Drawings Part 2 Bldg 490.pdf

PDF 1 MB Posted

Attached to
511/23366. JLM; Alpena CRTC - Replace Generators Bldg. 490
Solicitation number
RFQ 171 260000000276 3
Issued by
Allegan County, Flint City, Michigan

About this file

This is a technical drawings document prepared for the State of Michigan Department of Military and Veterans Affairs for Building 490 at the Alpena Consolidated Resource Training Center (CRTC), specifically for a backup generator replacement and relocation project. The drawings include demolition plans, new equipment installation plans, and operational details for replacing existing generators with new Cummins-brand equipment. The project involves removing an existing 80-kilowatt generator and associated automatic transfer switch (ATS) from an interior location, removing a 20-kilowatt generator and related infrastructure, and installing a new 80-kilowatt generator with a 625-gallon sub-base tank at an outdoor location, plus installing a new 20-kilowatt generator on an existing pad. The work includes installing new Cummins BTPCB 150-amp automatic transfer switches, surge protective devices, conduit systems buried 36 inches below grade, and load bank testing equipment. Contractor responsibilities include cutting and patching for new underground raceways, core drilling walls, removing existing natural gas lines, providing security fencing modifications, and coordinating all power outages with the owner in advance.

The drawings specify detailed conductor sizing requirements based on circuit distances, with branch circuit wire sizes ranging from #12 to #8 AWG depending on voltage and distance from panels. All installations must conform to federal, state, and local laws and codes, and contractors must verify existing piping, ductwork, and structural details prior to bidding. The project documents note that contractor costs must include all labor, materials, cutting and patching work, and any premium time required for work performed outside regular hours. Existing equipment remaining in service must be operational upon job completion, with recircuiting required as necessary. The design is the exclusive property of Sidock Group, Inc., and all work is intended for the Michigan Air National Guard facility at Alpena CRTC in Alpena, Michigan.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SCALE:

SCHOOLCRAFT

MANISTEE

OCEANA

MUSKEGON

MASON

BERRIEN

GOGEBIC

DICKINSON

MENOMINEE

DELTA

ONTONAGON

IRON

BARAGA

HOUGHTON

KEWEENAW

MARQUETTE

ALGER

ST.

CLAIR

HILLSDALE

CASS ST.

JOSEPH BRANCH

LENAWEE MONROE

GLADWIN

MIDLAND

JACKSON

BARRY

VAN

BUREN

ALLEGAN

KALAMAZOO

OTTAWA

KENT

EATON

CALHOUN

IONIA CLINTON

MECOSTA

OSCEOLA

NEWAYGO

LAKE

ISABELLA

MONTCALM GRATIOT

CLARE

INGHAM

WASHTENAW

LIVINGSTON

SHIAWASSEE

GENESEE

OAKLAND

WAYNE

LAPEER

MACOMB

TUSCOLA

SAGINAW

ARENAC

BAY

SANILAC

HURON

ANTRIM

GRAND

TRAVERSE

WEXFORD

LELANAU

BENZIE

MISSAUKEE ROSCOMMON

KALKASKA CRAWFORD

OTSEGO

CHALEVOIX

EMMET

CHEBOYGAN

MACKINAC

OGEMAW IOSCO

OSCODA

MONTMORENCY

ALCONA

ALPENA

PRESQUE

ISLE

LUCE

CHIPPEWA

LOCATION MAP

NO SCALELAKE

MICHIGAN

LAKE

SUPERIOR

LAKE

ERIE

LAKE

HURON

PANELBOARD,ATS,SPD, LOAD BANK OR FUEL TANK: AS NOTED

DUPLEX RECEPTACLE

VARIABLE FREQUENCY DRIVE

POWER SYMBOLS

NOTE SYMBOLS

ELECTRICAL DEMOLITION PLAN NOTES

POWER PLAN NOTESPx

COMBINATION STARTER; SEE SCHEDULE FOR DETAILS

NONFUSED DISCONNECT; SEE SCHEDULE FOR DETAILS

FUSED DISCONNECT; SEE SCHEDULE FOR DETAILS

DUPLEX RECEPTACLE, GROUND FAULT CIRCUIT INTERRUPTGFI

SPECIAL RECEPTACLE; SEE DRAWINGS

JUNCTION BOXJ

NOT ALL SYMBOLS MAY BE USED

Dx

LIGHTING PLAN NOTESLx

TECHNOLOGY PLAN NOTESTx

A

AFF

AFG

AHU

BSI

C

CUH

EMT

EF

EWC

EWH

FA

FMC

GFCI

AMPERE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

BUILDING SYSTEM INTEGRATION

CONDUIT

CABINET UNIT HEATER

ELECTRICAL METALLIC TUBING

EXHAUST FAN

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FIRE ALARM

FLEXIBLE METALLIC TUBING

GROUND FAULT CIRCUIT INTERRUPTER

GRC

IG

N/L

PVC

P R

RL

RTU

TEL

TV

WC

WG

WP

GALVANIZED RIGID CONDUIT

ISOLATED GROUND

NIGHT LIGHT

CONDUIT

PHOTO-ELECTRIC DETECTOR

REMOVE

LOW VOLTAGE RELAY

ROOF TOP UNIT

TELEPHONE

TELEVISION

WATER COOLER

WIRE GUARD

WEATHERPROOF

ABBREVIATIONS

GENERAL NOTES - APPLY TO ALL SHEETS:

• INSTALLATIONS SHALL CONFORM WITH FEDERAL, STATE, AND LOCAL LAWS,

CODES, ORDINANCES, RULES, AND REGULATIONS WHICH ARE HEREBY MADE A

PART OF THESE CONTRACT DOCUMENTS THE SAME AS IF REPEATED HEREIN.

• CONTRACTOR SHALL INCLUDE IN BID/PROPOSAL COST REQUIRED TO

COMPLETELY AND PROPERLY INSTALL WORK REQUIRED FOR THE PROJECT.

• CONTRACTOR SHALL INCLUDE IN BID/PROPOSAL COST FOR CUTTING AND

PATCHING AS REQUIRED TO INSTALL NEW OR EXISTING WORK, EQUIPMENT OR

SYSTEMS.

• CLEARANCES INDICATED ARE BASED ON BEST AVAILABLE INFORMATION.

CONTRACTOR SHALL VERIFY PIPING, DUCTWORK, ROUTING, AND STRUCTURAL

DETAILS PRIOR TO SUBMITTING A BID/PROPOSAL AND INCLUDE SUCH COSTS

AS REQUIRED TO INSTALL WORK AS SHOWN AND INTENDED.

• ALL POWER OUTAGES SHALL BE COORDINATED AND SCHEDULED IN ADVANCE

WITH THE OWNER.

• WHEREAS PLANS GENERALLY SHOW INDIVIDUAL HOME RUN SINGLE PHASE

BRANCH CIRCUITS, CONTRACTOR MAY RUN UP TO THREE (3) SUCH CIRCUITS IN

A RACEWAY.

• WIRE SIZES: BRANCH CIRCUIT WIRE SIZES SHALL BE BASED ON THE VALUES

INDICATED BELOW

1. 120/208V CABLING FROM PANEL TO THE ELECTRICAL LOAD SHALL BE

ADJUSTED AS FOLLOWS UNLESS SPECIFICALLY NOTED OTHERWISE.

A. 0 TO 100FT: #12AWG MINIMUM

B. 100 TO 200FT: #10AWG MINIMUM

C. 200 TO 250FT: #8AWG MINIMUM

2. 277/480V CABLING FROM PANEL TO THE ELECTRICAL LOAD SHALL BE

ADJUSTED AS FOLLOWS UNLESS SPECIFICALLY NOTED OTHERWISE.

A. 0 TO 150FT: #12AWG MINIMUM

B. 150 TO 250FT: #10AWG MINIMUM

C. 250 TO 350FT: #8AWG MINIMUM

• CIRCUIT NUMBERS SHOWN FOR EXISTING PANELS ARE BASED ON EXISTING

DRAWINGS, SCHEDULES, AND FIELD SURVEY. FIELD VERIFY AS REQUIRED.

• CONTRACT DOCUMENTS CONSIST OF BOTH PROJECT MANUAL AND DRAWINGS

AND BOTH ARE MEANT TO BE COMPLEMENTARY. ANYTHING APPEARING ON

EITHER MUST BE EXECUTED THE SAME AS IF SHOWN ON BOTH.

• SOME ELECTRICAL WORK MAY BE REQUIRED TO BE PERFORMED OFF REGULAR

WORK HOURS. COST FOR PREMIUM TIME SHALL BE INCLUDED IN THE

BID/PROPOSAL.

