Attachment_J-9_Facility_Survey_ABQ_JUNE_2013_Final_Vol_2.pdf

PDF 19 MB Posted

Attached to
Albuquerque JCC/OA/CTS Federal contract opportunity
Solicitation number
DOL-ETA-16-R-00006
Issued by
Department of Labor Employment and Training Administration

About this file

Attachment J-9 Facility Survey ABQ JUNE 2013 Final Vol 2

View the file

Other files for this federal contract opportunity

Other files attached to Albuquerque JCC/OA/CTS, newest first.
File Type Posted
PRH_Chapter_3_Exhibit_3-5_CTT_Programs_Student_Teacher_Ratios_Amendment_4.pdf PDF
Q_and_A_DOL-ETA-16-R-00006_Amendment_4_ALBQ_05_16_16.pdf PDF
Sol_DOL-ETA-16-R-00006_Amd_000004.pdf PDF
Sol_DOL-ETA-16-R-00006_Amd_000003.pdf PDF
Albuquerque_Section_L_DOL-ETA-16-R-00006_Amendment_2.pdf PDF
Albuquerque_DOL-ETA-16-R-00006_Amendment_2_Q_and_A.pdf PDF
Albuquerque_Vehicle_List_DOL-ETA-16-R-00006_Amendment_2.pdf PDF
Sol_DOL-ETA-16-R-00006_Amd_000002.pdf PDF
Sol_DOL-ETA-16-R-00006_Amd_000001.pdf PDF
Attachment_J-4_STAFFING_CHART_ABQ.docx DOCX document
Attachment_J-18_SCA_Wage_Determinations_01_05_2016_ABQ.docx DOCX document
Attachment_J-2_Statement_of_Financial_Capability_ETA_8554_ABQ.docx DOCX document
Attachment_J-1_Cost_Detail_Template_Albuquerque.xlsx XLSX spreadsheet
Attachment_J-17_DB_Wage_Determinations_ABQ.docx DOCX document
Attachment_J-6_Subcontracting_Plan_Albuquerque.docx DOCX document
Sol_DOL-ETA-16-R-00006.pdf PDF
Attachment_J-9_Facility_Survey_ABQ_JUNE_2013_Final_Vol_1.pdf PDF
Attachment_J-15_Regional_Career_Pathway_Plan_ABQ.pdf PDF
Attachment_J-11_Inventory_Estimate_01-26-2016.pdf PDF
Attachment_J-8__SF_1413_Statement_and_Acknowledgement.docx DOCX document
Attachment_J-3_Financial_Display_ETA_2110_ABQ.docx DOCX document
Attachment_J-7_Past_Performance_Confirmation_Questionnaire_Albuquerque.docx DOCX document
Attachment_J-5_CTST_Albuquerque.docx DOCX document
Attachment_J-10_Computerized_Property_Management_Listing_ABQ.pdf PDF
Attachment_J-13_National_Staff_Compensation_Report_Data_ABQ.pdf PDF
Attachment_J-12_Utility_Usage_Data_Energy_01-26-2016.pdf PDF
Pre-Solicitation_Notice_Albuquerque_JCC_OACTS.docx DOCX document
Show all 27

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Albuquerque

Job Corps Center Albuquerque, NM

Facility Planning Report Volume II

Supporting Data

Final June 2013

Department of Labor/ Office of Job Corps

22Albuquerque Job Corps Center

Albuquerque

Job Corps Center Albuquerque, NM

Facility Planning Report Volume II

Supporting Data

Final June 2013

Student Promenade

33 Albuquerque Job Corps Center

CONTENTS

ALBUQUERQUE JOB CORPS CENTER

FACILITY PLANNING REPORT

VOLUME I - Planning Strategy

• Existing Site Plan

• Center Statistics

INTRODUCTION

• Purpose

• Report Contents

EXECUTIVE SUMMARY

A. EXISTING CONDITIONS

• Background

• General Site Conditions

• General Building Conditions

• Preventive Maintenance

• Ownership

• Facility Assessment by Function

• Energy

• Environmental Issues

• Sustainability

• Accessibility Standards

• Health and Life Safety Issues

• Summary of Defi ciencies

B. RECOMMENDATIONS

• Status of the Previous (PY09) Plan

• Signifi cant Issues

• PY 12 Plan Overview

• Summary of Proposed Projects

• Proposed Site Plan

• Implementation Plan

• Summary of National Projects

• Project Data Sheets

C. PLANNING ANALYSIS

• Purpose

• Planning Objectives and Assumptions

• Space Utilization Analysis

• Federal Real Property Asset Management

• Mission Dependency Site Plan

• Defi ciency Analysis

• Facility Condition Summary Report

• Building Condition by Function

• Building Condition Site Plan

VOLUME II - Supporting Data

• Vicinity Map

• Location Map

• Existing Site Plan

D. DESCRIPTIONS

• Buildings and Structures

• Space Utilization By Function

• NSF by Building

• Energy Management Report

• Environmental Management

Asbestos Report Radon Report

• Site Descriptions

• Building Descriptions

E. DEFICIENCIES

F. CORRESPONDENCE AND REPORTS

• Center Review Meeting Minutes

• Survey Brief

• RA and Student Facility Feedback Questionnaire

• Life Safety Defi ciencies Transmittal and List

• O & M Defi ciency List

• Active Warranty Report

• FRPC Performance Measures Matrix

44Albuquerque Job Corps Center

55 Albuquerque Job Corps Center

66Albuquerque Job Corps Center

77 Albuquerque Job Corps Center

D Descriptions

BUILDINGS AND STRUCTURES

00605 ALBUQUERQUE 06/14/2013

1Page: of Date:

A & B - ADMINISTRATION

C - FOOD SERVICE & MED/DENTAL

C1 - CAFE ANNEX

CDC - CHILD DEVELOPMENT CTR

CTST - STORAGE

D - SECURITY

E - STUDENT TRAINING

J - SOCIAL DEVELOPMENT

K - MATERIAL CONTROL

L - VOCATIONAL STORAGE

M - MAINTENANCE

N1 - DORMITORY

N2 - DORMITORY

O - MULTI-PURPOSE RECREATION

P - VOCATIONAL

Q & R - VACANT

S & T - CHARTER SCHOOL

U & V - CHARTER SCHOOL/LAUNDRY

W & X - DORMITORIES

Y & Z - DORMITORIES

0013 - RECREATION STORAGE

0014 - RECREATION STORAGE

0017 - LAUNDRY STORAGE

0018 - MATERIAL CONTROL STORAGE

0019 - DIESEL STORAGE TANK

0020 - DRUM STORAGE

0021 - MAINTENANCE STORAGE

0023 - TRAILER

0024 - MAINTENANCE STORAGE

0025 - RECREATION TOILET

0026 - PELLET STORAGE SILO

0027 - PELLET BOILER BUILDING

0028 - AMPHITHEATER

0029 - WELDING STORAGE 1

0030 - WELDING STORAGE 2

02 -PAVILION

04 - PAVILION

06 - STORAGE

08 - STORAGE

09 - STORAGE

12 - STORAGE

5 - STORAGE

Name GSF

12,750 11,345 1,140 8,245 1,980

21,390 4,990 5,615 3,200 4,890

32,310 25,963 20,290 20,640 5,720 5,720 5,720 8,275 8,275

Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active

StatusType

Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure

Use Group Built Flrs Const

Business Assembly Assembly Day Care Storage Business Business Business Storage Business Storage Residential Residential Assembly Factory/Ind.

Residential Business Residential Residential Residential Storage Storage Storage Storage Utility/Misc.

Storage Storage Utility/Misc.

Storage Utility/Misc.

Utility/Misc.

Utility/Misc.

Assembly Storage Storage

Storage

Good Good Good Good Good Good Good Fair

Good Good Good Good Good Good Good Fair

Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good

ConditionAsset Number

0060500002 0060500004 0060500028 0060500023 0060500029 0060500005 0060500006 0060500010 0060500011 0060508050 0060500013 0060500027 0060508040 0060500014 0060500015 0060500016 0060500017 0060500018 0060500019 0060500020 0060508052 0060508053 0060508054 0060508055 0060508056 0060508057 0060508058 0060508059 0060508060 0060508061 0060508062 0060508063 0060508064 0060508065 0060508066 0060500025 0060508042 0060508044 0060508046 0060508047 0060508051 0060500021

BUILDINGS AND STRUCTURES

00605 ALBUQUERQUE 06/14/2013

2Page: of Date:

20 209,438

22 3,582

42 213,020

Buildings

Structures

Total

GSF

GSF

GSF

Summary

06/14/2013

Space Utilization By Function 00605 Albuquerque Page: 1 of Date:

HOUSING

EDUCATION

FOOD SERVICE

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Residents 325 Non Residents 90

415Total Students

(325)

(415)

(415)

DIFFERENCE

32,500

26,630

7,470

52,810

45,692

5,605

Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage

Academic (415) Non-Academic

20 -- ACT (Off-Ctr) 30 -- Advanced Welding + 24 -- Carpentry + 24 -- Cement Masonry + 24 -- Electrician Apprentice + 24 -- Facilities Maint. and Const. + 30 -- Health Occupations (Off-Ctr) 60 -- Office Administration 24 -- Plumbing + 48 -- Welding +

Vocational Theory (198)

Dining (2 Servings) Food Preparation Food Storage

6,460 5,865 5,230

33,940 1,315

13,751 8,706

2,130 4,199 2,110 2,286 2,255

2,215 2,030 3,385

2,625

2,825 1,630 1,150

3,250

3,900 23,400

1,950

4,150 4,150

2,250 1,800 1,800 1,200 1,800

2,700 1,200 3,600

1,980

3,320 2,490 1,660

3,210

1,330 10,540

-635

9,601 4,556

-120 2,399

1,086

-485 -215

-495 -860 -510

Vocations

20,310

19,062

-1,865

06/14/2013

Space Utilization By Function 00605 Albuquerque Page: 2 of Date:

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

VACANT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

TOTAL 257.45 106,840 153,072

(415)

(415)

(415)

(415)

(0)

DIFFERENCE

209,438

0.73

TOTAL GSF

NET TO GROSS RATIO

17,600

2,680

11,660

8,300

19,465

2,355

13,730

8,815

4,600

Activity Room Arts & Crafts Assembly Hall Gymnasium Learning Resource Center/Library Men's Exercise Room Miscellaneous Recreation Non-Resident Lounge Snack Bar Theater/Recreation Hall Women's Exercise Room

Medical/Dental

Administration Child Development Center (42)

Operations & Maintenance Warehouse

Vacant

6.46

2,525 1,160 1,000 7,665

1,765 1,425 1,280

1,155 1,070

2,355

7,425 6,305

4,255 4,560

4,600

2,680

8,300 3,360

3,320 4,980

-325

-875 2,945

-420

RESIDENT

NON-RESIDENT

(325)

(90) 15

50 16,250 1,350

1,865

-325

2,070

4,600

46,232

Net Square Footage By Building Date: 06/14/2013 Page: 1

Center: ALBUQUERQUE (00605) of 4

HOUSING

Sleeping excl. SPD

Lounge

Storage

Shower/Toilet

Other

Function Suggested

NSF

4,140 4,140

13,660 12,000

2,800

2,600

2,210 2,000

2,160 1,925 1,000

Y & Z - DORMITORIES

W & X - DORMITORIES

N1 - DORMITORY

N2 - DORMITORY

Y & Z - DORMITORIES

N2 - DORMITORY

W & X - DORMITORIES

N1 - DORMITORY

W & X - DORMITORIES

Y & Z - DORMITORIES

N1 - DORMITORY

N1 - DORMITORY

N2 - DORMITORY

Y & Z - DORMITORIES

W & X - DORMITORIES

W & X - DORMITORIES

Y & Z - DORMITORIES

N2 - DORMITORY

N1 - DORMITORY

U & V - CHARTER SCHOOL/LAUNDRY

Bldg Name Actual NSF Difference

33,940

6,460

1,315

5,230

5,865

Sub Total: 52,810

23,400

3,250

1,950

3,900

32,500

10,540

3,210

-635

1,330

5,865

( 325

20,310 rooms; beds rooms; beds rooms; beds rooms; beds

Page: 2

Center: ALBUQUERQUE (00605) of 4

EDUCATION

Academic

Vocational Theory (198)

Carpentry

Cement Masonry

Plumbing

Welding

Facilities Maint. and Const.

