drawing - FIRE ALARM_QAC Historic Courthouse RFQ_2026.07.01.pdf
PDF 2 MB Posted
- Attached to
- Historic Courthouse Renovation
- Solicitation number
- BPM057809
- Issued by
- Queen Anne's County, Maryland
About this file
This is a fire alarm system drawing for the Historic Courthouse renovation project in Queen Anne's County, Maryland. The drawing provides technical specifications and layout details for the fire alarm installation as part of the comprehensive renovation of the 17,800-square-foot Historic Courthouse located at 100 Courthouse Square in Centreville. The fire alarm system represents one component of the electrical and life safety systems being newly installed in the building, which will include a new electrical service, back-up power generator, lightning protection, and other integrated building systems. The drawing serves as a reference document for general contractors and subcontractors bidding on or executing the construction work to understand the fire alarm system design, placement, and integration requirements within the overall renovation scope.
The fire alarm drawing is a technical specification document that does not independently address pricing terms, contract set-asides, incumbent information, or funding details. This drawing functions as a supporting exhibit to the Request for Qualifications (RFQ) for General Contractor services and should be reviewed in conjunction with the primary RFQ documents, bid specifications, and project scope of work to obtain complete information regarding cost requirements, project timeline, and award criteria for the Historic Courthouse renovation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
FA001
FIR
E A
LA
RM
C O
VE
R
SH
EE
T
REFERENCE
PRESENTATION
FIRE ALARM
FIRE ALARM CONVENTIONS
SPECIAL NOTE (APPLIES WHERE INDICATED ON THE DRAWING)1
FIRE ALARM EQUIPMENT DESIGNATED BY SOLID HEAVY
LINEWEIGHT INDICATES NEW WORK TO BE PROVIDED.
FIRE ALARM EQUIPMENT DESIGNATED BY SOLID LIGHT
LINEWEIGHT INDICATES EXISTING EQUIPMENT TO REMAIN,
UNLESS OTHERWISE INDICATED.
FIRE ALARM EQUIPMENT DESIGNATED BY DASHED HEAVY
LINEWEIGHT REPRESENTS EXISTING EQUIPMENT TO BE
REMOVED AND DISPOSED, UNLESS INDICATED TO BE
REMOUNTED, RELOCATED, OR TURNED OVER TO OWNER.
CANDELA RATING
DEVICE TYPE
15cd
NOTES: (APPLICABLE TO FIRE ALARM LEGEND ONLY)
1. THE MOUNTING HEIGHTS GIVEN ON THIS SHEET IN THE FIRE ALARM LEGEND ARE GENERAL AND SHALL BE
USED ONLY WHEN MOUNTING HEIGHTS CANNOT BE ESTABLISHED BY REFERENCE TO DETAILS,
ELEVATIONS, AND NOTES ON THE DRAWINGS.
2. ALL MOUNTING HEIGHTS, UNLESS OTHERWISE NOTED, SHALL BE MEASURED FROM THE FINISHED FLOOR
TO THE CENTERLINE OF THE OUTLET OR DEVICE.
3. HEIGHTS OF ALL ITEMS NOT COVERED BY THE FIRE ALARM LEGEND AND NOT SHOWN ON THE DRAWINGS
SHALL BE AS DIRECTED BY THE ARCHITECT OR ENGINEER.
4. WHERE PLACING ANY ITEM AT THE HEIGHTS LISTED OR NOTED WILL CAUSE INTERFERENCE WITH THE WORK OF OTHER TRADES, OR IS NOT PHYSICALLY POSSIBLE OR DESIRABLE FOR ONE REASON OR ANOTHER, THE ITEM SHALL BE INSTALLED AT A LOCATION APPROVED BY THE ARCHITECT OR ENGINEER.
