1815_W_Vine_St___Sewer_Inspection.pdf

PDF 3 MB Posted

Attached to
Haven on Vine Renovation Project State and local contract opportunity
Solicitation number
RFP2025-010
Issued by
Polk County, Lake Harbor CDP, Florida

About this file

This document is a sewer line inspection report prepared by National Property Inspections for the City of Kissimmee, Florida, focusing on the sewer systems of multiple buildings located at 1815 W Vine Street. The inspection was conducted on March 29, 2024, and covered the main building, apartment buildings, an annex building, and a gym building. The comprehensive evaluation utilized camera inspections to assess the condition of drain lines, accessing various points including clean-outs, plumbing stacks, and entry points across different structures.

The inspection revealed multiple significant issues across the property's sewer systems, including improper slopes, debris accumulation, scale build-up, extensive deterioration, potential seepage, and deteriorated couplings. Of particular concern were observations of high staining indicating previous backups, potential clogs, and sections of drain lines that appeared non-functional or obstructed. The report consistently recommends further evaluation by a qualified plumbing contractor and suggests comprehensive line clearing and potential repairs. These findings are particularly relevant to the City of Kissimmee's Haven on Vine Renovation Project, which aims to convert the property into emergency housing and apartment units, indicating that significant infrastructure work may be necessary before the development can be completed.

View the file

Other files for this state and local contract opportunity

Other files attached to Haven on Vine Renovation Project, newest first.
File Type Posted
abstract._RFP2025-010_Haven_on_Vine_Project_Renovation_Project.pdf PDF
2025-05-07_REV_1_Sheets.dwf.pdf PDF
Mailboxes.pdf PDF
E801_-_ELECTRICAL_SCHEDULES_AND_DIAGRAMS.pdf PDF
2025-05-07_REV_1_Sheets.dwf.pdf PDF
Mailboxes.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
2025-05-07_REV_1_Sheets.dwf.pdf PDF
E001_-_ELECTRICAL_-_GENERAL.pdf PDF
Addendum_2_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
Lead_Survey_Report.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
City_of_Kissimmee_Super_8_Motel_Inspection_Report_2_8_23_-_Structural_Comments.pdf PDF
Lead_Survey_Report.pdf PDF
1815_W_Vine_St___Sewer_Inspection.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
Lead_Survey_Report.pdf PDF
LMA_Report.pdf PDF
Lead_Survey_Report.pdf PDF
Lead_Survey_Report.pdf PDF
Super_8_Hotel_Structural_Inspection_Report_S&S.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
Addendum_1_RFP2025-010_Haven_on_Vine_Restoration_Project.pdf PDF
LMA_Report.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_M_-_Project_Location.pdf PDF
Attachment_I_-_Phase_2B_–_Office_Building_Renovation.pdf PDF
Attachment_D_-_Phase_1A_–_43-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_E_-_Phase_1A_–_Energy_Cals.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_I_-_Phase_2B_–_Office_Building_Renovation.pdf PDF
Attachment_D_-_Phase_1A_–_43-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_E_-_Phase_1A_–_Energy_Cals.pdf PDF
Attachment_I_-_Phase_2B_–_Office_Building_Renovation.pdf PDF
Attachment_D_-_Phase_1A_–_43-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_J_-_Phase_2B_–_Energy_Conservation_Checklist-2B-022025-Signed.pdf PDF
Attachment_K_–_Specifications.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_I_-_Phase_2B_–_Office_Building_Renovation.pdf PDF
Attachment_D_-_Phase_1A_–_43-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_M_-_Project_Location.pdf PDF
Attachment_K_–_Specifications.pdf PDF
Attachment_L_-_General_Wage_Decision_3.29.24.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Attachment_H_-_Phase_2A_–_Energy_Conservation_Checklist-2A-022025-Signed.pdf PDF
Attachment_F_-_Phase_1B_–_Ten_Fourplex_Apartment_Building_Renovation.pdf PDF
Attachment_G_-_Phase_2A_–_40-Efficiency_Studio_Apartment_Units.pdf PDF
Show all 50

Haven on Vine Renovation Project has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1815 W Vine St City of Kissimmee

National Property Inspections Page 1 of 26

NATIONAL PROPERTY INSPECTIONS

407-277-4555 josh.rogers@npiinspect.com https://www.npiweb.com/orlando1/

SEWER INSPECTION

1815 W Vine St Kissimmee, FL 34741

City of Kissimmee

MARCH 29, 2024

Inspector

Joshua Rogers Fl Lic # HI8805 407-277-4555 josh.rogers@npiinspect.com tel:407-277-4555 mailto:josh.rogers@npiinspect.com https://www.npiweb.com/orlando1/ tel:407-277-4555 mailto:josh.rogers@npiinspect.com