Non-Academic

Electrician Apprentice

Office Administration

Function Suggested

NSF

1,260 3,600 1,825

4,600 1,260

2,625

1,844 1,675

1,430

2,030

3,385

1,575

1,358 2,686

1,605

1,476

2,215

E - STUDENT TRAINING

E - STUDENT TRAINING

U & V - CHARTER SCHOOL/LAUNDRY

E - STUDENT TRAINING

E - STUDENT TRAINING

S & T - CHARTER SCHOOL

E - STUDENT TRAINING

P - VOCATIONAL

P - VOCATIONAL

CTST - STORAGE

L - VOCATIONAL STORAGE

P - VOCATIONAL

L - VOCATIONAL STORAGE

P - VOCATIONAL

P - VOCATIONAL

L - VOCATIONAL STORAGE

P - VOCATIONAL

E - STUDENT TRAINING

E - STUDENT TRAINING

E - STUDENT TRAINING

A & B - ADMINISTRATION

E - STUDENT TRAINING

J - SOCIAL DEVELOPMENT

J - SOCIAL DEVELOPMENT

J - SOCIAL DEVELOPMENT

J - SOCIAL DEVELOPMENT

E - STUDENT TRAINING

P - VOCATIONAL

L - VOCATIONAL STORAGE

CTST - STORAGE

E - STUDENT TRAINING

Bldg Name Actual NSF Difference

13,751

2,625

4,199

2,110

2,030

3,385

2,255

8,706

2,286

2,215

4,150

1,980

1,800

1,800

1,200

3,600

1,800

4,150

1,200

2,700

9,601

2,399

-215

4,556

1,086

-485

( 415 )

Page: 3

Center: ALBUQUERQUE (00605) of 4

EDUCATION

FOOD SERVICE

RECREATION

Advanced Welding

Dining (2 Servings)

Food Preparation

Food Storage

Snack Bar

Arts & Crafts

Gymnasium

Miscellaneous Recreation

Assembly Hall

Theater/Recreation Hall

Activity Room

Non-Resident Lounge

Men's Exercise Room

Women's Exercise Room

Learning Resource Center/Libr

Function Suggested

NSF

2,130

2,825

1,630

1,150

1,160

7,665

1,425

1,000

1,155

2,525

1,280

1,765

1,070

P - VOCATIONAL

C - FOOD SERVICE & MED/DENTAL

C - FOOD SERVICE & MED/DENTAL

C - FOOD SERVICE & MED/DENTAL

O - MULTI-PURPOSE RECREATION

O - MULTI-PURPOSE RECREATION

O - MULTI-PURPOSE RECREATION

O - MULTI-PURPOSE RECREATION

C1 - CAFE ANNEX

O - MULTI-PURPOSE RECREATION

O - MULTI-PURPOSE RECREATION

J - SOCIAL DEVELOPMENT

O - MULTI-PURPOSE RECREATION

O - MULTI-PURPOSE RECREATION

O - MULTI-PURPOSE RECREATION

Bldg Name Actual NSF Difference

2,130

2,825

1,630

1,150

1,160

7,665

1,425

1,000

1,155

2,525

1,280

1,765

1,070

Sub Total:

Sub Total:

Sub Total:

45,692

5,605

19,465

2,250

3,320

2,490

1,660

26,630

7,470

17,600

-120

-495

-860

-510

19,062

-1,865

1,865

Page: 4

Center: ALBUQUERQUE (00605) of 4

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

VACANT

Medical/Dental

Administration

Child Development Center

Warehouse

Operations & Maintenance

Vacant

Function Suggested

NSF

2,355

6,475

6,305

4,560

3,580

4,600

C - FOOD SERVICE & MED/DENTAL

D - SECURITY

A & B - ADMINISTRATION

CDC - CHILD DEVELOPMENT CTR

K - MATERIAL CONTROL

K - MATERIAL CONTROL

M - MAINTENANCE

Q & R - VACANT

Bldg Name Actual NSF Difference

2,355

7,425

6,305

4,560

4,255

4,600

Sub Total:

Sub Total:

Sub Total:

Sub Total:

2,355

13,730

8,815

4,600

2,680

8,300

3,360

4,980

3,320

2,680

11,660

8,300

-325

-875

2,945

-420

4,600

-325

2,070

4,600

Energy Management Report Center: ALBUQUERQUE (00605)

Page: 1 Date: 06/14/2013 of 3

CENTER ENERGY DATA

Yes

ENERGY CONSUMPTION ASSESSMENT

30% 86,120

96,833 122,574

ENERGY USE BY FUEL TYPE

Energy Audit :

Date of Audit :

Status of Energy Conservation Measure Recommendations :

Electric Company :

Percent Change since Baseline Year :

Natural Gas Company :

Property Status :

11/1/1997 Implemented Public Service Utility Co. of NM New Mexico Gas

Federally Owned (DOL)

1,831,401 6,249=

Total 18,037

MBtu

MBtu

Total $259,313 MBtu/ $14.377

BTU/GSF

BTU/GSF

BTU/GSF

Electricity

Natural Gas kWh

11,434 MCF = 11,788 MBtu

$188,018 $0.103= kWhElectricity

Natural Gas $71,295 = $6.235 MCF

ENERGY COST BY FUEL TYPE

COMMENTS

12/03- Retro fitted to T8s, Sensors installed on outside lights, New furnaces in Dorms & Student life bldg.

