL PENETRATIONS SHALL
NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.
4.7. THE OUTLET BOX SHALL BE SEPARATED FROM OPENINGS ON THE
OPPOSITE SIDE OF THE RATED PARTITION BY A MINIMUM HORIZONTAL
DISTANCE OF 24 INCHES.
4.8. THE ANNULAR SPACE SHALL NOT EXCEED 1/8" INCH BETWEEN THE
EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
5. THE OUTLET BOX SHALL BE SECURELY FASTENED TO A PARTITION FRAMING
MEMBER BY MEANS OF AN APPROVED ATTACHMENT METHOD.
6. LOCATIONS OF EQUIPMENT SHOWN ON THE DRAWINGS ARE APPROXIMATE.
COORDINATE EXACT EQUIPMENT LOCATION AND CONNECTION
REQUIREMENTS IN THE FIELD PRIOR TO INSTALLATION.
7. FOR EXACT LOCATION OF CEILING MOUNTED EQUIPMENT REFER TO THE
ARCHITECTURAL REFLECTED CEILING PLAN. LOCATIONS OF EQUIPMENT NOT
INCLUDED ON THE REFLECTED CEILING PLAN SHALL BE COORDINATED WITH
THOSE ITEMS SHOWN. COORDINATION OF CEILING MOUNTED EQUIPMENT
SHALL BE DONE PRIOR TO ANY ROUGH-IN. NOTIFY ENGINEER OF ANY
DISCREPANCY.
8. PROVIDE FINAL CONNECTIONS TO OWNER PROVIDED EQUIPMENT WHERE
INDICATED ON THE DRAWINGS AND SPECIFICATIONS.
9. PRIOR TO ROUGH-IN AND INSTALLATION OF ANY FLOOR MOUNTED DEVICE,
VERIFY LOCATION WITH THE OWNER AND ARCHITECT.
10. VERIFY AND COORDINATE THE LOCATION OF REQUIRED DIVISION 28 OUTLETS
WITH OTHER TRADE DRAWINGS AND OWNER PROVIDED EQUIPMENT.
11. EACH TELEVISION OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG
OUTLET BOX WITH A SINGLE GANG PLASTER RING AND (1) ONE INCH CONDUIT
STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING OR
TO AN ACCESSIBLE CABLE TRAY WHERE PROVIDED.
12. THE DESIGNATION 'N.I.C.' SHALL DENOTE ITEMS WHICH ARE 'NOT IN
CONTRACT'.
13. THE DESIGNATION 'U.S.C.' SHALL DENOTE ITEMS WHICH ARE 'UNDER
SEPARATE CONTRACT'.
14. THE DESIGNATION 'F.B.O.' SHALL DENOTE ITEMS WHICH ARE 'FURNISHED BY
OTHERS'.
15. THE DESIGNATION 'O.F.E.' SHALL DENOTE ITEMS WHICH ARE 'OWNER
FURNISHED EQUIPMENT'.
16. ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE
DIVISION 27 AND 28 EQUIPMENT SHALL BE PROVIDED UNDER THIS CONTRACT.
PROVIDE COORDINATION FOR THE INSTALLATION OF THIS RACEWAY WITH
THE ELECTRICAL CONTRACTOR.
17. THE SYMBOL LEGENDS SHOWN ON THIS SHEET ARE ALL INCLUSIVE,
SYMBOLS INCLUDED IN THE LEGEND MAY OR MAY NOT BE USED FOR THIS
PROJECT.
18. THE FLOOR MOUNTED VOICE / DATA OUTLET SHALL HAVE A SINGLE GANG
SPACE WITHIN THE FLOOR BOX AND A (1) 1" CONDUIT CONCEALED IN SLAB
THAT IS STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED
CEILING OR TO AN ACCESSIBLE CABLE TRAY WHERE PROVIDED. RACEWAY
INSTALLATION BY ELECTRICAL CONTRACTOR.
