ELECTRICAL PLAN SET.pdf
PDF 5 MB Posted
- Solicitation number
- IFB-106250
- Issued by
- York County, Virginia
About this file
This electrical plan set document, prepared by York County Department of Public Works in Yorktown, Virginia, outlines the design specifications for electrical site work supporting the construction of a proposed stage awning and pavilion at the Freight Shed facility located at 331 Water Street, Yorktown, VA 23690. The project encompasses the installation of electrical conduit, conductors, and associated equipment, including routing power to and from each location and making necessary connections to the existing electrical panel. Key work components include installation of two new 100-amp, 1-phase, 120/240V subfed electrical panels (designated SSFP and PSFP); approximately 750 linear feet of Schedule 40 PVC and fiberglass conduit; multiple weatherproof electrical receptacle and communication boxes; one 36x24x18 electrical pull box; one 24x6x6 electrical wireway trough; and various site work elements such as electrical trenching at depths ranging from 18 to 24 inches and five 2-inch round conduit penetrations through existing walls. The contractor is responsible for all material procurement and installation unless specifically marked as owner-provided, and must ensure full testing and functionality of all electrical systems prior to project closeout.
The project specifications require compliance with the 2017 National Electrical Code (NFPA 70), 2017 Virginia Electrical Code, 2018 Virginia Construction Code, and applicable local York County codes and standards. The contractor must obtain and pay for any additional permits beyond standard building permits (such as LDA and VSPM permits), submit all material submittals for owner approval, and coordinate extensively with existing facilities to avoid disrupting power, lighting, communication, fire systems, and other services in surrounding areas. Site restoration is required for all disturbed areas including brick pavers, concrete, landscape, asphalt, and fencing. The scope includes field verification of existing underground utility locations, removal and proper disposal of designated demolition materials, and restoration of entrances, restrooms, and walkways to maintain accessibility throughout construction. All electrical materials must comply with specified industry standards, including Square D or approved equal panels, commercial-grade weather-resistant GFCI receptacles, and marine-grade stainless steel enclosures for ground-mounted equipment.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FR
EI
GH
T
SH
ED
P
A
VI
LI
O
N A
N D
S
TA
GE
A
W N
IN
G
EL
EC
TR
IC
A L
CO
VE
R
SH
EE
T
PROJECT NARRATIVE:
THIS PROJECT IS TO CONSTRUCT ELECTRICAL SITE WORK FOR THE PROPOSED STAGE AWNING AND PAVILION, INCLUDING THE INSTALLATION OF CONDUIT, CONDUCTORS, AND ASSOCIATED EQUIPMENT. WORK WILL ALSO INCLUDE ROUTING POWER TO AND FROM EACH LOCATION
AND MAKING THE NECESSARY CONNECTIONS TO THE EXISTING ELECTRICAL PANEL.
INDEX OF DRAWINGS
G - 001 COVER SHEET
G - 002 GENERAL NOTES AND SPECS
E - 101 SITE PLAN - POWER DEMO
E - 102 SITE PLAN - POWER CONSTRUCTION
E - 103 POWER PANEL SCHEDULES
E - 104 ELECTRICAL DETAILS
E - 105 ELECTRICAL DETAILS (2)
ABBREVIATIONS
ACK - ACKNOWLEDGE
AFF - ABOVE FINISHED FLOOR
APP - APPROXIMATELY
AV - AUDIO / VISUAL
BLDG - BUILDING
CP - CEILING PIPE
E - EAST
DSC - DISCONNECT
DWN - DOWN
EMT - ELECTRICAL METALLIC TUBING
FLS - FIRE LIFE SAFETY
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
LTG - LIGHTING
LF - LINEAR FEET
MAX - MAXIMUM
MC - METAL CONDUIT
MIN - MINIMUM
MTS - MANUAL TRANSFER SWITCH
NTS - NOT TO SCALE
N - NORTH
NW - NORTHWEST
NE - NORTHEAST
REC - RECEPTACLE
RTRC - REINFORCED THERMOSETTING RESIN CONDUIT
SF - SQUARE FEET
S - SOUTH
SE - SOUTHEAST
SW - SOUTHWEST
SCH. - SCHEDULE
TYP - TYPICAL
UNK - UNKNOWN
UON - UNLESS OTHERWISE NOTED
W - WEST
FREIGHT SHED - PAVILION AND STAGE AWNING ELECTRICAL
331 WATER STREET
YORKTOWN, VA 23690
VICINITY MAP
SCALE: NTS
SITE #1
SITE #2
FREIGHT
SHED
WATER ST (ROUTE 1020)
BUCKNER ST
FREIGHT SHED
AUXILIARY BUILDING
LOCATION MAP
SCALE: NTS
PROPERTY LINE
FREIGHT
SHED
WATER ST (ROUTE 1020)
FREIGHT SHED
AUXILIARY
BUILDING
SITE #1
SITE #2
GENERAL LEGEND
DEMO
ASPHALT
BRICK
GRANITE CURB
LIMIT OF
DISTURBANCE
PROJECT AREA
EXISTING ELECTRICAL
PANEL
HOMERUN (ELECTRICAL)
ELECTRICAL WIRING
RECEPTACLE; DUPLEX
EXTERIOR RECEPTACLE;
QUADRUPLEX
ENLARGED PLAN
LIGHT SWITCH
AV COMMUNICATION
BOX
E
T
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CWH III
AutoCAD SHX Text
AutoCAD SHX Text G-001
AutoCAD SHX Text
YORK COUNTY
AutoCAD SHX Text Dept. of Public Works
AutoCAD SHX Text 105 Service Drive
AutoCAD SHX Text Post Office Box 532
AutoCAD SHX Text Yorktown, Virginia 23690-0532
AutoCAD SHX Text
(757) 890-3800 FAX: 890-3801
AutoCAD SHX Text Revisions/Comments/Notes
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 04/10/2026
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text
ENL3
AutoCAD SHX Text P-110
GH
T
SH
ED
P
A
VI
LI
O
N A
N D
S
TA
GE
A
W N
IN
G
EL
EC
TR
IC
A L
GE
N
ER
A
L N
O
TE
S A
N D
S
PE
CS
GENERAL NOTES (ALL SHEETS):
1. THE OWNER SHALL WAIVE ALL YORK COUNTY BUILDING PERMIT FEES (PLUMBING, ELECTRICAL, BUILDING, MECHANICAL, ETC.). ANY ADDITIONAL PERMITS
(LDA, VSPM, ETC.) SHALL BE OBTAINED AND PAID FOR BY THE CONTRACTOR.
2. CONTRACTOR SHALL SUBMIT ALL MATERIAL SUBMITTALS AND ASSOCIATED INFORMATION TO THE OWNER FOR APPROVAL PRIOR TO COMMENCING
WORK WITHIN THE PROJECT AREA.
3. ALL MATERIALS AND WORK SHALL COMPLY WITH INDUSTRY STANDARDS AND APPLICABLE CODES CURRENTLY ENFORCED IN YORK COUNTY AND THE STATE
OF VIRGINIA.
4. THE CONTRACTOR IS RESPONSIBLE FOR THE PURCHASE AND INSTALLATION OF ALL ITEMS LISTED IN THE DRAWING PACKAGE UNLESS CLEARLY MARKED AS "OWNER PROVIDED," "OWNER," OR "THIRD PARTY INSTALLED." IN SOME CASES, THE CONTRACTOR IS REQUIRED TO INSTALL OWNER-PROVIDED
EQUIPMENT OR SYSTEMS.
5. CONTRACTOR SHALL ENSURE THAT ALL ELECTRICAL SYSTEMS AND RELATED COMPONENTS INSTALLED UNDER THIS PROJECT ARE FULLY TESTED AND FUNCTIONING AS INTENDED. THIS INCLUDES VERIFYING THAT ALL NEW AND EXISTING PANELS, CONDUITS, RECEPTACLES, AND ASSOCIATED EQUIPMENT OPERATE PROPERLY AND INTERFACE CORRECTLY WITH ONE ANOTHER. ALL CONNECTIONS, CIRCUITS, AND COMMUNICATION PATHWAYS SHALL BE
COMPLETED AND CONFIRMED FULLY FUNCTIONAL PRIOR TO PROJECT CLOSEOUT.
6. ALL ITEMS SUPPLIED TO THE CONTRACTOR BY THE OWNER SHALL BECOME THE RESPONSIBILITY OF THE CONTRACTOR UPON DELIVERY. ANY DAMAGE NOT IDENTIFIED TO THE OWNER UPON DELIVERY OR DAMAGE OCCURRING THEREAFTER SHALL BE THE CONTRACTOR’S RESPONSIBILITY.
7. CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF ALL MATERIAL AND EQUIPMENT DESIGNATED FOR DEMOLITION THROUGHOUT THE PLANS, UNLESS OTHERWISE NOTIFIED TO SALVAGE TO THE OWNER. MATERIAL AND EQUIPMENT REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR, UNLESS OTHERWISE NOTED.
8. ALL EXISTING BRICK, CONCRETE, LANDSCAPE, ASPHALT, FENCING, DITCHES, AND OTHER ITEMS THAT MAY BE DISTURBED OR DAMAGED DURING CONSTRUCTION SHALL BE RESTORED TO EQUAL OR BETTER CONDITION AT COMPLETION OF THE PROJECT.
9. CONTRACTOR SHALL ENSURE THAT ALL ENTRANCES, RESTROOMS, AND WALKWAYS TO THE PROJECT AREA ARE ACCESSIBLE AND KEPT CLEAR OF DEBRIS, EQUIPMENT, AND MATERIAL THROUGHOUT THE DURATION OF THE PROJECT. IF TEMPORARY CLOSURE OF ENTRANCES, RESTROOMS, AND/OR WALKWAYS IS REQUIRED, NOTIFY THE OWNER IN ADVANCE TO MINIMIZE IMPACT ON ADJACENT FACILITIES.
10. CONTRACTOR SHALL TAKE CARE NOT TO DISRUPT SERVICES IN OTHER AREAS OR PARTS OF THE SURROUNDING FACILITIES. NOTIFY THE OWNER PRIOR TO COMMENCING WORK THAT MAY AFFECT POWER, LIGHTING, COMMUNICATION/DATA, FIRE SYSTEMS, OR OTHER SERVICES.
11. HORIZONTAL AND VERTICAL LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR.
ANY ERRORS OR DISCREPANCIES SHALL BE REPORTED TO THE OWNER BEFORE PROCEEDING WITH WORK.
12. NO NEW PENETRATIONS SHALL BE MADE INTO EXISTING FOUNDATION OR CMU BLOCK WALLS WITHOUT PRIOR APPROVAL FROM THE OWNER.
13. ALL GRAY/LIGHT LINE WORK THROUGHOUT THIS PLAN INDICATE EXISTING ITEMS FOUND IN THE PROJECT AREA. ALL BLACK/DARK LINE WORK THROUGHOUT THIS PLAN INDICATE ITEMS TO BE DEMOLISHED OR ADDED FOR CONSTRUCTION WITHIN THE PROJECT AREA.
14. THE OWNER SHALL BE RESPONSIBLE FOR PROVIDING COMPACTION TEST RESULTS BY A GEOTECH ENGINEER (F&R) FOR VERIFICATION OF PROPER
COMPACTION AND PROOF ROLL PRIOR TO PAVING.
15. COORDINATE WITH ARCHITECTURAL, STRUCTURAL, AND SITE DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS PLAN.
GENERAL NOTES - SURROUNDING AREAS (ALL SHEETS):
1. CONTRACTOR TO TAKE CARE AS TO NOT DISRUPT SERVICES IN OTHER AREAS/PARTS OF THE SURROUNDING FACILITIES. PLEASE NOTIFY THE OWNER PRIOR TO COMMENCING SUCH WORK AS THE REMOVAL, RELOCATION, AND/OR ADDITION OF A CIRCUIT, UTILITY, OR ITEM MAY DISRUPT POWER, LIGHTING, COMMUNICATION/DATA, FIRE SYSTEMS, OR SOME OTHER SERVICE IN OTHER OCCUPIED AREAS THROUGHOUT.
2. CONTRACTOR TO ENSURE THAT ALL ENTRANCES, RESTROOMS, AND WALKWAYS TO THE PROJECT AREA ARE MADE ACCESSIBLE AND KEPT CLEAR OF DEBRIS, EQUIPMENT, AND MATERIAL THROUGHOUT THE DURATION OF THE PROJECT. IF CLOSURE OF ENTRANCE IS REQUIRED, INFORM THE OWNER IN
ADVANCE TO ENSURE THAT SURROUNDING FACILITIES ARE NOT NEGATIVELY IMPACTED.
3. IF CLOSURE OF WALKWAY(S), RESTROOM(S), OR HALLWAY(S) IS REQUIRED, CONTRACTOR TO INFORM THE OWNER 24-48 HOURS PRIOR. CONTRACTOR TO COORDINATE WITH THE OWNER IN ADVANCE TO ENSURE THAT SURROUNDING FACILITIES ARE NOT NEGATIVELY IMPACTED.
ALL APPLICABLE CODES
THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE LAWS AND BUILDING CODES GOVERNING THIS PROJECT. WHERE LAWS AND CODES ARE IN DIRECT CONFLICT, THE MORE STRINGENT REQUIREMENTS SHALL PREVAIL.SUCH COMPLIANCE SHALL INCLUDE, BUT NOT LIMITED TO THE LATEST ADOPTION VERSIONS
OF:
1. 2018 VIRGINIA CONSTRUCTION CODE (VCC)
2. 2018 VIRGINIA MECHANICAL CODE
3. 2018 VIRGINIA PLUMBING CODE
4. 2018 VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC)
5. 2018 VIRGINIA ENERGY CONSERVATION AND ENVIRONMENTAL STANDARD (VEES)
6. 2017 VIRGINIA ELECTRICAL CODE
7. 2017 ICC A117.1-2017 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
8. 2017 NATIONAL ELECTRICAL CODE (NPFA 70)
9. 2016 NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72)
10. 2010 AMERICANS WITH DISABILITIES ACT (ASD)
11. ACI STANDARD 530-13 "BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES"
12. OSHA, OCCUPATIONAL SAFETY AND HEALTH REGULATIONS
13. ASTM STANDARDS IN BUILDING CODES, VOLUME I AND II, LATEST EDITION
PROJECT SPECIFICATIONS (CONTINUED):
ELECTRICAL:
1. ELECTRICAL PANEL "SSFP" (NEW SUBFED PANEL):
1.1. 100 AMP, 1 PHASE, 120/240V, 24PACE PANEL. PRODUCT #30YE81 MANUFACTURED BY SQUARE D OR APPROVED EQUAL.
1.1.1. MODEL NUMBER: QO124M100P
1.1.2. TYPE: MAIN LUG OR MAIN BREAKER CONVERTIBLE LOAD CENTER
1.1.3. BUS: TIN-PLATED COPPER BUS BAD
1.1.4. ENCLOSURE: NEAM 1, INDOOR RATED STEEL ENCLOSURE
1.1.5. RATING: 22KA SHORT CIRCUIT CURRENT RATING
1.1.6. CIRCUIT BREAKERS: COMPATIBLE WITH SQUARE D QO SERIES BREAKERS
1.1.1.1. TO INCLUDE PANEL COVER
2. ELECTRICAL PANEL "PSFP" (NEW SUBFED PANEL):
2.1. 100 AMP, 1 PHASE, 120/240V, 24PACE PANEL. PRODUCT #30YE81 MANUFACTURED BY SQUARE D OR APPROVED EQUAL.
2.1.1. MODEL NUMBER: QO124M100P
2.1.2. TYPE: MAIN LUG OR MAIN BREAKER CONVERTIBLE LOAD CENTER
2.1.3. BUS: TIN-PLATED COPPER BUS BAD
2.1.4. ENCLOSURE: NEAM 1, INDOOR RATED STEEL ENCLOSURE
2.1.5. RATING: 22KA SHORT CIRCUIT CURRENT RATING
2.1.6. CIRCUIT BREAKERS: COMPATIBLE WITH SQUARE D QO SERIES BREAKERS
2.1.6.1. TO INCLUDE PANEL COVER
3. CONDUIT:
3.1. SCHEDULE 40 PVC
3.1.1. TYPE: SOLID WALL
3.1.2. USE: UNDERGROUND INSTALLATION
3.1.2.1. PROVIDE ALL REQUIRED CONDUIT FITTINGS, BODIES, AND ACCESSORIES NECESSARY FOR A COMPLETE AND FUNCTIONAL INSTALLATION
3.2. FIBERGLASS (RTRC):
3.2.1. TYPE: SOLID WALL
3.2.2. USE: ABOVE GROUND INSTALLATION
3.2.2.1. PROVIDE ALL REQUIRED CONDUIT FITTINGS, BODIES, AND ACCESSORIES NECESSARY FOR A COMPLETE AND FUNCTIONAL INSTALLATION
4. RECEPTACLE:
4.1. WALL MOUNTED
4.1.1. COMMERCIAL GRADE, WEATHER-RESISTANT, GFCI RECEPTACLE
4.1.1.1. MATERIAL: CORROSION-RESISTANT FOR EXTERIOR USE
4.1.1.1.1. SIZE: MID-SIZE
4.1.1.1.2. COLOR: IVORY
4.1.1.2. COVER: WEATHERPROOF SELF-CLOSING VERTICAL COVER, PASS & SEYMOUR CA26-WV OR APPROVED EQUAL
4.2. GROUND MOUNTED
4.2.1. COMMERCIAL GRADE, WEATHER-RESISTANT, GFCI RECEPTACLE
4.2.1.1. TYPE: ENCLOSURE SHALL BE CONSTRUCTED OF MARINE GRADE STAINLESS STEEL OR EQUIVALENT CORROSION RESISTANT MATERIAL
4.2.1.1.1. RATING: IP66 (dust/water protection), UL LISTED FOR EXTERIOR WET LOCATION SERVICE
4.2.1.1.2. COVER: POP-UP OR LIFT-OUT STYLE WEATHERPROOF COVER SUITABLE FOR OUTDOOR INSTALLATION WITHIN BRICK PAVERS
4.2.1.1.3. COLOR: GOLD BRASS
5. PULL BOX
5.1. 36x24x18 HEAVY DUTY VAULT BOX, MODEL PG2436BA18, MANUFACTURED BY QUAZITE OR APPROVED EQUAL
5.1.1. MATERIAL: REINFORCED PRECAST CONCRETE
5.1.2. LOAD RATING: ANSI TIER 22
5.1.2.1. TO INCLUDE SAME RATED COVER
6. WIREWAY
6.1. 24x6x6 HEAVY DUTY METAL WIRE TROUGH, MODEL 84GG1, MANUFACTURED BY HAMMOND MANUFACTURING OR APPROVED EQUAL
6.1.1. MATERIAL: GALVANIZED STEEL CORROSION RESISTANT FINISH
6.1.2. COVER: REMOVABLE CORROSION RESISTANT
6.1.3. RATING: UL LISTED
UNIT PAVERS:
1. BRICK:
1.1. GLEN GERY 53DD 3 5/8" BY 7 5/8" OR APPROVED EQUAL.
2. SAND:
2.1. LEVELING COURSE: SOUND, SHARP, WASHED, NATURAL SAND OR CRUSHED STONE COMPLYING WITH GRADATION REQUIREMENT OF ASTM C33 FOR
FINE AGGREGATE.
