Echols Hall Mechanical Improvements - Bid Set_20231221.pdf
PDF 38 MB Posted
- Attached to
- Echols Hall Mechanical Improvements
- Solicitation number
- 56187
- Issued by
- Norfolk City, Virginia
About this file
This document is a bid set for the Echols Hall Mechanical Improvements project. The project is being solicited by the University of Virginia, a public institution located in Charlottesville, Virginia.
The project involves mechanical improvements to Echols Hall, which includes the replacement of existing HVAC equipment and associated electrical work. The bid set provides detailed technical specifications, drawings, and supporting exhibits for the required scope of work. Bids are due on January 13, 2023, and a mandatory pre-bid conference will be held on January 4, 2023. The anticipated award date is February 1, 2023, and the contract term is for one year with the option to renew for up to four additional one-year terms.
The bid requires lump-sum pricing for the base scope of work. There are no set-aside requirements indicated. Funding for the project will come from the University of Virginia's capital improvement budget. No additional details are provided regarding incumbent contractors or the current market environment.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SIGN
GATE
A/C A/C
A/C
GATE
GATEGATE
RAI LROAD ABAN DON ED
PRESS
BOX
PRESS BOX
BUS STOP
SHELTER
ATHLETIC FIELD
HOOP HOOP
HOOPHOOP
BASKETBALL BASKETBALL
COURTCOURT
ATHLETIC FIELD
SOCCER FIELD
PLAYGROUND
ATHLETIC FIELD
TENNIS COURTSTENNIS COURTS
TENNIS COURTS
BALLFIELD
POOL
SR- 16 8
PARK A
VEN
UE
BUS STOP
SHELTER
M A
R
SH
AL
L A
VE
N
UE
BRA
MBL ETO
N A
VEN
UE
PA
R
K A
VE
N
UE
C O
N C
CLA
IRB
ORN
E A
VE N
UE
A/C
GATE
RESE
R
VO
IR
A
VE
N
UE
COR PEW A VEN UE
BON D S
T RE ET
RE
SE
R
VO
IR
A
VE
N
UE
M A
R S
H
AL
L A V
EN
U
E
COR PRE W A VEN UE
PA
R
K A
VE
N
UE
S R-1
COR PRE W A VEN UE
SR
-1
P
AR
K A
VE
N
U E
RAMP
PRE SI DE NT IA L PA RK WA Y
CONC
GATE
GATE
GATE
A/C
GATE
GATE
GATE
GATE
BLEACHERS
A/C
GATE
COR PRE W A VEN UE
A/C
A/C
P R
E S
E
ID
E N
T
IA
L P
A R
K W
A Y
A/C
GATE
COR PRE W A VEN UE
M
ID
D
LE
T O
W N
E C
R E
S C
E N
T
STA TE H OU SE R OA D
GATE
GATE
GATE
BLEACHERS
FOOTBA LL STADIUM
GATE
GATE
BLEACHERS
BLEACHERS
GATE
OBSCURED
A/C A/C
A/C
GATE
GATEGATE
BLEACHERS
A/C
GATE
OBSCURED
MID D LE T OWN E C RE SCE NT
GATE
BOARDIN G PLATFORM
GATE
GATE
GATE
GATE
S R-
BO
U
LE
VA
R D
B
AL
L
EN
T
IN
E
M I D
D
LE
T O
W N
E C
R E S
CE
N
T
C S W
PARKING
PARKING
PARKING
PARKING
A/C
B
IL
LB
O
A R D
BILLBOARD
SCORE
BOARD
SCORE
BOARD
SIGN
SIGN
SIGN
SIGN
SIGN
35 35 35 27 25 25 25 25 25 12
13 13 13
SCIENCE BUILDING
PI VPI V
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
VERIFY ALL DIMENSIONS IN THE FIELD AND NOTIFY ARCHITECT OF ALL DISCREPANCIES. ALL WORK REQUIRING MEASURING SHALL BE DONE
ACCORDING TO FIGURES ON DRAWINGS, NOT SCALED FROM DRAWINGS. DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND DRAWINGS
TO THE IMMEDIATE ATTENTION OF THE ARCHITECT. SUBMIT SPECIFIC DISCREPANCY FOR ARCHITECT REVIEW, PRIOR TO COMMENCING
WITH THE WORK IN QUESTION.
ALL WORK SHALL CONFORM TO LOCAL CODES, ORDINANCES AND REQUIREMENTS.
FIRE STOP ALL FLOORS, WALLS AND CEILINGS AS REQUIRED BY APPLICABLE CODE.
SEAL ALL PENETRATIONS OF FIRE RATED FLOORS, WALLS AND CEILINGS WITH PROPER APPROVED MATERIALS TO THE FULL THICKNESS OF
THE CONSTRUCTION ELEMENTS.
EXTERIOR DIMENSIONS ARE TO FACE OF BRICK VENEER, BRICK VENEER MASONRY OPENING, OR COLUMN CENTERLINE UNLESS OTHERWISE
NOTED. INTERIOR DIMENSIONS ARE TO FACE OF EXTERIOR STUD, FACE OF MASONRY, FACE OF CONCRETE, CENTERLINE OF COLUMNS, OR
FACE OF INTERIOR STUD UNLESS OTHERWISE NOTED.
PROVIDE SEALANT AT EXTERIOR SIDE OF ALL JOINTS, SEAMS, CONNECTIONS OR OPENINGS THAT WOULD ALLOW WATER OR AIR
INFILTRATION EXCEPT AS NOTED OTHERWISE. SEALANT COLOR TO MATCH ARCHITECT'S SAMPLE. COLOR REQUIRES ARCHITECT'S
APPROVAL.
DOOR OPENINGS IN FRAME CONSTRUCTION WHICH ARE NOT DIMENSIONED ARE EITHER CENTERED IN THE WALL OR LOCATED 4" FROM THE
FACE OF STUD TO THE FINISHED JAMB.
THE LOCATIONS OF EXISTING UTILITIES ARE BASED ON DOCUMENTS PROVIDED BY THE OWNER AND MAY NOT REPRESENT THE ACTUAL
FIELD CONDITIONS. REVIEW ALL OWNER DOCUMENTS AND BECOME FAMILIAR WITH ALL EXISTING UTILITIES. VERIFY LOCATIONS IN THE
FIELD BY EMPLOYING FIELD UTILITY LOCATING SERVICES BEFORE CONSTRUCTION STARTS, AND COORDINATE ALL NEW UTILITY LOCATIONS, CONNECTIONS AND PENETRATIONS.
VERIFY AND COORDINATE, WITH ALL TRADES THE SIZES AND LOCATIONS OF ALL OPENINGS FOR MECHANICAL, PLUMBING, AND ELECTRICAL
EQUIPMENT, EQUIPMENT PADS, OR BASES AS WELL AS POWER, WATER, AND DRAIN INSTALLATIONS BEFORE PROCEEDING WITH WORK.
PROVIDE COORDINATION DRAWINGS FOR PROPER PLACEMENT OF ALL TRADES' WORK. BRING ALL CONCERNS, SPACE LIMITATIONS OR
STRUCTURAL CONFLICTS TO THE IMMEDIATE ATTENTION OF THE ARCHITECT, PRIOR TO COMMENCING WITH THE WORK IN QUESTION.
COORDINATE AND LOCATE ELECTRICAL, DATA, AND PHONE RECEPTACLES, SWITCHES, ETC. TO AVOID CONFLICTS WITH CASEWORK, DOORS, AND OTHER TRADES.
GENERAL NOTES
1.
2.
3.
4.
5.
PROTECT EXISTING FINISHES TO REMAIN FOR THE DURATION OF THE WORK. REPAIR OR REPLACE DAMAGED MATERIALS CAUSED BY THE
WORK.
PATCH AND PAINT WALLS, CEILINGS, AND/OR ADJACENT SURFACES TO MATCH EXISTING WHERE DEMOLITION WORK OCCURED.
PATCH AND REPAIR AREAS OF WALLS WHERE RADIATORS AND ALL ASSOCIATED PIPING AND HARDWARE WERE REMOVED.
PATCH AND REPAIR WALL WHERE EXISTING PENETRATIONS ARE REMOVED OR NEW PENETRATIONS ARE INSTALLED.
PENETRATIONS IN WALLS, CEILINGS, AND FLOORS NEED TO BE FIRE CAULKED USING APPROVED FIRE CAULKING FOR ALL RATED
CONSTRUCTION.
GENERAL NEW WORK NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
GENERAL DEMOLITION NOTES ARE APPLICABLE TO ALL CONSTRUCTION
PRIOR TO PROCEEDING WITH ANY WORK UNDER THIS CONTRACT, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL
NECESSARY SAFEGUARDS TO MAINTAIN ALL PARTS OF THE EXISTING SITE AND BUILDING IN A SAFE AND OCCUPIABLE CONDITION
THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL PROTECT THE EXISTING BUILDING, IT'S CONTENTS, AND ALL
BUILDING MECHANICAL, ELECTRICAL, AND TELECOMMUNICATION SYSTEMS FROM DAMAGE AT ALL TIMES. ALL DAMAGES RESULTING
DIRECTLY OR INDIRECTLY FROM THE CONTRACTOR'S OPERATIONS SHALL BE REPAIRED TO A "LIKE NEW" CONDITION AT THE CONTRACTOR'S
EXPENSE WITHOUT ANY ADDITIONAL COST TO THE OWNER
THE INFORMATION INDICATED ON THE CONTRACT DOCUMENTS IS BASED ON EXISTING DRAWINGS AND FIELD MEASUREMENTS. ALL
DIMENSIONAL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. THE CONTRACTOR SHALL BECOME TOTALLY
FAMILIAR WITH AND VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS THAT AFFECT THE CONTRACT. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE DIMENSIONS, ELEVATIONS, AND SEQUENCES OF WORK NECESSARY FOR THE PROPER CONSTRUCTION AND
ALIGNMENT OF PORTIONS OF THE PROJECT THAT INTERFACE WITH EXISTING CONDITIONS TO REMAIN. THE CONTRACTOR SHALL MAKE ALL
MEASUREMENTS NECESSARY FOR THE PROPER EXECUTION, FABRICATION AND ERECTION OF ALL WORK ASSOCIATED WITH THIS
CONTRACT.
