This is an Electrical One Line Diagram and Panel Schedule document prepared by SGM Engineering for Volusia County Government's DeLand Courthouse Central Energy Plant (CEP) Upgrades project. The electrical design, prepared by engineer Justin L. Mundell (FL License No. 70700), outlines the power distribution system required to support the chiller system replacement and associated mechanical and electrical upgrades at the courthouse facility located at 101 N. Alabama Avenue, DeLand, FL 32724. The diagram specifies two main distribution panels (MDP-A and MDP-B), each rated at 277/480V, 3-phase, 4-wire service with 3000-ampere capacity. MDP-A carries a connected load of 3,019.5 kVA with a demand load of 2,189.8 kVA (2,635 amps), while MDP-B carries a connected load of 2,946.9 kVA with a demand load of 2,045.7 kVA (2,462 amps). The system includes multiple circuit breakers ranging from 60 amperes to 1,200 amperes supporting lighting, receptacles, HVAC components, chillers, and emergency mechanical systems. The design document is issued as 100% Construction Documents dated November 27, 2024, with engineering stamps indicating professional certification and compliance with Florida engineering standards.

The electrical design incorporates comprehensive load calculations for both panels, with specific demand factors applied to lighting (1.0), receptacles (0.5), computer/receptacle loads (0.65), HVAC systems (0.9), and emergency mechanical systems (0.7). Technical specifications require all feeders to maintain less than 2% total voltage drop and all branch circuits to maintain less than 3% voltage drop in compliance with electrical code standards. The diagram distinguishes between existing systems to remain (indicated in light color) and systems to be removed (indicated in dark color), with coordination requirements across all construction trades. Additional requirements include protection of building systems during construction, maintenance of service continuity, field verification of existing conditions prior to demolition, and wall patching to match existing conditions. The design incorporates surge protection for critical loads and references general notes, symbols, and specifications detailed on sheets E001, E501, and E701 of the construction document set.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SGM

ENGINEERING

5301 Waterford District Dr Miami, Fl. 33126

Tel: 954-421-1944 Fax: 954-421-1944

CA-00006208

Copyright © 2024 SGM Engineering, Inc.

www.sgmengineering.com

Issue: 100% CONSTRUCTION DOCUMENTS 2024-11-27

Project Name:

State Project Number: Drawing File Name:

Scale:

Design By:

Drawn By:

Checked By:

Engineer of Record:

License Number:

Sheet Name:

Sheet Number:

Seal:

JUSTIN L. MUNDELL

FL 70700

N . A

LA

BA

M A

AV

EN

U E

D

EL

AN

D

F L, SGM # 2024-358

STATE OF

ENEIL

ADIROLF

ROFES OI NAS L E N

NGI

E E

C S

RP

5/

/2

:5 5:

A

M

As-shown

C :\U se rs

\ro an

\D oc um en ts \B as em en t H

VA

C

_M &E

_R

_R O

AN

G

5E

SU

.rv t

2024-358

E701

ELECTRICAL ONE LINE

DIAGRAM

Volusia County Government

- Deland Courthouse - CEP Upgrades

VO

LU

SI

A

C O

U N

TY

C

LE

R

K O

F

TH

E C

IR

C

U

IT

C O

U R

T

NO. DESCRIPTION DATE

LIGHTING

LOAD CALCULATIONS

MDP-A

RECEPTACLES

COMP. REC.

HVAC

CHILLER

TOTAL

CONNECTED KVA

213.9 441.3 294.4 1737.5

3019.5

332.4

CONNECTED KVA CONNECTED KVA

1.0 0.5 0.65 0.9

213.9 220.7 191.4 1563.8

2189.8 (2635 AMPS)

LIGHTING

LOAD CALCULATIONS

MDP-B

RECEPTACLES

COMP. REC.

HVAC

CHILLER

TOTAL

CONNECTED KVA

279.9 348.3 171.0

948.6

2946.9

332.4

CONNECTED KVA CONNECTED KVA

1.0 0.5 0.65

0.9

279.9 174.2 11.2

853.7

2045.7 (2462 AMPS)

EMERGENCY

MECHANICAL

66.7 800.0

1.0 0.7

66.7 560.0

GENERAL NOTES:

a. REFER TO GENERAL NOTES AND SYMBOLS ON SHEET E001

b. REFER TO BOOK SPECIFICATIONS.

c. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP

AND ALL BRANCH CRICUITS SHALL HAVE LESS THAN 3% VOLTAGE

DROP.

d. PROTECT BUILDNG SYSTEMS AT ALL TIMES DURING

CONSTRUCTION. MAINTAIN CONTINUITY OF SYSTEMS TO REMAIN.