19. ALL BONDING AND GROUNDING ELEMENTS UTILIZED FOR THE TECHNOLOGY
SYSTEM CABLING SYSTEM SHALL BE IN COMPLIANCE WITH SPECIFICATIONS.
20. PROVIDE ALL SLEEVES AS REQUIRED FOR ALL LOW VOLTAGE CABLE
PATHWAYS. RESTORE THE FIRE RATING OF THE SURFACE, ONCE SLEEVES
ARE INSTALLED. SLEEVE ASSEMBLIES SHALL BE LISTED FOR THE MEDIUM
BEING PENETRATED.
21. CABLE UNDER SLAB SHALL USE INDOOR / OUTDOOR JACKET.
22. ALL REQUIRED JUNCTION BOXES ARE NOT SHOWN ON FLOOR PLANS.
PROVIDE JUNCTION BOXES AS REQUIRED PER SPECIFICATIONS.
23. ALL RACEWAYS SHOWN ON THESE DRAWINGS ARE ONLY FOR TECHNOLOGY
SYSTEMS. FOR ELECTRICAL RACEWAYS, SEE ELECTRICAL DRAWINGS.
GENERAL SYSTEM NOTES
1. ALL DOUBLE DOORS ARE TO RECEIVE (1) DOOR POSITION SWITCH ON EACH
DOOR LEAF AND SHALL REPORT AS ONE ALARM POINT.
2. ALL 120V POWER WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT.
3. ALL CONDUIT ABOVE GRADE SHALL BE METALLIC, ALL CONDUIT BELOW
GRADE SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.
4. ALL CARD READERS AND KEYPADS DEDICATED FOR ELEVATOR FLOOR
CONTROL ARE SHOWN INSIDE THE ELEVATOR CAB ON THE LOWEST LEVEL
FLOOR PLAN TO WHICH THE ELEVATOR TRAVELS.
5. ALL CONDUIT, WIRING AND ASSOCIATED BACK BOXES SHALL BE FULLY
CONCEALED WITHIN WALLS, FLOORS AND CEILINGS.
6. INSTALLATION OF BALANCE TWISTED PAIR CABLE SHALL BE IN ACCORDANCE
WITH SPECIFICATION SECTION 271000 GUIDELINES, CABLE INSTALLATION AND
TERMINATIONS THAT DO NOT COMPLY SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST.
6.1. THE MAXIMUM PULLING TENSION SHALL NOT EXCEED 25 POUNDS TO
AVOID STRETCHING THE CONDUCTORS.
6.2. THE MINIMUM BEND RADIUS OF THE CABLE SHALL NOT BE LESS THAN
FOUR TIMES THE OUTSIDE DIAMETER OF THE CABLE.
6.3. THE CABLE SHALL BE INSTALLED WITHOUT KINKS OR TWISTS. THE
APPLICATION OF CABLE TIES SHALL NOT DEFORM THE CABLE BUNDLE.
6.4. STRIP BACK ONLY AS MUCH CABLE JACKET AS REQUIRED TO TERMINATE
THE CABLE. CABLE PAIRS SHALL NOT BE UNTWISTED MORE THAN 1/2".
7. INSTALLATION OF FIBER OPTIC CABLES SHALL BE IN ACCORDANCE WITH
SPECIFICATION SECTION 271000. CABLE INSTALLATION AND TERMINATIONS
THAT DO NOT COMPLY SHALL BE REPLACED BY THE CONTRACTOR AT NO
ADDITIONAL COST.
7.1. THE BEND RADIUS FOR HORIZONTAL FIBER OPTIC CABLE SHALL NOT BE
LESS THAN 1 INCH UNDER NO-LOAD CONDITIONS. WHEN UNDER A
MAXIMUM TENSILE LOAD OF 50 LBF, THE BEND RADIUS SHALL NOT BE
LESS THAN 2 INCHES.
7.2. THE BEND RADIUS FOR INTRABUILDING OPTICAL FIBER BACKBONE
SHALL NOT BE LESS THAN THAT RECOMMENDED BY THE
MANUFACTURER IF NO RECOMMENDATION IS KNOWN, THEN THE
APPLIED BEND RADIUS SHALL NOT BE LESS THAN 10 TIMES THE CABLE
OUTSIDE DIAMETER UNDER NO-LOAD CONDITIONS AND NOT LESS THAN
15 TIMES THE CABLE OUTSIDE DIAMETER WHEN THE CABLE IS UNDER
TENSILE LOAD.
8. COORDINATE LOCATION OF ALL FIRE RATED PENETRATIONS PRIOR TO
PROCEEDING WITH INSTALLATION. ALL PENETRATIONS THROUGH FIRE
RATED BARRIERS SHALL BE COMPLETELY SEALED WITH A LISTED FIRE STOP
SYSTEM IN ACCORDANCE WITH NFPA AND THE AUTHORITY HAVING
JURISDICTION.
9. THE DESIGNATION 'D.H.C.' SHALL DENOTE ITEMS WHICH ARE 'DOOR
HARDWARE CONTRACTOR'.
SECURITY SYSTEM NOTESBASIC MATERIALS
DESCRIPTIONSYMBOL
JUNCTION BOX (LABEL COVER WITH PERMANENT MARKER.
BOX WITH NO NUMBER IS NOT REFERENCED FROM OTHER
SHEETS)
JUNCTION BOX - FLOOR MOUNTED
JUNCTION BOX - PEDESTAL MOUNTED
PB IN-GROUND PULLBOX
CONDUIT CONCEALED ABOVE CEILING OR IN WALL.
ALL CONDUITS ARE 1" UNLESS OTHERWISE LABELED
CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER
FLOOR. ALL CONDUITS ARE 1" UNLESS OTHERWISE NOTED
CONDUIT EXPOSED
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT STUB
CONDUIT CONTINUED
SLEEVE TURNING UP
SLEEVE TURNING DOWN
CABLE TRAY
WALL PENETRATION CONDUIT SLEEVE
SECURITY CAMERA POLE. POLE TO MATCH UTILITY PACKAGE
SPECIFICATIONS FOR LIGHTING POLES IN THE SAME AREA
DATA SYSTEM
DESCRIPTIONSYMBOL
COMMUNICATIONS OUTLET, MOUNTED AT RECEPTACLE HEIGHT
UNLESS OTHERWISE NOTED. MODULE AND FACEPLATE
DESCRIPTIONS AS INDICATED IN THE SPECIFICATIONS.
N = NUMBER OF 8P8C OUTLETS
X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE
WALL TELEPHONE OUTLET FOR WALL PHONE.
MOUNTED AT 48" ABOVE FINISHED FLOOR TO CENTER
CEILING MOUNTED WIRELESS ACCESS POINT OUTLET.
X = MOUNTING (F)LUSH, (S)URFACE, (C)EILING
N = NUMBER OF 8P8C JACKS.
TELEPHONE OUTLET IN ELEVATOR MACHINE ROOM.
(S)URFACE MOUNTED.
COMBINED VOICE / DATA, AUDIO / VIDEO AND POWER OUTLETS
IN FLOOR BOX. POWER RECEPTACLE IS SHOWN FOR
REFERENCE ONLY. CONDUIT, BOX AND POWER RECEPTACLE
PROVIDED BY DIV. 26. REFER TO DETAILS FOR FLOOR BOX
CONFIGURATION.
