Drawings-2.pdf

PDF 6 MB Posted

Attached to
472/22442. JBB; MBP - Primary Elec. Infrastructure Upgrades
Solicitation number
RFQ - 171 - 240000000053
Issued by
Alger County, Michigan

About this file

This document contains the electrical scope of work and riser diagrams for a primary electrical infrastructure upgrades project at multiple buildings and sites managed by the Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The key aspects include:

The project involves the replacement and installation of new primary cables, switches, transformers, and related electrical equipment at the Food Warehouse, A-Dorm, Outside Kitchen, Aerial South, Aerial Service North, TD Chapel, Building Trades, Brooks Center, Administration Building, Central Kitchen, and Programs Building. The work includes demolition of existing infrastructure, providing new pad-mounted transformers and switchgear, and connecting to the existing systems. The project is bid as a single package with a fixed completion date of October 24, 2023.

The bid documents provide detailed electrical drawings, riser diagrams, and equipment specifications. Pricing is based on unit rates and lump sum amounts. The project is funded through the State's capital improvement budget. Bidders must be prequalified with the State and comply with all applicable regulations and requirements. The contract will be awarded to the responsive and responsible bidder submitting the lowest total bid amount.

View the file

Other files

File Type Posted
Addendum 2.pdf PDF
Technical Specifications.pdf PDF
Addendum 4.pdf PDF
DTMB-0415 Advertisement (Rev 10-22).pdf PDF
LEIN Request 22442.pdf PDF
Front End Specification.pdf PDF
Addendum 3.pdf PDF
Prevailing Wages 231024 Marquette County 22442.pdf PDF
Addendum 1.pdf PDF
Drawings-1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P13

P14

TW

J J

EXISTING

TAP BOX

NEW

TAP BOX

EXISTING

TRANSFORMER 150KVA

NEW

SWITCH

NEMA3R

EX

EX

EX

EX

EXISTING

UNDERGROUND

LIGHTING FEEDER

EXISTING

UNDERGROUND

FIBER

EXISTING

SECURITY FENCE

EXISTING

FIBER CABINET

P15

J

EXISTING

A DORM

SWITCHGEAR

EXISTING

TAP BOX

EX

EX

EXISTING

UNDERGROUND

LIGHTING FEEDER

EXISTING

SECURITY FENCE

ELECTRICAL KEY NOTES

REPLACE PRIMARY CABLE FROM POWER HOUSE TO FOOD WAREHOUSE.

INSTALL NEW PRIMARY CABLES IN CONDUIT.

PROVIDE AND INSTALL NEW TAP BOX IN TUNNEL ON LOOP #2.

PROVIDE AND INSTALL NEW TWO POSITION SWITCHES AND REFEED

EXISTING TRANSFORMER FROM THIS SWITCH.

REPLACE LOOP #1 PRIMARY CABLE AND PROVIDE NEW LOOP #2 FEEDER

FROM TAP BOX IN TUNNEL TO FOOD WAREHOUSE. INSTALL NEW PRIMARY

CABLES IN CONDUIT.

REPLACE PRIMARY CABLE FROM FOOD WAREHOUSE TO A-DORM. INSTALL

NEW PRIMARY CABLES IN CONDUIT.

PROVIDE AND INSTALL NEW PAD MOUNT TRANSFORMER (150KVA, PRIM:

2400V - 3Ø, SEC: 120/240V - 3Ø). FEED TRANSFORMER FROM POWER PLANT

THRU EXISTING CONDUIT UNDERGROUND CONDUIT. RECONNECT EXISTING

BUILDING SERVICE TO NEW TRANSFORMER.

EXISTING CONDUIT TO REMAIN. REMOVE THE EXISTING WIRE AND PROVIDE

AND INSTALL NEW WIRING.

PROVIDE AND INSTALL NEW PAD TO ACCOMMODATE NEW EQUIPMENT AS

SHOWN. MINIMUM 12" FROM EQUIPMENT TO EDGE OF PAD. SEE DETAIL #1

ON E100.

PROVIDE PREVENTIVE MAINTENANCE ON EQUIPMENT.

PROVIDE AND INSTALL NEW TRANSFORMER (37.5KVA, PRIM: 2400V - 3Ø, SEC:

120/240V - 1Ø). FEED TRANSFORMER FROM PANEL "MDPK"

PROVIDE AND INSTALL NEW FEEDER TO TRANSFORMER.

NEW

PNL "MDPK"

TK

EXISTING

UNDERGROUND

KITCHEN BUILDING FEEDER

6 7

EXISTING

POWER POLE

TEX

1 1

T T T

TK2

10NEW

TRANSFORMER

NEW

TRANSFORMER

11 2

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE BACK TO SOURCE.

DISCONNECT & REMOVE EXISTING ELECTRICAL OVERHEAD LINE.

DEMOLITION NOTES

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

SCALE: 1/8" = 1'-0"

0 1 5 10 20

FOOD WAREHOUSE - MAIN LEVEL - NEW ELECTRICAL POWER

SCALE: 1/8" = 1'-0"

0 1 5 10 20

A-DORM - BASEMENT LEVEL - NEW ELECTRICAL POWER

SCALE: 1/8" = 1'-0"

0 1 5 10 20

OUTSIDE KITCHEN - MAIN LEVEL - NEW ELECTRICAL POWER

E-500

JKB

JFS

ELECTRICAL SCOPE OF WORK -

AREAS #1 - FOOD WAREHOUSE,

#2 - A DORM, AND #3 - OUTSIDE

KITCHEN

E500

E500

E500

2222222

P23

P24

P25

P26

P31

P32

P33P34 P35P36

P22A

P36A

P27

HH

HH

EX

EX

EXEX

EX

EXEX

EXEXEX

EX

EX

EXEX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EXISTING

UNDERGROUND

LIGHTING FEEDER

EXISTING

UNDERGROUND

LIGHTING FEEDER

EXISTING

UNDERGROUND

LIGHTING FEEDER

EX

EX

EXISTING

SECURITY FENCE

EXISTING

SECURITY FENCE

EXISTING

SECURITY FENCE

EXISTING

UNDERGROUND

FIBER

EXISTING

UNDERGROUND

FIBER

EXISTING

UNDERGROUND

CAT 6 LINE

EXISTING

UNDERGROUND

CAT 6 LINE

EXISTING

UNDERGROUND

FEEDER

EXISTING

ELECTRICAL

OVERHEAD LINES

HH

TEX

EXISTING

TRANSFORMER

HH

TEX

TEX

TEX

HH

1 3

EXISTING

200A PNL "BB"

EXISTING

TRANSFORMER

EXISTING

150KVA

TRANSFORMEREXISTING

200A PNL "BA"

T

DEMO

TRANSFORMER (LTG)

DEMO

PANEL (120/240V)

DISCONNECT & REMOVE EXISTING ELECTRICAL OVERHEAD LINE.

EXISTING POLE TO REMAIN UNLESS NOTED OTHERWISE.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE.

DEMOLITION NOTES ELECTRICAL KEY NOTES

PROVIDE AND INSTALL QUAZITE BOX OR EQUAL.

PROVIDE, INSTALL, AND DIRECTIONAL BORE NEW PRIMARY LINE.

RECONNECT PRIMARY LINE AT THIS LOCATION TO EXISTING TRANSFORMER.

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

AERIAL SOUTH - NEW ELECTRICAL POWER

SCALE: 1" = 40'-0"

100 5 20 40 80 100

E-501

JKB

JFS

ELECTRICAL SCOPE OF WORK -

AREAS #4 - AERIAL SOUTH

E501

EXISTING

UNDERGROUND

FEEDER

EXISTING

ELECTRICAL

OVERHEAD LINES

T

THH1 3

EX

EXISTING

MAN HOLE

EXISTING

PNL "MDP"

EXISTING

UNDERGROUND FEEDS

T

DISCONNECT & REMOVE EXISTING ELECTRICAL OVERHEAD LINE.

EXISTING POLE TO REMAIN UNLESS NOTED OTHERWISE.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE.

DISCONNECT & REMOVE EXISTING PRIMARY ELECTRICAL FEEDER.

DEMOLITION NOTES

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL QUAZITE BOX OR EQUAL.

PROVIDE, INSTALL, AND DIRECTIONAL BORE NEW PRIMARY LINE.

RECONNECT PRIMARY LINE AT THIS LOCATION TO EXISTING TRANSFORMER.

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

AERIAL SERVICE NORTH - NEW ELECTRICAL POWER

SCALE: 1" = 40'-0"

100 5 20 40 80 100

E-502

JKB

JFS

ELECTRICAL SCOPE OF WORK -

AREAS #5 - AERIAL SERVICE

NORTH

E502

TEX

J J J

EXISTING

MANHOLE

J

J J

EXISTING

TRANSFORMER

NEW

SWITCH

NEMA3R

EXISTING

TAP BOX

EXISTING

TAP BOX

REMOVE

SWITCH

EXISTING

UNDERGROUND

LIGHTING FEEDER EXISTING

LIGHTING CONTACTOR

EXISTING

PANEL "MDP"

EXISTING

HIGH VOLTAGE

DISCONNECT SWITCH

EXISTING

ELECTRICAL FEEDER

EXISTING

LIGHTING CONTROL FEEDER

EXISTING

GROUND ROD TYP.

EXISTING

BARE COPPER GROUND

CONDUCTOR

12"+ BELOW GRADE

EXISTING

PAD

MATCH LINE 6

MATCH LINE 7A

MATCH LINE 6

MATCH LINE 7A

DISCONNECT & REMOVE EXISTING GROUND WIRE TO EXTEND PAD.

DISCONNECT & REMOVE EXISTING FEEDER AS SHOWN.

DISCONNECT & REMOVE EXISTING PRIMARY CABLE FROM TD CHAPEL

SWITCH THRU MANHOLE IN SALLY PORT TO EXISTING TRANSFORMER

NORTH OF BUILDING TRADES. UPON COMPILATION OF NEW PRIMARY CABLE.

DEMOLITION NOTES

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW TAP BOX IN TUNNEL ON LOOP #1.

PROVIDE AND INSTALL NEW TAP BOX IN TUNNEL ON LOOP #2.

PROVIDE AND INSTALL NEW TWO POSITION SWITCHES AND REFEED

EXISTING HIGH VOLTAGE DISCONNECT SWITCH FROM THIS SWITCH.

PROVIDE AND INSTALL NEW PAD TO ACCOMMODATE NEW EQUIPMENT AS

SHOWN. MINIMUM 12" FROM EQUIPMENT TO EDGE OF PAD. SEE DETAIL #1

ON E100.

EXTEND EXISTING #6 BARE COPPER GROUND CONDUCTOR AT 12" MINIMUM

BELOW GRADE.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM TD CHAPEL SWITCH

THRU MANHOLE IN SALLY PORT TO EXISTING TRANSFORMER NORTH OF

BUILDING TRADES. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE PREVENTIVE MAINTENANCE ON SWITCHGEAR.

PROVIDE AND INSTALL NEW PRIMARY LOOP #1 CABLE FROM TD CHAPEL

SWITCH FROM POWER HOUSE. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

EXISTING

POWER POLE

MATCH LINE 6

MATCH LINE 7A

MATCH LINE 6

MATCH LINE 7A

MATCH LINE 7A

MATCH LINE 7B

MATCH LINE 7A

MATCH LINE 7B

T

EXISTING

TRANSFORMER

MATCH LINE 7A

MATCH LINE 7B

MATCH LINE 7A

MATCH LINE 7B

EXISTING

SALLY PORT FENCE

EXISTING

SECURITY FENCE

EXISTING

MANHOLE

EXISTING

SALLY PORT GATES

EX

EX

EXISTING

UNDERGROUND

FIBER

EXISTING

LOOP #1

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

TD CHAPEL - MAIN LEVEL - NEW ELECTRICAL POWER

BUILDING TRADES - MAIN LEVEL - NEW ELECTRICAL POWER

SCALE: 1/8" = 1'-0"

0 1 5 10 20

SCALE: 1/8" = 1'-0"

0 1 5 10 20

E-503

JKB

JFS

ELECTRICAL SCOPE OF WORK -

AREAS #6 - TD CHAPEL, AND

#7 - BUILDING TRADES

E503

E503

T

T

MTS

LOOP #2

X-RAY DISC.

EXISTING

TRANSFORMER

(X-RAY)

MECHANICAL ROOM

ELECTRICAL ROOM

2400V

LOOP #1

T

EXISTING

TRANSFORMER

EXISTING

TRANSFORMER

WARDEN

EXISTING

TRANSFORMER

225 KVA

2400V

MA

TC

H

LIN

E

MA

TC

H

LIN

E

MA

TC

H

LIN

E

MA

TC

H

LIN

E

LOOP #1

EXISTING

SWITCH 11

J

MA

TC

H

LIN

E

MA

TC

H

LIN

E

MA

TC

H

LIN

E

MA

TC

H

LIN

E

T

TT

NEW

SWITCH

NEMA3R

TT

NEW

TRANSFORMER

NEW

277/480V-3Ø, 4W

PNL "MDP-A"

NEW

TRANSFORMER

NEW

120/208V-3Ø, 4W

PNL "CAGE"

MATCH LINE 9

MATCH LINE 8MATCH LINE 9

MATCH LINE 8

REMOVE

SWITCH3

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM BROOKS CENTER TO

NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN TO

NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW TWO POSITION SWITCHES.

PROVIDE AND INSTALL NEW PAD TO ACCOMMODATE NEW EQUIPMENT AS

SHOWN. MINIMUM 12" FROM EQUIPMENT TO EDGE OF PAD. SEE DETAIL #1

ON E100.

PROVIDE AND INSTALL NEW 750 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW AMDIN SWITCH (LOOP #2 FEED).

PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A" 277/480V-3Ø, 4W 800A

PROVIDE AND INSTALL NEW 150 KVA TRANSFORMER PRIM: 277/480V/ SEC:

120/208V - 3Ø, 4W FEED FROM NEW 480V PANEL "MDP-A".

PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A1" 120/208V-3Ø, 4W 800A.

PROVIDE AND INSTALL NEW 150 KVA TRANSFORMER PRIM: 2400V/ SEC:

120/208V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN NORTH SWITCH

(LOOP #2 FEED).

PROVIDE AND INSTALL NEW FEEDER FROM PANEL "PP1" TO NEW 150 KVA

TRANSFORMER (4) 500 KCMIL, (1) 3 1/2" CONDUIT.

PROVIDE PREVENTIVE MAINTENANCE ON EQUIPMENT.

PROVIDE AND INSTALL NEW FEEDER FROM PANEL "PP1 TO BUCK BOOST

15KVA TRANSFORMER IN CHAPEL.

PROVIDE AND INSTALL NEW 15 KVA TRANSFORMER PRIM: 277/480V/ SEC:

120/208V - 3Ø, 4W FEED FROM CENTRAL KITCHEN PANEL "PP1".

DISCONNECT & REMOVE EXISTING PRIMARY CABLE FROM BROOKS CENTER

TO NEW SWITCH. UPON COMPILATION OF NEW PRIMARY CABLE.

DISCONNECT & REMOVE EXISTING PRIMARY CABLE FROM CENTRAL KITCHEN

TO NEW SWITCH. UPON COMPILATION OF NEW PRIMARY CABLE.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE BACK TO SOURCE.

DISCONNECT & REMOVE EXISTING EQUIPMENT. RELOCATE ASSOCIATED

CONDUIT & WIRE TO NEW GEAR LINE UP UPON COMPILATION OF NEW GEAR

LINE UP.

DEMOLITION NOTES

J

T

MATCH LINE 9

MATCH LINE 8MATCH LINE 9

MATCH LINE 8

NEW

TRANSFORMER

REMOVE

SWITCH

NEW

SWITCH

NEMA3R

T

T

T

T T T

EXISTING

PNL "PP1"

3 3 3

MATCH LINE 10

MATCH LINE 11MATCH LINE 10

MATCH LINE 11

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

BROOKS CENTER - MAIN LEVEL - NEW ELECTRICAL POWER

ADMINISTRATION - MAIN LEVEL/ BASEMENT - NEW ELECTRICAL POWER

CENTRAL KITCHEN - MAIN LEVEL - NEW ELECTRICAL POWER

SCALE: 1/8" = 1'-0"

0 1 5 10 20

SCALE: 1/8" = 1'-0"

0 1 5 10 20

SCALE: 1/8" = 1'-0"

0 1 5 10 20

E-504

JKB

JFS

ELECTRICAL SCOPE OF WORK -

AREAS #8 - BROOK CENTER,

#9 - ADMINISTRATION, AND #10 -

CENTRAL KITCHEN

E504

E504

E504

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN NORTH

TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN SOUTH

TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW TWO POSITION SWITCHES.

PROVIDE AND INSTALL NEW PAD TO ACCOMMODATE NEW EQUIPMENT AS

SHOWN. MINIMUM 12" FROM EQUIPMENT TO EDGE OF PAD. SEE DETAIL #1 ON

E100.

PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN SOUTH SWITCH (LOOP

#2 FEED).

PROVIDE AND INSTALL NEW 225 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW PROGRAMS SWITCH (LOOP #2 FEED).

PROVIDE AND INSTALL NEW 50 KVA TRANSFORMER PRIM: 277/480V/ SEC:

120/240V - 1Ø, 3W FEED FROM NEW 225 KVA PROGRAMS TRANSFORMER.

PROVIDE AND INSTALL NEW FEEDER FROM 225 KVA PROGRAMS

TRANSFORMER TO NEW 50 KVA TRANSFORMER (3) #3/0, (1) 2" CONDUIT.

PROVIDE AND INSTALL QUAZITE BOX OR EQUAL.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROMPROGRAMS BUILDING TO

NEW SWITCH IN TUNNEL. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

DISCONNECT & REMOVE EXISTING PRIMARY CABLE FROM CENTRAL KITCHEN

NORTH TO NEW SWITCH. UPON COMPILATION OF NEW PRIMARY CABLE.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE BACK TO SOURCE.

DISCONNECT & REMOVE EXISTING PRIMARY CABLE FROM CENTRAL KITCHEN

SOUTH TO NEW SWITCH. UPON COMPILATION OF NEW PRIMARY CABLE.

DISCONNECT & REMOVE EXISTING PRIMARY CABLE FROM PROGRAMS TO

NEW SWITCH IN TUNNEL. UPON COMPILATION OF NEW PRIMARY CABLE.

DEMOLITION NOTES

T

NEW

SWITCH

NEMA3R

NEW

TRANSFORMER

MATCH LINE 10

MATCH LINE 11MATCH LINE 10

MATCH LINE 11

J

T

J

NEW

SWITCH

NEMA3R

NEW

TRANSFORMER

REMOVE

SWITCH2

REMOVE

SWITCH 2

MA

TC

H

LIN

E

MA

TC

H

LIN

E

MA

TC

H

LIN

E

MA

TC

H

LIN

E

EXISTING

SECURITY FENCE

EXISTING

SECURITY FENCE

TT

T

T

T T T

EXISTING

PNL "MDP2"

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

CENTRAL KITCHEN - MAIN LEVEL - NEW ELECTRICAL POWER

SCALE: 1/8" = 1'-0"

0 1 5 10 20

PROGRAMS BUILDING - MAIN LEVEL - NEW ELECTRICAL POWER

SCALE: 1/8" = 1'-0"

0 1 5 10 20

E-505

JKB

JFS

ELECTRICAL SCOPE OF WORK -

AREAS #11 - CENTRAL KITCHEN,

AND #12 - PROGRAMS BUILDING11

E505

E505

GENERATOR

CIRCUIT

BREAKER

G

GENERATOR

TRANSFORMER

480V-2.4KV, 3PH

GENERATOR HVDS

400A

250AF

MN UTIL

23.86MVA

8 (X/R)

23.86MVA

8 (X/R)

MN UTIL TX

750 KVA

2.4 - 2.4KV

5.5%

1- 1/C

-5

K

CM

IL

INCOMING LINE

250A

#3/0

ATS

SECTION 1 SECTION 2/3

SAPRE AERIAL

SECTION 4

HOUSE #1 LOOP #1

SECTION 5

HOUSE #2 LOOP #2

SECTION 6

PRIMARY SWITCHGEAR - 2400V-3 PHASE, 1200A

TD KIT A TX

37.5 KVA

2.4-0.240KV

2.75%

1- 1/C

-2 A

W G

T3X50KVA (150

KVA) 2.4-0.240KV

4%

1- 1/C

-2 A

W G

PAD

TRANSFORMER

CAN

(3) TRANSFORMER

3X50KVA (150 KVA)

2.4-0.240KV

4%

POLE

TRANSFORMER

1- 1/C

-2 A

W G

LN POLE 1

1- 1/C

-2 A

W G

1- 1/C

-4 /0

AW

G

TD KIT-A

DISC

SQD Q2

225/150A

PANEL

KITCHEN

"B"

1- 1/C

-2 A

W G

PANEL

TD KITCHEN

MBRK

C-H HLA600

600/600

PANEL

TD KITCHEN

"1"

SQD LA

400/400

PANEL

TD KITCHEN

"2"

SQD LA

250/225

1- 1/C

-2

K

CM

IL

1- 1/C

-3 /0

AW

G

PANEL

KITCHEN

"C. MBRK"

SQD LA

400/400

1- 1/C

-1 A

W G

PANEL

"MCC2"

PANEL

KITCHEN

"D"

250A 250A 75A N.C.

100A 100A 100A 100A

P-DORM TX

150 KVA

2.4-0.240KV

4%

1- 1/C

-4 /0

AW

G

1- 1/C

-2 A

W G

A-WING

DISC

BUSS REN (H)

80A

1- 1/C

-4 A

W G

PANEL

"A-WING"

1- 1/C

-2 A

W G

B-WING

DISC

BUSS REN (H)

80A

1- 1/C

-4 A

W G

PANEL

"B-WING"

1- 1/C

-2 A

W G

C-WING

DISC

BUSS REN (H)

80A

1- 1/C

-4 A

W G

PANEL

"C-WING"

1- 1/C

-2 A

W G

D-WING

DISC

BUSS REN (H)

80A

1- 1/C

-4 A

W G

PANEL

"D-WING"

BARN

1-PAD

1-CAN

BARN

1-POLE

ERT BUILDING

1 POLE 1Ø

2- 1/C

-2

K

CM

IL

KITCHEN

DISC

PNL "C"

MBRK

100A

KITCHEN

OH

UG

OH

UG

UG

SAWMILL

SHEET E-600

SHEET E-601

SHEET E-600

SHEET E-601

2 2

4 4

3 OUTSIDE KITCHEN

UGUG

5 5

4 AERIAL SOUTH

1 1 1

1 1 1

1 1 1 1

2 2 2 2

2 2 2 2

4 2

2 2 77

EXISTING EQUIPMENT TO REMAIN.

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO REMAIN.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE BACK TO SOURCE.

DISCONNECT & REMOVE EXISTING FEEDER. REMOVE ASSOCIATED CONDUIT

& WIRE BACK TO SOURCE.

DISCONNECT & REMOVE EXISTING ELECTRICAL OVERHEAD LINE.

DISCONNECT & REMOVE EXISTING FEEDER. ASSOCIATED CONDUIT TO

REMAIN.

DISCONNECT & REMOVE EXISTING PRIMARY CABLE. ASSOCIATED CONDUIT

TO REMAIN.

TO BE DISCONNECTED AND REMOVED BY UTILITY COMPANY.

DEMOLITION NOTES

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

E-600

JKB

JFS

ELECTRICAL RISER DIAGRAM -

DEMOLITION

ELECTRICAL RISER DIAGRAM - DEMOLITION

SCALE:

HOUSE TX.7

SQD KAL

250/225

POWERHOUSE BUILDING

HOUSE TX.2

WEST LAB

400/300

HOUSE TX.3

WEST JA

225/125

HOUSE TX.4

WEST JA

225/200

HOUSE TX.1

SQD KAL

250/225

HOUSE SERV 1 TX

HOUSE 1

1- 1/C

-1 /0

AW

G

1- 1/C

-2

K

CM

IL

HOUSE TX

300 KVA

0.48-0.240KV

4%ELC FD PMP CP.MDS

SHAWMUT TRS (RK5)

150A

1- 1/C

-1 /0

AW

G

0.48 KV

ELC FD PMP

PANEL

"MCC-1"

PANEL

MAIN

"LTG"

1- 1/C

-1 /0

AW

G

PANEL

TURBINE

"RM"

1- 1/C

-1 /0

AW

G

MDP-1

100A

MAIN DISTRIBUTION PANEL "MDP"

MDP-2

200A

MDP-3

200A

MDP-4

200A

MDP-5

20A

HOUSE SERV 1 TX

MDP-6

60A

MDP-7

60A

MDP-8

50A

MDP-9

150A

PANEL

"CHAPEL"

PANEL

"O-DORM"

PANEL

"QUARTER

MASTER"

PANEL

"PROP/

LAUNDRY"

PANEL

"GREENHOUSE"

O-DORM

DISC

SQD Q2

225/200A

MBRK

LC-1 LC-2 LCP

LIGHTING CONTROLS

NORTH

SITE

LIGHTS

SOUTH

SITE

LIGHTS

BIG GATE TRASH

COMPACTOR

POST

2 & 3

TOWERS

PANEL

"TD

SCHOOL

HEALTHCARE"

MDP

DISC

600A

1- 1/C

-4 /0

AW

G

T-1

300KVA

2.4-0.240KV

MAIN

TRANSFORMER

"HVDS"

HIGH VOLTAGE

DISCONNECT SWITCH

MSI PNL A TX

45 KVA

0.48-0.240KV

4%

1- 1/C

-6 A

W G

1- 1/C

-6 A

W G

1- 1/C

-6 A

W G

1- 1/C

-4 /0

AW

G

1- 1/C

-4 /0

AW

G

1- 1/C

-4 /0

AW

G

MSI PNL B TX

45 KVA

0.48-0.240KV

6.11%

ANEX TX

45 KVA

0.48-0.240KV

6.11%

ANNEX

DISC

SQD KA

250/125A

MBRK

1- 1/C

-4 /0

AW

G

PANEL

"ANNEX"

PANEL

"MSI-B"

PANEL

"MSI--A"

MSI A.19

DISC

C-H GHB

100/60

MBRK

ANNEX

DISC

BUSS RES (H)

250/125A

FUSE

MSI A.15

DISC

C-H GHB

100/60

MBRK

1- 1/C

-4 /0

AW

G

1- 1/C

-6 A

W G

MSI

DISC

BUSS NOS (H)

100/600A

250A

FUSE

1- 1/C

-4 /0

AW

G

MSI TX

150KVA

2.4-0.48KV

4%

PAD MOUNT

BUILDING TRADES

1-1/C-350 KCMIL 1-

1/C

-3

K

CM

IL

1- 1/C

-4 /0

AW

G

N DORM

112KVA

2.4-0.240KV

1.6%

PAD MOUNT1-

1/C

-2 /0

AW

G

N DRM

DISC

WEST LAB

400/300

MBRK

1- 1/C

-4 /0

AW

G

N DRM PNL-3

WEST JB

250/200

PANEL "N DORM"

N DRM PNL-2

WEST JB

250/200

N DRM PNL-5

WEST JB

250/200

1- 1/C

-1 /0

AW

G

1- 1/C

-1 /0

AW

G

1- 1/C

-1 /0

AW

G

PANEL

"WEST WING"

PANEL

"EAST WING"

PANEL

"N DORM-A"

HS 2 SWGR.XX

SQD KAL

250/225

HS 2 SWGR

HOUSE 2

1- 1/C

-4 /0

AW

G

HS 2 TX

300KVA

2.4-0.48KV

5.6%

1- 1/C

-3

K

CM

IL

HS 2 SWGR.2

SQD KAL

250/225

HS 2 SWGR.4

SQD KAL

250/125

HS 2 SWGR.6

SQD FAL

100/70

HS 2 SWGR.X

SQD KAL

250/125

1- 1/C

-4 /0

AW

G

1- 1/C

-1 A

W G

1- 1/C

-4 A

W G

1- 1/C

-1 A

W G

PANEL

"MCC-2"

PANEL

"OFFICE"

PANEL

"CHILLER #2"

PANEL

"CHILLER #1"

HS 2 SWGR

SQD LA

400/400

HOUSE SERV 1 TX

300 KVA

2.4-0.240KV

5.45%

A DRM SWGR.1

WEST KA

225/100

A-DORM

A DRM SWGR.2

WEST KA

225/150

A DRM SWGR.3

WEST KA

225/225

A DRM SWGR.4

WEST KA

225/150

A DRM SWGR.6

WEST KA

225/200

A DRM SWGR.7

WEST KA

225/175

A DRM SWGR.8

WEST KA

225/100

1- 1/C

-1 A

W G

1- 1/C

-3 /0

AW

G

1- 1/C

-4 /0

AW

G

1- 1/C

-4 /0

AW

G

1- 1/C

-4 /0

AW

G

1- 1/C

-4 /0

AW

G

1- 1/C

-4 /0

AW

G

PANEL

"H"

