drawing - PLUMBING_QAC Historic Courthouse RFQ_2026.07.01.pdf
PDF 3 MB Posted
- Attached to
- Historic Courthouse Renovation
- Solicitation number
- BPM057809
- Issued by
- Queen Anne's County, Maryland
About this file
This is a plumbing drawing for a Historic Courthouse renovation project in Queen Anne's County, Maryland. The drawing depicts the plumbing system design and layout for the complete renovation of the 17,800-square-foot Historic Courthouse located at 100 Courthouse Square in Centreville. The project scope includes the installation of all new plumbing fixtures and piping throughout the three-level building, including the courtroom on the second floor, Register of Wills office and Orphans Courtroom on the ground floor, and flexible meeting and office spaces, break room, restrooms, and utility spaces in the basement. The new plumbing system also incorporates a sprinkler system and new water service to support the renovated facility's operational requirements. The drawing provides the technical specifications and spatial arrangement necessary for the General Contractor and subcontractors to execute the plumbing installation as part of the broader Historic Courthouse renovation initiative.
The plumbing drawing serves as a technical document to support the qualification and bidding process for construction services. This drawing is one component of a comprehensive set of construction documents that outline the requirements for the complete renovation project, which also includes new HVAC systems, electrical service, fire alarm systems, and various other building systems and architectural improvements. The document is essential for General Contractor candidates to understand the scope and complexity of the plumbing work involved in the Historic Courthouse renovation project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THE LOCATION OF ALL EXISTING UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. REPAIR ALL DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL EXISTING UTILITIES.
RUN ALL SOIL, WASTE AND DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL BE GRADED TO DRIP
BACK TO THE SOIL OR WASTE PIPE BY GRAVITY.
ELEVATIONS NOTED ARE TO CENTERLINES OF PIPES FOR ALL PRESSURE LINES AND TO INVERT FOR ALL GRAVITY FLOW LINES.
ADJUST SEWER INVERTS TO KEEP TOPS OF PIPE IN LINE WHERE PIPE SIZE CHANGES.
MAINTAIN MINIMUM OF 3'-0" COVER OVER UNDERGROUND WATER MAIN AND MINIMUM OF 2'-6" COVER OVER UNDERGROUND SEWERS AND DRAINS.
PROVIDE SHUTOFF VALVES IN DOMESTIC WATER SYSTEMS IN BRANCH LINES SERVING TWO OR MORE FIXTURES.
UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF SLAB OR STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.
INSTALL PIPING SO THAT ALL VALVES ARE ACCESSIBLE.
COORDINATE ALL PLUMBING WORK WITH MECHANICAL, ELECTRICAL WORK, ETC., SHOWN ON OTHER DRAWINGS.
MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL AND
ELECTRICAL ROOMS.
UNLESS OTHERWISE NOTED, WHERE HOT AND COLD WATER PIPING DROPS INTO PIPE CHASE, THE SIZE SHOWN FOR THE PIPE DROPS SHALL BE USED TO THE
LAST FIXTURE.
CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS.
WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES REQUIRE CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CHECK FOR THE PRESENCE OF EXISTING MECHANICAL AND / OR ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION AND EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO HIS PERSONNEL DUE TO CONTACT WITH SAME. WHERE PRACTICAL, SUCH EXISTING SERVICES SHALL BE TEMPORARILY DISCONNECTED DURING THE CUTTING OPERATION. SUCH
OUTAGES IN SERVICE SHALL BE SCHEDULED IN ADVANCE WITH THE OWNER.
FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT. VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. ADDITIONAL VALVES, PRESSURE GAUGES, ETC. SHALL BE PROVIDED AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS AND DETAILS FOR PIPE SIZES NOT INDICATED ON FLOW SCHEDULES AND RISER DIAGRAMS.
CONTRACTOR SHALL BE RESPONSIBLE FOR RESEARCHING ALL SYSTEMS THAT A PARTICULAR OUTAGE WILL AFFECT AS WELL AS LOCATING ALL SHUTOFF POINTS.
THIS INFORMATION SHALL BE INCLUDED IN THE OUTAGE PLAN TO BE SUBMITTED TO OWNER FOR APPROVAL.
USE OF COMBINATION WYE FITTINGS OR CROSS TEES IN THE PLUMBING SANITARY SYSTEM ARE NOT ALLOWED.
INFORMATION SHOWN ON THE PLUMBING DRAWINGS PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMOLITION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING AND AWAIT WRITTEN DIRECTION
BEFORE PROCEEDING WITH THE WORK.
REMOVE ALL EXISTING PIPING, FIXTURES, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE COR, OR ARE INDICATED TO REMAIN THE PROPERTY OF OWNER SHALL BE DELIVERED BY THE CONTRACTOR WHERE DIRECTED BY THE OWNER. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES.
DISCONNECT EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR OTHERWISE) AND REMOVE PIPING BACK TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR NOTED ON PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. CAP, PLUG, OR SEAL EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE. NO EXISTING PIPING SHALL BE LEFT UNSEALED VALVE ALL TERMINATED PRESSURE PIPE.
EXISTING PLUMBING PIPING, FIXTURES, EQUIPMENT, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS. ALL WORK SHALL BE COMPLETED TO THE
SATISFACTION OF THE COR AND AT NO ADDITIONAL CONTRACT COST.
REMOVE ALL ACCESSORIES, CONTROLS, ENCLOSURES, SUPPORTS, HANGERS, PADS, ETC. ASSOCIATED WITH ALL EQUIPMENT SHOWN TO BE REMOVED. REPAIR AND PAINT DAMAGED SURFACES AND ALL SURFACES BEHIND ALL EQUIPMENT SHOWN TO BE DEMOLISHED TO MATCH EXISTING ADJACENT SURFACES.
PRIOR TO SUBMITTING SHOP DRAWINGS TO ENGINEER FOR EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS, COORDINATE ELECTRICAL REQUIREMENTS BETWEEN CONTRACTORS OF ALL TRADES ASSOCIATED WITH THE INSTALLATION. THE GENERAL CONTRACTOR'S STAMP ON THE SUBMITTAL MUST STATE THAT COORDINATION BETWEEN ALL TRADES HAS BEEN VERIFIED AND THAT THE SUBMITTAL HAS BEEN APPROVED FOR ENGINEER'S REVIEW. IF CONTRACTOR SUBMITS EQUIPMENT WITH POWER REQUIREMENTS THAT ARE DIFFERENT FROM POWER CONNECTION INDICATED ON THE CONTRACT DOCUMENTS, CONTRACTOR MUST PROVIDE A REASON FOR THE CHANGE AND WRITTEN CONFIRMATION THAT THE CHANGE HAS BEEN FULLY COORDINATED WITH ALL ASSOCIATED TRADES. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO ELECTRICAL CONNECTION, COORDINATE AND MAKE REQUIRED CHANGES TO PROVIDE A COMPLETE INSTALLATION IN ACCORDANCE WITH APPLICABLE CODES. CHANGE ORDERS AND EXTRAS WILL NOT BE AWARDED DUE TO CONTRACTOR'S FAILURE TO COORDINATE WITH ALL ASSOCIATED TRADES. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO COORDINATE EQUIPMENT SUBMITTALS AMONG THE SUBCONTRACTORS, NOT THE ENGINEER'S.
(APPLICABLE TO ALL PLUMBING DRAWINGS)
GENERAL PLUMBING NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
PLUMBING ABBREVIATIONS
(APPLICABLE TO ALL PLUMBING DRAWINGS)
ACU AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
BAS BUILDING AUTOMATION SYSTEM
BFP BACKFLOW PREVENTER
CO CLEANOUT
COND CONDENSATE
CW COLD WATER
CX CONNECT TO EXISTING
D DEEP / DEPTH / DIAMETER / DRAIN
DEG DEGREES
DIA DIAMETER
DN DOWN
DWH DOMESTIC WATER HEATER
EFT ENTERING FLUID TEMPERATURE
EL ELEVATION
ELEV ELEVATION / ELEVATOR
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
FD FLOOR DRAIN
FPD FLUID PRESSURE DROP
FT FEET / FOOT
GAL GALLON
GPM GALLONS PER MINUTE
H HEIGHT / HIGH
HP HORSEPOWER
HW HOT WATER
HWR HOT WATER RETURN
HZ HERTZ
IN INCH / INCHES
INV INVERT
KW KILOWATT
L LENGTH
LAV LAVATORY
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MIN MINIMUM
N NORTH
NTS NOT TO SCALE
P PLUMBING / PLUMBING FIXTURE TYPE
PD PUMP DISCHARGE / PLUMBING DEMOLITION
PH PHASE
R RADIUS
RD ROOF DRAIN
RECIRC RECIRCULATION
RX REMOVE EXISTING
S SANITARY
SH SHOWER
SS SERVICE SINK
SW STORM WATER
T TEMPERATURE SENSOR
TEMP TEMPERATURE
TYP TYPICAL
UR URINAL
V VENT / VOLTS
VTR VENT THROUGH ROOF
W WIDTH
WC WATER CLOSET
WH WALL HYDRANT
DWC DRINKING WATER COOLER
FCO FLOOR CLEANOUT
MV MIXING VALVE
BLDG BUILDING
BWV BACKWATER VALVE
CP CONDENSATE PUMP
ERV ENERGY RECOVERY VENTILATOR
FCU FAN COIL UNIT
HB HOSE BIBB
GPH GALLONS PER HOUR
M METER
NO NUMBER
PDI PLUMBING DRAINAGE INSTITUTE
PSI POUNDS PER SQUARE INCH
RPM ROTATIONS PER MINUTE
SAN SANITARY
STM STEAM
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PL
UM
BIN
G
C O
VE
R
SH
EE
T
(APPLICABLE TO ALL PLUMBING DRAWINGS)
PLUMBING LEGEND
DOMESTIC WATER SERVICE REDUCED PRESSURE ZONE BACKFLOW PREVENTER
DESCRIPTIONSYMBOL
BALANCING VALVE
SHUTOFF VALVE
RELIEF VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
UNION
THERMOMETER
STRAINER
SECONDARY STORM WATERSSW
STORM WATERSW
PLAN/ SECTION DESIGNATION
TOP - PLAN/ SECTION REFERENCE,
BOTTOM - REFERENCED DRAWING
A M-1
CONNECT TO EXISTING
CONDENSATE DRAIND
WATER METERM
WALL HYDRANT
HOSE BIBB
DRAIN (ALL TYPES)D-(-)
BACK WATER VALVEBWV
PUMP DISCHARGEPD
VENT
SOIL OR WASTE
HOT WATER RETURN
HOT WATER
COLD WATER
HWR
HW
CW
MAV
P001
END POINT OF REMOVAL OF EXISTING
140 DEGREE F HOT WATER140 HW
PRESSURE GAGE
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
D
W V
W V
W V
W V
EX. 6" W
M
W V
WV
C/OC/O
D
W V
W V
WV
W V
C/O C/O
S
EEREER
C/O C/O
W
58.5
59.5
S
S
S
S
C/OC/O
C/O
C/O
S
IRR M
WM
WM
WM
WM
WM
WM
WMWMWM
EX 6" INCOMING
COMBINED SERVICE
RX WATER METER
RX 6" INCOMING
COMBINED SERVICE
EX PD OUT
OF BLDG
RX 4" S OUT
OF BLDG
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PD002
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
0 10 40 80 FT20
1" = 20' - 0"
4N
PD002
PLUMBING SITE PLAN - DEMOLITION
1" = 20'-0"
SEE CIVIL DRAWINGS FOR CONTINUATION
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text T
PD300
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
0 4 16 24 FT8
1/8" = 1' - 0"
XX
PL
UM
BIN
G
D
EM
O
LIT
IO
N
PL
AN
PD100
FOUNDATION - PLUMBING - DEMOLITION PLAN
1/8" = 1'-0" N
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
REMOVE ALL EXISTING DOMESTIC WATER PIPING , SANITARY PIPING, VENT PIPING,
CONDENSATE PIPING, PLUMBING FIXTURES, AND PLUMBING EQUIMENT UNLESS
OTHERWISE NOTED.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
PD100
4.
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
30 x x 68
COURTROOM
OFFICE 10
OFFICE 9
OFFICE 8
OFFICE 11
OFFICE 13
OFFICE 12
LOBBY
VAULTELEV.
