Cross Connection Sheets.pdf

PDF 7 MB Posted

Attached to
Z1DA--667-18-119, Upgrade Water Distribution System, Main Hospital
Solicitation number
667-22-4-1404-0033
Issued by

About this file

This document contains cross connection survey sheets for the Overton Brooks VAMC Upgrade Water Distribution System project in Shreveport, Louisiana. The sheets identify over 100 potential cross connection hazards across the facility and provide recommendations for remediation, including replacing unprotected hose bibs, soap dispensers, and threaded faucets with models incorporating backflow prevention, and verifying the proper operation of existing backflow prevention devices. Remediation is needed to prevent potential contamination of the potable water system from backsiphonage or backpressure due to cross connections per codes and regulations. The related solicitation is for Project 667-18-119 to upgrade the main hospital's water distribution system to improve Legionella prevention in cooling towers and storage tanks. Offerors must be SDVOSB verified in VIP and SAM to respond to the 100% SDVOSB set-aside by the response date in accordance with the solicitation package issued by the VA Veterans Health Administration VISN 16.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Overton Brooks VAMC Upgrade Water Distribution System

To Improve Legionella Prevention, Cooling Towers & Storage Tanks

1-SUB-4-001

Sub Basement

Hose

Backsiphonage

1/PL-106

02/27/2020 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Piping connections to a potential backsiphonage source from submergence of hose in a contaminated source and unprotected hose bibb. Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

Image Not Available

©Northeast Infrastructure, LLC 2021

Cooling Towers & Storage Tanks

1-SUB-4-002

Sub Basement

Closed Valve

Backsiphonage

1/PL-101

04/08/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Cooling Towers & Storage Tanks

1-SUB-STAIRS-001

Sub Basement

Stairs

Spigot

Backsiphonage

1/PL-105

02/27/2020 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

Cooling Towers & Storage Tanks

1-SUB-STAIRS-002

Sub Basement

Stairs

Spigot

Backsiphonage

1/PL-106

02/27/2020 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

Cooling Towers & Storage Tanks

1-B-D11-001

Basement

D11

Hose

Backsiphonage

1/PL-110

04/08/2019

Piping connections to a potential backsiphonage source from submergence of hose in a contaminated source and unprotected hose bibb. Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Picture of Potential Cross Connection

8046-7

Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-B-E23A-001

Basement

E23A

Mop Sink

Backsiphonage

1/PL-108

11/06/2019

1643-4

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Picture of Potential Cross Connection

Cooling Towers & Storage Tanks

1-B-N6-001

Basement

N6

Multiple Hoses

Backsiphonage

1/PL-109

04/08/2019

Dual piping connections to a potential non-potable water usage reprentsents a cross contamination risk due to either backpressure or backsiphonage backflow, potential high hazard source. Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Picture of Potential Cross Connection

Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-B-N6-002

Basement

N6

Hose

Backsiphonage

1/PL-109

04/08/2019

Picture of Potential Cross Connection

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Floor:

Room Number:

Case Number:

Device:

Hazard:

Piping connections to a potential backsiphonage source from submergence of hose in a contaminated source.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Drawing Reference #:

Date of Survey:

Cooling Towers & Storage Tanks

1-B-N10-001

Basement

N10

Hose

Backsiphonage

1/PL-109

04/10/2019

Picture of Potential Cross Connection

Date of Survey:

674-75

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Piping connections to a potential backsiphonage source from submergence of hose in a contaminated source and unprotected hose bibb. Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-B-N10-002

Basement

N10

Soap Dispenser

Backsiphonage

4/PL-113

04/10/2019

Picture of Potential Cross Connection

Date of Survey:

576-77

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Piping connections to a potential backsiphonage source from submergence of hose in a contaminated source or backsiphonage from soap dispenser. Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-B-N10-003

Basement

N10

Soap Dispenser

Backsiphonage

4/PL-113

04/10/2019

Picture of Potential Cross Connection

Date of Survey:

682-83

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-B-N10-004

Basement

N10

Soap Dispenser

Backsiphonage

1/PL-113

04/10/2019

Picture of Potential Cross Connection

Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Piping connections to a potential backsiphonage source from submergence of hose in a contaminated source or backsiphonage from soap dispenser. Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-B-S2-001

Basement

S2

Soap Dispenser

Backsiphonage

1/PL-111

11/06/2019

1639-40

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to have a broken atmospheric vacuum breaker upstream of the faucet, and presents a potential cross connect hazard.

Recommendation is to replace atmospheric vacuum breaker with new atmospheric vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-B-Outside-001

Basement

Outside

Spigot

Backsiphonage

1/PL-112

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1442-43

Cooling Towers & Storage Tanks

1-B-Outside-002

Basement

Outside

Spigot/Hose

Backsiphonage

1/PL-112

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1412-3

Cooling Towers & Storage Tanks

1-B-Outside-003

Basement

Outside

Spigot/Hose

Backsiphonage

1/PL-109

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1416-8

Cooling Towers & Storage Tanks

1-B-Outside-004

Basement

Outside

Spigot/Hose

Backsiphonage

1/PL-109

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1416-8

Cooling Towers & Storage Tanks

1-B-Outside-005

Basement

Outside

Spigot

Backsiphonage

1/PL-109

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1414-5

Cooling Towers & Storage Tanks

1-B-Outside-006

Basement

Outside

Spigot

Backsiphonage

1/PL-112

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1437-9

Cooling Towers & Storage Tanks

1-B-Outside-007

Basement

Outside

Spigot

Backsiphonage

1/PL-111

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1435-6

Cooling Towers & Storage Tanks

1-B-Outside-008

Basement

Outside

Spigot

Backsiphonage

1/PL-111

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1430-2

Cooling Towers & Storage Tanks

1-B-Outside-009

Basement

Outside

Spigot

Backsiphonage

1/PL-111

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1433-4

Cooling Towers & Storage Tanks

1-B-Outside-010

Basement

Outside

Spigot

Backsiphonage

1/PL-111

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1428-9

Cooling Towers & Storage Tanks

1-1-E300C-001

E300C

Soap Dispenser

Backsiphonage

7/PL-119

11/06/2019

1630-1

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-1-S2-001

S2

Soap Dispenser

Backsiphonage

1/PL-118

11/06/2019

1632-3

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-1-Outside-001

Outside

Spigot

Backsiphonage

5/PL-119

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1419-20

Cooling Towers & Storage Tanks

1-1-Outside-002

Outside

Spigot

Backsiphonage

1/PL-117

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1421-22

Cooling Towers & Storage Tanks

1-1-Outside-003

Outside

Spigot

Backsiphonage

1/PL-117

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing outside spigot appears to be protected with an existing in-line vacuum breaker. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1423-5

Cooling Towers & Storage Tanks

1-1-Outside-004

Outside

Spigot/Hose

Backsiphonage

1/PL-117

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1426-7

Cooling Towers & Storage Tanks

1-1-Outside-005

Outside

Spigot

Backsiphonage

1/PL-118

08/29/2019 Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Broken Spigot - Potential Dead Leg Hazard.

The subject spigot is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace spigot with new spigot incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Picture of Potential Cross Connection

1440-1

Cooling Towers & Storage Tanks

1-2-E101-001

E101

Spigot

Backsiphonage

1/PL-123

11/06/2019

Picture of Potential Cross Connection

Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject spigot is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-2-N8-001

N8

Threaded Faucet

Backsiphonage

1/PL-122

11/06/2019

Picture of Potential Cross Connection

Date of Survey:

1624-5

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject faucet is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace faucet with new faucet incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-2-N19-001

N19

Drain Pipe

Backsiphonage

1/PL-122

08/28/2019

Picture of Potential Cross Connection

Date of Survey:

1354-6

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-2-S36-001

S36

Soap Dispenser

Backsiphonage

1/PL-124

11/06/2019

Picture of Potential Cross Connection

Date of Survey:

