This document is Addendum No. 2 for the Marquette Branch Prison - Primary Electrical Infrastructure Upgrades project, issued by the Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division in the State of Michigan. The addendum provides clarification and responses to questions regarding electrical specifications, including information on panels, transformers, cables, and conduits. It also includes an electrical riser diagram with key notes on the new electrical system components. The project is funded under File #472/22442.JBB and involves upgrades to the primary electrical infrastructure at the Marquette Branch Prison facility.

The addendum provides details on the electrical equipment and cabling to be installed, including voltage ratings, amperage, number of poles, and conductor sizes. It confirms that the utility company will provide the transformer and base, and that the contractor will need to install new primary cables in conduit. The project appears to involve multiple buildings and electrical system modifications throughout the prison facility.

View the file

Other files

File Type Posted
Technical Specifications.pdf PDF
Addendum 4.pdf PDF
Drawings-2.pdf PDF
DTMB-0415 Advertisement (Rev 10-22).pdf PDF
LEIN Request 22442.pdf PDF
Front End Specification.pdf PDF
Addendum 3.pdf PDF
Prevailing Wages 231024 Marquette County 22442.pdf PDF
Addendum 1.pdf PDF
Drawings-1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1601 E. CÉSAR E. CHÁVEZ AVENUE, LANSING, MI 48906

PHONE: (517) 487-2511

FAX: (517) 487-2544

ADDENDUM NO. 2

Date: 12/01/23 Project Name: Marquette Branch Prison - Primary Electrical Infrastructure Upgrades File # 472/22442.JBB Funding Code # 472/MBPMaintProj

This Addendum is issued for the purpose of modifying and/or clarifying the original Contract Documents and shall take precedence over them.

All work included herein shall be in accordance with the original drawings and specifications except as specifically noted herein. All incidental items required to provide the following modifications shall be included even though not specifically described.

This addendum is being sent to all bidders receiving plans and specifications. Receipt of this Addendum shall be noted on the Bid Summary in the appropriate location.

Clarification and Questions:

A2.1 Question: Please provide information on panel “OK”?

Response: 480V-3PH, 400 Amp Main Breaker 42 circuit panel with the following breakers:

a. (1) 200-amp, 3-pole

A2.2 Question: Please provide specs/details for PMH feeding Barn 1 and Barn 2”

Response: PMH shall be a S&C PMH 11 or equal.

A2.3 Clarification: Please clarify who is providing the utility transformer and base?

Response: The utility company will provide.

A2.4 Question: Please provide information on panel “DP-L”?

Response: 480V-3PH, 400 Amp Main Breaker 42 circuit panel with the following breakers:

a. (1) 200-amp, 3-pole

b. (1) 100-amp, 3-pole

ADDENDUM NO. 2

c. (1) 40-amp, 3-pole

A2.5 Question: Please provide information on panel “DP-A”?

Response: 480V-3PH, 800 Amp Main Breaker 42 circuit panel with the following breakers:

a. (1) 400-amp, 3-pole

b. (2) 200-amp, 3-pole

A2.6 Question: Please provide information on panel “MDP-A”?

Response: 480V-3PH, 800 Amp Main Breaker 42 circuit panel with the following breakers:

a. (1) 400-amp, 3-pole

b. (1) 125-amp, 3-pole

A2.7 Question: Please confirm the cable from the utility XFMR to the primary SWGR is one single conductor?

Response: The cable shall be 1-3C 500 KCMIL

A2.8 Question: Please confirm if the cable from the utility XFMR to the primary SWGR should be in conduit?

Response: Yes, this is correct.

A2.9 Queston: Where is the location of the pole mounted transformer that feeds the sawmill?

Response: The transformer feeding the sawmill is located on a pole near the powerhouse building.

A2.10 Question: Please provide specs/details for new tap box in the tunnel.

Response: New tap box shall be galvanized steel with screw on cover. Tap box shall be sized per wire and bending radius within the box.