2.2. JOINTS: FINE, SHARP, WASHED, NATURAL SAND OR CRUSHED STONE WITH 100 PERCENT PASSING NO. 16 SIEVE AND NO MORE THAN 10 PERCENT
PASSING NO. 200 SIEVE.
3. MORTAR:
3.1. PORTLAND CEMENT/LIME SETTING-BED, TYPE M, COMPLYING WITH ASTM C270, PROPORTION SPECIFICATION OR APPROVED EQUAL.
3.1.1. COLOR: HERITAGE BUFF, TYPE S.
MISCELLANEOUS MATERIAL:
1. WOOD BACKING:
1.1. 3/4" FIRE-RATED PLYWOOD, APPROPRIATE SIZE TO SUPPORT ELECTRICAL PANELS.
1.1.1. PAINT: SHERWIN-WILLIAMS INTERIOR FIRE RETARDANT LATEX PAINT OR APPROVED EQUAL.
1.1.1.1. COLOR: SW 7005 PURE WHITE
2. CONDUITS SLEEVES:
2.1. CORROSION-RESISTANT STEEL (ABOVE GRADE)
2.1.1. SIZE: MATCH EXTERIOR DIAMETER OF CONDUIT WITH MINIMUM 1/2" CLEARANCE AROUND CONDUIT
2.1.2. USE: PROVIDE SLEEVES AT ALL WALL AND FOUNDATION PENETRATIONS WHERE CONDUIT PASSES THROUGH MASONRY OR CMU WALLS
3. SEALANT / FIRESTOP:
3.1. INTUMESCENT FIRESTOP SEALANT OR ACRYLIC/ELASTOMERIC SEALANT SUITABLE FOR EXTERIOR USE
3.1.1. RATING: UL LISTED OR FM APPROVED FOR 2-HOUR RATED WALL PENETRATIONS
3.1.2. COLOR: NEUTRAL OR MATCH WALL COLOR WHERE VISIBLE
4. WARNING TAPE:
4.1. HIGH-VISIBILITY POLYETHYLENE TAPE, MINIMUM 6" WIDE, PRINTED WITH “CAUTION – ELECTRIC LINE BELOW”
4.4. COLOR: BRIGHT YELLOW WITH BLACK LETTERING, UL OR FM APPROVED FOR UNDERGROUND ELECTRICAL IDENTIFICATION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CWH III
AutoCAD SHX Text
AutoCAD SHX Text G-002
AutoCAD SHX Text
YORK COUNTY
AutoCAD SHX Text Dept. of Public Works
AutoCAD SHX Text 105 Service Drive
AutoCAD SHX Text Post Office Box 532
AutoCAD SHX Text Yorktown, Virginia 23690-0532
AutoCAD SHX Text
(757) 890-3800 FAX: 890-3801
AutoCAD SHX Text Revisions/Comments/Notes
AutoCAD SHX Text Date
AutoCAD SHX Text No.
04/10/2026
WATER STREET
FREIGHT SHED AUXILIARY BUILDING
FR
EI
GH
T
SH
ED
P
A
VI
LI
O
N A
N D
S
TA
GE
A
W N
IN
G
EL
EC
TR
IC
A L
SI
TE
P
LA
N
PO
W
ER
D
EM
O
GENERAL NOTES (THIS SHEET ONLY):
1. ALL MATERIALS AND WORK SHALL BE IN ACCORDANCE WITH INDUSTRY STANDARDS AND APPLICABLE CODES AS CURRENTLY ENFORCED IN THE COUNTY OF YORK AND/OR WITHIN THE STATE OF VIRGINIA.
2. ALL GRAY/LIGHT LINE WORK THROUGHOUT THIS PLAN INDICATE EXISTING ITEMS FOUND IN THE PROJECT AREA. ALL BLACK/DARK LINE WORK THROUGHOUT THIS PLAN INDICATE ITEMS TO BE DEMOLISHED OR
ADDED FOR CONSTRUCTION WITHIN THE PROJECT AREA.
3. THE PURPOSE OF THIS DRAWING SHEET IS TO PROVIDE A REFERENCE OVERALL SITE AND ELECTRICAL PLAN TO ASSIST WITH COMMUNICATING ALL SITE AND BUILDING SCOPE OF WORK. COORDINATE WITH ALL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS NOT SHOWN.
4. CONTRACTOR TO TAKE CARE AS TO NOT DISRUPT SERVICES IN OTHER AREAS/PARTS OF THE SURROUNDING FACILITIES. PLEASE NOTIFY THE OWNER PRIOR TO COMMENCING SUCH WORK AS THE REMOVAL, RELOCATION, AND/OR ADDITION OF A CIRCUIT, UTILITY, OR ITEM MAY DISRUPT POWER, LIGHTING, COMMUNICATION/DATA, FIRE SYSTEMS, OR SOME OTHER SERVICE IN OTHER OCCUPIED AREAS
THROUGHOUT.
5. CONTRACTOR TO ENSURE THAT ALL ENTRANCES, RESTROOMS, AND WALKWAYS TO THE PROJECT AREA ARE MADE ACCESSIBLE AND KEPT CLEAR OF DEBRIS, EQUIPMENT, AND MATERIAL THROUGHOUT THE DURATION OF THE PROJECT. IF CLOSURE OF ENTRANCE, RESTROOM, AND/OR WALKWAY IS REQUIRED, INFORM THE OWNER IN ADVANCE TO ENSURE THAT SURROUNDING FACILITIES ARE NOT NEGATIVELY IMPACTED.
6. HORIZONTAL AND VERTICAL LOCATION OF EXISTING UNDERGROUND UTILITIES ARE APPROXIMATE ONLY AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR. ANY ERRORS OR DISCREPANCIES SHALL BE REPORTED
TO THE OWNER BEFORE PROCEEDING WITH ANY WORK.
7. ALL EXISTING LANDSCAPE, BRICK, CONCRETE BASE, ASPHALT, FENCING, DITCHES, AND ANY OTHER ITEMS THAT MAY BE DAMAGED DURING CONSTRUCTION SHOULD BE RESTORED BACK TO EQUAL OR BETTER
CONDITIONS AT THE COMPLETION OF THE PROJECT.
8. CONTRACTOR TO REMOVE AND DISPOSE OF ALL RELATED MATERIAL SHOWN AS DEMOLISHED
THROUGHOUT THE PLANS, UNLESS OTHERWISE NOTIFIED TO SALVAGE TO THE OWNER. ALL MATERIAL AND EQUIPMENT SUBJECT TO BE REMOVED BECOMES PROPERTY OF THE CONTRACTOR, UNLESS OTHERWISE NOTED. CONTRACTOR SHALL PROPERLY DISPOSE OF ALL SUCH MATERIAL AND EQUIPMENT OFF SITE.
9. CONTRACTOR TO REMOVE ALL ABANDONED ELECTRICAL WIRING, SECURE, AND PROPERLY FASTEN SUCH WIRING WITHIN THE PROJECT AREA. SECURE ANY EXISTING ELECTRICAL BOXES THAT ARE REMAINING AND
DISCONNECT ALL EXISTING WIRING, AS REQUESTED.
10. ALL EXISTING PAVERS DISTURBED BY CONSTRUCTION SHALL BE CAREFULLY REMOVED, SALVAGED, AND REUSED TO THE GREATEST EXTENT POSSIBLE. ANY DAMAGED OR UNSUITABLE PAVERS SHALL BE REPLACED WITH NEW PAVERS MATCHING EXISTING IN SIZE, COLOR, AND FINISH. REINSTALL ALL PAVERS TO MATCH
ORIGINAL PATTERN, GRADE, AND ALIGNMENT.
11. SEE SHEET E-103 FOR EXISTING ELECTRICAL PANEL SCHEDULES.
KEY NOTES (THIS SHEET ONLY):
1. ALL ELECTRICAL ITEMS WITHIN THIS AREA AND ITS ASSOCIATED JUNCTION BOXES, WIRING, AND HOMERUNS
TO REMAIN, UNLESS OTHERWISE NOTED.
2. CONTRACTOR TO EXCAVATE +/- 30 LF OF ELECTRICAL TRENCH. TRENCH SHALL BE 18 INCHES IN MINIMUM DEPTH FROM FINISHED GRADE TO TOP OF CONDUIT AND 6 INCHES IN MINIMUM WIDTH. SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" AND "CONDUIT TRENCH DETAIL - BELOW EARTH" ON SHEET
E-104 FOR TRENCH REQUIREMENTS.
3. CONTRACTOR TO EXCAVATE +/- 105 LF OF ELECTRICAL TRENCH. TRENCH SHALL BE 18 INCHES IN MINIMUM DEPTH FROM FINISHED GRADE TO TOP OF CONDUIT AND 10 INCHES IN MINIMUM WIDTH. SEE "CONDUIT
TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" ON SHEET E-104 FOR TRENCH REQUIREMENTS
4. CONTRACTOR TO EXCAVATE +/- 40 LF OF ELECTRICAL TRENCH. TRENCH SHALL BE 24 INCHES IN MINIMUM DEPTH FROM FINISHED GRADE TO TOP OF CONDUIT AND 14 INCHES IN MINIMUM WIDTH. SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" AND "CONDUIT TRENCH DETAIL - BELOW EARTH" ON SHEET
E-104 FOR TRENCH REQUIREMENTS.
5. CONTRACTOR TO EXCAVATE +/- 40 LF OF ELECTRICAL TRENCH. TRENCH SHALL BE 18 INCHES IN MINIMUM DEPTH FROM FINISHED GRADE TO TOP OF CONDUIT AND 10 INCHES IN MINIMUM WIDTH. SEE "CONDUIT
TRENCH DETAIL - BELOW EARTH" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
6. CONTRACTOR TO EXCAVATE +/- 190 LF OF ELECTRICAL TRENCH. TRENCH SHALL BE 18 INCHES IN MINIMUM DEPTH FROM FINISHED GRADE TO TOP OF CONDUIT AND 10 INCHES IN MINIMUM WIDTH. SEE "CONDUIT
TRENCH DETAIL - BELOW EARTH" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
7. CONTRACTOR SHALL CORE DRILL FIVE (5) 2" ROUND OPENINGS INTO THE EXISTING WALL AS REQUIRED TO ACCOMMODATE INSTALLATION OF FVE (5) 2" CONDUIT PENETRATIONS. CAREFULLY REMOVE ONLY THE PORTION OF WALL NECESSARY FOR INSTALLATION OF NEW SLEEVES AND CONDUITS WITHOUT DAMAGING
SURROUNDING STRUCTURE.
8. DO NOT CUT OR COMPROMISE STRUCTURAL ELEMENTS. COORDINATE EXACT PENETRATION LOCATIONS
WITH NEW WORK AND VERIFY CONDITIONS IN FIELD.
9. REMOVE ALL DEBRIS AND PREPARE OPENINGS FOR NEW WORK. PATCH AND RESTORE ALL DISTURBED
AREAS TO MATCH EXISTING CONDITIONS AFTER INSTALLATION.
10. CONTRACTOR TO SAWCUT AND REMOVE EXISTING BRICK PAVERS, SAND SETTING BED, AND CONCRETE BASE FOR NEW ELECTRICAL PULL BOX. CONTRACTOR TO ENSURE OPENING EXCEEDS 6" OUTSIDE THE DIMENSIONS OF THE BOX. SEE "ELECTRICAL PULL BOX DETAIL" ON SHEET E-105 FOR ADDITIONAL INFORMATION.
11. CONTRACTOR TO REMOVE MATERIAL TO A DEPTH SUFFICIENT TO ACCOMMODATED THE PROPOSED PULL BOX, STONE BASE, AND RECONSTRUCTED WALKWAY/SIDEWALK SECTION. SEE "ELECTRICAL PULL BOX
DETAIL" ON SHEET E-105 FOR ADDITIONAL INFORMATION.
12. COORDINATE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN
ON THIS PLAN.
13. COORDINATE SITE DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS PLAN.
00 100 200
FREIGHT SHED
BUILDING
EXIST IT
COMMUNICATION BOX
FR
EIG
HT S
HED
AUXILI
ARY B
UILD
IN
G
EXIST DOMESTIC
WATER VALVES
(TYP. OF 2)
EXIST. IRRIGATION
BLOWOFF VALVE
EXIST. ELECTRICAL
PANEL "F2"
ELE
CTR
IC
AL
ROOM
BRICK PAVER
FLOWER BED (TYP.)
EXIST. BRICK
PAVERS (TYP.)
GRANITE
CURB (TYP.)
PROPOSED LOCATION
OF PAVILION (SITE #1)
PROPOSED LO
CATIO
N
OF STAGE AWNIN
G
(S
ITE #2
10 11
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text 1:100
AutoCAD SHX Text
CWH III
AutoCAD SHX Text
AutoCAD SHX Text E-101
AutoCAD SHX Text
YORK COUNTY
AutoCAD SHX Text Dept. of Public Works
AutoCAD SHX Text 105 Service Drive
AutoCAD SHX Text Post Office Box 532
AutoCAD SHX Text Yorktown, Virginia 23690-0532
AutoCAD SHX Text
(757) 890-3800 FAX: 890-3801
AutoCAD SHX Text Revisions/Comments/Notes
AutoCAD SHX Text Date
AutoCAD SHX Text No.
WATER STREET
FREIGHT SHED AUXILIARY BUILDING
TT
TT
TT
FR
EI
GH
T
SH
ED
P
A
VI
LI
O
N A
N D
S
TA
GE
A
W N
IN
G
EL
EC
TR
IC
A L
SI
TE
P
LA
N
PO
W
ER
C O
N
ST
RU
CT
IO
N
GENERAL NOTES (THIS SHEET ONLY):
1. ALL MATERIALS AND WORK SHALL BE IN ACCORDANCE WITH INDUSTRY STANDARDS AND APPLICABLE CODES AS
CURRENTLY ENFORCED IN THE COUNTY OF YORK AND/OR WITHIN THE STATE OF VIRGINIA.
2. ALL GRAY/LIGHT LINE WORK THROUGHOUT THIS PLAN INDICATE EXISTING ITEMS FOUND IN THE PROJECT AREA. ALL BLACK/DARK LINE WORK THROUGHOUT THIS PLAN INDICATE ITEMS TO BE DEMOLISHED OR ADDED FOR
CONSTRUCTION WITHIN THE PROJECT AREA.
3. THE PURPOSE OF THIS DRAWING SHEET IS TO PROVIDE A REFERENCE OVERALL SITE AND ELECTRICAL PLAN TO ASSIST WITH COMMUNICATING ALL SITE AND BUILDING SCOPE OF WORK. COORDINATE WITH ALL DRAWINGS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS NOT SHOWN.
4. CONTRACTOR TO TAKE CARE AS TO NOT DISRUPT SERVICES IN OTHER AREAS/PARTS OF THE SURROUNDING FACILITIES. PLEASE NOTIFY THE OWNER PRIOR TO COMMENCING SUCH WORK AS THE REMOVAL, RELOCATION, AND/OR ADDITION OF A CIRCUIT, UTILITY, OR ITEM MAY DISRUPT POWER, LIGHTING, COMMUNICATION/DATA, FIRE
SYSTEMS, OR SOME OTHER SERVICE IN OTHER OCCUPIED AREAS THROUGHOUT.
5. CONTRACTOR TO ENSURE THAT ALL ENTRANCES, RESTROOMS, WALKWAYS TO THE PROJECT AREA ARE MADE ACCESSIBLE AND KEPT CLEAR OF DEBRIS, EQUIPMENT, AND MATERIAL THROUGHOUT THE DURATION OF THE PROJECT. IF CLOSURE OF ENTRANCE, RESTROOM, AND/OR WALKWAY IS REQUIRED, INFORM THE OWNER IN
ADVANCE TO ENSURE THAT SURROUNDING FACILITIES ARE NOT NEGATIVELY IMPACTED.
6. THE CONTRACTOR IS RESPONSIBLE FOR THE PURCHASE AND INSTALLATION OF ALL ITEMS LISTED IN THE DRAWING PACKAGE UNLESS CLEARLY MARKED AS "OWNER PROVIDED," "OWNER," OR "THIRD PARTY INSTALLED." IN SOME CASES THE CONTRACTOR IS REQUIRED TO INSTALL OWNER PROVIDED EQUIPMENT AND SYSTEMS.
7. HORIZONTAL AND VERTICAL LOCATION OF EXISTING UNDERGROUND UTILITIES ARE APPROXIMATE ONLY AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR. ANY ERRORS OR DISCREPANCIES SHALL BE REPORTED TO THE OWNER
BEFORE PROCEEDING WITH ANY WORK.
8. ALL EXISTING LANDSCAPE, BRICK, CONCRETE BASE, ASPHALT, FENCING, DITCHES, AND ANY OTHER ITEMS THAT MAY BE DAMAGED DURING CONSTRUCTION SHOULD BE RESTORED BACK TO EQUAL OR BETTER CONDITIONS AT THE
COMPLETION OF THE PROJECT.
9. ALL NEW AND EXISTING ELECTRICAL WIRING INSTALLED WITHIN NEW CONDUITS SHALL BE CONTINUOUS TO AND TERMINATED AT NEW SUBFED PANELS. PROVIDE ALL REQUIRED CONNECTIONS, INCLUDING EQUIPMENT
GROUNDING CONDUCTORS, IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS.
10. CONTRACTOR SHALL PROVIDE ALL CONDUCTORS REQUIRED FOR A COMPLETE AND FUNCTIONAL SYSTEM.
CONDUCTOR TYPE, SIZE, AND INSTALLATION SHALL BE DETERMINED BY THE CONTRACTOR BASED ON PANEL
SCHEDULES, LOAD REQUIREMENTS, AND APPLICABLE CODES.
11. ALL 2" SCH. 40 PVC CONDUIT THAT IS INSTALLED ABOVE GROUND TO BE SECURELY ATTACHED THE ADJACENT STRUCTURE USING APPROPRIATE CORROSION-RESISTANT STRAPS, CLAMPS, OR HANGERS. WHICH SHOULD BE SPACED PER CODE AND MANUFACTURER’S RECOMMENDATIONS. CONDUIT SHALL BE ALIGNED AND SUPPORTED TO
PREVENT SAGGING OR MOVEMENT.
12. DUE TO THE CONCEALMENT OF THE EXISTING ELECTRICAL WIRING, SOME MINOR FIELD MODIFICATIONS TO THIS
PLAN MAY BE REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
13. NOT ALL CONDUIT IS SHOWN WITHIN THIS AREA FOR CLARITY PURPOSES.
14. CONTRACTOR TO ENSURE THAT AV COMMUNICATION CONDUIT SHOULD BE LEFT EMPTY. CONTRACTOR SHALL
PROVIDE PULL STRING WITHIN CONDUIT AND SECURE AT BOTH ENDS FOR FUTURE USE. OWNER TO HIRE 3RD PARTY
CONTRACTOR TO INSTALL CAT5E WIRING.
15. SEE SHEET E-103 FOR EXISTING AND NEW ELECTRICAL PANEL SCHEDULES.
16. SEE SHEET G-002 FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION.
KEY NOTES (THIS SHEET ONLY):
1. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) WEATHERPROOF, GROUND MOUNTED ELECTRICAL BOX.
2. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) WEATHERPROOF, GROUND MOUNTED ELECTRICAL BOX.
3. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) WEATHERPROOF, MOUNTED RECEPTACLE BOX. ELECTRICAL BOX TO BE MOUNTED 6" AFF DIRECTLY TO THE EXISTING GRANITE CURB WITH APPROPRIATE HARDWARE.
4. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) WEATHERPROOF, MOUNTED COMMUNICATION GANG BOX.
COMMUNICATION BOX TO BE MOUNTED 6" AFF DIRECTLY TO THE EXISTING GRANITE CURB WITH APPROPRIATE
HARDWARE.
5. CONTRACTOR TO INSTALL +/- 180 LF OF TWO (2) 2" ROUND SCH. 40 PVC CONDUITS TO ELECTRICAL PULL BOX. SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
6. CONTRACTOR SHALL UTILIZE THE TWO (2) 2" ROUND CONDUITS WITHIN COLUMN CAVITY. EXTEND CONDUIT FROM COLUMN TO THE FREIGHT SHED AUXILIARY ELECTRICAL ROOM. RUN ELECTRICAL WIRING THROUGH CONDUIT AND
MAKE ALL REQUIRED CONNECTIONS AT NEW SUBFED ELECTRICAL PANEL "PSFP".
7. CONTRACTOR TO INSTALL +/- 25 LF OF ONE (1) 2" ROUND SCH. 40 PVC CONDUIT. SEE "CONDUIT TRENCH DETAIL -
BELOW WALKWAY/SIDEWALK" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
8. CONTRACTOR TO EXTEND CONDUIT FROM WEATHERPROOF, GROUND MOUNTED BOX TO COLUMN AND TIE INTO 2" ROUND FIBERGLASS (RTRC) CONDUIT WITHIN COLUMN CAVITY. RUN ELECTRICAL WIRING WITHIN BUILDING CAVITY
AND ROUTE WIRING BACK TO NEW SUBFED ELECTRICAL PANEL "SSFP".
9. CONTRACTOR TO INSTALL +/- 40 LF OF ONE (1) 2" ROUND SCH. 40 PVC CONDUIT TO ELECTRICAL PULL BOX.
CONDUIT SHALL BE UTILIZED FOR CAT5E CABLING. SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" AND "CONDUIT TRENCH DETAIL - BELOW EARTH" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
10. CONTRACTOR TO INSTALL +/- 25 LF OF ONE (1) 2" ROUND SCH. 40 PVC CONDUIT TO ELECTRICAL PULL BOX. SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" AND "CONDUIT TRENCH DETAIL - BELOW EARTH" ON
SHEET E-104 FOR TRENCH REQUIREMENTS.
11. CONTRACTOR TO INSTALL +/- 40 LF OF ONE (1) 2" ROUND SCH. 40 PVC CONDUIT TO ELECTRICAL PULL BOX. SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
12. CONTRACTOR TO INSTALL ONE (1) WALL MOUNTED, 1 PHASE, SUBFED ELECTRICAL PANEL WITHIN ELECTRICAL ROOM. PANEL SHALL BE DESIGNATED "PSFP" AND CONNECTED TO THE EXISTING ELECTRICAL PANEL LABELED "F2".
SEE "ENLARGED PLAN - ENL1" ON SHEET E-104 FOR ADDITIONAL REQUIREMENTS.
13. CONTRACTOR TO INSTALL ONE (1) WALL MOUNTED, 1 PHASE, SUBFED ELECTRICAL PANEL WITHIN ELECTRICAL ROOM. PANEL SHALL BE DESIGNATED "SSFP" AND CONNECTED TO THE EXISTING ELECTRICAL PANEL LABELED "F2".
SEE "ENLARGED PLAN - ENL1" ON SHEET E-104 FOR ADDITIONAL REQUIREMENTS.
14. CONTRACTOR TO INSTALL +/- 190 LF OF ONE (1) 2" ROUND SCH. 40 PVC CONDUIT TO ELECTRICAL PULL BOX.
CONDUIT SHALL BE UTILIZED FOR CAT5E CABLING AND SHALL EXTEND FROM OTHER LOCATIONS. SEE "CONDUIT
TRENCH DETAIL - BELOW EARTH" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
15. CONTRACTOR TO INSTALL +/- 190 LF OF ONE (1) 2" ROUND SCH. 40 PVC CONDUIT. SEE "TRENCH DETAIL BELOW
EARTH" ON SHEET E-104 FOR TRENCH REQUIREMENTS.
16. CONTRACTOR TO PROVIDE AND INSTALL TWO (2) WEATHERPROOF MOUNTED RECEPTACLE BOXES AND TWO (2)
WEATHERPROOF MOUNTED COMMUNICATION GANG BOXES AT TWO DIFFERENT LOCATIONS.
ELECTRICAL/COMMUNICATION BOX TO BE MOUNTED 6" AFF DIRECTLY TO THE EXISTING GRANITE CURB WITH
APPROPRIATE HARDWARE.
17. CONTRACTOR TO INSTALL ONE (1) 24x6x6 ELECTRICAL WIREWAY TROUGH. SEE "ELECTRICAL ROOM - SECTION VIEW
(2)" ON SHEET E-105 FOR ADDITIONAL INFORMATION.
18. CONTRACTOR TO INSTALL +/- 50 LF OF FIVE (5) 2" ROUND SCH. 40 PVC CONDUITS FROM ELECTRICAL PULL BOX TO ELECTRICAL WIREWAY. SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" ON SHEET E-104 FOR
TRENCH REQUIREMENTS.
19. CONTRACTOR SHALL INSTALL FIVE (5) 2" CONDUITS RISING FROM BELOW GRADE AND TRANSITIONING INTO ELECTRICAL WIREWAY TROUGH. PROVIDE LONG SWEEP ELBOWS TO ROUTE CONDUITS FROM BELOW GRADE TO UNDERSIDE OF ELECTRICAL WIREWAY TROUGH. SEE "ELECTRICAL ROOM - SECTION VIEW (1)" ON SHEET E-104 FOR
ADDITIONAL INFORMATION.
20. CONTRACTOR TO INSTALL ONE (1) 34x24x18 ELECTRICAL PULL BOX. SEE "ELECTRICAL PULL BOX DETAIL" ON SHEET
E-105 FOR ADDITIONAL INFORMATION.
21. ALL ELECTRICAL WIRING WILL BE RUN ABOVE THE SOFFIT PANEL CEILING THROUGHOUT THE ENTIRE BUILDING AREA. COORDINATE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS PLAN.
22. ALL ELECTRICAL WIRING SHOULD BE RUN FROM THE SOFFIT PANEL CEILING DOWN THROUGH TWO (2) 2" ROUND FIBERGLASS (RTRC) CONDUITS CONNECTING TO THE 2" SCH. 40 ROUND PVC CONDUITS THAT LEAD TO THE FREIGHT SHED AUXILIARY BUILDING ELECTRICAL ROOM. COORDINATE ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION NOT SHOWN ON THIS PLAN.
23. IMAGE ENLARGED FOR CLARITY PURPOSES ONLY.
24. COORDINATE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS
PLAN.
25. COORDINATE SITE DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS PLAN.
FR
EIG
HT S
HED
AUXILI
ARY B
UILD
IN
G
FREIGHT SHED
BUILDING
EXIST. ELECTRICAL
PANEL "F2"
STAGE AWNING
COLUMN (TYP)
PAVILION
EXIST DOMESTIC
WATER VALVES
(TYP. OF 2)
EXIST IT
COMMUNICATION BOX
NEW BRICK
PAVERS (TYP.)
NEW BRICK
PAVERS (TYP.)
00 100 200
COLUMN (TYP)
ELE
CTR
IC
AL
ROOM
ENLARGED PLAN - ENL2
SCALE: 3/16" = 1'-0"
SUBFED PANELS
"SSFP" AND "PSFP"
BRICK PAVER
FLOWER BED (TYP.)