National Property Inspections Page 2 of 26

TABLE OF CONTENTS

1: General Information

2: Inspection Details

3: Main Building - Qualitative Survey of Main Sewer Line

4: Apartments - Qualitative Survey of Main Sewer Line

5: Annex Building - Qualitative Survey of Main Sewer Line

6: Gym Building - Qualitative Survey of Main Sewer Line

7: Main Building - Video(s)

8: Apartments - Video(s)

9: Annex Building - Video(s)

10: Gym Building - Video(s)

National Property Inspections Page 3 of 26

3.1.1 Main Building - Qualitative Survey of Main Sewer Line - Drain System: Belly or Improper Slope

3.1.2 Main Building - Qualitative Survey of Main Sewer Line - Drain System: Debris

3.1.3 Main Building - Qualitative Survey of Main Sewer Line - Drain System: Scale Build Up

3.1.4 Main Building - Qualitative Survey of Main Sewer Line - Drain System: Extensive Deterioration and Occlusion

3.1.5 Main Building - Qualitative Survey of Main Sewer Line - Drain System: End of Liner

3.1.6 Main Building - Qualitative Survey of Main Sewer Line - Drain System: Apparent Seepage

3.1.7 Main Building - Qualitative Survey of Main Sewer Line - Drain System: Camera not inserted due to debris

3.1.8 Main Building - Qualitative Survey of Main Sewer Line - Drain System: Coupling Deteriorated

4.1.1 Apartments - Qualitative Survey of Main Sewer Line - Drain System: Belly or Improper Slope

4.1.2 Apartments - Qualitative Survey of Main Sewer Line - Drain System: O�set

4.1.3 Apartments - Qualitative Survey of Main Sewer Line - Drain System: Debris

4.1.4 Apartments - Qualitative Survey of Main Sewer Line - Drain System: Scale Build Up

4.1.5 Apartments - Qualitative Survey of Main Sewer Line - Drain System: Grease

4.1.6 Apartments - Qualitative Survey of Main Sewer Line - Drain System: High Staining

5.1.1 Annex Building - Qualitative Survey of Main Sewer Line - Drain System: Debris

5.1.2 Annex Building - Qualitative Survey of Main Sewer Line - Drain System: High Staining

SUMMARY

RECOMMENDATION

National Property Inspections Page 4 of 26

Overview

National Property Inspections was retained for a survey of the building main sewer line in an e�ort to identify areas of suspect clogs or damage and to document the areas for further review. Further investigations of these areas or destructive testing may reveal additional conditions that were not readily visible at time of inspection. This report is based on information obtained at the site at the given date and time. We document our �ndings with videos and visual photographs of the areas. The purpose of any sewer scan service is to document problems in sewer lines. Our inspection is designed to comply with accepted industrial standards when at all possible and will be performed in a non-destructive manner, however at times destructive testing may be necessary. Prior to any destructive testing, the client will be noti�ed and approval by the client prior to commencing additional testing. Our inspection is not meant to be a guarantee of all a�ected areas; only those that reveal themselves to our sewer camera, visual inspection and our experience.

This report is for the exclusive use of our Client and is not intended for any other purpose. The report is based on the information available to us at this time as described in the report. Should additional information become available at a later date, we reserve the right to determine the impact, if any, the new information may have on our discovery and recommendations and to revise our opinions and conclusions if necessary and warranted. We can make no representations regarding conditions that may be present but concealed or inaccessible during the survey. With access and an opportunity for inspection, additional reportable conditions may be discovered. Inspection of the inaccessible areas will be performed at an additional cost after access is provided.

Orientation

We will describe the locations of the various features of this property, left or right, etc., as though we were standing in street looking at the front of building or looking at it as the cover photo.

Comment key and de�nitions

Moderate = The area while perhaps functioning as intended is in need of moderate repair, service; is showing signs of wear or deterioration that could result in an adverse condition at some point in the future; or considerations should be made in upgrading the area to enhance the proper function. Items falling into this category can frequently be addressed by a quali�ed contractor and are not considered routine maintenance or DIY items.

Major = The area noted poses a Major concern to the sewer lateral and or main drain line of the home.