Y = NUMBER OF 8P8C JACKS
X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE
DIRECTIONAL MOTION DETECTOR
CR
KP
SECURITY SYSTEM
DESCRIPTIONSYMBOL
KEYPAD
CARD READER
MD
X
ALARM SIREN
WP: WEATHERPROOF
X
S
WP
ELECTRO MAGNETIC LOCK
ELECTRIC STRIKE FRAME
DOOR / WINDOW CONTACT
ES
DC
360° MOTION DETECTOR
FIXED CCTV CAMERA
x = 1, 2, 3....CAMERA TYPE
PAN / TILT / ZOOM CCTV CAMERA
x = 1, 2, 3....CAMERA TYPE
SECURITY PANEL
KEY SWITCH
REMOTE DOOR RELEASE BUTTON
DURESS BUTTON
X = TYPE
INTERCOM MASTER STATION
X = 1, 2, 3....TYPE
INTERCOM SUB-STATION
REQUEST TO EXIT MOTION SENSOR
PERSONAL COMPUTER WORKSTATION
REQUEST TO EXIT PUSH-BUTTON
CARD READER / KEYPAD
BIOMETRIC READER
ELECTRIC LOCK
DELAYED EGRESS LOCK
MD
CK
BR
ML
DE
SEC
KS
RR
IS
RS
RB
PC
D X
IM X
LADDER TRAY
TP
'X' DENOTES USE (P-PAGING OR S-SECURITY)
'Y' DENOTES FLOOR
'Z' DENOTES NUMBER
JJ X,Y,Z
JJ
JJ
X,N
W
S2
SYS
WAP
XN
X, Y, Z
ADAPTER, (P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH,
(PD) PEDESTAL, (L)FLOOR
ADAPTER, (P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH, (PD)
PEDESTAL, (L)FLOOR
Z = TYPE
EL
NEW TERMINAL BUILDING
AIRCRAFT PARKING
COMM.
COMM.
ES001
vo ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
GENERAL NOTES:
A. REFER TO SPECIFICATION.
B. REFER TO GENERAL NOTES.
C. DO NOT SCALE ELECTRICAL DRAWING FOR ANY DIMENSIONS.
D. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL
CODES.
E. PROVIDE GROUNDING AND BONDING PER NEC 250.
F. FIELD VERIFY EXACT LOCATION OF ALL CONDUITS AND COORDINATE WITH CIVIL PLANS PRIOR
TO ROUGH IN.
N
PLAN NORTH
KEY NOTES:
1. LOCAL EXCHANGE CARRIER SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN FOR
CONDUIT SIZE AND QUANTITY.
2. CATV PROVIDER SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN FOR CONDUIT SIZE
AND QUANTITY.
3. FACILITY COMMUNICATIONS CONDUITS. REFER TO FLOOR PLAN FOR CONDUIT SIZE AND
QUANTITY. STUB CONDUIT 5' OUT OF BUILDING.
4. COMMUNICATIONS CONDUITS BETWEEN COMMUNICATIONS ROOM. REFER TO FLOOR PLAN
FOR CONDUIT SIZE.
5. SPARE CONDUIT. REFER TO FLOOR PLAN FOR CONDUIT SIZE AND QUANTITY. STUB CONDUIT 5'
OUT OF BUILDING.
6. CAP AND MARK LOCATIONS OF CONDUITS.
N
E
S
W
L2 L2
WAP
C2
F2
F2
F2
F2
F2
F2
F2
F2
F2 F2
F2
F2
WAP
C2
WAP
C2
F2
F2 F2
WAP
F2
WAP
F2
F1
W
WAP
C2
WAP
C2
WAP
C2
WAP
C2
WAP
C2
WAP
C2
F2
F2
F2
TVTVF2 L2 L2F2
F2
F2
F1
F1
F2
L2 L2
F2
L2F2
F2
F2
F2
F2F2
F2
F2
CR DC
EL
DC EL
CR
CR DC
ELCR
CR
CR
DC EL DC EL
CR
DC EL DC EL
CR
DC EL
CR
DC EL
CR
DC EL
CR
CR
DC EL DC EL
OFFICE
FILE ROOM
CONFERENCE
ROOM
ASSISTANT TO
DIRECTOR
STAFF OFFICE
VENDING
DIRECTOR
ELECTRICAL
CLOSET
SERVING
AREA
EXECUTIVE
CONF. RM.
RECEPTION
LOBBY
FBO OFFICE
OPS OFFICE
BREAK RM
COMM
FUTURE TENANT
FUTURE TENANT
CREW LINE
COVERED
CANOPY
101A
1160 SF
PORTE
COCHERE
FUTURE TENANT
PERSONAL
BRK. RM.
PERSONAL
BRK. RM.
CREW LOUNGE
FLIGHT
PLANNING
MECH.
PERSONAL
BRK. RM.
CORR.
STOR.
JAN.
RESTROOM
117D
RESTROOM
117A 117B
117C
ELECT.
OFFICE
RESTROOM
124A CLOSET
124B
JAN.
RESTROOM
RESTROOM
CLOSET
CONTR.
LULA LIFT
101B
CORR.
CORR.
JAN.
MEN'S
WOMEN'S
MECHANICAL
COMM
FIRE R.
VEST
COVERED
CANOPY
CA-02
CA-09
CA-10CA-08
CA-11
CA-07
CA-06
CA-03 CA-14
CA-13
CA-21CA-12
CA-19
CA-05 CA-18
CA-04 CA-17
CA-16
CA-20
CA-15
CA-01
25 26 26
MDMDMD
MD
MD
KP
PC
TYP.
TV
L2
L2
L2
L2
MDMD
DCDCDC
W
DC
DC
DC
DC
F2
S
W P
ES101
KP
MD
TYP.
TYP.
MD
TYP.
CR
MD
MD
MDMD
DC
DC
DC
DC
TV 20
TYP.
MD
DC
ES101
TV
TV
TV
TV
F2
F2
F2 F2 F2
TV
F2F2
TV
TV
TV
TV
F2
F2 F2
F2
TV
F2
F2
F2 S2
TV
S2
COMM
5 16
SE
C
AC
S
COMM
SE
C
AC
S
12 18
ES101
vo ic e
7.
0.
w w w
.k m ad g.
ne t
AA
N
PLAN NORTH
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
A. REFER TO SPECIFICATION.
B. REFER TO GENERAL NOTES.
C. DO NOT SCALE ELECTRICAL DRAWINGS FOR ANY DIMENSIONS.
D. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL
CODES.
E. PROVIDE GROUNDING AND BONDING PER NEC 250.
F. FIELD VERIFY EXACT LOCATION OF ALL DEVICES AND EQUIPMENT PRIOR TO ROUGH IN.
KEY NOTES:
GENERAL NOTES:
1. 3
4" X 4' X 8' CLASS A/B RESISTANT PLYWOOD TERMINATION BACKBOARD. COAT BACKBOARD
WITH GRAY CLASS A FLAME SPREAD, FIRE RETARDANT PAINT. INSTALL BACKBOARD ON WALLS
AS INDICATED ON PLAN. BACKBOARD SHALL BE INSTALLED 4" AFF.
2. MAIN SYSTEMS GROUND BUSBAR WITH #2/0 IN 1" CONDUIT TO 120 VOLT POWER SOURCE
GROUND.
3. SYSTEMS GROUND BUSBAR WITH #2/0 IN 1" CONDUIT TO MAIN SYSTEMS GROUND BUSBAR.
4. OVERHEAD 12" LADDER CABLE TRAY. BOND TO SYSTEMS GROUND BUSBAR.
5. COMMUNICATIONS 2 POST OPEN RACK. LOCATE VIDEO MANAGEMENT SERVER, ACCESS
CONTROL SERVER AND SECURITY NETWORK SWITCHES IN THIS COMMUNICATIONS RACK.
BOND TO SYSTEMS GROUND BUSBAR.
6. COMMUNICATIONS 2 POST OPEN RACK. LOCATE VIDEO AND SECURITY NETWORK SWITCHES IN
THIS COMMUNICATIONS RACK. BOND TO SYSTEMS GROUND BUSBAR.
7. ACCESS CONTROL SYSTEM (ACS) POWER SUPPLY AND DOOR CONTROLLER CABINET.
8. (2) 2" RIGID CONDUITS TO ROOF WITH GOOSE NECK AT ROOF TOP. BOND TO SYSTEMS GROUND
BUSBAR.