COLUMN (TYP.)
PAVILION
ELECTRICAL
TRENCH
PSFP - 2
SSFP - 17
PSFP - 1
SSFP - 17
PSFP - 2
PSFP - 1
SSFP - 18
LIGHT SWITCH
(TYP.)
2" ROUND SCH. 40 PVC
CONDUIT
10 10
16 25
21 2422
AutoCAD SHX Text
ENL1
AutoCAD SHX Text E-104
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text 1:100
AutoCAD SHX Text
CWH III
AutoCAD SHX Text
AutoCAD SHX Text E-102
AutoCAD SHX Text
YORK COUNTY
AutoCAD SHX Text Dept. of Public Works
AutoCAD SHX Text 105 Service Drive
AutoCAD SHX Text Post Office Box 532
AutoCAD SHX Text Yorktown, Virginia 23690-0532
AutoCAD SHX Text
(757) 890-3800 FAX: 890-3801
AutoCAD SHX Text Revisions/Comments/Notes
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 04/10/2026
AutoCAD SHX Text
ENL2
E-102
GH
T
SH
ED
P
A
VI
LI
O
N A
N D
S
TA
GE
A
W N
IN
G
EL
EC
TR
IC
A L
PO
W
ER
P
A N
EL
S
CH
ED
U
LE
S
P:
\M y Pi ct ur es \C ou nt y Lo go _1
0x
0.
pn g
NOTES (THIS SCHEDULE ONLY):
1. EXISTING ELECTRICAL PANEL SHOWN FOR REFERENCE PURPOSE ONLY.
2. EXISTING ELECTRICAL PANEL LOCATED WITHIN FREIGHT SHED. EXISTING ELECTRICAL PANEL IS FED FROM PANEL "F".
3. PANEL SCHEDULE INFORMATION IS BASED ON AVAILABLE RECORDS AND MAY NOT REFLECT CURRENT FIELD CONDITIONS. CIRCUIT NAMES, LOADS, AND DESIGNATIONS MAY BE INACCURATE OR NO LONGER IN SERVICE. CONTRACTOR SHALL FIELD VERIFY ALL CIRCUITS AND TRACE AS REQUIRED PRIOR TO
ANY MODIFICATIONS OR CONNECTIONS.
NOTES (THIS SCHEDULE ONLY):
1. EXISTING BREAKERS 2, 4, 6, AND 8, 10, 12 TO BE USED FOR NEW SUBFED PANELS. THESE SUBFED PANELS ARE ASSOCIATED WITH THE FREIGHT SHED
PAVILION AND STAGE AWNING.
2. EXISTING ELECTRICAL PANEL LOCATED WITHIN FREIGHT SHED AUXILIARY BUILDING ELECTRICAL ROOM. EXISTING ELECTRICAL PANEL IS FED FROM PANEL "F".
3. PANEL SCHEDULE INFORMATION IS BASED ON AVAILABLE RECORDS AND MAY NOT REFLECT CURRENT FIELD CONDITIONS. CIRCUIT NAMES, LOADS, AND DESIGNATIONS MAY BE INACCURATE OR NO LONGER IN SERVICE. CONTRACTOR SHALL FIELD VERIFY ALL CIRCUITS AND TRACE AS REQUIRED PRIOR TO
ANY MODIFICATIONS OR CONNECTIONS.
NOTES (THIS SCHEDULE ONLY):
1. ELECTRICAL PANEL SHOWN FOR REFERENCE PURPOSE ONLY.
2. EXISTING ELECTRICAL PANEL LOCATED WITHIN FREIGHT SHED AUXILLARY BUILDING MECHANICAL ROOM. EXISTING ELECTRICAL PANEL IS FED FROM
PANEL "PS".
3. EXISTING PANEL SCHEDULE INFORMATION IS BASED ON AVAILABLE RECORDS AND MAY NOT REFLECT CURRENT FIELD CONDITIONS. CIRCUIT NAMES, LOADS, AND DESIGNATIONS MAY BE INACCURATE OR NO LONGER IN SERVICE. CONTRACTOR SHALL FIELD VERIFY ALL CIRCUITS AND TRACE AS REQUIRED
PRIOR TO ANY MODIFICATIONS OR CONNECTIONS.
NOTES (THIS SCHEDULE ONLY):
1. NEW SUBFED ELECTRICAL PANEL THAT SERVES NEW STAGE AWNING. SEE SHEET E-102 FOR LOCATION OF NEW PANEL.
2. NEW ELECTRICAL PANEL TO BE FED FROM PANEL "F2" BREAKER 2, 4, AND 6.
3. PARENTHESES INDICATE EQUIPMENT LOCATION WITHIN THE ELECTRICAL PANELS SERVING THE ASSOCIATED STRUCTURE.
4. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE "PROJECT SPECIFICATIONS" ON SHEETS G-002.
NOTES (THIS SCHEDULE ONLY):
1. NEW SUBFED ELECTRICAL PANEL THAT SERVES NEW PAVILION. SEE SHEET E-102 FOR LOCATION OF NEW PANEL.
2. NEW ELECTRICAL PANEL TO BE FED FROM PANEL "F2" BREAKER 8, 10, AND 12.
3. PARENTHESES INDICATE EQUIPMENT LOCATION WITHIN THE ELECTRICAL PANELS SERVING THE ASSOCIATED STRUCTURE.
4. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE "PROJECT SPECIFICATIONS" ON SHEETS G-002.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CWH III
AutoCAD SHX Text
AutoCAD SHX Text E-103
AutoCAD SHX Text
YORK COUNTY
AutoCAD SHX Text Dept. of Public Works
AutoCAD SHX Text 105 Service Drive
AutoCAD SHX Text Post Office Box 532
AutoCAD SHX Text Yorktown, Virginia 23690-0532
AutoCAD SHX Text
(757) 890-3800 FAX: 890-3801
AutoCAD SHX Text Revisions/Comments/Notes
AutoCAD SHX Text Date
AutoCAD SHX Text No.
EXIST ELECTRICAL
PANEL "F2"
NEW SUBFED
ELECTRICAL
PANEL "SSFP"
NEW SUBFED
ELECTRICAL
PANEL "PSFP"
FR
EI
GH
T
SH
ED
P
A
VI
LI
O
N A
N D
S
TA
GE
A
W N
IN
G
EL
EC
TR
IC
A L
EL
EC
TR
IC
A L
D
ET
A
IL
S
ENLARGED PLAN - ENL1
SCALE: 1/2" = 1'-0"
ELECTRICAL
ROOM
E-104
ELECTRICAL ROOM - SECTION VIEW (1)
SCALE: 3/4" = 1'-0"
CONDUIT UP TO CEILING;TO EXIST.
ELECTRICAL PANEL "F"
EXIST. LIGHT FIXTURE
CONDUIT UP TO CEILING
CONDUIT UP TO JUNCTION BOX
QUADRUPLEX EXTERIOR
RECEPTACLE
NOTES:
1. CONTRACTOR SHALL INSTALL ONE (1) SUBFED ELECTRICAL PANEL. MOUNT PANEL AT HEIGHT REQUIRED TO FACILITATE PROPER CONNECTION TO EXISTING ELECTRICAL PANEL "F2". SEE SHEET E-103 FOR NEW AND EXISTING ELECTRICAL SCHEDULES
ASSOCIATED WITH THIS WORK.
2. CONTRACTOR SHALL INSTALL ONE (1) SUBFED ELECTRICAL PANEL. MOUNT PANEL AT HEIGHT REQUIRED TO FACILITATE PROPER CONNECTION TO EXISTING ELECTRICAL PANEL "F2". SEE SHEET E-103 FOR NEW AND EXISTING ELECTRICAL SCHEDULES
ASSOCIATED WITH THIS WORK.
3. CONTRACTOR TO INSTALL 3/4" FIRE RATED PLYWOOD BACKING BEHIND SUBFED ELECTRICAL PANELS AS REQUIRED. PLYWOOD TO BE PAINTED WITH FIRE-RETARDANT PAINT. FINISH COLOR TO MATCH ADJACENT SURFACES.
4. CONTRACTOR TO INSTALL ONE (1) ELECTRICAL WIREWAY TROUGH 24" AFF. SEE "ENLARGED PLAN - ENL3" ON SHEET E-105 FOR ADDITIONAL INFORMATION.
5. CONTRACTOR SHALL CORE DRILL FIVE (5) 2" ROUND OPENINGS INTO THE EXISTING WALL AS REQUIRED TO ACCOMMODATE INSTALLATION OF FVE (5) 2" CONDUIT PENETRATIONS. CAREFULLY REMOVE ONLY THE PORTION OF WALL NECESSARY FOR INSTALLATION OF NEW SLEEVES AND CONDUITS WITHOUT DAMAGING SURROUNDING STRUCTURE. SEE "ENLARGED PLAN - EL3" ON SHEET E-105 FOR ADDITIONAL INFORMATION REGARDING PENETRATIONS.
6. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE"PROJECT SPECIFICATIONS" ON SHEET G-002.
