drawing - MECHANICAL_QAC Historic Courthouse RFQ_2026.07.01.pdf

PDF 3 MB Posted

Attached to
Historic Courthouse Renovation
Solicitation number
BPM057809
Issued by
Queen Anne's County, Maryland

About this file

This is a mechanical drawing cover sheet and technical specifications document for the Historic Courthouse Renovation project in Centreville, Maryland, prepared by Torchio Architects for Queen Anne's County. The document establishes comprehensive mechanical installation requirements and standards for the complete HVAC system renovation of the 17,800-square-foot dormant courthouse building. The project includes demolition of 1960s-era HVAC and electrical systems, with new mechanical systems comprising multiple variable refrigerant flow (VRF) units, both ducted and ductless mini-split units, energy recovery ventilators, and an integrated control system. The drawing set includes detailed mechanical notes, abbreviations, legends, and symbols to guide contractor installation, coordination with other trades, and compliance with applicable building codes.

The specifications detail extensive technical requirements for refrigerant piping installation compliant with ASHRAE 15-2022, including pipe protection standards, prohibited installation locations, brazing and soldering specifications, hanger and support requirements, and refrigerant equipment installation protocols. Testing and inspection requirements mandate engagement of a qualified testing agency to perform strength tests using inert gases and leakage tests with specific vacuum and pressure parameters before system operation. All refrigeration systems containing 55 pounds or more of refrigerant require a certificate of test issued by the installing contractor and signed verification documenting test dates, pressures, refrigerant designation, and test medium. The document emphasizes contractor responsibility for coordinating all mechanical work with plumbing, electrical, and other trades; determining exact existing utility locations; and obtaining approval from the Contracting Officer Representative before proceeding with work when site conditions prevent execution as indicated on drawings.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(APPLICABLE TO ALL MECHANICAL DRAWINGS)

COORDINATE ALL MECHANICAL WORK WITH PLUMBING WORK, ELECTRICAL WORK, AND WORK OF OTHER TRADES SHOWN ON OTHER DRAWINGS.

THE LOCATION OF EXISTING UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. REPAIR ALL DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UTILITIES.

RUN ALL DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED.

ELEVATIONS NOTED ARE TO CENTERLINES OF PIPES FOR ALL PRESSURE LINES AND TO INVERT FOR ALL GRAVITY FLOW LINES.

INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE.

UNLESS OTHERWISE NOTED, ROUTE ALL PIPING AND DUCTWORK OVERHEAD, TIGHT TO UNDERSIDE OF SLAB, WITH SPACE FOR INSULATION IF REQUIRED.

MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL

AND ELECTRICAL ROOMS.

CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN DUCTWORK AND PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS. CONTRACTOR SHALL ENSURE MANUFACTURER'S INSTALLATION

REQUIREMENTS INCLUDING BUT NOT LIMITED TO REQUIRED MAINTENANCE CLEARANCE.

WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES REQUIRES CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., CHECK FOR THE PRESENCE OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION. EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO PERSONNEL DUE TO CONTACT WITH SAME. TEMPORARILY DISCONNECT SERVICES DURING THE CUTTING OPERATION. SCHEDULE SERVICE OUTAGES IN ADVANCE WITH THE OWNER.

FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT. VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. PROVIDE ADDITIONAL VALVES, PRESSURE GAUGES, ETC. AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS AND DETAILS FOR PIPE SIZES NOT INDICATED ON FLOW SCHEDULES AND RISER DIAGRAMS.

CONTRACTOR SHALL BE RESPONSIBLE FOR RESEARCHING ALL SYSTEMS THAT A PARTICULAR OUTAGE WILL AFFECT AS WELL AS LOCATING ALL SHUTOFF POINTS.

INCLUDE THIS INFORMATION IN THE OUTAGE PLAN AND SUBMIT TO THE OWNER FOR APPROVAL.

EXCEPT AS OTHERWISE NOTED, LOCATE ALL ROOM TEMPERATURE SENSORS ABOVE FINISHED FLOOR ON SAME HORIZONTAL CENTERLINE AS LIGHT SWITCH.

WHERE LIGHT SWITCH AND TEMPERATURE SENSOR ARE ADJACENT TO EACH OTHER, LIGHT SWITCH SHALL BE CLOSEST TO THE DOOR. COORDINATE WITH ELECTRICAL CONTRACTOR. NOTIFY THE ENGINEER OF ROOMS WHERE THE ABOVE LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON

LOCATION.

INSTALL CEILING MOUNTED DIFFUSERS, REGISTERS, AND GRILLE IN ACCORDANCE WITH CEILING GRID.

INFORMATION SHOWN ON THE MECHANICAL DRAWINGS PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMOLITION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING AND AWAIT WRITTEN DIRECTION

BEFORE PROCEEDING WITH THE WORK.

REMOVE ALL EXISTING PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE COR, OR ARE INDICATED TO REMAIN THE PROPERTY OF OWNER SHALL BE DELIVERED BY THE CONTRACTOR WHERE DIRECTED BY THE OWNER. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES.

DISCONNECT EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR OTHERWISE) AND REMOVE PIPING BACK TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR NOTED ON PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. CAP, PLUG, OR SEAL EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE. NO EXISTING PIPING SHALL BE LEFT UNSEALED VALVE ALL TERMINATED PRESSURE PIPE.

EXISTING MECHANICAL PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS. ALL WORK SHALL BE COMPLETED TO THE

SATISFACTION OF THE COR AND AT NO ADDITIONAL CONTRACT COST.

REMOVE ALL ACCESSORIES, CONTROLS, ENCLOSURES, SUPPORTS, HANGERS, PADS, ETC. ASSOCIATED WITH ALL EQUIPMENT SHOWN TO BE REMOVED. REPAIR AND PAINT DAMAGED SURFACES AND ALL SURFACES BEHIND ALL EQUIPMENT SHOWN TO BE DEMOLISHED TO MATCH EXISTING ADJACENT SURFACES.

PRIOR TO SUBMITTING SHOP DRAWINGS TO ENGINEER FOR EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS, COORDINATE ELECTRICAL REQUIREMENTS BETWEEN CONTRACTORS OF ALL TRADES ASSOCIATED WITH THE INSTALLATION. THE GENERAL CONTRACTOR'S STAMP ON THE SUBMITTAL MUST STATE THAT COORDINATION BETWEEN ALL TRADES HAS BEEN VERIFIED AND THAT THE SUBMITTAL HAS BEEN APPROVED FOR ENGINEER'S REVIEW. IF CONTRACTOR SUBMITS EQUIPMENT WITH POWER REQUIREMENTS THAT ARE DIFFERENT FROM POWER CONNECTION INDICATED ON THE CONTRACT DOCUMENTS, CONTRACTOR MUST PROVIDE A REASON FOR THE CHANGE AND WRITTEN CONFIRMATION THAT THE CHANGE HAS BEEN FULLY COORDINATED WITH ALL ASSOCIATED TRADES. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO ELECTRICAL CONNECTION, COORDINATE AND MAKE REQUIRED CHANGES TO PROVIDE A COMPLETE INSTALLATION IN ACCORDANCE WITH APPLICABLE CODES. CHANGE ORDERS AND EXTRAS WILL NOT BE AWARDED DUE TO CONTRACTOR'S FAILURE TO COORDINATE WITH ALL ASSOCIATED TRADES. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO COORDINATE EQUIPMENT SUBMITTALS AMONG THE SUBCONTRACTORS, NOT THE ENGINEER'S.

GENERAL MECHANICAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

A AMPS / COMPRESSED AIR

ACCU AIR COOLED CONDENSER

ACV AUTOMATIC CONTROL VALVE

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

APD AIR PRESSURE DROP

APPROX APPROXIMATE

ARCH ARCHITECTURAL

B BOTTOM

BAS BUILDING AUTOMATION SYSTEM

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BLDG BUILDING

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

CAP CAPACITY

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CIRC CIRCULATING

CL CENTERLINE

CLG CEILING / COOLING

COMP COMPRESSOR

COND CONDENSATE / CONDENSER / CONDENSING

CW COLD WATER

CX CONNECT TO EXISTING

D DAMPER / DIAMETER / DIFFUSER / DRAIN / DROP

DB DRY BULB

DEG DEGREES

DET DETAIL

DIA DIAMETER

DIFF DIFFUSER

DN DOWN

DP DIFFERENTIAL PRESSURE

DWGS DRAWINGS

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

EL ELEVATION

ELEC ELECTRIC / ELECTRICAL

ELEV ELEVATOR

EQ EQUAL

EQUIP EQUIPMENT

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETR EXISTING TO REMAIN

EVAP EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EX EXISTING

EXH EXHAUST

F FAHRENHEIT / FAN

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT

FD FIRE DAMPER / FLOOR DRAIN

FLA FULL LOAD AMPS

FLR FLOOR

FPD FLUID PRESSURE DROP

FPM FEET PER MINUTE

FT FEET / FOOT

G GAS / GRILLE

GPM GALLONS PER MINUTE

H HEIGHT

HC HEATING COIL

HP HORSEPOWER

HTG HEATING

HVAC HEATING, VENTILATING AND AIR CONDITIONING

HZ HERTZ

IN INCH / INCHES

MECHANICAL ABBREVIATIONS

(APPLICABLE TO ALL MECHANICAL DRAWINGS)

KW KILOWATTS

L LENGTH

LAT LEAVING AIR TEMPERATURE

LFT LEAVING FLUID TEMPERATURE

LLS LIQUID LEVEL SENSOR

LSD LINEAR SLOT DIFFUSER

LVG LEAVING

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH THOUSANDS BTU PER HOUR

MECH MECHANICAL

MER MECHANICAL EQUIPMENT ROOM

MIN MINIMUM

MOD MOTOR OPERATED DAMPER

N NORTH

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN / NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OA OUTDOOR AIR

OC ON CENTER

OED OPEN END DUCT

PD PRESSURE DROP / PUMP DISCHARGE

PHC PREHEAT COIL

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI PRESSURE - POUNDS PER SQUARE INCH

PSIG PRESSURE - POUNDS PER SQUARE INCH GAGE

R RADIUS / REGISTER / RISE / RISER

RA RETURN AIR

RAD RADIUS

RD ROUND

REFRIG REFRIGERANT

REG REGISTER

RET RETURN

REV REVISION

RH REHEAT / RELATIVE HUMIDITY

RHC REHEAT COIL

RL REFRIGERANT LIQUID

RM ROOM / REFRIGERANT MONITOR

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RV RELIEF VALVE

RX REMOVE EXISTING

S SWITCH

SA SUPPLY AIR

SAF SUPPLY AIR FAN

SD SMOKE DAMPER / SMOKE DETECTORS

SEER SEASONAL ENERGY EFFICIENCY RATIO

SENS SENSIBLE COOLING

SP STATIC PRESSURE

SPEC SPECIFICATION

T TEMPERATURE SENSOR / THERMOSTAT

TEMP TEMPERATURE / TEMPORARY

THRU THROUGH

TOT TOTAL

TYP TYPICAL

UH UNIT HEATER

UON UNLESS OTHERWISE NOTED

V VALVE / VENT / VOLTS

VD VOLUME DAMPER

W WATT / WIDTH

W/ WITH

W/O WITHOUT

WB WET BULB

WPD WATER PRESSURE DROP

CR CONDENSER WATER RETURN

CS CONDENSER WATER SUPPLY / CURRENT SENSOR

HRU HEAT RECOVERY UNIT

STM STEAM

VRF VARIABLE REFRIGERANT FLOW

BS BRANCH SELECTOR BOX

BDD BACKDRAFT DAMPER

ACU AIR CONDITIONING UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP / CONTROL PANEL

ERV ENERGY RECOVERY VENTILATOR

ES END SWITCH

QTY QUANTITY

LBS POUNDS

M MECHANICAL

MCA MINIMUM CIRCUIT AMPACITY

MOCP MAXIMUM OVERCURRENT PROTECTION

PH PHASE

TSP TOTAL STATIC PRESSURE

WG WATER GAUGE

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

MD MECHANICAL DEMOLITION

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

MAV

M

EC

HA

NI

CA

L C

O

VE

R

SH

EE

T

DESCRIPTIONSYMBOL

DIFFUSER TAG:

TOP - NECK SIZE, SPECIFICATION TYPE

BOTTOM - AIRFLOW IN CFM

FLEXIBLE CONNECTION

VOLUME DAMPER

FIRE DAMPER

DUCT MOUNTED SMOKE DETECTOR

THERMOSTAT/TEMPERATURE SENSORT

RETURN AIR DUCT

OUTDOOR AIR OR SUPPLY AIR DUCT

EXHAUST AIR DUCT

SHUTOFF VALVE

UNION

THERMOMETER

CAP (PIPE OR DUCT)

PLAN/ SECTION DESIGNATION

TOP - PLAN/ SECTION REFERENCE

BOTTOM - REFERENCED DRAWING

A M-1

END POINT OF REMOVAL OF EXISTING

CONNECT TO EXISTING

HOT WATER HEATING SUPPLYHS

HOT WATER HEATING RETURNHR

(APPLICABLE TO ALL MECHANICAL DRAWINGS)

MECHANICAL LEGEND

CR CONDENSER RETURN

CS CONDENSER SUPPLY

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

X#

X#

X# STEAM SUPPLY

X# STEAM RETURN

LPS LOW PRESSURE STEAM

M001

8"ø D-1, 250 CFM

COMBINATION FIRE AND SMOKE DAMPER

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

REFRIGERANT PIPING INSTALLATION REQUIREMENTS

1. CODE COMPLIANCE: ASHRAE 15-2022.

2. SHAFT ENCLOSURES: MECHANICALLY VENTILATED SHAFTS IN ACCORDANCE WITH ASHRAE 15-2022.

3. INSTALL PER MANUFACTURER'S REQUIREMENTS. EQUIPMENT MANUFACTURERS SHALL SIZE ALL PIPING.

4. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF SYSTEMS; INDICATED LOCATIONS AND. INSTALL PIPING AS INDICATED

UNLESS DEVIATIONS TO LAYOUT ARE APPROVED ON SHOP DRAWINGS.

5. INSTALL REFRIGERANT PIPING IN ACCORDANCE WITH ASHRAE 15-2022.

6. PIPE PROTECTION. THE EXTERIOR OF THE PIPE SHALL BE PROTECTED FROM CORROSION, DEGRADATION, GALVANIC CORROSION AND ABRASION. REFRIGERANT PIPE SHALL NOT BE IN CONTACT WITH BUILDING MATERIALS THAT CAN ABRADE THE PIPE. REFRIGERANT PIPE SHALL BE INSTALLED AS FOLLOWS IN ACCORDANCE WITH ASHRAE 15-2022:

A. PIPING INSTALLED IN A WALL OR FLOOR SPACE OR WITHIN A PROTECTIVE ENCLOSURE SHALL BE PROTECTED AS FOLLOWS:

1) IN CONCEALED LOCATIONS WHERE COPPER TUBE IS INSTALLED THROUGH HOLES OR NOTCHES IN STUDS, JOISTS OR SIMILAR MEMBER LESS THAN 1.5 INCHES FROM THE NEAREST EDGE OF THE MEMBER, THE TUBE SHALL BE PROTECTED BY STEEL SHIELD PLATES WITH A MINIMUM THICKNESS OF 0.0575 INCH.

2) PROTECTIVE STEEL SHIELD PLATES SHALL COVER THE AREA OF THE TUBE WHERE THE MEMBER IS NOTCHED OR BORED AND SHALL EXTEND NOT LESS THAN 2

INCHES ABOVE SOLE PLATES AND BELOW TOP PLATES.

B. PIPING EXPOSED INSIDE OF A BUILDING SHALL BE INSTALLED AT AN ELEVATION THAT IS MORE THAN 7 FEET 3 INCHES ABOVE THE FINISHED FLOOR OR WHEN THE PIPING IS WITHIN 6 FEET OF THE APPLIANCE TO WHICH IT CONNECTS. OTHERWISE INSTALL REFRIGERANT PIPING IN RIGID OR FLEXIBLE CONDUIT AND IN LOCATIONS WHERE EXPOSED

TO MECHANICAL INJURY.

C. PIPING IN AN ATTIC OR CRAWL SPACE, PROVIDED THAT COPPER TUBE IS INSTALLED 1.5 INCHES FROM THE NEAREST EDGE OF THE MEMBER, THE TUBE SHALL BE PROTECTED BY STEEL SHIELD PLATES HAVING A MINIMUM THICKNESS OF 0.0575 INCH (NO. 16 GAGE). PROTECTIVE STEEL PLATES ARE NOT REQUIRED IN LOCATIONS

WHERE THE REFRIGERANT PIPING IS EXPOSED.

D. PIPING OUTSIDE THE BUILDING SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:

1) PROTECTED FROM DAMAGE FROM THE WEATHER, INCLUDING BUT NOT LIMITED TO HAIL, ICE AND SNOW LOADS.

2) PROTECTED FROM DAMAGE WHERE LOCATED IN AN EXPECTED FOOT OR TRAFFIC PATH.

3) UNDERGROUND BELOW THE FROST LINE AND NOT LESS THAN 8 INCHES BELOW FINISH GRADE.

7. REFRIGERANT PIPING SHALL NOT BE INSTALLED IN ANY OF THE FOLLOWING LOCATIONS:

A. EXPOSED WITHIN A FIRE-RESISTANCE-RATED EXIT ACCESS CORRIDOR.

B. EXPOSED WITHIN AN INTERIOR EXIT STAIRWAY.

C. WITHIN AN INTERIOR EXIT RAMP ENCLOSURE.

D. WITHIN AN EXIT PASSAGEWAY.

E. WITHIN AN ELEVATOR, DUMBWAITER OR OTHER SHAFT CONTAINING A MOVING OBJECT.

F. INSIDE AN AIR DUCT OR AIR DUCT PLENUM.

8. REFRIGERANT PIPING INSTALLED IN CONCRETE FLOORS SHALL BE ENCASED IN PIPE, CONDUIT OR DUCTS. THE REFRIGERANT PIPING SHALL BE PROTECTED TO PREVENT

DAMAGE FROM VIBRATION, STRESS AND CORROSION.

