This document is a comprehensive staking sheet for Mountain Parks Electric's (MPEI) electrical infrastructure project located in Grand County, Colorado, specifically addressing a double circuit overhead-to-underground (OH-UG) conversion along County Road 5. The project, identified as Work Order #20220284, involves converting existing overhead electrical lines to underground infrastructure, focusing on the Granby and Fraser electrical circuits. The staking sheet provides detailed technical specifications for pole replacements, wire configurations, transformer locations, and underground conduit installations across multiple station points, with precise measurements and conductor types documented across 65 detailed pages.
The project appears to be part of a broader wildfire mitigation initiative, likely funded through state or federal grant programs, aimed at improving electrical infrastructure resilience. The work involves complex underground cable installations, splice vault constructions, fiber optic conduit placements, and transformer replacements along a significant length of County Road 5. The documentation indicates multiple phases of work, including retiring existing overhead lines, installing new underground circuits, and establishing new connection points, with specific attention to maintaining electrical service continuity throughout the conversion process. The technical complexity suggests a sophisticated engineering approach to modernizing rural electrical distribution infrastructure.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet No. 1 of 65
Name:
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S Range: 76W Section: 13
Pri Voltage: Sec Voltage: Loan No.:
Ruling Span: Primary Wire Size: RUS Code:
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 38229 286 (3) U-500 0
R P45-3 2009
VC7-HB-M
(2) UM22-
P-45-6
M2-11 (2) E1-3F78 (2) F1-6S
R UC5
EXPOSE EXISTING 3PH UG 500 FRASER CIRCUIT. REROUTE AND SPLICE IN NEW SPLICE VAULT SV#1.
Sheet No. 2 of 65
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E SV#1 277 (3) U-500
(277) UM20-
PVC6
C
UMH1-CS
(6) UM22-
UM6-6
UM1-6CSG-
R2
(2) UM24-P-
C-6
BM55
(4) UM22-
P-22-6
C UM12
(90) U-MA-
COMP
C (90) UR2-LIFT
(20) UM20-
PVC6
C (90) UR2-NT
C ADFO-U1
ADFO-
HANDHOLE
24X36X
C HACO(144)
C (48) HO1
EXPOSE EXISTING GRANBY AND FRASER 3PH UG 500 CIRCUITS. REROUTE AND SPLICE IN SPLICE VAULT SV#1. EXPOSE EXISTING FIBER IN 2" C SPLICE IN NEW HANDHOLE W/144CT IN 2"C. 1-2" C SPARE
R 38237 P40-3 2009
42 (3) U-500 UC5
(42) UM20-
PVC6
-16 M2-11 (2) E1-3F78 (2) F1-6S
R
VC7-HB-M
C 42 U-500 (45) UO144
C (84) UR2-LIFT
C (42) UR2-ST
(42) U-MA-
(40) UM20-
EXPOSE EXISTING GRANBY 3PH UG 500 CIRCUIT. SPLICE IN SPLICE VAULT SV#1. INSTALL NEW 3PH UG 500 DOUBLE CIRCUIT FOR GRANBY AND FRASER CIRCUITS IN JOINT TRENCH. INSTALL 144CT FIBER IN 2" ORANGE C W/2"C SPARE.
Sheet No. 3 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 10748 P45-4 1967 6 M2-11 K11
R 128 (3) ACSR 477 VOC1-2P 15 KVA 15
R 128 ACSR 4/0 VC9-1 VG105
128 (3) U-500 UM5
(12) UM20-
FLEX3
5 (50) U-4/0-TPLEX
(128) U-MA-
C (128) UR2-ST
(4) CREW
HOURS
(140) UM20-
(256) UR2-
LIFT
RETIRE XFMR AND POLE TOP ASSEMBLIES.INSTALL SECONDARY RISER AND WIRE UP P0LE TO REFEED SERVICE FROM 1PH XFMR#1. CUTOFF TOP OF POLE ABOVE SECONDARY.
C 1PH XFMR#1 219 U-1/0-CIC UM6-34 UM12F -170 U15 KVA 15 UM6-6 UJ2-8-500-B
C UM1-7NC UG7 (2) UJ2-6-500
C UM6-1
INSTALL 1PH 1/0 UG IN DBL CIRCUIT TRENCH TO 15KVA XFMR TO REFEED SERVICE FROM PVID10749.
R 10748 WIRE 128 (3) ACSR 477 -2
R 128 ACSR 4/0
128 (3) U-500
5 (50) U-4/0-TPLEX
C (5) UR2-SEC
C (5) UR2-LIFT
(5) U-MA-
INSTALL SECONDARY WIRE FROM XFMR UP POLE TO EXISTING OH SECONDARY.
