drawing - MECHANICAL_QAC Historic Courthouse RFQ_2026.07.01.pdf
PDF 3 MB Posted
- Attached to
- Historic Courthouse Renovation
- Solicitation number
- BPM057809
- Issued by
- Queen Anne's County, Maryland
About this file
This is a mechanical drawing cover sheet and technical specifications document for the Historic Courthouse Renovation project in Centreville, Maryland, prepared by Torchio Architects for Queen Anne's County. The document establishes comprehensive mechanical installation requirements and standards for the complete HVAC system renovation of the 17,800-square-foot dormant courthouse building. The project includes demolition of 1960s-era HVAC and electrical systems, with new mechanical systems comprising multiple variable refrigerant flow (VRF) units, both ducted and ductless mini-split units, energy recovery ventilators, and an integrated control system. The drawing set includes detailed mechanical notes, abbreviations, legends, and symbols to guide contractor installation, coordination with other trades, and compliance with applicable building codes.
The specifications detail extensive technical requirements for refrigerant piping installation compliant with ASHRAE 15-2022, including pipe protection standards, prohibited installation locations, brazing and soldering specifications, hanger and support requirements, and refrigerant equipment installation protocols. Testing and inspection requirements mandate engagement of a qualified testing agency to perform strength tests using inert gases and leakage tests with specific vacuum and pressure parameters before system operation. All refrigeration systems containing 55 pounds or more of refrigerant require a certificate of test issued by the installing contractor and signed verification documenting test dates, pressures, refrigerant designation, and test medium. The document emphasizes contractor responsibility for coordinating all mechanical work with plumbing, electrical, and other trades; determining exact existing utility locations; and obtaining approval from the Contracting Officer Representative before proceeding with work when site conditions prevent execution as indicated on drawings.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
COORDINATE ALL MECHANICAL WORK WITH PLUMBING WORK, ELECTRICAL WORK, AND WORK OF OTHER TRADES SHOWN ON OTHER DRAWINGS.
THE LOCATION OF EXISTING UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. REPAIR ALL DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UTILITIES.
RUN ALL DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED.
ELEVATIONS NOTED ARE TO CENTERLINES OF PIPES FOR ALL PRESSURE LINES AND TO INVERT FOR ALL GRAVITY FLOW LINES.
INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE.
UNLESS OTHERWISE NOTED, ROUTE ALL PIPING AND DUCTWORK OVERHEAD, TIGHT TO UNDERSIDE OF SLAB, WITH SPACE FOR INSULATION IF REQUIRED.
MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL
AND ELECTRICAL ROOMS.
CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN DUCTWORK AND PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS. CONTRACTOR SHALL ENSURE MANUFACTURER'S INSTALLATION
REQUIREMENTS INCLUDING BUT NOT LIMITED TO REQUIRED MAINTENANCE CLEARANCE.
WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES REQUIRES CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., CHECK FOR THE PRESENCE OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION. EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO PERSONNEL DUE TO CONTACT WITH SAME. TEMPORARILY DISCONNECT SERVICES DURING THE CUTTING OPERATION. SCHEDULE SERVICE OUTAGES IN ADVANCE WITH THE OWNER.
FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT. VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. PROVIDE ADDITIONAL VALVES, PRESSURE GAUGES, ETC. AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS AND DETAILS FOR PIPE SIZES NOT INDICATED ON FLOW SCHEDULES AND RISER DIAGRAMS.
CONTRACTOR SHALL BE RESPONSIBLE FOR RESEARCHING ALL SYSTEMS THAT A PARTICULAR OUTAGE WILL AFFECT AS WELL AS LOCATING ALL SHUTOFF POINTS.
INCLUDE THIS INFORMATION IN THE OUTAGE PLAN AND SUBMIT TO THE OWNER FOR APPROVAL.
EXCEPT AS OTHERWISE NOTED, LOCATE ALL ROOM TEMPERATURE SENSORS ABOVE FINISHED FLOOR ON SAME HORIZONTAL CENTERLINE AS LIGHT SWITCH.
WHERE LIGHT SWITCH AND TEMPERATURE SENSOR ARE ADJACENT TO EACH OTHER, LIGHT SWITCH SHALL BE CLOSEST TO THE DOOR. COORDINATE WITH ELECTRICAL CONTRACTOR. NOTIFY THE ENGINEER OF ROOMS WHERE THE ABOVE LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON
LOCATION.
INSTALL CEILING MOUNTED DIFFUSERS, REGISTERS, AND GRILLE IN ACCORDANCE WITH CEILING GRID.
INFORMATION SHOWN ON THE MECHANICAL DRAWINGS PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMOLITION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING AND AWAIT WRITTEN DIRECTION
BEFORE PROCEEDING WITH THE WORK.
REMOVE ALL EXISTING PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE COR, OR ARE INDICATED TO REMAIN THE PROPERTY OF OWNER SHALL BE DELIVERED BY THE CONTRACTOR WHERE DIRECTED BY THE OWNER. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES.
DISCONNECT EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR OTHERWISE) AND REMOVE PIPING BACK TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR NOTED ON PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. CAP, PLUG, OR SEAL EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE. NO EXISTING PIPING SHALL BE LEFT UNSEALED VALVE ALL TERMINATED PRESSURE PIPE.
EXISTING MECHANICAL PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS. ALL WORK SHALL BE COMPLETED TO THE
SATISFACTION OF THE COR AND AT NO ADDITIONAL CONTRACT COST.
REMOVE ALL ACCESSORIES, CONTROLS, ENCLOSURES, SUPPORTS, HANGERS, PADS, ETC. ASSOCIATED WITH ALL EQUIPMENT SHOWN TO BE REMOVED. REPAIR AND PAINT DAMAGED SURFACES AND ALL SURFACES BEHIND ALL EQUIPMENT SHOWN TO BE DEMOLISHED TO MATCH EXISTING ADJACENT SURFACES.
PRIOR TO SUBMITTING SHOP DRAWINGS TO ENGINEER FOR EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS, COORDINATE ELECTRICAL REQUIREMENTS BETWEEN CONTRACTORS OF ALL TRADES ASSOCIATED WITH THE INSTALLATION. THE GENERAL CONTRACTOR'S STAMP ON THE SUBMITTAL MUST STATE THAT COORDINATION BETWEEN ALL TRADES HAS BEEN VERIFIED AND THAT THE SUBMITTAL HAS BEEN APPROVED FOR ENGINEER'S REVIEW. IF CONTRACTOR SUBMITS EQUIPMENT WITH POWER REQUIREMENTS THAT ARE DIFFERENT FROM POWER CONNECTION INDICATED ON THE CONTRACT DOCUMENTS, CONTRACTOR MUST PROVIDE A REASON FOR THE CHANGE AND WRITTEN CONFIRMATION THAT THE CHANGE HAS BEEN FULLY COORDINATED WITH ALL ASSOCIATED TRADES. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO ELECTRICAL CONNECTION, COORDINATE AND MAKE REQUIRED CHANGES TO PROVIDE A COMPLETE INSTALLATION IN ACCORDANCE WITH APPLICABLE CODES. CHANGE ORDERS AND EXTRAS WILL NOT BE AWARDED DUE TO CONTRACTOR'S FAILURE TO COORDINATE WITH ALL ASSOCIATED TRADES. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO COORDINATE EQUIPMENT SUBMITTALS AMONG THE SUBCONTRACTORS, NOT THE ENGINEER'S.