9. INSTALL REFRIGERANT PIPING IN PROTECTIVE CONDUIT WERE INSTALLED BELOW GROUND. THE PIPING SHALL BE PROTECTED TO PREVENT DAMAGE FROM VIBRATION, STRESS AND CORROSION.

10. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED OTHERWISE. INSTALL PIPING AS SHORT AND DIRECT AS POSSIBLE, WITH A MINIMUM NUMBER OF JOINTS, ELBOWS, AND FITTINGS. REFRIGERANT PIPING SHALL BE INSTALLED SO AS TO PREVENT STRAINS AND STRESSES THAT EXCEED THE STRUCTURAL STRENGTH OF THE PIPE.

11. INSULATE ALL REFRIGERANT PIPING IN ACCORDANCE WITH SPECIFICATION SECTION 232300 “REFRIGERANT PIPING”.

12. INSTALL PIPING WITH ADEQUATE CLEARANCE BETWEEN PIPE AND ADJACENT WALLS AND HANGERS OR BETWEEN PIPES FOR INSULATION INSTALLATION.

13. INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR CEILING PANEL REMOVAL.

14. INSTALL PIPING ADJACENT TO EQUIPMENT TO ALLOW SERVICE AND MAINTENANCE.

15. INSTALL PIPING FREE OF SAGS AND BENDS.

16. INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH CONNECTIONS.

17. SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER THAN SYSTEM OPERATING PRESSURE.

18. ARRANGE PIPING TO ALLOW INSPECTION AND SERVICE OF REFRIGERATION EQUIPMENT. INSTALL VALVES AND SPECIALTIES IN ACCESSIBLE LOCATIONS TO ALLOW FOR SERVICE AND INSPECTION. INSTALL ACCESS DOORS OR PANELS AS SPECIFIED IN SECTION 083113 "ACCESS DOORS AND FRAMES" IF VALVES OR EQUIPMENT REQUIRING

MAINTENANCE IS CONCEALED BEHIND FINISHED SURFACES.

19. SLOPE REFRIGERANT PIPING IN ACCORDANCE WITH EQUIPMENT MANUFACTURER REQUIREMENTS.

20. WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS AND SIGHT GLASSES; ALSO REMOVE VALVE STEMS, SEATS, PACKING, AND ACCESSIBLE INTERNAL PARTS

OF REFRIGERANT SPECIALTIES. DO NOT APPLY HEAT NEAR EXPANSION-VALVE BULB.

21. IDENTIFY REFRIGERANT PIPING AND VALVES IN ACCORDANCE WITH SECTION 230553 "IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT." FOR GROUP A2L REFRIGERANTS, THE IDENTIFICATION SHALL ALSO INCLUDE THE FOLLOWING STATEMENT: “WARNING-RISK OF FIRE. FLAMMABLE REFRIGERANT.”

22. INSTALL SLEEVES FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS. COMPLY WITH REQUIREMENTS FOR SLEEVES SPECIFIED IN SECTION 230500 "COMMON

WORK RESULTS FOR HVAC."

23. INSTALL SLEEVE SEALS FOR PIPING PENETRATIONS OF CONCRETE WALLS AND SLABS. COMPLY WITH REQUIREMENTS FOR SLEEVE SEALS SPECIFIED IN SECTION 230500

"COMMON WORK RESULTS FOR HVAC."

24. INSTALL ESCUTCHEONS FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS. COMPLY WITH REQUIREMENTS FOR ESCUTCHEONS SPECIFIED IN SECTION 230500

"COMMON WORK RESULTS FOR HVAC."

25. PIPE JOINT CONSTRUCTION

A. REAM ENDS OF PIPES AND TUBES AND REMOVE BURRS.

B. REMOVE SCALE, SLAG, DIRT, AND DEBRIS FROM INSIDE AND OUTSIDE OF PIPE AND FITTINGS BEFORE ASSEMBLY.

C. SOLDERED JOINTS: CONSTRUCT JOINTS IN ACCORDANCE WITH ASTM B828 OR CDA'S "COPPER TUBE HANDBOOK."

D. BRAZED JOINTS: CONSTRUCT JOINTS IN ACCORDANCE WITH AWS BRH, "BRAZING HANDBOOK," CH. 35, "PIPE AND TUBING."

1) USE TYPE BCUP (COPPER-PHOSPHORUS) ALLOY FOR JOINING COPPER SOCKET FITTINGS WITH COPPER PIPE.

2) USE TYPE BAG (CADMIUM-FREE SILVER) ALLOY FOR JOINING COPPER WITH BRONZE OR STEEL.

27. INSTALLATION OF HANGERS AND SUPPORTS

A. COMPLY WITH SECTION 230529 "HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT" FOR HANGERS, SUPPORTS, AND ANCHOR DEVICES.

B. INSTALL THE FOLLOWING PIPE ATTACHMENTS:

1) ADJUSTABLE STEEL CLEVIS HANGERS FOR INDIVIDUAL HORIZONTAL RUNS LESS THAN 20 FT. (6 M) LONG.

2) ROLLER HANGERS AND SPRING HANGERS FOR INDIVIDUAL HORIZONTAL RUNS 20 FT. (6 M) OR LONGER.

3) PIPE ROLLER: MSS SP-58, TYPE 44 FOR MULTIPLE HORIZONTAL PIPING 20 FT. (6 M) OR LONGER, SUPPORTED ON A TRAPEZE.

4) SPRING HANGERS TO SUPPORT VERTICAL RUNS.

5) COPPER-CLAD HANGERS AND SUPPORTS FOR HANGERS AND SUPPORTS IN DIRECT CONTACT WITH COPPER PIPE.

D. INSTALL HANGERS FOR COPPER TUBING, WITH MAXIMUM HORIZONTAL SPACING AND MINIMUM ROD DIAMETERS, TO COMPLY WITH MSS SP-58, LOCALLY ENFORCED CODES, AND AUTHORITIES HAVING JURISDICTION REQUIREMENTS, WHICHEVER ARE MOST STRINGENT.

E. SUPPORT HORIZONTAL PIPING WITHIN 12 INCHES OF EACH FITTING.

F. SUPPORT VERTICAL RUNS OF COPPER TUBING TO COMPLY WITH MSS SP-58, LOCALLY ENFORCED CODES, AND AUTHORITIES HAVING JURISDICTION REQUIREMENTS, WHICHEVER ARE MOST STRINGENT.

REFRIGERANT EQUIPMENT INSTALLATION REQUIREMENTS

1. CODE COMPLIANCE: ASHRAE 15-2022.

2. REFRIGERATION SYSTEMS SHALL BE LISTED IN ACCORDANCE WITH UL 484 OR UL 60335-2-40/CSA C22.2 NO. 60335-2-40.

3. THE REFRIGERATION SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH ASHRAE 15-2022, THE LISTING, THE MANUFACTURER'S INSTRUCTIONS AND ANY MARKINGS ON THE EQUIPMENT

RESTRICTING THE INSTALLATION.

A. THE ASHRAE 15-2022 REQUIRED NAME PLATE, SHALL INCLUDE A SYMBOL INDICATING THAT A FLAMMABLE REFRIGERANT IS USED.

B. A LABEL INDICATING A FLAMMABLE REFRIGERANT IS INSTALLED, SHALL BE PLACED ADJACENT TO SERVICE PORTS AND OTHER LOCATIONS WHERE SERVICE INVOLVING COMPONENTS

CONTAINING REFRIGERANT IS PERFORMED.

4. EQUIPMENT SHALL HAVE A FACTORY INSTALLED REFRIGERANT DETECTION SYSTEM IN ACCORDANCE WITH ASHRAE 15-2022.

5. EQUIPMENT PRESSURE RELIEF DEVICES

A. DIFFERENT REFRIGERANTS SHALL NOT BE VENTED INTO A COMMON RELIEF PIPING SYSTEM.

B. PRESSURE RELIEF DEVICES DESIGNED TO DISCHARGE EXTERNAL TO THE REFRIGERATION SYSTEM SHALL BE ARRANGED TO DISCHARGE OUTSIDE OF THE BUILDING AND COMPLY WITH

ALL OF THE FOLLOWING:

1) THE POINT OF VENT DISCHARGE SHALL BE LOCATED NOT LESS THAN 15 FEET ABOVE THE ADJOINING GROUND LEVEL.

2) THE POINT OF VENT DISCHARGE SHALL BE LOCATED NOT LESS THAN 20 FEET FROM WINDOWS, BUILDING VENTILATION OPENINGS, PEDESTRIAN WALKWAYS ABOVE OR BELOW GRADE, PITS, RAMPS OR BUILDING EXITS. THE RELIEF VENT SHALL NOT DISCHARGE INTO AN ENCLOSED OUTDOOR SPACE SUCH AS A COURTYARD.