PD300
COURTROOM
JURY CONFERENCE
OFFICE
JUDGE'S CHAMBER
HOLDING CELL
ELEV.
PD300
PD300
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
BASEMENT
MECHANICAL
MECHANICAL
KITCHEN
CELL 1
CELL 2
OFFICE
LAV.
SECURITY/SURVEILLANCE
OFFICE
OFFICE
OFFICE
OFFICE
OLD LAW LIBRARY
SAFE
IT
BACK-UP 911 CENTER
OFFICE
OFFICE OFFICE
OFFICE
WOMEN
MEN
ELEV.
OFFICE
PD301
EX FCU
EX FCU
EX FCU
EX FCU
EX FCU
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PD101
GROUND LEVEL - PLUMBING - DEMOLITION PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"N PL
UM
BIN
G D
EM
O
LIT
IO
N
PL
AN
PD101
UPPER LEVEL - PLUMBING - DEMOLITION PLAN
1/8" = 1'-0" N
RX CW, RX HW, RX SAN IN THIS SPACE UP TO PLUMBING FIXTURES ABOVE.
RX CONDENSATE DRAIN PIPING IN THIS SPACE FROM EX FCU'S.
CONTRACTOR TO FIELD VERIFY ROUTING OF EXISTING PIPING.
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
REMOVE ALL EXISTING DOMESTIC WATER PIPING , SANITARY PIPING, VENT PIPING,
CONDENSATE PIPING, PLUMBING FIXTURES, AND PLUMBING EQUIMENT UNLESS
OTHERWISE NOTED.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
PD1011
PD101
LOWER LEVEL - PLUMBING - DEMOLITION PLAN
1/8" = 1'-0" N
4.
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PD102
ATTIC - PLUMBING - DEMOLITION PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"
N PL
UM
BIN
G
D
EM
O
LIT
IO
N
PL
AN
PD102
ROOF - PLUMBING - DEMOLITION PLAN
1/8" = 1'-0" N
RX VENT PIPING IN THIS SPACE UP TO VTR'S. RX VTR'S ABOVE. PATCH
AND SEAL ROOF OPENING. SEE ARCHITECTURAL DRAWINGS.
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
REMOVE ALL EXISTING DOMESTIC WATER PIPING , SANITARY PIPING, VENT PIPING,
CONDENSATE PIPING, PLUMBING FIXTURES, AND PLUMBING EQUIMENT UNLESS
OTHERWISE NOTED.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
PD102
4.
NOT FOR BID
DIN
G
OR C
EX SEWAGE
EJECTOR BASIN
RX 3" S UP TO FD
RX 2" V UP
RX 3" S UP TO SINK
RX 2" S UP
TO UR
RX 4"RX 4"2
1 1
1 1
RX 4"
RX 4"
RX 2" V UP
RX 3" S UP TO FD
RX 2" V UP
RX 3" S UP TO FD
RX 3" S UP TO FD
RX 3" S UP TO FD
4 4
OFFICE 12
RX
RX
RX 4" S DN,
RX 2" V UP
RX 1-1/2" S DN,
RX 1-1/2" V UP
RX 1" CW DN
HOLDING CELL
ELEV.
RX
RX
RX
RX
RX
RX
RX 4" S DN,
RX 2" V UP
RX 1" CW DN
RX 1-1/2" S DN,
RX 1-1/2" V UP
RX 4" S DN,
RX 2" V UP
RX 1" CW DN
RX 1-1/2" S DN,
RX 1-1/2" V UP
RX 1-1/2" S DN,
RX 1-1/2" V UP
RX 4" S DN,
RX 2" V UP
RX 1" CW DN
JUDGE'S CHAMBER
OFFICE
RX
RX 4" S DN,
RX 2" V UPRX 1-1/2" S DN,
RX 1-1/2" V UP
RX 1-1/2" S DN,
RX 1-1/2" V UP
RX 4" S DN,
RX 2" V UP
RX 1" CW DN
RX 1" CW DN
RX
RXRX
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PL
UM
BIN
G
P
AR
T P
LA
NS
DE
M
O
LIT
IO
N
PD300
FOUNDATION - PLUMBING - DEMOLITION PART PLAN
1/8" = 1'-0" N
RX 1-1/2" S UP TO LAV
RX 4" S UP TO WC
RX 1/2" CW DN, RX 1/2" HW DN
CAP EXISTING BASIN PIPE PENETRATIONS THAT WILL NO LONGER BE
USED AND MAKE WATER TIGHT.
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
0 2 8 12 FT4
1/4" = 1' - 0"
PD300
CONTRACTOR SHALL FIELD VERIFY SUB SLAB PIPE ROUTING.
REMOVE ALL EXISTING DOMESTIC WATER PIPING , SANITARY PIPING, VENT
PIPING, CONDENSATE PIPING, PLUMBING FIXTURES, AND PLUMBING
EQUIMENT UNLESS OTHERWISE NOTED.
4.
PD300
GROUND LEVEL - PLUMBING - DEMOLITION PART PLAN
1/8" = 1'-0" N
PD300
UPPER LEVEL - PLUMBING - DEMOLITION PART PLAN
1/8" = 1'-0" N
PD300
UPPER LEVEL - PLUMBING - DEMOLITION PART PLAN
1/8" = 1'-0" N
NOTE: LOWER LEVEL PLAN SHOWN FOR REFERENCE ONLY
5.
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
RX FD
RX FD
RX FD
RX FD
MEN MECHANICAL
WOMEN
ELEV.
CRAWL SPACE
KITCHEN
LAV.
