E.7_-_Annual_Fire_Pump.Fire_extinguisher.Sprinkler_Inspections.pdf
PDF 1 MB Posted
- Attached to
- Request for Proposal ("RFP") Property Management Services at Francis L. Cardozo Education Campus
- Solicitation number
- DCAM-25-NC-RFP-0006
- Issued by
- District of Columbia
About this file
This file contains two annual fire safety inspection reports from National Fire Protection, LLC for Cardozo High School in Washington, DC, dated December 14, 2023. The first report is an Annual Fire Pump Flow Test documenting a comprehensive inspection of the building's fire pump system, performed in accordance with NFPA 25 Standard for Inspection, Test, and Maintenance of Water-Based Fire Protection Systems. The inspection covered multiple aspects of the fire pump system, including electrical components, supervisory devices, pump performance, and pressure measurements, with all tested elements passing inspection.
The second report is a Fire Extinguisher Inspection, also conducted on December 14, 2023, in compliance with NFPA 10, 2010 Edition. The inspection covered 52 fire extinguishers throughout the Cardozo High School facility, with various sizes and types of extinguishers (5/ABC, 10/ABC, 10/CO2, 6/K, 6/Water) manufactured between 2015 and 2019. The majority of extinguishers passed inspection, with a few noted as replaced or requiring recharging. The technician, Paul Olson, noted that some extinguishers need to be mounted in specific rooms (C502, C205, 1603) and that several extinguishers were recharged in rooms 3504, T105, and 1603.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
785923 Cardozo
Powered by ASURiO Inspection Systems, Copyright 2017. All Rights Reserved ASURiO
Annual Fire Pump Flow Test
National Fire Protection, LLC 207A Perry Pkwy
Gaithersburg, MD 20877
Tel: 301-340-6500 Fax: 301-309-1284 www.natlfire.com
Customer Inspection Location
RWD Consulting Cardoza High School 7 8 5 9 2 3
1300 Clifton Ave NW 1300 Clifton Ave NW
Washington, DC Washington, DC
Phone: Fax: Phone: Fax:
Inspection Date:
Flow Test Results
Basement Fire Pump Room The results of the fire pump test indicate pump is within 5% of the rated PSI/GPM readings from the original pump curve or fire pump nameplate.
Inspection performed in accordance with NFPA 25 Standard for Inspection, Test, and Maintenance of Water-Based Fire Protection Systems 2014 ed.
12/14/2023 http://www.natlfire.com/
Fire Pump System
Fire Pump House/Room
Basement Fire Pump Room
Ventilating louvers free to operate, no excessive water collecting on floor. (8.2.2) Pass
Coupling guard in place. (8.2.2) Pass
Supervisory Devices
Fire Pump Phase Reversal
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Pump Phase Reversal annunciated properly when tested. (13.2.8.2) Pass
Fire Pump Power
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Fire Pump Power supervision annunciated properly when tested. (13.2.8.2) Pass
Fire Pump Running
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Fire Pump Running supervision annunciated properly when tested. (13.2.8.2) Pass
Fire Pump Supervision
Basement Fire Pump Room
Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass
Fire Pump supervision annunciated properly when tested. (13.2.8.2) Pass
Electric Pump Inspection