3) THE TERMINATION POINT OF A VENT DISCHARGE LINE SHALL BE MADE IN A MANNER THAT PREVENTS FOREIGN MATERIAL OR DEBRIS.

6. INSTALL VALVE AND SPECIALTY APPLICATIONS AS REQUIRED BY EQUIPMENT LISTING AND, MANUFACTURERS REQUIREMENTS AS FOLLOWS:

A. STOP VALVES SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS:

1) REFRIGERATION SYSTEM CONTAINING MORE THAN 6.6 POUNDS OF REFRIGERANT.

· THE SUCTION INLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.

· THE DISCHARGE OUTLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.

· THE OUTLET OF EACH LIQUID RECEIVER.

2) REFRIGERATION SYSTEMS CONTAINING MORE THAN 100 POUNDS OF REFRIGERANT.

· THE SUCTION INLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.

· THE DISCHARGE OUTLET OF EACH COMPRESSOR, COMPRESSOR UNIT OR CONDENSING UNIT.

· THE OUTLET OF EACH LIQUID RECEIVER.

· EACH INLET OF EACH LIQUID RECEIVER.

· EACH INLET AND EACH OUTLET OF EACH CONDENSER WHERE MORE THAN ON CONDENSER IS USED IN PARALLEL.

B. STOP VALVES SHALL BE SUPPORTED TO PREVENT STRESS AND STRAIN ON THE REFRIGERANT PIPING SYSTEM. THE PIPING SYSTEM SHALL NOT BE UTILIZED TO SUPPORT STOP VALVES

ON COPPER TUBING 1-INCH OUTSIDE DIAMETER OR LARGER.

C. STOP VALVES SHALL BE IDENTIFIED WHERE THEIR INTENDED PURPOSE IS NOT OBVIOUS. WHERE VALVES ARE IDENTIFIED BY A NUMBERING OR LETTERING SYSTEM, LEGEND(S) OR KEY(S) FOR THE VALVE IDENTIFICATION SHALL BE LOCATED IN THE ROOM CONTAINING THE INDOOR REFRIGERATION EQUIPMENT. THE MINIMUM HEIGHT OF LETTERING OF THE IDENTIFICATION

SHALL BE ½-INCH.

7. LIQUID-LEVEL-GAGE GLASS COLUMNS SHALL HAVE AUTOMATIC CLOSING SHUTOFF VALVES. ALL SUCH GLASS COLUMNS SHALL BE PROTECTED AGAINST EXTERNAL DAMAGE AND PROPERLY

SUPPORTED.

A. EXCEPTION: LIQUID-LEVEL-GAGE GLASSES OF THE BULL'S-EYE TYPE.

8. WHEN A PRESSURE GAGE IS PERMANENTLY INSTALLED ON THE HIGH SIDE OF A REFRIGERATING SYSTEM, ITS DIAL SHALL BE GRADUATED TO AT LEAST 1.2 TIMES THE DESIGN PRESSURE.

9. LIQUID RECEIVERS, OR PARTS OF A SYSTEM DESIGNED TO RECEIVE THE REFRIGERANT CHARGE DURING PUMP DOWN SHALL HAVE SUFFICIENT CAPACITY TO RECEIVE THE PUMP DOWN CHARGE. THE LIQUID SHALL NOT OCCUPY MORE THAN 90 PERCENT OF THE VOLUME WHEN TEMPERATURE OF THE REFRIGERANT IS 90 DEG F.

10. SERVICE PROVISIONS

A. ALL SERVICEABLE COMPONENTS OF REFRIGERATING SYSTEMS SHALL BE PROVIDED WITH SAFE ACCESS.

B. CONDENSING UNITS OR COMPRESSOR UNITS WITH ENCLOSURES SHALL BE PROVIDED WITH SAFE ACCESS WITHOUT THE NEED TO CLIMB OVER OR REMOVE ANY OBSTACLES OR TO USE

PORTABLE ACCESS DEVICES TO GET TO THE EQUIPMENT.

C. ALL SYSTEMS SHALL HAVE PROVISIONS TO HANDLE THE REFRIGERANT CHARGE FOR SERVICE PURPOSES. WHEN REQUIRED, THERE SHALL BE LIQUID AND VAPOR TRANSFER VALVES, A TRANSFER COMPRESSOR OR PUMP AND REFRIGERANT STORAGE TANKS OR APPROPRIATE VALVED CONNECTIONS FOR REMOVAL BY A RECLAIM, RECYCLE OR RECOVERY DEVICE.

11. SYSTEM CHARGING IN ACCORDANCE WITH ASHRAE 15-2022.

12. SYSTEM ADJUSTING IN ACCORDANCE WITH ASHRAE 15-2022.

REFRIGERANT DUCTWORK INSTALLATION REQUIREMENTS

1. CODE COMPLIANCE: ASHRAE 15-2022.

2. UNCLASSIFIED ELECTRICAL DEVICES SHALL NOT BE LOCATED WITHIN DUCTWORK.

3. DEVICES CONTAINING HOT SURFACES EXCEEDING 1290 DEGREES F SHALL NOT BE LOCATED IN DUCTWORK UNLESS THERE IS AN AVERAGE AIRFLOW VELOCITY NOT LESS THAN 200 FEET/MIN ACROSS THE HEATING DEVICE(S) AND THERE IS PROOF OF AIRFLOW BEFORE THE HEATING DEVICE(S) IS ENERGIZED. AVERAGE AIRFLOW VELOCITY SHALL BE DETERMINED BY

VOLUMETRIC AIRFLOW RATE DIVIDED BY DUCT FLOW RATE.

4. DUCT HEATERS SHALL BE SHUT DOWN BY A REFRIGERANT DETECTION SYSTEM. CONTRACTOR SHALL PROVIDE A REFRIGERANT DETECTION SYSTEM TO SHUTDOWN DUCT MOUNTED

HEATERS WHEN A REFRIGERANT LEAK IS SENSED.

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

RE

FR

IG

ER

AN

T N

O

TE

S

M002

NOT FOR BID

DIN

G

OR C

REFRIGERANT PIPING TEST AND INSPECTIONS

1. CODE COMPLIANCE: PIPING SHALL BE TESTED IN ACCORDANCE WITH ASHRAE 15-2022.

2. TESTING AGENCY: ENGAGE A QUALIFIED TESTING AGENCY TO PERFORM TESTS AND INSPECTIONS.

3. TESTS AND INSPECTIONS:

A. GENERAL. REFRIGERATING SYSTEMS FABRICATED, ASSEMBLED, OR ERECTED ON THE PREMISES SHALL BE TESTED TO THE APPLICABLE REQUIREMENTS OF THIS SECTION. TESTS SHALL INCLUDE BOTH THE HIGH SIDES AND LOW SIDES OF EACH SYSTEM. SYSTEM COMPONENTS THAT HAVE BEEN STRENGTH TESTED UNDER PRESSURE BY THE COMPONENT MANUFACTURER, FABRICATOR, OR ASSEMBLER ARE NOT REQUIRED TO BE STRENGTH TESTED AGAIN ON THE PREMISES UNLESS MODIFIED OR REPAIRED. LISTED EQUIPMENT NOT MODIFIED OR REPAIRED SHALL NOT BE REQUIRED TO BE STRENGTH TESTED ON THE PREMISES. AFTER INSTALLATION AND BEFORE BEING PLACED IN OPERATION, SYSTEM COMPONENTS NOT PREVIOUSLY STRENGTH TESTED SHALL BE STRENGTH TESTED UNDER PRESSURE IN ACCORDANCE WITH PIPING SYSTEM STRENGTH TEST BELOW. AFTER SUCCESSFUL COMPLETION OF THE REQUIRED STRENGTH TESTS AND BEFORE BEING PLACED IN OPERATION, SYSTEM COMPONENTS AND FIELD INSTALLED CONNECTIONS SHALL BE LEAK TESTED FOR TIGHTNESS IN ACCORDANCE WITH

LEAKAGE TEST BELOW.

B. REFRIGERANT PIPE AND JOINTS INSTALLED IN THE FIELD SHALL BE EXPOSED FOR VISUAL INSPECTION AND TESTING PRIOR TO BEING COVERED OR ENCLOSED.

C. TEST GASES. THE MEDIUM USED FOR FIELD PRESSURE TESTING THE REFRIGERANT SYSTEM SHALL BE ONE OF THE FOLLOWING INERT GASES: OXYGEN-FREE NITROGEN, HELIUM, ARGON OR PREMIXED NONFLAMMABLE OXYGEN-FREE NITROGEN WITH A TRACER GAS OF HYDROGEN OR HELIUM.

1) TEST GASES NOT PERMITTED. OXYGEN, AIR, REFRIGERANTS OTHER THAN THOSE IDENTIFIED ABOVE, COMBUSTIBLE GASES AND MIXTURES CONTAINING SUCH GASES SHALL NOT BE

USED AS THE TEST MEDIUM.

D. FIELD TEST APPARATUS. THE MEANS USED TO PRESSURIZE THE REFRIGERANT PIPING SYSTEM SHALL HAVE EITHER A PRESSURE-LIMITING DEVICE OR A PRESSURE-REDUCING DEVICE AND A TEST PRESSURE MEASURING DEVICE ON THE OUTLET SIDE. THE TESTS PRESSURE MEASURING DEVICE SHALL HAVE AN ACCURACY OF +/-3 PERCENT OR LESS OF THE TEST

PRESSURE AND SHALL HAVE A RESOLUTION OF 3 PERCENT OR LESS OF THE TEST PRESSURE.

E. PIPING SYSTEM STRENGTH TEST. REFRIGERATING SYSTEM COMPONENTS AND REFRIGERANT PIPING SHALL BE TESTED IN ACCORDANCE WITH ASME B31.5 OR THIS SECTION. SEPARATE TESTS FOR ISOLATED PORTIONS OF THE SYSTEM ARE PERMITTED, PROVIDED THAT ALL REQUIRED PORTIONS ARE TESTED AT LEAST ONCE. PRESSURIZE WITH TEST GAS FOR A MINIMUM OF 10 MINUTES TO NOT LESS THAN THE LOWER OF (A) THE LOWEST DESIGN PRESSURE FOR ANY SYSTEM COMPONENT OR (B) THE LOWEST VALUE OF SET PRESSURE FOR ANY PRESSURE RELIEF DEVICES IN THE SYSTEM. THE DESIGN PRESSURES FOR DETERMINATION OF TEST PRESSURE SHALL BE THE PRESSURE IDENTIFIED ON THE LABEL NAMEPLATE OF THE CONDENSING UNIT, COMPRESSOR, COMPRESSOR UNIT, PRESSURE VESSEL OR OTHER SYSTEM COMPONENT WITH A NAMEPLATE. A PASSING TEST RESULT SHALL HAVE NO RUPTURE OR STRUCTURAL FAILURE OF ANY SYSTEM COMPONENT OR REFRIGERANT PIPING. PRESSURE RELIEF DEVICES MAY NEED TO BE TEMPORARILY REMOVED AND REPLACED WITH PLUGS

DURING THE STRENGTH TEST.

F. LEAKAGE TEST. THE LEAK TEST SHALL BE IN ACCORDANCE WITH ASHRAE STANDARD 147, ASME B31.5, OR THIS SECTION.

1) LEAK TESTING PROTOCOL. AFTER THE TIME TO COMPLETE THE STRENGTH TEST, CONTINUE TO PRESSURE TEST IN ACCORDANCE WITH PIPING SYSTEM STRENGTH TEST ABOVE FOR A MINIMUM PERIOD AS SPECIFIED IN THE FOLLOWING TABLE, DURATION OF LEAK TEST. THE SYSTEM SHALL SHOW NO LOSS IN PRESSURE ON THE PRESSURE MEASURING DEVICE DURING THE PRESSURE TEST. CALCULATION OF THE PRESSURE DIFFERENTIAL BASED ON A CHANGE IN AMBIENT TEMPERATURE SHALL BE PERMITTED. A VACUUM OF 0.0097 PSI ABSOLUTE OR LOWER SHALL BE ACHIEVED. AFTER ACHIEVING A VACUUM, THE SYSTEM SHALL BE ISOLATED FROM THE VACUUM PUMP. THE SYSTEM PRESSURE SHALL NOT RISE ABOVE 0.029 PSI ABSOLUTE FOR A MINIMUM PERIOD AS SPECIFIED IN THE FOLLOWING TABLE, DURATION OF LEAK TEST. THE VACUUM PUMP SHOULD GRADUALLY CREATE A

VACUUM TO AVOID FREEZING OF ANY MOISTURE IN THE PIPING SYSTEM.

DURATION OF LEAK TEST

NOTE: THE MAXIMUM PIPE SIZE IS THE LARGEST INTERCONNECTING FIELD PIPING INSTALLED.

G. CONTRACTOR DECLARATION. THE INSTALLING CONTRACTOR SHALL ISSUE A CERTIFICATE OF TEST, VERIFYING STRENGTH TEST IN ACCORDANCE WITH PIPING SYSTEM STRENGTH TEST, AND LEAKAGE TEST IN ACCORDANCE WITH LEAKAGE TEST, TO THE AHJ FOR ALL SYSTEMS CONTAINING 55 LB OR MORE OF REFRIGERANT. THE CERTIFICATE SHALL GIVE THE TEST DATE, PHOTOGRAPH OF THE PRESSURE GAGE AT THE TEST PRESSURE, REFRIGERANT DESIGNATION, TEST MEDIUM, AND THE FIELD TEST PRESSURE APPLIED TO THE HIGH SIDE AND THE LOW SIDE OF THE SYSTEM. THE CERTIFICATION OF TEST SHALL BE SIGNED BY THE INSTALLING CONTRACTOR AND SHALL BE MADE PART OF THE PUBLIC RECORD.

LEAK TEST

PRESSURE

TEST

VACUUM

TEST

PIPE LENGTH,

L (FEET)

MAXIMUM PIPE

SIZE (INCH)

MINIMUM PERIOD

OF TEST (HOURS)

L <= 100 3

4 OR LESS 0.25

1 TO 3 1

GREATER THAN 3 24

3 OR LESS 1

GREATER THAN 3 24

ANY 24

100 < L <= 200

200 < L

L <= 100 3

4 OR LESS 1

1 TO 3 8

GREATER THAN 3 24

3 OR LESS 8

GREATER THAN 3 24

ANY 24

100 < L <= 200

200 < L

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

RE

FR

IG

ER

AN

T N

O

TE

S

M003

NOT FOR BID

DIN

G

OR C

D

W V

W V

W V

W V

EX. 6" W

M

WV

D

W V

W V

WV

W V

EEREER

W

58.5

59.5

S

S

S

S

C/OC/O

C/O

C/O

S

IRR M

WM

WM

WM

WMWMWM

MD002

RX RS/L BELOW

GRADE WITHIN

CARRIER PIPE,

TYP OF 2 SETS

RX CARRIER PIPE

BELOW GRADE

RX RS/L, TYP

OF 2 SETS.

RX 4" CS ABOVE /

RX 3" CS BELOW

RX 2-1/2" CR ABOVE /

RX 2" CR BELOW

RX VENT PIPE TO

BELOW GRADE

RX FOS/R DN

RX CR DN

RX CS DN

RX RS/L DN,

TYP OF 2 SETS

RX GENERATOR

RX FUEL OIL TANK

RX COOLING TOWER

EX ACCU

EX ACCU

RX CS DN

1 2

RX CARRIER PIPE

RX RS/L BELOW

GRADE WITHIN

CARRIER PIPE,

TYP OF 2 SETS

RX CARRIER PIPE

BELOW GRADE

RX 4" CS

RX 2-1/2" CR

RX 3" CS

RX 2" CR

RX PIPING BELOW GRADE

TO COOLING TOWER

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

MD002

MECHANICAL SITE PLAN - DEMOLITION

1" = 20'-0" N

SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION

RX ALL ASSOCIATED SUPPORTS, CONTROLS, WIRING, ETC.

SEE DRAWING MD301 FOR CONTINUATION.

TEMPORARILY REMOVE AND SALVAGE EXISTING ACCU TO ALLOW FOR

EQUIPMENT YARD SLAB REMOVAL. REINSTALL EXISTING ACCU AS SHOWN

ON DRAWING M002.

EXISTING SHOWN WITH LIGHT WEIGHT LINE,

DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS

HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD

OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN

DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO

FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE

DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE

PROCEEDING WITH THE WORK.

EXISTING TO REMAIN VRF SYSTEM AND SPLIT SYSTEM UTILIZE R-410A

REFRIGERANT.

1.

2.

3.

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

M

EC

HA

NI

CA

L S

ITE

P

LA

N

- D

EM

O

LIT

IO

N

MAV

0 10 40 80 FT20

1" = 20' - 0"

MD002

EQUIPMENT YARD - MECHANICAL - DEMOLITION PART PLAN

1/4" = 1'-0" N

0 2 8 12 FT4

1/4" = 1' - 0"

MD002

4.

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

AutoCAD SHX Text T

COURTROOM

OFFICE 10

OFFICE 9

OFFICE 8

OFFICE 13

OFFICE 12

LOBBY

VAULTELEV.

T

T

OFFICE 11

T

T

T

RX DUCTWORK, TYP

RX

RX EA LOUVER

RX

RX EF

RX EA LOUVER

RX EF

RX

RX

RX LOUVER

RX

RX DUCTWORK, TYP

RX LOUVER

CRAWL SPACE

CRAWL SPACE

CRAWL SPACE

BASEMENT

OFFICE

OFFICE

OFFICE

OFFICE

OLD LAW LIBRARY

OFFICE

ELEV.

OFFICE

T

T

MECHANICAL

MECHANICAL

KITCHEN

CELL 1

CELL 2

LAV.