PANEL

"E"

PANEL

"A"

PANEL

"C"

PANEL

"D"

PANEL

"B"

PANEL

"G"

LOOP 2 BK FD

225KVA

2.4-0.208KV

4.8%

A DRM TX

225 KVA

2.4-0.208KV

4.8%

TAP-BOX

PAD

TRANSFORMER

60 KVA

4TH FLOOR

DRY TYPE

CAN

TRANSFORMER 60 KVA

4TH FLOOR

DRY TYPE

WRH HS

SQD Q2

225/100

1- 1/C

-1 A

W G

1- 1/C

-2

K

CM

IL

PANEL

WAREHOUSE

"A"

WRH HS

WEST KA

225/200

MBRK

NO NC

NORTH SOUTH

EXISTING TUNNEL

SWITCH WEST OF TD

CHAPEL

EXISTING

150KVA

2.4-0.48KV

TAP-BOX

K K

SHEET E-600

SHEET E-601

SHEET E-600

SHEET E-601

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

FOOD

WAREHOUSE

FOOD

WAREHOUSE

1 FOOD WAREHOUSE

EXISTING

PULL BOX (BASEMENT

OF PENTHOUSE)

2 2

3 3 3 3 3 3 3

1 1 1 1 1 1 1

2 A-DORM

EXISTING

TAP-BOX IN

A-DORM BASEMENT

A-DORM SWITCHGEAR

33333333

3 3

3 33

11 1 1 1

1 1 1 1

1 1

33 3 3 3 3 3 3 3

6 TD CHAPEL

BUILDING TRADES

1 1

3 33

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT & REMOVE EXISTING LOOP #1 PRIMARY CABLE. ASSOCIATED

CONDUIT TO REMAIN.

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO REMAIN.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE.

DEMOLITION NOTES

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

E-601

JKB

JFS

ELECTRICAL RISER DIAGRAM -

DEMOLITION

LOOP 2 MAIN

SWITCH

KIT

150 KVA

SERV TX

225 KVA 2.4-0.48KV

3%

1- 1/C

-2 /0

AW

G

1- 1/C

-2

K

CM

IL

KIT

DISC

400A

CHAPEL 1 TX

15 KVA

2.4-0.24KV

2.1%

1- 1/C

-6 A

W G

1- 1/C

-1 A

W G

VOC SCHOOL

37.5 KVA

PANEL

"VOC

SCHOOL"

PANEL

"CHAPEL 1"

MECHANICAL ROOM CAN TRANSFORMER

SERV

MN

WEST LAB

400/200

1- 1/C

-3 /0

AW

G

KIT

DISC

BUSS FRS-R

(RK15)

200A

LAUNDRY

DISC

BUSS FRS-R

(RK15)

100A

1- 1/C

-3 /0

AW

G

1- 1/C

-3 A

W G

PANEL

"LAUNDRY"

KIT TX

112.5 KVA

0.48-0.208KV

4.7%

1- 1/C

-3 /0

AW

G

1- 1/C

-3

K

CM

IL

KIT

DISC-1

SHAWMUT TR

(RK5)

350A

1- 1/C

-4 /0

AW

G

AA

DISC

BUSS FRS-R

(RK5)

200A

BB

DISC

BUSS FRS-R

(RK5)

200A

1- 1/C

-4 /0

AW

G

1- 1/C

-4 /0

AW

G

PANEL

"RP5"

1- 1/C

-4 /0

AW

G

PANEL

"MCC1"

INDUSTTRYS TX

150 KVA

2.4-0.48KV

2.8%

1- 1/C

-4 /0A

W G

1- 1/C

-2 /0

AW

G

INDUSTRY

DISC

WEST EHB

100/100

1- 1/C

-1 /0

AW

G

PANEL

"LIBRARY"

PANEL

"INDUSTRY"

LIBRARY

DISC

WEST EHB

100/100

LIBRARY THROUGH

CAN

TRANSFORMER

CAN

TRANSFORMER

22.5 KVA

4TH FLOOR

DRY TYPE

60 KVA

4TH FLOOR

DRY TYPE

PP-1 TX

150 KVA

2.4-0.208KV

4%

1- 1/C

-2 /0

AW

G

1- 1/C

-3

K

CM

IL

PP-1

MAIN

WEST LAB

400/400

PANEL

"PP-1"

CAN

TRANSFORMER

CAN

TRANSFORMER

1- 1/C

-3

K

CM

IL

CENTRAL

SWITCH

CAGE TX

150 KVA

2.4-0.208KV

3%

1- 1/C

-6 A

W G

1- 1/C

-5

K

CM

IL

PAD

TRANSFORMER

1- 1/C

-2 /0

AW

G

PANEL

"B-BLOCK"

1- 1/C

-4 /0

AW

G

PANEL

"G-BLOCK"

1- 1/C

-2 /0

AW

G

PANEL

"D-BLOCK"

1- 1/C

-4 /0

AW

G

PANEL

"E-BLOCK"

PANEL "CAGE"

CAGE

ITE JD

400/400

CAGE PNL.2

ITE JD

400/400

CAGE PNL.4

ITE JD

225/150

CAGE PNL.6

ITE JD

225/125

CAGE PNL.3

ITE JD

225/125

ADMIN TX

150 KVA

2.4-0.208KV

3.9%

1- 1/C

-6 A

W G

1- 1/C

-5

K

CM

IL

PAD

TRANSFORMER

1- 1/C

-4 /0

AW

G

ROT

DISC

SCD Q2L

225/200

1- 1/C

-4 /0

AW

G

PANEL

"ADMIN"

PANEL

"ROT"

ADMIN

DISC

SQD Q2L

225/200

PDP-1

75 KVA

2.4-0.48KV

2.7%

1- 1/C

-6 A

W G

1- 1/C

-3 /0

AW

G

PANEL

"PDP-1"

SQD FH

100/60

PDP-1

DISC

SQD LAL

400/125

1- 1/C

-6 A

W G

PANEL

"ERU"

SQD FH

1- 1/C

-3

K

CM

IL

BRK CNTR

MAIN

SWITCH

WARDEMS TX

75 KVA

2.4-0.48KV

1.8%

PAD

TRANSFORMER

1- 1/C

-6 A

W G

1- 1/C

-4 /0

AW

G

WARDEN

DISC

SQD Q2

225/200

MBRK

PANEL

"WARDEN"

112.5 KVA

PAD

TRANSFORMER

BRR CNTR MN.1

GE TFK

225/70

BROOK CENTER

BRK CNTR MN

1- 1/C

-6 A

W G

1- 1/C

-1 /0

AW

G

1- 1/C

-2 A

W G

1- 1/C

-2 A

W G

1- 1/C

-2

K

CM

IL

PANEL

"MECH RM"

PANEL

"RM 112"

PANEL

"E HALL"

"EMERG"

PANEL

"LPA"

PANEL

"PPA"

BRK CENTER TX

225 KVA

2.4-0.208KV

4.8%

BRR CNTR MN.2

GE TFK

225/125

BRR CNTR MN.3

GE TFK

225/70

1- 1/C

-2 A

W G

1- 1/C

-2 A

W G

PANEL

"E"