Pump suction, discharge and by-pass control valves fully open,and piping free of leaks. (8.2.2(2)) Pass
Suction line pressure gauge reading is within acceptable range. (8.2.2(2c)) Pass
System line pressure gauge reading is within acceptable range. (8.2.2(2d)) Pass
Suction reservoir has required water level & wet pit suction screen in place and unobstructed. (8.2.2(2)) N/A
Waterflow valve in closed position, hose connection valve closed, test valve line free of water. (8.2.2(2)) Pass
Controller pilot light (power on) illuminated (8.2.2(3)) Pass
Oil level in vertical motor sight glass, if available, within acceptable range. (8.2.2(3)) N/A
Power to Jockey pump is provided, if applicable. (8.2.2(3)) Pass
Record pump starting pressure. (8.3.2.9(1a) 130
Record the system suction pressure gauge readings with pump running. (8.3.2.9(1b)) Pass
Time (sec) controller is on first step. (8.3.2.9(2)) 2
Time (sec.) for driver to accelerate to full speed. (8.3.2.9(2)) 3
Record time pump runs after starting (for auto stop controller). (8.3.2.9(2)) 10
Record the discharge pressure gauge readings with pump running. (8.3.2.9(1b)) 155
With pump running, check for slight discharge from packing glands; Pump free from any unusual noise or vibration. (8.3.2.9 (1))
Pass
Packing boxes, bearing, or pump casing maintain an acceptable temperature during the test. (8.3.2.9(1)) Pass
Pump run minimum 10 minutes. (8.3.2.3) Pass
Fire pump alarm conditions and supervisory sensors operate when tested through simulation. (8.3.3.10) Pass
Parallel and angular alignment of pump and driver without any misalignments. (8.3.6.4) Pass
Suction screens inspected and cleaned after water flow. (8.3.3.12) N/A
Pressure gauge and sensors, when compared to a calibrated gauge, is less than 5% calibration or have been recalibrated or replaced. (8.1.1.2.21)
Yes
Nameplate Information
Rated GPM 1000 Rated PSI 80 Rated RPM 1770
Max PSI 90.9 150% PSI 67.9 150% GPM 1500
Churn
Suction Discharge Net PSI Speed
65 55 -10 1798
L1: L2: L3:
Volts 468 468 471
Amps 41 41 42
Test Point 1
Flow Test Point %:
102.8 Measured Flow: 1028 Adj. Flow 1014 Measured Press: 80 Adj. Press.: 78
Press. Test Point %:
98%
Outlet Size 1.75 1.75 1.75 1.75
Coefficient 1.15 1.15 1.15
Pitot 6 6 6 6
Flow 257 257 257 257
Suction Discharge Net PSI Speed
50 130 80 1794
L1: L2: L3:
Volts 467 467 470
Amps 45 46 47
Test Point 2
Flow Test Point %:
151.6 Measured Flow: 1516 Adj. Flow 1502 Measured Press: 70 Adj. Press.: 69
Press. Test Point %:
102%
Outlet Size 1.75 1.75 1.75 1.75
Coefficient 1.15 1.15 1.15 1.15
Pitot 13 13 13 13
Flow 379 379 379 379
Suction Discharge Net PSI Speed
15 85 70 1787
L1: L2: L3:
Volts 465 465 466
Amps 53 54 54
Paul Olson
Fire Extinguisher Inspection
National Fire Protection, LLC 207A Perry Parkway
Gaithersburg, MD 20877
Tel: 301-340-6500 Fax: 301-309-1294
24 Hour Emergency Service: 800-741-5137 www.natlfire.com
Inspector : Date:
Inspection at Location
Cardozo High School
1300 Clifton Road NW
Washington, DC 20009
For Customer:
Cardozo High School
1300 Clifton Road NW
Washington, DC 20009
Work performed in accordance with
NFPA 10, 2010 Edition
12/14/2023 http://www.natlfire.com/
Service Codes: R = Repairs RC = Recharge C = Compliance NC = Non Compliance
H = 12 Year Hydro I = 6 Year Internal M = Maintenance X = Condemned
Pass/Fail Next
Size/Type MFRS. Date Serial # Code Location Service Date