Center has an active Center Energy Conservation Committee. Center has improved lighting, installed outside timers.

New furnaces were in the dorms and Student Life. There are 2 fuel efficient vehicles at the center.

WATER CONSUMPTION ASSESSMENT

Percent Reduction Compared to Goal:

1,000 Gallons

1,000 Gallons

FY 2012 Energy Goal:

Energy Goals are being met. Keep up the Good Work to further Reduce Energy Usage.

FY 2012 Energy Consumption:

Note: The Federal Government has set a goal of 3% Energy Consumption reduction per year in EO 13423.

10,064 9,058 14,232

- 57%

Further Reduction in Water Usage is needed to meet Water Reduction Goals.

Note:

FY 2012 Goal:

FY 2012 Water Consumption:

1,000 Gallons

FY 2003 Energy Baseline:

FY 2007 Baseline:

The Federal Government has set a goal of 2% Water Consumption reduction per year in EO 13423 compared to the FY 2007 Baseline.

Page: 2 of 3

Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.

1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:

a. Turn it down (lights, heating & cooling),

b. Turn it off (lights, computers, other equipment),

c. Keep it tight (close doors and windows, use window blinds)

2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:

a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.

b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.

c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.

d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.

e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.

f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.

g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.

h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.

i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.

Page: 3 of 3

j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.

k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.

l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.

m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.

n. Caulk and fill cracks around doors and windows to reduce costly air leaks.

o. When replacing broken glass, use high transmittance, low heat gain windows.

p. Make sure automatic door closers are functioning properly to avoid drafts.

3. Buy energy efficient, buy EnergyStar (www.energystar.gov).

a. Buy EnergyStar appliances and equipment.

b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).

c. Replace broken thermostats with EnergyStar labeled programmable products.

d. Replace broken exit signs with EnergyStar LED exit signs.

Environmental Management Report

Page: 1 Date: 06/14/2013 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

Commercial Waste Service

HAZARDOUS MATERIALS STORAGE (EPCRA)

No Maintenance building

Pesticides (3 gallons), Propane (4 cylinders) Yes

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

N/A0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

N/A None

Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazadous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

HazMat Spill Response Plan :

Number of Regulated USTs :

Number of Un-regulated USTs :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance

ID LocationFuel Type Capacity

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

AHERA Regulated :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Waste Management, Inc.

Yes Oil based paint (1 gal/month), organic solvent (5 gals/month)

Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service

Safety Kleen, Inc.

No No

Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

No N/A

07/24/1987 Friable/Non-Friable Jan Slaughterbeck 02/01/2000 Yes No N/A Yes Yes

ID Fuel Type Capacity Location Overfill

Prevention Secondary Containment

1 Petroleum - Gasoline 250 Building K No Yes

Tank Status Active

Tank Status Prevention/Detection

Asbestos-Containing Materials Inventory

Date: 06/14/2013Center : Albuquerque (00605) Page: 1 of 2

Floor Finishes Floor Finishes

Floor Finishes Floor Finishes Floor Finishes

Floor Finishes Floor Finishes

Floor Finishes Floor Finishes Floor Finishes

Floor Finishes Floor Finishes Floor Finishes

Floor Finishes Floor Finishes

Bldg System

Bldg System

Bldg System

Bldg System

Bldg System

Bldg System

Mastic beneath floor tile 12x12 floor tile

Mastic beneath 12x12 tile 12x12 floor tile Mastic beneath 12x12 tile

Mastic beneath floor tile 12x12 floor tile

Mastic beneath 12x12 tile 12x12 floor tile, off-white Linoleum (covered)

Linoleum (covered) Mastic beneath 12x12 tile 12x12 floor tile, off-white

Mastic beneath 12x12 tile 12x12 floor tile, off-white

Category Description

Category Description

Category Description

Category Description

Category Description

Category Description

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Location

Location

Location

Location

Location

Location

Unit

Unit

Unit

Unit

Unit

Unit

Quantity

Quantity

Quantity

Quantity

Quantity

Quantity

Mech. room stairwell Mech. room stairwell

Arts/crafts room Arts/crafts room Game room

Throughout Throughout

Throughout Throughout Lounge

Lounge Throughout Throughout

Wing W Wing W

Building :

Building :

Building :

Building :

Building :

Building :

A & B - ADMINISTRATION

O - MULTI-PURPOSE RECREATION

Q & R - VACANT

S & T - CHARTER SCHOOL

U & V - CHARTER SCHOOL/LAUNDRY

W & X - DORMITORIES

Asbestos-Containing Materials Inventory

Page: 2 of 2

Ceiling Finishes Floor Finishes Floor Finishes

Bldg System Textured paint Mastic beneath 12x12 tile 12x12 floor tile

Category Description Sq. Ft.

Sq. Ft.

Sq. Ft.

Location Unit Quantity Bathrooms, wing Y Throughout Throughout

Building : Y & Z - DORMITORIES

Radon

Page: 1 of 1

A & B - ADMINISTRATION

C - FOOD SERVICE & MED/DENTAL

C1 - CAFE ANNEX

CDC - CHILD DEVELOPMENT CTR

CTST - STORAGE

D - SECURITY

E - STUDENT TRAINING

J - SOCIAL DEVELOPMENT

K - MATERIAL CONTROL

L - VOCATIONAL STORAGE

M - MAINTENANCE

N1 - DORMITORY

N2 - DORMITORY

O - MULTI-PURPOSE RECREATION

P - VOCATIONAL

Q & R - VACANT

S & T - CHARTER SCHOOL

U & V - CHARTER SCHOOL/LAUNDRY

W & X - DORMITORIES

Y & Z - DORMITORIES

Bldg Name

06/06/1990

06/06/1990

06/06/1990

06/06/1990

06/06/1990

06/06/1990

06/06/1990

06/06/1990

06/06/1990

06/06/1990

06/06/1990

Test Date

Yes

Yes

N/A

No

No

Yes

No

Yes

N/A

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Radon Testing

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

< 4 pCi

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.

Site Description

ALBUQUERQUE

Aerial View of Albuquerque JCC

Page: 1 Date: 06/14/2013 of 4

Comments:

Paving Type for Roads & Parking

Access road to Dormitory N1 is gravel.

Paving Type for Sidewalks

Asphalt and Gravel Concrete

Comments:

Topography Buildings and Structures

Center is fully enclosed by fencing. There is a metal mesh fence in the southern part of the center. Chain link fence has been superimposed on some parts of the metal mesh fence. There are also chain link fences around some of the buildings' mechanical equipment and CDC outdoor play areas.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water System

Treatment Type Storage Type Storage Capacity(Gallons)

NoMasterAlbuquerque Bernalillo County Water UtilPublic Water Authority

None 0None

The center is provided with two master water meters, located outside the property line. One meter is located at the northwest corner of the center. The other water meter is located on the east of Multi-Purpose Recreation Building O.

Comments:

Comments:

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time (Minutes)

Yes 0 3None Municipal

The nearest city fire station is about 0.5 miles away from the center and the emergency response time is about 3 minutes.

Number of Deficiencies = 1

Number of Deficiencies = 1

SITE FEATURES

UTILITIES

2. Fire Protection System

Buildings Structures20 22Flat

Surrounding

Outdoor Recreation

Light Commercial, Residential

Basketball, Running Track, Soft/Baseball, Volleyball Public Road

Part of The Site

Part of The Site

Chain Link

Wrought Iron

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good

Fencing

Other Features

Page: 2 Date: 06/14/2013 of 4

Comments:

Sewage Treatment Flow

Center sanitary system discharges waste into the city sanitary sewer system operated by the Albuquerque-Bernalillo County Water Utility Authority.

Center

Publicly Owned Treatment Works

Center

Gravity

Maintenance ResponsibilityOwnership

Comments: The underground natural gas distribution system is provided with two master gas meters and serves as a fuel source for facility heating, cooking and domestic hot water. One meter is located at the east corner of Administration Building A & B. The other gas meter is located on the northwest corner of Student Training Building E.

New Mexico Gas

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

Public Service Utility Co. of NM

The primary services are brought to the site from overhead lines along the center's eastern and western boundary.

Services enter the center at three locations, one at the western, one at the northeastern and one at the southeastern boundary. The overhead lines at all three service points transit to underground before entering the center. Each service has its own meter. Except Dormitory Buildings N1 and N2, the northeast service provides secondary services to all buildings via pad-mounted transformers. The shoutheast service serves Dormitory Building N1 via a pad-mounted transformer. Similarly, the west service serves Dormitory Building N2 Dormitory via a pad-mounted transformer. The center owns and maintains all pad-mounted transformers via an outside electrical contractor.

Pad Center

Utility Utility

No

12.47/7.2 kV, 3-Phase, 4 Wire

120/208V, 3-Phase, 4 WireUnderground

Overhead & UndergroundPrimary Service

Secondary Service

Distribution Characteristics

3. Sanitary Sewer System/ Sewage Treatment Plant

5. Fuel Distribution System

Number of Deficiencies = 3

System Capacity Adequate System Condition

Yes Good

4. Storm Water System

Drain Type On-Site Storm Water Management

Surface Run-off N/A

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes GoodCenter

Comments: Three storm water ditches fill during heavy rain and slowly percolate.

Gas Company Metering

Master

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

7. Electrical (Service)

Transformer Maint Resp

Center

System Capacity Adequate System Condition

Yes Good

Generator

None

ATS MTS

No No

6. Central Plant: None

Metering Master

Page: 3 Date: 06/14/2013 of 4

Comments:

Telephone Company

On-site Line Owner

Telephone service is provided by Qwest with four T1 lines which terminate in the main telephone switch room located in the basement of Administration Building A&B. One T1 line is reserved for Siatech, two others are utilized by the center and a fourth one is a spare. Local telephone service is provided by Qwest. Long distance telephone voice over internet protocol (VoIP) service and LAN/WAN networks are maintained by the Job Corps Data Center (JCDC). All data communication equipment and devices are located in the server room behind the student record office on the first floor. The main telephone switch room and the server room are supported by a 1 kVA and an 8 kVA UPS module respectively. The center has a public address system via phones and speakers.

The site security system includes Closed Circuit Television (CCTV) cameras, color monitors and gate operators.

CCTV cameras are installed on the exterior of Dormitory Building N1 scanning the southeastern corner of the campus. The cameras are monitored from the RA office. There are a vehicular gate operator at the north parking entrance and two chain link gate operators at the northeast parking entrances. The gate operators are remotely controlled from the security office in Administration Building A&B. The fire alarm system in buildings on center is stand alone. Cable TV is provided by Comcast in the dormitories, dining and other recreational facilities.

Qwest

Maint. Responsibility

Center Center

CCTV Cameras, B&W Monitor, Color Monitor, Door Alarms, Electric Gate Operator

01/01/1980CenterActive AbovegroundBuilding K NoPetroleum - Gasoline

STORAGE TANKS

TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID

Reg.

9. Electrical (Communication/Alarm/Security)

Equip/Veh Fueling

Purpose

Yes

Stand-Alone

VOIP

System Capacity Adequate System Condition

GoodYes

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Pole Pole Building Pole

Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Comments: The site lighting system is owned and maintained by the center. Lighting around the running track has recently been enhanced by four new solar powered pole lights.

Number of Deficiencies = 3

Number of Deficiencies = 7

Fire Alarm Security

Page: 4 Date: 06/14/2013 of 4

ACCESSIBILITY

Yes

Site is mostly flat and easily accessible.Comments:

Comments:

UnknownNoUnknown

Building J - Social Development, built in 1932, is the last remaining building of the Saint Anthony's School that previously occupied the site, and it is a good example of local architecture of that period.

No

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Earthquake Risk

Medium Low LowLow LowIBC Low

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

The center is located in a dessert type of environment.Comments:

Number of Deficiencies = 2

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

N/AYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X Good Fair Poor

HISTORIC PRESERVATION

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Active Energy Use Reduction Program

Active Water Use Reduction Program

Approximate or Measured Waste Recycled

Use of School Dude or CMMS for Preventative Maintenance

Green Purchasing Policy Practiced

Site Stormwater Absorption Measures in Place

Center has Onsite Renewable Energy (PV or Wind)

Center has a Chartered Green Committee & Roster

Center Uses Green Cleaning Practices

SUSTAINABILITY

NO

NO

NO

NO

NO

NO

NO

NO

Building Descriptions and Utilities

BUILDING A & B - ADMINISTRATION

Building Descriptions

Page: 1 of 99

Building: A & B - ADMINISTRATION

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood

Brick Masonry

Wall Roof Rigid Rigid

Metal - Metal Frame Storefront - Metal Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Business 12,750 8,080 1 Owned 1962 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

Yes

N/A

No

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material

There are gutters and downspouts at entrances.

Drainage Year Life

Remaining Type Area Served

Built-up Roofing Surface Run-off 2008 16 Gable Entire Building

Comments:

3. Roof

Entire Building

Area Served

Page: 2 of 99

Building: A & B - ADMINISTRATION

INTERIOR FINISH

Carpet Ceramic Tile Concrete

Brick CMU Drywall Plaster Wood Paneling

Metal Unit - Metal Frame Wood Units - Metal Frame

VERTICAL CIRCULATION

Concrete Stairs

Comments: The stairs go to the basement mechanical, telephone, and electrical rooms.

Awning Units - Steel Frame; Single Glazing; Fixed - Aluminum Frame; Double Glazing;

Fixed - Steel Frame; Single Glazing; Fixed - Wood Frame; Single Glazing;

Acoustical Tile Exposed Structure Gypsum Board Wood

Windows6.

Floors1. Asbestos: Yes

Interior Walls2.

3.

Interior Doors4.

Ceilings

Page: 3 of 99

Building: A & B - ADMINISTRATION

Mechanical Restroom

Comments: Ceiling and roof-mounted exhaust fans ventilate the bathrooms.

Ventilation Area Served

Evaporative Cooler

Packaged Direct

Expansion (Air Source)

Single Duct

Window Unit

None

None

Electric

Electric

Mechanical

Natural

None

None

Entire Building

Offices

Exhaust Ventilation

Roof-mounted evaporative cooling units provide cooling and fresh air to Buildings A & B.

Window air conditioning units provide supplemental DX-cooling to the basement storage/electrical and student accountability records administrator.

Comments:

Comments:

Number of Deficiencies = 2

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

A horizontal air-handling unit with hot water heating coils provides ducted heating and ventilation air to most of the offices in Buildings A & B. The unit is a Trane Torrivent, model T-31, S/N U77485. It is located in the basement equipment room. Originally, the flow control valve for this unit was pneumatically controlled. Since the pneumatic control system failed and had even been partially dismantled, the unit controls have been manipulated and on a trial-and-error basis. This lack of automatic control is inefficient and does not offer the comfort level the H&V unit was designed to deliver.

A gas-fired hot water boiler provides heating water pumped by a floor-mounted end suction pump (A.

O. Smith, model E102, 2.0 HP) to the floor-mounted baseboard heaters serving most of the offices and reception extension in Buildings A & B. The unit is a Weil McLain hot water boiler, model J-10-B, S/N JB, 1485 MBH gas input and 1188 MBH output. It is located in the basement equipment room.

Originally, 8-zone heating water distribution system was pneumatically controlled. Since the pneumatic control system failed and had even been partially dismantled, the zoned water distribution system controls have been manipulated and on a trial-and-error basis. This lack of automatic control is inefficient and does not offer the comfort level the heating system was designed to deliver.

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Hot Water Boiler

Gas-Fired Hot Water Boiler

Single Duct

Baseboard

Two-Pipe

Two-Pipe

Pneumatic

Pneumatic

Mechanical

Natural

None

None

Entire Building

Entire Building

Ventilation2.

System Type

Number of Deficiencies = 3

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

3. Air Conditioning

Page: 4 of 99

Building: A & B - ADMINISTRATION

A 30-gallon capacity Rheem gas-fired water heater (model 22V30S-30F, S/N RHLN0708V11888, 30 MBH gas input, built in 07/2008) provides domestic hot water to Buildings A & B. It is located in the basement equipment room. In addition, two Chronomite instant flow electric water heaters (model 5R- 30L/120, 3.6 kW) provide domestic hot water to the reception extension male and female toilets in Building A.

Comments:

Cast-Iron None None

Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Sink Urinal Water Closet (Tank)

Gas (Natural)

None None ABC Type Fire Extinguisher

Comments: Service is brought to the building from a pad-mounted 75 kVA transformer outside. Service enters a 350A MCB main distribution panel (MDP) located in the storage room in Building B. The MDP has a transient voltage surge suppressor protection unit.

Galvanized Steel Galvanized Steel Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

High Intensity Discharge (HID)

Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3. Number of Deficiencies = 1

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

LIGHTING

Page: 5 of 99

Building: A & B - ADMINISTRATION

FIRE ALARM

Comments: The fire alarm control/annunciator panel is located in the reception/security desk area in this building.

Comments: The center's main telephone switchboard is located in the basement storage room of this building.

