E.8_Annual_Fire_Pump_Inspection_-_December_2023.pdf
PDF 306 KB Posted
- Attached to
- Request for Proposal ("RFP") Property Management Services at Francis L. Cardozo Education Campus
- Solicitation number
- DCAM-25-NC-RFP-0006
- Issued by
- District of Columbia
About this file
The document is an Annual Fire Pump Flow Test report prepared by National Fire Protection, LLC for the fire pump system located in the basement of Cardozo High School in Washington, DC, conducted on December 14, 2023. The inspection was performed in accordance with NFPA 25 Standard for Inspection, Test, and Maintenance of Water-Based Fire Protection Systems (2014 edition). The test comprehensively evaluated the fire pump's performance, including electrical systems, pressure readings, flow rates, and supervisory device functionality.
The test results indicate that the fire pump system is functioning within acceptable parameters, with all critical components passing inspection. Key measurements include a rated pump capacity of 1000 GPM at 80 PSI, with test points showing measured flows of 1028 GPM and 1516 GPM at various pressure levels. The inspection verified that the pump's voltage, amperage, speed, and pressure readings were within the manufacturer's specified ranges, and all supervisory devices like phase reversal, power monitoring, and running status checks were successfully tested and passed.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
785923 Cardozo
Powered by ASURiO Inspection Systems, Copyright 2017. All Rights Reserved ASURiO
Annual Fire Pump Flow Test
National Fire Protection, LLC 207A Perry Pkwy
Gaithersburg, MD 20877
Tel: 301-340-6500 Fax: 301-309-1284 www.natlfire.com
Customer Inspection Location
RWD Consulting Cardoza High School 7 8 5 9 2 3
1300 Clifton Ave NW 1300 Clifton Ave NW
Washington, DC Washington, DC
Phone: Fax: Phone: Fax:
Inspection Date:
Flow Test Results
Basement Fire Pump Room The results of the fire pump test indicate pump is within 5% of the rated PSI/GPM readings from the original pump curve or fire pump nameplate.
Inspection performed in accordance with NFPA 25 Standard for Inspection, Test, and Maintenance of Water-Based Fire Protection Systems 2014 ed.
12/14/2023 http://www.natlfire.com/
Fire Pump System
Fire Pump House/Room
Basement Fire Pump Room
Ventilating louvers free to operate, no excessive water collecting on floor. (8.2.2) Pass
Coupling guard in place. (8.2.2) Pass
Supervisory Devices
Fire Pump Phase Reversal
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Pump Phase Reversal annunciated properly when tested. (13.2.8.2) Pass
Fire Pump Power
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Fire Pump Power supervision annunciated properly when tested. (13.2.8.2) Pass
Fire Pump Running
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Fire Pump Running supervision annunciated properly when tested. (13.2.8.2) Pass
Fire Pump Supervision
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Fire Pump supervision annunciated properly when tested. (13.2.8.2) Pass
Electric Pump Inspection
Pump suction, discharge and by-pass control valves fully open,and piping free of leaks. (8.2.2(2)) Pass
Suction line pressure gauge reading is within acceptable range. (8.2.2(2c)) Pass
System line pressure gauge reading is within acceptable range. (8.2.2(2d)) Pass
Suction reservoir has required water level & wet pit suction screen in place and unobstructed. (8.2.2(2)) N/A
Waterflow valve in closed position, hose connection valve closed, test valve line free of water. (8.2.2(2)) Pass
Controller pilot light (power on) illuminated (8.2.2(3)) Pass
Oil level in vertical motor sight glass, if available, within acceptable range. (8.2.2(3)) N/A
Power to Jockey pump is provided, if applicable. (8.2.2(3)) Pass
Record pump starting pressure. (8.3.2.9(1a) 130
Record the system suction pressure gauge readings with pump running. (8.3.2.9(1b)) Pass
Time (sec) controller is on first step. (8.3.2.9(2)) 2
Time (sec.) for driver to accelerate to full speed. (8.3.2.9(2)) 3
Record time pump runs after starting (for auto stop controller). (8.3.2.9(2)) 10
Record the discharge pressure gauge readings with pump running. (8.3.2.9(1b)) 155
With pump running, check for slight discharge from packing glands; Pump free from any unusual noise or vibration. (8.3.2.9 (1))
Pass
Packing boxes, bearing, or pump casing maintain an acceptable temperature during the test. (8.3.2.9(1)) Pass
Pump run minimum 10 minutes. (8.3.2.3) Pass
Fire pump alarm conditions and supervisory sensors operate when tested through simulation. (8.3.3.10) Pass
Parallel and angular alignment of pump and driver without any misalignments. (8.3.6.4) Pass
Suction screens inspected and cleaned after water flow. (8.3.3.12) N/A
Pressure gauge and sensors, when compared to a calibrated gauge, is less than 5% calibration or have been recalibrated or replaced. (8.1.1.2.21)
Yes
Nameplate Information
Rated GPM 1000 Rated PSI 80 Rated RPM 1770
Max PSI 90.9 150% PSI 67.9 150% GPM 1500
Churn
Suction Discharge Net PSI Speed
65 55 -10 1798
L1: L2: L3:
Volts 468 468 471
Amps 41 41 42
Test Point 1
Flow Test Point %:
102.8 Measured Flow: 1028 Adj. Flow 1014 Measured Press: 80 Adj. Press.: 78
Press. Test Point %:
98%
Outlet Size 1.75 1.75 1.75 1.75
Coefficient 1.15 1.15 1.15
Pitot 6 6 6 6
Flow 257 257 257 257
Suction Discharge Net PSI Speed
50 130 80 1794
L1: L2: L3:
Volts 467 467 470
Amps 45 46 47
Test Point 2
Flow Test Point %:
151.6 Measured Flow: 1516 Adj. Flow 1502 Measured Press: 70 Adj. Press.: 69
Press. Test Point %:
102%
Outlet Size 1.75 1.75 1.75 1.75
Coefficient 1.15 1.15 1.15 1.15
Pitot 13 13 13 13
Flow 379 379 379 379
Suction Discharge Net PSI Speed
15 85 70 1787
L1: L2: L3:
Volts 465 465 466
Amps 53 54 54