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 4 of 65
35 0 35
SCALE IN FEET
Sheet No. 5 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
Sheet No. 6 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10749 P45-4 1967
214 (3) ACSR 4/0 UC2
(3) OH-FUSE
50CL
-178 M2-11 (2) E2-2F78
R 214 ACSR 1/0 VC1-2-M E2-2
R VC2-M
214 (3) U-500 BM53
(220) UM20-
C (214) UR2-ST
(428) UR2-
(214) U-MA-
(440) UM20-
PVC2
C (220) UO144
INSTALL 3PH UG 500 DBL CIRCUIT IN JOINT TRENCH. RETIRE EX. 3PH OH WIRE AND POLE. INSTALL 144CT FIBER IN 2"C W/2"C SPARE.
R 10318 P45-4 1967 388 ACSR 1/0 -3 (3) E1-2 (2) F1-2
R 388 (3) ACSR 477
388 (3) U-500
(400) UM20-
RETIRE SPAN GUYS, POLE, DOWN GUYS AND ANCHORS. INSTALL FRASER CIRCUIT 3PH UG 500 IN TRENCH WITH GRANBY CIRCUIT SPLICE IN PMH#1
E PME#1 10 (3) U-1/0 -10
10 (3) U-500 (5)
UM6-3-1/0
(260) UO144
UM6-6
C UM1-6CSG (20) UR2-LIFT
UM3E-3
PMH9
(2) UM12
(6)
UM6-3-500
(10) U-MA-
BM53
(5) UG-
FUSE-200E
(3)
UM6-28-500
C (10) UR2-ST
EXPOSE 1/0UG 3PH. RETERM IN PME#1. INSTALL 3PH UG500 DBL CKT. TERMINATE GRANBY CKT IN PME. SPLICE FRASER CKT IN PME VLT. INSTALL 1PH 1/0 UG TO XFMR BY PVID10748 & 1PH 1/0 UG E ALONG CRD5 TO REFEED 1PH SERVICES.
INSTALL 144CT FO, 2"C,250'STORAGE LOOP, 1-2"
R 10319 P45-4 1967 257 (3) ACSR 4/0 VC2-M 14 M2-11
R 257 ACSR 1/0 VC1-2-M
RETIRE POLE AND DBL CIRCUIT WIRE
Sheet No. 7 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 10320 62 (6) E2-2F78
R P40-4 1967 (6) E2-2F78 (2) F1-2
R (2) E1-2
R 10319RWIRE 257 (3) ACSR 477 13
R 257 ACSR 1/0
RETIRE FRASER DBL CIRCUIT OH WIRE
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 8 of 65
37 0 37
Sheet No. 9 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 10321 P45-4 1967 -8 M2-11
R 233 (3) ACSR 4/0 VOC1-2P 25 KVA 25
R 233 ACSR 1/0 VC9-1 VG105
UM5
RETIRE XFMR, OH WIRE AND POLE TOP ASSEMBLIES. INSTALL SECONDARY RISER AND WIRE TO REFEED EX SERVICE. CUTOFF TOP OF POLE ABOVE SECONDARY.
R 10321RWIRE 233 (3) ACSR 477 -8
R 233 ACSR 1/0
Sheet No. 10 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C 1PH XFMR#2 521 U-1/0 (2) UM6-1
(4) UM22-
P-90-4
21 UG7 UM6-6 UJ2-8-500-B
C UM1-7NC UM22-P-45-4 U25 KVA 25 (2) UJ2-6-500
C UM12F
(520) UM20-
PVC4
INSTALL 1/0 UG IN DBL CIRCUIT TRENCH.
C 10321 WIRE (5) UR2-LIFT -30 5 (50) U-4/0-TPLEX
R 10323 P45-4 1967 234 ACSR 1/0 VC2-M 2 15 KVA 15 M2-11
R 234 (3) ACSR 4/0 VC1-2-M VG105
R VC9
R 10323RWIRE 234 ACSR 1/0 2
R 234 (3) ACSR 477
E 31018 P30-5 90 M2-11
R K11 26 (26) TPLEX 2
RETIRE #2 OH TPX AND OH RISER/WEATHERHEAD. REFEED MTR UG. CUTOFF TOP OF POLE ABOVE METER.
C 1PH XFMR#3 238 U-1/0 (2) UM6-1
(240) UM20-
PVC4
-2 U15 KVA 15 UM6-6 (2) UJ2-6-500
UM1-7NC
P-90-4
UG7 UJ2-8-500-B
UM22-P-90-
24-3-C
INSTALL 1/0 UG IN DBL CIRCUIT TRENCH.
C 31018 WIRE
(20) U-MA-
COMP
86 20 (20) U-4/0-TPLEX LB 2
C (20) UR2-SEC
C (20) UR2-LIFT
C UM22-P-90-2
INSTALL UG SECONDARY WIRE & CONDUIT TO SERVE EX MTR ON POLE.
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 11 of 65
41 0 41
Sheet No. 12 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10324 P45-4 1967 232 (3) ACSR 4/0 VC2-M 0 M2-11
R 232 ACSR 1/0 VC1-2-M
E 10325 93 (13) E2-2F78
R P40-5 1967 (6) E2-2F78 (2) F1-2
R (2) E1-2
R 10324RWIRE 231 (3) ACSR 477 0
R 231 ACSR 1/0
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 13 of 65
32 0 32
Sheet No. 14 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10326 P45-4 1967
241 ACSR 1/0 VC8-HB-M
OH-FUSE 40
CL
-3 M2-11
R 241 (3) ACSR 4/0 VA5-2-M
R UA1
R VC8-HBN-M
Customer Adding 18" fill to bring up to parking grade at transformer and meter location must be done before construction.
R 10326RWIRE 237 (3) ACSR 477 -3
R 237 ACSR 1/0
Sheet No. 15 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C 1PH SC#1 476 U-1/0 UM6-10 UM22-P-22-4 -3 UM6-6
C UM6-22 (2) UM12
UM3-14
(480) UM20-
C (3) UM6-1 UM22-P-45-4
INSTALL 1PH SECTOR CABINET. RETERMINATE EX. 1/0 UG IN NEW CABINET
E 54879 335 U-1/0-CIC UM6-1 (295) UR2-NT 87 U25 KVA UM6-6 (2) UJ2-6-500
E UM1-7NC UM12F UG7 UJ2-8-500-B
E
(295) U-MA-
(295) UR2-
R UM6-34
C UM6-1
C 1PH XFMR #4 185 U-1/0 UM6-1 UM12F 90 UG7 UM6-6 (2) UJ2-6-500
UM6-34
(200) UM20-
U15 KVA 15 UJ2-8-500-B
C UM1-7NC (185) UR2-NT
(185) U-MA-
(185) UR2-
R 10327 P40-5 1967 85 (4) E1-2 (3) F1-2
(16) E2-2F78
E 10328 P40-5 1991 120 M2-11
R 322 (2) ACSR 2 VA5-M 15 KVA 15 E1-2 F1-2 J2-5-250B
R UM5 VG105 M5-23-78 (2) J2-5-250
UM5
RETIRE EXISTING UM5 REROUTE EXISTING TPX TO NEW UG XFMR. RETIRE XFRM, POLE TOP ASSEMBLY, GUY, AND ANCHOR. INSTALL NEW UM5 TO REFEED OH TPX. CUTOFF TOP OF POLE.
C 10328 WIRE
CREW
HOURS
89 5 (5) U-4/0-TPLEX
C (5) UR2-LIFT
C UM24-P-C-3
PVC3
(3) UM22-
P-90-24-3
INSTALL SECONDARY WIRE TO EXISTING POLE PVID10328 TO REFEED OH SERVICE. EXTEND EX UG SERVICE TO NEW UG XFMR.
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 16 of 65
50 0 50
Sheet No. 17 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10330 P45-4 1967 236 (3) ACSR 4/0 VC1-2-M -29 M2-11
R 236 ACSR 1/0 VC2-M
R 10330RWIRE 233 (3) ACSR 477 -30
R 233 ACSR 1/0
R 10331 P45-4 1967
255 (3) ACSR 4/0 VA5-2-M
OH-FUSE-40
K
-1 M2-11
R 255 ACSR 1/0 VC1-2-M VM5-9L
Sheet No. 18 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10331RWIRE 256 ACSR 1/0 0
R 256 (3) ACSR 477
C SV#2 1720 (3) U-500
UM1-6CSG-
R2
(1720) UR2-
ST
9 UM6-6
P-90-6
C (6) BM53 UM22-P-45-6
C (4) UM12
(3440) UR2-
(1720) UM20-
(24) UM24-P-
SPB-6
(1720) U-MA-
C (2005) UO144
(3440) UM20-
INSTALL SPLICE VAULT. SPLICE GRANBY AND FRASER UG 500 CIRCUITS IN VAULT. INSTALL FO HANDHOLE, 144CT FO IN 2" ORANGE C, 2" ORANGE C SPARE. 250' STOARAGE LOOP IN FO HAND HOLE
C SV#2 WIRE 1730 (3) U-500
(1740) UM20-
PVC6
-2
C UM22-P-45-6
INSTALL UG 500 FOR FRASER CIRCUIT.