Audible Alarm Duct Smoke Detector Heat Detector Main Control/Annunciator Panel Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System Magnetic Door/Alarm Connected to Main System None

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

Comments: Building A has a tritium gas exit sign which expires in February 2013.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Reception

Lounges

Conference Rooms

Corridors & Stairs

Toilets

Equipment Rooms (Elec/Mech)

Storage Rooms

Mail Room

Area Recommended Level

Recorded Level Light Type

Battery Backup Battery Backup

Emergency Exit

Number of Deficiencies = 2

Interior Lighting2. Number of Deficiencies = 2

Emergency /Exit Lighting3. Number of Deficiencies = 1

COMMUNICATION

Electric Water Gas No YesNo

BUILDING UTILITY METERING

Type Location None None

Comments: There are no CO detectors in this building. It is required by DOL Directive Information Notice 12-27 and

NFPA 720, 2012.

CARBON MONOXIDE DETECTION

Page: 6 of 99

Building: A & B - ADMINISTRATION

GENERAL BUILDING CONDITION

Rating

Comments:

X Good Fair Poor

The hot water boiler and heating/ventilating units are obsolete (40-year old). The pneumatic control of zoned heating water distribution and air distribution systems do not function properly. This lack of automatic control is inefficient and does not offer the comfort level the heating system was designed to deliver.

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Structure: Good Exterior: Good Interior: Good Mechanical: Fair Electrical: Good

BUILDING C - FOOD SERVICE & MED/DENTAL

Page: 7 of 99

Building: C - FOOD SERVICE & MED/DENTAL

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Steel

Brick Masonry

Wall Roof Batt Batt

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Assembly 11,345 7,960 1 Owned 1962 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

N/A

N/A

No

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material

There are gutters and downspouts at the entrances.

Drainage Year Life

Remaining Type Area Served

Built-up Roofing

Rolled Asphalt

Metal

Surface Run-off

Surface Run-off

Surface Run-off

Gable

Shed

Shed

Original Building

Vestibule

Building Addition

Comments:

3. Roof

Page: 8 of 99

Building: C - FOOD SERVICE & MED/DENTAL

INTERIOR FINISH

Ceramic Tile Concrete Quarry Tile Terrazzo Vinyl Tile

Brick Ceramic Tile Drywall Glass Block Stainless Steel

Wood Unit - Metal Frame

VERTICAL CIRCULATION

None

Metal Units - Metal Frame Wood Unit - Metal Frame

Fixed - Aluminum Frame; Double Glazing; Fixed - Steel Frame; Single Glazing;

Acoustical Tile Mirror Lay-in Tiles Plaster

Exterior Doors5.

Windows6.

Floors1. Number of Deficiencies = 1

Interior Walls2.

3.

Interior Doors4.

Page: 9 of 99

Building: C - FOOD SERVICE & MED/DENTAL

Mechanical

Mechanical

Bathrooms

Kitchen

Comments:

Comments:

Ceiling and roof-mounted exhaust fans ventilate the bathrooms.

A make up air unit using a hot water heating coil is located in the mechanical room and supplies make-up air to the kitchen. Roof mounted exhaust fans serve the kitchen and dishwasher hoods.

Ventilation Area Served

Evaporative Cooler

Packaged Direct

Expansion (Air Source)

Single Duct

Single Duct

None

None

Electric

Electric

Mechanical

Mechanical

None

None

Entire Building

Medical/Dental

Exhaust Ventilation

Roof-mounted evaporative cooling units provide cooling air to the kitchen and dining areas.

Two rooftop-packaged gas-fired units provide DX-cooling and fresh air to the medical/dental rooms.

The typical unit is a Carrier model 48TJE004-511. Ceiling fans enhance room air circulation in some of the medical/dental offices.

Comments:

Comments:

Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

An air-handling unit with ducted hot water heating coils provides heating and make-up air to the kitchen. The unit is a Sterling/Alton model HEDM1250, S/N 93-56030, located in the mechanical room.

A gas-fired hot water boiler provides heating water pumped by an in-line pump to the floor-mounted baseboard heaters and heating ventilation unit. The unit is a Peerless packaged hot water boiler, model 210-10-W, 1890 MBH gas input and 1512 MBH output. It is located in the mechanical room. The electric water booster heater that supports the dishwasher system is Hatco model C-54-1803489604, 54 kW, 480V/3-phase, 6-gallon storage capacity, 552 GPH recovery at 40 degrees rise and 315 GPH at 70 degrees rise.

Two rooftop-packaged gas-fired units provide heating and fresh air to the medical/dental rooms. The typical unit is a Carrier model 48TJE004-511. Ceiling fans enhance room air circulation in some of the medical/dental offices.

Two small capacity electric radiant heaters provide heating to the covered queuing entrance foyer.

Comments:

Comments:

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Hot Water Boiler

Gas-Fired Hot Water Boiler

Gas-Fired Packaged

Electric Resistance

Single Duct

Baseboard

Single Duct

Radiant Heater

Two-Pipe

Two-Pipe

None

None

Thermostatic Valves

Electric

Electric

Electric

Mechanical

Natural

Mechanical

Natural

None

None

None

None

Kitchen

Dining Hall

Medical/Dental

Vestibules

Ventilation2.

System Type

Number of Deficiencies = 3

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Page: 10 of 99

Building: C - FOOD SERVICE & MED/DENTAL

A 130-gallon capacity A. O. Smith gas-fired water heater (model BTU500A104, S/N 1231M001541,

499.9 MBH gas input, 575.64 GPH recovery, built in 08/2012) provides domestic hot water to the building. It is located in the mechanical room. The hot water loop has an in-line Taco circulating pump (model 0010-F2, 1/8 HP) and a Culligan water softener system.

Comments:

Cast-Iron Outdoor None

Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Multi-Compartment Sink Service Sink Shower/Bathtub Urinal Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical

Comments: A wet chemical automatic fire suppression system is provided in the kitchen hood.

