Drawings-1.pdf
PDF 3 MB Posted
- Solicitation number
- RFQ - 171 - 240000000053
- Issued by
- Alger County, Michigan
About this file
The document is a set of electrical drawings and specifications related to a state and local contract opportunity issued by the State of Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The scope of work includes upgrading the primary electrical infrastructure at various facilities, such as installing new transformers, switches, and distribution panels. The work involves replacing cables, installing new conduits, and performing preventative maintenance on existing electrical gear. The project will be awarded as a single construction contract, with a completion date of October 24, 2023. Contractors are required to visit the site during the pre-bid walkthrough to determine the full extent of the work. The contract also includes concrete specifications, trench details, and electrical symbols and legends.
The document does not provide pricing terms or funding information. It also does not mention any set-asides, incumbents, or renewal options. Contractors must submit their bids through the SIGMA VSS online system, with a deadline of 2:00 PM on the due date. Questions should be emailed to the designated contact, and contractors experiencing issues with the electronic submission process should notify the Office of Design and Construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum 2.pdf | ||
| Technical Specifications.pdf | ||
| Addendum 4.pdf | ||
| Drawings-2.pdf | ||
| DTMB-0415 Advertisement (Rev 10-22).pdf | ||
| LEIN Request 22442.pdf | ||
| Front End Specification.pdf | ||
| Addendum 3.pdf | ||
| Prevailing Wages 231024 Marquette County 22442.pdf | ||
| Addendum 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N MAP
JFS
JKB
E-000
TITLE PAGE
SCALE: N.T.S.
file no.
checked by drawn by consultant issue date contract order no.
472MBPMAINTPROJ
consultant job no.
22612.00
M a tr ix
472/224422.JBB
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N xx
CD SET 10/24/2023
X
X
X
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE
DOCK LIGHT FIXTURE
TELEPHONE / DATA OUTLET
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
ELECTRICAL SYMBOLS LEGEND
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER
MAGNETIC STARTER
DISCONNECT SWITCH
TRANSFORMER
CONTROL
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
DESIGNATIONS
(by E.C.)
(by others)
TT
G
WW
PC
CT
TS
T
H
TC
T
1,3
OR
PM
WM
BD
UFD
F S
J
J
D
WH
PP
J
DIGITAL EQUIPMENT METER, AS REQUIRED
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST (E)
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
GENERAL ELECTRICAL NOTES
1. ALL NON-FIRE RATED SURFACES ARE TO BE PATCHED WITH LIKE
MATERIAL TO MAINTAIN ORIGINAL RATING.
2. ALL PENETRATIONS THROUGH FIRE RATED SURFACES ARE TO BE
SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL RATING.
3. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID
WALK THROUGH TO DETERMINE THE EXACT EXTENT OF THE WORK
REQUIRED BEFORE BIDDING THE PROJECT.
4. REMOVE ALL EXISTING EXPOSED CONDUIT, WIRE, AND EQUIPMENT
NOT TO BE RE-USED WHERE WORK IS BEING DONE EXCEPT ITEMS
NOTED OTHERWISE.
5. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL
REMAIN CONCEALED AND DOES NOT INTERFERE WITH ANY NEW
WORK OF ANY TRADE NEED NOT BE REMOVED. HOWEVER, ALL
CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND THEN
PATCHED AND PAINTED TO MATCH, OR AS NOTED.
6. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF
OLD WORK, SURFACES SHALL BE PATCHED AND PAINTED TO MATCH
ADJACENT.
7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE
MODIFIED OR ENLARGED TO SUIT THE NEW SYSTEMS AS REQUIRED.
PROVIDE ALL REQUIRED CUTTING AND PATCHING.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING
WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE
MOUNTED EQUIPMENT.
9. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENTS AND
CASUAL FIELD OBSERVATION. REPORT ANY DISCREPANCIES TO
ENGINEER FOR CLARIFICATION.
10. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. ALL FLEXIBLE CONDUIT
RACEWAYS SHALL BE LIQUID TITE, MAXIMUM 36" LENGTH. REFER TO
SPECIFICATION 260533 - RACEWAY AND BOXES FOR ELECTRICAL
SYSTEMS.
11. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING
REQUIREMENTS:
11.1. STRAP DISTANCE: 5 FEET.
11.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
11.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED-
GRC.
11.4. FITTINGS: COMPRESSION.
11.5. BELL BOXES: FS TYPE.
11.6. NO KNOCKOUTS.
11.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND
ENCLOSURES.
12. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING
REQUIREMENTS:
12.1. STRAP DISTANCE: 3 FEET.
12.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
12.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED -
GRC.
12.4. FITTINGS: COMPRESSION.
12.5. BELL BOXES: FS TYPE.
12.6. NO KNOCKOUTS.
12.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND
ENCLOSURES
13. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE
WIRING ABOVE CEILINGS IS ACCEPTABLE.
14. ALL NEW CONDUITS AND WIRES SHALL BE INSTALLED STRAIGHT AND
LEVEL AND SHALL BE PARALLEL OR PERPENDICULAR TO THE
BUILDING LINES.
15. ALL NEW CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING
PIPING AND STRUCTURAL STEEL.
16. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE
SURFACE MOUNTED CONDUIT FOLLOWING NOTES 10 THROUGH 12
ABOVE.
17. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE
CUT INTO WALL.
18. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC,
TYPE EPC-40-PVC
19. ALL ELECTRICAL OUTAGES SHALL NOT LAST OVER 2-HOURS.
PORTABLE GENERATORS SHALL BE USED TO REPLACE ANY
ELECTRICAL SERVICE EXCEEDING THAT DURATION.
20. IN RELATION TO RELOCATING ANY ELECTRICAL DEVICE,
CONTRACTOR SHALL COMPLETE THE RELOCATION IN ONE DAY AND
VERIFY THAT ALL DEVICES RELOCATED ARE WORKING PROPERLY
PRIOR TO LEAVING THE SITE.
21. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED
COMPONENTS, RACEWAYS, WIRE, AND HARDWARE AS INDICATED ON
DRAWINGS.
22. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT
CONTRACTORS RISK.
23. CONTRACTOR SHALL CONTACT COMMTECH FOR SPECIFICATIONS
FOR CAT6 AND OTHER LOW VOLTAGE REQUIREMENTS.
24. CONTRACTOR SHALL PERFORM GROUND PENETRATION RADAR
(GPR) SURVEY TO LOCATE SUB-SURFACE UTILITIES AND OBSTACLES
PRIOR TO EXCAVATION. CONTRACTOR IS RESPONSIBLE FOR
REPAIRS TO ITEMS DAMAGED DURING EXCAVATION AND BORING.
FACILITY SHALL BE INFORMED IMMEDIATELY WHENEVER AN
INCIDENT OCCURS. CONTRACTOR SHALL PROVIDE A REPORT PER
SPECIFICATION SECTION 023123 - ELECTROMAGNETIC
INVESTIGATIONS.
25. ALL DIGGING DONE WITHIN THE SECURE PERIMETER SHALL BE
HYDRO-EXCAVATED PER SPECIFICATION SECTION - 023200.
1. MAIN SERVICE
INSTALL NEW UTILITY SERVICE EQUIPMENT AND FEEDERS. DISCONNECT EXISTING UTILITY FEED. COORDINATE ALL WORK WITH UTILITY
COMPANY.
2. OUTSIDE KITCHEN
REMOVE FOUR TRANSFORMERS AT SOUTH END OF BUILDING. INSTALL NEW PAD MOUNTED TRANSFORMER, 2400 VOLT TO 480 VOLT-3 PHASE, 150 KVA. INSTALL 480V TO 120/240V TRANSFORMER FEED TRANSFORMER. FROM POWER PLANT THRU EXISTING CONDUIT AND
NEW WIRE RECONNECT SERVICES FROM BUILDING TO NEW TRANSFORMER
3. PROGRAMS BUILDING
INSTALL NEW PRIMARY LOOP SWITCH NW OF PROGRAMS BUILDING. INSTALL NEW 2400 VOLT TO 480 VOLT, 225 KVA TRANSFORMER.
INSTALL SECONDARY FEED FROM TRANSFORMER TO PENTHOUSE OF PROGRAMS BUILDING. INSTALL STEP DOWN 50 KVA TRANSFORMER FOR 120/240VOLT LOADS. EXTEND LOOP 2 FROM CENTRAL KITCHEN / SOUTH TO LOOP SWITCH AND FROM LOOP
SWITCH BACK TO POWERHOUSE.
4. CENTRAL KITCHEN / SOUTH
INSTALL NEW PRIMARY LOOP SWITCH SE OF CENTRAL KITCHEN. INSTALL NEW PAD MOUNTED 2400 VOLT TO 480 VOLT, 300 KVA TRANSFORMER SE OF CENTRAL KITCHEN. RECONNECT LOADS IN LOWER LEVEL OF SOUTH SIDE OF CENTRAL KITCHEN. EXTEND LOOP 2
FROM CENTRAL KITCHEN / NORTH TO NEW LOOP SWITCH.
