Drawings_2023 06 30 21085_Part4.pdf
PDF 3 MB Posted
- Attached to
- 511/21085. MAA; Midland Armory Construction
- Solicitation number
- RFQ - 171 - 230000000626
- Issued by
- Lenawee County, Michigan
About this file
This document appears to be related to a state and local contract opportunity for the construction of the Midland Armory Addition and Renovation project located in Midland, Michigan. The project is being managed by the Department of Military and Veteran's Affairs (DMVA) in the State of Michigan. The project includes the construction of a new addition and renovation to the existing Midland Armory building. The bid attachments and drawings include details on the mechanical, electrical, and plumbing systems, as well as architectural plans. Bidders must submit their proposals electronically via the SIGMA VSS system by the deadline of 2:00 pm on the specified date. Bidders are advised not to submit questions online, but rather to email them directly to the project manager. The contract will be awarded by DMVA, but the specific award date is not provided.
In terms of pricing and funding, the solicitation does not provide specific budget information. However, it indicates that the project is being funded by the State of Michigan. The solicitation does not mention any set-aside requirements or incumbents. Bidders should review the complete bid documents carefully for all terms and conditions related to pricing, payment, and other key contract requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VOLUME CONTROL
DAMPER
45° TAKEOFF COLLAR
WITHOUT DAMPER
RECTANGULAR LOW
PRESSURE DUCT
ROUND LOW
PRESSURE DUCT
RETURN AIR PLENUM
W/ 1" DUCT LINER
BIRD SCREEN
DUCT TO RTU
M
IN
ROOFING
ROOF CURB
ROOF INSULATION
ROOF STRUCTURE
MIN.
W/2
WIDTH = W
PLENUM EQUAL TO GRILLE
NECK SIZE. HEIGTH TO VARY
PER INSTALLATION
REQUIREMENTS.
RA/EA DUCT. REFER TO PLAN
FOR SIZE/SHAPE.
PAINT INSIDE OF
PLENUM FLAT BLACK
MANUAL BALANCE DAMPER
WITH BRIGHTLY PAINTED
EXTENDED STAND-OFF.
CEILING, LAY-IN OR HARD.
RA / EA GRILLE
NOTES:
REFER TO PLANS & SCHEDULE FOR DIFFUSERS
H (NOTE 1)
A
FRAME LENGTH
F R A M
E
W
ID
TH
H (N
OTE
1)
A
60° B
ARREL
ROTA
TIO
N
DIMENSION "H" EQUALS HEIGHT OF DAMPER BLADE
PLUS 2" (MIN.) TO ALLOW FOR INSTALLATION OF
DAMPER WITHOUT DAMPER BLADE PROTRUDING INTO
STREAM OF BRANCH MAIN DUCT.
SEAL (SUITABLE FOR PAINTING) ALL SEAMS AND
JOINTS AIR TIGHT (TYP.)
2.
1.
PAINT TO MATCH SUPPLY DUCTWORK
RECTANGULAR S.A. BOX WITH
END FACE FOR MOUNTING
FRAME OF S.A. GRILLE.
ROUND/OVAL S.A. DUCT
SEE PLANS FOR SIZE
NOTE 2
(TYP)
NOTES:
1"
SEE NOTE 3
GALV. HANGER
1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACE BY ANGLE. FOR CROSS SECTION AREA MORE
THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.
2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.
3. SUPPORTS SHALL BE SPACED AND SIZED PER SMACNA.
THREADED
HANGER ROD
HANGER
STRAP
UNISTRUT OR
ANGLE IRON
MAX. 60"
OVER 60"
SUPPLY DUCTWORK DUCT INSULATION,
REFER TO SPECIFICATIONS
SUPPLY DUCT BOOT
TEE W/ END CAP
MAXIMUM OF 3 FEET
OF INSULATED FLEX
DUCT
SUPPLY AIR DIFFUSER,
REFER TO SCHEDULE
MANUAL BALANCE DAMPER
WITH QUAD. LOCK
ROUND DIFFUSER THROAT
VERIFY CEILING TYPE WITH
ARCH CEILING PLANS
RETURN/EXHAUST AIR
SUPPLY AIR
VD
MAIN DUCT
BRANCH DUCT
TAPERED CONNECTION 45° ANGLE (IF MAIN DUCT
IS RECTANGULAR) OR CONICAL CONNECTION (IF
MAIN DUCT IS ROUND) L=1/4 W; 4" MIN
W
L
HS
HR
CIRCULATING PUMP
STRAINER
SHUT-OFF VALVE (TYP.)
CHECK VALVE
BALANCING VALVE
3-WAY CONTROL
VALVE
3'-0" MIN.
FOR 2" PIPE
AND SMALLER
5'-0" MIN.
FOR 2 1/2" PIPE
AND LARGER
HS
C.P.
PRESSURE
GAUGE (TYP.)
N.O.
C.
N.C.
UNIONS OR FLANGES (TYP.)
OFFSET PIPING TO ALLOW
FOR EASY COIL REMOVAL
HOSE BIBB DRAIN
HEATING COIL
THERMOMETER (TYP.)
BALL VALVE AIR VENT OFF
OF COIL. TERMINATE OUTSIDE
AHU WITH 3/4" HOSE
THREAD (TYP.)
CALIBRATED BALANCING VALVE
W/ SHUT-OFF VALVE
FROM
MAIN
HR
REDUCER IF REQUIRED
ECCENTRIC TYPE W/ LEVEL
SIDE UP. TYPICAL FOR ALL
HYDRONIC HORIZONTAL
REDUCERS.
MANUAL AIR VENTS @
HIGH POINTS (TYP.)
UNION
CONTROL VALVE
FIN ENCLOSURE
DRAIN
MANUAL AIR
TOP FED CONFIGURATION
SHUT-OFF VALVE
HR
H S
H R
HS
H R
HR
SHUT-OFF VALVE
REDUCER IF REQUIRED ECCENTRIC
TYPE W/ LEVEL SIDE UP. TYPICAL ALL
HYDRONIC HORIZONTAL REDUCERS
OPTIONAL RETURN IN
ENCLOSURE CONFIGURATION.
PROVIDE ENCLOSURE WITH
SUFFICIENT HEIGHT
OPTIONAL
BOTTOM FED
CONFIGURATION
CALIBRATED
BALANCING
VALVE
OPTIONAL
BOTTOM FED
CONFIGURATION
MANUAL
AIR VENT
PRESSURE GAGE
INLINE
PUMP
ECCENTRIC REDUCER
W/ LEVEL SIDE UP
CHECK VALVE
BALL VALVE
FLANGED CONNECTION
BALL VALVE
BALL VALVE
STRAINER
C D
ACCU-210
SS-210
ACCU-210
FC-210
"AIREDALE" MODEL CSD18, 1.5 TON COOLING
CAP., 208/1/60. 18,900 BTU/HR. COOLING CAP.,
3.0KW ELECTRIC HEATING CAP.,540 CFM, 40 CFM
(OA),120 WATT FAN
OPTIONS: KNOCKOUTS FOR BRANCH SUPPLY AIR
AND OUTDOOR AIR DUCTWORK.
CONTROLS: PROVIDE CAREL CONTROLLER WITH
BACNET CARD FOR BAS INTERFACE. CAREL WALL
SENSOR.
CONDENSATE LIFT PUMP, BASED ON
"LITTLE GIANT" VCC-20ULS. 25 GPH AT 15'
TDH 115/1/60, 1.5 A
ROOF
SPILL CONDENSATE ON
ROOF
SWEAT CONNECTIONS
PIPING PORTAL,
REFER TO DETAIL
CONDENSATE PIPING TO ROOF
COND. & DX REFRIGERANT PIPING
TO ROOF
REDUCER IF REQUIRED
ECCENTRIC TYPE W/ LEVEL
SIDE UP. TYPICAL FOR ALL HYDRONIC
HORIZONTAL REDUCERS
UNION
CALIBRATED
BALANCING VALVE
MANUAL AIR VENT (TYP.)
HR
HS
DRAIN
SHUT-OFF VALVE (TYP.)
CONTROL VALVE
AI
R
FL
O W
INLET STRAINER
BUTT ENDS
& SEAL
FOR HANGING DUCT:
TRAPEZE DUCT OR
STRAP HANGER AROUND
DUCT COMPLETELY. DO
NOT USE ANY SCREWS,
BECAUSE THEY
INTERFERE WITH DAMPER
BLADE(S)
PROVIDE EXTRA LENGTH
TO AVOID "PINCHING"
OF INSULATION AT
CORNERS
PROVIDE LOCKING
QUADRANT ARM
STANDOFF
F
IL
E N
U M
B E
R
S T
A T
E I
N D
E X
N U
M B
E R
S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
TR
U
C
TI
O N
D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T
A N
D B
U D
G E
T S
T A
T E
O F
M
IC
H
IG
A N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig a n
-5
.3
.6
P H
O N
E
.3
.6
3F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O N
E
.4
.5
6F
A X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
M E
C H
A N
IC
A
L S
C H
E D
U L E
S A
N D
D E
T A
IL
S
-1
.0
M
J U
N E
M
ID
L A
N D
A R
M O
R Y
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
A
IR
P
O R
T R
O A
D
M
ID
L A
N D
M
I
D E
P A
R T
M E
N T
O F
M
IL
IT
A
R Y
A N
D V
E T
E R
A N
'S A
F F
A
IR
S
/2
.C
A K
/1
/2
SCALE: NONE
TAKEOFF DETAIL - RECTANGULAR TO ROUND
SCALE: NONE
RTU RETURN AIR PLENUM DETAIL
SCALE: NONE
RETURN / EXHAUST AIR GRILLE PLENUM DETAIL
SCALE: NONE
DUCT MOUNTED DIFFUSER DETAIL
SCALE: NONE
DUCT HANGER SUPPORT DETAIL
SCALE: NONE
CEILING MOUNTED SUPPLY DIFFUSER DETAIL - TYPICAL
SCALE: NONE
BRANCH TAKE OFFS DETAIL
SCALE: NONE
AHU HEATING COIL PIPING DETAIL - SINGLE COIL 3-WAY VALVE
SCALE: NONE
FIN RADIATION PIPING DETAIL - SINGLE ROW
SCALE: NONE
PUMP - INLINE PIPING DETAIL
SCALE: NONE
SPLIT SYSTEM UNIT PIPING DETAIL
SCALE: NONE
CABINET HEATER PIPING DETAIL
ISSUED FOR DATE
SCALE: NONE
VOLUME DAMPER SUPPORT DETAIL
"YORK" MODEL CSD18, 1.5 TON COOLING CAPACITY,
208/1/60. PROVIDE WITH WINTER START KIT, LOW
AMBIENT CONTROLLER, AND CRANKCASE HEATER
RA IN
AFM-1
T-1
D-1
H-1
T-3
H-2
HPSL-1
EF-1
EF-1
EF-1
P R E F
IL
TE
R S
E C
TI
O N
SF-1
SF-1
SF-1
TS
S U P P
LY
F A N
HS
TS
E X H A U S T
F A N
T-4
H-3
HS TS
OUTDOOR AIR CONDITIONS
T-5
H-4
HS TS
INDOOR AIR CONDITIONS
SP-3
PS
AS
SA OUT
P
M
IX
ED
A
IR
D
AM
PE
R
SE
CT
IO
N OA IN
EA OUT
M
VFD
SF-1
VFD
EF-1
DX-1
DX-1
DX-1
PACKAGED DX
SYSTEM
DX-1
D X C
O
IL
S E C T
IO
N
T-2
TS
D-1
HS
LPSL-1
P
F
IN
A L
F
IL
T E R S
E C
TI
O N
CP-1
HCV-1
HCV-1
CP-1
M
SF-1
HEATING
F 31
FS-132
T-6
TS
CO2-1
CO2
RA IN
AFM-1
T-1
D-1
H-1
T-3
H-2
HPSL-1
EF-1
EF-1
EF-1
P R E F
IL
TE
R S
E C
TI
O N
SF-1
SF-1
SF-1
TS
S U P P
LY
F A N
HS
TS
E X H A U S T
F A N
T-4
H-3
HS TS
OUTDOOR AIR CONDITIONS
T-5
H-4
HS TS
INDOOR AIR CONDITIONS
SP-3
PS
AS
SA OUT
P
M
IX
ED
A
IR
D
AM
PE
R
SE
CT
IO
N OA IN
EA OUT
M
VFD
SF-1
VFD
EF-1
T-2
TS
D-1
HS
LPSL-1
P
F
IN
A L
F
IL
T E R S
E C
TI
O N
CP-1
HCV-1
HCV-1
CP-1
SF-1
M
HEATING
F
T-6
TS
FS-1
CO2-1
CO2
F
IL
E N
U M
B E
R
S T
A T
E I
N D
E X
N U
M B
E R
S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
TR
U
C
TI
O N
D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T
A N
D B
U D
G E
T S
T A
T E
O F
M
IC
H
IG
A N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
3F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O N
E
.4
.5
6F
A X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T E
M P
E R
A T
U R
E C
O N
T R
O L S
-1
.0
M
J U
N E
M
ID
L A
N D
A R
M O
R Y
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
A
IR
P
O R
T R
O A
D
M
ID
L A
N D
M
I
D E
P A
R T
M E
N T
O F
M
IL
IT
A
R Y
A N
D V
E T
E R
A N
'S A
F F
A
IR
S
/2
.C
A K
/1
/2
SEQUENCE OF OPERATIONS
NOTE: ALL LABOR, MATERIAL, EQUIPMENT AND SOFTWARE NOT SPECIFICALLY INDICATED
WITHIN CONTROLS DRAWINGS THAT IS REQUIRED TO MEET THE FUNCTIONAL INTENT
OF THE SEQUENCE OF OPERATIONS SHALL BE PROVIDED WITHOUT ADDITIONAL
COST. POINT LISTS SHALL BE A GUIDE TO THE POINTS REQUIRED FOR CONTROL
SYSTEM. FINAL POINTS SHALL BE DETERMINED BY SEQUENCE OF OPERATIONS. ALL
SET POINTS SHALL BE OPERATOR ADJUSTABLE THROUGH THE BMS. ALL POINTS
SHALL BE TRENDABLE.
ROOFTOP UNIT (RTU-1, RTU-4, RTU-5) CONTROLS
1. PROVIDE DIRECT DIGITAL CONTROLS FOR ROOFTOP SYSTEM OPERATION. UNIT(S) ARE A
COMBINATION OF AN OUTDOOR SINGLE ZONE VARIABLE VOLUME UNIT, SUPPLY FAN(S),
VARIABLE FREQUENCY CONTROLLER(S), PACKAGED DX SYSTEM, DIRECT EXPANSION COIL,
DUCT-MOUNTED HEATING HOT WATER COIL, CONTROL VALVE (CV) AND ACTUATOR WITH
CIRCULATING PUMP, MERV 13 FINAL & MERV 8 PRE-FILTERS, OUTDOOR –
RELIEF/EXHAUST - RETURN AIR DAMPERS AND ACTUATOR(S), RELIEF FAN(S), VARIABLE
FREQUENCY CONTROLLER(S) AND AIR TEMPERATURE/AIRFLOW/HUMIDITY SENSOR(S).
2. ROOFTOP UNIT ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:
A. TIME OF DAY (TOD) SCHEDULE.
a. TO BE DETERMINED BY OWNER (CONSULT WITH OWNER).
B. ENABLED AND DISABLED BASED ON MANUAL OVERRIDE FROM DDC.
3. ROOFTOP UNIT ADJUSTABLE SETPOINTS:
A. OCCUPIED 74°F COOLING / 70°F HEATING
B. UNOCCUPIED 85°F COOLING / 62°F HEATING
4. START/STOP, CONTROLLED DEVICES SHALL RESPOND AS FOLLOWS:
A. WHEN INDEXED TO STOP:
a. DISABLE SUPPLY AND RETURN/RELIEF FAN(S) SIMULTANEOUSLY.
b. DISABLE DX COOLING.
c. HEATING CV SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE
SENSOR AT 80°F (ADJ.), WHEN OUTDOOR AIR TEMPERATURE IS BELOW 45°F (ADJ.).
d. OUTDOOR AND RELIEF/EXHAUST AIR DAMPERS 100% CLOSED.
e. RETURN AIR DAMPER 100% OPENED.
B. WHEN INDEXED TO START:
a. ENABLE RETURN/RELIEF FAN(S) FIRST, THEN SUPPLY FAN(S).
b. OPERATION OF SYSTEM TO RESUME AFTER START-UP DELAY.
5. SUPPLY FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE SUPPLY FAN MOTOR(S)
VARIABLE FREQUENCY DRIVE(S), HEATING AND COOLING SOURCES AND MIXED AIR
DAMPERS TO MAINTAIN AN ADJUSTABLE SPACE TEMPERATURE SETPOINT MEASURED BY A
SPACE TEMPERATURE THERMOSTAT.
A. HEATING – UPON A FALL IN SPACE TEMPERATURE BELOW SPACE TEMPERATURE
SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:
a. MODULATE HEATING SOURCE (AS FIRST STAGE HEATING) TO MAINTAIN SPACE
TEMPERATURE SETPOINT.
• INCLUDE A MAXIMUM HEATING DISCHARGE TEMPERATURE OF 95°F (ADJ.).
• SUPPLY FAN(S) AT MINIMUM CFM/SPEED SETPOINT.
b. MODULATE SUPPLY FAN SPEED (AS SECOND STAGE HEATING) TO MAINTAIN ACTIVE
CFM/SPEED SETPOINT MEASURED BY A DUCT/FAN INLET AIR FLOW MEASURING
STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.
• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (80% OF DESIGN CFM) CFM
SETPOINTS (ADJ.).
c. UPON A CALL FOR ADDITIONAL HEAT BASED ON SUPPLY FAN(S) ARE DELIVERING
MAXIMUM CFM/SPEED (AS THIRD STAGE OF HEATING) OVERRIDE MAXIMUM
HEATING DISCHARGE TEMPERATURE.
• ALLOW HEATING CV TO MODULATE TO MAINTAIN SPACE TEMPERATE SETPOINT.
B. COOLING – UPON A RISE IN SPACE TEMPERATURE ABOVE SPACE TEMPERATURE
SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:
a. MODULATE SUPPLY FAN SPEED (AS FIRST STAGE COOLING) TO MAINTAIN ACTIVE
CFM/SPEED SETPOINT MEASURED BY DUCT/FAN INLET AIR FLOW MEASURING
STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.
• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (100% OF DESIGN CFM) CFM
SETPOINTS (ADJ.).
• ECONOMIZER SHALL BE UTILIZED (AS FIRST STAGE COOLING) IF APPLICABLE
AND NOT ALLOWING DISCHARGE AIR TEMPERATURE TO DROP BELOW 55°F,
THEN SUPPLY FAN.
b. MODULATE COOLING SOURCE (AS SECOND STAGE COOLING) TO MAINTAIN SPACE
TEMPERATURE SETPOINT.
• SUPPLY FAN(S) SHALL BE AT MAXIMUM CFM SETPOINT.
c. IF ECONOMIZER IS ENABLED, DAMPERS SHALL BE 100% OPEN TO OUTDOORS.
6. RETURN/RELIEF FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE RETURN/RELIEF
FAN MOTOR(S) VARIABLE FREQUENCY DRIVE(S) TO MAINTAIN SPACE PRESSURE SETPOINT
MEASURED BY A SPACE PRESSURE CONTROLLER LOCATED IN SPACE SERVED.
A. THE SPACE STATIC PRESSURE SETPOINT (ADJ.) SHALL BE A SETPOINT THAT CONTROLS
TO A SLIGHTLY POSITIVE PRESSURE.
7. COIL PUMP CONTROL BASED ON THE FOLLOWING:
A. HEATING HOT WATER COIL PUMP SHALL RUN WHEN THE SYSTEM IS IN HEATING MODE
(WHEN CV IS GREATER THAN 10% OPEN).
B. PUMP(S) SHALL RUN CONTINUOUSLY WHENEVER THE OUTDOOR AIR TEMPERATURE IS
LESS THAN 40°F.
8. ECONOMIZER CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR DAMPERS TO
MEET UNIT DISCHARGE AIR TEMPERATURE SETPOINT WHEN OUTDOOR AIR ENTHALPY IS
BELOW THE RETURN AIR ENTHALPY BUT ABOVE ECONOMIZING SETPOINT.
A. WHEN BTU CALCULATION FOR OUTDOOR AIR CONDITIONS EXCEEDS 28 BTUH/LB
(ADJ.), ECONOMIZER SHALL BE DISABLED.
9. MINIMUM OUTDOOR AIR CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR
DAMPERS TO MAINTAIN MINIMUM CFM SETPOINT MEASURED BY AN OUTDOOR AIR FLOW
MEASURING STATION. LIMIT THE CLOSING OF THE OUTDOOR AIR DAMPER TO PROVIDE
ABSOLUTE MINIMUM OUTDOOR AIR FLOW.
A. OUTDOOR – RELIEF/EXHAUST – RETURN MODULATING WITH ONE SIGNAL FROM
CONTROLLER.
B. REFER TO UNIT SCHEDULE FOR THE ABSOLUTE MINIMUM OUTDOOR AIRFLOW CFM
SETPOINT.
10. FILTER MONITORING - SYSTEM CONTROLLER SHALL MONITOR AND ALARM FILTER
PRESSURE DIFFERENTIAL PRESSURE DROP(S) FOR THE FOLLOWING:
A. FINAL FILTERS
a. MONITORING OF PSID
b. ALARM SETPOINT 1.00” W.C. (ADJ.)
B. PRE-FILTERS
a. MONITORING OF PSID
b. ALARM SETPOINT 0.5”W.C. (ADJ.)
11. UNOCCUPIED CONTROL – SYSTEM CONTROLLER SHALL INITIATE THE FOLLOWING BASED
ON A FALL OR RISE IN SPACE TEMPERATURE:
A. HEATING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED HEATING
MODE) WHEN A CALL FOR HEAT IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)
DURING UNOCCUPIED MODE AND HEATING SYSTEM IS OR CAN BE ENABLED. SYSTEM
SHALL RESPOND BASED ON THE FOLLOWING:
a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE
CONTROL OPERATION TO PROVIDE HEATING TO ZONE WITH THE EXCEPTION TO THE
FOLLOWING:
• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%
OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.
• COOLING SHALL BE DISABLED.
b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR HEAT AND HEATING CV SHALL
REMAIN UNDER CONTROL OF MIXED/DISCHARGE AIR TEMPERATURE CONTROL.
B. COOLING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED COOLING
MODE) WHEN A CALL FOR COOL IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)
DURING UNOCCUPIED MODE AND COOLING SYSTEM IS OR CAN BE ENABLED.
a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE
CONTROL OPERATION TO PROVIDE COOLING TO THE ZONE WITH THE EXCEPTION
TO THE FOLLOWING:
• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%
OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.
• HEATING SHALL BE DISABLED.
• ECONOMIZER SHALL BE ENABLE IF SPACE TEMPERATURE IS GREATER THAN
OUTDOOR AIR TEMPERATURE BY 10°F (ADJ.).
b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR COOL.
12. INITIAL STARTUP CONTROL - SYSTEM CONTROLLER SHALL ENABLE UNIT PRIOR TO
SCHEDULED OCCUPANCY UTILIZING OPTIMUM START LOGIC TO ADJUST STARTUP TIME
FOR UNIT BASED ON OUTDOOR AIR TEMPERATURE, BUILDING TEMPERATURE AND
HISTORIC ELAPSE TIME TO REACH SETPOINT.
A. UNIT SHALL ENERGIZE AND PROVIDE HEATING AND COOLING BASED ON THE SPACE
TEMPERATURE SENSOR(S) TO BRING SPACE TO OCCUPIED SETPOINT. THE OUTDOOR
AND RELIEF/EXHAUST AIR DAMPERS SHALL BE CLOSED UNLESS ECONOMIZER IS
ENABLED. ONCE OCCUPIED SETPOINT HAS BEEN REACHED, THE UNIT SHALL SWITCH
TO OCCUPIED MODE.
13. CO2 CONTROL - SYSTEM CONTROLLER SHALL OVERRIDE MIXED AIR DAMPER CONTROLS
IN NON-ECONOMIZING MODE USING SPACE CO2 SENSOR TO INCREASE OUTDOOR
MINIMUM CFMTO A MAXIMUM CFM. INCLUDE CORRESPONDING CLOSING RETURN AIR
DAMPER AND OPENING OF RELIEF/EXHAUST AIR DAMPERS.
A. UPON RETURN SPACE C02 SENSOR EXCEEDING SETPOINT (800 PPM ADJ.), START TO
MODULATE MIXED AIR DAMPERS (OUTDOOR AIR DAMPER OPENING) IN GRADUAL
INCREMENTS UNTIL C02 SENSOR SETPOINT IS SATISFIED.
a. MODULATE MIXED AIR DAMPERS DOWN TO ITS ABSOLUTE MINIMUM POSITION
UPON SATISFYING SENSOR SETPOINT.
B. ALARM HIGH C02, 1,200 PPM (ADJ.)
C. REFER TO UNIT SCHEDULE FOR THE MAXIMUM OUTDOOR AIRFLOW CFM SETPOINT.
14. SAFETY SHUTDOWNS:
A. PROVIDE A LOW-TEMPERATURE PROTECTION THERMOSTAT(S) ON THE LEAVING SIDE OF
HEATING HOT WATER COIL WHICH WILL DE-ENERGIZE UNIT, CLOSE MIXED AIR DAMPERS
(CLOSING OUTDOOR/RELIEF/EXHAUST AIR DAMPER(S)) AND THE HEATING HOT WATER
COIL CONTROL VALVE SHALL BE FULLY OPENED AND COIL PUMP ENERGIZED. PROVIDE
MANUAL RESET.
B. PROVIDE A HIGH STATIC PRESSURE SENSOR IN THE SUPPLY DISCHARGE PLENUM TO
DE-ENERGIZE THE UNIT UPON SENSING A HIGH STATIC PRESSURE OF 4.0" W.C..
PROVIDE MANUAL RESET.
C. PROVIDE A LOW PRESSURE STATIC LIMIT IN THE RETURN PLENUM TO DE-ENERGIZE THE
UNIT UPON SENSING A HIGH NEGATIVE STATIC PRESSURE OF -4.0" W.C.. PROVIDE
MANUAL RESET.
D. DUCT MOUNTED IONIZATION SMOKE DETECTOR(S) PROVIDED BY DIVISION 28 SHALL
DE-ENERGIZE THE UNIT WHENEVER PRODUCTS OF COMBUSTION ARE SENSED.
SCALE: NONE
RTU-1, RTU-4, RTU-5 ROOFTOP UNIT CONTROLS DIAGRAM
CONTROL POINTS
NUMBER TAG DESCRIPTION ALARM TREND I/O MISC. REMARKS
PACKAGED ROOFTOP UNIT (DX COOLING, HW HEAT)
01 H-1 RETURN AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
02 T-1 RETURN AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
03 LPSL-1 LOW PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET
04 EF-1 SPEED CONTROL ■ OUTPUT
05 EF-1 STATUS ■ ■ INPUT
06 EF-1 ENABLE/DISABLE ■ OUTPUT
07 AFM-1 OUTDOOR AIR FLOW ■ INPUT
08 D-1 MIXED AIR DAMPER OUTPUT ■ OUTPUT
09 D-1 MIXED AIR DAMPER POSITION ■ INPUT
10 T-2 MIXED AIR TEMPERATURE ■ ■ INPUT ALARM AT 45°F ADJ.
11 CP-1 STATUS ■ ■ INPUT
12 CP-1 ENABLE/DISABLE ■ OUTPUT
13 SF-1 FAN AIR FLOW ■ INPUT
14 SF-1 SPEED CONTROL ■ OUTPUT
15 SF-1 STATUS ■ ■ INPUT
16 SF-1 ENABLE/DISABLE ■ OUTPUT
17 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT
18 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT
19 DX-1 COOLING SYSTEM ALARM STATUS ■ ■ INPUT
20 DX-1 COOLING SYSTEM RUN STATUS ■ INPUT
21 DX-1 COOLING SYSTEM ENABLE/DISABLE ■ OUTPUT
22 DX-1 COOLING SYSTEM STAGING ■ OUTPUT
23 HPSL-1 HIGH PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET
24 T-3 DISCHARGE AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
25 H-2 DISCHARGE AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
26 H-3 OUTDOOR AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)
27 T-4 OUTDOOR AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)
28 SP-3 ROOM STATIC PRESSURE ■ INPUT
29 H-4 INDOOR AIR HUMIDITY SENSOR ■ INPUT
30 T-5 INDOOR AIR TEMPERATURE ■ INPUT
31 FS-1 FREEZE STAT ALARM STATUS ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET
32 T-6 HEATING COIL DISCHARGE TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
33 CO2-1 CO2 RETURN CONCENTRATION ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET
PACKAGED ROOFTOP UNIT (HW HEAT)
01 H-1 RETURN AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
02 T-1 RETURN AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
03 LPSL-1 LOW PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET
04 EF-1 SPEED CONTROL ■ OUTPUT
05 EF-1 STATUS ■ ■ INPUT
06 EF-1 ENABLE/DISABLE ■ OUTPUT
07 AFM-1 OUTDOOR AIR FLOW ■ INPUT
08 D-1 MIXED AIR DAMPER OUTPUT ■ OUTPUT
09 D-1 MIXED AIR DAMPER POSITION ■ INPUT
10 T-2 MIXED AIR TEMPERATURE ■ ■ INPUT ALARM AT 45°F ADJ.
11 CP-1 STATUS ■ ■ INPUT
12 CP-1 ENABLE/DISABLE ■ OUTPUT
13 SF-1 FAN AIR FLOW ■ INPUT
14 SF-1 SPEED CONTROL ■ OUTPUT
15 SF-1 STATUS ■ ■ INPUT
16 SF-1 ENABLE/DISABLE ■ OUTPUT
17 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT
18 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT
19 HPSL-1 HIGH PRESSURE STATIC LIMIT ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET
20 T-3 DISCHARGE AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
21 H-2 DISCHARGE AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
22 H-3 OUTDOOR AIR HUMIDITY ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)
23 T-4 OUTDOOR AIR TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS (GLOBAL)
24 SP-3 ROOM STATIC PRESSURE ■ INPUT
25 H-4 INDOOR AIR HUMIDITY SENSOR ■ INPUT
26 T-5 INDOOR AIR TEMPERATURE ■ INPUT
27 T-6 HEATING COIL DISCHARGE TEMPERATURE ■ INPUT ■ DISPLAY ENTHALPY BASED ON T&H READINGS
28 FS-1 FREEZE STAT ALARM STATUS ■ ■ INPUT ■ HARD WIRED SAFETY - MANUAL RESET
29 CO2-1 CO2 RETURN CONCENTRATION ■ ■ INPUT
SCALE: NONE
RTU-2, RTU-3 ROOFTOP UNIT CONTROLS DIAGRAM
SEQUENCE OF OPERATIONS (CONT'D)
ROOFTOP UNIT (RTU-2, RTU-3) CONTROLS
1. PROVIDE DIRECT DIGITAL CONTROLS FOR ROOFTOP SYSTEM OPERATION. UNIT(S) ARE A
COMBINATION OF AN OUTDOOR SINGLE ZONE VARIABLE VOLUME UNIT, SUPPLY FAN(S),
VARIABLE FREQUENCY CONTROLLER(S), DUCT-MOUNTED HEATING HOT WATER COIL,
CONTROL VALVE (CV) AND ACTUATOR WITH CIRCULATING PUMP, MERV 13 FINAL & MERV 8
PRE-FILTERS, OUTDOOR – RELIEF/EXHAUST - RETURN AIR DAMPERS AND ACTUATOR(S),
RELIEF FAN(S), VARIABLE FREQUENCY CONTROLLER(S) AND AIR
TEMPERATURE/AIRFLOW/HUMIDITY SENSOR(S).
2. ROOFTOP UNIT ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:
A. TIME OF DAY (TOD) SCHEDULE.
a. TO BE DETERMINED BY OWNER (CONSULT WITH OWNER).
B. ENABLED AND DISABLED BASED ON MANUAL OVERRIDE FROM DDC.
3. ROOFTOP UNIT ADJUSTABLE SETPOINTS:
A. OCCUPIED 74°F COOLING / 70°F HEATING
B. UNOCCUPIED 85°F COOLING / 62°F HEATING
4. START/STOP, CONTROLLED DEVICES SHALL RESPOND AS FOLLOWS:
A. WHEN INDEXED TO STOP:
a. DISABLE SUPPLY AND RETURN/RELIEF FAN(S) SIMULTANEOUSLY.
b. HEATING CV SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE
SENSOR AT 80°F (ADJ.), WHEN OUTDOOR AIR TEMPERATURE IS BELOW 45°F (ADJ.).
c. OUTDOOR AND RELIEF/EXHAUST AIR DAMPERS 100% CLOSED.
d. RETURN AIR DAMPER 100% OPENED.
B. WHEN INDEXED TO START:
a. ENABLE RETURN/RELIEF FAN(S) FIRST, THEN SUPPLY FAN(S).
b. OPERATION OF SYSTEM TO RESUME AFTER START-UP DELAY.
5. SUPPLY FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE SUPPLY FAN MOTOR(S)
VARIABLE FREQUENCY DRIVE(S), HEATING AND COOLING SOURCES AND MIXED AIR
DAMPERS TO MAINTAIN AN ADJUSTABLE SPACE TEMPERATURE SETPOINT MEASURED BY A
SPACE TEMPERATURE THERMOSTAT.
A. HEATING – UPON A FALL IN SPACE TEMPERATURE BELOW SPACE TEMPERATURE
SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:
a. MODULATE HEATING SOURCE (AS FIRST STAGE HEATING) TO MAINTAIN SPACE
TEMPERATURE SETPOINT.
• INCLUDE A MAXIMUM HEATING DISCHARGE TEMPERATURE OF 95°F (ADJ.).
• SUPPLY FAN(S) AT MINIMUM CFM/SPEED SETPOINT.
b. MODULATE SUPPLY FAN SPEED (AS SECOND STAGE HEATING) TO MAINTAIN ACTIVE
CFM/SPEED SETPOINT MEASURED BY A DUCT/FAN INLET AIR FLOW MEASURING
STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.
• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (80% OF DESIGN CFM) CFM
SETPOINTS (ADJ.).
c. UPON A CALL FOR ADDITIONAL HEAT BASED ON SUPPLY FAN(S) ARE DELIVERING
MAXIMUM CFM/SPEED (AS THIRD STAGE OF HEATING) OVERRIDE MAXIMUM
HEATING DISCHARGE TEMPERATURE.
• ALLOW HEATING CV TO MODULATE TO MAINTAIN SPACE TEMPERATE SETPOINT.
B. COOLING – UPON A RISE IN SPACE TEMPERATURE ABOVE SPACE TEMPERATURE
SETPOINT, CONTROLLER SHALL RESPOND BASED ON THE FOLLOWING:
a. MODULATE SUPPLY FAN SPEED (AS FIRST STAGE COOLING) TO MAINTAIN ACTIVE
CFM/SPEED SETPOINT MEASURED BY DUCT/FAN INLET AIR FLOW MEASURING
STATION TO MAINTAIN SPACE TEMPERATURE SETPOINT.
• MINIMUM (30% OF DESIGN CFM) AND MAXIMUM (100% OF DESIGN CFM) CFM
SETPOINTS (ADJ.).
• ECONOMIZER SHALL BE UTILIZED (AS FIRST STAGE COOLING) IF APPLICABLE
AND NOT ALLOWING DISCHARGE AIR TEMPERATURE TO DROP BELOW 55°F,
THEN SUPPLY FAN.
b. IF ECONOMIZER IS ENABLED, DAMPERS SHALL BE 100% OPEN TO OUTDOORS.
6. RETURN/RELIEF FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE RETURN/RELIEF
FAN MOTOR(S) VARIABLE FREQUENCY DRIVE(S) TO MAINTAIN SPACE PRESSURE SETPOINT
MEASURED BY A SPACE PRESSURE CONTROLLER LOCATED IN SPACE SERVED.
A. THE SPACE STATIC PRESSURE SETPOINT (ADJ.) SHALL BE A SETPOINT THAT CONTROLS
TO A SLIGHTLY POSITIVE PRESSURE.
7. COIL PUMP CONTROL BASED ON THE FOLLOWING:
A. HEATING HOT WATER COIL PUMP SHALL RUN WHEN THE SYSTEM IS IN HEATING MODE
(WHEN CV IS GREATER THAN 10% OPEN).
B. PUMP(S) SHALL RUN CONTINUOUSLY WHENEVER THE OUTDOOR AIR TEMPERATURE IS
LESS THAN 40°F.
8. ECONOMIZER CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR DAMPERS TO
MEET UNIT DISCHARGE AIR TEMPERATURE SETPOINT WHEN OUTDOOR AIR ENTHALPY IS
BELOW THE RETURN AIR ENTHALPY BUT ABOVE ECONOMIZING SETPOINT.
A. WHEN BTU CALCULATION FOR OUTDOOR AIR CONDITIONS EXCEEDS 28 BTUH/LB
(ADJ.), ECONOMIZER SHALL BE DISABLED.
9. MINIMUM OUTDOOR AIR CONTROL - SYSTEM CONTROLLER SHALL MODULATE MIXED AIR
DAMPERS TO MAINTAIN MINIMUM CFM SETPOINT MEASURED BY AN OUTDOOR AIR FLOW
MEASURING STATION. LIMIT THE CLOSING OF THE OUTDOOR AIR DAMPER TO PROVIDE
ABSOLUTE MINIMUM OUTDOOR AIR FLOW.
A. OUTDOOR – RELIEF/EXHAUST – RETURN MODULATING WITH ONE SIGNAL FROM
CONTROLLER.
B. REFER TO UNIT SCHEDULE FOR THE ABSOLUTE MINIMUM OUTDOOR AIRFLOW CFM
SETPOINT.
10. FILTER MONITORING - SYSTEM CONTROLLER SHALL MONITOR AND ALARM FILTER
PRESSURE DIFFERENTIAL PRESSURE DROP(S) FOR THE FOLLOWING:
A. FINAL FILTERS
a. MONITORING OF PSID
b. ALARM SETPOINT 1.00” W.C. (ADJ.)
B. PRE-FILTERS
a. MONITORING OF PSID
b. ALARM SETPOINT 0.5”W.C. (ADJ.)
11. UNOCCUPIED CONTROL – SYSTEM CONTROLLER SHALL INITIATE THE FOLLOWING BASED
ON A FALL OR RISE IN SPACE TEMPERATURE:
A. HEATING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED HEATING
MODE) WHEN A CALL FOR HEAT IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)
DURING UNOCCUPIED MODE AND HEATING SYSTEM IS OR CAN BE ENABLED. SYSTEM
SHALL RESPOND BASED ON THE FOLLOWING:
a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE
CONTROL OPERATION TO PROVIDE HEATING TO ZONE WITH THE EXCEPTION TO THE
FOLLOWING:
• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%
OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.
• COOLING SHALL BE DISABLED.
b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR HEAT AND HEATING CV SHALL
REMAIN UNDER CONTROL OF MIXED/DISCHARGE AIR TEMPERATURE CONTROL.
B. COOLING - SYSTEM CONTROLLER SHALL CYCLE SYSTEM ON (UNOCCUPIED COOLING
MODE) WHEN A CALL FOR COOL IS INITIATED BY A SPACE TEMPERATURE SENSOR(S)
DURING UNOCCUPIED MODE AND COOLING SYSTEM IS OR CAN BE ENABLED.
a. ENABLE FAN(S) AND SYSTEM SHALL FUNCTION AS DESCRIBED IN TEMPERATURE
CONTROL OPERATION TO PROVIDE COOLING TO THE ZONE WITH THE EXCEPTION
TO THE FOLLOWING:
• MIXED AIR DAMPERS SHALL REMAIN CLOSED WITH RETURN DAMPER 100%
OPENED AND OUTDOOR AND RELIEF/EXHAUST 100% CLOSED.
• HEATING SHALL BE DISABLED.
• ECONOMIZER SHALL BE ENABLE IF SPACE TEMPERATURE IS GREATER THAN
OUTDOOR AIR TEMPERATURE BY 10°F (ADJ.).
b. SYSTEM DISABLED UPON SATISFYING THE CALL FOR COOL.
12. INITIAL STARTUP CONTROL - SYSTEM CONTROLLER SHALL ENABLE UNIT PRIOR TO
SCHEDULED OCCUPANCY UTILIZING OPTIMUM START LOGIC TO ADJUST STARTUP TIME
FOR UNIT BASED ON OUTDOOR AIR TEMPERATURE, BUILDING TEMPERATURE AND
HISTORIC ELAPSE TIME TO REACH SETPOINT.
A. UNIT SHALL ENERGIZE AND PROVIDE HEATING AND COOLING BASED ON THE SPACE
TEMPERATURE SENSOR(S) TO BRING SPACE TO OCCUPIED SETPOINT. THE OUTDOOR
AND RELIEF/EXHAUST AIR DAMPERS SHALL BE CLOSED UNLESS ECONOMIZER IS
ENABLED. ONCE OCCUPIED SETPOINT HAS BEEN REACHED, THE UNIT SHALL SWITCH
TO OCCUPIED MODE.
13. CO2 CONTROL - SYSTEM CONTROLLER SHALL OVERRIDE MIXED AIR DAMPER CONTROLS
IN NON-ECONOMIZING MODE USING SPACE CO2 SENSOR TO INCREASE OUTDOOR
MINIMUM CFMTO A MAXIMUM CFM. INCLUDE CORRESPONDING CLOSING RETURN AIR
DAMPER AND OPENING OF RELIEF/EXHAUST AIR DAMPERS.
