Hawaii/Maui
Job Corps Center Makawao, Maui, HI
Facility Planning Report Volume II
Supporting Data
Final June 2009
Department of Labor/ Office of Job Corps
Hawaii/Maui
Job Corps Center Makawao, Maui, HI
Facility Planning Report Volume II
Supporting Data
Final June 2009
Oahu Female Dorm Building 9
• Building Condition by Function
• Building Condition Site Plan
VOLUME II - Supporting Data
• VICINITY MAP
• LOCATION MAP
• EXISTING SITE PLAN
D. DESCRIPTIONS
• Program Descriptions
— Square Footage Details (GSF by Building, Space Utilization Comparison, NSF by Building)
— Energy Management
— Environmental Management (Environmetal Management Report, Asbestos Report and Radon Report)
• Site Descriptions
• Building Descriptions
E. DEFICIENCIES
F. CORRESPONDENCE AND REPORTS
• Center Review Brief
• Survey Brief
• RA and Student Facility Feedback Questionnaire
• Life Safety Defi ciencies Transmittal and List
• O & M Defi ciency List
• Active Warranty Report
• FRPC Performance Measures Matrix
VOLUME I - Planning Strategy
• Existing Site Plan
• Center Statistics
INTRODUCTION
• Purpose
• Report Contents
EXECUTIVE SUMMARY
• Signifi cant Issues
• Recommended Plan
• Summary of Proposed Projects
A. EXISTING CONDITIONS
• Background
• General Site Conditions
• General Building Conditions
• Ownership
• Facility Assessment by Function
• Energy
• Environmental Issues
• Sustainability
• Accessibility Standards
• Current and Completed Projects Since the Last Survey
• Health and Life Safety Issues
• Summary of Defi ciencies
B. RECOMMENDATIONS
• Status of the Previous (PY05) Plan
• Issues
• PY 08 Plan Overview
• Regional Projects
• Proposed Site Plan
C. PLANNING ANALYSIS
• Purpose
• Planning Objectives and Assumptions
• Space Utilization Analysis
• Federal Real Property Asset Management
• Mission Dependency Site Plan
• Defi ciency Analysis
• Facility Condition Summary Report
CONTENTS
HAWAII/MAUI JOB CORPS CENTER
FACILITY PLANNING REPORT
D Descriptions
BUILDINGS AND STRUCTURES
00912 HAWAII/MAUI 09-JUN-09
1Page:
0001 - HAWAII ADMINISTRATION
BUILDING
0002 - MIP FEMALE DORM
0003 - MIP MALE DORM
0004 - LANA'I MAINTENANCE
0006 - MIP LOUNGE
0009 - OAHU FEMALE DORM
0010 - MAUI MALE DORM
0011 - MOLOKA'I DINING HALL
0013 - KAUA'I OA/CTS/BUSINESS
0005 - FLAMMABLE MATERIALS STOR
0014 - STORAGE
0017 - FRONT GAZEBO
0018 - GAZEBO #2
0019 - MAINTENANCE STORAGE
0020 - RECEIVING/BREAK AREA
Name GSF
24,065
2,025 2,025 1,680
7,825 7,825 4,540 2,850
Active
Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building
Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business
Residential Residential Business Residential Residential Residential Assembly Business Storage Storage Assembly Assembly Storage Storage
Good
Good Good Good Good Good Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0091200002
0091200003 0091200004 0091200013 0091200007 0091208009 0091208010 0091200010 0091200012 0091200014 0091200015 0091208012 0091208013 0091208014 0091208015
9 53,715
6 1,706
15 55,421
Buildings
Structures
Total
GSF
GSF
GSF
Summary
June 09, 2009 Space Utilization By Function 00912 Hawaii/Maui
HOUSING
EDUCATION
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 112 Non Residents 0
112Total Students
(112)
(82)
(112)
(112)
(112)
DIFFERENCE
11,200
6,280
2,016
5,600
16,045
11,433
2,580
4,346
1,500
Lounge Other Shower/Toilet Sleeping Storage
Academic (82) Non-Academic
12 -- ACT (Off-Ctr) 30 -- Business Office Technologies 20 -- Culinary Arts + 24 -- Facilities Maint. and Const. +
18 -- OCT
Vocational Theory (44)
Dining (2 Servings) Food Preparation Food Storage
Miscellaneous Recreation Multipurpose Room Resource Center T.V. Room Weight Room
Medical/Dental
7.3
2,110
2,670 9,420
4,559 2,002
1,355 1,492 1,635
1,160 1,040
1,104
1,275
1,500
1,120
1,344 8,064
1,200 1,200 1,800
1,326 1,356
3,739 1,182
-165
-50
-68
Vocations
RESIDENT
NON-RESIDENT
(112)
(0) 15
50 5,600
4,845
5,153
-1,254
June 09, 2009 Space Utilization By Function 00912 Hawaii/Maui
ADMINISTRATION
STORAGE/SUPPORT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
TOTAL 271.37 30,394 42,207
(112)
(112)
DIFFERENCE
53,715
0.79
TOTAL GSF
NET TO GROSS RATIO
2,240
2,240
2,318
3,985
Administration
Operations & Maintenance Warehouse
2,318
1,565 2,420
2,240
1,344
1,076
1,745
11,813
Net Square Footage By Building Date: 06/09/2009 Page: 1Center: HAWAII/MAUI (00912)
HOUSING
Sleeping
Lounge
Storage
Shower/Toilet
Other
Function Suggested NSF
3,285 1,425 3,285 1,425
1,025
1,025
0009 - OAHU FEMALE DORM
0002 - MIP FEMALE DORM
0010 - MAUI MALE DORM
0003 - MIP MALE DORM
0009 - OAHU FEMALE DORM
0010 - MAUI MALE DORM
0006 - MIP LOUNGE
0003 - MIP MALE DORM
0010 - MAUI MALE DORM
0009 - OAHU FEMALE DORM
0002 - MIP FEMALE DORM
0002 - MIP FEMALE DORM
0009 - OAHU FEMALE DORM
0003 - MIP MALE DORM
0010 - MAUI MALE DORM
0010 - MAUI MALE DORM
0009 - OAHU FEMALE DORM
0006 - MIP LOUNGE
Bldg Name Actual NSF Difference
9,420
2,110
2,670
Sub Total: 16,045
8,064
1,120
1,344
11,200
1,356
1,326
( 112
4,845
Page: 2Center: HAWAII/MAUI (00912)
EDUCATION
FOOD SERVICE
Academic
Vocational Theory (44)
Culinary Arts
Facilities Maint. and Const.
Non-Academic
Business Office Technologie
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested NSF
2,350
1,492
1,635
1,355
1,160
1,040
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0011 - MOLOKA'I DINING HALL
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0013 - KAUA'I OA/CTS/BUSINESS
0001 - HAWAII ADMINISTRATION BUILDING
0013 - KAUA'I OA/CTS/BUSINESS
0011 - MOLOKA'I DINING HALL
0011 - MOLOKA'I DINING HALL
0011 - MOLOKA'I DINING HALL
Bldg Name Actual NSF Difference
4,559
1,492
1,635
2,002
1,355
1,160
1,040
Sub Total:
Sub Total:
11,433
2,580
1,200
1,800
1,200
6,280
2,016
3,739
-50
-165
1,182
-68
5,153
Page: 3Center: HAWAII/MAUI (00912)
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
Multipurpose Room
Weight Room
Miscellaneous Recreation
T.V. Room
Resource Center
Medical/Dental
Administration
Warehouse
Operations & Maintenance
Function Suggested NSF
1,104
1,275
1,500
2,318
2,420
1,565
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0013 - KAUA'I OA/CTS/BUSINESS
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0001 - HAWAII ADMINISTRATION BUILDING
0004 - LANA'I MAINTENANCE
Bldg Name Actual NSF Difference
1,104
1,275
1,500
2,318
2,420
1,565
Sub Total:
Sub Total:
Sub Total:
Sub Total:
4,346
1,500
2,318
3,985
2,240
1,344
5,600
2,240
2,240
1,076
-1,254
1,745
Energy Management Report
Center: HAWAII/MAUI (00912) Page: 1 Date: 06/09/2009
CENTER ENERGY DATA
None
ENERGY CONSUMPTION STATISTICS
46,067
ENERGY USE BY FUEL TYPE
Energy Audit :
Date of Audit :
Electric Company :
1985 Baseline :
2005 Goal (30% Reduction) :
Current Consumption Rate :
Percent Change :
Average Program Goal :
Natural Gas Company :
Property Status :
N/A
Maui Electric Company Maui Gas
Leased
462,520 1,578=
Total 2,474
MBtu
MBtu
Total $176,430 MBtu/ $71.314
88,276
Btu/GSF/YR Btu/GSF/YR Btu/GSF/YR
Btu/GSF/YR
Data from the most recent four quarters
Electricity
Propane kWh
9,386 Gal = 896 MBtu
$147,749 $0.319= kWhElectricity
Propane $28,681 = $3.056 Gal
ENERGY COST BY FUEL TYPE
COMMENTS
2/01 -PM activities, checking for leaking plumbing and R/R to T8s
Page: 2 Date: 06/09/2009
Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.
