E.7_-_Annual_Fire_Pump.Fire_extinguisher.Sprinkler_Inspections.pdf

PDF 1 MB Posted

Attached to
Request for Proposal ("RFP") Property Management Services at Francis L. Cardozo Education Campus
Solicitation number
DCAM-25-NC-RFP-0006
Issued by
District of Columbia

About this file

This file contains two annual fire safety inspection reports from National Fire Protection, LLC for Cardozo High School in Washington, DC, dated December 14, 2023. The first report is an Annual Fire Pump Flow Test documenting a comprehensive inspection of the building's fire pump system, performed in accordance with NFPA 25 Standard for Inspection, Test, and Maintenance of Water-Based Fire Protection Systems. The inspection covered multiple aspects of the fire pump system, including electrical components, supervisory devices, pump performance, and pressure measurements, with all tested elements passing inspection.

The second report is a Fire Extinguisher Inspection, also conducted on December 14, 2023, in compliance with NFPA 10, 2010 Edition. The inspection covered 52 fire extinguishers throughout the Cardozo High School facility, with various sizes and types of extinguishers (5/ABC, 10/ABC, 10/CO2, 6/K, 6/Water) manufactured between 2015 and 2019. The majority of extinguishers passed inspection, with a few noted as replaced or requiring recharging. The technician, Paul Olson, noted that some extinguishers need to be mounted in specific rooms (C502, C205, 1603) and that several extinguishers were recharged in rooms 3504, T105, and 1603.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

785923 Cardozo

Powered by ASURiO Inspection Systems, Copyright 2017. All Rights Reserved ASURiO

Annual Fire Pump Flow Test

National Fire Protection, LLC 207A Perry Pkwy

Gaithersburg, MD 20877

Tel: 301-340-6500 Fax: 301-309-1284 www.natlfire.com

Customer Inspection Location

RWD Consulting Cardoza High School 7 8 5 9 2 3

1300 Clifton Ave NW 1300 Clifton Ave NW

Washington, DC Washington, DC

Phone: Fax: Phone: Fax:

Inspection Date:

Flow Test Results

Basement Fire Pump Room The results of the fire pump test indicate pump is within 5% of the rated PSI/GPM readings from the original pump curve or fire pump nameplate.

Inspection performed in accordance with NFPA 25 Standard for Inspection, Test, and Maintenance of Water-Based Fire Protection Systems 2014 ed.

12/14/2023 http://www.natlfire.com/

Fire Pump System

Fire Pump House/Room

Basement Fire Pump Room

Ventilating louvers free to operate, no excessive water collecting on floor. (8.2.2) Pass

Coupling guard in place. (8.2.2) Pass

Supervisory Devices

Fire Pump Phase Reversal

Basement Fire Pump Room

Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass

Pump Phase Reversal annunciated properly when tested. (13.2.8.2) Pass

Fire Pump Power

Basement Fire Pump Room

Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass

Fire Pump Power supervision annunciated properly when tested. (13.2.8.2) Pass

Fire Pump Running

Basement Fire Pump Room

Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass

Fire Pump Running supervision annunciated properly when tested. (13.2.8.2) Pass

Fire Pump Supervision

Basement Fire Pump Room

Visual inspection verifying unit was free of physical damage. (13.2.8.1) Pass

Fire Pump supervision annunciated properly when tested. (13.2.8.2) Pass

Electric Pump Inspection

Pump suction, discharge and by-pass control valves fully open,and piping free of leaks. (8.2.2(2)) Pass

Suction line pressure gauge reading is within acceptable range. (8.2.2(2c)) Pass

System line pressure gauge reading is within acceptable range. (8.2.2(2d)) Pass

Suction reservoir has required water level & wet pit suction screen in place and unobstructed. (8.2.2(2)) N/A

Waterflow valve in closed position, hose connection valve closed, test valve line free of water. (8.2.2(2)) Pass

Controller pilot light (power on) illuminated (8.2.2(3)) Pass

Oil level in vertical motor sight glass, if available, within acceptable range. (8.2.2(3)) N/A

