Albuquerque
Job Corps Center Albuquerque, NM
Facility Planning Report Volume II
Supporting Data
Final June 2013
Department of Labor/ Office of Job Corps
22Albuquerque Job Corps Center
Albuquerque
Job Corps Center Albuquerque, NM
Facility Planning Report Volume II
Supporting Data
Final June 2013
Student Promenade
33 Albuquerque Job Corps Center
CONTENTS
ALBUQUERQUE JOB CORPS CENTER
FACILITY PLANNING REPORT
VOLUME I - Planning Strategy
• Existing Site Plan
• Center Statistics
INTRODUCTION
• Purpose
• Report Contents
EXECUTIVE SUMMARY
A. EXISTING CONDITIONS
• Background
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Ownership
• Facility Assessment by Function
• Energy
• Environmental Issues
• Sustainability
• Accessibility Standards
• Health and Life Safety Issues
• Summary of Defi ciencies
B. RECOMMENDATIONS
• Status of the Previous (PY09) Plan
• Signifi cant Issues
• PY 12 Plan Overview
• Summary of Proposed Projects
• Proposed Site Plan
• Implementation Plan
• Summary of National Projects
• Project Data Sheets
C. PLANNING ANALYSIS
• Purpose
• Planning Objectives and Assumptions
• Space Utilization Analysis
• Federal Real Property Asset Management
• Mission Dependency Site Plan
• Defi ciency Analysis
• Facility Condition Summary Report
• Building Condition by Function
• Building Condition Site Plan
VOLUME II - Supporting Data
• Vicinity Map
• Location Map
• Existing Site Plan
D. DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Energy Management Report
• Environmental Management
Asbestos Report Radon Report
• Site Descriptions
• Building Descriptions
E. DEFICIENCIES
F. CORRESPONDENCE AND REPORTS
• Center Review Meeting Minutes
• Survey Brief
• RA and Student Facility Feedback Questionnaire
• Life Safety Defi ciencies Transmittal and List
• O & M Defi ciency List
• Active Warranty Report
• FRPC Performance Measures Matrix
44Albuquerque Job Corps Center
55 Albuquerque Job Corps Center
66Albuquerque Job Corps Center
77 Albuquerque Job Corps Center
D Descriptions
BUILDINGS AND STRUCTURES
00605 ALBUQUERQUE 06/14/2013
1Page: of Date:
A & B - ADMINISTRATION
C - FOOD SERVICE & MED/DENTAL
C1 - CAFE ANNEX
CDC - CHILD DEVELOPMENT CTR
CTST - STORAGE
D - SECURITY
E - STUDENT TRAINING
J - SOCIAL DEVELOPMENT
K - MATERIAL CONTROL
L - VOCATIONAL STORAGE
M - MAINTENANCE
N1 - DORMITORY
N2 - DORMITORY
O - MULTI-PURPOSE RECREATION
P - VOCATIONAL
Q & R - VACANT
S & T - CHARTER SCHOOL
U & V - CHARTER SCHOOL/LAUNDRY
W & X - DORMITORIES
Y & Z - DORMITORIES
0013 - RECREATION STORAGE
0014 - RECREATION STORAGE
0017 - LAUNDRY STORAGE
0018 - MATERIAL CONTROL STORAGE
0019 - DIESEL STORAGE TANK
0020 - DRUM STORAGE
0021 - MAINTENANCE STORAGE
0023 - TRAILER
0024 - MAINTENANCE STORAGE
0025 - RECREATION TOILET
0026 - PELLET STORAGE SILO
0027 - PELLET BOILER BUILDING
0028 - AMPHITHEATER
0029 - WELDING STORAGE 1
0030 - WELDING STORAGE 2
02 -PAVILION
04 - PAVILION
06 - STORAGE
08 - STORAGE
09 - STORAGE
12 - STORAGE
5 - STORAGE
Name GSF
12,750 11,345 1,140 8,245 1,980
21,390 4,990 5,615 3,200 4,890
32,310 25,963 20,290 20,640 5,720 5,720 5,720 8,275 8,275
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business Assembly Assembly Day Care Storage Business Business Business Storage Business Storage Residential Residential Assembly Factory/Ind.
Residential Business Residential Residential Residential Storage Storage Storage Storage Utility/Misc.
Storage Storage Utility/Misc.
Storage Utility/Misc.
Utility/Misc.
Utility/Misc.