7. ALL ITEMS INDICATED AS EXISTING SHALL REMAIN UNLESS OTHERWISE NOTED.
CHRISTMAS TREE JUNCTION BOX
(HAND-OFF-AUTO CONTROL BOX)
PHOTO CONTROL BOX
FOR EXTERIOR LIGHTING
RECEPTACLE
SEE NOTE 3
NOTES:
1. NEW SUBFED ELECTRICAL PANELS "SSFP" AND "PSFP" TO BE INSTALLED VERTICALLY, SIDE BY SIDE. SEE "ELECTRICAL ROOM - SECTION VIEW (1)" ON THIS SHEET FOR CLARIFICATION.
2. CONTRACTOR SHALL INSTALL TWO (2) SUBFED ELECTRICAL PANELS. MOUNT PANEL AT HEIGHT REQUIRED TO FACILITATE PROPER CONNECTION TO EXISTING ELECTRICAL PANEL "F2". SEE SHEET E-103 FOR NEW
AND EXISTING ELECTRICAL SCHEDULES ASSOCIATED WITH THIS WORK.
3. CONTRACTOR TO INSTALL ONE (1) ELECTRICAL WIREWAY TROUGH 24" AFF.
4. PROVIDE CONDUIT AND ELECTRICAL WIRING FROM STAGE AWNING AND PAVILION TO NEW SUBFED PANELS AS SHOWN.
5. CONTRACTOR SHALL PROVIDE FEEDER CONDUCTORS, INCLUDING EQUIPMENT GROUNDING CONDUCTOR, FROM EXISTING PANEL "F2" TO NEW SUBFED PANELS. MAINTAIN ISOLATED NEUTRAL AND GROUND IN
SUBPANELS.
6. CONTRACTOR TO FIRESTOP ALL WALL PENETRATIONS IN RATED ASSEMBLIES WITH APPROVED MATERIALS.
7. LABEL ALL NEW PANELS, CIRCUITS, AND ASSOCIATED EQUIPMENT IN ACCORDANCE WITH PROJECT REQUIREMENTS. SEE SHEET E-103 FOR NEW AND EXISTING ELECTRICAL SCHEDULES ASSOCIATED WITH THIS
WORK.
8. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE "PROJECT SPECIFICATIONS" ON SHEET G-002.
9. ALL ITEMS INDICATED AS EXISTING SHALL REMAIN UNLESS OTHERWISE NOTED.
10. NOT ALL ITEMS SHOWN FOR CLARITY. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND ROUTING PRIOR TO INSTALLATION.
DUPLEX INTERIOR RECEPTACLE
STAGE AWNING SUPPORT
COLUMNS (TYP.)
FIVE (5) 2" ROUND
CONDUIT; SEE NOTE 4SEE NOTES 1 AND 2
STAGE AWNING
OVERHANG
EXIST ELECTRICAL
PANEL "F2"
CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK
SCALE: NTS
WIDTH VARIES
DEPTH
VARIES
1'-0"
DETECTABLE WARNING TAPE
SUITABLE BACKFILL
3" THICK A3 CONCRETE
1/2" MIN. TO 3/4" MAX. VA #10
OR SAND SETTING BED
2 3/8" UNIT PAVERS WITH SAND JOINTS
(NEW AND/OR EXISTING)
NOTES:
1. CONTRACTOR TO INSTALL CONDUIT CENTERED IN TRENCH WITH A MINIMUM OF 3" CLEARANCE ON EACH SIDE.
2. IF TRENCH INCLUDES MULTIPLE CONDUIT INSTALL CONDUITS PARALLEL AND CENTERED IN TRENCH WITH A MINIMUM OF 3" CLEARANCE ON EACH SIDE AND A MINIMUM OF 3" SEPARATION BETWEEN CONDUITS.
3. INSTALL DETECTABLE WARNING TAPE 12" ABOVE CONDUIT.
4. BACKFILL REMAINING TRENCH WITH APPROVED MATERIAL IN LIFTS NOT EXCEEDING 8", COMPACT SOIL TO 95% STANDARD PROCTOR DENSITY. RESTORE SURFACE TO MATCH EXISTING GRADE AND CONDITIONS
UNLESS OTHERWISE NOTED.
5. EXISTING BRICK PAVERS, SAND, BACKFILL MAY BE REUSED WHERE FEASIBLE. AREAS DISTURBED BY TRENCH CONSTRUCTION MAY REQUIRE NEW BRICK PAVERS, SAND, AND BACKFILL OR REINSTALLATION OF EXISTING PAVERS, SAND, AND BACKFILL. COORDINATE WITH SITE DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DETAIL.
6. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE"PROJECT SPECIFICATIONS" ON SHEET G-002.
CONDUIT TRENCH DETAIL - BELOW EARTH
SCALE: NTS
WIDTH VARIES
DEPTH
VARIES
1'-0"
DETECTABLE WARNING TAPE
SUITABLE BACKFILL
4" MIN
NOTES:
1. CONTRACTOR TO INSTALL CONDUIT CENTERED IN TRENCH WITH A MINIMUM OF 3" CLEARANCE ON EACH SIDE.
2. IF TRENCH INCLUDES MULTIPLE CONDUIT INSTALL CONDUITS PARALLEL AND CENTERED IN TRENCH WITH A MINIMUM OF 3" CLEARANCE ON EACH SIDE AND A MINIMUM OF 3" SEPARATION BETWEEN CONDUITS.
3. INSTALL DETECTABLE WARNING TAPE 12" ABOVE CONDUIT.
4. BACKFILL REMAINING TRENCH WITH APPROVED MATERIAL IN LIFTS NOT EXCEEDING 8", COMPACT SOIL TO 95% STANDARD PROCTOR DENSITY. RESTORE SURFACE TO MATCH EXISTING GRADE AND CONDITIONS UNLESS OTHERWISE NOTED.
5. IN MOWED AREAS PLACE TOPSOIL, FERTILIZER, SEED AND MULCH. COORDINATE WITH SITE DRAWINGS FOR APPROPRIATE SOD REQUIRED FOR THE PROJECT AREA AND ADDITIONAL INFORMATION NOT SHOWN ON THIS DETAIL.
6. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE"PROJECT SPECIFICATIONS" ON SHEET G-002.
AV COMMUNICATION CONDUIT
F2 - 2,4,6
F2 - 8,10,12
2" SCH. 40 PVC CONDUIT (TYP.)
F2 - 41
F2 - 27,29
F2 - 39
PANEL F
F2 - 31, 33
CONDUIT
CONDUIT
SEE NOTE 5
24"
FIVE (5) 2" SCH. 40
PVC CONDUIT; DOWN
TO TRENCH
DUPLEX INTERIOR
RECEPTACLE
24x6x6 ELECTRICAL
WIREWAY TROUGH
24x6x6 ELECTRICAL
WIREWAY TROUGH
AutoCAD SHX Text
ENL3
AutoCAD SHX Text E-105
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CWH III
AutoCAD SHX Text
AutoCAD SHX Text E-104
AutoCAD SHX Text
YORK COUNTY
AutoCAD SHX Text Dept. of Public Works
AutoCAD SHX Text 105 Service Drive
AutoCAD SHX Text Post Office Box 532
AutoCAD SHX Text Yorktown, Virginia 23690-0532
AutoCAD SHX Text
(757) 890-3800 FAX: 890-3801
AutoCAD SHX Text Revisions/Comments/Notes
AutoCAD SHX Text Date
AutoCAD SHX Text No.
GH
T
SH
ED
P
A
VI
LI
O
N A
N D
S
TA
GE
A
W N
IN
G
EL
EC
TR
IC
A L
EL
EC
TR
IC
A L
D
ET
A
IL
S (2
ENLARGED PLAN - ENL3
SCALE: NTS
ELECTRICAL ROOM - SECTION VIEW (2)
SCALE: NTS
NOTES:
1. CONTRACTOR TO INSTALL ONE (1) 24x6x6 ELECTRICAL WIREWAY TROUGH 24" AFF. CONTRACTOR TO SECURE WIREWAY TO THE EXISTING SIDING PER MANUFACTURERS RECOMMENDATIONS. CONTRACTOR TO PROVIDE ALL NECESSARY MOUNTING
HARDWARE, BUSHINGS, AND FITTINGS TO COMPLETE INSTALLATION.
2. CONTRACTOR SHALL CORE DRILL FIVE (5) 2" ROUND OPENINGS INTO THE EXISTING WALL AS REQUIRED TO ACCOMMODATE INSTALLATION OF FVE (5) 2" CONDUIT PENETRATIONS. CAREFULLY REMOVE ONLY THE PORTION OF WALL NECESSARY FOR
INSTALLATION OF NEW SLEEVES AND CONDUITS WITHOUT DAMAGING SURROUNDING
3. CONTRACTOR TO INSTALL FIVE (5) 2" CONDUITS THROUGH INDIVIDUAL SLEEVES AT WALL PENETRATION. SLEEVES SHALL BE SIZED TO ALLOW REQUIRED CLEARANCE AND SHALL BE PROPERLY ALIGNED AND SECURED.
4. CONTRACTOR TO SEAL THE ANNULAR SPACE BETWEEN CONDUITS AND SLEEVES WITH APPROVED WATERPROOF AND FIRE-RATED SEALANT AS REQUIRED. PROVIDE WATERTIGHT SEAL AT EXTERIOR SIDE TO PREVENT MOISTURE INTRUSION.
5. CONTRACTOR TO COORDINATE PENETRATION LOCATIONS WITH STRUCTURAL AND ARCHITECTURAL ELEMENTS. DO NOT CUT OR COMPROMISE FOUNDATION. VERIFY EXACT ROUTING AND CONDITIONS IN FIELD PRIOR TO INSTALLATION.