WOMEN

MEN

SECURITY/

SURVEILLANCE

OFFICE

OFFICE

OFFICE

BACK-UP 911 CENTER

IT

SAFE

EX FCU

EX FCU

EX FCU

EX FCU

1 1

1 1

EX FCU

EX

RX DUCTWORK, TYP

EX

RX DUCTWORK, TYP

MD300

COURTROOM

OFFICE

ELEV.

T

JURY

CONFERENCE

JUDGE'S

CHAMBER

T

T

RX 18x12 EA

LOUVER

RX

1 1

RX EF, TYP

1 1

RX

RX

RX DUCTWORK, TYP

RX DUCTWORK, TYP

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

MD100

GROUND LEVEL - DUCTWORK - DEMOLITION PLAN

1/8" = 1'-0"

0 4 16 24 FT8

1/8" = 1' - 0"N

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

DU

CT

W O

RK

D

EM

O

LIT

IO

N

PL

AN

MD100

LOWER LEVEL - DUCTWORK - DEMOLITION PLAN

1/8" = 1'-0" N

RX AIR DEVICE

RX 10x14 SA DN, RX 10x18 SA DN, RX 48x18 SA DN, RX 10x18 SA DN, RX 16x14 SA DN, RX 44x18 RA DN

RX 10x18 SA UP, RX 48x18 SA UP, RX 10x18 SA UP, RX 44x18 RA UP

RX 10x18 SA DN, RX 48x18 SA UP/DN, RX 10x18 SA DN, RX 44x18 RA DN

TEMPORARILY REMOVE AND SALVAGE EXISTING FCU TO ALLOW FOR NEW

CEILING INSTALLATION. REINSTALL EXISTING FCU AS SHOWN ON DRAWING

M100.

PATCH AND SEAL EXISTING WALL OPENING TO MAKE AIR AND WATER TIGHT.

SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

MD100

UPPER LEVEL - DUCTWORK - DEMOLITION PLAN

1/8" = 1'-0" N

EXISTING SHOWN WITH LIGHT WEIGHT LINE,

DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS

HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD

OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN

DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO

FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE

DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE

PROCEEDING WITH THE WORK.

1.

2.

3.

MAV

MD100

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

30 x x 68

RX DUCTWORK, TYP

RX 48x18 SA DN

25 5

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

MD101

ATTIC LEVEL - DUCTWORK - DEMOLITION PLAN

1/8" = 1'-0" 0 4 16 24 FT8

1/8" = 1' - 0"N

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

DU

CT

W O

RK

D

EM

O

LIT

IO

N

PL

AN

MD101

ROOF - DUCTWORK - DEMOLITION PLAN

1/8" = 1'-0" N

RX AIR DEVICE

RX ATTIC VENTILATION FAN

RX EXHAUST FAN

RX DUCT DN TO AIR DEVICE

PATCH AND SEAL EXISTING ROOF OPENING TO MAKE AIR AND WATER TIGHT.

SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS

HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD

OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN

DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO

FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE

DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE

PROCEEDING WITH THE WORK.

1.

2.

MAV

MD101

NOT FOR BID

DIN

G

OR C

COURTROOM

OFFICE 10

OFFICE 9

OFFICE 8

OFFICE 11

OFFICE 13

OFFICE 12

LOBBY

VAULTELEV. 1

RX ACCU

RX FCU

CRAWL SPACE

CRAWL SPACE

CRAWL SPACE

BASEMENT

MECHANICAL

MECHANICAL

KITCHEN

CELL 1

CELL 2

OFFICE

LAV.

SECURITY/SURVEILLANCE

OFFICE

OFFICE

OFFICE

OFFICE

OLD LAW LIBRARY

SAFE

IT

BACK-UP 911 CENTER

OFFICE

OFFICE OFFICE

OFFICE

WOMEN

MEN

ELEV.

OFFICE

EX FCU

EX FCU

EX FCU

EX FCU

EX FCU

MD301

EX RS/L, TYP

OF 2 SETS

EX RS/L

EX RS/L

COURTROOM

JURY CONFERENCE

OFFICE

JUDGE'S CHAMBER

HOLDING CELL

ELEV.

1 1

RX ELEC HEATER

RX ELEC HEATER

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

MD200

GROUND LEVEL - MECHANICAL PIPING - DEMOLITION PLAN

1/8" = 1'-0"

0 4 16 24 FT8

1/8" = 1' - 0"N

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

M

EC

HA

NI

CA

L P

IPI

NG

D

EM

O

LIT

IO

N

PL

AN

MD200

LOWER LEVEL - MECHANICAL PIPING - DEMOLITION PLAN

1/8" = 1'-0" N

RX RADIATOR INCLUDING ALL ASSOCIATED PIPING AND CONTROLS.

RX STM/STM COND UP/DN

TEMPORARILY REMOVE AND SALVAGE EXISTING FCU TO ALLOW FOR NEW

CEILING INSTALLATION. REINSTALL EXISTING FCU AS SHOWN ON DRAWING

M100.

PATCH AND SEAL EXISTING WALL OPENING TO MAKE AIR AND WATER TIGHT.

SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

MD200

UPPER LEVEL - MECHANICAL PIPING - DEMOLITION PLAN

1/8" = 1'-0" N

EXISTING SHOWN WITH LIGHT WEIGHT LINE,

DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS

HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD

OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN

DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO

FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE

DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE

PROCEEDING WITH THE WORK.

1.

2.

3.

MAV

MD200

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

RX AHU-1

RX AHU-2

OFFICELAV.

CELL 2

CELL 1

KITCHEN

MECHANICAL

MECHANICAL

MEN

WOMEN

1 1

RX EF

RX EF

RX FAN

RX DUCTWORK, TYP

RX DUCTWORK, TYP

ELEV.

CRAWL SPACE

CRAWL SPACE

BASEMENT

CRAWL SPACE

TRX

RX DUCTWORK, TYP

RX 12x12 UP

RX PLENUMRX EA DUCT UP

MD300

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

M

EC

HA

NI

CA

L P

AR

T P

LA

NS

DE

M O

LIT

IO

N

MD300

LOWER LEVEL - DUCTWORK - DEMOLITION PART PLAN

1/4" = 1'-0" N

0 2 8 12 FT4

1/4" = 1' - 0"

DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS

HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD

OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN

DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO

FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE

DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE

PROCEEDING WITH THE WORK.

1.

2.

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

MAV

RX AIR DEVICE

RX 48x64 RA LOUVER BETWEEN MECHANICAL ROOM AND CORRIDOR.

RX 106x22 OA LOUVER TO EXTERIOR

RX RELIEF LOUVER TO EXTERIOR

RX 10x14 SA UP, RX 10x18 SA UP, RX 48x18 SA UP, RX 10x18 SA UP, RX 16x14 SA UP, RX 44x18 RA UP

RX 12x12 OED

RX RETURN AIR DUCT TO EXISTING SHAFT AND UP THROUGH SHAFT.

RX ALL ASSOCIATED CONCRETE PADS, SUPPORTS, CONTROLS, WIRING, ETC

MD300

MD300

LOWER LEVEL - EX OA LOUVER SECTION

1/4" = 1'-0"

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

OFFICELAV.

CELL 2

CELL 1

KITCHEN MECHANICAL

MECHANICAL

MEN

WOMEN

ELEV.

CRAWL SPACE

CRAWL SPACE

BASEMENTCRAWL SPACE

RX 4" CS ABOVE /

RX 3" CS BELOW

RX 3" CS ABOVE /

RX 2-1/2" CR BELOW

RX STM

COND PUMP

RX BOILER

RX RS/L

RX CONDENSER

WATER PUMP

RX CHEMICAL

TREATMENT

RX STM TO

DOMESTIC HW

CONVERTER

RX CONDENSER

WATER PUMP

RX RS/L

RX CHILLER-1RX AIR

COMPRESSOR

RX AHU-1

RX AHU-2

RX CHILLER-2

RX STM/STM COND

RX CS/RRX CS/R

RX STM/STM COND

RX RS/L, TYP

OF 2 SETS

EX RS/L

EX RS/L, TYP OF 2 SETS

RX CARRIER

PIPE

3 3

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

M

EC

HA

NI

CA

L P

AR

T P

LA

NS

DE

M O

LIT

IO

N

MD301

LOWER LEVEL - MECHANICAL PIPING - DEMOLITION PART PLAN

1/4" = 1'-0" N

0 2 8 12 FT4

1/4" = 1' - 0"

EXISTING SHOWN WITH LIGHT WEIGHT LINE,

DEMOLITION WORK SHOWN WITH HEAVY WEIGHT DASHED LINE,

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS

HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD

OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN

DETAIL OR DIMENSION. VERIFY THE ACTUAL EXISTING CONDITIONS PRIOR TO

FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITONS BE

DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED,

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE

PROCEEDING WITH THE WORK.

EXISTING TO REMAIN VRF SYSTEM AND SPLIT SYSTEM UTILIZE R-410A

REFRIGERANT.

1.

2.

3.

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

MAV

RX ALL ASSOCIATED PIPING THROUGHOUT ENTIRE BUILDING

RX STM/STM COND UP TO RADIATOR

RX ALL ASSOCIATE HOUSEKEEPING PADS, SUPPORTS, WIRING,

CONTROLS, ETC.

RX FLUE UP THROUGH CHIMNEY.

MD301

4.

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

AutoCAD SHX Text 30 x x 68

D

W V

W V

W V

W V

W V

EX. 6" W

M

WV

D

W V

W V

WV

W V

EEREER

W

58.5

59.5

S

S

S

S

C/OC/O

C/O

C/O

S

IRR M

WM

WM

WM

WMWMWM

M002

GENERATOR 1

HRU-2

HRU-3

HRU-1

EX ACCU

EX ACCU

RS/L DN TO BASEMENT,

TYP OF 9 SETS. SEE DRAWING

M301 FOR CONTINUATION

RACK RS/L PIPING

ALONG WALL, TYP

GENERATOR

DOCKING STATION 1

ACCU-2

ACCU-1

ACCU-3

ACCU-4

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

M004

MECHANICAL SITE PLAN - NEW WORK

1" = 20'-0" N

SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION

MOUNT ON 4" CONCRETE PAD

PROVIDE PIPE HOOD ASSEMBLY FOR REFRIGERANT LINES. DOGHOUSE /

PIPE PENETRATIONS SHALL BE AIR AND WATER TIGHT. SEE DETAIL ON

DRAWING M501 FOR MORE INFORMATION.

FOLLOWING COMPLETION OF ASSOCIATED PIPING MODIFICATION

RE-CHARGE SYSTEM AND MAKE OPERATIONAL. THIS SYSTEM UTILIZES

R-410A REFRIGERANT

REINSTALL EXISTING ACCU IN THIS LOCATION. RELOCATE/REPLACE

ASSOCIATED REFRIGERANT PIPING AS NECESSARY. RE-CHARGE SYSTEM

AND RECONNECT TO EXISTING PIPING, WIRING, CONTROLS, ETC TO MAKE

SYSTEM FULLY OPERATIONAL. THIS SYSTEM UTILIZES R-410A

REFRIGERANT.

EXISTING SHOWN WITH LIGHT WEIGHT LINE,

NEW WORK SHOWN WITH HEAVY WEIGHT LINE,

ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,

MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.

EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF

VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR

TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS

REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR

RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.

1.

2.

3.

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

M

EC

HA

NI

CA

L S

ITE

P

LA

N

- N

EW

W O

RK

MAV

M004

EQUIPMENT YARD - MECHANICAL - NEW WORK PART PLAN

1/4" = 1'-0" N

0 10 40 80 FT20

1" = 20' - 0"

0 2 8 12 FT4

1/4" = 1' - 0"

M004

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

T

TBREAK AREA

STAIRS

ELEV. LOBBY

LOBBY

ORPHAN'S COURTROOM

RECEPTION

RECORDS

CORRIDOR

R.O.W. OFFICE

CHIEF DEPUTY

DEPUTY

ELEV

13 UNISEX

UNISEX

OFFICE OF THE

CLO.

109A

REGISTER OF WILLS

10x6 D-2, 210 CFM

10x8 D-2, 255 CFM

24x24 R-4, 1,010 CFM

14x16 OA UP/DN

8x4 R-3, 75 CFM

8x4 R-3, 75 CFM

12x8 D-2, 330 CFM

8x4 EA DN

8x4 EA DN

10x16 EA UP/DN

10x8 D-2, 255 CFM

12x8 D-2, 350 CFM

12x8 D-2, 350 CFM

12x8 D-2, 350 CFM

12x8 D-2, 350 CFM

18x10 R-2, 575 CFM

14x26 R-4, 640 CFM

AHU-2.2

AHU-2.1

8x6 D-2, 160 CFM

8x4 D-2, 90 CFM

AHU-2.3

14x6 D-2, 275 CFM

12x8 D-2, 340 CFM

14x6 D-2, 265 CFM

14x6 D-2, 265 CFM

10x8 D-2, 225 CFM

10x6 R-2, 210 CFM

12x24 R-4, 495 CFM

AHU-2.4

12x8 R-2, 315 CFM

16x8 RA DN 12x8 RA DN

24x8 RA DN

10x8 D-2, 255 CFM

T

T

T

T

TT

T T

T

MECHANICAL

MEN'S

WOMEN'S

J.C.

ELEV.

BSMT. / MECH.

ROOM

CORRIDOR

SECONDARY PSAP

I.T.

20A

MEETING ROOM

OPEN OFFICE AREA

ELECTRICAL

SPRINKLER

VAULT

22A

OPEN OFFICE AREA

OFFICE

OFFICE

BREAK

I.T.

UT

ILI

TY

TU

NN

EL

A

MECHANICAL/STORAGE

MACHINE

STAIRS

CRAWL SPACE

CLO.

LOWER LOBBY

CRAWL

CRAWL SPACE

SPACE CRAWL SPACE

MECH. CL.

30A

1 ACU-1

1 1

AHU-1.10

FCU-1.8

M300

EX

EX

EX FCU

EX FCU

EX FCU

EX FCU

EX FCU

FCU-1.5A

FCU-1.5B

FCU-1.5C

FCU-1.6

FCU-1.7A

FCU-1.7B

FCU-1.9A

FCU-1.9B

10"ø D-1, 390 CFM

14x10 OA

10x6 4x4

8x8 6x8

8x8

AHU-1.4

10"ø

6"ø D-1, 140 CFM

6"ø D-1, 140 CFM

8x8

8x8 RA OED

6"ø

6"ø

6"ø

6"ø

4"ø

6"ø 6"ø

20 21

10x6

6x8

14x10

T ACU-1

FCU-1.6

FCU-1.7A, FCU-1.7B

FCU-1.9A,

FCU-1.9B

AHU-1.10

FCU-1.8

6"ø D-1, 110 CFM

10x6

6"ø D-1, 110 CFM

6"ø D-1, 110 CFM

6"ø D-1, 110 CFM

6"ø D-1, 110 CFM

6"ø D-1, 110 CFM

6"ø D-1, 110 CFM

6"ø D-1, 110 CFM

T

T

T

UPPER LOBBY

COURTROOM

CONFERENCE

200A

ELEV. LOBBY

STAIRS

JUDGE'S CHAMBER

REST LOBBY

UNISEX

UNISEX

ELEV

TOILET

205A

CLOSET

205B

T

10"ø D-3, 365 CFM

12x8 RA UP

12x10 EA UP

30x18 R-4, 920 CFM

30x18 R-4, 605 CFM

14x16 OA UP/DN 10x16 EA UP/DN18x8 D-4, 440 CFM

26x22 R-4, 920 CFM

8x8 D-4, 180 CFM

12x6 D-4, 230 CFM

12x12 D-4, 470 CFM

12x10 D-4, 375 CFM

12x10 D-4, 385 CFM

AHU-3.4

AHU-3.2

AHU-3.3

AHU-3.1

26x6 RA UP

8x16 RA UP

10"ø D-3, 370 CFM

10"ø D-3, 370 CFM

10"ø D-3, 365 CFM

10"ø D-3, 340 CFM

10"ø D-3, 340 CFM

10"ø D-3, 340 CFM

10"ø D-3, 340 CFM

16x30 R-4, 775 CFM 3

TAHU-3.5

36 4x4 OA, 10x6 EA 37

6x6 OA

6x6 OA UP

4x4 OA UP, 10x6 EA UP

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

M100

GROUND LEVEL - DUCTWORK - NEW WORK PLAN

1/8" = 1'-0"

0 4 16 24 FT8

1/8" = 1' - 0"

N

EXISTING SHOWN WITH LIGHT WEIGHT LINE,

NEW WORK SHOWN WITH HEAVY WEIGHT LINE,

ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,

MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.

EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF

VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR

TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS

REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR

RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.

IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR

DEVICE NECK SIZE.

DO NOT CUT ANY JOISTS WITHOUT APPROVAL FROM STRUCTURAL ENGINEER.

1.

2.

3.

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

DU

CT

W O

RK

N

EW

W

O

RK

P

LA

N

M100

LOWER LEVEL - DUCTWORK - NEW WORK PLAN

1/8" = 1'-0" N

22x22 G-1

12x10 R-5, 410 CFM

12x10 R-5, 365 CFM

6x4 INTERNALLY LINED TRANSFER DUCT

6x6 INTERNALLY LINED TRANSFER DUCT

8x6 INTERNALLY LINED TRANSFER DUCT

8x8 INTERNALLY LINED TRANSFER DUCT

10x8 INTERNALLY LINED TRANSFER DUCT

12x8 INTERNALLY LINED TRANSFER DUCT

10x6 R-5, 160 CFM

12x6 R-5, 210 CFM

12x12 R-5, 425 CFM

ACCESS HATCH TO ATTIC

MOUNT TOP OF REGISTER APPROXIMATELY 8" BELOW CEILING

MOUNT ABOVE DOOR

VD, 65 CFM

VD, 70 CFM

VD, 125 CFM

VD, 15 CFM

VD, 45 CFM

VD, 50 CFM

VD, 35 CFM

VD, 195 CFM

REINSTALL EXISTING FCU IN THIS LOCATION. RECONNECT TO EXISTING

PIPING, WIRING, CONTROLS, ETC TO MAKE SYSTEM FULLY OPERATIONAL.

RELOCATE/REPLACE ASSOCIATED REFRIGERANT PIPING AS NECESSARY.

THIS SYSTEM UTILIZES R-410A REFRIGERANT.

THIS THERMOSTAT SHALL CONTROL FCU-1.15A, 1.15B, AND 1.15C.

MOUNT BOTTOM OF REGISTER APPROXIMATELY 10" AFF.

VD, 280 CFM

VD, 200 CFM

6x6 D-4, 60 CFM

NOT USED

NOT USED

6x6 R-1, 75 CFM

24x12 G-4

32x12 G-4

MOUNT ON STAND. SEE FAN COIL UNIT - VERTICAL DETAIL ON DRAWING M502.

10"x10" A2L REFRIGERANT ENCLOSURE SYSTEM. SEE SPECIFICATION

SECTION 232310.

SEE DRAWING M101 FOR CONTINUATION.

VD, 250 CFM

24" LONG INSULATED PLENUM. WIDTH AND HEIGHT SHALL MATCH FCU

CONNECTION SIZE

48"L x 12"H x 2"D FILTER RACK

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

M100

UPPER LEVEL - DUCTWORK - NEW WORK PLAN

1/8" = 1'-0" N

4.

5.

MAV

M100

NOT FOR BID

DIN

G

OR C

ONSTRUCTIO

N

AutoCAD SHX Text 1 "38"

AutoCAD SHX Text

K-PR5452-T1D

AutoCAD SHX Text

URINAL

AutoCAD SHX Text

K-PR5452-T1D

URINAL

UH-1

14x16 OA DN 10x16 EA DN

ERV-2

FC

UH-4

UH-2

16x8 RA DN12x12 RA DN

26x6 RA DN

AHU-3.3

FC

FC

FC

FC

FC

FC

12x14 EA

FC

14x14 OA

MOD

MOD

12x14 EA

14x16 OA

12x14 EA

AHU-3.2

AHU-3.1

AHU-3.4

18x6

12x8

12x6

12x8

8x6

16x6

10x8 OA

12x8 OA

6x6 OA DN

6x6 OA

8x4 OA

14x16 OA 8

ATTIC

M401

M401

M401

10x6 RA

14x6

SS

FAN-1

FCFC

MOD

MOD

10x16 EA 8x8 EA

8x8 EA

12x12 RA

FC

FCU-3.6

FCU-3.7

FCU-3.9

FCU-3.8

MOD

12x12 8x8 SA DN

12x6 SA DN

10x6 RA DN

12x6 EA DN

12x12 SA DN

12x8

12x12 RA DN

18x8 SA DN

10x6 EA

12x10 RA DN

12x10 SA DN

4x4 OA

6x6 EA DN

6x6 EA DN

8x4

8x412x6

12x10 RA DN 12x14 4x4 OA DN

6x10 EA DN

12x10

EA DN

18x8 SA DN

10"ø SA DN

10"ø SA DN

10"ø SA DN

10"ø SA DN

16x8

16x8 RA

6x6 12X12

10"ø

SA DN

10"ø SA DN

10"ø SA DN

10"ø SA DN

14x14

18x6 20x8

BS-3.1

BS-3.2

FC

FC

FC

12x8

14X6

12x8

14x6

M401

8x8 OA

12X12 SA

14x14

AHU-3.5

11 12

M400

M401

12x8 RA

6x4

14x16

14x16 OED

14x16 OED17

UH-3

R

D

DR

R

D

D

R

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

M101

ATTIC - DUCTWORK - NEW WORK PLAN

1/4" = 1'-0" N

NEW WORK SHOWN WITH HEAVY WEIGHT LINE,

ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,

MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.

EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF

VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR

TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS

REQUIREMENT AND CONTRACT DRAWINGS IN WRITING TO THE OWNER FOR

RESOLUTION AND AWAIT WRITTEN DIRECTIONS BEFORE PROCEEDING W/ WORK.

IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR

DEVICE NECK SIZE.

1.

2.

3.

(APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES:

DU

CT

W O

RK

N

EW

W

O

RK

P

LA

N

ACCESS HATCH. KEEP CLEAR

24" LONG INSULATED PLENUM. WIDTH AND HEIGHT SHALL MATCH FCU

CONNECTION SIZE

26"L x 16"H x 14"D EA PLENUM

ABOVE:22" DEEP INSULATED OA PLENUM. WIDTH AND HEIGHT SHALL

MATCH ERV CONNECTION SIZE

BELOW:22" DEEP INSULATED EA PLENUM. WIDTH AND HEIGHT

SHALL MATCH ERV CONNECTION SIZE

28" LONG INSULATED PLENUM. WIDTH AND HEIGHT SHALL MATCH FCU

CONNECTION SIZE

INSTALL TIGHT TO STRUCTURE ABOVE

DUCT DOWN FROM MAIN ATTIC SPACE

INSTALL AT FLOOR LEVEL

TERMINATE 8x8 EA OED WITH FIRE DAMPER WITHIN REFRIGERANT

ENCLOSURE SYSTEM

VD, 110 CFM

VD, 495 CFM

VD, 90CFM

VD, 45 CFM

MOUNT ON ATTIC FLOOR. PROVIDE DRAIN PAN BENEATH UNIT. SEE FAN

COIL UNIT - HORIZONTAL - ATTIC DETAIL ON DRAWING M502.

SUPPORT FROM ATTIC STRUCTURE

MOUNT TO CHIMNEY STRUCTURE

PROVIDE BIRD SCREEN

MOUNT ON ATTIC FLOOR WITH VIBRATION ISOLATOR PER SPECIFICATION

SECTION 230548

TERMINATE DUCT WITHIN CHIMNEY WITH OED. PROVIDE BIRDSCREEN

SEE DRAWING M100 FOR CONTINUATION

48"L x 12"H x 2"D FILTER RACK

(APPLICABLE TO THIS DRAWING ONLY)SPECIAL NOTES:

MAV

M1010 2 8 12 FT4

1/4" = 1' - 0"

NOT FOR BID

DIN

G

OR C

BREAK AREA

STAIRS

ELEV. LOBBY

LOBBY

ORPHAN'S COURTROOM

RECEPTION

RECORDS

CORRIDOR

R.O.W. OFFICE

CHIEF DEPUTY

DEPUTY

ELEV

UNISEX

UNISEX

OFFICE OF THE

CLO.

109A

REGISTER OF WILLS

RS/L UP/DN1

MECHANICAL

MEN'S

WOMEN'S

J.C.

ELEV.

BSMT. / MECH.

ROOM

CORRIDOR

SECONDARY PSAP

I.T.

20A

MEETING ROOM

OPEN OFFICE AREA

ELECTRICAL

SPRINKLER

VAULT

22A

OPEN OFFICE AREA

OFFICE

OFFICE

BREAK

I.T.

UT

ILI

TY

TU

NN

EL

A

MECHANICAL/STORAGE

MACHINE

STAIRS

CRAWL SPACE

CLO.

LOWER LOBBY

CRAWL

CRAWL SPACE

SPACE CRAWL SPACE

MECH. CL.

30A

EX FCU

EX FCU

EX FCU

EX FCU

M301

EX RS/L, TYP

OF 2 SETS

EX FCU

EX RS/L

RS/L

RS/L

ACU-1

AHU-1.10

FCU-1.5A

FCU-1.5B

FCU-1.5C

FCU-1.6

FCU-1.7A

FCU-1.7B

FCU-1.9A

FCU-1.9B

EX RS/L

RS/L

RS/L

FCU-1.8

UPPER LOBBY

COURTROOM

CONFERENCE

200A

ELEV. LOBBY

STAIRS

JUDGE'S CHAMBER

REST LOBBY

UNISEX

UNISEX

ELEV

TOILET

205A

CLOSET

205B

RS/L UP/DN

2 SETS OF RS/L UP2 SETS OF RS/L UP

SEE M201 FOR CONTINUATION SEE M201 FOR CONTINUATION

Torchio Architects, Inc.

COPYRIGHT C

Project Number:

Date:

Revisions:

Drawn By:

Sheet:

A2112

Q

AC

H

IST

O

RIC

C O

UR

TH

O

US

E R

EN

O

VA

TIO

N

0 C

O

UR

TH

O

US

E S

Q

UA

RE

CE

NT

RE

VI

LL

E, M

AR

YL

AN

D

06.05.26

PROGRESS SET

NOT FOR CONSTRUCTION

M200

GROUND LEVEL - MECHANICAL PIPING - NEW WORK PLAN

1/8" = 1'-0"

0 4 16 24 FT8

1/8" = 1' - 0"N

EXISTING SHOWN WITH LIGHT WEIGHT LINE,

NEW WORK SHOWN WITH HEAVY WEIGHT LINE,

ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING,

MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE.

EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF

VALVES, FILTERS, STRAINERS,…