Z2DA--PROJECT # 528A4-21-210 Kitchen Equipment Site Prep BATAVIA VAMC
Solicitation number
36C24225B0043
Issued by

About this file

This document is a detailed electrical panel schedule for a Kitchen Equipment Panel at the Batavia VA Medical Center. The panel is a 208Y/120-volt, 3-phase, 4-wire surface-mounted panel with a 200-amp main circuit breaker, fed from Panel-P in Room G22C. The panel has a 22 KAIC rating and includes specifications for circuit breakers, with multiple spare circuits and dedicated circuits for a dishwasher and booster heater.

Key technical specifications include a NEMA-4X stainless steel surface mount design with a lockable door, mounting on stainless steel uni-strut (no wood), and a feeder from the basement panel consisting of (4) 3/0 and (1) #6 AWG ground wire in a 2-1/2" galvanized rigid steel conduit. The panel schedule notes require circuit breakers for all spare positions, the dishwasher, and booster heater, with a panel frame rated at 225 amps but a main circuit breaker limited to 200 amps. Additionally, the document specifies a black plastic nameplate with recessed white letters to be affixed to the panel.

View the file

Other files

File Type Posted
36C24225B0043 0002.docx DOCX document
REQUEST FOR INFORMATION.docx DOCX document
site visit - sign in sheet.pdf PDF
B 2 drawings binder.pdf PDF
36C24225B0043 0001.docx DOCX document
ELECTRICAL EQUIPMENT SCHEDULE.pdf PDF
36C24225B0043_1.docx DOCX document
Schedules and Requirements.zip ZIP file
P07 - WAGE DETERMINATION.pdf PDF
Specifications.zip ZIP file
LIMITATIONS OF SUBCONTRACTING CERTIFICATE 852.219-75.docx DOCX document
BUY AMERICAN ACT CERTIFICATE 52.225-2.docx DOCX document
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CKT. Amps SERVING SERVING Amps CKT.

1 20 SPARE SPARE 20 2

3 20 SPARE SPARE 20 4

5 20 SPARE SPARE 20 6

7 - - 8

9 - - 10

11 - - 12

13 - - 14

15 - - 16

17 - - 18

19 - 20

21 - 22

23 - 24

25 26

27 28

29 30

H. PROVIDE A PLASTIC NAMEPLATE AFFIXED TO THE PANEL WITH NAME OF THE PANEL THAT IS BLACK WITH

RECESSED WHITE LETTERS.

G. REFER TO ELECTRICAL SPECIFICATIONS 260511 SECTION 1.11 FOR LABELING OF THE PANEL. VA COR TO

PROVIDE NAME FOR NEW PANEL

ELECTRICAL PANEL GENERAL NOTES:

B. 200-AMP, 3-POLE, 4-WIRE CIRCUIT BREAKER PROVIDED ON PANEL-P.

A. FEEDER FROM BASEMENT PANEL-P TO THIS PANEL IS: (4) 3/0, (1) #6 AWG GROUND IN 2-1/2" GALVANIZED

RIDGID STEEL (GRS) CONDUIT. AWG IS AMERICAN WIRE GUAGE. ALL CONDUCTORS AND GROUND WIRES SHALL

BE COPPER, REFER TO ELECTRICAL SPECIFICATIONS.

E. PROVIDE PULL BOXES AS NEEDED FOR FEEDER. FOR BIDDING PURPOSES THE CONTRACTOR SHALL USE

MINIMUM OF TWO PULL BOXES FOR EASE OF INSTALLATION (GALVANIZED) FOR CORROSION RESISTANCE.

F. PROVIDE TYPE D PANEL SCHEDULE INSIDE THE DOOR.

KITCHEN EQUIPMENT PANEL

22 KAIC RATING

F. PANEL FRAME IS 225-AMPS HOWEVER THE MAIN CIRCUIT BREAKER (MCB) SHALL BE 200-AMPS. THE MCB

SHALL NOT BE ATTACHED TO THE (3) BUS IN THE THE PAENL AND CONNECTED TO THE BUS ONLY VIA CABLES.

THE MCB SHALL BE A TRUE MAIN CIRCUIT BREKAER AND NOT CIRCUIT BREAKERS BOLTED TOGETHER

CONNECTED DIRECTLY TO THE BUS.

E. CIRCUIT BREAKERS SHALL BE COMPATIBLE WITH PANEL. PROVIDE CIRCUIT BREAKERS FOR ALL SPARES, DISHWASHER, BOOSTER HEATER AND ANY EQUIPMENT ON THE PANEL.

C. PANEL SHALL BE NEMA-4X STAINLESS STEEL SURFACE MOUNT AND PANEL DOOR SHALL BE LOCKABLE

D. PROVIDE STAINLESS STEEL UNI-STRUT TO MOUNT ON WALLS. NO WOOD FOR MOUNTING PANEL, AVOID TRIP

HAZARDS ON FLOOR (PROVIDE SHOP DRAWING FOR VA COR APPROVAL).

208Y/120-VOLTS, 3-PHASE, 4-WIRE SURFACE MOUNTED PANEL, 200-AMPS MAIN CIRCUIT BREAKER

FED FROM PANEL-P, ROOM G22C, BREAKER #2 (200-AMPS)

SPARE

DISHWASHER BOOSTER HEATER60