IF NECESSARY PROVIDE TEMPORARY OR PERMANENT RE-WIRING

TO RECONNECT SYSTEM DEVICES TO THE BUILDING SYSTEMS SO

SERVICES ARE NOT INTERRUPTED DURING CONSTRUCTION.

e. COORDINATE WORK WITH ALL OTHER TRADES BEFORE ANY

ROUGH-INS. FIELD VERIFY EXISTING CONDITIONS PRIOR TO

DEMOLITION.

f. ALL SYMBOLS SHOWN IN "LIGHT" COLOR INDICATE EXISTING TO

REMAIN; NO WORK REQUIRED UNLESS NOTED OTHERWISE.

g. ALL SYMBOLS SHOWN IN "DARK" COLOR INDICATE TO BE

REMOVED, UNLESS NOTED OTHERWISE.

h. PATCH WALLS AFFECTED BY DEMOLITION OR NEW WORK AS

REQUIRED TO MATCH EXISTING CONDITIONS.

AutoCAD SHX Text No. 70700

AutoCAD SHX Text

MDP-A

AutoCAD SHX Text

277/480V, 3PH, 4W 3000A 85 KAIC

AutoCAD SHX Text 250A

AutoCAD SHX Text 225A

AutoCAD SHX Text 800A

AutoCAD SHX Text 800A

AutoCAD SHX Text 200A

AutoCAD SHX Text 150A

AutoCAD SHX Text 300A

AutoCAD SHX Text 400A

AutoCAD SHX Text 600A

AutoCAD SHX Text 800A

AutoCAD SHX Text 225A

AutoCAD SHX Text 400A

AutoCAD SHX Text 60A

AutoCAD SHX Text

CH-1

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text Surge protection

AutoCAD SHX Text To existing load

AutoCAD SHX Text

MDP-B

AutoCAD SHX Text

277/480V, 3PH, 4W 3000A 42 KAIC

AutoCAD SHX Text 400A

AutoCAD SHX Text 225A

AutoCAD SHX Text 800A

AutoCAD SHX Text 400A

AutoCAD SHX Text 400A

AutoCAD SHX Text 400A

AutoCAD SHX Text 300A

AutoCAD SHX Text 300A

AutoCAD SHX Text 150A

AutoCAD SHX Text 1200A

AutoCAD SHX Text 150A

AutoCAD SHX Text 400A

AutoCAD SHX Text 60A

AutoCAD SHX Text

CH-2

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text To existing load

AutoCAD SHX Text Surge protection

AutoCAD SHX Text To existing load

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

SGM

ENGINEERING

5301 Waterford District Dr Miami, Fl. 33126

Tel: 954-421-1944 Fax: 954-421-1944

CA-00006208

Copyright © 2024 SGM Engineering, Inc.

www.sgmengineering.com

Issue: 100% CONSTRUCTION DOCUMENTS 2024-11-27

Project Name:

State Project Number: Drawing File Name:

Scale:

Design By:

Drawn By:

Checked By:

Engineer of Record:

License Number:

Sheet Name:

Sheet Number:

Seal:

JUSTIN L. MUNDELL

FL 70700

N . A

LA

BA

M A

AV

EN

U E

D

EL

AN

D

F L, SGM # 2024-358

STATE OF

ENEIL

ADIROLF

RO FES OI NAS L E N

NGI

E E

C S

RP

5/

/2

:5 5:

A

M

As-shown

C :\U se rs

\ro an

\D oc um en ts \B as em en t H

VA

C

_M &E

_R

_R O

AN

G

5E

SU

.rv t

2024-358

E701

ELECTRICAL PANEL

SCHEDULES

Volusia County Government

- Deland Courthouse - CEP Upgrades

VO

LU

SI

A

C O

U N

TY

C

LE

R

K O

F

TH

E C

IR

C

U

IT

C O

U R

T

NO. DESCRIPTION DATE

AutoCAD SHX Text No. 70700

E501 - ELECTRICAL ONE LINE DIAGRAM.pdf
E701 - ELECTRICAL PANEL SCHEDULES.pdf

File details come from the government source that posted it. Updated .