THE BUILDING SHALL REMAIN OCCUPIED AND IN OPERATION DURING THE ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL
ENSURE THAT UTILITY SERVICES TO THE EXISTING FACILITY ARE NOT DISRUPTED BY THE CONTRACTOR'S ACTIVITIES WITHOUT ADVANCE
APPROVAL FROM THE OWNER.
REFERENCE MECHANICAL AND ELECTRICAL SERIES DRAWINGS FOR DEMOLITION SCOPE.
UNLESS OTHERWISE NOTED, REMOVE EXISTING CONSTRUCTION ON DEMOLITION PLANS THAT IS INDICATED BY A DASHED LINE, EXISTING
CONSTRUCTION TO REMAIN IS INDICATED BY SOLID LINES
AREAS OF LIMITED RENOVATION SCOPE INDICATED WITH HATCH PATTERN. HATCHED AREA IS OUTSIDE OF MAIN WORK AREA BUT MAY HAVE
LIMITED REMOVAL / REPLACEMENT OF CEILINGS FOR ROUTING OF NEW SERVICES - COORDINATE EXTENTS WITH MECHANICAL AND
ELECTRICAL DRAWINGS.
ALL PATCHES AND REPAIRS OF EXISTING / NEW FINISHES SHALL ALIGN WITH ADJACENT FINISH FACE AND SHALL MATCH IN MATERIAL, COLOR, AND TEXTURE. REPAIRS TO DAMAGED EQUIPMENT, MECHANICAL SYSTEMS, PLUMBING SYSTEMS, ELECTRICAL SYSTEMS AND
TELECOMMUNICATION SYSTEMS SHALL BE MADE WITH MATERIALS THAT ARE IDENTICAL TO MATERIALS, ITEMS AND SYSTEMS PATCHED
UNLESS SPECIFICALLY INDICATED OTHERWISE.
REMOVE ABANDONED SERVICES AT FLOOR AND CEILING DECK, COMPLETE. PREP PENETRATIONS FOR PLUG AND FILL, TYPICAL
REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR REMOVAL OF CEILING MOUNTED DEVICES, PIPING, AND EXISTING DUCTWORK.
REMOVE ALL ABANDONED FASTENERS, BRACKETS, LEDGERS, ETC. WITHIN THE PROJECT SCOPE BOUNDARY AND ASSOCIATED WITH THE
DEMOLISHED AND MODIFIED SYSTEMS.
MISCELLANEOUS DEMOLITION/CUTTING & PATCHING BEYOND WHAT IS INDICATED ON THE DRAWINGS MAY BE NECESSARY FOR CONDUITS
AND PIPING. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ROUTING OF THESE ITEMS.
GENERAL DEMOLITION NOTES
PROJECT DESCRIPTION
THIS PROJECT INCLUDES REMOVING EXISTING AIR HANDLING UNITS, TERMINAL BOXES, AND CONTROLS. THE WORK SHALL INCLUDE REPLACING THE
DEMOLISHED SYSTEMS IN-KIND WITH UPGRADED AIR HANDLING UNITS, TERMINAL BOXES, AND MECHANICAL CONTROLS.THE WORK WILL REQUIRE
SELECTIVE DEMOLITION AND REPAIRS TO SUPPORT MECHANICAL SYSTEMS INSTALLATION.
CODES AND STANDARDS
VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) - 2018
VIRGINIA EXISTING BUILDING CODE (VEBC) - 2018
VIRGINIA MAINTENANCE CODE - 2018
CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL (CPSM) - 2021
ACCESSIBILITY CODE: ADA STANDARDS FOR ACCESIBLE DESIGN - 2010
OTHER DESIGN STANDARDS:
VIRGINIA PLUMBING CODE - 2018 EDITION
VIRGINIA MECHANICAL CODE - 2018 EDITION
VIRGINIA FUEL GAS CODE - 2018 EDITION
VIRGINIA ENERGY CONSERVATION CODE (VECC) - 2018 EDITION
CONSTRUCTION CLASSIFICATIONS
THIS UNDERTAKING WILL NOT CHANGE THE USE GROUP CLASSIFICATION OR THE BUILDING OCCUPANCY
PROJECT DATA
REFLECTED CEILING PLAN SYMBOLS
GENERAL NOTES:
1. SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURES - SEE MECHANICAL DRAWINGS FOR DIFFUSERS AND GRILLES AND ADDITIONAL SCOPE.
2. CEILING FIXTURES AND DEVICES NOT SHOWN ON ARCHITECTURAL DRAWINGS. FIXTURE LOCATIONS TO REMAIN AS EXISTING. ANY FIXTURES
TEMPORARILY RELOCATED DURING CONSTRUCTION TO BE REPLACED IN ORIGINAL LOCATION, UNLESS OTHERWISE SPECIFICALLY NOTED IN
DESIGN DOCUMENTS.
2' x 2' CEILING GRID GRAY HATCH INDICATES "NOT IN SCOPE"
ABBREVIATIONS
SYMBOL INDICATIONS
MATERIAL INDICATIONS
ADA
AFF
BES
BLDG
BLKG
CSMU
CL CMU
CONC
COORD
CONT
CJ
DIAG
DIM
DTL
DWG
EA
ELEC
ELEV
AMERICANS WITH DISABILITIES ACT
ABOVE FINISH FLOOR
BUILD EXPANSION JOINT
BUILDING
BLOCKING
CALCIUM SILICATE MASONRY UNIT
CENTERLINE, CLEAR
CONCRETE MASONRY UNIT
CONCRETE
COORDINATE
CONTINUOUS
CONTROL JOINT
DIAGONAL
DIMENSION
DETAIL
DRAWING
EACH
ELECTRICAL
ELEVATION
EQ
ERTS
EXT
FEC
FLR
FD
FRT
FV
GALV
GYP BD
HIR
HORIZ
HT
HPDL
MAX
MFR
OC
OPP
EQUAL
EMERGENCY RESPONSE
TELEPHONE SYSTEM
EXTERIOR
FIRE EXTINGUISHER CABINET
FLOOR
FLOOR DRAIN
FIRE RETARDANT TREATED
FIELD VERIFY
GALVANIZED
GYPSUM BOARD
HEARING IMPAIRED ROOM
HORIZONTAL
HEIGHT
HIGH PRESSURE DECORATIVE
LAMINATE
MAXIMUM
MANUFACTURER
ON CENTER
OPPOSITE
PART
PT
PJ
RD
REQD
SCHED
SIM
SPEC
T&G
TYP
UL
UON
VERT
W/
PARTIAL
PAINT, POINT
PANEL JOINT
ROOF DRAIN
REQUIRED
SCHEDULE
SIMILIAR
SPECIFICATION
TONGUE AND GROOVE
TYPICAL
UNDERWRITERS LABORATORY
UNLESS OTHERWISE NOTED
VERTICAL
WITH
BUILDING SECTION NUMBER
SHEET WHERE SECTION IS FOUND
WALL SECTION NUMBER
SHEET WHERE SECTION IS FOUND
DETAIL NUMBER OR LETTER
SHEET WHERE DETAIL IS FOUND
EXTERIOR ELEVATION LETTER
SHEET WHERE ELEVATION IS FOUND
INTERIOR ELEVATION LETTER
SHEET WHERE ELEVATION IS FOUND
ROOM NUMBER
WITH LETTER OR NUMBER
INDICATES CENTERLINE OF
COLUMN
PARTITION TYPE
DOOR NUMBER
MORTAR
CONCRETE
CMU
ROUGH CARPENTRY
BLOCKING - SIZED AS REQUIRED
RIGID INSULATION
C
A
B
D
A
SPEC NOTE
A101
A101
12.00.00
SERVICE ENTRANCE
CONSTRUCTION LAY-DOWN
AREA AND TRAILER SITE -
MAINTAIN DRIVEWAY
ACCESS THROUGHOUT
CONSTRUCTION
ECHOLS HALL
SITE PLAN
JOSEPH ECHOLS HALL
CONSTRUCTION
ENTRANCE -
ACCESS GATE #8
GOOGLE MAPS
VICINITY MAPLOCATION MAP - NORFOLK STATE UNIVERSITY
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :2
P
M
Author
Checker
COVER SHEET,
PROJECT DATA AND
DRAWING INDEX
G001
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P
R O
V E
M E
N T
S
N O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
INDEX OF DRAWINGS - ARCHITECTURAL
SHEET
NUMBER SHEET NAME
AD103 THIRD FLOOR DEMOLITION PLAN - PART A
AD104 THIRD FLOOR DEMOLITION PLAN - PART B
A100 FIRST FLOOR REFERENCE PLAN - OVERALL
A101 FIRST FLOOR REFLECTED CEILING PLAN - PART A
A102 FIRST FLOOR REFLECTED CEILING PLAN - PART B
A103 THIRD FLOOR PLAN - PART A
A104 THIRD FLOOR PLAN - PART B
A201 EXTERIOR ELEVATIONS
A202 EXTERIOR ELEVATIONS
A203 EXTERIOR ELEVATION
A301 SECTIONS AND DETAILS
INDEX OF DRAWINGS - GENERAL
SHEET
NUMBER SHEET NAME
G001 COVER SHEET, PROJECT DATA AND DRAWING INDEX
G002 KEYNOTE MASTER LIST
INDEX OF DRAWINGS - MECHANICAL DEMOLITION
SHEET
NUMBER SHEET NAME
MD101 FIRST FLOOR PLAN - PART A DEMOLITION - DUCTWORK
MD102 FIRST FLOOR PLAN - PART B DEMOLITION -
DEMOLITION
MD103 THIRD FLOOR PLAN - PART A DEMOLITION
MD104 THIRD FLOOR PLAN - PART B DEMOLITION
MD201 FIRST FLOOR PLAN - PART A DEMOLITION - PIPING
