E801_-_ELECTRICAL_SCHEDULES_AND_DIAGRAMS.pdf

PDF 415 KB Posted

Attached to
Haven on Vine Renovation Project State and local contract opportunity
Solicitation number
RFP2025-010
Issued by
Polk County, Lake Harbor CDP, Florida

About this file

The document E801 is an electrical schedules and diagrams sheet for the Haven on Vine Renovation Project in Kissimmee, Florida, prepared by Forefront Architecture & Engineering LLC and Cabral Engineering Inc. The sheet provides comprehensive electrical design details for a multi-unit residential renovation, including a voltage drop schedule, feeder schedule, fault current schedule, and circuit length tables for a 1200-amp service that will support 43 residential units. The electrical design covers a meter center (MC1) with 43 100-amp tenant breakers and two 400-amp tenant breakers, designed to handle a total diversified demand of 1,006 amps at 208V and a total unit load of 652,138 VA.

The electrical design reflects the project's complex infrastructure requirements, utilizing an Isolite E3-375-LCV1-1S-2S model meter center with specific provisions for residential unit electrical distribution. The project is funded through multiple sources including American Rescue Funds, County and City funds, HOME Investment Partnerships American Rescue Plan, and Community Development Block Grant. The electrical system is designed with multiple safety and efficiency considerations, including arc energy mitigation for protective devices over 1200A, NEMA 3R rated exterior equipment, and detailed circuit length calculations to ensure voltage drop does not exceed 3%. The design also incorporates specific lighting control programming for different areas, including automatic occupancy and daylight sensors to optimize energy efficiency across various building spaces.

View the file

Other files for this state and local contract opportunity

Other files attached to Haven on Vine Renovation Project, newest first.
File Type Posted
abstract._RFP2025-010_Haven_on_Vine_Project_Renovation_Project.pdf PDF
Mailboxes.pdf PDF
2025-05-07_REV_1_Sheets.dwf.pdf PDF
Mailboxes.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
E001_-_ELECTRICAL_-_GENERAL.pdf PDF
E801_-_ELECTRICAL_SCHEDULES_AND_DIAGRAMS.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
2025-05-07_REV_1_Sheets.dwf.pdf PDF
E001_-_ELECTRICAL_-_GENERAL.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
LMA_Report.pdf PDF
Super_8_Hotel_Structural_Inspection_Report_S&S.pdf PDF
LMA_Report.pdf PDF
Super_8_Hotel_Structural_Inspection_Report_S&S.pdf PDF
1815_W_Vine_St___Sewer_Inspection.pdf PDF
Super_8_Hotel_Structural_Inspection_Report_S&S.pdf PDF
Super_8_Hotel_Structural_Inspection_Report_S&S.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
LMA_Report.pdf PDF
1815_W_Vine_St___Sewer_Inspection.pdf PDF
Attachment_D_-_Phase_1A_–_43-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_E_-_Phase_1A_–_Energy_Cals.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_J_-_Phase_2B_–_Energy_Conservation_Checklist-2B-022025-Signed.pdf PDF
Attachment_K_–_Specifications.pdf PDF
Attachment_E_-_Phase_1A_–_Energy_Cals.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_K_–_Specifications.pdf PDF
Attachment_M_-_Project_Location.pdf PDF
RFP20205-010_HAVEN_ON_VINE_-_Renovation_Project.pdf PDF
Attachment_E_-_Phase_1A_–_Energy_Cals.pdf PDF
Attachment_M_-_Project_Location.pdf PDF
RFP20205-010_HAVEN_ON_VINE_-_Renovation_Project.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_I_-_Phase_2B_–_Office_Building_Renovation.pdf PDF
Attachment_D_-_Phase_1A_–_43-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_M_-_Project_Location.pdf PDF
Attachment_K_–_Specifications.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Show all 50

Haven on Vine Renovation Project has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TC/PC