A2.11 Attachments: Electrical Sheets E603 and E605

GENERATOR

GENERATOR

CIRCUIT

BREAKER

G

GENERATOR

TRANSFORMER

480V-2.4KV, 3PH

GENERATOR HVDS

400A

250AF

MN UTIL

23.86MVA

8 (X/R)

23.86MVA

8 (X/R)

MN UTIL TX

750 KVA

2.4 - 2.4KV

5.5%

1- 3/C

-5

K

CM

IL

INCOMING LINE

250A

#3/0

ATS

SECTION 1 SECTION 2/3

SAPRE AERIAL

SECTION 4

HOUSE #1 LOOP #1

SECTION 5

HOUSE #2 LOOP #2

SECTION 6

EXISTING

PRIMARY SWITCHGEAR - 2400V-3 PHASE, 1200A

OUTSIDE KITCHEN

150 KVA

0.480-0.240KV

KITCHEN (150 KVA)

2.4-0.480KV

4%

CAN

TRANSFORMER

CAN

TRANSFORMER

3X50KVA (150 KVA)

2.4-0.240KV

4%

POLE

TRANSFORMER

LN POLE 1

TD KIT-A

DISC

SQD Q2

225/150A

PANEL

KITCHEN

"B"

PANEL

TD KITCHEN

MBRK

C-H HLA600

600/600

PANEL

TD KITCHEN

"1"

SQD LA

400/400

PANEL

TD KITCHEN

"2"

SQD LA

250/225

PANEL

KITCHEN

"C. MBRK"

SQD LA

400/400

PANEL

"MCC2"

PANEL

KITCHEN

"D"

250A 250A 75A N.C.

100A 100A 100A 100A

P-DORM TX

150 KVA

2.4-0.240KV

4%

A-WING

DISC

BUSS REN (H)

80A

PANEL

"A-WING"

B-WING

DISC

BUSS REN (H)

80A

PANEL

"B-WING"

C-WING

DISC

BUSS REN (H)

80A

PANEL

"C-WING"

D-WING

DISC

BUSS REN (H)

80A

PANEL

"D-WING"

BARN 1

1-POLE

BARN 2

1-POLE

KITCHEN

DISC

PNL "C"

MBRK

100A

KITCHEN

UG

UG

UG

SAWMILL

3 OUTSIDE KITCHEN

EXIST.

EXIST.

EXIST.

EXIST. EXIST.

EXIST. EXIST.

EXIST.

EXIST.

1 1

3 UG

AERIAL SOUTH

1 1 6 1 6

NEWEXIST.

EXIST.

EXIST.

SHEET E-603

SHEET E-604

SHEET E-603

SHEET E-604

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND#2/0 (5KV)

(1) 4" CND

HANDHOLE

PMH

PANEL

NEW

"OK"

480 V

3Ø, 4W

400A MCB

2 SETS OF

(4) 4/0

(1) #4 GND

(1) 2-1/2" CND

2 SETS OF

(4) 300KCMIL

(1) #1 GND

(1) 3" CND

(4) #3/0

(1) #6 GND

(1) 2" CND

(4) 600KCMIL

(1) #3 GND

(1) 4" CND

ELECTRICAL KEY NOTES

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO

REMAIN.

PROVIDE AND INSTALL NEW PAD MOUNT TRANSFORMER (150KVA, PRIM:

2400V - 3Ø, SEC: 120/240V - 3Ø). FEED TRANSFORMER FROM POWER PLANT

THRU EXISTING CONDUIT UNDERGROUND CONDUIT. RECONNECT EXISTING

BUILDING SERVICE TO NEW TRANSFORMER.

EXISTING CONDUIT TO REMAIN. REMOVE THE EXISTING WIRE AND PROVIDE

AND INSTALL NEW WIRING.

PROVIDE AND INSTALL NEW TRANSFORMER (150KVA, PRIM: 277/480V - 3Ø,

SEC: 120/240V - 3Ø). FEED TRANSFORMER FROM PANEL "MDPK"

RECONNECT EXISTING EQUIPMENT TO TRANSFORMER.

REPLACE PRIMARY CABLE. INSTALL NEW PRIMARY CABLES IN CONDUIT.

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a t r ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/20/2023

E-603

JKB

JFS

ELECTRICAL RISER DIAGRAM -

NEW

ELECTRICAL RISER DIAGRAM - NEW

SCALE:

ADDENDUM #2 10/20/2023 1

KIT

DISC

400AF/400A

PANEL

EXIST.

"VOC

SCHOOL"

400AF/200A

PANEL

EXIST.

"CHAPEL 1"

SERV

MN

WEST LAB

400AF/200A

KIT

DISC

BUSS FRS-R

(RK15)

200A

LAUNDRY

DISC

BUSS FRS-R

(RK15)

100A

PANEL

EXIST.

"LAUNDRY"

KIT TX

112.5 KVA

0.48-0.208KV

4.7%

KIT

DISC-1

SHAWMUT TR

(RK5)

350A

AA

DISC

BUSS FRS-R

(RK5)

200A

BB

DISC

BUSS FRS-R

(RK5)

200A

PANEL

EXIST.

"RP5"

PANEL

EXIST.

"MCC1"

INDUSTRY

DISC

WEST EHB

100/100

PANEL

EXIST.

"LIBRARY"

PANEL

EXIST.

"INDUSTRY"

LIBRARY

DISC

WEST EHB

100/100

EXISTING

LIBRARY THROUGH

PP-1 TX

150 KVA

2.4-0.208KV

4%

PP-1

MAIN

WEST LAB

400/400

PANEL

EXIST.

"PP-1"

NEW

TRANSFORMER

CAGE TX

250 KVA

0.48-0.208KV

3%

PANEL

EXIST.

"B-BLOCK"

PANEL

EXIST.

"G-BLOCK"

PANEL

EXIST.

"D-BLOCK"

PANEL

EXIST.

"E-BLOCK"

PANEL "CAGE"

CAGE

800 CAGE PNL.2

ITE JD

400/400

CAGE PNL.4

ITE JD

225/150

CAGE PNL.6

ITE JD

225/125

CAGE PNL.3

ITE JD

225/125

ROT

DISC

SCD Q2L

225/200

PANEL

EXIST.

"ADMIN"

PANEL

EXIST.

"ROT"

ADMIN

DISC

SQD Q2L

225/200

1- 1/C

-3 /0

AW

G

PANEL

EXIST.

"PDP-1"

SQD FH

100/60

PDP-1

DISC

SQD LAL

400/125A

PANEL

EXIST.

"ERU"

SQD FH

BRK CNTR

MAIN

SWITCH

WARDEMS TX

75 KVA

2.4-0.48KV

1.8%

EXISTING

TRANSFORMER

WARDEN

DISC

SQD Q2

225/200

MBRK

PANEL

EXIST.

"WARDEN"

112.5 KVA

EXISTING

TRANSFORMER

BRR CNTR MN.1

GE TFK

225/70

BROOK CENTER

EXISTING

BRK CNTR MN

PANEL

EXIST.

"MECH RM"

PANEL

EXIST.

"RM 112"

PANEL

EXIST.

"E HALL"

"EMERG"

PANEL

EXIST.

"LPA"

PANEL

EXIST.

"PPA"

BRK CENTER TX

225 KVA

2.4-0.208KV

4.8%

BRR CNTR MN.2

GE TFK

225/125

BRR CNTR MN.3

GE TFK

225/70

PANEL

EXIST.

"E"

PANEL

EXIST.

"N"

E ACCU

DISC

BUSS FRS-R

(RK-5)

100A

N ACCU

DISC

BUSS FRS-R

(RK-5)

100A

BRR CNTR MN.4

GE TFK

225/70

BRR CNTR MN.XX

GE TFK

225/100

BRR CNTR MN.XX

GE TFK

225/100

BRR CNTR MN.7

GE TJK4

400/400

BRK CNTR

MAIN

SWITCH

NEW

2.4-.48KV

300 KVA

PANEL

NEW

"DP-A"

277/480V

3Ø 4W

600A MCB

NEW

.48-.24KV

15 KVA

NEW

2.4-.48KV

225KVA

PANEL

NEW

"DP-L"

277/480V

3Ø 4W

400A MCB

NEW

.48-.208KV

30KVA

NEW

.48-.24KV

75KVA

ADMIN

750 KVA

2.4-0.48KV

PANEL

NEW

"MDP-A"

277/480V

3Ø 4W

800A MCB

CAGE PNL.3

ITE JD

225/200

CAGE PNL.3

ITE JD

225/200

NEW

TRANSFORMER

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

SH

EE

T E-

NCNO

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

NCNC

EXIST. EXIST.

EXIST.

EXIST.EXIST.

EXIST. EXIST.

EXIST.EXIST.

EXIST. EXIST.

EXIST. EXIST.

EXIST.

EXIST.

EXIST.

7 77

777777

NEW

TRANSFORMER

7 7

8 BROOKS CENTER

9 ADMIN BUILDING

NCNC

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

131313131313

EXIST.

10 CENTRAL KITCHEN/ NORTH

NCNC

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

11 CENTRAL KITCHEN/ SOUTH

NCNC

NEW

SWITCH NEMA 3R

LOCATE NEXT TO

NEW XMRF

12 PROGRAMS BUILDING

414 1415

EXIST.

EXIST.

(4) 350 KCMIL

(1) #4 GND

(1) 3" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

#2/0 (5KV)

(1) 4" CND

(4) #2

(1) #8 GND

(1) 1 1/4" CND

(4) #3/0

(1) #6 GND

(1) 3" CND

(4) #2

(1) #8 GND

(1) 1 1/4" CND

3 SETS OF

(4) 350 KCMIL

(1) #2/0 GND

(1) 3" CND

(4) 500 KCMIL

(1) #3 GND

(1) 3" CND

(4) 500 KCMIL

(1) #3 GND

(1) 3" CND

(4) 500 KCMIL

(1) #3 GND

(1) 3" CND

(4) #2 KCMIL

(1) #8 GND

(1) 1 1/4" CND

(4) #10

(1) #12 GND

(1) 3/4" CND

(4) 400 KCMILL

(1) #1/0 GND

(1) 3" CND

(4) 600 KCMILL

(1) #3 GND

(1) 4" CND

2 SETS OF

(4) 400 KCMILL

(1) #1/0 GND

(1) 3" CND

(4) #1

(1) #6 GND

(1) 1 1/2" CND

(4) #8

(1) #10 GND

(1) 3/4" CND

(4) #2

(1) #8 GND

(1) 1 1/4" CND

131313

ELECTRICAL KEY NOTES

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM BROOKS CENTER TO

NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN TO

NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.

PROVIDE AND INSTALL NEW TWO POSITION SWITCHES AND REFEED

EXISTING TRANSFORMER FROM THIS SWITCH.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN

SOUTH TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN

SOUTH TO NEW SWITCH IN TUNNEL. INSTALL NEW PRIMARY CABLES IN

EXISTING CONDUIT.

PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A" 277/480V-3Ø, 4W 800A

EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO

REMAIN.

PROVIDE AND INSTALL NEW 750 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW AMDIN SWITCH (LOOP #2 FEED).

PROVIDE PREVENTIVE MAINTENANCE ON EQUIPMENT.

PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 277/480V/ SEC:

120/208V - 3Ø, 4W FEED FROM NEW 480V PANEL "MDP-A".

PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A1" 120/208V-3Ø, 4W 800A.

PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 2400V/ SEC:

120/208V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN NORTH SWITCH

(LOOP #2 FEED).

RECONNECT FEEDER FROM EQUIPMENT BEING ADD. ASSOCIATED CONDUIT

& WIRE TO REMAIN.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN

SOUTH TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

PROVIDE AND INSTALL NEW PRIMARY CABLE FROMPROGRAMS BUILDING TO

NEW SWITCH IN TUNNEL. INSTALL NEW PRIMARY CABLES IN EXISTING

CONDUIT.

PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN SOUTH SWITCH

(LOOP #2 FEED).

PROVIDE AND INSTALL NEW 225 KVA TRANSFORMER PRIM: 2400V/ SEC:

277/480V - 3Ø, 4W FEED FROM NEW PROGRAMS SWITCH (LOOP #2 FEED).

PROVIDE AND INSTALL NEW 50 KVA TRANSFORMER PRIM: 277/480V/ SEC:

120/240V - 1Ø, 3W FEED FROM NEW 225 KVA PROGRAMS TRANSFORMER.

file no.

checked by drawn by consultant issue date contract order no.

472MBPMAINTPROJ

consultant job no.

22612.00

M a t r ix

472/224422.JBB

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N xx

CD SET 10/20/2023

E-605

JKB

JFS

ELECTRICAL RISER DIAGRAM -

NEW

ELECTRICAL RISER DIAGRAM - NEW

SCALE:

ADDENDUM #2 10/20/2023 1

Addendum No 2w
E603-2261200-Layout1
E605-2261200-Layout1