Drawings_2023 06 30 21085_Part4.pdf

PDF 3 MB Posted

Attached to
511/21085. MAA; Midland Armory Construction
Solicitation number
RFQ - 171 - 230000000626
Issued by
Lenawee County, Michigan

About this file

This document appears to be related to a state and local contract opportunity for the construction of the Midland Armory Addition and Renovation project located in Midland, Michigan. The project is being managed by the Department of Military and Veteran's Affairs (DMVA) in the State of Michigan. The project includes the construction of a new addition and renovation to the existing Midland Armory building. The bid attachments and drawings include details on the mechanical, electrical, and plumbing systems, as well as architectural plans. Bidders must submit their proposals electronically via the SIGMA VSS system by the deadline of 2:00 pm on the specified date. Bidders are advised not to submit questions online, but rather to email them directly to the project manager. The contract will be awarded by DMVA, but the specific award date is not provided.

In terms of pricing and funding, the solicitation does not provide specific budget information. However, it indicates that the project is being funded by the State of Michigan. The solicitation does not mention any set-aside requirements or incumbents. Bidders should review the complete bid documents carefully for all terms and conditions related to pricing, payment, and other key contract requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VOLUME CONTROL

DAMPER

45° TAKEOFF COLLAR

WITHOUT DAMPER

RECTANGULAR LOW

PRESSURE DUCT

ROUND LOW

PRESSURE DUCT

RETURN AIR PLENUM

W/ 1" DUCT LINER

BIRD SCREEN

DUCT TO RTU

M

IN

ROOFING

ROOF CURB

ROOF INSULATION

ROOF STRUCTURE

MIN.

W/2

WIDTH = W

PLENUM EQUAL TO GRILLE

NECK SIZE. HEIGTH TO VARY

PER INSTALLATION

REQUIREMENTS.

RA/EA DUCT. REFER TO PLAN

FOR SIZE/SHAPE.

PAINT INSIDE OF

PLENUM FLAT BLACK

MANUAL BALANCE DAMPER

WITH BRIGHTLY PAINTED

EXTENDED STAND-OFF.

CEILING, LAY-IN OR HARD.

RA / EA GRILLE

NOTES:

REFER TO PLANS & SCHEDULE FOR DIFFUSERS

H (NOTE 1)

A

FRAME LENGTH

F R A M

E

W

ID

TH

H (N

OTE

1)

A

60° B

ARREL

ROTA

TIO

N

DIMENSION "H" EQUALS HEIGHT OF DAMPER BLADE

PLUS 2" (MIN.) TO ALLOW FOR INSTALLATION OF

DAMPER WITHOUT DAMPER BLADE PROTRUDING INTO

STREAM OF BRANCH MAIN DUCT.

SEAL (SUITABLE FOR PAINTING) ALL SEAMS AND

JOINTS AIR TIGHT (TYP.)

2.

1.

PAINT TO MATCH SUPPLY DUCTWORK

RECTANGULAR S.A. BOX WITH

END FACE FOR MOUNTING

FRAME OF S.A. GRILLE.

ROUND/OVAL S.A. DUCT

SEE PLANS FOR SIZE

NOTE 2

(TYP)

NOTES:

1"

SEE NOTE 3

GALV. HANGER

1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACE BY ANGLE. FOR CROSS SECTION AREA MORE

THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.

2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.

3. SUPPORTS SHALL BE SPACED AND SIZED PER SMACNA.

THREADED

HANGER ROD

HANGER

STRAP

UNISTRUT OR

ANGLE IRON

MAX. 60"

OVER 60"

SUPPLY DUCTWORK DUCT INSULATION,

REFER TO SPECIFICATIONS

SUPPLY DUCT BOOT

TEE W/ END CAP

MAXIMUM OF 3 FEET

OF INSULATED FLEX

DUCT

SUPPLY AIR DIFFUSER,

REFER TO SCHEDULE

MANUAL BALANCE DAMPER

WITH QUAD. LOCK

ROUND DIFFUSER THROAT

VERIFY CEILING TYPE WITH

ARCH CEILING PLANS

RETURN/EXHAUST AIR

SUPPLY AIR

VD

MAIN DUCT

BRANCH DUCT

TAPERED CONNECTION 45° ANGLE (IF MAIN DUCT

IS RECTANGULAR) OR CONICAL CONNECTION (IF

MAIN DUCT IS ROUND) L=1/4 W; 4" MIN

W

L

HS

HR

CIRCULATING PUMP

STRAINER

SHUT-OFF VALVE (TYP.)

CHECK VALVE

BALANCING VALVE

3-WAY CONTROL

VALVE

3'-0" MIN.

FOR 2" PIPE

AND SMALLER

5'-0" MIN.

FOR 2 1/2" PIPE

AND LARGER

HS

C.P.

PRESSURE

GAUGE (TYP.)

N.O.

C.

N.C.

UNIONS OR FLANGES (TYP.)

OFFSET PIPING TO ALLOW

FOR EASY COIL REMOVAL

HOSE BIBB DRAIN

HEATING COIL

THERMOMETER (TYP.)

BALL VALVE AIR VENT OFF

OF COIL. TERMINATE OUTSIDE

AHU WITH 3/4" HOSE

THREAD (TYP.)

CALIBRATED BALANCING VALVE

W/ SHUT-OFF VALVE

FROM

MAIN

HR

REDUCER IF REQUIRED

ECCENTRIC TYPE W/ LEVEL

SIDE UP. TYPICAL FOR ALL

HYDRONIC HORIZONTAL

REDUCERS.

MANUAL AIR VENTS @

HIGH POINTS (TYP.)

UNION

CONTROL VALVE

FIN ENCLOSURE

DRAIN

MANUAL AIR

TOP FED CONFIGURATION

SHUT-OFF VALVE

HR

H S

H R

HS

H R

HR

SHUT-OFF VALVE

REDUCER IF REQUIRED ECCENTRIC

TYPE W/ LEVEL SIDE UP. TYPICAL ALL

HYDRONIC HORIZONTAL REDUCERS

OPTIONAL RETURN IN

ENCLOSURE CONFIGURATION.

PROVIDE ENCLOSURE WITH

SUFFICIENT HEIGHT

OPTIONAL

BOTTOM FED

CONFIGURATION

CALIBRATED

BALANCING

VALVE

OPTIONAL

BOTTOM FED

CONFIGURATION

MANUAL

AIR VENT

PRESSURE GAGE

INLINE

PUMP

ECCENTRIC REDUCER

W/ LEVEL SIDE UP

CHECK VALVE

BALL VALVE

FLANGED CONNECTION

BALL VALVE

BALL VALVE

STRAINER

C D

ACCU-210

SS-210

ACCU-210

FC-210

"AIREDALE" MODEL CSD18, 1.5 TON COOLING

CAP., 208/1/60. 18,900 BTU/HR. COOLING CAP.,

3.0KW ELECTRIC HEATING CAP.,540 CFM, 40 CFM

(OA),120 WATT FAN

OPTIONS: KNOCKOUTS FOR BRANCH SUPPLY AIR

AND OUTDOOR AIR DUCTWORK.

CONTROLS: PROVIDE CAREL CONTROLLER WITH

BACNET CARD FOR BAS INTERFACE. CAREL WALL

SENSOR.

CONDENSATE LIFT PUMP, BASED ON

"LITTLE GIANT" VCC-20ULS. 25 GPH AT 15'

TDH 115/1/60, 1.5 A

ROOF

SPILL CONDENSATE ON

ROOF

SWEAT CONNECTIONS

PIPING PORTAL,

REFER TO DETAIL

CONDENSATE PIPING TO ROOF

COND. & DX REFRIGERANT PIPING

TO ROOF

REDUCER IF REQUIRED

ECCENTRIC TYPE W/ LEVEL

SIDE UP. TYPICAL FOR ALL HYDRONIC

HORIZONTAL REDUCERS

UNION

CALIBRATED

BALANCING VALVE

MANUAL AIR VENT (TYP.)

HR

HS

DRAIN

SHUT-OFF VALVE (TYP.)

CONTROL VALVE

AI

R

FL

O W

INLET STRAINER

BUTT ENDS

& SEAL

FOR HANGING DUCT:

TRAPEZE DUCT OR

STRAP HANGER AROUND

DUCT COMPLETELY. DO

NOT USE ANY SCREWS,

BECAUSE THEY

INTERFERE WITH DAMPER

BLADE(S)

PROVIDE EXTRA LENGTH

TO AVOID "PINCHING"