6. CONTRACTOR TO SECURELY ATTACH ALL 2" SCH. 40 PVC CONDUIT TO THE EXTERIOR WALL USING APPROPRIATE CORROSION-RESISTANT STRAPS, CLAMPS, OR HANGERS SPACED PER CODE AND MANUFACTURER’S RECOMMENDATIONS. CONDUIT SHALL
BE ALIGNED AND SUPPORTED TO PREVENT SAGGING OR MOVEMENT.
7. NOT ALL CONDUIT IS SHOWN WITHIN THIS AREA FOR CLARITY. SEE "ELECTRICAL ROOM SECTION VIEW (2)" ON THIS SHEET FOR ADDITIONAL INFORMATION.
8. FOR TRENCHING DEPTH AND SPACING SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" AND "CONDUIT TRENCH DETAIL - BELOW EARTH" ON SHEET E-104 FOR ADDITIONAL TRENCH REQUIREMENTS.
9. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE"PROJECT SPECIFICATIONS" ON SHEET G-002.
E-105
24x6x6 ELECTRICAL WIREWAY TROUGH
24"
FIVE (5) 2" SCH. 40 PVC CONDUIT; DOWN TO TRENCH
DUPLEX INTERIOR RECEPTACLE
EXTERIOR WALL OF ELECTRICAL ROOM
2" SCH. 40 PVC CONDUIT; TO NEW
SUBFED PANELS "SSFP" AND "PSFP"
SEE NOTES 2, 3, 4, AND 5
NOTES:
1. CONTRACTOR TO INSTALL ONE (1) 24x6x6 ELECTRICAL WIREWAY TROUGH 24" AFF. CONTRACTOR TO SECURE WIREWAY TO THE EXISTING SIDING PER MANUFACTURERS RECOMMENDATIONS. CONTRACTOR TO PROVIDE ALL NECESSARY MOUNTING HARDWARE, BUSHINGS, AND FITTINGS TO COMPLETE INSTALLATION.
2. CONTRACTOR SHALL CORE DRILL FIVE (5) 2" ROUND OPENINGS INTO THE EXISTING WALL AS REQUIRED TO ACCOMMODATE INSTALLATION OF FVE (5) 2" CONDUIT PENETRATIONS. CAREFULLY REMOVE ONLY THE PORTION OF WALL NECESSARY FOR INSTALLATION OF NEW SLEEVES AND CONDUITS WITHOUT DAMAGING SURROUNDING STRUCTURE.
3. CONTRACTOR TO INSTALL FIVE (5) 2" CONDUITS THROUGH INDIVIDUAL SLEEVES AT WALL PENETRATION. SLEEVES SHALL BE SIZED TO ALLOW REQUIRED CLEARANCE AND SHALL BE PROPERLY ALIGNED AND SECURED.
4. CONTRACTOR TO SEAL THE ANNULAR SPACE BETWEEN CONDUITS AND SLEEVES WITH APPROVED WATERPROOF AND FIRE-RATED SEALANT AS REQUIRED. PROVIDE WATERTIGHT SEAL AT EXTERIOR SIDE TO PREVENT
MOISTURE INTRUSION.
5. CONTRACTOR TO COORDINATE PENETRATION LOCATIONS WITH STRUCTURAL AND ARCHITECTURAL ELEMENTS. DO NOT CUT OR COMPROMISE FOUNDATION. VERIFY EXACT ROUTING AND CONDITIONS IN FIELD PRIOR
TO INSTALLATION.
6. CONTRACTOR TO ENSURE THAT AV COMMUNICATION CONDUIT SHOULD BE LEFT EMPTY. CONTRACTOR SHALL PROVIDE PULL STRING WITHIN CONDUIT AND SECURE AT BOTH ENDS FOR FUTURE USE. OWNER TO HIRE
3RD PARTY CONTRACTOR TO INSTALL CAT5E WIRING.
7. CONTRACTOR TO SECURELY ATTACH ALL 2" SCH. 40 PVC CONDUIT TO THE EXTERIOR WALL USING APPROPRIATE CORROSION-RESISTANT STRAPS, CLAMPS, OR HANGERS SPACED PER CODE AND MANUFACTURER’S RECOMMENDATIONS. CONDUIT SHALL BE ALIGNED AND SUPPORTED TO PREVENT SAGGING OR MOVEMENT.
8. FOR TRENCHING DEPTH AND SPACING SEE "CONDUIT TRENCH DETAIL - BELOW WALKWAY/SIDEWALK" AND "CONDUIT TRENCH DETAIL - BELOW EARTH" ON SHEET E-104 FOR ADDITIONAL TRENCH REQUIREMENTS.
9. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE"PROJECT SPECIFICATIONS" ON SHEET G-002.
24"
DEPTH VARIES
2" MIN (TYP.)
6"
24"
ELECTRICAL WIREWAY TROUGH
(SEE NOTES 2, 3, 4, AND 5)
2" SCH. 40 PVC CONDUIT (TYP.)
FIVE (5) 2" SCH. 40 PVC
CONDUIT; DOWN TO TRENCH
AV COMMUNICATION
CONDUIT; SEE NOTE 6
EXTERIOR WALL OF
ELECTRICAL ROOM (TYP.)
EXIST. SIDING
EXIST. BRICK FOUNDATION
ELECTRICAL PULL BOX DETAIL
SCALE: NTS
2 3/8" UNIT PAVERS
WITH SAND JOINTS
1/2" MIN. TO 3/4" MAX. VA
#10 OR SAND SETTING BED
3" THICK A3 CONCRETE
6"
6" (TYP.)
6"x6" COLLAR (TYP. ALL AROUND)
FIVE (5) 2" SCH. 40 PVC CONDUIT AV COMMUNICATION CONDUIT
2" SCH. 40 PVC CONDUIT; TO WIREWAY
ON EXTERIOR OF ELECTRICAL ROOM
ELECTRICAL PULL BOX
ELECTRICAL PULL BOX LID
NOTES:
1. CONTRACTOR TO INSTALL ONE (1) ELECTRICAL PULL BOX. CONTRACTOR TO SET PULL BOX ON STONE BASE, ENSURING THE UNIT IS LEVEL AND THE TOP OF FRAME IS FLUSH WITH FINAL FINISHED GRADE.
2. CONTRACTOR TO INSTALL 6" OF COMPACTED CRUSHED STONE BASE (VDOT #21A OR APPROVED EQUAL) UNDERNEATH ELECTRICAL PULL BOX.
3. CONTRACTOR TO PROVIDE A 6"x6" CAST-IN-PLACE CONCRETE COLLAR AROUND THE ELECTRICAL PULL BOX. TOP OF COLLAR SET APPROXIMATELY 3" BELOW FINISHED GRADE TO ACCOMMODATE BRICK AND SAND SETTING BED. COLLAR SHALL SIT ON
COMPACTED CRUSHED STONE BASE (VDOT #21A OR APPROVED EQUAL) .
4. CONTRACTOR TO DOWEL NEW CONCRETE COLLAR INTO EXISTING CONCRETE WALKWAY/SIDEWALK BASE USING #4 REINFORCING BARS AT 12" O.C.. DOWELS TO BE DRILLED AND EPOXIED A MINIMUM OF 4" INTO EXISTING CONCRETE. EXTEND DOWELS INTO NEW CONCRETE COLLAR TO PROVIDE POSITIVE CONNECTION BETWEEN NEW AND EXISTING WORK.
5. EXISTING BRICK PAVERS, SAND, BACKFILL MAY BE REUSED WHERE FEASIBLE. AREA DISTURBED BY ELECTRICAL PULL BOX CONSTRUCTION MAY REQUIRE NEW BRICK PAVERS, SAND, AND BACKFILL OR REINSTALLATION OF EXISTING PAVERS, SAND, AND BACKFILL. COORDINATE WITH SITE DRAWINGS FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS DETAIL.
6. FOR MATERIAL SELECTIONS AND DETAILED PRODUCT INFORMATION SEE"PROJECT SPECIFICATIONS" ON SHEET G-002.
6" COMPACTED CRUSHED STONE BASE
6"x6" COLLAR (TYP.
ALL AROUND)
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CWH III
AutoCAD SHX Text
AutoCAD SHX Text E-105
AutoCAD SHX Text
YORK COUNTY
AutoCAD SHX Text Dept. of Public Works
AutoCAD SHX Text 105 Service Drive
AutoCAD SHX Text Post Office Box 532
AutoCAD SHX Text Yorktown, Virginia 23690-0532
AutoCAD SHX Text
(757) 890-3800 FAX: 890-3801
AutoCAD SHX Text Revisions/Comments/Notes
AutoCAD SHX Text Date
AutoCAD SHX Text No.
| Sheets and Views |
| Freight Shed_Electrical Work_04.08.26-Cover Sheet |
| Freight Shed_Electrical Work_04.08.26-General Notes & Specs |
| Freight Shed_Electrical Work_04.08.26-Site Plan - Power Demo |
| Freight Shed_Electrical Work_04.08.26-Site Plan - Power Construction |
| Freight Shed_Electrical Work_04.08.26-Power Panel Schedules |
| Freight Shed_Electrical Work_04.08.26-Electrical Details |
| Freight Shed_Electrical Work_04.08.26-Electrical Details (2) |