D.1.c. Recommendations for Retaining Structures for Intersection Improvements at Bayfront Highway.pdf
PDF 134 KB Posted
- Solicitation number
- B27000553
- Issued by
- Hawaii County, Hawaii
About this file
This is a technical memorandum from GEOLABS, INC., a geotechnical engineering firm, dated June 5, 2026, addressing the Hawaii Department of Transportation's Hilo Bayfront Highway Intersection Improvements project (Work Order 8467-00). The memorandum provides geotechnical engineering recommendations for the design and construction of retaining structures required for the proposed intersection improvement project on the Island of Hawaii. The recommendations are based on field exploration and subsurface conditions analysis, with design criteria derived from AASHTO LRFD Bridge Design Specifications, 9th Edition, 2020. The document specifies technical parameters for retaining structure foundations, lateral earth pressures, dynamic seismic loads, and drainage systems necessary to support the project's construction activities.
The memorandum establishes critical design specifications including shallow foundation systems with ultimate bearing capacities of 5,500 psf for extreme limit states and 2,500 psf for strength limit states on gravelly surficial fill. Static lateral earth pressure recommendations range from 40 to 60 pcf depending on backfill conditions, while dynamic lateral earth forces from seismic loading (based on a peak bedrock acceleration of 0.602g) are estimated at 48.4 pounds per linear foot for restrained conditions and 14.3 pounds per linear foot for unrestrained conditions. The memorandum mandates comprehensive drainage systems utilizing 12-inch permeable material zones with perforated pipes and specifies backfill compaction requirements of 90 to 95 percent relative compaction. These technical recommendations serve as foundational engineering guidance for contractors bidding on the Hilo Bayfront Highway intersection improvements project.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GEOLABS, INC. TECHNICAL
Geotechnical Engineering and Drilling Services MEMORANDUM
94-429 Koaki Street, Suite 200 • Waipahu, Hawaii 96797
Telephone: (808) 841-5064 • E-mail: hawaii@geolabs.net Hawaii • California
DATE: June 5, 2026 @ 5:17 PM W.O. No.: 8467-00 TO: AECOM FROM: John Chen/Taylor Onizuka ATTN: Ms. Jessica Samura NO. OF PAGES: 4 SUBJECT: Intersection Improvements at Bayfront Highway Recommendations for Retaining Structures E-MAIL: Jessica.Samura@aecom.com COPY TO: Blum@kaihawaii.com File / Original
This technical memorandum presents our geotechnical recommendations in support of the design of retaining structures for the Intersection Improvements at Bayfront Highway project on the Island of Hawaii.
We anticipate that retaining wall systems may be required for the proposed intersection improvement project. Therefore, based on the design criteria provided by AASHTO LRFD Bridge Design Specifications 9th Edition, 2020, the following recommendations may be considered for the design of retaining structures.
Retaining Structure Foundations
Based on the subsurface conditions encountered during our field exploration, we recommend that the retaining structure foundations consist of a shallow foundation system, such as spread/strip footings. We believe an ultimate bearing capacity of up to 5,500 psf may be used to evaluate the extreme limit state of the footings bearing on the gravelly surficial fill. To evaluate the strength limit state of the structure foundations, a bearing pressure of up to 2,500 psf may be used based on a resistance factor of 0.45.
In general, the retaining wall should be embedded a minimum of 24 inches below the lowest adjacent finished grade. In addition, the footing should be extended deeper to obtain a minimum 6-foot setback distance measured horizontally from the outside edge of the footing to the face of the slope for sloping ground conditions. To protect the foundation from potential erosion, we also recommend placing grouted riprap protection (GRP) within the setback area.
The wall subgrades should be compacted to a minimum of 90 percent relative compaction to provide a firm and unyielding base. Soft and/or loose soils encountered at the wall subgrades should be over-excavated to a minimum depth of 24 inches below the bottom of the wall elevation. The over-excavation should also extend a minimum of 24 inches laterally beyond the front face of the walls. The resulting over-excavation should be backfilled with aggregate subbase materials.
Intersection Improvements at Bayfront Highway Page 2 Recommendations for Retaining Structures W.O. 8467-00 June 5, 2026
GEOLABS, INC.
Hawaii • California
Based on our field exploration, we anticipate that cobbles/boulders may be encountered within the surficial fill material. Where the cobbles/boulders are encountered within the footing subgrade, we recommend over-excavating the footing subgrade at least 12 inches to be backfilled with aggregate subbase material, to provide uniform support.
Lateral loads acting on the foundations may be resisted by frictional resistance between the base of the foundation and the bearing material and by passive earth pressure acting against the near-vertical faces of the foundation system. The following coefficient of friction values of the extreme event and strength limit states may be used for preliminary design purposes. The adhesion component of sliding resistance should be neglected in the design.
COEFFICIENT OF SLIDING FRICTION
Bearing Material Extreme Event Limit State
Strength Limit State
Gravelly Surficial Fill 0.58 0.46
Lateral load resistance due to passive pressure for footings may be estimated using a triangular distribution of 350 pounds per square foot per foot of depth (pcf) for the extreme event limit state. Passive pressure with a triangular distribution of 175 pcf may be used to resist lateral loads for the strength limit state. It should be noted that the amount of deflection needed to mobilize the full passive pressure is at least 0.5 inches. For deflections less than that needed to mobilize full passive pressure, a linearly interpolated reduced passive pressure may be used in evaluating the lateral load resistance of the footing. Unless covered by pavements or slabs, the passive resistance in the upper 12 inches should be neglected.
Static Lateral Earth Pressure
Retaining structures should be designed to resist the lateral earth pressures due to the adjacent soils and surcharge effects. The recommended lateral earth pressures for the design of retaining walls, expressed in equivalent fluid pressures of pounds per square foot per foot of depth (pcf), are presented in the following table
Intersection Improvements at Bayfront Highway Page 3
STATIC LATERAL EARTH PRESSURES FOR
DESIGN OF RETAINING STRUCTURES
Backfill Condition Earth Pressure Component
Active (pcf)
At-Rest
(pcf)
Level Backfill
Horizontal 40 60
Vertical None None
The values provided above assume that the excavated on-site materials (consisting of particles less than 3 inches in the largest dimension) and/or select borrow material will be used to backfill behind the retaining structures. It is assumed that the backfill behind the retaining structure will be compacted to between 90 and 95 percent relative compaction. Over-compaction of the retaining structure backfill should be avoided.
In general, an active condition may be used for gravity retaining walls and structure walls that are free to deflect by as much as 0.5 percent of the wall height. If the tops of the walls are not free to deflect beyond this degree, or are restrained, the walls should be designed for the at-rest condition. The lateral earth pressure values provided above do not include hydrostatic pressure that may be caused by groundwater trapped behind the retaining wall structure.
Surcharge stresses due to areal surcharges, line loads, and point loads within a horizontal distance equal to the depth of the structure should be considered in the design. For uniform surcharge stresses imposed on the loaded side of the structure, a rectangular distribution with a uniform pressure equal to 33 percent of the vertical surcharge pressure acting on the entire height of the structure, which is free to deflect (cantilever), may be used in the design. For structures that are restrained, a rectangular distribution equal to 50 percent of the vertical surcharge pressure acting over the entire height of the structure may be used for design.
Additional analyses during design may be needed to evaluate the surcharge effects of point loads and line loads.
Dynamic Lateral Earth Pressure
Dynamic lateral earth forces due to seismic loading will need to be considered in the design of the retaining structures based on AASHTO LRFD Bridge Design Specifications 9th Edition, 2020.
Seismic loading (amax= 0.301g) is used to estimate the dynamic lateral earth pressures based on a peak bedrock acceleration (PBA) of 0.602g. The table below summarizes the dynamic lateral earth forces acting on the retaining structure in the event of an earthquake versus the estimated wall displacements.
Intersection Improvements at Bayfront Highway Page 4
DESIGN OF RETAINING STRUCTURES DYNAMIC LATERAL EARTH PRESSURES FOR
Lateral Movement
Dynamic Lateral Earth Forces (H2 pounds per linear foot)
Restrained (up to 0.5 inch lateral deflection) 48.4
Unrestrained (up to 3 inches lateral deflection) 14.3
It should be noted that the resultant force should be assumed to act through the mid-height of the wall. The dynamic lateral earth forces are in addition to the static lateral earth pressures provided above. An appropriately reduced factor of safety may be used when dynamic lateral earth forces are accounted for in the design of the retaining structures.
Drainage
In general, the retaining structures should be well drained to reduce the potential for the build-up of hydrostatic pressures. A typical drainage system would consist of a 12-inch wide zone of permeable material, such as No. 3B Fine gravel (ASTM C33, No.67 gradation), placed directly around a perforated pipe (perforations facing down) at the base of the wall discharging to an appropriate outlet or weep holes. As an alternative, a prefabricated drainage product, such as MiraDrain or EnkaDrain, may be used instead of the drainage material. The prefabricated drainage product also should be hydraulically connected to a perforated pipe at the base of the wall.
The backfill from the bottom of the wall to the bottom of the perforated pipe or weephole should consist of relatively impervious materials to reduce the potential for significant water infiltration into the subsurface. In addition, the upper 12 inches of the retaining structure backfill should consist of relatively impervious materials to reduce the potential for significant water infiltration behind the retaining structure unless covered by concrete slabs at the surface.
CLOSURE