5. CENTRAL KITCHEN / NORTH
INSTALL NEW PRIMARY LOOP SWITCH NE OF CENTRAL KITCHEN. INSTALL NEW PAD MOUNTED 2400 TO 208 VOLT, 150 KVA TRANSFORMER. RECONNECT PP1 TO NEW TRANSFORMER. EXTEND LOOP 2 FROM ADMIN SWITCH TO LOOP SWITCH FEED CHAPEL
FROM PP1 AND BUCK BOOST 15 KVA TRANSFORMER.
6. ADMIN BUILDING
INSTALL NEW TWO POSITION PAD MOUNT SWITCHES WEST OF ADMIN. INSTALL NEW PRIMARY FEED FROM BROOKS CENTER TO NEW SWITCH (LOOP 2). INSTALL NEW 2400 VOLT TO 480 VOLT THREE PHASE 500 KVA TRANSFORMER. INSTALL 480 TO 208 VOLT, 150 KVA
TRANSFORMER. RECONNECT LOADS.
7. FOOD WAREHOUSE
REPLACE PRIMARY CABLE FROM POWERHOUSE TO FOOD WAREHOUSE - BOTH LOOP 1 AND 2, CABLES IN CONDUIT, CONDUIT IN TUNNEL. ADD TAP AND PULL BOX IN TUNNEL ON LOOP 2. ADD TWO POSITION SWITCH ON GRADE NEXT TO TRANSFORMER AND FEED
TRANSFORMER FROM THIS SWITCH.
8. A DORM
REPLACE BOTH LOOP #1 AND LOOP 2 PRIMARY CABLES FROM FOOD WAREHOUSE TO A DORM
PM SWITCHGEAR IN BASEMENT, CABLES IN CONDUIT, CONDUIT IN TUNNEL
9. AERIAL SERVICE - SOUTH
REMOVE OVERHEAD LINES FROM POLE WEST OF POWERHOUSE THAT FEEDS P DORM AND TWO BARNS OUTSIDE THE SECURE
PERIMETER. DIRECTIONAL BORE NEW PRIMARY LINES TO REFEED P DORM AND BARNS.
10. AERIAL SERVICE - NORTH
REMOVE OVERHEAD LINES FROM POLE WEST OF POWERHOUSE THAT FEEDS ERT TRANSFORMER AND BUILDING. REMOVE
TRANSFORMER, REFEED ERT FROM BUILDING TRADES BUILDING.
11. TD CHAPEL
INSTALL NEW PAD MOUNTED PRIMARY SWITCH WEST OF TD CHAPEL. INSTALL NEW LOOP 1 FEED FROM POWERHOUSE TO SWITCH
THRU TUNNEL IN EXISTING CONDUIT.
12. BUILDING TRADES
REPLACE PRIMARY CABLE FROM TD CHAPEL SWITCH THRU MANHOLE IN SALLY PORT TO TRANSFORMER NORTH OF BUILDING TRADES.
PREVENTATIVE MAINTENANCE ON SWITCHGEAR. RECONNECT LOADS.
13. BROOKS CENTER
PM ALL PRIMARY GEAR IN BROOKS CENTER ELECTRICAL ROOM
ELECTRICAL SEQUENCE OF WORK SUMMARY CONCRETE SPECIFICATIONS
1. CONCRETE MATERIAL SHALL BE:
1.1. ASTM C150 - TYPE 1 PORTLAND, COLOR SHALL MATCH EXISTING.
1.2. FINE AND COARSE AGGREGATES: ASTM C33, FINE MDOT DESIGNATED 2NS,
COARSE MDOT DESIGNATED 6AA.
1.3. WATER: CLEAN AND NOT DETRIMENTAL TO CONCRETE.
1.4. MIX CONCRETE IN ACCORDANCE WITH ASTM C94. MIXTURE SHALL BE
HIGH-EARLY IN ACCORDANCE WITH MDOT CONCRETE P-NC PER MDOT
STANDARD SPECIFCATIONS FOR CONSTRUCTION 2020, SECTION 603 AND
801.
2. THE CONCRETE DEPTH IS INDICATED ON THE DETAILS.
3. GRANULAR BASE SHALL BE 21AA CRUSHED LIMESTONE.
4. ADMIXTURES:
4.1. AIR ENTRAINMENT ASTM C260
4.2. CHEMICAL ASTM C494, TYPE B AND D ONLY, TYPE B - RETARDING TYPE D -
WATER REDUCING AND TESTING.
5. FORMED JOINTS:
5.1. PLACE EXPANSION JOINT FILLER BETWEEN PAVING COMPENTS, AND
BUILDING OR OTHER APPURTENANCES, EXCEPT WHERE SIDEWALK ABUTS
BITUMINOUS PAVEMENT. RECESS TOP OF FILLER 1/2 INCH.
6. PSI OF THE CONCRETE SHALL BE A MINIMUM OF 4,000 W/6-8% AIR INTRADEMENT
LIMESTONE MIX 4.5 TO 6.5 SLUMP.
7. REBAR SHALL BE PLACED IN CONCRETE PER THE INDUSTRY STANDARDS.
8. PLACING CONCRETE:
8.1. IN ACCORDANCE WITH ACI 301
8.2. ENSURE REINFORCEMENT, INSERTS, EMBEDDED PARTS AND FORMED
JOINTS ARE NOT DISTURBED DURING CONCRETE PLACEMENT.
8.3. POOR CONTINUOUSLY BETWEEN PREDETERMINED CONSTRUCTION JOINTS.
DO NOT BREAK OR INTERRUPT SUCCESSIVE POURS SUCH THAT COLD
JOINTS OCCUR.
9. SEALER:
9.1. PROVIDE AND INSTALL A PENETRATING SEALING COMPOUND ON BASES
EQUAL TO PENTREAT 244-100.
9.1.1. DESIGN TO LIMIT THE INTRUSION OF MOISTURE AND CHLORIDES INTO
THE SUBSTRATE.
9.1.2. REDUCES SPALLING.
9.1.3. PENETRATES DEEPLY FOR MAXIMUM PROTECTION.
9.1.4. MINIMIZES PENETRATION FROM DE-ICING CHEMICALS, SALT, WATER
THAT MIGHT DAMAGE CONCRETE SURFACES.
9.1.5. SEALS PORES AND CAPILLARIES OF SUBSTRATE, PREVENTING LIQUID
ABSORPTION WHILE ALLOWING EXCELLENT VAPOR TRANSMISSION.
9.1.6. LEAVES NO RESIDUE AND REQUIRES NO CLEANING AFTER
APPLICATION.
12" DEEP 4,000 PSI W/6-8% AIR INTRADMENT LIMESTONE MIX 4.5 TO
6.5 SLUMP FIBER MESH CONCRETE PAD WITH #4 REBAR
TOP OF CONCRETE PAD TO BE MINIMUM 4" ABOVE GRADE. REFER
TO CONCRETE SPECIFICATIONS ON SHEET E-100
1" BY 1"
CHAMFER
(ALL ROUND)
4'
12"
GRADE GRADE
8"
HOUSE KEEPING PADS PROVIDE 4" PAST THE
EQUIPMENT AND PROVIDE A 1" X 1" CHAMFER
AROUND ALL EDGES TYP.
1 CONCRETE PAD SECTION
SCALE:NTS
BASED ON
MANUFACTURER'S
RECOMMENDATIONS
BASED ON
MANUFACTURER'S
RECOMMENDATIONS
6" 6"
PLAN
2O"
ELECTRICAL
COMPOSITE GASKETED BOX, 2
REQUIRED,
QUASITE OR EQUAL
HEAVY DUTY, SKID-RESISTANT
COVER, BOLT-DOWN TYPE, TAMPER
RESISTANT HARDWARE
3" MIN. SAND OR
GRANULAR BACKFILL
3 ELECTRICAL HANDHOLE DETAIL
SCALE:NTS
LIFTING EYE
FINISHED GRADE
UNDISTURBED EARTH
CONDUIT
SECTION
36" MIN.
12" MIN.
BACKFILL WITH SITE EXCAVATED
MATERIAL. COMPACT TO 95%.
EXISTING GRADE
CONDUITS. SIZE AND QUANTITY AS
SHOWN ON SITE PLAN.
RESTORE SURFACE TO
ORIGINAL CONDITION.
2 TYPICAL TRENCH DETAIL
SCALE:NTS
file no.
checked by drawn by consultant issue date contract order no.
472MBPMAINTPROJ
consultant job no.
22612.00
M a tr ix
472/224422.JBB
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N xx
CD SET 10/24/2023
E-100
JKB
JFS
ELECTRICAL SYMBOLS, NOTES,
AND ABBREVIATIONS
EXISTING
SWITCH
EXISTING
SWITCH
LOOP #2 OPEN
LOOP #1 CLOSE
T
ELECTRICAL ROOM MAIN
FLOOR
ELECTRICAL ROOM (BASEMENT)
T
EXISTING
XMRF-T-1
EXISTING
MDP
EXIST
FUSES
T
EXISTING
TAP BOX
EXISTING
TAP BOX
EXISTING
A DORM
SWITCH GEAR
LOCATED IN
BASEMENT
EXISTING
TRANSFORMER
EXISTING
PULL BOX (BASEMENT)
EXISTING
PULL BOX (BASEMENT)
T
EXISTING
TRANSFORMER (LTG)
EXISTING
PANEL (120/240V)
EXISTING
PRIMARY (MAIN LEVEL)
EXISTING
GEAR (BASEMENT)
TO
UTILITY
MAN HOLE
T
EXISTING
HVSW
T
EXISTING
TRANSFORMER
EXISTING
TRANSFORMER
EXISTING
TRANSFORMER
(WARDEN)
EXISTING
LIGHT POLE
T
EXISTING
TRANSFORMER
T
EXISTING
TRANSFORMER
EXISTING
SWITCH
EXISTING
SWITCH
T
T
EXISTING
TRANSFORMERS
EXISTING
TRANSFORMERS
IN PENTHOUSE
T
EXISTING
TRANSFORMER
T
EXISTING
TRANSFORMER
T
T
T
EXISTING
TRANSFORMER
EXISTING
TRANSFORMER
EXISTING
GEAR
file no.
checked by drawn by consultant issue date contract order no.
472MBPMAINTPROJ
consultant job no.
22612.00
M a tr ix
472/224422.JBB
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N xx
CD SET 10/24/2023
N ELECTRICAL SITE PLAN - EXISTING LAYOUT
SCALE: 1" = 60'-0"
400 10 20 80 150
E-200
JKB
JFS
ELECTRICAL SITE PLAN -
EXISTING LAYOUT
J
TW
JJ
EXISTING
TAP BOX
EXISTING
A DORM
SWITCH GEAR
LOCATED IN
BASEMENT
LOOP #1
EXISTING
TRANSFORMER
NEW
SWITCH
NEMA3R
NEW
TAP BOX
LOOP #2
EXISTING
TAP BOX
EXISTING
PULL BOX (BASEMENT)
EXISTING
PRIMARY (MAIN LEVEL)
EXISTING
GEAR (BASEMENT)
EXISTING
PULL BOX (BASEMENT)
TK
NEW
TRANSFORMER
PMH
HH
HH
HH
TEX
TEX
TEX
HH
NEW
HANDHOLE
NEW
HANDHOLE
NEW
HANDHOLE
EXISTING
TRANSFORMER
EXISTING
TRANSFORMER
EXISTING
TRANSFORMER
NEW
HANDHOLE
HH
EXISTING
PNL "MDP"
NEW
HANDHOLE
TEX
EXISTING
TRANSFORMER
T
J J
EXISTING
TRANSFORMER
EXISTING
PANEL "MDP"
NEW
SWITCH
NEMA3R
NEW
TAP BOX
EXISTING
MANHOLE
LOOP #2T
TEXTEX
EXISTING
TRANSFORMER
EXISTING
SWITCH
TT
LOOP #1
NEW
TRANSFORMER
NEW
SWITCH
NEMA3RNEW
277/480V-3Ø, 4W
PNL "MDP-A"NEW
120/208V-3Ø, 4W
PNL "MDP-A1"
T
T
T
HH
NEW
TRANSFORMER
NEW
HANDHOLE
NEW
TRANSFORMER
NEW
TRANSFORMER
NEW
SWITCH
NEMA3R
NEW
SWITCH
NEMA3R
NEW
TRANSFORMER
NEW
TRANSFORMER
EXISTING
PNL "PP1"
EXISTING
PNL "MDP2"
T
T
T
HH
T
NEW
TRANSFORMER
NEW
PMH
file no.
checked by drawn by consultant issue date contract order no.
472MBPMAINTPROJ
consultant job no.
22612.00
M a tr ix
472/224422.JBB
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N xx
CD SET 10/24/2023
N ELECTRICAL SITE PLAN - NEW LAYOUT
SCALE: 1" = 60'-0"
400 10 20 80 150
E-201
JKB
JFS
ELECTRICAL SITE PLAN -
NEW LAYOUT
T
POWER
POLE
POWER
POLE
T
T
LOCATED IN BASEMENT
T
T
MAN HOLE
T
T
T
T
T T
TT
T
E500
E500
E500
E501
E502
E503
E503
E504
E505
E505
E504
E504
T file no.
checked by drawn by consultant issue date contract order no.
472MBPMAINTPROJ
consultant job no.
22612.00
M a tr ix
472/224422.JBB
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N xx
CD SET 10/24/2023
N ELECTRICAL SCOPE OF WORK - SITE PLAN
SCALE: 1" = 60'-0"
400 10 20 80 150
E-202
JKB
JFS
ELECTRICAL SCOPE OF WORK -
SITE PLAN
| E-000-2261200-E-000 |