• ALL EXISTING EQUIPMENT THAT IS TO REMAIN IS INTENDED TO BE

OPERATIONAL AT THE COMPLETION OF THE JOB. THIS CONTRACTOR SHALL

RECIRCUIT WHERE NECESSARY TO ENSURE THIS CONTINUED OPERATION.

FOR SITE OWNED UTILITIES

THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF

SIDOCK GROUP, INC. AND CANNOT BE REPRODUCED,

COPIED, OR USED IN ANY MANNER WITHOUT THE PRIOR

WRITTEN CONSENT OF SIDOCK GROUP, INC. 2022C SH

EE

T

TI

TL

E:

SH

EE

T

ID

EN

TI

FI

CA

TI

O N

NO

PR

O

JE

C

T N

O

FI

LE

N O

./I N

D

EX

C O

D E:

IS

SU

ED

F

O R:

PR

EL

IM

IN

AR

Y

C O

N

ST

R U

C

TI

O N

FI

N

AL

R

EC

O

R D

DA

TE

D R

AW

N

D

ES

IG

N

ED

C H

EC

KE

D

AP

PR

O

VE

D

ST

AT

E O

F M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

TE

C

H N

O

LO

G Y, M

AN

AG

EM

EN

T, A N

D B

U D

G

ET

FA

C

IL

IT

IE

S

AN

D

B U

SI

N

ES

S

SE

R

VI

C

ES

A

D M

IN

IS

TR

AT

IO

N

AD

AM

P . L

AR

C

H , R

.A

D

IR

EC

TO

R

DE

SI

G

N

AN

D

CO

NS

TR

UC

TI

O N

DI

VI

SI

O

N

CALL:

PH:

MR. KENDZIORSKI

(989) 657-3026

ALPENA CRTC ENGINEERING

1/

6.

JL

M

X C

S0

C O

VE

R

S H

EE

T

-B U

IL

D

IN

G

AL

PE

NA

C.

R.

T.

C.

M

UL

TI

PL

E

BL

DG

S- G

EN

ER

AT

O

R

RE

PL

AC

EM

EN

T D

EP

AR

TM

EN

T O

F M

IL

IT

AR

Y

AN

D

V

ET

ER

AN

S

AF

FA

IR

S

AL

PE

N

A C

.R .T

.C

AL

PE

N A, M I

M

RI

M

RI

LR M

RI

-3 0-

SITE

REPAIR/REPLACE BACKUP GENERATORS

BLDG 490 - ALPENA C.R.T.C.

MICHIGAN AIR NATIONAL GUARD

ALPENA, MICHIGAN

Sheet List Sheet Number Sheet Name

CS000 COVER SHEET - BUILDING 490

E100 DEMOLITION PLAN - BUILDING 490

E200 NEW EQUIPMENT PLAN - BUILDING 490

E300 OPERATIONAL DETAILS - BUILDING 490

ATS

UP

DN

DN

UP

UP

DOWN

RAMP

DOWN

ELEVATOR

TRANSF.

106116

114 101

112 111

14414

146 147 148

126 127

DN

2'

- 1

1/

2"

80KW GEN.

DP-EM

SWITCHBOARD

D1

D2 D5D6

100A A.T.S

EXISTING MAIN

SWITCHBOARD

RM 159

600A M.C.B.

80KW

GENERATOR #3

20KW

GENERATOR #4

(OUTDOORS)

FROM

TRANSFORMER

125A A.T.S

EXIST.

PANEL

'DP-EM'

BLDG 490

EMERG LOADS

MAINTAIN CONDUIT AS MUCH AS POSSIBLE FOR REUSE

277/480V, 3PH, 4W

100A

MAINTAIN CONDUIT

FOR REUSE

EXIST.

PANEL

'RB-1B'

RM L161

100A

120/240V

1PH,3W

EXIST.

PANEL

'EM-1'

125A

120/240V

1PH,3W

MAINTAIN CONDUIT AS MUCH AS POSSIBLE FOR REUSE

RM 159

277/480V

3PH, 4W

EXISTING 80KW GENERATOR #3 TO BE REMOVED

EXISTING

FOUNDATION

DIMENSIONS

4' - 0"

9'

- 8

EXISTING PANEL EM-1

EXISTING CONDUITS TO REMAIN, NEW CONDUCTORS

9' - 0"

6'

- 0

20KW GENERATOR

D3

D4

FOR SITE OWNED UTILITIES

THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF

SIDOCK GROUP, INC. AND CANNOT BE REPRODUCED,

COPIED, OR USED IN ANY MANNER WITHOUT THE PRIOR

WRITTEN CONSENT OF SIDOCK GROUP, INC. 2022C SH

EE

T

TI

TL

E:

SH

EE

T

ID

EN

TI

FI

CA

TI

O N

NO

PR

O

JE

C

T N

O

FI

LE

N O

./I N

D

EX

C O

D E:

IS

SU

ED

F

O R:

PR

EL

IM

IN

AR

Y

C O

N

ST

R U

C

TI

O N

FI

N

AL

R

EC

O

R D

DA

TE

D R

AW

N

D

ES

IG

N

ED

C H

EC

KE

D

AP

PR

O

VE

D

ST

AT

E O

F M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

TE

C

H N

O

LO

G Y, M

AN

AG

EM

EN

T, A N

D B

U D

G

ET

FA

C

IL

IT

IE

S

AN

D

B U

SI

N

ES

S

SE

R

VI

C

ES

A

D M

IN

IS

TR

AT

IO

N

AD

AM

P . L

AR

C

H , R

.A

D

IR

EC

TO

R

DE

SI

G

N

AN

D

CO

NS

TR

UC

TI

O N

DI

VI

SI

O

N

CALL:

PH:

MR. KENDZIORSKI

(989) 657-3026

ALPENA CRTC ENGINEERING

1/

6.

JL

M

X E1

D

EM

O

LI

TI

O

N P

LA

N

BU

IL

D

IN

G

AL

PE

NA

C.

R.

T.

C.

M

UL

TI

PL

E

BL

DG

S- G

EN

ER

AT

O

R

RE

PL

AC

EM

EN

T D

EP

AR

TM

EN

T O

F M

IL

IT

AR

Y

AN

D

V

ET

ER

AN

S

AF

FA

IR

S

AL

PE

N

A C

.R .T

.C

AL

PE

N A, M I

M

RI

M

RI

LR M

RI

-3 0-

1/4" = 1'-0"E100

1 BUILDING 490 ELECTRICAL DEMOLITION PLAN

N.T.S.

PHOTO - EXISTING GENERATOR

N.T.S.

PHOTO - EXISTING 80KW ATS

SHEET SPECIFIC ELECTRICAL DEMOLITION PLAN NOTES

D1 REMOVE EXISTING AUTOMATIC TRANSFER SWITCH ENTIRELY. COORDINATE REMOVAL WITH OWNER TO MINIMIZE ANY DOWNTIME FOR EQUIPMENT ASSOCIATED WITH THIS A.T.S.

D2 REMOVE EXISTING GENERATOR ENTIRELY AND ALL SUPPORTING ACCESSORIES, I.E. BATTERY CHARGER, ETC. REMOVE PAD ENTIRELY AND ASSOCIATED ANCHOR BOLTS. PATCH

FLOOR TO BE FLUSH WITH SURROUNDING FLOOR.

D3 REMOVE EXISTING GENERATOR ENTIRELY. RETAIN PAD AND UNDERGROUND CONDUIT SYSTEM FOR REUSE WITH NEW GENERATOR IN SAME LOCATION.

D4 REMOVE EXISTING AUTOMATIC TRANSFER SWITCH ENTIRELY. REMOVE CONDUIT FROM THIS ATS TO WIREWAY BENEATH. RETAIN WIREWAY FOR REUSE.

D5 REMOVE DUCTWORK ASSOCIATED WITH GENERATOR ENTIRELY.

D6 REMOVE EXISTING NATURAL GAS LINE BACK TO NEAREST METER POINT AND CAP.

N.T.S.

EXISTING RISER DIAGRAM

N.T.S.

PHOTO- EXISTING 20KW GENERATOR

1" = 20'-0"E100

7 BUILDING 490 REFERENCE PLAN

N.T.S.

PHOTO - EXISTING 20KW ATS

N.T.S.E100

4 BUILDING 490 20KW DEMOLITION PLAN DETAIL VIEW

112 111

14414

146 147 148

DN

ATS

0"

AP

PR

O X

5'

NOTE: DIMENSIONS SHOWN ARE APPROXIMATE.

PROJECT INTENT IS TO PLACE NEW GENERATOR AS CLOSE TO DRIVE

AS IS PRACTICAL. COORDINATE EXACT PLACEMENT WITH OWNER.

P5

P6

P9

NEW 80KW GENERATOR

W/625 GAL. SUB-BASE

EXISTING FENCING

P14

LOAD

BANK

EXISTING

FOUNDATION

DIMENSIONS

4' - 0"

9'

- 8

EXISTING PANEL EM-1

P7

EXISTING CONDUITS TO REMAIN, NEW CONDUCTORS

9' - 0"

6'

- 0

LOAD BANK/ PORT. GEN.

CONNECTION CABINET

P8

20KW ATS

P10

P12

GENERATOR #4

P13

S.P.D.

DP-EM

SWITCHBOARD

EXISTING SIDEWALK

P1

P2 P3

P4

S.P.D.

(ABOVE ATS)

LOAD BANK/PORT. GEN. CONTROL

P11

S.P.D.

#3

100KW

LOAD

BANK

P15

150A A.T.S

EXISTING MAIN

SWITCHBOARD

RM 159

600A M.C.B.

NEW 80KW

GENERATOR

OUTDOORS

NEW 20KW

GENERATOR

(OUTDOORS)

FROM

TRANSFORMER

150A A.T.S

EXIST.

PANEL

'DP-EM'

BLDG 490

EMERG LOADS

277/480V, 3PH, 4W

1OOA

MAINTAIN CONDUIT FOR REUSE.

PROVIDE NEW CONDUCTORS

EXIST.

PANEL

'RB-1B'

RM L161

1OOA

120/240V

1PH,3W

EXIST.

PANEL

'EM-1'

125A

120/240V

1PH,3W

RM 159

1-1/4" C. - (3) - #2 AWG + #8 GRD.

EXTEND RACEWAYS AS REQUIRED FROM PREVIOUS ATS LOCATION TO NEW.

SURGE PROTECTIVE DEVICE TPD MODEL TK-TTLP-3Y480-FL (GENERATOR SIDE)

INSTALL WITH SHORTEST CONDUCTOR LENGTH POSSIBLE.

SURGE PROTECTIVE DEVICE TPD MODEL TK-TTLP-1S240-FL (GENERATOR SIDE)

INSTALL WITH SHORTEST CONDUCTOR LENGTH POSSIBLE

LOAD

BANK/

PORT.

GEN.

CNTRL.

PORTABLE

LOAD

BANK

LOAD

BANK/

PORT.

GEN.

CNTRL.

LOAD

BANK

1-1/4" C. - (4) - #1/0 AWG + #6 GRD.1-1/4" C. - (4) - #1/0 AWG + #6 GRD.

277/480V

3PH, 4W

PROVIDE 30/3 BREAKER AND INSTALL SURGE PROTECTIVE

DEVICE TPD MODEL TK-TTLP-3Y480-FL

WITH SHORTEST CONDUCTOR LENGTH POSSIBLE.

1-1/4" C. - (3) - #2 AWG + #8 GRD.

EXTEND RACEWAYS AS REQUIRED FROM PREVIOUS ATS LOCATION TO NEW.

1-1/4" C. - (3) - #2 AWG + #8 GRD. TEMPORARY CABLING DURING TESTING ONLY

FOR SITE OWNED UTILITIES

THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF

SIDOCK GROUP, INC. AND CANNOT BE REPRODUCED,

COPIED, OR USED IN ANY MANNER WITHOUT THE PRIOR

WRITTEN CONSENT OF SIDOCK GROUP, INC. 2022C SH

EE

T

TI

TL

E:

SH

EE

T

ID

EN

TI

FI

CA

TI

O N

NO

PR

O

JE

C

T N

O

FI

LE

N O

./I N

D

EX

C O

D E:

IS

SU

ED

F

O R:

PR

EL

IM

IN

AR

Y

C O

N

ST

R U

C

TI

O N

FI

N

AL

R

EC

O

R D

DA

TE

D R

AW

N

D

ES

IG

N

ED

C H

EC

KE

D

AP

PR

O

VE

D

ST

AT

E O

F M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

TE

C

H N

O

LO

G Y, M

AN

AG

EM

EN

T, A N

D B

U D

G

ET

FA

C

IL

IT

IE

S

AN

D

B U

SI

N

ES

S

SE

R

VI

C

ES

A

D M

IN

IS

TR

AT

IO

N

AD

AM

P . L

AR

C

H , R

.A

D

IR

EC

TO

R

DE

SI

G

N

AN

D

CO

NS

TR

UC

TI

O N

DI

VI

SI

O

N

CALL:

PH:

MR. KENDZIORSKI

(989) 657-3026

ALPENA CRTC ENGINEERING

1/

6.

JL

M

X E2

N

EW

E Q

U

IP

M

EN

T

PL

AN

BU

IL

D

IN

G

AL

PE

NA

C.

R.

T.

C.

M

UL

TI

PL

E

BL

DG

S- G

EN

ER

AT

O

R

RE

PL

AC

EM

EN

T D

EP

AR

TM

EN

T O

F M

IL

IT

AR

Y

AN

D

V

ET

ER

AN

S

AF

FA

IR

S

AL

PE

N

A C

.R .T

.C

AL

PE

N A, M I

M

RI

M

RI

LR M

RI

-3 0-

1" = 20'-0"E200

1 BUILDING 490 80KW REPLACEMENT/RELOCATION PLAN

N.T.S.

GOOGLE VIEW

1/4" = 1'-0"E200

4 BUILDING 490 20KW REPLACEMENT PLAN DETAIL VIEW

SHEET SPECIFIC NEW EQUIPMENT POWER PLAN NOTES

P1 PROVIDE AND INSTALL CUMMINS BTPCB 150 AMP, THREE PHASE, 4 POLE AUTOMATIC TRANSFER SWITCH AT THIS LOCATION. REUSE EXISTING RACEWAY FROM SWITCHBOARD TO THIS DEVICE.

MODIFY/EXTEND AS NECESSARY. PROVIDE NEW CONDUCTORS THOUGHOUT.

P2 CUT SIDEWALK AS NECESSSARY AND PATCH FOR NEW UNDERGROUND RACEWAY FROM GENERATOR TO BUILDING AND LOAD BANK TO CONNECTION CABINET.

P3 CORE DRILL WALL AT 12' A.F.F. FOR CONDUITS OUT TO GENERATOR AND LOAD BANK. UTILIZE LB'S TO TRANSITION FROM WALL SURFACE TO UNDERGROUND.

P4 REUSE EXISTING RACEWAY FROM EXISTING 100A BREAKER TO ATS LOCATION.

P5 PROVIDE REQUIRED SCHEDULE 40 RACEWAYS BURIED 36" BELOW GRADE FROM NEW GENERATOR PAD TO BUILDING.

P6 PROVIDE 3' SIDEWALK AND 3' GATE IN FENCE FROM DRIVE TO GENERATOR TO ALLOW DIESEL FUEL REFILLING FROM DRIVE. FENCE WAS SUPPLIED BY ELITE FENCE.

P7 EXTEND CONDUIT FROM EXISTING WIREWAY TO NEW ATS LOCATION AND ADD NEW CONDUIT FROM NEW ATS TO PANEL RB-1B.

P8 PROVIDE AND INSTALL CUMMINS BTPCB 150 AMP, 4 POLE AUTOMATIC TRANSFER SWITCH AT THIS LOCATION. PROVIDE NEW CONDUCTORS FROM GENERATOR AND TO AND FROM PANEL RB-1B.

P9 PROVIDE NEW PAD WITH DIMENSIONS EXCEEDING GENERATOR BY 3" ON ALL SIDES. PROVIDE & INSTALL CUMMINS C80D6C 80KW, 277/480 VOLT, 3 PHASE, 4 WIRE GENERATOR WITH OUTDOOR ENCLOSURE

AND 625 GALLON SUB-BASE TANK.

P10 PROVIDE AND INSTALL CUMMINS C20D6 20KW, 120/240 VOLT, SINGLE PHASE GENERATOR WITH 195 GALLON SUB-BASE TANK ON EXISTING PAD. ORIENT ON PAD TO REUSE EXISTING UNDERGROUND

CONDUIT SYSTEM.

P11 PROVIDE AND INSTALL FOXFAB FFIS-C3-200-TM-U4-GL-ALU-LA CABINET OR APPROVED EQUAL AT THIS LOCATION.

P12 PROVIDE AND INSTALL FOXFAB FFIS-C3-100-TM-U1-GL-ALU-LA CABINET OR APPROVED EQUAL AT THIS LOCATION.

P13 PROVIDE AFTRON PORTABLE LOAD BANK MODEL 2600, 21.75KW, 120/240V LOAD BANK OR APPROVED EQUAL. UNIT TO LOCATED (STORED) BY OWNER.

P14 PROVIDE AND INSTALL SECURITY GATE LOCK BY (SUMO GLZSCMGCD) WWW.LOCKEYUSA.COM/SUMO.

P15 MOUNT LOAD BANK CONTROL TO TOP OF LOAD BANK.

1/4" = 1'-0"E200

5 BUILDING 490 ELECTRICAL NEW 80KW ATS PLAN

N.T.S.

NEW RISER DIAGRAM

NOTE REUSE EXISTING RACEWAYS WHEREVER PRACTICAL. PROVIDE NEW CONDUCTORS FOR ALL NEW EQUIPMENT.

100A 3P

MAIN LOAD CENTER

ROOM 159

600A 277/480V 3P 4W

FROM

TRANSFORMER

3P LOAD

BANK

PORTABLE GENERATOR LUGS

3P

80KW

277/480V

3PH, 4W

GENERATOR

GENERATOR BREAKER

LOAD BANK CONTROL

PANEL

LOAD BANK/

PORT. GEN.

CONNECTION

CABINET

DP-EM

100A 277/480V 3P 4W

2P LOAD

BANK

PORTABLE GENERATOR LUGS

2P

20KW

120/240V

1PH, 3W

GENERATOR

GENERATOR BREAKER

LOAD BANK CONTROL

PANEL

LOAD BANK/

PORT. GEN.

CONNECTION

CABINET

EXISTING

SEQUENCES OF OPERATION

AUTOMATIC TRANSFER SWITCH

1. NORMAL - UTILITY POWER AVAILABLE. NORMAL SWITCH IN CLOSED POSITION, EMERGENCY SWITCH OPEN AND UTILITY POWERS LOADS. BYPASS SWITCHES OPEN.

2. EMERGENCY - UTILITY POWER UNAVAILABLE. GENERATOR IS POWERED UP, NORMAL SWITCH OPENED AND EMERGENCY SWITCH CLOSED

EMERGENCY GENERATOR POWERS LOADS. BYPASS SWITCHES OPEN.

3. BYPASS - AUTOMATIC TRANSFER SWITCH CONTACTS DISCONNECTED (DRAWN OUT). MANUAL BYPASS SWITCH IS ENERGIZED. AUTOMATIC SWITCH DE-ENERGIZED

FOR TESTING OR SERVICE.

LOAD BANK/PORTABLE GENERATOR CONNECTION CABINET OPERATION

SEQUENCE OF OPERATION (NORMAL LOAD BANK TEST)

1. MAIN CABINET BREAKER OFF. SYSTEM COLD

2. GENERATOR STARTED MANUALLY FROM GENERATOR PANEL.

3. MAIN BREAKER TURNED ON. SYSTEM POWERS UP AND STATUS SHOWN ON CONTROLLER.

4. SYSTEM ARMED AND TIMED OR CONTINUOUS TEST IS SELECTED.

5. OPERATOR STARTS LOAD TEST VIA "START LOAD TEST" PUSHBUTTON.

6. TEST LOAD IS MODULATED AT LOAD BANK CONTROL PANEL.

7. TEST RUNS UNTIL OPERATOR STOPS OR UNIT TIMES OUT (AUTO TEST MODE.)

8. MAIN BREAKER IS SHUT OFF AND SYSTEM IS COLD AND TEST COMPLETE.

9. IF DURING TEST, UTILITY POWER IS LOST, MAIN BREAKER DISENGAGED INSTANTLY AND FULL GENERATOR POWER OUTPUT AVAILABLE TO BUILDING.

SEQUENCE OF OPERATION (PORTABLE GENERATOR CONNECTION)

1. MAIN CABINET BREAKER OFF. SYSTEM COLD. PORTABLE GENERATOR PLUGGED INTO RECEPTACLE.

2. MAIN GENERATOR BREAKER LOCKED OFF.

3. SELECTOR SWITCH TURNED TO "BACK-UP-POWER" MODE.

4. PORTABLE GENERATOR STARTED.

5. MAIN CABINET BREAKER TURNED ON.

BYPASS ISOLATION

TRANSFER SWITCH

BYPASS ISOLATION

TRANSFER SWITCH

PANEL RB-1B

120/240V

1PH, 3W

ROOM L161

PANEL EM-1

120/240V

1PH, 3W

125A, 24 CKT.

EXISTINGEXISTING

600A 3P

BUILDING 490

RAPCON,

OPERATION &

COMM. LOADS

4P SW

4P SW

A.T.S.

B.T.S.

3P SW

3P SW

A.T.S.

B.T.S.

E

L

N

FOR SITE OWNED UTILITIES

THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF

SIDOCK GROUP, INC. AND CANNOT BE REPRODUCED,

COPIED, OR USED IN ANY MANNER WITHOUT THE PRIOR

WRITTEN CONSENT OF SIDOCK GROUP, INC. 2022C SH

EE

T

TI

TL

E:

SH

EE

T

ID

EN

TI

FI

CA

TI

O N

NO

PR

O

JE

C

T N

O

FI

LE

N O

./I N

D

EX

C O

D E:

IS

SU

ED

F

O R:

PR

EL

IM

IN

AR

Y

C O

N

ST

R U

C

TI

O N

FI

N

AL

R

EC

O

R D

DA

TE

D R

AW

N

D

ES

IG

N

ED

C H

EC

KE

D

AP

PR

O

VE

D

ST

AT

E O

F M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

TE

C

H N

O

LO

G Y, M

AN

AG

EM

EN

T, A N

D B

U D

G

ET

FA

C

IL

IT

IE

S

AN

D

B U

SI

N

ES

S

SE

R

VI

C

ES

A

D M

IN

IS

TR

AT

IO

N

AD

AM

P . L

AR

C

H , R

.A

D

IR

EC

TO

R

DE

SI

G

N

AN

D

CO

NS

TR

UC

TI

O N

DI

VI

SI

O

N

CALL:

PH:

MR. KENDZIORSKI

(989) 657-3026

ALPENA CRTC ENGINEERING

1/

6.

JL

M

X E3

O

PE

R

AT

IO

N

AL

D

ET

AI

LS

BU

IL

D

IN

G

AL

PE

NA

C.

R.

T.

C.

M

UL

TI

PL

E

BL

DG

S- G

EN

ER

AT

O

R

RE

PL

AC

EM

EN

T D

EP

AR

TM

EN

T O

F M

IL

IT

AR

Y

AN

D

V

ET

ER

AN

S

AF

FA

IR

S

AL

PE

N

A C

.R .T

.C

AL

PE

N A, M I

M

RI

M

RI

LR M

RI

-3 0-

N.T.S.E300

1 OPERATIONAL ONE LINE DIAGRAM BUILDING 490

Sheets
CS000 - COVER SHEET - BUILDING 490
E100 - DEMOLITION PLAN - BUILDING 490
E200 - NEW EQUIPMENT PLAN - BUILDING 490
E300 - OPERATIONAL DETAILS - BUILDING 490
23452 - CRTC Generator Replacements - Bldg 490 - Sheet - E100 - DEMOLITION PLAN - BUILDING 490.pdf
Sheets
CS000 - COVER SHEET - BUILDING 490
E100 - DEMOLITION PLAN - BUILDING 490
E200 - NEW EQUIPMENT PLAN - BUILDING 490
E300 - OPERATIONAL DETAILS - BUILDING 490
23452 - CRTC Generator Replacements - Bldg 490 - Sheet - E200 - NEW EQUIPMENT PLAN - BUILDING 490.pdf
Sheets
CS000 - COVER SHEET - BUILDING 490
E100 - DEMOLITION PLAN - BUILDING 490
E200 - NEW EQUIPMENT PLAN - BUILDING 490
E300 - OPERATIONAL DETAILS - BUILDING 490
23452 - CRTC Generator Replacements - Bldg 490 - Sheet - E300 - OPERATIONAL DETAILS - BUILDING 490.pdf
Sheets
CS000 - COVER SHEET - BUILDING 490
E100 - DEMOLITION PLAN - BUILDING 490
E200 - NEW EQUIPMENT PLAN - BUILDING 490
E300 - OPERATIONAL DETAILS - BUILDING 490