GENERAL MECHANICAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
A AMPS / COMPRESSED AIR
ACCU AIR COOLED CONDENSER
ACV AUTOMATIC CONTROL VALVE
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
APPROX APPROXIMATE
ARCH ARCHITECTURAL
B BOTTOM
BAS BUILDING AUTOMATION SYSTEM
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CAP CAPACITY
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CIRC CIRCULATING
CL CENTERLINE
CLG CEILING / COOLING
COMP COMPRESSOR
COND CONDENSATE / CONDENSER / CONDENSING
CW COLD WATER
CX CONNECT TO EXISTING
D DAMPER / DIAMETER / DIFFUSER / DRAIN / DROP
DB DRY BULB
DEG DEGREES
DET DETAIL
DIA DIAMETER
DIFF DIFFUSER
DN DOWN
DP DIFFERENTIAL PRESSURE
DWGS DRAWINGS
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EL ELEVATION
ELEC ELECTRIC / ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETR EXISTING TO REMAIN
EVAP EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EX EXISTING
EXH EXHAUST
F FAHRENHEIT / FAN
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT
FD FIRE DAMPER / FLOOR DRAIN
FLA FULL LOAD AMPS
FLR FLOOR
FPD FLUID PRESSURE DROP
FPM FEET PER MINUTE
FT FEET / FOOT
G GAS / GRILLE
GPM GALLONS PER MINUTE
H HEIGHT
HC HEATING COIL
HP HORSEPOWER
HTG HEATING
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HZ HERTZ
IN INCH / INCHES
MECHANICAL ABBREVIATIONS
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
KW KILOWATTS
L LENGTH
LAT LEAVING AIR TEMPERATURE
LFT LEAVING FLUID TEMPERATURE
LLS LIQUID LEVEL SENSOR
LSD LINEAR SLOT DIFFUSER
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSANDS BTU PER HOUR
MECH MECHANICAL
MER MECHANICAL EQUIPMENT ROOM
MIN MINIMUM
MOD MOTOR OPERATED DAMPER
N NORTH
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN / NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTDOOR AIR
OC ON CENTER
OED OPEN END DUCT
PD PRESSURE DROP / PUMP DISCHARGE
PHC PREHEAT COIL
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI PRESSURE - POUNDS PER SQUARE INCH
PSIG PRESSURE - POUNDS PER SQUARE INCH GAGE
R RADIUS / REGISTER / RISE / RISER
RA RETURN AIR
RAD RADIUS
RD ROUND
REFRIG REFRIGERANT
REG REGISTER
RET RETURN
REV REVISION
RH REHEAT / RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID
RM ROOM / REFRIGERANT MONITOR
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RV RELIEF VALVE
RX REMOVE EXISTING
S SWITCH
SA SUPPLY AIR
SAF SUPPLY AIR FAN
SD SMOKE DAMPER / SMOKE DETECTORS
SEER SEASONAL ENERGY EFFICIENCY RATIO
SENS SENSIBLE COOLING
SP STATIC PRESSURE
SPEC SPECIFICATION
T TEMPERATURE SENSOR / THERMOSTAT
TEMP TEMPERATURE / TEMPORARY
THRU THROUGH
TOT TOTAL
TYP TYPICAL
UH UNIT HEATER
UON UNLESS OTHERWISE NOTED
V VALVE / VENT / VOLTS
VD VOLUME DAMPER
W WATT / WIDTH
W/ WITH
W/O WITHOUT
WB WET BULB
WPD WATER PRESSURE DROP
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY / CURRENT SENSOR
HRU HEAT RECOVERY UNIT
STM STEAM
VRF VARIABLE REFRIGERANT FLOW
BS BRANCH SELECTOR BOX
BDD BACKDRAFT DAMPER
ACU AIR CONDITIONING UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP / CONTROL PANEL
ERV ENERGY RECOVERY VENTILATOR
ES END SWITCH
QTY QUANTITY
LBS POUNDS
M MECHANICAL
MCA MINIMUM CIRCUIT AMPACITY
MOCP MAXIMUM OVERCURRENT PROTECTION
PH PHASE
TSP TOTAL STATIC PRESSURE
WG WATER GAUGE
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
MD MECHANICAL DEMOLITION
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
MAV
M
EC
HA
NI
CA
L C
O
VE
R
SH
EE
T
DESCRIPTIONSYMBOL
DIFFUSER TAG:
TOP - NECK SIZE, SPECIFICATION TYPE
BOTTOM - AIRFLOW IN CFM
FLEXIBLE CONNECTION
VOLUME DAMPER
FIRE DAMPER
DUCT MOUNTED SMOKE DETECTOR
THERMOSTAT/TEMPERATURE SENSORT
RETURN AIR DUCT
OUTDOOR AIR OR SUPPLY AIR DUCT
EXHAUST AIR DUCT
SHUTOFF VALVE
UNION
THERMOMETER
CAP (PIPE OR DUCT)
PLAN/ SECTION DESIGNATION
TOP - PLAN/ SECTION REFERENCE
BOTTOM - REFERENCED DRAWING
A M-1
END POINT OF REMOVAL OF EXISTING
CONNECT TO EXISTING
HOT WATER HEATING SUPPLYHS
HOT WATER HEATING RETURNHR
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
MECHANICAL LEGEND
CR CONDENSER RETURN
CS CONDENSER SUPPLY
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
X#
X#
X# STEAM SUPPLY
X# STEAM RETURN
LPS LOW PRESSURE STEAM
M001
8"ø D-1, 250 CFM
COMBINATION FIRE AND SMOKE DAMPER
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
REFRIGERANT PIPING INSTALLATION REQUIREMENTS
1. CODE COMPLIANCE: ASHRAE 15-2022.
2. SHAFT ENCLOSURES: MECHANICALLY VENTILATED SHAFTS IN ACCORDANCE WITH ASHRAE 15-2022.
3. INSTALL PER MANUFACTURER'S REQUIREMENTS. EQUIPMENT MANUFACTURERS SHALL SIZE ALL PIPING.
4. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF SYSTEMS; INDICATED LOCATIONS AND. INSTALL PIPING AS INDICATED
UNLESS DEVIATIONS TO LAYOUT ARE APPROVED ON SHOP DRAWINGS.
5. INSTALL REFRIGERANT PIPING IN ACCORDANCE WITH ASHRAE 15-2022.
6. PIPE PROTECTION. THE EXTERIOR OF THE PIPE SHALL BE PROTECTED FROM CORROSION, DEGRADATION, GALVANIC CORROSION AND ABRASION. REFRIGERANT PIPE SHALL NOT BE IN CONTACT WITH BUILDING MATERIALS THAT CAN ABRADE THE PIPE. REFRIGERANT PIPE SHALL BE INSTALLED AS FOLLOWS IN ACCORDANCE WITH ASHRAE 15-2022:
A. PIPING INSTALLED IN A WALL OR FLOOR SPACE OR WITHIN A PROTECTIVE ENCLOSURE SHALL BE PROTECTED AS FOLLOWS:
1) IN CONCEALED LOCATIONS WHERE COPPER TUBE IS INSTALLED THROUGH HOLES OR NOTCHES IN STUDS, JOISTS OR SIMILAR MEMBER LESS THAN 1.5 INCHES FROM THE NEAREST EDGE OF THE MEMBER, THE TUBE SHALL BE PROTECTED BY STEEL SHIELD PLATES WITH A MINIMUM THICKNESS OF 0.0575 INCH.
2) PROTECTIVE STEEL SHIELD PLATES SHALL COVER THE AREA OF THE TUBE WHERE THE MEMBER IS NOTCHED OR BORED AND SHALL EXTEND NOT LESS THAN 2
INCHES ABOVE SOLE PLATES AND BELOW TOP PLATES.
B. PIPING EXPOSED INSIDE OF A BUILDING SHALL BE INSTALLED AT AN ELEVATION THAT IS MORE THAN 7 FEET 3 INCHES ABOVE THE FINISHED FLOOR OR WHEN THE PIPING IS WITHIN 6 FEET OF THE APPLIANCE TO WHICH IT CONNECTS. OTHERWISE INSTALL REFRIGERANT PIPING IN RIGID OR FLEXIBLE CONDUIT AND IN LOCATIONS WHERE EXPOSED
TO MECHANICAL INJURY.
C. PIPING IN AN ATTIC OR CRAWL SPACE, PROVIDED THAT COPPER TUBE IS INSTALLED 1.5 INCHES FROM THE NEAREST EDGE OF THE MEMBER, THE TUBE SHALL BE PROTECTED BY STEEL SHIELD PLATES HAVING A MINIMUM THICKNESS OF 0.0575 INCH (NO. 16 GAGE). PROTECTIVE STEEL PLATES ARE NOT REQUIRED IN LOCATIONS
WHERE THE REFRIGERANT PIPING IS EXPOSED.
D. PIPING OUTSIDE THE BUILDING SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:
1) PROTECTED FROM DAMAGE FROM THE WEATHER, INCLUDING BUT NOT LIMITED TO HAIL, ICE AND SNOW LOADS.
2) PROTECTED FROM DAMAGE WHERE LOCATED IN AN EXPECTED FOOT OR TRAFFIC PATH.
3) UNDERGROUND BELOW THE FROST LINE AND NOT LESS THAN 8 INCHES BELOW FINISH GRADE.
7. REFRIGERANT PIPING SHALL NOT BE INSTALLED IN ANY OF THE FOLLOWING LOCATIONS:
A. EXPOSED WITHIN A FIRE-RESISTANCE-RATED EXIT ACCESS CORRIDOR.
B. EXPOSED WITHIN AN INTERIOR EXIT STAIRWAY.
C. WITHIN AN INTERIOR EXIT RAMP ENCLOSURE.
D. WITHIN AN EXIT PASSAGEWAY.
E. WITHIN AN ELEVATOR, DUMBWAITER OR OTHER SHAFT CONTAINING A MOVING OBJECT.
F. INSIDE AN AIR DUCT OR AIR DUCT PLENUM.
8. REFRIGERANT PIPING INSTALLED IN CONCRETE FLOORS SHALL BE ENCASED IN PIPE, CONDUIT OR DUCTS. THE REFRIGERANT PIPING SHALL BE PROTECTED TO PREVENT
DAMAGE FROM VIBRATION, STRESS AND CORROSION.
9. INSTALL REFRIGERANT PIPING IN PROTECTIVE CONDUIT WERE INSTALLED BELOW GROUND. THE PIPING SHALL BE PROTECTED TO PREVENT DAMAGE FROM VIBRATION, STRESS AND CORROSION.
10. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED OTHERWISE. INSTALL PIPING AS SHORT AND DIRECT AS POSSIBLE, WITH A MINIMUM NUMBER OF JOINTS, ELBOWS, AND FITTINGS. REFRIGERANT PIPING SHALL BE INSTALLED SO AS TO PREVENT STRAINS AND STRESSES THAT EXCEED THE STRUCTURAL STRENGTH OF THE PIPE.
11. INSULATE ALL REFRIGERANT PIPING IN ACCORDANCE WITH SPECIFICATION SECTION 232300 “REFRIGERANT PIPING”.
12. INSTALL PIPING WITH ADEQUATE CLEARANCE BETWEEN PIPE AND ADJACENT WALLS AND HANGERS OR BETWEEN PIPES FOR INSULATION INSTALLATION.
13. INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR CEILING PANEL REMOVAL.
14. INSTALL PIPING ADJACENT TO EQUIPMENT TO ALLOW SERVICE AND MAINTENANCE.
15. INSTALL PIPING FREE OF SAGS AND BENDS.
16. INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH CONNECTIONS.
17. SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER THAN SYSTEM OPERATING PRESSURE.
18. ARRANGE PIPING TO ALLOW INSPECTION AND SERVICE OF REFRIGERATION EQUIPMENT. INSTALL VALVES AND SPECIALTIES IN ACCESSIBLE LOCATIONS TO ALLOW FOR SERVICE AND INSPECTION. INSTALL ACCESS DOORS OR PANELS AS SPECIFIED IN SECTION 083113 "ACCESS DOORS AND FRAMES" IF VALVES OR EQUIPMENT REQUIRING
MAINTENANCE IS CONCEALED BEHIND FINISHED SURFACES.
19. SLOPE REFRIGERANT PIPING IN ACCORDANCE WITH EQUIPMENT MANUFACTURER REQUIREMENTS.
20. WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS AND SIGHT GLASSES; ALSO REMOVE VALVE STEMS, SEATS, PACKING, AND ACCESSIBLE INTERNAL PARTS
OF REFRIGERANT SPECIALTIES. DO NOT APPLY HEAT NEAR EXPANSION-VALVE BULB.
21. IDENTIFY REFRIGERANT PIPING AND VALVES IN ACCORDANCE WITH SECTION 230553 "IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT." FOR GROUP A2L REFRIGERANTS, THE IDENTIFICATION SHALL ALSO INCLUDE THE FOLLOWING STATEMENT: “WARNING-RISK OF FIRE. FLAMMABLE REFRIGERANT.”
22. INSTALL SLEEVES FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS. COMPLY WITH REQUIREMENTS FOR SLEEVES SPECIFIED IN SECTION 230500 "COMMON
WORK RESULTS FOR HVAC."
23. INSTALL SLEEVE SEALS FOR PIPING PENETRATIONS OF CONCRETE WALLS AND SLABS. COMPLY WITH REQUIREMENTS FOR SLEEVE SEALS SPECIFIED IN SECTION 230500
"COMMON WORK RESULTS FOR HVAC."
24. INSTALL ESCUTCHEONS FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS. COMPLY WITH REQUIREMENTS FOR ESCUTCHEONS SPECIFIED IN SECTION 230500
"COMMON WORK RESULTS FOR HVAC."
25. PIPE JOINT CONSTRUCTION
A. REAM ENDS OF PIPES AND TUBES AND REMOVE BURRS.
B. REMOVE SCALE, SLAG, DIRT, AND DEBRIS FROM INSIDE AND OUTSIDE OF PIPE AND FITTINGS BEFORE ASSEMBLY.
C. SOLDERED JOINTS: CONSTRUCT JOINTS IN ACCORDANCE WITH ASTM B828 OR CDA'S "COPPER TUBE HANDBOOK."
D. BRAZED JOINTS: CONSTRUCT JOINTS IN ACCORDANCE WITH AWS BRH, "BRAZING HANDBOOK," CH. 35, "PIPE AND TUBING."
1) USE TYPE BCUP (COPPER-PHOSPHORUS) ALLOY FOR JOINING COPPER SOCKET FITTINGS WITH COPPER PIPE.
2) USE TYPE BAG (CADMIUM-FREE SILVER) ALLOY FOR JOINING COPPER WITH BRONZE OR STEEL.
27. INSTALLATION OF HANGERS AND SUPPORTS
A. COMPLY WITH SECTION 230529 "HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT" FOR HANGERS, SUPPORTS, AND ANCHOR DEVICES.
B. INSTALL THE FOLLOWING PIPE ATTACHMENTS:
1) ADJUSTABLE STEEL CLEVIS HANGERS FOR INDIVIDUAL HORIZONTAL RUNS LESS THAN 20 FT. (6 M) LONG.
2) ROLLER HANGERS AND SPRING HANGERS FOR INDIVIDUAL HORIZONTAL RUNS 20 FT. (6 M) OR LONGER.
3) PIPE ROLLER: MSS SP-58, TYPE 44 FOR MULTIPLE HORIZONTAL PIPING 20 FT. (6 M) OR LONGER, SUPPORTED ON A TRAPEZE.
4) SPRING HANGERS TO SUPPORT VERTICAL RUNS.
5) COPPER-CLAD HANGERS AND SUPPORTS FOR HANGERS AND SUPPORTS IN DIRECT CONTACT WITH COPPER PIPE.
D. INSTALL HANGERS FOR COPPER TUBING, WITH MAXIMUM HORIZONTAL SPACING AND MINIMUM ROD DIAMETERS, TO COMPLY WITH MSS SP-58, LOCALLY ENFORCED CODES, AND AUTHORITIES HAVING JURISDICTION REQUIREMENTS, WHICHEVER ARE MOST STRINGENT.
E. SUPPORT HORIZONTAL PIPING WITHIN 12 INCHES OF EACH FITTING.
F. SUPPORT VERTICAL RUNS OF COPPER TUBING TO COMPLY WITH MSS SP-58, LOCALLY ENFORCED CODES, AND AUTHORITIES HAVING JURISDICTION REQUIREMENTS, WHICHEVER ARE MOST STRINGENT.
REFRIGERANT EQUIPMENT INSTALLATION REQUIREMENTS
1. CODE COMPLIANCE: ASHRAE 15-2022.
2. REFRIGERATION SYSTEMS SHALL BE LISTED IN ACCORDANCE WITH UL 484 OR UL 60335-2-40/CSA C22.2 NO. 60335-2-40.
3. THE REFRIGERATION SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH ASHRAE 15-2022, THE LISTING, THE MANUFACTURER'S INSTRUCTIONS AND ANY MARKINGS ON THE EQUIPMENT
RESTRICTING THE INSTALLATION.
A. THE ASHRAE 15-2022 REQUIRED NAME PLATE, SHALL INCLUDE A SYMBOL INDICATING THAT A FLAMMABLE REFRIGERANT IS USED.
B. A LABEL INDICATING A FLAMMABLE REFRIGERANT IS INSTALLED, SHALL BE PLACED ADJACENT TO SERVICE PORTS AND OTHER LOCATIONS WHERE SERVICE INVOLVING COMPONENTS
CONTAINING REFRIGERANT IS PERFORMED.
4. EQUIPMENT SHALL HAVE A FACTORY INSTALLED REFRIGERANT DETECTION SYSTEM IN ACCORDANCE WITH ASHRAE 15-2022.
5. EQUIPMENT PRESSURE RELIEF DEVICES
A. DIFFERENT REFRIGERANTS SHALL NOT BE VENTED INTO A COMMON RELIEF PIPING SYSTEM.
B. PRESSURE RELIEF DEVICES DESIGNED TO DISCHARGE EXTERNAL TO THE REFRIGERATION SYSTEM SHALL BE ARRANGED TO DISCHARGE OUTSIDE OF THE BUILDING AND COMPLY WITH
ALL OF THE FOLLOWING:
1) THE POINT OF VENT DISCHARGE SHALL BE LOCATED NOT LESS THAN 15 FEET ABOVE THE ADJOINING GROUND LEVEL.
