511.21085.MAA_Addendum #2 ALL DOCUMENTS.pdf
PDF 5 MB Posted
- Attached to
- 511/21085. MAA; Midland Armory Construction
- Solicitation number
- RFQ - 171 - 230000000626
- Issued by
- Lenawee County, Michigan
About this file
This document is an Addendum related to a state and local contract opportunity for the Midland Armory Construction project, issued by the State of Michigan Department of Military and Veterans Affairs (DMVA).
The Addendum includes changes to the original Bidding Documents and previously issued addenda. It covers revisions to the HVAC Instrumentation and Controls specification, responses to RFI questions on fencing, lighting, and electrical, and changes to various drawings including clarification of general notes, addition of WWR to concrete, correction of demo notes, and revisions to door frame materials and countertop finishes. The bid due date is June 30, 2023, and the project involves the construction of an administrative, supply, and classroom addition to the existing Midland Armory facility. The contract will be awarded by the State of Michigan.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Nurturing curiosity through design since 1953 • towerpinkster.com
©2023 Tower Pinkster Titus Associates, Inc.
ADDENDUM NO. 2
DATE OF ISSUANCE: August 16, 2023
PROJECT: Midland Armory – Construct Admin. / Supply / Classroom Addition
2847 Airport Road
Midland, MI 48460
OWNER: State of Michigan – Department of Military and Veterans Affairs
ARCHITECT’S PROJECT NO.: 26C1020004 (DMVA) / 511/21085.MAA (DTMB) / 21-139.00 (TPTA)
ORIGINAL BID ISSUE DATE: June 30, 2023
SCOPE OF WORK
This Addendum includes changes to, or clarifications of, the original Bidding Documents and any previously issued addenda, and shall be included in the Bid. All of these Addendum items form a part of the Contract Documents. The Bidder shall acknowledge receipt of this Addendum in the appropriate space provided on the Bid Form. Failure to do so may result in disqualification of the Bid.
DOCUMENTS INCLUDED IN THIS ADDENDUM
This Addendum includes four (4) pages of text and the following documents:
• Bidding Documents: None
• Contract Conditions: None
• Specification Sections: 23 0900
• Bid RFI’s 6 - 9
• Drawings: G002, C601, AD101, A200, A321, A501, A621, ED 010, ES 010, E 201
CHANGES TO PREVIOUSLY ISSUED ADDENDA
Issuing missing sheet A501.
CHANGES TO BIDDING REQUIREMENTS
ADD-2 Item No. B-1 - NONE
X.
CHANGES TO CONTRACT CONDITIONS
ADD-2 Item No. C-1 - NONE
X.
8.16.2023 Addendum No. 2 // Midland Armory Addition & Remodeling // 21-139.00 2
CHANGES TO SPECIFICATIONS
ADD-2 Item No. S-1 - 23 0900 – HVAC Instrumentation and Controls
Refer to Specification Section: 23 0900 (Attached with the following changes made)
Part 1.B – Summary – Revised programming to be by contractor instead of owner.
Part 2 – Section 2.1 (Items G-M) – Added additional requirements for BAS software development.
Part 2 – Section 2.2A – Added approved contractors.
BID RFI QUESTIONS
ADD-2 QUESTION 6: in Addendum # 1 under documents included in this Addendum Bullet #6, there are (2) two sheets of A 351, but no sheet A501. Please send sheet A501.
ADD-2 RESPONSE 6: See Attached Sheer A501 which has Clouded information for both Addendum 1 and 2.
ADD-2 QUESTION 7: There are some discrepancies between the drawings and specs that need clarification with regards to fencing. It appears the drawings are more in keeping with armed service specification and the specification #32 3113 is lighter duty.
ADD-2 RESPONSE 7: The Contractor should base their costs on the details provided on sheet C6.2. (Details were provided by the Armory).
ADD-2 QUESTION 8: Within the electrical section, E001 General lighting notes #3 they refer to “clouds”.
Please clarify what they mean?
ADD-2 RESPONSE 8: Disregard reference to “Clouds”. Project does not have any independently suspended
“Cloud” ceilings.
ADD-2 QUESTION 9: Is MC or luminaire cable approved for use above the hard lid and drop ceiling or do they want conduit to each fixture?
ADD-2 RESPONSE 9: Per the 26 0519.3.1 (H) spec, Type MC cable may be used for light fixture whips only, with a maximum length of 6 feet.
CHANGES TO DRAWINGS
ADD-2 Item No. D-1 - Clarified General Note 18.
Refer to Sheet(s): G002
8.16.2023 Addendum No. 2 // Midland Armory Addition & Remodeling // 21-139.00 3
ADD-2 Item No. D-2 - Added WWR to concrete walks.
Refer to Sheet(s): C601
Added welded wire reinforcing to concrete pavement sections
ADD-2 Item No. D-3 - Corrected Demo Note 15
Refer to Sheet(s): AD101
Revised Demo note 15 to reference Shelving Units not Lockers.
ADD-2 Item No. D-4 - Clarified Type (s) of wall(s) being demolished
Refer to Sheet(s): AD101
Added notes clarifying the wall construction being removed.
ADD-2 Item No. D-5 - Clarified Vestibule 200 and 212 Ceiling(s)
Refer to Sheet(s): A201
Coordinated annotation with graphics and enlarged detail at vestibule ceilings.
ADD-2 Item No. D-6 - Clarified width of horizontal perimeter insulation
Refer to Sheet(s): A321
On wall Section 1/A321 clarified the width of horizontal slab insulation as 2’-0” (Typ)
ADD-2 Item No. D-7 - Corrected Ex. Vault door frame material
Refer to Sheet(s): A501
Revised frame material of ex. reused vault door from Aluminum to Steel.
ADD-2 Item No. D-8 - Missing sheet referenced in Addendum 1 Provided.
Refer to Sheet(s): A501
Providing sheet A501 which was referenced but errantly not provided in Addendum 1.
8.16.2023 Addendum No. 2 // Midland Armory Addition & Remodeling // 21-139.00 4
ADD-2 Item No. D-9 - Corrected Countertop Material
Refer to Sheet(s): A621
Revised countertop material annotation from SS-1 to SSM-1
ADD-2 Item No. D-10 - Expanded Elevation
Expanded Elevation to include Women’s lockers. Added 3” filler strip.
ADD-2 Item No. D-11 - Added Plan Enlargement of Lactation Room
Added enlarged plan of Lactation Room in order to indicate added soap dispenser and paper towel dispenser.
ADD-2 Item No. D-12 - Added Exit Signs
Refer to Sheet(s): E201
Added exist signs to Corridors 201, 213, 220, and 220B.
ADD-2 Item No. D-13 - Existing Feeders to FMS Building
Refer to Sheet(s): ED010 & ES010
Added existing feeder to the FMS building to be disconnected from the existing transformer and rerouted to the new transformer location.
END OF ADDENDUM.
PROJECT NO. 21139.00 HVAC INSTRUMENTATION AND CONTROLS
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 1
DEPARTMENT OF MILITARY AND VETERAN'S AFFAIRS 6/30/2023
[Copyright] 2023 Tower Pinkster Titus Associates - All Rights Reserved
SECTION 23 0900 - HVAC INSTRUMENTATION AND CONTROLS
PART ONE - GENERAL
PART 1 - SUMMARY
A. This Section includes control equipment for HVAC systems and components.
B. The Main HVAC Control Unit shall be installed and Programmed by the contractor.
The contractor shall also provide and install all other components including end devices and wire to each of the points shown on DRAWING SHEETS M601 thru M603 and specified in this specification.
1.2 SUBMITTALS
A. Product Data: For each control device indicated.
1. Submittals shall be marked with Part Number.
B. Shop Drawings:
1. Schematic flow diagrams.
2. Power, signal, and control wiring diagrams.
3. Details of control panel faces.
4. Damper schedule.
5. Valve schedule.
6. DDC System Hardware: Wiring diagrams, schematic floor plans, and schematic control diagrams.
C. Field quality-control test reports.
D. Operation and maintenance data.
1.3 QUALITY ASSURANCE
A. The HVAC Control System shall be furnished, and installed by Licensed Trade Technicians.
The contractor shall be an Echelon Certified Network Integrator or LonWorks Integrator. The contractor shall employ technicians who have completed Echelon factory authorized training.
The contractor shall employ technicians to provide instruction, routine maintenance, and emergency service within 24 hours upon receipt of request.
B. The manufacturer of the hardware and software components must be primarily engaged in the manufacture of Lonworks based systems as specified herein, and must have been so for a minimum of three (3) years.
C. The manufacturer of the hardware and software components as well as its subsidiaries must be a member in good standing of the LonMark Organization.
D. The manufacturer of the hardware and software components shall have an authorized
8-16-2023
SEE ADDENDUM 2 FOR EDITS
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 2
representative capable of providing service and support as referenced in section B above, and must have done so for a minimum of three (3) years.
E. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
1.4 ACCEPTANCE PROCEDURE
A. Upon completion of the installation, Contractor shall start-up the system and perform all necessary calibration and testing to ensure proper operation of the project control systems.
B. Schedule a hardware demonstration and system acceptance test in the presence of the
Contracting Officer and/or the Engineer. The acceptance testing is defined as demonstrating the sequence of operation as indicated in the drawings. The hardware demonstration is specified in this Section. The Contractor shall perform all tests prior to scheduling the acceptance test and hardware demonstration to insure the overall system is ready for inspection and observations.
C. When the system performance is deemed satisfactory in whole or in part by these observers, the system parts will be accepted for beneficial use and be deemed substantially complete as defined in Division 1.
1.5 WARRANTY
A. The HVAC Control System shall be free from defects in workmanship and material under normal use and service. If within eighteen (18) months from the date of substantial completion, the installed equipment is found to be defective in operation, workmanship or materials, the building systems contractor shall replace, repair or adjust the defect at no cost. Service shall be provided within 4 hours upon notice from Owner’s designated Representative.
B. The warranty shall extend to material that is supplied and installed by the Contractor. Material supplied but not installed by the Contractor shall be covered per the above to the extent of the product only. Installation labor shall be the responsibility of the trade contractor performing the installation.
1.6 PRODUCT DELIVERY, STORAGE AND HANDLING
A. Do not install electronic hardware in the project until non-condensing environmental conditions have been established. Products installed in violation of this request maybe requested to be replaced at no additional cost to the project.
B. Coordinate storage requirements for factory mounted terminal control units on air terminal devices, air handling units or other packaged control equipment. Do not store control units on site in non-conditioned areas for more than two weeks.
C. Factory-Mounted Components: Where control devices specified in this section are indicated to be factory mounted on equipment, arrange for shipping control devices to unit manufacturer.
PART TWO – PRODUCTS
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 3
2.1 PRODUCTS GENERAL
A. All products (PROGRAMMABLE CONTROLLER’s, TDCU’s and ID’s) shall contain ANSI
EIA 709.1 LonTalk Protocol networking elements to allow ease of integration of devices from multiple vendors.
B. All materials, equipment and software shall be standard components, regularly manufactured for this and other systems and custom designed for this project. All systems and components shall be thoroughly tested.
C. Control system components shall be new and in conformance with the following applicable standards for products specified:
1. LonMark certified, and LNS Based.
2. ANSI EIA 709.1 LonTalk Protocol
D. Utilize standard PC components for all assemblies. Custom hardware, operating system, and utility software are not acceptable.
E. All products (PROGRAMMABLE CONTROLLER’s, TDCU’s and ID’s) shall contain ANSI
EIA 709.1 LonTalk Protocol networking elements to allow ease of integration of devices from multiple vendors.
F. All materials, equipment and software shall be standard components, regularly manufactured for this and other systems and custom designed for this project. All systems and components shall be thoroughly tested.
G. The BAS database shall be developed utilizing a LonWorks LNS network software tool. This software tool shall be Circon Systems (EBAC) Network Integrator.
H. All database development must be performed with this LNS tool including controller and component population of the database, programming, data bindings and commissioning.
I. LNS “Plug-ins” must be available, and furnished with the database, for configuration and programming of the main systems controllers.
J. At completion of the project, a complete LNS database backup must be furnished to the owner that includes all programming files and data bindings (peer-to-peer data shared between controllers). Imbedded within the LNS database backup shall be a database backup of the
CatNet Web server.
K. All passwords, software tools, or other items required for the Owner to independently operate, access, program, or modify the BAS must be furnished at project completion.
L. Any other database development software, method or type is strictly forbidden.
M. All Source code including any and all relevant files need to be handed over to the State of
Michigan representative at time of commissioning. Include any/all customs function blocks or
UDD needed in order to run the program in real time.
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 4
2.2 PROGRAMMING CONTROL UNIT AND PROGRAMMING SOFTWARE
A. Approved Contractors:
a. J B Electric, Inc.
b. W. J. O’Neil Co.
2.3 OPERATOR’s WORKSTATION
A. The Operators Workstation shall be Laptop
1. Basis of Design: Subject to compliance with requirements provide: Dell Latitude e5530 laptap or approved equal.
a. Operating System - Windows 7 pro.
b. 32bit.
c. 4 GB RAM
d. 120 GB Storage.
e. Screen Size -14” or larger.
f. USB interface for connection capable of connecting with Controller by owner.
g. Ethernet port.
h. All software required for system shall be installed on laptop for owner.
i. Coordinate software requirements with DMVA control technicians.
2.4 PROGRAMABLE UNIT CONTROLLERS (DDC-1)
A. Basis of Design, subject to requirements provide products indicated on the DRAWINGS or pre-approved equal.
2.5 TRANSFORMER (T-1)
1. Provide with outlet.
2.6 DDC ENCLOSURE (ENC-1)
1. Provide with slotted wire duct and din rails as indicated on DRAWINGS.
2. Coordinate with DMVA Control Technicians for Control Unit Mounting.
2.7 TEMPERATURE SENSORS AND TRANSMITTERS (TEMP#) (OAT-1)
2.8 CO2 SENSOR (CO2-1)
2.9 FREEZESTAT (FR-1)
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 5
2.10 VALVE ACTUATORS (ACT-1)
2.11 THERMOWELLS
A. When thermowells are required, the sensor and well shall be supplied as a complete assembly including well head and greenfield fitting.
B. Thermowells shall be pressure rated and constructed in accordance with the system working pressure
C. Thermowells and sensors shall be mounted in a threadolet or 1/2" NPT saddle and allow easy access to the sensor for repair or replacement.
D. Thermowells shall be constructed of the following materials:
1. Chilled and Hot Water; brass.
2.12 CURRENT TRANSFORMERS
A. The current transformers shall be designed to be installed or removed without dismantling the primary bus or cables. The transformer shall be of a split core design.
B. The core and windings shall be completely encased in a UL approved thermoplastic rated
94VA. No metal parts shall be exposed other than the terminals.
C. The current transformers shall meet the following specifications:
1. Frequency Limits: 50 to 400 Hz.
2. Insulation: 0.6 KV Class, 10 KV BIL.
3. Accuracy: 1% at 5.0 to 25.0 VA accuracy class with U.P.F. burden.
4. Provide a disconnect switch for each current transformer.
2.13 ELECTRICAL CONTROL POWER AND LOW VOLTAGE WIRING
A. Provide interlock wiring between supply and exhaust fans, electrical wiring for relays
(including power feed) for temperature and pressure indication.
B. Provide power wiring, conduit and connections for low temperature thermostats, high temperature thermostats, alarms, flow switches, actuating devices for temperature, humidity, pressure and flow indication, point resets and user disconnect switches for electric heating, appliances controlled by this Section.
C. Provide all other wiring required for the complete operation of the specified systems.
D. Install all wiring raceway systems complying with the requirements of the National Electrical
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 6
Code. All installations shall be installed in EMT.
E. Network Communication Requirements
1. Wired network communication shall be via channels consisting of a 22 AWG twisted pair installed in a 3/4 EMT. Echelon approved wire only
2. In all communication conduits, provide one spare twisted pair to be installed, tagged and labeled at each end.
3. Communication conduits shall not be installed closer than six feet from high power transformers or run parallel within six feet of electrical high power cables. Care shall be taken to route the cable as far from interference generating devices as possible.
4. All shields shall be ground (earth ground) at one point only, to eliminate ground loops.
5. There shall be no power wiring, in excess of 30 VAC rms, run in conduit with communications wiring. In cases where signal wiring is run in conduit with communication wiring, all communication wiring and signal wiring shall be run using separate twisted shielded pairs (22awg) with the shields grounded in accordance with the manufacturer’s wiring practices.
F. Input/Output Control Wiring
1. RTD wiring shall be two-wire or four-wire twisted, shielded, minimum number 18 gauge.
2. Other analog inputs shall be a minimum of number 18 gauge, twisted, shielded.
3. Binary control function wiring shall be a minimum of number 18 gauge.
4. Analog output control functions shall be a minimum of number 18 gauge, twisted, shielded.
5. Binary input wiring shall be a minimum of number 18 gauge.
6. Control wiring color: White.
G. Splices
1. Splices in shielded cables shall consist of terminations and the use of shielded cable couplers, which maintain the integrity of the shielding. Terminations shall be in accessible locations. Cables shall be harnessed with cable ties as specified herein.
H. Conduit and Fittings
1. Conduit for Control Wiring, Control Cable and Transmission Cable: Electrical metallic tubing (EMT) with compression fittings, cold rolled steel, zinc coated or zinc-coated rigid steel with threaded connections, Minimum size ¾”.
2. Outlet Boxes (Dry Location): Sheradized or galvanized drawn steel suited to each application, in general, four inches square or octagon with suitable raised cover.
3. Outlet Boxes (Exposed to Weather): Threaded hub cast aluminum or iron boxes with gasket device plate.
4. Pull and Junction Boxes: Size according to number, size, and position of entering raceway as required by National Electrical Codes. Enclosure type shall be suited to location.
I. Relays
1. Relays other than those associated with digital output cards shall be general purpose, enclosed plug-in type with 8-pin octal plug and protected by a heat and shock resistant duct cover. Number of contacts and operational function shall be as required.
J. Solid State Relays (SSR): Input/output isolation shall be greater than lOE9 ohms with a breakdown voltage of 1500V root mean square or greater at 60 Hz. The contact life shall be 10
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 7
x 10 E6 operations or greater. The ambient temperature range of SSRs shall be -20 to +140F.
Input impedance shall not be less than 500 ohms. Relays shall be rated for the application.
Operating and release time shall be for 100 milliseconds or less. Transient suppression shall be provided as an integral part of the relay.
K. Contactors: Contactors shall be of the single coil, electrically operated, mechanically held type. Positive locking shall be obtained without the use of hooks, latches, or semi permanent magnets. Contractor shall be double-break-silver-to-silver type protected by arcing contacts.
The number of contacts and rating shall be selected for the application. Operating and release times shall be 100 milliseconds or less. Contactors shall be equipped with coil transient suppression devices.
2.14 IDENTIFICATION
A. Automatic Control Valve Tags
1. For valves, etc., use metal tags with a 2-inch minimum diameter, fabricated of brass, stainless steel or aluminum. Attach tags with chain of same materials. For lubrication instructions, use linen or heavy duty shipping tag.
2. Tag valves with identifying number and system. Number valves by floor level, column location and system served.
3. Prepare lists of all tagged valves showing location, floor level, and tag number, use.
Prepare separate lists for each system. Include copies in each maintenance manual. And post in boiler room.
B. Wire Tags
1. All multi-conductor cables in pull boxes, at end devices, controllers and terminal strip cabinets shall be labeled.
2. Provide wire Tags as per Division 16.
C. Conduit Tags
1. Provide tagging or labeling of conduit so that it is always readily observable which conduit was installed or used in implementation of this Work.
D. Miscellaneous Equipment Identification
1. Screwed-on, engraved black lamicoid sheet with white lettering on all control panels and remote processing panels. Lettering sizes subject to approval.
2. Inscription, subject to review and acceptance, indicating equipment, system numbers, functions and switches. For panel interior wiring, input/output modules, local control panel device identification.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verify that systems are ready to receive work.
B. Beginning of installation means installer accepts existing conditions.
C. The project plans shall be thoroughly examined for control device and equipment locations, and any discrepancies, conflicts, or omissions shall be reported to the Architect/Engineer for
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 8
resolution before rough-in work is started.
D. The contractor shall inspect the site to verify that equipment is installable as show, and any discrepancies, conflicts, or omissions shall be reported to the Architect/Engineer for resolution before rough-in work is started.
E. The Control System Contractor shall examine the drawings and specifications for other parts of the work, and if head room or space conditions appear inadequate or if any discrepancies occur between the plans and his work and the plans for the work of others, he shall report such discrepancies to the Architect/Engineer and shall obtain written instructions for any changes necessary to accommodate his work with the work of others.
3.2 GENERAL INSTALLATION REQUIREMENTS
A. Install all control components in accordance with manufacturer's instructions and recommendations.
B. Mount control panels adjacent to associated equipment on vibration-free walls or freestanding angle iron supports. One cabinet may accommodate more than one system in same equipment room. Provide nameplates for instruments and controls inside cabinet and nameplates on cabinet face.
C. After completion of installation, test and adjust control equipment. Submit data showing setpoints and final adjustments of controls.
D. Install equipment, piping, wiring/conduit parallel to building lines (i.e., horizontal, vertical, and parallel to walls) wherever possible.
E. Provide sufficient slack and flexible connections to allow for vibration of piping and equipment.
F. Verify integrity of all wiring to ensure continuity and freedom from shorts and grounds.
G. All equipment, installation, and wiring shall comply with acceptable industry specifications and standards for performance, reliability, and compatibility and be executed in strict adherence to local codes and standard practices.
3.3 ELECTRICAL SYSTEM INSTALLATION
A. Install all low voltage power and LON and LAN communication trunks in conduit regardless of local building code allowances otherwise.
B. Conceal conduit within finished shafts, ceilings and wall as required. Install exposed conduit parallel with or at right angles to the building walls.
C. Where Class 2 wires are in concealed and accessible locations including ceiling return air plenums, approved cables not in raceway may be used provided that:
1. Circuits meet NEC Class 2 (current-limited) requirements. (Low-voltage power circuits shall be sub-fused when required to meet Class 2 current-limit.)
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 9
2. All cables shall be UL listed for application, i.e., cables used in ceiling plenums shall be
UL listed specifically for that purpose.
D. All wire-to-device connections shall be made at a terminal blocks or terminal strip. All wire-to-wire connections shall be at a terminal block, or with a crimped connector. All wiring within enclosures shall be neatly bundled and anchored to permit access and prevent restriction to devices and terminals.
E. Plug or cap all unused conduit openings and stub-ups. Do not use caulking compound.
F. Route all conduit to clear beams, plates, footings and structure members. Do not route conduit through column footings or grade beams.
G. Set conduits as follows:
1. Expanding silicone fire stop material sealed watertight where conduit is run between floors and through walls of fireproof shaft.
2. Oakum and lead, sealed watertight penetration through outside foundation walls.
H. Cap open ends of conduits until conductors are installed.
I. Where conduit is attached to vibrating or rotating equipment, flexible metal conduit with a minimum length of 18 inches and maximum length of 36 inches shall be installed and anchored in such a manner that vibration and equipment noise will not be transmitted to the rigid conduit.
J. Where exposed to the elements or in damp or wet locations, waterproof flexible conduit shall be installed. Installation shall be as specified for flexible metal conduit.
K. Provide floor, wall, and ceiling plates for all conduits passing through walls, floors or ceilings.
Use prime coated cast iron, split-ring type plates, except with polished chrome-plated finish in exposed finished spaces.
3.4 TEMPERATURE SENSORS
A. Temperature sensor assemblies shall be readily accessible and adaptable to each type of application in such manner as to allow for quick, easy replacement and servicing without special tools or skills.
B. Strap-on mountings shall not be permitted.
C. Outdoor installations shall be; of weatherproof construction or in appropriate NEMA enclosures. These installations shall be protected from solar radiation and wind effects.
Protective shield shall be stainless steel.
D. Sensors shall be with enclosure where located in finished space.
E. Sensors in ducts shall be mounted in locations to sense the correct temperature of the air only and shall not be located in dead air spaces or positions obstructed by ducts, equipment, and so
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 10
forth. Locations where installed shall be within the vibration and velocity limit of the sensing element. Ducts shall be securely sealed where elements or connections penetrate ducts to avoid measuring false conditions.
F. All sensors measuring temperatures in pipes larger than 2 inches in diameter or in pressure vessels shall be supplied with wells properly fabricated for the service. Wells shall be noncorrosive to the medium being measured and shall have sufficient physical strength to withstand pressures and velocities to which they are subjected. Wells shall be installed in the piping at elbows where piping is smaller than the length of the well to affect proper flow across the entire area of the well.
3.5 ACTUATORS
A. Mount and link control damper actuators per manufacturer's instructions.
B. Valves - Actuators shall be mounted on valves with adapters approved by the actuator manufacturer. Actuators and adapters shall be mounted following manufacturer's recommendations.
3.6 IDENTIFICATION OF HARDWARE AND WIRING
A. All wiring and cabling including that within factory-fabricated panels shall be labeled at each end within 2" of termination with a cable identifier and other descriptive information.
B. Permanently label or code each point of field terminal strips to show the instrument or item served.
C. Identify control panels with minimum 1 inch letters on nameplates.
D. Identify all other control components with permanent labels. Identifiers shall match record documents.
E. Identify room sensors relating to terminal box or valves with nameplates.
3.7 CLEANING
A. This contractor shall clean up all debris resulting from his or her activities daily. The contractor shall remove all cartons, containers, crates, etc. under his control as soon as their contents have been removed. Waste shall be collected and placed in a location designated by the Construction
Manager or General Contractor.
B. At the completion of work in any area, the Contractor shall clean all of his/her work, equipment, etc., making it free from dirt and debris, etc.
C. At the completion of work, all equipment furnished under this Section shall be checked for paint damage, and any factory-finished paint that has been damaged shall be repaired to match the adjacent areas. Any metal cabinet or enclosure that has been deformed shall be replaced with new material and repainted to match the adjacent areas.
MIDLAND ARMORY ADDITION & REMODELING 23 0900 - 11
3.8 PROTECTION
A. The Contractor shall protect all work and material from damage by his/her work or workers, and shall be liable for all damage thus caused.
B. The Contractor shall be responsible for his/her work and equipment until finally inspected, tested, and accepted. The Contractor shall protect his/her work against theft or damage, and shall carefully store material and equipment received on-site that is not immediately installed.
The Contractor shall close all open ends of work with temporary covers or plugs during storage and construction to prevent entry of foreign objects.
3.9 FIELD QUALITY CONTROL
A. All work, materials and equipment shall comply with the rules and regulations of applicable local, state, and federal codes and ordinances as identified in Part 1 of this Section.
B. Contractor shall continually monitor the field installation for code compliance and quality of workmanship. All visible piping and/or wiring runs shall be installed parallel to building lines and properly supported.
C. Contractor shall arrange for field inspections by local and/or state authorities having jurisdiction over the work.
3.10 CHECK OUT, START UP AND TESTING
A. The control system shall be properly commissioned prior to acceptance. The Contractor shall coordinate with others (including mechanical, electrical and test and balance) to properly start up and verify the operation of the system. Provide as-built documentation as detailed in Part 1 of this Section.
3.11 ACCEPTANCE
A. The control systems will not be accepted as meeting the requirements of Completion until all tests described in this specification have been performed to the satisfaction of both the
Engineer and Owner. Any tests that cannot be performed due to circumstances beyond the control of the Contractor may be exempt from the Completion requirements if stated as such in writing by the Owner's representative. Such tests shall then be performed as part of the warranty.
END OF SECTION 23 0900
A101A
TYPICAL SYMBOLS & REFERENCES
NOTE:
ROOM NAMES AND NUMBERS ON PLANS ARE
FOR CONSTRUCTION PURPOSES ONLY.
COORDINATE WITH OWNER REGARDING
PROPOSED NUMBERS FOR ALL SIGNAGE,
SCHEDULE AND PANEL DESIGNATIONS.
ROOM IDENTIFICATION TAG
ROOM NAME
ROOM NUMBER
DETAIL TITLE
1 DETAIL TITLE
1" = 0'-1"A101
DETAIL NUMBER
SHEET NUMBER
UNIT MATCHLINES
U N
IT
A
U N
IT
B
TYPICAL NOTATION SYMBOLS
CALLOUT REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
EXTERIOR ELEVATION REFERENCE BUBBLE
A301
A
ELEVATION LETTER
SHEET NUMBER
INTERIOR ELEVATION REFERENCE BUBBLE
4 A 652
ELEVATION NUMBER
SHEET NUMBER
DETAIL REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
BUILDING SECTION REFERENCE BUBBLE
A 311
DETAIL NUMBER
SHEET NUMBER
ELEVATION AND SECTION REFERENCE TOOLS
ELEVATION TAG - EXISTING
FINISH FLOOR
ELEVATION 100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
100'-0" ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
ELEVATION TAG - NEW
FINISH FLOOR
ELEVATION 100'-0"
100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
WORKING POINT LAYOUT TAG
100'-0" : 100'-0"
DISTANCE IN THE "Y" DIRECTION FROM THE
"X" BASE LINE
DISTANCE IN THE "X" DIRECTION FROM THE
"Y" BASE LINE
BORROWED LIGHT AND DOOR IDENTIFICATION
A 502
SHEET NUMBER
ELEVATION NUMBER
DOOR NUMBER - CORRESPONDS TO THE ROOM NUMBER
LETTER DESIGNATES MORE THAN ONE IN ROOM
SYMBOLS
BARRIER-FREE
B1 REVISION IDENTIFIER (ADDENDUM AND BULLETIN)
COLUMN BUBBLE AND LINE
CLASSROOM
A000A
GENERAL DEMOLITION NOTES
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS
WHICH ARE A PART OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS
AND BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY
AND ALL DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
GENERAL NOTES - ARCHITECTURAL
1. THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT PRIOR
TO COMMENCEMENT OF CONTRACTED DEMOLITION WORK.
2. ALL EXISTING CONDITIONS SHOULD BE FIELD VERIFIED BEFORE WORK BEGINS.
3. DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR TO
THE FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.
4. DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR
CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN QUESTION.
5. EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/DECK ABOVE
UNLESS NOTED OR DETAILED OTHERWISE.
6. WITHIN BUILDING INTERIOR PROVIDE BULLNOSE BLOCK IN CMU WALL ASSEMBLIES AT
ALL EXPOSED OUTSIDE CORNERS, INCLUDING WINDOW AND DOOR JAMBS, UNLESS
NOTED OR DETAILED OTHERWISE. PROVIDE SQUARE OUTSIDE CORNERS AT ALL
LOCATIONS FINISHED WITH WALL TILE, REFER TO FINISH PLANS (A600 SHEETS)
FOR LOCATIONS.
7. TOOTH-IN MASONRY AT NEW OPENINGS IN EXISTING WALLS.
8. TOOTH-IN NEW MASONRY INFILL INTO EXISTING OPENINGS AT ALL BULLNOSE BLOCK
LOCATIONS.
9. STEEL STUD WALLS SHALL BE A MINIMUM OF 20 GAGE. REGARDLESS OF HEIGHT
10. STEEL STUD WALLS SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20 GAGE.
11. DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR DIMENSIONED
OTHERWISE.
12. FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES
AND CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.
13. FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH
FIRE AND/OR SMOKE RATED ASSEMBLIES.
14. FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR
FLOOR PLANS.
15. PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT
FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.
16. PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT OR
ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY MANUFACTURER.
17. PROVIDE ALL ASSOCIATED CURBS FOR ROOF TOP EQUIPMENT AND MECHANICAL
ROOF TOP UNITS. LARGE VOIDS BELOW THE AIR HANDLING UNITS SHALL BE FILLED
WITH INSULATION AS SPECIFIED FOR NOISE CONTROL.
18. ALL EXISTING ROOF TOP PENETRATIONS BEING REMOVED REQUIRE ROOF PATCHING
TO MATCH EXISTING ADJACENT. WORK TO BE DONE IN SUCH MANNER THAT ROOF
WARRANTY IS MAINTAINED.
A2
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD BOTH SIDES;
(1 HOUR FIRE) U.L. ASSEMBLY U465
WHERE NOTED ON PLANS
METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS (AT CHASE
WALLS ONLY) - UNLESS
NOTED OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD ON ROOM SIDE - BRACE
WALL @ 4'-0" O.C. MAXIMUM.
METAL STUD CHASE WALL OR
FURRING
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH
5/8" TYPE "X" GYPSUM BOARD BOTH
SIDES TO DECK
STRUCTURAL METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
FLOOR CONSTRUCTION
METAL CH STUDS @ 16" O.C. WITH 5/8"
TYPE "X" GYPSUM BOARD ON ROOM
SIDE AND 1" TYPE "X" GYPSUM BOARD
PANEL ON CHASE SIDE
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM
BOARD BOTH SIDES
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN ALL
WALLS - UNLESS
NOTED OTHERWISE -
WEAVE IN-BETWEEN
STUDS
FLOOR CONSTRUCTION
6" TOP AND BOTTOM TRACK WITH 3 5/8"
METAL STUD FRAMING @ 16" O.C.
(OFFSET) WITH 5/8" GYPSUM BOARD BOTH
SIDES
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
BOND BEAM
SEALANT
FLOOR CONSTRUCTION
4" CONCRETE MASONRY UNITS
CMU WALL
U.L. ASSEMBLY - U905
(1 HOUR AND 2 HOUR)
HEAD
PLAN
SILL
CMU WALL WITH FURRING CMU WALL WITH FURRING BOTH SIDES
C H A S E S
ID
E
R O
O M
S
ID
E
METAL STUD CHASE WALL (1 HOUR FIRE)
U.L. ASSEMBLY U415
METAL STUD WALL (2 HOUR FIRE)
U.L. ASSEMBLY U425 METAL STUD SOUND WALL
6" CONCRETE MASONRY UNITS
8" CONCRETE MASONRY UNITS
10" CONCRETE MASONRY UNITS
STRUCTURE /
DECK ABOVE
BOND BEAM
FLOOR CONSTRUCTION
STRUCTURE /
DECK ABOVE
BOND BEAM
FLOOR CONSTRUCTION
HEAD
PLAN
SILL
4" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
6" CONCRETE MASONRY UNITS METAL FURRING
AND 5/8" GYPSUM BOARD
8" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
10" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
4" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
12" CONCRETE MASONRY UNITS 12" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD
1X 2X 4X 5X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
FLOOR CONSTRUCTION
METAL CH STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM BOARD
ON ROOM SIDE AND 1" TYPE "X"
GYPSUM BOARD PANEL ON CHASE SIDE
METAL STUD CHASE WALL (2 HOUR FIRE)
U.L. ASSEMBLY U438
6X 7X 8
6" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
8" CONCRETE MASONRY UNITS WITH METAL FURRING
AND 5/8" GYPSUM BOARD - BOTH SIDES
10" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD - BOTH SIDES
12" CONCRETE MASONRY UNITS WITH METAL
FURRING AND 5/8" GYPSUM BOARD - BOTH SIDES
9X
10X
11X
12X
13X
9XX
10XX
11XX
12XX
13XX
SEALANT SEALANT
METAL STUDS @ 16" O.C. WITH
1/2" RATED PLYWOOD ONE SIDE
AND 5/8" GYPSUM BOARD ON
BOTH SIDES.
3X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
1/2" RATED
PLYWOOD
FLOOR CONSTRUCTION
METAL STUD WALL WITH
PLYWOOD BACKING
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
WOOD STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD BOTH SIDES;
(1 HOUR FIRE) U.L. ASSEMBLY U305
WHERE NOTED ON PLANS
WOOD STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
SEALANT
SOUND BATTS IN ALL
WALLS - UNLESS
NOTED OTHERWISE
FLOOR CONSTRUCTION
WOOD STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD ON ROOM SIDE -
BRACE WALL @ 4'-0" O.C. MAXIMUM.
WOOD STUD CHASE WALL
C H A S E S
ID
E
R O
O M
S
ID
E
14X 15X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
WOOD STUDS @ 16" O.C. WITH (2)
LAYERS 5/8" TYPE "X" GYPSUM
BOARD BOTH SIDES
WOOD STUD WALL (2 HOUR FIRE)
U.L. ASSEMBLY U301
16X
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
BOND BEAM
SEALANT
FLOOR CONSTRUCTION
CMU WALL
U.L. ASSEMBLY - U906
(3 HOUR)
8" CONCRETE MASONRY UNITS11
PARAPET
METAL COPING
NOT SHOWN
INTERSECTION OF NON-RATED AT
1 HOUR RATED PARTITION
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U425
1 HOUR RATED
PARTITION - REFER
TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
2 HOUR RATED
PARTITION -
REFER TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U438
2 HOUR RATED
PARTITION -
REFER TO PLAN
CH STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF
CONCRETE/MASONRY AT 1 HOUR
RATED PARTITION
CONCRETE OR MASONRY
WALL - REFER TO PLAN
1 HOUR RATED PARTITION -
REFER TO PLAN
METAL FURRING
GYPSUM BOARD CONTROL
JOINT NON-RATED PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
BACKER
ROD AND
SEALANT
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 1 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
(2) LAYERS TYPE
"X" GYPSUM
BOARD
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 2 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
METAL STUD FRAMING
(2) LAYERS TYPE "X"
GYPSUM BOARD
CONTROL JOINT
(2) LAYERS TYPE
"X" GYPSUM
BOARD
NOTE:
MOUNT EQUIPMENT AS SHOWN UNLESS SPECIFIED OTHERWISE.
MAX TWO DEVICES IN ONE HIGHER MOUNT
LOCATION AT LATCH SIDE OF DOOR, PROVIDE RFI
IF MORE DEVICES ARE NECESSARY. WHERE THERE
IS ONE DEVICE, CENTER OVER LOWER DEVICE. (TO
BE WITHIN ADA HEIGHT). (IF SWITCH CANNOT BE
LOCATED ON LATCH SIDE, LOCATE ONE DOOR
LEAF AWAY ON HINGE SIDE.)
DOOR
LOW DEVICES
RECEPTACLEVOICE/DATA
MASONRY COURSING
(WHERE APPLICABLE)
LIGHT SWITCH
F.A. AUDIO/VISUAL
ALIGNMENT NOTES
• ALIGN AND LOCATE CLOSE TOGETHER ANY DEVICES INSTALLED WITHIN 6' HORIZONTALLY.
• CENTER ALL DEVICES WHERE INDICATED ON COLUMN WRAP OR BUMP OUT; STACK AND ALIGN VERTICALLY.
• INSTALL DEVICES AT HEIGHTS INDICATED IN SYMBOL LEGEND UNLESS STACKING PER THIS DETAIL.
• WHERE HEIGHT IS SPECIFICALLY NOTED ON FLOOR PLANS, USE THAT MOUNTING HEIGHT
• CENTER ON DOORFRAME OR WHITEBOARDS ANY DEVICES INDICATED ABOVE.
O R L
A N D
IN
G
F R O
M F
LO
O
R
F R O
M F
LO
O
R O
R L
A N D
IN
G
6' - 0" MIN.
4" MAX
CAMERAS, CLOCKS, WALL
OCCUPANCY SENSORS
WHITE BOARD (WHERE APPLICABLE -
VERIFY WITH DETAILS/PLANS PROPER
INSTALL HEIGHT) CENTER ANY SINGLE
DEVICE WITH CENTER OF WHITE BOARD
ANY DEVICES
SHOWN OVER DOOR
TO BE CENTERED.
EQ EQ
EQ EQ
F R O
M F
LO
O
R O
R L
A N D
IN
G
SHORT THROW PROJECTOR
WHERE APPLICABLE
~12"
FA PULL STATION - HINGE SIDE
OF DOOR 1-LEAF AWAY WITHIN
5'-0" OF EXTERIOR OR STAIR
DOORS, WHEN WALL MOUNT
STROBES ARE ON PROJECT,
ALIGN ABOVE.
WHEN DEVICES ARE WITHIN DIMENSION, STACK
HIGH/LOW VERTICALLY AND GROUP DEVICES AT
SAME HEIGHT. UNLESS DEVICES IS PART OF
TECHNOLOGY DETAIL GROUPING OR SERVING A
FURNITURE GROUP.
CASEWORK, COORDINATE DEVICE BOTTOM
TO BE 2" OVER BACKSPLASH OR OVER
COUNTERTOP (IF NO BACKSPLASH). FOR
LARGE FORMAT TILE, ALIGN EDGE OF DEVICE
WITH HORIZONTAL GROUT LINE CLOSEST TO
COUNTERTOP.
COORDINATE OUTLET LOCATIONS WITH
GROUT LINES, EDGE OF DEVICE ON GROUT
LINE IF POSSIBLE. COORDINATE WITH
INTERIOR DESIGN DRAWINGS.
TYPICAL COLUMN
ENCLOSURE, CHASE OR
BUMP-OUT WITH DEVICES
INDICATED IN PLANS.
EQ EQ
EQEQEQEQ
THERMOSTAT,
SENSORS OR AV
CONTROLLER, CARD
READER, ETC.
GENERAL PARTITION NOTES
1. NOT ALL WALL TYPES MAY BE USED ON PROJECT.
2. REFER TO CODE COMPLIANCE PLANS FOR LOCATIONS OF SMOKE AND FIRE-RATED
PARTITIONS.
3. ALL PARTITIONS EXTEND TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.
4. LINE OF STRUCTURE/DECK AS SHOWN AT THE HEAD CONDITION OF EACH PARTITION
TYPE IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION
CONDITIONS. TERMINATE RATED PARTITIONS AT UNDERSIDE OF STRUCTURAL DECK TO
MAINTAIN RATING. PROVIDE APPROPRIATE FRAMING AND GYPSUM BOARD TO OFFSET
AROUND STRUCTURE OR OTHER OBSTRUCTIONS, SUCH AS PIPING OR DUCTWORK.
5. PARTITIONS MAY TERMINATE AT STRUCTURAL MEMBERS WITH A RATING GREATER THAN
OR EQUAL THE PARTITION, PROVIDED THAT RATING IS CONTINUOUS TO STRUCTURAL
DECK ABOVE.
6. NON-RATED PARTITIONS THAT EXTEND TO STRUCTURE SHALL TERMINATE AT
UNDERSIDE OF STRUCTURAL DECK TO MAINTAIN A CONTINUOUS PLANE OF GYPSUM
BOARD AS A NOISE, SMOKE OR OTHER TYPE OF BARRIER.
7. ALL PARTITIONS EXTENDING TO STRUCTURE ABOVE SHALL TERMINATE WITH
DEFLECTION TRACK - SEE TYPICAL DETAILS ON THIS SHEET.
8. ALL GYPSUM BOARD PARTITIONS NOT EXTENDING TO THE STRUCTURE MUST BE
BRACED.
9. UL DESIGN NUMBERS REFER TO THE FIRE RESISTANCE DIRECTORY; UNDERWRITERS
LABORATORY, LATEST EDITION.
10. MISCELLANEOUS NON-RATED CHASES TO BE 5/8" GYPSUM BOARD ON 3 5/8" METAL
STUD FRAMING AT 16" O.C., UNLESS NOTED OTHERWISE.
11. MISCELLANEOUS FURRING AROUND COLUMNS TO BE 5/8" GYPSUM BOARD ON 11/2"
STUDS, UNLESS NOTED OTHERWISE.
12. FIRE-RATED PARTITIONS TO HAVE FIRE-STOPPING SEALANTS AT HEAD, SILL JUNCTURE
WITH DISSIMILAR MATERIALS, ETC. AND AROUND ALL PENETRATIONS AND OPENINGS.
13. CONSTRUCT ALL PARTITIONS WITH SOUND ATTENUATION BATTS WITH THE FOLLOWING
SOUND BATT THICKNESS: 2 1/2" OR LESS METAL STUD - 1 1/2" THICKNESS, 3 5/8"
OR LARGER METAL STUD - 3" THICKNESS. UNLESS NOTED OTHERWISE.
1X
METAL STUD/FURRING, CH STUD AND WOOD STUD KEY
METAL STUD/FURRING
DESIGNATION SIZE
A GYPSUM BOARD DIRECT APPLIED TO CMU
B 7/8"
C 1 1/2"
D 1 5/8"
E 2 1/2"
F 3 1/2"
G 3 5/8"
H 4"
J 5 1/2"
K 6"
L 8"
M 10"
N 12"
P (OPEN)
Q (OPEN)
CH STUD
DESIGNATION SIZE
R 2 1/2"
S 4"
T 6"
PARTITION TYPE TAG (REFER TO FLOOR PLANS)
PARTITION TYPE
NUMBER
METAL STUD, FURRING OR
CH STUD FRAMING LETTER
FIRE-RATING, IF REQUIRED
1X
WOOD STUD
DESIGNATION SIZE
U 2"x4"
V 2"x6"
W 2"x8"
F
IL
E N
U M
B E
R
S T
A T
E I
N D
E X
N U
M B
E R
S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T
A N
D B
U D
G E
T S
T A
T E
O F
M
IC
H
IG
A N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
IN
T
E R
IO
R
P A
R T
IT
IO
N T
Y P
E S
T
Y P
IC
A
L S
Y M
B O
L S
G
E N
E R
A L
N O
T E
S
-1
.0
G
J u n e
M
ID
L A
N D
A R
M O
R Y
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
A
IR
P
O R
T R
O A
D
M
ID
L A
N D
M
I
D E
P A
R T
M E
N T
O F
M
IL
IT
A
R Y
A N
D V
E T
E R
A N
'S A
F F
A
IR
S
/2
.M
A A
/1
/2
/3
/2
ISSUED FOR DATE
ADDENDUM 1 08-03-2023
ADDENDUM 2 08-16-2023
E as t K al am az oo A ve nu e, S ui te
K al am az oo , M ic hi ga n
-5
9.
3.
33 P
H O
N E
.3
.6
TO
W
E R
P
IN
K S
TE
R
.C O
M A
LL
R
IG
H
TS
R
E S
E R
V E
D
E as t F ul to n S tre et
, S ui te
G ra nd
R ap id s, M ic hi ga n
6.
6.
44 P
H O
N E
.4
.5
6FA
X
SH
EE
T
TI
TL
E
SH
EE
T N
U M
B
ER
O W
N
ER
D A
TE
ISSUED FOR DATE
-1
.0
JU
NE
, 2
RE
NO
VA
TE
A
RM
OR
Y
A
IR
PO
RT
R
OA
D
MI
DL
AN
D, M
I 4
DE
PA
RT
ME
NT
O
F M
ILI
TA
RY
A
ND
VE
TE
RA
N'
S
AF
FA
IR
S
FIL
E
NU
MB
ER
ST
AT
E
IN
DE
X
NU
MB
ER
S
Co ns tru cti on Fin al Re co rd
Iss ue d f or
Pr eli mi na ry Da te
DE
SIG
N
AN
D
CO
NS
TR
UC
TIO
N
DI
VIS
IO
N
DE
PA
RT
ME
NT
O F T
EC
HN
OL
OG
Y, M
AN
AG
EM
EN
T, AN
D
BU
DG
ET
ST
AT
E
OF
M
IC
HI
GA
N
AD
AM
P . L
AC
H, R A, D
IR
EC
TO
R
ST
AT
E
FA
CI
LIT
IE
S
AD
MI
NI
ST
RA
TIO
N
PR
O
JE
C
T
TI
TL
E
JU
NE
, 2
SI
TE
D
ET
AI
LS
S H
EE
T
C
SECTION
RESERVED
PARKING
ONLY
ACCESSIBLE
VAN
ADDENDUM #2 AUG. 16, 2023
UP
DN
UP
D G K L M P
E F H J N R SCBA T
AD 301
AD 301
AD 301
OFFICE
OFFICE
OFFICE
SHOWERS
LOCKERS
TOILET
CLOSET
SCULLERY
HOT FOOD
PREP
COLD FOOD
PREP
MESS OFFICE
CHAIR / TABLE
STORAGE
SUPPLY ROOM
OFFICE
OFFICE
OFFICE
CLOSET
WOMENS
TOILET
WOMENS
TOILET
LOCKERS
BLDG
MAINT.
GENERAL
PURPOSE
MAINT. BAY
BOILER ROOM
SERVICE
OFFICE
220-324
SERVICE
PARTS / TOOLS
600-400
STORAGE
CLASSROOM
3460-2422
ASSEMBLY
HALL
5400-7780
CORRIDOR
2 5
23 24
25 25
± 18' - 3 3/4"± 7' - 0 1/4"
AD 302
AD 302
AD 302
AD 302
AD 302
AD 302
AD 302
AD 302
1B
/8
36"
/2
7' - 4 3/4" 3' - 4"
6' - 6"
REMOVE
PORTIONS
OF CMU
WALLS
3' - 4"
V
IF
BRICK AND BLOCK
TO BE TOOTHED IN
BRICK AND BLOCK WALL
A2
A2
A2
STRUCTURAL
TILE WALLS
STRUCTURAL
TILE WALLS
A2 A2
CMU WALLS
A2
GYP BRD
WALLS
SLAVAGE EX.
LADDER FOR
REUSE
EX. VAULT
DOOR TO BE
SALVAGED
FOR REUSE
A2
P
R S T
OPEN TO BELOW
MECH. FLOOR
F
IL
E N
U M
B E
R
S T
A T
E I
N D
E X
N U
M B
E R
S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T
A N
D B
U D
G E
T S
T A
T E
O F
M
IC
H
IG
A N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
D E
M O
L
IT
IO
N
P L A
N
-1
.0
A D
J u n e
M
ID
L A
N D
A R
M O
R Y
A D
D
IT
IO
N
A N
D R
E N
O V
A T
IO
N
A
IR
P
O R
T R
O A
D
M
ID
L A
N D
M
I
D E
P A
R T
M E
N T
O F
M
IL
IT
A
R Y
A N
D V
E T
E R
A N
'S A
F F
A
IR
S
/2
.M
A A
/1
/2
/3
/2
KEYED NOTES - DEMOLITION
1 REMOVE EXISTING DOOR AND HARDWARE
2 REMOVE EXISTING WALL
3 REMOVE EXISTING SHOWER WALL
4 REMOVE EXISTING SHOWER STALL
5 REMOVE EXISTING SHOWER HEADS AND ACCESSORIES
6 REMOVE EXISTING SHOWER LOCKERS
8 REMOVE EXISTING WINDOW, PREPARE FOR WALL INFILL
9 REMOVE EXISTING SINKS, PREPARE TO PATCH WALL
10 REMOVE EXISTING WALL-MOUNTED URINALS, PREPARE FOR INSTALLATION OF NEW
URINALS
11 REMOVE EXISTING WALL-MOUNTED URINALS PARTITIONS, PREPARE FOR INSTALLATION
OF NEW URINAL PARTITIONS
12 REMOVE EXISTING WALL-MOUNTED TOILETS, PREPARE FOR INSTALLATION OF NEW
WALL-MOUNTED TOILETS
13 REMOVE EXISTING TOILET PARTITIONS
14 REMOVE EXISTING TOILET GRAB BARS
15 REMOVE EXISTING SHELVING UNITS
16 REMOVE EXISTING GRID CEILING
17 REMOVE EXISTING GYPSUM CEILING
18 REMOVE EXISTING ALUMINUM LOUVER CEIILING, PREPARE FOR NEW CEILING
19 REMOVE PORTION OF EXISTING WALL, PREPARE FOR INSTALLATION OF NEW DOOR
21 REMOVE EXISTING LOUVER, PREPARE FOR WALL INFILL
22 REMOVE PORTION OF EXISTING WALL, PREPARE FOR ADDITION OF NEW INTERIOR
WALLS AT CORRIDOR
23 REMOVE EXISTING BABY CHANGING STATION
24 REMOVE EXISTING SANITARY DISPENSER
25 REMOVE EXISTING STOREFRONT, DOORS AND HARDWARE, SALVAGE FOR
RESTALLATION AT NEW LOCATIONS
26 REMOVE PORTION OF EXISTING WALL, SALVAGE EXTERIOR BRICK, PREPARE TO ADD
AS FINISH ON NEW EXTERIOR WALLS
27 REMOVE EXISTING DOOR AND HARDWARE, SALVAGE FOR REINSTALLATION
28 REMOVE END PORTION OF RAMP RAIL TO BE 2" AWAY FORM THE CORNER OF NEW
WALL
29 REMOVE EXISTING DOOR AND HARDWARE, PREPARE FOR INSTALLATION OF NEW
DOORS AND HARDWARE
30 REMOVE PORTION OF EXISTING WALL, PREPARE FOR FINISH AND INSTALLATION OF
NEW WALLS BEHIND EXISTING BRICK WALL
31 REMOVE EXISTING HARDWARE ON EXISTING DOOR, PREPARE FOR INSTALLATION OF
NEW HARDWARE
32 REMOVE EXISTING OVERHEAD DOOR, METAL PANEL AND FRAME
33 REMOVE EXISTING DRINKING FOUNTAIN, PREPARE FR INSTALLATION OF NEW DOUBLE
FOUNTAINS
34 REMOV MECHANICAL EQUPMENT, PREPARE TO FILL WALL OPENING WITH SIMILAR WALL
CONSTRUCTION
35 SAWCUT AND REMOVE CONCRETE SLAB TO ALLOW ACCESS FOR NEW PLUMBING,
FOUNDATION AND FLOOR SLAB, COORDINATE WITH PLUMBING AND STRUCTURAL
36 PREPARE EXISTING CONCRETE FLOOR FOR NEW CARPET INSTALLATION
37 REMOVE EXISTING TILES, PREPARE FOR NEW FLOORING
38 REMOVE EXISTING CARPET, PREPARE FOR NEW
39 PREPARE EXISTING CONCRETE FLOOR FOR NEW WORKROOM FLOORING
40 REMOVE EXISTING CAST STONE SILL, PREPARE FOR BRICK VENEER INFILL
1/8" = 1'-0"
DEMOLITON FLOOR PLAN
MIDLAND ARMORY
KEY PLAN
E
A A
C
DB
SCALE: NO SCALE
EXISTING
NEW
BCD
F G
H
I
1/8" = 1'-0"AD 101
2 MEZANINE FLOOR DEMOLITION PLAN
TOILET ROOM 701 TO
REMAIN IN USE DURING
ENTIRE CONSTRUCTION
PROCESS.
ISSUED FOR DATE
A2
F
F
J
J
J
J
J
V
EQ
EQ
EQ
EQ
EQ
J
J
J
EQJ
J
J
WAP
WAP