OF INSULATION AT

CORNERS

PROVIDE LOCKING

QUADRANT ARM

STANDOFF

F

IL

E N

U M

B E

R

S T

A T

E I

N D

E X

N U

M B

E R

S

C o ns tr uc tio n

F in a l R e co rd

Is su e d f o r

P re lim in a ry

D a te

D E

S

IG

N A

N D

C O

N S

TR

U

C

TI

O N

D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T

A N

D B

U D

G E

T S

T A

T E

O F

M

IC

H

IG

A N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

E a s t

K a la m a z o o A v e n u e

S u it e

K a la m a z o o

M ic h ig a n

-5

.3

.6

P H

O N

E

.3

.6

3F A

X

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

E a s t

F u lt o n S tr e e t, S u it e

G ra n d R a p id s

M ic h ig a n

.4

.9

P H

O N

E

.4

.5

6F

A X

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

M E

C H

A N

IC

A

L S

C H

E D

U L E

S A

N D

D E

T A

IL

S

-1

.0

M

J U

N E

M

ID

L A

N D

A R

M O

R Y

A D

D

IT

IO

N

A N

D R

E N

O V

A T

IO

N

A

IR

P

O R

T R

O A

D

M

ID

L A

N D

M

I

D E

P A

R T

M E

N T

O F

M

IL

IT

A

R Y

A N

D V

E T

E R

A N

'S A

F F

A

IR

S

/2

.C

A K

/1

/2

SCALE: NONE

TAKEOFF DETAIL - RECTANGULAR TO ROUND

SCALE: NONE

RTU RETURN AIR PLENUM DETAIL

SCALE: NONE

RETURN / EXHAUST AIR GRILLE PLENUM DETAIL

SCALE: NONE

DUCT MOUNTED DIFFUSER DETAIL

SCALE: NONE

DUCT HANGER SUPPORT DETAIL

SCALE: NONE

CEILING MOUNTED SUPPLY DIFFUSER DETAIL - TYPICAL

SCALE: NONE

BRANCH TAKE OFFS DETAIL

SCALE: NONE

AHU HEATING COIL PIPING DETAIL - SINGLE COIL 3-WAY VALVE

SCALE: NONE

FIN RADIATION PIPING DETAIL - SINGLE ROW

SCALE: NONE

PUMP - INLINE PIPING DETAIL

SCALE: NONE

SPLIT SYSTEM UNIT PIPING DETAIL

SCALE: NONE

CABINET HEATER PIPING DETAIL

ISSUED FOR DATE

SCALE: NONE

VOLUME DAMPER SUPPORT DETAIL

"YORK" MODEL CSD18, 1.5 TON COOLING CAPACITY,

208/1/60. PROVIDE WITH WINTER START KIT, LOW

AMBIENT CONTROLLER, AND CRANKCASE HEATER

RA IN

AFM-1

T-1

D-1

H-1

T-3

H-2

HPSL-1

EF-1

EF-1

EF-1

P R E F

IL

TE

R S

E C

TI

O N

SF-1

SF-1

SF-1

TS

S U P P

LY

F A N

HS

TS

E X H A U S T

F A N

T-4

H-3

HS TS

OUTDOOR AIR CONDITIONS

T-5

H-4

HS TS

INDOOR AIR CONDITIONS

SP-3

PS

AS

SA OUT

P

M

IX

ED

A

IR

D

AM

PE

R

SE

CT

IO

N OA IN

EA OUT

M

VFD

SF-1

VFD

EF-1

DX-1

DX-1

DX-1

PACKAGED DX

SYSTEM

DX-1

D X C

O

IL

S E C T

IO

N

T-2

TS

D-1

HS

LPSL-1

P

F

IN

A L

F

IL

T E R S

E C

TI

O N

CP-1

HCV-1

HCV-1

CP-1

M

SF-1

HEATING

F 31

FS-132

T-6

TS

CO2-1

CO2

RA IN

AFM-1

T-1

D-1

H-1

T-3

H-2

HPSL-1

EF-1

EF-1

EF-1

P R E F

IL

TE

R S

E C

TI

O N

SF-1

SF-1

SF-1

TS

S U P P

LY

F A N

HS

TS

E X H A U S T

F A N

T-4

H-3

HS TS

OUTDOOR AIR CONDITIONS

T-5

H-4

HS TS

INDOOR AIR CONDITIONS

SP-3

PS

AS

SA OUT

P

M

IX

ED

A

IR

D

AM

PE

R

SE

CT

IO

N OA IN

EA OUT

M

VFD

SF-1

VFD

EF-1

T-2

TS

D-1

HS

LPSL-1

P

F

IN

A L

F

IL

T E R S

E C

TI

O N

CP-1

HCV-1

HCV-1

CP-1

SF-1

M

HEATING

F

T-6

TS

FS-1

CO2-1

CO2

F

IL

E N

U M

B E

R

S T

A T

E I

N D

E X

N U

M B

E R

S

C o ns tr uc tio n

F in a l R e co rd

Is su e d f o r

P re lim in a ry

D a te

D E

S

IG

N A

N D

C O

N S

TR

U

C

TI

O N

D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T

A N

D B

U D

G E

T S

T A

T E

O F

M

IC

H

IG

A N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

E a s t

K a la m a z o o A v e n u e

S u it e

K a la m a z o o

M ic h ig

-5

.3

.6

P H

O

.3

.6

3F A

X

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

E a s t

F u lt o n S tr e e t, S u it e

G ra n d R a p id s

M ic h ig a n

.4

.9

P H

O N

E

.4

.5

6F

A X

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

T E

M P

E R

A T

U R

E C

O N

T R

O L S

-1

.0

M

J U

N E

M

ID

L A

N D

A R

M O

R Y

A D

D

IT

IO

N

A N

D R

E N

O V

A T

IO

N

A

IR

P

O R

T R

O A

D

M

ID

L A

N D

M

I

D E

P A

R T

M E

N T

O F

M

IL

IT

A

R Y

A N

D V

E T

E R

A N

'S A

F F

A

IR

S

/2

.C

A K

/1

/2

SEQUENCE OF OPERATIONS

NOTE: ALL LABOR, MATERIAL, EQUIPMENT AND SOFTWARE NOT SPECIFICALLY INDICATED

WITHIN CONTROLS DRAWINGS THAT IS REQUIRED TO MEET THE FUNCTIONAL INTENT

OF THE SEQUENCE OF OPERATIONS SHALL BE PROVIDED WITHOUT ADDITIONAL

COST. POINT LISTS SHALL BE A GUIDE TO THE POINTS REQUIRED FOR CONTROL

SYSTEM. FINAL POINTS SHALL BE DETERMINED BY SEQUENCE OF OPERATIONS. ALL

SET POINTS SHALL BE OPERATOR ADJUSTABLE THROUGH THE BMS. ALL POINTS

SHALL BE TRENDABLE.

ROOFTOP UNIT (RTU-1, RTU-4, RTU-5) CONTROLS

1. PROVIDE DIRECT DIGITAL CONTROLS FOR ROOFTOP SYSTEM OPERATION. UNIT(S) ARE A

COMBINATION OF AN OUTDOOR SINGLE ZONE VARIABLE VOLUME UNIT, SUPPLY FAN(S),

VARIABLE FREQUENCY CONTROLLER(S), PACKAGED DX SYSTEM, DIRECT EXPANSION COIL,

DUCT-MOUNTED HEATING HOT WATER COIL, CONTROL VALVE (CV) AND ACTUATOR WITH

CIRCULATING PUMP, MERV 13 FINAL & MERV 8 PRE-FILTERS, OUTDOOR –

RELIEF/EXHAUST - RETURN AIR DAMPERS AND ACTUATOR(S), RELIEF FAN(S), VARIABLE

FREQUENCY CONTROLLER(S) AND AIR TEMPERATURE/AIRFLOW/HUMIDITY SENSOR(S).

2. ROOFTOP UNIT ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:

A. TIME OF DAY (TOD) SCHEDULE.

a. TO BE DETERMINED BY OWNER (CONSULT WITH OWNER).

B. ENABLED AND DISABLED BASED ON MANUAL OVERRIDE FROM DDC.

3. ROOFTOP UNIT ADJUSTABLE SETPOINTS:

A. OCCUPIED 74°F COOLING / 70°F HEATING

B. UNOCCUPIED 85°F COOLING / 62°F HEATING

4. START/STOP, CONTROLLED DEVICES SHALL RESPOND AS FOLLOWS:

A. WHEN INDEXED TO STOP:

a. DISABLE SUPPLY AND RETURN/RELIEF FAN(S) SIMULTANEOUSLY.

b. DISABLE DX COOLING.

c. HEATING CV SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE

SENSOR AT 80°F (ADJ.), WHEN OUTDOOR AIR TEMPERATURE IS BELOW 45°F (ADJ.).

d. OUTDOOR AND RELIEF/EXHAUST AIR DAMPERS 100% CLOSED.

e. RETURN AIR DAMPER 100% OPENED.

B. WHEN INDEXED TO START:

a. ENABLE RETURN/RELIEF FAN(S) FIRST, THEN SUPPLY FAN(S).

b. OPERATION OF SYSTEM TO RESUME AFTER START-UP DELAY.

5. SUPPLY FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE SUPPLY FAN MOTOR(S)

VARIABLE FREQUENCY DRIVE(S), HEATING AND COOLING SOURCES AND MIXED AIR

DAMPERS TO MAINTAIN AN ADJUSTABLE SPACE TEMPERATURE SETPOINT MEASURED BY A

SPACE TEMPERATURE THERMOSTAT.

A. HEATING – UPON A FALL IN SPACE TEMPERATURE BELOW SPACE TEMPERATURE

SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:

a. MODULATE HEATING SOURCE (AS FIRST STAGE HEATING) TO MAINTAIN SPACE

TEMPERATURE SETPOINT.

• INCLUDE A MAXIMUM HEATING DISCHARGE TEMPERATURE OF 95°F (ADJ.).

• SUPPLY FAN(S) AT MINIMUM CFM/SPEED SETPOINT.

b. MODULATE SUPPLY FAN SPEED (AS SECOND STAGE HEATING) TO MAINTAIN ACTIVE

CFM/SPEED SETPOINT MEASURED BY A DUCT/FAN INLET AIR FLOW MEASURING

STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.

• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (80% OF DESIGN CFM) CFM

SETPOINTS (ADJ.).

c. UPON A CALL FOR ADDITIONAL HEAT BASED ON SUPPLY FAN(S) ARE DELIVERING

MAXIMUM CFM/SPEED (AS THIRD STAGE OF HEATING) OVERRIDE MAXIMUM

HEATING DISCHARGE TEMPERATURE.

• ALLOW HEATING CV TO MODULATE TO MAINTAIN SPACE TEMPERATE SETPOINT.

B. COOLING – UPON A RISE IN SPACE TEMPERATURE ABOVE SPACE TEMPERATURE

SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:

a. MODULATE SUPPLY FAN SPEED (AS FIRST STAGE COOLING) TO MAINTAIN ACTIVE

CFM/SPEED SETPOINT MEASURED BY DUCT/FAN INLET AIR FLOW MEASURING

STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.

• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (100% OF DESIGN CFM) CFM

SETPOINTS (ADJ.).

• ECONOMIZER SHALL BE UTILIZED (AS FIRST STAGE COOLING) IF APPLICABLE

AND NOT ALLOWING DISCHARGE AIR TEMPERATURE TO DROP BELOW 55°F,

THEN SUPPLY FAN.

b. MODULATE COOLING SOURCE (AS SECOND STAGE COOLING) TO MAINTAIN SPACE

TEMPERATURE SETPOINT.

• SUPPLY FAN(S) SHALL BE AT MAXIMUM CFM SETPOINT.

c. IF ECONOMIZER IS ENABLED, DAMPERS SHALL BE 100% OPEN TO OUTDOORS.

6. RETURN/RELIEF FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE RETURN/RELIEF

FAN MOTOR(S) VARIABLE FREQUENCY DRIVE(S) TO MAINTAIN SPACE PRESSURE SETPOINT

MEASURED BY A SPACE PRESSURE CONTROLLER LOCATED IN SPACE SERVED.

A. THE SPACE STATIC PRESSURE SETPOINT (ADJ.) SHALL BE A SETPOINT THAT CONTROLS

TO A SLIGHTLY POSITIVE PRESSURE.

7. COIL PUMP CONTROL BASED ON THE FOLLOWING:

A. HEATING HOT WATER COIL PUMP SHALL RUN WHEN THE SYSTEM IS IN HEATING MODE

(WHEN CV IS GREATER THAN 10% OPEN).

B. PUMP(S) SHALL RUN CONTINUOUSLY WHENEVER THE OUTDOOR AIR TEMPERATURE IS

LESS THAN 40°F.

8. ECONOMIZER CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR DAMPERS TO

MEET UNIT DISCHARGE AIR TEMPERATURE SETPOINT WHEN OUTDOOR AIR ENTHALPY IS

BELOW THE RETURN AIR ENTHALPY BUT ABOVE ECONOMIZING SETPOINT.