OFFICE
CELL 2
MECHANICAL
CELL 1
CRAWL SPACE
BASEMENT
CRAWL SPACE
RX FD
EX SEWAGE
EJECTOR PIT
RX CW
RX
RX STM TO HW
CONVERTER
RX DWH
RX AHU-2
RX AHU-1
EX PD
RX 4" S
RX PD
RX RX RX
RX
RX 3" S DN
RX 2" V DN
RX 2" V DN
RX 2" S DN
RX CW,
RX HW
RX CW
RX RX
RXRX
RX CW,
RX HW
1 1
2 2
RX 2" V DN RX CW,
RX HW
RX RX
RX
RX CW,
RX HW
RX CW,
RX HW RX 3" V
RX BFP
RX 3" V
RX METER
RX CW MAKE-UP
TO CONDENSER
WATER SYSTEM
6 7
6 7
RX ALL SANITARY PIPING
WITHIN THE CRAWLSPACE
RX V DN
RX V DN
RX V DN
RX V DN
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PL
UM
BIN
G
P
AR
T P
LA
NS
DE
M
O
LIT
IO
N
PD301
LOWER LEVEL - PLUMBING - DEMOLITION PART PLAN
1/8" = 1'-0" N
RX 1-1/2" S DN
RX 4" S DN
SEE DRAWING PD002 FOR CONTINUATION
RX CW, RX HW, RX SAN IN THIS SPACE UP TO PLUMBING FIXTURES
RX SEWAGE EJECTOR PUMPS INCLUDING ALL ASSOCIATED WIRING,
CONTROLS, ETC
SEE MECHANICAL DRAWINGS FOR MORE INFORMATION
RX CONDENSATE DRAIN
CONTRACTOR TO FIELD VERIFY EXACT ROUTING/LOCATION.
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
REMOVE ALL EXISTING DOMESTIC WATER PIPING , SANITARY PIPING, VENT PIPING,
CONDENSATE PIPING, PLUMBING FIXTURES, AND PLUMBING EQUIMENT UNLESS
OTHERWISE NOTED.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
0 2 8 12 FT4
1/4" = 1' - 0"
PD301
4.
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
D
W V
W V
W V
W V
EX. 6" W
M
W V
WV
D
W V
W V
WV
W V
EEREER
W
58.5
59.5
S
S
S
S
C/OC/O
C/O
C/O
S
IRR M
WM
WM
WM
WM
WM
WMWMWM
6" INCOMING
COMBINED
SERVICE
EX PD OUT
OF BLDG
4" S OUT
OF BLDG
2" SW 1
2" SW1
P002
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
P002
PLUMBING SITE PLAN - NEW WORK
1" = 20'-0" N PL
UM
BIN
G
SI
TE
P
LA
N
- N
EW
W O
RK
SEE CIVIL DRAWINGS FOR CONTINUATION
INV EL 58.7 +/-
INV EL 58.2 +/-
INV EL 56.6 +/-
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
0 10 40 80 FT20
1" = 20' - 0"
P002
P002
EQUIPMENT YARD - PLUMBING - NEW WORK PART PLAN
1/4" = 1'-0" N
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
T
PUMP-1
2" PD UP
P300
3" S UP
TO SINK
2" V UP
3" S
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
0 4 16 24 FT8
1/8" = 1' - 0" PL
UM
BIN
G N
EW
W
O
RK
P
LA
N
P100
FOUNDATION - PLUMBING - NEW WORK PLAN
1/8" = 1'-0" N
COORDINATE EXACT LOCATION OF SUMP PUMP WITH ELEVATOR
CONTRACTOR
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
P100
4. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF EXISTING FOOTINGS AND
COORDINATE SANITARY PIPE ROUTING WITH EXISTING FOOTINGS
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text
K-PR5452-T1D
AutoCAD SHX Text
URINAL
AutoCAD SHX Text
K-PR5452-T1D
URINAL
P300
P- 7
P- 4B
BREAK AREA
STAIRS
ELEV. LOBBY
LOBBY
ORPHAN'S COURTROOM
RECEPTION
RECORDS
CORRIDOR
R.O.W. OFFICE
CHIEF DEPUTY
DEPUTY
ELEV
UNISEX
UNISEX
OFFICE OF THE
CLO.
109A
REGISTER OF WILLS
1/2" CW DN
2" PD DN
1-1/2" V UP
P300
3" V UP/DN UPPER LOBBY
COURTROOM
CONFERENCE
200A
ELEV. LOBBY
STAIRS
JUDGE'S CHAMBER
REST LOBBY
UNISEX
UNISEX
ELEV
TOILET
205A
CLOSET
205B
1-1/2" V UP/DN
P301
MECHANICAL
MEN'S
WOMEN'S
J.C.
ELEV.
BSMT. / MECH.
ROOM
CORRIDOR
SECONDARY PSAP
I.T.
20A
MEETING ROOM
OPEN OFFICE AREA
ELECTRICAL
SPRINKLER
VAULT
22A
OPEN OFFICE AREA
OFFICE
OFFICE
BREAK
I.T.
UT
ILI
TY
TU
NN
EL
A
MECHANICAL/STORAGE
MACHINE
STAIRS
CRAWL SPACE
CLO.
LOWER LOBBY
CRAWL
CRAWL SPACE
SPACE CRAWL SPACE
MECH. CL.
30A
EX FCU
EX FCU
EX FCU
EX FCU
EX FCU
ACU-1
AHU-1.10
FCU-1.8
FCU-1.5A
FCU-1.5B
FCU-1.5C
FCU-1.6
FCU-1.7A
FCU-1.7B
FCU-1.9A FCU-1.9B
1-1/2" D 1-1/2" D
1-1/2" D
CO
1-1/2" D
3/4
1" PD
1-1/2" PD
1" PD
1-1/2" PD
3/4" D
1-1/2" PD
1-1/2" D
1-1/2" PD
1" PD
CO
CO
CO
CO
CO
CO
CO
CO
COCO
CO
CO
CO
4 4
PD
PD
PD
PD
PD
PD PD
3/4" 3/4"
3/4"
3/4"
3/4"
1-1/2"
3/4"
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
P101
GROUND LEVEL - PLUMBING - NEW WORK PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"N PL
UM
BIN
G N
EW
W
O
RK
P
LA
N
P101
UPPER LEVEL - PLUMBING - NEW WORK PLAN
1/8" = 1'-0" N
ACCESS HATCH TO ATTIC
PROVIDE CONDENSATE PUMP CP-4
TERMINATE 2" PD THROUGH WALL 1FT ABOVE FINISHED GRADE WITH 90
DEG ELBOW DOWN
INSTALL PIPE ABOVE CEILING SLOPED AS REQUIRED
1/2" HWR DN. CONNECT HWR WITHIN 2 FT OF FIXTURE.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
MAV
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
P1011 P101
LOWER LEVEL - PLUMBING - NEW WORK PLAN
1/8" = 1'-0" N
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 1 "38"
AutoCAD SHX Text + 6"6"
AutoCAD SHX Text
K-PR5452-T1D
AutoCAD SHX Text
URINAL
AutoCAD SHX Text
K-PR5452-T1D
3" V UP/DN3" V UP/DN
ERV-2
AHU-3.2
AHU-3.5
AHU-3.4
2 2
1-1/2" D DN
ATTIC
1-1/2" D DN
D D
D
AHU-3.3
PD
PD D
AHU-3.1
FCU-3.6
FCU-3.7
FCU-3.8
FCU-3.9
3/4"
1" PD
COCO
CO
CO
CO
CO
CO
CO
CO
CO
PD
1"
1"
3/4"
1-1/2" V DN
3/4"
1-1/2"
3/4"
1-1/2"
3/4"
P400
P400
P400
3" VTR3" VTR 2 2
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
P102
ATTIC - PLUMBING - NEW WORK PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"N PL
UM
BIN
G N
EW
W
O
RK
P
LA
N
P102
ROOF - PLUMBING - NEW WORK PLAN
1/8" = 1'-0" N
ACCESS HATCH. KEEP CLEAR
LOCATION TO BE APPROVED BY THE ARCHITECT
PROVIDE CONDENSATE PUMP CP-4
INSTALL PIPING AS HIGH AS POSSIBLE
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
MAV
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
P102
NOT FOR BID
DIN
G
OR C
3" FD-1
3" FD-1
3" FD-1
UPPER LOBBY
COURTROOM
JUDGE'S CHAMBER
REST LOBBY
UNISEX
UNISEX
TOILET
205A
3" V UP/DN
P-1B
P-1B P-3A
P-3A
P-1B
P-6
P-3A
4" FCO
2"1-1/2" D UP/DN
1" D UP/DN
2" V UP
2" V UP
3" FD-1
3" FD-1
ELEV. LOBBY
LOBBY
ORPHAN'S COURTROOM
RECEPTION
CORRIDOR
ELEV
UNISEX
UNISEX
OFFICE OF THE
CLO.
109A
REGISTER OF WILLS
P-1B P-3A
P-1B P-3A
3" V UP
4" S DN
3" V DN
3" V UP/DN
7 1
1-1/2" S UP TO DWC
4" S
1-1/2" D UP/DN
1-1/4" D UP/DN
CO
2" CW DN,
3/4" HW DN,
1/2" HWR DN
CW
HW
HWR
(0.5 GPM)
(0.5 GPM)
1" CW UP
1/2" CW UP
1/2" HW UP
4"
4"
4" S UP
TO FCO
2-1/2"
2-1/2" 10
EX SEWAGE
EJECTOR BASIN
2" V UP
2" S UP TO UR
2" V UP
2" S UP TO SINK
2" V UP
1 11
4 44
2" S UP TO UR
4" S UP TO FCO
2" V UP2" V UP
4" S UP TO FCO
2" S UP TO FCO
2" S UP TO FCO
2" V UP 2" V UP 2" V UP 2" V UP
4" S UP TO FCO
3" S
4" S
4" S
4"3"
4"
2"
2-1/2"
4"
2"
4"
4"
2"
2" S UP TO FCO
2" S UP TO FCO
SAN
SA
N
SA
N
SAN
SAN
BWV
4"
4"
4" S UP TO FD
4" S UP TO FD
4"
4" S UP
TO FCO
3" S UP
TO FD
2" V UP
3"
2" V UP
2" V UP
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PL
UM
BIN
G
P
AR
T P
LA
NS
NE
W
W O
RK
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
MAV
P300
FOUNDATION - PLUMBING - NEW WORK PART PLAN
1/4" = 1'-0" N
P300
GROUND LEVEL - PLUMBING - NEW WORK PART PLAN
1/4" = 1'-0" N
P300
UPPER LEVEL - PLUMBING - NEW WORK PART PLAN
1/4" = 1'-0" N
4" S UP TO WC
2-1/2" S/WET-VENT UP TO LAV
3" S UP TO FD
2" S UP TO LAV
PROVIDE TRAP PRIMER VALVE TO PRIME FLOOR DRAINS IN THIS SPACE
ACCESS HATCH TO ATTIC
2" V DN
1-1/2" CW, 3/4" HW TO (2) LAV'S AND (2) WC'S
1/2" HWR UP. CONNECT HWR WITHIN 2 FT OF FIXTURE.
1/2" HWR DN. CONNECT HWR WITHIN 2 FT OF FIXTURE.
0 2 8 12 FT4
1/4" = 1' - 0"
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF EXISTING FOOTINGS AND
COORDINATE SANITARY PIPE ROUTING WITH EXISTING FOOTINGS.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
4.
P300
1-1/2"
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text
K-PR5452-T1D
AutoCAD SHX Text
URINAL
AutoCAD SHX Text
K-PR5452-T1D
K-PR5452-T1DURINAL
K-PR5452-T1DURINAL
3" FD-1
3" FD-1
M
4" FD-1
3" FD-1
CW
HWR
HW
MECHANICAL
MEN'S
WOMEN'S
J.C.
ELEV.
BSMT. / MECH.
ROOM
CORRIDOR
ELECTRICAL
SPRINKLER
BREAK
I.T.
UT
ILI
TY
TU
NN
EL
A
MECHANICAL/STORAGE
MACHINE
STAIRS
CR
AW
L S
PA
CE
CLO.