MD202 FIRST FLOOR PLAN - PART B DEMOLITION - PIPING
MD203 THIRD FLOOR PLAN - PART A DEMOLITION
MD204 THIRD FLOOR PLAN - PART B DEMOLITION
MD301 SECTIONS
MD401 ENLARGED PLANS
INDEX OF DRAWINGS - STRUCTURAL
SHEET
NUMBER SHEET NAME
S001 GENERAL NOTES & SPECIAL INSPECTIONS
S101 MEZZANINE FRAMING PLAN – AREA A
S102 MEZZANINE FRAMING PLAN – AREA B
S501 TYPICAL DETAILS
INDEX OF DRAWINGS - MECHANICAL
SHEET
NUMBER SHEET NAME
M001 LEGEND, NOTES AND ABBREVIATIONS
M101 FIRST FLOOR DUCTWORK PLAN - PART A NEW WORK
M102 FIRST FLOOR DUCTWORK PLAN - PART B NEW WORK
M103 THIRD FLOOR DUCTWORK PLAN - PART A NEW WORK
M104 THIRD FLOOR DUCTWORK PLAN - PART B NEW WORK
M201 FIRST FLOOR PIPING PLAN - PART A NEW WORK
M202 FIRST FLOOR PIPING PLAN - PART B NEW WORK
M203 THIRD FLOOR PIPING PLAN - PART A NEW WORK
M204 THIRD FLOOR PIPING PLAN - PART B NEW WORK
M301 SECTIONS
M401 ENLARGED PLANS
M501 DETAILS
M601 SCHEDULES
M701 CONTROLS
M702 CONTROLS
M703 CONTROLS
M704 CONTROLS
M705 CONTROLS
ECHOLS HALL MECHANICAL IMPROVEMENTS
NORFOLK STATE UNIVERSITY
700 PARK AVENUE, NORFOLK, VIRGINIA BID SET - DECEMBER 21, 2023
INDEX OF DRAWINGS - ELECTRICAL
SHEET
NUMBER SHEET NAME
E001 LEGEND, NOTES AND ABBREVIATIONS
E-201 FIRST FLOOR POWER PLAN - PART A NEW WORK
E-202 FIRST FLOOR POWER PLAN - PART B NEW WORK
E-203 THIRD FLOOR POWER PLAN - PART A NEW WORK
E-204 THIRD FLOOR POWER PLAN - PART B NEW WORK
E-601 PANELBOARD SCHEDULES AND RISER DIAGRAMS
INDEX OF DRAWINGS - ELECTRICAL DEMOLITION
SHEET
NUMBER SHEET NAME
ED201 FIRST FLOOR PLAN - PART A DEMOLITION
ED202 FIRST FLOOR PLAN - PART B DEMOLITION
ED203 THIRD FLOOR PLAN - PART A DEMOLITION
ED204 THIRD FLOOR PLAN - PART B DEMOLITION
ISSUE FOR BID
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :2
P
M
Author
Checker
KEYNOTE MASTER
LIST
G002
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
KEYNOTE LEGEND
Key Value Keynote Text
024119.01 DISMANTLE EXISTING METAL WALL PANEL SECTIONS TO EXTENT SHOWN AND STORE FOR REUSE (SEE PLAN DIMENSIONS AND HATCH PATTERN ON ELEVATIONS). CONTRACTOR TO PROVIDE TEMPORARY WEATHER PROTECTIVE BARRIER DURING CONSTRUCTION TO PREVENT WEATHER INFILTRATION AND DAMAGE TO
BUILDING INTERIOR DURING CONSTRUCTION.
024119.02 EXISTING ATTIC ACCESS LADDER TO REMAIN
024119.03 EXISTING ATTIC ACCESS LADDER OPENING - REMOVE ALL IMPEDING MATERIAL
024119.04 SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DUCTWORK, PIPING, AND WIRING REMOVAL EXTENTS
024119.05 AT EXTERIOR WALL LOCATIONS BEING USED FOR MEZZANINE ACCESS OPENINGS, REMOVE BATT INSULATION FROM STUD CAVITY OF WORK AREA - PREPARE AREA TO RECEIVE NEW INSULATION
024119.06 EXISTING LOUVERS AND GRILLES TO REMAIN. WHERE REMOVAL IS REQUIRED, LOUVERS AND GRILLES SHALL BE SALVAGED FOR RE-INSTALLATION. AT FIRST FLOOR, EXISTING LOUVERS TO BE REMOVED FOR
EQUIPMENT PATHWAY, TYPICAL, FOR ALL AIR HANDLER LOCATIONS
024119.07 EXISTING ACCESS DOOR TO REMAIN
024119.08 DEMOLISH LIGHT GAUGE METAL STUDS TO EXTENTS SHOWN - CLIP HEADER AND SILL TRACK - PROVIDE SMOOTH EDGE CONDITION. PREPARE OPENING TO RECEIVE NEW DEMOUNTABLE RIGID STUD FRAME AFTER
USE AS TEMPORARY CONSTRUCTION OPENING
024119.09 COMPONENTS OF STRUCTURAL STEEL TO BE TEMPORARILY REMOVED AS NEEDED FOR EQUIPMENT ACCESS - REFERENCE STRUCTURAL DRAWINGS FOR DETAILS, SHORING, AND OTHER REQUIREMENTS. FOR CONDITIONS NOT IDENTIFIED IN CONTRACT DOCUMENTS, CONTRACTOR TO REQUEST ADDITIONAL
INFORMATION FROM STRUCTURAL ENGINEER.
024119.10 EXISTING ROOF SYSTEM - PROTECT 'EXISTING TO REMAIN' FOR THE DURATION OF THE WORK, TYPICAL.
REPAIR OR REPLACE DAMAGED MATERIALS CAUSED BY THE WORK.
024119.11 EXISTING COPING TO REMAIN. WHERE REMOVAL OR MANIPULATION IS REQUIRED, COPING SHALL BE
SALVAGED FOR RE-INSTALLATION OR READJUSTED TO LIKE-NEW CONDITION.
024119.12 EXISTING STRUCTURAL STEEL SHOWN SHADED (GRAY) TO REMAIN.
024119.13 REMOVE EXISTING SUSPENDED ACOUSTICAL PANEL CEILING GRID AND TILES IN WORK AREA - PROTECT AND STORE FOR REUSE. ASSUME REPLACEMENT OF 1000 SF OF SAPC TOTAL THROUGHOUT ALL AREAS INDICATED WITH THIS KEYNOTE. REMOVAL MAY BE REQUIRED IN AREAS BEYOND SCOPE BOUNDARY.
REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR CONCENTRATED AREAS OF WORK AT
EQUIPMENT LOCATIONS.
024119.14 EXISTING INSULATED KNEE WALL TO REMAIN - PROTECT IT AND RELATED ROOF BASE FLASHING ASSEMBLY
DURING ENTIRE WORK SEQUENCE TYPICAL
024119.15 DEMOLISH EXISTING WOOD PLATFORM AND STEP - PREPARE AREA TO RECEIVE NEW PREFABRICATED
METAL TREADS
024119.16 DEMOLISH EXISTING SUSPENDED ACOUSTICAL PANEL CEILING GRID AND TILES IN THIS CONTIGUOUS AREA.
REPLACE WITH ALL NEW CEILING AND GRID. FIELD VERIFY EXISTING CEILING SYSTEM AND REPLACE TO MATCH EXISTING. EXISTING LIGHTS AND SYSTEMS NOT IN REPLACEMENT SCOPE ARE TO BE PROTECTED
FOR REUSE.
035113.01 REMOVE ALL EXISTING TECTUM PANELS WITH DAMAGE OR FAILURE PRESENTING A HAZARDOUS CONDITION, TYPICAL AT MEZZANINE LEVEL. REPLACEMENT MAY BE REQUIRED BEYOND WHAT IS INDICATED ON THE DRAWINGS. INSPECT ANY UNDERLYING STRUCTURE AND PREPARE SURFACES TO RECEIVE NEW TECTUM
PANEL CUT TO FIT & SUPPORT TO MATCH EXISTING CONDITIONS.
035113.02 NEW TECTUM PANEL THIS LOCATION - FIELD VERIFY PANEL SIZE TO MATCH EXISTING OPENING. ADDITIONAL PANELS MAY BE REQUIRED BEYOND WHAT IS INDICATED ON THE DRAWINGS - CONTRACTOR TO FIELD
VERIFY.
035113.03 FILL AND PATCH ALL PENETRATIONS IN TECTUM WALL PANELS THAT ALLOW VISIBILITY TO ADJACENT SPACE, TYPICAL (ASSUME 100 SF TOTAL PATCH AND FILL AT TECTUM WALLS, FLOORS, AND CEILING AT MEZZANINE
LEVEL). PATCH AND FILL MAY BE REQUIRED BEYOND WHAT IS INDICATED ON THE DRAWINGS.
035113.04 REPLACE TECTUM FLOOR PANELS AT CONDITIONS WITH ABANDONED PENETRATIONS OVER 2" DIAMETER AND EXPOSURE TO ADJACENT SPACE, TYPICAL (ASSUME 400 SF). PATCH AND FILL OPENINGS IN EXISTING TO REMAIN PANELS WITH PENETRATIONS SMALLER THAN 2" DIAMETER (WEDGE CUT ROUGH OPENING SUCH THAT INFILL MATERIAL CANNOT FALL THRU OPENINGS, TYPICAL). REPLACEMENT OR PATCH AND FILL MAY BE REQUIRED BEYOND WHAT IS INDICATED ON THE DRAWINGS, FIELD VERIFY ENTIRE WORK AREA AND REPORT
ANY DISCREPANCIES TO THE ARCHITECT.
035113.05 EXISTING EXPOSED TECTUM ROOF DECK/CEILING TO REMAIN. FILL AND PATCH ANY HOLES, UTILITY PENETRATIONS, OR DEVICE CONNECTIONS NOT TO BE REUSED. PATCH, REPAIR, AND SEAL ALL PENETRATIONS IN ROOF DECK, WITH VISIBLE DAYLIGHT, LEAKS, OR OTHER WEATHER PERMEABLE
CONDITIONS, TYPICAL
055000.01 GALVANIZED METAL 3-STEP SHIPS LADDER TO ROOF ACCESS - FIELD VERIFY CLEARANCE AND STEPS
REQUIRED PRIOR TO FABRICATION
055119.01 STEEL STAIRS WITH 5 EQUAL RISER (INCLUDING EXISTING METAL SILL / DOOR THRESHOLD AT EXISTING DOORS) AND MINIMUM 12" DEEP BY WIDTH OF DOOR FRAME STEEL-BAR-GRATING TREADS - PROVIDE PIPERAIL TYPE GUARDRAIL ON EITHER SIDE AS SHOWN TYPICAL - FIELD VERIFY RISER DIMENSIONS REQUIRED AND WIDTH OF EXISTING DOOR FRAME - GUARDRAILS TO ABUT EXISTING DOOR FRAME ON
EITHER SIDE TYPICAL
064116.01 DEMOLISH EXISTING BASE CABINET COMPLETE. EXISTING SURROUNDING FINISHES AND EQUIPMENT TO REMAIN. PROTECT FLOOR, WALLS, SECURITY GRILLE, AND SURROUNDING CONDITIONS FROM DAMAGE AND DISTURBANCE DURING CONSTRUCTION. INSTALL NEW BASE CABINET TO MATCH ORIGINAL CABINET LOCATION AND ALIGNING FLOOR FINISHES. COORDINATE COUNTER INSTALLATION WITH EXISTING
OVERHEAD ROLLING SECURITY GRILLE.
072100.01 FOIL FACED INSULATION TYPE, THICKNESS & R-VALUE TO MATCH EXISTING - FIT TIGHTLY BETWEEN STUDS AND RUNNER TRACKS AND ATTACH WITH FOIL FACED ADHESIVE TAPE TYPICAL, FOR A COMPLETE
INSULATED SEAL
074213.01 CUSTOM FIT METAL PANEL INFILL PLATE AT CORRUGATED EXTERIOR WALL PANEL BASE – CAULK PERIMETER JOINT COMPLETE WITH MOISTURE RETARDANT SEALANT AND PACK TIGHTLY WITH INSULATION
AND NEOPRENE GASKET (ASSUME 40 L.F.)
078413.01 WHERE ALTERNATION OF PENETRATIONS OCCUR PROVIDE CONTINUOUS FIRESTOP SEALANT TO MATCH
EXISTING UL FLOOR PENETRATION DESIGN
078443.01 WHERE FIRE RATED JOINT CONDITIONS ARE REQUIRED OR MODIFIED PROVIDE CONTINIUOUS JOINT
FIRESTOPPING
092216.01 60"X60" DEMOUNTABLE FULLY WELDED 14 GAUGE LIGHT GAUGE BENT PLATE FRAME WITH 6" STUDS AT 16" O.C. - FIELD VERIFY MAXIMUM HORIZONTAL AND VERTICAL DIMENSION POSSIBLE AT EACH CONDITION - AT EACH LOCATION STENCIL "ACCESS PANEL BEYOND" IN 3" BLOCK LETTERS WITHIN 6" OF BOTTOM OF ALL EXTERIOR RIBBED METAL PANELS ON OUTSIDE OF DEMOUNTABLE FRAME LOCATIONS - PROVIDE 3/8" STAINLESS STEEL CARRIAGE BOLTS AT 12" OC & WITHIN 4" OF EACH CORNER THRU-BOLTED TO EXISTING CLIP ANGLE AT TOP AND EXISTING CHANNEL AT BOTTOM OF OPENING TYPICAL. WHERE ACCESS OPENINGS ARE SHOWN GREATER THAN 60" WIDE, PROVIDE MULTIPLE RIGID FRAMES TO MEET THE REQUIRED WIDTH.
092216.02 20 GAUGE NON-STRUCTURAL 6" RUNNER TRACK - TACK WELD TO 14 GAUGE BENT PLATE FRAME @ 12" OC
TYPICAL
092216.03 14 GAUGE LIGHT GAUGE BENT PLATE 4-SIDED FRAME FULLY WELDED - FIELD VERIFY EACH ROUGH OPENING
SO THAT ENTIRE ASSEMBLY IS EASILY REMOVABLE FROM EACH LOCATION TYPICAL
092216.04 20 GAUGE NON-STRUCTURAL 6" STUDS @ 16" OC EQUALLY SPACED FROM SIDE OF FRAME - TACK WELD TO 14 GAGE BENT PLATE FRAME @ 12" OC (SIDE STUDS) AND TOP AND BOTTOM OF INTERMEDIATE STUDS
092900.01 PATCH AND REPAIR GYPSUM BOARD OR CMU AT LOCATIONS ABOVE AND BELOW CEILING, IMPACTED BY THE
WORK, TYPICAL THROUGHOUT ENTIRE WORK AREA
IIIRISK CATEGORY
CLASSIFICATION OF BUILDING
LIVE LOADS - UNIFORM:
20 PSFROOF
128 MPHULTIMATE DESIGN WIND SPEED (VULT)
99 MPHNOMINAL DESIGN (VASD) WIND SPEED
±0.18INTERNAL PRESSURE COEFFICIENT
BEXPOSURE CATEGORY
WIND LOADS:
1.0IMPORTENCE FACTOR (IW)
D (ASSUMED)SITE CLASSIFICATION
ASEISMIC DESIGN CATEGORY
1.25IMPORTANCE FACTOR (IE)
SEISMIC LOADS:
SPECTRAL RESPONSE ACCELERATIONS:
0.086S 0.040S 0.137S 0.095S 0.092S 0.063S
1. THE STRUCTURAL DRAWINGS MUST BE USED IN CONJUNCTION WITH THE
ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. THE CONTRACTOR
MUST VERIFY THE REQUIREMENTS OF OTHER TRADES AS TO SLEEVES, CHASES,
HANGERS, INSERTS, ANCHORS, HOLES, AND ADDITIONAL ITEMS TO BE PLACED
OR SET IN THE STRUCTURAL WORK.
2. THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE PROVISIONS
OF THE VIRGINIA CONSTRUCTION CODE, 2018 EDITION.
3. THE CONTRACTOR MUST PROVIDE TEMPORARY SHORING AND BRACING
REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL
PERMANENT SUPPORTS AND LATERAL BRACING ARE IN PLACE.
4. PORTIONS OF THE STRUCTURE NOT ALTERED AND NOT AFFECTED BY THE
ALTERATION HAVE NOT BEEN REVIEWED FOR COMPLIANCE WITH THE CODE
REQUIREMENTS FOR A NEW STRUCTURE.
5. BEFORE PROCEEDING WITH WORK WITHIN THE EXISTING STRUCTURE, THE
CONTRACTOR MUST BECOME FAMILIAR WITH THE EXISTING STRUCTURAL
CONDITIONS. THE CONTRACTOR MUST BE SOLELY RESPONSIBLE FOR THE
DESIGN AND ERECTION OF ANY AND ALL SAFEGUARDS NECESSARY TO PROTECT
THE EXISTING STRUCTURE.
6. PRIOR TO ISSUING THE STRUCTURAL DRAWINGS FOR ANY PURPOSE,
AUTHORIZATION MUST BE OBTAINED FROM THE STRUCTURAL ENGINEER OF
RECORD. WHEN AUTHORIZED, THE DOCUMENTS THAT ARE RELEASED MUST BE
CLEARLY IDENTIFIED WITH THE AUTHORIZED PURPOSE AND MUST INCLUDE THE
DATE OF RELEASE.
7. DESIGN CRITERIA:
GENERAL NOTES:
S 1
MS M1
DS D1
1. STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE AMERICAN INSTITUTE
OF STEEL CONSTRUCTION (AISC) 360.
2. STRUCTURAL STEEL SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS:
A. STRUCTURAL STEEL SHAPES, PLATES AND BARS (EXCEPT W-SHAPES) -
ASTM A 36, Fy = 36 KSI
3. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1, "STRUCTURAL WELDING
CODE - STEEL." WELD ELECTRODES MUST BE E70XX LOW HYDROGEN. UNLESS
OTHERWISE NOTED, PROVIDE CONTINUOUS FILLET WELDS WITH MINIMUM SIZE
REQUIRED BY TABLE J2.4, PART 4 OF THE AMERICAN INSTIYUTE OF STEEL
CONSTRUCTION (AISC) 360.
4. COORDINATE ALL MEMBER LOCATIONS, UNIT WEIGHTS, OPENING SIZES, AND
CURB DIMENSIONS FOR MECHANICAL EQUIPMENT WITH THE ACTUAL EQUIPMENT
FURNISHED.
STRUCTURAL STEEL NOTES:
1. COLD-FORMED METAL FRAMING MUST BE IN ACCORDANCE WITH THE AMERICAN
IRON AND STEEL INSTITUTE (AISI) "NORTH AMERICAN STANDARD FOR COLD-
FORMED STEEL FRAMING - GENERAL PROVISIONS"
2. COLD-FORMED METAL FRAMING MEMBERS MUST CONFORM TO ASTM C955, AND
BE FORMED OF CORROSION-RESISTANT STEEL CONFORMING TO ASTM A653 AND
ASTM C955 WITH A MINIMUM YIELD STRENGTH OF 33 KSI FOR 43 MIL AND
THINNER MEMBERS AND 50 KSI FOR ALL OTHER MEMBERS.
3. MEMBER SECTION PROPERTIES MUST CONFORM TO PART 'I' OF THE "COLD-
FORMED STEEL DESIGN MANUAL."
COLD-FORMED METAL FRAMING NOTES:
ARCH
BOT, B
CFMF
CL
CLR
CONN
CONT
DWGS
EA
EXIST
FV, ±
MAX
MECH
NTS
ARCHITECT
BOTTOM
COLD-FORMED METAL
FRAMING
CENTERLINE
CLEAR
CONNECTION
CONTINUOUS
DRAWINGS
EACH
EXISTING
FIELD VERIFY
MAXIMUM
MECHANICAL
NOT TO SCALE
OC
OPH
PAF
PL
PME
REF
SCHED
STD
T&B
TYP
UON
VERT
W/
ON CENTER
OPPOSITE HAND
POWDER ACTUATED
FASTENER
PLATE
PLUMBING, MECHANICAL &
ELETRICAL
REFERENCE, REFER TO
SCHEDULE
STANDARD
TOP & BOTTOM
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
WITH
ABBREVIATIONS:
X
= CHANGE IN ELEVATION -
REF ARCH DWGS FOR DIMENSIONS
PLAN KEY NOTE MARK=
COLUMN GRID MARK=
PLAN LEGEND:
X
Structural Engineers
LM Project #V21.111
400 Granby St Suite 401
Norfolk, VA 23510
757.671.8626 - lynchmykins.com
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2023
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/23 BID SET
/2
/2
:5 :2
P
M
PINN
JDT
GENERAL NOTES &
SPECIAL
INSPECTIONS
S001
12.21.2023
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
12.21.2023
K
L
M
N2
O
P
Q
R
S
T
U
18171615.81514131110986543.2321
TYP
TYP
AREA OF WORK
Structural Engineers
LM Project #V21.111
400 Granby St Suite 401
Norfolk, VA 23510
757.671.8626 - lynchmykins.com
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2023
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/23 BID SET
/2
/2
:5 :2
P
M
PINN
JDT
MEZZANINE
FRAMING PLAN -
AREA A
S101
12.21.2023
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
12.21.2023
KEY NOTES
01 EXISTING DOUBLE JOISTS MUST BE REINFORCED AS SHOWN ON THE
TYPICAL EXISTING JOIST STRENGTHENING DETAILS ON S501.
02 EXISTING ROOF BEAM.
03 EXISTING LONG-SPAN ROOF TRUSS.
04 EXISTING ROOF JOIST.
05 EXISTING STEEL COLUMN.
06 EXISTING ROOF FRAMING NOT SHOWN FOR CLARITY.
07 NEW OPENING IN EXISTING WALL. REFER TO TYPICAL NEW WALL OPENING
DETAIL ON S501. REFER TO ARCHITECTURAL DRAWINGS FOR OPENING
DIMENSIONS.
08 EXISTING SUPPORTS ON TOP OF FRAMING TO SUPPORT MECHANICAL
EQUIPMENT. REFER TO "TYPICAL EXISTING MECHANICAL UNIT SUPPORT
MODIFICATION DETAILS" WHERE NEW UNIT DIMENSIONS DO NOT MATCH
EXISTING SUPPORT DIMENSIONS.
1/8" = 1'-0"
MEZZANINE FRAMING PLAN - AREA A
A1
FRAMING PLAN NOTES
A. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT SHOWN.
B. NOT ALL EXISTING FRAMING MEMBERS SHOWN ON PLAN. ROOF FRAMING
IS ONLY SHOWN AT AREAS REQUIRING MODIFICATIONS FOR SUPPORT OF
NEW MECHANICAL EQUIPMENT.
C. EXISTING FRAMING ON TOP OF ROOF FRAMING MEMBERS SHALL BE
RE-USED TO SUPPORT NEW MECHANICAL EQUIPMENT.
NTS
KEY PLAN
A
B
C
E
F
H
I
J
18171615.81514131110986543.2321
TYP
TYP
AREA OF WORK
Structural Engineers
LM Project #V21.111
400 Granby St Suite 401
Norfolk, VA 23510
757.671.8626 - lynchmykins.com
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2023
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/23 BID SET
/2
/2
:5 :2
P
M
PINN
JDT
MEZZANINE
FRAMING PLAN -
AREA B
S102
12.21.2023
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
12.21.2023
KEY NOTES
01 EXISTING DOUBLE JOISTS MUST BE REINFORCED AS SHOWN ON THE
TYPICAL EXISTING JOIST STRENGTHENING DETAILS ON S501.
02 EXISTING ROOF BEAM.
03 EXISTING LONG-SPAN ROOF TRUSS.
04 EXISTING ROOF JOIST.
05 EXISTING STEEL COLUMN.
06 EXISTING ROOF FRAMING NOT SHOWN FOR CLARITY.
07 NEW OPENING IN EXISTING WALL. REFER TO TYPICAL NEW WALL OPENING
DETAIL ON S501. REFER TO ARCHITECTURAL DRAWINGS FOR OPENING
DIMENSIONS.
08 EXISTING SUPPORTS ON TOP OF FRAMING TO SUPPORT MECHANICAL
EQUIPMENT. REFER TO "TYPICAL EXISTING MECHANICAL UNIT SUPPORT
MODIFICATION DETAILS" WHERE NEW UNIT DIMENSIONS DO NOT MATCH
EXISTING SUPPORT DIMENSIONS.
FRAMING PLAN NOTES
A. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT SHOWN.
B. NOT ALL EXISTING FRAMING MEMBERS SHOWN ON PLAN. ROOF FRAMING
IS ONLY SHOWN AT AREAS REQUIRING MODIFICATIONS FOR SUPPORT OF
NEW MECHANICAL EQUIPMENT.
C. EXISTING FRAMING ON TOP OF ROOF FRAMING MEMBERS SHALL BE
RE-USED TO SUPPORT NEW MECHANICAL EQUIPMENT.
1/8" = 1'-0"
MEZZANINE FRAMING PLAN - AREA B
A1 NTS
KEY PLAN
NTS
TYPICAL EXISTING JOIST STRENGTHENING DETAILS
CL OF SUPPORT
JOIST SPAN
EXIST JOIST TOP
CHORD
ADD L1x1x1/8 EA
SIDE OF EXIST
WEB MEMBERS
LAP ANGLES 3/4"
ONTO VERT LEGS
OF CHORD
MEMBERS
EXIST JOIST
BOT CHORD
ELEVATION SECTION
NOTES :
A. PROVIDE ADDED WEB ANGLES AT
EACH END OF JOIST EXTENDING FROM
SUPPORT CENTERLINE TO A DISTANCE
OF 1/4 THE SUPPORT JOIST SPAN.
B. DO NOT SUPPORT ANY NEW LOAD
(CEILING, DUCTS, LIGHTS, PLUMBING,
ELECTRICAL, EQUIPMENT, ETC) ON
EXISTING JOISTS UNTIL ALL
REINFORCING IS INSTALLED.
1/8
TYP
NTS
TYPICAL NEW WALL OPENING DETAIL
(2) 600S200-54
JAMB STUDS (TYP)
(2) PAF EXISTING
SUPPORTING
STRUCTURE
3/4" CLR
VERT SLIP CONN
EA SIDE OF JAMB
W/ MIN 350#
LATERAL FORCE
& MIN 3/4"
MOVEMENT
CONT 600T300-97
JAMB STUD
AT UNDERSIDE
9'-0" MAX
STUDS AS REQUIRED FOR NEW OPENING
REMOVE EXISTING PANEL AND CFMF
NTS
DETAIL AT SUPPORT
A
A
A
EXIST STUDS (TYP)
NTS
DETAIL AT BASE
B
REF ARCH DWGS
JAMB STUD
EXIST CHANNEL
16 GAGE RIGID
CLIP EA SIDE OF
JAMB
B
B
EXIST SUPPORT
EXIST SUPPORT
(2) #10 SCREWS
(2) 0.157"Ø PAF
NEW UNIT SMALLER THAN
EXISTING SUPPORT PLAN
ADDED SUPPORT
PLATE AT NEW UNIT
NTS
TYPICAL EXISTING MECHANICAL UNIT SUPPORT MODIFICATION DETAILS
EXIST
BEAM
PL3/8
BEAM -
REF PLAN
STD CONN
3/16
SIDES
SECTION
MAX
8"
3/16 3-12
1"
CONT PL5/16 -
PLATE CAN EXTEND
1'-0" MAX BEYOND
BEAM EA END
NEW MECH UNIT -
REF PME DWGS
EXIST W8 SUPPORT
EXIST ATTIC FLOOR
DETAIL APPLIES WHERE NEW UNIT BEARS
LESS THAN 2" ON EXIST BEAM FLANGE
FV
F V
MECH DWGS
COORD W/
M E
C H
D W
G S
C O
O R
D W
W8x24
EXIST 8x24
(TYP)
EXIST PIPE
SUPPORT
(TYP)
W x
Structural Engineers
LM Project #V21.111
400 Granby St Suite 401
Norfolk, VA 23510
757.671.8626 - lynchmykins.com
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2023
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/23 BID SET
/2
/2
:5 :2
P
M
PINN
JDT
TYPICAL DETAILS
S501
12.21.2023
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
12.21.2023
1 2 43 5 6 8 9 10 11 13 14 16 17 18
T
S
R
P
O
M
L
K
Q
U
15 15.83.2
N2
A4
A301
024119.01
024119.08
024119.06
024119.06
024119.09
024119.01
024119.08
024119.09
+/- 8"12' - 0"
024119.08
024119.09
024119.01
+/- 8" 12' - 0"
024119.08
024119.09
024119.01
024119.06024119.06 024119.07
024119.02
024119.03
024119.10024119.10 024119.10024119.10
024119.10024119.10
024119.04
024119.04024119.04
024119.04
024119.15
024119.15 024119.15
035113.01
024119.05 024119.05
024119.05024119.05
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
GENERAL DEMOLITION NOTES ARE APPLICABLE TO ALL CONSTRUCTION
PRIOR TO PROCEEDING WITH ANY WORK UNDER THIS CONTRACT, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL
NECESSARY SAFEGUARDS TO MAINTAIN ALL PARTS OF THE EXISTING SITE AND BUILDING IN A SAFE AND OCCUPIABLE CONDITION
THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL PROTECT THE EXISTING BUILDING, IT'S CONTENTS, AND ALL
BUILDING MECHANICAL, ELECTRICAL, AND TELECOMMUNICATION SYSTEMS FROM DAMAGE AT ALL TIMES. ALL DAMAGES RESULTING
DIRECTLY OR INDIRECTLY FROM THE CONTRACTOR'S OPERATIONS SHALL BE REPAIRED TO A "LIKE NEW" CONDITION AT THE CONTRACTOR'S
EXPENSE WITHOUT ANY ADDITIONAL COST TO THE OWNER
THE INFORMATION INDICATED ON THE CONTRACT DOCUMENTS IS BASED ON EXISTING DRAWINGS AND FIELD MEASUREMENTS. ALL
DIMENSIONAL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. THE CONTRACTOR SHALL BECOME TOTALLY
FAMILIAR WITH AND VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS THAT AFFECT THE CONTRACT. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE DIMENSIONS, ELEVATIONS, AND SEQUENCES OF WORK NECESSARY FOR THE PROPER CONSTRUCTION AND
ALIGNMENT OF PORTIONS OF THE PROJECT THAT INTERFACE WITH EXISTING CONDITIONS TO REMAIN. THE CONTRACTOR SHALL MAKE ALL
MEASUREMENTS NECESSARY FOR THE PROPER EXECUTION, FABRICATION AND ERECTION OF ALL WORK ASSOCIATED WITH THIS
CONTRACT.
THE BUILDING SHALL REMAIN OCCUPIED AND IN OPERATION DURING THE ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL
ENSURE THAT UTILITY SERVICES TO THE EXISTING FACILITY ARE NOT DISRUPTED BY THE CONTRACTOR'S ACTIVITIES WITHOUT ADVANCE
APPROVAL FROM THE OWNER.
REFERENCE MECHANICAL AND ELECTRICAL SERIES DRAWINGS FOR DEMOLITION SCOPE.
UNLESS OTHERWISE NOTED, REMOVE EXISTING CONSTRUCTION ON DEMOLITION PLANS THAT IS INDICATED BY A DASHED LINE, EXISTING
CONSTRUCTION TO REMAIN IS INDICATED BY SOLID LINES
AREAS OF LIMITED RENOVATION SCOPE INDICATED WITH HATCH PATTERN. HATCHED AREA IS OUTSIDE OF MAIN WORK AREA BUT MAY HAVE
LIMITED REMOVAL / REPLACEMENT OF CEILINGS FOR ROUTING OF NEW SERVICES - COORDINATE EXTENTS WITH MECHANICAL AND
ELECTRICAL DRAWINGS.
ALL PATCHES AND REPAIRS OF EXISTING / NEW FINISHES SHALL ALIGN WITH ADJACENT FINISH FACE AND SHALL MATCH IN MATERIAL, COLOR, AND TEXTURE. REPAIRS TO DAMAGED EQUIPMENT, MECHANICAL SYSTEMS, PLUMBING SYSTEMS, ELECTRICAL SYSTEMS AND
TELECOMMUNICATION SYSTEMS SHALL BE MADE WITH MATERIALS THAT ARE IDENTICAL TO MATERIALS, ITEMS AND SYSTEMS PATCHED
UNLESS SPECIFICALLY INDICATED OTHERWISE.
REMOVE ABANDONED SERVICES AT FLOOR AND CEILING DECK, COMPLETE. PREP PENETRATIONS FOR PLUG AND FILL, TYPICAL
REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR REMOVAL OF CEILING MOUNTED DEVICES, PIPING, AND EXISTING DUCTWORK.
REMOVE ALL ABANDONED FASTENERS, BRACKETS, LEDGERS, ETC. WITHIN THE PROJECT SCOPE BOUNDARY AND ASSOCIATED WITH THE
DEMOLISHED AND MODIFIED SYSTEMS.
MISCELLANEOUS DEMOLITION/CUTTING & PATCHING BEYOND WHAT IS INDICATED ON THE DRAWINGS MAY BE NECESSARY FOR CONDUITS
AND PIPING. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ROUTING OF THESE ITEMS.
GENERAL DEMOLITION NOTES
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :2
P
M
Author
Checker
THIRD FLOOR
DEMOLITION PLAN -
PART A
AD103
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
1/8" = 1'-0"A1
THIRD FLOOR DEMOLITION PLAN - PART A
KEYNOTE LEGEND - SHEET
Key Value Keynote Text
024119.01 DISMANTLE EXISTING METAL WALL PANEL SECTIONS TO EXTENT SHOWN AND STORE FOR REUSE (SEE PLAN DIMENSIONS AND HATCH PATTERN ON ELEVATIONS). CONTRACTOR TO PROVIDE TEMPORARY WEATHER PROTECTIVE BARRIER DURING CONSTRUCTION TO PREVENT WEATHER INFILTRATION AND
DAMAGE TO BUILDING INTERIOR DURING CONSTRUCTION.
024119.02 EXISTING ATTIC ACCESS LADDER TO REMAIN
024119.03 EXISTING ATTIC ACCESS LADDER OPENING - REMOVE ALL IMPEDING MATERIAL
024119.04 SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DUCTWORK, PIPING, AND WIRING REMOVAL EXTENTS
024119.05 AT EXTERIOR WALL LOCATIONS BEING USED FOR MEZZANINE ACCESS OPENINGS, REMOVE BATT INSULATION FROM STUD CAVITY OF WORK AREA - PREPARE AREA TO RECEIVE NEW INSULATION
024119.06 EXISTING LOUVERS AND GRILLES TO REMAIN. WHERE REMOVAL IS REQUIRED, LOUVERS AND GRILLES SHALL BE SALVAGED FOR RE-INSTALLATION. AT FIRST FLOOR, EXISTING LOUVERS TO BE REMOVED FOR
EQUIPMENT PATHWAY, TYPICAL, FOR ALL AIR HANDLER LOCATIONS
024119.07 EXISTING ACCESS DOOR TO REMAIN
024119.08 DEMOLISH LIGHT GAUGE METAL STUDS TO EXTENTS SHOWN - CLIP HEADER AND SILL TRACK - PROVIDE SMOOTH EDGE CONDITION. PREPARE OPENING TO RECEIVE NEW DEMOUNTABLE RIGID STUD FRAME
AFTER USE AS TEMPORARY CONSTRUCTION OPENING
024119.09 COMPONENTS OF STRUCTURAL STEEL TO BE TEMPORARILY REMOVED AS NEEDED FOR EQUIPMENT ACCESS - REFERENCE STRUCTURAL DRAWINGS FOR DETAILS, SHORING, AND OTHER REQUIREMENTS.
FOR CONDITIONS NOT IDENTIFIED IN CONTRACT DOCUMENTS, CONTRACTOR TO REQUEST ADDITIONAL
INFORMATION FROM STRUCTURAL ENGINEER.
024119.10 EXISTING ROOF SYSTEM - PROTECT 'EXISTING TO REMAIN' FOR THE DURATION OF THE WORK, TYPICAL.
REPAIR OR REPLACE DAMAGED MATERIALS CAUSED BY THE WORK.
024119.15 DEMOLISH EXISTING WOOD PLATFORM AND STEP - PREPARE AREA TO RECEIVE NEW PREFABRICATED
METAL TREADS
035113.01 REMOVE ALL EXISTING TECTUM PANELS WITH DAMAGE OR FAILURE PRESENTING A HAZARDOUS CONDITION, TYPICAL AT MEZZANINE LEVEL. REPLACEMENT MAY BE REQUIRED BEYOND WHAT IS INDICATED ON THE DRAWINGS. INSPECT ANY UNDERLYING STRUCTURE AND PREPARE SURFACES TO
RECEIVE NEW TECTUM PANEL CUT TO FIT & SUPPORT TO MATCH EXISTING CONDITIONS.
8' 16' 24'0'
UP
J
I
H
F
E
C
B
A
15 15.83.2
C5
A301
024119.07
024119.06
035113.04
024119.02
024119.05
024119.03
024119.01
024119.08
024119.09
024119.01
024119.08
024119.09
+/- 8" 12' - 0"
024119.08
024119.09
024119.01
+/- 8" 12' - 0"
024119.08
024119.09
024119.01
024119.07 024119.06024119.06
024119.10024119.10 024119.10024119.10
024119.10024119.10
024119.04
024119.04
024119.04
024119.04
024119.04
024119.05
024119.15
024119.15 024119.15
035113.01
024119.05
024119.05
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :2
P
M
Author
Checker
THIRD FLOOR
DEMOLITION PLAN -
PART B
AD104
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
1/8" = 1'-0" A1
THIRD FLOOR DEMOLITION PLAN - PART B
KEYNOTE LEGEND - SHEET
Key Value Keynote Text
024119.01 DISMANTLE EXISTING METAL WALL PANEL SECTIONS TO EXTENT SHOWN AND STORE FOR REUSE (SEE PLAN DIMENSIONS AND HATCH PATTERN ON ELEVATIONS). CONTRACTOR TO PROVIDE TEMPORARY WEATHER PROTECTIVE BARRIER DURING CONSTRUCTION TO PREVENT WEATHER INFILTRATION
AND DAMAGE TO BUILDING INTERIOR DURING CONSTRUCTION.