1 5/ABC 2017 C84042248 C Inside C101 Pass
2 10/ABC 2017 L89994617 C Inside C101E (EMR) Pass
3 5/ABC 2017 C92515807 C Inside 3406 Pass
4 5/ABC 2017 C84042267 C Inside 3501 Pass
5 10/CO2 2019 F65983061 C Inside 3511 (Electric Room) Pass
6 10/ABC 2017 C93841444 C Inside 3502 Pass
7 5/ABC 2015 A37736414 I Inside 3504 Replaced
8 10/CO2 2019 F56496399 C Inside 3211 (Electric Room) Pass
9 5/ABC 2017 C84042246 C Inside 2204 Pass
10 10/CO2 2019 F56496420 C Inside 2211 (Electric Room) Pass
11 10/ABC 2019 F76151883 C Inside 2501 Pass
12 10/CO2 2019 F65983045 C Inside 2611 (Electric Room) Pass
13 5/ABC 2017 C84042240 C Inside 2602 Pass
14 5/ABC 2017 C92515256 C Inside 2604 Pass
15 5/ABC 2017 C84042256 C Inside 2104 Pass
16 10/ABC 2018 A40323189 C Inside 1611 Pass
17 5/ABC 2017 C84042238 RC Inside 1603 Pass
18 10/CO2 2019 F65983059 C Inside 1603 (Electric Room) Pass
19 5/ABC 2017 C84042237 C Inside 1503 Pass
20 5/ABC 2017 C84042241 C Inside 1501 Pass
21 5/ABC 2017 C92516866 C Inside 1401 Pass
22 10/ABC 2019 F76151884 C Inside 1304 Pass
23 5/ABC 2017 C84042236 C Inside 1301 Pass
24 10/CO2 2019 F65983048 C Inside 1211 (Electric Room) Pass
25 5/ABC 2017 C84042268 C Inside C205 Pass
26 10/CO2 2019 F65983048 C Inside C207 (Electric Room) Pass
27 5/ABC 2017 C84042256 C Inside C302 Pass
28 6/K 2019 F65996168 C Inside C118 (Kitchen) Pass
29 10/CO2 2019 F56496404 C Inside C502 (Electric Room) Pass
30 5/ABC 2017 C84042249 RC Inside C504 Replaced
31 10/CO2 2019 F56496406 C Inside C613 (Electric Room) Pass
32 5/ABC 2017 C84042239 C Inside LT33 (EMR) Pass
33 5/ABC 2017 C84042258 C Inside T302 Pass
34 5/ABC 2017 C84042247 C Inside T301 Pass
35 10/ABC 2017 B80239075 C Inside T209 Pass
36 10/ABC 2017 C89237294 C Inside T201 Pass
37 5/ABC 2017 C84042269 RC Spare Replaced
38 6/Water 2019 F75724398 C Inside Filtration Room Pass
39 10/CO2 2019 F56496422 Spare Pass
40 10/CO2 2019 F56496421 Spare Pass
Service Codes: R = Repairs RC = Recharge C = Compliance NC = Non Compliance
H = 12 Year Hydro I = 6 Year Internal M = Maintenance X = Condemned
Pass/Fail Next
Size/Type MFRS. Date Serial # Code Location Service Date
41 10/ABC 2019 F76151885 Spare Pass
42 10/ABC 2019 F76151919 Spare Pass
43 10/ABC 2019 F76151886 Spare Pass
44 10/ABC 2019 F78151884 C Inside Staff Workroom 1304 Pass
45 5/ABC 2017 C84042249 RC Inside Transtem Coord C504 Replaced
46 5/ABC 2017 C84042243 C Inside Room C609 Pass
47 5/ABC 2017 C92515089 C Inside Room C304 Pass
48 10/ABC 2017 C89292389 C Inside Room T204 Pass
49 5/ABC 2017 C84042257 RC Inside T105 Replaced
50 10/ABC 2019 F76151920 C Inside Staff Workroom T108 Pass
51 10/ABC 2017 C84042270 C Inside Daycare Pass
52 10/CO2 2019 F65983062 C Inside Mechanical Room LT02 Pass
Notes
Owner and/or representative acknowledges NFP inspected fire extinguished visually and did not mannually operate the extinguishers. The inspection is limited to the moment the NFP technisian inspected the extinguisher. NFP is not responsible for any changes to the extinguisher after the inspection.
12/14/23 Paul Olson
12/14/23
Customer - Print: Technician: Paul Olson
Extinguishers need to be mounted insdie C502, C205, 1603. Recharged in room 3504, T105, 1603.
Extinguishers should be mounted by door.
File details come from the government source that posted it. Updated .