9. (2) 4" COMMUNICATIONS SERVICE ENTRANCE CONDUITS TO SERVICE ENTRANCE. COORDINATE
WITH SITE UTILITIES FOR ADDITIONAL INFORMATION. CONDUITS SHALL HAVE MINIMUM 36"
SWEEPS. BOND TO SYSTEMS GROUND BUSBAR.
10. (3) 2" CONDUITS TO COMM. ROOM 118.
11. (2) 4" COMMUNICATIONS CONDUIT SLEEVES FOR VOICE DATA CABLES. BOND TO SYSTEMS
GROUND BUSBAR.
12. (3) 2" CONDUITS FROM COMM. ROOM 134.
13. (1) 4" CONDUIT FOR FACILITY COMMUNICATIONS. COORDINATE WITH SITE UTILITIES FOR
ADDITIONAL INFORMATION. CONDUITS SHALL HAVE MINIMUM 36" SWEEPS. BOND TO SYSTEMS
GROUND BUSBAR.
14. (1) 3" CONDUIT FOR CATV SERVICE ENTRANCE CONDUITS TO SERVICE ENTRANCE.
COORDINATE WITH SITE UTILITIES FOR ADDITIONAL INFORMATION. CONDUITS SHALL HAVE
MINIMUM 36" SWEEPS. BOND TO SYSTEMS GROUND BUSBAR.
15. INTRUSION SECURITY SYSTEM CONTROL PANEL AND POWER SUPPLY.
16. OWNER PROVIDER COMMUNICATIONS RACK.
17. ACCESS CONTROL REMOTE CONTROL PANEL AND POWER SUPPLY.
18. INTRUSION SECURITY SYSTEM REMOTE CONTROL PANEL AND POWER SUPPLY.
19. SECURITY SYSTEMS DEDICATED WORKSTATION COMPUTER. COMPUTER SHALL INTEGRATE
WITH VIDEO MANAGEMENT SOFTWARE AND ACCESS CONTROL SYSTEM. PROVIDE DEDICATED
COMMUNICATIONS OUTLET WITH (2) GREEN CAT 6 PLENUM CABLE TO COMM. ROOM 134.
20. PROVIDE WALL MOUNTED TV OUTLET ADJACENT TO 120VAC DUPLEX RECEPTACLE.
COORDINATE MOUNTING HEIGHT WITH ELECTRICAL AND ARCHITECT DRAWINGS PRIOR TO
ROUGH IN. PROVIDE (1) CAT 6 UTP PLENUM RATED CABLE AND (1) RG-6 COAX PLENUM RATED
CABLE TO NEAREST COMM. ROOM.
21. WALL MOUNTED DATA OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO NEAREST COMM.
ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END WITH CAT 6
HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND TESTED. REFER TO
SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.
22. FLOOR BOX MOUNTED DATA OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO NEAREST
COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END WITH CAT
6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND TESTED. REFER
TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.
23. CEILING MOUNTED WIRELESS ACCESS POINT OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6
CABLES TO NEAREST COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT
EACH END WITH CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED
AND TESTED. REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.
24. WALL MOUNTED WIRELESS ACCESS POINT. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO
NEAREST COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END
WITH CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND
TESTED. REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.
25. WALL MOUNTED CAMERA ABOVE COVERED CANOPY AT APPROXIMATELY 15' AFF. COORDINATE
PRIOR TO ROUGH IN.
26. CEILING MOUNT CAMERA UNDER COVERED AREA. COORDINATE PRIOR TO ROUGH IN.
27. WALL MOUNT CAMERA AT APPROXIMATELY 15' AFF. COORDINATE PRIOR TO ROUGH IN.
N
E
S
W
OBSERV.MEZZ.
LULA LIFT
201A
CLOSET
F2
WAP
F2
F2
OBSERV. DECK
CA-22
DC
TYP.
DC
TV
TV
ES102
vo ic e
7.
