This document provides details for a federal solicitation notice seeking offers to upgrade the water distribution system at the main hospital in Shreveport, Louisiana. The solicitation number is 667-22-4-1404-0033 and concerns project 667-18-119 under the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16. Offerors must be registered in the System for Award Management and Vendor Information Pages databases and verified as a Service-Disabled Veteran-Owned Small Business. Responses are due in accordance with the solicitation package. The requirement is fully set aside for SDVOSBs. The North American Industry Classification System code for this project is 236220, with a size standard of $39.5 million.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Overton Brooks VAMC Upgrade Water Distribution System

To Improve Legionella Prevention, Cooling Towers & Storage Tanks

1-SUB-4-001-A

Sub-Basement

Center of room

N/A

Cu

8"

1"

CW

A

Plug

None

Ball

N/A

Class I

1/PL-105

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

7881-7883

©Northeast Infrastructure, LLC 2021

Cooling Towers & Storage Tanks

1-SUB-4-002-A

Sub-Basement

Center of room

N/A

Cu

18"

3"

CW

A

Closed Valve

None

Gate

N/A

Class I

1/PL-105

03/20/2019

Picture of Dead Leg

7884-78877

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Cooling Towers & Storage Tanks

1-SUB-4-003-A

Sub-Basement

Center of room

N/A

Cu

8"

3/4"

CW

A

Plug

None

Ball

N/A

Class I

1/PL-105

03/20/2019

Picture of Dead Leg

7888-90

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-004-A

Sub-Basement

Center of room

N/A

Cu

21"

3/4"

CW

A

Closed Valve

None

Gate

N/A

Class I

1/PL-106

03/20/2019

Picture of Dead Leg

7891-7894

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-005-A

Sub-Basement

Center of room

N/A

Cu

54"

4"

CW

B

Spigot

None

Gate

N/A

Class I

1/PL-106

03/20/2019

Picture of Dead Leg

7895-7897

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-006-A

Sub-Basement

Center of room

N/A

Cu

11"

1 1/2"

HW

A

Cap

None

Ball

11"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7898-7902

Cooling Towers & Storage Tanks

1-SUB-4-007-A

Sub-Basement

Center of room

N/A

Cu

20"

4"

HW

A

Cap

None

None

None

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7903-7910

Cooling Towers & Storage Tanks

1-SUB-4-008-A

Sub-Basement

Center of room

N/A

Cu

36"

6"

HW

A

Cap

None

Gate

6"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7911-7913

Cooling Towers & Storage Tanks

1-SUB-4-009-A

Sub-Basement

Center of room

N/A

Cu

8"

1"

HW

A

Closed Valve

None

Ball

6"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7926-7930

Cooling Towers & Storage Tanks

1-SUB-4-010-B

Sub-Basement

West Wall

N/A

Cu

276''

3/4"

HW

B

Spigot

None

Globe

108"

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Old Connection For Washing Machine

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7931-7935

Cooling Towers & Storage Tanks

1-SUB-4-011-B

Sub-Basement

West Wall

N/A

Cu

144''

3/4"

CW

B

Spigot

None

Globe

N/A

Class I

1/PL-106

03/20/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Old Connection For Washing Machine

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

7931-7935

Cooling Towers & Storage Tanks

1-SUB-4-012-A

Sub-Basement

Center of room

N/A

Cu

196"

4"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-106

03/21/2019

Picture of Dead Leg

8001-8002

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-013-A

Sub-Basement

Center of room

N/A

Cu

16"

1 1/4"

HWR

A

Cap

None

None

2"

Class I

1/PL-106

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-016-A

Sub-Basement

Center of room

N/A

Cu

18"

2"

HWR

A

Cap

None

Ball

None

Class I

1/PL-106

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-017-A

Sub-basement

Center of room

N/A

Cu

24"

1/2"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-101

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-018-A

Sub-Basement

Center of room

N/A

Cu

168"

1"

HWR

A

Closed Valve

None

Gate

84"

Class I

1/PL-107

03/21/2019

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-019-A

Sub-Basement

Center of room

N/A

Cu

10"

1/2"

CW

A

Cap

None

None

N/A

Class I

1/PL-106

03/21/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

8012-14

Cooling Towers & Storage Tanks

1-SUB-4-020-A

Sub-Basement

East Wall

N/A

Cu

28"

1/2"

CW

A

Cap

None

None

N/A

Class I

2/PL-107

03/22/2019

Picture of Dead Leg

8015-8017

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-021-A

Sub-Basement

East Wall

N/A

Cu

120"

1/2"

HWR

A

Cap

None

None

120"

Class I

2/PL-107

03/22/2019

Picture of Dead Leg

8015-8017

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Tagged as HW instead of HWR

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-022-A

Sub-Basement

Center of room

N/A

Cu

302''

2"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-023-A

Sub-Basement

Center of room

N/A

Cu

7''

3/4"

HW

A

Cap

None

None

7"

Class I

1/PL-101

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-024-B

Sub-Basement

Center of room

N/A

Cu

78''

1/2"

CW

B

Fixture

Eyewash

Ball

N/A

Class I

1/PL-101

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-025-A

Sub-Basement

Center of room

N/A

Cu

20''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-106

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-026-A

Sub-Basement

Center of room

N/A

Cu

20''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-106

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-027-B

Sub-Basement

East Wall

N/A

Cu

160''

1/2"

CW

B

Fixture

Eyewash

None

N/A

Class I

1/PL-105

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-028-B

Sub-Basement

Center of room

N/A

Cu

8"

3/4"

CW

B

Spigot

None

None

N/A

Class I

1/PL-106

02/27/2020

Picture of Dead Leg

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-4-029-A

Sub-Basement

Center of room

N/A

Cu

88''