LOWER LOBBY
CRAWL
CRAWL SPACE
06SPACE
CRAWL SPACE
4" FD-1
EX PD
EX SEWAGE
EJECTOR BASIN
DWH-1
3" V UP
3" V UP
2" V UP
2" V DN
P-8
2" S DN
2" V DN
(0.5 GPM)
3/4" CW,
1/2" HWR
P-4A
P-1B
P-1A
P-5
P-3C
P-2A
P-2A
2" S DN
PUMP-2
2" PD DN
(1.0 GPM)
2" S DN
6" INCOMING
COMBINED SERVICE
PUMP-3
BFP-1
4" S UP
2" V UP
1 1/2" CW UP,
1-1/2" S UP,
1/2" HW UP
1/2" CW UP,
1-1/2" S UP,
1/2" HW UP
2" V UP,
1" CW UP
(0.5 GPM)
(0.5 GPM)
AHU-1.4
ERV-1
FCU-1.2
ACU-4
AHU-2.1
AHU-2.2
ACU-2
ACU-3
AHU-1.1
AHU-2.3
AHU-2.4
FCU-1.3
2" V DN
2" V DN
MV-1
2" PD
P-1B
P-1A P-1A P-1A
2" S DN
2" S DN
2" V DN 2" V DN 2" V DN
1/2" CW UP
1/2" CW UP,
1-1/2" S UP,
1/2" HW UP
2" V DN
2" V DN
3" S DN
4" S
2" V UP,
1" CW UP
CO
CO
3" FCO
4" FCO
4" FCO
4" FCO
3" FCO
4"
4"
4" 4" S
1-1/2" D1-1/2" D
CO
3/4" D
CO
3/4" PD
4"
PD
4"
2" FCO
1-1/2" 3/4"
1-1/2"
3" 3"
2"
2"
1" CW,
1" HW,
1/2" 1-1/2" D
CP-1
1/2" 2"
2"
1" CW,
1/2" HW,
1-1/2" D
1-1/2" D
CW
HWR
HW
CWHW
R
HW
CW
HWRHW
CW HW
R
HW
CW HW
R
HW
CW HW
R
HW
3/4"
1-1/2" D UP
1/2"
CP-3
1-1/2" D UP
2" 1" 1/2"
3/4"
2-1/2" 1-1/4"
1/2"
1-1/2" 1/2" 1-1/4" 2-1/2"
CP-2
1-1/2"
3"
CO
CO
CO
CO
CO
CO
CO
D
PD
SW
BWV
CO
2" SW 7
1"
SW
2" SW7
CO
BWV
PDPD
PD
PD
1"
1"
D
D
D
PD
CO
CO
CO
CO
CO
CO
CO CO
CO
CO
CO
CO
CO
CO
CO
2" CW UP,
3/4" HW UP,
1/2" HWR UP
3/4"
CO
1-1/2"
1-1/4" 1"
1-1/4" 1/2"
(0.5 GPM)
2"
2"
3"
3"
13 13
3" FD-1
3" FD-1
3" FD-1
3" FD-1
(1.0 GPM)
3/4"
3/4"
ET-1 15
(2.5 GPM)
(2.0 GPM)
2" V DN
2" V DN
4" FCO
1"
(1.0 GPM)
3/4"
3/4"
3/4"
2" V DN
1-1/2"
2"
2" V DN
1-1/2"
4"
DRAIN
VALVE
CO
CO
CO
P-3B
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PL
UM
BIN
G
P
AR
T P
LA
NS
NE
W
W O
RK
4" S UP TO WC
PROVIDE TRAP PRIMER VALVE TO PRIME FLOOR DRAINS IN THIS SPACE
3" S UP TO FD
TRAP PRIMER. MOUNT ON WALL WITH TOP OF UNIT APPROXIMATELY 60"
AFF.
MOUNT ON 4" HOUSEKEEPING PAD
MOUNT ON WALL WITH TOP OF UNIT APPROXIMATELY 60" AFF.
SEE DRAWING P002 FOR CONTINUATION
OIL MINDER CONTROL PANEL. MOUNT ON WALL WITH TOP OF UNIT
APPROXIMATELY 60" AFF
SEE FIRE PROTECTION DRAWINGS
PROVIDE CONDENSATE PUMP CP-4
BLADDER TANK FOR BOOSTER PUMP SYSTEM. SEE DETAIL ON P501.
MOUNT ON 4" HOUSEKEEPING PAD.
PUMP-4. MOUNT IN EXISTING BASIN. PROVIDE NEW BASIN COVER.
1/2" HWR UP. CONNECT HWR WITHIN 2 FT OF FIXTURE.
1/2" HWR DN. CONNECT HWR WITHIN 2 FT OF FIXTURE.
SUPPORT FROM ABOVE
FIXTURE BRANCH SHALL BE WITHIN 2 FT OF MAIN
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
P301
LOWER LEVEL - PLUMBING - NEW WORK PART PLAN
1/4" = 1'-0" N
MAV
0 2 8 12 FT4
1/4" = 1' - 0"
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
P301
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text
K-PR5452-T1D
AutoCAD SHX Text
URINAL
AutoCAD SHX Text
K-PR5452-T1D
ATTIC
ROOF LINE
127'-0"
ROOF PEAK
141'-11"
ERV-22
ACCESS HATCH.
KEEP CLEAR
1-1/2" D
FCU-3.8
AHU-3.1 AHU-3.2
COCOCO
CO
1" PD
3/4" D
1" D1" D
1" PD 3/4" D
3" VTR
1-1/2" D 3" V
1-1/2" D
CO
CO
1" PD
1" PD
3/4" PD
FCU-3.6
3" VTR
1-1/2" V
ATTIC
ROOF LINE
127'-0"
ROOF PEAK
141'-11"
ERV-2
EX CHIMNEY
EX ROOF
AHU-3.2
AHU-3.2
1" PD
3/4" D
3/4" D
CP-4
1-1/2" D
3/4" PD
FCU-3.9
1-1/2" V
CO
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
PL
UM
BIN
G
SE
CT
IO
NS
NOT USED
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
MAV
M4010 2 8 12 FT4
1/4" = 1' - 0"
P400
PLUMBING - ATTIC SECTION 3 - NEW WORK
1/4" = 1'-0"
BS-3.1
BS-3.1
P400
PLUMBING - ATTIC SECTION 2 - NEW WORK
1/4" = 1'-0"
P400
PLUMBING - ATTIC SECTION 1 - NEW WORK
1/4" = 1'-0"
NOT FOR BID
DIN
G
OR C
PUMP DISCHARGE.