0.
w w w
.k m ad g.
ne t
AA
N
PLAN NORTH
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
LAWRENCE M. STOFF
P.E. #78586
A. REFER TO SPECIFICATION.
B. REFER TO GENERAL NOTES.
C. DO NOT SCALE ELECTRICAL DRAWINGS FOR ANY DIMENSIONS.
D. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, NATIONAL, STATE AND LOCAL
CODES.
E. PROVIDE GROUNDING AND BONDING PER NEC 250.
F. FIELD VERIFY EXACT LOCATION OF ALL DEVICES AND EQUIPMENT PRIOR TO ROUGH IN.
KEY NOTES:
GENERAL NOTES:
1. WALL MOUNTED DATA OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6 CABLES TO NEAREST
COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED AT EACH END WITH
CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE LABELED AND TESTED.
REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.
2. WALL MOUNTED WIRELESS ACCESS POINT OUTLET. PROVIDE CAT 6 JACKS WITH CAT 6
CABLES TO NEAREST COMM. ROOM. ALL COMMUNICATIONS CABLES SHALL BE TERMINATED
AT EACH END WITH CAT 6 HARDWARE OR GREATER. ALL CABLES AND JACKS SHALL BE
LABELED AND TESTED. REFER TO SYMBOL LEGEND FOR JACK AND CABLE QUANTITY.
ES200
ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
LAN/WAN
COMPOSITE
ACCESS CONTROL
CABLE (TYP.)
CAT 6 PATCH
CORD (TYP.)
RS485
ES201
ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
ETH
ER
N
ET N
ETW
O
R K
ES202
ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
ES203
ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
COMMUNICATION RISER DIAGRAM
1. REFER TO SHEET ES000 FOR SYMBOL LEGEND.
2. REFER TO SHEET ES000 FOR GENERAL NOTES.
3. REFER TO PROJECT MANUAL.
4. INSTALL BUSHINGS TO ALL RACEWAY TERMINATIONS.
GENERAL NOTES
REFERENCE NOTES
1. PLYWOOD BACKBOARD. REFER TO SPECIFICATIONS AND FLOOR PLANS FOR ADDITIONAL
REQUIREMENTS.
2. CABLE TRAY. INSTALL ABOVE EQUIPMENT RACKS AND/OR CABINETS. REFER TO FLOOR
PLANS FOR LAYOUT.
3. LOCAL EXCHANGE CARRIER SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN
FOR CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE PRIOR
TO ROUGH IN.
4. FACILITY COMMUNICATIONS SERVICE ENTRANCE CONDUITS. REFER TO FLOOR PLAN
FOR CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE PRIOR
TO ROUGH IN.
5. CATV PROVIDER SERVICE ENTRANCE CONDUITS. REFER TO SITE PLAN FOR CONDUIT
SIZE, QUANTITY AND CABLE REQUIREMENTS. COORDINATE PRIOR TO ROUGH IN.
6. COMMUNICATIONS CONDUITS BETWEEN COMMUNICATIONS ROOM. REFER TO FLOOR
PLAN FOR CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE
PRIOR TO ROUGH IN.
7. SPARE CONDUIT STUB OUT AND CAP 5' OUT OF BUILDING. COORDINATE PRIOR TO
ROUGH IN.
8. COMMUNICATIONS CONDUIT SLEEVES FOR VOICE DATA CABLES.
9. CONDUITS TO ROOF WITH GOOSE NECK AT ROOF TOP. REFER TO FLOOR PLAN FOR
CONDUIT SIZE, QUANTITY AND ADDITIONAL REQUIREMENTS. COORDINATE PRIOR TO
ROUGH IN.
SLAB
ROOF
COMM. 134 COMM. 118
8 8
2 2
1 1
ES400
ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
ES401
ic e
7.
0.
w w w
.k m ad g.
ne t
AA
JL
C&O
Joseph, Lawrence & Co
Consulting Engineers 317 riveredge blvd. suite 110 cocoa, Florida 32770 Tel: 321.972.4466 www.jlceng.com
CA No. 28730
Space Coast
BLAKE LAWRENCE SUDDETH
P.E. #69060
File details come from the government source that posted it. Updated .