A. WHEN BTU CALCULATION FOR OUTDOOR AIR CONDITIONS EXCEEDS 28 BTUH/LB

(ADJ.), ECONOMIZER SHALL BE DISABLED.

9. MINIMUM OUTDOOR AIR CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR

DAMPERS TO MAINTAIN MINIMUM CFM SETPOINT MEASURED BY AN OUTDOOR AIR FLOW

MEASURING STATION. LIMIT THE CLOSING OF THE OUTDOOR AIR DAMPER TO PROVIDE

ABSOLUTE MINIMUM OUTDOOR AIR FLOW.

A. OUTDOOR – RELIEF/EXHAUST – RETURN MODULATING WITH ONE SIGNAL FROM

CONTROLLER.

B. REFER TO UNIT SCHEDULE FOR THE ABSOLUTE MINIMUM OUTDOOR AIRFLOW CFM

SETPOINT.

10. FILTER MONITORING - SYSTEM CONTROLLER SHALL MONITOR AND ALARM FILTER

PRESSURE DIFFERENTIAL PRESSURE DROP(S) FOR THE FOLLOWING:

A. FINAL FILTERS

a. MONITORING OF PSID

b. ALARM SETPOINT 1.00” W.C. (ADJ.)

B. PRE-FILTERS

a. MONITORING OF PSID

b. ALARM SETPOINT 0.5”W.C. (ADJ.)

11. UNOCCUPIED CONTROL – SYSTEM CONTROLLER SHALL INITIATE THE FOLLOWING BASED

ON A FALL OR RISE IN SPACE TEMPERATURE:

A. HEATING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED HEATING

MODE) WHEN A CALL FOR HEAT IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)

DURING UNOCCUPIED MODE AND HEATING SYSTEM IS OR CAN BE ENABLED. SYSTEM

SHALL RESPOND BASED ON THE FOLLOWING:

a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE

CONTROL OPERATION TO PROVIDE HEATING TO ZONE WITH THE EXCEPTION TO THE

FOLLOWING:

• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%

OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.

• COOLING SHALL BE DISABLED.

b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR HEAT AND HEATING CV SHALL

REMAIN UNDER CONTROL OF MIXED/DISCHARGE AIR TEMPERATURE CONTROL.

B. COOLING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED COOLING

MODE) WHEN A CALL FOR COOL IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)

DURING UNOCCUPIED MODE AND COOLING SYSTEM IS OR CAN BE ENABLED.

a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE

CONTROL OPERATION TO PROVIDE COOLING TO THE ZONE WITH THE EXCEPTION

TO THE FOLLOWING:

• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%

OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.

• HEATING SHALL BE DISABLED.

• ECONOMIZER SHALL BE ENABLE IF SPACE TEMPERATURE IS GREATER THAN

OUTDOOR AIR TEMPERATURE BY 10°F (ADJ.).

b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR COOL.

12. INITIAL STARTUP CONTROL - SYSTEM CONTROLLER SHALL ENABLE UNIT PRIOR TO

SCHEDULED OCCUPANCY UTILIZING OPTIMUM START LOGIC TO ADJUST STARTUP TIME

FOR UNIT BASED ON OUTDOOR AIR TEMPERATURE, BUILDING TEMPERATURE AND

HISTORIC ELAPSE TIME TO REACH SETPOINT.

A. UNIT SHALL ENERGIZE AND PROVIDE HEATING AND COOLING BASED ON THE SPACE

TEMPERATURE SENSOR(S) TO BRING SPACE TO OCCUPIED SETPOINT. THE OUTDOOR

AND RELIEF/EXHAUST AIR DAMPERS SHALL BE CLOSED UNLESS ECONOMIZER IS

ENABLED. ONCE OCCUPIED SETPOINT HAS BEEN REACHED, THE UNIT SHALL SWITCH

TO OCCUPIED MODE.

13. CO2 CONTROL - SYSTEM CONTROLLER SHALL OVERRIDE MIXED AIR DAMPER CONTROLS

IN NON-ECONOMIZING MODE USING SPACE CO2 SENSOR TO INCREASE OUTDOOR

MINIMUM CFMTO A MAXIMUM CFM. INCLUDE CORRESPONDING CLOSING RETURN AIR

DAMPER AND OPENING OF RELIEF/EXHAUST AIR DAMPERS.

A. UPON RETURN SPACE C02 SENSOR EXCEEDING SETPOINT (800 PPM ADJ.), START TO

MODULATE MIXED AIR DAMPERS (OUTDOOR AIR DAMPER OPENING) IN GRADUAL

INCREMENTS UNTIL C02 SENSOR SETPOINT IS SATISFIED.

a. MODULATE MIXED AIR DAMPERS DOWN TO ITS ABSOLUTE MINIMUM POSITION

UPON SATISFYING SENSOR SETPOINT.

B. ALARM HIGH C02, 1,200 PPM (ADJ.)

C. REFER TO UNIT SCHEDULE FOR THE MAXIMUM OUTDOOR AIRFLOW CFM SETPOINT.

14. SAFETY SHUTDOWNS:

A. PROVIDE A LOW-TEMPERATURE PROTECTION THERMOSTAT(S) ON THE LEAVING SIDE OF

HEATING HOT WATER COIL WHICH WILL DE-ENERGIZE UNIT, CLOSE MIXED AIR DAMPERS

(CLOSING OUTDOOR/RELIEF/EXHAUST AIR DAMPER(S)) AND THE HEATING HOT WATER

COIL CONTROL VALVE SHALL BE FULLY OPENED AND COIL PUMP ENERGIZED. PROVIDE

MANUAL RESET.

B. PROVIDE A HIGH STATIC PRESSURE SENSOR IN THE SUPPLY DISCHARGE PLENUM TO

DE-ENERGIZE THE UNIT UPON SENSING A HIGH STATIC PRESSURE OF 4.0" W.C..

PROVIDE MANUAL RESET.

C. PROVIDE A LOW PRESSURE STATIC LIMIT IN THE RETURN PLENUM TO DE-ENERGIZE THE

UNIT UPON SENSING A HIGH NEGATIVE STATIC PRESSURE OF -4.0" W.C.. PROVIDE

MANUAL RESET.

D. DUCT MOUNTED IONIZATION SMOKE DETECTOR(S) PROVIDED BY DIVISION 28 SHALL

DE-ENERGIZE THE UNIT WHENEVER PRODUCTS OF COMBUSTION ARE SENSED.

SCALE: NONE

RTU-1, RTU-4, RTU-5 ROOFTOP UNIT CONTROLS DIAGRAM

CONTROL POINTS

NUMBER TAG DESCRIPTION ALARM TREND I/O MISC. REMARKS

PACKAGED ROOFTOP UNIT (DX COOLING, HW HEAT)

01 H-1 RETURN AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

02 T-1 RETURN AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

03 LPSL-1 LOW PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET

04 EF-1 SPEED CONTROL ■ OUTPUT

05 EF-1 STATUS ■ ■ INPUT

06 EF-1 ENABLE/DISABLE ■ OUTPUT

07 AFM-1 OUTDOOR AIR FLOW ■ INPUT

08 D-1 MIXED AIR DAMPER OUTPUT ■ OUTPUT

09 D-1 MIXED AIR DAMPER POSITION ■ INPUT

10 T-2 MIXED AIR TEMPERATURE ■ ■ INPUT ALARM AT 45°F ADJ.

11 CP-1 STATUS ■ ■ INPUT

12 CP-1 ENABLE/DISABLE ■ OUTPUT

13 SF-1 FAN AIR FLOW ■ INPUT

14 SF-1 SPEED CONTROL ■ OUTPUT

15 SF-1 STATUS ■ ■ INPUT

16 SF-1 ENABLE/DISABLE ■ OUTPUT

17 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT

18 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT

19 DX-1 COOLING SYSTEM ALARM STATUS ■ ■ INPUT

20 DX-1 COOLING SYSTEM RUN STATUS ■ INPUT

21 DX-1 COOLING SYSTEM ENABLE/DISABLE ■ OUTPUT

22 DX-1 COOLING SYSTEM STAGING ■ OUTPUT

23 HPSL-1 HIGH PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET

24 T-3 DISCHARGE AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

25 H-2 DISCHARGE AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

26 H-3 OUTDOOR AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)

27 T-4 OUTDOOR AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)

28 SP-3 ROOM STATIC PRESSURE ■ INPUT

29 H-4 INDOOR AIR HUMIDITY SENSOR ■ INPUT

30 T-5 INDOOR AIR TEMPERATURE ■ INPUT

31 FS-1 FREEZE STAT ALARM STATUS ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET

32 T-6 HEATING COIL DISCHARGE TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

33 CO2-1 CO2 RETURN CONCENTRATION ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET

PACKAGED ROOFTOP UNIT (HW HEAT)

01 H-1 RETURN AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

02 T-1 RETURN AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

03 LPSL-1 LOW PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET

04 EF-1 SPEED CONTROL ■ OUTPUT

05 EF-1 STATUS ■ ■ INPUT

06 EF-1 ENABLE/DISABLE ■ OUTPUT

07 AFM-1 OUTDOOR AIR FLOW ■ INPUT

08 D-1 MIXED AIR DAMPER OUTPUT ■ OUTPUT

09 D-1 MIXED AIR DAMPER POSITION ■ INPUT

10 T-2 MIXED AIR TEMPERATURE ■ ■ INPUT ALARM AT 45°F ADJ.

11 CP-1 STATUS ■ ■ INPUT

12 CP-1 ENABLE/DISABLE ■ OUTPUT

13 SF-1 FAN AIR FLOW ■ INPUT

14 SF-1 SPEED CONTROL ■ OUTPUT

15 SF-1 STATUS ■ ■ INPUT

16 SF-1 ENABLE/DISABLE ■ OUTPUT

17 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT

18 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT

19 HPSL-1 HIGH PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET

20 T-3 DISCHARGE AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

21 H-2 DISCHARGE AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

22 H-3 OUTDOOR AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)

23 T-4 OUTDOOR AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)

24 SP-3 ROOM STATIC PRESSURE ■ INPUT

25 H-4 INDOOR AIR HUMIDITY SENSOR ■ INPUT

26 T-5 INDOOR AIR TEMPERATURE ■ INPUT

27 T-6 HEATING COIL DISCHARGE TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS

28 FS-1 FREEZE STAT ALARM STATUS ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET

29 CO2-1 CO2 RETURN CONCENTRATION ■ ■ INPUT

SCALE: NONE

RTU-2, RTU-3 ROOFTOP UNIT CONTROLS DIAGRAM

SEQUENCE OF OPERATIONS (CONT'D)

ROOFTOP UNIT (RTU-2, RTU-3) CONTROLS

1. PROVIDE DIRECT DIGITAL CONTROLS FOR ROOFTOP SYSTEM OPERATION. UNIT(S) ARE A

COMBINATION OF AN OUTDOOR SINGLE ZONE VARIABLE VOLUME UNIT, SUPPLY FAN(S),

VARIABLE FREQUENCY CONTROLLER(S), DUCT-MOUNTED HEATING HOT WATER COIL,

CONTROL VALVE (CV) AND ACTUATOR WITH CIRCULATING PUMP, MERV 13 FINAL & MERV 8

PRE-FILTERS, OUTDOOR – RELIEF/EXHAUST - RETURN AIR DAMPERS AND ACTUATOR(S),

RELIEF FAN(S), VARIABLE FREQUENCY CONTROLLER(S) AND AIR

TEMPERATURE/AIRFLOW/HUMIDITY SENSOR(S).