Assembly Storage Storage
Storage
Good Good Good Good Good Good Good Fair
Good Good Good Good Good Good Good Fair
Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0060500002 0060500004 0060500028 0060500023 0060500029 0060500005 0060500006 0060500010 0060500011 0060508050 0060500013 0060500027 0060508040 0060500014 0060500015 0060500016 0060500017 0060500018 0060500019 0060500020 0060508052 0060508053 0060508054 0060508055 0060508056 0060508057 0060508058 0060508059 0060508060 0060508061 0060508062 0060508063 0060508064 0060508065 0060508066 0060500025 0060508042 0060508044 0060508046 0060508047 0060508051 0060500021
BUILDINGS AND STRUCTURES
00605 ALBUQUERQUE 06/14/2013
2Page: of Date:
20 209,438
22 3,582
42 213,020
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/14/2013
Space Utilization By Function 00605 Albuquerque Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 325 Non Residents 90
415Total Students
(325)
(415)
(415)
DIFFERENCE
32,500
26,630
7,470
52,810
45,692
5,605
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (415) Non-Academic
20 -- ACT (Off-Ctr) 30 -- Advanced Welding + 24 -- Carpentry + 24 -- Cement Masonry + 24 -- Electrician Apprentice + 24 -- Facilities Maint. and Const. + 30 -- Health Occupations (Off-Ctr) 60 -- Office Administration 24 -- Plumbing + 48 -- Welding +
Vocational Theory (198)
Dining (2 Servings) Food Preparation Food Storage
6,460 5,865 5,230
33,940 1,315
13,751 8,706
2,130 4,199 2,110 2,286 2,255
2,215 2,030 3,385
2,625
2,825 1,630 1,150
3,250
3,900 23,400
1,950
4,150 4,150
2,250 1,800 1,800 1,200 1,800
2,700 1,200 3,600
1,980
3,320 2,490 1,660
3,210
1,330 10,540
-635
9,601 4,556
-120 2,399
1,086
-485 -215
-495 -860 -510
Vocations
20,310
19,062
-1,865
06/14/2013
Space Utilization By Function 00605 Albuquerque Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 257.45 106,840 153,072
(415)
(415)
(415)
(415)
(0)
DIFFERENCE
209,438
0.73
TOTAL GSF
NET TO GROSS RATIO
17,600
2,680
11,660
8,300
19,465
2,355
13,730
8,815
4,600
Activity Room Arts & Crafts Assembly Hall Gymnasium Learning Resource Center/Library Men's Exercise Room Miscellaneous Recreation Non-Resident Lounge Snack Bar Theater/Recreation Hall Women's Exercise Room
Medical/Dental
Administration Child Development Center (42)
Operations & Maintenance Warehouse
Vacant
6.46
2,525 1,160 1,000 7,665
1,765 1,425 1,280
1,155 1,070
2,355
7,425 6,305
4,255 4,560
4,600
2,680
8,300 3,360
3,320 4,980
-325
-875 2,945
-420
RESIDENT
NON-RESIDENT
(325)
(90) 15
50 16,250 1,350
1,865
-325
2,070
4,600
46,232
Net Square Footage By Building Date: 06/14/2013 Page: 1
Center: ALBUQUERQUE (00605) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
4,140 4,140
13,660 12,000
2,800
2,600
2,210 2,000
2,160 1,925 1,000
Y & Z - DORMITORIES
W & X - DORMITORIES
N1 - DORMITORY
N2 - DORMITORY
Y & Z - DORMITORIES
N2 - DORMITORY
W & X - DORMITORIES
N1 - DORMITORY
W & X - DORMITORIES
Y & Z - DORMITORIES
N1 - DORMITORY
N1 - DORMITORY
N2 - DORMITORY
Y & Z - DORMITORIES
W & X - DORMITORIES
W & X - DORMITORIES
Y & Z - DORMITORIES
N2 - DORMITORY
N1 - DORMITORY
U & V - CHARTER SCHOOL/LAUNDRY
Bldg Name Actual NSF Difference
33,940
6,460
1,315
5,230
5,865
Sub Total: 52,810
23,400
3,250
1,950
3,900
32,500
10,540
3,210
-635
1,330
5,865
( 325
20,310 rooms; beds rooms; beds rooms; beds rooms; beds
Page: 2
Center: ALBUQUERQUE (00605) of 4
EDUCATION
Academic
Vocational Theory (198)
Carpentry
Cement Masonry
Plumbing
Welding
Facilities Maint. and Const.