Copper Copper Gas-Fired Water Softener No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

Location UL300 Compliance Status Kitchen Compliant

Comments: The kitchen hood is provided with a wet chemical fire suppression system with an automatic gas shut-off valve, which meets the requirements of standard UL-300.

UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION

Page: 11 of 99

Building: C - FOOD SERVICE & MED/DENTAL

Comments: Service is brought to the building from a utility-owned, pad-mounted 75 kVA transformer outside. Service enters to a 300A MCB main distribution panel (MDP) located in the mechanical room. This transformer also serves Building S&T. The MDP also subfeeds Cafe Annex Building CA.

FIRE ALARM

Comments: The fire alarm devices in this building are connected to the main fire alarm control/annunciator panel in the security office in Building A.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

Comments: This building has two tritium gas exit signs which expire in February 2013.

Compact Fluorescent High Intensity Discharge (HID)

Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Incandescent

Incandescent

Offices

Food Preparation

Dining/Lunch Rooms

Dishwashing

Medical/Dental

Wards (Patient)

Reception

Lounges

Corridors & Stairs

Toilets

Storage Rooms

Equipment Rooms (Elec/Mech)

Toilets

Area Recommended Level

Recorded Level Light Type

Battery Backup Battery Backup

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 1

Page: 12 of 99

Building: C - FOOD SERVICE & MED/DENTAL

Connected to Main System None Connected to Main System Local Cable Company

Telephone Security Public Address Television

GENERAL BUILDING CONDITION

Rating

Comments:

X Good Fair Poor

The interior configuration is inadequate, undersized and below DOL standards.

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No NoNo

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good

This building has been recommended for demolition in the Long Range Development Plan after construction of new cafeteria.

The demolition is included in Project 3299.

DEMOLITION RECOMMENDATION

Type Location None None

Comments: There are no CO detectors in this building. It is required by DOL Directive Information Notice 12-27 and

BUILDING C1 - CAFE ANNEX

Page: 13 of 99

Building: C1 - CAFE ANNEX

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Wood Wood

CMU Masonry Glass Block Stucco Wood

Wall Roof None None

Metal Units - Metal Frame Wood Unit - Metal Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Assembly 1,140 1,000 1 Owned 1998 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

N/A

N/A

Yes

N/A

N/A

N/A

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material Drainage Year Life

Remaining Type Area Served

Metal Gutters and Downspouts 1998 26 Shed Entire Building

3. Roof

Page: 14 of 99

Building: C1 - CAFE ANNEX

INTERIOR FINISH

Concrete

Stucco on CMU Windows

None

Natural Entire Building

Ventilation Area Served

VERTICAL CIRCULATION

None

Sliding - Aluminum Frame; Double Glazing;

Evaporative Cooler

Single Duct None Electric Mechanical None Entire Building

Exposed Structure

Exhaust Ventilation

Two roof-mounted evaporative cooling units provide cooling air to the building.Comments:

Number of Deficiencies = 1

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

A vertical gas-fired furnace provides heating to the building. The unit is a Trane model TUE1B080A9361AC, 80 MBH gas input, built in 02/2009. It is located in the mechanical closet.

Comments:

HVAC

Heat1.

Gas-Fired Furnace

Single Duct None Electric Natural None Entire Building

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Page: 15 of 99

Building: C1 - CAFE ANNEX

Cast Iron None None

Electric Water Cooler

Gas (Natural)

None None ABC Type Fire Extinguisher

Comments: Service to this building is sub-fed from Cafeteria Building C to a 100A, 12 circuit loadcenter mounted on the exterior wall.

None Copper None None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Comments: The recorded footcandle level includes natural light contribution.

High Intensity Discharge (HID)

Comments: Exterior lighting is provided by surrounding area pole-mounted light fixtures which are controlled by time clock and photocells.

T8 - Fluorescent50Recreation 50

Area Recommended Level

Recorded Level Light Type

None None

Main Loadcenter 120/208V, 1-Phase, 3 Wire Loadcenter Receptacles, Switches

Sprinkler System Stand Pipe System Fire Suppression

Emergency Exit

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

Page: 16 of 99

Building: C1 - CAFE ANNEX

FIRE ALARM

None

None None None None

Telephone Security Public Address Television

Number of Deficiencies = 1

GENERAL BUILDING CONDITION

Rating

Comments:

X Good Fair Poor

Interiors and exterior are worn and in fair condition.

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No NoNo

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good

This building has been recommended for demolition in the Long Range Development Plan after Construction of new cafeteria.

The demolition is included in Project 3299.

DEMOLITION RECOMMENDATION

Type Location None None

Comments: There are no CO detectors in this building. It is required by DOL Directive Information Notice 12-27 and

BUILDING CDC - CHILD DEVELOPMENT CTR

Page: 17 of 99

Building: CDC - CHILD DEVELOPMENT CTR

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel

Brick Masonry Metal Siding

Comments: The building has brick end walls.

Wall Roof Batt Batt

Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Day Care 8,245 6,305 1 Owned 1994 Not Evaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

No

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material Drainage Year Life

Remaining Type Area Served

Metal Gutters and Downspouts 1994 22 Shed Entire Building

3. Roof

Page: 18 of 99

Building: CDC - CHILD DEVELOPMENT CTR

INTERIOR FINISH

Carpet VCT Vinyl Tile

Ceramic Tile Drywall Prefabricated panels

Wood Unit - Metal Frame

Mechanical

Mechanical

Restroom

Kitchen

Comments:

Comments:

Ceiling-mounted exhaust fans ventilate the restrooms.

A roof-mounted exhaust fan ventilates the Greenheck kitchen hood.

Ventilation Area Served

VERTICAL CIRCULATION

None

Double Hung - Aluminum Frame; Double Glazing;

Acoustical Tile

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Eight vertical gas-fired furnaces provide heating to the building.