2. ROOFTOP UNIT ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:

A. TIME OF DAY (TOD) SCHEDULE.

a. TO BE DETERMINED BY OWNER (CONSULT WITH OWNER).

B. ENABLED AND DISABLED BASED ON MANUAL OVERRIDE FROM DDC.

3. ROOFTOP UNIT ADJUSTABLE SETPOINTS:

A. OCCUPIED 74°F COOLING / 70°F HEATING

B. UNOCCUPIED 85°F COOLING / 62°F HEATING

4. START/STOP, CONTROLLED DEVICES SHALL RESPOND AS FOLLOWS:

A. WHEN INDEXED TO STOP:

a. DISABLE SUPPLY AND RETURN/RELIEF FAN(S) SIMULTANEOUSLY.

b. HEATING CV SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE

SENSOR AT 80°F (ADJ.), WHEN OUTDOOR AIR TEMPERATURE IS BELOW 45°F (ADJ.).

c. OUTDOOR AND RELIEF/EXHAUST AIR DAMPERS 100% CLOSED.

d. RETURN AIR DAMPER 100% OPENED.

B. WHEN INDEXED TO START:

a. ENABLE RETURN/RELIEF FAN(S) FIRST, THEN SUPPLY FAN(S).

b. OPERATION OF SYSTEM TO RESUME AFTER START-UP DELAY.

5. SUPPLY FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE SUPPLY FAN MOTOR(S)

VARIABLE FREQUENCY DRIVE(S), HEATING AND COOLING SOURCES AND MIXED AIR

DAMPERS TO MAINTAIN AN ADJUSTABLE SPACE TEMPERATURE SETPOINT MEASURED BY A

SPACE TEMPERATURE THERMOSTAT.

A. HEATING – UPON A FALL IN SPACE TEMPERATURE BELOW SPACE TEMPERATURE

SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:

a. MODULATE HEATING SOURCE (AS FIRST STAGE HEATING) TO MAINTAIN SPACE

TEMPERATURE SETPOINT.

• INCLUDE A MAXIMUM HEATING DISCHARGE TEMPERATURE OF 95°F (ADJ.).

• SUPPLY FAN(S) AT MINIMUM CFM/SPEED SETPOINT.

b. MODULATE SUPPLY FAN SPEED (AS SECOND STAGE HEATING) TO MAINTAIN ACTIVE

CFM/SPEED SETPOINT MEASURED BY A DUCT/FAN INLET AIR FLOW MEASURING

STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.

• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (80% OF DESIGN CFM) CFM

SETPOINTS (ADJ.).

c. UPON A CALL FOR ADDITIONAL HEAT BASED ON SUPPLY FAN(S) ARE DELIVERING

MAXIMUM CFM/SPEED (AS THIRD STAGE OF HEATING) OVERRIDE MAXIMUM

HEATING DISCHARGE TEMPERATURE.

• ALLOW HEATING CV TO MODULATE TO MAINTAIN SPACE TEMPERATE SETPOINT.

B. COOLING – UPON A RISE IN SPACE TEMPERATURE ABOVE SPACE TEMPERATURE

SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:

a. MODULATE SUPPLY FAN SPEED (AS FIRST STAGE COOLING) TO MAINTAIN ACTIVE

CFM/SPEED SETPOINT MEASURED BY DUCT/FAN INLET AIR FLOW MEASURING

STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.

• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (100% OF DESIGN CFM) CFM

SETPOINTS (ADJ.).

• ECONOMIZER SHALL BE UTILIZED (AS FIRST STAGE COOLING) IF APPLICABLE

AND NOT ALLOWING DISCHARGE AIR TEMPERATURE TO DROP BELOW 55°F,

THEN SUPPLY FAN.

b. IF ECONOMIZER IS ENABLED, DAMPERS SHALL BE 100% OPEN TO OUTDOORS.

6. RETURN/RELIEF FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE RETURN/RELIEF

FAN MOTOR(S) VARIABLE FREQUENCY DRIVE(S) TO MAINTAIN SPACE PRESSURE SETPOINT

MEASURED BY A SPACE PRESSURE CONTROLLER LOCATED IN SPACE SERVED.

A. THE SPACE STATIC PRESSURE SETPOINT (ADJ.) SHALL BE A SETPOINT THAT CONTROLS

TO A SLIGHTLY POSITIVE PRESSURE.

7. COIL PUMP CONTROL BASED ON THE FOLLOWING:

A. HEATING HOT WATER COIL PUMP SHALL RUN WHEN THE SYSTEM IS IN HEATING MODE

(WHEN CV IS GREATER THAN 10% OPEN).

B. PUMP(S) SHALL RUN CONTINUOUSLY WHENEVER THE OUTDOOR AIR TEMPERATURE IS

LESS THAN 40°F.

8. ECONOMIZER CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR DAMPERS TO

MEET UNIT DISCHARGE AIR TEMPERATURE SETPOINT WHEN OUTDOOR AIR ENTHALPY IS

BELOW THE RETURN AIR ENTHALPY BUT ABOVE ECONOMIZING SETPOINT.

A. WHEN BTU CALCULATION FOR OUTDOOR AIR CONDITIONS EXCEEDS 28 BTUH/LB

(ADJ.), ECONOMIZER SHALL BE DISABLED.

9. MINIMUM OUTDOOR AIR CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR

DAMPERS TO MAINTAIN MINIMUM CFM SETPOINT MEASURED BY AN OUTDOOR AIR FLOW

MEASURING STATION. LIMIT THE CLOSING OF THE OUTDOOR AIR DAMPER TO PROVIDE

ABSOLUTE MINIMUM OUTDOOR AIR FLOW.

A. OUTDOOR – RELIEF/EXHAUST – RETURN MODULATING WITH ONE SIGNAL FROM

CONTROLLER.

B. REFER TO UNIT SCHEDULE FOR THE ABSOLUTE MINIMUM OUTDOOR AIRFLOW CFM

SETPOINT.

10. FILTER MONITORING - SYSTEM CONTROLLER SHALL MONITOR AND ALARM FILTER

PRESSURE DIFFERENTIAL PRESSURE DROP(S) FOR THE FOLLOWING:

A. FINAL FILTERS

a. MONITORING OF PSID

b. ALARM SETPOINT 1.00” W.C. (ADJ.)

B. PRE-FILTERS

a. MONITORING OF PSID

b. ALARM SETPOINT 0.5”W.C. (ADJ.)

11. UNOCCUPIED CONTROL – SYSTEM CONTROLLER SHALL INITIATE THE FOLLOWING BASED

ON A FALL OR RISE IN SPACE TEMPERATURE:

A. HEATING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED HEATING

MODE) WHEN A CALL FOR HEAT IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)

DURING UNOCCUPIED MODE AND HEATING SYSTEM IS OR CAN BE ENABLED. SYSTEM

SHALL RESPOND BASED ON THE FOLLOWING:

a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE

CONTROL OPERATION TO PROVIDE HEATING TO ZONE WITH THE EXCEPTION TO THE

FOLLOWING:

• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%

OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.

• COOLING SHALL BE DISABLED.

b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR HEAT AND HEATING CV SHALL

REMAIN UNDER CONTROL OF MIXED/DISCHARGE AIR TEMPERATURE CONTROL.

B. COOLING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED COOLING

MODE) WHEN A CALL FOR COOL IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)

DURING UNOCCUPIED MODE AND COOLING SYSTEM IS OR CAN BE ENABLED.

a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE

CONTROL OPERATION TO PROVIDE COOLING TO THE ZONE WITH THE EXCEPTION

TO THE FOLLOWING:

• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%

OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.

• HEATING SHALL BE DISABLED.

• ECONOMIZER SHALL BE ENABLE IF SPACE TEMPERATURE IS GREATER THAN

OUTDOOR AIR TEMPERATURE BY 10°F (ADJ.).

b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR COOL.

12. INITIAL STARTUP CONTROL - SYSTEM CONTROLLER SHALL ENABLE UNIT PRIOR TO

SCHEDULED OCCUPANCY UTILIZING OPTIMUM START LOGIC TO ADJUST STARTUP TIME

FOR UNIT BASED ON OUTDOOR AIR TEMPERATURE, BUILDING TEMPERATURE AND

HISTORIC ELAPSE TIME TO REACH SETPOINT.

A. UNIT SHALL ENERGIZE AND PROVIDE HEATING AND COOLING BASED ON THE SPACE

TEMPERATURE SENSOR(S) TO BRING SPACE TO OCCUPIED SETPOINT. THE OUTDOOR

AND RELIEF/EXHAUST AIR DAMPERS SHALL BE CLOSED UNLESS ECONOMIZER IS

ENABLED. ONCE OCCUPIED SETPOINT HAS BEEN REACHED, THE UNIT SHALL SWITCH

TO OCCUPIED MODE.

13. CO2 CONTROL - SYSTEM CONTROLLER SHALL OVERRIDE MIXED AIR DAMPER CONTROLS

IN NON-ECONOMIZING MODE USING SPACE CO2 SENSOR TO INCREASE OUTDOOR

MINIMUM CFMTO A MAXIMUM CFM. INCLUDE CORRESPONDING CLOSING RETURN AIR

DAMPER AND OPENING OF RELIEF/EXHAUST AIR DAMPERS.

A. UPON RETURN SPACE C02 SENSOR EXCEEDING SETPOINT (800 PPM ADJ.), START TO

MODULATE MIXED AIR DAMPERS (OUTDOOR AIR DAMPER OPENING) IN GRADUAL

INCREMENTS UNTIL C02 SENSOR SETPOINT IS SATISFIED.

a. MODULATE MIXED AIR DAMPERS DOWN TO ITS ABSOLUTE MINIMUM POSITION

UPON SATISFYING SENSOR SETPOINT.

B. ALARM HIGH C02, 1,200 PPM (ADJ.)

C. REFER TO UNIT SCHEDULE FOR THE MAXIMUM OUTDOOR AIRFLOW CFM SETPOINT.

14. SAFETY SHUTDOWNS:

A. PROVIDE A LOW-TEMPERATURE PROTECTION THERMOSTAT(S) ON THE LEAVING SIDE OF

HEATING HOT WATER COIL WHICH WILL DE-ENERGIZE UNIT, CLOSE MIXED AIR DAMPERS

(CLOSING OUTDOOR/RELIEF/EXHAUST AIR DAMPER(S)) AND THE HEATING HOT WATER

COIL CONTROL VALVE SHALL BE FULLY OPENED AND COIL PUMP ENERGIZED. PROVIDE

MANUAL RESET.

B. PROVIDE A HIGH STATIC PRESSURE SENSOR IN THE SUPPLY DISCHARGE PLENUM TO

DE-ENERGIZE THE UNIT UPON SENSING A HIGH STATIC PRESSURE OF 4.0" W.C..

PROVIDE MANUAL RESET.

C. PROVIDE A LOW PRESSURE STATIC LIMIT IN THE RETURN PLENUM TO DE-ENERGIZE THE

UNIT UPON SENSING A HIGH NEGATIVE STATIC PRESSURE OF -4.0" W.C.. PROVIDE

MANUAL RESET.

D. DUCT MOUNTED IONIZATION SMOKE DETECTOR(S) PROVIDED BY DIVISION 28 SHALL

DE-ENERGIZE THE UNIT WHENEVER PRODUCTS OF COMBUSTION ARE SENSED.

ISSUED FOR DATE

HCV-1

HCV-1

M

T-1

TS

ZONE AIR CONDITIONS

HEATING COIL

FAN FAN

SF-1

SF-1

HCV-1

HCV-1

T-1

TS

ZONE AIR CONDITIONS

M

H E A

TI

N G

SA OUT

D-1

CP-1

T-3

H-2

HCV-1

HPSL-1 02

D-120

HCV-1

CP-1

LPSL-1

S U P P

LY

F A N 10

SF-1

SF-1

SF-1

SF-1

EA IN

T-5

H-3

E X H A U S T

F A N

EF-1

EF-1

EF-1

EF-1

FS-1

ERW

F

IL

TE

R S

E C

TI

O N

OA IN

D-4

D-4

EA OUT

D-3

D-3

D-2

D-2

EW-1

EW-1

EW-1

T-6

T-7

T-1

T-2

HS TS D

A M

P E R

M

D A M

P E R

M

TS TS

TSTS

P

D A M

P E R

M

VFD

EF-1

D A M

P E R

M

F

P

M

TSHS

VFD

SF-1

ERW

T-8

H-4

HS TS

OUTDOOR AIR CONDITIONS

T-9

H-5

HS TS

INDOOR AIR CONDITIONS

SP-3

PS

T-4

TS

REF (S)

REF (L)

TS

T-1

ZONE AIR

CONDITIONS

INDOOR UNIT

F

IL

E N

U M

B E

R

S T

A T

E I

N D

E X

N U

M B

E R

S

C o ns tr uc tio n

F in a l R e co rd

Is su e d f o r

P re lim in a ry

D a te

D E

S

IG

N A

N D

C O

N S

TR

U

C

TI

O N

D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T

A N

D B

U D

G E

T S

T A

T E

O F

M

IC

H

IG

A N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

E a s t

K a la m a z o o A v e n u e

S u it e

K a la m a z o o

M ic h ig

-5

.3

.6

P H

O

.3

.6

3F A

X

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

E a s t

F u lt o n S tr e e t, S u it e

G ra n d R a p id s

M ic h ig a n

.4

.9

P H

O N

E

.4

.5

6F

A X

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

T E

M P

E R

A T

U R

E C

O N

T R

O L S

-1

.0

M

J U

N E

M

ID

L A

N D

A R

M O

R Y

A D

D

IT

IO

N

A N

D R

E N

O V

A T

IO

N

A

IR

P

O R

T R

O A

D

M

ID

L A

N D

M

I

D E

P A

R T

M E

N T

O F

M

IL

IT

A

R Y

A N

D V

E T

E R

A N

'S A

F F

A

IR

S

/2

.C

A K

/1

/2

SCALE: NONE

FINNED TUBE RADIATION CONTROLS DIAGRAM

SCALE: NONE

CABINET UNIT HEATER CONTROLS DIAGRAM

CONTROL POINTS

NUMBER TAG DESCRIPTION ALARM TREND I/O REMARKS

CEILING CASSETTE AIR CONDITIONER

01 T-1 SPACE TEMPERATURE ■ ■ INPUT

ENERGY RECOVERY SYSTEM (ENTHALPY WHEEL DX)

01 D-1 OUTDOOR AIR DAMPER OUTPUT ■ OUTPUT

02 D-1 OUTDOOR AIR DAMPER POSITION ■ ■ INPUT

03 T-1 ERW ENTERING OUTDOOR AIR TEMPERATURE ■ INPUT

04 EW-1 ENTHALPY WHEEL SPEED CONTROL ■ OUTPUT

05 EW-1 ENTHALPY WHEEL RUN STATUS ■ ■ INPUT

06 EW-1 ENTHALPY WHEEL ENABLE/DISABLE ■ OUTPUT

07 D-2 OUTDOOR AIR BY-PASS DAMPER OUTPUT ■ OUTPUT

08 D-2 OUTDOOR AIR BY-PASS DAMPER POSITION ■ ■ INPUT

09 T-2 ERW LEAVING OUTDOOR AIR TEMPERATURE ■ INPUT

10 SF-1 SPEED CONTROL ■ OUTPUT

11 SF-1 FAN AIR FLOW ■ INPUT

12 SF-1 VFD FAULT STATUS ■ ■ INPUT

13 SF-1 ENABLE/DISABLE ■ OUTPUT

14 HPSL-1 HIGH PRESSURE STATIC LIMIT ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET

15 T-3 DISCHARGE AIR TEMPERATURE ■ ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS

16 H-2 DISCHARGE AIR HUMIDITY ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS

17 CP-1 STATUS ■ ■ INPUT

18 CP-1 ENABLE/DISABLE ■ OUTPUT

19 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT

20 HCV-1 HEATING CONTROL VALVE POSITION ■ ■ INPUT

21 FS-1 FREEZE STAT ALARM STATUS ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET

22 T-4 HEATING COIL DISCHARGE TEMPERATURE ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS

23 H-3 EXHAUST AIR HUMIDITY ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS

24 T-5 EXHAUST AIR TEMPERATURE ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS

25 T-6 ERW ENTERING EXHAUST AIR TEMPERATURE ■ INPUT

26 D-3 EXHAUST AIR BY-PASS DAMPER OUTPUT ■ OUTPUT

27 D-3 EXHAUST AIR BY-PASS DAMPER POSITION ■ ■ INPUT

28 T-7 ERW LEAVING EXHAUST AIR TEMPERATURE ■ INPUT

29 LPSL-1 LOW PRESSURE STATIC LIMIT ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET

30 EF-1 FAN AIR FLOW ■ INPUT

31 EF-1 SPEED CONTROL ■ OUTPUT

32 EF-1 VFD FAULT STATUS ■ ■ INPUT

33 EF-1 ENABLE/DISABLE ■ OUTPUT

34 D-4 EXHAUST AIR DAMPER POSITION ■ ■ INPUT

35 D-4 EXHAUST AIR DAMPER OUTPUT ■ OUTPUT

36 H-4 OUTDOOR AIR HUMIDITY ■ INPUT GLOBAL

37 T-8 OUTDOOR AIR TEMPERATURE ■ INPUT GLOBAL

38 SP-3 ROOM STATIC PRESSURE ■ INPUT

39 H-5 INDOOR AIR HUMIDITY SENSOR ■ INPUT

40 T-9 INDOOR AIR TEMPERATURE ■ INPUT

FINNED TUBE RADIATION

01 T-1 ZONE AIR TEMPERATURE ■ ■ INPUT

02 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT

03 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT

CABINET UNIT HEATER

01 T-1 ZONE AIR TEMPERATURE ■ ■ INPUT

02 SF-1 STATUS ■ ■ INPUT

03 SF-1 ENABLE/DISABLE ■ OUTPUT

04 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT

05 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT

SEQUENCE OF OPERATIONS

NOTE: ALL LABOR, MATERIAL, EQUIPMENT AND SOFTWARE NOT SPECIFICALLY INDICATED

WITHIN CONTROLS DRAWINGS THAT IS REQUIRED TO MEET THE FUNCTIONAL INTENT

OF THE SEQUENCE OF OPERATIONS SHALL BE PROVIDED WITHOUT ADDITIONAL

COST. POINT LISTS SHALL BE A GUIDE TO THE POINTS REQUIRED FOR CONTROL

SYSTEM. FINAL POINTS SHALL BE DETERMINED BY SEQUENCE OF OPERATIONS. ALL

SET POINTS SHALL BE OPERATOR ADJUSTABLE THROUGH THE BMS. ALL POINTS

SHALL BE TRENDABLE.

SEQUENCE OF OPERATIONS (CONT'D)

SCALE: NONE

ENERGY RECOVERY SYSTEM (ENTHALPY WHEEL) CONTROLS DIAGRAM

ENERGY RECOVERY UNIT (HRU-1) CONTROLS

1. PROVIDE DIRECT DIGITAL CONTROLS (DDC) FOR ENERGY RECOVERY UNIT OPERATION.

UNIT(S) ARE A COMBINATION OF AN OUTDOOR SINGLE ZONE CONSTANT VOLUME UNIT,

SUPPLY FAN(S), VARIABLE FREQUENCY CONTROLLER(S), HEATING HOT WATER COIL,

CONTROL VALVE (CV) AND ACTUATOR WITH CIRCULATING PUMP, ENERGY RECOVERY

WHEEL, MERV 11/13 FINAL/MERV 7/8 PRE-FILTERS, OUTDOOR – EXHAUST - BYPASS AIR

DAMPERS AND ACTUATOR(S), EXHAUST FAN(S), VARIABLE FREQUENCY CONTROLLER(S)

AND AIR TEMPERATURE/HUMIDITY SENSOR(S).

2. ENERGY RECOVERY UNIT ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:

A. TIME OF DAY (TOD) SCHEDULE.

a. TO BE DETERMINED BY OWNER (CONSULT WITH OWNER).