FIRE ALARM SYSTEM - SMOKE DETECTOR - AREA, CEILING/WALL MOUNT
SUBSCRIPTS:
P: PHOTOELECTRIC TYPE (DEFAULT IF NO SUBSCRIPT INDICATED)
I: IONIZATION TYPE
E: ELEVATOR RECALL FUNCTION
SEE DETAIL
SS
FIRE ALARM ADDRESSABLE MODULE 78" TO TOPAM
SYMBOL DESCRIPTION MOUNTING
HEIGHT
FIRE ALARM LEGEND
SEE DETAIL
FIRE ALARM SYSTEM - HEAT DETECTOR, CEILING/WALL MOUNT
SUBSCRIPTS:
F: FIXED TEMPERATURE (DEFAULT IF NO SUBSCRIPT INDICATED)
FIRE ALARM SYSTEM - SPRINKLER FLOW DETECTION SWITCH - -FS
FIRE ALARM SYSTEM - MANUAL FIRE ALARM BOX 46"F
86"FIRE ALARM SYSTEM - BELL
- - / 86"
FIRE ALARM SYSTEM - STROBE, CEILING/WALL MOUNT
SUBSCRIPTS:
WP: WEATHERPROOF
WG: WIRE GUARD
- - / 86"
FIRE ALARM SYSTEM - LOUDSPREAKER , CEILING/WALL MOUNT
SUBSCRIPTS:
WP: WEATHERPROOF
WG: WIRE GUARD
EP: EXPLOSION PROOF
FIRE ALARM SYSTEM - FIRE ALARM CONTROL PANEL 78" TO TOPFACP
TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM FOR RESCUE
ASSISTANCE – CALL STATION 46"AR
FIRE ALARM SYSTEM DOCUMENTATION CABINET --FADC
FIRE ALARM SYSTEM - VALVE WITH TAMPER DETECTION SWITCH - -TS
BVT
A AMPERE
ADA AMERICANS WITH DISIBILITIES ACT
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AGM ABSORBED GLASS MAT
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIM ADDRESSABLE INTERFACE MODULE
ANSI AMERICAN NATIONAL STANDARDSINSTITUTE
AWG AMERICAN WIRE GAUGE
BDA BI-DIRECTIONAL AMPLIFIER
BLDG BUILDING
BOD BASIS OF DESIGN
C CONDUIT
CB CIRCUIT BREAKER
CD CANDELA
CI CIRCUIT INTEGRITY
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CARBON MONOXIDE
COMM COMMUNICATIONS
CX CONNECT TO EXISTING
DACT DIGITAL ALARM
COMMUNICATORTRANSMITTER
DAS DISTRIBUTED ANTENNA SYSTEM
DB DECIBEL
DN DOWN
DOAS DEDICATED OUTDOOR AIR SYSTEM
DWG DRAWING
E EMERGENCY
ECS EMERGENCY COMMUNICATIONSSYSTEM
EMR ELEVATOR MACHINE ROOM
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EQUIP EQUIPMENT
ERCCS EMERGENCY
RESPONDERCOMMUNICATIONS
COVERAGESYSTEM
ERCES EMERGENCY RESPONDERCOMMUNICATIONS
ENHANCEMENTSYSTEM
ERRCS EMERGENCY RESPONDER RADIOCOVERAGE
SYSTEM
ETR EXISTING TO REMAIN
EVACS EMERGENCY
VOICE/ALARMCOMMUNICATIONS
SYSTEMEX EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FACU FIRE ALARM CONTROL UNIT
FAID FIRE ALARM INITIATING DEVICE
FEO FIREFIGHTERS'
EMERGENCYOPERATION
FMC FLEXIBLE METAL CONDUIT
FSAE FIRE SERVICE ACCESS ELEVATOR
FT FEET
G GROUND
GND GROUND
GW GROUND WIRE
HLI HIGH LEVEL INTERFACE
HVAC HEATING VENTILATING
AIRCONDITIONING
HVI HEARING AND VISUALLY IMPAIRED
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
IDC INITIATING DEVICE CIRCUIT
FIRE ALARM ABBREVIATIONS
IEBC INTERNATIONAL EXISTING BUILDINGCODE
IFC INTERNATIONAL FIRE CODE
IN INCH
JB JUNCTION BOX
LCD LIQUID CRYSTAL DISPLAY
LED LIGHT EMITTING DIODE
MAX MAXIMUM
MI MINERAL INSULATED
MIN MINIMUM
MNS MASS NOTIFICATION SYSTEM
MTD MOUNTED
NAC NOTIFICATION APPLIANCE CIRCUIT
NC NORMALLY CLOSED
NCP NETWORK CONTROL PANEL
NEC NATIONAL ELECTRICAL CODE
NECA NATIONAL ELECTRICALCONTRACTORS'
ASSOCIATION
NEMA NATIONAL ELECTRICALMANUFACTURERS'
ASSOCIATION
NESC NATIONAL ELECTRICAL SAFETY CODE
NFPA NATIONAL FIRE
PROTECTIONASSOCIATION
NIC NOT IN CONTRACT
NICET NATIONAL INSTITUTE FORCERTIFICATION IN
ENGINEERINGTECHNOLOGIES
NO NUMBER, NORMALLY OPEN
NPLFA NON-POWER LIMITED FIRE ALARM
NTS NOT TO SCALE
OC ON CENTER
OEE OCCUPANT EVACUATION ELEVATOR
OSHA OCCUPATIONAL SAFETY AND
HEALTHADMINISTRATION
P POLE, PHASE
PA PUBLIC ADDRESS
PC PERSONAL COMPUTER
PH PHASE
PLC POWER LIMITED CIRCUIT
PLFA POWER-LIMITED FIRE ALARM
POE POWER OVER ETHERNET
PVC POLYVINYL CHLORIDE
PWR POWER
QTY QUANTITY
R RACEWAY
RA RETURN AIR
RM ROOM
RTU ROOF TOP UNIT
RX REMOVE EXISTING
SA SUPPLY AIR
SF SQUARE FEET
SLC SIGNALING LINE CIRCUIT
SPD SURGE PROTECTION DEVICE
TYP TYPICAL
UG UNDERGROUND
UL UNDERWRITER'S LABORATORY
UON UNLESS OTHERWISE NOTED
V VOLTS
VRLA VALVE REGULATED LEAD ACID
W WIRE, WATTS
W/ WITH
WP WEATHERPROOF
FIRE ALARM SYSTEM - FIRE ALARM SYSTEM ANNUNCIATOR PANEL 78" TO TOPFAAP
TWO-WAY EMERGENCY COMMUNICATIONS SYSTEM FOR RESCUE
ASSISTANCE – ANNUNCIATOR PANEL / MASTER STATION 78" TO TOPARAP
FIRE ALARM SYSTEM - MAGNETIC DOOR HOLDER COORDINATE
W/ DOOR
DH
GENERAL FIRE ALARM NOTES
1. VERIFY THAT EXISTING FIRE ALARM SYSTEM IS OPERATIONAL BEFORE MAKING CHANGES OR CONNECTIONS.
2. DO NOT INTERRUPT EXISTING FIRE ALARM SYSTEM WITHOUT [CONTRACTING OFFICER'S] [OWNER'S] [OWNER'S REPRESENTATIVE'S] [ENGINEER'S] [ARCHITECT'S] WRITTEN
PERMISSION.
3. DRAWINGS ARE CONCEPTUAL, INTENDED TO SHOW GENERAL SYSTEM CONFIGURATION AND PERFORMANCE. PREPARE SHOP DRAWINGS AND PROVIDE CONDUITS, WIRING, SYSTEM COMPONENTS AND EQUIPMENT FOR A COMPLETE AND OPERATIONAL SYSTEM IN COMPLIANCE WITH NFPA 70, NFPA 72, NFPA 90A, NFPA 101 IBC, THE
AUTHORITY HAVING JURISDICTION AND THE CONTRACT DOCUMENTS.
4. SCHEDULE PRELIMINARY REVIEW WITH FIRE MARSHAL. COORDINATE FIRE ALARM WORK WITH LOCAL FIRE MARSHAL, FIRE ALARM PLANS REVIEW, AND FIRE
DEPARTMENT INSPECTORS.
5. OBTAIN AND PAY FOR PERMITS REQUIRED FOR INSTALLATION OF FIRE ALARM SYSTEM. PROVIDE SHOP DRAWING SUBMITTAL DOCUMENTS TO AUTHORITY HAVING JURISDICTION TO OBTAIN PERMIT. SUBMITTAL SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:
A. SCALED FLOOR PLANS WITH ROOM NAMES AND NUMBERS WHICH INDICATE USE OF ALL ROOMS.
B. FIRE ALARM DEVICE AND CABLE SYMBOL LEGEND.
C. FLOOR PLAN LAYOUT SHOWING LOCATIONS OF ALL DEVICES AND CONTROL EQUIPMENT, INCLUDING MOUNTING HEIGHTS OF ALARM INITIATING DEVICES AND
NOTIFICATION DEVICES.