Power to Jockey pump is provided, if applicable. (8.2.2(3)) Pass

Record pump starting pressure. (8.3.2.9(1a) 130

Record the system suction pressure gauge readings with pump running. (8.3.2.9(1b)) Pass

Time (sec) controller is on first step. (8.3.2.9(2)) 2

Time (sec.) for driver to accelerate to full speed. (8.3.2.9(2)) 3

Record time pump runs after starting (for auto stop controller). (8.3.2.9(2)) 10

Record the discharge pressure gauge readings with pump running. (8.3.2.9(1b)) 155

With pump running, check for slight discharge from packing glands; Pump free from any unusual noise or vibration. (8.3.2.9 (1))

Pass

Packing boxes, bearing, or pump casing maintain an acceptable temperature during the test. (8.3.2.9(1)) Pass

Pump run minimum 10 minutes. (8.3.2.3) Pass

Fire pump alarm conditions and supervisory sensors operate when tested through simulation. (8.3.3.10) Pass

Parallel and angular alignment of pump and driver without any misalignments. (8.3.6.4) Pass

Suction screens inspected and cleaned after water flow. (8.3.3.12) N/A

Pressure gauge and sensors, when compared to a calibrated gauge, is less than 5% calibration or have been recalibrated or replaced. (8.1.1.2.21)

Yes

Nameplate Information

Rated GPM 1000 Rated PSI 80 Rated RPM 1770

Max PSI 90.9 150% PSI 67.9 150% GPM 1500

Churn

Suction Discharge Net PSI Speed

65 55 -10 1798

L1: L2: L3:

Volts 468 468 471

Amps 41 41 42

Test Point 1

Flow Test Point %:

102.8 Measured Flow: 1028 Adj. Flow 1014 Measured Press: 80 Adj. Press.: 78

Press. Test Point %:

98%

Outlet Size 1.75 1.75 1.75 1.75

Coefficient 1.15 1.15 1.15

Pitot 6 6 6 6

Flow 257 257 257 257

Suction Discharge Net PSI Speed

50 130 80 1794

L1: L2: L3:

Volts 467 467 470

Amps 45 46 47

Test Point 2

Flow Test Point %:

151.6 Measured Flow: 1516 Adj. Flow 1502 Measured Press: 70 Adj. Press.: 69

Press. Test Point %:

102%

Outlet Size 1.75 1.75 1.75 1.75

Coefficient 1.15 1.15 1.15 1.15

Pitot 13 13 13 13

Flow 379 379 379 379

Suction Discharge Net PSI Speed

15 85 70 1787

L1: L2: L3:

Volts 465 465 466

Amps 53 54 54

Paul Olson

Fire Extinguisher Inspection

National Fire Protection, LLC 207A Perry Parkway

Gaithersburg, MD 20877

Tel: 301-340-6500 Fax: 301-309-1294

24 Hour Emergency Service: 800-741-5137 www.natlfire.com

Inspector : Date:

Inspection at Location

Cardozo High School

1300 Clifton Road NW

Washington, DC 20009

For Customer:

Cardozo High School

1300 Clifton Road NW

Washington, DC 20009

Work performed in accordance with

NFPA 10, 2010 Edition

12/14/2023 http://www.natlfire.com/

Service Codes: R = Repairs RC = Recharge C = Compliance NC = Non Compliance

H = 12 Year Hydro I = 6 Year Internal M = Maintenance X = Condemned

Pass/Fail Next

Size/Type MFRS. Date Serial # Code Location Service Date

1 5/ABC 2017 C84042248 C Inside C101 Pass

2 10/ABC 2017 L89994617 C Inside C101E (EMR) Pass

3 5/ABC 2017 C92515807 C Inside 3406 Pass

4 5/ABC 2017 C84042267 C Inside 3501 Pass

5 10/CO2 2019 F65983061 C Inside 3511 (Electric Room) Pass

6 10/ABC 2017 C93841444 C Inside 3502 Pass

7 5/ABC 2015 A37736414 I Inside 3504 Replaced

8 10/CO2 2019 F56496399 C Inside 3211 (Electric Room) Pass

9 5/ABC 2017 C84042246 C Inside 2204 Pass

10 10/CO2 2019 F56496420 C Inside 2211 (Electric Room) Pass

11 10/ABC 2019 F76151883 C Inside 2501 Pass

12 10/CO2 2019 F65983045 C Inside 2611 (Electric Room) Pass

13 5/ABC 2017 C84042240 C Inside 2602 Pass

14 5/ABC 2017 C92515256 C Inside 2604 Pass

15 5/ABC 2017 C84042256 C Inside 2104 Pass

16 10/ABC 2018 A40323189 C Inside 1611 Pass

17 5/ABC 2017 C84042238 RC Inside 1603 Pass

18 10/CO2 2019 F65983059 C Inside 1603 (Electric Room) Pass

19 5/ABC 2017 C84042237 C Inside 1503 Pass

20 5/ABC 2017 C84042241 C Inside 1501 Pass

21 5/ABC 2017 C92516866 C Inside 1401 Pass

22 10/ABC 2019 F76151884 C Inside 1304 Pass

23 5/ABC 2017 C84042236 C Inside 1301 Pass

24 10/CO2 2019 F65983048 C Inside 1211 (Electric Room) Pass

25 5/ABC 2017 C84042268 C Inside C205 Pass

26 10/CO2 2019 F65983048 C Inside C207 (Electric Room) Pass

27 5/ABC 2017 C84042256 C Inside C302 Pass

28 6/K 2019 F65996168 C Inside C118 (Kitchen) Pass

29 10/CO2 2019 F56496404 C Inside C502 (Electric Room) Pass

30 5/ABC 2017 C84042249 RC Inside C504 Replaced

31 10/CO2 2019 F56496406 C Inside C613 (Electric Room) Pass

32 5/ABC 2017 C84042239 C Inside LT33 (EMR) Pass

33 5/ABC 2017 C84042258 C Inside T302 Pass

34 5/ABC 2017 C84042247 C Inside T301 Pass

35 10/ABC 2017 B80239075 C Inside T209 Pass

36 10/ABC 2017 C89237294 C Inside T201 Pass

37 5/ABC 2017 C84042269 RC Spare Replaced

38 6/Water 2019 F75724398 C Inside Filtration Room Pass

39 10/CO2 2019 F56496422 Spare Pass

40 10/CO2 2019 F56496421 Spare Pass

Service Codes: R = Repairs RC = Recharge C = Compliance NC = Non Compliance

H = 12 Year Hydro I = 6 Year Internal M = Maintenance X = Condemned

Pass/Fail Next

Size/Type MFRS. Date Serial # Code Location Service Date

41 10/ABC 2019 F76151885 Spare Pass

42 10/ABC 2019 F76151919 Spare Pass

43 10/ABC 2019 F76151886 Spare Pass

44 10/ABC 2019 F78151884 C Inside Staff Workroom 1304 Pass

45 5/ABC 2017 C84042249 RC Inside Transtem Coord C504 Replaced

46 5/ABC 2017 C84042243 C Inside Room C609 Pass

47 5/ABC 2017 C92515089 C Inside Room C304 Pass

48 10/ABC 2017 C89292389 C Inside Room T204 Pass

49 5/ABC 2017 C84042257 RC Inside T105 Replaced

50 10/ABC 2019 F76151920 C Inside Staff Workroom T108 Pass

51 10/ABC 2017 C84042270 C Inside Daycare Pass

52 10/CO2 2019 F65983062 C Inside Mechanical Room LT02 Pass

Notes

Owner and/or representative acknowledges NFP inspected fire extinguished visually and did not mannually operate the extinguishers. The inspection is limited to the moment the NFP technisian inspected the extinguisher. NFP is not responsible for any changes to the extinguisher after the inspection.

12/14/23 Paul Olson

12/14/23

Customer - Print: Technician: Paul Olson

Extinguishers need to be mounted insdie C502, C205, 1603. Recharged in room 3504, T105, 1603.

Extinguishers should be mounted by door.