Drawings - Mechanical 22037.pdf
PDF 5 MB Posted
- Solicitation number
- RFQ - 171 - 230000000356
- Issued by
- Jackson County, Michigan
About this file
This document contains mechanical drawings and specifications for the Parnall Correctional Facility Mental Health Office Remodel and Addition project in Jackson County, Michigan. The project involves the demolition and replacement of various HVAC equipment, including air conditioners, unit heaters, and rooftop units. The drawings provide details on new HVAC ductwork, diffusers, control panels, and other related components. Key details include the installation of a new rooftop unit, condensing unit, and exhaust fan. The project also requires the contractor to coordinate with electrical and architectural trades. Bids for this state-funded project are due by 2:00 PM on a specified date, with submissions required via the SIGMA VSS online portal.
The mechanical equipment and ductwork must be installed according to the specifications and in compliance with applicable Michigan mechanical codes. Pricing terms, funding sources, and other salient commercial details are not provided in the drawings. Contractors must comply with requirements related to handling silica dust, using tamper-proof hardware, and coordinating with the facility's operations during construction.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLSHVAC PIPING
HVAC DUCTWORK
SD
F/S
F/S s s
TEMPERATURE CONTROL SYMBOLS
M
P
M
H
S
T P T N
T
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
GENERAL HVAC NOTES
1. LOCATE EXHAUST OUTLETS OF PLUMBING VENTS AT LEAST 10
FEET FROM OUTDOOR AIR INTAKES.
2. NOTIFY OWNER OF ANY DEMOLITION THAT MAY AFFECT
NORMAL OPERATION OF OTHER AREAS.
3. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE
AND BRANCH DUCT.
4. PROVIDE FLEXIBLE DUCT IN ACCESSIBLE CEILINGS. 6 FT MAX
LENGTH. KEEP BENDS TO A MINIMUM.
5. PROVIDE 5 FT MIN BEFORE ANY DUCT TAKEOFF FOR
DUCTWORK DOWNSTREAM OF VAV BOXES.
6. PROVIDE 1 1/2 DUCT DIAMETERS MIN. DUCT LENGTH OF HIGH
PRESSURE BRANCH DUCTWORK ON THE UPSTREAM SIDE OF
VAV BOXES.
7. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
8. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS
THAT MAY AFFECT THE WORK.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
10. ALL WORK SHALL BE PERFORMED BY LICENSED
CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY
LAW.
11. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
12. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT
FITTINGS IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED
OR VANED TEES, ETC.) DUCTWORK SHALL BE GALVANIZED
SHEET METAL, MIN. 26 GA.
13. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSION.
INCREASE DUCT SIZE FOR LINING.
14. LINE 10'-0" OF SUPPLY DUCTWORK AFTER EACH VAV BOX.
15. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE
FLEXIBLE DUCT CONNECTORS.
16. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA
AIR GAP.
17. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
18. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL
NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
DO NOT SCALE FROM DRAWINGS.
19. DX, VENT, GAS ROOF PENETRATIONS TO INCLUDE A CURB AND
CURB CAP. PATCH AND SEAL ROOF PENETRATIONS TO BE
WATER TIGHT.
20. ALL ROOF PENETRATIONS SHALL BE SEALED WATER TIGHT.
21. CONNECT ALL HVAC ALARM CONTACTS TO STARNET 2 SYSTEM
THRU ETHERNET CONTACT CLOSURE. CONNECT TO SECURITY
IT RACK WITH PURPLE CAT-6 CABLES(S) AS REQUIRED TO
CONNECT TO STARNET 2 SYSTEM. CONTRACTOR TO HIRE AND
COORDINATE CONNECTION TO SECURITY IT RACK WITH BRETT
EMERSON FROM COMMTECH DESIGN (PHONE 616-433-7210).
22. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL
USE TAMPERPROOF SCREWS.
23. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN
ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO
DISABLE THE FIRE ALARM.
24. CONTRACTOR TO PATCH AND PAINT EXISTING WALLS AS
NEEDED TO MATCH EXISTING WHERE DEMOLITION AND/OR
NEW WORK IS COMPLETED. REFER TO ARCHITECTURAL FOR
MORE DETAILS.
25. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO
OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED
THROUGHOUT THE PROJECT.
26. ALL DUST & DEBRIS MUST BE CONTAINED WITHIN THE
CONSTRUCTION AREA VIA TARP AND SEAL. THE CONTRACTOR
SHALL SUPPLY TEMPORARY EXHAUST FANS, DUCTWORK,
AND HEPA FILTERS AS REQUIRED TO MAINTAIN A CLEAN AIR
ENVIRONMENT ADJACENT TO THE CONSTRUCTION AREA.
SILICA DUST MUST BE HANDLED/DISCARDED IN ACCORDANCE
WITH MIOSHA REQUIREMENTS.
R ev ie w
D
AT
E
3/
/2
BI
D S
ET
AR
C
H
IT
EC
TS
EN
G
IN
EE
R S
M A
T R
I X
M
EN
TA
L
H
EA
LT
H
O
FF
IC
E
R
EM
O D
EL
AN
D A
D D
IT
IO
N
PA
R
N
AL
L C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
JC
/E
N G
B Y
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A N
C A
R B
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
PR
O
JE
C T
N O
2/
7.
H
JD
N
LS
N
LS
H
VA
C
SY
M
BO
LS
N
O
TE
S, A
N D
AB
BR
EV
IA
TI
O
N S
M -1
DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING
ABANDONED AIR CONDITIONER. DEMO ASSOCIATED
PIPING, CONTROLS, AND ALL ASSOCIATED
ACCESSORIES IN ITS ENTIRETY.
DISCONNECT, REMOVE, AND DEMO EXISTING UNIT
HEATER. DEMO ASSOCIATED GAS REGULATOR,
CONTROLS, COMBUSTION AIR / VENT PIPING, AND ALL
ASSOCIATED ACCESSORIES IN ITS ENTIRETY. DEMO
GAS PIPING BACK TO MAIN AND CAP. PATCH ROOF AS
REQUIRED TO MATCH EXISTING AND SEAL WATER
TIGHT.
DISCONNECT, REMOVE, AND SALVAGE EXISTING AIR
CONDITIONER. SALVAGED AIR CONDITIONER TO BE
TURNED OVER TO FACILITY UPON REMOVAL. PATCH
EXISTING WALL OPENING AS REQUIRED TO MATCH
EXISTING WALL. COORDINATE WITH ARCHITECTURAL
TRADES.
X-UH
X-UH
X-AC 1X-AC 1
X-SA
X-SD ---
X-SA
X-SD ---
X-RG ---
10x10 ---
X-RG ---
10x10 ---
X-RA
X-RA
T
X-RTU
X-AC 3
X-IT RACK
R ev ie w
D
AT
E
3/
/2
BI
D S
ET
AR
C
H
IT
EC
TS
EN
G
IN
EE
R S
M A
T R
I X
M
EN
TA
L
H
EA
LT
H
O
FF
IC
E
R
EM
O D
EL
AN
D A
D D
IT
IO
N
PA
R
N
AL
L C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
JC
/E
N G
B Y
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A N
C A
R B
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
PR
O
JE
C T
N O
2/
7.
H
JD
N BUILDING 80 - PARTIAL FLOOR PLAN - HVAC DEMOLITION
SCALE: 3/16" = 1'-0"
10 5 10 13
N
LS
N
LS
BU
IL
D
IN
G
PA
R
TI
AL
F
LO
O R
P
LA
N
H
VA
C D
EM
O
LI
TI
O N
M -3
X-UH
X-SA
X-SD ---
X-SA
X-SD ---
X-RG ---
10x10 ---
X-RG ---
10x10 ---
X-RA
X-RA
T
X-RTU
X-IT RACK
RTU-1
(LOCATED ON ROOF)
VAV-1
DDC TOUCHSCREEN
CONTROL PANEL
20x12 SA UP TO RTU-1
24x14 RA UP
TO RTU-1
VAV-5
VAV-7
VAV-9
EF-1
(LOCATED
ON ROOF)
VAV-8
10x6 SA
VAV-4
VAV-7
SD-2 150
6"ø ---
RG-1 150
24x6 ---
SD-1 150
8"ø TYP. 3
RG-1 450
24x12 ---
SD-1 125
6"ø ---
RG-1 125
24x6 ---
SD-1 135
6"ø TYP. 3
RG-1 405
24x12 ---
RG-1 450
24x12 ---
SD-1 150
8"ø TYP. 3
SD-2 125
6"ø ---
SD-2 125
6"ø ---
RG-1 125
24x6 ---
SD-1 200
8"ø ---
SD-1 75
6"ø ---
EG-1 75
12x12 ---
SD-3 50
6"ø ---
10x10 EA
CUH-1
VAV-10
VAV-6
S
SD-1 100
6"ø ---
20x12 SA10x12 SA
10x6 SA
12x10 SA
8x10 SA
24x14 RA
24x14 RA
12x10 RA
12x10 RA
8x8 RA
16x14 RA
6x6 RA
10x10 SA
10x10 SA
8x10 SA
6x8 SA
14x8 SA10x8 SA
6x8 SA
6x8 SA
6x6 EA
EG-1 400
12x12 ---
10x10 EA
AC-1
T
DX PIPING
(LOCATED ON ROOF)
CU-1
(LOCATED ON ROOF)
3/4" CD
X-FD
6x8 SA
VAV-2
RG-1 125
24x6 ---
VAV-3
RG-1 125
24x6 ---
VAV-6
6x8 SA
VAV-8
VAV ACCESS
PANEL (TYP.)
10x6 SA
6x8 SA
SD-2 125
6"ø ---
SD-2 125
6"ø ---
VAV-4
RG-1 125
24x6 ---
S
S
S
S
S
S
S
S
S S
6x8 SA
6x8 SA
6x10 SA
6x10 SA
10x6 SA
8x14 RA
3/4" CD
CO
DX PIPING
12x10 RA
BAS
HVAC KEY NOTES
INSTALL NEW DDC TOUCHSCREEN CONTROL PANEL AT
LOCATION SHOWN PER MANUFACTURES INSTALLATION
INSTRUCTIONS.
INSTALL RETURN GRILLE AT LOCATION SHOWN. RETURN AIR
BRANCH DUCTWORK SIZE SHALL BE 10x10.
INSTALL RETURN GRILLE AT LOCATION SHOWN. RETURN AIR
BRANCH DUCTWORK SIZE SHALL BE 6x6.
INSTALL WALL MOUNTED AIR CONDITIONER AT LOCATION
SHOWN. INSTALL TOP OF AIR CONDITIONER 1' BELOW CEILING.
INSTALL PER MANUFACTURES INSTALLATION INSTRUCTIONS.
INSTALL ROOFTOP UNIT AND ROOF CURB AT LOCATION
SHOWN. INSTALL ROOFTOP UNIT AND ASSOCIATED
ACCESSORIES PER MANUFACTURES INSTALLATIONS
INSTRUCTIONS.
INSTALL CONDENSING UNIT ON ROOF AT LOCATION SHOWN
PER MANUFACTURES INSTALLATION INSTRUCTIONS.
CONNECT NEW DDC CONTROL PANEL TO DARK NETWORK I.T.
RACK WITH PURPLE CAT-6 CABLE(S) AS REQUIRED TO SEE THE
BUILDING FROM THE MAINTENANCE BUILDING. CONTRACTOR
TO HIRE AND COORDINATE CONNECTION TO DARK NETWORK
IT RACK WITH BRET EMERSON FROM COMMTECH DESIGN
(PHONE 616-433-7219).
REFER TO ARCHITECTURAL PLANS FOR EXACT ACCESS PANEL
LOCATION.
CONNECT DDC CONTROL PANEL TO I.T. RACK SYSTEM TO
ALLOW FOR REMOTE TRACKING AND MONITORING. SYSTEM TO
SEND ALARM POINT TO STARNET 2 SYSTEM THROUGH AN
ETHERNET CONTACT CLOSURE.
INSTALL ROOF MOUNTED EXHAUST FAN AT LOCATION SHOWN.
10x10 EXHAUST AIR DUCTWORK UP TO NEW EXHAUST FAN.
INSTALL RETURN GRILLE AT LOCATION SHOWN. RETURN AIR
BRANCH DUCTWORK SIZE SHALL BE 10x8.
GENERAL HVAC NOTES
1. INSTALL ALL FLAT PLATE SENSORS WITH TAMPER
PROOF SCREWS.
2. CONTRACTOR TO COORDINATE VAV AND DUCTWORK
INSTALLATION WITH ACCESS PANEL LOCATIONS.
3. ALL VAV BOXES MUST BE FULLY SERVICEABLE FROM
ACCESS PANELS. CONTRACTOR SHALL COORDINATE
VAV LOCATIONS WITH ARCHITECTURAL TRADES.
R ev ie w
D
AT
E
3/
/2
BI
D S
ET
AR
C
H
IT
EC
TS
EN
G
IN
EE
R S
M A
T R
I X
M
EN
TA
L
H
EA
LT
H
O
FF
IC
E
R
EM
O D
EL
AN
D A
D D
IT
IO
N
PA
R
N
AL
L C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
JC
/E
N G
B Y
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A N
C A
R B
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
PR
O
JE
C T
N O
2/
7.
H
JD
N BUILDING 80 - PARTIAL FLOOR PLAN - HVAC NEW
SCALE: 3/16" = 1'-0"
10 5 10 13
N
LS
N
LS
M -4
BU
IL
D
IN
G
PA
R
TI
AL
F
LO
O
R P
LA
N
H
VA
C
N
EW
5 DUCT HANGER DETAIL
SCALE: NTSSCALE: NTSSCALE: NTS
HANGER STRAPS HANGER RODS
STRAP HANGER TRAPEZE HANGER
NO POP RIVETS ALLOWED, USE
SELF-TAPPING SHEETMETAL SCREWS
ONLY (TYP)
4 DUCT TRANSITION DETAIL
SCALE: NTS
VD
NOTES:
1. "ALTERNATE" FITTINGS SHALL BE
ACCEPTABLE ONLY WHEN DUCT HEIGHT
DOES NOT PERMIT THE USE OF
"PERMITTED" FULL SIZE BELLMOUTH
CONNECTION
2. THIS DETAIL APPLIES TO SINGLE TAKEOFFS
TO DIFFUSER AS WELL AS BRANCH
TAKEOFFS. IT ALSO APPLIES TO TAKEOFFS
IN THE HORIZONTAL AS WELL AS THE
VERTICAL DIRECTION.
DUCT SIZE:
(SEE PLANS)
PREFERRED
TAKE-OFF DETAIL
STANDARD
45° RECTANGULAR
DUCT CONNECTION
(SUPPLY SHOWN,
RETURN/EXHAUST SIMILAR)
BELLMOUTH
CONNECTION
MANUAL VOLUME
DAMPER TYPICAL AT
ALL DUCT
TAKE-OFFS
MAIN DUCT
AIR FLOW
6" min.
1 DUCT TRANSITION DETAIL
SCALE: NTS
L
W
SA FLOW
RA FLOW
MAIN AIR DUCT
BALANCING DAMPER IN ALL
SA AND RA BRANCHES TO
AIR OUTLETS
BRANCH AIR DUCT
(TYPICAL)
NOTE:
L=1/4 W (4" MIN.)
45°
TURNING VANES FOR
SQUARE ELBOW DETAIL
SCALE: NTS
FRAME
VANED ELBOW
LOCKING LUG
2-1/4"R
4-1/2"R
TURNING VANE
NOTES:
1. LOCKING LUGS INTEGRAL WITH VANE
2. MAXIMUM UNSUPPORTED VANE LENGTH 48"
3. FRAMES - BOLTED OR RIVETED TO ELBOW
4. VANES AND FRAMES - SAME GAUGE AS ELBOW
2 1 /4"
3 1 /2"
RECTANGULAR TRANSITIONS, OFFSETS,
AND ELBOWS
SCALE: NTS
RADIUS ELBOW
NOTE:
90° ELBOW SHOWN
SIMILAR RADIUS
CONSTRUCTION FOR
ALL ANGLES
R
R
OFFSET
ELBOW
FULL RADIUS
(R=W)
FLOW
AIR
TRANSITION - CONTRACTION FLOW
TRANSITION - DIVERGING FLOW
15°
FLOW
AIR
15°
W
W
W
R=1/ W
15°
15°
7 VAV TERMINAL UNIT DETAIL
SCALE: NTS
NOTES:
1. FLEXIBLE DUCTWORK SHALL NOT BE PERMITTED
UPSTREAM OF VAV BOXES.
2. DUCT TRANSITIONS SHALL BE A MINIMUM OF 3
DUCT DIAMETERS UPSTREAM OF ANY VAV BOX.
REDUCER OR INCREASER
IF REQUIRED
LINED SHEET METAL RUN-OUT
SIZE AS SHOWN ON PLAN 5 FT.
MIN. BEFORE TAKE OFF
SUPPLY DIFFUSER (SEE
SCHED. FOR TYPE)
COLLAR
FLEX ELBOW
DIFFUSER
NECK SIZE
FLEXIBLE DUCT
PROVIDE HANGER
CEILING
SHEET METAL RUN-OUT
SIZE AS SHOWN ON PLAN
BALANCE DAMPER
FLOW RING
TERMINAL UNIT
SUPPLY AIR
DUCT
CONICAL TAP.
TRANSITION AS
REQUIRED
3 DUCT
DIA. MIN.
5 DUCT DIA. MIN.
6'-0" MAX.
6 FLAT ROOF EXHAUST FAN DETAIL
SCALE: NTS
ELECTRICAL WIRING THROUGH CURB
OPENING WITH FLEXIBLE CONDUIT TO
DISCONNECT IN MOTOR HOUSING BY
E.C.
ROOF OPENING FRAMING BY
GENERAL TRADES
SPUN ALUMINUM FAN
HOUSING
ALUMINUM BIRD SCREEN
ALL AROUND
SECURE FAN TO CURB WITH
SHEET METAL SCREWS 12" O.C.
ALL AROUND
REFER TO DRAWINGS FOR
DUCT SIZE
12" HIGH INSULATED PRE-
FAB. ROOF CURB
FAN IMPELLAR
DIRECT DRIVE
MOTOR
COUNTER FLASHING
ROOFING MATERIALBACKDRAFT
DAMPER
RTU
CURB
G
ROOF
UNION
GAS COCK
WATERTIGHT
FLASHING
5/8" EXTERIOR SHEATHING (TYP)
2" SOUND-BOARD, INSULATION (TYP)
5/8" EXTERIOR SHEATHING (TYP)
2" SOUND-BOARD, INSULATION (TYP)
5/8" EXTERIOR SHEATHING (TYP)
DECKING
DRIP LEG
8 ROOF TOP UNIT DETAIL
SCALE: NTS
SA/RA DUCTWORK
EITHER DOWN FLOW
OR SIDE DISCHARGE
AS SHOWN ON
PLANS, LINE FIRST 10'
R ev ie w
D
AT
E
3/
/2
BI
D S
ET
AR
C
H
IT
EC
TS
EN
G
IN
EE
R S
M A
T R
I X
M
EN
TA
L
H
EA
LT
H
O
FF
IC
E
R
EM
O D
EL
AN
D A
D D
IT
IO
N
PA
R
N
AL
L C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
JC
/E
N G
B Y
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A N
C A
R B
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
PR
O
JE
C T
N O
2/
7.
H
JD
N
LS
N
LS
M -8
H
VA
C
D
ET
AI
LS
R ev ie w
D
AT
E
3/
/2
BI
D S
ET
AR
C
H
IT
EC
TS
EN
G
IN
EE
R S
M A
T R
I X
M
EN
TA
L
H
EA
LT
H
O
FF
IC
E
R
EM
O D
EL
AN
D A
D D
IT
IO
N
PA
R
N
AL
L C
O R
R
EC
TI
O
N
AL
F
AC
IL
IT
Y
JC
/E
N G
B Y
IN
D
EX
PC
A
D R
AW
N
B Y
D
ES
IG
N
ED
B
Y
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A N
C A
R B
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
PR
O
JE
C
T D
ES
C
R
IP
TI
O
N
PR
O
JE
C T
N O
2/
7.
H
JD
N
LS
N
LS
H
VA
C S
C H
ED
U
LE
S
M -9
| Sheets and Views |
| FP300-2213700-FP300 |
| FP400-2213700-FP400 |
| M100-2213700-M100 |
| M300-2213700-M300 |
| M400-2213700-M400 |
| M800-2213700-M800 |
| M900-2213700-M900 |
| P100-2213700-P100 |
| P300-2213700-P300 |
| P301-2213700-P301 |
| P400-2213700-P400 |
| P401-2213700-P401 |
File details come from the government source that posted it. Updated .