Central Michigan Correctional Facility - HVAC Improvements - Phase 1 - CD Drawings 25362Part-1.pdf

PDF 14 MB Posted

Attached to
472/25362. CTS; Central Michigan C. F. HVAC Imprv. PH I
Solicitation number
RFQ 171 260000000155 4
Issued by
Gogebic County, Michigan

About this file

This document comprises construction drawings and specifications for HVAC improvements at Central Michigan Correctional Facility, prepared by the State of Michigan Department of Technology, Management and Budget for the Department of Corrections. The project encompasses Phase 1 mechanical, electrical, and HVAC system upgrades across multiple facility buildings including West Administration, West Food Service, West Housing Units A-B, C-D, and G-H, and East Housing Units L-M and N-P. The scope includes replacement of boilers, installation of new air handling units, ductwork modifications, piping systems, controls integration, and condensing units. Work is divided into priority phases with the West Administration Building designated as highest priority, followed by East Education, West Food Service, and housing unit buildings. The drawings specify that boiler replacements must occur between May 15 and September 30, with all heating equipment fully operational by October 1; the contractor bears responsibility for temporary heating if this deadline is not met. Equipment must be in hand prior to demolition commencement, and the contractor must conduct pre-construction and post-construction testing and balancing of air handling units and associated terminal units.

The contractor is required to attend 6-month and 11-month post-construction warranty meetings with the engineer and owner, track and document recycled materials throughout the project, and provide two facility escorts during work. All work must conform to Michigan Department of Corrections standards and applicable codes including the Michigan Mechanical Code. The contractor shall install tamperproof fasteners in all inmate-accessible areas and coordinate boiler alarm connections to the facility's StarNet 2 system through a designated IT contact. Roof penetrations require new curbs and boots with water-tight sealing to maintain existing roof warranties held by Precision Roofing. The project requires coordination with existing building automation systems and future integration capabilities for all equipment. Specific mechanical notes address piping slopes, condensate drainage, equipment clearances, wall and ceiling patching and painting, and the installation of new equipment per manufacturer specifications to ensure service accessibility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL DRAWING INDEX

320 HUBBARD STREET

ST. LOUIS, MI 48880

FILE NUMBER: 472/25362.CTS

MATRIX PROJECT NUMBER: 250689.00MECHANICAL/ELECTRICAL ENGINEER

STATE OF MICHIGAN

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

FOR DEPARTMENT OF CORRECTIONS

CENTRAL MICHIGAN CORRECTIONAL FACILITY - HVAC IMPROVEMENTS PHASE 1

N SITE MAP

MECHANICAL DRAWING INDEX

WEST HOUSING UNIT E-F

WEST HOUSING UNIT G-H

WEST FOOD SERVICE

WEST ADMINISTRATION

EAST HOUSING UNIT L-M

EAST HOUSING UNIT N-P

EAST HOUSING UNIT J-K

EAST HOUSING UNIT Q-R

WEST HOUSING UNIT C-D

WEST HOUSING UNIT A-B

EAST EDUCATION

T-000

TITLE SHEET

BRH

MTJ

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

250689.00

M a t r ix

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

FA

C

IL

IT

IE

S

A N

D B

U

SI

N

ES

S

SE

R V

IC

ES

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

472/25362.CTS

funding code sheet description

CD Set 02/12/2026

GENERAL HVAC NOTES

1. LOCATE EXHAUST OUTLETS OF COMBUSTION EQUIPMENT

STACKS VENTS AT LEAST 10 FEET FROM OUTDOOR AIR

INTAKES.

2. ALL EXISTING SYSTEMS (INCLUDING EXHAUST FANS; AIR

HANDLING UNITS; PUMPS) THAT SERVES AREAS BEING

RENOVATED SHALL BE REBALANCED AS REQUIRED.

CONTRACTOR TO CONDUCT PRE-CONSTRUCTION TAB TO

VERIFY EXISTING AIR FLOWS AND HYDRONIC FLOW RATES ON

EXISTING WEST ADMINISTRATION AREA SERVED BY GROUND

MOUNTED AHU-2. CONTRACTOR ALSO TO CONDUCT

POST-CONSTRUCTION TAB TO VERIFY NEW AIR FLOWS AND

HYDRONIC FLOW RATES.

3. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION

THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.

4. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY

CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS

NEEDED.

5. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER

DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.

6. PROVIDE MANUAL AIR VENTS WITH 3/4" HOSE CONNECTION AT

ALL HIGH POINTS.

7. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.

8. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,

ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT

MAY AFFECT THE WORK.

9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING

THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"

CONDITION DURING CONSTRUCTION.

10. ALL WORK SHALL BE PERFORMED BY LICENSED

CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.

11. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,

LATEST APPLICABLE EDITION.

12. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.

13. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA

AIR GAP.

14. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR

SPECIFICATIONS THE MORE STRINGENT AND GREATER COST

ITEM SHALL BE USED.

15. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF

TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.

IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL

NECESSARY OFFSETS. INSTALL WORK IN MANNER TO

CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.

DO NOT SCALE FROM DRAWINGS.

16. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST

CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER

TO REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.

17. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO

OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED

THROUGHOUT THE PROJECT.

18. CONTRACTOR WILL HAVE 2 ESCORTS TO WORK WITH

THROUGH AT THE PROJECT.

19. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING

WALLS/CEILINGS AS NEEDED TO MATCH EXISTING WHERE

DEMOLITION AND/OR NEW WORK IS COMPLETED.

20. FIELD VERIFY EXISTING SIZE OF ALL DAMPER

ACTUATORS/CONTROL VALVES AND EQUIPMENT PRIOR TO

ORDERING.

21. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN

ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO

DISABLE THE FIRE ALARM.

22. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL

USE TAMPERPROOF SCREWS.

23. COMBUSTION AIR AND VENT ROOF PENETRATIONS TO INCLUDE

A CURB AND ROOF CURB BOOT. PATCH AND SEAL ROOF

PENETRATIONS TO BE WATER TIGHT. ALL ROOF

PENETRATIONS SHALL BE SEALED WATER TIGHT AND SHALL

MAINTAIN ALL EXISTING WARRANTIES.

24. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR POWERING

AND INSTALLATION OF ALL 24 VOLT CONTROL WIRING AND

CONTROL PANELS AS REQUIRED TO LOCALLY CONTROL ALL

HVAC AND PLUMBING EQUIPMENT PER THE SEQUENCE OF

OPERATIONS. ALL EQUIPMENT AND ACCESSORIES SHALL BE

CAPABLE OF CONNECTING TO A FACILITY WIDE BUILDING

AUTOMATION SYSTEM IN THE FUTURE. REFER TO MECHANICAL

SPECIFICATIONS AND COORDINATE WITH MECHANICAL

CONTRACTOR. ELECTRICAL CONTRACTOR IS RESPONSIBLE

FOR INSTALLING WIRING AND RACEWAY PER ELECTRICAL

SPECIFICATIONS. ALL INSTALLATIONS SHALL COMPLY WITH

MICHIGAN DEPARTMENT OF CORRECTIONS STANDARDS.

25. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING

AND INSTALLING ALL MECHANICAL/PLUMBING EQUIPMENT.

26. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL OTHER

HARDWARE REQUIRED TO WIRING THE HVAC AND PLUMBING

EQUIPMENT PER THE SEQUENCE OF OPERATIONS.

27. CONTRACTOR TO REINSTALL ATTIC INSULATION AROUND

AREAS WHERE NEW PIPING HAS BEEN INSTALLED OR IN AREAS

WHERE INSULATION HAS BEEN DISTURBED DURING

CONSTRUCTION.

28. ALL EQUIPMENT MUST BE IN HAND PRIOR TO ANY DEMOLITION

STARTING.

29. CONTRACTOR TO FLUSH ENTIRE HEATING HOT WATER SYSTEM

AND FILL/TREAT HYDRONIC LOOP AS REQUIRED TO MEET

BOILER REQUIREMENTS FOR EACH BUILDING WITH BOILERS

BEING REPLACED.

30. CONNECT ALL BOILER ALARM CONTACTS TO STARNET 2

SYSTEM THRU ETHERNET CONTACT CLOSURE. CONNECT TO

SECURITY IT RACK WITH PURPLE CAT-6 CABLE(S) AS REQUIRED

TO CONNECT TO STARNET 2 SYSTEM. CONTRACTOR TO HIRE

AND COORDINATE CONNECTION TO SECURITY IT RACK AND

PROGRAMMING OF THE ALARM POINTS ONTO THE STARNET 2

SYSTEM WITH BRET EMERSON FROM COMMTECH DESIGN

(PHONE#: (616)-446-4545).

31. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

32. CONTRACTOR TO REFER TO ALL ELECTRICAL CONSTRUCTION

DOCUMENTS AND DIVISION 26 SPECIFICATIONS FOR CONTROL

WIRING RACEWAYS. ALL CONTROL WIRING RACEWAYS ARE TO

MEET MDOC REQUIREMENTS.