C 1PH SC#2 491 U-1/0 UM6-22 (2) UM12 -30 UM6-6
(3) UM6-1
(500) UM20-
P-45-4
C UM3-14
INSTALL 1PH SECTOR CABINET. INSTALL NEW 1/0 UG CIC TO NEW RISER POLE PVID10332
C 10332 WIRE 33 U-1/0-CIC (33) UR2-NT 89
C 31 U-1/0-CIC (33) UR2-LIFT
(33) U-MA-
INSTALL NEW 1/0 UG TO REFEED OH AT PVID10332
Sheet No. 19 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 10332 P45-5 1967 VA5-1-M 90 M2-11 E1-2 F1-2
R 33 ACSR 2 VA5-3-M
R 33 ACSR 4
C UA2
RETIRE OH WIRE, INSTALL NEW PRIMARY 1PH RISER TO REFEED OH LINE.
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 20 of 65
38 0 38
Sheet No. 21 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10335 P45-4 1967 275 (3) ACSR 4/0 VC1-2-M 0 M2-11
R 275 ACSR 1/0 VC2-M
R 10335RWIRE 275 (3) ACSR 477 0
R 275 ACSR 1/0
R 10336 P45-4 1967 241 ACSR 1/0 VC2-M 0 M2-11
R 241 (3) ACSR 4/0 VA5-2-M
R VC1-2-M
Sheet No. 22 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10336RWIRE 230 ACSR 1/0 0
R 230 (3) ACSR 477
C 1PH SC#3 517 U-1/0 (3) UM6-1
(3) UM22-
P-90-4
-1 UM6-6
UM6-22
(520) UM20-
C UM3-14 UM22-P-45-4
C UM1-7NC (2) UM12
C UM6-10 UM22-P-22-4
INSTALL 1PH IN DBL CIRCUIT TRENCH. INSTALL 1PH SECTOR.
R 10337 P40-5 1993 51 ACSR 4 VA5-M -91 M2-11
R 51 ACSR 2 UA2
C UM1-7RR (5) UR2-NT UM6-6
C UM6-28-1/0
INSTALL NEW 1PH SPLICE VAULT AT BASE OF POLE. SPLICE EX 1/0UG IN VAULT WITH NEW 1/0UG BORED ACROSS RD. RETIRE OH POLE AND WIRE XING RD.
C 10337 BORE 51 U-1/0
(60) U-BORE
4"
-91
BORE 1/0 IN 4"C XING CR5 TO SPLICE VAULT AT BASE OF PVID10337 - NEED PRICE FOR BORE
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 23 of 65
39 0 39
Sheet No. 24 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10339 P45-4 1967 264 ACSR 1/0 VC1-2-M 0 M2-11
R 264 (3) ACSR 4/0 VC2-M
R 10339RWIRE 274 (3) ACSR 477 0
R 274 ACSR 1/0
R 10340 P45-4 1967 264 (3) ACSR 4/0 VC1-2-M VM5-9 0 M2-11
R 264 ACSR 1/0 VA5-2-M
Sheet No. 25 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10340RWIRE 265 ACSR 1/0 0
R 265 (3) ACSR 477
C 1PH SC#4 528 U-1/0 (3) UM6-1 UM22-P-45-4 0 UM6-6
C UM6-10 UM22-P-22-4
(540) UM20-
C UM6-22 (2) UM12
INSTALL 1PH SECTOR REFEED PVID10341 W/UG 1/O
E 10341 P40-4 1999 VA6-1-M 97 M2-11 E1-2 F1-2
R 39 (2) ACSR 2 VA5-1-M
C UA2
RETIRE OH WIRE. INSTALL NEW RISER AND REFEED UG FROM 1PH SC#4
C 10341 WIRE 36 U-1/0
(40) UM20-
PVC4
C (36) UR2-LIFT
C UM22-P-90-4
C (36) UR2-NT
(36) U-MA-
TRENCH AND INSTALL UG 1/0 TO REFEED PVID10341.
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 26 of 65
Sheet No. 27 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10343 P45-4 1967 231 ACSR 1/0 VC2-M 1 M2-11
R 231 (3) ACSR 4/0 VC1-2-M
R 10343RWIRE 231 (3) ACSR 477 1
R 231 ACSR 1/0
R 10344 P45-4 1967 226 ACSR 1/0 VC2-M -1 M2-11
R 226 (3) ACSR 4/0 VC1-2-M
R 10344RWIRE 224 ACSR 1/0 -1
R 224 (3) ACSR 477
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 28 of 65
Sheet No. 29 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10345 P45-4 1967 231 (3) ACSR 4/0 VC1-2-M VM5-9LB 0 M2-11 E1-2 F1-2
R 231 ACSR 1/0 VC2-M
R VA5-2-M
R 10345RWIRE 234 (3) ACSR 477 0
R 234 ACSR 1/0
Sheet No. 30 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C 1PH SC#5 688 U-1/0 UM6-10 UM22-P-22-4 0 UM6-6
(700) UM20-
C UM6-22 UM22-P-45-4
C (3) UM6-1 (2) UM12
INSTALL 1PH SECTOR REFEED PVID10346 W/UG 1/O
E 10346 P40-5 2001 VA6-1-M 95 M2-11 E1-2 F1-2
R 34 (2) ACSR 2 VA5-1-M
C UA2
RETIRE OH WIRE. INSTALL NEW RISER AND REFEED UG FROM 1PH SC#5
C 10346 WIRE 32 U-1/0 (32) UR2-LIFT 93
(32) U-MA-
C UM22-P-90-4
C (32) UR2-NT
(32) UM20-
TRENCH AND INSTALL UG 1/0 TO REFEED PVID10346.
R 10348 P45-4 1967 231 (3) ACSR 4/0 VC1-2-M 2 M2-11
R 231 ACSR 1/0 VC2-M
R 10348RWIRE 231 ACSR 1/0 2
R 231 (3) ACSR 477
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 31 of 65
Sheet No. 32 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
Sheet No. 33 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C PME#2 2425 (3) U-500
(6)
UM6-3-500
(3)
UM6-28-500
-24 UM6-6
UM1-6CSG
(2425) U-MA-
UM3E-3
PMH9
(2425) UR2-
ST
(2440) UM20-
(5)
UM6-3-1/0
(5) UM12
BM55
UG-FUSE-20
0E
(8) BM53
(4850) UR2-
C (2475) UO144
C (144) HO1
(4860) UM20-
INSTALL PME-9. TERMINATE GRANBY CIRCUIT IN PME. SPLICE FRASER CRT IN VLT. N.OPEN FOR 1/0 FROM WEST. REFEED 1PH TAP TO SOUTH, 2 XFMR TO WEST, 1PH TAP XING RD TO NORTH, AND NEW 1PH TAP XING RD AND HEADING WEST
DOWN NORTH SIDE OF RD.INSTALL 144CT, FOHH, 2"C
C PME#2 WIRE 2425 (3) U-500
(2440) UM20-
PVC6
-24
INSTALL 3PH UG 500 FOR FRASER CIRCUIT. SPLICE IN SW VAULT.
R 10349 P45-4 1967 225 (3) ACSR 4/0 VC1-2-M 0 M2-11
R 225 ACSR 1/0 VC2-M
R 10349RWIRE 225 ACSR 1/0 0
R 225 (3) ACSR 477
R 10304 P45-4 1967 235 (3) ACSR 4/0 VC2-M VM5-9L 0 M2-11 E1-2 F1-2
235 ACSR 1/0 (2) VA5-2-M
OH-FUSE-40
K
R VC1-2-M
R 10304RWIRE 216 (3) ACSR 477 0
R 216 ACSR 1/0
C
PME#2
1PH WIRE
691 U-1/0
(700) UM20-
PVC4
1PH TIE, NORMAL OPEN FOR LINE FROM WEST
R 10309 P35-5 1980 22 (2) ACSR 2 VM3-10A 91 M2-11
R VA6-M
C 22 U-1/0-CIC UA2 E1-2F78 F1-3S
RETIRE OH WIRE, REPLACE 35' POLE. INSTALL NEW UG RISER AND UG 1/0 CABLE FROM PMH.
Sheet No. 34 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 10309.5 12 (2) ACSR 4 1
C P40-5 VA6-1-M M2-11
C VM3-10A
INSTALL NEW POLE IN LINE W/RELCOSER.
R 10305 P35-5 1980 50 (2) ACSR 4 VA1U-M -93 M2-11
R 10305 NEW 32 (2) ACSR 4 3
C P40-5 VA5-M M2-11 E1-2F78 F1-3S
C UA2
INSTALL NEW POLE W/1PH RISER, GUY, & ANC. REFEED UG FROM PMH
C 10305
NEW WIRE
88 U-1/0 UM22-P-90-4 -88
(100) UM20-
C (45) UR2-NT
C (45) UR2-LIFT
(45) U-MA-
INSTALL 1PH 1/0 UG IN JOINT TRENCH XING RD W/DBL CIRCUIT. CONT. TRENCH TO NEW POLE UP DRIVE PVID10305 NEW.
R 10350 P45-4 1967 112 (3) ACSR 4/0 M5-15 JU-QWEST -1 15 KVA 15 M2-11
R 112 ACSR 1/0 VOC1-2P (3) VM5-7 VG105
R M5-13
R UM5
TOP POLE ABOVE CENTURY LINK
R 10350RWIRE 131 (3) ACSR 477 -1
R 131 ACSR 1/0
C 1PH XFMR #5 113 U-1/0 UM1-7NC (5) UR2-LIFT -2 U15 KVA 15 UM6-6 UJ2-8-500-B
(2) UM6-1
(2) UJ2-6-500
C (5) UR2-NT
(120) UM20-
C U-BORE 4"
INSTALL NEW UG XFMR. EXPOSE EXISTING SECONDARY RETERMINATE IN NEW XFMR.- NEED PRICE FOR BORE.
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 35 of 65
44 0 44
Sheet No. 36 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10351 P45-4 1967 257 ACSR 1/0 VC1-2-M JU-QWEST 0 VG105 M2-11
R 257 (3) ACSR 4/0 VC2-M 15 KVA 15
RETIRE PRIMARY WIRE, XFMR AND POLE TOP. INSTALL DOUBLE PEDASTAL TO REFEED HOME AND SHOP SERVICES. TOP POLE ABOVE CENTURY LINK
R 10351RWIRE 256 ACSR 1/0 0
R 256 (3) ACSR 477
Sheet No. 37 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E MOP 117 F2S
R 9 (9) TPLEX 2
(5) UR2-LIFT
(30) U-350-
TPLEX
UM8-3A
RETIRE EXISTING METER WEATHERHEAD AND WIRE. INSTALL NEW DOUBLE PEDESTAL NEAR POLE AND REFEED RETERMINATE EXISTING SHOP SERVICE IN NEW PEDESTAL. rEFEED HOUSE METER UG FROM NEW PEDESTAL.
C 1PH XFMR#6 258 (3) U-1/0 UM6-34 UM12F 2 U15 KVA 15 UM6-6 UJ2-8-500-B
UM6-1
UG7 (2) UJ2-6-500
C (5) UR2-NT
(260) U-BORE
4"
INSTALL NEW UG XFMR TO SERVE UG SERVICE TO SHOP AND NEW UG SERVICE TO HOUSE.
C 1PH SC#6 436 U-1/0 UM3-14
(440) UM20-
PVC4
-8 UM6-6
C (3) UM6-1 (2) UM12
C UM1-7NC UM22-P-22-4
UM6-22
C UM6-10 UM22-P-45-4
INSTALL NEW SECTOR CABINET EAST OF DRIVEWAY TO REFFED PVID10355 UP DRIVEWAY WITH UG 1/0 CABLE.
R 10352 P45-4 0 271 ACSR 1/0 VOC1-2P VM5-9LB 0 M2-11 E1-2 F1-2S
R 271 (3) ACSR 4/0 VC9-1
R VA5-2-M
TOP POLE ABOVE CENTURY LINK
R 10352RWIRE 275 ACSR 1/0 0
R 275 (3) ACSR 477
R 10353 P30-5 1999 106 (2) ACSR 2 VA2-M -144 M2-11 E1-2 F1-2
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 38 of 65
41 0 41
Sheet No. 39 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10354 P40-5 1999 280 (2) ACSR 2 VA3-M 33 M2-11 E1-2 F1-2
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 40 of 65
35 0 35
Sheet No. 41 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 10355 P40-5 1999 33 M2-11
R 253 (2) ACSR 2 VA5-M 10 KVA 10 (2) E1-2 (2) F1-2
R VG105
C UM5 E1-2F12 F1-3S
RETIRE POLE TOP AND XFMR. CUTOFF TOP OF POLE ABOVE SECONDARY ADD GUY AND ANCHOR FOR SECONDARY
Sheet No. 42 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C 1PH XFMR#7 552 U-1/0-CIC UM6-1
(552) U-MA-
COMP
-69 UG7 UM6-6 (2) UJ2-6-500
C UM1-7NC (552) UR2-NT U15 KVA 15 UJ2-8-500-B
(552) UR2-
INSTALL NEW XFMR NEAR PVID10355.