D. FIRE ALARM CONTROL PANEL AND ANNUNCIATOR LOCATION.
E. POWER CONNECTION.
F. BATTERY CALCULATIONS.
G. VOLTAGE DROP CALCULATIONS FOR NOTIFICATION APPLIANCE CIRCUITS.
H. SIZE, TYPE, AND NUMBER OF CONDUCTORS.
I. MANUFACTURER'S TECHNICAL DATA SHEETS INCLUDING MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES, AND MATERIALS.
J. DETAILS OF CEILING HEIGHT AND CONSTRUCTION.
K. INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS.
L. FIRE ALARM SYSTEM RISER.
M. SEQUENCE OF OPERATIONS INPUT/OUTPUT MATRIX.
N. DEVICE TO DEVICE WIRING.
O. LOUDNESS AND CANDELA SETTINGS FOR EVERY NOTIFICATION APPLIANCE.
6. FIRE ALARM BRANCH CIRCUIT IDENTIFICATION MUST COMPLY WITH NFPA 70 AND NFPA 72:
· PROVIDE APPROVED RED CIRCUIT BREAKER LOCKOUT DEVICE FOR EACH CIRCUIT BREAKER SERVING A FIRE ALARM CIRCUIT.
· IDENTIFY EACH FIRE ALARM CIRCUIT WITH A RED PHENOLIC NAMEPLATE WITH WHITE LETTERING. NAMEPLATE SHALL READ "FIRE ALARM CIRCUIT". FASTEN
NAMEPLATE IN PANELBOARD ADJACENT TO CIRCUIT BREAKER.
7. IDENTIFY POWER SOURCE AND LOCATION OF BRANCH CIRCUIT DISCONNECT SERVING FIRE ALARM EQUIPMENT. FASTEN PHENOLIC NAMEPLATE TO FIRE ALARM SYSTEM
PANEL(S) INDICATING LOCATION OF DEDICATED BRANCH CIRCUIT DISCONNECTING MEANS. NAMEPLATE SHALL READ "THIS PANEL FED FROM PANEL ____, CIRCUIT NO.
____, LOCATED IN _____."
8. IDENTIFY EACH FIRE ALARM DEVICE AND EQUIPMENT ENCLOSURE. DEVICE LABELS SHALL INDICATE ADDRESS AND ZONE.
9. IDENTIFY FIRE ALARM CIRCUITS AT TERMINAL AND JUNCTION LOCATIONS WITH PERMANENT LABELS. PAINT FIRE ALARM CIRCUIT JUNCTION BOX COVERS RED AND LABEL
COVER "FIRE ALARM". PAINT CONDUITS CARRYING FIRE ALARM SYSTEM CIRCUITS RED.
FIRE ALARM SYSTEM ROOM TEMPERATURE SWITCH - -FRZ
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
FA002
FIR
E A
LA
RM
C O
VE
R
SH
EE
T
FA002
FIRE ALARM DEVICE MOUNTING DETAIL
NOT TO SCALE
SIDE WALL
SIDE WALLSIDE WALL
ANNUNCIATOR PANEL OR
LISTED CEILING MOUNTED
NOTIFICATION APPLIANCE
FINISHED FLOOR
CEILING
AUDIBLE/STROBE COMBINATION
1'-0" MAX.1'-0" MAX
6'-6" MAX
5'-0" MIN TO
OF DEVICE
OR
0'-6" BELOW
FINISHED CEILING,
WHICHEVER IS
LOWER
7'-6" TO TOP
FROM STROBE
LENS TO FLOOR
OR
WITHIN 0'-6" OF
FINISHED CEILING,
WHICHEVER IS
LOWER
6'-8" MIN TO 8'-0" MAX
OPERATING HANDLE TO FLOOR
3'-10"� FROM
5'-0" MAX
3'-0" MIN0'-4" MIN
0'-4" MIN.
0'-4" MIN.