Non-Academic
Electrician Apprentice
Office Administration
Function Suggested
NSF
1,260 3,600 1,825
4,600 1,260
2,625
1,844 1,675
1,430
2,030
3,385
1,575
1,358 2,686
1,605
1,476
2,215
E - STUDENT TRAINING
E - STUDENT TRAINING
U & V - CHARTER SCHOOL/LAUNDRY
E - STUDENT TRAINING
E - STUDENT TRAINING
S & T - CHARTER SCHOOL
E - STUDENT TRAINING
P - VOCATIONAL
P - VOCATIONAL
CTST - STORAGE
L - VOCATIONAL STORAGE
P - VOCATIONAL
L - VOCATIONAL STORAGE
P - VOCATIONAL
P - VOCATIONAL
L - VOCATIONAL STORAGE
P - VOCATIONAL
E - STUDENT TRAINING
E - STUDENT TRAINING
E - STUDENT TRAINING
A & B - ADMINISTRATION
E - STUDENT TRAINING
J - SOCIAL DEVELOPMENT
J - SOCIAL DEVELOPMENT
J - SOCIAL DEVELOPMENT
J - SOCIAL DEVELOPMENT
E - STUDENT TRAINING
P - VOCATIONAL
L - VOCATIONAL STORAGE
CTST - STORAGE
E - STUDENT TRAINING
Bldg Name Actual NSF Difference
13,751
2,625
4,199
2,110
2,030
3,385
2,255
8,706
2,286
2,215
4,150
1,980
1,800
1,800
1,200
3,600
1,800
4,150
1,200
2,700
9,601
2,399
-215
4,556
1,086
-485
( 415 )
Page: 3
Center: ALBUQUERQUE (00605) of 4
EDUCATION
FOOD SERVICE
RECREATION
Advanced Welding
Dining (2 Servings)
Food Preparation
Food Storage
Snack Bar
Arts & Crafts
Gymnasium
Miscellaneous Recreation
Assembly Hall
Theater/Recreation Hall
Activity Room
Non-Resident Lounge
Men's Exercise Room
Women's Exercise Room
Learning Resource Center/Libr
Function Suggested
NSF
2,130
2,825
1,630
1,150
1,160
7,665
1,425
1,000
1,155
2,525
1,280
1,765
1,070
P - VOCATIONAL
C - FOOD SERVICE & MED/DENTAL
C - FOOD SERVICE & MED/DENTAL
C - FOOD SERVICE & MED/DENTAL
O - MULTI-PURPOSE RECREATION
O - MULTI-PURPOSE RECREATION
O - MULTI-PURPOSE RECREATION
O - MULTI-PURPOSE RECREATION
C1 - CAFE ANNEX
O - MULTI-PURPOSE RECREATION
O - MULTI-PURPOSE RECREATION
J - SOCIAL DEVELOPMENT
O - MULTI-PURPOSE RECREATION
O - MULTI-PURPOSE RECREATION
O - MULTI-PURPOSE RECREATION
Bldg Name Actual NSF Difference
2,130
2,825
1,630
1,150
1,160
7,665
1,425
1,000
1,155
2,525
1,280
1,765
1,070
Sub Total:
Sub Total:
Sub Total:
45,692
5,605
19,465
2,250
3,320
2,490
1,660
26,630
7,470
17,600
-120
-495
-860
-510
19,062
-1,865
1,865
Page: 4
Center: ALBUQUERQUE (00605) of 4
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Medical/Dental
Administration
Child Development Center
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
2,355
6,475
6,305
4,560
3,580
4,600
C - FOOD SERVICE & MED/DENTAL
D - SECURITY
A & B - ADMINISTRATION
CDC - CHILD DEVELOPMENT CTR
K - MATERIAL CONTROL
K - MATERIAL CONTROL
M - MAINTENANCE
Q & R - VACANT
Bldg Name Actual NSF Difference
2,355
7,425
6,305
4,560
4,255
4,600
Sub Total:
Sub Total:
Sub Total:
Sub Total:
2,355
13,730
8,815
4,600
2,680
8,300
3,360
4,980
3,320
2,680
11,660
8,300
-325
-875
2,945
-420
4,600
-325
2,070
4,600
Energy Management Report Center: ALBUQUERQUE (00605)
Page: 1 Date: 06/14/2013 of 3
CENTER ENERGY DATA
Yes
ENERGY CONSUMPTION ASSESSMENT
30% 86,120
96,833 122,574
ENERGY USE BY FUEL TYPE
Energy Audit :
Date of Audit :
Status of Energy Conservation Measure Recommendations :
Electric Company :
Percent Change since Baseline Year :
Natural Gas Company :
Property Status :
11/1/1997 Implemented Public Service Utility Co. of NM New Mexico Gas
Federally Owned (DOL)
1,831,401 6,249=
Total 18,037
MBtu
MBtu
Total $259,313 MBtu/ $14.377
BTU/GSF
BTU/GSF
BTU/GSF
Electricity
Natural Gas kWh
11,434 MCF = 11,788 MBtu
$188,018 $0.103= kWhElectricity
Natural Gas $71,295 = $6.235 MCF
ENERGY COST BY FUEL TYPE
COMMENTS
12/03- Retro fitted to T8s, Sensors installed on outside lights, New furnaces in Dorms & Student life bldg.
Center has an active Center Energy Conservation Committee. Center has improved lighting, installed outside timers.
New furnaces were in the dorms and Student Life. There are 2 fuel efficient vehicles at the center.