The areas noted that are Not functioning as intended, or needs further evaluation by a specialized quali�ed licensed plumbing contractor or can cause problems to the sewer lines. Areas that can be repaired to satisfactory condition may not need replacement.

Summary of �ndings:

We recommend attention to the items noted in this report. It should be understood that sometimes due to extent of debris or roots found, we are unable to fully access line. We recommend further review of lines in these cases when cleared and the lines can be better accessed at that time. Due to the complexity of the sewer lines; there are times where the full drain can not be accessed. We are not a plumbing company. We do highly recommend that everything be double checked by a licensed sewer expert.

There may be problems in video not listed in report. Problem areas may be shown in video; however photos may just be of 1 problem that continues to show again and again or something that did not photo well.

1: GENERAL INFORMATION

Information section-YzJjZDUyYWMtYWEyZi00MDIzLWJmMWQtZDYxZWJhNjM5M2Ni

National Property Inspections Page 5 of 26

Analysis and Recommendations

We recommend that your maintenance team carefully review this report. Then, with reference to the imagery and areas denoted in the report, these areas should be physically located and given a thorough visual examination. When warranted, these areas should be subjected to a destructive investigation to con�rm the analysis and determine the possible detrimental e�ects the blockage may have caused. We recommend a specialist conduct additional testing as needed to evaluate the reliability of system. Any destructive testing performed as authorized by the client must be repaired by others and is not considered in this scope of our work. Services such as interpretation of visual patterns documented in this report and any remedial and replacement recommendations should be performed by knowledgeable experts.

We recommend all areas we locate in this report showing blockage and other anomalies should be evaluated further to �nd out the cause and repaired. Our recommendations are not intended as criticisms of the building, but rather as professional opinions regarding conditions that we observed.

Our reports are designed to be clear, concise and useful. Please review this report carefully. If there is anything you would like us to explain, or if there is other information you would like, please feel free to call us as we would be happy to answer any questions.

National Property Inspections Page 6 of 26

In Attendance

Employees Occupancy

Partially Occupied Type of Building

Multi-Family

Weather Conditions

Clear

Photo and Video Locations

To determine the location of photos and videos refer to the linear foot located at the top left of the photo or video.

This is the linear from the access point.

2: INSPECTION DETAILS

Information

Limitations section-N2RkNjEyMmQtYzNhZi00MDJhLWExMzgtMDBhMzJhNTM0MDgx

General

CLIENTS REPORT

This report is for the person(s) named in the Client section only. Unauthorized use is prohibited with out said Client(s) and Anarumo Inspections permission. Liability under this report is limited to the party identi�ed on the cover page of this report.

General

SEWER SCAN

A Sewer Scan was requested of the main drain line from house/building to city/county or private sewer connection. The following is a report of our �ndings.

General

LIMITED INSPECTION AND FURTHER EVALUATION BY A PLUMBER

National Property Inspections Page 7 of 26

The inspection of the sewer lateral system was limited due to lack of accessibility, size of the property, directional clean outs, obstructions and age of the sewer lateral system. A more in-depth inspection may be available for an additional cost.

The inspector was unable to determine for certain where this property's sewer lateral system ends and the city's begins. Ponding and/or a slow �ow was observed in the proximity of these areas.

It is recommended a plumbing contractor further review the sewer lateral system after a thorough review of this report.

National Property Inspections Page 8 of 26

Drain System: Main Drain(s)

Access Location(s)

Entry, Left front corner of building, Left middle corner of building, Left rear of building, Plumbing Stacks via Roof

Drain System: Materials from access

Cast Iron, PVC, Clay (appears to be)

All sewer line materials are not always identi�able.

3: MAIN BUILDING - QUALITATIVE SURVEY OF MAIN

SEWER LINE

Information

Observations section-ODBlMGMxNzItNjk4Ni00YTc5LWJkOTctODdkZTYwNzlhNDlh

3.1.1 Drain System

BELLY OR IMPROPER SLOPE

There appears to be a low point or improper slope in the drain line which may promote clogging. We recommend further review and repair as needed.

Recommendation

Contact a quali�ed plumbing contractor.

Accessed from clean out at front left of building

Accessed from middle plumbing stack Accessed from front plumbing stack

National Property Inspections Page 9 of 26

Accessed from front plumbing stack Accessed from rear plumbing stack

3.1.2 Drain System

DEBRIS

There is debris build up in the line, we recommend clearing as needed to prevent further clogging.

Recommendation

Contact a quali�ed plumbing contractor.

Accessed from rear plumbing stack Accessed from front plumbing stack Accessed from front plumbing stack

Accessed from middle plumbing stack

3.1.3 Drain System

SCALE BUILD UP

There is scale build up inside sewer line which will promote clogging. We recommend repair as needed.

Recommendation

Contact a quali�ed plumbing contractor.

Accessed from clean out at front left of building

Accessed from clean out left rear of

Accessed from front plumbing stack

National Property Inspections Page 10 of 26

Accessed from clean out at front left of building

Accessed from middle plumbing stack Accessed from middle plumbing stack

3.1.4 Drain System

EXTENSIVE DETERIORATION AND OCCLUSION

Extensive deterioration and occlusion were observed to the drain line. It appears the line is completed obstructed or no longer in service. Recommend further evaluation by a plumbing contractor.

Recommendation

Contact a quali�ed plumbing contractor.

Accessed from clean out at entry

Accessed from clean out at entry

Accessed from clean outs left middle of building

Accessed from clean outs left middle of building

3.1.5 Drain System

END OF LINER

An obstruction that appears to be the end of a liner was observed.

Recommend further evaluation by a plumber.

Recommendation

Contact a quali�ed plumbing contractor.

Accessed from clean out left rear of

National Property Inspections Page 11 of 26

3.1.6 Drain System

APPARENT SEEPAGE

Standing water was observed in the pipe and appears to be from seepage from above the obstruction/liner. Recommend further evaluation by a plumber.

Recommendation

Contact a quali�ed professional. Accessed from clean out left rear of building

3.1.7 Drain System

CAMERA NOT INSERTED DUE TO DEBRIS

The camera was not inserted in one location due to extensive debris.

This drain line appears to be clogged or no longer in service.

Recommendation

Contact a quali�ed plumbing contractor.

Clean out left rear of building

3.1.8 Drain System

COUPLING DETERIORATED

One fernco coupling was observed deteriorated. It appears this drain line is no longer in service or clogged. Recommend further evaluation by a plumber.

Recommendation

Contact a quali�ed plumbing contractor.

Left middle of building

National Property Inspections Page 12 of 26

Drain System: Main Drain Access

Location

Rear of Buildings

Drain System: Materials from access

Cast Iron, PVC

All sewer line materials are not always identi�able.

4: APARTMENTS - QUALITATIVE SURVEY OF MAIN SEWER

LINE

Information

Observations section-YWJkYTI2ZGEtN2ExNC00MjA2LWFhMTctMDc1YmFkNjM3M2Ey

4.1.1 Drain System

BELLY OR IMPROPER SLOPE

There appears to be a low point or improper slope in the drain line which may promote clogging. We recommend further review and repair as needed.

Recommendation

Apartment Building B Apartment Building A Apartment Building C

National Property Inspections Page 13 of 26

Apartment Building D Apartment Building E Apartment Building F

Apartment Building G Apartment Building G Apartment Building H

Apartment Building I Apartment Building I Apartment Building J

Apartment Building J Apartment Building J

4.1.2 Drain System

OFFSET

There is a o�set in the drain line where two pipes are not properly connected and there is a "lip" which can cause clogging. We recommend further review and repair as needed.

Recommendation

Contact a quali�ed plumbing contractor. Apartment Building H

4.1.3 Drain System

DEBRIS

There is debris build up in the line, we recommend clearing as needed to prevent further clogging.

Recommendation

National Property Inspections Page 14 of 26

Apartment Building B Apartment Building A Apartment Building C

Apartment Building D Apartment Building E Apartment Building F

Apartment Building F Apartment Building F Apartment Building G

Apartment Building G Apartment Building G Apartment Building I

Apartment Building J

4.1.4 Drain System

SCALE BUILD UP

There is scale build up inside sewer line which will promote clogging. We recommend repair as needed.

National Property Inspections Page 15 of 26

Apartment Building B Apartment Building B Apartment Building B

Apartment Building B Apartment Building B Apartment Building A

Apartment Building C Apartment Building C Apartment Building F

Apartment Building D Apartment Building E Apartment Building G

Apartment Building H Apartment Building I Apartment Building J

4.1.5 Drain System

GREASE

There is grease build up in the line, we recommend clearing as needed to prevent further clogging.

National Property Inspections Page 16 of 26

Apartment Building A Apartment Building C Apartment Building G

Apartment Building I Apartment Building A

Apartment Building E

Apartment Building F Apartment Building J

4.1.6 Drain System

HIGH STAINING

High staining was observed which is typically an indication of previous back ups or clogs. Recommend monitor and have a qualied plumber �ush or clean lines as needed.