EXIT
SMOKE OR HEAT
DETECTOR
DO NOT LOCATE
HEAT DETECTOR
WITHIN THIS AREA
HEAT DETECTOR MOUNTING
PLACEMENT REQUIREMENTS
HEAT DETECTOR
HEAT
DETECTOR
FROM EXIT OPENING
MOUNT FIRE ALARM DEVICES ON APPROVED BOXES.NOTE:
REMOTE LAMP
W/ TEST SWITCH
HEAT
DETECTOR
MOUNT DETECTOR
ON APPROVED BOX 6'-0" MAX LENGTH FLEXIBLE RACEWAY TO DEVICE
MOUNTED ON SUSPENDED CEILING
FLOOR-CEILING ASSEMBLY
CEILING
AUDIBLE
DEVICE
SMOKE
DETECTOR
FINISHED FLOOR
MANUAL
PULL STATION
STROBE
FIRE ALARM CONTROL
PANEL OR EMERGENCY
VOICE PANEL
TERMINAL CABINET
JUNCTION BOX
CONDUIT
AIR SUPPLY DIFFUSER OR
RETURN AIR OPENING
INSTALL PER NATIONAL
ELECTRICAL CODE
BVT
FA002
ELEVATOR FIRE ALARM AND SPRINKLER WORK SUMMARY
NOT TO SCALE
NOT FOR BID
DIN
G
OR C
ELEVATOR 1
STAIR 1
FIRE
DEPARTMENT
CONNECTION
FACP
STAIR 2
EXIT EXIT EXIT
ELEVATOR 1 ELEVATOR
MACHINE ROOM
STAIR 1
STAIR 2
ELEVATOR 1
STAIR 1
STAIR 3
EXIT
ATTIC ACCESS
ATTIC ACCESS
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
FA003
FIR
E A
LA
RM
G
RA
PH
IC
M
AP
LA
YO
UT
FA003
FIRE ALARM GRAPHIC MAP LAYOUT
1/16" = 1'-0"
BVT
0 8 32 48 FT16
1/16" = 1' - 0"
GROUND LEVEL
LOWER LEVEL
UPPER LEVEL
ATTIC
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text + 6"6"
COURTROOM
OFFICE 10
OFFICE 9
OFFICE 8
OFFICE 11
OFFICE 13
OFFICE 12
LOBBY
VAULTELEV.
F
FAAP
F
F
S
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
BASEMENT
MECHANICAL
MECHANICAL
KITCHEN
CELL 1
CELL 2
OFFICE
LAV.
SECURITY/SURVEILLANCE
OFFICE
OFFICE
OFFICE
OFFICE
OLD LAW LIBRARY
SAFE
IT
BACK-UP 911 CENTER
OFFICE
OFFICE OFFICE
OFFICE
WOMEN
MEN
ELEV.
OFFICE
FA
IP
F
F
S
S
CRAWL SPACE
CRAWL SPACE
COURTROOM
JURY CONFERENCE
OFFICE
JUDGE'S CHAMBER
HOLDING CELL
ELEV.
F
S
F
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
FAD100
GROUND LEVEL - FIRE ALARM - DEMOLITION PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"N FAD100
FIR
E A
LA
RM
DE
M O
LIT
IO
N
FAD100
LOWER LEVEL - FIRE ALARM - DEMOLITION PLAN
1/8" = 1'-0" N
FAD100
UPPER LEVEL - FIRE ALARM - DEMOLITION PLAN
1/8" = 1'-0" N
SPECIAL NOTES: (APPLICABLE TO THIS SHEET ONLY)
--1
DRAWING NOTES: (APPLICABLE TO THIS SHEET ONLY)
1. UNLESS OTHERWISE NOTED, FIRE ALARM ITEMS SHOWN BY DASHED HEAVY
LINEWEIGHT ( ) INDICATE EXISTING ITEMS TO BE REMOVED. FIRE ALARM
ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( ) INDICATE EXISTING ITEMS
TO REMAIN.
2. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR
GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING
CONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE
FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION
OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED
THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR
SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT WRITTEN
DIRECTION BEFORE PROCEEDING WITH THE WORK.
ZAJ
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
30 x x 68
S E
F F
WP
FADC FACP
F F
ARAP
FA
AP
DH
DH
FIRE DEPARTMENT
CONNECTION30
REGISTER OF WILLS
BREAK AREA
STAIRS
ELEV. LOBBY
LOBBY
ORPHAN'S COURTROOM
RECEPTION
109RECORDS
CORRIDOR
R.O.W. OFFICE
CHIEF DEPUTY
DEPUTY
ELEV
UNISEX
UNISEX
OFFICE OF THE
CLO.
109A
FSTS
AE TEAM TO COORDINATE
LOCATION OF FACP ON LOWER
LEVEL WITH DPWS
E
S E
AM
AM
60 15
F
30 30
AR
AMAMAM
F
MECHANICAL
MEN'S
WOMEN'S
J.C.
ELEV.
BSMT. / MECH.
ROOM
CORRIDOR
SECONDARY PSAP
I.T.
20A
MEETING ROOM
OPEN OFFICE AREA
ELECTRICAL
SPRINKLER
VAULT
22A
OPEN OFFICE AREA
OFFICE
OFFICE
BREAK
I.T.
UT
ILI
TY
TU
NN
EL
A
MECHANICAL/STORAGE
MACHINE
STAIRS
CRAWL SPACE
CLO.
LOWER LOBBY
CRAWL
CRAWL SPACE
SPACE
CRAWL SPACE
MECH. CL.
30A
F
TS
TS FS TS TS
TS
AM
TS
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
FA100
GROUND LEVEL - LIGHTING - NEW WORK
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"
N
FA100
FIR
E A
LA
RM
NE
W W
O
RK
FA100
LOWER LEVEL - FIRE ALARM - NEW WORK
1/8" = 1'-0" N
SPECIAL NOTES: (APPLICABLE TO THIS SHEET ONLY)
CONTROL RELAY MODULE FOR ELEVATOR CONTROLLER INTERFACE TO
INITIATE RECALL TO DESIGNATED LEVEL.
DRAWING NOTES: (APPLICABLE TO THIS SHEET ONLY)
1. UNLESS OTHERWISE NOTED, FIRE ALARM ITEMS SHOWN BY SOLID HEAVY
LINEWEIGHT ( ) INDICATE NEW WORK TO BE PROVIDED. FIRE ALARM ITEMS
SHOWN BY SOLID LIGHT LINEWEIGHT ( ) INDICATE EXISTING ITEMS TO
REMAIN.
2. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING
THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE
OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT WRITTEN
DIRECTION BEFORE PROCEEDING WITH THE WORK.
CONTROL RELAY MODULE FOR ELEVATOR CONTROLLER INTERFACE TO
INITIATE RECALL TO ALTERNATE LEVEL.
CONTROL RELAY MODULE FOR ELEVATOR CONTROLLER INTERFACE TO
ACTIVATE CAR WARNING SIGNAL.
BVT
COORDINATE EXACT LOCATION OF FIRE ALARM DEVICES IN THIS ROOM WITH
ELEVATOR CONTRACTOR.
FOR MONITORING SHUNT TRIP CONTROL VOLTAGE.6
FOR ACTIVATING SHUNT TRIP.7
PROVIDE A HEAT DETECTOR ADJACENT TO EACH SPRINKLER. MAKE
CONNECTION THROUGH FIRE ALARM CONTROL PANEL TO ELEVATOR SHUNT
TRIP DEVICE.
FOR SPRINKLER FLOW NOTIFICATION. COORDINATE FINAL LOCATION WITH
AHJ.
NOT FOR BID
DIN
G
OR C
S E
F
AR
UPPER LOBBY
COURTROOM
CONFERENCE
200A
ELEV. LOBBY
206STAIRS
JUDGE'S CHAMBER
REST LOBBY
UNISEX
UNISEX
ELEV
TOILET
205A
CLOSET
205B
F
FRZ FRZ
FRZ FRZ
FRZ FRZ
FRZ
FRZ
FSTS
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
0 4 16 24 FT8
1/8" = 1' - 0"
FA101
FIR
E A
LA
RM
NE
W W
O
RK
SPECIAL NOTES: (APPLICABLE TO THIS SHEET ONLY)
--------------------------1
DRAWING NOTES: (APPLICABLE TO THIS SHEET ONLY)
1. UNLESS OTHERWISE NOTED, FIRE ALARM ITEMS SHOWN BY SOLID HEAVY
LINEWEIGHT ( ) INDICATE NEW WORK TO BE PROVIDED. FIRE ALARM ITEMS
SHOWN BY SOLID LIGHT LINEWEIGHT ( ) INDICATE EXISTING ITEMS TO
REMAIN.
2. INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING
THE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE
OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT WRITTEN
DIRECTION BEFORE PROCEEDING WITH THE WORK.
