E.9_Fire_Extinguisher_-_December_2023.pdf
PDF 134 KB Posted
- Attached to
- Request for Proposal ("RFP") Property Management Services at Francis L. Cardozo Education Campus
- Solicitation number
- DCAM-25-NC-RFP-0006
- Issued by
- District of Columbia
About this file
This document is a Fire Extinguisher Inspection report conducted by National Fire Protection, LLC for Cardozo High School located at 1300 Clifton Road NW in Washington, DC on December 14, 2023. The inspection was performed in accordance with NFPA 10, 2010 Edition, and covered a comprehensive survey of 52 fire extinguishers throughout the school's various rooms and locations. The inspection involved visual examination of each extinguisher, recording their size, type, manufacturer's date, serial number, and current location, with each extinguisher receiving a "Pass" status or being marked for replacement.
Notable details from the inspection include several extinguishers that were replaced (items 7, 30, 37, 45, and 49), and specific recommendations noted in the technician's comments. The technician, Paul Olson, indicated that certain extinguishers need to be mounted in specific rooms (C502, C205, 1603) and that some extinguishers require recharging in rooms 3504, T105, and 1603. The report also emphasizes that the inspection was limited to a visual assessment and that the company is not responsible for any changes to the extinguishers after the inspection. The extinguishers varied in size and type, including 5/ABC, 10/ABC, 10/CO2, 6/K, and 6/Water models, manufactured between 2015 and 2019.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Paul Olson
Fire Extinguisher Inspection
National Fire Protection, LLC 207A Perry Parkway
Gaithersburg, MD 20877
Tel: 301-340-6500 Fax: 301-309-1294
24 Hour Emergency Service: 800-741-5137 www.natlfire.com
Inspector : Date:
Inspection at Location
Cardozo High School
1300 Clifton Road NW
Washington, DC 20009
For Customer:
Cardozo High School
1300 Clifton Road NW
Washington, DC 20009
Work performed in accordance with
NFPA 10, 2010 Edition
12/14/2023 http://www.natlfire.com/
Service Codes: R = Repairs RC = Recharge C = Compliance NC = Non Compliance
H = 12 Year Hydro I = 6 Year Internal M = Maintenance X = Condemned
Pass/Fail Next
Size/Type MFRS. Date Serial # Code Location Service Date
1 5/ABC 2017 C84042248 C Inside C101 Pass
2 10/ABC 2017 L89994617 C Inside C101E (EMR) Pass
3 5/ABC 2017 C92515807 C Inside 3406 Pass
4 5/ABC 2017 C84042267 C Inside 3501 Pass
5 10/CO2 2019 F65983061 C Inside 3511 (Electric Room) Pass
6 10/ABC 2017 C93841444 C Inside 3502 Pass
7 5/ABC 2015 A37736414 I Inside 3504 Replaced
8 10/CO2 2019 F56496399 C Inside 3211 (Electric Room) Pass
9 5/ABC 2017 C84042246 C Inside 2204 Pass
10 10/CO2 2019 F56496420 C Inside 2211 (Electric Room) Pass
11 10/ABC 2019 F76151883 C Inside 2501 Pass
12 10/CO2 2019 F65983045 C Inside 2611 (Electric Room) Pass
13 5/ABC 2017 C84042240 C Inside 2602 Pass
14 5/ABC 2017 C92515256 C Inside 2604 Pass
15 5/ABC 2017 C84042256 C Inside 2104 Pass
16 10/ABC 2018 A40323189 C Inside 1611 Pass
17 5/ABC 2017 C84042238 RC Inside 1603 Pass
18 10/CO2 2019 F65983059 C Inside 1603 (Electric Room) Pass
19 5/ABC 2017 C84042237 C Inside 1503 Pass
20 5/ABC 2017 C84042241 C Inside 1501 Pass
21 5/ABC 2017 C92516866 C Inside 1401 Pass
22 10/ABC 2019 F76151884 C Inside 1304 Pass
23 5/ABC 2017 C84042236 C Inside 1301 Pass
24 10/CO2 2019 F65983048 C Inside 1211 (Electric Room) Pass
25 5/ABC 2017 C84042268 C Inside C205 Pass
26 10/CO2 2019 F65983048 C Inside C207 (Electric Room) Pass
27 5/ABC 2017 C84042256 C Inside C302 Pass
28 6/K 2019 F65996168 C Inside C118 (Kitchen) Pass
29 10/CO2 2019 F56496404 C Inside C502 (Electric Room) Pass
30 5/ABC 2017 C84042249 RC Inside C504 Replaced
31 10/CO2 2019 F56496406 C Inside C613 (Electric Room) Pass
32 5/ABC 2017 C84042239 C Inside LT33 (EMR) Pass
33 5/ABC 2017 C84042258 C Inside T302 Pass
34 5/ABC 2017 C84042247 C Inside T301 Pass
35 10/ABC 2017 B80239075 C Inside T209 Pass
36 10/ABC 2017 C89237294 C Inside T201 Pass
37 5/ABC 2017 C84042269 RC Spare Replaced
38 6/Water 2019 F75724398 C Inside Filtration Room Pass
39 10/CO2 2019 F56496422 Spare Pass
40 10/CO2 2019 F56496421 Spare Pass
Service Codes: R = Repairs RC = Recharge C = Compliance NC = Non Compliance
H = 12 Year Hydro I = 6 Year Internal M = Maintenance X = Condemned
Pass/Fail Next
Size/Type MFRS. Date Serial # Code Location Service Date
41 10/ABC 2019 F76151885 Spare Pass
42 10/ABC 2019 F76151919 Spare Pass
43 10/ABC 2019 F76151886 Spare Pass
44 10/ABC 2019 F78151884 C Inside Staff Workroom 1304 Pass
45 5/ABC 2017 C84042249 RC Inside Transtem Coord C504 Replaced
46 5/ABC 2017 C84042243 C Inside Room C609 Pass
47 5/ABC 2017 C92515089 C Inside Room C304 Pass
48 10/ABC 2017 C89292389 C Inside Room T204 Pass
49 5/ABC 2017 C84042257 RC Inside T105 Replaced
50 10/ABC 2019 F76151920 C Inside Staff Workroom T108 Pass
51 10/ABC 2017 C84042270 C Inside Daycare Pass
52 10/CO2 2019 F65983062 C Inside Mechanical Room LT02 Pass
Notes
Owner and/or representative acknowledges NFP inspected fire extinguished visually and did not mannually operate the extinguishers. The inspection is limited to the moment the NFP technisian inspected the extinguisher. NFP is not responsible for any changes to the extinguisher after the inspection.
12/14/23 Paul Olson
12/14/23
Customer - Print: Technician: Paul Olson
Extinguishers need to be mounted insdie C502, C205, 1603. Recharged in room 3504, T105, 1603.
Extinguishers should be mounted by door.
File details come from the government source that posted it. Updated .