B. ENABLED AND DISABLED BASED ON MANUAL OVERRIDE FROM DDC.

3. ENERGY RECOVERY UNIT ADJUSTABLE SETPOINTS:

A. OCCUPIED 74°F COOLING / 70°F HEATING

B. UNOCCUPIED 85°F COOLING / 62°F HEATING

4. START/STOP, CONTROLLED DEVICES SHALL RESPOND AS FOLLOWS:

A. WHEN INDEXED TO STOP:

a. DISABLE SUPPLY AND EXHAUST FAN(S) SIMULTANEOUSLY.

b. HEATING CV SHALL MODULATE TO MAINTAIN HEATING COIL DISCHARGE AIR

TEMPERATURE SENSOR AT 80°F (ADJ.), WHEN OUTDOOR AIR TEMPERATURE IS

BELOW 45°F (ADJ.).

c. OUTDOOR AND EXHAUST AIR DAMPERS 100% CLOSED, ONCE SYSTEM FANS HAVE

BEEN DISABLED.

d. WHEEL BYPASS DAMPERS 100% OPENED.

B. WHEN INDEXED TO START:

a. OUTDOOR AND EXHAUST AIR DAMPERS 100% OPENED.

b. ENABLE SUPPLY AND EXHAUST FAN(S).

c. OPERATION OF SYSTEM TO RESUME AFTER START-UP DELAY.

5. EXHAUST FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE EXHAUST FAN

MOTOR(S) VARIABLE FREQUENCY CONTROLLER(S) TO MAINTAIN SPACE PRESSURE

SETPOINT MEASURED BY A SPACE PRESSURE CONTROLLER LOCATED IN SPACE SERVED.

A. THE SPACE STATIC PRESSURE SETPOINT (ADJ.) SHALL BE A SETPOINT THAT CONTROLS

TO A SLIGHTLY NEGATIVE PRESSURE.

6. FAN VARIABLE FREQUENCY CONTROLLER(S) SHALL BE MONITORED BASED ON THE

FOLLOWING:

a. VIA LONWORKS CONNECTION (POWER USAGE / SPEED % AND HZ / HOURS / FAULT /

ALARM)

7. FAN(S) INITIAL START-UP CONTROL – WHEN INDEXED TO START, SYSTEM CONTROLLER

SHALL ENABLE FAN(S) BASED ON THE FOLLOWING:

A. WHEN ENABLED, AND AFTER A DELAY OF TWO (2) MINUTES (ADJ.) WITH NO STATUS

SENSED, DDC SHALL INDICATE A CRITICAL ALARM.

a. IF ANY FAN (SUPPLY OR EXHAUST) STATUS IS NOT SENSED, THE SYSTEM SHALL BE

DISABLED.

B. WHEN ENABLED AND STATUS IS SENSED BY THE CURRENT SENSOR, A TOTALIZES OF

RUN HOURS FOR FAN WILL BE ACTIVE.

8. DISCHARGE AIR TEMPERATURE CONTROL - SYSTEM CONTROLLER SHALL MODULATE/CYCLE

HEATING SOURCES AND MIXED AIR DAMPERS TO MAINTAIN A FIXED DISCHARGE AIR

TEMPERATURE SETPOINT MEASURED BY A DUCT TEMPERATURE SENSOR LOCATED

DOWNSTREAM OF UNIT.

A. WHEN SYSTEM IS IN COOLING MODE DAT SHALL BE 55°F (ADJ.).

B. WHEN SYSTEM IS IN HEATING MODE DAT SHALL BE 95°F (ADJ.).

C. HEATING/COOLING MODE – WHEN OUTDOOR AIR TEMPERATURE IS GREATER OR LESS

THAN DISCHARGE AIR TEMPERATURE SETPOINT BY 3°F (ADJ.), THE FOLLOWING SHALL

BE INITIATED:

a. BYPASS DAMPERS 100% CLOSED.

b. ENABLE WHEEL AND MODULATE SPEED TO MAINTAIN ACTIVE DAT SETPOINT.

• IF WHEEL IS UNABLE TO MAINTAIN DAT SETPOINT, THE HEATING/COOLING CV

SHALL MODULATE TO MAINTAIN SETPOINT.

D. VENTILATION MODE – WHEN OUTDOOR AIR TEMPERATURE IS EQUAL TO DISCHARGE

AIR TEMPERATURE SETPOINT BY LESS THAN 3°F (ADJ.), THE FOLLOWING SHALL BE

INITIATED:

a. BYPASS DAMPERS 100% OPENED.

b. DISABLE WHEEL.

E. FROST MODE - WHEN OUTDOOR AIR TEMPERATURE IS BELOW THE FROST CONTROL

SETPOINT OF 32°F (ADJ.).

a. THE WHEEL OUTDOOR BYPASS DAMPER WILL MODULATE TO VARY THE

EFFECTIVENESS OF THE WHEEL TO PREVENT THE EXHAUST AIR FROM BEING

COOLED BELOW THE SATURATION POINT.

b. THE WHEEL SPEED WILL MODULATE TO VARY THE EFFECTIVENESS OF THE WHEEL

TO PREVENT THE EXHAUST AIR FROM BEING COOLED BELOW THE SATURATION

POINT.

9. COIL PUMP CONTROL BASED ON THE FOLLOWING:

A. HEATING HOT WATER COIL PUMP SHALL RUN WHEN THE SYSTEM IS IN HEATING MODE

(WHEN CV IS GREATER THAN 10% OPEN).

B. PUMP(S) SHALL RUN CONTINUOUSLY WHENEVER THE OUTDOOR AIR TEMPERATURE IS

LESS THAN 40°F.

10. FILTER MONITORING - SYSTEM CONTROLLER SHALL MONITOR AND ALARM FILTER

PRESSURE DIFFERENTIAL PRESSURE DROP(S) FOR THE FOLLOWING:

A. FINAL FILTERS

a. MONITORING OF PSID

b. ALARM SETPOINT 1.00” W.C. (ADJ.)

B. PRE-FILTERS (BOTH OUTDOOR AND EXHAUST)

a. MONITORING OF PSID

b. ALARM SETPOINT 0.5”W.C. (ADJ.)

11. UNOCCUPIED CONTROL – SYSTEM CONTROLLER SHALL INITIATE THE FOLLOWING BASED

ON A FALL OR RISE IN SPACE TEMPERATURE:

A. HEATING AND COOLING CONTROL WILL BE THE SAME AS OCCUPIED CONTROL.

12. INITIAL STARTUP CONTROL - SYSTEM CONTROLLER SHALL ENABLE UNIT PRIOR TO

SCHEDULED OCCUPANCY UTILIZING OPTIMUM START LOGIC TO ADJUST STARTUP TIME

FOR UNIT BASED ON OUTDOOR AIR TEMPERATURE, BUILDING TEMPERATURE AND

HISTORIC ELAPSE TIME TO REACH SETPOINT.

A. UNIT SHALL ENERGIZE AND PROVIDE HEATING AND COOLING BASED ON THE SPACE

TEMPERATURE SENSOR(S) TO BRING SPACE TO OCCUPIED SETPOINT. THE OUTDOOR

AND RELIEF/EXHAUST AIR DAMPERS SHALL BE CLOSED UNLESS ECONOMIZER IS

ENABLED. ONCE OCCUPIED SETPOINT HAS BEEN REACHED, THE UNIT SHALL SWITCH

TO OCCUPIED MODE.

13. SAFETY SHUTDOWNS:

A. PROVIDE A LOW-TEMPERATURE PROTECTION THERMOSTAT(S) ON THE LEAVING SIDE OF

HEATING HOT WATER COIL WHICH WILL DE-ENERGIZE UNIT, CLOSE MIXED AIR DAMPERS

(CLOSING OUTDOOR/RELIEF/EXHAUST AIR DAMPER(S)) AND THE HEATING HOT WATER

COIL CONTROL VALVE SHALL BE FULLY OPENED AND COIL PUMP ENERGIZED. PROVIDE

MANUAL RESET.

B. PROVIDE A HIGH STATIC PRESSURE SENSOR IN THE SUPPLY DISCHARGE PLENUM TO

DE-ENERGIZE THE UNIT UPON SENSING A HIGH STATIC PRESSURE OF 4.0" W.C..

PROVIDE MANUAL RESET.

C. PROVIDE A LOW PRESSURE STATIC LIMIT IN THE RETURN PLENUM TO DE-ENERGIZE THE

UNIT UPON SENSING A HIGH NEGATIVE STATIC PRESSURE OF -4.0" W.C.. PROVIDE

MANUAL RESET.

D. DUCT MOUNTED IONIZATION SMOKE DETECTOR(S) PROVIDED BY DIVISION 28 SHALL

DE-ENERGIZE THE UNIT WHENEVER PRODUCTS OF COMBUSTION ARE SENSED.

FINNED TUBE CONTROLS

1. PROVIDE DIRECT DIGITAL CONTROLS (DDC) FOR FINNED TUBE OPERATION. FINNED TUBE

IS A COMBINATION OF A HEATING ELEMENT, CONTROL VALVE (CV) AND ACTUATOR AND

AIR TEMPERATURE SENSOR.

2. FINNED TUBE ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:

A. SCHEDULED WITH ASSOCIATED ZONE HVAC SYSTEM.

3. FINNED TUBE ADJUSTABLE SETPOINTS:

A. OCCUPIED 68°F HEATING

B. UNOCCUPIED 60°F HEATING

4. OPERATION SHALL BE BASED ON THE FOLLOWING:

A. OPERATION BASED ON WALL MOUNTED THERMOSTAT THAT WILL ENABLE UNIT

WHENEVER SPACE TEMPERATURE FALLS BELOW HEATING SETPOINT.

5. ENABLED/DISABLED BASED ON THE FOLLOWING:

A. WHEN INDEXED DISABLED, CONTROLLED DEVICES SHALL RESPOND AS NOTED:

a. HEATING CV 100% CLOSED.

B. WHEN INDEXED TO ENABLED, CONTROLLED DEVICES SHALL RESPOND AS NOTED:

a. HEATING CV 100% OPENED.

6. MONITORING AND ALARMING OF THE FOLLOWING:

A. SPACE AIR TEMPERATURE.

CABINET UNIT HEATER CONTROLS

1. PROVIDE DIRECT DIGITAL CONTROLS (DDC) FOR CABINET HEATER OPERATION. CABINET

HEATER IS A COMBINATION OF A CONSTANT VOLUME FAN, FILTER, HEATING COIL,

CONTROL VALVE(CV) AND ACTUATOR, AND AIR TEMPERATURE SENSOR.

2. CABINET HEATER ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:

A. SCHEDULED WITH MAIN BUILDING SCHEDULE.

3. OPERATION SHALL BE BASED ON THE FOLLOWING:

A. OPERATION BASED ON UNIT MOUNTED RETURN AIR TEMPERATURE SENSOR THAT WILL

ENABLE UNIT WHENEVER RETURN AIR TEMPERATURE FALLS BELOW HEATING SETPOINT.

