ELECTRICAL EQUIPMENT SCHEDULE.pdf

PDF 92 KB Posted

Attached to
Z2DA--PROJECT # 528A4-21-210 Kitchen Equipment Site Prep BATAVIA VAMC
Solicitation number
36C24225B0043
Issued by

About this file

The document is an Electrical Equipment Connections Schedule detailing electrical specifications for two kitchen equipment items: a dishwasher and a booster heater. The schedule provides technical details including voltage (208V), amperage (52.15 for dishwasher, 75 for booster heater), circuit breaker ratings (60 and 100 amps respectively), and electrical connection requirements. The schedule specifies copper conductors, galvanized rigid steel conduit, and NEMA 4X lockable disconnect switches, both to be mounted on a stainless steel uni-strut. Additional notes emphasize conductor and conduit specifications, including maximum flexible conduit length of 4 feet and requirements for labeling disconnect switches with identifying tags.

View the file

Other files

File Type Posted
36C24225B0043 0002.docx DOCX document
REQUEST FOR INFORMATION.docx DOCX document
site visit - sign in sheet.pdf PDF
B 2 drawings binder.pdf PDF
36C24225B0043 0001.docx DOCX document
36C24225B0043_1.docx DOCX document
Schedules and Requirements.zip ZIP file
P07 - WAGE DETERMINATION.pdf PDF
Specifications.zip ZIP file
LIMITATIONS OF SUBCONTRACTING CERTIFICATE 852.219-75.docx DOCX document
BUY AMERICAN ACT CERTIFICATE 52.225-2.docx DOCX document
Panel Schedule.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FULL

LOAD

CIRCUIT

BREAKER

DISHWASHER DW 208 52.15 60 - 3/3

NEW KITCHEN

EQUIPMENT

PANEL

(3) #4 AWG &

(1) #10 AWG

GROUND

1-1/2"

GALVANIZED

RIDGID STEEL

60-AMPS,

NEMA-4X,

LOCKABLE

1,2,3,4,5

BOOSTER

HEATER

BH 208 75 100 27 3/3

NEW KITCHEN

EQUIPMENT

PANEL

(3) #2 AWG &

(1) #8 AWG

GROUND

1-1/2"

GALVANIZED

RIDGID STEEL

100-AMPS,

NEMA 4X,

LOCKABLE

1,2,3,4,5

ELECTRICAL EQUIPMENT CONNECTIONS SCHEDULE

AMPS

1. ALL CONDUCTORS AND GROUND CONDUCTORS SHALL BE COPPER, REFER TO ELECTRICAL SPECIFICATIONS. AWG IS AMERICAN WIRE GUAGE.

2. MOUNT DISCONNECT SWITCHES NEXT TO COLUMN ON STAINLESS STEEL UNI-STRUT PROVIDED BY THIS CONTRACT.

3. STRANDED CONDUCOTRS AND FLEXIBLE GALVANIZED CONDUIT FROM DISCONNECT SWITCHES TO EQUIPMENT SHALL NOT EXCEED 4 FEET IN LENGTH.

4. REFER TO ELECTRICAL SPECIFICATIONS 260511 SECTION 1.11 FOR LABELING OF DISCONNECT SWITCHES.

5. PROVIDE A PLASTIC RIDGID BLACK NAME TAG WITH RECESSED WHITE LETTERS ON THE DISCONNECT SWITHES TO IDENTIFY WHAT EQUIPEMNT THEY

SERVE.

EQUIPMENT DESIGNATION VOLTS kW

PHASE /

WIRES

FED FROM

PANEL

CONDUCTORS CONDUIT

DISCONNECT

SWITCH

RATING

NOTES

NOTES: