CVCC 260-B0260-042 (MR20023) Project Drawings 2026-02-13.pdf
PDF 2 MB Posted
- Attached to
- Replace Roof Bedford Hall at Central Virginia Community College, PC#260-B0260-042 (MR20023)
- Solicitation number
- DBB-114885
- Issued by
- Caroline County, Virginia
About this file
Replace Roof Bedford Hall Project – Architectural and Engineering Drawings
This is a project drawings package prepared by SFCS Inc. for the Virginia Community College System (VCCS) for the replacement of the roof at Bedford Hall, Central Virginia Community College (CVCC) located at 3506 Wards Road, Lynchburg, Virginia 24502. The project involves complete demolition of the existing roofing system (approximately 12,310 square feet of ballasted single-ply EPDM roof installed in 1994) and installation of a new fully adhered EPDM membrane roofing system with polyisocyanurate insulation. The scope includes removal of existing roof drains, curbs, skylights, and associated mechanical and electrical equipment; infill of abandoned roof openings; reinstallation of rooftop mechanical units on new curbs with elevated flashing (minimum 8 inches above new roof); reinstallation of the existing lightning protection system; and incidental mechanical, electrical, and plumbing work. The project also requires asbestos abatement, as ACM was identified in inspection reports included in the project specifications. The design complies with the 2021 Virginia Uniform Statewide Building Code (VUSBC), 2021 Virginia Energy Conservation Code (VECC), 2020 NFPA 70 National Electrical Code, and 2020 NFPA 780 Lightning Protection Standards. A pre-bid conference is scheduled for March 12, 2026, at 11:30 A.M. at the project site, with sealed bids due by 3:00 P.M. on April 1, 2026, and public bid opening on April 2, 2026.
Bidders must be registered vendors in eVA and must submit a Standard Commonwealth Bid Bond (form CO-10.2) and contract security regardless of bid amount. All pay applications and invoices must be processed through the owner's web-based e-Builder project management software. The drawings package, dated February 13, 2026, includes architectural sheets covering demolition plans, roof plans, and detailed sections; mechanical sheets detailing HVAC equipment relocation and ductwork requirements; and electrical sheets addressing roof-mounted receptacles, conduit removal and reinstallation, and new lightning protection system installation. Design wind speed is specified at 115 MPH with wind exposure category B. All hazardous materials encountered during work must be immediately reported to the architect and the owner, with the removal of hazardous materials being the owner's responsibility. The contractor shall verify field conditions and notify the architect in writing of any discrepancies between existing conditions and those shown on the drawings.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VCCS PROJECT CODE: CVCC 260-B0260-042 MR20023
DATE: FEBRUARY 13, 2026
COMM. NO. 20301.03
3506 WARDS ROAD, LYNCHBURG, VA 24502
T1
REPLACE ROOF BEDFORD HALL
VICINITY MAP LOCATION MAP
PROJECT
SITE
PROJECT
SITE
NORTH
NORTH
Architecture Engineering Planning InteriorsSF
C S.
co m
ROANOKE OFFICE (CORPORATE) CHARLOTTE OFFICE
305 SOUTH JEFFERSON STREET
ROANOKE, VA 24011-2003
800.873.2788
1927 SOUTH TRYON STREET, SUITE 207
CHARLOTTE, NC 28203
704.372.7327
LOUISVILLE OFFICE
2115 LEXINGTON ROAD, SUITE 100
LOUISVILLE, KY 40206
502.414.4545
PHILADELPHIA OFFICE
1777 SENTRY PARKWAY WEST
VEVA 17, SUITE 220
BLUE BELL, PA 19422
610.825.1288
DRAWING INDEX
COVER SHEET
T1 COVER SHEET
ARCHITECTURE
A0.0 PROJECT DATA, SYMBOLS AND ABBREVIATIONS
AD1.1 ROOF PLAN - DEMOLITION
A1.1 ROOF PLAN
A6.1 SECTIONS AND DETAILS
MECHANICAL
M1.1 ROOF PLAN - HVAC
ELECTRICAL
E0.0 ELECTRICAL SYMBOL LEGEND & ABBREVIATIONS
E1.1 ROOF PLAN - ELECTRICAL
PROJECT DESCRIPTION
DESIGN CRITERIA
PROJECT INFORMATION
THE EXISTING BEDFORD HALL WAS MOST RECENTLY REROOFED IN 1994. THE ROOF CONSISTS OF AN APPROXIMATELY 12,310 SF BALLASTED SINGLE-PLY EPDM ROOF OVER A BUILT-UP ASPHALT ROOF WITH GRAVEL OVER A SLOPED STEEL DECK. THE PROJECT INCLUDES DEMOLITION OF EXISTING ROOFING, INSULATION, DRAINS, AND OTHER MISCELLANEOUS ROOFTOP ELEMENTS AS INDICATED. ABANDONED ROOF OPENINGS WILL BE INFILLED AS PART OF THE WORK AND NEW ROOFING, INSULATION, DRAINS, CURBS, ROOF SPECIALTIES AND ACCESSORIES WILL BE PROVIDED AS PART OF THE WORK. AN EXISTING LIGHTNING PROTECTION SYSTEM WILL BE REMOVED AND REINSTALLED. WORK WILL REQUIRE INCIDENTAL
MECHANICAL AND ELECTRICAL WORK, AND ASBESTOS ABATEMENT.
2021 VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) PARTS I, II & III
2021 VIRGINIA CONSTRUCTION (VCC) (ADOPTS IBC 2021 WITH AMENDMENTS): VUSBC PART I
2021 VIRIGINA EXISTING BUILDING CODE (VEBC) (ADOPTS IEBC 2021 WITH AMENDMENTS): VUSBC PART II
2021 VIRGINIA PROPERTY MAINTENANCE CODE: VUSBC PART III
2021 VIRGINIA PLUMBING CODE (ADOPTS IPC 2021 WITH AMENDMENTS)
2021 VIRGINIA MECHANICAL CODE (ADOPTS IMC 2021 WITH AMENDMENTS)
2021 VIRGINIA ENERGY CONSERVATION CODE (VECC) (ADOPTS IECC 2021 WITH AMENDMENTS)
2020 NPFA 70, NATIONAL ELECTRICAL CODE (NEC)
2025 CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL 2025 (CPSM), REV 0 issued 03/17/25
ADA90-Title II (2010 ASAD Chapter 2 for Scoping, ICC A117.1-2017 Chapters 1 and 3 thru 11 for Technical Requirements).
BUILDING TYPE*: CLASSROOM / OFFICE SPACE / CAFE / LIBRARY
CONSTRUCTION TYPE*: 2B
USE GROUPS: NON-SEPARATED MIXED OCCUPANCY
A-3 ASSEMBLY
B - BUSINESS (EDUCATIONAL OCCUPANCY FOR
STUDENTS ABOVE THE 12TH GRADE)
ULTIMATE DESIGN WIND SPEED 115 MPH
WIND EXPOSURE CATEGORY EXPOSURE B
TOTAL ROOF AREA 12,310 SF
*INFORMATION TAKEN FROM CENTRAL VIRGINIA COMMUNITY COLLEGE BEDFORD HALL
RENOVATION EXISTING WORKING DRAWINGS DATED 2008.
ASBESTOS DISCLOSURE STATEMENT
LEAD MATERIALS DISCLOSURE STATEMENT
NO ASBESTOS CONTAINING MATERIALS SHALL BE USED ON THIS PROJECT.
AN ASBESTOS INSPECTION WAS PERFORMED AND ACM WAS FOUND GENERALLY IN THE AREA INDICATED.
THE ASBESTOS INSPECTION REPORT IS INCLUDED AS AN APPENDIX TO THE PROJECT SPECIFICATIONS.
ASBESTOS-CONTAINING BUILDING MATERIALS SHALL NOT BE DISTURBED IN THIS WORK EXCEPT WHERE SPECIFICALLY INDICATED AND REQUIRED. WHERE SUCH ACTIONS ARE REQUIRED, THE CONTRACTOR SHALL HAVE THE ACM REMOVED BY A LICENSED ASBESTOS CONTRACTOR USING APPROVED PROCEDURES AS SPECIFIED.
THE WORK REQUIRED FOR ASBESTOS ABATEMENT IS PERMITTED WITHIN THE OVERALL BUILDING PERMIT ISSUED. THE ACM THAT IS TO REMAIN AND THE NEW NON-ASBESTOS CONTAINING MATERIAL SHALL BE LABELED ACCORDINGLY. THE ASBESTOS ABATEMENT CONTRACTOR SHALL MARK UP THE RECORD DRAWINGS RESULTING FROM ITS WORK TO INCLUDE AREAS WHERE ASBESTOS WAS ABATED, AREAS WHERE ASBESTOS WAS ENCAPSULATED, AND AREAS WHERE ACM EXIST BUT WERE LEFT IN PLACE. THE GENERAL CONTRACTOR
SHALL REVIEW AND CERTIFY THE LOCATIONS WHERE ACM WAS ABATED, AREAS WHERE ACM WAS
ENCAPSULATED, AND AREAS WHERE ACM WAS LEFT IN PLACE AS MARKED ON THE RECORD DRAWINGS AND
WILL PROVIDE THE DRAWINGS TO THE ARCHITECT.
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS BEEN CONDUCTED AND CAN BE FOUND IN THE PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE CONTRACTOR'S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING ALL LOCAL, STATE, AND FEDERAL REQUIREMENTS FOR THE PROTECTION OF HIS PERSONNEL AND THE ENVIRONMENT DURING RENOVATION/DEMOLITION ACTIVITIES.
TESTING OF DEMOLITION DEBRIS (TCLP'S) TO DETERMINE ITS DISPOSITION AS HAZARDOUS WASTE AND ITS PROPER DISPOSAL IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. RESULTS OF SUCH TESTS AND WASTE MANIFESTS SHALL BE PROVIDED TO THE OWNER AT COMPLETION OF THE PROJECT. IF METAL DEMOLITION COMPONENTS ARE RECYCLED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFICATION TO THE RECYCLER
THAT THE COMPONENTS UTILIZE LEAD BASED PAINT.
HIGH PERFORMANCE BUILDINGS ACT
IN ACCORDANCE WITH THE HIGH PERFORMANCE BUILDINGS ACT, THE BUILDING IS EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE RENOVATIONS DOES NOT EXCEED 50% OF THE VALUE OF THE BUILDING.
VIRGINIA ENERGY CONSERVATION CODE
IN ACCORDANCE WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL COMPLY
WITH VECC SECTIONS C402 THROUGHH C405 AND C408.
POINTS OF CONTACT
Paul Shope, RA, VCCO, LEED BD-C (804) 819-4914 pshope@vccs.edu
John Rocha Jr. FACILITIES MANAGER CVCC (540) 529-0563 rochaj@centralvirginia.edu
02/13/2026 02/13/2026
Chios Walker
PLAN NORTH
Equipment Not In Contract
Equipment Number
Matchline
Center Line
Plan Spot Elevation
Glass Type
Window Type
Storefront Type
Revision Number
Toilet Accessories
Partition Information
Door Information
Room Information
North Symbol
Column Grid Line
Plan Note
Plan Detail Reference
Enlarged Plan Reference
Plan & Vertical Section Reference
Section Detail Reference
ARCHITECTURAL SHEET NUMBERING SERIES
ARCHITECTURAL ABBREVIATIONS ARCHITECTURAL SYMBOLS ARCHITECTURAL SYMBOLS
ARCHITECTURAL DEMOLITION
FLOOR PLANS, ROOF PLAN
REFLECTED CEILING PLANS
A8.
A9.
A6.
A7.
A4.
A5.
A3.
AD1.
A1.
A2.
WALL SECTIONS,
INTERIOR DETAILS,
VERTICAL CIRCULATION
SPECIAL CONSTRUCTION
AND EXTERIOR DETAILS
ELEVATIONS, SECTIONS
ENLARGED PLANS
SCHEDULES
EXTERIOR ELEVATIONS,
BUILDING SECTIONS
A0. GENERAL INFORMATION,
FIRE PROTECTION PLANS
SF2
A
UNLESS NOTED OTHERWISE
VEST
W/O
WHL CHR
W/
TRN
TYP
UNO
TOW
TLT
TOJ
TOM
TOS
VESTIBULE
WHEELCHAIR
WITHOUT
WITH
TOP OF JOIST
TOP OF MASONRY
TOP OF STEEL
TOP OF WALL
TRAINING
TYPICAL
TOILET
RECPT
SPEC
STOR
STRUCT
RM
RO
SHT
SCHED
PT
R
RE
OC
OD
RECEPTION
SCHEDULED
STRUCTURAL
ROUGH OPENING
SPECIFICATION
STORAGE
ROOM
SHEET
ON CENTER
OUTSIDE DIAMETER
PRESSURE TREATED
RADIUS
REFER
CONCRETE MASONRY UNIT
FIRE RETARDANT TREATED
LP
NA
NIC
MO
NTS
MACH
MAINT
MECH
ISOL
J.C.
LOC
HR
IL
INT
ID
LOW POINT
MECHANICAL
MAINTENANCE
MASONRY OPENING
NOT APPLICABLE
NOT IN CONTRACT
NOT TO SCALE
MACHINE
ISOLATION
INSIDE DIAMETER
INDEPENDENT LIVING
LIMITS OF CONSTRUCTION
JANITOR CLOSET
HOUR
INTERIOR
EXIST
GWB
GALV
HP
EXT
FL
FRT
ELEC
ELEV
EQ
EQUIP
EL
DIA
EJ
EB
EXISTING
EXTERIOR
GALVANIZED
GYPSUM WALL BOARD
HIGH POINT
FLOOR
DIAMETER
ELECTRICAL
ELEVATOR
EQUIPMENT
ELEVATION
EXPANSION JOINT
EXPANSION BOLT
EQUAL
CONC
CW
CONF
CONT
CONTR
CI
CMU
CJ
ARCH
BLDG
BR
AB
ALT
AFF
ADD
CAST IRON
CONCRETE
CASEWORK
CONFERENCE
CONTINUOUS
CONTRACTOR
CONTROL JOINT
ADDENDUM
ALTERNATE
BEDROOM
ABOVE FINISH FLOOR
ARCHITECTURAL
ANCHOR BOLT
BUILDING
FEC FIRE EXTINGUISHER CABINET
FIBERGLASS REINFORCED POLYESTERFRP
OH OPPOSITE HAND
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
EPS EXTRUDED POLYSTYRENE
SA SELF-ADHERING
EWC ELECTRIC WATER COOLER
F FILLER
CORR CORRIDOR
SIM SIMILAR
HORZ HORIZONTAL
DEFS DIRECT APPLIED EXTERIOR FINISH SYSTEM
CR CHAIR RAIL
CG CORNER GUARD
HR HANDRAIL
DWG DRAWING
RES RESIDENT
VIF VERIFY IN FIELD
MTD MOUNTED
WRB WEATHER RESISTANT BARRIER
Curtain Wall TypeCW2
Elevation: Multiple Elevation
COLUMN NUMBER
PARTITION TYPE
FIRE RATING
(IF APPLICABLE)
INDICATES ACOUSTIC
INSULATION
(IF APPLICABLE)
XX
OPENING NUMBER
RE: SPECIFICATIONS
FOR HARDWARE SET
DOOR MARK
(IF DIFFERENT FROM
OPENING NUMBER)
ROOM NAME
ROOM NUMBER
INDICATES
DIRECTION
OF CUT
SECTION
NUMBER
SHEET NUMBER DRAWN
INDICATES
DIRECTION
OF CUT
DETAIL
NUMBER
DETAIL NUMBER
DETAIL NUMBER
DETAIL NUMBER
SHEET NUMBER
DRAWN
"CW" PREFIX
GLASS TYPE
NUMBER
"SF" PREFIX
N.I.C.
NOTE: THESE ARE STANDARD SYMBOLS AND ALL SYMBOLS
NOTED ON THIS SHEET MAY NOT APPLY.
NOTE: THESE ARE STANDARD SHEET SERIES NUMBERS AND
ALL SHEET SERIES NOTED ON THIS SHEET MAY NOT APPLY.
89.2
CL
Room name
SIM
A6.1A1.1
SIM
A6.1A1.1
SIM
A6.1A1.1
A6.1A1.1
A6.1A1.1
WINDOW TYPE
A101
112 3
MATCHLINE A
RE: A101
S A1
Wood Blocking
Sand, Cement, Grout
Gypsum Wall Board
Glass
Plywood
Batt Insulation
Rigid Insulation
Finish Wood
Concrete Masonry Units
Steel
Brick
Cast-in-place Concrete
Porous Fill (Stone Or Gravel)
Earth
New Construction
Dimension Line
Building Elevation
Limits Of Construction
1'-2" 6' - 0" FINISH FACE
OF PARTITION
NOTE: THESE ARE STANDARD SYMBOLS AND ALL SYMBOLS
NOTED ON THIS SHEET MAY NOT APPLY.
Name
Elevation
L.O.C.
-RFI 004
Supplemental Drawing Reference Number
T20 "T" PREFIX
SHEET NUMBER TAKEN
SHEET NUMBER DRAWN
SHEET NUMBER TAKEN
SHEET NUMBER DRAWN
SHEET NUMBER TAKEN
SHEET NUMBER DRAWN
SHEET NUMBER TAKEN
Architecture Engineering Planning Interiors
SFCS Inc. 305 South Jefferson Street Roanoke, Virginia 24011.2003
540.344.6664 Fax 540.343.6925
www.sfcs.com
:PROJECT ENGINEER
OF
DRAWING
COMM. NO.
SHEET
DATE
REVISION DESCRIPTION
DRAWING TITLE
APPROVED BY
CHECKED BY
NO.
DRAWN BY
DATE
PROJECT ARCHITECT
PROJECT DESIGNER
PROJECT TITLE
FEBRUARY 13, 2026
REPLACE ROOF
BEDFORD HALL
JBW
20301.03
PROJECT CODE: CVCC 260-B0260-042 MR20023
2/13/2026
10:05:56 AM
Autodesk Docs://20301.03 - VCCS - Re-Roof Bedford Hall Building at DCC (2025)/20301.03- VCCS- RE-ROOF BEDFORD HALL BUILDING CVCC- ARCH.rvt
JBW
JAW
PROJECT DATA,
SYMBOLS AND
ABBREVIATIONS
A0.0
1. BEFORE WORK HAS BEGUN, CONTRACTORS SHALL MAKE A THOROUGH SURVEY OF THE BUILDING AND NOTIFY THE OWNER IN WRITING OF ALL DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THOSE SHOWN ON THE DRAWINGS. FAILURE BY THE CONTRACTOR TO HAVE ACQUAINTED HIMSELF WITH AVAILABLE INFORMATION CONCERNING EXISTING CONDITIONS SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITIES OF PERFORMANCE OF WORK IN ACCORDANCE WITH REQUIREMENTS OF THE CONTRACT DOCUMENTS.
2. THESE DRAWINGS HAVE BEEN DEVELOPED FROM EXISTING DRAWINGS AND MAY NOT REFLECT ACTUAL FIELD CONDITIONS. THE CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND NOTIFY THE ARCHITECT IN WRITING OF ANY WORK DESCRIBED IN THE CONTRACT
DOCUMENTS WHICH CANNOT BE PERFORMED DUE TO EXISTING CONDITIONS.
3. PROTECT FROM DAMAGE ALL MATERIALS TO REMAIN.
4. DEMOLITION WORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THOSE ITEMS NOTED. OTHER ITEMS OF A MINOR NATURE WHICH MAY EXIST BUT ARE NOT SPECIFICALLY NOTED ON THE DRAWINGS ARE TO BE REMOVED AS REQUIRED, TO PROVIDE ACCESS AND ALLOW
ALTERATION OR NEW WORK TO PROCEED.
5. NOT ALL MECHANICAL, ELECTRICAL AND PLUMBING, EQUIPMENT WHICH IS REQUIRED TO BE REMOVED IS SHOWN. CONTRACTOR SHALL REMOVE ALL SUCH EQUIPMENT WHICH WILL INTERFERE WITH NEW CONSTRUCTION. EQUIPMENT WHICH WILL NO LONGER BE USED (EG.
PIPES, CONDUITS AND DUCTS) SHALL BE REMOVED COMPLETELY BACK TO THE POINT OF SERVICE AND CAPPED OR PLUGGED. ALSO SEE
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION NOTES.
6. IF ANY HAZARDOUS MATERIALS ARE ENCOUNTERED BY THE GENERAL CONTRACTOR, INCLUDING BUT NOT LIMITED TO MATERIALS CONTAINING ASBESTOS, LEAD PAINT, ETC., WORK IS TO BE STOPPED AND THE ARCHITECT IMMEDIATELY NOTIFIED.
7. AREAS NOT SCHEDULED FOR DEMOLITION WHICH BECOME DAMAGED SHALL BE REPAIRED TO MATCH ADJACENT SURFACE THICKNESS, FINISH AND TEXTURE.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL SHORING AND BRACING NECESSARY TO PROTECT EXISTING CONSTRUCTION TO REMAIN. CONTRACTOR SHALL PROVIDE SUITABLE SHORING AND BRACING AS REQUIRED TO SUPPORT LOADS IMPOSED OR RESULTING
FROM DEMOLITION WORK.
GENERAL DEMOLITION NOTES
Architecture Engineering Planning Interiors
SFCS Inc. 305 South Jefferson Street Roanoke, Virginia 24011.2003
540.344.6664 Fax 540.343.6925
www.sfcs.com
:PROJECT ENGINEER
OF
DRAWING
COMM. NO.
SHEET
DATE
REVISION DESCRIPTION
DRAWING TITLE
APPROVED BY
CHECKED BY
NO.
DRAWN BY
DATE
PROJECT ARCHITECT
PROJECT DESIGNER
PROJECT TITLE
FEBRUARY 13, 2026
REPLACE ROOF
BEDFORD HALL
DEMOLITION NOTES
JBW
20301.03
PROJECT CODE: CVCC 260-B0260-042 MR20023
2/13/2026
10:05:56 AM
Autodesk Docs://20301.03 - VCCS - Re-Roof Bedford Hall Building at DCC (2025)/20301.03- VCCS- RE-ROOF BEDFORD HALL BUILDING CVCC- ARCH.rvt
JBW
JAW
ROOF PLAN -
DEMOLITION
AD1.1
1/8" = 1'-0"AD1.1
ROOF PLAN - DEMOLITION1
8 DISCONNECT AND PROTECT EXISTING ROOF TOP MECHANICAL UNIT
AS REQUIRED IN PREPARATION TO RAISE AND PLACE ON NEW
CURB, RE: MECHANICAL DWGS.
11 REMOVE AND DISPOSE OF EXISTING SUPPORT FOR PREVIOUSLY
REMOVED ROOF TOP MECHANICAL UNIT.
10 REMOVE EXISTING SKYLIGHT IN PREPARATION FOR INFILL
CONSTRUCTION, RE: ROOF PLAN.
12 REMOVE AND DISPOSE OF EXISTING WALK PAD.
1 REMOVE EXISTING ROOFING SYSTEM IN PREPARATION FOR
INSTALLATION OF NEW ROOFING AND INSULATION, RE: ROOF PLAN.
EXISTING ROOFING SYSTEM CONSISTS OF BALLASTED SINGLE-PLY
EPDM ON 1.5" ISOBOARD ON BUR WITH GRAVEL ON 2" PERLITE ON
ASPHALTIC VAPOR BARRIER ON SLOPED STEEL DECK. STEEL DECK
TO REMAIN.
5 REMOVE AND PROTECT EXISTING ROOF HATCH IN PREPARATION
FOR REINSTALLATION ON NEW CURB, RE: ROOF PLAN.
2 REMOVE EXISTING ROOF DRAIN IN ITS ENTIRETY INCLUDING
FLASHING, CLAMPING RINGS, DRAIN BOLTS, AND DOMES IN
PREPARATION FOR INSTALLATION OF NEW ROOF DRAIN, RE: ROOF
PLAN.
6 EXISTING CHIMNEY TO REMAIN.
7 EXISTING VENT PIPE TO REMAIN.
3 REMOVE EXISTING OVERFLOW SCUPPER IN PREPARATION FOR
INSTALLATION OF NEW OVERFLOW SCUPPER IN SAME LOCATION,
RE: ROOF PLAN.
9 REMOVE EXISTING METAL COPING AT PARAPET IN PREPARATION
FOR INSTALLATION OF NEW METAL COPING, RE: ROOF PLAN.
4 REMOVE AND PROTECT EXISTING FAN IN PREPARATION FOR
REINSTALLATION ON NEW CURB, RE: ROOF PLAN.
1.
2.
3.
REMOVE AND DISPOSE OF EXISTING ROOF CURBS INCLUDED
ASSOCIATED MEMBRANE FLASHING AT ALL MECHANICAL
EQUIPMENT SCHEDULED FOR REMOVAL.
REMOVE AND DISPOSE OF EXISTING ROOF SLEEVES INCLUDING
ASSOCIATED MEMBRANE FLASHING AT MECHANICAL DUCT AND
PIPE PENETRATIONS.
IT IS THE INTENT THAT ALL ROOF MOUNTED EQUIPMENT BE RAISED
AND PROVIDED WITH NEW CURB AS REQ'D TO ACHEIVE A MINIMUM 8"
HIGH FLASHING CONDITION AS INDICATED ON DRAWINGS. MECHANICAL
AND ELECTRICAL DEVICES SHALL BE DISCONNECTED & RECONNECTED
TO ACCOMMODATE NEW MOUNTING CONDITION, INCLUDING
DUCTWORK & ELECTRICAL EXTENSIONS & ANY REQ'D PLUMBING VENT
ADJUSTMENTS.
0' 4' 8' 16'
SCALE : 1/8" = 1'-0"
13 SELECTIVELY REMOVE METAL DECK @ STRUCTURE FOR
GUARDRAIL ATTACHMENT, COORDINATE W/ NEW WORK
GENERAL NOTES
RIDGE = +5.7"
LP = +5.7"
LP = +5.7"
LP = +5.7"
LP = +5.7"
LP = +5.7"
LP = +5.7"
114' - 0" VIF
8'
- 0 " V
IF
8'
- 0 " V
IF
6'
- 0 " V
IF
30' - 0" VIF 54' - 0" VIF 30' - 0" VIF
114' - 0" VIF
10 10
A6.1
A6.1
A6.14
A6.1
A6.1
A6.1
A6.18
A6.18
A6.18
A6.18
A6.1 8
A6.1 8
A6.1 8
A6.1 8
A6.1
10' - 0"
HP = +7.8"HP = +7.8"
HP = +13.2"
HP = +13.6"
HP = +13.2
HP = +7.8"
HP = +13.6"
0"
HP = +8.36" HP = +8.36"
LP = +5.7"
LP = +5.7"
LP = +5.7"
LP = +5.7"
A6.1
8' - 0"
VIF
9' - 9 1/2"
CENTER PEDESTAL ON
STL JOIST BELOW (TYP)
CENTER PEDESTAL ON
STL JOIST BELOW (TYP)
VIF
5' - 3 1/2"
3' - 9"
OFFSET PEDESTAL 1" FROM
OF W14 BEAM BELOW
3'
- 9
VI
F 4'
- 1
VI
F
2'
- 0
1' - 6"
45.00°
VI
F
4'
- 1
1 1 /2"
VI
F
4'
- 1
1'
- 1
CENTER PEDESTAL ON
STL JOIST BELOW (TYP)
TYP.
30.00°
8'
- 9
2' - 0"
8'
- 9
2' - 0"
Architecture Engineering Planning Interiors
SFCS Inc. 305 South Jefferson Street Roanoke, Virginia 24011.2003
540.344.6664 Fax 540.343.6925
www.sfcs.com
:PROJECT ENGINEER
OF
DRAWING
COMM. NO.
SHEET
DATE
REVISION DESCRIPTION
DRAWING TITLE
APPROVED BY
CHECKED BY
NO.
DRAWN BY
DATE
PROJECT ARCHITECT
PROJECT DESIGNER
PROJECT TITLE
FEBRUARY 13, 2026
REPLACE ROOF
BEDFORD HALL
PLAN NOTES
GENERAL NOTES
JBW
20301.03
PROJECT CODE: CVCC 260-B0260-042 MR20023
2/13/2026
10:05:56 AM
Autodesk Docs://20301.03 - VCCS - Re-Roof Bedford Hall Building at DCC (2025)/20301.03- VCCS- RE-ROOF BEDFORD HALL BUILDING CVCC- ARCH.rvt
JBW
JAW/JDK
ROOF PLAN
A1.1
1/8" = 1'-0"A1.1
ROOF PLAN1
2 PROVIDE 4" ROOF DRAIN PER SPECIFICATIONS AT EXISTING LEADER
LOCATION. L.P. = +5.7"
8 RAISE EXISTING ROOF TOP MECHANICAL UNIT AND PLACE ON NEW
CURB, RE: 3A6.1 AND MECHANICAL DRAWINGS.
9 PROVIDE METAL COPING AT PARAPET, RE: 1A6.1.
4 REINSTALL EXISTING FAN ON NEW CURB, RE: 3A6.1. PROVIDE
GUARDRAIL SYSTEM ATTACHED TO BUILDING STRUCTURE AT ALL
LOCATIONS WITHIN 10' OF ROOF EDGE.
6 EXISTING CHIMNEY TO REMAIN. PROVIDE SURFACE MOUNTED
FLASHING PER 7A6.1.
5 REINSTALL EXISTING ROOF HATCH ON NEW CURB, RE: 3A6.1.
PROVIDE HATCH MANUFACTURERS STANDARD SAFETY RAILING
SYSTEM MOUNTED TO HATCH WITH SELF LATCHING GATE. INSTALL
SELF-LATCHING LADDER SAFETY POST. EQUIPMENT & INSTALLATION
SHALL BE IN COMPLIANCE WITH 29 CFR 1910.23.
7 EXISTING VENT PIPE TO REMAIN, RE: 6A6.1.
1.
2.
3.
4.
5.
EXISTING ROOF STRUCTURE IS SLOPED 1/4" PER FOOT FROM CENTER
RIDGE TOWARD ROOF DRAINS AS INDICATED ON ROOF PLAN.
CONTRACTOR TO TEST FOR PONDING WATER AND MAKE
ADJUSTMENTS PER MANUFACTURER'S RECOMMENDATIONS.
LP: LOW POINT DIM = TOP OF INSUL COVER BOARD ABOVE MTL DECK.
HP: HIGH POINT DIM = TOP OF INSUL COVER BOARD ABOVE MTL DECK.
PROVIDE 2 LAYERS OF 2.6" MIN. POLYISOCYANURATE INSULATION
THICKNESS, JOINTS STAGGERED BOTH DIRECTIONS, WITH 1/2" HD
POLYISO COVER BOARD FOR TOTAL LP THICKNESS OF 5.7".
INSULATION THICKNESS GIVEN ASSUMES R-5.7 PER 1" THICKNESS.
CONTRACTOR SHALL ADJUST INSULATION THICKNESS AS REQ'D
BASED ON MINIMUM R-30 REQUIRED AT LOW POINT.
ROOF DRAIN LOCATIONS INDICATED ARE BASED UPON EXISTING
DRAWINGS. CONTRACTOR SHALL VERIFY ACTUAL LOCATIONS PRIOR
TO SHOP DRAWING PREPARATION.
1 PROVIDE NEW FULLY ADHERED EPDM MEMBRANE ROOFING ON
POLYISOCYANURATE INSULATION PER SPECIFICATIONS. SEE
GENERAL NOTES THIS SHEET AND DETAILS ON SHEET A6.1.
3 EXISTING SCUPPER, RE: 8A6.1.
0' 4' 8' 16'
SCALE : 1/8" = 1'-0"
10 PROVIDE CRICKETS SLOPED IN DIRECTION INDICATED ON PLAN,
INSULATION TAPERED @ 1/2" PER FOOT. MIN. THICKNESS IS 1/2"
11 PROVIDE WALKWAY PADS PER SPECIFICATIONS.
GENERAL NOTES
12 INFILL EXISTING SKYLIGHT OPENING
13 INSTALL PERMANENT SAFETY GUARDRAIL AS SPECIFIED, MOUNTED
TO ROOF STRUCTURE, SEE 12/A6.1. VERIFY BOLT LOCATIONS ARE
CLEAR OF PANEL POINTS ON BAR JOISTS.
N
14 OVERFLOW CHANNEL THRU TAPERED INSULATION. SEE 9/A6.1
MI
N8"
PREFABRICATED METAL CURB
2X WOOD NAILER
COUNTER FLASHING
INSULATION
2X WOOD NAILERS
MEMBRANE FLASHING ON
FLASHING CEMENT
FULLY ADHERED MEMBRANE
ROOFING SYSTEM
1/2" COVER BOARD ON RIGID
INSULATION ON EXIST DECK
TOP OF DECK
TOP OF COVER BOARD
CANT STRIP
FULLY ADHERED MEMBRANE
ROOFING SYSTEM
MEMBRANE FLASHING
STRAINER
1/2" HD COVER BOARD ON RIGID
POLYISO INSUL.
DECK CLAMP
EXIST TOP OF MASONRY - VIF
EXIST TOP OF DECK - VIF
H.P. BEYOND = +5.7"
PREFABRICATED,PREFIN. METAL
COPING w/ CONCEALED SPLICE
PLATES ON PT 2X WOOD NAILER
WRAP EPDM ROOFING MEMBRANE
UP PARAPET & OVER PT WD NAILER
EXISTING SLOPED STRUCTURE
EXISTING METAL DECK
NEW 4" ROOF DRAIN AS SPEC'D
EXISTING ROOF LEADER
3' - 0" VIF
12" 1/4"
7 1 /4"
EXISTING MASONRY WALL
H. P. OF CRICKET BEYOND
CANT STRIP CONTIN.
EXISTING PLUMBING VENT
STACK
MEMBRANE FLASHING ON
FLASHING CEMENT
FULLY ADHERED MEMBRANE
ROOFING SYSTEM
1/2" COVER BOARD ON
RIGID INSULATION
LEAD FLASHING
ROLL LEAD FLASHING
APPROX. 1" INTO PIPE
TOP OF DECK
TOP OF COVER BOARD
NOTE:
THE TOP OF VENT ABOVE THE ROOF MEMBRANE SHALL BE EQUAL TO:
THE BALANCED SNOW LOAD PER ASCE 7, CH. 7, PLUS 4",
OR THE MIN. HEIGHT PRESCRIBED BY THE ROOFING MANUF., PLUS 4",
OR TWELVE (12) INCHES, WHICHEVER IS GREATEST.
8" M
IN
TOP OF DECK
1/2" COVER BOARD ON
RIGID INSULATION ON
EXISTING DECK
FULLY ADHERED MEMBRANE ROOFING SYSTEM
MEMBRANE BASE FLASHING
2X WOOD NAILER
2X CANT STRIP ATTACHED TO CURB
COUNTERFLASHING
FLASHING RECEIVER
SHEET METAL ENCLOSURE
TOP OF COVER BOARD
5.7
" M
AX
8"
M
IN
EXISTING MASONRY CHIMNEY
FULLY ADHERED MEMBRANE ROOFING
SYSTEM
MEMBRANE FLASHING ON FLASHING
CEMENT
METAL COUNTER FLASHING
METAL REGLET
SEALANT
1/2" COVER BOARD ON RIGID
INSULATION ON EXISTING DECK
TOP OF DECK
TOP OF COVER BOARD
CANT STRIP
EXIST TOP OF MASONRY
EXIST TOP OF DECK = +0"
A6.1
EXISTING STRUCTURE
EXISTING MASONRY
WALL
FULLY ADHERED MEMBRANE
ROOFING ON 1/2" COVER
BOARD ON RIGID INSULATION
H.P. = +5.7"
EXIST TOP OF MASONRY
EXIST TOP OF DECK
H.P. = +5.7"
FULLY ADHERED EPDM
MEMBRANE ROOFING
ON 1/2" HD POLYISO
COVER BOARD ON
RIGID POLYISO INSUL.
EXISTING BLOCKING
EXISTING NAILER
EXISTING MASONRY
PT 2X WD NAILER
PREFABRICATED, PREFIN.
METAL COPING WITH
CONCEALED SPLICE PLATES
GALV METAL
ANCHOR CLIP, TYPICAL
3"
CANT STRIP CONTIN.
WRAP EPDM ROOFING
MEMBRANE UP PARAPET
& OVER PT WD NAILER
2.6
2.6
1/2
4"
EXIST TOP OF MASONRY - VIF
EXIST TOP OF DECK - VIF
EXISTING SLOPED STRUCTURE
EXISTING MASONRY
WALL
FULLY ADHERED MEMBRANE
ROOFING ON 1/2" HD POLYISO
COVER BD ON POLYISO INSUL.
H.P. BEYOND = +5.7"
EXIST BOTTOM OF
SCUPPER OPENING - VIF
PREFABRICATED, PREFIN.
.050" ALUM THRU-WALL
SCUPPER - SIZE TO FIT EXIST
OPENING
SLOPE TO EXISTING
SCUPPER AS REQ'D
LINE OF ROOF BEYOND
EXISTING METAL DECK
PREFABRICATED, PREFIN.
METAL COPING w/
CONCEALED SPLICE
PLATES ON PT 2X WOOD
NAILER
WRAP EPDM ROOFING MEMBRANE
UP PARAPET & OVER PT WD NAILER
4"
12"5/16"
OVERFLOW CHANNEL, CREST INSUL. @ 2"
ABOVE ROOF DRAIN INLET ELEVATION
5.2
12" 1/4"
CANT STRIP BEYOND
EXISTING MASONRY
WALL
PREFABRICATED,
PREFINISHED THRU-WALL
.050" ALUM SCUPPER -
SIZE TO FIT EXIST OPENING
PREFABRICATED,
PREFINISHED METAL COPING
COVER ON PT 2X WOOD NAILER
EXIST TOP OF MASONRY - VIF
EXIST BOTTOM OF
SCUPPER OPENING - VIF
A6.1
4" M
IN
EXISTING TOP OF STRUCTURE
FULLY ADHERED EPDM MEMBRANE ROOFING
EXISTING STRUCTURE SLOPED 1/4" PER 1'-0"
EXISTING METAL DECK
2 LAYERS OF 2.6" POLISOCYANURATE
INSUL., JOINTS STAGGERED, R - 30
1/2" HD POLYISO COVER BOARD
EXISTING TOP OF DECK = +0"
+5.7"
EXISTING TOP OF STRUCTURE
FULLY ADHERED MEMBRANE ROOFING
EXISTING STRUCTURE
SLOPED 1/4" PER 1'-0"
EXISTING NARROW RIB METAL DECK
2" NOM. WELDED PIPE PEDESTAL w 3" x 6" x 3/8"
MOUNTING PLATES, BOTTOM PLATE TO MATCH
JOIST SLOPE (1/4" : 12"). HOT DIP GALVANIZED
AFTER FAB. COORD. WITH GUARDRAIL LAYOUT &
APPROVED SHOP DWGS.
1/2" HD POLYISO COVER BD ON 2 LAYERS
OF 2.6" POLYISOCYANURATE INSUL.
ATTACH PEDESTAL TO STEEL JOISTS WITH BOLTS
THRU GAP BETWEEN TOP CHORD MEMBERS.
LENGTHEN PLATE TO STRADDLE PANEL POINT IF
NECESSARY DUE TO CONFLICT.
DO NOT CAUSE DAMAGE TO JOISTS.
EPDM MEMBRANE FLASHING ON
FLASHING CEMENT WITH SS CLAMPING
COLLAR, SEALANT AT ALL EDGES
4" M
IN
CAST ALUM. POST FLANGE BOLTED TO
GALVANIZED PIPE PEDESTAL
EXISTING METAL DECK = +0"
1 1/2"
FIELD VERIFY AT CRICKET
+5.7"
1 1/2" SQ x 1/4" PLATE WASHER TYP.
1/2" DIAM. BOLTS WITH NUT, LOCK & FLAT WASHERS
(3/8" DIAM. BOLTS AT SMALL JOIST @ ROOF HATCH.)
91.
19°
1.9" OD ALUMINUM PIPE
NOTE:
TOP OF GUARDRAIL TO BE 42" ABOVE ROOF WALKING
SURFACE. MID RAIL TO BE CENTERED BETWEEN ROOF
SURFACE AND TOP RAIL. 1/16" NYLON OR TEFLON SPACER TO PREVENT
GALVANIC CORROSION, TYPICAL
FULLY ADHERED MEMBRANE ROOFING ON
1/2" HD POLYISO COVER BOARD
EXISTING STRUCTURE
SLOPED 1/4" PER 12"
EXISTING
METAL DECK
2 LAYERS OF 2.6" POLYISOCYANURATE
INSUL., JOINTS STAGGERED, R-30
METAL DECK - MATCH
EXISTING SIZE AND GAUGE
3' - 0" INFILL OPENING
NEW L2x2x1/4 ALL
FOUR SIDES OF
EXISTING
OPENING, TYP.
EXISTING STEEL
ANGLE AROUND
OPENING
PERIMETER, TYP.
1/8 1-12
Architecture Engineering Planning Interiors
SFCS Inc. 305 South Jefferson Street Roanoke, Virginia 24011.2003
540.344.6664 Fax 540.343.6925
www.sfcs.com
:PROJECT ENGINEER
OF
DRAWING
COMM. NO.
SHEET
DATE
REVISION DESCRIPTION
DRAWING TITLE
APPROVED BY
CHECKED BY
NO.
DRAWN BY
DATE
PROJECT ARCHITECT
PROJECT DESIGNER
PROJECT TITLE
FEBRUARY 13, 2026
REPLACE ROOF
BEDFORD HALL
JBW
20301.03
PROJECT CODE: CVCC 260-B0260-042 MR20023
2/13/2026
10:05:56 AM
Autodesk Docs://20301.03 - VCCS - Re-Roof Bedford Hall Building at DCC (2025)/20301.03- VCCS- RE-ROOF BEDFORD HALL BUILDING CVCC- ARCH.rvt
JBW
JAW
SECTIONS AND
DETAILS
A6.1
1 1/2" = 1'-0"A1.1 A6.1
3 PREFABRICATED CURB
1 1/2" = 1'-0"A1.1 A6.1
4 SECTION AT ROOF DRAIN
1 1/2" = 1'-0"A1.1 A6.1
6 SECT. @ TYP. PLUMBING VENT
1 1/2" = 1'-0"A6.1
5 SECTION @ TYP. DOGHOUSE
1 1/2" = 1'-0"A1.1 A6.1
7 SURFACE MOUNTED FLASHING
1 1/2" = 1'-0"A1.1 A6.1
1 SECT. AT TYP. PARAPET
3" = 1'-0"A6.1 A6.1
2 TYPICAL PARAPET
1 1/2" = 1'-0"A6.1 A6.1
9 SECT. @ OVERFLOW SCUPPER
1 1/2" = 1'-0"A1.1 A6.1
8 TYPICAL SCUPPER ELEVATION
3" = 1'-0"A6.1
10 ROOF ASSEMBLY DETAIL TYP.
3" = 1'-0"A6.1
SECT. @ GUARDRAIL
ATTACHMENT
1 1/2" = 1'-0"A1.1 A6.1
11 SECTION AT SKYLIGHT INFILL
ROOF TO BE RAISED FROM CURRENT ROOF HEIGHT.
REMOVE AND REINSTALL EXISTING ROOFTOP UNIT AT NEW
ROOF HEIGHT WITH NEW CURB. NEW CURB TO BE
INSTALLED 14" ABOVE NEW ROOF. PROVIDE NEW SUPPLY
AND RETURN DUCTS TO CONNECT TO EXISTING
DUCTWORK. PROVIDE REFRIGERANT LINE EXTENSIONS AS
NECESSARY. PROVIDE CONDENSATE LINE EXTENSIONS AS
NECESSARY.
DUCTS CONNECTED TO ROOFTOP UNIT:
a. PRESSURE CLASS: POSITIVE OR NEGATIVE 3-INCH WG.
b. MINIMUM SMACNA SEAL CLASS: A.
c. SMACNA LEAKAGE CLASS FOR RECTANGULAR: 8.
EXISTING ROOFTOP UNIT
ROOF TO BE RAISED FROM CURRENT ROOF HEIGHT.
REMOVE AND REINSTALL EXISTING EXHAUST FAN AT NEW
ROOF HEIGHT WITH NEW CURB. NEW CURB TO BE INSTALLED
AT 14" ABOVE NEW ROOF. PROVIDE NEW EXHAUST DUCTS TO
CONNECT WITH EXISTING DUCTWORK.
DUCTS CONNECTED TO EXHAUST FAN:
a. PRESSURE CLASS: POSITIVE OR NEGATIVE 2-INCH WG.
b. MINIMUM SMACNA SEAL CLASS: A.
c. SMACNA LEAKAGE CLASS FOR RECTANGULAR: 12.
ROOF TO BE RAISED FROM CURRENT ROOF HEIGHT.
REMOVE AND REINSTALL EXISTING EXHAUST FAN AT NEW
ROOF HEIGHT WITH NEW CURB. NEW CURB TO BE INSTALLED
AT 14" ABOVE NEW ROOF. PROVIDE NEW EXHAUST DUCTS TO
CONNECT WITH EXISTING DUCTWORK.
DUCTS CONNECTED TO EXHAUST FAN:
a. PRESSURE CLASS: POSITIVE OR NEGATIVE 2-INCH WG.
b. MINIMUM SMACNA SEAL CLASS: A.
c. SMACNA LEAKAGE CLASS FOR RECTANGULAR: 12.
EXISTING EXHAUST FAN
EXISTING EXHAUST FAN
1.
2.
3.
A.
B.
C.
D.
E.
4.
GENERAL: ALL WORK SHALL BE INSTALLED TO CONFORM TO ALL REQUIREMENTS OF ALL REGULATORY AGENCIES HAVING JURISDICTION. THIS SHALL INCLUDE LOCAL, STATE AND FEDERAL AUTHORITIES. OBTAIN PERMITS AND PAY ALL REQUIRED FEES FOR WORK SPECIFIED AS PART OF THE HVAC PORTION OF THIS
PROJECT.
FLEXIBLE DUCT CONNECTIONS: PROVIDE FLEXIBLE DUCT CONNECTIONS WHEREVER DUCTWORK CONNECTS TO GAS FURNACE. CONSTRUCT FLEXIBLE CONNECTIONS OF NEOPRENE-COATED FLAMEPROOF FABRIC CRIMPED INTO DUCT FLANGES FOR ATTACHMENT TO DUCT AND EQUIPMENT. MAKE AIRTIGHT JOINT.
PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR THERMAL, AXIAL, TRANSVERSE, AND TORSIONAL MOVEMENT, AND ALSO CAPABLE OF ABSORBING VIBRATIONS OF CONNECTED EQUIPMENT. FLEXIBLE CONNECTIONS ON HEATING AND COOLING AIR SYSTEMS SHALL BE INSULATED TYPE WITH 1" THICK FIBERGLASS INSULATION IN-FILL. PROVIDE FLEXIBLE CONNECTIONS BY DURO DYNE CORP.; OR VENTFABRICS, INC.
SHEET METAL: GALVANIZED SHEET STEEL COMPLYING WITH ASTM A 527, LOCK FORMING QUALITY; WITH G 90 ZINC COATING IN ACCORDANCE WITH ASTM A 525;
AND MILL PHOSPHATIZED FOR PAINTING IN EXPOSED LOCATIONS.
SHOP FABRICATE DUCTWORK IN 4, 5, 8, 10 OR 12-FT LENGTHS, UNLESS REQUIRED TO COMPLETE RUNS. PREASSEMBLE WORK IN SHOP TO GREATEST EXTENT POSSIBLE, SO AS TO MINIMIZE FIELD ASSEMBLY OF SYSTEMS. DISASSEMBLE SYSTEMS ONLY TO EXTENT NECESSARY FOR SHIPPING AND HANDLING. MATCH-
MARK SECTIONS FOR REASSEMBLY AND COORDINATED INSTALLATION.
SHOP FABRICATE DUCTWORK OF GAUGES AND REINFORCEMENT COMPLYING WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS".
FABRICATE DUCT FITTINGS TO MATCH ADJOINING DUCTS. LOW PRESSURE 90º ELBOWS MAY BE SQUARE TYPE WITH TURNING VANES OR LONG RADIUS TYPE AT THE DISCRETION OF THE CONTRACTOR. ELBOWS IN ROUND AND FLAT OVAL DUCTWORK SHALL BE RADIUS TYPE ONLY. FABRICATE RADIUS TYPE ELBOWS WITH CENTER-LINE RADIUS EQUAL TO ONE AND ONE-HALF TIMES THE ASSOCIATED DUCT WIDTH; AND FABRICATE TO INCLUDE TURNING VANES IN ELBOWS WHERE SHORTER RADIUS IS NECESSARY. LIMIT ANGULAR TRANSITIONS TO 30º FOR CONTRACTING AND EXPANDING TAPERS.
FABRICATE DUCTWORK WITH ACCESSORIES INSTALLED DURING FABRICATION TO THE GREATEST EXTENT POSSIBLE.
ALL SHOP BUILT WORK MAY, AS A CONTRACTOR OPTION, BE ASSEMBLED USING A SYSTEM OF FACTORY-FABRICATED FRAMES, CLIPS, CLEATS, GASKETS, CONNECTORS, ACCESS PANELS, HANGERS, SUPPORTS, ETC. AS MANUFACTURED BY DUCTMATE INDUSTRIES, INC.
DUCT INSULATION SHALL BE FLEXIBLE FIBERGLASS BLANKET TYPE INSULATION, MINIMUM 0.75 LB. DENSITY, HAVING A MINIMUM “K” RATING OF 0.29 AT 75°F MEAN TEMPERATURE; VAPOR BARRIER SHALL BE COMBINATION ALUMINUM FOIL REINFORCED WITH GLASS FIBER YARN MESH AND LAMINATED TO 40 LB FLAME RETARDANT KRAFT PAPER HAVING A 2 INCH TAB. ALL RIGID SUPPLY DUCTWORK SHALL BE EXTERNALLY INSULATED WITH MINIMUM 3.5 ” THICK DUCT INSULATION, PENDING CONTRACTOR VERIFICATION THAT THE FINAL INSULATION THICKNESS WILL MEET THE REQUIREMENTS OF THE ENERGY CODE. RETURN DUCTWORK LOCATED IN THE MECHANICAL ROOMS ONLY SHALL BE EXTERNALLY INSULATED WITH MINIMUM 2.5 ” THICK DUCT INSULATION. INSULATION SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER ’S RECOMMENDATIONS WITH ALL SEAMS AND JOINTS VAPOR SEALED.
SPECIFICATIONS
SUPPORT
DUCT FROM
TOP OF CURB
SEAL WATERTIGHT
ROOF CURB
(8" ABOVE MIN. HIGH POINT)
GASKET MATERIAL
FURNISHED WITH
ROOF CURB ROOF TOP HEAT PUMP UNIT
SECURE FLASHING TO
CURB NAILER STRIP (TYP)
FLASHING
INSULATED ROOF CURB
1" RIGID BOARD INSULATION
2 LAYERS OF 5/8" FIRE RATED
GYPSUM WALL BOARD WITH
STAGGERD TAPE JOINTS
NOTES:
1. ALL ROOF FLASHING SHALL BE PER ROOF
MANUFACTURER'S RECOMMENDATIONS.
2. ROOF CURB SHALL BE INSTALLED PER ROOF CURB
MANUFACTURER'S RECOMMENDATIONS AND 8" ABOVE
MINIMUM HIGH ROOF HIGH POINT.
DUCT OPENING (MAX. 1" GAP) FILL VOID
WITH FIBERGLASS INSULATION AND
SEAL WITH BACKER ROD AND SILICONE
SEALANT
SEAL AROUND CURB INSIDE PERIMETER WITH
SILCONE SEALANT
EXISTING ROOF CURB
ROOF STRUCTURE
Architecture Engineering Planning Interiors
SFCS Inc. 305 South Jefferson Street Roanoke, Virginia 24011.2003
540.344.6664 Fax 540.343.6925
www.sfcs.com
:PROJECT ENGINEER
OF
DRAWING
COMM. NO.
SHEET
DATE
REVISION DESCRIPTION
DRAWING TITLE
APPROVED BY
CHECKED BY
NO.
DRAWN BY
DATE
PROJECT ARCHITECT
PROJECT DESIGNER
PROJECT TITLE
FEBRUARY 13, 2026
REPLACE ROOF
BEDFORD HALL
JBW
20301.03
PROJECT CODE: CVCC 260-B0260-042 MR20023
2/17/2026
2:28:04 PM
Autodesk Docs://20301.03 - VCCS - Re-Roof Bedford Hall Building at DCC (2025)/20301.03- VCCS- RE-ROOF BEDFORD HALL BUILDING CVCC- MECH.rvt
Checker
CYL
ROOF PLAN - HVAC
M1.1
CYL
1/8" = 1'-0"M1.1
ROOF PLAN - HVAC1
12" = 1'-0"M1.1
DUCTWORK ROOF PENETRATION3
12" = 1'-0"M1.1
ROOFTOP UNIT ROOF CURB4
02/13/2026
1. THESE ARE STANDARD SYMBOLS AND MAY NOT ALL APPEAR ON THE
PROJECT DRAWINGS. HOWEVER, WHEREVER THIS SYMBOL
APPEARS ON THE PROJECT DRAWINGS, THE ITEM SHALL BE
FURNISHED AND INSTALLED.
2. UNLESS NOTED OTHERWISE, MOUNTING HEIGHTS ARE FROM
FINISHED FLOOR TO CENTERLINE OF OUTLET. WHERE THE
MOUNTING HEIGHT INDICATED ON PLAN IS DIFFERENT FROM THE
LEGEND, THE PLAN TAKES PREDEDENT.
3. INSTALL RECEPTACLE AND TELEPHONE OUTLET BOXES (OR OTHER
OUTLET BOXES SUCH AS TV, COMPUTER, ETC.) 6" APART (EDGE TO
EDGE) WHERE SHOWN SIDE BY SIDE ON WALL.
4. SEE ELECTRICAL ABBREVIATIONS FOR ALPHABETIC SUBSCRIPT
WITH SYMBOL, UNO.
5. ARROW(S) INDICATE DIRECTION OF MAXIMUM LIGHT DISTRIBUTION.
6. " " = LUMINAIRE CONNECTED TO EMERGENCY CIRCUIT.
7. INSTALL DETECTOR BETWEEN 0'-4" AND 1'-0" DOWN FROM THE
CEILING TO THE TOP OF THE DETECTOR, UNO.
8. REFER TO THE OTHER ABBREVATION LISTS ELSEWHERE IN THESE
DOCUMENTS FOR ABBREVIATIONS NOT LISTED HERE.
9. FIRE ALARM VISUAL DEVICE (STAND-ALONE OR INTEGRAL STROBE)
SHALL BE LOCATED 80 INCHES TO THE BOTTOM ABOVE OF HIGHEST
FLOOR LEVEL WITHIN THE SPACE OR 6" TO THE TOP BELOW CEILING,
WHICHEVER IS LOWER.
PLAN NOTE DESIGNATION.1
1 KITCHEN EQUIPMENT DESIGNATION.
JUNCTION BOX, WALL.J2'-0"
ELEVATIONS - ELECTRICAL & FIRE ALARM DEVICES
4"
NO SCALE
DOOR WIDTH LESS 3"
6"
5'-0" MAX TO EXIT DOOR
4"
4"
" M
A X
3'-0" MIN
6"
SIDE WALL
48" MAX (ADA)
42" MIN/54" MAX (NFPA)
NFPA 72 LATEST
ENFORCED EDITION
CEILING
NOTE: MEASUREMENTS SHOWN
ARE TO CLOSEST EDGE OF
THE DETECTOR
A/C SUPPLY
OR RETURN
DIFFUSER
80" (ADA)
80" MIN/96" MAX (NFPA)
NFPA 72 LATEST
ENFORCED EDITION
SYNCRONIZE MORE THAN
TWO APPLIANCES IN ANY
FIELD OF VIEW.
NFPA 72 LATEST ENFORCED EDITION
REFER TO SYMBOL LEGEND ON THIS SHEET FOR EXACT HEIGHT OF DEVICES INDICATED.1
1 1
ELECTRICAL ABBREVIATIONS
ELEC SYMBOL LEGEND
(NOTE 2) (NOTES 3 & 4)
(NOTE 1)
(NOTE 2) (NOTES 3 & 4)
LUMINAIRE TYPE DESIGNATION.1
ELECTRIC WATER COOLEREWC
SCC SHORT CIRCUIT CURRENT
IG
IMC
INC
INTERMEDIATE METAL CONDUIT
INCANDESCENT
ISOLATED GROUND
GF OR
FLUORFLUOR
HPF
HZ
IC
HW
HPS
HTR
HP
HID
HOA
HG
H
GND
FC
GEN
GFI
FXTRFXTR
FSSFSS
FACPFACP
FDR
FA
EXIST
EXT
HIGH INTENSITY DISCHARGE
HORSEPOWER OR HEAT PUMP
HIGH PRESSURE SODIUM
INTERCOM OR INTERRUPTING
HIGH POWER FACTOR
HAND-OFF-AUTOMATIC
HOT WATER
CAPACITY
HERTZ
HEATER
HORIZONTAL
HOSPITAL GRADE
GROUND
FUSIBLE SAFETY SWITCHFUSIBLE SAFETY SWITCH
FIRE ALARM CONTROL PANELFIRE ALARM CONTROL PANEL
FOOTCANDLE
GENERATOR
FLUORESCENTFLUORESCENT
GROUND FAULT
FIXTUREFIXTURE
EXISTING
EXTERIOR
FIRE ALARM
FEEDER
WP WEATHERPROOF
TRANSFORMER
TRANSFER
XFMR
XFER
TC TIME CLOCK
VOLT-AMPERE
UNDERGROUND
WATT OR WIRE
VOLT-AMPERE REACTIVE
UNLESS NOTED OTHERWISE
VOLT
VOLTMETER
W
VM
V
VAR
VA
UNDERFLOOR
TYPICAL
TELEVISION
TELEPHONE
UG
UNO
UF
TYP
TV
TEL
MOTOR OPERATED SMOKE DAMPER
SURGE SUPPRESSOR/
ISOLATED GROUND
SYMMETRICAL
SWITCHBOARD
SURFACE RACEWAY
SOLID NEUTRAL
SURFACE METAL RACEWAY
STR STARTER
SWITCHGEAR
SWITCH
SYM
S/N
SWGR
SWBD
SW
SECONDARY
SPEAKERSPKR
SS
SR
SDR
SEC
SMR
COMB
EMER
E OR
ENG
ER
EQUIP
EP
ENCL
EMT
EML
EM
EMN
ELEC
EL
CTRL
DC
DR
DISC
CW
CU
COND
CONT
CT
CONN
CND
CNTR
EXIST REMOVED AND
RELOCATED TO THIS POSITION
EXISTING TO BE RELOCATED
EXISTING TO BE REMOVED
EXISTING TO BE REMOVED
ELECTRICAL METALLIC TUBING
AND NEW INSTALLED
EXISTING TO REMAIN
EQUIPMENT
ENCLOSURE
EXPLOSIONPROOF
ENGINE
EMERGENCY
ELECTRIC(AL)
DOOR RELEASE SERVICE
CURRENT TRANSFORMER
CONTROL
DISCONNECT
DIRECT CURRENT
COLD WATER
COPPER
CONTACTOR
CONNECTION
CONDUCTOR
COMBINATION
CENTER
CONDUIT
BRKR
ASYM
AMP
AWG
CATV
CCTV
CF
CKT
CLG
CB
CAB
CA
BD
BEL
AM
ATS
AMPL
AIC
AL
AFF
ABV
AFD
AC
ACB
A OR
AMERICAN WIRE GAGE
COMPACT FLUORESCENT
CLOSED CIRCUIT TELEVISION
COMMUNITY ANTENNA
TELEVISION OR CABLE
CIRCUIT BREAKER
TELEVISION
CIRCUIT
CEILING
BUS DUCT
BREAKER
CABINET
CABLE
BELOW
ADJUSTABLE FREQUENCY DRIVE
ABOVE FINISHED FLOOR
ALTERNATING CURRENT
ABOVE COUNTER BACKSPLASH
AMPERES INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
AMMETER
ALUMINUM
AMPLIFIER
ASYMMETRICAL
ABOVE
AMPERE
MS
PBS PUSHBUTTON STATION
PANELBOARD
POLYVINYL CHLORIDE
RIGID STEEL CONDUIT
POTENTIAL TRANSFORMER
RECEPTACLE
QUANTITY
RECPT
RSC
QTY
POWER
PANEL
PHASE
PRIMARY
PT
PVC
PWR
PRI
PNLBD
PH( )
PNL
PULL BOX OR PUSHBUTTON
MOUNTED OR MOUNTING
MAGNETIC STARTER
MERCURY VAPOR
NON-FUSIBLE SAFETY SWITCH
NATIONAL ELECTRICAL CODE
NFSS
OVERHEAD
POLE
NUMBER
PB
P
OH
NO
NEUTRAL
METER
NEUT
NEC
MTG
MV
MTR
LTG LIGHTING
MOTOR/GENERATOR
MAIN LUGS ONLY
THOUSAND CIRCULAR MILS
MOTOR CONTROL CENTER
METAL HALIDE OR MOUNTING
MOTOR OPERATED DAMPER
MASTER ANTENNA TELEVISION
MAIN CIRCUIT BREAKER
MOTOR
MOD
MOT
MLO
MCM
M/G
MH
HEIGHT
LUMENS
MANUAL
MAGNETIC
MAN
MATV
MCC
MCB
MAG
LUM
JUNCTION BOX
LIGHTNING ARRESTER
LOW PRESSURE SODIUM
KILOWATT-HOUR
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KWH
LPS
LA
KVAR
KW
KVA
INITIAL
KILOVOLT
KNOCKOUT
JB
KO
KV
INIT
(NOTE 8)
DB DOOR BELL
DS DOOR SWITCH
GD GARAGE DOOR
C COUNTERTOP
ERC ELEVATOR RECALL
ELEV ELEVATION/ELEVATOR
UNDERWRITERS' LABORATORIESUL
HGT
HEIGHT
REFRIGERATORREFRIG
BOTT BOTTOM
DIM DIMENSION
MINIMUMMIN
DWG DRAWING
AFCI ARC FAULT CIRCUIT INTERRUPTER
LOADCENTERLC
MTG. HGT. SYMBOL
DESCRIPTION
GENERAL
MTG. HGT. SYMBOL
DESCRIPTION
POWER
SPEAKER/VISUAL &
VISUAL DEVICES
FIRE
PHONE
JACK
MANUAL PULL
STATION MAGNETIC DOOR
HOLDER
LIGHT
SWITCH(ES)
TELEDATA OUTLET
VERTICALLY
ORIENTED, UNO.
ADDITIONAL LIGHT SWITCHES AS REQUIRED
ON DRAWINGS IN TWO, THREE, FOUR, OR
MORE GANG BOXES
WALL OUTLETS VERTICALLY ORIENTED WITH
GROUND SLOT UP, UNO
FINISHED FLOOR
CONCEALED 1/2" EC TO JB IN
ACCESSIBLE LOCATION AT ALL
EXTERIOR DOORS.
DOOR TRIM
ACCEPTED HERE
NEVER HERE
WALL MOUNTED
SMOKE/HEAT
DETECTOR
CEILING MOUNTED
SMOKE/HEAT DETECTOR
DUPLEX GROUND FAULT CIRCUIT INTERUPTER RECEPTACLE, WALL. ALPHA-NUMERIC SUBSCRIPT
WHERE SHOWN, INDICATES CIRCUITS (TYPICAL FOR ALL RECEPTACLES).
2'-0"
"AF" = ARC FAULT CIRCUIT INTERRUPTER DEVICE
"E" = EMERGENCY DEVICE
"WP" = WEATHERPROOF DEVICE
"U" = USB DEVICE
"C" = MOUNT BOTTOM 0'-1" ABOVE BACKSPLASH/COUNTER
"T" = TAMPER RESISTANT DEVICE
(NOTE 2) (NOTES 3 & 4)
WALL MOUNTED LUMINAIRE. (NOTE 6)
MTG. HGT. SYMBOL
DESCRIPTION
LIGHTING
• 2021 VIRGINIA CONSTRUCTION CODE
• 2020 VIRGINIA ELECTRICAL CODE
• 2020 NFPA 780 - STANDARD FOR THE INSTALLATION OF
LIGHTNING PROTECTION SYSTEMS
• 2025 STATE OF VIRGINIA CPSM, REVISION 0
CODE SUMMARY
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
PERFORM WORK IN ACCORDANCE WITH THE CODES AND STANDARDS SHOWN IN THE CODE SUMMARY THIS SHEET.
FIELD VERIFY DIMENSIONS AND ELEVATIONS IN THE AREA OF WORK PRIOR TO THE START OF WORK.
MODIFICATIONS TO THESE DOCUMENTS DUE TO UNFORESEEN FIELD CONDITIONS MUST BE APPROVED BY THE ENGINEER OF RECORD AND INDICATED ON THE AS-BUILT
DRAWINGS.
PROVIDE NEW EQUIPMENT LISTED AND LABELED FOR ITS INTENDED USE UNLESS INSTRUCTED OTHERWISE.
SEAL PENETRATIONS OF FIRE RATED CONSTRUCTION WITH U.L. APPROVED FIRE STOPPING MATERIAL TO RESTORE THE ORIGINAL FIRE RESISTANCE RATING OF THE
PENETRATED CONSTRUCTION.
WHERE PROVIDED. EQUIPMENT MODEL NUMBERS INDICATE THE BASIS OF DESIGN EQUIPMENT. PRODUCTS FROM LISTED APPROVED EQUAL MANUFACTURERS ARE ACCEPTABLE.
THESE DOCUMENTS CALL FOR FINISHED WORK, TESTED AND READY FOR OPERATION. THE TERM "PROVIDE" MEANS "FURNISHED AND INSTALLED COMPLETE AND READY FOR USE." COORDINATE EXACT LOCATIONS OF DEVICES WITH EQUIPMENT VENDORS PRIOR TO INSTALLATION.
PROVIDE EQUIPMENT GROUNDING CONDUCTIOR FOR EACH CIRCUIT INDICATED IN PANEL SCHEDULES.
PROVIDE NYLON PULL STRING IN EMPTY CONDUITS.
LABEL JUNCTION BOXES, DISCONNECT SWITCHES AND RECEPTACLES WITH PANEL DESIGNATION AND CIRCUIT NUMBER.
DISCONNECT SWITCH LABELS SHALL BE SELF-ADHESIVE LAMINATED ACRYLIC OR MELAMINE PLASTIC. SIGNS SHALL WHITE WITH BLACK LETTERING SIMILAR TO EXISTING
EQUIPMENT LABELS.
PRIOR TO FINAL ACCEPTANCE; CLEAN DEVICES, DEVICE PLATES, CABINETS, LUMINAIRES, AND OTHER EQUIPMENT PROVIDED UNDER THIS CONTRACT; ENSURE THAT PANEL DIRECTORIES ARE REVISED AND/OR COMPLETED AND IN PLACE; AND THAT MARKING AND IDENTIFICATION OF COMPONENT IS COMPLETE.
REPAIR OF REPLACE, AND AT NO ADDITIONAL COST, ITEMS DAMAGED DURING THE COURSE OF THE WORK.
REPLACE AND RETEST DEFECTIVE WIRING, DEVICES, AND EQUIPMENT THAT IS ENCOUNTERED DURING THE COURSE OF TESTING.
MAKE FINAL CONNECTIONS TO DEVICES AND EQUIPMENT FURNISHED BY OTHER TRADES.
ABBREVIATIONS ARE SHOWN FOR REFERENCE ONLY AND MAY NOT BE USED IN DRAWING PACKAGE.
SYMBOLS ARE SHOWN FOR REFERENCE ONLY AND MAY NOT BE USED IN DRAWING PACKAGE.
IN ACCORDANCE WITH NEC 300.7, PROVIDE REQUIRED SEALING WHERE PORTIONS OF A RACEWAY OR SLEEVE ARE KNOWN TO BE SUBJECTED TO DIFFERENT TEMPERATURES.
WHERE PASSING FROM THE INTERIOR TO THE EXTERIOR OF A BUILDING, THE RACEWAY OR SLEEVE SHALL BE FILLED WITH AN APPROVED MATERIAL TO PREVENT THE
CIRCULATION OF WARM AIR TO A COLDER SECTION OF THE RACEWAY OR SLEEVE.
ALL CONDUCTORS, RACEWAYS AND CABLES SHALL BE CONCEALED IN CEILING OR WALLS IN FINISHED SPACES.
ALL RACEWAYS RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH EXPANSION FITTINGS.
PROVIDE REVISED TYPED PANELBOARD SCHEDULES TO REPLACE EXISTING PANELBOARD SCHEDULES ONCE ALL CIRCUIT REVISIONS HAVE BEEN MADE.
BASE ELECTRICAL REQUIREMENTS
PROVIDE ALL NECESSARY ITEMS FOR A COMPLETE INSTALLATION OF ELECTRICALLY OPERATED EQUIPMENT, AS INDICATED ON THE DRAWINGS. ARRANGE EQUIPMENT AS INDICATED, AND MAKE DEVIATIONS ONLY WHERE NECESSARY TO AVOID INTERFERENCE. ALL ELECTRICAL WORK SHALL BE PERFORMED BY, OR UNDER THE SUPERVISION OF
AN ELECTRICIAN LICENSED TO WORK IN THE COMMONWEALTH OF VIRGINIA.
CONDUITS
EXCEPT AS NOTED BELOW, ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (MINIMUM SIZE 3/4"). SUPPORT CONDUITS EVERY EIGHT FEET, WITHIN 3 FEET OF TERMINATIONS, AND WITHIN ONE FOOT OF ANY CHANGE IN DIRECTION. CONDUIT SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS OR STRUCTURAL
MEMBERS. RIGHT ANGLE TURNS SHALL CONSIST OF SYMMETRICAL BENDS OR FITTINGS.
MC CABLE MAY BE USED IN SIZES #12AWG AND #10AWG IN THE FOLLOWING APPLICATIONS:
-VERTICAL AND HORIZONTAL RUNS TO AND BETWEEN DEVICES IN NEW FURRED OR OTHER HOLLOW WALL CONSTRUCTION
-WHERE FISHED TO DEVICES IN EXISTING HOLLOW WALL CONSTRUCTION
-AS THE LAST SIX FEET OF CONNECTIONS TO LIGHT FIXTURES IN ACCESSIBLE CEILINGS (FIXTURE WHIPS)
MC CABLE MAY NOT BE USED:
-FOR FEEDERS
-IN HORIZONTAL RUNS ABOVE ACCESSIBLE CEILING EXCEPT AS NOTED ABOVE
-IN A CONNECTION TO MACHINERY
-IN EXPOSED APPLICATIONS
-IN AWG SIZES GREATER THAN #10
MC CABLE MUST ORIGINATE AT A JUNCTION BOX CONNECTED TO UPSTREAM EMT OR RIGID CONDUIT WIRING METHODS.
FOR CONNECTIONS TO MOTORS, EQUIPMENT SUBJECT TO VIBRATION, NOISE TRANSMISSION, OR MOVEMENT, PROVIDE FLEXIBLE METAL CONDUIT (MINIMUM SIZE 3/4"). IN DAMP
OR WET APPLICATIONS, USE LIQUID TIGHT FLEXIBLE METALLIC CONDUIT (LFMC).
PULL AND JUNCTION BOXES
ALL BOXES SHALL BE CONSTRUCTED OF SHEET METAL, NEMA 1 ENCLOSURE FOR INTERIOR USE, 14 GAUGE GALVANIZED STEEL.
POWER CONDUCTORS
ALL CONDUCTORS SHALL BE COPPER WITH THHN/THWN INSULATION, RATED FOR 75 DEGREES CELSIUS OR ABOVE. FORM AND TIE ALL WIRING IN PANELBOARDS AT SIX INCH INTERVALS. IDENTIFY ALL BRANCH CIRCUIT WIRING AT ALL POINTS OF ACCESS. PROVIDE CIRCUITS WITH INDIVIDUAL NEUTRALS. DERATE CONDUCTOR AMPACITY, IN
ACCORDANCE WITH WITH NEC, FOR MULTIPLE CONDUCTORS IN A CONDUIT.
WIRING DEVICES
ALL DEVICES SHALL BE RATED AT 20 AMP MINIMUM. LABEL ALL RECEPTACLES WITH CIRCUIT AND PANEL DESIGNATION. RECETPACLE DEVICE SHALL BE GREY COLOR WITH
STAINLESS STEEL COVER PLATE TO MATCH EXISTING DEVICES.
DISCONNECT SWITCHES
ALL DISCONNECTS SHALL BE HEAVY DUTY RATED.
GROUNDING AND BONDING
PROVIDE INSULATED EQUIPMENT GROUNDING CONDUCTORS WIITH ALL FEEDERS AND BRANCH CIRCUITS.
SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
PROVIDE STEEL SLOTTED SUPPORT SYSTEMS. SUPPORTS SHALL BE GALVANIZED STEEL 1-5/8" CHANNEL, HOT DIPPED GALVANIZED AFTER FABRICATION.
CONDUIT SUPPORT DEVICES SHALL BE STEEL HANGERS, CLAMPS, AND ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY TO BE SUPPORTED.
SPECIFICATIONS:
Architecture Engineering Planning Interiors
SFCS Inc. 305 South Jefferson Street Roanoke, Virginia 24011.2003
540.344.6664 Fax 540.343.6925
www.sfcs.com
:PROJECT ENGINEER
OF
DRAWING
COMM. NO.
SHEET
DATE
REVISION DESCRIPTION
DRAWING TITLE
APPROVED BY
CHECKED BY
NO.
DRAWN BY
DATE
PROJECT ARCHITECT
PROJECT DESIGNER
PROJECT TITLE
FEBRUARY 13, 2026
REPLACE ROOF
BEDFORD HALL
GENERAL NOTES
JBW
REBID SET
20301.03
PROJECT CODE: CVCC 260-B0260-042 MR20023
2/16/2026
3:12:24 PM
Autodesk Docs://20301.03 - VCCS - Re-Roof Bedford Hall Building at DCC (2025)/20301.03- VCCS- RE-ROOF BEDFORD HALL BUILDING CVCC- ELEC.rvt
JBW
MAR
ELECTRICAL SYMBOL
LEGEND &
ABBREVIATIONS
E0.0
CIW
SHEET LIST
SHEET
NUMBER SHEET NAME
E0.0 ELECTRICAL SYMBOL LEGEND & ABBREVIATIONS
E1.1 ROOF PLAN - ELECTRICAL
BEFORE WORK IS COMMENCED, CONTRACTORS SHALL MAKE A THOROUGH SURVEY OF THE
FACILITY AND NOTIFY THE OWNER IN WRITING OF ANY DISCREPANCIES BETWEEN THE EXISTING
CONDITIONS AND THOSE SHOWN ON THE DRAWINGS. FAILURE BY THE CONTRACTOR TO HAVE
ACQUAINTED HIMSELF WITH AVAILABLE INFORMATION CONCERNING EXISTING CONDITIONS SHALL
NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITY TO PERFORM THE WORK IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
THIS DRAWING WAS PREPARED WITH LIMITED FIELD MEASUREMENTS AND MAY NOT FULLY
REFLECT ACTUAL FIELD CONDITIONS. THE CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND
NOTIFY THE ARCHITECT IN WRITING OF ANY WORK DESCRIBED IN THE CONTRACT DOCUMENTS
WHICH CANNOT BE PERFORMED DUE TO EXISTING CONDITIONS.
EXISTING EXIT DOORS, ACCESS TO EXITS AND FIRE PROTECTION SHALL BE MAINTAINED DURING
DEMOLITION. ALL FIRE PROTECTION, ACCESS AND EXITS SHALL BE OPERATIONAL AFTER
COMPLETION OF DEMOLITION WORK.
VERIFY WITH OWNER FINAL DISPOSITION OF ALL ELECTRICAL EQUIPMENT TO BE REMOVED. ITEMS
TO BE SALVAGED FOR OWNER SHALL BE COLLECTED AND STORED AT OWNER DESIGNATED
LOCATION WITHIN THE BUILDING FOR REMOVAL BY OWNER. ITEMS REFUSED BY THE OWNER SHALL
BE REMOVED BY THE CONTRACTOR AND BE PROPERLY DISPOSED OF OFF-SITE WITHIN FIVE
WORKING DAYS.
PROTECT FROM DAMAGE ALL MATERIALS TO REMAIN. ANY WORK DAMAGED DURING
CONSTRUCTION SHALL BE RESTORED TO MATCH CONDITION PRIOR TO CONSTRUCTION.
DEMOLITION WORK INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THOSE ITEMS NOTED. OTHER ITEMS OF A MINOR NATURE MAY EXIST WHICH ARE NOT SPECIFICALLY NOTED ON THE DRAWINGS ARE TO BE REMOVED AS REQUIRED, TO PROVIDE ACCESS AND ALLOW ALTERATION OR NEW WORK
TO PROCEED.
CONTRACTOR SHALL USE CAUTION WHEN PERFORMING DEMOLITION AT OR NEAR FIRE-RATED
ASSEMBLIES SCHEDULED TO REMAIN SO AS NOT TO DISRUPT THE INTEGRITY OF THE FIRE RATING
AND SHALL REPAIR ANY DAMAGE TO THOSE TO INSURE CONTINUOUS RATING AS REQUIRED.
NOT ALL ELECTRICAL EQUIPMENT WHICH IS REQUIRED TO BE REMOVED IS SHOWN. CONTRACTOR
SHALL REMOVE ALL SUCH EQUIPMENT WHICH WILL INTERFERE WITH NEW CONSTRUCTION.
EQUIPMENT WHICH WILL NO LONGER BE USED (E.G. PIPES, CONDUITS AND DUCTS) SHALL BE
REMOVED COMPLETELY BACK TO THE POINT OF SERVICE TO BE REUSED AND CAPPED OR
PLUGGED AS INDICATED ON ELECTRICAL DRAWINGS.
REFER TO ARCHITECTURAL DEMO DRAWINGS TO DETERMINE EXTENT OF DEMOLITION. DASHED
LINES INDICATE WALLS TO BE REMOVED. WHERE DASHED LINES ARE SHOWN, EXCEPT WHERE
OTHERWISE SHOWN OR NOTED ON DRAWINGS.
ALL EXISTING ELECTRICAL EQUIPMENT AND MATERIAL IN AREAS TO BE REMODELED/ALTERED
SHALL BE REMOVED WHERE THEY INTERFERE WITH NEW CONSTRUCTION AND/OR INTERFERE
WITH PROPOSED USAGE OF SPACE BY OWNER.
THIS DEMOLITION INCLUDES, BUT IS NOT NECESSARILY LIMITED TO THE FOLLOWING:
REMOVE ALL LIGHTING FIXTURES, SWITCHES, AND ASSOCIATED WIRING BACK TO THE POINT OF
SERVICE AS REQUIRED TO FIT SCHEME OF NEW WORK.
REMOVE ALL ELECTRICAL DEVICES, COVERPLATES, OUTLET BOXES, CONDUITS AND ASSOCIATED
WIRING BACK TO THE POINT OF SERVICE TO FIT SCHEME OF NEW WORK.
REMOVE ALL PANELBOARDS, CONDUITS AND ASSOCIATED WIRING BACK TO POINT OF SERVICE TO
FIT SCHEME OF NEW WORK.
REMOVE ALL ELECTRICAL ITEMS ASSOCIATED WITH MECHANICAL EQUIPMENT BEING DEMOLISHED.
REMOVE ALL MOTOR STARTERS, DISCONNECT SWITCHES AND ASSOCIATED WIRING BACK TO
POINT OF SERVICE TO FIT SCHEME OF NEW WORK.
REMOVE ALL FIRE ALARM DEVICES, CONDUITS AND ASSOCIATED WIRING BACK TO THE POINT OF
SERVICE AS REQUIRED TO FIT SCHEME OF NEW WORK.
REMOVE ALL LOW VOLTAGE SYSTEMS AS REQUIRED TO FIT SCHEME OF NEW WORK.
WHERE CONDUIT ASSOCIATED WITH AN ITEM TO BE REMOVED IS IN AN INACCESSIBLE AREA, SUCH AS ENCASED IN CONCRETE, THE INACCESSIBLE CONDUIT ONLY SHALL BE ABANDONED IN PLACE.
ALL WIRING SHALL BE REMOVED AND CONDUIT SHALL BE CUT OFF FLUSH AND FINISHED OVER
WITH A MATERIAL TO MATCH EXISTING.\
IN REMODELED/ALTERED AREAS ANY FEEDERS, CONDUITS, BRANCH CIRCUITS, SIGNAL,
TELEPHONE OR OTHER LOW VOLTAGE SYSTEMS, ETC. PASSING THROUGH THE REMODELED AREAS
TO SERVE (OR BE SERVED FROM EXISTING ADJACENT, REMOTE OR SURROUNDING AREA THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE REROUTED IN ALL CASES
WHERE THEY INTERFERE WITH ANY NEW WORK.
WHERE DEVICES ARE OMITTED FROM PRESENT BRANCH CIRCUITS, THE REMAINING DEVICES
SHALL BE REWIRED AS REQUIRED.
ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS TO BE FAMILIARIZED
WITH EXTENT OF REMODELING WORK AND MORE SPECIFICALLY NOTE WHERE NEW PARTITIONING
IS BEING INSTALLED, WHERE EXISTING PARTITIONING IS BEING REMOVED AND WHERE CEILINGS
ARE BEING REMOVED AND/OR REPLACED.
PROVIDE FLOOR AND WALL PENETRATIONS AS REQUIRED FOR NEW MECHANICAL AND ELECTRICAL
WORK.
PORTIONS OF THE BUILDING WILL BE OCCUPIED DURING THIS RENOVATION. THE GENERAL
CONTRACTOR SHALL TAKE ALL MEASURES NECESSARY TO PROVIDE FOR THE PROTECTION AND
SAFETY OF THE BUILDINGS OCCUPANTS.
IF ANY SUSPECT HAZARDOUS MATERIALS ARE ENCOUNTERED BY CONTRACTOR, INCLUDING BUT
NOT LIMITED TO MATERIALS CONTAINING ASBESTOS, LEAD PAINT, ETC, WORK IS TO BE STOPPED IN
THE AREA WHERE SUCH MATERIALS WERE FOUND AND THE OWNER IMMEDIATELY NOTIFIED IN
WRITING. THE REMOVAL OF HAZARDOUS MATERIALS WILL BE THE OWNER'S RESPONSIBILITY.
RELOCATE EXISTING SECURITY, FIRE ALARM AND TELEPHONE EQUIPMENT AS NECESSARY TO
CONDUCT NORMAL OPERATIONS IN A REMOTE LOCATION DURING CONSTRUCTION OF THIS PHASE.
1.
2.
3.
4.
5.
6.
7.
8.
8A.
8B.
8C.
8D.
8E.
8F.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
GENERAL DEMOLITION NOTES
cwallace Snapshot
SECTION A-A(1
2"
) M A
X
(1 8"
) M A
X
2-GANG,
NEMA 3R JUNCTION BOX
WITH THREADED HUBS
RIGID STEEL CONDUIT FOR
WIRING
RIGID STEEL CONDUIT FOR
SUPPORT PER N.E.C.ART.
"WHILE-IN-USE" WP
COVER(S) &
RECEPTACLE(S)
ROOF PENETRATION. FLASH AND SEAL PER
SPECIFICATION SECTIONS 076200 AND 079200.
COORDINATE INSTALLATION WITH ROOF INSTALLER.
A
A
EXISTING FAN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING FAN
EXISTING FAN
EXISTING FAN
EXISTING
ROOF HATCH
EXISTING
CHIMNEY
EXISTING VENT
PIPE
EXISTING
VENT PIPE
EXISTING
VENT PIPE
EXISTING
VENT PIPE
EXISTING
VENT PIPE
EXISTING
MECHANICAL UNIT
EXISTING
LIGHTNING
PROTECTION
SYSTEM (TYP)
EXISTING AIR
TERMINAL (TYP)
WP
EXISTING
CONDUIT
50' - 0" MAX
EXISTING FAN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING
ROOF DRAIN
EXISTING FAN
EXISTING FAN
EXISTING FAN
EXISTING
ROOF HATCH
EXISTING
CHIMNEY
EXISTING VENT
PIPE
EXISTING
VENT PIPE
EXISTING
VENT PIPE
EXISTING
VENT PIPE
EXISTING
VENT PIPE
EXISTING
MECHANICAL UNIT
EXISTING
LIGHTNING
PROTECTION
SYSTEM (TYP)
EXISTING AIR
TERMINAL (TYP)
WP
EXISTING
CONDUIT
6 6
• 2021 VIRGINIA CONSTRUCTION CODE
• 2020 VIRGINIA ELECTRICAL CODE
• 2020 NFPA 780 - STANDARD FOR THE INSTALLATION OF
LIGHTNING PROTECTION SYSTEMS
• 2025 STATE OF VIRGINIA CPSM, REVISION 0
CODE SUMMARY
Architecture Engineering Planning Interiors
SFCS Inc. 305 South Jefferson Street Roanoke, Virginia 24011.2003
540.344.6664 Fax 540.343.6925
www.sfcs.com
:PROJECT ENGINEER
OF
DRAWING
COMM. NO.
SHEET
DATE
REVISION DESCRIPTION
DRAWING TITLE
APPROVED BY
CHECKED BY
NO.
DRAWN BY
DATE
PROJECT ARCHITECT
PROJECT DESIGNER
PROJECT TITLE
FEBRUARY 13, 2026
REPLACE ROOF
BEDFORD HALL
PLAN NOTES
GENERAL NOTES
JBW
REBID SET
20301.03
PROJECT CODE: CVCC 260-B0260-042 MR20023
2/16/2026
3:12:24 PM
Autodesk Docs://20301.03 - VCCS - Re-Roof Bedford Hall Building at DCC (2025)/20301.03- VCCS- RE-ROOF BEDFORD HALL BUILDING CVCC- ELEC.rvt
JBW
MAR
ROOF PLAN -
ELECTRICAL
E1.1
CIW
1 DISCONNECT EXISTING MECHANICAL EQUIPMENT.
REMOVE POWER CONNECTION FROM EXISTING
MECHANICAL EQUIPMENT AND CAP OFF IN JUNCTION
BOX. AFTER NEW ROOF IS INSTALLED, RECONNECT
EXISTING MECHANICAL EQUIPMENT FROM EXISTING
POWER FROM CAPPED OFF JUNCTION BOX.
DISCONNECT AND REMOVE EXISTING SURFACE
MOUNTED CONDUIT. REINSTALL BELOW ROOF ONCE
EXISTING ROOF HAS BEEN REMOVED. COORDINATE
WITH EXISTING STRUCTURE TO MAINTAIN SIMILAR
ROUTING.
REMOVE EXISTING ROOF TOP RECEPTACLE AND
INSTALL NEW HEAVY GRADE, GREY 20A, GFCI WEATHER
RESISTANT RECEPTACLE IN WEATHERPROOF
ENCLOSURE.
EXISTING ROOF PENETRATION. MAINTAIN EXISTING
CIRCUIT AND COORDINATE WITH ROOF RE-
INSTALLATION.
DISCONNECT AND REMOVE EXISTING ROOF
PENETRATION AS WELL AS ASSOCIATED CONDUIT AND
WIRING TO BELOW NEW ROOF.
REMOVE EXISTING LIGHTNING PROTECTION
CONDUCTOR AND ASSOCIATED AIR TERMINALS.
PROVIDE NEW LIGHTNING PROTECTION CONDUCTOR
AND ASSOCIATED TERMINALS AS INDICATED.
LIGHTNING PROTECTION SHALL NOT BE INSTALLED
PENETRATI…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .