Addendum 2.pdf
PDF 720 KB Posted
- Solicitation number
- RFQ - 171 - 240000000053
- Issued by
- Alger County, Michigan
About this file
This document is Addendum No. 2 for the Marquette Branch Prison - Primary Electrical Infrastructure Upgrades project, issued by the Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division in the State of Michigan. The addendum provides clarification and responses to questions regarding electrical specifications, including information on panels, transformers, cables, and conduits. It also includes an electrical riser diagram with key notes on the new electrical system components. The project is funded under File #472/22442.JBB and involves upgrades to the primary electrical infrastructure at the Marquette Branch Prison facility.
The addendum provides details on the electrical equipment and cabling to be installed, including voltage ratings, amperage, number of poles, and conductor sizes. It confirms that the utility company will provide the transformer and base, and that the contractor will need to install new primary cables in conduit. The project appears to involve multiple buildings and electrical system modifications throughout the prison facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Technical Specifications.pdf | ||
| Addendum 4.pdf | ||
| Drawings-2.pdf | ||
| DTMB-0415 Advertisement (Rev 10-22).pdf | ||
| LEIN Request 22442.pdf | ||
| Front End Specification.pdf | ||
| Addendum 3.pdf | ||
| Prevailing Wages 231024 Marquette County 22442.pdf | ||
| Addendum 1.pdf | ||
| Drawings-1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1601 E. CÉSAR E. CHÁVEZ AVENUE, LANSING, MI 48906
PHONE: (517) 487-2511
FAX: (517) 487-2544
ADDENDUM NO. 2
Date: 12/01/23 Project Name: Marquette Branch Prison - Primary Electrical Infrastructure Upgrades File # 472/22442.JBB Funding Code # 472/MBPMaintProj
This Addendum is issued for the purpose of modifying and/or clarifying the original Contract Documents and shall take precedence over them.
All work included herein shall be in accordance with the original drawings and specifications except as specifically noted herein. All incidental items required to provide the following modifications shall be included even though not specifically described.
This addendum is being sent to all bidders receiving plans and specifications. Receipt of this Addendum shall be noted on the Bid Summary in the appropriate location.
Clarification and Questions:
A2.1 Question: Please provide information on panel “OK”?
Response: 480V-3PH, 400 Amp Main Breaker 42 circuit panel with the following breakers:
a. (1) 200-amp, 3-pole
A2.2 Question: Please provide specs/details for PMH feeding Barn 1 and Barn 2”
Response: PMH shall be a S&C PMH 11 or equal.
A2.3 Clarification: Please clarify who is providing the utility transformer and base?
Response: The utility company will provide.
A2.4 Question: Please provide information on panel “DP-L”?
Response: 480V-3PH, 400 Amp Main Breaker 42 circuit panel with the following breakers:
a. (1) 200-amp, 3-pole
b. (1) 100-amp, 3-pole
ADDENDUM NO. 2
c. (1) 40-amp, 3-pole
A2.5 Question: Please provide information on panel “DP-A”?
Response: 480V-3PH, 800 Amp Main Breaker 42 circuit panel with the following breakers:
a. (1) 400-amp, 3-pole
b. (2) 200-amp, 3-pole
A2.6 Question: Please provide information on panel “MDP-A”?
Response: 480V-3PH, 800 Amp Main Breaker 42 circuit panel with the following breakers:
a. (1) 400-amp, 3-pole
b. (1) 125-amp, 3-pole
A2.7 Question: Please confirm the cable from the utility XFMR to the primary SWGR is one single conductor?
Response: The cable shall be 1-3C 500 KCMIL
A2.8 Question: Please confirm if the cable from the utility XFMR to the primary SWGR should be in conduit?
Response: Yes, this is correct.
A2.9 Queston: Where is the location of the pole mounted transformer that feeds the sawmill?
Response: The transformer feeding the sawmill is located on a pole near the powerhouse building.
A2.10 Question: Please provide specs/details for new tap box in the tunnel.
Response: New tap box shall be galvanized steel with screw on cover. Tap box shall be sized per wire and bending radius within the box.
A2.11 Attachments: Electrical Sheets E603 and E605
GENERATOR
GENERATOR
CIRCUIT
BREAKER
G
GENERATOR
TRANSFORMER
480V-2.4KV, 3PH
GENERATOR HVDS
400A
250AF
MN UTIL
23.86MVA
8 (X/R)
23.86MVA
8 (X/R)
MN UTIL TX
750 KVA
2.4 - 2.4KV
5.5%
1- 3/C
-5
K
CM
IL
INCOMING LINE
250A
#3/0
ATS
SECTION 1 SECTION 2/3
SAPRE AERIAL
SECTION 4
HOUSE #1 LOOP #1
SECTION 5
HOUSE #2 LOOP #2
SECTION 6
EXISTING
PRIMARY SWITCHGEAR - 2400V-3 PHASE, 1200A
OUTSIDE KITCHEN
150 KVA
0.480-0.240KV
KITCHEN (150 KVA)
2.4-0.480KV
4%
CAN
TRANSFORMER
CAN
TRANSFORMER
3X50KVA (150 KVA)
2.4-0.240KV
4%
POLE
TRANSFORMER
LN POLE 1
TD KIT-A
DISC
SQD Q2
225/150A
PANEL
KITCHEN
"B"
PANEL
TD KITCHEN
MBRK
C-H HLA600
600/600
PANEL
TD KITCHEN
"1"
SQD LA
400/400
PANEL
TD KITCHEN
"2"
SQD LA
250/225
PANEL
KITCHEN
"C. MBRK"
SQD LA
400/400
PANEL
"MCC2"
PANEL
KITCHEN
"D"
250A 250A 75A N.C.
100A 100A 100A 100A
P-DORM TX
150 KVA
2.4-0.240KV
4%
A-WING
DISC
BUSS REN (H)
80A
PANEL
"A-WING"
B-WING
DISC
BUSS REN (H)
80A
PANEL
"B-WING"
C-WING
DISC
BUSS REN (H)
80A
PANEL
"C-WING"
D-WING
DISC
BUSS REN (H)
80A
PANEL
"D-WING"
BARN 1
1-POLE
BARN 2
1-POLE
KITCHEN
DISC
PNL "C"
MBRK
100A
KITCHEN
UG
UG
UG
SAWMILL
3 OUTSIDE KITCHEN
EXIST.
EXIST.
EXIST.
EXIST. EXIST.
EXIST. EXIST.
EXIST.
EXIST.
1 1
3 UG
AERIAL SOUTH
1 1 6 1 6
NEWEXIST.
EXIST.
EXIST.
SHEET E-603
SHEET E-604
SHEET E-603
SHEET E-604
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND#2/0 (5KV)
(1) 4" CND
HANDHOLE
PMH
PANEL
NEW
"OK"
480 V
3Ø, 4W
400A MCB
2 SETS OF
(4) 4/0
(1) #4 GND
(1) 2-1/2" CND
2 SETS OF
(4) 300KCMIL
(1) #1 GND
(1) 3" CND
(4) #3/0
(1) #6 GND
(1) 2" CND
(4) 600KCMIL
(1) #3 GND
(1) 4" CND
ELECTRICAL KEY NOTES
EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO
REMAIN.
PROVIDE AND INSTALL NEW PAD MOUNT TRANSFORMER (150KVA, PRIM:
2400V - 3Ø, SEC: 120/240V - 3Ø). FEED TRANSFORMER FROM POWER PLANT
THRU EXISTING CONDUIT UNDERGROUND CONDUIT. RECONNECT EXISTING
BUILDING SERVICE TO NEW TRANSFORMER.
EXISTING CONDUIT TO REMAIN. REMOVE THE EXISTING WIRE AND PROVIDE
AND INSTALL NEW WIRING.
PROVIDE AND INSTALL NEW TRANSFORMER (150KVA, PRIM: 277/480V - 3Ø,
SEC: 120/240V - 3Ø). FEED TRANSFORMER FROM PANEL "MDPK"
RECONNECT EXISTING EQUIPMENT TO TRANSFORMER.
REPLACE PRIMARY CABLE. INSTALL NEW PRIMARY CABLES IN CONDUIT.
file no.
checked by drawn by consultant issue date contract order no.
472MBPMAINTPROJ
consultant job no.
22612.00
M a t r ix
472/224422.JBB
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N xx
CD SET 10/20/2023
E-603
JKB
JFS
ELECTRICAL RISER DIAGRAM -
NEW
ELECTRICAL RISER DIAGRAM - NEW
SCALE:
ADDENDUM #2 10/20/2023 1
KIT
DISC
400AF/400A
PANEL
EXIST.
"VOC
SCHOOL"
400AF/200A
PANEL
EXIST.
"CHAPEL 1"
SERV
MN
WEST LAB
400AF/200A
KIT
DISC
BUSS FRS-R
(RK15)
200A
LAUNDRY
DISC
BUSS FRS-R
(RK15)
100A
PANEL
EXIST.
"LAUNDRY"
KIT TX
112.5 KVA
0.48-0.208KV
4.7%
KIT
DISC-1
SHAWMUT TR
(RK5)
350A
AA
DISC
BUSS FRS-R
(RK5)
200A
BB
DISC
BUSS FRS-R
(RK5)
200A
PANEL
EXIST.
"RP5"
PANEL
EXIST.
"MCC1"
INDUSTRY
DISC
WEST EHB
100/100
PANEL
EXIST.
"LIBRARY"
PANEL
EXIST.
"INDUSTRY"
LIBRARY
DISC
WEST EHB
100/100
EXISTING
LIBRARY THROUGH
PP-1 TX
150 KVA
2.4-0.208KV
4%
PP-1
MAIN
WEST LAB
400/400
PANEL
EXIST.
"PP-1"
NEW
TRANSFORMER
CAGE TX
250 KVA
0.48-0.208KV
3%
PANEL
EXIST.
"B-BLOCK"
PANEL
EXIST.
"G-BLOCK"
PANEL
EXIST.
"D-BLOCK"
PANEL
EXIST.
"E-BLOCK"
PANEL "CAGE"
CAGE
800 CAGE PNL.2
ITE JD
400/400
CAGE PNL.4
ITE JD
225/150
CAGE PNL.6
ITE JD
225/125
CAGE PNL.3
ITE JD
225/125
ROT
DISC
SCD Q2L
225/200
PANEL
EXIST.
"ADMIN"
PANEL
EXIST.
"ROT"
ADMIN
DISC
SQD Q2L
225/200
1- 1/C
-3 /0
AW
G
PANEL
EXIST.
"PDP-1"
SQD FH
100/60
PDP-1
DISC
SQD LAL
400/125A
PANEL
EXIST.
"ERU"
SQD FH
BRK CNTR
MAIN
SWITCH
WARDEMS TX
75 KVA
2.4-0.48KV
1.8%
EXISTING
TRANSFORMER
WARDEN
DISC
SQD Q2
225/200
MBRK
PANEL
EXIST.
"WARDEN"
112.5 KVA
EXISTING
TRANSFORMER
BRR CNTR MN.1
GE TFK
225/70
BROOK CENTER
EXISTING
BRK CNTR MN
PANEL
EXIST.
"MECH RM"
PANEL
EXIST.
"RM 112"
PANEL
EXIST.
"E HALL"
"EMERG"
PANEL
EXIST.
"LPA"
PANEL
EXIST.
"PPA"
BRK CENTER TX
225 KVA
2.4-0.208KV
4.8%
BRR CNTR MN.2
GE TFK
225/125
BRR CNTR MN.3
GE TFK
225/70
PANEL
EXIST.
"E"
PANEL
EXIST.
"N"
E ACCU
DISC
BUSS FRS-R
(RK-5)
100A
N ACCU
DISC
BUSS FRS-R
(RK-5)
100A
BRR CNTR MN.4
GE TFK
225/70
BRR CNTR MN.XX
GE TFK
225/100
BRR CNTR MN.XX
GE TFK
225/100
BRR CNTR MN.7
GE TJK4
400/400
BRK CNTR
MAIN
SWITCH
NEW
2.4-.48KV
300 KVA
PANEL
NEW
"DP-A"
277/480V
3Ø 4W
600A MCB
NEW
.48-.24KV
15 KVA
NEW
2.4-.48KV
225KVA
PANEL
NEW
"DP-L"
277/480V
3Ø 4W
400A MCB
NEW
.48-.208KV
30KVA
NEW
.48-.24KV
75KVA
ADMIN
750 KVA
2.4-0.48KV
PANEL
NEW
"MDP-A"
277/480V
3Ø 4W
800A MCB
CAGE PNL.3
ITE JD
225/200
CAGE PNL.3
ITE JD
225/200
NEW
TRANSFORMER
SH
EE
T E-
SH
EE
T E-
SH
EE
T E-
SH
EE
T E-
NCNO
NEW
SWITCH NEMA 3R
LOCATE NEXT TO
NEW XMRF
NCNC
EXIST. EXIST.
EXIST.
EXIST.EXIST.
EXIST. EXIST.
EXIST.EXIST.
EXIST. EXIST.
EXIST. EXIST.
EXIST.
EXIST.
EXIST.
7 77
777777
NEW
TRANSFORMER
7 7
8 BROOKS CENTER
9 ADMIN BUILDING
NCNC
NEW
SWITCH NEMA 3R
LOCATE NEXT TO
NEW XMRF
131313131313
EXIST.
10 CENTRAL KITCHEN/ NORTH
NCNC
NEW
SWITCH NEMA 3R
LOCATE NEXT TO
NEW XMRF
11 CENTRAL KITCHEN/ SOUTH
NCNC
NEW
SWITCH NEMA 3R
LOCATE NEXT TO
NEW XMRF
12 PROGRAMS BUILDING
414 1415
EXIST.
EXIST.
(4) 350 KCMIL
(1) #4 GND
(1) 3" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
#2/0 (5KV)
(1) 4" CND
(4) #2
(1) #8 GND
(1) 1 1/4" CND
(4) #3/0
(1) #6 GND
(1) 3" CND
(4) #2
(1) #8 GND
(1) 1 1/4" CND
3 SETS OF
(4) 350 KCMIL
(1) #2/0 GND
(1) 3" CND
(4) 500 KCMIL
(1) #3 GND
(1) 3" CND
(4) 500 KCMIL
(1) #3 GND
(1) 3" CND
(4) 500 KCMIL
(1) #3 GND
(1) 3" CND
(4) #2 KCMIL
(1) #8 GND
(1) 1 1/4" CND
(4) #10
(1) #12 GND
(1) 3/4" CND
(4) 400 KCMILL
(1) #1/0 GND
(1) 3" CND
(4) 600 KCMILL
(1) #3 GND
(1) 4" CND
2 SETS OF
(4) 400 KCMILL
(1) #1/0 GND
(1) 3" CND
(4) #1
(1) #6 GND
(1) 1 1/2" CND
(4) #8
(1) #10 GND
(1) 3/4" CND
(4) #2
(1) #8 GND
(1) 1 1/4" CND
131313
ELECTRICAL KEY NOTES
PROVIDE AND INSTALL NEW PRIMARY CABLE FROM BROOKS CENTER TO
NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.
PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN TO
NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING CONDUIT.
PROVIDE AND INSTALL NEW TWO POSITION SWITCHES AND REFEED
EXISTING TRANSFORMER FROM THIS SWITCH.
PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN
SOUTH TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING
CONDUIT.
PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN
SOUTH TO NEW SWITCH IN TUNNEL. INSTALL NEW PRIMARY CABLES IN
EXISTING CONDUIT.
PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A" 277/480V-3Ø, 4W 800A
EXISTING FEEDER TO REMAIN. ASSOCIATED CONDUIT AND WIRE TO
REMAIN.
PROVIDE AND INSTALL NEW 750 KVA TRANSFORMER PRIM: 2400V/ SEC:
277/480V - 3Ø, 4W FEED FROM NEW AMDIN SWITCH (LOOP #2 FEED).
PROVIDE PREVENTIVE MAINTENANCE ON EQUIPMENT.
PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 277/480V/ SEC:
120/208V - 3Ø, 4W FEED FROM NEW 480V PANEL "MDP-A".
PROVIDE AND INSTALL NEW NEMA-3R PANEL "MDP-A1" 120/208V-3Ø, 4W 800A.
PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 2400V/ SEC:
120/208V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN NORTH SWITCH
(LOOP #2 FEED).
RECONNECT FEEDER FROM EQUIPMENT BEING ADD. ASSOCIATED CONDUIT
& WIRE TO REMAIN.
PROVIDE AND INSTALL NEW PRIMARY CABLE FROM CENTRAL KITCHEN
SOUTH TO NEW SWITCH. INSTALL NEW PRIMARY CABLES IN EXISTING
CONDUIT.
PROVIDE AND INSTALL NEW PRIMARY CABLE FROMPROGRAMS BUILDING TO
NEW SWITCH IN TUNNEL. INSTALL NEW PRIMARY CABLES IN EXISTING
CONDUIT.
PROVIDE AND INSTALL NEW 300 KVA TRANSFORMER PRIM: 2400V/ SEC:
277/480V - 3Ø, 4W FEED FROM NEW CENTRAL KITCHEN SOUTH SWITCH
(LOOP #2 FEED).
PROVIDE AND INSTALL NEW 225 KVA TRANSFORMER PRIM: 2400V/ SEC:
277/480V - 3Ø, 4W FEED FROM NEW PROGRAMS SWITCH (LOOP #2 FEED).
PROVIDE AND INSTALL NEW 50 KVA TRANSFORMER PRIM: 277/480V/ SEC:
120/240V - 1Ø, 3W FEED FROM NEW 225 KVA PROGRAMS TRANSFORMER.
file no.
checked by drawn by consultant issue date contract order no.
472MBPMAINTPROJ
consultant job no.
22612.00
M a t r ix
472/224422.JBB
acct. template sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N xx
CD SET 10/20/2023
E-605
JKB
JFS
ELECTRICAL RISER DIAGRAM -
NEW
ELECTRICAL RISER DIAGRAM - NEW
SCALE:
ADDENDUM #2 10/20/2023 1
| Addendum No 2w |
| E603-2261200-Layout1 |
| E605-2261200-Layout1 |
File details come from the government source that posted it. Updated .