1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:
a. Turn it down (lights, heating & cooling),
b. Turn it off (lights, computers, other equipment),
c. Keep it tight (close doors and windows, use window blinds)
2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:
a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.
b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.
c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.
d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.
e. Reasonable set points: Try 68°F in the heating season and 78°F in the cooling season.
f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.
g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.
h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.
i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.
Page: 3 Date: 06/09/2009
j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.
k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.
l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.
m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.
n. Caulk and fill cracks around doors and windows to reduce costly air leaks.
o. When replacing broken glass, use high transmittance, low heat gain windows.
p. Make sure automatic door closers are functioning properly to avoid drafts.
3. Buy energy efficient, buy EnergyStar (www.energystar.gov).
a. Buy EnergyStar appliances and equipment.
b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).
c. Replace broken thermostats with EnergyStar labeled programmable products.
d. Replace broken exit signs with EnergyStar LED exit signs.
Environmental Management Report
Page: 1 Date: 06/09/2009
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Maintenance Shops/Facilities Maintenance Trade
No
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
None None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Non-PCB Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Maui/Best Desposal Service No
HIR000111435
Municipal Hazardous Waste Disposal Service
Maui County Landfill
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
N/A N/A
01/01/2001 Non-Friable Only Kalani Vaivela
No Yes
No Yes
ID Fuel Type Capacity Location Overfill Secondary ContainmentTank Status
Tank Status
Asbestos-Containing Materials Inventory
Date: Jun. 09, 2009Center : Hawaii/Maui (00912) Page: 1 of 1
Floor Finishes Floor Finishes
Bldg System
9" x 9" vinyl floor tiles Vinyl floor sheeting
Category Description
Sq. Ft.
Sq. Ft.
Location Unit Quantity
Basement Medical Wing
Building : 0001 - HAWAII ADMINISTRATION BUILDING
Radon
Page: 1 of 1
0001 - HAWAII ADMINISTRATION BUILDING
0002 - MIP FEMALE DORM
0003 - MIP MALE DORM
0004 - LANA'I MAINTENANCE
0006 - MIP LOUNGE
0009 - OAHU FEMALE DORM
0010 - MAUI MALE DORM
0011 - MOLOKA'I DINING HALL
0013 - KAUA'I OA/CTS/BUSINESS
Bldg Name Test Date
No
No
No
No
No
No
No
No
No
Radon Testing
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Page: 1 Date: 06/09/2009
ACCESSIBILITY
Yes
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Drain System Soil Erosion Soil Erosion Location
No N/ASurface Run-off
Paving Type for Roads & Parking Paving Type for Sidewalks
Asphalt Concrete
Structures Fencing Outdoor Recreation
There are four storage structures and two gazebos.
None Ball Field, Basketball, Volleyball
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water
Treatment Type Storage Type Storage Capacity Maintenance Responsibility
Center
NoMasterCounty of Maui Department of WPublic Water Authority
None 0None
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity Pressure Source # of Fire Pumps
Yes 0 0None Municipal
Nearest fire department is the Makawao/Paia fire department. Response time is 5-7 minutes.
Sewage Treatment Sewer Line Owner
10,000On-site Septic System CenterCenter
Maintenance ResponsibilityCapacity(Gallons)
Number of Deficiencies = 2
Number of Deficiencies = 1
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
HISTORIC PRESERVATION
STORM WATER SYSTEM
Number of Deficiencies = 1SITE FEATURES
UTILITY
3. Sanitary Sewer System/ Sewage Treatment Plant
2. Fire Protection
Page: 2 Date: 06/09/2009
Propane
None
Comments:
Electric Company
PCB Transformer Mounting
Transformer Ownership
Systems Ownership
Maintenance Responsibility
Maui Electric Company
The overhead service is brought to the center from power poles along Ike Drive. Service enters the center at the main entrance southwest of the campus and distributes power to buildings via pole-mounted transformers around the center perimeter running from south, then east and terminated in the north. A 50 kVA and two 25 kVA pole-mounted transformers along the south side serve MIP Female Dormitory Building 2, MIP Male Dormitory Building 3, MIP Lounge Building 6, Lana'i Maintenance Building 4 and Oahu Female Dormitory Building 9. A 25 kVA pole-mounted transformer at the northeast serves Maui Male Dormitory Building 10. Two 75 kVA pole-mounted transformers at the north provide services to Administration Building 1, Moloka'i Dining Hall Building 11 and Kaua'i OA/CTS/Business Building 13. All buildings are metered individually except Building 11 which shares the same meter installed at Building 1. The site lighting consists of mostly building-mounted exterior lights and some post-mounted lights along the center main entrance roadway. The basketball court is provided with sport lights which are controlled by a local switch. The building-mounted and post-mounted lights are controlled by photocells and time clock. The center owns and maintains the site lighting system.
Pole Utility Utility UtilityNo
Comments:
Telephone Company On-site Line Owner
Telephone service is brought to the center by Hawaiian Telephone Company and terminated in the server room located on the first floor of Administration Building 1. From this location Job Corps Data Center provides and maintains the digital voice over IP (VoIP) and data network for the entire center. The digital voice over IP (VoIP) and data network are provided and maintained by the Job Corps Data Center. The fire alarm system in Oahu Female Dormitory Building 9 and Kaua'i OA/CTS/Business Building 13 is a stand-alone. The fire alarm system in other buildings is connected to the main fire alarm control/annunciator panel located in the security office in Administration Building 1. Dormitory Buildings 2, 3, 9 and 10 are provided with satellite dishes.
Hawaiian Telephone Company
Maint. Responsibility
Center Center
Security
Door Alarms
01/01/1992
01/01/1992
01/01/1992
01/01/2002
01/01/2005
Private
Private
Private
Private
Private
Active
Active
Active
Active
Active
Aboveground
Aboveground
Aboveground
Aboveground
Aboveground
Near Building 1
Near Building 6
Near Building 11
Near Building 9
Near Building 10
Propane is used for domestic hot water and cooking equipment.
No
No
No
No
No
Propane
Propane
Propane
Propane
Propane
STORAGE TANK
Comments:
TypeStatus Location Owner Fuel Type Capacity Install Date
12.4 kV, 3-Phase, 3 Wire
120/240V, 1-Phase, 3 WireOverhead
OverheadPrimary Service
Secondary Service
Distribution Characteristics
ID
Reg.
4. Gas
5. Central Plant
6. Electric
7. Communication
Other
Other
Other
Other
Other
Purpose
Page: 3 Date: 06/09/2009
Earthquake Risk
Medium Low LowMedium LowUniform Medium
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
GENERAL SITE CONDITION
Rating X Good Fair Poor
NATURAL HAZARDS
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Building Descriptions and Utilities Hawaii/Maui Job Corps Center
BUILDING 1 - HAWAII ADMINISTRATION BUILDING
Building Descriptions
Page: 1 of 38
Building: 0001 - HAWAII ADMINISTRATION BUILDING
BUILDING ENVELOPE
Foundation RoofBuilding
Wood Piers & Beams Wood Wood
Wood Siding
Wall Roof None None
Metal Rollup - Metal Frame Metal Unit - Metal Frame Wood Unit - Metal Frame Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Business 24,065 18,320 3 Leased 1900 Candidate
Comments: The existing fire alarm system in the building does not include visual alarm appliances.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
Yes
N/A
Yes
Yes
Yes
No
No
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
The roof has holes and is leaking. There are funded deficiencies to address this issue.