C 10355 WIRE
(12) UM20-
FLEX3
135 5
(55) U-350-
TPLEX
INSTALL UG 350TPX SECONDARY TO REFEED OH ON PVID10355
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 43 of 65
46 0 46
Sheet No. 44 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 10357 P45-3 1967
293 (3) ACSR 4/0 VA5-2-M
OH-FUSE-40
K
0 M2-11
R 293 ACSR 1/0 VC2-M VM5-9L
R VC1-2-M JU-QWEST
TOP POLE ABOVE CENTURY LINK
R 10357RWIRE 250 ACSR 1/0 0
R 250 (3) ACSR 477
Sheet No. 45 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C 1PH XFMR#8 524 U-1/0 (2) UM6-1 UM20-PVC4 8 UG7 UM6-6 UJ2-8-500-B
C UM1-7NC UM12F U25 KVA 25 (2) UJ2-6-500
C UM22-P-90-3
24-3
R 12946 P35-5 2005 180 (2) ACSR 4 VA5-M -103 15 KVA 15 M2-11 E1-2 F1-2
R VG105
LB 2
C UM22-P-90-3
(2) CREW
MA-3
CUT OFF POLE ABOVE METER. REFEED SECONDARY W/350TPX IN 3"C. WILL NEED 3" LB. ONLY SHOW 2".
C 12946 WIRE
UM22-P-90-
24-3-C
-101 141
(175) U-350-
P-45-3
(140) UM20-
INSTALL UG SECONDARY ALONG DRIVEWAY TO REFEED METER ON PVID12946
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 46 of 65
40 0 40
Sheet No. 47 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 10358 P35-5 1953 JU-QWEST 80 M2-11
R 120 (2) ACSR 4 VA5-M VG105 E1-2 F1-2
R 15 KVA 15
C UM5
RETIRE XFMR AND POLE TOP. INSTALL SECONDARY RISER TO REFEED OH SECONDARY. TOP POLE OFF ABOVE SECONDARY
Sheet No. 48 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C 10358 WIRE
(2) UM24-P-
C-3
78 174
(211) U-350-
C U-BORE 3"
WILL NEED PRICE FOR BORE
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 49 of 65
42 0 42
Sheet No. 50 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
Sheet No. 51 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C SV#3 1373 (3) U-500
UM1-6CSG-
R2
(1373) U-MA-
COMP
-2 UM6-6
(24) UM24-P-
SPB-6
(4) BM53
(2746) UR2-
C UM22-P-22-6
C UM6-28-1/0
C (3) UM12
(1373) UR2-
ST
(2750) UM20-
(1380) UM20-
C (1650) UO144
INSTALL 3PH SPLICE VALUT. SPLICE UG 500 FOR GRANBY AND FRASER CRTS. INSTALL FO HANDHOLE, 144CT FO IN 2" ORANGE C W/2" ORANGE C SPARE AND 250' STORAGE LOOP IN FO VAULT
C SV#3 WIRE 1380 (3) U-500 UM22-P-90-6 -2
C UM20-PVC6
C UM22-P-22-6
E 10360 P45-4 1967 JU-QWEST 0 M2-11
R 272 ACSR 1/0 VC1-2-M 15 KVA 15
R 272 (3) ACSR 4/0 VC2-M VG105
C UM5
RETIRE OH WIRE, POLE TOP AND XFMR. INSTALL SECONDARY RISER TO REFEED SERVICE FROM NEW UG XFMR. TOP POLE OFF ABOVE SECONDARY
R 10360RWIRE 285 (3) ACSR 477 0
R 285 ACSR 1/0
C 1PH SV 298 U-1/0 UM1-7RR
(2) UM22-
P-90-4
0 UM6-6
P-45-4
(300) UM20-
C UM6-28-1/0
C 1PH XFMR #9 54 U-1/0 UM6-1
UM22-P-90-
24-3
90 UG7 UM6-6 (2) UJ2-6-500
C UM1-7NC UM12F U15 KVA 15 UJ2-8-500-B
(60) U-BORE
4"
C UM22-P-90-4
Sheet No. 52 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
INSTALL XFMR NEAR PVID10360. INSTALL NEW UG350TPX AND RISER TO REFFED OH SECONDARY.WILL NEED PRICE FOR BORE
C 10360 WIRE
(20) UM20-
PVC3
-144 5
(55) U-350-
INSTALL 350TPX TO REFEED SECONDARY ON PVID10360
R 10199 P50-5 1967 285 ACSR 1/0 VC1-2-M 0 M2-11
R 285 (3) ACSR 4/0 VC2-M
R 10199RWIRE 285 (3) ACSR 477 0
R 285 ACSR 1/0
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 53 of 65
45 0 45
Sheet No. 54 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
Sheet No. 55 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
C PME#3 727 (3) U-500
UM3E-3
PMH9
(739) UR2-ST 6 UM48-5
(739) UR2-
C UM6-25-1/0 UM22-P-90-6
C UM1-6CSG (2) UM12
(2) BM53
(740) UM20-
(739) U-MA-
(1480) UM20-
C (1005) UO144
INSTALL PME9. EXPOSE GRANBY UG500 AND SPLICE IN VLT WITH NEW UG GRANBY FDR. TERMINATE FRASER FDR IN PME. INSTALL NEW UG1/0 3PH EAST TO REFEED PVID40141. INSTALL NEW UG500 3PH DOWN CR TO REFEED
PVID42032.INSTALL FO HANDHOLE, 144CT FO IN 2" ORG C , 2"C SPA
C PME#3 WIRE 730 (3) U-500
(740) UM20-
PVC6
C UM22-P-45-6
C-6
C UM22-P-22-6
R 10200 P50-5 1967 280 (3) ACSR 4/0 VC2-M JU-MPEI 0 M2-11 (3) E2-2F78
R 280 ACSR 1/0 VC7-HB-M E2-2
R VC1-2-M
TOP POLE OFF LEAVE FOR CENTURY LINK
R 10200RWIRE 295 ACSR 1/0 0
R 295 (3) ACSR 477
R 10202 P45-4 1967
234 ACSR 1/0 UC5 0 M2-11
(7) M5-23-78
R 234 (3) ACSR 4/0 VC7-HBN-M
R VC7-FN-M
R VC7H-M
R 10202RWIRE 224 (3) ACSR 477 2
R 224 ACSR 1/0
R 10203 P40-4 1965
Unknown gs_span_guy
4 (4) E1-2 (4) F1-2
R 10201 P50-5 1967
Unknown gs_span_guy
-101 (5) E1-3 (4) F1-2
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 56 of 65
Sheet No. 57 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E UM20-PVC6 424 1 397
C U-1/0 6550 1 5967
C U-1/0 2332 3 669
C U-1/0-CIC 1068 1 857
C U-350-TPLEX 526 1 333
C U-4/0-TPLEX 125 1 53
C U-500 42 1 42
C U-500 44027 3 14042
C UO144 8660 1 7294
PRIMARY GUY & ANCHOR SECONDARY SERVICE
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
R 50882 P40-3 2018
301 (4) ACSR 1/0 VC7-FN-M
(3) OH-
FUSE-20K
-2 M2-11 (2) E1-3F78 F1-6P
R UC2
RETIRE 3PH OH. EXPOSE EXISTING 6" C. EXTEND NEW 6" C WEST TO PMH#3
Sheet No. 58 of 65
* STATION NUMBER POLE SPAN
FEET
WIRE SIZE PRIMARY UNIT MISC UNIT LINE
ANGLE
XFMR KVA GRND UNIT GUY LEAD ANCHOR UNIT SPAN
FEET
UNIT "J OR U" WIRE SIZE SPAN
FEET
UNIT "K
OR U"
WIRE SIZE METER OR LOOP
E 40141 UM1-6NC
(3) UM22-
P-90-6
-38 UM6-6
UM1-6NCL
(147) UM20-
120 (3) U-1/0
UM6-28-1/0
C 40141 WIRE 411 (3) U-1/0 (2) UM12 -15
(280) UM20-
INSTALL NEW 3PH UG 1/0 IN 6" C TO EXISTING PVID40141. 270' NEW 6" C TO INTERCEPT EXISTING 6" C AT PVID50882.
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Sheet No. 59 of 65
Sheet No. 60 of 65
Map Location:
Description: MPEI G 38229 CR 5 DOUBLE CIRCUIT OH-UG
County: GRAND Township: 1S
Substation: MT4 - Mettler 4 Feeder: Granby Phase: ABC
SO Number: Work Order #: 20220284
Staked By: Date:
Eng Review By: Date:
Released By: Date:
Const Comp By: Date:
Inspected By: Inspected By Date:
Comments:
CR 5 DOUBLE CIRCUIT OH TO UG PVID 38229
Directions:
Operations Notes
As-Built
Revised Employee #s Start Date Completed Date
Action Conductor Wire Feet No. of Wires
Pole Line
R ACSR 1/0 12804 1 12804
R ACSR 1/0 1200 4 301
R ACSR 2 1480 2 1056
R ACSR 2 84 1 84
R ACSR 4 84 1 84
R ACSR 4 704 2 382
R ACSR 4/0 884 1 884
R ACSR 4/0 18987 3 6329
R ACSR 477 22077 3 7359
R E2-2F78 16 1 17
R TPLEX 2 35 1 35
R U-1/0 484 3 120
R U-500 60 3 42
R UM20-PVC6 42 1 42
R Unknown gs_span_guy 85 1 86
E ACSR 4 24 2 12
E E2-2F78 6 0 7
E E2-2F78 13 1 13
E U-1/0 30 3 10
E U-1/0-CIC 335 1 335
E U-500 1967 3 563
E…