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

100A

400A

200A

3.3%

VOLTAGE DROP SCHEDULE

DEVICE FEEDER

VOLTAGE DROP WIRE SIZE LENGTH

MC1 0.36% (4)#500kcmil AL 30'

H 1.77% (2)#300kcmil AL 120'

ATS-LV 2.35% / 0.48% #1/0 AL / #2/0 AL 120' / 120'

LV1 #4/0 AL 250'

LV2 2.92% #4/0 AL 360'

INV1 1.8% #10 5'

POOL 2.97% #300kcmil AL 350'

H1 2.95% (2)#250kcmil AL 390'

INV2 3% #10 5'

FAULT CURRENT SCHEDULE

DEVICE FAULT AIC

RATING

L-L

VOLTS

TRANSFORMER

KVA Z% FAULT AT

PRIMARY

Utility T1 41,659 65,000 208V 300 2 UTILITY

MC1 37,026 65,000 208V

H 15,811 65,000 208V

ATS-LV 3,858 35,000 208V

LV1 2,065 10,000 208V

LV2 1,714 10,000 208V

INV1 9,540 22,000 120V

POOL 3,332 10,000 208V

H1 5,798 22,000 208V

INV2 4,603 22,000 120V

30/1

125.C

175/2.D

225.A

400.D

450.A

1200.B

FEEDER SCHEDULE

ID FEEDER

AMPS

CONDUIT AND FEEDER

30 1#10,#10N,#10G,1/2"C

110 3#1/0 AL,#1/0 AL N,#6G,2"C

125 3#2/0 AL,#2/0 AL N,#4G,2"C

175 2#4/0 AL,#4/0 AL N,#2G,2"C

225 3#300kcmil AL,#300kcmil AL N,#1G,3"C

400 (2)3#250kcmil AL,#250kcmil AL N,#3G,3"C

450 (2)3#300kcmil AL,#300kcmil AL N,#1G,3"C

1200 (4)3#500kcmil AL,#500kcmil AL N,#3/0G,4"C

USE CU GROUNDS

1ST FLR

2ND FLR

ROOF

#3/0 CU

METALLIC

WATER PIPE

BLDG LPS

CONCRETE

ENCASED

BLDG STEEL

ST

MC1

208Y/120V 3P 4W

1200A BUS

1200A MCB

450.A

208Y/120V 1P 3W

UNIT

PANEL P1

100A

MLO

Typical of 23

XFMR Utility T1

ASSUMED 300 KVA

208Y/120V

PANEL

POOL

200A MLO

208Y/120V 3P 4W

225.A

INV1

120V

30/1

INV2

120V

30/1

PANEL

LV1

60A

MCB

208/120V 2P 3W

1200.B

ATS-LV

208Y/120V

3P 4W

NEMA 3R

100A

PANEL

LV2

60A

MCB

208/120V 2P 3W

G1 208Y/120V

3P 4W

35KW

125.C

100/3

175/2.D

175/2.D

TC/PC

400.D

UNIT

PANEL P1

100A

MLO

208Y/120V 1P 3W

Typical of 17

UNIT

PANEL P2

100A

MLO

208Y/120V 1P 3W

Typical of 3

PANEL H

MCB

400A

208Y/120V 3P 4W

PANEL H1

MCB

200A

208Y/120V 3P

4W N E LOADS

MAX LENGTH (FT) / COPPER GND SIZE

#12 AWG

1/2" PVC

1/2" EMT

#10 AWG

1/2" PVC

1/2" EMT

#8 AWG

3/4" PVC

3/4" EMT

#6 AWG

3/4" PVC

3/4" EMT

#4 AWG

1" PVC

1" EMT

220' / #12 340' / #10 540' / #8 870' / #6

110' / #12 170' / #10 270' / #8 430' / #6 690' / #4

70' / #12 110' / #10 180' / #8 290' / #6 450' / #4

50' / #12 80' / #10 130' / #8 210' / #6 340' / #4

50' / #10 90' / #8 140' / #6 230' / #4

70' / #10 110' / #8 170' / #6

50' / #10 80' / #8 140' / #6

70' / #10 110' / #8

100' / #8

120V SINGLE PHASE CIRCUIT LENGTH

BREAKER

AMPACITY

(AMPS)

MAX

CIRCUIT

LOAD

(AMPS)

20 4

20 8

20 12

20 16

30 24

40 32

50 40

60 48

70 56

208V SINGLE PHASE CIRCUIT LENGTH

MAX LENGTH (FT) / COPPER GND SIZE

2/0

2" PVC

2" EMT

3/0

2" PVC

2" EMT

4/0

2-1/2" PVC

2-1/2" EMT

20 4 360' / #12 580' / #10 920' / #8 1400' / #6

20 180' / #12 290' / #10 460' / #8 730' / #6

20 120' / #12 180' / #10 300' / #8 490' / #6 770' / #4

20 80' / #12 130' / #10 220' / #8 350' / #6 580' / #4

30 80' / #10 150' / #8 230' / #6 390' / #4 490' / #3

40 110' / #10 180' / #8 290' / #6 360' / #4 450' / #4 560' / #3

50 80' / #10 130' / #8 240' / #6 290' / #4 350' / #4 460' / #3 590' / #1

60 110' / #10 180' / #8 240' / #6 300' / #6 360' / #4 490' / #3 500' / #2 700' / #1

70 170' / #8 200' / #6 250' / #6 310' / #4 410' / #3 470' / #2 600' / #1 700' / #1

80 140' / #8 180' / #6 220' / #6 270' / #4 360' / #3 410' / #2 510' / #1 600' / #1

90 170' / #8 200' / #6 240' / #4 320' / #3 360' / #2 450' / #1 590' / #1

100 140' / #8 180' / #6 210' / #4 290' / #3 320' / #2 410' / #1 540' / #1

110 160' / #6 190' / #4 260' / #3 290' / #2 360' / #1 430' / #1

125 160' / #6 220' / #4 250' / #4 310' / #3 370' / #2

NOTE:

1. FOR 240V SINGLE PHASE, MULTIPLY LENGTH BY 1.15.

2. FOR 277V SINGLE PAHSE, MULTIPLY LENGTH BY 1.32.

3. FOR 480V SINGLE PHASE, MULTIPLY LENGTH BY 2.3.

BREAKER

AMPACITY

(AMPS)

MAX

CIRCUIT

LOAD

(AMPS)

#12 AWG

1/2" PVC

1/2" EMT

#10 AWG

1/2" PVC

1/2" EMT

#8 AWG

3/4" PVC

3/4" EMT

#6 AWG

1" PVC

1" EMT

#4 AWG

1" PVC

1" EMT

#3 AWG

1-1/4" PVC

1-1/4" EMT

#2 AWG

1-1/4" PVC

1-1/4" EMT

#1 AWG

1-1/2" PVC

1-1/2" EMT

1/0

2" PVC

2" EMT

20 8

20 12

20 16

30 24

40 32

50 40

60 48

70 56

80 64

90 72

100 80

110 88

125 100

NOTE:

1. FOR 240V 3-PHASE, MULTIPLY LENGTH BY 1.12.

2. FOR 480V 3-PHASE, MULTIPLY LENGTH BY 2.2.

208V THREE PHASE CIRCUIT LENGTH

MAX LENGTH (FT) / COPPER GND SIZE

2/0

2" PVC

2" EMT

3/0

2" PVC

2" EMT

4/0

2-1/2" PVC

2-1/2" EMT

20 4 390' / #12 610' / #10 970' / #8

20 190' / #12 300' / #10 480' / #8 770' / #6

20 120' / #12 190' / #10 320' / #8 520' / #6 810' / #4

20 90' / #12 130' / #10 230' / #8 370' / #6 610' / #4

30 90' / #10 160' / #8 250' / #6 410' / #4 520' / #3

40 120' / #10 190' / #8 300' / #6 380' / #4 480' / #4 600' / #3

50 90' / #10 140' / #8 250' / #6 310' / #4 370' / #4 480' / #3 650' / #1

60 120' / #10 190' / #8 260' / #6 320' / #6 400' / #4 540' / #3 640' / #2 790' / #1

70 180' / #8 220' / #6 270' / #6 350' / #4 460' / #3 520' / #2 660' / #1 840' / #1

80 160' / #8 210' / #6 260' / #6 320' / #4 400' / #3 460' / #2 560' / #1 660' / #1

90 170' / #8 210' / #6 270' / #4 350' / #3 400' / #2 510' / #1 600' / #1

100 150' / #8 190' / #6 240' / #4 320' / #3 370' / #2 450' / #1 540' / #1

110 170' / #6 220' / #4 290' / #3 330' / #2 420' / #1 530' / #1

125 180' / #6 250' / #4 290' / #4 350' / #3 370' / #2

BREAKER

AMPACITY

(AMPS)

MAX

CIRCUIT

LOAD

(AMPS)

#12 AWG

1/2" PVC

1/2" EMT

#10 AWG

1/2" PVC

1/2" EMT

#8 AWG

3/4" PVC

3/4" EMT

#6 AWG

1" PVC

1" EMT

#4 AWG

1" PVC

1" EMT

#3 AWG

1-1/4" PVC

1-1/4" EMT

#2 AWG

1-1/4" PVC

1-1/4" EMT

#1 AWG

1-1/2" PVC

1-1/2" EMT

1/0

2" PVC

2" EMT

20 8

20 12

20 16

30 24

40 32

50 40

60 48

70 56

80 64

90 72

100 80

110 88

125 100

OFFICES, JANITOR CLOSETS, MULTIPURPOSE

ROOMS, STORAGE ROOMS, GREEN ROOM,

LIBRARY MEDIA CENTER, INDOOR PLAY, CONTROL,

KITCHEN, GYMNASIUM

1. ON: MANUAL ON THROUGH LOCAL SWITCH(ES). OFF: AUTOMATIC OFF THROUGH ROOM

OCCUPANCY SENSOR(S) WITHIN 20 MINUTES OF NO OCCUPANCY.

2. LOCAL SWITCH(ES): FOR MANUAL ON/OFF & DIMMING CONTROL.

3. DAYLIGHT SENSOR: FOR AUTOMATIC CONTROL OF LIGHTING FOR DIMMING FIXTURES BASED

ON DAYLIGHT LEVELS FOR ROOMS ON THE BUILDING PERIMETER. ONCE DAYLIGHT SENSOR

AUTO CALIBRATES IN THE ROOM, SET DAYLIGHT SENSOR TO DIM TO NO LESS THAN 30%, AND

"FAST" DIMMING RATE.

MECHANICAL, ELEC, AND IDF

ROOM

RESTROOMS, TOILETS

AREAS (WHERE APPLICABLE) CONTROL SCHEME

CORRIDORS

EXTERIOR BLDG WALL LIGHTS, EXTERIOR

CANOPY LIGHTS, EXTERIOR PATHWAY AND

PARKING LOT LIGHTING

1. LIGHTING ON/OFF BY LOCAL SWITCH

1. ON: AUTOMATIC ON THROUGH OCCUPANCY SENSORS DURING & AFTER PROGRAMMED

NORMAL OPERATING HOURS. OFF: AUTOMATIC OFF THROUGH OCCUPANCY SENSOR(S)

WITHIN 20 MINUTES OF NO OCCUPANCY.

1. ON: AUTOMATIC ON THROUGH TIME OF DAY SCHEDULE DURING PROGRAMMED NORMAL

OPERATING HOURS. OFF: AUTOMATIC OFF AFTER PROGRAMMED OPERATING HOURS.

2. LOCAL SWITCH(ES): (SLVO) ARE OVERRIDE SWITCHES FOR HOUSEKEEPING/MAINTENANCE

PURPOSES AFTER PROGRAMMED NORMAL OPERATING HOURS. LIGHTS SHALL STAY ON FOR A

MAXIMUM OF TWO HOURS.

3. DAYLIGHT SENSOR: FOR AUTOMATIC CONTROL OF LIGHTING FOR DIMMING FIXTURES BASED

ON DAYLIGHT LEVELS FOR LIGHTS WITHIN DAYLIGHT ZONES SHOWN AT BUILDING PERIMETER.

ONCE DAYLIGHT SENSOR AUTOCOLLIMATORS IN THE ARE, SET DAYLIGHT SENSOR TO DIM TO

NO LESS THAN 30% "FAST" DIMMING RATE.

1. ON: AUTOMATIC ON THROUGH LIGHTING CONTROL RELAY PANEL SYSTEM PHOTOCELL AT

DUSK OFF AT DAWN BY LIGHTING CONTROL RELAY PANEL SYSTEM PHOTOCELL.

2. PARKING LOT AND NON-FACADE SITE LIGHTING: AUTO-ON/OFF VIA PHOTOCELL. FIXTURES

SHALL BE PROVIDED WITH INTEGRAL MOTION SENSOR TO DIM TO 50% FROM ONE HR AFTER

AND PRIOR TO NORMAL BUSINESS HOURS WHEN ACTIVITY HAS NOT BEEN DETECTED FOR

MORE THAN 15 MINUTES.

PROGRAMMING NOTES

1. TIME CLOCK/LIGHTING CONTRACTOR IS TO BE PROGRAMMED FOR THE TIME-OF-DAY SCHEDULE FOR NORMAL OPERATING HOURS.

2. VERIFY OPERATING HOURS WITH OWNERS REPRESENTATIVE PRIOR TO PROGRAMMING.

3. ALL OTHER DAYS AND TIMES SHALL BE CONSIDERED "AFTER NORMAL OPERATING HOURS" FOR THE PURPOSES OF PROGRAMMING DESCRIPTIONS.

CONTROL TYPE

STAND-ALONE LIGHTING

CONTROL

STAND-ALONE LIGHTING

CONTROL

STAND-ALONE LIGHTING

CONTROL

LIGHTING CONTROL

RELAY PANEL

LIGHTING CONTROL

RELAY PANEL

WAREHOUSES

1. ON: OCCUPANT SENSORS OR TIMECLOCK. OFF: OCCUPANT SENSORS, TIMECLOCK.

2. LOCAL SWITCH(ES): MANUAL OVERRIDES.

3. OCCUPANT SENSOR SHALL REDUCE LIGHT TO 50% AFTER 20 MINUTES OF NO

OCCUPANCY.

LIGHTING CONTROL

RELAY PANEL

ALL LIGHTING SHALL BE CONTROLLED AS SPECIFIED BELOW

LIGHTING CONTROL PROGRAMMING/COMMISSIONING REQUIREMENTS

1230 Oakley Seaver Drive, Suite 100 Clermont, Florida 34711

888.850.FFAE (3323)

www.forefrontae.com

A R C H I T E C T U R E

E N G I N E E R I N G

Engineering - Consulting - Project Management 934 N Magnolia Ave, Suite 326, Orlando, FL 32803

(321) 246 - 4041 C.A. No. 33227 CEI Project # 24.86

This item has been electronically signed and sealed by francisco cabral, PE on the date and/or time stamp shown using a digital signature. Printed copies of this document are not considered signed & sealed and, the signature must be verified on any electronic copies.

C FOREFRONT ARCHITECTURE & ENGINEERING LLC 2014 THIS DOCUMENT AND/OR THE DESIGN CONCEPTS EXPRESSED HEREIN ARE THE PROPERTY OF FOREFRONT ARCHITECTURE & ENGINEERING LLC AND ALL RIGHTS OF OWNERSHIP, INCLUDING COPYRIGHT OF INTELLECTUAL PROPERTY, ARE RESERVED. ANY REPRODUCTIONS, COPYING, OR USE OF THIS DOCUMENT AND/OR THE DESIGN CONCEPT WITHOUT THE WRITTEN CONSENT OF FOREFRONT ARCHITECTURE & ENGINEERING LLC IS STRICTLY PROHIBITED AND PROTECTED BY UNITED STATES AND INTERNATIONAL LAW. IF PRINTED ON 11X17 SCALE IS HALF THE SIZE NOTED.C:sersichaelCucuta\OneDrive - cabralengineering.com\DESIGN\ACTIVE\Haven On Vine\02 Client Input\20240710 exisitng P1A, P1B\HAVEN ON VINE - Standard\TTB; Plot Date: Tuesday, December 05, 2023,1:10:09 PM; Plotted By: MichaelCucuta

ANY DISCREPANCY OR

ERROR IN DIMENSIONS OR

NOTES SHALL BE BROUGHT

TO THE ATTENTION OF THE

DESIGN PROFESSIONAL FOR

CLARIFICATION PRIOR TO

COMMENCEMENT OF

CONSTRUCTION.

JOB # :

JO

B N

A M

E

S H

E E T N

A M

E

ISSUE - REVISION LOG

AR102538 - CA30900

SHEET NUMBER :

H A V E N

O N

V

IN

E

A

W

E S T V

IN

E S

T R

E E T K

IS

S

IM

M E E F L

M A R

K D

A T E

D E S C R

IP

T

IO

N

24-13596

/1 /2

A d d e n d u m

E L

E C

T R

IC

A

L S

C H

E D

U L

E S

A N

D D

IA

G

R A

M S

E801

RISER DIAGRAM KEY NOTES

1. ALL PROTECTIVE DEVICES 1200A OR LARGER SHALL BE PROVIDED WITH

ARC ENERGY MITIGATION AS REQUIRED BY THE NEC.

2. ALL SERVICE EQUIPMENT SHAL LBE FROM THE UTIITY-APPROVED

EQUIPMENT LIST. CONSULT UTILITY COMPANY FOR REQUIREMENTS.

3. ALL EXTERIOR EQUIPMENT SHAL LHAVE A MINIMUM RATING OF NEMA 3R.

4. CONTRACTOR SHALL NOT USED DESIGN AND CALCULAITON LENGTHS FOR

BIDDING OR PROCUREMENT. CONTRACTOR SHALL PERFORM FIELD

MEASUREMENTS AND IS RESPONSUIBLE FOR PROVIDING ENOUGH

MATERIAL FOR A SAFE AND COMPLETE INSTALLATION.

5. PROVIDE 100% RATED SERVICE DISCONNECTS AND MAIN BREAKERS FOR

PANELS "H" AND "H1".

LIVING UNIT LOAD CENTER SINGLE-PHASE FEEDER SCHEDULE (MAX VD<=3%)

LOAD CENTER

AMP RATING

FEEDER LENGTH

FROM METER CENTER

TO LOAD CENTER SINGLE-PHASE ALUMINUM FEEDER SINGLE-PHASE COPPER FEEDER

100 AMP

UP TO 130' 2#1 AL,#1 AL N,#8G,1-1/2"C 2#3,#3N,#8G,1-1/4"C

131' TO 180' 2#1/0 AL,#1/0 AL N,#4G,1-1/2"C 2#2,#2N,#6G,1-1/4"C

181' TO 220' 2#2/0 AL,#2/0 AL N,#4G,2"C 2#1,#1N,#4G,1-1/2"C

221' TO 280' 2#3/0 AL,#3/0 AL N,#3G,2"C 2#1/0,#1/0N,#3G,1-1/2"C

281' TO 320' 2#4/0 AL,#4/0 AL N,#2G,2"C 2#2/0,#/0N,#2G,2"C

NOTES

1. INCREASE LUG SIZE FOR ALL METER CENTER MAINS AND LOAD CENTERS AS REQUIRED TO ACCOMMODATE ALL

CONDUCTORS.

2. ALL GROUNDS ARE CU.

3. ASSUMES LENGTH FROM TRANSFORMER TO METER CENTER IS NOT GREATER THAN 100'

SHUNT TRIP KNOCK BOX. COODRIDNATE

LOCATION WITH FIRE MARSHALL

METER CENTER MC1

1. EZ METER PAK (OR EQUAL)

2. NEMA 3R

3. MAIN SECTION:

A. 1200A, 120/208V, 3Ø, 4W

B. 1200A, 3Ø MAIN CIRCUIT

BREAKER.

4. BRANCH SECTIONS:

A. 43 - 100A, 120/208V, 1Ø, 3W

TENANT BREAKERS AND

METER CANS.

B. 2 - 400A, 120/208V, 3Ø, 4W

TENANT BREAKER AND

METER CAN.

MODEL:

ISOLITE E3-375-LC-

V1-1S-2S

SEE LIVING UNIT FEEDER SCHEDULE FOR

APARTMENT UNIT FEEER SIZING

SIZED, F&I BY UTILITY

COMPANY

CIRCUIT LENGTH TABLES NOTES

1. UON, CIRCUIT MAXIMUM DISTANCE IS BASED ON NEC CHAPTER 9, TABLE 8

CONDUCTOR PROPERTIES FOR COATED COPPER CONDUCTORS AT 75 DEGREES

CELSIUS. CONTRACTOR SHALL RECALCULATE AMPACITIES AND CIRCUIT

LENGTHS WHEN USING ALUMINUM OR IF TEMPERATURE RATINGS ARE

DIFFERENT.

2. BASED OF MAX VD=3%.

3. BASED ON UP TO 3 CURRENT-CARRYING CONDUCTORS IN A RACEWAY.

CONTRACTOR SHALL DE-RATE PER NEC AS REQUIRED WHEN INSTALLING MORE

THAN 3 CURRENT-CARRYING CONDUCTORS IN A SINGLE RACEWAY.

4. SIZE CONDUIT BASED ON TYPE FOR A MAX 40% FILL.

5. CONTRACTOR SHALL SIZE GROUND CONDUCTOR PER NEC AND INCREASE AS

REQUIRED FOR VOLTAGE DROP.

6. CONTRACTOR SHALL USE CABLE REDUCERS WHEN REQUIRED TO CONNECT

UPSIZED CONDUCTORS.

7. USE COPPER GROUND. SIZE GROUND CONDUCTOR PER NEC 250.122.

8. SIZE CONDUIT PER NEC ANNEX C TABLES. BASED ON CONDUIT TYPE, NUMBER

OF CONDUCTORS AND INSTALLATION ENVIRONMENT.

MODEL:

ISOLITE E3-375-LC-

V1-1S-2S-3S-4S

SERVICE SIZE (AMPS) 1200

DEMAND AMPS AT 208V 3-PHASE (AMPS) 1006

METER CENTER TOTAL (VA) 361987

HOUSE PANEL LOAD (VA) (H + H1) 185,910

TOTAL DWELLING DIVERSIFIED DEMAND (VA) 176077

NEC TABLE 220.84 FACTOR 0.27

NUMBER OF UNITS 43

UNIT TOTAL LOAD (VA) 652138

RESIDENTIAL UNIT 43 15166 652138

UNIT TYPE COUNT

UNIT LOAD

(VA) TOTAL (VA)

METER CENTER FEEDER CALCULATION

Sheets
E801 - ELECTRICAL SCHEDULES AND DIAGRAMS
2025-05-06T17:18:52-0400
Francisco J Cabral