Recommendation

Apartment Building G Apartment Building J

National Property Inspections Page 17 of 26

Drain System: Main Drain Access

Location

Middle of Interior Chase

Drain System: Materials from access

PVC

All sewer line materials are not always identi�able.

5: ANNEX BUILDING - QUALITATIVE SURVEY OF MAIN

SEWER LINE

Information

Observations section-ZjBhNjA1NGEtMDk0Ny00NDFiLThjNjUtZjJlMzdjNTMyNjgx

5.1.1 Drain System

DEBRIS

There is debris build up in the line, we recommend clearing as needed to prevent further clogging.

National Property Inspections Page 18 of 26

5.1.2 Drain System

HIGH STAINING

High staining was observed which is typically an indication of previous back ups or clogs. Recommend monitor and have a qualied plumber �ush or clean lines as needed.

National Property Inspections Page 19 of 26

Drain System: Main Drain Access

Location

Front of building

Drain System: Materials from access

PVC

All sewer line materials are not always identi�able.

6: GYM BUILDING - QUALITATIVE SURVEY OF MAIN

SEWER LINE

Information

Limitations section-Nzc5MDc4YmMtYTNiNC00NmQwLWEzMWQtYTY1ZGU4MjFlNTkz

Drain System

NOT INSPECTED

It appeared the drain pipe size and con�guration prevented the camera from entering.

National Property Inspections Page 20 of 26

Video(s)

Informational video(s) from clean out at left middle corner of building.

Video(s)

Informational video(s) from clean out at left rear of building.

Video(s)

Informational video(s) from clean out at entry.

Video(s)

Informational video(s) from clean out at left front of building.

7: MAIN BUILDING - VIDEO(S)

Information section-YzM2YzU1OTUtYmJhMC00NjBiLWI3MmItYzUzMzhjNTg5YWI2

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web) https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab

National Property Inspections Page 21 of 26

Video(s)

Informational video(s) from plumbing stack at front of building.

Video(s)

Informational video(s) from plumbing stack at middle of building.

Video(s)

Informational video(s) from plumbing stack at rear of building.

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web) https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-c36c5595-bba0-460b-b72b-c5338c589ab6-information-tab

National Property Inspections Page 22 of 26

Video(s)

Informational Video(s) from clean out at Apartment Building A.

Video(s)

Informational Video(s) from clean out at Apartment Building B.

Video(s)

Informational Video(s) from clean out at Apartment Building C.

Video(s)

Informational Video(s) from clean out at Apartment Building D.

8: APARTMENTS - VIDEO(S)

Information section-OGYwMDBlOTMtMTZjNi00MTNkLWFjYTktNWM3MzNkNGVhNDE3

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web) https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab

National Property Inspections Page 23 of 26

Video(s)

Informational Video(s) from clean out at Apartment Building E.

Video(s)

Informational Video(s) from clean out at Apartment Building F.

Video(s)

Informational Video(s) from clean out at Apartment Building G.

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web) https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab

National Property Inspections Page 24 of 26

Video(s)

Informational Video(s) from clean out at Apartment Building H.

Video(s)

Informational Video(s) from clean out at Apartment Building I.

Video(s)

Informational Video(s) from clean out at Apartment Building J.

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web) https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-8f000e93-16c6-413d-aca9-5c733d4ea417-information-tab

National Property Inspections Page 25 of 26

Video(s)

Informational Video(s) from clean out at Annex Building.

9: ANNEX BUILDING - VIDEO(S)

Information section-MTUwNjgzMzMtYmQzNC00ZGIwLWFiMGItNjFhOTI5YThmMTZm

Video (click here to view on web)

Video (click here to view on web)

Video (click here to view on web) https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-15068333-bd34-4db0-ab0b-61a929a8f16f-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-15068333-bd34-4db0-ab0b-61a929a8f16f-information-tab https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-15068333-bd34-4db0-ab0b-61a929a8f16f-information-tab

National Property Inspections Page 26 of 26

Video(s)

Informational Video(s) from clean out at front of Gym Building.

10: GYM BUILDING - VIDEO(S)

Information section-MzkzNzE1NDUtNmZhNS00ZjdkLWExOTItZWYxMWEwYmRjMTI5

Video (click here to view on web) https://app.spectora.com/reports/6e638c4a-3169-4da8-8dbe-a43163ff5e4f#section-39371545-6fa5-4f7d-a192-ef11a0bdc129-information-tab

File details come from the government source that posted it. Updated .