Drainage Year Life
Type Area Served
Asphalt Shingles Gutters and Downspouts 1985 0 Hip Original Building
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 38
Building: 0001 - HAWAII ADMINISTRATION BUILDING
INTERIOR FINISH
Carpet Ceramic Tile Resilient Vinyl Tile
Ceramic Tile Drywall Plaster Wood
Metal Unit - Metal Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
Mechanical
Mechanical
Janitor's Closet
Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
Metal Stairs Wood Stairs
Double Hung - Wood Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;
Sliding - Aluminum Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board Wood
Exhaust Ventilation
Number of Deficiencies = 2
Number of Deficiencies = 1
Windows6. Number of Deficiencies = 1
Floors1. Asbestos: Yes Number of Deficiencies = 1
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Ventilation2. Number of Deficiencies = 2
Ceilings
Page: 3 of 38
Building: 0001 - HAWAII ADMINISTRATION BUILDING
Domestic hot water is provided by a Ruud model PH50P water heater.Comments:
Cast-Iron None None
Electric Bottled Water Cooler Electric Water Cooler Emergency Eye Wash Hose Bibb Lavatory Shower Shower/Bathtub Sink Urinal Water Closet (Tank)
Gas (Propane)
Wet None ABC Type Fire Extinguisher
Comments: A wet pipe sprinkler system serves basement level.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Window Unit
Single Duct
Portable Air Conditioner
None
Refrigerant
None
Electric
Electric
Electric
Natural
Natural
Natural
None
None
None
Offices
Medical/Dental
Offices
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Window units also cool the math classroom and an electronic equipment room.
This is a Rheem model RBHC-24J00NHG air handler with evaporator coils matched to a Rheem RAMC-060JAZ condensing unit.
One office is cooled by a Freecom model M2000 unit.
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Page: 4 of 38
Building: 0001 - HAWAII ADMINISTRATION BUILDING
Comments: Service is brought from a 75 kVA pole-mounted transformer north of the building and terminated in a wiretrough which feeds a 350A, two 250A, two 200A disconnect switches, a C/T cabinet and a meter.
The two 200A and two 250A disconnect switches serve panels in Building 1 and the 350A switch serves Moloka'i Dining Hall Building 11.
FIRE ALARM
Comments: The main fire alarm control/annunciator panel is a Simplex model 4020 located in the security office in this building. The fire alarm system components in Buildings 2, 3, 4 and 6, and the fire alarm panels in Buildings 1, 10 and 11 are connected to this main panel.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Flow/Tamper Switch Heat Detector Manual Pull Station Smoke Detector
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
LIGHTING
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Conference Rooms
Mail Room
Lounges
Medical/Dental
Reception
Wards (Patient)
Classrooms
Recreation
Corridors & Stairs
Storage Rooms
Toilets
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Disconnect Switch 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 1
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 2
Page: 5 of 38
Building: 0001 - HAWAII ADMINISTRATION BUILDING
Connected to Main System Magnetic Door/Alarm None Satellite Dish
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
BUILDING 2 - MIP FEMALE DORM
Page: 6 of 38
Building: 0002 - MIP FEMALE DORM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Piers Wood Wood
Wood Siding
Wall Roof None Rigid
Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Residential 2,025 1,855 1 Leased 1960 Unevaluated
Comments: The existing fire alarm system in the building does not include visual alarm appliances.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
Yes
Yes
N/A
Yes
Yes
Yes
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Built-up Roofing Surface Run-off 2006 18 Gable Entire Building
3. Roof
Page: 7 of 38
Building: 0002 - MIP FEMALE DORM
INTERIOR FINISH
Carpet Ceramic Tile Vinyl Tile Wood
Ceramic Tile Drywall
Wood Unit - Metal Frame Wood Unit - Wood Frame
Mechanical
Mechanical
Janitor's Closet
Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Wood Stairs
Comments: Wood and concrete stairs lead to the entries.
Jal - Aluminum Frame; Single Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Ventilation2.
Page: 8 of 38
Building: 0002 - MIP FEMALE DORM
Hot water is supplied from Building 3.Comments:
Cast-Iron None None
Hose Bibb Lavatory Portable Bottled Water Cooler Shower Sink Urinal Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 25 kVA pole-mounted transformer southwest of the building and terminates in a 100A disconnect and a meter installed on the building exterior.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
None None None None Natural None None
Incandescent
Comments: Exterior building-mounted light fixtures are controlled by timeclock and photocell.
LIGHTING
Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Page: 9 of 38
Building: 0002 - MIP FEMALE DORM
FIRE ALARM
Comments: The fire alarm system components in this building are connected to the central fire alarm control/annunciator panel in the security office in Building 1.
Audible Alarm Manual Pull Station Smoke Detector
Connected to Main System Magnetic Door/Alarm None Satellite Dish
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Sleeping Rooms
Corridors & Stairs
Toilets
Shower
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 2
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
This building has been recommended for demolition in the Long Range Development Plan after construction of new dormitory. The demolition is included in Project 3031.
DEMOLITION RECOMMENDATION
BUILDING 3 - MIP MALE DORM
Page: 10 of 38
Building: 0003 - MIP MALE DORM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Piers Wood Wood
Wood Siding
Wall Roof None Rigid
Wood Unit - Metal Frame Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Residential 2,025 1,855 1 Leased 1960 Unevaluated
Comments: The existing fire alarm system in the building does not include visual alarm appliances.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
Yes
Yes
N/A
Yes
Yes
Yes
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Built-up & Membrane Surface Run-off 2006 18 Gable Entire Building
3. Roof
Page: 11 of 38
Building: 0003 - MIP MALE DORM
INTERIOR FINISH
Carpet Ceramic Tile Vinyl Tile Wood
Ceramic Tile Drywall
Wood Unit - Metal Frame Wood Unit - Wood Frame
Mechanical
Mechanical
Janitor's Closet
Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
Wood Stairs
Comments: Wood stairs lead to the entries.
Jal - Aluminum Frame; Single Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Page: 12 of 38
Building: 0003 - MIP MALE DORM
Domestic hot water is provided by a Rheem model G76-200-1 water heater.Comments:
Cast-Iron None None
Hose Bibb Lavatory Portable Bottled Water Cooler Shower Sink Urinal Water Closet (Tank)
Gas (Propane)
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 50 kVA pole-mounted transformer to the south of the building and terminates in a 100A disconnect switch and a meter installed on the building exterior. This transformer also serves Buildings 4 and 6.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
None None None None Natural None None
Incandescent
Comments: Exterior building-mounted light fixtures are controlled by timeclock and photocell.
LIGHTING
Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Page: 13 of 38
Building: 0003 - MIP MALE DORM
FIRE ALARM
Comments: The fire alarm system components in this building are connected to the central fire alarm control/annunciator panel in the security office in Building 1.
Audible Alarm Manual Pull Station Smoke Detector
Connected to Main System None None Satellite Dish
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Sleeping Rooms
Corridors & Stairs
Toilets
Shower
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 1
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
This building has been recommended for demolition in the Long Range Development Plan after construction of new
BUILDING 4 - LANA'I MAINTENANCE
Page: 14 of 38
Building: 0004 - LANA'I MAINTENANCE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Wood Siding
Wall Roof None Batt
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Business 1,680 1,565 1 Leased 1992 Unevaluated
Comments: The existing fire alarm system in the building does not include visual alarm appliances.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
N/A
N/A
N/A
Yes
N/A
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Corrugated Aluminum
Metal
Surface Run-off
Surface Run-off
Shed
Gable
Storage
Original Building
3. Roof
Page: 15 of 38
Building: 0004 - LANA'I MAINTENANCE
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
CMU Ceramic Tile Drywall
Wood Unit - Wood Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
None
Jal - Aluminum Frame; Single Glazing; Sliding - Aluminum Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Page: 16 of 38
Building: 0004 - LANA'I MAINTENANCE
Hot water is provided by an undersink electric instantaneous water heater.Comments:
Cast-Iron None None
Electric Bottled Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Sink Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 50 kVA pole-mounted transformer to the south of the building and terminates in a 100A disconnect switch and a meter installed on the building exterior. This transformer also serves Buildings 3 and 6.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
None None None None Natural None None
Incandescent
Comments: Exterior building-mounted light fixtures are controlled by timeclock and photocell.
LIGHTING
Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
ELECTRICAL SERVICES
Page: 17 of 38
Building: 0004 - LANA'I MAINTENANCE
FIRE ALARM
Comments: The fire alarm system components in this building are connected to the central fire alarm control/annunciator panel in the security office in Building 1. A fire alarm horn is installed on the exterior at the building entrance.
Audible Alarm Manual Pull Station Smoke Detector
None None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Storage/Warehouse-Active
Toilets
Area Recommended Recorded Light Type
None Tritium Gas
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING 6 - MIP LOUNGE
Page: 18 of 38
Building: 0006 - MIP LOUNGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Piers Wood Wood
Wood Siding
Wall Roof None Rigid
Metal Unit - Wood Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Residential 880 795 1 Leased 1960 Unevaluated
Comments: The lounge has a step in the room. The existing fire alarm system in the building does not include visual alarm appliances.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
Yes
N/A
N/A
Yes
No
Yes
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Built-up Roofing Surface Run-off 2006 18 Gable Entire Building
3. Roof
Page: 19 of 38
Building: 0006 - MIP LOUNGE
INTERIOR FINISH
Carpet Concrete Vinyl Tile
Drywall
Wood Unit - Metal Frame Wood Unit - Wood Frame
Mechanical
Mechanical
Janitor's Closet
Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Wood Stairs
Comments: Wood and concrete stairs lead to the entries.
Fixed - Wood Frame; Single Glazing; Jal - Wood Frame; Single Glazing;
Exposed structure Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Page: 20 of 38
Building: 0006 - MIP LOUNGE
Domestic hot water is provided by a Ruud model PE2-40-2 water heater.Comments:
Cast-Iron None None
Electric Water Cooler Hose Bibb Lavatory Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 50 kVA pole-mounted transformer to the south of the building and terminates in a 100A disconnect switch and a meter installed on the building exterior. This transformer also serves Buildings 3 and 4.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
None None None None Natural None None
High Intensity Discharge (HID)
Comments: Exterior building-mounted light fixtures are controlled by timeclock and photocell.
LIGHTING
Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Page: 21 of 38
Building: 0006 - MIP LOUNGE
FIRE ALARM
Comments: The fire alarm system components in this building are connected to the central fire alarm control/annunciator panel in the security office in Building 1. A fire alarm horn is installed on the exterior at the building entrance.
Comments: A TV and VCR are provided in the lounge.
Audible Alarm Manual Pull Station Smoke Detector
Connected to Main System None None Satellite Dish
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Recreation
Storage/Warehouse-Active
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 1
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
This building has been recommended for demolition in the Long Range Development Plan after construction of new
BUILDING 9 - OAHU FEMALE DORM
Page: 22 of 38
Building: 0009 - OAHU FEMALE DORM
BUILDING ENVELOPE
Foundation RoofBuilding
CMU Wood Wood
Vinyl Siding
Wall Roof Batt Batt
Metal Unit - Metal Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Residential 7,825 5,770 1 Owned 2000 Unevaluated
Comments: The designated accessible bedroom is provided with a fire alarm strobe but its bathroom is not.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Asphalt Shingles
Single Ply
Gutters and Downspouts
Gutters and Downspouts
Gable
Shed
MainBuilding
Walkway
3. Roof
Page: 23 of 38
Building: 0009 - OAHU FEMALE DORM
INTERIOR FINISH
Carpet Concrete Sheet Vinyl
Ceramic Tile Drywall
Wood Unit - Metal Frame
Mechanical Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
Wood Stairs
Comments: Wood stairs lead to one entry and mechanical room.
Double Hung - Vinyl Frame; Double Glazing; Sliding - Vinyl Frame; Double Glazing;
None None None None Natural None None
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Area Served
Page: 24 of 38
Building: 0009 - OAHU FEMALE DORM
Hot water is provided by a Rheem 76-gallon gas water heater with a 193 GPH recovery rate. Storage is in an A.O. Smith 120-gallon storage tank.
Comments:
PVC None None
Electric Bottled Water Cooler Hose Bibb Lavatory Shower/Bathtub Sink Water Closet (Tank)
Gas (Propane)
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 50 kVA pole-mounted transformer to the southwest of the building and terminates in a 200A disconnect switch and a meter installed on the exterior wall of the building electrical room.
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Comments: Exterior building-mounted light fixtures are controlled by timeclock and photocell.
LIGHTING
Main Disconnect Switch 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Page: 25 of 38
Building: 0009 - OAHU FEMALE DORM
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex model 4004 located in the RA office.
Comments: A pay phone is provided in the lanai for student use.
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Magnetic Door/Alarm None Satellite Dish
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. In addition to fluorescent lights, the bedrooms, offices and lanai are furnished with ceiling-mounted paddle fans with compact fluorescent lights.
T8 - Fluorescent
Incandescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Incandescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Sleeping Rooms
Study Room
Housing Lounge
Laundry Room
Corridors & Stairs
Toilets
Shower
Storage Rooms
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 1
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesYes
BUILDING 10 - MAUI MALE DORM
Page: 26 of 38
Building: 0010 - MAUI MALE DORM
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Wood Siding
Wall Roof Batt Batt
Metal Unit - Metal Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Residential 7,825 5,770 1 Owned 2005 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Asphalt Shingles
Single Ply
Gutters and Downspouts
Gutters and Downspouts
Gable
Shed
Main Building
Walkway
3. Roof
Page: 27 of 38
Building: 0010 - MAUI MALE DORM
INTERIOR FINISH
Carpet Concrete Vinyl Tile
Ceramic Tile Drywall
Wood Unit - Metal Frame
Mechanical Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
Wood Stairs
Comments: Wood stairs lead to one entry and mechanical room.
Double Hung - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Double Glazing;
None None None None Natural None None
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None None
Ventilation2.
System Type
Number of Deficiencies = 2
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Area Served
Page: 28 of 38
Building: 0010 - MAUI MALE DORM
Hot water is provided by two Ruud 100-gallon gas-fired water heaters, each having a 182 GPH recovery rate.
Comments:
PVC None None
Electric Bottled Water Cooler Hose Bibb Lavatory Shower/Bathtub Sink Water Closet (Tank)
Gas (Propane)
Wet None ABC Type Fire Extinguisher
Comments: The building is served by a 50 kVA pole-mounted transformer northeast of the building.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Comments: Exterior building-mounted light fixtures are controlled by timeclock and photocell.
LIGHTING
Main Distribution Panel 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Page: 29 of 38
Building: 0010 - MAUI MALE DORM
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Simplex model 4005 located in the RA office. A sprinkler riser with flow and tamper switch is installed outside the building. The fire alarm panel in this building is connected to the main panel in the security office of Building 1.
Comments: A pay phone is provided in the lanai for student use.
Audible Alarm Control/Annunciator Panel Flow Switch Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Connected to Main System Magnetic Door/Alarm None Satellite Dish
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. In addition to fluorescent lights, the bedrooms, offices and lanai are furnished with ceiling-mounted paddle fans with compact fluorescent lights.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Sleeping Rooms
Study Room
Housing Lounge
Laundry Room
Corridors & Stairs
Toilets
Shower
Storage Rooms
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No YesYes
BUILDING 11 - MOLOKA'I DINING HALL
Page: 30 of 38
Building: 0011 - MOLOKA'I DINING HALL
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Metal Siding
Wall Roof None Batt
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
Assembly 4,540 4,072 1 Leased 1988 Unevaluated
Comments: The culinary arts addition has visual alarm devices but the toilets do not.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
N/A
No
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material Drainage Year Life
Type Area Served
Metal
Metal
Asphalt Shingles
Surface Run-off
Surface Run-off
Gutters and Downspouts
Gable
Shed
Shed
Original Building
Culinary Arts Addition
Canopy
Number of Deficiencies = 13. Roof
Page: 31 of 38
Building: 0011 - MOLOKA'I DINING HALL
INTERIOR FINISH
Ceramic Tile Quarry Tile Resilient Vinyl Tile
Drywall Plastic Laminate
Wood Unit - Metal Frame
Mechanical
Mechanical
Restroom
Kitchen
Ventilation Area Served
VERTICAL CIRCULATION
None
Metal Unit - Metal Frame
Sliding - Aluminum Frame; Single Glazing;
Acoustical…
This is the start of the file's text. The full file is on GovTribe.