BVT
FA101
ATTIC - FIRE ALARM - NEW WORK
1/8" = 1'-0" N
FA101
UPPER LEVEL - FIRE ALARM - NEW WORK
1/8" = 1'-0" N
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
+ 6"6"
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
FA300
FIR
E A
LA
RM
M
AT
RIX
FIRE ALARM SYSTEM AC POWER FAILURE
FIRE ALARM SYSTEM LOW BATTERY
FIRE ALARM SYSTEM OPEN CIRCUIT
FIRE ALARM SYSTEM GROUND FAULT
FIRE ALARM SYSTEM NOTIFICATION
APPLIANCE SHORT CIRCUIT
HVAC DUCT SMOKE DETECTOR
SMOKE DETECTOR AT SMOKE DAMPER
SMOKE DETECTOR AT FIRE-SMOKE DAMPER
CLOSE ASSOCIATED SMOKE DAMPER
A B C D E F G H I K L M N O P Q R V W X Y Z AAS T U
SYSTEM INPUTS
SYSTEM OUTPUTS
SUPPLEMENTARY
BB
ILL
UMINATE PROPER LE
D AT GRAPHIC ANNUNCIATOR
POST INDICATOR VALVE TAMPER SWITCH
J
CC DD
RELEASE MAGNETICALLY
HELD SMOKE DOORS
RECALL
ELEVATOR TO ALTERNATE LE
VEL
RECALL
ELEVATOR TO DESIGNATED LE
VEL
ACTUATE ASSOCIATED FAN SHUT DOWN SIGNAL
EMERGENCY CONTROL FUNCTION
SHUT DOWN POWER TO ELEVATOR
SHUT DOWN RESPECTIVE AIR HANDLIN
G UNIT
ACTUATE WARNING TO ELEVATOR CAB
CLOSE ASSOCIATED FIRE/SMOKE DAMPER
ELEVATOR LOBBY SMOKE DETECTOR
DESIGNATED LEVEL ELEVATOR LOBBY
SMOKE DETECTOR
ELEVATOR MACHINE ROOM SMOKE
DETECTOR
ELEVATOR MACHINE ROOM HEAT
DETECTOR
ELEVATOR SHUNT TRIP CONTROL POWER
SUPERVISING RELAY
SPRINKLER SYSTEM WATER FLOW SWITCH IN
ELEVATOR PIT
ACTUATE COMMON SUPERVISORY SIGNAL IN
DICATOR
ACTUATE AUDIBLE SUPERVISORY SIGNAL
ACTUATE COMMON ALARM SIGNAL IN
DICATOR
ACTUATE COMMON TROUBLE SIGNAL IN
DICATOR
ACTUATE AUDIBLE ALARM SIGNAL
ACTUATE AUDIBLE COMMON TROUBLE SIGNAL
ACTUATE ASSOCIATED FLOOR ALARM INDICATOR
CONTROL UNIT ANNUNCIATION
GENERATOR STATUS RUNNING
RECORD INFORMATION ON CPU
DISPLAY DEVICE ADDRESS AT CONTROL U
NIT
ACTUATE DISTINCT VISIBLE ELEVATOR RECALL
ALARM
MANUAL FIRE ALARM BOX
AREA SMOKE OR HEAT DETECTOR
ACTUATE LO
CAL V
ISUAL A
ND TEMPORAL 4
AUDIBLE SIGNAL
TRANSMIT FIRE ALARM SIGNAL T
O SUPERVISING STATION
TRANSMIT SUPERVISORY SIGNAL T
O SUPERVISING STATION
TRANSMIT TROUBLE SIGNAL T
O SUPERVISING STATION
NOTIFICATION
ACTUATE EXTERIOR AUDIBLE/VISUAL S
IGNAL
ACTUATE AUDIBLE AND VISUAL E
VACUATION SIGNALS
CARBON MONOXIDE DETECTOR
SPRINKLER WATER FLOW SWITCH
SPRINKLER OR STANDPIPE VALVE TAMPER
A B C D E F G H I K L M N O P Q R V W X Y Z AAS T U BBJ CC DD
ROOM TEMPERATURE SENSORS AT OR
BELOW 40 DEGREES F
FA-201
FIRE ALARM MATRIX
NTS
FA-201
ELEVATOR FIRE ALARM MATRIX
NTS
BVT
NOT FOR BID
DIN
G
OR C