REFER TO FLOOR PLANS
FOR CONTINUATION
POWER CABLE, PROBE CABLE
AND FLOAT CABLE EXTENDED
TO JUNCTION BOX
FLUSH TO FINISH FLOOR
SUMP PIT GRATING
ELEVATOR SHAFT COMPONENTS
UNDER ANOTHER DIVISION FLOOR LEVEL
UNION
CONCRETE SUMP PIT
PROVIDED UNDER
ANOTHER DIVISIONSUMP PUMP
HIGH WATER ALARM
PUMP ON
PUMP OFF
CHECK VALVE
CONCRETE FOUNDATION
PROVIDED UNDER ANOTHER
DIVISION
ELEVATOR PIT - SUBMERSIBLE SUMP PUMP
ELEVATOR SHAFT
SHUTOFF VALVE
OIL MINDER CONTROL
PANEL. REFER TO FLOOR
PLANS FOR LOCATION.
PROVIDE ALARM
CONNECTION TO BAS.
JUNCTION BOX
PUMP
IN-LINE CIRCULATOR
CHECK VALVE
BALANCING VALVE
SHUTOFF VALVE, TYP
P/T PLUG, TYP PRESSURE GAGE
AND COCK, TYP
FLEXIBLE CONNECTION, TYP
VIBRATION ISOLATION, TYP
DRAIN PAN
SIZE AS INDICATED
EXCEPT NO SMALLER
THAN DRAIN PAN
NIPPLE.
CLEANOUT PLUG
DEPTH OF SEAL AS
REQUIRED TO
OVERCOME OPERATING
STATIC PRESSURE
DIFFERENTAL.
4" MINIMUM
PITCH
FCU CONDENSATE DRAIN TRAP
PIPE TO FLOOR
CHECK VALVE (TYP)
THERMOMETER (TYP)
MV-1
TOP OF DOMESTIC WATER
MIXING VALVE SHALL BE
INSTALLED BELOW TOP OF
DOMESTIC WATER HEATER
PIPE TO DRAIN PAN
1/2" HB 27" HEAT TRAP
ET-1
TEMPERATURE AND
PRESSURE RELIEF
VALVE (TYP)
PUMP-2
DWH-1
1-1/2" CW
3/4" HWR
1-1/2" HW
DRAIN PAN
ELECTRIC WATER HEATER
1/2" 140 HW
140140
CONDENSATE PUMP WITH CHECK VALVE
CONDENSATE PUMP
PD
COD
PD
CHECK VALVE
DUPLEX DOMESTIC WATER BOOSTER PUMP
DRAIN VALVE
RELIEF VALVE. DISCHARGE TO
NEAREST FLOOR DRAIN
BLADDER TANK
BOOSTER
PUMP
SYSTEM DOMESTIC
WATER TO
BUILDING
INCOMING
DOMESTIC
WATER
NORMALLY
CLOSED BYPASS
4" HOUSEKEEPING PAD
SHUT-OFF VALVE
CHECK VALVE
UNION
FINISHED FLOORFINISHED FLOOR
FLUSH TO FINISH FLOOR
PUMP COVER
INCOMING SAN PIPE,
INVERT ELEVATION AS REQUIRED
SEWAGE EJECTOR
DUPLEX SEWAGE EJECTOR
CONCRETE PIT. REFER TO
STRUCTURAL DRAWINGS
VENT TO
NEAREST
VENT PIPE
VENT PER MANUFACTURER
REQUIREMENTS
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PL
UM
BIN
G
D
ET
AI
LS
MAV
P501
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text
LOWER LEVEL
GROUND LEVEL
UPPER LEVEL
LOWER LEVEL
GROUND LEVEL
UPPER LEVEL
ATTIC ATTIC
SERV SINK
LAV
LAVWC
205A
DWC
LAV WC
LAV WC
204 203 204
WC
LAV
WC
SINKICEMAKER
UR
UR WC WC LAV
LAV LAV
LAV LAV WC
WC WC WC
SINKICEMAKER
6" INCOMING COMBINED SERVICE
M BFP-1 PUMP-3
TO DWH. SEE
DETAIL ON P501.
(1.0 GPM)
(0.5 GPM)
(0.5 GPM)
(0.5 GPM)
(PDI-B) SHOCK ABSORBER, TYP.
(1.0 GPM)
(PDI-A)
(PDI-A)
(PDI-B)
(PDI-C) (PDI-A)
(PDI-A)
(PDI-C)
(PDI-A)
3" CW
1-1/2"
1-1/2" HW
3/4" HWR
ICEMAKER
027023
TRAP PRIMER
TRAP PRIMER
SEE FIRE
PROTECTION
DRAWINGS
3"
2" 1" 1/2"
1-1/2"
1-1/4" CW1-1/4"
1" 1/2"
2-1/2" 1-1/4" 1/2"
1/2" 3/4"
2"1-1/4"
2"2" 3/4" 1/2"
1/2"1/2"
2" 3/4" 1/2"
3/4" 1-1/2"
1-1/2"
1/2"
1/2"
2-1/2" 2"
3"
3/4"
(0.5 GPM)
2" 2"
(1.5 GPM)
(2.5 GPM)
(0.5 GPM)
(0.5 GPM)
(1.0) GPM) 3/4"1"1"
(PDI-A)
(PDI-A)
(PDI-A)(PDI-A)
(PDI-A)
(PDI-A) (PDI-A)
(PDI-A)
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
DO
M
ES
TIC
W
AT
ER
R
ISE
R
DI
AG
RA
M
S
MAV
P601
P601
DOMESTIC WATER RISER DIAGRAM
NTS
NOT FOR BID
DIN
G
OR C
UPPER LEVEL
LOWER LEVEL
GROUND LEVEL
UPPER LEVEL
ATTIC ATTIC
4" S
4"
SINK
2"
CO
WC
FD
LAV
4"
CO
LAV
FD
WC
4"
2-1/2" WET-VENT
LAV
205A
4" FCO
3" VTR 3" VTR
A2A1
4"
3" 3"
3" 3"
2-1/2"
2-1/2"
2"
CO
CO
CO
WC205A
FD
205A
DWC
4" 2-1/2" WET-VENT
LAV
WC204
FD
4" 2-1/2" WET-VENT
LAV
WC203
FD
4"
2" 2" 2"
2-1/2"
1-1/2"
3" 4"
1-1/2"
3" 4" 1-1/2"
3" 4"
3" 4"
3" 4"
4"
2"
CO
CO
CO
LOWER LEVEL
GROUND LEVEL
LOWER LEVEL
GROUND LEVEL
EX SEWAGE
EJECTOR
EX PD
4" PD
4" S
SERV SINK
4"
2" 4"
LAV
LAV LAV
2" FCO
WC
WC WC
FD
WC
4" FCO
4" 2-1/2"
UR
UR
2" FCO
4"
WC
FD
WC
LAV LAV
2" FCO
4"
4" FCO
4"
FD
SINK
FD
FD
4" FCO
4"
2"2" 2"
2" 2" 2" 3"
2"4" 4"
A2A1
3" 3" 3" 1-1/2"
2"
3"3"
3"
3" 1-1/2"2"
2" 2"
2" FCO
FD
FD
FD
FD
A3 A3
4"4"3"
2" 2"
4"
3"
2"
2"
2"
3" 4"
1-1/2"2"
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
SA
NI
TA
RY
R
ISE
R
DI
AG
RA
M S
MAV
P602
P602
SANITARY RISER DIAGRAM
NTS
P602
SANITARY RISER DIAGRAM
NTSNOT FOR BID
DIN
G
OR C
UPPER LEVEL
LOWER LEVEL
GROUND LEVEL
UPPER LEVEL
ATTIC ATTIC
AHU-3.1FCU-3.8AHU-3.4FCU-3.6FCU-3.7
FCU-2.2FCU-2.1
015015
ATTICATTIC
CO
1-1/2" D
1-1/2" D1-1/2" D
CO
1" PD
CP-3
1-1/2" D
1-1/2" D
CP-4
CP-4
CP-4 CP-4
COSW
AHU-3.5 AHU-3.9 FCU-3.3
COCO
CO
2"
3/4" 3/4"
3/4"
3/4"3/4" 1" 3/4" 3/4"
3/4"
3/4" 3/4"
3/4"
1"
3/4" 3/4"
1-1/2" 3/4"3/4"
CO
CP-4
COCO
CO
CO
CO
CO
AHU-3.2
3/4" CO
LOWER LEVEL
GROUND LEVEL
LOWER LEVEL
GROUND LEVEL
EX FCU FCU-1.5A EX FCU ACU-1
020A020020020
FCU-1.5B
FCU-1.6
EX FCUFCU-1.5C
020020
CO
EX FCU
CP-1
FCU-1.1FCU-2.4FCU-2.3
ACU-2
016016
CO
FCU-1.2 1-1/2" D
1-1/2" D
1" PD
1-1/2" PD
CP-4CP-4CP-4CP-4
CP-4 CP-4SW2" A1
3/4"3/4"3/4" 3/4"
3/4"
3/4"1"3/4"
1-1/2"
1"
3/4"
1"
3/4" 3/4" 3/4"
3/4"
3/4" 3/4" 1"
3/4"
CO
COCO
COCOCOCO
CO
CP-4
CP-4 CP-4 CP-4
CO
EX FCU
020A
CP-4
CO
LOWER LEVEL
GROUND LEVEL
LOWER LEVEL
GROUND LEVEL
FCU-1.9B
030019
CO
FCU-1.10
030A
FCU-1.8
FCU-1.9A
FCU-1.7B
FCU-1.7A
1" PD
ACU-4
025026
ACU-3
FCU-1.4
FCU-1.3
CO
CP-2
1-1/2" D
1-1/2"D 1-1/2"D
1" PD
CP-4
CP-4 CP-4
CO
SW
2"
A1 CO
1" 3/4"
3/4" 1" 3/4" 3/4"
3/4" 3/4"3/4"
3/4" 3/4"3/4"3/4"1"
COCOCOCOCO
CO
COCO
CP-4
CO
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
CO
ND
EN
SA
TE
R
ISE
R
DI
AG
RA
M
S
MAV
P6033 P603
CONDENSATE RISER DIAGRAM
NTS
P603
CONDENSATE RISER DIAGRAM
NTS
P603
CONDENSATE RISER DIAGRAM
NTS
NOT FOR BID
DIN
G
OR C
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
PL
UM
BIN
G
SC
HE
DU
LE
S
GENERAL NOTES: (APPLICABLE TO ALL PLUMBING SCHEDULES)
1.
2.
3.
4.
5.
6.
UNIT NUMBERS ARE INDICATED WHERE ALL UNITS ARE LISTED AND NUMBERED INDIVIDUALLY.
UNIT SYMBOLS ARE INDICATED WHERE ALL UNITS ARE NOT LISTED AND NUMBERED
INDIVIDUALLY.
UNIT TYPES ARE DESCRIBED IN THE SPECIFICATIONS.
TEMPERATURE VALUES ARE LISTED IN DEGREES FAHRENHEIT.
FLUID PRESSURE VALUES ARE LISTED IN FEET OF WATER GAGE.
PIPE SIZES ARE LISTED IN SINGLE-NUMBER INCHES OF NOMINAL DIAMETER OR MULTIPLE
NUMBER INCHES OF INDICATED PARAMETER. CONNECTION SIZES ARE FROM MAINS TO UNIT
INLETS. SINGLE PIPE SIZE IS TYPICAL FOR SUPPLY AND RETURN.
MAV
P801
NOT FOR BID
DIN
G
OR C
| P001 PLUMBING COVER SHEET |
| P002 PLUMBING SITE PLAN - NEW WORK |
| P100 PLUMBING NEW WORK PLAN |
| P101 PLUMBING NEW WORK PLAN |
| P102 PLUMBING NEW WORK PLAN |
| P300 PLUMBING PART PLANS - NEW WORK |
| P301 PLUMBING PART PLANS - NEW WORK |
| P400 PLUMBING SECTIONS |
| P501 PLUMBING DETAILS |
| P601 DOMESTIC WATER RISER DIAGRAMS |
| P602 SANITARY RISER DIAGRAMS |
| P603 CONDENSATE RISER DIAGRAMS |
| P801 PLUMBING SCHEDULES |
| PD002 PLUMBING SITE PLANS DEMOLITION |
| PD100 PLUMBING DEMOLITION PLAN |
| PD101 PLUMBING DEMOLITION PLAN |
| PD102 PLUMBING DEMOLITION PLAN |
| PD300 PLUMBING PART PLANS - DEMOLITION |
| PD301 PLUMBING PART PLANS - DEMOLITION |
File details come from the government source that posted it. Updated .