4. TEMPERATURE SETPOINT:

A. FOR CABINET HEATERS IN VESTIBULES, UNIT SHALL DE-ENERGIZE WHEN OUTDOOR AIR

TEMPERATURES ARE ABOVE 45°F. VESTIBULE CABINET HEATERS SHALL BE

CONTROLLED BY A ZONE THERMOSTAT TO A SETPOINT OF 60°F (MAX).

5. START/STOP BASED ON THE FOLLOWING:

A. WHEN INDEXED TO STOP, CONTROLLED DEVICES SHALL RESPOND AS NOTED:

a. DISABLE FAN.

b. HEATING CV 100% CLOSED.

B. WHEN INDEXED TO START, CONTROLLED DEVICES SHALL RESPOND AS NOTED:

a. HEATING CV 100% OPENED.

b. ENABLE FAN.

6. MONITORING AND ALARMING OF THE FOLLOWING:

A. FAN MOTOR STATUS.

a. WHEN ENABLED, AND AFTER A DELAY OF TWO (2) MINUTES (ADJ.) WITH NO STATUS

SENSED, THE DDC SHALL INDICATE A GENERAL ALARM.

b. WHEN ENABLED AND STATUS IS SENSED BY THE CURRENT SENSOR, A TOTALIZES

OF RUN HOURS FOR CABINET HEATER WILL BE ACTIVE.

B. SPACE AIR TEMPERATURE.

ISSUED FOR DATE

SCALE: NONE

MINI-SPLIT (CEILING CASSETTE) CONTROLS DIAGRAM

SPLIT SYSTEM CONTROLS (DX)

1. FACTORY CONTROLS.

2. SYSTEM START / STOP.

A. UNIT SUPPLY FAN AND MECHANICAL HEATING/COOLING SHALL CYCLE BASED ON SPACE

DEMAND.

3. DDC CONTROL SYSTEM SHALL MONITOR AND ALARM SPACE TEMPERATURE.

4. TEMPERATURE SETPOINT: CONTROLLED BY OCCUPANCY.

DDC-1

DIN RAIL RELAY SOCKET & RELAY

AS REQUIRED AND (1) SPARE

DIN RAIL TERMINAL BLOCKS AS

REQUIRED FOR ALL 24V POWER

AND COMMON & (4) SPARE

DIN RAIL CIRCUIT BREAKER FOR

EACH CONTROLLER

4x4x24" WIREWAY

AC/DC CONVERTER, ACDC-1

T-1

ENCLOSURE ENC-1

1.5X2.25 SLOTTED WIRE DUCT VERTICAL

1.0X1.5 SLOTTED WIRE DUCT HORIZONTAL

DIN RAIL TYP

NEW 3/4" EMT FOR CONTROL

WIRES AS REQUIRED

CIRCUIT FROM POWER PANEL

T-2 VAV

TRANSFORMER

T-2 VAV

TRANSFORMER DDC-1 DDC-1

GENERAL DDC NOTES:

DDC EQUIPMENT SCHEDULE

BASIS OF DESIGN SERVICE QTY / WIRE SIZE

TO EQUIPMENT

NOTES

ROOM TEMP

AIRSTREAM TEMP

OAT

DDC

DESCRIPTION

ROOM TEMPERATURE SENSOR

PROGRAMMABLE CONTROLLER

DUCT/EQUIP TEMPERATURE SENSOR

OUTDOOR AIR TEMP SENSOR

LOCATION

SEE LAYOUT, WALL MOUNTED 60" AFF

RETURN DUCT AFTER FRESH AIR

BLDG EXTERIOR

DDC ENCLOSURE

ENC-1CATNET - CLI-FTCATNET INTERFACE W/ LON CARD ONE PER BUILDING, ENC-1

KELE - RET2620 DDC EQUIPMENT ENCLOSUREDDC ENCLOSURE MECHANICAL ROOM -

BAPI - BA/10K-3-B4

BAPI - BA/10K-3-O-EU

3 CONDUCTOR / 18 GA.

WATER TEMPPIPE TEMPERATURE SENSOR SUPPLY DUCTBAPI - BA/10K3-S

3 CONDUCTOR / 18 GA.

4 CONDUCTOR / 18 GA.

NO SUBSTITUTIONS

(2) SINGLE POLE DOUBLE THROW 15A

CIRCRON - UHC 400

LABEL

TEMP-1-AREA

TEMP-2-AHU# or RTU#

OAT-1

DDC-1

CATNET

ENC-1

TEMP-3-AHU# or RTU#

MARK

TEMP-1

TEMP-2

OAT-1

DDC-1

DDC-2

ENC-1

TEMP-3

AIR PROD. & CONTROLS - T-PB-202-0TRANSFORMER w/ OUTLET DDC ENCLOSURE -T-1-ENC#T-1

NO SUBSTITUTIONS

CS-1 AHU/PUMPS/EXHAUST FANSACI - A/MSCSCURRENT SENSOR VARIES

RELAY VARIESRELAY-1 RIB - RIBU1C MECHANICAL EQUIP

2 CONDUCTOR / 18 GA.

CS-1-(DEVICE NAME)

(VARIES ON DEVICE)

DIN RAIL RELAY SOCKET MECH ROOMRELAY-2 VERIS - VBD1B-F MECHANICAL EQUIP

DIN RAIL RELAY SPDT MECH ROOMRELAY-3 VERIS - VMD1B-F24A MECHANICAL EQUIP

2 CONDUCTOR / 18 GA.

DIN RAIL DDC ENCLOSURE / RTUDIN RAIL KELI - BAM-1000 MECHANICAL EQUIP

SEE DETAILS FOR EXACT LOCATION

DDC ENCLOSURE EQUIPMENT

CIRCUIT BREAKER FOR CONTROLLERBRKR - CBI ELECTRIC - QL-2 DDC ENCLOSURE / RTU

BAPI - BA/10K-3-D-18"

WIRE DUCT - SLOTTED WIRE DUCT IBOCO - T1E-2222W MECHANICAL EQUIP DDC ENCLOSURE

SEE DETAILS FOR EXACT LOCATION

PROGRAMMABLE CONTROLLER

SEE DETAILS FOR EXACT LOCATION2 CONDUCTOR / 18 GA.

SINGLE POLE DOUBLE THROW 2A

18 INCHES, TEMP. AVERAGING

3 CONDUCTOR / 18 GA.

SD-1 AHU/RTUAIR PRODUCTS & CONTROLS - SL-2000-PSMOKE DETECTOR RETURN DUCT BEFORE FRESH AIR

3 CONDUCTOR / 18 GA.

SD-1

TERMINAL BLOCK DDC ENCLOSURE / RTUTBLCK KELE - CDU4N MECHANICAL EQUIP

CO2-1 CO2VERIS - CDEDUCT CO2 SENSOR RETURN DUCT

3 CONDUCTOR / 18 GA.

CO2-1-AHU#

2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR

OR APPROVED EQUAL

RELAY VARIESRELAY-4 RIB - RIB2421SB AHU/RTU FANS & ALL PUMPS

2 CONDUCTOR / 18 GA.

(VARIES ON DEVICE)

SINGLE POLE DOUBLE THROW 2A

ENC-1CATNET - HMI CH-2CATNET WEBSERVER -WEBSERVERDDC-3 NO SUBSTITUTIONS

ENC-1CATNET - CMI-485INTERFACE MODBUS DDC ENCLOSURE -MODBUSDDC-4 NO SUBSTITUTIONS

ONE PER BUILDING, ENC-1

OCC-1 ROOM OCCUPANCYWATTSTOPPER - CX100OCCUPANY SENSOR SEE LAYOUT, WALL MOUNTED 6" FROM CEILINGOCC-1-RM#

ACDC-1 ACDC-1 AC TO DC VOLTAGE CONVERTER ACI - PS1.5 OCCUPANCY SENSORS DDC ENCLOSURE

2 CONDUCTOR / 18 GA., 2 CONDUCTOR / 18 GA. PWR

KELE - RET2620 DDC EQUIPMENT ENCLOSUREDDC ENCLOSURE MECHANICAL ROOM - NO SUBSTITUTIONSENC-2ENC-2

ACT-1 DAMPERSKMC CONTROLS - MEP-7552DAMPER ACTUATOR VARIESACT-1-(DEVICE NAME) 2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR

ACT-2 CONTROL VALVESKMC CONTROLS - MEP-4252V½" & ¾" VALVE ACTUATOR VARIESACT-2-(DEVICE NAME) 2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR

KELE - RET2620 DDC EQUIPMENT ENCLOSUREDDC ENCLOSURE MECHANICAL ROOM - NO SUBSTITUTIONSENC-3ENC-3

MECH EQUIPMENTFREEZESTAT COOLING COILACI - FS-4FR-1-AHU# or RTU#FR-1 3 CONDUCTOR / 18 GA.

ACT-3 CONTROL VALVESKMC CONTROLS - MEP-4552V1" - 3" VALVE ACTUATOR VARIESACT-3-(DEVICE NAME) 2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR

RIB - PSH200A-LVCTRANSFORMER DDC ENCLOSURE -T-2-ENC#T-2 VAV CONTROLLERS

CIRCON - VAV-332-IMVTERMINAL UNIT CONTROLLER SEE MECHANICAL SHEETS 2 CONDUCTOR / 18 GA. PWRVAV-#-LOCATIONVAV-1-20 HVAC EQUIP NO SUBSTITUTIONS, POWER WIRE FROM T-2

ACI - A/LP2-3-10DUCT PRESSURE SENSOR MAIN SUPPLY DUCT 4 CONDUCTOR / 18 GA. SHIELDDP-1DP-1 MECHANICAL EQUIP

NOTES:

1. CONTRACTOR TO FURNISH AND INSTALL MATERIALS IN SCHEDULE. WIRE SHOWN TO BE PULLED INTO ENCLOSURES, LABELED AND COILED AT EACH END.

2. SUBSTITUTIONS SHALL BE REVIEWED AND APPROVED BY DMVA ENGINEERING PRIOR TO INSTALLATION.

3. ACTUATOR ACT-1 MODEL NUMBER DEPENDS ON DEVICE SIZE. INSTALL PROPERLY SIZED TORQUE ACTUATOR BASED ON MANUFACTURER'S RECOMMENDATIONS.

1. PRIOR TO ANY INSTALLATION OF DDC EQUIPMENT OR DDC WIRING, CONTRACTOR SHALL REQUEST A DDC PRECONSTRUCTION MEETING WITH DMVA

IN-HOUSE TECHNICIAN TO DISCUSS CONSTRUCTION SCHEDULING, PRECISE DDC EQUIPMENT LOCATIONS, STARTUPS, LABELING PROCEDURES, AND

COMMISSIONING.