024119.02 EXISTING ATTIC ACCESS LADDER TO REMAIN
024119.03 EXISTING ATTIC ACCESS LADDER OPENING - REMOVE ALL IMPEDING MATERIAL
024119.04 SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DUCTWORK, PIPING, AND WIRING REMOVAL EXTENTS
024119.05 AT EXTERIOR WALL LOCATIONS BEING USED FOR MEZZANINE ACCESS OPENINGS, REMOVE BATT INSULATION FROM STUD CAVITY OF WORK AREA -
PREPARE AREA TO RECEIVE NEW INSULATION
024119.06 EXISTING LOUVERS AND GRILLES TO REMAIN. WHERE REMOVAL IS REQUIRED, LOUVERS AND GRILLES SHALL BE SALVAGED FOR RE-INSTALLATION. AT FIRST FLOOR, EXISTING LOUVERS TO BE REMOVED FOR EQUIPMENT PATHWAY, TYPICAL, FOR ALL AIR HANDLER LOCATIONS
024119.07 EXISTING ACCESS DOOR TO REMAIN
024119.08 DEMOLISH LIGHT GAUGE METAL STUDS TO EXTENTS SHOWN - CLIP HEADER AND SILL TRACK - PROVIDE SMOOTH EDGE CONDITION. PREPARE OPENING TO RECEIVE NEW DEMOUNTABLE RIGID STUD FRAME AFTER USE AS TEMPORARY CONSTRUCTION OPENING
024119.09 COMPONENTS OF STRUCTURAL STEEL TO BE TEMPORARILY REMOVED AS NEEDED FOR EQUIPMENT ACCESS - REFERENCE STRUCTURAL DRAWINGS FOR DETAILS, SHORING, AND OTHER REQUIREMENTS. FOR CONDITIONS NOT IDENTIFIED IN CONTRACT DOCUMENTS, CONTRACTOR TO REQUEST
ADDITIONAL INFORMATION FROM STRUCTURAL ENGINEER.
024119.10 EXISTING ROOF SYSTEM - PROTECT 'EXISTING TO REMAIN' FOR THE DURATION OF THE WORK, TYPICAL. REPAIR OR REPLACE DAMAGED MATERIALS
CAUSED BY THE WORK.
024119.15 DEMOLISH EXISTING WOOD PLATFORM AND STEP - PREPARE AREA TO RECEIVE NEW PREFABRICATED METAL TREADS
035113.01 REMOVE ALL EXISTING TECTUM PANELS WITH DAMAGE OR FAILURE PRESENTING A HAZARDOUS CONDITION, TYPICAL AT MEZZANINE LEVEL.
REPLACEMENT MAY BE REQUIRED BEYOND WHAT IS INDICATED ON THE DRAWINGS. INSPECT ANY UNDERLYING STRUCTURE AND PREPARE SURFACES
TO RECEIVE NEW TECTUM PANEL CUT TO FIT & SUPPORT TO MATCH EXISTING CONDITIONS.
035113.04 REPLACE TECTUM FLOOR PANELS AT CONDITIONS WITH ABANDONED PENETRATIONS OVER 2" DIAMETER AND EXPOSURE TO ADJACENT SPACE, TYPICAL (ASSUME 400 SF). PATCH AND FILL OPENINGS IN EXISTING TO REMAIN PANELS WITH PENETRATIONS SMALLER THAN 2" DIAMETER (WEDGE CUT ROUGH OPENING SUCH THAT INFILL MATERIAL CANNOT FALL THRU OPENINGS, TYPICAL). REPLACEMENT OR PATCH AND FILL MAY BE REQUIRED BEYOND WHAT IS INDICATED ON THE DRAWINGS, FIELD VERIFY ENTIRE WORK AREA AND REPORT ANY DISCREPANCIES TO THE ARCHITECT.
A202
A202
C1
A1
T T
S S
R R
P P
O O
M M
L L
K K
J J
I I
H H
F F
E E
C C
B B
A A
Q Q
U U
15.8
15.8
3.2
3.2
N2 N2
A201C2
A201A2A203 C2
A203 A2
RECEPTION
OFFICE
OFFICE
OFFICE
104 OFFICE
OFFICE
COMP LAB
OFFICE
109B
OFFICE
109A
OFFICE
MEN'S
RESTROOM
PE STORAGE
AA
ROTC STORAGE
A
WOMEN'S
RESTROOM
HALL OF FAME
CLASSROOM
CLASSROOOM
CONFERENCE
CLASSROOM
WOMEN'S
RESTROOM
MECH
123A
STORAGE
STORAGE
119A
MEN'S
RESTROOM
STORAGE
MECH
STORE ROOM
127A
MECH
M LOCKER
W LOCKER
W LOCKER
M LOCKER
OFFICE
OFFICE
WOMEN'S
RESTROOM
M LOCKER
OFFICE
W LOCKER
ELEC
142A
MEN'S
RESTROOM
MECH
LAUNDRY
OFFICE
OFFICE
OFFICE
W LOCKER
151B
STORAGE
OFFICE
OFFICE
M LOCKER
MEN'S
RESTROOM
RECEPTION
STORAGE
OFFICE
OFFICE
RECEPTION
OFFICE
OFFICE
OFFICE
OFFICE
MECH
AAA
MEN'S
RESTROOM
OFFICE
STORAGE
170A
A301 C1 A301B1
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :0
P
M
Author
Checker
FIRST FLOOR
REFERENCE PLAN -
OVERALL
A100
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P
R O
V E
M E
N T
S
N O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
16' 32'0' 48' 1/16" = 1'-0"A1
FIRST FLOOR REFERENCE PLAN - OVERALL
REFERENCE REFLECTED CEILING PLANS
FOR WORK THIS LEVEL
S
R
P
O
M
L
K
Q
U
15 15.83.2
N2
024119.06
024119.06
024119.06
024119.16
024119.13
024119.13
024119.13
024119.16
024119.13 024119.13
024119.13
024119.13
024119.13
024119.13
024119.13
024119.13
024119.13
024119.13
024119.13
024119.13
024119.13024119.13
024119.13
024119.16
024119.16
024119.16
024119.16
W LOCKER
M LOCKER
OFFICE
OFFICE
WOMEN'S
RESTROOM
M LOCKER
OFFICE
W LOCKER
ELEC
142A
MEN'S
RESTROOM
MECH
LAUNDRY
OFFICE
OFFICE
OFFICE
W LOCKER
151B
STORAGE
OFFICE
OFFICE
M LOCKER
MEN'S
RESTROOM
RECEPTION
STORAGE
OFFICE
OFFICE
RECEPTION
OFFICE
OFFICE
OFFICE
OFFICE
MECH
AAAMEN'S
RESTROOM
OFFICE
STORAGE
170A
LOUNGE AREA
151A
092900.01
092900.01
092900.01
092900.01
092900.01
1.
2.
3.
4.
5.
PROTECT EXISTING FINISHES TO REMAIN FOR THE DURATION OF THE WORK. REPAIR OR REPLACE DAMAGED MATERIALS CAUSED BY THE
WORK.
PATCH AND PAINT WALLS, CEILINGS, AND/OR ADJACENT SURFACES TO MATCH EXISTING WHERE DEMOLITION WORK OCCURED.
PATCH AND REPAIR AREAS OF WALLS WHERE RADIATORS AND ALL ASSOCIATED PIPING AND HARDWARE WERE REMOVED.
PATCH AND REPAIR WALL WHERE EXISTING PENETRATIONS ARE REMOVED OR NEW PENETRATIONS ARE INSTALLED.
PENETRATIONS IN WALLS, CEILINGS, AND FLOORS NEED TO BE FIRE CAULKED USING APPROVED FIRE CAULKING FOR ALL RATED
CONSTRUCTION.
GENERAL NEW WORK NOTESREFLECTED CEILING PLAN SYMBOLS
GENERAL NOTES:
1. SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURES - SEE MECHANICAL DRAWINGS FOR DIFFUSERS AND GRILLES AND ADDITIONAL SCOPE.
2. CEILING FIXTURES AND DEVICES NOT SHOWN ON ARCHITECTURAL DRAWINGS. FIXTURE LOCATIONS TO REMAIN AS EXISTING. ANY FIXTURES
TEMPORARILY RELOCATED DURING CONSTRUCTION TO BE REPLACED IN ORIGINAL LOCATION, UNLESS OTHERWISE SPECIFICALLY NOTED IN
DESIGN DOCUMENTS.
2' x 2' CEILING GRID GRAY HATCH INDICATES "NOT IN SCOPE"
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :0
P
M
Author
Checker
FIRST FLOOR
REFLECTED
CEILING PLAN -
PART A
A101
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
1/8" = 1'-0"A1
FIRST FLOOR REFLECTED CEILING PLAN - PART A
KEYNOTE LEGEND - SHEET
Key Value Keynote Text
024119.06 EXISTING LOUVERS AND GRILLES TO REMAIN. WHERE REMOVAL IS REQUIRED, LOUVERS AND GRILLES SHALL BE SALVAGED FOR RE-INSTALLATION. AT FIRST FLOOR, EXISTING LOUVERS TO BE REMOVED FOR
EQUIPMENT PATHWAY, TYPICAL, FOR ALL AIR HANDLER LOCATIONS
024119.13 REMOVE EXISTING SUSPENDED ACOUSTICAL PANEL CEILING GRID AND TILES IN WORK AREA - PROTECT AND STORE FOR REUSE. ASSUME REPLACEMENT OF 1000 SF OF SAPC TOTAL THROUGHOUT ALL AREAS INDICATED WITH THIS KEYNOTE. REMOVAL MAY BE REQUIRED IN AREAS BEYOND SCOPE BOUNDARY.
REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR CONCENTRATED AREAS OF WORK AT
EQUIPMENT LOCATIONS.
024119.16 DEMOLISH EXISTING SUSPENDED ACOUSTICAL PANEL CEILING GRID AND TILES IN THIS CONTIGUOUS AREA. REPLACE WITH ALL NEW CEILING AND GRID. FIELD VERIFY EXISTING CEILING SYSTEM AND REPLACE TO MATCH EXISTING. EXISTING LIGHTS AND SYSTEMS NOT IN REPLACEMENT SCOPE ARE TO BE
PROTECTED FOR REUSE.
092900.01 PATCH AND REPAIR GYPSUM BOARD OR CMU AT LOCATIONS ABOVE AND BELOW CEILING, IMPACTED BY
THE WORK, TYPICAL THROUGHOUT ENTIRE WORK AREA
J
I
H
F
E
C
B
A
15 15.83.2
024119.06
024119.06
024119.06
024119.13
024119.13
024119.13
024119.13
024119.13 024119.13
024119.13024119.13
024119.13
024119.13
024119.16
024119.13
024119.16
024119.13
024119.13
024119.13
024119.13
024119.13
024119.13
RECEPTION
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
COMP LAB
OFFICE
109B
OFFICE
109A
OFFICE
MEN'S
RESTROOM
PE STORAGE
AA
ROTC STORAGE
A
WOMEN'S
RESTROOM
HALL OF FAME
CLASSROOM
CLASSROOOM
CONFERENCE
CLASSROOM
WOMEN'S
RESTROOM
MECH
123A
STORAGE
STORAGE
119A
MEN'S
RESTROOM
STORAGE
MECH
STORE ROOM
127A
MECH
M LOCKER
W LOCKER
092900.01
092900.01
092900.01
024119.16
078413.01
078443.01 078413.01
078443.01
A301 C1 A301B1
1.
2.
3.
4.
5.
PROTECT EXISTING FINISHES TO REMAIN FOR THE DURATION OF THE WORK. REPAIR OR REPLACE DAMAGED MATERIALS CAUSED BY THE
WORK.
PATCH AND PAINT WALLS, CEILINGS, AND/OR ADJACENT SURFACES TO MATCH EXISTING WHERE DEMOLITION WORK OCCURED.
PATCH AND REPAIR AREAS OF WALLS WHERE RADIATORS AND ALL ASSOCIATED PIPING AND HARDWARE WERE REMOVED.
PATCH AND REPAIR WALL WHERE EXISTING PENETRATIONS ARE REMOVED OR NEW PENETRATIONS ARE INSTALLED.
PENETRATIONS IN WALLS, CEILINGS, AND FLOORS NEED TO BE FIRE CAULKED USING APPROVED FIRE CAULKING FOR ALL RATED
CONSTRUCTION.
GENERAL NEW WORK NOTESREFLECTED CEILING PLAN SYMBOLS
GENERAL NOTES:
1. SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURES - SEE MECHANICAL DRAWINGS FOR DIFFUSERS AND GRILLES AND ADDITIONAL SCOPE.
2. CEILING FIXTURES AND DEVICES NOT SHOWN ON ARCHITECTURAL DRAWINGS. FIXTURE LOCATIONS TO REMAIN AS EXISTING. ANY FIXTURES
TEMPORARILY RELOCATED DURING CONSTRUCTION TO BE REPLACED IN ORIGINAL LOCATION, UNLESS OTHERWISE SPECIFICALLY NOTED IN
DESIGN DOCUMENTS.
2' x 2' CEILING GRID GRAY HATCH INDICATES "NOT IN SCOPE"
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :0
P
M
Author
Checker
FIRST FLOOR
REFLECTED
CEILING PLAN -
PART B
A102
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
1/8" = 1'-0"A1
FIRST FLOOR REFLECTED CEILING PLAN - PART B
KEYNOTE LEGEND - SHEET
Key Value Keynote Text
024119.06 EXISTING LOUVERS AND GRILLES TO REMAIN. WHERE REMOVAL IS REQUIRED, LOUVERS AND GRILLES SHALL BE SALVAGED FOR RE-INSTALLATION. AT FIRST FLOOR, EXISTING LOUVERS TO BE REMOVED FOR
EQUIPMENT PATHWAY, TYPICAL, FOR ALL AIR HANDLER LOCATIONS
024119.13 REMOVE EXISTING SUSPENDED ACOUSTICAL PANEL CEILING GRID AND TILES IN WORK AREA - PROTECT AND STORE FOR REUSE. ASSUME REPLACEMENT OF 1000 SF OF SAPC TOTAL THROUGHOUT ALL AREAS INDICATED WITH THIS KEYNOTE. REMOVAL MAY BE REQUIRED IN AREAS BEYOND SCOPE BOUNDARY.
REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR CONCENTRATED AREAS OF WORK AT
EQUIPMENT LOCATIONS.
024119.16 DEMOLISH EXISTING SUSPENDED ACOUSTICAL PANEL CEILING GRID AND TILES IN THIS CONTIGUOUS AREA. REPLACE WITH ALL NEW CEILING AND GRID. FIELD VERIFY EXISTING CEILING SYSTEM AND REPLACE TO MATCH EXISTING. EXISTING LIGHTS AND SYSTEMS NOT IN REPLACEMENT SCOPE ARE TO BE
PROTECTED FOR REUSE.
078413.01 WHERE ALTERNATION OF PENETRATIONS OCCUR PROVIDE CONTINUOUS FIRESTOP SEALANT TO MATCH
EXISTING UL FLOOR PENETRATION DESIGN
078443.01 WHERE FIRE RATED JOINT CONDITIONS ARE REQUIRED OR MODIFIED PROVIDE CONTINIUOUS JOINT
FIRESTOPPING
092900.01 PATCH AND REPAIR GYPSUM BOARD OR CMU AT LOCATIONS ABOVE AND BELOW CEILING, IMPACTED BY
THE WORK, TYPICAL THROUGHOUT ENTIRE WORK AREA
ETR
ETR
ETR
ETR ETRETRETR
ETR
E
E
E
E E
E
E
E
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
1 2 43 5 6 8 9 10 11 13 14 16 17 18
T
S
R
P
O
M
L
K
Q
U
15 15.83.2
N2
A4
A301
092216.01
072100.01
024119.01
024119.08
024119.06
024119.06
024119.01
024119.08
024119.08
024119.01
024119.08
024119.01
024119.06024119.06 024119.07
024119.10024119.10 024119.10024119.10
024119.10024119.10
035113.05035113.05
074213.01
035113.04
035113.05035113.05
035113.04
055000.01
055000.01055000.01
035113.03
035113.03
024119.02
TYP
A301
A2
TYP
035113.02
072100.01
092216.01 092216.01
092216.01
072100.01 072100.01
1.
2.
3.
4.
5.
PROTECT EXISTING FINISHES TO REMAIN FOR THE DURATION OF THE WORK. REPAIR OR REPLACE DAMAGED MATERIALS CAUSED BY THE
WORK.
PATCH AND PAINT WALLS, CEILINGS, AND/OR ADJACENT SURFACES TO MATCH EXISTING WHERE DEMOLITION WORK OCCURED.
PATCH AND REPAIR AREAS OF WALLS WHERE RADIATORS AND ALL ASSOCIATED PIPING AND HARDWARE WERE REMOVED.
PATCH AND REPAIR WALL WHERE EXISTING PENETRATIONS ARE REMOVED OR NEW PENETRATIONS ARE INSTALLED.
PENETRATIONS IN WALLS, CEILINGS, AND FLOORS NEED TO BE FIRE CAULKED USING APPROVED FIRE CAULKING FOR ALL RATED
CONSTRUCTION.
GENERAL NEW WORK NOTES
HANBURY EVANS WRIGHT VLATTAS + COMPANY
COPYRIGHT © 2022
DRAWN BY:
CHECKED BY:
PROJECT CODE:
DESCRIPTIONDATEMARK
SHEET TITLE:
SHEET NUMBER:
3 42 51 6
21 43 5 6
C
A
B
D
E
C
A
B
D
E
C O
N S
U L T
A N
T
P R
IN
T
E D
K E
Y P
L A
N
DATE:
HANBURY PROJECT NO:
213-2122-012
P R
O J E
C T
C O
D E
-2
-0
12/21/2023 BID SET
/2
/2
:4 :0
P
M
Author
Checker
THIRD FLOOR PLAN
- PART A
A103
Issue Date
E C
H O
L S
H A
L L
M E
C H
A N
IC
A
L
IM
P R
O V
E M
E N
T
SN
O
R F
O L K
V
IR
G
IN
IA
N O
R F
O L K
S T
A T
E U
N
IV
E R
S
IT
Y
21069.02
1/8" = 1'-0"A1
THIRD FLOOR PLAN - PART A
8' 16' 24'0'
KEYNOTE LEGEND - SHEET
Key Value Keynote Text
024119.01 DISMANTLE EXISTING METAL WALL PANEL SECTIONS TO EXTENT SHOWN AND STORE FOR REUSE (SEE PLAN DIMENSIONS AND HATCH PATTERN ON ELEVATIONS). CONTRACTOR TO PROVIDE TEMPORARY WEATHER PROTECTIVE BARRIER DURING CONSTRUCTION TO PREVENT WEATHER INFILTRATION AND
DAMAGE TO BUILDING INTERIOR DURING CONSTRUCTION.
024119.02 EXISTING ATTIC ACCESS LADDER TO REMAIN
024119.06 EXISTING LOUVERS AND GRILLES TO REMAIN. WHERE REMOVAL IS REQUIRED, LOUVERS AND GRILLES SHALL BE SALVAGED FOR RE-INSTALLATION. AT FIRST FLOOR, EXISTING LOUVERS TO BE REMOVED FOR
EQUIPMENT PATHWAY, TYPICAL, FOR ALL AIR HANDLER LOCATIONS
024119.07 EXISTING ACCESS DOOR TO REMAIN
024119.08 DEMOLISH LIGHT GAUGE METAL STUDS TO EXTENTS SHOWN - CLIP HEADER AND SILL TRACK - PROVIDE SMOOTH EDGE CONDITION. PREPARE OPENING TO RECEIVE NEW DEMOUNTABLE RIGID STUD FRAME
AFTER USE AS TEMPORARY CONSTRUCTION OPENING
024119.10 EXISTING ROOF SYSTEM - PROTECT…