2) THE POINT OF VENT DISCHARGE SHALL BE LOCATED NOT LESS THAN 20 FEET FROM WINDOWS, BUILDING VENTILATION OPENINGS, PEDESTRIAN WALKWAYS ABOVE OR BELOW GRADE, PITS, RAMPS OR BUILDING EXITS. THE RELIEF VENT SHALL NOT DISCHARGE INTO AN ENCLOSED OUTDOOR SPACE SUCH AS A COURTYARD.
3) THE TERMINATION POINT OF A VENT DISCHARGE LINE SHALL BE MADE IN A MANNER THAT PREVENTS FOREIGN MATERIAL OR DEBRIS.
6. INSTALL VALVE AND SPECIALTY APPLICATIONS AS REQUIRED BY EQUIPMENT LISTING AND, MANUFACTURERS REQUIREMENTS AS FOLLOWS:
A. STOP VALVES SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS:
1) REFRIGERATION SYSTEM CONTAINING MORE THAN 6.6 POUNDS OF REFRIGERANT.
· THE SUCTION INLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.
· THE DISCHARGE OUTLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.
· THE OUTLET OF EACH LIQUID RECEIVER.
2) REFRIGERATION SYSTEMS CONTAINING MORE THAN 100 POUNDS OF REFRIGERANT.
· THE SUCTION INLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.
· THE DISCHARGE OUTLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.
· THE OUTLET OF EACH LIQUID RECEIVER.
· EACH INLET OF EACH LIQUID RECEIVER.
· EACH INLET AND EACH OUTLET OF EACH CONDENSER WHERE MORE THAN ON CONDENSER IS USED IN PARALLEL.
B. STOP VALVES SHALL BE SUPPORTED TO PREVENT STRESS AND STRAIN ON THE REFRIGERANT PIPING SYSTEM. THE PIPING SYSTEM SHALL NOT BE UTILIZED TO SUPPORT STOP VALVES
ON COPPER TUBING 1-INCH OUTSIDE DIAMETER OR LARGER.
C. STOP VALVES SHALL BE IDENTIFIED WHERE THEIR INTENDED PURPOSE IS NOT OBVIOUS. WHERE VALVES ARE IDENTIFIED BY A NUMBERING OR LETTERING SYSTEM, LEGEND(S) OR KEY(S) FOR THE VALVE IDENTIFICATION SHALL BE LOCATED IN THE ROOM CONTAINING THE INDOOR REFRIGERATION EQUIPMENT. THE MINIMUM HEIGHT OF LETTERING OF THE IDENTIFICATION
SHALL BE ½-INCH.
7. LIQUID-LEVEL-GAGE GLASS COLUMNS SHALL HAVE AUTOMATIC CLOSING SHUTOFF VALVES. ALL SUCH GLASS COLUMNS SHALL BE PROTECTED AGAINST EXTERNAL DAMAGE AND PROPERLY
SUPPORTED.
A. EXCEPTION: LIQUID-LEVEL-GAGE GLASSES OF THE BULL'S-EYE TYPE.
8. WHEN A PRESSURE GAGE IS PERMANENTLY INSTALLED ON THE HIGH SIDE OF A REFRIGERATING SYSTEM, ITS DIAL SHALL BE GRADUATED TO AT LEAST 1.2 TIMES THE DESIGN PRESSURE.
9. LIQUID RECEIVERS, OR PARTS OF A SYSTEM DESIGNED TO RECEIVE THE REFRIGERANT CHARGE DURING PUMP DOWN SHALL HAVE SUFFICIENT CAPACITY TO RECEIVE THE PUMP DOWN CHARGE. THE LIQUID SHALL NOT OCCUPY MORE THAN 90 PERCENT OF THE VOLUME WHEN TEMPERATURE OF THE REFRIGERANT IS 90 DEG F.
10. SERVICE PROVISIONS
A. ALL SERVICEABLE COMPONENTS OF REFRIGERATING SYSTEMS SHALL BE PROVIDED WITH SAFE ACCESS.
B. CONDENSING UNITS OR COMPRESSOR UNITS WITH ENCLOSURES SHALL BE PROVIDED WITH SAFE ACCESS WITHOUT THE NEED TO CLIMB OVER OR REMOVE ANY OBSTACLES OR TO USE
PORTABLE ACCESS DEVICES TO GET TO THE EQUIPMENT.
C. ALL SYSTEMS SHALL HAVE PROVISIONS TO HANDLE THE REFRIGERANT CHARGE FOR SERVICE PURPOSES. WHEN REQUIRED, THERE SHALL BE LIQUID AND VAPOR TRANSFER VALVES, A TRANSFER COMPRESSOR OR PUMP AND REFRIGERANT STORAGE TANKS OR APPROPRIATE VALVED CONNECTIONS FOR REMOVAL BY A RECLAIM, RECYCLE OR RECOVERY DEVICE.
11. SYSTEM CHARGING IN ACCORDANCE WITH ASHRAE 15-2022.
12. SYSTEM ADJUSTING IN ACCORDANCE WITH ASHRAE 15-2022.
REFRIGERANT DUCTWORK INSTALLATION REQUIREMENTS
1. CODE COMPLIANCE: ASHRAE 15-2022.
2. UNCLASSIFIED ELECTRICAL DEVICES SHALL NOT BE LOCATED WITHIN DUCTWORK.
3. DEVICES CONTAINING HOT SURFACES EXCEEDING 1290 DEGREES F SHALL NOT BE LOCATED IN DUCTWORK UNLESS THERE IS AN AVERAGE AIRFLOW VELOCITY NOT LESS THAN 200 FEET/MIN ACROSS THE HEATING DEVICE(S) AND THERE IS PROOF OF AIRFLOW BEFORE THE HEATING DEVICE(S) IS ENERGIZED. AVERAGE AIRFLOW VELOCITY SHALL BE DETERMINED BY
VOLUMETRIC AIRFLOW RATE DIVIDED BY DUCT FLOW RATE.
4. DUCT HEATERS SHALL BE SHUT DOWN BY A REFRIGERANT DETECTION SYSTEM. CONTRACTOR SHALL PROVIDE A REFRIGERANT DETECTION SYSTEM TO SHUTDOWN DUCT MOUNTED
HEATERS WHEN A REFRIGERANT LEAK IS SENSED.
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
RE
FR
IG
ER
AN
T N
O
TE
S
M002
NOT FOR BID
DIN
G
OR C
REFRIGERANT PIPING TEST AND INSPECTIONS
1. CODE COMPLIANCE: PIPING SHALL BE TESTED IN ACCORDANCE WITH ASHRAE 15-2022.
2. TESTING AGENCY: ENGAGE A QUALIFIED TESTING AGENCY TO PERFORM TESTS AND INSPECTIONS.
3. TESTS AND INSPECTIONS:
A. GENERAL. REFRIGERATING SYSTEMS FABRICATED, ASSEMBLED, OR ERECTED ON THE PREMISES SHALL BE TESTED TO THE APPLICABLE REQUIREMENTS OF THIS SECTION. TESTS SHALL INCLUDE BOTH THE HIGH SIDES AND LOW SIDES OF EACH SYSTEM. SYSTEM COMPONENTS THAT HAVE BEEN STRENGTH TESTED UNDER PRESSURE BY THE COMPONENT MANUFACTURER, FABRICATOR, OR ASSEMBLER ARE NOT REQUIRED TO BE STRENGTH TESTED AGAIN ON THE PREMISES UNLESS MODIFIED OR REPAIRED. LISTED EQUIPMENT NOT MODIFIED OR REPAIRED SHALL NOT BE REQUIRED TO BE STRENGTH TESTED ON THE PREMISES. AFTER INSTALLATION AND BEFORE BEING PLACED IN OPERATION, SYSTEM COMPONENTS NOT PREVIOUSLY STRENGTH TESTED SHALL BE STRENGTH TESTED UNDER PRESSURE IN ACCORDANCE WITH PIPING SYSTEM STRENGTH TEST BELOW. AFTER SUCCESSFUL COMPLETION OF THE REQUIRED STRENGTH TESTS AND BEFORE BEING PLACED IN OPERATION, SYSTEM COMPONENTS AND FIELD INSTALLED CONNECTIONS SHALL BE LEAK TESTED FOR TIGHTNESS IN ACCORDANCE WITH
LEAKAGE TEST BELOW.
B. REFRIGERANT PIPE AND JOINTS INSTALLED IN THE FIELD SHALL BE EXPOSED FOR VISUAL INSPECTION AND TESTING PRIOR TO BEING COVERED OR ENCLOSED.
C. TEST GASES. THE MEDIUM USED FOR FIELD PRESSURE TESTING THE REFRIGERANT SYSTEM SHALL BE ONE OF THE FOLLOWING INERT GASES: OXYGEN-FREE NITROGEN, HELIUM, ARGON OR PREMIXED NONFLAMMABLE OXYGEN-FREE NITROGEN WITH A TRACER GAS OF HYDROGEN OR HELIUM.
1) TEST GASES NOT PERMITTED. OXYGEN, AIR, REFRIGERANTS OTHER THAN THOSE IDENTIFIED ABOVE, COMBUSTIBLE GASES AND MIXTURES CONTAINING SUCH GASES SHALL NOT BE
USED AS THE TEST MEDIUM.
D. FIELD TEST APPARATUS. THE MEANS USED TO PRESSURIZE THE REFRIGERANT PIPING SYSTEM SHALL HAVE EITHER A PRESSURE-LIMITING DEVICE OR A PRESSURE-REDUCING DEVICE AND A TEST PRESSURE MEASURING DEVICE ON THE OUTLET SIDE. THE TESTS PRESSURE MEASURING DEVICE SHALL HAVE AN ACCURACY OF +/-3 PERCENT OR LESS OF THE TEST
PRESSURE AND SHALL HAVE A RESOLUTION OF 3 PERCENT OR LESS OF THE TEST PRESSURE.
E. PIPING SYSTEM STRENGTH TEST. REFRIGERATING SYSTEM COMPONENTS AND REFRIGERANT PIPING SHALL BE TESTED IN ACCORDANCE WITH ASME B31.5 OR THIS SECTION. SEPARATE TESTS FOR ISOLATED PORTIONS OF THE SYSTEM ARE PERMITTED, PROVIDED THAT ALL REQUIRED PORTIONS ARE TESTED AT LEAST ONCE. PRESSURIZE WITH TEST GAS FOR A MINIMUM OF 10 MINUTES TO NOT LESS THAN THE LOWER OF (A) THE LOWEST DESIGN PRESSURE FOR ANY SYSTEM COMPONENT OR (B) THE LOWEST VALUE OF SET PRESSURE FOR ANY PRESSURE RELIEF DEVICES IN THE SYSTEM. THE DESIGN PRESSURES FOR DETERMINATION OF TEST PRESSURE SHALL BE THE PRESSURE IDENTIFIED ON THE LABEL NAMEPLATE OF THE CONDENSING UNIT, COMPRESSOR, COMPRESSOR UNIT, PRESSURE VESSEL OR OTHER SYSTEM COMPONENT WITH A NAMEPLATE. A PASSING TEST RESULT SHALL HAVE NO RUPTURE OR STRUCTURAL FAILURE OF ANY SYSTEM COMPONENT OR REFRIGERANT PIPING. PRESSURE RELIEF DEVICES MAY NEED TO BE TEMPORARILY REMOVED AND REPLACED WITH PLUGS
DURING THE STRENGTH TEST.
F. LEAKAGE TEST. THE LEAK TEST SHALL BE IN ACCORDANCE WITH ASHRAE STANDARD 147, ASME B31.5, OR THIS SECTION.
1) LEAK TESTING PROTOCOL. AFTER THE TIME TO COMPLETE THE STRENGTH TEST, CONTINUE TO PRESSURE TEST IN ACCORDANCE WITH PIPING SYSTEM STRENGTH TEST ABOVE FOR A MINIMUM PERIOD AS SPECIFIED IN THE FOLLOWING TABLE, DURATION OF LEAK TEST. THE SYSTEM SHALL SHOW NO LOSS IN PRESSURE ON THE PRESSURE MEASURING DEVICE DURING THE PRESSURE TEST. CALCULATION OF THE PRESSURE DIFFERENTIAL BASED ON A CHANGE IN AMBIENT TEMPERATURE SHALL BE PERMITTED. A VACUUM OF 0.0097 PSI ABSOLUTE OR LOWER SHALL BE ACHIEVED. AFTER ACHIEVING A VACUUM, THE SYSTEM SHALL BE ISOLATED FROM THE VACUUM PUMP. THE SYSTEM PRESSURE SHALL NOT RISE ABOVE 0.029 PSI ABSOLUTE FOR A MINIMUM PERIOD AS SPECIFIED IN THE FOLLOWING TABLE, DURATION OF LEAK TEST. THE VACUUM PUMP SHOULD GRADUALLY CREATE A
VACUUM TO AVOID FREEZING OF ANY MOISTURE IN THE PIPING SYSTEM.
DURATION OF LEAK TEST
NOTE: THE MAXIMUM PIPE SIZE IS THE LARGEST INTERCONNECTING FIELD PIPING INSTALLED.
G. CONTRACTOR DECLARATION. THE INSTALLING CONTRACTOR SHALL ISSUE A CERTIFICATE OF TEST, VERIFYING STRENGTH TEST IN ACCORDANCE WITH PIPING SYSTEM STRENGTH TEST, AND LEAKAGE TEST IN ACCORDANCE WITH LEAKAGE TEST, TO THE AHJ FOR ALL SYSTEMS CONTAINING 55 LB OR MORE OF REFRIGERANT. THE CERTIFICATE SHALL GIVE THE TEST DATE, PHOTOGRAPH OF THE PRESSURE GAGE AT THE TEST PRESSURE, REFRIGERANT DESIGNATION, TEST MEDIUM, AND THE FIELD TEST PRESSURE APPLIED TO THE HIGH SIDE AND THE LOW SIDE OF THE SYSTEM. THE CERTIFICATION OF TEST SHALL BE SIGNED BY THE INSTALLING CONTRACTOR AND SHALL BE MADE PART OF THE PUBLIC RECORD.
LEAK TEST
PRESSURE
TEST
VACUUM
TEST
PIPE LENGTH,
L (FEET)
MAXIMUM PIPE
SIZE (INCH)
MINIMUM PERIOD
OF TEST (HOURS)
L <= 100 3
4 OR LESS 0.25
1 TO 3 1
GREATER THAN 3 24
3 OR LESS 1
GREATER THAN 3 24
ANY 24
100 < L <= 200
200 < L
L <= 100 3
4 OR LESS 1
1 TO 3 8
GREATER THAN 3 24
3 OR LESS 8
GREATER THAN 3 24
ANY 24
100 < L <= 200
200 < L
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
RE
FR
IG
ER
AN
T N
O
TE
S
M003
NOT FOR BID
DIN
G
OR C
D
W V
W V
W V
W V
EX. 6" W
M
WV
D
W V
W V
WV
W V
EEREER
W
58.5
59.5
S
S
S
S
C/OC/O
C/O
C/O
S
IRR M
WM
WM
WM
WMWMWM
MD002
RX RS/L BELOW
GRADE WITHIN
CARRIER PIPE,
TYP OF 2 SETS
RX CARRIER PIPE
BELOW GRADE
RX RS/L, TYP
OF 2 SETS.
RX 4" CS ABOVE /
RX 3" CS BELOW
RX 2-1/2" CR ABOVE /
RX 2" CR BELOW
RX VENT PIPE TO
BELOW GRADE
RX FOS/R DN
RX CR DN
RX CS DN
RX RS/L DN,
TYP OF 2 SETS
RX GENERATOR
RX FUEL OIL TANK
RX COOLING TOWER
EX ACCU
EX ACCU
RX CS DN
1 2
RX CARRIER PIPE
RX RS/L BELOW
GRADE WITHIN
CARRIER PIPE,
TYP OF 2 SETS
RX CARRIER PIPE
BELOW GRADE
RX 4" CS
RX 2-1/2" CR
RX 3" CS
RX 2" CR
RX PIPING BELOW GRADE
TO COOLING TOWER
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
MD002
MECHANICAL SITE PLAN - DEMOLITION
1" = 20'-0" N
SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION
RX ALL ASSOCIATED SUPPORTS, CONTROLS, WIRING, ETC.
SEE DRAWING MD301 FOR CONTINUATION.
TEMPORARILY REMOVE AND SALVAGE EXISTING ACCU TO ALLOW FOR
EQUIPMENT YARD SLAB REMOVAL. REINSTALL EXISTING ACCU AS SHOWN
ON DRAWING M002.
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
EXISTING TO REMAIN VRF SYSTEM AND SPLIT SYSTEM UTILIZE R-410A
REFRIGERANT.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
M
EC
HA
NI
CA
L S
ITE
P
LA
N
- D
EM
O
LIT
IO
N
MAV
0 10 40 80 FT20
1" = 20' - 0"
MD002
EQUIPMENT YARD - MECHANICAL - DEMOLITION PART PLAN
1/4" = 1'-0" N
0 2 8 12 FT4
1/4" = 1' - 0"
MD002
4.
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text T
COURTROOM
OFFICE 10
OFFICE 9
OFFICE 8
OFFICE 13
OFFICE 12
LOBBY
VAULTELEV.
T
T
OFFICE 11
T
T
T
RX DUCTWORK, TYP
RX
RX EA LOUVER
RX
RX EF
RX EA LOUVER
RX EF
RX
RX
RX LOUVER
RX
RX DUCTWORK, TYP
RX LOUVER
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
BASEMENT
OFFICE
OFFICE
OFFICE
OFFICE
OLD LAW LIBRARY
OFFICE
ELEV.
OFFICE
T
T
MECHANICAL
MECHANICAL
KITCHEN
CELL 1
CELL 2
LAV.
WOMEN
MEN
SECURITY/
SURVEILLANCE
OFFICE
OFFICE
OFFICE
BACK-UP 911 CENTER
IT
SAFE
EX FCU
EX FCU
EX FCU
EX FCU
1 1
1 1
EX FCU
EX
RX DUCTWORK, TYP
EX
RX DUCTWORK, TYP
MD300
COURTROOM
OFFICE
ELEV.
T
JURY
CONFERENCE
JUDGE'S
CHAMBER
T
T
RX 18x12 EA
LOUVER
RX
1 1
RX EF, TYP
1 1
RX
RX
RX DUCTWORK, TYP
RX DUCTWORK, TYP
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
MD100
GROUND LEVEL - DUCTWORK - DEMOLITION PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"N
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
DU
CT
W O
RK
D
EM
O
LIT
IO
N
PL
AN
MD100
LOWER LEVEL - DUCTWORK - DEMOLITION PLAN
1/8" = 1'-0" N
RX AIR DEVICE
RX 10x14 SA DN, RX 10x18 SA DN, RX 48x18 SA DN, RX 10x18 SA DN, RX 16x14 SA DN, RX 44x18 RA DN
RX 10x18 SA UP, RX 48x18 SA UP, RX 10x18 SA UP, RX 44x18 RA UP
RX 10x18 SA DN, RX 48x18 SA UP/DN, RX 10x18 SA DN, RX 44x18 RA DN
TEMPORARILY REMOVE AND SALVAGE EXISTING FCU TO ALLOW FOR NEW
CEILING INSTALLATION. REINSTALL EXISTING FCU AS SHOWN ON DRAWING
M100.
PATCH AND SEAL EXISTING WALL OPENING TO MAKE AIR AND WATER TIGHT.
SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
MD100
UPPER LEVEL - DUCTWORK - DEMOLITION PLAN
1/8" = 1'-0" N
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
1.
2.
3.
MAV
MD100
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
30 x x 68
RX DUCTWORK, TYP
RX 48x18 SA DN
25 5
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
MD101
ATTIC LEVEL - DUCTWORK - DEMOLITION PLAN
1/8" = 1'-0" 0 4 16 24 FT8
1/8" = 1' - 0"N
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
DU
CT
W O
RK
D
EM
O
LIT
IO
N
PL
AN
MD101
ROOF - DUCTWORK - DEMOLITION PLAN
1/8" = 1'-0" N
RX AIR DEVICE
RX ATTIC VENTILATION FAN
RX EXHAUST FAN
RX DUCT DN TO AIR DEVICE
PATCH AND SEAL EXISTING ROOF OPENING TO MAKE AIR AND WATER TIGHT.
SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
1.
2.
MAV
MD101
NOT FOR BID
DIN
G
OR C
COURTROOM
OFFICE 10
OFFICE 9
OFFICE 8
OFFICE 11
OFFICE 13
OFFICE 12
LOBBY
VAULTELEV. 1
RX ACCU
RX FCU
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
BASEMENT
MECHANICAL
MECHANICAL
KITCHEN
CELL 1
CELL 2
OFFICE
LAV.
SECURITY/SURVEILLANCE
OFFICE
OFFICE
OFFICE
OFFICE
OLD LAW LIBRARY
SAFE
IT
BACK-UP 911 CENTER
OFFICE
OFFICE OFFICE
OFFICE
WOMEN
MEN
ELEV.
OFFICE
EX FCU
EX FCU
EX FCU
EX FCU
EX FCU
MD301
EX RS/L, TYP
OF 2 SETS
EX RS/L
EX RS/L
COURTROOM
JURY CONFERENCE
OFFICE
JUDGE'S CHAMBER
HOLDING CELL
ELEV.
1 1
RX ELEC HEATER
RX ELEC HEATER
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
MD200
GROUND LEVEL - MECHANICAL PIPING - DEMOLITION PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"N
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
M
EC
HA
NI
CA
L P
IPI
NG
D
EM
O
LIT
IO
N
PL
AN
MD200
LOWER LEVEL - MECHANICAL PIPING - DEMOLITION PLAN
1/8" = 1'-0" N
RX RADIATOR INCLUDING ALL ASSOCIATED PIPING AND CONTROLS.
RX STM/STM COND UP/DN
TEMPORARILY REMOVE AND SALVAGE EXISTING FCU TO ALLOW FOR NEW
CEILING INSTALLATION. REINSTALL EXISTING FCU AS SHOWN ON DRAWING
M100.
PATCH AND SEAL EXISTING WALL OPENING TO MAKE AIR AND WATER TIGHT.
SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
MD200
UPPER LEVEL - MECHANICAL PIPING - DEMOLITION PLAN
1/8" = 1'-0" N
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
1.
2.
3.
MAV
MD200
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
RX AHU-1
RX AHU-2
OFFICELAV.
CELL 2
CELL 1
KITCHEN
MECHANICAL
MECHANICAL
MEN
WOMEN
1 1
RX EF
RX EF
RX FAN
RX DUCTWORK, TYP
RX DUCTWORK, TYP
ELEV.
CRAWL SPACE
CRAWL SPACE
BASEMENT
CRAWL SPACE
TRX
RX DUCTWORK, TYP
RX 12x12 UP
RX PLENUMRX EA DUCT UP
MD300
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
M
EC
HA
NI
CA
L P
AR
T P
LA
NS
DE
M O
LIT
IO
N
MD300
LOWER LEVEL - DUCTWORK - DEMOLITION PART PLAN
1/4" = 1'-0" N
0 2 8 12 FT4
1/4" = 1' - 0"
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
1.
2.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
RX AIR DEVICE
RX 48x64 RA LOUVER BETWEEN MECHANICAL ROOM AND CORRIDOR.
RX 106x22 OA LOUVER TO EXTERIOR
RX RELIEF LOUVER TO EXTERIOR
RX 10x14 SA UP, RX 10x18 SA UP, RX 48x18 SA UP, RX 10x18 SA UP, RX 16x14 SA UP, RX 44x18 RA UP
RX 12x12 OED
RX RETURN AIR DUCT TO EXISTING SHAFT AND UP THROUGH SHAFT.
RX ALL ASSOCIATED CONCRETE PADS, SUPPORTS, CONTROLS, WIRING, ETC
MD300
MD300
LOWER LEVEL - EX OA LOUVER SECTION
1/4" = 1'-0"
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
OFFICELAV.
CELL 2
CELL 1
KITCHEN MECHANICAL
MECHANICAL
MEN
WOMEN
ELEV.
CRAWL SPACE
CRAWL SPACE
BASEMENTCRAWL SPACE
RX 4" CS ABOVE /
RX 3" CS BELOW
RX 3" CS ABOVE /
RX 2-1/2" CR BELOW
RX STM
COND PUMP
RX BOILER
RX RS/L
RX CONDENSER
WATER PUMP
RX CHEMICAL
TREATMENT
RX STM TO
DOMESTIC HW
CONVERTER
RX CONDENSER
WATER PUMP
RX RS/L
RX CHILLER-1RX AIR
COMPRESSOR
RX AHU-1
RX AHU-2
RX CHILLER-2
RX STM/STM COND
RX CS/RRX CS/R
RX STM/STM COND
RX RS/L, TYP
OF 2 SETS
EX RS/L
EX RS/L, TYP OF 2 SETS
RX CARRIER
PIPE
3 3
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
M
EC
HA
NI
CA
L P
AR
T P
LA
NS
DE
M O
LIT
IO
N
MD301
LOWER LEVEL - MECHANICAL PIPING - DEMOLITION PART PLAN
1/4" = 1'-0" N
0 2 8 12 FT4
1/4" = 1' - 0"
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS
HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD
OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN
DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO
FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE
DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE
PROCEEDING WITH THE WORK.
EXISTING TO REMAIN VRF SYSTEM AND SPLIT SYSTEM UTILIZE R-410A
REFRIGERANT.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
MAV
RX ALL ASSOCIATED PIPING THROUGHOUT ENTIRE BUILDING
RX STM/STM COND UP TO RADIATOR
RX ALL ASSOCIATE HOUSEKEEPING PADS, SUPPORTS, WIRING,
CONTROLS, ETC.
RX FLUE UP THROUGH CHIMNEY.
MD301
4.
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
AutoCAD SHX Text 30 x x 68
D
W V
W V
W V
W V
W V
EX. 6" W
M
WV
D
W V
W V
WV
W V
EEREER
W
58.5
59.5
S
S
S
S
C/OC/O
C/O
C/O
S
IRR M
WM
WM
WM
WMWMWM
M002
GENERATOR 1
HRU-2
HRU-3
HRU-1
EX ACCU
EX ACCU
RS/L DN TO BASEMENT,
TYP OF 9 SETS. SEE DRAWING
M301 FOR CONTINUATION
RACK RS/L PIPING
ALONG WALL, TYP
GENERATOR
DOCKING STATION 1
ACCU-2
ACCU-1
ACCU-3
ACCU-4
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
M004
MECHANICAL SITE PLAN - NEW WORK
1" = 20'-0" N
SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION
MOUNT ON 4" CONCRETE PAD
PROVIDE PIPE HOOD ASSEMBLY FOR REFRIGERANT LINES. DOGHOUSE /
PIPE PENETRATIONS SHALL BE AIR AND WATER TIGHT. SEE DETAIL ON
DRAWING M501 FOR MORE INFORMATION.
FOLLOWING COMPLETION OF ASSOCIATED PIPING MODIFICATION
RE-CHARGE SYSTEM AND MAKE OPERATIONAL. THIS SYSTEM UTILIZES
R-410A REFRIGERANT
REINSTALL EXISTING ACCU IN THIS LOCATION. RELOCATE/REPLACE
ASSOCIATED REFRIGERANT PIPING AS NECESSARY. RE-CHARGE SYSTEM
AND RECONNECT TO EXISTING PIPING, WIRING, CONTROLS, ETC TO MAKE
SYSTEM FULLY OPERATIONAL. THIS SYSTEM UTILIZES R-410A
REFRIGERANT.
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
M
EC
HA
NI
CA
L S
ITE
P
LA
N
- N
EW
W O
RK
MAV
M004
EQUIPMENT YARD - MECHANICAL - NEW WORK PART PLAN
1/4" = 1'-0" N
0 10 40 80 FT20
1" = 20' - 0"
0 2 8 12 FT4
1/4" = 1' - 0"
M004
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
T
TBREAK AREA
STAIRS
ELEV. LOBBY
LOBBY
ORPHAN'S COURTROOM
RECEPTION
RECORDS
CORRIDOR
R.O.W. OFFICE
CHIEF DEPUTY
DEPUTY
ELEV
13 UNISEX
UNISEX
OFFICE OF THE
CLO.
109A
REGISTER OF WILLS
10x6 D-2, 210 CFM
10x8 D-2, 255 CFM
24x24 R-4, 1,010 CFM
14x16 OA UP/DN
8x4 R-3, 75 CFM
8x4 R-3, 75 CFM
12x8 D-2, 330 CFM
8x4 EA DN
8x4 EA DN
10x16 EA UP/DN
10x8 D-2, 255 CFM
12x8 D-2, 350 CFM
12x8 D-2, 350 CFM
12x8 D-2, 350 CFM
12x8 D-2, 350 CFM
18x10 R-2, 575 CFM
14x26 R-4, 640 CFM
AHU-2.2
AHU-2.1
8x6 D-2, 160 CFM
8x4 D-2, 90 CFM
AHU-2.3
14x6 D-2, 275 CFM
12x8 D-2, 340 CFM
14x6 D-2, 265 CFM
14x6 D-2, 265 CFM
10x8 D-2, 225 CFM
10x6 R-2, 210 CFM
12x24 R-4, 495 CFM
AHU-2.4
12x8 R-2, 315 CFM
16x8 RA DN 12x8 RA DN
24x8 RA DN
10x8 D-2, 255 CFM
T
T
T
T
TT
T T
T
MECHANICAL
MEN'S
WOMEN'S
J.C.
ELEV.
BSMT. / MECH.
ROOM
CORRIDOR
SECONDARY PSAP
I.T.
20A
MEETING ROOM
OPEN OFFICE AREA
ELECTRICAL
SPRINKLER
VAULT
22A
OPEN OFFICE AREA
OFFICE
OFFICE
BREAK
I.T.
UT
ILI
TY
TU
NN
EL
A
MECHANICAL/STORAGE
MACHINE
STAIRS
CRAWL SPACE
CLO.
LOWER LOBBY
CRAWL
CRAWL SPACE
SPACE CRAWL SPACE
MECH. CL.
30A
1 ACU-1
1 1
AHU-1.10
FCU-1.8
M300
EX
EX
EX FCU
EX FCU
EX FCU
EX FCU
EX FCU
FCU-1.5A
FCU-1.5B
FCU-1.5C
FCU-1.6
FCU-1.7A
FCU-1.7B
FCU-1.9A
FCU-1.9B
10"ø D-1, 390 CFM
14x10 OA
10x6 4x4
8x8 6x8
8x8
AHU-1.4
10"ø
6"ø D-1, 140 CFM
6"ø D-1, 140 CFM
8x8
8x8 RA OED
6"ø
6"ø
6"ø
6"ø
4"ø
6"ø 6"ø
20 21
10x6
6x8
14x10
T ACU-1
FCU-1.6
FCU-1.7A, FCU-1.7B
FCU-1.9A,
FCU-1.9B
AHU-1.10
FCU-1.8
6"ø D-1, 110 CFM
10x6
6"ø D-1, 110 CFM
6"ø D-1, 110 CFM
6"ø D-1, 110 CFM
6"ø D-1, 110 CFM
6"ø D-1, 110 CFM
6"ø D-1, 110 CFM
6"ø D-1, 110 CFM
T
T
T
UPPER LOBBY
COURTROOM
CONFERENCE
200A
ELEV. LOBBY
STAIRS
JUDGE'S CHAMBER
REST LOBBY
UNISEX
UNISEX
ELEV
TOILET
205A
CLOSET
205B
T
10"ø D-3, 365 CFM
12x8 RA UP
12x10 EA UP
30x18 R-4, 920 CFM
30x18 R-4, 605 CFM
14x16 OA UP/DN 10x16 EA UP/DN18x8 D-4, 440 CFM
26x22 R-4, 920 CFM
8x8 D-4, 180 CFM
12x6 D-4, 230 CFM
12x12 D-4, 470 CFM
12x10 D-4, 375 CFM
12x10 D-4, 385 CFM
AHU-3.4
AHU-3.2
AHU-3.3
AHU-3.1
26x6 RA UP
8x16 RA UP
10"ø D-3, 370 CFM
10"ø D-3, 370 CFM
10"ø D-3, 365 CFM
10"ø D-3, 340 CFM
10"ø D-3, 340 CFM
10"ø D-3, 340 CFM
10"ø D-3, 340 CFM
16x30 R-4, 775 CFM 3
TAHU-3.5
36 4x4 OA, 10x6 EA 37
6x6 OA
6x6 OA UP
4x4 OA UP, 10x6 EA UP
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
M100
GROUND LEVEL - DUCTWORK - NEW WORK PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"
N
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR
DEVICE NECK SIZE.
DO NOT CUT ANY JOISTS WITHOUT APPROVAL FROM STRUCTURAL ENGINEER.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
DU
CT
W O
RK
N
EW
W
O
RK
P
LA
N
M100
LOWER LEVEL - DUCTWORK - NEW WORK PLAN
1/8" = 1'-0" N
22x22 G-1
12x10 R-5, 410 CFM
12x10 R-5, 365 CFM
6x4 INTERNALLY LINED TRANSFER DUCT
6x6 INTERNALLY LINED TRANSFER DUCT
8x6 INTERNALLY LINED TRANSFER DUCT
8x8 INTERNALLY LINED TRANSFER DUCT
10x8 INTERNALLY LINED TRANSFER DUCT
12x8 INTERNALLY LINED TRANSFER DUCT
10x6 R-5, 160 CFM
12x6 R-5, 210 CFM
12x12 R-5, 425 CFM
ACCESS HATCH TO ATTIC
MOUNT TOP OF REGISTER APPROXIMATELY 8" BELOW CEILING
MOUNT ABOVE DOOR
VD, 65 CFM
VD, 70 CFM
VD, 125 CFM
VD, 15 CFM
VD, 45 CFM
VD, 50 CFM
VD, 35 CFM
VD, 195 CFM
REINSTALL EXISTING FCU IN THIS LOCATION. RECONNECT TO EXISTING
PIPING, WIRING, CONTROLS, ETC TO MAKE SYSTEM FULLY OPERATIONAL.
RELOCATE/REPLACE ASSOCIATED REFRIGERANT PIPING AS NECESSARY.
THIS SYSTEM UTILIZES R-410A REFRIGERANT.
THIS THERMOSTAT SHALL CONTROL FCU-1.15A, 1.15B, AND 1.15C.
MOUNT BOTTOM OF REGISTER APPROXIMATELY 10" AFF.
VD, 280 CFM
VD, 200 CFM
6x6 D-4, 60 CFM
NOT USED
NOT USED
6x6 R-1, 75 CFM
24x12 G-4
32x12 G-4
MOUNT ON STAND. SEE FAN COIL UNIT - VERTICAL DETAIL ON DRAWING M502.
10"x10" A2L REFRIGERANT ENCLOSURE SYSTEM. SEE SPECIFICATION
SECTION 232310.
SEE DRAWING M101 FOR CONTINUATION.
VD, 250 CFM
24" LONG INSULATED PLENUM. WIDTH AND HEIGHT SHALL MATCH FCU
CONNECTION SIZE
48"L x 12"H x 2"D FILTER RACK
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
M100
UPPER LEVEL - DUCTWORK - NEW WORK PLAN
1/8" = 1'-0" N
4.
5.
MAV
M100
NOT FOR BID
DIN
G
OR C
ONSTRUCTIO
N
AutoCAD SHX Text 1 "38"
AutoCAD SHX Text
K-PR5452-T1D
AutoCAD SHX Text
URINAL
AutoCAD SHX Text
K-PR5452-T1D
URINAL
UH-1
14x16 OA DN 10x16 EA DN
ERV-2
FC
UH-4
UH-2
16x8 RA DN12x12 RA DN
26x6 RA DN
AHU-3.3
FC
FC
FC
FC
FC
FC
12x14 EA
FC
14x14 OA
MOD
MOD
12x14 EA
14x16 OA
12x14 EA
AHU-3.2
AHU-3.1
AHU-3.4
18x6
12x8
12x6
12x8
8x6
16x6
10x8 OA
12x8 OA
6x6 OA DN
6x6 OA
8x4 OA
14x16 OA 8
ATTIC
M401
M401
M401
10x6 RA
14x6
SS
FAN-1
FCFC
MOD
MOD
10x16 EA 8x8 EA
8x8 EA
12x12 RA
FC
FCU-3.6
FCU-3.7
FCU-3.9
FCU-3.8
MOD
12x12 8x8 SA DN
12x6 SA DN
10x6 RA DN
12x6 EA DN
12x12 SA DN
12x8
12x12 RA DN
18x8 SA DN
10x6 EA
12x10 RA DN
12x10 SA DN
4x4 OA
6x6 EA DN
6x6 EA DN
8x4
8x412x6
12x10 RA DN 12x14 4x4 OA DN
6x10 EA DN
12x10
EA DN
18x8 SA DN
10"ø SA DN
10"ø SA DN
10"ø SA DN
10"ø SA DN
16x8
16x8 RA
6x6 12X12
10"ø
SA DN
10"ø SA DN
10"ø SA DN
10"ø SA DN
14x14
18x6 20x8
BS-3.1
BS-3.2
FC
FC
FC
12x8
14X6
12x8
14x6
M401
8x8 OA
12X12 SA
14x14
AHU-3.5
11 12
M400
M401
12x8 RA
6x4
14x16
14x16 OED
14x16 OED17
UH-3
R
D
DR
R
D
D
R
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
M101
ATTIC - DUCTWORK - NEW WORK PLAN
1/4" = 1'-0" N
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR
RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.
IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR
DEVICE NECK SIZE.
1.
2.
3.
(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:
DU
CT
W O
RK
N
EW
W
O
RK
P
LA
N
ACCESS HATCH. KEEP CLEAR
24" LONG INSULATED PLENUM. WIDTH AND HEIGHT SHALL MATCH FCU
CONNECTION SIZE
26"L x 16"H x 14"D EA PLENUM
ABOVE:22" DEEP INSULATED OA PLENUM. WIDTH AND HEIGHT SHALL
MATCH ERV CONNECTION SIZE
BELOW:22" DEEP INSULATED EA PLENUM. WIDTH AND HEIGHT
SHALL MATCH ERV CONNECTION SIZE
28" LONG INSULATED PLENUM. WIDTH AND HEIGHT SHALL MATCH FCU
CONNECTION SIZE
INSTALL TIGHT TO STRUCTURE ABOVE
DUCT DOWN FROM MAIN ATTIC SPACE
INSTALL AT FLOOR LEVEL
TERMINATE 8x8 EA OED WITH FIRE DAMPER WITHIN REFRIGERANT
ENCLOSURE SYSTEM
VD, 110 CFM
VD, 495 CFM
VD, 90CFM
VD, 45 CFM
MOUNT ON ATTIC FLOOR. PROVIDE DRAIN PAN BENEATH UNIT. SEE FAN
COIL UNIT - HORIZONTAL - ATTIC DETAIL ON DRAWING M502.
SUPPORT FROM ATTIC STRUCTURE
MOUNT TO CHIMNEY STRUCTURE
PROVIDE BIRD SCREEN
MOUNT ON ATTIC FLOOR WITH VIBRATION ISOLATOR PER SPECIFICATION
SECTION 230548
TERMINATE DUCT WITHIN CHIMNEY WITH OED. PROVIDE BIRDSCREEN
SEE DRAWING M100 FOR CONTINUATION
48"L x 12"H x 2"D FILTER RACK
(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:
MAV
M1010 2 8 12 FT4
1/4" = 1' - 0"
NOT FOR BID
DIN
G
OR C
BREAK AREA
STAIRS
ELEV. LOBBY
LOBBY
ORPHAN'S COURTROOM
RECEPTION
RECORDS
CORRIDOR
R.O.W. OFFICE
CHIEF DEPUTY
DEPUTY
ELEV
UNISEX
UNISEX
OFFICE OF THE
CLO.
109A
REGISTER OF WILLS
RS/L UP/DN1
MECHANICAL
MEN'S
WOMEN'S
J.C.
ELEV.
BSMT. / MECH.
ROOM
CORRIDOR
SECONDARY PSAP
I.T.
20A
MEETING ROOM
OPEN OFFICE AREA
ELECTRICAL
SPRINKLER
VAULT
22A
OPEN OFFICE AREA
OFFICE
OFFICE
BREAK
I.T.
UT
ILI
TY
TU
NN
EL
A
MECHANICAL/STORAGE
MACHINE
STAIRS
CRAWL SPACE
CLO.
LOWER LOBBY
CRAWL
CRAWL SPACE
SPACE CRAWL SPACE
MECH. CL.
30A
EX FCU
EX FCU
EX FCU
EX FCU
M301
EX RS/L, TYP
OF 2 SETS
EX FCU
EX RS/L
RS/L
RS/L
ACU-1
AHU-1.10
FCU-1.5A
FCU-1.5B
FCU-1.5C
FCU-1.6
FCU-1.7A
FCU-1.7B
FCU-1.9A
FCU-1.9B
EX RS/L
RS/L
RS/L
FCU-1.8
UPPER LOBBY
COURTROOM
CONFERENCE
200A
ELEV. LOBBY
STAIRS
JUDGE'S CHAMBER
REST LOBBY
UNISEX
UNISEX
ELEV
TOILET
205A
CLOSET
205B
RS/L UP/DN
2 SETS OF RS/L UP2 SETS OF RS/L UP
SEE M201 FOR CONTINUATION SEE M201 FOR CONTINUATION
Torchio Architects, Inc.
COPYRIGHT C
Project Number:
Date:
Revisions:
Drawn By:
Sheet:
A2112
Q
AC
H
IST
O
RIC
C O
UR
TH
O
US
E R
EN
O
VA
TIO
N
0 C
O
UR
TH
O
US
E S
Q
UA
RE
CE
NT
RE
VI
LL
E, M
AR
YL
AN
D
06.05.26
PROGRESS SET
NOT FOR CONSTRUCTION
M200
GROUND LEVEL - MECHANICAL PIPING - NEW WORK PLAN
1/8" = 1'-0"
0 4 16 24 FT8
1/8" = 1' - 0"N
EXISTING SHOWN WITH LIGHT WEIGHT LINE,
NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS, STRAINERS,…