PANEL

"N"

E ACCU

DISC

BUSS FRS-R

(RK-5)

100A

N ACCU

DISC

BUSS FRS-R

(RK-5)

100A

1- 1/C

-2 A

W G

1- 1/C

-2 A

W G

BRR CNTR MN.4

GE TFK

225/70

BRR CNTR MN.XX

GE TFK

225/100

BRR CNTR MN.XX

GE TFK

225/100

BRR CNTR MN.7

GE TJK4

400/400

CAGE

SWITCH

0V

0V

0V

BRK CNTR

MAIN

SWITCHDEMO/REMOVE

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

1 1 1111 1

1 1 11111

1 1

1 1

1 1

NCNO

333333

3 3

8 BROOKS CENTER

9 ADMIN BUILDING

3 3 3

33 3

4 44

5 555

10 CENTRAL KITCHEN/ NORTH

6 6 6

11 CENTRAL KITCHEN/ SOUTH

12 PROGRAMS BUILDING

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT & REMOVE EXISTING LOOP #2 PRIMARY CABLE. ASSOCIATED

CONDUIT TO REMAIN.

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO REMAIN.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE.

DISCONNECT & REMOVE FEEDER FROM EQUIPMENT BEING REMOVED.

ASSOCIATED CONDUIT & WIRE TO REMAIN.

DISCONNECT & REMOVE EXISTING FEEDER. REMOVE ASSOCIATED CONDUIT

& WIRE.

DEMOLITION NOTES

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

E-602

JKB

JFS

ELECTRICAL RISER DIAGRAM -

DEMOLITION

CIRCUIT

BREAKER

G

GENERATOR

TRANSFORMER

480V-2.4KV, 3PH

GENERATOR HVDS

400A

250AF

MN UTIL

23.86MVA

8 (X/R)

23.86MVA

8 (X/R)

MN UTIL TX

750 KVA

2.4 - 2.4KV

5.5%

1- 1/C

-5

K

CM

IL

INCOMING LINE

250A

#3/0

ATS

SECTION 1 SECTION 2/3

SAPRE AERIAL

SECTION 4

HOUSE #1 LOOP #1

SECTION 5

HOUSE #2 LOOP #2

SECTION 6

EXISTING

PRIMARY SWITCHGEAR - 2400V-3 PHASE, 1200A

OUTSIDE KITCHEN

150 KVA

0.480-0.240KV

KITCHEN (150 KVA)

2.4-0.480KV

4%

CAN

TRANSFORMER

CAN

TRANSFORMER

3X50KVA (150 KVA)

2.4-0.240KV

4%

POLE

TRANSFORMER

LN POLE 1

TD KIT-A

DISC

SQD Q2

225/150A

PANEL

KITCHEN

"B"

PANEL

TD KITCHEN

MBRK

C-H HLA600

600/600

PANEL

TD KITCHEN

"1"

SQD LA

400/400

PANEL

TD KITCHEN

"2"

SQD LA

250/225

PANEL

KITCHEN

"C. MBRK"

SQD LA

400/400

PANEL

"MCC2"

PANEL

KITCHEN

"D"

250A 250A 75A N.C.

100A 100A 100A 100A

P-DORM TX

150 KVA

2.4-0.240KV

4%

A-WING

DISC

BUSS REN (H)

80A

PANEL

"A-WING"

B-WING

DISC

BUSS REN (H)

80A

PANEL

"B-WING"

C-WING

DISC

BUSS REN (H)

80A

PANEL

"C-WING"

D-WING

DISC

BUSS REN (H)

80A

PANEL

"D-WING"

BARN 1

1-POLE

BARN 2

1-POLE

KITCHEN

DISC

PNL "C"

MBRK

100A

KITCHEN

UG

UG

UG

SAWMILL

3 OUTSIDE KITCHEN

EXIST.

EXIST.

EXIST.

EXIST. EXIST.

EXIST. EXIST.

EXIST.

EXIST.

1 1

3 UG

AERIAL SOUTH

1 1 6 1 6

NEWEXIST.

EXIST.

EXIST.

SHEET E-603

SHEET E-604

SHEET E-603

SHEET E-604

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND#2/0 (5KV)

(1) 4" CND

HANDHOLE

PMH

PANEL

NEW

"OK"

3Ø, 4W

2 SETS OF

(4) 4/0

(1) #4 GND

(1) 2-1/2" CND

2 SETS OF

(4) 300KCMIL

(1) #1 GND

(1) 3" CND

2 SETS OF

(4) 3/0

(1) #6 GND

(1) 2" CND

2 SETS OF

(4) 300KCMIL

(1) #1 GND

(1) 3" CND

ELECTRICAL KEY NOTES

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO

REMAIN.

PROVIDE AND INSTALL NEW PAD MOUNT TRANSFORMER (150KVA, PRIM:

2400V - 3Ø, SEC: 120/240V - 3Ø). FEED TRANSFORMER FROM POWER PLANT

THRU EXISTING CONDUIT UNDERGROUND CONDUIT. RECONNECT EXISTING

BUILDING SERVICE TO NEW TRANSFORMER.

EXISTING CONDUIT TO REMAIN. REMOVE THE EXISTING WIRE AND PROVIDE

AND INSTALL NEW WIRING.

PROVIDE AND INSTALL NEW TRANSFORMER (150KVA, PRIM: 277/480V - 3Ø,

SEC: 120/240V - 3Ø). FEED TRANSFORMER FROM PANEL "MDPK"

RECONNECT EXISTING EQUIPMENT TO TRANSFORMER.

REPLACE PRIMARY CABLE. INSTALL NEW PRIMARY CABLES IN CONDUIT.

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

E-603

JKB

JFS

ELECTRICAL RISER DIAGRAM -

NEW

ELECTRICAL RISER DIAGRAM - NEW

MN UTIL

23.86MVA

HOUSE TX.7

SQD KAL

250/225

POWERHOUSE BUILDING

HOUSE TX.2

WEST LAB

400/300

HOUSE TX.3

WEST JA

225/125

HOUSE TX.4

WEST JA

225/200

HOUSE TX.1

SQD KAL

250/225

HOUSE SERV 1 TX

EXISTING

HOUSE 1

HOUSE TX

300 KVA

0.48-0.240KV

4%

EXISTING

ELC FD PMP CP.MDS

SHAWMUT TRS (RK5)

150A

0.48 KV

EXISTING

ELC FD PMP PANEL

EXIST.

"MCC-1"

PANEL

EXIST.

"LTG"

MAIN

PANEL

EXIST.

"RM"

TURBINE

MDP-1

100A

EXISTING

MAIN DISTRIBUTION PANEL "MDP"

MDP-2

200A

MDP-3

200A

MDP-4

200A

MDP-5

20A

HOUSE SERV 1 TX

MDP-6

60A

MDP-7

60A

MDP-8

50A

MDP-9

150A

PANEL

EXIST.

"CHAPEL"

PANEL

EXIST.

"O-DORM"

PANEL

EXIST.

"QUARTER

MASTER"

PANEL

EXIST.

"PROP/

LAUNDRY"

PANEL

EXIST.

"GREENHOUSE"

O-DORM

DISC

SQD Q2

225/200A

MBRK

LC-1 LC-2 LCP

EXIST.

LIGHTING CONTROLS

EXIST.

NORTH

SITE

LIGHTS

EXIST.

SOUTH

SITE

LIGHTS

EXIST.

BIG GATE

EXIST.

TRASH

COMPACTOR

EXIST.

POST

2 & 3

TOWERS

PANEL

EXIST.

"TD

SCHOOL

HEALTHCARE"

MDP

DISC

600A

T-1

300KVA

2.4-0.240KV

EXISTING

MAIN

TRANSFORMER

EXISTING

"HVDS"

HIGH VOLTAGE

DISCONNECT SWITCH

MSI PNL A TX

45 KVA

0.48-0.240KV

4%

MSI PNL B TX

45 KVA

0.48-0.240KV

6.11%

ANEX TX

45 KVA

0.48-0.240KV

6.11%

ANNEX

DISC

SQD KA

250/125A

MBRK

PANEL

EXIST.

"ANNEX"

PANEL

EXIST.

"MSI-B"

PANEL

EXIST.

"MSI--A"

MSI A.19

DISC

C-H GHB

100/60

MBRK

ANNEX

DISC

BUSS RES (H)

250/125A

FUSE

MSI A.15

DISC

C-H GHB

100/60

MBRK

MSI

DISC

BUSS NOS (H)

100/600A

250A

FUSE

MSI TX

150KVA

2.4-0.48KV

4%

PAD MOUNT

BUILDING TRADES

J-BOX

N DORM

112KVA

2.4-0.240KV

1.6%

N DRM

DISC

WEST LAB

400/300

MBRK

N DRM PNL-3

WEST JB

250/200

EXISTING

PANEL "N DORM"

N DRM PNL-2

WEST JB

250/200

N DRM PNL-5

WEST JB

250/200

PANEL

EXIST.

"WEST WING"

PANEL

EXIST.

"EAST WING"

PANEL

EXIST.

"N DORM-A"

HS 2 SWGR.XX

SQD KAL

250/225

HS 2 SWGR

EXISTING

HOUSE 2

HS 2 TX

300KVA

2.4-0.48KV

5.6%

HS 2 SWGR.2

SQD KAL

250/225

HS 2 SWGR.4

SQD KAL

250/125

HS 2 SWGR.6

SQD FAL

100/70

HS 2 SWGR.X

SQD KAL

250/125

PANEL

EXIST.

"MCC-2"

PANEL

EXIST.

"OFFICE"

PANEL

EXIST.

"CHILLER #2"

PANEL

EXIST.

"CHILLER #1"

HS 2 SWGR

SQD LA

400/400

HOUSE SERV 1 TX

300 KVA

2.4-0.240KV

5.45%

A DRM SWGR.1

WEST KA

225/100

A-DORM

A DRM SWGR.2

WEST KA

225/150

A DRM SWGR.3

WEST KA

225/225

A DRM SWGR.4

WEST KA

225/150

A DRM SWGR.6

WEST KA

225/200

A DRM SWGR.7

WEST KA

225/175

A DRM SWGR.8

WEST KA

225/100

PANEL

EXIST.

"H"

PANEL

EXIST.

"E"

PANEL

EXIST.

"A"

PANEL

EXIST.

"C"

PANEL

EXIST.

"D"

PANEL

EXIST.

"B"

PANEL

EXIST.

"G"

LOOP 2 BK FD

225KVA

2.4-0.208KV

4.8%

A DRM TX

225 KVA

2.4-0.208KV

4.8%

TAP-BOX

EXISTING

60 KVA

4TH FLOOR

DRY TYPE

CAN

TRANSFORMER

60 KVA

4TH FLOOR

DRY TYPE

WRH HS

SQD Q2

225/100

1- 1/C

-1 A

W G

PANEL

EXIST.

"A"

WAREHOUSE

WRH HS

WEST KA

225/200

MBRK

NO NC

NORTH SOUTH

EXISTING

150KVA

2.4-0.48KV

EXISTING

TAP-BOX IN

TUNNEL

K

WAREHOUSE

K

NEW

TAP BOX IN TUNNEL

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

EXISTING XMRF1 FOOD WAREHOUSE

SHEET E-600

SHEET E-601

SHEET E-600

SHEET E-601

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

2 A-DORM

EXISTING

TAP-BOX IN

A-DORM BASEMENT

EXISTING

A-DORM SWITCHGEAR

8 8

EXIST.

EXIST.

7 7 7 7 7 7 7

EXISTING

PULL BOX (BASEMENT

OF PENTHOUSE)

NONC

NONC

NEW

TAP BOX IN TUNNEL

NEW

TAP BOX IN TUNNEL

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

EXISTING XMRF

6 TD CHAPEL

77 7 7 7 7 7 7 7

7 7 7

EXIST.

EXIST.

777 7 7 7 7 7 7

EXISTING

TRANSFORMER

EXISTING

SWITCH

EXISTING

SWITCH

EXISTING

PAD MOUNT

TRANSFORMER

EXIST.

7 7

7 7

7 7

9 9 9

7 BUILDING TRADES

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

PANEL

EXIST.

"ERT"

100A

(4) #2

(1) #8 GND

(1) 2" CND

ELECTRICAL KEY NOTES

REPLACE PRIMARY CABLE FROM POWER HOUSE TO FOOD WAREHOUSE.

INSTALL NEW PRIMARY CABLES IN CONDUIT.

PROVIDE AND INSTALL NEW TAP BOX IN TUNNEL ON LOOP #2.

PROVIDE AND INSTALL NEW TWO POSITION SWITCHES AND REFEED

EXISTING TRANSFORMER FROM THIS SWITCH.

REPLACE LOOP #1 PRIMARY CABLE FROM TAP BOX IN TUNNEL TO FOOD

WAREHOUSE. INSTALL NEW PRIMARY CABLES IN CONDUIT.

PROVIDE AND INSTALL NEW LOOP #2 FEEDER FROM TAP BOX IN TUNNEL TO

FOOD WAREHOUSE. INSTALL NEW PRIMARY CABLES IN CONDUIT.

RECONNECT EXISTING TRANSFORMER TO NEW SWITCH.

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO

REMAIN.

REPLACE PRIMARY CABLE FROM FOOD WAREHOUSE TO A-DORM. INSTALL

NEW PRIMARY CABLES IN CONDUIT.

PROVIDE PREVENTIVE MAINTENANCE ON EQUIPMENT.

PROVIDE AND INSTALL NEW PRIMARY LOOP #1 CABLE FROM TD CHAPEL

SWITCH FROM POWER HOUSE. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM TD CHAPEL SWITCH

THRU MANHOLE IN SALLY PORT TO EXISTING TRANSFORMER NORTH OF

BUILDING TRADES. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

E-604

JKB

JFS

ELECTRICAL RISER DIAGRAM -

NEW

KIT

DISC

400A

PANEL

EXIST.

"VOC

SCHOOL"

PANEL

EXIST.

"CHAPEL 1"

SERV

MN

WEST LAB

400/200

KIT

DISC

BUSS FRS-R

(RK15)

200A

LAUNDRY

DISC

BUSS FRS-R

(RK15)

100A

PANEL

EXIST.

"LAUNDRY"

KIT TX

112.5 KVA

0.48-0.208KV

4.7%

KIT

DISC-1

SHAWMUT TR

(RK5)

350A

AA

DISC

BUSS FRS-R

(RK5)

200A

BB

DISC

BUSS FRS-R

(RK5)

200A

PANEL

EXIST.

"RP5"

PANEL

EXIST.

"MCC1"

INDUSTRY

DISC

WEST EHB

100/100

PANEL

EXIST.

"LIBRARY"

PANEL

EXIST.

"INDUSTRY"

LIBRARY

DISC

WEST EHB

100/100

EXISTING

LIBRARY THROUGH

PP-1 TX

150 KVA

2.4-0.208KV

4%

PP-1

MAIN

WEST LAB

400/400

PANEL

EXIST.

"PP-1"

NEW

TRANSFORMER

CAGE TX

300 KVA

0.48-0.208KV

3%

PANEL

EXIST.

"B-BLOCK"

PANEL

EXIST.

"G-BLOCK"

PANEL

EXIST.

"D-BLOCK"

PANEL

EXIST.

"E-BLOCK"

PANEL "CAGE"

CAGE

800 CAGE PNL.2

ITE JD

400/400

CAGE PNL.4

ITE JD

225/150

CAGE PNL.6

ITE JD

225/125

CAGE PNL.3

ITE JD

225/125

ROT

DISC

SCD Q2L

225/200

PANEL

EXIST.

"ADMIN"

PANEL

EXIST.

"ROT"

ADMIN

DISC

SQD Q2L

225/200

1- 1/C

-3 /0

AW

G

PANEL

EXIST.

"PDP-1"

SQD FH

100/60

PDP-1

DISC

SQD LAL

400/125

PANEL

EXIST.

"ERU"

SQD FH

BRK CNTR

MAIN

SWITCH

WARDEMS TX

75 KVA

2.4-0.48KV

1.8%

EXISTING

TRANSFORMER

WARDEN

DISC

SQD Q2

225/200

MBRK

PANEL

EXIST.

"WARDEN"

112.5 KVA

EXISTING

TRANSFORMER

BRR CNTR MN.1

GE TFK

225/70

BROOK CENTER

EXISTING

BRK CNTR MN

PANEL

EXIST.

"MECH RM"

PANEL

EXIST.

"RM 112"

PANEL

EXIST.

"E HALL"

"EMERG"

PANEL

EXIST.

"LPA"

PANEL

EXIST.

"PPA"

BRK CENTER TX

225 KVA

2.4-0.208KV

4.8%

BRR CNTR MN.2

GE TFK

225/125

BRR CNTR MN.3

GE TFK

225/70

PANEL

EXIST.

"E"

PANEL

EXIST.

"N"

E ACCU

DISC

BUSS FRS-R

(RK-5)

100A

N ACCU

DISC

BUSS FRS-R

(RK-5)

100A

BRR CNTR MN.4

GE TFK

225/70

BRR CNTR MN.XX

GE TFK

225/100

BRR CNTR MN.XX

GE TFK

225/100

BRR CNTR MN.7

GE TJK4

400/400

BRK CNTR

MAIN

SWITCH

NEW

2.4-.48KV

300 KVA

PANEL

NEW

"DP-A"

277/480V 3Ø 4W

1000A MCB

NEW

.48-.24KV

15 KVA

NEW

2.4-.48KV

225KVA

PANEL

NEW

"DP-L"

277/480V 3Ø 4W

300A MCB

NEW

.48-.208KV

NEW

.48-.24KV

ADMIN

750 KVA

2.4-0.48KV

PANEL

NEW

"MDP-A"

277/480V 3Ø 4W

800A MCB

CAGE PNL.3

ITE JD

225/200

CAGE PNL.3

ITE JD

225/200

NEW

TRANSFORMER

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

NCNO

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

NCNC

EXIST. EXIST.

EXIST.

EXIST.EXIST.

EXIST. EXIST.

EXIST.EXIST.

EXIST. EXIST.

EXIST. EXIST.

EXIST.

EXIST.

EXIST.

7 77

777777

NEW

TRANSFORMER

7 7

8 BROOKS CENTER

9 ADMIN BUILDING

NCNC

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

131313131313

EXIST.

10 CENTRAL KITCHEN/ NORTH

NCNC

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

11 CENTRAL KITCHEN/ SOUTH

NCNC

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

12 PROGRAMS BUILDING

414 1415

EXIST.

EXIST.

(4) 350 KCMIL

(1) #4 GND

(1) 3" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

(4) #2

(1) #8 GND

(1) 1 1/4" CND

(4) 350 KCMIL

(1) #4 GND

(1) 3" CND

(4) #2

(1) #8 GND

(1) 1 1/4" CND

3 SETS OF

(4) 350 KCMIL

(1) #2/0 GND

(1) 3" CND

(4) 500 KCMIL

(1) #3 GND

(1) 3" CND

(4) 500 KCMIL

(1) #3 GND

(1) 3" CND

(4) 500 KCMIL

(1) #3 GND

(1) 3" CND

(4) #2 KCMIL

(1) #8 GND

(1) 1 1/4" CND

(4) #10

(1) #12 GND

(1) 3/4" CND

(4) 400 KCMILL

(1) #1/0 GND

(1) 3" CND

2 SETS OF

(4) 400 KCMILL

(1) #1/0 GND

(1) 3" CND

2 SETS OF

(4) 400 KCMILL

(1) #1/0 GND

(1) 3" CND

(4) #1

(1) #6 GND

(1) 1 1/2" CND

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM BROOKS CENTER TO

NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN TO

NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW TWO POSITION SWITCHES AND REFEED

EXISTING TRANSFORMER FROM THIS SWITCH.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN

SOUTH TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN

SOUTH TO NEW SWITCH IN TUNNEL. INSTALL NEW PRIMARY CABLES IN

EXISTING CONDUIT.

PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A" 277/480V-3Ø, 4W 800A

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO

REMAIN.

PROVIDE AND INSTALL NEW 750 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW AMDIN SWITCH (LOOP #2 FEED).

PROVIDE PREVENTIVE MAINTENANCE ON EQUIPMENT.

PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 277/480V/ SEC:

120/208V - 3Ø, 4W FEED FROM NEW 480V PANEL "MDP-A".

PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A1" 120/208V-3Ø, 4W 800A.

PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 2400V/ SEC:

120/208V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN NORTH SWITCH

(LOOP #2 FEED).

RECONNECT FEEDER FROM EQUIPMENT BEING ADD. ASSOCIATED CONDUIT

& WIRE TO REMAIN.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN

SOUTH TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROMPROGRAMS BUILDING TO

NEW SWITCH IN TUNNEL. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN SOUTH SWITCH

(LOOP #2 FEED).

PROVIDE AND INSTALL NEW 225 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW PROGRAMS SWITCH (LOOP #2 FEED).

PROVIDE AND INSTALL NEW 50 KVA TRANSFORMER PRIM: 277/480V/ SEC:

120/240V - 1Ø, 3W FEED FROM NEW 225 KVA PROGRAMS TRANSFORMER.

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a tr ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/24/2023

E-605

JKB

JFS

ELECTRICAL RISER DIAGRAM -

NEW

E500-2261200-Layout1
E501-2261200-Layout1
E502-2261200-Layout1
E503-2261200-Layout1
E504-2261200-Layout1
E505-2261200-Layout1
E600-2261200-30x40 - E600
E601-2261200-30x40 - E601
E602-2261200-30x40 - E600
E603-2261200-Layout1
E604-2261200-Layout1
E605-2261200-Layout1

File details come from the government source that posted it. Updated .