1636-7

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-2-W11-001

W11

Soap Dispenser

Backsiphonage

2/PL-124

08/28/2019

Picture of Potential Cross Connection

Date of Survey:

1345-9

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-E13-001

E13

Soap Dispenser

Backsiphonage

1/PL-132

08/24/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N7-001

N7

Spigot

Backsiphonage

1/PL-128

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-3-N11-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N11-001

N11

Spigot

Backsiphonage

4/PL-131

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

111512

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N13-001

N13

Spigot

Backsiphonage

1/PL-128

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-3-N11-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N14-001

N14

Spigot

Backsiphonage

1/PL-128

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-3-N11-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N15-001

N15

Spigot

Backsiphonage

5/PL-131

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-3-N11-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N16-001

N16

Spigot

Backsiphonage

5/PL-131

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-3-N11-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N19-001

N19

Spigot

Backsiphonage

1/PL-128

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-3-N11-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-N20-001

N20

Spigot

Backsiphonage

1/PL-128

06/17/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-3-N11-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing spigot appears to be protected with an existing in-line vacuum breaker upstream of the faucet.

Recommended replacement and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-3-W60A-001

W60A

1 1/4" galvanized/steel piping

Cross-Contamination

1/PL-131

06/16/2019

Picture of Potential Cross Connection

Date of Survey:

115405-115437

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Recommendation is to remove galvanized water piping and replace with copper piping. See drawing 1/PL-131 for full note on galvanized domestic water piping.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-4-E20G-001

E20G

Threaded Faucet

Backsiphonage

6/PL-135

06/15/2019

Picture of Potential Cross Connection

Date of Survey:

083242-083246

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-4-E20G-002

E20G

Threaded Faucet

Backsiphonage

6/PL-135

06/15/2019

Picture of Potential Cross Connection

Date of Survey:

083242-083246

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-4-N3-001

N3

Soap Dispenser

Backsiphonage

1/PL-133

11/06/2019

1610-1

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-4-W34-001

W34

Spigot

Backsiphonage

3/PL-134

06/13/2019

Picture of Potential Cross Connection

Date of Survey:

180515

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject hose bibb is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace hose bibb with new hose bibb incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-5-E3-001

E3

Slop Sink

Backsiphonage

1/PL-136

11/06/2019

Picture of Potential Cross Connection

Date of Survey:

1595-6

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-5-W33-001

W33

Soap Dispenser

Backsiphonage

1/PL-136

06/11/2019

Picture of Potential Cross Connection

Date of Survey:

181445-181452

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N4-001

N4

Soap Dispenser

Backsiphonage

1/PL-139

11/06/2019

1582-3

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-6-N8-001

N8

Threaded Faucet

Backsiphonage

1/PL-140

11/06/2019

1585-6

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-6-N10-001

N10

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-6-N8-001, 1-6-N25-

001, and 1-6-N28-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N12-001

N12

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-6-N8-001, 1-6-N25-

001, and 1-6-N28-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N17-001

N17

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-6-N8-001, 1-6-N25-

001, and 1-6-N28-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N19-001

N19

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-6-N8-001, 1-6-N25-

001, and 1-6-N28-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N22-001

N22

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-6-N8-001, 1-6-N25-

001, and 1-6-N28-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N23-001

N23

Threaded Faucet

Backsiphonage

4/PL-142

11/06/2019

1589-90

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject faucet is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace faucet with new faucet incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-6-N24-001

N24

Threaded Faucet

Backsiphonage

4/PL-142

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-6-N8-001, 1-6-N25-

001, and 1-6-N28-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N25-001

N25

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

1329-31

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-6-N26-001

N26

Threaded Faucet

Backsiphonage

1/PL-140

11/06/2019

Picture of Potential Cross Connection

Date of Survey:

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject faucet is not provided with required backflow prevention for backsiphonage (vacuum breaker), and present a potential cross connect hazard.

Recommendation is to replace faucet with new faucet incorporating a vacuum breaker, or use an in-line vacuum breaker.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N27-001

N27

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

All sink in these rooms are equipted with the same spigot assembly as 1-6-N8-001, 1-6-N25-

001, and 1-6-N28-001

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-6-N28-001

N28

Threaded Faucet

Backsiphonage

1/PL-140

08/27/2019

1337-9

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Drawing Reference #:

Date of Survey:

Cross Connection Identification

Cooling Towers & Storage Tanks

1-7-E7A-001

E7A

Soap Dispenser

Backsiphonage

2/PL-144

11/06/2019

Picture of Potential Cross Connection

Cross Connection Identification

Date of Survey:

Bao Phone 003

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-7-N13B-001

N13B

Soap Dispenser

Backsiphonage

1/PL-144

11/06/2019

Picture of Potential Cross Connection

Cross Connection Identification

Date of Survey:

Bao Phone 004

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-7-W27-001

W27

Soap Dispenser

Backsiphonage

1/PL-143

11/06/2019

Picture of Potential Cross Connection

Cross Connection Identification

Date of Survey:

Bao Phone 001

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-7-W55-001

W55

Slop Sink

Backsiphonage

1/PL-143

08/28/2019

Picture of Potential Cross Connection

Cross Connection Identification

Date of Survey:

1357-60

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-8-W60-001

W60

Drain Pipe

Backsiphonage

2/PL-149

08/29/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject is not provided with required backflow prevention for backsiphonage, and present a potential cross connect hazard. Recommendation is to install check valve and provide an appropriate air gap for drain piping.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-8-W60-002

W60

Drain Pipe

Backsiphonage

2/PL-149

08/29/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject is not provided with required backflow prevention for backsiphonage, and present a potential cross connect hazard. Recommendation is to install check valve and provide an appropriate air gap for drain piping.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-8-W60-003

W60

Drain Pipe

Backsiphonage

2/PL-149

08/29/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject is not provided with required backflow prevention for backsiphonage, and present a potential cross connect hazard. Recommendation is to install check valve and provide an appropriate air gap for drain piping.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-8-W60-004

W60

Drain Pipe

Backsiphonage

2/PL-149

08/29/2019

Picture of Potential Cross Connection

Date of Survey:

Image Not Available

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

The subject is not provided with required backflow prevention for backsiphonage, and present a potential cross connect hazard. Recommendation is to install check valve and provide an appropriate air gap for drain piping.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-9-E4-001

E4

Soap Dispenser

Backsiphonage

2/PL-153

08/23/2019

Picture of Potential Cross Connection

Cross Connection Identification

Date of Survey:

1231-6

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-9-N4-001

N4

Soap Dispenser

Backsiphonage

1/PL-155

08/25/2019

Picture of Potential Cross Connection

Cross Connection Identification

Date of Survey:

1259-63

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-9-W22-001

W22

Soap Dispenser

Backsiphonage

1/PL-152

08/25/2019

Picture of Potential Cross Connection

Date of Survey:

1280-2

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-10-E22-001

E22

Soap Dispenser

Backsiphonage

2/PL-157

08/27/2019

Picture of Potential Cross Connection

Date of Survey:

1339-42

Cross Connection Identification

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-10-N2-001

N2

Soap Dispenser

Backsiphonage

1/PL-156

08/23/2019

Picture of Potential Cross Connection

Cross Connection Identification

Date of Survey:

1222-6

Identification of existing backflow cross connection sources per Codes and Regulations as provided in original VA SOW

Description

Cross Connection Number: Comments / Recommendations

Building Number:

Existing sink faucet water source appears to be protected with an existing atmospheric vacuum breaker upstream of the faucet. Recommended inspection and verification of proper operation.

Floor:

Room Number:

Case Number:

Device:

Hazard:

Cooling Towers & Storage Tanks

1-11-C1-001

C1

Spigot/Hose

Backsiphonage

2/PL-158

06/27/2019

Picture…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .