CVG_WEST_VAULT_PERMIT_ELECTRICAL_DRAWINGS.pdf

PDF 362 KB Posted

Attached to
West Vault Electric Service Upgrade
Solicitation number
25-026-ITB
Issued by
Kenton County, Kentucky

About this file

These electrical drawings document the West Vault Electrical Improvements project for the Cincinnati/Northern Kentucky International Airport (CVG) located in Hebron, Kentucky. The project involves upgrading the electrical service infrastructure, including installing a new Automatic Transfer Switch (ATS), generator docking station, service entrance equipment, and associated conduit and wiring modifications. The drawings include detailed plans for electrical site utility, floor plans, single-line diagrams, and electrical details across multiple levels of the West Vault facility.

The electrical service upgrade will utilize the existing 1200A service, with calculated loads showing minimal additional demand. The project scope includes removing existing electrical conductors, installing new conduits and conductors, providing a new NEMA-3R service-entrance rated ATS with generator docking capabilities, and integrating a new Schneider Electric PM8000 TAB meter into the existing infrastructure. The electrical system will maintain compatibility with existing facility standards, with careful coordination required to ensure minimal disruption to current operations. The drawings specify detailed requirements for equipment installation, conduit routing, floor penetrations, and electrical system labeling, emphasizing compliance with national electrical codes and local utility requirements.

View the file

Other files

File Type Posted
West_Vault_Electric_Service_Upgrade_(Addendum_#1_Revision).pdf PDF
25-026-ITB_West_Vault_Utility_Map.pdf PDF
#25-026-ITB_West_Vault_Electric_Service_Upgrade_Bidders_List.docx DOCX document
25-026-ITB_West_Vault_Electric_Service_Upgrade_-_Ad.pdf PDF
25-026-ITB_West_Vault_Electric_Service_Upgrade_-_Concrete_Walk_Dwg.pdf PDF
25-026-ITB_West_Vault_Electric_Service_Upgrade_-_Exhibit_B_-_Contract_&_Bonds.pdf PDF
25-026-ITB_West_Vault_Electric_Service_Upgrade_-_Exhibit_A_-_Proposal_Forms.pdf PDF
25-026-ITB_West_Vault_Electric_Service_Upgrade_-_Drawings.pdf PDF
25-026-ITB_West_Vault_Electric_Service_Upgrade_-_Technical_Specifications.pdf PDF
24-51_West_Vault_Electrical_Service_Upgrade.1CB5D75E-4FA2-4707-A2B6-90DD2A62A5EB.pdf.pdf PDF
24-0281_CD-241031-signed.pdf PDF
DIV_26_DIV_27_SPECS_COMBINED.pdf PDF
Affirmative_Action_Certification.docx DOCX document
Non_Debarment_or_Suspension_Certification.docx DOCX document
NonSegregated_Facilities_Certification.docx DOCX document
Buy_American_Certification-Equipment-Building_Projects.docx DOCX document
Disclosure_of_Lobbying_Activities_Certification.docx DOCX document
Certification_of_Offeror-Bidder_Regarding_Tax_Delinquency_and_Felony_Convictions.docx DOCX document
EEO_Certification.docx DOCX document
Buy_American_Certification-Construction_Projects.docx DOCX document
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UON

EM

CFOI

OFOI

CFCI

OFCI

DESCRIPTION

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

UNLESS OTHERWISE NOTED

INDICATES EMERGENCY POWER

ABBREVIATIONS

M O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

IN

G

S Y

M B

O L

C A

B L

IN

G

C

O N

D U

C T

O R

S

O F

O I

C A

B L

IN

G

C

O N

D U

C T

O R

S

O F

C I

C O

N D

U

IT

R

O U

G H

-I N

O

F O

I

IT

E

M U

S E

D O

N P

R O

J E

C T

D E

V

IC

E S

O

F C

I

D E

V

IC

E S

C

F C

I

SYSTEM D

E

V

IC

E S

O

F O

I

SYSTEM

RESPONSIBILITY

MATRIX

#DDATA OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF DATA JACKS

DATA / VOICE

1'-6"

DESCRIPTION M

O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

M B

O L

DESCRIPTION M

O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

M B

O L

DESCRIPTION

C O

N D

U

IT

R

O U

G H

-I N

O

F C

I

C O

N D

U

IT

R

O U

G H

-I N

C

F C

I

C A

B L

IN

G

C

O N

D U

C T

O R

S

C F

C I

P R

O G

R A

M M

IN

G

S

E T

U P

O

F O

I

P R

O G

R A

M M

IN

G

S

E T

U P

O

F C

I

P R

O G

R A

M M

IN

G

S

E T

U P

C

F C

I

STRUCTURED CABLING

SYSTEM RESPONSIBILITY GENERAL NOTES:

A. CMTA IS NOT RESPONSIBILE FOR ASSIGNING SCOPE(S) OR WORK. THE INTENT OF

CONTRACTOR IN THIS MATRIX IS TO SEPERATE OWNER PROVIDED ITEMS FROM THE

GENERAL CONTRACTOR / CONSTRUCTION MANAGER. THE GC OR CM SHALL BE

RESPONSIBLE FOR A COMPLETE SCOPE OF WORK.

B. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TO

VENDOR-FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGS SHALL

BE INCLUDED BY THE CONTRACTOR.

C. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESS CONTROL

DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.

D. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS.

CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT

INSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL

SYSTEMS PRIOR TO CONSTRUCTION.

E. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS, CONTRACTOR

SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO CABLE PATHS AS

REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS AT CABINETS/ON

BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH APPROPRIATE

VENDORS PRIOR TO CONSTRUCTION.

F. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS

INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING,

LABELING, ETC.

G. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM

COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE

CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID. ALL

SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY COMPATIBLE

WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL COORDINATE EXACT

SYSTEM REQUIREMENTS WITH OWNER PRIOR TO BID. NEW COMPONENTS SHALL BE

INTERCONNECTED WITH EXISTING SYSTEMS WHERE POSSIBLE. ALL NEW SYSTEM

DESIGNS AND PROGRAMMING SHALL BE COORDINATED WITH THE OWNER PRIOR TO

ORDERING. ALL PROGRAMMING SHALL BE INCLUDED AS REQUIRED BY THE OWNER.

PROVIDE 4 HOURS OF TRAINING FOR EACH SYSTEM.

LEGEND

INDICATES SELECTED SYSTEM

INDICATES NOT AVAILALBE

INDICATES NOT SELECTED

INTERMEDIATE DISTRIBUTION FRAME - REFERENCE

DATA SYSTEM SCHEMATICS AND DETAILS FOR

ADDITIONAL REQUIREMENTS

IDF

J

S

GROUND FAULT PROTECTED DUPLEX WITH

WEATHER-PROOF "WHILE IN USE" TYPE DIE-CAST

METAL COVERPLATE WITH LOCKABLE

ENCLOSURE AT OUTLET - SEE SPECIFICATIONS

WP

DUPLEX FOR ELECTRIC WATER COOLER: PROVIDE

REMOTE, READILY ACCESSIBLE GFI DEVICE AT 48"

ADJACENT TO WATER COOLER, COORDINATE EXACT

LOCATION WITH PLUMBING CONTRACTOR TO

CONCEAL OUTLET BEHIND COOLER

EWC

SLASH THROUGH ANY DEVICE INDICATES MOUNTING

ABOVE COUNTERTOP 2" ABOVE BACKSPLASH, OR AT

48" WHERE NO COUNTER IS PRESENT

FILLED CENTER BAR INDICATES INTEGRAL GROUND

FAULT PROTECTION (GFCI)

POWER OUTLETS

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE-SAFETY TYPE,

TAMPER-RESISTANT

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

JUNCTION BOX, CEILING OR WALL

VOLTAGE/1PH RECEPTACLE, AS NOTED

VOLTAGE/3PH RECEPTACLE, AS NOTED

1'-6"

1'-6"

1'-6"

1'-6"

1'-6"

1'-6"

2'-2"

AS NOTED

FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL

USB OUTLETS IN ADDITION TO POWER RECEPTACLES

1'-6"

, J

DUPLEX RECEPTACLE, CEILING MOUNTED CLG

MAIN CONTROL PANEL CENTRAL PROCESSING

UNIT (CPU)

6'-6'' TO

TOP

46" TO

LEVER

PULL STATION : DOUBLE ACTION

AUDIO-ONLY NOTIFICATION APPLIANCE

VISUAL-ONLY NOTIFICATION APPLIANCE

AUDIO/VISUAL NOTIFICATION APPLIANCE WALL, CLG

V

A

F

F

FIRE ALARM

FACP

WALL, CLG

WALL, CLG V

A

F

CONDUIT CONCEALED IN WALLS OR IN CEILING

SPACE: ARROW(S) INDICATE(S) HOME RUN & #

OF CIRCUITS: HASHMARKS INDICATE # OF

CONDUCTORS. DASHED LINE INDICATES

CONDUIT BELOW FLOOR.

MISCELLANEOUS

METER 5'-0"

GROUND

NEUTRAL

PHASE

PANELBOARD, SURFACE OR FLUSH MOUNTED,

HATCHING INDICATES EMERGENCY

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

AS NOTEDTRANSFORMER

TAGGED NOTE

REVISION TAG

EQUIP-1

LOW VOLTAGE CABLE PATH

MOTOR CONNECTION, REFER TO EQUIPMENT

CONNECTION SCHEDULE

WP

WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.

PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR

OUTDOORS.

AUTOMATIC TRANSFER SWITCH

E,EMINDICATES EMERGENCY POWER

ATS

CONDUIT UP

CONDUIT DOWN

AUTOMATIC TRANSFER SWITCH

ATS

AUTOMATIC TRANSFER SWITCH

ATS

METER 5'-0" M

M

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 Sycamore St. Suite 400

Cincinnati, OH 45202

T: 513.429.4404

C

U se rs \A ly ss a .M e h n e rt

\D o cu m e n ts

\O C V G

-0

M

E P R A ly ss a .M e h n e rt

Y J5

W H

.r v t

/3

/2

:4 :2

P

M

E-000

AM

JBM

W E S T V

A U

L T E

L E C T R

IC

A L I

M P R

O V E M

E N

T S

C V G

Y o u e ll

R o a d

H e b ro n

K Y

E L E C T R

IC

A L L

E G

E N

D

CONSTRUCTION

OCVG24-01

ELECTRICAL GENERAL NOTES:

A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID

CONFLICT WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.

B. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES.

INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.

C. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.

D. INSTALL NO CONDUIT IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THE COLLECTION

OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.

E. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID

DATE, TO ALLOW CLARIFICATION BY WRITTEN ADDENDUM.

F. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT

REQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.

G. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS

AND MUST BE SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.

H. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).

I. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.

J. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S

RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT

DOCUMENTS, ADVISE THE ENGINEER PRIOR TO INSTALLATION FOR CLARIFICATION.

K. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE

RATING. NO INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.

L. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.

M. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER.

WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER

N. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER

WARRANTY PERIODS FOR EQUIPMENT ARE SPECIFIED.

O. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH

ARCHITECT.

P. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND

ARCHITECT.

Q. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).

R. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT S. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE

THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO

ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE

RESPONSIBILITY OF THE PURCHASER.

T. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO

ENGAGED THEM ON THIS PROJECT.

U. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY

THE ENGINEER IN WRITING.

V. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO

TERMINAL POINT.

W. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER

TRADES (I.E. VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.

X. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL

APPLY.

Y. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN

PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN WRITING.

Z. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING

PREMIUM TIME AS NEEDED.

AA. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK.

ALL CUTTING AND PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH

WORK.

BB. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH

WORK.

CC. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGER NOTIFICATION PERIOD, SO

PROVIDE.

DD. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE

MOST STRINGENT SHALL APPLY.

EE. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM

DIMENSIONED DRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.

FF. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO

CONSTRUCTION.

GG. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO

CONSTRUCTION.

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID

LINES INDICATE EXISTING ITEMS TO REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING

CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO

REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS

INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT

OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON

THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.

"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF

POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE NEW

TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS

DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE

DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING

CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT

ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK

INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS

SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR

THE BID WHICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS

FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),

WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND

REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES

ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW

FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED

FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO

OWNER AT THEIR OPTION.

F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR

RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED

WITH THEIR EQUIPMENT.

G. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /

CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR

INSTALLED.

H. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE

CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC

REQUIREMENTS.

I. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION

SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND

EQUIPMENT SHOWN ON PLANS.

J. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF

BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND

AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE

RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN

INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS

REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL

AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER

REQUIREMENTS.

K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL

BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND

INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES

OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE

DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL

ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.

UNUSED BREAKERS SHALL BE IN OFF POSITION.

GENERAL NOTES (POWER):

A. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED

ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER

HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED

NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE

CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN

THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE

ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH

CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A COMMON

NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

B. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE

LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVE

EMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. MARK INSIDES

OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.

REVISIONS

1 BID AND PERMIT 10.31.24

J

DN

2120191817161514131211109

M

J

M

EXISTING DUKE

TRANSFORMER

(750 kVA)

EXISTING DUKE

UTILITY POLE

EXISTING GENERATOR

GAS STORAGE AND

FILL TANKS

EXISTING GENERATOR

GAS STORAGE TANK

EXISTING

AOA FENCE

EXISTING DUKE

PRIMARY CONDUITS.

ESTIMATED ROUTING.

EXISTING

AOA FENCE

MTS

E1

E2 E3

E4

E5

E7

E8

E13

E14

-17WVL-1

-19WVL-1

E16

W1-EM

WP

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 Sycamore St. Suite 400

Cincinnati, OH 45202

T: 513.429.4404

C

U se rs \A ly ss a .M e h n e rt

\D o cu m e n ts

\O C V G

-0

M

E P R A ly ss a .M e h n e rt

Y J5

W H

.r v t

/3

/2

:4 :2

P

M

E-100

AM

JBM

W E S T V

A U

L T E

L E C T R

IC

A L I

M P R

O V E M

E N

T S

C V G

Y o u e ll

R o a d

H e b ro n

K Y

E L E C T R

IC

A L S

IT

E U

T

IL

IT

Y P

L A N

CONSTRUCTION

OCVG24-01

TAGGED NOTES

E1 EC SHALL PULL NEW CONDUCTORS FROM TRANSFORMER TO

EXISTING MANHOLE AND THROUGH NEW UNDERGROUND

CONDUIT PATH TO BUILDING. CONTRACTOR TO CONFIRM

MANHOLE IS IN WORKABLE CONDITION.

E2 EXISTING CONDUCTORS FOR EXISTING ELECTRICAL SERVICE

TO BE REMOVED.

E3 EXISTING CONDUIT FROM EXISTING MANHOLE TO BUILDING TO

BE ABANDONED. EC TO FILL EMPTY CONDUIT.

E4 CVG TO PROVIDE NEW DOOR FOR ACCESS THROUGH THE

EXISTING AOA FENCE. DOOR SIZE AND FINAL LOCATION TO BE

SELECTED BY CVG AND COORDINATED IN THE FIELD.

E5 EXISTING UTILITY METER TO REMAIN.

E7 PROVIDE NEW SERVICE-ENTRANCE RATED ATS IN NEMA 3R

ENCLOSURE. ATS MUST ACCOMMODATE ROLL-UP

GENERATOR BY CAM LOCK AND CONTAIN TERMINAL BLOCK

FOR CONTROLS. CONNECT NEW SERVICE CONDUCTORS TO

NEW ATS NORMAL LUGS.

E8 PROVIDE NEW UNDERGROUND CONDUITS FROM MANHOLE TO

THE SERVICE DISCONNECT. PRIOR TO RUNNING CONDUIT

CONTRACTOR SHALL HYDROEXCAVATE THE ENTIRE RUN OF

CONDUIT TO AVOID DAMAGING ANY UNDERGROUND UTILITIES.

MANHOLE SHALL BE FULLY EXPOSED TO DETERMINE WHERE

CONDUIT ENTRIES CAN BE SAFELY DRILLED. IT IS EXPECTED

THAT THE CONDUITS WILL NEED TO BE RUN DEEPER IN

LOCATIONS TO AVOID EXISTING CONDUITS. CONDUITS SHALL

RUN AT A SLOPE DOWNWARD TOWARD THE MANHOLE TO

FACILITATE DRAINAGE OF WATER INTO THE MANHOLE.

E13 PROVIDE 120V CIRCUIT FOR GFCI SERVICE RECEPTACLE

INTEGRAL TO ATS AND 120V CIRCUIT FOR HEATER.

E14 PROVIDE NEW SERVICE-ENTRANCE BREAKER IN NEMA-3R

ENCLOSURE. SEE SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

E16 PROVIDE A 4" SLAB AROUND NEW EQUIPMENT, WITH A

MINIMUM OF 36" IN FRONT OF THE EQUIPMENT. SEE

ELECTRICAL SPECIFICATIONS FOR CONCRETE BASE

REQUIREMENTS.

1/8" = 1'-0"E-100

CVG WEST VAULT MAIN LEVEL SITE UTILITY PLAN1

UP

2120191817161514131211109

SD

SD

F

V

F

SD

F

F

SD

J

DN

2120191817161514131211109

J

M

RTE

SUMP

M

RTE

(E)GEN

(E)ATS

E10

E12

E15

(E)WVL-1

(E)T-WVL1

(E)WVH-1

(E)WVH-2

NEW

ATS

E9

E6

E11

E13

NEW

BREAKER

-19WVL-1

-17WVL-1

W1-EM

GENERATOR DOCKING STATION

(MTS) SURFACE MOUNTED ON

EXTERIOR OF BUILDING. REFER

TO ELECTRICAL FLOOR PLAN FOR

LOCATION.

GENERATOR DOCKING STATION

WITH MANUAL TRANSFER SWITCH

GENERAL NOTES:

A. REFER TO NEC SECTION 700.3 (F) FOR ADDITIONAL REQUIREMENTS.

B. REFER TO DRAWINGS AND SPECIFICATIONS FOR THE GENERATOR DOCKING STATION MANUFACTURER AND

MODEL NUMBER.

GRADE

PORTABLE / TEMPORARY

GENERATOR FOR REPAIRING AND

MAINTENANCE OF EMERGENCY

SYSTEMS, PER NEC 700.3(F).

FEMALE CAMLOCK CONNECTION

BOX FOR POWER INLET ONLY NOT

FOR USE AS OUTLET

TEMPORARY / PORTABLE CABLE

PROVIDED TEMPORARY /

PORTABLE GENERATOR VENDOR.

PROVIDE 120V, 20 AMP

GFCI INTEGRAL

RECEPTACLE

GENERATOR DOCKING STATION

(MTS) MANUAL TRANSFER

SWITCH SURFACE MOUNTED ON

EXTERIOR OF BUILDING.

TO ATS

TO ELECTRICAL

SERVICE

GENERATOR DOCKING STATION ELEVATION

DETAILED GENERATOR DOCKING ONE-LINE DIAGRAM

(REFER TO ELECTRICAL SINGLE-LINE FOR ADDITIONAL INFORMATION)

CAMLOCK INPUT CONNECTIONS

TYPICALLY FEMALE CAMLOCKS

TEMPORARY CONNECTION

HOUSING

TEMPORARY / PORTABLE CABLES

PROVIDED TEMPORARY / PORTABLE

GENERATOR VENDOR, TYPICALLY

WITH MALE CAMLOCKS

TO TEMPORARY /

PORTABLE GENERATOR

G N

DON'T BOND

NEUTRAL AND

GROUND

CONDUCTORS

TOGETHER

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 Sycamore St. Suite 400

Cincinnati, OH 45202

T: 513.429.4404

C

U se rs \A ly ss a .M e h n e rt

\D o cu m e n ts

\O C V G

-0

M

E P R A ly ss a .M e h n e rt

Y J5

W H

.r v t

/3

/2

:4 :2

P

M

E-101

AM

JBM

W E S T V

A U

L T E

L E C T R

IC

A L I

M P R

O V E M

E N

T S

C V G

Y o u e ll

R o a d

H e b ro n

K Y

E L E C T R

IC

A L F

L O

O R

P L A N

S

CONSTRUCTION

OCVG24-01

1/4" = 1'-0"E-101

CVG WEST VAULT APRON LEVEL ELECTRICAL PLAN1

TAGGED NOTES

E6 PROVIDE NEW PM8000 TAB METER. CONNECT TO NEW MTS

AND CONNECT DATA TO IT RACK INSIDE WEST VAULT ON MAIN

FLOOR. SEE ELECTRICAL SPECIFICATIONS AND CVGAA DCM

FOR EXACT METERING SPECIFICATIONS.

E9 STUB CONDUIT AND CONDUCTORS FROM ATS THROUGH WALL

INTO PULL BOX INSIDE BUILDING.

E10 STUB CONDUIT DOWN FROM BOX THROUGH MAIN LEVEL SLAB

AND RUN UNDER MAIN LEVEL SLAB NORTH OF SUPPORT

BEAM.

E11 CONNECT TAB METER TO EXISTING DATA RACK.

E12 CONNECT NEW CONDUCTORS AND CONDUIT TO EXISTING

ATS.

E13 PROVIDE 120V CIRCUIT FOR GFCI SERVICE RECEPTACLE

INTEGRAL TO ATS AND 120V CIRCUIT FOR HEATER.

E15 DEMOLISH EXISTING MAIN DISCONNECT NEXT TO ATS.

1/4" = 1'-0"E-101

CVG WEST VAULT MAIN LEVEL ELECTRICAL PLAN2

SCALE: NONE

GENERATOR DOCKING STATION - MANUAL TRANSFER

SWITCH

GENERAL NOTES:

A. NORMAL POWER LABELS SHALL BE BLACK WITH WHITE LETTERS.

B. EMERGENCY POWER LABELS SHALL BE RED WITH WHITE LETTERS. LABEL SHOULD ALSO INCLUDE

THE WORD "EMERGENCY" IN 1/4" LETTERS.

C. EMERGENCY POWER LABELS IN HEALTHCARE APPLICATIONS SHOULD INCLUDE SYSTEM SEVERED

"LIFE SAFETY", "CRITICAL" OR "EQUIPMENT" .

D. UTILIZE SCREW-ON TYPE LAMACOID PLATES.

E. THIS DETAILS APPLIES TO ALL ELECTRICAL EQUIPMENT INCLUDING PANELS, SWITCHGEAR, DISCONNECTS, TRANSFORMERS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES (VDF'S), SPECIAL DEVICE PLATES, INVERTER, AND SIMILAR MATERIALS SHALL BE CLEARLY MARKED AS TO

THEIR FUNCTION AND USE.

TYPICAL POWER PANEL NAMEPLATE DETAIL

NO SCALE

1/2'' HIGH

LETTERS

1/4'' HIGH

LETTERS

PANEL LXW

120/208V/3PH/4W

FEED: 200 AMPS

(4) #3/0, #6 GND, 2" C.

FED FROM: MDP

NO SCALE

PUMP P-1

208V/3PH/4W

FEED: 600 AMPS

FED FROM: MDP

CKT # 6

TYPICAL EQUIPMENT NAMEPLATE

LAMACOID

NAME PLATE

1/2'' HIGH

LETTERS

1/4'' HIGH

LETTERS

LAMACOID

NAME PLATE

GENERAL FLOOR PENETRATION NOTES :

A. WHERE CONDUITS PENETRATE A FLOOR SLAB AND ARE EXPOSED, PROVIDE SQUARE 4'' HIGH

CONCRETEPAD AROUND CONDUIT SLEEVE AND EXTEND SLEEVE 4'' ABOVE PAD.

B. WHERE CONDUITS OR SLEEVES PENETRATE FLOORS IN GROUPS, THE CONCRETE PAD SHOULD BE

CONTINUOUS AROUND ALL CONDUITS OR SLEEVES.

2" EA. SIDE

CONDUIT SLEEVE 2'' LARGER IN DIAMETER

THAN CONDUIT(S) PASSING THROUGH SHALL

BE RIGID STEEL.

IF RATED FLOOR, PROVIDE CAULKING-STYLE

FIRESTOPPING BETWEEN SLEEVE AND WALL

MATERIAL TO ANCHOR SLEEVE AND

RESTORE RATING OF WALL PER LOCAL AUTH.

HAVING JURISDICTION.

TYPICAL CONDUIT PASSING

THROUGH A SUSPENDED FLOOR.

IF RATED FLOOR, PROVIDE REMOVABLE

FIRESTOPPING PILLOW (FSB OR EQUAL) IN

UL LISTED FIRESTOPPING ASSEMBLY TO

ALLOW FOR EASY REMOVAL AND

INSTALLATION OF NEW CABLES AND/OR

CONDUITS.

FLOOR

PROVIDE REMOVABLE FIRESTOPPING PILLOW (FSB OR

EQUAL) IN UL LISTED FIRESTOPPING ASSEMBLY TO ALLOW

FOR EASY REMOVAL AND INSTALLATION OF NEW CABLES.

8"+, TO CLEAR

OBSTRUCTIONS

CL

2" EA. SIDE

CEILING

STRUCTURE

LOCATE SO THAT ACCESSIBLE CEILING IS AT EACH SIDE OF

SLEEVES OR PROVIDE ACCESS PANEL.

PROVIDE CAULKING-STYLE FIRESTOPPING BETWEEN

SLEEVE AND WALL MATERIAL TO ANCHOR SLEEVE AND

RESTORE RATING OF WALL PER LOCAL AUTH. HAVING

JURISDICTION.

SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH

INSULATED THROAT CONDUIT TERMINATORS ON EACH

END. PROVIDE A THREADED CAP ON EACH END IF NOT

USED FOR WIRING . LINE-UP WITH "CABLE TRAY" OR ''HOOK

PATH'' WHERE APPLICABLE.

FIRE/SMOKE RATED OR UN-RATED PARTITION OF VARIOUS

CONSTRUCTIONS. REFER TO ARCHITECTURAL PLANS OR

FIELD VERIFY TYPE.

GENERAL NOTES:

A. PROVIDE ONE 2" SPARE CONDUIT SLEEVE THROUGH ALL FULL HEIGHT

PARTITIONS FOR FUTURE USE. LABEL AS SPARE FOR OWNER'S USE ONLY.

REFER TO ARCHITECTURAL PLANS FOR FULL HEIGHT PARTITION LOCATIONS.

B. USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS,

ETC.

NOTE: IF THE SLEEVE SIZE AND NUMBER

INDICATED ON PLANS WILL NOT BE ADEQUATE TO

CONTAIN ALL CABLES AND STILL LEAVE 25%

SPARE CAPACITY, PROVIDE ADD'L SLEEVES AS

NEEDED TO PROVIDE THIS SPARE CAPACITY.

O R

P E

R P

L A

N S

M

IN

MANUFACTURED SAND BACKFILL

FINISHED GRADE

6 MIL x 6" WIDE, RED, "DANGER - HIGH

VOLTAGE" POLYETHYLENE WARNING TAPE

CLEAN SELECT BACKFILL TO

MATCH GRADE, PATCH AND

REPAIR SURFACE

UNDISTURBED EARTH

#4 REBAR AT EACH CORNER WITH 2"

MIN COVER, OVERLAP ENDS MIN 4"

4000 PSI CONCRETE

PVC SCH 40, 7.5" SPACING, MIN

3" COVER ON ALL SIDES

SUPPORT RACK, UNDERGROUND

DEVICES 4W30-2 (OR EQUAL)

1' - 6"

MINIMUM WIDTH

PROVIDE METAL TRACER

AROUND CONDUIT, ENDS TO

BE ACCESSIBLE FOR TRACING

M

IN

IM

U

M H

E

IG

H T

GENERAL NOTES:

A. USE RIGID STEEL SWEEPING ELBOWS AT ALL TURNS, WHERE RISING ON UTILITY POWER

POLE, TURNING UP INTO PAD MOUNTED UTILITY TRANSFORMER AND TURNING UP INTO

BUILDING.

B. REFER TO POWER RISER, FLOOR PLANS AND PLAN NOTES FOR EXACT QUANTITY AND SIZE

OF CONDUITS.

C. COMMUNICATIONS/FIBER RACEWAYS SHALL BE ROUTED IN DUCT BANK ENCASED

CONSTRUCTION, CONSTRUCTED SAME AS SHOWN, EXCEPT FOR NUMBER AND SIZE OF

CONDUIT.

D. POUR CONCRETE AGAINST UNDISTURBED EARTH.

E. REFER TO SPECIFICATIONS FOR EXCAVATION, TRENCHING, BACKFILLING AND GRADING

REQUIREMENTS. REFER TO EARTHWORK SPECIFICATIONS FOR GENERAL ROCK REMOVAL

AND EARTHWORK REQUIREMENTS.

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 Sycamore St. Suite 400

Cincinnati, OH 45202

T: 513.429.4404

C

U se rs \A ly ss a .M e h n e rt

\D o cu m e n ts

\O C V G

-0

M

E P R A ly ss a .M e h n e rt

Y J5

W H

.r v t

/3

/2

:4 :2

P

M

E-500

AM

JBM

W E S T V

A U

L T E

L E C T R

IC

A L I

M P R

O V E M

E N

T S

C V G

Y o u e ll

R o a d

H e b ro n

K Y

E L E C T R

IC

A L D

E T A

IL

S

CONSTRUCTION

OCVG24-01

SCALE: NONE

ELECTRICAL EQUIPMENT NAMEPLATE

SCALE: NONE

CONDUIT FLOOR PENETRATION SLEEVE INSTALLATION

SCALE: NONE

CONDUIIT WALL SLEEVE INSTALLATION

SCALE: NONE

DUCT BANK DETAIL - 4 CONDUIT

APRON LEVEL

MAIN LEVEL

ROOF

FINISHED

GRADE

FINISHED GRADE

GENERAL POWER RISER NOTES:

A. REFER TO SPECIFICATIONS FOR CONDUCTOR REQUIREMENTS. FEEDERS SHALL

BE COPPER.

B. PROVIDE ENGRAVED LAMACOID LABELS FOR ALL POWER DISTRIBUTION

EQUIPMENT FURNISHED OR MODIFIED IN THIS PROJECT, LABELS PER DETAILS

AND SPECIFICATIONS.

C. CONTRACTOR SHALL INSTALL SEPARATE CONDUITS, PULL BOXES, ETC. FOR EACH

EMERGENCY POWER BRANCH & NORMAL POWER PER NEC FOR COMPLETE

SEPARATION OF POWER SERVICES.

D. MINIMUM PANEL MOUNTING SPACE IS NOTED ON DRAWINGS AND SCHEDULES.

ALL MOUNTING SPACE SHALL BE PREPARED TO ACCEPT FUTURE BREAKERS.

E. NO CONDUIT SHALL BE INSTALLED UNDERGROUND, EXCEPT FOR DISTRIBUTION

EQUIPMENT FEEDERS, EXTERIOR CONDUITS, PARKING LOT ISLANDS, UNLESS

REQUIRED FOR THE APPLICATION (FLOOR BOXES, ISLANDS, ETC,) OR

SPECIFICALLY INDICATED AS SUCH IN CONSTRUCTION DOCUMENTS. NO CONDUIT

SHALL BE INSTALLED WITHIN CONCRETE SLABS.

F. PROVIDE PORTABLE GENERATOR CONNECTION CABINET FOR BACK-UP OF THE

SERVICE DURING MAINTENANCE/OUTAGES ON THE PERMANENT GENERATOR.

CABINET SHALL BE A LISTED MANUAL TRANSFER SWITCH WITH GENERATOR

STARTUP CAPABILITY AND 120V/208V CONNECTIONS FOR GENERATOR

ACCESSORIES. PROVIDE WITH KIRK-KEY INTERLOCK WITH GENERATOR LIFE-

SAFETY ATS FEEDER BREAKER.

N E

ATS

1200A

GEN1

938kVA/750kW

DIESEL

GENERATOR

480Y/277V/3Φ/4W

1200A

750 KVA,

480VOLT, 3-PHASE SECONDARY

EXISTING

PAD-MOUNTED UTILITY

TRANSFORMER

17.25 KAFC

M

N E

ATS

1200A

ATS

LINEUP

LINEUP

WVH-2

1200AF/

1000AT

LSIG

EXISTING WVH1 MAIN ELECTRIC ROOM

480Y/277V 3-PHASE, 4-WIRE

1200A BUSSING

DISTRIBUTION SECTION(S)

A

/3 P

A

/3 P

A

/3 P

A

/3 P

KEYNOTES

1. EXISTING ELECTRICAL SERVICE ENTRANCE PAST MANHOLE TO

BE ABANDONED. REMOVE CONDUCTORS AND FILL CONDUIT

FROM MANHOLE TO BUILDING.

2. PROVIDE NEMA-3R SERVICE-ENTRANCE RATED, 4-POLE,

AUTOMATIC TRANSFER SWITCH/GENERATOR DOCKING

STATION, REFER TO DETAIL FOR ADDITIONAL INFORMATION.

3. REMOVE EXISTING SERVICE CONDUCTORS AND CONDUIT

INSIDE BUILDING FEEDING ATS NORMAL POWER.

4. EXISTING MANHOLE IS POINT OF CONNECTING FOR NEW

CONDUIT FOR NEW ELECTRICAL SERVICE TO BUILDING.

5. CONNECT NEW CONDUCTORS FROM NEW ATS TO EXISTING

ATS.

6. PROVIDE NEW LSIG CIRCUIT BREAKER WITH EMRS INSIDE

NEMA-3R ENCLOSURE.

7. PROVIDE NEW SCHNEIDER ELECTRIC PM8000 TAB METER.

PROVIDE ALL WIRING AND INTEGRATION REQUIRED TO TIE INTO

THE EXISTING CVG SOFTWARE INFRASTRUCTURE. CT'S SHALL

BE INSTALLED IN THE ATS AND PIPED INTO THE METER

ENCLOSURE INSIDE. T1

TRANSFORMER

75 kVA

208Y/120V,3Φ,4W

WVL-1

225A MCB

PANEL

(3) #1 AWG CU AND

(1) #8 GND IN

1" C.

(4) #4/0 AWG CU AND

(1) #4 GND IN

2-1/2" C.

(3) SETS

(4) #500KCMIL AWG CU AND

(1) #4 GND IN

3-1/2" C.

PROJECT SCOPE

PROJECT SCOPE

ELECTRICAL SERVICE CALCULATIONS:

EXISTING DEMAND FROM UTILITY COMPANY 273.6 kW +25% PER NEC 220.87 342.0 kW LOAD REMOVED BY DEMOLITION -00.0 kW ADDITIONAL LOAD BY PROJECT 00.7 kW

CALCULATED LOAD 342.7 kW

412.2A @ 480V, 3PH

EXISTING 1200A SERVICE IS SUFFICIENT FOR PLANNED

RENOVATIONS.

33.4KAFC

M

1000A

33.1 KAFC

1000AT/

1200AF

4CU-1000A

4CU-1000A

4CU-1000A

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 Sycamore St. Suite 400

Cincinnati, OH 45202

T: 513.429.4404

C

U se rs \A ly ss a .M e h n e rt

\D o cu m e n ts

\O C V G

-0

M

E P R A ly ss a .M e h n e rt

Y J5

W H

.r v t

/3

/2

:4 :2

P

M

E-700

AM

JBM

W E S T V

A U

L T E

L E C T R

IC

A L I

M P R

O V E M

E N

T S

C V G

Y o u e ll

R o a d

H e b ro n

K Y

E L E C T R

IC

A L S

IN

G

L E L

IN

E

CONSTRUCTION

OCVG24-01

SCALE: NONE

CVG WEST VAULT ELECTRICAL SINGLE LINE

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.

TOTAL ESTIMATED DEMAND CURRENT: 2 A

TOTAL CONNECTED CURRENT: 2 A

REC 180 VA 100.00% 180 VA TOTAL ESTIMATED DEMAND: 680 VA

EQUIP 500 VA 100.00% 500 VA TOTAL CONNECTED LOAD: 680 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

4 A 0 A 2 A

0.5 kVA 0.0 kVA 0.2 kVA

(E) FIRE ALARM PANEL 20 1 41 0.0 0.0 42 1 20 (E) SPARE

(E) SECURITY SYSTEM 20 1 39 0.0 0.0 40 1 20 (E) SPARE

(E) VEEDER ROOT 20 1 37 0.0 0.0 38 1 20 (E) TO HVAC PANEL

(E) DAY TANK PUMP 20 1 35 0.0 0.0 36 1 20 (E) FAA FIBER EQUIPMENT

(E) GENERATOR BATTERY CHARGER 20 1 33 0.0 0.0 34 1 20 (E) EXISTING LOAD

(E) EXISTING LOAD 20 1 31 0.0 0.0 32 1 20 (E) RVR IN GEN ROOM

29 0.0 0.0 30 1 20 (E) RVR IN GEN ROOM

WATER HEATER 20 2

27 0.0 0.0 28

(E) SEWAGE PUMP RCPT 20 1 25 0.0 0.0 26

2 20 RESTROOM HEATER

23 0.0 0.0 24 1 20 (E) CAMERA POWER

(E) GENERATOR BLOCK HEATER 20 2

21 0.0 0.0 22 1 20 (E) HONEYWELL PANEL HVAC

MTS HEATER/CONTROLS 20 1 19 0.5 0.0 20 1 20 (E) REG ROOM VENT EF3

MTS SERVICE GFCI 20 1 17 0.2 0.0 18 1 20 (E) GEN ROOM VENT EF2

(E) NIGHT LIGHTS 20 1 15 0.0 0.0 16 1 20 (E) WORK ROOM VENT EF1

(E) EXT LIGHTS 20 1 13 0.0 0.0 14 1 20 (E) REG RM LIGHTS WEST

(E) GENERATOR ROOM LIGHTS 20 1 11 0.0 0.0 12 1 20 (E) REG RM LIGHTS EAST

(E) WORK ROOM BENCH LIGHTS 20 1 9 0.0 0.0 10 1 20 (E) RESTROOM RCPT

(E) WORK ROOM LIGHTS 20 1 7 0.0 0.0 8 1 20 (E) RESTROOM LIGHT FAN

(E) GENERATOR ROOM RCPT 20 1 5 0.0 0.0 6 1 20 (E) SOUTH RCPT WORKROOM

(E) WORK ROOM NORTH RCPT 20 1 3 0.0 0.0 4 1 20 (E) NORTHWEST RCPT REG ROOM FIBER...

(E) WORK ROOM NORTH RCPT 20 1 1 0.0 0.0 2 1 20 (E) SW RCPT REG ROOM RADIO

CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION

AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: T-WVL1

VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION:

PANEL: WVL-1 MAINS TYPE: 225A MLO PANEL INTERRUPTING RATING: EXISTING PANEL

PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING PANEL

REVISIONS

1 BID AND PERMIT 10.31.24

Wire Feeder Schedule

Type WireSize

4CU-1000A (3) SETS OF (4) #400 CU & #2/0 CU GND IN 3-1/2"C EACH

ELECTRICAL - LUMINAIRE SCHEDULE

TYPE DESCRIPTION BASIS OF DESIGN EQUAL MANUFACTURERS MOUNTING LAMPS / CCT

MINIMUM

LUMENS

MAXIMUM

WATTAGE VOLTAGE REMARKS

W1-EM EXTERIOR LED WALL PACK WITH BATTERY

BACKUP. WET LOCATION. INTEGRAL

PHOTOCELL. FINISH BY ARCHITECT.

ILP OWM 3L/5L U CCTS BLK PCU EMCT8 OR APPROVED EQUAL SURFACE

WALL

MATCH EXISTING 5231 LUMENS 40 120 MOUNT 10' AFF. PROVIDE UL924 DEVICE.

Sheets
E-000 - ELECTRICAL LEGEND
E-100 - ELECTRICAL SITE UTILITY PLAN
E-101 - ELECTRICAL FLOOR PLANS
E-500 - ELECTRICAL DETAILS
E-700 - ELECTRICAL SINGLE LINE

File details come from the government source that posted it. Updated .