WATER CONSUMPTION ASSESSMENT
Percent Reduction Compared to Goal:
1,000 Gallons
1,000 Gallons
FY 2012 Energy Goal:
Energy Goals are being met. Keep up the Good Work to further Reduce Energy Usage.
FY 2012 Energy Consumption:
Note: The Federal Government has set a goal of 3% Energy Consumption reduction per year in EO 13423.
10,064 9,058 14,232
- 57%
Further Reduction in Water Usage is needed to meet Water Reduction Goals.
Note:
FY 2012 Goal:
FY 2012 Water Consumption:
1,000 Gallons
FY 2003 Energy Baseline:
FY 2007 Baseline:
The Federal Government has set a goal of 2% Water Consumption reduction per year in EO 13423 compared to the FY 2007 Baseline.
Page: 2 of 3
Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.
1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:
a. Turn it down (lights, heating & cooling),
b. Turn it off (lights, computers, other equipment),
c. Keep it tight (close doors and windows, use window blinds)
2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:
a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.
b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.
c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.
d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.
e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.
f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.
g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.
h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.
i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.
Page: 3 of 3
j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.
k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.
l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.
m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.
n. Caulk and fill cracks around doors and windows to reduce costly air leaks.
o. When replacing broken glass, use high transmittance, low heat gain windows.
p. Make sure automatic door closers are functioning properly to avoid drafts.
3. Buy energy efficient, buy EnergyStar (www.energystar.gov).
a. Buy EnergyStar appliances and equipment.
b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).
c. Replace broken thermostats with EnergyStar labeled programmable products.
d. Replace broken exit signs with EnergyStar LED exit signs.
Environmental Management Report
Page: 1 Date: 06/14/2013 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
No Maintenance building
Pesticides (3 gallons), Propane (4 cylinders) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Waste Management, Inc.
Yes Oil based paint (1 gal/month), organic solvent (5 gals/month)
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service
Safety Kleen, Inc.
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
07/24/1987 Friable/Non-Friable Jan Slaughterbeck 02/01/2000 Yes No N/A Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary Containment
1 Petroleum - Gasoline 250 Building K No Yes
Tank Status Active
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 06/14/2013Center : Albuquerque (00605) Page: 1 of 2
Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Floor Finishes
Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Floor Finishes
Floor Finishes Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Mastic beneath floor tile 12x12 floor tile
Mastic beneath 12x12 tile 12x12 floor tile Mastic beneath 12x12 tile
Mastic beneath floor tile 12x12 floor tile
Mastic beneath 12x12 tile 12x12 floor tile, off-white Linoleum (covered)
Linoleum (covered) Mastic beneath 12x12 tile 12x12 floor tile, off-white
Mastic beneath 12x12 tile 12x12 floor tile, off-white
Category Description
Category Description
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Quantity
Mech. room stairwell Mech. room stairwell
Arts/crafts room Arts/crafts room Game room
Throughout Throughout
Throughout Throughout Lounge
Lounge Throughout Throughout
Wing W Wing W
Building :
Building :
Building :
Building :
Building :
Building :
A & B - ADMINISTRATION
O - MULTI-PURPOSE RECREATION
Q & R - VACANT
S & T - CHARTER SCHOOL
U & V - CHARTER SCHOOL/LAUNDRY
W & X - DORMITORIES
Asbestos-Containing Materials Inventory
Page: 2 of 2
Ceiling Finishes Floor Finishes Floor Finishes
Bldg System Textured paint Mastic beneath 12x12 tile 12x12 floor tile
Category Description Sq. Ft.
Sq. Ft.
Sq. Ft.
Location Unit Quantity Bathrooms, wing Y Throughout Throughout
Building : Y & Z - DORMITORIES
Radon
Page: 1 of 1
A & B - ADMINISTRATION
C - FOOD SERVICE & MED/DENTAL
C1 - CAFE ANNEX
CDC - CHILD DEVELOPMENT CTR
CTST - STORAGE
D - SECURITY
E - STUDENT TRAINING
J - SOCIAL DEVELOPMENT
K - MATERIAL CONTROL
L - VOCATIONAL STORAGE
M - MAINTENANCE
N1 - DORMITORY
N2 - DORMITORY
O - MULTI-PURPOSE RECREATION
P - VOCATIONAL
Q & R - VACANT
S & T - CHARTER SCHOOL
U & V - CHARTER SCHOOL/LAUNDRY
W & X - DORMITORIES
Y & Z - DORMITORIES
Bldg Name
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
Test Date
Yes
Yes
N/A
No
No
Yes
No
Yes
N/A
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
ALBUQUERQUE
Aerial View of Albuquerque JCC
Page: 1 Date: 06/14/2013 of 4
Comments:
Paving Type for Roads & Parking
Access road to Dormitory N1 is gravel.
Paving Type for Sidewalks
Asphalt and Gravel Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing. There is a metal mesh fence in the southern part of the center. Chain link fence has been superimposed on some parts of the metal mesh fence. There are also chain link fences around some of the buildings' mechanical equipment and CDC outdoor play areas.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterAlbuquerque Bernalillo County Water UtilPublic Water Authority
None 0None
The center is provided with two master water meters, located outside the property line. One meter is located at the northwest corner of the center. The other water meter is located on the east of Multi-Purpose Recreation Building O.
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 3None Municipal
The nearest city fire station is about 0.5 miles away from the center and the emergency response time is about 3 minutes.
Number of Deficiencies = 1
Number of Deficiencies = 1
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures20 22Flat
Surrounding
Outdoor Recreation
Light Commercial, Residential
Basketball, Running Track, Soft/Baseball, Volleyball Public Road
Part of The Site
Part of The Site
Chain Link
Wrought Iron
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Fencing
Other Features
Page: 2 Date: 06/14/2013 of 4
Comments:
Sewage Treatment Flow
Center sanitary system discharges waste into the city sanitary sewer system operated by the Albuquerque-Bernalillo County Water Utility Authority.
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: The underground natural gas distribution system is provided with two master gas meters and serves as a fuel source for facility heating, cooking and domestic hot water. One meter is located at the east corner of Administration Building A & B. The other gas meter is located on the northwest corner of Student Training Building E.
New Mexico Gas
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Public Service Utility Co. of NM
The primary services are brought to the site from overhead lines along the center's eastern and western boundary.
Services enter the center at three locations, one at the western, one at the northeastern and one at the southeastern boundary. The overhead lines at all three service points transit to underground before entering the center. Each service has its own meter. Except Dormitory Buildings N1 and N2, the northeast service provides secondary services to all buildings via pad-mounted transformers. The shoutheast service serves Dormitory Building N1 via a pad-mounted transformer. Similarly, the west service serves Dormitory Building N2 Dormitory via a pad-mounted transformer. The center owns and maintains all pad-mounted transformers via an outside electrical contractor.
Pad Center
Utility Utility
No
12.47/7.2 kV, 3-Phase, 4 Wire
120/208V, 3-Phase, 4 WireUnderground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
Number of Deficiencies = 3
System Capacity Adequate System Condition
Yes Good
4. Storm Water System
Drain Type On-Site Storm Water Management
Surface Run-off N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Comments: Three storm water ditches fill during heavy rain and slowly percolate.
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Center
System Capacity Adequate System Condition
Yes Good
Generator
None
ATS MTS
No No
6. Central Plant: None
Metering Master
Page: 3 Date: 06/14/2013 of 4
Comments:
Telephone Company
On-site Line Owner
Telephone service is provided by Qwest with four T1 lines which terminate in the main telephone switch room located in the basement of Administration Building A&B. One T1 line is reserved for Siatech, two others are utilized by the center and a fourth one is a spare. Local telephone service is provided by Qwest. Long distance telephone voice over internet protocol (VoIP) service and LAN/WAN networks are maintained by the Job Corps Data Center (JCDC). All data communication equipment and devices are located in the server room behind the student record office on the first floor. The main telephone switch room and the server room are supported by a 1 kVA and an 8 kVA UPS module respectively. The center has a public address system via phones and speakers.
The site security system includes Closed Circuit Television (CCTV) cameras, color monitors and gate operators.
CCTV cameras are installed on the exterior of Dormitory Building N1 scanning the southeastern corner of the campus. The cameras are monitored from the RA office. There are a vehicular gate operator at the north parking entrance and two chain link gate operators at the northeast parking entrances. The gate operators are remotely controlled from the security office in Administration Building A&B. The fire alarm system in buildings on center is stand alone. Cable TV is provided by Comcast in the dormitories, dining and other recreational facilities.
Qwest
Maint. Responsibility
Center Center
CCTV Cameras, B&W Monitor, Color Monitor, Door Alarms, Electric Gate Operator
01/01/1980CenterActive AbovegroundBuilding K NoPetroleum - Gasoline
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
9. Electrical (Communication/Alarm/Security)
Equip/Veh Fueling
Purpose
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Pole
Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Comments: The site lighting system is owned and maintained by the center. Lighting around the running track has recently been enhanced by four new solar powered pole lights.
Number of Deficiencies = 3
Number of Deficiencies = 7
Fire Alarm Security
Page: 4 Date: 06/14/2013 of 4
ACCESSIBILITY
Yes
Site is mostly flat and easily accessible.Comments:
Comments:
UnknownNoUnknown
Building J - Social Development, built in 1932, is the last remaining building of the Saint Anthony's School that previously occupied the site, and it is a good example of local architecture of that period.
No
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Low LowLow LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
The center is located in a dessert type of environment.Comments:
Number of Deficiencies = 2
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
N/AYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
NO
NO
NO
NO
NO
NO
NO
Building Descriptions and Utilities
BUILDING A & B - ADMINISTRATION
Building Descriptions
Page: 1 of 99
Building: A & B - ADMINISTRATION
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry
Wall Roof Rigid Rigid
Metal - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 12,750 8,080 1 Owned 1962 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
There are gutters and downspouts at entrances.
Drainage Year Life
Remaining Type Area Served
Built-up Roofing Surface Run-off 2008 16 Gable Entire Building
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 99
Building: A & B - ADMINISTRATION
INTERIOR FINISH
Carpet Ceramic Tile Concrete
Brick CMU Drywall Plaster Wood Paneling
Metal Unit - Metal Frame Wood Units - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs
Comments: The stairs go to the basement mechanical, telephone, and electrical rooms.
Awning Units - Steel Frame; Single Glazing; Fixed - Aluminum Frame; Double Glazing;
Fixed - Steel Frame; Single Glazing; Fixed - Wood Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board Wood
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Ceilings
Page: 3 of 99
Building: A & B - ADMINISTRATION
Mechanical Restroom
Comments: Ceiling and roof-mounted exhaust fans ventilate the bathrooms.
Ventilation Area Served
Evaporative Cooler
Packaged Direct
Expansion (Air Source)
Single Duct
Window Unit
None
None
Electric
Electric
Mechanical
Natural
None
None
Entire Building
Offices
Exhaust Ventilation
Roof-mounted evaporative cooling units provide cooling and fresh air to Buildings A & B.
Window air conditioning units provide supplemental DX-cooling to the basement storage/electrical and student accountability records administrator.
Comments:
Comments:
Number of Deficiencies = 2
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A horizontal air-handling unit with hot water heating coils provides ducted heating and ventilation air to most of the offices in Buildings A & B. The unit is a Trane Torrivent, model T-31, S/N U77485. It is located in the basement equipment room. Originally, the flow control valve for this unit was pneumatically controlled. Since the pneumatic control system failed and had even been partially dismantled, the unit controls have been manipulated and on a trial-and-error basis. This lack of automatic control is inefficient and does not offer the comfort level the H&V unit was designed to deliver.
A gas-fired hot water boiler provides heating water pumped by a floor-mounted end suction pump (A.
O. Smith, model E102, 2.0 HP) to the floor-mounted baseboard heaters serving most of the offices and reception extension in Buildings A & B. The unit is a Weil McLain hot water boiler, model J-10-B, S/N JB, 1485 MBH gas input and 1188 MBH output. It is located in the basement equipment room.
Originally, 8-zone heating water distribution system was pneumatically controlled. Since the pneumatic control system failed and had even been partially dismantled, the zoned water distribution system controls have been manipulated and on a trial-and-error basis. This lack of automatic control is inefficient and does not offer the comfort level the heating system was designed to deliver.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Single Duct
Baseboard
Two-Pipe
Two-Pipe
Pneumatic
Pneumatic
Mechanical
Natural
None
None
Entire Building
Entire Building
Ventilation2.
System Type
Number of Deficiencies = 3
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Air Conditioning
Page: 4 of 99
Building: A & B - ADMINISTRATION
A 30-gallon capacity Rheem gas-fired water heater (model 22V30S-30F, S/N RHLN0708V11888, 30 MBH gas input, built in 07/2008) provides domestic hot water to Buildings A & B. It is located in the basement equipment room. In addition, two Chronomite instant flow electric water heaters (model 5R- 30L/120, 3.6 kW) provide domestic hot water to the reception extension male and female toilets in Building A.
Comments:
Cast-Iron None None
Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Sink Urinal Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Service is brought to the building from a pad-mounted 75 kVA transformer outside. Service enters a 350A MCB main distribution panel (MDP) located in the storage room in Building B. The MDP has a transient voltage surge suppressor protection unit.
Galvanized Steel Galvanized Steel Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
LIGHTING
Page: 5 of 99
Building: A & B - ADMINISTRATION
FIRE ALARM
Comments: The fire alarm control/annunciator panel is located in the reception/security desk area in this building.
Comments: The center's main telephone switchboard is located in the basement storage room of this building.
Audible Alarm Duct Smoke Detector Heat Detector Main Control/Annunciator Panel Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System Magnetic Door/Alarm Connected to Main System None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
Comments: Building A has a tritium gas exit sign which expires in February 2013.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Reception
Lounges
Conference Rooms
Corridors & Stairs
Toilets
Equipment Rooms (Elec/Mech)
Storage Rooms
Mail Room
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 2
Interior Lighting2. Number of Deficiencies = 2
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
Electric Water Gas No YesNo
BUILDING UTILITY METERING
Type Location None None
Comments: There are no CO detectors in this building. It is required by DOL Directive Information Notice 12-27 and
NFPA 720, 2012.
CARBON MONOXIDE DETECTION
Page: 6 of 99
Building: A & B - ADMINISTRATION
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The hot water boiler and heating/ventilating units are obsolete (40-year old). The pneumatic control of zoned heating water distribution and air distribution systems do not function properly. This lack of automatic control is inefficient and does not offer the comfort level the heating system was designed to deliver.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Structure: Good Exterior: Good Interior: Good Mechanical: Fair Electrical: Good
BUILDING C - FOOD SERVICE & MED/DENTAL
Page: 7 of 99
Building: C - FOOD SERVICE & MED/DENTAL
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry
Wall Roof Batt Batt
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Assembly 11,345 7,960 1 Owned 1962 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
There are gutters and downspouts at the entrances.
Drainage Year Life
Remaining Type Area Served
Built-up Roofing
Rolled Asphalt
Metal
Surface Run-off
Surface Run-off
Surface Run-off
Gable
Shed
Shed
Original Building
Vestibule
Building Addition
Comments:
3. Roof
Page: 8 of 99
Building: C - FOOD SERVICE & MED/DENTAL
INTERIOR FINISH
Ceramic Tile Concrete Quarry Tile Terrazzo Vinyl Tile
Brick Ceramic Tile Drywall Glass Block Stainless Steel
Wood Unit - Metal Frame
VERTICAL CIRCULATION
None
Metal Units - Metal Frame Wood Unit - Metal Frame
Fixed - Aluminum Frame; Double Glazing; Fixed - Steel Frame; Single Glazing;
Acoustical Tile Mirror Lay-in Tiles Plaster
Exterior Doors5.
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Page: 9 of 99
Building: C - FOOD SERVICE & MED/DENTAL
Mechanical
Mechanical
Bathrooms
Kitchen
Comments:
Comments:
Ceiling and roof-mounted exhaust fans ventilate the bathrooms.
A make up air unit using a hot water heating coil is located in the mechanical room and supplies make-up air to the kitchen. Roof mounted exhaust fans serve the kitchen and dishwasher hoods.
Ventilation Area Served
Evaporative Cooler
Packaged Direct
Expansion (Air Source)
Single Duct
Single Duct
None
None
Electric
Electric
Mechanical
Mechanical
None
None
Entire Building
Medical/Dental
Exhaust Ventilation
Roof-mounted evaporative cooling units provide cooling air to the kitchen and dining areas.
Two rooftop-packaged gas-fired units provide DX-cooling and fresh air to the medical/dental rooms.
The typical unit is a Carrier model 48TJE004-511. Ceiling fans enhance room air circulation in some of the medical/dental offices.
Comments:
Comments:
Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
An air-handling unit with ducted hot water heating coils provides heating and make-up air to the kitchen. The unit is a Sterling/Alton model HEDM1250, S/N 93-56030, located in the mechanical room.
A gas-fired hot water boiler provides heating water pumped by an in-line pump to the floor-mounted baseboard heaters and heating ventilation unit. The unit is a Peerless packaged hot water boiler, model 210-10-W, 1890 MBH gas input and 1512 MBH output. It is located in the mechanical room. The electric water booster heater that supports the dishwasher system is Hatco model C-54-1803489604, 54 kW, 480V/3-phase, 6-gallon storage capacity, 552 GPH recovery at 40 degrees rise and 315 GPH at 70 degrees rise.
Two rooftop-packaged gas-fired units provide heating and fresh air to the medical/dental rooms. The typical unit is a Carrier model 48TJE004-511. Ceiling fans enhance room air circulation in some of the medical/dental offices.
Two small capacity electric radiant heaters provide heating to the covered queuing entrance foyer.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Packaged
Electric Resistance
Single Duct
Baseboard
Single Duct
Radiant Heater
Two-Pipe
Two-Pipe
None
None
Thermostatic Valves
Electric
Electric
Electric
Mechanical
Natural
Mechanical
Natural
None
None
None
None
Kitchen
Dining Hall
Medical/Dental
Vestibules
Ventilation2.
System Type
Number of Deficiencies = 3
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 10 of 99
Building: C - FOOD SERVICE & MED/DENTAL
A 130-gallon capacity A. O. Smith gas-fired water heater (model BTU500A104, S/N 1231M001541,
499.9 MBH gas input, 575.64 GPH recovery, built in 08/2012) provides domestic hot water to the building. It is located in the mechanical room. The hot water loop has an in-line Taco circulating pump (model 0010-F2, 1/8 HP) and a Culligan water softener system.
Comments:
Cast-Iron Outdoor None
Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Multi-Compartment Sink Service Sink Shower/Bathtub Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: A wet chemical automatic fire suppression system is provided in the kitchen hood.
Copper Copper Gas-Fired Water Softener No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
Location UL300 Compliance Status Kitchen Compliant
Comments: The kitchen hood is provided with a wet chemical fire suppression system with an automatic gas shut-off valve, which meets the requirements of standard UL-300.
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 11 of 99
Building: C - FOOD SERVICE & MED/DENTAL
Comments: Service is brought to the building from a utility-owned, pad-mounted 75 kVA transformer outside. Service enters to a 300A MCB main distribution panel (MDP) located in the mechanical room. This transformer also serves Building S&T. The MDP also subfeeds Cafe Annex Building CA.
FIRE ALARM
Comments: The fire alarm devices in this building are connected to the main fire alarm control/annunciator panel in the security office in Building A.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Comments: This building has two tritium gas exit signs which expire in February 2013.
Compact Fluorescent High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Incandescent
Incandescent
Offices
Food Preparation
Dining/Lunch Rooms
Dishwashing
Medical/Dental
Wards (Patient)
Reception
Lounges
Corridors & Stairs
Toilets
Storage Rooms
Equipment Rooms (Elec/Mech)
Toilets
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
Page: 12 of 99
Building: C - FOOD SERVICE & MED/DENTAL
Connected to Main System None Connected to Main System Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The interior configuration is inadequate, undersized and below DOL standards.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good
This building has been recommended for demolition in the Long Range Development Plan after construction of new cafeteria.
The demolition is included in Project 3299.
DEMOLITION RECOMMENDATION
Type Location None None
Comments: There are no CO detectors in this building. It is required by DOL Directive Information Notice 12-27 and
BUILDING C1 - CAFE ANNEX
Page: 13 of 99
Building: C1 - CAFE ANNEX
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
CMU Masonry Glass Block Stucco Wood
Wall Roof None None
Metal Units - Metal Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Assembly 1,140 1,000 1 Owned 1998 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
N/A
N/A
Yes
N/A
N/A
N/A
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Metal Gutters and Downspouts 1998 26 Shed Entire Building
3. Roof
Page: 14 of 99
Building: C1 - CAFE ANNEX
INTERIOR FINISH
Concrete
Stucco on CMU Windows
None
Natural Entire Building
Ventilation Area Served
VERTICAL CIRCULATION
None
Sliding - Aluminum Frame; Double Glazing;
Evaporative Cooler
Single Duct None Electric Mechanical None Entire Building
Exposed Structure
Exhaust Ventilation
Two roof-mounted evaporative cooling units provide cooling air to the building.Comments:
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A vertical gas-fired furnace provides heating to the building. The unit is a Trane model TUE1B080A9361AC, 80 MBH gas input, built in 02/2009. It is located in the mechanical closet.
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Single Duct None Electric Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 15 of 99
Building: C1 - CAFE ANNEX
Cast Iron None None
Electric Water Cooler
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Service to this building is sub-fed from Cafeteria Building C to a 100A, 12 circuit loadcenter mounted on the exterior wall.
None Copper None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: The recorded footcandle level includes natural light contribution.
High Intensity Discharge (HID)
Comments: Exterior lighting is provided by surrounding area pole-mounted light fixtures which are controlled by time clock and photocells.
T8 - Fluorescent50Recreation 50
Area Recommended Level
Recorded Level Light Type
None None
Main Loadcenter 120/208V, 1-Phase, 3 Wire Loadcenter Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Page: 16 of 99
Building: C1 - CAFE ANNEX
FIRE ALARM
None
None None None None
Telephone Security Public Address Television
Number of Deficiencies = 1
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Interiors and exterior are worn and in fair condition.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Good Electrical: Good
This building has been recommended for demolition in the Long Range Development Plan after Construction of new cafeteria.
The demolition is included in Project 3299.
DEMOLITION RECOMMENDATION
Type Location None None
Comments: There are no CO detectors in this building. It is required by DOL Directive Information Notice 12-27 and
BUILDING CDC - CHILD DEVELOPMENT CTR
Page: 17 of 99
Building: CDC - CHILD DEVELOPMENT CTR
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry Metal Siding
Comments: The building has brick end walls.
Wall Roof Batt Batt
Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Day Care 8,245 6,305 1 Owned 1994 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Metal Gutters and Downspouts 1994 22 Shed Entire Building
3. Roof
Page: 18 of 99
Building: CDC - CHILD DEVELOPMENT CTR
INTERIOR FINISH
Carpet VCT Vinyl Tile
Ceramic Tile Drywall Prefabricated panels
Wood Unit - Metal Frame
Mechanical
Mechanical
Restroom
Kitchen
Comments:
Comments:
Ceiling-mounted exhaust fans ventilate the restrooms.
A roof-mounted exhaust fan ventilates the Greenheck kitchen hood.
Ventilation Area Served
VERTICAL CIRCULATION
None
Double Hung - Aluminum Frame; Double Glazing;
Acoustical Tile
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Eight vertical gas-fired furnaces provide heating to the building.