CVG_WEST_VAULT_PERMIT_ELECTRICAL_DRAWINGS.pdf
PDF 362 KB Posted
- Attached to
- West Vault Electric Service Upgrade
- Solicitation number
- 25-026-ITB
- Issued by
- Kenton County, Kentucky
About this file
These electrical drawings document the West Vault Electrical Improvements project for the Cincinnati/Northern Kentucky International Airport (CVG) located in Hebron, Kentucky. The project involves upgrading the electrical service infrastructure, including installing a new Automatic Transfer Switch (ATS), generator docking station, service entrance equipment, and associated conduit and wiring modifications. The drawings include detailed plans for electrical site utility, floor plans, single-line diagrams, and electrical details across multiple levels of the West Vault facility.
The electrical service upgrade will utilize the existing 1200A service, with calculated loads showing minimal additional demand. The project scope includes removing existing electrical conductors, installing new conduits and conductors, providing a new NEMA-3R service-entrance rated ATS with generator docking capabilities, and integrating a new Schneider Electric PM8000 TAB meter into the existing infrastructure. The electrical system will maintain compatibility with existing facility standards, with careful coordination required to ensure minimal disruption to current operations. The drawings specify detailed requirements for equipment installation, conduit routing, floor penetrations, and electrical system labeling, emphasizing compliance with national electrical codes and local utility requirements.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UON
EM
CFOI
OFOI
CFCI
OFCI
DESCRIPTION
CONTRACTOR FURNISHED OWNER INSTALLED
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
UNLESS OTHERWISE NOTED
INDICATES EMERGENCY POWER
ABBREVIATIONS
M O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
IN
G
S Y
M B
O L
C A
B L
IN
G
C
O N
D U
C T
O R
S
O F
O I
C A
B L
IN
G
C
O N
D U
C T
O R
S
O F
C I
C O
N D
U
IT
R
O U
G H
-I N
O
F O
I
IT
E
M U
S E
D O
N P
R O
J E
C T
D E
V
IC
E S
O
F C
I
D E
V
IC
E S
C
F C
I
SYSTEM D
E
V
IC
E S
O
F O
I
SYSTEM
RESPONSIBILITY
MATRIX
#DDATA OUTLET : NUMBER BESIDE OUTLET
INDICATES NUMBER OF DATA JACKS
DATA / VOICE
1'-6"
DESCRIPTION M
O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
M B
O L
DESCRIPTION M
O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
M B
O L
DESCRIPTION
C O
N D
U
IT
R
O U
G H
-I N
O
F C
I
C O
N D
U
IT
R
O U
G H
-I N
C
F C
I
C A
B L
IN
G
C
O N
D U
C T
O R
S
C F
C I
P R
O G
R A
M M
IN
G
S
E T
U P
O
F O
I
P R
O G
R A
M M
IN
G
S
E T
U P
O
F C
I
P R
O G
R A
M M
IN
G
S
E T
U P
C
F C
I
STRUCTURED CABLING
SYSTEM RESPONSIBILITY GENERAL NOTES:
A. CMTA IS NOT RESPONSIBILE FOR ASSIGNING SCOPE(S) OR WORK. THE INTENT OF
CONTRACTOR IN THIS MATRIX IS TO SEPERATE OWNER PROVIDED ITEMS FROM THE
GENERAL CONTRACTOR / CONSTRUCTION MANAGER. THE GC OR CM SHALL BE
RESPONSIBLE FOR A COMPLETE SCOPE OF WORK.
B. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TO
VENDOR-FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGS SHALL
BE INCLUDED BY THE CONTRACTOR.
C. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESS CONTROL
DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.
D. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS.
CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT
INSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL
SYSTEMS PRIOR TO CONSTRUCTION.
E. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS, CONTRACTOR
SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO CABLE PATHS AS
REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS AT CABINETS/ON
BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH APPROPRIATE
VENDORS PRIOR TO CONSTRUCTION.
F. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS
INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING,
LABELING, ETC.
G. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM
COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE
CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID. ALL
SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY COMPATIBLE
WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL COORDINATE EXACT
SYSTEM REQUIREMENTS WITH OWNER PRIOR TO BID. NEW COMPONENTS SHALL BE
INTERCONNECTED WITH EXISTING SYSTEMS WHERE POSSIBLE. ALL NEW SYSTEM
DESIGNS AND PROGRAMMING SHALL BE COORDINATED WITH THE OWNER PRIOR TO
ORDERING. ALL PROGRAMMING SHALL BE INCLUDED AS REQUIRED BY THE OWNER.
PROVIDE 4 HOURS OF TRAINING FOR EACH SYSTEM.
LEGEND
INDICATES SELECTED SYSTEM
INDICATES NOT AVAILALBE
INDICATES NOT SELECTED
INTERMEDIATE DISTRIBUTION FRAME - REFERENCE
DATA SYSTEM SCHEMATICS AND DETAILS FOR
ADDITIONAL REQUIREMENTS
IDF
J
S
GROUND FAULT PROTECTED DUPLEX WITH
WEATHER-PROOF "WHILE IN USE" TYPE DIE-CAST
METAL COVERPLATE WITH LOCKABLE
ENCLOSURE AT OUTLET - SEE SPECIFICATIONS
WP
DUPLEX FOR ELECTRIC WATER COOLER: PROVIDE
REMOTE, READILY ACCESSIBLE GFI DEVICE AT 48"
ADJACENT TO WATER COOLER, COORDINATE EXACT
LOCATION WITH PLUMBING CONTRACTOR TO
CONCEAL OUTLET BEHIND COOLER
EWC
SLASH THROUGH ANY DEVICE INDICATES MOUNTING
ABOVE COUNTERTOP 2" ABOVE BACKSPLASH, OR AT
48" WHERE NO COUNTER IS PRESENT
FILLED CENTER BAR INDICATES INTEGRAL GROUND
FAULT PROTECTION (GFCI)
POWER OUTLETS
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE-SAFETY TYPE,
TAMPER-RESISTANT
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
JUNCTION BOX, CEILING OR WALL
VOLTAGE/1PH RECEPTACLE, AS NOTED
VOLTAGE/3PH RECEPTACLE, AS NOTED
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
2'-2"
AS NOTED
FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL
USB OUTLETS IN ADDITION TO POWER RECEPTACLES
1'-6"
, J
DUPLEX RECEPTACLE, CEILING MOUNTED CLG
MAIN CONTROL PANEL CENTRAL PROCESSING
UNIT (CPU)
6'-6'' TO
TOP
46" TO
LEVER
PULL STATION : DOUBLE ACTION
AUDIO-ONLY NOTIFICATION APPLIANCE
VISUAL-ONLY NOTIFICATION APPLIANCE
AUDIO/VISUAL NOTIFICATION APPLIANCE WALL, CLG
V
A
F
F
FIRE ALARM
FACP
WALL, CLG
WALL, CLG V
A
F
CONDUIT CONCEALED IN WALLS OR IN CEILING
SPACE: ARROW(S) INDICATE(S) HOME RUN & #
OF CIRCUITS: HASHMARKS INDICATE # OF
CONDUCTORS. DASHED LINE INDICATES
CONDUIT BELOW FLOOR.
MISCELLANEOUS
METER 5'-0"
GROUND
NEUTRAL
PHASE
PANELBOARD, SURFACE OR FLUSH MOUNTED,
HATCHING INDICATES EMERGENCY
EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE
AS NOTEDTRANSFORMER
TAGGED NOTE
REVISION TAG
EQUIP-1
LOW VOLTAGE CABLE PATH
MOTOR CONNECTION, REFER TO EQUIPMENT
CONNECTION SCHEDULE
WP
WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.
PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR
OUTDOORS.
AUTOMATIC TRANSFER SWITCH
E,EMINDICATES EMERGENCY POWER
ATS
CONDUIT UP
CONDUIT DOWN
AUTOMATIC TRANSFER SWITCH
ATS
AUTOMATIC TRANSFER SWITCH
ATS
METER 5'-0" M
M
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 Sycamore St. Suite 400
Cincinnati, OH 45202
T: 513.429.4404
C
U se rs \A ly ss a .M e h n e rt
\D o cu m e n ts
\O C V G
-0
M
E P R A ly ss a .M e h n e rt
Y J5
W H
.r v t
/3
/2
:4 :2
P
M
E-000
AM
JBM
W E S T V
A U
L T E
L E C T R
IC
A L I
M P R
O V E M
E N
T S
C V G
Y o u e ll
R o a d
H e b ro n
K Y
E L E C T R
IC
A L L
E G
E N
D
CONSTRUCTION
OCVG24-01
ELECTRICAL GENERAL NOTES:
A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID
CONFLICT WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.
B. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES.
INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.
C. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.
D. INSTALL NO CONDUIT IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THE COLLECTION
OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.
E. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID
DATE, TO ALLOW CLARIFICATION BY WRITTEN ADDENDUM.
F. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.
G. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS
AND MUST BE SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.
H. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).
I. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.
J. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S
RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT
DOCUMENTS, ADVISE THE ENGINEER PRIOR TO INSTALLATION FOR CLARIFICATION.
K. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE
RATING. NO INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.
L. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.
M. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER.
WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER
N. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER
WARRANTY PERIODS FOR EQUIPMENT ARE SPECIFIED.
O. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH
ARCHITECT.
P. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND
ARCHITECT.
Q. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).
R. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT S. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE
THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO
ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE
RESPONSIBILITY OF THE PURCHASER.
T. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO
ENGAGED THEM ON THIS PROJECT.
U. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY
THE ENGINEER IN WRITING.
V. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO
TERMINAL POINT.
W. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER
TRADES (I.E. VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.
X. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL
APPLY.
Y. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN
PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN WRITING.
Z. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING
PREMIUM TIME AS NEEDED.
AA. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK.
ALL CUTTING AND PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH
WORK.
BB. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH
WORK.
CC. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGER NOTIFICATION PERIOD, SO
PROVIDE.
DD. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE
MOST STRINGENT SHALL APPLY.
EE. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM
DIMENSIONED DRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.
FF. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO
CONSTRUCTION.
GG. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO
CONSTRUCTION.
ELECTRICAL DEMOLITION NOTES:
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID
LINES INDICATE EXISTING ITEMS TO REMAIN.
B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING
CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO
REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS
INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT
OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON
THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER.
"LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF
POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE NEW
TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS
DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE
DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING
CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT
ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK
INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS
SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR
THE BID WHICH HE PROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS
FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE),
WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND
REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES
ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO RECEIVE NEW
FINISHES - SEE ARCHITECTURAL PLANS).
E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED
FOR DEMOLITION) WITH OWNER. TURN OVER ITEMS REMOVED TO
OWNER AT THEIR OPTION.
F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR
RELOCATION OF ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED
WITH THEIR EQUIPMENT.
G. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS /
CEILINGS AS REQUIRED WHERE DEVICES ARE BEING REMOVED OR
INSTALLED.
H. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE
CEILINGS SHALL BE REMOVED IN ACCORDANCE WITH NEC
REQUIREMENTS.
I. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION
SHALL BE RELOCATED TO PERMIT INSTALLATION OF DEVICES AND
EQUIPMENT SHOWN ON PLANS.
J. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF
BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND
AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE
RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN
INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS
REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL
AND ENGINEERING PLANS AND SPECIFICATIONS FOR FURTHER
REQUIREMENTS.
K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL
BE PROVIDED WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND
INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES
OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE
DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL
ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC.
UNUSED BREAKERS SHALL BE IN OFF POSITION.
GENERAL NOTES (POWER):
A. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED
ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER
HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED
NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE
CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN
THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE
ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH
CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A COMMON
NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
B. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE
LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVE
EMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. MARK INSIDES
OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.
REVISIONS
1 BID AND PERMIT 10.31.24
J
DN
2120191817161514131211109
M
J
M
EXISTING DUKE
TRANSFORMER
(750 kVA)
EXISTING DUKE
UTILITY POLE
EXISTING GENERATOR
GAS STORAGE AND
FILL TANKS
EXISTING GENERATOR
GAS STORAGE TANK
EXISTING
AOA FENCE
EXISTING DUKE
PRIMARY CONDUITS.
ESTIMATED ROUTING.
EXISTING
AOA FENCE
MTS
E1
E2 E3
E4
E5
E7
E8
E13
E14
-17WVL-1
-19WVL-1
E16
W1-EM
WP
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 Sycamore St. Suite 400
Cincinnati, OH 45202
T: 513.429.4404
C
U se rs \A ly ss a .M e h n e rt
\D o cu m e n ts
\O C V G
-0
M
E P R A ly ss a .M e h n e rt
Y J5
W H
.r v t
/3
/2
:4 :2
P
M
E-100
AM
JBM
W E S T V
A U
L T E
L E C T R
IC
A L I
M P R
O V E M
E N
T S
C V G
Y o u e ll
R o a d
H e b ro n
K Y
E L E C T R
IC
A L S
IT
E U
T
IL
IT
Y P
L A N
CONSTRUCTION
OCVG24-01
TAGGED NOTES
E1 EC SHALL PULL NEW CONDUCTORS FROM TRANSFORMER TO
EXISTING MANHOLE AND THROUGH NEW UNDERGROUND
CONDUIT PATH TO BUILDING. CONTRACTOR TO CONFIRM
MANHOLE IS IN WORKABLE CONDITION.
E2 EXISTING CONDUCTORS FOR EXISTING ELECTRICAL SERVICE
TO BE REMOVED.
E3 EXISTING CONDUIT FROM EXISTING MANHOLE TO BUILDING TO
BE ABANDONED. EC TO FILL EMPTY CONDUIT.
E4 CVG TO PROVIDE NEW DOOR FOR ACCESS THROUGH THE
EXISTING AOA FENCE. DOOR SIZE AND FINAL LOCATION TO BE
SELECTED BY CVG AND COORDINATED IN THE FIELD.
E5 EXISTING UTILITY METER TO REMAIN.
E7 PROVIDE NEW SERVICE-ENTRANCE RATED ATS IN NEMA 3R
ENCLOSURE. ATS MUST ACCOMMODATE ROLL-UP
GENERATOR BY CAM LOCK AND CONTAIN TERMINAL BLOCK
FOR CONTROLS. CONNECT NEW SERVICE CONDUCTORS TO
NEW ATS NORMAL LUGS.
E8 PROVIDE NEW UNDERGROUND CONDUITS FROM MANHOLE TO
THE SERVICE DISCONNECT. PRIOR TO RUNNING CONDUIT
CONTRACTOR SHALL HYDROEXCAVATE THE ENTIRE RUN OF
CONDUIT TO AVOID DAMAGING ANY UNDERGROUND UTILITIES.
MANHOLE SHALL BE FULLY EXPOSED TO DETERMINE WHERE
CONDUIT ENTRIES CAN BE SAFELY DRILLED. IT IS EXPECTED
THAT THE CONDUITS WILL NEED TO BE RUN DEEPER IN
LOCATIONS TO AVOID EXISTING CONDUITS. CONDUITS SHALL
RUN AT A SLOPE DOWNWARD TOWARD THE MANHOLE TO
FACILITATE DRAINAGE OF WATER INTO THE MANHOLE.
E13 PROVIDE 120V CIRCUIT FOR GFCI SERVICE RECEPTACLE
INTEGRAL TO ATS AND 120V CIRCUIT FOR HEATER.
E14 PROVIDE NEW SERVICE-ENTRANCE BREAKER IN NEMA-3R
ENCLOSURE. SEE SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
E16 PROVIDE A 4" SLAB AROUND NEW EQUIPMENT, WITH A
MINIMUM OF 36" IN FRONT OF THE EQUIPMENT. SEE
ELECTRICAL SPECIFICATIONS FOR CONCRETE BASE
REQUIREMENTS.
1/8" = 1'-0"E-100
CVG WEST VAULT MAIN LEVEL SITE UTILITY PLAN1
UP
2120191817161514131211109
SD
SD
F
V
F
SD
F
F
SD
J
DN
2120191817161514131211109
J
M
RTE
SUMP
M
RTE
(E)GEN
(E)ATS
E10
E12
E15
(E)WVL-1
(E)T-WVL1
(E)WVH-1
(E)WVH-2
NEW
ATS
E9
E6
E11
E13
NEW
BREAKER
-19WVL-1
-17WVL-1
W1-EM
GENERATOR DOCKING STATION
(MTS) SURFACE MOUNTED ON
EXTERIOR OF BUILDING. REFER
TO ELECTRICAL FLOOR PLAN FOR
LOCATION.
GENERATOR DOCKING STATION
WITH MANUAL TRANSFER SWITCH
GENERAL NOTES:
A. REFER TO NEC SECTION 700.3 (F) FOR ADDITIONAL REQUIREMENTS.
B. REFER TO DRAWINGS AND SPECIFICATIONS FOR THE GENERATOR DOCKING STATION MANUFACTURER AND
MODEL NUMBER.
GRADE
PORTABLE / TEMPORARY
GENERATOR FOR REPAIRING AND
MAINTENANCE OF EMERGENCY
SYSTEMS, PER NEC 700.3(F).
FEMALE CAMLOCK CONNECTION
BOX FOR POWER INLET ONLY NOT
FOR USE AS OUTLET
TEMPORARY / PORTABLE CABLE
PROVIDED TEMPORARY /
PORTABLE GENERATOR VENDOR.
PROVIDE 120V, 20 AMP
GFCI INTEGRAL
RECEPTACLE
GENERATOR DOCKING STATION
(MTS) MANUAL TRANSFER
SWITCH SURFACE MOUNTED ON
EXTERIOR OF BUILDING.
TO ATS
TO ELECTRICAL
SERVICE
GENERATOR DOCKING STATION ELEVATION
DETAILED GENERATOR DOCKING ONE-LINE DIAGRAM
(REFER TO ELECTRICAL SINGLE-LINE FOR ADDITIONAL INFORMATION)
CAMLOCK INPUT CONNECTIONS
TYPICALLY FEMALE CAMLOCKS
TEMPORARY CONNECTION
HOUSING
TEMPORARY / PORTABLE CABLES
PROVIDED TEMPORARY / PORTABLE
GENERATOR VENDOR, TYPICALLY
WITH MALE CAMLOCKS
TO TEMPORARY /
PORTABLE GENERATOR
G N
DON'T BOND
NEUTRAL AND
GROUND
CONDUCTORS
TOGETHER
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 Sycamore St. Suite 400
Cincinnati, OH 45202
T: 513.429.4404
C
U se rs \A ly ss a .M e h n e rt
\D o cu m e n ts
\O C V G
-0
M
E P R A ly ss a .M e h n e rt
Y J5
W H
.r v t
/3
/2
:4 :2
P
M
E-101
AM
JBM
W E S T V
A U
L T E
L E C T R
IC
A L I
M P R
O V E M
E N
T S
C V G
Y o u e ll
R o a d
H e b ro n
K Y
E L E C T R
IC
A L F
L O
O R
P L A N
S
CONSTRUCTION
OCVG24-01
1/4" = 1'-0"E-101
CVG WEST VAULT APRON LEVEL ELECTRICAL PLAN1
TAGGED NOTES
E6 PROVIDE NEW PM8000 TAB METER. CONNECT TO NEW MTS
AND CONNECT DATA TO IT RACK INSIDE WEST VAULT ON MAIN
FLOOR. SEE ELECTRICAL SPECIFICATIONS AND CVGAA DCM
FOR EXACT METERING SPECIFICATIONS.
E9 STUB CONDUIT AND CONDUCTORS FROM ATS THROUGH WALL
INTO PULL BOX INSIDE BUILDING.
E10 STUB CONDUIT DOWN FROM BOX THROUGH MAIN LEVEL SLAB
AND RUN UNDER MAIN LEVEL SLAB NORTH OF SUPPORT
BEAM.
E11 CONNECT TAB METER TO EXISTING DATA RACK.
E12 CONNECT NEW CONDUCTORS AND CONDUIT TO EXISTING
ATS.
E13 PROVIDE 120V CIRCUIT FOR GFCI SERVICE RECEPTACLE
INTEGRAL TO ATS AND 120V CIRCUIT FOR HEATER.
E15 DEMOLISH EXISTING MAIN DISCONNECT NEXT TO ATS.
1/4" = 1'-0"E-101
CVG WEST VAULT MAIN LEVEL ELECTRICAL PLAN2
SCALE: NONE
GENERATOR DOCKING STATION - MANUAL TRANSFER
SWITCH
GENERAL NOTES:
A. NORMAL POWER LABELS SHALL BE BLACK WITH WHITE LETTERS.
B. EMERGENCY POWER LABELS SHALL BE RED WITH WHITE LETTERS. LABEL SHOULD ALSO INCLUDE
THE WORD "EMERGENCY" IN 1/4" LETTERS.
C. EMERGENCY POWER LABELS IN HEALTHCARE APPLICATIONS SHOULD INCLUDE SYSTEM SEVERED
"LIFE SAFETY", "CRITICAL" OR "EQUIPMENT" .
D. UTILIZE SCREW-ON TYPE LAMACOID PLATES.
E. THIS DETAILS APPLIES TO ALL ELECTRICAL EQUIPMENT INCLUDING PANELS, SWITCHGEAR, DISCONNECTS, TRANSFORMERS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES (VDF'S), SPECIAL DEVICE PLATES, INVERTER, AND SIMILAR MATERIALS SHALL BE CLEARLY MARKED AS TO
THEIR FUNCTION AND USE.
TYPICAL POWER PANEL NAMEPLATE DETAIL
NO SCALE
1/2'' HIGH
LETTERS
1/4'' HIGH
LETTERS
PANEL LXW
120/208V/3PH/4W
FEED: 200 AMPS
(4) #3/0, #6 GND, 2" C.
FED FROM: MDP
NO SCALE
PUMP P-1
208V/3PH/4W
FEED: 600 AMPS
FED FROM: MDP
CKT # 6
TYPICAL EQUIPMENT NAMEPLATE
LAMACOID
NAME PLATE
1/2'' HIGH
LETTERS
1/4'' HIGH
LETTERS
LAMACOID
NAME PLATE
GENERAL FLOOR PENETRATION NOTES :
A. WHERE CONDUITS PENETRATE A FLOOR SLAB AND ARE EXPOSED, PROVIDE SQUARE 4'' HIGH
CONCRETEPAD AROUND CONDUIT SLEEVE AND EXTEND SLEEVE 4'' ABOVE PAD.
B. WHERE CONDUITS OR SLEEVES PENETRATE FLOORS IN GROUPS, THE CONCRETE PAD SHOULD BE
CONTINUOUS AROUND ALL CONDUITS OR SLEEVES.
2" EA. SIDE
CONDUIT SLEEVE 2'' LARGER IN DIAMETER
THAN CONDUIT(S) PASSING THROUGH SHALL
BE RIGID STEEL.
IF RATED FLOOR, PROVIDE CAULKING-STYLE
FIRESTOPPING BETWEEN SLEEVE AND WALL
MATERIAL TO ANCHOR SLEEVE AND
RESTORE RATING OF WALL PER LOCAL AUTH.
HAVING JURISDICTION.
TYPICAL CONDUIT PASSING
THROUGH A SUSPENDED FLOOR.
IF RATED FLOOR, PROVIDE REMOVABLE
FIRESTOPPING PILLOW (FSB OR EQUAL) IN
UL LISTED FIRESTOPPING ASSEMBLY TO
ALLOW FOR EASY REMOVAL AND
INSTALLATION OF NEW CABLES AND/OR
CONDUITS.
FLOOR
PROVIDE REMOVABLE FIRESTOPPING PILLOW (FSB OR
EQUAL) IN UL LISTED FIRESTOPPING ASSEMBLY TO ALLOW
FOR EASY REMOVAL AND INSTALLATION OF NEW CABLES.
8"+, TO CLEAR
OBSTRUCTIONS
CL
2" EA. SIDE
CEILING
STRUCTURE
LOCATE SO THAT ACCESSIBLE CEILING IS AT EACH SIDE OF
SLEEVES OR PROVIDE ACCESS PANEL.
PROVIDE CAULKING-STYLE FIRESTOPPING BETWEEN
SLEEVE AND WALL MATERIAL TO ANCHOR SLEEVE AND
RESTORE RATING OF WALL PER LOCAL AUTH. HAVING
JURISDICTION.
SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH
INSULATED THROAT CONDUIT TERMINATORS ON EACH
END. PROVIDE A THREADED CAP ON EACH END IF NOT
USED FOR WIRING . LINE-UP WITH "CABLE TRAY" OR ''HOOK
PATH'' WHERE APPLICABLE.
FIRE/SMOKE RATED OR UN-RATED PARTITION OF VARIOUS
CONSTRUCTIONS. REFER TO ARCHITECTURAL PLANS OR
FIELD VERIFY TYPE.
GENERAL NOTES:
A. PROVIDE ONE 2" SPARE CONDUIT SLEEVE THROUGH ALL FULL HEIGHT
PARTITIONS FOR FUTURE USE. LABEL AS SPARE FOR OWNER'S USE ONLY.
REFER TO ARCHITECTURAL PLANS FOR FULL HEIGHT PARTITION LOCATIONS.
B. USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS,
ETC.
NOTE: IF THE SLEEVE SIZE AND NUMBER
INDICATED ON PLANS WILL NOT BE ADEQUATE TO
CONTAIN ALL CABLES AND STILL LEAVE 25%
SPARE CAPACITY, PROVIDE ADD'L SLEEVES AS
NEEDED TO PROVIDE THIS SPARE CAPACITY.
O R
P E
R P
L A
N S
M
IN
MANUFACTURED SAND BACKFILL
FINISHED GRADE
6 MIL x 6" WIDE, RED, "DANGER - HIGH
VOLTAGE" POLYETHYLENE WARNING TAPE
CLEAN SELECT BACKFILL TO
MATCH GRADE, PATCH AND
REPAIR SURFACE
UNDISTURBED EARTH
#4 REBAR AT EACH CORNER WITH 2"
MIN COVER, OVERLAP ENDS MIN 4"
4000 PSI CONCRETE
PVC SCH 40, 7.5" SPACING, MIN
3" COVER ON ALL SIDES
SUPPORT RACK, UNDERGROUND
DEVICES 4W30-2 (OR EQUAL)
1' - 6"
MINIMUM WIDTH
PROVIDE METAL TRACER
AROUND CONDUIT, ENDS TO
BE ACCESSIBLE FOR TRACING
M
IN
IM
U
M H
E
IG
H T
GENERAL NOTES:
A. USE RIGID STEEL SWEEPING ELBOWS AT ALL TURNS, WHERE RISING ON UTILITY POWER
POLE, TURNING UP INTO PAD MOUNTED UTILITY TRANSFORMER AND TURNING UP INTO
BUILDING.
B. REFER TO POWER RISER, FLOOR PLANS AND PLAN NOTES FOR EXACT QUANTITY AND SIZE
OF CONDUITS.
C. COMMUNICATIONS/FIBER RACEWAYS SHALL BE ROUTED IN DUCT BANK ENCASED
CONSTRUCTION, CONSTRUCTED SAME AS SHOWN, EXCEPT FOR NUMBER AND SIZE OF
CONDUIT.
D. POUR CONCRETE AGAINST UNDISTURBED EARTH.
E. REFER TO SPECIFICATIONS FOR EXCAVATION, TRENCHING, BACKFILLING AND GRADING
REQUIREMENTS. REFER TO EARTHWORK SPECIFICATIONS FOR GENERAL ROCK REMOVAL
AND EARTHWORK REQUIREMENTS.
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 Sycamore St. Suite 400
Cincinnati, OH 45202
T: 513.429.4404
C
U se rs \A ly ss a .M e h n e rt
\D o cu m e n ts
\O C V G
-0
M
E P R A ly ss a .M e h n e rt
Y J5
W H
.r v t
/3
/2
:4 :2
P
M
E-500
AM
JBM
W E S T V
A U
L T E
L E C T R
IC
A L I
M P R
O V E M
E N
T S
C V G
Y o u e ll
R o a d
H e b ro n
K Y
E L E C T R
IC
A L D
E T A
IL
S
CONSTRUCTION
OCVG24-01
SCALE: NONE
ELECTRICAL EQUIPMENT NAMEPLATE
SCALE: NONE
CONDUIT FLOOR PENETRATION SLEEVE INSTALLATION
SCALE: NONE
CONDUIIT WALL SLEEVE INSTALLATION
SCALE: NONE
DUCT BANK DETAIL - 4 CONDUIT
APRON LEVEL
MAIN LEVEL
ROOF
FINISHED
GRADE
FINISHED GRADE
GENERAL POWER RISER NOTES:
A. REFER TO SPECIFICATIONS FOR CONDUCTOR REQUIREMENTS. FEEDERS SHALL
BE COPPER.
B. PROVIDE ENGRAVED LAMACOID LABELS FOR ALL POWER DISTRIBUTION
EQUIPMENT FURNISHED OR MODIFIED IN THIS PROJECT, LABELS PER DETAILS
AND SPECIFICATIONS.
C. CONTRACTOR SHALL INSTALL SEPARATE CONDUITS, PULL BOXES, ETC. FOR EACH
EMERGENCY POWER BRANCH & NORMAL POWER PER NEC FOR COMPLETE
SEPARATION OF POWER SERVICES.
D. MINIMUM PANEL MOUNTING SPACE IS NOTED ON DRAWINGS AND SCHEDULES.
ALL MOUNTING SPACE SHALL BE PREPARED TO ACCEPT FUTURE BREAKERS.
E. NO CONDUIT SHALL BE INSTALLED UNDERGROUND, EXCEPT FOR DISTRIBUTION
EQUIPMENT FEEDERS, EXTERIOR CONDUITS, PARKING LOT ISLANDS, UNLESS
REQUIRED FOR THE APPLICATION (FLOOR BOXES, ISLANDS, ETC,) OR
SPECIFICALLY INDICATED AS SUCH IN CONSTRUCTION DOCUMENTS. NO CONDUIT
SHALL BE INSTALLED WITHIN CONCRETE SLABS.
F. PROVIDE PORTABLE GENERATOR CONNECTION CABINET FOR BACK-UP OF THE
SERVICE DURING MAINTENANCE/OUTAGES ON THE PERMANENT GENERATOR.
CABINET SHALL BE A LISTED MANUAL TRANSFER SWITCH WITH GENERATOR
STARTUP CAPABILITY AND 120V/208V CONNECTIONS FOR GENERATOR
ACCESSORIES. PROVIDE WITH KIRK-KEY INTERLOCK WITH GENERATOR LIFE-
SAFETY ATS FEEDER BREAKER.
N E
ATS
1200A
GEN1
938kVA/750kW
DIESEL
GENERATOR
480Y/277V/3Φ/4W
1200A
750 KVA,
480VOLT, 3-PHASE SECONDARY
EXISTING
PAD-MOUNTED UTILITY
TRANSFORMER
17.25 KAFC
M
N E
ATS
1200A
ATS
LINEUP
LINEUP
WVH-2
1200AF/
1000AT
LSIG
EXISTING WVH1 MAIN ELECTRIC ROOM
480Y/277V 3-PHASE, 4-WIRE
1200A BUSSING
DISTRIBUTION SECTION(S)
A
/3 P
A
/3 P
A
/3 P
A
/3 P
KEYNOTES
1. EXISTING ELECTRICAL SERVICE ENTRANCE PAST MANHOLE TO
BE ABANDONED. REMOVE CONDUCTORS AND FILL CONDUIT
FROM MANHOLE TO BUILDING.
2. PROVIDE NEMA-3R SERVICE-ENTRANCE RATED, 4-POLE,
AUTOMATIC TRANSFER SWITCH/GENERATOR DOCKING
STATION, REFER TO DETAIL FOR ADDITIONAL INFORMATION.
3. REMOVE EXISTING SERVICE CONDUCTORS AND CONDUIT
INSIDE BUILDING FEEDING ATS NORMAL POWER.
4. EXISTING MANHOLE IS POINT OF CONNECTING FOR NEW
CONDUIT FOR NEW ELECTRICAL SERVICE TO BUILDING.
5. CONNECT NEW CONDUCTORS FROM NEW ATS TO EXISTING
ATS.
6. PROVIDE NEW LSIG CIRCUIT BREAKER WITH EMRS INSIDE
NEMA-3R ENCLOSURE.
7. PROVIDE NEW SCHNEIDER ELECTRIC PM8000 TAB METER.
PROVIDE ALL WIRING AND INTEGRATION REQUIRED TO TIE INTO
THE EXISTING CVG SOFTWARE INFRASTRUCTURE. CT'S SHALL
BE INSTALLED IN THE ATS AND PIPED INTO THE METER
ENCLOSURE INSIDE. T1
TRANSFORMER
75 kVA
208Y/120V,3Φ,4W
WVL-1
225A MCB
PANEL
(3) #1 AWG CU AND
(1) #8 GND IN
1" C.
(4) #4/0 AWG CU AND
(1) #4 GND IN
2-1/2" C.
(3) SETS
(4) #500KCMIL AWG CU AND
(1) #4 GND IN
3-1/2" C.
PROJECT SCOPE
PROJECT SCOPE
ELECTRICAL SERVICE CALCULATIONS:
EXISTING DEMAND FROM UTILITY COMPANY 273.6 kW +25% PER NEC 220.87 342.0 kW LOAD REMOVED BY DEMOLITION -00.0 kW ADDITIONAL LOAD BY PROJECT 00.7 kW
CALCULATED LOAD 342.7 kW
412.2A @ 480V, 3PH
EXISTING 1200A SERVICE IS SUFFICIENT FOR PLANNED
RENOVATIONS.
33.4KAFC
M
1000A
33.1 KAFC
1000AT/
1200AF
4CU-1000A
4CU-1000A
4CU-1000A
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 Sycamore St. Suite 400
Cincinnati, OH 45202
T: 513.429.4404
C
U se rs \A ly ss a .M e h n e rt
\D o cu m e n ts
\O C V G
-0
M
E P R A ly ss a .M e h n e rt
Y J5
W H
.r v t
/3
/2
:4 :2
P
M
E-700
AM
JBM
W E S T V
A U
L T E
L E C T R
IC
A L I
M P R
O V E M
E N
T S
C V G
Y o u e ll
R o a d
H e b ro n
K Y
E L E C T R
IC
A L S
IN
G
L E L
IN
E
CONSTRUCTION
OCVG24-01
SCALE: NONE
CVG WEST VAULT ELECTRICAL SINGLE LINE
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.
TOTAL ESTIMATED DEMAND CURRENT: 2 A
TOTAL CONNECTED CURRENT: 2 A
REC 180 VA 100.00% 180 VA TOTAL ESTIMATED DEMAND: 680 VA
EQUIP 500 VA 100.00% 500 VA TOTAL CONNECTED LOAD: 680 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
4 A 0 A 2 A
0.5 kVA 0.0 kVA 0.2 kVA
(E) FIRE ALARM PANEL 20 1 41 0.0 0.0 42 1 20 (E) SPARE
(E) SECURITY SYSTEM 20 1 39 0.0 0.0 40 1 20 (E) SPARE
(E) VEEDER ROOT 20 1 37 0.0 0.0 38 1 20 (E) TO HVAC PANEL
(E) DAY TANK PUMP 20 1 35 0.0 0.0 36 1 20 (E) FAA FIBER EQUIPMENT
(E) GENERATOR BATTERY CHARGER 20 1 33 0.0 0.0 34 1 20 (E) EXISTING LOAD
(E) EXISTING LOAD 20 1 31 0.0 0.0 32 1 20 (E) RVR IN GEN ROOM
29 0.0 0.0 30 1 20 (E) RVR IN GEN ROOM
WATER HEATER 20 2
27 0.0 0.0 28
(E) SEWAGE PUMP RCPT 20 1 25 0.0 0.0 26
2 20 RESTROOM HEATER
23 0.0 0.0 24 1 20 (E) CAMERA POWER
(E) GENERATOR BLOCK HEATER 20 2
21 0.0 0.0 22 1 20 (E) HONEYWELL PANEL HVAC
MTS HEATER/CONTROLS 20 1 19 0.5 0.0 20 1 20 (E) REG ROOM VENT EF3
MTS SERVICE GFCI 20 1 17 0.2 0.0 18 1 20 (E) GEN ROOM VENT EF2
(E) NIGHT LIGHTS 20 1 15 0.0 0.0 16 1 20 (E) WORK ROOM VENT EF1
(E) EXT LIGHTS 20 1 13 0.0 0.0 14 1 20 (E) REG RM LIGHTS WEST
(E) GENERATOR ROOM LIGHTS 20 1 11 0.0 0.0 12 1 20 (E) REG RM LIGHTS EAST
(E) WORK ROOM BENCH LIGHTS 20 1 9 0.0 0.0 10 1 20 (E) RESTROOM RCPT
(E) WORK ROOM LIGHTS 20 1 7 0.0 0.0 8 1 20 (E) RESTROOM LIGHT FAN
(E) GENERATOR ROOM RCPT 20 1 5 0.0 0.0 6 1 20 (E) SOUTH RCPT WORKROOM
(E) WORK ROOM NORTH RCPT 20 1 3 0.0 0.0 4 1 20 (E) NORTHWEST RCPT REG ROOM FIBER...
(E) WORK ROOM NORTH RCPT 20 1 1 0.0 0.0 2 1 20 (E) SW RCPT REG ROOM RADIO
CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION
AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: T-WVL1
VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION:
PANEL: WVL-1 MAINS TYPE: 225A MLO PANEL INTERRUPTING RATING: EXISTING PANEL
PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING PANEL
REVISIONS
1 BID AND PERMIT 10.31.24
Wire Feeder Schedule
Type WireSize
4CU-1000A (3) SETS OF (4) #400 CU & #2/0 CU GND IN 3-1/2"C EACH
ELECTRICAL - LUMINAIRE SCHEDULE
TYPE DESCRIPTION BASIS OF DESIGN EQUAL MANUFACTURERS MOUNTING LAMPS / CCT
MINIMUM
LUMENS
MAXIMUM
WATTAGE VOLTAGE REMARKS
W1-EM EXTERIOR LED WALL PACK WITH BATTERY
BACKUP. WET LOCATION. INTEGRAL
PHOTOCELL. FINISH BY ARCHITECT.
ILP OWM 3L/5L U CCTS BLK PCU EMCT8 OR APPROVED EQUAL SURFACE
WALL
MATCH EXISTING 5231 LUMENS 40 120 MOUNT 10' AFF. PROVIDE UL924 DEVICE.
| Sheets |
| E-000 - ELECTRICAL LEGEND |
| E-100 - ELECTRICAL SITE UTILITY PLAN |
| E-101 - ELECTRICAL FLOOR PLANS |
| E-500 - ELECTRICAL DETAILS |
| E-700 - ELECTRICAL SINGLE LINE |