2. CONTRACTOR MUST FOLLOW A DDC WIRE COLOR SCHEDULE FOR ALL DDC WIRING INSTALLED. THIS SCHEDULE WILL BE AGREED UPON DURING THE

PRECONSTRUCTION MEETING.

A. WIRE COLOR FOR ALL CONTROL WIRING IS TO BE WHITE.

3. CONTRACTOR TO INSTALL A MINIMUM ¾" CONDUIT FOR ALL DDC WIRING. CONTRACTOR IS ALLOWED TO INSTALL J-HOOKS 4' O.C. FOR DDC

CONTROL WIRING ONLY IN AREAS ABOVE A SUSPENDED CEILING. ALL CONDUIT IN WALLS TO BE STUBBED INTO CEILING SPACE.

A. ALL EXPOSED WIRE IS TO BE IN CONDUIT

B. HIDDEN WIRE CAN BE RUN IN BRIDAL RINGS

4. CONTRACTOR SHALL PULL ALL DDC WIRING AS SHOWN ON DDC FLOOR PLAN AND DDC EQUIPMENT SCHEDULE. ALL WIRES SHALL BE LABELED WITH A

LABEL MAKER APPROVED BY DMVA ENGINEERING. NO HAND WRITTEN LABELS WILL BE ALLOWED. ALL LABELS LOCATED IN ENCLOSURE ENC-1 MUST

BE PLACED 6" DOWN ON WIRE ONCE INSIDE THE ENCLOSURE, DO NOT LOCATE LABEL AT THE END OF WIRE.

5. ALL INPUT/OUTPUT CONTROL WIRES TO BE LON RATED, SEE SPECIFICATIONS.

6. DDC SEQUENCE AND PROGRAMMING WILL BE COMPLETED BY CONTROLS CONTRACTOR.

7. INSTALL TEMPERATURE SENSORS, TEMP-1, 60" AFF.

8. INSTALL OCCUPANCY SENSORS, OCC-1, 6" FROM CEILING.

9. INSTALL OAT-1 ON NORTH FACING EXTERIOR WALL OUT OF DIRECT SUNLIGHT AND CLEAR OF ANY LOUVERS, DOORS OR OPERABLE WINDOWS; MAKE

WEATHERTIGHT.

10. PRINT COPY OF DDC WIRE COLOR SCHEDULE AND SCHEMATIC AND SECURE TO THE BACK OF THE DOOR IN ENC-1.

11. PROVIDE AND INSTALL ALL END DEVICES SHOWN.

12. CONTROL WIRING TO BE TERMINATED AT END DEVICES AND BROUGHT INTO CONTROL PANEL, TEMERANTED AND LABLED.

F

IL

E N

U M

B E

R

S T

A T

E I

N D

E X

N U

M B

E R

S

C o ns tr uc tio n

F in a l R e co rd

Is su e d f o r

P re lim in a ry

D a te

D E

S

IG

N A

N D

C O

N S

TR

U

C

TI

O N

D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T

A N

D B

U D

G E

T S

T A

T E

O F

M

IC

H

IG

A N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

E a s t

K a la m a z o o A v e n u e

S u it e

K a la m a z o o

M ic h ig

-5

.3

.6

P H

O

.3

.6

3F A

X

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

E a s t

F u lt o n S tr e e t, S u it e

G ra n d R a p id s

M ic h ig a n

.4

.9

P H

O N

E

.4

.5

6F

A X

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

T E

M P

E R

A T

U R

E C

O N

T R

O L S

D E

T A

IL

S

A N

D S

C H

E D

U L E

S

-1

.0

M

J U

N E

M

ID

L A

N D

A R

M O

R Y

A D

D

IT

IO

N

A N

D R

E N

O V

A T

IO

N

A

IR

P

O R

T R

O A

D

M

ID

L A

N D

M

I

D E

P A

R T

M E

N T

O F

M

IL

IT

A

R Y

A N

D V

E T

E R

A N

'S A

F F

A

IR

S

/2

.C

A K

/1

/2

ISSUED FOR DATE

SCALE: NONE

DDC PANEL DETAIL

EXISTING TEMPERAURE CONTROL PANEL (FOR REFERENCE ONLY)

PC

WF

OSS

S 33S

TCP

FIRE ALARM SYMBOLS

NOTES:

RECEPTACLE SYMBOLS

DH

FS

SD

SD

HD

DD

F

V

BD

V

F

F

RT

SPD

OSY

P

J

LC

T

R

C

G

M

S F

SLV-a

SP

SD

3KS

S

SK

S

S

SS

4KS

MAGNETIC DOOR HOLDER

FIRE ALARM SMOKE DETECTOR - DUCT TYPE

FIRE ALARM SMOKE DETECTOR - CEILING TYPE

FIRE ALARM HEAT DETECTOR - CEILING TYPE

FIRE ALARM DUCT DETECTOR REMOTE TEST STATION

FIRE ALARM MANUAL PULL STATION

SPRINKLER VALVE MONITOR SWITCH

SPRINKLER SYSTEM FLOW SWITCH

FIRE ALARM ANNUNCIATOR PANEL REMOTE - FLUSH MTD.

FIRE ALARM - VISUAL ALARM, CANDELA INDICATED

FIRE ALARM CONTROL PANEL - FLUSH MTD.

FIRE ALARM AUDIO/VISUAL ALARM, WALL MTD., CANDELA INDICATED

FIRE ALARM - BELL

FACP

FIRE SHUTTER

SMOKE/FIRE DAMPER, PROVIDE WITH DUCT DETECTOR AND 120V POWER

SURGE PROTECTION DEVICE

MOTOR - HP AS INDICATED

BUSSMANN "SSU" W/FUSES

COMBINATION DISCONNECT/MAGNETIC MOTOR STARTER

DISCONNECT SWITCH - UNFUSED

DISTRIBUTION PANELBOARD

MOTOR CONTROL CENTER

PANELBOARD

SWITCH

FUSE

POWER FACTOR CORRECTION CAPACITOR

CIRCUIT BREAKER

60" TO TOP

72" TO TOP

72" TO TOP

90" TO TOP

72" TO TOP

PULL BOX - SIZE AND TYPE AS REQUIRED

JUNCTION BOX - SIZE AND TYPE AS REQUIRED

80"

80"

40"

60"

MOUNT DEVICES AT HEIGHTS INDICATED UNLESS INDICATED

OTHERWISE ON PLANS. HEIGHTS ARE TO BOTTOM OF DEVICE.

RELAY

CONTACTS - NORMALLY CLOSED

CONTACTS - NORMALLY OPEN

TRANSFORMER

LIGHTING CONTACTOR

PUSH-BUTTON STATION - 2 HOLE

PUSH-BUTTON STATION - 1 HOLE

EMERGENCY MUSHROOM HEAD PUSH-BUTTON STATION - 1 HOLE

SYSTEM GROUND - REFER TO SPECIFICATIONS

40"

40"

40"

COIL

CURRENT TRANSFORMER

THERMAL OVERLOADS

INDICATOR LIGHT (R=RED, G=GREEN, B=BLUE, Y=YELLOW, A=AMBER)

DUPLEX RECEPTACLE - WITH GFI

DOUBLE DUPLEX RECEPTACLE

DUPLEX RECEPTACLE - WET LOCATION ENCLOSURE WITH GFI

DUPLEX RECEPTACLE - FOR ELECTRIC WATER COOLER, WITH GFI

WP

GFI

24"

HAND/HAIR DRYER

DUPLEX RECEPTACLE

HD

16"

DUPLEX RECEPTACLE - EMERGENCY

SPECIAL PURPOSE RECEPTACLE

MANUAL MOTOR STARTER WITH PILOT LIGHT 40"

LOW VOLTAGE CONTROL SWITCH, REFER TO DETAIL

SWITCH AND PILOT LIGHT

DIMMER SWITCH (NON-SYSTEM TYPE) 0-10 ELV DIMMER

THREE-WAY SWITCH

SINGLE POLE SWITCH

FOUR-WAY SWITCH

KEY OPERATED, SINGLE POLE SWITCH

KEY OPERATED, THREE-WAY SWITCH

40"

EXIT SIGN - CEILING MOUNTED

EXTERIOR POLE LIGHT

PHOTOCONTROL

OCCUPANCY SENSOR (SET TO VACANCY MODE) - SWITCH MOUNTED

EWC

TRANSFORMER

DUAL SINGLE POLE SWITCH

CIRCUIT BREAKER - ELECTRONIC TRIPET

CEILING FAN

CEILING FAN SPEED CONTROL 40"

OS

OS

OCCUPANCY SENSOR (SET TO VACANCY MODE) CEILING MOUNTED

OCCUPANCY SENSOR (SET TO VACANCY MODE) - WALL MOUNTED

FIRE ALARM - VISUAL ALARM, CEILING MTD., CANDELA INDICATED

FIRE ALARM AUDIO/VISUAL ALARM, CEILING MTD., CANDELA INDICATED

DUPLEX RECEPTACLE - 4" ABOVE COUNTER BACKSPLASH

FLOOR DUPLEX RECEPTACLE

HUBBELL #BA253641, w/ #SFA3925 COVER

STROBE PANELNAC 72" TO TOP

FAA

DISCONNECT SWITCH - FUSED

PUSH-BUTTON STATION - 3 HOLE 40"

DUAL THREE-WAY SWITCH

KEY OPERATED, FOUR-WAY SWITCH

M ELECTRIC METER

EXIT SIGN - WALL MOUNTED

16"

BEAM DETECTOR

TEMPERATURE CONTROL PANEL 72" TO TOP

VARIABLE FREQUENCY DRIVEVFD

S FIRE ALARM SPEAKER

40"

40"

40"

40"

40"

40"

40"

40"

40"

40"

40"

88"

LOCAL, NON-SYSTEM 0-10V DIMMING CONTROLLER, SEE DETAILD A 40"

GFI GFCI REMOTE TRIP DEVICE, CONNECT NEARBY OUTLET TO LOAD SIDE 40"

DUPLEX RECEPTACLE - SURFACE MOUNTED #WM500

RECEPTACLES VARIATIONS - HEIGHT PER ABOVE UNLESS INDICATED ON DRAWINGS:

RECTANGULAR LIGHT FIXTURE

RECTANGULAR EMERGENCY LIGHT FIXTURE ON EMERGENCY

POWER, SWITCHABLE

DOWNLIGHT WALL WASH FIXTURE

WALL MTD. LIGHT FIXTURE

DOWNLIGHT FIXTURE

INDUSTRIAL LIGHT FIXTURE

DOWNLIGHT FIXTURE - EMERGENCY, SWITCHABLE

ELECTRICAL…