1"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-101

04/08/2019Date of Inspection:

Picture of Dead Leg

Image Not Available

Pipe Function

Dead Leg Type

Termination

Fixture Served

Valve Type

Hot Non-Insulated

Location in ICRA

Drawing Number

Comments / Recommendations

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Location in Room

Wall Type

Piping Material

Pipe Length

Pipe Size

Cooling Towers & Storage Tanks

1-SUB-4-030-A

Sub-Basement

Center of room

N/A

Cu

26''

1"

HW

A

Closed Valve

None

Ball

None

Class I

1/PL-101

04/08/2019Date of Inspection:

Picture of Dead Leg

Image Not Available

Pipe Function

Dead Leg Type

Termination

Fixture Served

Valve Type

Hot Non-Insulated

Location in ICRA

Drawing Number

Comments / Recommendations

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Location in Room

Wall Type

Piping Material

Pipe Length

Pipe Size

Cooling Towers & Storage Tanks

1-SUB-CS-001-B

Sub-Basement

Crawlspace

Center of room

N/A

Cu

7''

3/4"

CW

B

Spigot

None

Gate

N/A

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-002-B

Sub-Basement

Crawlspace

Center of room

N/A

Cu

7''

3/4"

HW

B

Spigot

None

Gate

7"

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-003-B

Sub-Basement

Crawlspace

Center of room

N/A

Cu

6"

1 1/4"

HWR

B

Spigot

None

Gate

6"

Class I

1/PL-103

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Comments / Recommendations

Pipe Size

Pipe Function

Dead Leg Type

Termination

Date of Inspection:

Location in Room

Wall Type

Piping Material

Pipe Length

Fixture Served

Valve Type

Hot Non-Insulated

Location in ICRA

Drawing Number

Picture of Dead Leg

Image Not Available

Cooling Towers & Storage Tanks

1-SUB-CS-004-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

135''

1 1/4"

CW

A

Closed Valve

None

Ball

N/A

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-005-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

174''

3/4"

HWR

A

Closed Valve

None

Ball

N/A

Class I

1/PL-103

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-006-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

718''

3/4"

HW

A

Closed Valve

None

Ball

718"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-007-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

717''

3/4"

CW

A

Closed Valve

None

None

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-008-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

159''

3/4"

HW

A

Closed Valve

None

Ball

159"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Open Ended Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-009-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

408''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Bent Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-010-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

384''

1/2"

HW

A

Cap

None

None

384"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Bent Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-011-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

41''

1"

HWR

A

Cap

None

None

41"

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-012-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-013-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-014-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-015-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

54''

1/2"

CW

A

Cap

None

Ball

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-016-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

24''

3/4"

HW

A

Closed Valve

None

Ball

24"

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-017-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

110''

3/4"

CW

A

Cap

None

None

N/A

Class I

2/PL-104

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-018-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

13''

3/4"

CW

A

Cap

None

None

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-019-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

27''

3/4"

CW

A

Cap

None

None

N/A

Class I

1/PL-100

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-020-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

129''

3/4"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-021-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

185''

1"

HW

A

Cap

None

Gate

185"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-022-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

195''

1"

CW

A

Cap

None

Gate

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-023-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

402''

1"

HW

A

Cap

None

None

None

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-024-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

74''

1"

CW

A

Cap

None

Gate

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-025-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

4"

1/2"

HW

A

Cap

None

None

4"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-026-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

4"

1/2"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-027-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

10''

3/4"

HW

A

Cap

None

Gate

10"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-028-A

Sub-Basement

Crawlspace

East Wall

N/A

Cu

131''

3/4"

HW

A

Cap

None

Gate

131"

Class I

1/PL-101

03/22/2019

Picture of Dead Leg

Image Not Available

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Cooling Towers & Storage Tanks

1-SUB-CS-029-A

Sub-Basement

Crawlspace

East Wall

N/A

Cu

147''

3/4"

CW

A

Cap

None

Gate

N/A

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-030-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

111''

3/4"

HW

A

Closed Valve

None

Ball

111"

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-031-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

762''

1 1/2"

HW

A

Cap

None

None

None

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-032-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

159''

1/2"

CW

A

Cap

None

None

N/A

Class I

1/PL-101

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Asbestos Insulated Pipe

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-033-B

Sub-Basement

Crawlspace

North Wall

N/A

Cu

6"

3/4"

CW

B

Spigot

None

None

N/A

Class I

1/PL-102

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-CS-034-A

Sub-Basement

Crawlspace

Center of room

N/A

Cu

6"

3/4"

CW

A

Plug

None

None

N/A

Class I

1/PL-102

03/22/2019

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-STAIRS-001-B

Sub-Basement

Stairs

East Wall

N/A

Cu

228''

3/4"

CW

B

Spigot

None

None

N/A

Class I

1/PL-105

02/27/2020

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap, valve, or fitting

Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used fixture

Type C - Pipe length greater than 25 feet terminating at a frequently used plumbing fixture

Description

Dead Leg Tag Number

Building Number

Floor Number

Room Number

Dead Leg #

Pipe Size

Pipe Function

Dead Leg Type

Termination

Location in Room

Piping Material

Pipe Length Comments / Recommendations

Fixture Served

Wall Type

Valve Type

Hot Non-Insulated

Drawing Number

Date of Inspection:

Location in ICRA

Picture of Dead Leg

Cooling Towers & Storage Tanks

1-SUB-STAIRS-002-B

Sub-Basement

Stairs

East Wall

N/A

Cu

96''

3/4"

CW

B

Spigot

None

Gate

N/A

Class I

1/PL-106

02/27/2020

Dead Leg Criteria Check List

Type A - Pipe Length greater than twice the diameter of the pipes size terminating at a cap,…