A. UPON RETURN SPACE C02 SENSOR EXCEEDING SETPOINT (800 PPM ADJ.), START TO
MODULATE MIXED AIR DAMPERS (OUTDOOR AIR DAMPER OPENING) IN GRADUAL
INCREMENTS UNTIL C02 SENSOR SETPOINT IS SATISFIED.
a. MODULATE MIXED AIR DAMPERS DOWN TO ITS ABSOLUTE MINIMUM POSITION
UPON SATISFYING SENSOR SETPOINT.
B. ALARM HIGH C02, 1,200 PPM (ADJ.)
C. REFER TO UNIT SCHEDULE FOR THE MAXIMUM OUTDOOR AIRFLOW CFM SETPOINT.
14. SAFETY SHUTDOWNS:
A. PROVIDE A LOW-TEMPERATURE PROTECTION THERMOSTAT(S) ON THE LEAVING SIDE OF
HEATING HOT WATER COIL WHICH WILL DE-ENERGIZE UNIT, CLOSE MIXED AIR DAMPERS
(CLOSING OUTDOOR/RELIEF/EXHAUST AIR DAMPER(S)) AND THE HEATING HOT WATER
COIL CONTROL VALVE SHALL BE FULLY OPENED AND COIL PUMP ENERGIZED. PROVIDE
MANUAL RESET.
B. PROVIDE A HIGH STATIC PRESSURE SENSOR IN THE SUPPLY DISCHARGE PLENUM TO
DE-ENERGIZE THE UNIT UPON SENSING A HIGH STATIC PRESSURE OF 4.0" W.C..
PROVIDE MANUAL RESET.
C. PROVIDE A LOW PRESSURE STATIC LIMIT IN THE RETURN PLENUM TO DE-ENERGIZE THE
UNIT UPON SENSING A HIGH NEGATIVE STATIC PRESSURE OF -4.0" W.C.. PROVIDE
MANUAL RESET.
D. DUCT MOUNTED IONIZATION SMOKE DETECTOR(S) PROVIDED BY DIVISION 28 SHALL
DE-ENERGIZE THE UNIT WHENEVER PRODUCTS OF COMBUSTION ARE SENSED.
ISSUED FOR DATE
HCV-1
HCV-1
M
T-1
TS
ZONE AIR CONDITIONS
HEATING COIL
FAN FAN
SF-1
SF-1
HCV-1
HCV-1
T-1
TS
ZONE AIR CONDITIONS
M
H E A
TI
N G
SA OUT
D-1
CP-1
T-3
H-2
HCV-1
HPSL-1 02
D-120
HCV-1
CP-1
LPSL-1
S U P P
LY
F A N 10
SF-1
SF-1
SF-1
SF-1
EA IN
T-5
H-3
E X H A U S T
F A N
EF-1
EF-1
EF-1
EF-1
FS-1
ERW
F
IL
TE
R S
E C
TI
O N
OA IN
D-4
D-4
EA OUT
D-3
D-3
D-2
D-2
EW-1
EW-1
EW-1
T-6
T-7
T-1
T-2
HS TS D
A M
P E R
M
D A M
P E R
M
TS TS
TSTS
P
D A M
P E R
M
VFD
EF-1
D A M
P E R
M
F
P
M
TSHS
VFD
SF-1
ERW
T-8
H-4
HS TS
OUTDOOR AIR CONDITIONS
T-9
H-5
HS TS
INDOOR AIR CONDITIONS
SP-3
PS
T-4
TS
REF (S)
REF (L)
TS
T-1
ZONE AIR
CONDITIONS
INDOOR UNIT
F
IL
E N
U M
B E
R
S T
A T
E I
N D
E X
N U
M B
E R
S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
TR
U
C
TI
O N
D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T
A N
D B
U D
G E
T S
T A
T E
O F
M
IC
H
IG
A N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
3F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O N
E
.4
.5
6F
A X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T E
M P
E R
A T
U R
E C
O N
T R
O L S
-1
.0
M
J U
N E
M
ID
L A
N D
A R
M O
R Y
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
A
IR
P
O R
T R
O A
D
M
ID
L A
N D
M
I
D E
P A
R T
M E
N T
O F
M
IL
IT
A
R Y
A N
D V
E T
E R
A N
'S A
F F
A
IR
S
/2
.C
A K
/1
/2
SCALE: NONE
FINNED TUBE RADIATION CONTROLS DIAGRAM
SCALE: NONE
CABINET UNIT HEATER CONTROLS DIAGRAM
CONTROL POINTS
NUMBER TAG DESCRIPTION ALARM TREND I/O REMARKS
CEILING CASSETTE AIR CONDITIONER
01 T-1 SPACE TEMPERATURE ■ ■ INPUT
ENERGY RECOVERY SYSTEM (ENTHALPY WHEEL DX)
01 D-1 OUTDOOR AIR DAMPER OUTPUT ■ OUTPUT
02 D-1 OUTDOOR AIR DAMPER POSITION ■ ■ INPUT
03 T-1 ERW ENTERING OUTDOOR AIR TEMPERATURE ■ INPUT
04 EW-1 ENTHALPY WHEEL SPEED CONTROL ■ OUTPUT
05 EW-1 ENTHALPY WHEEL RUN STATUS ■ ■ INPUT
06 EW-1 ENTHALPY WHEEL ENABLE/DISABLE ■ OUTPUT
07 D-2 OUTDOOR AIR BY-PASS DAMPER OUTPUT ■ OUTPUT
08 D-2 OUTDOOR AIR BY-PASS DAMPER POSITION ■ ■ INPUT
09 T-2 ERW LEAVING OUTDOOR AIR TEMPERATURE ■ INPUT
10 SF-1 SPEED CONTROL ■ OUTPUT
11 SF-1 FAN AIR FLOW ■ INPUT
12 SF-1 VFD FAULT STATUS ■ ■ INPUT
13 SF-1 ENABLE/DISABLE ■ OUTPUT
14 HPSL-1 HIGH PRESSURE STATIC LIMIT ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET
15 T-3 DISCHARGE AIR TEMPERATURE ■ ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS
16 H-2 DISCHARGE AIR HUMIDITY ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS
17 CP-1 STATUS ■ ■ INPUT
18 CP-1 ENABLE/DISABLE ■ OUTPUT
19 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT
20 HCV-1 HEATING CONTROL VALVE POSITION ■ ■ INPUT
21 FS-1 FREEZE STAT ALARM STATUS ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET
22 T-4 HEATING COIL DISCHARGE TEMPERATURE ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS
23 H-3 EXHAUST AIR HUMIDITY ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS
24 T-5 EXHAUST AIR TEMPERATURE ■ INPUT DISPLAY ENTHALPY BASED ON T&H READINGS
25 T-6 ERW ENTERING EXHAUST AIR TEMPERATURE ■ INPUT
26 D-3 EXHAUST AIR BY-PASS DAMPER OUTPUT ■ OUTPUT
27 D-3 EXHAUST AIR BY-PASS DAMPER POSITION ■ ■ INPUT
28 T-7 ERW LEAVING EXHAUST AIR TEMPERATURE ■ INPUT
29 LPSL-1 LOW PRESSURE STATIC LIMIT ■ ■ INPUT HARD WIRED SAFETY - MANUAL RESET
30 EF-1 FAN AIR FLOW ■ INPUT
31 EF-1 SPEED CONTROL ■ OUTPUT
32 EF-1 VFD FAULT STATUS ■ ■ INPUT
33 EF-1 ENABLE/DISABLE ■ OUTPUT
34 D-4 EXHAUST AIR DAMPER POSITION ■ ■ INPUT
35 D-4 EXHAUST AIR DAMPER OUTPUT ■ OUTPUT
36 H-4 OUTDOOR AIR HUMIDITY ■ INPUT GLOBAL
37 T-8 OUTDOOR AIR TEMPERATURE ■ INPUT GLOBAL
38 SP-3 ROOM STATIC PRESSURE ■ INPUT
39 H-5 INDOOR AIR HUMIDITY SENSOR ■ INPUT
40 T-9 INDOOR AIR TEMPERATURE ■ INPUT
FINNED TUBE RADIATION
01 T-1 ZONE AIR TEMPERATURE ■ ■ INPUT
02 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT
03 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT
CABINET UNIT HEATER
01 T-1 ZONE AIR TEMPERATURE ■ ■ INPUT
02 SF-1 STATUS ■ ■ INPUT
03 SF-1 ENABLE/DISABLE ■ OUTPUT
04 HCV-1 HEATING CONTROL VALVE POSITION ■ INPUT
05 HCV-1 HEATING CONTROL VALVE OUTPUT ■ OUTPUT
SEQUENCE OF OPERATIONS
NOTE: ALL LABOR, MATERIAL, EQUIPMENT AND SOFTWARE NOT SPECIFICALLY INDICATED
WITHIN CONTROLS DRAWINGS THAT IS REQUIRED TO MEET THE FUNCTIONAL INTENT
OF THE SEQUENCE OF OPERATIONS SHALL BE PROVIDED WITHOUT ADDITIONAL
COST. POINT LISTS SHALL BE A GUIDE TO THE POINTS REQUIRED FOR CONTROL
SYSTEM. FINAL POINTS SHALL BE DETERMINED BY SEQUENCE OF OPERATIONS. ALL
SET POINTS SHALL BE OPERATOR ADJUSTABLE THROUGH THE BMS. ALL POINTS
SHALL BE TRENDABLE.
SEQUENCE OF OPERATIONS (CONT'D)
SCALE: NONE
ENERGY RECOVERY SYSTEM (ENTHALPY WHEEL) CONTROLS DIAGRAM
ENERGY RECOVERY UNIT (HRU-1) CONTROLS
1. PROVIDE DIRECT DIGITAL CONTROLS (DDC) FOR ENERGY RECOVERY UNIT OPERATION.
UNIT(S) ARE A COMBINATION OF AN OUTDOOR SINGLE ZONE CONSTANT VOLUME UNIT,
SUPPLY FAN(S), VARIABLE FREQUENCY CONTROLLER(S), HEATING HOT WATER COIL,
CONTROL VALVE (CV) AND ACTUATOR WITH CIRCULATING PUMP, ENERGY RECOVERY
WHEEL, MERV 11/13 FINAL/MERV 7/8 PRE-FILTERS, OUTDOOR – EXHAUST - BYPASS AIR
DAMPERS AND ACTUATOR(S), EXHAUST FAN(S), VARIABLE FREQUENCY CONTROLLER(S)
AND AIR TEMPERATURE/HUMIDITY SENSOR(S).
2. ENERGY RECOVERY UNIT ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:
A. TIME OF DAY (TOD) SCHEDULE.
a. TO BE DETERMINED BY OWNER (CONSULT WITH OWNER).
B. ENABLED AND DISABLED BASED ON MANUAL OVERRIDE FROM DDC.
3. ENERGY RECOVERY UNIT ADJUSTABLE SETPOINTS:
A. OCCUPIED 74°F COOLING / 70°F HEATING
B. UNOCCUPIED 85°F COOLING / 62°F HEATING
4. START/STOP, CONTROLLED DEVICES SHALL RESPOND AS FOLLOWS:
A. WHEN INDEXED TO STOP:
a. DISABLE SUPPLY AND EXHAUST FAN(S) SIMULTANEOUSLY.
b. HEATING CV SHALL MODULATE TO MAINTAIN HEATING COIL DISCHARGE AIR
TEMPERATURE SENSOR AT 80°F (ADJ.), WHEN OUTDOOR AIR TEMPERATURE IS
BELOW 45°F (ADJ.).
c. OUTDOOR AND EXHAUST AIR DAMPERS 100% CLOSED, ONCE SYSTEM FANS HAVE
BEEN DISABLED.
d. WHEEL BYPASS DAMPERS 100% OPENED.
B. WHEN INDEXED TO START:
a. OUTDOOR AND EXHAUST AIR DAMPERS 100% OPENED.
b. ENABLE SUPPLY AND EXHAUST FAN(S).
c. OPERATION OF SYSTEM TO RESUME AFTER START-UP DELAY.
5. EXHAUST FAN CONTROL - SYSTEM CONTROLLER SHALL MODULATE EXHAUST FAN
MOTOR(S) VARIABLE FREQUENCY CONTROLLER(S) TO MAINTAIN SPACE PRESSURE
SETPOINT MEASURED BY A SPACE PRESSURE CONTROLLER LOCATED IN SPACE SERVED.
A. THE SPACE STATIC PRESSURE SETPOINT (ADJ.) SHALL BE A SETPOINT THAT CONTROLS
TO A SLIGHTLY NEGATIVE PRESSURE.
6. FAN VARIABLE FREQUENCY CONTROLLER(S) SHALL BE MONITORED BASED ON THE
FOLLOWING:
a. VIA LONWORKS CONNECTION (POWER USAGE / SPEED % AND HZ / HOURS / FAULT /
ALARM)
7. FAN(S) INITIAL START-UP CONTROL – WHEN INDEXED TO START, SYSTEM CONTROLLER
SHALL ENABLE FAN(S) BASED ON THE FOLLOWING:
A. WHEN ENABLED, AND AFTER A DELAY OF TWO (2) MINUTES (ADJ.) WITH NO STATUS
SENSED, DDC SHALL INDICATE A CRITICAL ALARM.
a. IF ANY FAN (SUPPLY OR EXHAUST) STATUS IS NOT SENSED, THE SYSTEM SHALL BE
DISABLED.
B. WHEN ENABLED AND STATUS IS SENSED BY THE CURRENT SENSOR, A TOTALIZES OF
RUN HOURS FOR FAN WILL BE ACTIVE.
8. DISCHARGE AIR TEMPERATURE CONTROL - SYSTEM CONTROLLER SHALL MODULATE/CYCLE
HEATING SOURCES AND MIXED AIR DAMPERS TO MAINTAIN A FIXED DISCHARGE AIR
TEMPERATURE SETPOINT MEASURED BY A DUCT TEMPERATURE SENSOR LOCATED
DOWNSTREAM OF UNIT.
A. WHEN SYSTEM IS IN COOLING MODE DAT SHALL BE 55°F (ADJ.).
B. WHEN SYSTEM IS IN HEATING MODE DAT SHALL BE 95°F (ADJ.).
C. HEATING/COOLING MODE – WHEN OUTDOOR AIR TEMPERATURE IS GREATER OR LESS
THAN DISCHARGE AIR TEMPERATURE SETPOINT BY 3°F (ADJ.), THE FOLLOWING SHALL
BE INITIATED:
a. BYPASS DAMPERS 100% CLOSED.
b. ENABLE WHEEL AND MODULATE SPEED TO MAINTAIN ACTIVE DAT SETPOINT.
• IF WHEEL IS UNABLE TO MAINTAIN DAT SETPOINT, THE HEATING/COOLING CV
SHALL MODULATE TO MAINTAIN SETPOINT.
D. VENTILATION MODE – WHEN OUTDOOR AIR TEMPERATURE IS EQUAL TO DISCHARGE
AIR TEMPERATURE SETPOINT BY LESS THAN 3°F (ADJ.), THE FOLLOWING SHALL BE
INITIATED:
a. BYPASS DAMPERS 100% OPENED.
b. DISABLE WHEEL.
E. FROST MODE - WHEN OUTDOOR AIR TEMPERATURE IS BELOW THE FROST CONTROL
SETPOINT OF 32°F (ADJ.).
a. THE WHEEL OUTDOOR BYPASS DAMPER WILL MODULATE TO VARY THE
EFFECTIVENESS OF THE WHEEL TO PREVENT THE EXHAUST AIR FROM BEING
COOLED BELOW THE SATURATION POINT.
b. THE WHEEL SPEED WILL MODULATE TO VARY THE EFFECTIVENESS OF THE WHEEL
TO PREVENT THE EXHAUST AIR FROM BEING COOLED BELOW THE SATURATION
POINT.
9. COIL PUMP CONTROL BASED ON THE FOLLOWING:
A. HEATING HOT WATER COIL PUMP SHALL RUN WHEN THE SYSTEM IS IN HEATING MODE
(WHEN CV IS GREATER THAN 10% OPEN).
B. PUMP(S) SHALL RUN CONTINUOUSLY WHENEVER THE OUTDOOR AIR TEMPERATURE IS
LESS THAN 40°F.
10. FILTER MONITORING - SYSTEM CONTROLLER SHALL MONITOR AND ALARM FILTER
PRESSURE DIFFERENTIAL PRESSURE DROP(S) FOR THE FOLLOWING:
A. FINAL FILTERS
a. MONITORING OF PSID
b. ALARM SETPOINT 1.00” W.C. (ADJ.)
B. PRE-FILTERS (BOTH OUTDOOR AND EXHAUST)
a. MONITORING OF PSID
b. ALARM SETPOINT 0.5”W.C. (ADJ.)
11. UNOCCUPIED CONTROL – SYSTEM CONTROLLER SHALL INITIATE THE FOLLOWING BASED
ON A FALL OR RISE IN SPACE TEMPERATURE:
A. HEATING AND COOLING CONTROL WILL BE THE SAME AS OCCUPIED CONTROL.
12. INITIAL STARTUP CONTROL - SYSTEM CONTROLLER SHALL ENABLE UNIT PRIOR TO
SCHEDULED OCCUPANCY UTILIZING OPTIMUM START LOGIC TO ADJUST STARTUP TIME
FOR UNIT BASED ON OUTDOOR AIR TEMPERATURE, BUILDING TEMPERATURE AND
HISTORIC ELAPSE TIME TO REACH SETPOINT.
A. UNIT SHALL ENERGIZE AND PROVIDE HEATING AND COOLING BASED ON THE SPACE
TEMPERATURE SENSOR(S) TO BRING SPACE TO OCCUPIED SETPOINT. THE OUTDOOR
AND RELIEF/EXHAUST AIR DAMPERS SHALL BE CLOSED UNLESS ECONOMIZER IS
ENABLED. ONCE OCCUPIED SETPOINT HAS BEEN REACHED, THE UNIT SHALL SWITCH
TO OCCUPIED MODE.
13. SAFETY SHUTDOWNS:
A. PROVIDE A LOW-TEMPERATURE PROTECTION THERMOSTAT(S) ON THE LEAVING SIDE OF
HEATING HOT WATER COIL WHICH WILL DE-ENERGIZE UNIT, CLOSE MIXED AIR DAMPERS
(CLOSING OUTDOOR/RELIEF/EXHAUST AIR DAMPER(S)) AND THE HEATING HOT WATER
COIL CONTROL VALVE SHALL BE FULLY OPENED AND COIL PUMP ENERGIZED. PROVIDE
MANUAL RESET.
B. PROVIDE A HIGH STATIC PRESSURE SENSOR IN THE SUPPLY DISCHARGE PLENUM TO
DE-ENERGIZE THE UNIT UPON SENSING A HIGH STATIC PRESSURE OF 4.0" W.C..
PROVIDE MANUAL RESET.
C. PROVIDE A LOW PRESSURE STATIC LIMIT IN THE RETURN PLENUM TO DE-ENERGIZE THE
UNIT UPON SENSING A HIGH NEGATIVE STATIC PRESSURE OF -4.0" W.C.. PROVIDE
MANUAL RESET.
D. DUCT MOUNTED IONIZATION SMOKE DETECTOR(S) PROVIDED BY DIVISION 28 SHALL
DE-ENERGIZE THE UNIT WHENEVER PRODUCTS OF COMBUSTION ARE SENSED.
FINNED TUBE CONTROLS
1. PROVIDE DIRECT DIGITAL CONTROLS (DDC) FOR FINNED TUBE OPERATION. FINNED TUBE
IS A COMBINATION OF A HEATING ELEMENT, CONTROL VALVE (CV) AND ACTUATOR AND
AIR TEMPERATURE SENSOR.
2. FINNED TUBE ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:
A. SCHEDULED WITH ASSOCIATED ZONE HVAC SYSTEM.
3. FINNED TUBE ADJUSTABLE SETPOINTS:
A. OCCUPIED 68°F HEATING
B. UNOCCUPIED 60°F HEATING
4. OPERATION SHALL BE BASED ON THE FOLLOWING:
A. OPERATION BASED ON WALL MOUNTED THERMOSTAT THAT WILL ENABLE UNIT
WHENEVER SPACE TEMPERATURE FALLS BELOW HEATING SETPOINT.
5. ENABLED/DISABLED BASED ON THE FOLLOWING:
A. WHEN INDEXED DISABLED, CONTROLLED DEVICES SHALL RESPOND AS NOTED:
a. HEATING CV 100% CLOSED.
B. WHEN INDEXED TO ENABLED, CONTROLLED DEVICES SHALL RESPOND AS NOTED:
a. HEATING CV 100% OPENED.
6. MONITORING AND ALARMING OF THE FOLLOWING:
A. SPACE AIR TEMPERATURE.
CABINET UNIT HEATER CONTROLS
1. PROVIDE DIRECT DIGITAL CONTROLS (DDC) FOR CABINET HEATER OPERATION. CABINET
HEATER IS A COMBINATION OF A CONSTANT VOLUME FAN, FILTER, HEATING COIL,
CONTROL VALVE(CV) AND ACTUATOR, AND AIR TEMPERATURE SENSOR.
2. CABINET HEATER ADJUSTABLE SCHEDULE BASED ON THE FOLLOWING:
A. SCHEDULED WITH MAIN BUILDING SCHEDULE.
3. OPERATION SHALL BE BASED ON THE FOLLOWING:
A. OPERATION BASED ON UNIT MOUNTED RETURN AIR TEMPERATURE SENSOR THAT WILL
ENABLE UNIT WHENEVER RETURN AIR TEMPERATURE FALLS BELOW HEATING SETPOINT.
4. TEMPERATURE SETPOINT:
A. FOR CABINET HEATERS IN VESTIBULES, UNIT SHALL DE-ENERGIZE WHEN OUTDOOR AIR
TEMPERATURES ARE ABOVE 45°F. VESTIBULE CABINET HEATERS SHALL BE
CONTROLLED BY A ZONE THERMOSTAT TO A SETPOINT OF 60°F (MAX).
5. START/STOP BASED ON THE FOLLOWING:
A. WHEN INDEXED TO STOP, CONTROLLED DEVICES SHALL RESPOND AS NOTED:
a. DISABLE FAN.
b. HEATING CV 100% CLOSED.
B. WHEN INDEXED TO START, CONTROLLED DEVICES SHALL RESPOND AS NOTED:
a. HEATING CV 100% OPENED.
b. ENABLE FAN.
6. MONITORING AND ALARMING OF THE FOLLOWING:
A. FAN MOTOR STATUS.
a. WHEN ENABLED, AND AFTER A DELAY OF TWO (2) MINUTES (ADJ.) WITH NO STATUS
SENSED, THE DDC SHALL INDICATE A GENERAL ALARM.
b. WHEN ENABLED AND STATUS IS SENSED BY THE CURRENT SENSOR, A TOTALIZES
OF RUN HOURS FOR CABINET HEATER WILL BE ACTIVE.
B. SPACE AIR TEMPERATURE.
ISSUED FOR DATE
SCALE: NONE
MINI-SPLIT (CEILING CASSETTE) CONTROLS DIAGRAM
SPLIT SYSTEM CONTROLS (DX)
1. FACTORY CONTROLS.
2. SYSTEM START / STOP.
A. UNIT SUPPLY FAN AND MECHANICAL HEATING/COOLING SHALL CYCLE BASED ON SPACE
DEMAND.
3. DDC CONTROL SYSTEM SHALL MONITOR AND ALARM SPACE TEMPERATURE.
4. TEMPERATURE SETPOINT: CONTROLLED BY OCCUPANCY.
DDC-1
DIN RAIL RELAY SOCKET & RELAY
AS REQUIRED AND (1) SPARE
DIN RAIL TERMINAL BLOCKS AS
REQUIRED FOR ALL 24V POWER
AND COMMON & (4) SPARE
DIN RAIL CIRCUIT BREAKER FOR
EACH CONTROLLER
4x4x24" WIREWAY
AC/DC CONVERTER, ACDC-1
T-1
ENCLOSURE ENC-1
1.5X2.25 SLOTTED WIRE DUCT VERTICAL
1.0X1.5 SLOTTED WIRE DUCT HORIZONTAL
DIN RAIL TYP
NEW 3/4" EMT FOR CONTROL
WIRES AS REQUIRED
CIRCUIT FROM POWER PANEL
T-2 VAV
TRANSFORMER
T-2 VAV
TRANSFORMER DDC-1 DDC-1
GENERAL DDC NOTES:
DDC EQUIPMENT SCHEDULE
BASIS OF DESIGN SERVICE QTY / WIRE SIZE
TO EQUIPMENT
NOTES
ROOM TEMP
AIRSTREAM TEMP
OAT
DDC
DESCRIPTION
ROOM TEMPERATURE SENSOR
PROGRAMMABLE CONTROLLER
DUCT/EQUIP TEMPERATURE SENSOR
OUTDOOR AIR TEMP SENSOR
LOCATION
SEE LAYOUT, WALL MOUNTED 60" AFF
RETURN DUCT AFTER FRESH AIR
BLDG EXTERIOR
DDC ENCLOSURE
ENC-1CATNET - CLI-FTCATNET INTERFACE W/ LON CARD ONE PER BUILDING, ENC-1
KELE - RET2620 DDC EQUIPMENT ENCLOSUREDDC ENCLOSURE MECHANICAL ROOM -
BAPI - BA/10K-3-B4
BAPI - BA/10K-3-O-EU
3 CONDUCTOR / 18 GA.
WATER TEMPPIPE TEMPERATURE SENSOR SUPPLY DUCTBAPI - BA/10K3-S
3 CONDUCTOR / 18 GA.
4 CONDUCTOR / 18 GA.
NO SUBSTITUTIONS
(2) SINGLE POLE DOUBLE THROW 15A
CIRCRON - UHC 400
LABEL
TEMP-1-AREA
TEMP-2-AHU# or RTU#
OAT-1
DDC-1
CATNET
ENC-1
TEMP-3-AHU# or RTU#
MARK
TEMP-1
TEMP-2
OAT-1
DDC-1
DDC-2
ENC-1
TEMP-3
AIR PROD. & CONTROLS - T-PB-202-0TRANSFORMER w/ OUTLET DDC ENCLOSURE -T-1-ENC#T-1
NO SUBSTITUTIONS
CS-1 AHU/PUMPS/EXHAUST FANSACI - A/MSCSCURRENT SENSOR VARIES
RELAY VARIESRELAY-1 RIB - RIBU1C MECHANICAL EQUIP
2 CONDUCTOR / 18 GA.
CS-1-(DEVICE NAME)
(VARIES ON DEVICE)
DIN RAIL RELAY SOCKET MECH ROOMRELAY-2 VERIS - VBD1B-F MECHANICAL EQUIP
DIN RAIL RELAY SPDT MECH ROOMRELAY-3 VERIS - VMD1B-F24A MECHANICAL EQUIP
2 CONDUCTOR / 18 GA.
DIN RAIL DDC ENCLOSURE / RTUDIN RAIL KELI - BAM-1000 MECHANICAL EQUIP
SEE DETAILS FOR EXACT LOCATION
DDC ENCLOSURE EQUIPMENT
CIRCUIT BREAKER FOR CONTROLLERBRKR - CBI ELECTRIC - QL-2 DDC ENCLOSURE / RTU
BAPI - BA/10K-3-D-18"
WIRE DUCT - SLOTTED WIRE DUCT IBOCO - T1E-2222W MECHANICAL EQUIP DDC ENCLOSURE
SEE DETAILS FOR EXACT LOCATION
PROGRAMMABLE CONTROLLER
SEE DETAILS FOR EXACT LOCATION2 CONDUCTOR / 18 GA.
SINGLE POLE DOUBLE THROW 2A
18 INCHES, TEMP. AVERAGING
3 CONDUCTOR / 18 GA.
SD-1 AHU/RTUAIR PRODUCTS & CONTROLS - SL-2000-PSMOKE DETECTOR RETURN DUCT BEFORE FRESH AIR
3 CONDUCTOR / 18 GA.
SD-1
TERMINAL BLOCK DDC ENCLOSURE / RTUTBLCK KELE - CDU4N MECHANICAL EQUIP
CO2-1 CO2VERIS - CDEDUCT CO2 SENSOR RETURN DUCT
3 CONDUCTOR / 18 GA.
CO2-1-AHU#
2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR
OR APPROVED EQUAL
RELAY VARIESRELAY-4 RIB - RIB2421SB AHU/RTU FANS & ALL PUMPS
2 CONDUCTOR / 18 GA.
(VARIES ON DEVICE)
SINGLE POLE DOUBLE THROW 2A
ENC-1CATNET - HMI CH-2CATNET WEBSERVER -WEBSERVERDDC-3 NO SUBSTITUTIONS
ENC-1CATNET - CMI-485INTERFACE MODBUS DDC ENCLOSURE -MODBUSDDC-4 NO SUBSTITUTIONS
ONE PER BUILDING, ENC-1
OCC-1 ROOM OCCUPANCYWATTSTOPPER - CX100OCCUPANY SENSOR SEE LAYOUT, WALL MOUNTED 6" FROM CEILINGOCC-1-RM#
ACDC-1 ACDC-1 AC TO DC VOLTAGE CONVERTER ACI - PS1.5 OCCUPANCY SENSORS DDC ENCLOSURE
2 CONDUCTOR / 18 GA., 2 CONDUCTOR / 18 GA. PWR
KELE - RET2620 DDC EQUIPMENT ENCLOSUREDDC ENCLOSURE MECHANICAL ROOM - NO SUBSTITUTIONSENC-2ENC-2
ACT-1 DAMPERSKMC CONTROLS - MEP-7552DAMPER ACTUATOR VARIESACT-1-(DEVICE NAME) 2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR
ACT-2 CONTROL VALVESKMC CONTROLS - MEP-4252V½" & ¾" VALVE ACTUATOR VARIESACT-2-(DEVICE NAME) 2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR
KELE - RET2620 DDC EQUIPMENT ENCLOSUREDDC ENCLOSURE MECHANICAL ROOM - NO SUBSTITUTIONSENC-3ENC-3
MECH EQUIPMENTFREEZESTAT COOLING COILACI - FS-4FR-1-AHU# or RTU#FR-1 3 CONDUCTOR / 18 GA.
ACT-3 CONTROL VALVESKMC CONTROLS - MEP-4552V1" - 3" VALVE ACTUATOR VARIESACT-3-(DEVICE NAME) 2 CONDUCTOR / 18 GA. SHIELD, 2 CONDUCTOR / 18 GA. PWR
RIB - PSH200A-LVCTRANSFORMER DDC ENCLOSURE -T-2-ENC#T-2 VAV CONTROLLERS
CIRCON - VAV-332-IMVTERMINAL UNIT CONTROLLER SEE MECHANICAL SHEETS 2 CONDUCTOR / 18 GA. PWRVAV-#-LOCATIONVAV-1-20 HVAC EQUIP NO SUBSTITUTIONS, POWER WIRE FROM T-2
ACI - A/LP2-3-10DUCT PRESSURE SENSOR MAIN SUPPLY DUCT 4 CONDUCTOR / 18 GA. SHIELDDP-1DP-1 MECHANICAL EQUIP
NOTES:
1. CONTRACTOR TO FURNISH AND INSTALL MATERIALS IN SCHEDULE. WIRE SHOWN TO BE PULLED INTO ENCLOSURES, LABELED AND COILED AT EACH END.
2. SUBSTITUTIONS SHALL BE REVIEWED AND APPROVED BY DMVA ENGINEERING PRIOR TO INSTALLATION.
3. ACTUATOR ACT-1 MODEL NUMBER DEPENDS ON DEVICE SIZE. INSTALL PROPERLY SIZED TORQUE ACTUATOR BASED ON MANUFACTURER'S RECOMMENDATIONS.
1. PRIOR TO ANY INSTALLATION OF DDC EQUIPMENT OR DDC WIRING, CONTRACTOR SHALL REQUEST A DDC PRECONSTRUCTION MEETING WITH DMVA
IN-HOUSE TECHNICIAN TO DISCUSS CONSTRUCTION SCHEDULING, PRECISE DDC EQUIPMENT LOCATIONS, STARTUPS, LABELING PROCEDURES, AND
COMMISSIONING.
2. CONTRACTOR MUST FOLLOW A DDC WIRE COLOR SCHEDULE FOR ALL DDC WIRING INSTALLED. THIS SCHEDULE WILL BE AGREED UPON DURING THE
PRECONSTRUCTION MEETING.
A. WIRE COLOR FOR ALL CONTROL WIRING IS TO BE WHITE.
3. CONTRACTOR TO INSTALL A MINIMUM ¾" CONDUIT FOR ALL DDC WIRING. CONTRACTOR IS ALLOWED TO INSTALL J-HOOKS 4' O.C. FOR DDC
CONTROL WIRING ONLY IN AREAS ABOVE A SUSPENDED CEILING. ALL CONDUIT IN WALLS TO BE STUBBED INTO CEILING SPACE.
A. ALL EXPOSED WIRE IS TO BE IN CONDUIT
B. HIDDEN WIRE CAN BE RUN IN BRIDAL RINGS
4. CONTRACTOR SHALL PULL ALL DDC WIRING AS SHOWN ON DDC FLOOR PLAN AND DDC EQUIPMENT SCHEDULE. ALL WIRES SHALL BE LABELED WITH A
LABEL MAKER APPROVED BY DMVA ENGINEERING. NO HAND WRITTEN LABELS WILL BE ALLOWED. ALL LABELS LOCATED IN ENCLOSURE ENC-1 MUST
BE PLACED 6" DOWN ON WIRE ONCE INSIDE THE ENCLOSURE, DO NOT LOCATE LABEL AT THE END OF WIRE.
5. ALL INPUT/OUTPUT CONTROL WIRES TO BE LON RATED, SEE SPECIFICATIONS.
6. DDC SEQUENCE AND PROGRAMMING WILL BE COMPLETED BY CONTROLS CONTRACTOR.
7. INSTALL TEMPERATURE SENSORS, TEMP-1, 60" AFF.
8. INSTALL OCCUPANCY SENSORS, OCC-1, 6" FROM CEILING.
9. INSTALL OAT-1 ON NORTH FACING EXTERIOR WALL OUT OF DIRECT SUNLIGHT AND CLEAR OF ANY LOUVERS, DOORS OR OPERABLE WINDOWS; MAKE
WEATHERTIGHT.
10. PRINT COPY OF DDC WIRE COLOR SCHEDULE AND SCHEMATIC AND SECURE TO THE BACK OF THE DOOR IN ENC-1.
11. PROVIDE AND INSTALL ALL END DEVICES SHOWN.
12. CONTROL WIRING TO BE TERMINATED AT END DEVICES AND BROUGHT INTO CONTROL PANEL, TEMERANTED AND LABLED.
F
IL
E N
U M
B E
R
S T
A T
E I
N D
E X
N U
M B
E R
S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
TR
U
C
TI
O N
D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T
A N
D B
U D
G E
T S
T A
T E
O F
M
IC
H
IG
A N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
3F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O N
E
.4
.5
6F
A X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
T E
M P
E R
A T
U R
E C
O N
T R
O L S
D E
T A
IL
S
A N
D S
C H
E D
U L E
S
-1
.0
M
J U
N E
M
ID
L A
N D
A R
M O
R Y
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
A
IR
P
O R
T R
O A
D
M
ID
L A
N D
M
I
D E
P A
R T
M E
N T
O F
M
IL
IT
A
R Y
A N
D V
E T
E R
A N
'S A
F F
A
IR
S
/2
.C
A K
/1
/2
ISSUED FOR DATE
SCALE: NONE
DDC PANEL DETAIL
EXISTING TEMPERAURE CONTROL PANEL (FOR REFERENCE ONLY)
PC
WF
OSS
S 33S
TCP
FIRE ALARM SYMBOLS
NOTES:
RECEPTACLE SYMBOLS
DH
FS
SD
SD
HD
DD
F
V
BD
V
F
F
RT
SPD
OSY
P
J
LC
T
R
C
G
M
S F
SLV-a
SP
SD
3KS
S
SK
S
S
SS
4KS
MAGNETIC DOOR HOLDER
FIRE ALARM SMOKE DETECTOR - DUCT TYPE
FIRE ALARM SMOKE DETECTOR - CEILING TYPE
FIRE ALARM HEAT DETECTOR - CEILING TYPE
FIRE ALARM DUCT DETECTOR REMOTE TEST STATION
FIRE ALARM MANUAL PULL STATION
SPRINKLER VALVE MONITOR SWITCH
SPRINKLER SYSTEM FLOW SWITCH
FIRE ALARM ANNUNCIATOR PANEL REMOTE - FLUSH MTD.
FIRE ALARM - VISUAL ALARM, CANDELA INDICATED
FIRE ALARM CONTROL PANEL - FLUSH MTD.
FIRE ALARM AUDIO/VISUAL ALARM, WALL MTD., CANDELA INDICATED
FIRE ALARM - BELL
FACP
FIRE SHUTTER
SMOKE/FIRE DAMPER, PROVIDE WITH DUCT DETECTOR AND 120V POWER
SURGE PROTECTION DEVICE
MOTOR - HP AS INDICATED
BUSSMANN "SSU" W/FUSES
COMBINATION DISCONNECT/MAGNETIC MOTOR STARTER
DISCONNECT SWITCH - UNFUSED
DISTRIBUTION PANELBOARD
MOTOR CONTROL CENTER
PANELBOARD
SWITCH
FUSE
POWER FACTOR CORRECTION CAPACITOR
CIRCUIT BREAKER
60" TO TOP
72" TO TOP
72" TO TOP
90" TO TOP
72" TO TOP
PULL BOX - SIZE AND TYPE AS REQUIRED
JUNCTION BOX - SIZE AND TYPE AS REQUIRED
80"
80"
40"
60"
MOUNT DEVICES AT HEIGHTS INDICATED UNLESS INDICATED
OTHERWISE ON PLANS. HEIGHTS ARE TO BOTTOM OF DEVICE.
RELAY
CONTACTS - NORMALLY CLOSED
CONTACTS - NORMALLY OPEN
TRANSFORMER
LIGHTING CONTACTOR
PUSH-BUTTON STATION - 2 HOLE
PUSH-BUTTON STATION - 1 HOLE
EMERGENCY MUSHROOM HEAD PUSH-BUTTON STATION - 1 HOLE
SYSTEM GROUND - REFER TO SPECIFICATIONS
40"
40"
40"
COIL
CURRENT TRANSFORMER
THERMAL OVERLOADS
INDICATOR LIGHT (R=RED, G=GREEN, B=BLUE, Y=YELLOW, A=AMBER)
DUPLEX RECEPTACLE - WITH GFI
DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - WET LOCATION ENCLOSURE WITH GFI
DUPLEX RECEPTACLE - FOR ELECTRIC WATER COOLER, WITH GFI
WP
GFI
24"
HAND/HAIR DRYER
DUPLEX RECEPTACLE
HD
16"
DUPLEX RECEPTACLE - EMERGENCY
SPECIAL PURPOSE RECEPTACLE
MANUAL MOTOR STARTER WITH PILOT LIGHT 40"
LOW VOLTAGE CONTROL SWITCH, REFER TO DETAIL
SWITCH AND PILOT LIGHT
DIMMER SWITCH (NON-SYSTEM TYPE) 0-10 ELV DIMMER
THREE-WAY SWITCH
SINGLE POLE SWITCH
FOUR-WAY SWITCH
KEY OPERATED, SINGLE POLE SWITCH
KEY OPERATED, THREE-WAY SWITCH
40"
EXIT SIGN - CEILING MOUNTED
EXTERIOR POLE LIGHT
PHOTOCONTROL
OCCUPANCY SENSOR (SET TO VACANCY MODE) - SWITCH MOUNTED
EWC
TRANSFORMER
DUAL SINGLE POLE SWITCH
CIRCUIT BREAKER - ELECTRONIC TRIPET
CEILING FAN
CEILING FAN SPEED CONTROL 40"
OS
OS
OCCUPANCY SENSOR (SET TO VACANCY MODE) CEILING MOUNTED
OCCUPANCY SENSOR (SET TO VACANCY MODE) - WALL MOUNTED
FIRE ALARM - VISUAL ALARM, CEILING MTD., CANDELA INDICATED
FIRE ALARM AUDIO/VISUAL ALARM, CEILING MTD., CANDELA INDICATED
DUPLEX RECEPTACLE - 4" ABOVE COUNTER BACKSPLASH
FLOOR DUPLEX RECEPTACLE
HUBBELL #BA253641, w/ #SFA3925 COVER
STROBE PANELNAC 72" TO TOP
FAA
DISCONNECT SWITCH - FUSED
PUSH-BUTTON STATION - 3 HOLE 40"
DUAL THREE-WAY SWITCH
KEY OPERATED, FOUR-WAY SWITCH
M ELECTRIC METER
EXIT SIGN - WALL MOUNTED
16"
BEAM DETECTOR
TEMPERATURE CONTROL PANEL 72" TO TOP
VARIABLE FREQUENCY DRIVEVFD
S FIRE ALARM SPEAKER
40"
40"
40"
40"
40"
40"
40"
40"
40"
40"
40"
88"
LOCAL, NON-SYSTEM 0-10V DIMMING CONTROLLER, SEE DETAILD A 40"
GFI GFCI REMOTE TRIP DEVICE, CONNECT NEARBY OUTLET TO LOAD SIDE 40"
DUPLEX RECEPTACLE - SURFACE MOUNTED #WM500
RECEPTACLES VARIATIONS - HEIGHT PER ABOVE UNLESS INDICATED ON DRAWINGS:
RECTANGULAR LIGHT FIXTURE
RECTANGULAR EMERGENCY LIGHT FIXTURE ON EMERGENCY
POWER, SWITCHABLE
DOWNLIGHT WALL WASH FIXTURE
WALL MTD. LIGHT FIXTURE
DOWNLIGHT FIXTURE
INDUSTRIAL LIGHT FIXTURE
DOWNLIGHT FIXTURE - EMERGENCY, SWITCHABLE
ELECTRICAL…