MECHANICAL SYMBOLS LEGEND

HVAC PIPING SYMBOLS

HVAC PIPING

HVAC DUCTWORK

SD

F/S F/S s s

TEMPERATURE CONTROL SYMBOLS

M

P

M

H

S

T P T N

T

MISCELLANEOUS NOTES

HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES

MECHANICAL ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AC AIR COMPRESSOR

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

A.T.C. ARCHITECTURAL TRADES CONTRACTOR

B BOILER

B.A.S. BUILDING AUTOMATION SYSTEM

CAF COMBUSTION AIR FAN

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CHLR CHILLER

CHP CONSOLE HEAT PUMP

CONV CONVECTOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CWP CHILLED WATER PUMP

DB DRY BULB

DFU DUCT FURNACE

DIA DIAMETER

DN DOWN

DPR DAMPER

DS DUCT SILENCER

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

E.T.C. ELECTRICAL TRADES CONTRACTOR

EVR EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

FF FINISH FLOOR

FPM FEET PER MINUTE

FT FEET

FTR FINNED TUBE RADIATION

FU FURNACE

GAL GALLON

GFRH GAS FIRED RADIANT HEATER

GR GRILLE

H HUMIDIFIER

HC HEATING COIL

HD HEAD (FT)

HP HORSE POWER

HHP HORIZONTAL HEAT PUMP

HTG HEATING

HVAC HEATING, VENTILATION, & AIR CONDITIONING

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IAH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LH LATENT HEAT (MBH)

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH BTU PER HOUR (THOUSAND)

MIN MINIMUM

M.T.C. MECHANICAL TRADES CONTRACTOR

MDOC MICHIGAN DEPARTMENT OF CORRECTIONS

N.C. NOISE CRITERIA

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

P PUMP

PCR PUMPED CONDENSATE RETURN

PD PRESSURE DROP

RCP RADIANT CEILING PANEL

REQ'D REQUIRED

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLH RELIEF HOOD

RTU ROOF TOP UNIT

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SG SUPPLY GRILLE

SH SENSIBLE HEAT (MBH)

SM SHEET METAL

SQ. FT. SQUARE FEET

SST SATURATED SUCTION TEMPERATURE

STR STRAINER

TC TOTAL COOLING (MBH)

TCL TEMPERATURE CONTROL

T&P TEMPERATURE & PRESSURE RELIEF VALVE

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME BOX

VRH VARIABLE AIR VOLUME REHEAT BOX

FPVAV FAN POWERED VARIABLE AIR VOLUME BOX

V.F.D VARIABLE FREQUENCY DRIVE

ZD ZONE DAMPER

X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)

ITEM

EXISTING

CONDENSATE DRAIN

HEATING WATER SUPPLY

HEATING WATER RETURN

DIRECT EXPANSION

GATE VALVE

GAS COCK

CHECK VALVE

BALANCE COCK

CIRCUIT SETTER

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

GLOBE VALVE

BALL VALVE

SOLENOID VALVE

EXPANSION VALVE WITH

THERMOSTATIC BULB

PLUG VALVE

BUTTERFLY VALVE

RELIEF VALVE

HOSE & DRAIN END VALVE

PRESSURE RELIEF VALVE

PRESSURE REDUCING VALVE

TRIPLE DUTY VALVE

GAS PRESSURE REGULATOR

STRAINER (BLOW-OFF)

FLOW DIRECTION

PIPING DROP

PIPING RISE

INLINE PIPING DROP

INLINE PIPING RISE

PIPING TEE

PIPING ELBOW

THERMOMETER

PUMP

UNION

PIPE ANCHOR

PIPE GUIDE

BACK FLOW PREVENTER

PIPE CAP

PIPE BREAK

THERMOMETER WELL

EXPANSION LOOP

EXPANSION COMPENSATOR

FLOAT & THERMOSTATIC STEAM TRAP

INVERTED BUCKET STEAM TRAP

THERMOSTAT

PROGRAMMABLE THERMOSTAT

THERMOSTAT (W/ NIGHT SETBACK)

ROOM SENSOR

HUMIDISTAT

PRESSURE GAUGE

DAMPER (ELECTRIC OPERATION)

DAMPER (PNEUMATIC OPERATION)

DAMPER BLADES

SUPPLY AIR DUCT

EXIST SUPPLY AIR DUCT

RETURN AIR DUCT

EXIST RETURN AIR DUCT

OUTSIDE AIR DUCT

EXIST OUTSIDE AIR DUCT

EXHAUST AIR DUCT

EXIST EXHAUST AIR DUCT

SUPPLY AIR DUCT RISER

RETURN AIR DUCT RISER

OUTSIDE AIR DUCT RISER (AS NOTED)

EXHAUST AIR DUCT

INSULATED DUCTWORK (AS NOTED)

SUPPLY AIR DIFFUSER (SQUARE)

SUPPLY AIR DIFFUSER (INLINE)

SURFACE MTD. GRILLE

SUPPLY AIR DIFFUSER (ROUND)

CONICAL TAKE-OFF

CONICAL TAKE-OFF W/ DAMPER

BALANCE DAMPER

RETURN AIR DUCT BOOT

ECCENTRIC REDUCER

CONCENTRIC REDUCER

VERTICAL FIRE DAMPER

HORIZONTAL FIRE DAMPER

VERTICAL SMOKE DAMPER

HORIZONTAL SMOKE DAMPER

VERTICAL FIRE / SMOKE DAMPER

HORIZONTAL FIRE / SMOKE DAMPER

DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,

PROVIDED & WIRED BY E.T.C.

UNIT HEATER

CEILING EXHAUST FAN

ROOF MOUNTED EXHAUST FAN

DEMOLITION

POINT OF CONNECTION BETWEEN NEW AND

EXISTING

POINT OF EXISTING TO REMAIN AND EXISTING

TO BE REMOVED

INDICATES PLAN NOTE

INDICATES DEMOLITION NOTE

DETAIL BUBBLE

DETAIL NUMBER

PAGE LOCATION INDICATES

DIRECTION OF DETAIL SECTION

X

X

XX

XXXX

XX

XXXX

SA

OA

X-OA

X-EA

EA

X-SA

X-RA

RA

HR

CD

HS

TAG CFM

NECK REMARKS

SIZE

BT

FT

SD-1 250

8"ø ---

1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING

DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING

STRUCTURE, EQUIPMENT FURNISHED AND ALL OTHER TRADES PRIOR TO

DEMOLITION AND CONFORM TO MDOC STANDARDS.

2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,

AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,

CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES

HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED AND

CONFORMING TO MDOC STANDARDS.

3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,

UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,

STATE FIRE INSURANCE REGULATION BODY, NFPA, MDOC STANDARDS, OR

OTHERS. THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT

INDICATED ON THE DRAWING AND SPECIFICATIONS .

4. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.

5. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY

KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.

6. PATCH AND REPAIR ALL FLOOR AND WALL SURFACES LEFT DAMAGED OR

INCOMPLETE FROM REMOVAL OF EXISTING PARTITIONS, MILLWORK,

CASEWORK, OR OTHER FIXED ACCESSORIES AND EQUIPMENT WITH

MATERIALS TO MATCH EXISTING, AS ACCEPTABLE TO THE ARCHITECT.

7. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL

ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE

DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE

REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR

RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE

NEW WORK AS SHOWN.

8. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE

REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO

FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF

THIS WORK.

9. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER/TENANT PRIOR TO

COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND

APPROVAL OF THE LOCAL CODE JURISDICTIONS AND CONFORM TO MDOC

STANDARDS.

10. ASBESTOS ABATEMENT: CONTRACTOR SHALL NOTIFY BUILDING

REPRESENTATIVE IMMEDIATELY WHEN AND IF ANY ITEMS ARE ENCOUNTERED

THAT IN ANY WAY, SHAPE, OR FORM APPEAR TO BE HAZARDOUS OF NATURE.

ASBESTOS ABATEMENT IS NOT PART OF THE SCOPE OF THE DESIGN

PROFESSIONALS DOCUMENTATION OR RESPONSIBILITY TO SURVEY, IDENTIFY,

OR FOR CONSULTATION OF PROPER DISPOSAL.

11. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN

APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.

12. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED

IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE

CONTRACTOR.

13. TEMPORARY LIGHTING AND POWER SHALL BE PART OF THE SCOPE OF THIS

WORK; SEE ELECTRICAL.

14. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING

REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE

DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.

15. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

GENERAL DEMOLITION NOTESPROJECT PHASING

1. BOILERS TO BE REPLACED FROM MAY 15TH THROUGH

SEPTEMBER 30TH.

2. EXISTING EQUIPMENT IS TO REMAIN OPERATIONAL UNTIL

NEW EQUIPMENT IS RECEIVED AND READY TO BE INSTALLED.

3. ALL HEATING EQUIPMENT IS TO BE FULLY OPERATIONAL BY

OCTOBER 1ST. IF NOT, CONTRACTOR IS RESPONSIBLE FOR

PROVIDING TEMPORARY HEATING UNTIL THE HEATING

SYSTEM IS FULLY FUNCTIONING. CONTRACTOR TO

COORDINATE WITH PROJECT TEAM REGARDING IMPENDING

COLD WEATHER.

4. PROJECT TO BE PHASED AS REQUIRED TO DEAL WITH HIGH

PRIORITY BUILDINGS FIRST. BUILDINGS LISTED BELOW FROM

HIGH PRIORITY AT THE TOP TO LOWER PRIORITY AT THE

BOTTOM.

4.1. WEST ADMINISTRATION BUILDING

4.2. EAST EDUCATION BUILDING

4.3. WEST FOOD SERVICE BUILDING

4.4. EAST AND WEST HOUSING UNIT BUILDINGS

DX

M-100

MECHANICAL SYMBOLS,

NOTES, AND

ABBREVIATIONS

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

250689.00

M a t r ix

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

FA

C

IL

IT

IE

S

A N

D B

U

SI

N

ES

S

SE

R V

IC

ES

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

472/25362.CTS

funding code sheet description

CD Set 02/12/2026

BRH

MTJ

X-SD 250

8"Ø TYP. 2

X-SD 225

8"Ø ---

X-SD 150

8"Ø ---

X-SD 150

8"Ø ---

X-SD 200

8"Ø TYP. 2

X-SD 125

8"Ø ---

X-SD 110

6"Ø ---

X-SD 25

6"Ø ---

X-SD 100

6"Ø TYP. 2

X-SD 125

6"Ø ---

X-SD 125

6"Ø ---

X-SD 150

8"Ø ---

X-SD 300

10"Ø TYP. 2

X-SD 150

8"Ø ---

X-SD 200

8"Ø TYP. 2

X-SD 50

6"Ø ---

X-SD 50

6"Ø ---

X-SD 150

8"Ø ---

X-SD 50

6"Ø ---

X-SD 100

6"Ø ---

X-SD 25

6"Ø ---

X-SD 100

6"Ø ---

X-SD 25

6"Ø TYP. 2

X-SD 125

6"Ø ---

X-SD 50

6"Ø ---

X-SD 50

6"Ø ---

X-SD 125

6"Ø ---

X-SD 125

6"Ø ---

X-SD 150

6"Ø ---

X-SD 225

8"Ø TYP. 2

X-SD 150

8"Ø TYP. 2

X-SD 250

8"Ø ---

X-SD 300

10"Ø TYP. 2

X-SD 200

8"Ø --- X-SD 50

6"Ø ---

X-SD 125

6"Ø ---

X-SD 200

8"Ø TYP. 2

X-SD 50

6"Ø ---

X-SD 250

8"Ø ---

X-SD 250

8"Ø

X-EF

X-EG 75

X-EG 75

X-RP

X-RP X-RP

X-RP

X-RP

X-RP X-RP

X-RP

X-RP

X-RP X-RP

X-RP

X-RP

X-VAV-A43

X-VAV-A43

X-VAV-A35

X-VAV-A34

X-VAV-A33

X-VAV-A24

X-VAV-A54

X-VAV-A30

X-VAV-A54

X-VAV-A51

X-VAV-A21

X-VAV-A20

X-HC

X-AHU-2

X-FCU

X-RP

X-VAV-A36

X-RG

24"x4"

X-6"x12" SA

X-10"x12" SA X-12"x10" RA

X-RG ---

24"x8" ---

X-8"x14" SA

X-10"x8" SA

X-12"x10"

SA

X-18"x14" RA

X-16"x12"

RA

X-RG ---

24"x8" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x12" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-8"x10" SA X-10"x10" SA X-14"x10" SA

X-12"x10" RA

X-16"x14" RA

X-12"x8" RAX-8"x8" RA

X-10"x6" RA

X-10"x6" RA

X-12"x12" RA X-12"x12" SA

X-14"x10" SA

X-8"x10" SA

X-8"x8" SA

X-6"x8" SA

X-14"x12" SA

X-12"x10" SA

X-8"x10" SA

X-10"x10" RA

X-8"x8" RA

X-14"x10" RA

X-14"x12" RA

X-16"x12" RA

X-16"x12" RA

X-32"x22" RA DNX-24"x20" SA

DN

X-22"x18" RA

X-24"x18" RA

X-24"x20" RA

X-32"x22" RA

X-10"x8" SA

X-10"x8" SA

X-12"x10" SA

X-6"x8" SA

X-8"x8" SA

X-6"x8" SA X-10"x8" SA

X-10"x10" SA

X-10"x8" SA X-6"x6" RAX-TG ---

24"x4" TYP. 2

X-10"x10" SA

X-10"x10" SA

X-10"x10" SA

X-12"x12" SA

X-10"x10" RA

X-8"x6" RA

X-14"x10" RA

X-12"x12" SAX-6"x12" SAX-12"x10" SA

X-10"x10"

SA

X-10"x8" SA

X-6"x8" SA

X-16"x14" SA

X-18"x16" SA

X-18"x18" SA

X-20"x20" SA

X-22"x20" SA

X-8"x6" RA

X-8"x6" RA

X-8"x6" RA

X-6"x6" RA

X-6"x6" RA X-10"x8" RA

X-6"x6" RA

X-6"x8" SA

X-10"x10" SA

M-310

VISITING

A41

X-SD 25

6"Ø TYP. 2

X-AC

X-AC

STOR.

A23

DENTAL SUITE

A24

OFFICE

A54

MEDICAL SUITE

A25

PSYCHIARTY

A26

NURSE SUPERVISOR

A51

EXAM WAITING

MED. PASS

A32

HOLDING

A50

HOLDING

A49

VESTIBULE

A52

CONTROL

A35

ELECTRICAL

A48

DEPUTY

SUPERINTENDENT

A42

ASSISTANT

DEPUTY

A43

ASSISTANT

DEPUTY

A44

DEPUTY

SUITE

A45

CORR.

A36

VIDEO

HEARINGS

EMERGENCY

A33

VENDING

A22

STORAGE

CONTROL

BUBBLE

A21

CORRIDOR

A20

VESTIBULE

A59

CORRIDOR

A34

INTERVIEW

A37

SHAKE

DOWN

A38 TOILET

A35

TOILET

A35

SOILED

UTILITY

A29

CLEAN

UTILITY

A55

ELEC.

A56

JANITOR

A28

TOILET

A27

CENTRAL SUPPLY

& STORAGE

A30

CORRIDOR

A47

VISITING

A56

VISITING

A57

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S S

S

S

S S

S S

X-RG ---

24"x4" ---

X-6"x6" RA

X-EF

X-12"x10" RA

X-EF

X-EF

X-EF

M-800

X-POWER EXHAUST 4

X-G DNX-G

X-CONCRETE PAD

NOT IN SCOPE

M-400

X-SD 250

8"Ø TYP. 2

X-SD 225

8"Ø ---

X-SD 150

8"Ø ---

X-SD 150

8"Ø ---

X-SD 200

8"Ø TYP. 2

X-SD 125

8"Ø ---

X-SD 110

6"Ø ---

X-SD 25

6"Ø ---

X-SD 100

6"Ø TYP. 2

X-SD 125

6"Ø ---

X-SD 125

6"Ø ---

X-SD 150

8"Ø ---

X-SD 300

10"Ø TYP. 2

X-SD 150

8"Ø ---

X-SD 200

8"Ø TYP. 2

X-SD 50

6"Ø ---

X-SD 50

6"Ø ---

X-SD 150

8"Ø ---

X-SD 50

6"Ø ---

X-SD 100

6"Ø ---

X-SD 25

6"Ø ---

X-SD 100

6"Ø ---

X-SD 25

6"Ø TYP. 2

X-SD 125

6"Ø ---

X-SD 50

6"Ø ---

X-SD 50

6"Ø ---

X-SD 125

6"Ø ---

X-SD 125

6"Ø ---

X-SD 150

6"Ø ---

X-SD 225

8"Ø TYP. 2

X-SD 150

8"Ø TYP. 2

X-SD 250

8"Ø ---

X-SD 300

10"Ø TYP. 2

X-SD 200

8"Ø --- X-SD 50

6"Ø ---

X-SD 125

6"Ø ---

X-SD 200

8"Ø TYP. 2

X-SD 50

6"Ø ---

X-SD 250

8"Ø ---

X-SD 250

8"Ø

X-EF

X-EG 75

X-EG 75

X-RP

X-RP X-RP

X-RP

X-RP

X-RP X-RP

X-RP

X-RP

X-RP X-RP

X-RP

X-RP

X-VAV-A43

X-VAV-A43

X-VAV-A35

X-VAV-A34

X-VAV-A33

X-VAV-A24

X-VAV-A54

X-VAV-A30

X-VAV-A54

X-VAV-A51

X-VAV-A21

X-VAV-A20

X-HC

X-FCU

X-RP

X-VAV-A36

X-RG

24"x4"

X-6"x12" SA

X-10"x12" SA X-12"x10" RA

X-RG ---

24"x8" ---

X-8"x14" SA

X-10"x8" SA

X-12"x10"

SA

X-18"x14" RA

X-16"x12"

RA

X-RG ---

24"x8" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x12" ---

X-RG ---

24"x4" ---

X-RG ---

24"x4" ---

X-RG ---

24"x8" ---

X-RG ---

24"x8" ---

X-RG ---

24"x4" ---

X-8"x10" SA X-10"x10" SA X-14"x10" SA

X-12"x10" RA

X-16"x14" RA

X-12"x8" RAX-8"x8" RA

X-10"x6" RA

X-10"x6" RA

X-12"x12" RA X-12"x12" SA

X-14"x10" SA

X-8"x10" SA

X-8"x8" SA

X-6"x8" SA

X-14"x12" SA

X-12"x10" SA

X-8"x10" SA

X-10"x10" RA

X-8"x8" RA

X-14"x10" RA

X-14"x12" RA

X-16"x12" RA

X-16"x12" RA

X-32"x22" RA DNX-24"x20" SA

DN

X-22"x18" RA

X-24"x18" RA

X-24"x20" RA

X-32"x22" RA

X-10"x8" SA

X-10"x8" SA

X-12"x10" SA

X-6"x8" SA

X-8"x8" SA

X-6"x8" SA X-10"x8" SA

X-10"x10" SA

X-10"x8" SA X-6"x6" RAX-TG ---

24"x4" TYP. 2

X-10"x10" SA

X-10"x10" SA

X-10"x10" SA

X-12"x12" SA

X-10"x10" RA

X-8"x6" RA

X-14"x10" RA

X-12"x12" SAX-6"x12" SAX-12"x10" SA

X-10"x10"

SA

X-10"x8" SA

X-6"x8" SA

X-16"x14" SA

X-18"x16" SA

X-18"x18" SA

X-20"x20" SA

X-22"x20" SA

X-8"x6" RA

X-8"x6" RA

X-8"x6" RA

X-6"x6" RA

X-6"x6" RA X-10"x8" RA

X-6"x6" RA

X-6"x8" SA

X-10"x10" SA

VISITING

A41

X-SD 25

6"Ø TYP. 2

X-AC

X-AC

STOR.

A23

DENTAL SUITE

A24

OFFICE

A54

MEDICAL SUITE

A25

PSYCHIARTY

A26

NURSE SUPERVISOR

A51

EXAM WAITING

MED. PASS

A32

HOLDING

A50

HOLDING

A49

VESTIBULE

A52

CONTROL

A35

ELECTRICAL

A48

DEPUTY

SUPERINTENDENT

A42

ASSISTANT

DEPUTY

A43

ASSISTANT

DEPUTY

A44

DEPUTY

SUITE

A45

CORR.

A36

VIDEO

HEARINGS

EMERGENCY

A33

VENDING

A22

STORAGE

CONTROL

BUBBLE

A21

CORRIDOR

A20

VESTIBULE

A59

CORRIDOR

A34

INTERVIEW

A37

SHAKE

DOWN

A38 TOILET

A35

TOILET

A35

SOILED

UTILITY

A29

CLEAN

UTILITY

A55

ELEC.

A56

JANITOR

A28

TOILET

A27

CENTRAL SUPPLY

& STORAGE

A30

CORRIDOR

A47

VISITING

A56

VISITING

A57

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S S

S

S

S S

S S

X-RG ---

24"x4" ---

X-6"x6" RA

X-EF

X-12"x10" RA

X-EF

X-EF

X-EF

X-G DN

X-CONCRETE PAD

NOT IN SCOPE

AHU-25 6

M-800 1-1/4" G

POWER EXHAUST 5

32"x22" RA 24"x20" SA

CONCRETE PAD5

C

M-400

X-AC

X-1/2"

T

X-AC

X-CD PUMP

X-DX

X-DX

X-CU X-

DX

X-

DX

X-CU

X-CONCRETE PAD

3 3

X-SECURITY

CONTROLLER

X-DX

X-DX

X-CONTROL PANEL

X-CD

X-1/2" CD

X-1/2" CD

X-IT RACK

X-IT RACK

X-IT RACK

X-CD

X-DX

X-DX

EXISTING CONDENSING UNIT, CONTROLS, CONTROL WIRING, DX PIPING, CONDENSATE

PIPING, CONDENSATE PUMP, CONCRETE PAD, AND ALL ASSOCIATED ACCESSORIES TO

REMAIN.

EXISTING CONTROL PANEL, CONTROLS, CONTROL WIRING AND ALL ASSOCIATED

ACCESSORIES TO REMAIN.

DISCONNECT, REMOVE, AND DEMO EXISTING SPLIT SYSTEM EVAPORATOR,

CONDENSING UNIT, THERMOSTAT, CONTROLS, CONTROL WIRING, DX PIPING,

CONDENSATE PIPING, AND ALL ASSOCIATED ACCESSORIES. CONTRACTOR TO PATCH,

PRIME, AND PAINT EXISTING WALL PENETRATIONS AS REQUIRED TO MATCH EXISTING

AND SEAL WATER TIGHT.

DISCONNECT, REMOVE, AND DEMO EXISTING ROOFTOP UNIT, CURB, POWER EXHAUST,

AND ALL ASSOCIATED ACCESSORIES. EXISTING CONCRETE PAD TO REMAIN. DEMO

EXISTING DUCTWORK, GAS PIPING, AND ALL ASSOCIATE ACCESSORIES AS REQUIRED

FOR INSTALLATION OF NEW ROOFTOP UNIT AND POWER EXHAUST IN THE SAME

LOCATION. COMPLETE A PRE-TEST, AIR BALANCE, AND HYDRONIC FLOW BALANCE OF

THE X-AHU-2 (SUPPLY, RETURN AND OUTSIDE AIR) AND ALL TERMINAL UNITS

ASSOCIATED WITH X-AHU-2 AND THE AREA THAT IT SERVES (INCLUDING RADIANT

HEATING PANELS) BEFORE DEMOLISHING UNIT.

DEMOLITION NOTES

GENERAL DEMOLITION NOTES

1. CONTRACTOR TO PATCH, PRIME, AND PAINT ALL WALL/CEILINGS AS REQUIRED

AFTER ALL DEMOLITION/NEW WORK IS COMPLETED. CONTRACTOR TO SEAL ALL

EXTERIOR WALL PENETRATIONS TO MATCH EXISTING AND SEAL WATER TIGHT.

2. COMPLETE A HYDRONIC PRE-TEST ON CFMS (MAX & MIN), GPMS AND

TEMPERATURES OF ALL VARIABLE AIR VOLUME BOXES AND ALL RADIANT CEILING

PANELS PRIOR TO DEMOLISHING X-AHU-2.

3. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

INSTALL NEW WALL MOUNTED AC UNIT, CONDENSING UNIT, THERMOSTAT,

CONTROL WIRING, CONTROLS, DX PIPING, CONDENSATE PIPING, AND ALL

ASSOCIATED ACCESSORIES IN LOCATION SHOWN PER MANUFACTURER'S

INSTALLATION INSTRUCTIONS. CONNECT NEW SPLIT SYSTEM TO EXISTING

DDC CONTROL SYSTEM. MODIFY EXISTING BAS FRONT END GRAPHICS AS

REQUIRED TO INTEGRATE NEW SPLIT SYSTEM. CONDENSING UNIT TO BE

MOUNTED ON A MANUFACTURE PROVIDED UNISTRUT STAND FASTENED

TO EXISTING/NEW CONCRETE PAD. CONDENSING UNIT TO BE INSTALLED

TO ACCOMMODATE ALL MANUFACTURER RECOMMENDED CLEARANCES.

ROUTE NEW DX PIPING AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOWN. DX PIPING TO PENETRATE EXISTING EXTERIOR WALL.

NEW EXTERIOR WALL PENETRATIONS ARE TO BE PATCHED TO MATCH

EXISTING AND SEAL WATER TIGHT. DX PIPING DROPS TO THE

EVAPORATOR ARE TO BE SURFACE MOUNTED ON THE WALL.

SUPPORT REFRIGERANT PIPING WITH PIPE SUPPORTS BASED ON MIRO

#5-RAH-7 OR APPROVED EQUIVALENT. SPACE PIPING SUPPORTS PER

MANUFACTURER'S RECOMMENDATIONS.

ROUTE NEW CONDENSATE PIPING AND ALL ASSOCIATED ACCESSORIES IN

THE LOCATION SHOWN. CONDENSATE PIPING TO PENETRATE EXISTING

EXTERIOR WALL. NEW EXTERIOR WALL PENETRATIONS ARE TO BE

PATCHED TO MATCH EXISTING AND SEAL WATER TIGHT. CONDENSATE

PIPING TO TERMINATE 24" ABOVE EXISTING GRADE.

FURNISH AND INSTALL GRADE MOUNTED ROOFTOP UNIT ON EXISTING

CONCRETE PAD AND MANUFACTURER PROVIDED CURB. INSTALL NEW

DUCTWORK, GAS PIPING, CONTROLS, POWERED EXHAUST, AND ALL

ASSOCIATED ACCESSORIES AS REQUIRED FOR A COMPLETE AND

OPERABLE SYSTEM. ADD ADDITIONAL DUCTWORK SUPPORTS AND

EQUIPMENT SUPPORTS AS REQUIRED. INSTALL NEW CONCRETE PAD AS

SHOWN EXTENDED TO BUILDING AS REQUIRED TO NOT ALLOW GRASS

UNDER DUCTWORK. CONNECT ROOFTOP UNIT TO EXISTING CONTROL

SYSTEM AS REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM.

COMPLETE A POST-TEST AND AIR BALANCE OF THE AHU-2 (SUPPLY,

RETURN AND OUTSIDE AIR) AND ALL TERMINAL UNITS ASSOCIATED WITH

AHU-2 .

REGRADE AND SEED AROUND NEW CONCRETE PAD TO MATCH EXISTING

GRADE.

MECHANICAL KEY NOTES

GENERAL MECHANICAL NOTES

1. CONTRACTOR TO MODIFY EXISTING INTERIOR WALLS AS REQUIRED TO

INSTALL NEW WALL MOUNTED EVAPORATOR, THERMOSTAT, CONTROL WIRING,

DX PIPING, CONDENSATE PIPING, AND ALL ASSOCIATED ACCESSORIES. AFTER

ALL NEW WORK IS COMPLETED, CONTRACTOR TO PATCH, PRIME, AND PAINT

WALLS AS REQUIRED TO MATCH EXISTING.

2. CONTRACTOR TO MODIFY EXISTING EXTERIOR WALL AS REQUIRED TO

PENETRATE AND INSTALL NEW DX PIPING AND CONDENSATE PIPING. AFTER

NEW DX PIPING AND CONDENSATE PIPING IS INSTALLED, CONTRACTOR TO

PATCH, PRIME, AND PAINT EXISTING WALL AS REQUIRED TO MATCH EXISTING

AND SEAL WATER TIGHT.

3. CONTRACTOR TO REMOVE AND REINSTALL EXISTING CEILING GRID AND

CEILING TILES AS REQUIRED TO COMPLETE THEIR WORK. THE CONTRACTOR IS

RESPONSIBLE FOR THE REPLACEMENT OF BROKEN/DAMAGED CEILING TILES.

4. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURE'S INSTALLATION

INSTRUCTIONS AND MAINTAIN PROPER CLEARANCES.

5. INSTALL 0.020" THICK ALUMINUM, STUCCO EMBOSSED JACKET AROUND ALL

EXTERIOR ROUTED REFRIGERANT PIPING.

6. EXTEND EXISTING CONCRETE PAD AS REQUIRED TO INSTALL NEW EXTERIOR

CONDENSING UNITS PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS

AND MAINTAIN ALL REQUIRED EQUIPMENT CLEARANCES. CONCRETE PAD TO

MATCH THICKNESS OF EXISTING CONCRETE PAD AND EXTEND ATLEAST 4"

PAST CU-2.

7. COMPLETE A HYDRONIC POST-TEST ON CFMS (MAX & MIN), GPMS AND

TEMPERATURES OF ALL VARIABLE AIR VOLUME BOXES AND ALL RADIANT

CEILING PANELS POST INSTALLATION OF AHU-2.

8. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

X-1/2"

X-CD PUMP

X-DX

X-DX

X-CU

X-CONCRETE PAD

X-SECURITY

CONTROLLER

X-DX

X-DX

X-CONTROL PANEL

X-CD

X-1/2" CD

X-IT RACK

X-IT RACK

X-IT RACK

X-CD

X-DX

X-DX

AC-1

CU-1

DX

T

AC-1

3/4" CD DN

DX

CU-2

DX

3 PIPE SUPPORT

(TYP.)

DX

AC-2

3/4" CD DN

CONCRETE PAD1

T

AC-21

M-400

WEST ADMINISTRATION

BUILDING - FIRST FLOOR

PLAN - MECHANICAL

DEMOLITION/NEW

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

250689.00

M a t r ix

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

FA

C

IL

IT

IE

S

A N

D B

U

SI

N

ES

S

SE

R V

IC

ES

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

472/25362.CTS

funding code sheet description

CD Set 02/12/2026

N WEST ADMINISTRATION BUILDING - FIRST FLOOR PLAN - MECHANICAL DEMOLITION

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N WEST ADMINISTRATION BUILDING - FIRST FLOOR PLAN - MECHANICAL NEW

SCALE: 1/8" = 1'-0"

0 1 5 10 20

BRH

MTJ

WEST ADMINISTRATION BUILDING - ENLARGED

ELECTRICAL ROOM - MECHANICAL DEMOLITION

SCALE: 1/2" = 1'-0"

WEST ADMINISTRATION BUILDING - ENLARGED

ELECTRICAL ROOM - MECHANICAL NEW

SCALE: 1/2" = 1'-0"

DISCONNECT, REMOVE, AND DEMO EXISTING BOILER, FLUE, BOILER PUMP,

CONTROLS, CONTROL WIRING, CONCRETE PAD, PIPING, VALVES, BOILER

SUPPORT FRAME, AND ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.

CONTRACTOR TO REMOVE COMMON VENT THROUGH ROOF AND PATCH,

PRIME, AND PAINT CEILING AS REQUIRED TO MATCH EXISTING. CONTRACTOR

TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL WATER TIGHT, AND

MAINTAIN ANY EXISTING ROOF WARRANTIES.

DISCONNECT, REMOVE, AND DEMO EXISTING HEATING SUPPLY PIPING,

HEATING RETURN PIPING, GAS PIPING, VALVES, FITTINGS, AND ALL

ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN. MODIFY EXISTING

PIPING AS REQUIRED FOR NEW CONNECTIONS SHOWN ON NEW DRAWING.

DEMOLITION NOTES

GENERAL DEMOLITION NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. ALL EQUIPMENT, PIPING, CONTROLS, CONTROL WIRING, CONCRETE PADS,

AND ASSOCIATED ACCESSORIES TO REMAIN AND BE REUSED UNLESS

OTHERWISE NOTED.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL

WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER

DEMOLITION/NEW WORK IS COMPLETE.

4. EXISTING ZONE PUMPS AND ALL CONTROLS ARE TO REMAIN.

5. DEMOILSH EXISTING PIPING AS REQUIRED TO MAKE SPACE TO INSTALL

NEW BOILERS, PIPING, PUMPS, AND ALL ASSOCIATED ACCESSORIES.

6. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

M-401

M-401

DEMONEW

X-FOOT SUPPORT

(TYP.)

P P

X-SUCTION

DIFFUSER (TYP.)

X-4" HS

X-4" HS

X-AS-4

X-P-8

X-B-5

X-B-4

X-P-9X-AS-5

X-B-4 ON

TOP OF X-B-5

X-P-10X-P-11

X-1" HS/HR

X-2 1/2" HS/HR

X-2"

HS/HR

X-3" CWS/CWR

X-GUH-3

X-MAU-1

X-AHU-1

X-AHU-2

X-2 1/2"

CWS X-2 1/2"

CWR

X-2" HR

X-2 1/2" HS

X-P-12

X-2 1/2"

CWS

X-3"

CWR

X-2 1/2"

CWR

X-40"x20" RA

DN TO X-AHU-2

X-34"Ø OA

X-38"Ø OA

X-40"Ø OA

X-20"Ø OA

DN TO X-AHU-2

X-44"x16" SA

DN TO X-AHU-2

X-40"x16" SA

DN TO X-MAU-1

X-34"Ø OA

DN TO X-MAU-1

X-26"Ø OA

DN TO X-AHU-1

X-60"x18" SA

DN TO X-AHU-1

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

X-4" G

X-3/4" G

X-4" G

X-4" G

X-2" G

X-2" G

X-12" FLUE

THRU ROOF

X-FS

(TYP. 4)

SEE HVAC

FOR CONTINUATION

X-DWH

X-4" G

X-T

X-STEAM BOILER

X-L

COMBUSTION AIR INTAKE DUCT

ROUTED UP AND DOWN OPEN

ENDED ON BOTH ENDS

M

X-CONCRETE PAD1

X-D

X-FOOT SUPPORT

(TYP.)

X-REDUCER (TYP.)

X-STRAINER (TYP.)

P P

DN TO X-DRAIN

X-FLEXIBLE CONN. (TYP.)

X-COMPOUND GAUGE (TYP.)

X-TRIPLE DUTY VALVE (TYP.)

X-UNION (TYP.)

X-BUTTERFLY VALVE (TYP.)

X-AS-5

X-P-9

X-SUCTION

DIFFUSER (TYP.)

X-3/4" CW

X-XT

X-1" CW

X-4" HS

X-B-5

X-CHECK

VALVE (TYP.)

VTR

X-PRESSURE RELIEF

VALVE (TYP.)

X-PIPE TO

FLOOR DRAIN

(TYP.)

X-THERMOMETER (TYP.)

X-B-4

VTR

X-10" V X-P-10

X-GAS COCK (TYP.)

X-DRIP LEG

(TYP.)

X-4" G X-R

X-CONDENSATE

NEUTRALIZING

KIT (TYP.)

X-4" CONCREATE

PAD (TYP.)

X-1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP.)

X-2" G

X-3" HS

X-4" HS

X-4" HS

X-4" HS

X-4" HS

X-4" HR

X-4" HR

X-P-11

X-2" G

X-BACKFLOW

PREVENTOR (TYP.)2

X-AS-4

X-P-8

X-P-9X-AS-5

X-1" HS/HR

X-2 1/2" HS/HR

X-2"

HS/HR

X-3" CWS/CWR

X-GUH-3

X-MAU-1

X-AHU-1

X-AHU-2

X-2 1/2"

CWS X-2 1/2"

CWR

X-2" HR

X-2 1/2" HS

X-P-12

X-2 1/2"

CWS

X-3"

CWR

X-2 1/2"

CWR

X-40"x20" RA

DN TO X-AHU-2

X-34"Ø OA

X-38"Ø OA

X-40"Ø OA

X-20"Ø OA

DN TO X-AHU-2

X-44"x16" SA

DN TO X-AHU-2

X-40"x16" SA

DN TO X-MAU-1

X-34"Ø OA

DN TO X-MAU-1

X-26"Ø OA

DN TO X-AHU-1

X-60"x18" SA

DN TO X-AHU-1

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

SEE HVAC

FOR CONTINUATION

X-4" G

X-3/4" G

X-4" G

X-4" G

X-2" G

X-2" G X-FS

(TYP. 4)

SEE HVAC

FOR CONTINUATION

X-DWH

X-4" G

X-T

X-STEAM BOILER

X-L

COMBUSTION AIR INTAKE DUCT

ROUTED UP AND DOWN OPEN

ENDED ON BOTH ENDS

M X-D

B-1FS

B-2FS

4" CA & 6" V THRU

ROOF (TYP.3)

BOILER EPO SWITCH3

S

CARBON MONOXIDE SENSOR4

BOILER EPO SWITCH

(BY EC) 3

HR

HS

B-3FS

G

1 CONCRETE PAD

X-FOOT SUPPORT

(TYP.)

X-REDUCER (TYP.)

X-STRAINER (TYP.)

P P

DN TO X-DRAIN

X-FLEXIBLE CONN. (TYP.)

X-COMPOUND GAUGE (TYP.)

X-TRIPLE DUTY VALVE (TYP.)

X-UNION (TYP.)

X-BUTTERFLY VALVE (TYP.)

X-AS-5

X-P-9

X-SUCTION

DIFFUSER (TYP.)

X-3/4" CW

X-XT

X-1" CW

X-GAS COCK (TYP.)

X-4" G X-R

X-2" G

X-4" HS

X-4" HS

X-4" HS

X-4" HS

X-4" HR

X-2" G

X-BACKFLOW

PREVENTOR (TYP.)

B-1FS

CONDENSATE

NEUTRALIZING

KIT (TYP.)

2"

TO FLOOR DRAIN (TYP.)

STRAINER (TYP)

UNION (TYP)

HR

G

HS

HR

B-3FS G

HS

HR

HR

HR

HS

HS

G

G

2" 2"

2"

2"

4"

4"

GAS COCK (TYP)

1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP)

DRIP LEG (TYP)

SHUTOFF VALVE

(TYP)

PRESSURE RELIEF

VALVE (TYP)

THERMOMETER (TYP)

CHECK VALVE (TYP)

P-1FS P-3FS

P/T (TYP.)

2"2"

1 1

4"

PIPE TO

FLOOR

(TYP.)

12" MAX

BOILER LOOP

TEMPERATURE

SENSOR

2 2

B-2FS

2"

G

HS

HR

2"

P-2FS

2"

G

CONCRETE PAD

VTR

CA

V

VTR

CA

V

VTR

CA

V

4"

4"

MECHANICAL KEY NOTES

GENERAL MECHANICAL NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. INSTALL EQUIPMENT TO ENSURE ALL MANUFACTURER REQUIRED

SERVICE CLEARANCES ARE MET.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL WATER

TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER DEMOLITION/NEW

WORK IS COMPLETE. EXISTING ROOF WARRANTY IS HELD BY PRECISION ROOFING

(PHONE#: 517-675-8509).

4. CONTRACTOR TO DRAIN AND FLUSH ENTIRE HEATING HOT WATER SYSTEM.

CONTRACTOR TO FILL/TREAT HYDRONIC LOOP AS REQUIRED TO MEET BOILER

REQUIREMENTS.

5. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

1 INSTALL NEW BOILER, BOILER PUMP, CONTROLS, CONTROL WIRING,

COMBUSTION AIR INLET, VENT OUTLET, PIPING, VALVES, FITTINGS, AND

ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE

MANUFACTURERS INSTALLATION INSTRUCTIONS. INSTALL NEW BOILER

ON NEW 4" THICK CONCRETE PAD WITH 4" OVERLAP IN ALL

DIRECTIONS. ROUTE VENT AND COMBUSTION AIR PIPING THROUGH

NEW ROOF CURBS AND NEW ROOF BOOTS. PATCH ROOF TO MATCH

EXISTING, SEAL WATER TIGHT, AND MAINTAIN ALL EXISTING ROOF

WARRANTIES. INSTALL BIRDSCREEN ON VENT PIPING. COORDINATE

COMBUSTION AIR AND VENT ROUTING WITH EXISTING

PIPING/DUCTWORK AND BUILDING COMPONENTS. FRAME NEW ROOF

PENETRATIONS WITH 2"x2"x4" ANGLE IRON CONNECTED TO ROOF

STRUCTURE.

INSTALL NEW HEATING SUPPLY PIPING, HEATING RETURN PIPING, GAS

PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOWN. CONNECT NEW HEATING SUPPLY PIPING, HEATING

RETURN PIPING, GAS PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED

ACCESSORIES TO EXISTING PIPING. MODIFY THE EXISTING PIPING AS

REQUIRED FOR NEW CONNECTION.

INSTALL NEW EPO SWITCH AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOW PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS AND CONNECT TO NEW BOILERS.

INSTALL NEW WALL MOUNTED CARBON MONOXIDE SENSOR (KIDDE M/N:

C3010-D OR APPROVED EQUIVALENT) AND ALL ASSOCIATED

ACCESSORIES IN THE LOCATION SHOWN. NEW CARBON MONOXIDE

SENOR TO MEET BOILER INSPECTION REQUIREMENTS.

M-401

WEST FOOD SERVICE

BUILDING - FIRST FLOOR

PLAN - MECHANICAL

DEMOLITION/NEW

BRH

MTJ

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

250689.00

M a t r ix

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O F

M

IC

H

IG

A N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

FA

C

IL

IT

IE

S

A N

D B

U

SI

N

ES

S

SE

R V

IC

ES

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

472/25362.CTS

funding code sheet description

CD Set 02/12/2026

N WEST FOOD SERVICE BUILDING - FIRST FLOOR PLAN - MECHANICAL DEMOLITION/NEW

WEST FOOD SERVICE BUILDING MECHANICAL ROOM -

MECHANICAL DEMOLITION

SCALE: 1/4" = 1'-0"

WEST FOOD SERVICE BUILDING MECHANICAL ROOM BOILER

PIPING DIAGRAM - DEMOLITION

SCALE: NTS

WEST FOOD SERVICE BUILDING MECHANICAL ROOM -

MECHANICAL NEW

SCALE: 1/4" = 1'-0"

WEST FOOD SERVICE BUILDING MECHANICAL ROOM BOILER

PIPING DIAGRAM - NEW

SCALE: NTS

SCALE: 1/16" = 1'-0"

10510 4020

M-402

M-402

DEMO NEW

DISCONNECT, REMOVE, AND DEMO EXISTING BOILER, FLUE, BOILER PUMP,

CONTROLS, CONTROL WIRING, CONCRETE PAD, PIPING, VALVES, AND ALL

ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. CONTRACTOR TO REMOVE

COMMON VENT THROUGH ROOF AND PATCH, PRIME, AND PAINT CEILING AS

REQUIRED TO MATCH EXISTING. CONTRACTOR TO PATCH ROOF PENETRATION

TO MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF

WARRANTIES.

DISCONNECT, REMOVE, AND DEMO EXISTING HEATING SUPPLY PIPING,

HEATING RETURN PIPING, GAS PIPING, VALVES, FITTINGS, AND ALL

ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN. MODIFY EXISTING

PIPING AS REQUIRED FOR NEW CONNECTIONS SHOWN ON NEW DRAWING.

EXISTING LOUVER, DAMPER, CONTROLS AND ALL ASSOCIATED ACCESSORIES

TIED TO DOMESTIC WATER HEATER TO REMAIN. DISCONNECT, REMOVE, AND

DEMO EXISTING CONTROLS AND ALL ASSOCIATED ACCESSORIES IN THEIR

ENTIRETY THAT ARE ASSOCIATED WITH THE BOILER BEING DEMOLISHED.

EXISTING SUPPLY AIR FAN TO REMAIN.

DEMOLITION NOTES

GENERAL DEMOLITION NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. ALL EQUIPMENT, PIPING, CONTROLS, CONTROL WIRING, CONCRETE PADS,

AND ASSOCIATED ACCESSORIES TO REMAIN AND BE REUSED UNLESS

OTHERWISE NOTED.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL

WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER

DEMOLITION/NEW WORK IS COMPLETE.

4. EXISTING ZONE PUMPS AND ALL CONTROLS ARE TO REMAIN.

5. DEMOLISH EXISTING PIPING AS REQUIRED TO MAKE SPACE TO INSTALL

NEW BOILERS, PIPING, PUMPS, AND ALL ASSOCIATED ACCESSORIES.

6. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

X-P 1A-1D

(STACKED)

X-B-1

X-SF-1

X-GUH

X-AS-1

X-L

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

X-4" FLUE

THRU ROOF

X-CT-1

X-P

X-SERVER RACK

X-FS

(TYP. 4) X-10" FLUE

THRU ROOF

X-1 1/2" G X-2" G

X-1 1/4" G

X-2" GX-3/4" G

X-2 1/2" HS

(STACKED)

X-2 1/2" HR

(STACKED)

1 X-DWH X-T

MECHANICAL ROOM

H4

(2) X-L(2) 40"x24" INTAKE

LOUVERS W/DAMPERS3

M

X-AS-1

X-CT-1

X-STRAINER (TYP.)

X-P-1A

X-P-1B

X-P-1C

X-P-1D

X-AIR VENT

X-THERMOMETER (TYP.)

P

P

P

P

X-3/4" CWX-BACKFLOW

PREVENTOR

(TYP.)

P

X-1 1/2" HR

X-CHECK VALVE (TYP.)

X-P-17

X-B-1

X-BYPASS POT

FEEDER

X-FUNNEL

X-CBV SET

AT 92 GPM

X-GAS COCK (TYP.)

X-DRIP LEG

(TYP.)

X-2" G X-2" GX-R

X-2" G

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HR

X-CONDENSATE

NEUTRALIZING

KIT (TYP.)

X-1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP.)

X-4" CONCRETE PAD

X-VTR

X-10" V

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-2 1/2" HS

X-2 1/2" HR

X-1/2" HS

2 2

DN TO X-DRAIN

X-2 1/2" HS2 1/2" HR

X-1/2" HR

X-P 1A-1D

(STACKED)

X-SF-1

X-GUH

X-AS-1

X-L

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

X-4" FLUE

THRU ROOF

X-CT-1

X-SERVER RACK

X-FS

(TYP. 4)

X-1 1/2" G X-2" G

X-1 1/4" G

X-3/4" G

X-2 1/2" HS

(STACKED)

X-2 1/2" HR

(STACKED)

X-DWH X-T

MECHANICAL ROOM

H4

(2) X-L(2) 40"x24" INTAKE

LOUVERS W/DAMPERS

M

B-1AB

CONCRETE PAD

B-2AB

G

HR

4" CA & 6" V THRU

ROOF (TYP.2)

BOILER EPO SWITCH3

S

CARBON MONOXIDE

SENSOR

HS

X-AS-1

X-CT-1

X-STRAINER (TYP.)

X-P-1A

X-P-1B

X-P-1C

X-P-1D

X-AIR VENT

X-THERMOMETER (TYP.)

P

P

P

P

X-3/4" CWX-BACKFLOW

PREVENTOR

(TYP.)

P

X-1 1/2" HR

X-CHECK VALVE (TYP.)

X-FUNNEL

X-2" G X-2" GX-R

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1/2" HS

DN TO X-DRAIN

X-2 1/2" HS2 1/2" HR

X-1/2" HR

4" CONCRETE

PAD

B-1AB

CONDENSATE

NEUTRALIZING

KIT (TYP.)

2-1/2"

TO FLOOR DRAIN (TYP.)

UNION (TYP)

HRHR

G

HS

HR

B-2AB G

HS

HS

HR

HR

HR

HS HS

G

G

GAS COCK (TYP)

1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP)

DRIP LEG (TYP)

SHUTOFF VALVE

(TYP)

PRESSURE RELIEF

VALVE (TYP)

THERMOMETER (TYP)

CHECK VALVE (TYP)

P-1AB P-2AB

P/T (TYP.)

G

1-1/2"1-1/2"

1 1

PIPE TO

FLOOR

(TYP.)

2 2

12" MAX

2"

VTR

CA

V

STRAINER (TYP)

VTR

CA

V

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

1-1/2"

2-1/2"

2-1/2"

BOILER LOOP

TEMPERATURE

SENSOR

MECHANICAL KEY NOTES

GENERAL MECHANICAL NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. INSTALL EQUIPMENT TO ENSURE ALL MANUFACTURER REQUIRED

SERVICE CLEARANCES ARE MET.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL WATER

TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER DEMOLITION/NEW

WORK IS COMPLETE. EXISTING ROOF WARRANTY IS HELD BY PRECISION ROOFING

(PHONE#: 517-675-8509).

4. CONTRACTOR TO DRAIN AND FLUSH ENTIRE HEATING HOT WATER SYSTEM.

CONTRACTOR TO FILL/TREAT HYDRONIC LOOP AS REQUIRED TO MEET BOILER

REQUIREMENTS.

5. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

1 INSTALL NEW BOILER, BOILER PUMP, CONTROLS, CONTROL WIRING,

COMBUSTION AIR INLET, VENT OUTLET, PIPING, VALVES, FITTINGS, AND

ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE

MANUFACTURERS INSTALLATION INSTRUCTIONS. INSTALL NEW BOILER

ON NEW 4" THICK CONCRETE PAD WITH 4" OVERLAP IN ALL

DIRECTIONS. ROUTE VENT AND COMBUSTION AIR PIPING THROUGH

NEW ROOF CURBS AND NEW ROOF BOOTS. PATCH ROOF TO MATCH

EXISTING, SEAL WATER TIGHT, AND MAINTAIN ALL EXISTING ROOF

WARRANTIES. INSTALL BIRDSCREEN ON VENT PIPING. COORDINATE

COMBUSTION AIR AND VENT ROUTING WITH EXISTING

PIPING/DUCTWORK AND BUILDING COMPONENTS. FRAME NEW ROOF

PENETRATIONS WITH 2"x2"x4" ANGLE IRON CONNECTED TO ROOF

STRUCTURE.

INSTALL NEW HEATING SUPPLY PIPING, HEATING RETURN PIPING, GAS

PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOWN. CONNECT NEW HEATING SUPPLY PIPING, HEATING

RETURN PIPING, GAS PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED

ACCESSORIES TO EXISTING PIPING. MODIFY THE EXISTING PIPING AS

REQUIRED FOR NEW CONNECTION.

INSTALL NEW EPO SWITCH AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOW PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS AND CONNECT TO NEW BOILERS.

INSTALL NEW WALL MOUNTED CARBON MONOXIDE SENSOR (KIDDE M/N:

C3010-D OR APPROVED EQUIVALENT) AND ALL ASSOCIATED

ACCESSORIES IN THE LOCATION SHOWN. NEW CARBON MONOXIDE

SENOR TO MEET BOILER INSPECTION REQUIREMENTS.

M-402

WEST HOUSING UNIT A-B

- FIRST FLOOR PLAN -

MECHANICAL

DEMOLITION/NEW

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

250689.00

M a t r ix

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

FA

C

IL

IT

IE

S

A N

D B

U

SI

N

ES

S

SE

R V

IC

ES

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

472/25362.CTS

funding code sheet description

CD Set 02/12/2026

N WEST HOUSING UNIT A-B - FIRST FLOOR PLAN - MECHANICAL DEMOLITION/NEW

WEST HOUSING UNIT A-B MECHANICAL ROOM -

MECHANICAL DEMOLITION

SCALE: 1/4" = 1'-0"

WEST HOUSING UNIT A-B MECHANICAL ROOM BOILER

PIPING DIAGRAM - DEMOLITION

SCALE: NTS

WEST HOUSING UNIT A-B MECHANICAL ROOM -

MECHANICAL NEW

SCALE: 1/4" = 1'-0"

WEST HOUSING UNIT A-B MECHANICAL ROOM BOILER

PIPING DIAGRAM - NEW

SCALE: NTS

SCALE: 1/16" = 1'-0"

10510 4020

M-403

M-403

DEMO NEW

DISCONNECT, REMOVE, AND DEMO EXISTING BOILER, FLUE, BOILER PUMP,

CONTROLS, CONTROL WIRING, CONCRETE PAD, PIPING, VALVES, AND ALL

ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. CONTRACTOR TO REMOVE

COMMON VENT THROUGH ROOF AND PATCH, PRIME, AND PAINT CEILING AS

REQUIRED TO MATCH EXISTING. CONTRACTOR TO PATCH ROOF PENETRATION

TO MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF

WARRANTIES.

DISCONNECT, REMOVE, AND DEMO EXISTING HEATING SUPPLY PIPING,

HEATING RETURN PIPING, GAS PIPING, VALVES, FITTINGS, AND ALL

ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN. MODIFY EXISTING

PIPING AS REQUIRED FOR NEW CONNECTIONS SHOWN ON NEW DRAWING.

EXISTING LOUVER, DAMPER, CONTROLS AND ALL ASSOCIATED ACCESSORIES

TIED TO DOMESTIC WATER HEATER TO REMAIN. DISCONNECT, REMOVE, AND

DEMO EXISTING CONTROLS AND ALL ASSOCIATED ACCESSORIES IN THEIR

ENTIRETY THAT ARE ASSOCIATED WITH THE BOILER BEING DEMOLISHED.

EXISTING SUPPLY AIR FAN TO REMAIN.

DEMOLITION NOTES

GENERAL DEMOLITION NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. ALL EQUIPMENT, PIPING, CONTROLS, CONTROL WIRING, CONCRETE PADS,

AND ASSOCIATED ACCESSORIES TO REMAIN AND BE REUSED UNLESS

OTHERWISE NOTED.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL

WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER

DEMOLITION/NEW WORK IS COMPLETE.

4. EXISTING ZONE PUMPS AND ALL CONTROLS ARE TO REMAIN.

5. DEMOLISH EXISTING PIPING AS REQUIRED TO MAKE SPACE TO INSTALL

NEW BOILERS, PIPING, PUMPS, AND ALL ASSOCIATED ACCESSORIES.

6. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

X-P 1A-1D

(STACKED)

X-B-1

X-SF-1

X-GUH

X-AS-1

X-L

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

X-4" FLUE

THRU ROOF

X-CT-1

X-P

X-SERVER RACK

X-FS

(TYP. 4) X-10" FLUE

THRU ROOF

X-1 1/2" G X-2" G

X-1 1/4" G

X-2" GX-3/4" G

X-2 1/2" HS

(STACKED)

X-2 1/2" HR

(STACKED)

1 X-DWH X-T

MECHANICAL ROOM

H4

(2) X-L

X-BOILER EPO SWITCH

M

(2) 40"x24" INTAKE

LOUVERS W/DAMPERS3

X-AS-1

X-CT-1

X-STRAINER (TYP.)

X-P-1A

X-P-1B

X-P-1C

X-P-1D

X-AIR VENT

X-THERMOMETER (TYP.)

P

P

P

P

X-3/4" CWX-BACKFLOW

PREVENTOR

(TYP.)

P

X-1 1/2" HR

X-CHECK VALVE (TYP.)

X-P-17

X-B-1

X-BYPASS POT

FEEDER

X-FUNNEL

X-CBV SET

AT 92 GPM

X-GAS COCK (TYP.)

X-DRIP LEG

(TYP.)

X-2" G X-2" GX-R

X-2" G

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HR

X-CONDENSATE

NEUTRALIZING

KIT (TYP.)

X-1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP.)

X-4" CONCRETE PAD

X-VTR

X-10" V

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-2 1/2" HS

X-2 1/2" HR

X-1/2" HS

DN TO X-DRAIN

X-2 1/2" HS2 1/2" HR

X-1/2" HR

X-P 1A-1D

(STACKED)

X-SF-1

X-GUH

X-AS-1

X-L

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

X-4" FLUE

THRU ROOF

X-CT-1

X-SERVER RACK

X-FS

(TYP. 4)

X-1 1/2" G X-2" G

X-1 1/4" G

X-3/4" G

X-2 1/2" HS

(STACKED)

X-2 1/2" HR

(STACKED)

X-DWH X-T

MECHANICAL ROOM

H4

(2) X-L

M

(2) 40"x24" INTAKE

LOUVERS W/DAMPERS

B-1CD

CONCRETE PAD

B-2CD

G

HR

4" CA & 6" V THRU

ROOF (TYP.2)

S

CARBON MONOXIDE

SENSOR

HS

BOILER EPO SWITCH

B-1CD B-2CD

P-2CD

X-AS-1

X-CT-1

X-STRAINER (TYP.)

X-P-1A

X-P-1B

X-P-1C

X-P-1D

X-AIR VENT

X-THERMOMETER (TYP.)

P

P

P

P

X-3/4" CWX-BACKFLOW

PREVENTOR

(TYP.)

P

X-1 1/2" HR

X-CHECK VALVE (TYP.)

X-FUNNEL

X-2" G X-2" GX-R

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1/2" HS

DN TO X-DRAIN

X-2 1/2" HS2 1/2" HR

X-1/2" HR

P-1CD

4" CONCRETE

PAD

CONDENSATE

NEUTRALIZING

KIT (TYP.)

TO FLOOR DRAIN (TYP.)

UNION (TYP)

HRHR

G

HS

HR

G

HS

HS

HR

HR

HR

HS HS

G

G

GAS COCK (TYP)

1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP)

DRIP LEG (TYP)

SHUTOFF VALVE

(TYP)

PRESSURE RELIEF

VALVE (TYP)

THERMOMETER (TYP)

CHECK VALVE (TYP)

P/T (TYP.)

G

1 1

PIPE TO

FLOOR

(TYP.)

12" MAX

2"

2-1/2" 1-1/2"1-1/2"VTR

CA

V

STRAINER (TYP)

VTR

CA

V

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

1-1/2"

2-1/2"

2-1/2"

BOILER LOOP

TEMPERATURE

SENSOR

MECHANICAL KEY NOTES

GENERAL MECHANICAL NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. INSTALL EQUIPMENT TO ENSURE ALL MANUFACTURER REQUIRED

SERVICE CLEARANCES ARE MET.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL WATER

TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER DEMOLITION/NEW

WORK IS COMPLETE. EXISTING ROOF WARRANTY IS HELD BY PRECISION ROOFING

(PHONE#: 517-675-8509).

4. CONTRACTOR TO DRAIN AND FLUSH ENTIRE HEATING HOT WATER SYSTEM.

CONTRACTOR TO FILL/TREAT HYDRONIC LOOP AS REQUIRED TO MEET BOILER

REQUIREMENTS.

5. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

1 INSTALL NEW BOILER, BOILER PUMP, CONTROLS, CONTROL WIRING,

COMBUSTION AIR INLET, VENT OUTLET, PIPING, VALVES, FITTINGS, AND

ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE

MANUFACTURERS INSTALLATION INSTRUCTIONS. INSTALL NEW BOILER

ON NEW 4" THICK CONCRETE PAD WITH 4" OVERLAP IN ALL

DIRECTIONS. ROUTE VENT AND COMBUSTION AIR PIPING THROUGH

NEW ROOF CURBS AND NEW ROOF BOOTS. PATCH ROOF TO MATCH

EXISTING, SEAL WATER TIGHT, AND MAINTAIN ALL EXISTING ROOF

WARRANTIES. INSTALL BIRDSCREEN ON VENT PIPING. COORDINATE

COMBUSTION AIR AND VENT ROUTING WITH EXISTING

PIPING/DUCTWORK AND BUILDING COMPONENTS. FRAME NEW ROOF

PENETRATIONS WITH 2"x2"x4" ANGLE IRON CONNECTED TO ROOF

STRUCTURE.

INSTALL NEW HEATING SUPPLY PIPING, HEATING RETURN PIPING, GAS

PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOWN. CONNECT NEW HEATING SUPPLY PIPING, HEATING

RETURN PIPING, GAS PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED

ACCESSORIES TO EXISTING PIPING. MODIFY THE EXISTING PIPING AS

REQUIRED FOR NEW CONNECTION.

INSTALL NEW EPO SWITCH AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOW PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS AND CONNECT TO NEW BOILERS.

INSTALL NEW WALL MOUNTED CARBON MONOXIDE SENSOR (KIDDE M/N:

C3010-D OR APPROVED EQUIVALENT) AND ALL ASSOCIATED

ACCESSORIES IN THE LOCATION SHOWN. NEW CARBON MONOXIDE

SENOR TO MEET BOILER INSPECTION REQUIREMENTS.

M-403

WEST HOUSING UNIT C-D

- FIRST FLOOR PLAN -

MECHANICAL

DEMOLITION/NEW

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

250689.00

M a t r ix

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

FA

C

IL

IT

IE

S

A N

D B

U

SI

N

ES

S

SE

R V

IC

ES

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

472/25362.CTS

funding code sheet description

CD Set 02/12/2026

N WEST HOUSING UNIT C-D - FIRST FLOOR PLAN - MECHANICAL DEMOLITION/NEW

WEST HOUSING UNIT C-D MECHANICAL ROOM -

MECHANICAL DEMOLITION

SCALE: 1/4" = 1'-0"

WEST HOUSING UNIT C-D MECHANICAL ROOM BOILER

PIPING DIAGRAM - DEMOLITION

SCALE: NTS

WEST HOUSING UNIT C-D MECHANICAL ROOM -

MECHANICAL NEW

SCALE: 1/4" = 1'-0"

WEST HOUSING UNIT C-D MECHANICAL ROOM BOILER

PIPING DIAGRAM - NEW

SCALE: NTS

SCALE: 1/16" = 1'-0"

10510 4020

M-404

M-404

DEMO NEW

DISCONNECT, REMOVE, AND DEMO EXISTING BOILER, FLUE, BOILER PUMP,

CONTROLS, CONTROL WIRING, CONCRETE PAD, PIPING, VALVES, AND ALL

ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. CONTRACTOR TO REMOVE

COMMON VENT THROUGH ROOF AND PATCH, PRIME, AND PAINT CEILING AS

REQUIRED TO MATCH EXISTING. CONTRACTOR TO PATCH ROOF PENETRATION

TO MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF

WARRANTIES.

DISCONNECT, REMOVE, AND DEMO EXISTING HEATING SUPPLY PIPING,

HEATING RETURN PIPING, GAS PIPING, VALVES, FITTINGS, AND ALL

ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN. MODIFY EXISTING

PIPING AS REQUIRED FOR NEW CONNECTIONS SHOWN ON NEW DRAWING.

EXISTING LOUVER, DAMPER, CONTROLS AND ALL ASSOCIATED ACCESSORIES

TIED TO DOMESTIC WATER HEATER TO REMAIN. DISCONNECT, REMOVE, AND

DEMO EXISTING CONTROLS AND ALL ASSOCIATED ACCESSORIES IN THEIR

ENTIRETY THAT ARE ASSOCIATED WITH THE BOILER BEING DEMOLISHED.

EXISTING SUPPLY AIR FAN TO REMAIN.

DEMOLITION NOTES

GENERAL DEMOLITION NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. ALL EQUIPMENT, PIPING, CONTROLS, CONTROL WIRING, CONCRETE PADS,

AND ASSOCIATED ACCESSORIES TO REMAIN AND BE REUSED UNLESS

OTHERWISE NOTED.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL

WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER

DEMOLITION/NEW WORK IS COMPLETE.

4. EXISTING ZONE PUMPS AND ALL CONTROLS ARE TO REMAIN.

5. DEMOLISH EXISTING PIPING AS REQUIRED TO MAKE SPACE TO INSTALL

NEW BOILERS, PIPING, PUMPS, AND ALL ASSOCIATED ACCESSORIES.

6. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

X-P 1A-1D

(STACKED)

X-B-1

X-SF-1

X-GUH

X-AS-1

X-L

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

X-4" FLUE

THRU ROOF

X-CT-1

X-P

X-SERVER RACK

X-FS

(TYP. 4) X-10" FLUE

THRU ROOF

X-1 1/2" G X-2" G

X-1 1/4" G

X-2" GX-3/4" G

X-2 1/2" HS

(STACKED)

X-2 1/2" HR

(STACKED)

1 X-DWH X-T

MECHANICAL ROOM

H4

M

(2) X-L

X-BOILER EPO SWITCH

(2) 40"x24" INTAKE

LOUVERS W/DAMPERS3

X-AS-1

X-CT-1

X-STRAINER (TYP.)

X-P-1A

X-P-1B

X-P-1C

X-P-1D

X-AIR VENT

X-THERMOMETER (TYP.)

P

P

P

P

X-3/4" CWX-BACKFLOW

PREVENTOR

(TYP.)

P

X-1 1/2" HR

X-CHECK VALVE (TYP.)

X-P-17

X-B-1

X-BYPASS POT

FEEDER

X-FUNNEL

X-CBV SET

AT 92 GPM

X-GAS COCK (TYP.)

X-DRIP LEG

(TYP.)

X-2" G X-2" GX-R

X-2" G

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HR

X-CONDENSATE

NEUTRALIZING

KIT (TYP.)

X-1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP.)

X-4" CONCRETE PAD

X-VTR

X-10" V

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-2 1/2" HS

X-2 1/2" HR

X-1/2" HS

DN TO X-DRAIN

X-2 1/2" HS2 1/2" HR

X-1/2" HR

X-P 1A-1D

(STACKED)

X-SF-1

X-GUH

X-AS-1

X-L

SEE HYDRONIC

FOR CONTINUATION

SEE HYDRONIC

FOR CONTINUATION

X-4" FLUE

THRU ROOF

X-CT-1

X-SERVER RACK

X-FS

(TYP. 4)

X-1 1/2" G X-2" G

X-1 1/4" G

X-3/4" G

X-2 1/2" HS

(STACKED)

X-2 1/2" HR

(STACKED)

X-DWH X-T

MECHANICAL ROOM

H4

M

(2) X-L(2) 40"x24" INTAKE

LOUVERS W/DAMPERS

B-1GH

CONCRETE PAD

B-2GH

G

HR

4" CA & 6" V THRU

ROOF (TYP.2)

S

CARBON MONOXIDE

SENSOR

HS

BOILER EPO SWITCH3

4" CONCRETE

PAD

CONDENSATE

NEUTRALIZING

KIT (TYP.)

TO FLOOR DRAIN (TYP.)

UNION (TYP)

HRHR

G

HS

HR

G

HS

HS

HR

HR

HR

HS HS

G

G

GAS COCK (TYP)

1-1/2" DRAIN

VALVE PIPE TO

FLOOR DRAIN.

(TYP)

DRIP LEG (TYP)

PRESSURE RELIEF

VALVE (TYP)

THERMOMETER (TYP)

CHECK VALVE (TYP)

P/T (TYP.)

G

1 1

PIPE TO

FLOOR

(TYP.)

12" MAX

X-AS-1

X-CT-1

X-STRAINER (TYP.)

X-P-1A

X-P-1B

X-P-1C

X-P-1D

X-AIR VENT

X-THERMOMETER (TYP.)

P

P

P

P

X-3/4" CWX-BACKFLOW

PREVENTOR

(TYP.)

P

X-1 1/2" HR

X-CHECK VALVE (TYP.)

X-FUNNEL

X-2" G X-2" GX-R

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HR

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1 1/2" HS

X-1/2" HS

DN TO X-DRAIN

X-2 1/2" HS2 1/2" HR

X-1/2" HR

B-1GH B-2GH

P-1GH P-2GH

2"

SHUTOFF VALVE

(TYP)

2-1/2" 1-1/2"1-1/2"VTR

CA

V

STRAINER (TYP)

VTR

CA

V

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

1-1/2"

2-1/2"

2-1/2"

BOILER LOOP

TEMPERATURE

SENSOR

MECHANICAL KEY NOTES

GENERAL MECHANICAL NOTES

1. REFER TO PIPING DIAGRAM FOR PIPE SIZING.

2. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. INSTALL EQUIPMENT TO ENSURE ALL MANUFACTURER REQUIRED

SERVICE CLEARANCES ARE MET.

3. CONTRACTOR TO PATCH ROOF PENETRATION TO MATCH EXISTING, SEAL WATER

TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES AFTER DEMOLITION/NEW

WORK IS COMPLETE. EXISTING ROOF WARRANTY IS HELD BY PRECISION ROOFING

(PHONE#: 517-675-8509).

4. CONTRACTOR TO DRAIN AND FLUSH ENTIRE HEATING HOT WATER SYSTEM.

CONTRACTOR TO FILL/TREAT HYDRONIC LOOP AS REQUIRED TO MEET BOILER

REQUIREMENTS.

5. ALL WORK SHALL CONFORM TO MDOC STANDARDS.

1 INSTALL NEW BOILER, BOILER PUMP, CONTROLS, CONTROL WIRING,

COMBUSTION AIR INLET, VENT OUTLET, PIPING, VALVES, FITTINGS, AND

ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE

MANUFACTURERS INSTALLATION INSTRUCTIONS. INSTALL NEW BOILER

ON NEW 4" THICK CONCRETE PAD WITH 4" OVERLAP IN ALL

DIRECTIONS. ROUTE VENT AND COMBUSTION AIR PIPING THROUGH

NEW ROOF CURBS AND NEW ROOF BOOTS. PATCH ROOF TO MATCH

EXIS…