C04b Attachment 2 Specs BSC LH 1240BH26R0013.pdf

PDF 1 MB Posted

Attached to
GAOA Blanchard Springs Caverns Tunnel Rehabilitation in Ozark-St. Francis NF
Solicitation number
1240BH26R0013
Issued by

About this file

This is a Project Manual and technical specifications document for the USDA Forest Service Blanchard Springs Caverns Handrail and Lighting Replacement project located in Fifty-Six, Arkansas. The document contains detailed specifications for the procurement, fabrication, and installation of aluminum pipe and tube railings, electrical power conductors and cables, grounding and bonding systems, electrical equipment supports, conduits, boxes, and covers required for this cavern infrastructure improvement project.

The project involves replacement of handrails and lighting systems within the caverns, managed under Task Order 12445221D0017/12445123F0023. Key specifications include aluminum railings fabricated from alloy 6063-T5/T52 extruded bars and tubing to ASTM standards with clear anodic finish, designed to withstand 50 lbf/ft uniform loads and 200 lbf concentrated loads. Electrical work requires copper building wire (Type XHHW-2) and metal-clad cable (Type MC) with aluminum interlocked armor and PVC jacket, installed using nonmetallic outlet boxes, PVC Schedule 40 and 80 rigid conduit, and appropriate grounding and bonding systems with maximum ground resistance of 25 ohms. All electrical components must be listed and labeled per NFPA 70 standards. Installation requirements emphasize protection of cavern surfaces using only natural materials available on-site, with cables concealed or hidden using rock debris rather than brought-in materials. The document specifies multiple manufacturer options for major components, requires shop assembly to minimize field splicing, mandates comprehensive testing and inspection protocols for electrical systems, and establishes strict quality control standards for both structural and electrical installations prior to substantial completion.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA-FS

Blanchard Springs Caverns Handrail and Lighting Replacement Fifty-Six, Arkansas

Prepared by Johnson, Laschober & Associates, P.C.

704 Blanchard Springs Road

Fifty-Six Arkansas 72533 Project Number Task Order 12445221D0017/12445123F0023 JLA#3094.2302

PROJECT

MANUAL

Blanchard Springs Caverns Handrail and Lighting

Replacement

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

12/09/2025

Contract Mod_R2

- 1

TABLE OF CONTENTS

PROCUREMENT AND CONTRACTING REQUIREMENTS GROUP

DIVISION 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS

INTRODUCTORY INFORMATION

00 01 10 Table of Contents

SPECIFICATIONS GROUP

FACILITY CONSTRUCTION SUBGROUP

DIVISION05 - METALS

05 52 13 PIPE AND TUBE RAILINGS

FACILITY SERVICES SUBGROUP

DIVISION26 - ELECTRICAL

26 05 19 LOW-VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES

26 05 26 GROUNDING AND BONDING FOR ELECTRICAL

SYSTEMS

26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL

SYSTEMS

26 05 33.13 CONDUITS FOR ELECTRICAL SYSTEMS

26 05 33.16 BOXES AND COVERS FOR ELECTRICAL

SYSTEMS

26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS

26 24 16 PANELBOARDS

26 27 16 ELECTRICAL CABINETS AND ENCLOSURES

26 27 26 WIRING DEVICES

26 28 13 FUSES

26 28 16 ENCLOSED SWITCHES AND CIRCUIT

BREAKERS

26 50 00 LIGHTING

END OF TABLE OF CONTENTS

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

PIPE AND TUBE RAILINGS 055213 - 1

SECTION 055213 - PIPE AND TUBE RAILINGS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Aluminum railings.

1.2 COORDINATION

A. Coordinate installation of anchorages for railings. Furnish setting drawings, templates, and directions for installing anchorages, including sleeves, concrete inserts, anchor bolts, and items with integral anchors, that are to be embedded in concrete or masonry. Deliver such items to

Project site in time for installation.

1.3 ACTION SUBMITTALS

A. Product Data:

1. Manufacturer's product lines of mechanically connected railings.

2. Woven-wire mesh infill panels.

3. Fasteners.

4. Post-installed anchors.

5. Handrail brackets.

6. Anchoring cement.

7. Metal finishes.

B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.

C. Samples for Verification: For each type of exposed finish required.

1. Sections of each distinctly different linear railing member, including handrails, top rails, posts, and balusters, including finish.

2. Fittings and brackets.

3. Assembled Sample of railing system, made from full-size components, including top rail, post, handrail, and infill. Sample need not be full height.

a. Show method of connecting members at intersections.

1.4 INFORMATIONAL SUBMITTALS

A. Research Reports: For post-installed anchors, from ICC-ES or other qualified testing agency

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

PIPE AND TUBE RAILINGS 055213 - 2

acceptable to authorities having jurisdiction.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Protect mechanical finishes on exposed surfaces of railings from damage by applying a strippable, temporary protective covering before shipping.

1.6 FIELD CONDITIONS

A. Field Measurements: Verify actual locations of walls and other construction contiguous with railings by field measurements before fabrication.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000

"Quality Requirements," to design railings, including attachment to building construction.

B. Structural Performance: Railings, including attachment to existing conditions, withstand the effects of gravity loads and the following loads and stresses within limits and under conditions indicated:

1. Handrails and Top Rails of Guards:

a. Uniform load of 50 lbf/ ft. applied in any direction.

b. Concentrated load of 200 lbf applied in any direction.

c. Uniform and concentrated loads need not be assumed to act concurrently.

2. Infill of Guards:

a. Concentrated load of 50 lbf applied horizontally on an area of 1 sq. ft..

b. Infill load and other loads need not be assumed to act concurrently.

2.2 METALS, GENERAL

A. Metal Surfaces, General: Provide materials with smooth surfaces, without seam marks, roller marks, rolled trade names, stains, discolorations, or blemishes.

B. Brackets, Flanges, and Anchors: Cast or formed metal of same type of material and finish as supported rails unless otherwise indicated.

1. Provide type of bracket with predrilled hole for exposed bolt anchorage and that provides

1-1/2-inch clearance from inside face of handrail to finished wall surface.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

PIPE AND TUBE RAILINGS 055213 - 3

2.3 ALUMINUM RAILINGS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Hollaender Mfg. Co.

2. Tuttle, a Dant Clayton Division

3. Greco Architectural Metal Products

B. Source Limitations: Obtain each type of railing from single source from single manufacturer.

C. Aluminum, General: Provide alloy and temper recommended by aluminum producer and finisher for type of use and finish indicated, and with not less than the strength and durability properties of alloy and temper designated below for each aluminum form required.

D. Extruded Bars and Tubing: ASTM B221, Alloy 6063-T5/T52.

E. Extruded Structural Pipe and Round Tubing: ASTM B429/B429M, Alloy 6063-T6.

1. Rails: Provide Standard Weight (Schedule 40) pipe unless otherwise indicated.

2. Posts: Provide Schedule 80 pipe posts. Maximum post spacing shall be 6'0" O.C.

F. Plate and Sheet: ASTM B209, Alloy 6061-T6.

G. Castings: ASTM B26/B26M, Alloy A356.0-T6.

H. Woven-Wire Mesh Infill Panels: Intermediate-crimp, square pattern, 4-inch woven-wire mesh, made from 0.162-inch- diameter aluminum wire complying with ASTM B211/B211M, Alloy

6061-T94.

2.4 FASTENERS

A. Fastener Materials:

1. Aluminum Railing Components: Type 316 stainless steel fasteners.

B. Fasteners for Anchoring Railings to Other Construction: Select fasteners of type, grade, and class required to produce connections suitable for anchoring railings to other types of construction and capable of withstanding design loads.

C. Fasteners for Interconnecting Railing Components:

1. Provide concealed fasteners for interconnecting railing components and for attaching them to other work, unless exposed fasteners are unavoidable or are the standard fastening method for railings indicated.

D. Post-Installed Anchors: Fastener systems with working capacity greater than or equal to the design load, according to an evaluation report acceptable to authorities having jurisdiction, Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

PIPE AND TUBE RAILINGS 055213 - 4

based on ICC-ES AC193.

1. Material for Exterior Locations and Where Stainless Steel Is Indicated: Alloy Group 2 stainless steel bolts, ASTM F593, and nuts, ASTM F594.

2.5 MISCELLANEOUS MATERIALS

A. Handrail Brackets: Cast aluminum, center of handrail 2-1/2 inches from face of railing, orwall.

B. Anchoring Cement: Factory-packaged, nonshrink, nonstaining, hydraulic-controlled expansion cement formulation for mixing with water at Project site to create pourable anchoring, patching, and grouting compound.

1. Water-Resistant Product: , provide formulation that is resistant to erosion from water exposure without needing protection by a sealer or waterproof coating and that is recommended by manufacturer for exterior use.

2.6 FABRICATION

A. General: Fabricate railings to comply with requirements indicated for design, dimensions, member sizes and spacing, details, finish, and anchorage, but not less than that required to support structural loads.

B. Shop assemble railings to greatest extent possible to minimize field splicing and assembly.

Disassemble units only as necessary for shipping and handling limitations.

1. Clearly mark units for reassembly and coordinated installation.

2. Use connections that maintain structural value of joined pieces.

C. Cut, drill, and punch metals cleanly and accurately.

1. Remove burrs and ease edges to a radius of approximately 1/32 inch unless otherwise indicated.

2. Remove sharp or rough areas on exposed surfaces.

D. Form work true to line and level with accurate angles and surfaces.

E. Fabricate connections that are exposed to weather in a manner that excludes water.

1. Provide weep holes where water may accumulate.

2. Locate weep holes in inconspicuous locations.

F. Cut, reinforce, drill, and tap as indicated to receive finish hardware, screws, and similar items.

G. Connections: Fabricate railings with nonwelded connections unless otherwise indicated.

H. Nonwelded Connections: Connect members with concealed mechanical fasteners and fittings.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

PIPE AND TUBE RAILINGS 055213 - 5

Fabricate members and fittings to produce flush, smooth, rigid, hairline joints.

I. Form changes in direction by bending or in a manner that will not result in distortion of railing member or by inserting prefabricated elbow fittings.

J. Bend members in jigs to produce uniform curvature for each configuration required. Maintain cross section of member throughout entire bend without buckling, twisting, cracking, or otherwise deforming exposed surfaces of components.

K. Close exposed ends of hollow railing members with prefabricated cap and end fittings of same metal and finish as railings.

L. Provide wall returns at ends of wall-mounted handrails unless otherwise indicated. Close ends of returns unless clearance between end of rail and wall is 1/4 inch or less.

M. Brackets, Flanges, Fittings, and Anchors: Provide wall brackets, flanges, miscellaneous fittings, and anchors to interconnect railing members to other work unless otherwise indicated.

N. Provide inserts and other anchorage devices for connecting railings to concrete or masonry work.

1. Fabricate anchorage devices capable of withstanding loads imposed by railings.

2. Coordinate anchorage devices with supporting structure.

O. Woven-Wire Mesh Infill Panels: Fabricate infill panels from aluminum woven-wire mesh crimped into 1-by-1/2-by-1/8-inch metal channel frames.

1. Fabricate wire mesh and frames from same metal as railings in which they are installed.

2. Orient wire mesh as indicated on Drawings.

P. Toe Boards: Where indicated, provide toe boards at railings around openings and at edge of open-sided floors and platforms.

1. Toe boards shall be at least 3 ½ inches in height from top edge to floor level and be capable of withstanding a force of 50 pounds applied in any direction.

2. Drainage clearance under toe boards is permitted.

2.7 ALUMINUM FINISHES

A. Clear Anodic Finish: AAMA 611, AA-M12C22A31.

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Perform cutting, drilling, and fitting required for installing railings.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

PIPE AND TUBE RAILINGS 055213 - 6

1. Fit exposed connections together to form tight, hairline joints.

2. Install railings level, plumb, square, true to line; without distortion, warp, or rack.

3. Set railings accurately in location, alignment, and elevation; measured from established lines and levels.

4. Do not weld, cut, or abrade surfaces of railing components that are coated or finished after fabrication and that are intended for field connection by mechanical or other means without further cutting or fitting.

5. Set posts plumb within a tolerance of 1/16 inch in 3 feet.

6. Align rails so variations from level for horizontal members and variations from parallel with rake of steps and ramps for sloping members do not exceed 1/4 inch in 12 feet.

B. Control of Corrosion: Prevent galvanic action and other forms of corrosion by insulating metals and other materials from direct contact with incompatible materials.

1. Coat concealed surfaces of aluminum that will be in contact with grout, concrete, masonry, wood, or dissimilar metals, with a heavy coat of bituminous paint.

2. Provide stainless-steel fasteners that will be in contact with aluminum with an insulating coating for contact with dissimilar metals.

C. Adjust railings before anchoring to ensure matching alignment at abutting joints.

D. Fastening to In-Place Construction: Use anchorage devices and fasteners where necessary for securing railings and for properly transferring loads to in-place construction.

3.2 RAILING CONNECTIONS

A. Nonwelded Connections: Use mechanical or adhesive joints for permanently connecting railing components. Use wood blocks and padding to prevent damage to railing members and fittings.

Seal recessed holes of exposed locking screws, using plastic cement filler colored to match finish of railings.

3.3 ANCHORING POSTS

A. Cover anchorage joint with flange of same metal as post, attached to post with setscrews.

3.4 ATTACHING RAILINGS

A. Anchor railing ends to concrete and masonry with flanges connected to railing ends and anchored to wall construction with anchors and bolts.

B. Secure base plates, wall brackets, and railing end flanges to existing conditions as follows:

1. For concrete and solid masonry anchorage, use stainless-steel epoxy anchors with 4" minimum embedment.

C. Ensure base plates and wall brackets are installed into sound material capable of resisting the

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

PIPE AND TUBE RAILINGS 055213 - 7

required load criteria.

D. For stone anchorage use Stainless-Steel epoxy anchors with 4" min. embedment.

3.5 CLEANING

A. Clean aluminum by washing thoroughly with clean water and soap and rinsing with clean water before installation.

3.6 PROTECTION

A. Protect finishes of railings from damage during construction period with temporary protective coverings approved by railing manufacturer. Remove protective coverings at time of Substantial

Completion.

B. Restore finishes damaged during installation and construction period, so no evidence remains of correction work. Return items that cannot be refinished in the field to the shop; make required alterations and refinish entire unit, or provide new units.

END OF SECTION 055213

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

LOW-VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES

260519 - 1

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

1.1 SUMMARY

A. Section Includes:

1. Copper building wire.

2. Metal-clad cable, Type MC.

3. Connectors and splices.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product.

1.3 INFORMATIONAL SUBMITTALS

A. Field quality-control reports.

PART 2 - PRODUCTS

2.1 COPPER BUILDING WIRE

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Encore Wire Corporation

2. General Cable; Prysmian Group North America

3. Service Wire Co.

4. Southwire Company, LLC

B. Description: Flexible, insulated and uninsulated, drawn copper current-carrying conductor with an overall insulation layer or jacket, or both, rated 600 V or less.

C. Standards:

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

2. Conductor and Cable Marking: Comply with wire and cable marking according to UL's

"Wire and Cable Marking and Application Guide."

D. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B8

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260519 - 2 for stranded conductors.

E. Conductor Insulation:

1. Type XHHW-2. Comply with UL 44.

2.2 METAL-CLAD CABLE, TYPE MC

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Encore Wire Corporation

2. General Cable; Prysmian Group North America

3. Southwire Company, LLC

B. Description: A factory assembly of one or more current-carrying insulated conductors in an overall metallic sheath.

C. Standards:

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

2. Comply with UL 1569.

3. Conductor and Cable Marking: Comply with wire and cable marking according to UL's

"Wire and Cable Marking and Application Guide."

D. Circuits:

1. Single circuit.

E. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B8 for stranded conductors.

F. Ground Conductor: Insulated.

G. Conductor Insulation:

1. Type TFN/THHN/THWN-2. Comply with UL 83.

2. Type XHHW-2. Comply with UL 44.

H. Armor: Aluminum, interlocked.

I. Jacket: PVC applied over armor.

1. Coordinate jacket color with Architect and Owner.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260519 - 3

2.3 CONNECTORS AND SPLICES

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. 3M Electrical Products

2. ABB, Electrification Business

3. Burndy; brand of Hubbell Electrical Solutions; Hubbell Incorporated

B. Description: Factory-fabricated connectors, splices, and lugs of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

C. Jacketed Cable Connectors: For steel and aluminum jacketed cables, zinc die-cast with set screws, designed to connect conductors specified in this Section.

D. Lugs: One piece, seamless, designed to terminate conductors specified in this Section.

1. Material: Copper.

2. Type: Two hole with long barrels.

3. Termination: Compression.

PART 3 - EXECUTION

3.1 CONDUCTOR MATERIAL APPLICATIONS

A. Feeders:

1. Copper; solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

B. Branch Circuits:

1. Copper:

a. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND

WIRING METHODS

A. Service Entrance: Type XHHW-2, single conductors in raceway.

B. Exposed Feeders: Type XHHW-2, single conductors in raceway.

C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Metal-clad cable, Type MC.

D. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type XHHW-2, single conductors in raceway.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260519 - 4

E. Exposed Branch Circuits, Including in Crawlspaces: Metal-clad cable, Type MC.

F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Metal-clad cable, Type MC.

G. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground: Type

XHHW-2, single conductors in raceway.

3.3 INSTALLATION, GENERAL

A. Conceal cables in finished walls, ceilings, and floors unless otherwise indicated.

B. Conceal cables with natural materials available in the Caverns ONLY. Do not bring materials into the Caverns from outside. Surface-run branch circuits out of view of observers on trails whenever possible. When not possible, conceal cables with rock debris. Do not bury cables.

C. Complete raceway installation between conductor and cable termination points in accordance with Section 260533.13 "Conduits for Electrical Systems" prior to pulling conductors and cables.

D. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

E. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

F. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

G. Support cables according to Section 260529 "Hangers and Supports for Electrical Systems."

3.4 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL

486A-486B.

B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inch of slack.

3.5 IDENTIFICATION

A. Identify and color-code conductors and cables according to Section 260553 "Identification for

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260519 - 5

Electrical Systems."

3.6 FIELD QUALITY CONTROL

A. Tests and Inspections:

1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors for compliance with requirements.

2. Perform each of the following visual and electrical tests:

a. Inspect exposed sections of conductor and cable for physical damage and correct connection according to the single-line diagram.

b. Test bolted connections for high resistance using one of the following:

1) A low-resistance ohmmeter.

2) Calibrated torque wrench.

3) Thermographic survey.

c. Inspect compression-applied connectors for correct cable match and indentation.

d. Inspect for correct identification.

e. Inspect cable jacket and condition.

f. Insulation-resistance test on each conductor for ground and adjacent conductors.

Apply a potential of 500 V(dc) for 300 V rated cable and 1000 V(dc) for 600 V rated cable for a one-minute duration.

g. Continuity test on each conductor and cable.

h. Uniform resistance of parallel conductors.

3. Initial Infrared Scanning: After Substantial Completion, but before Final Acceptance, perform an infrared scan of each splice in conductors No. 3 AWG and larger. Remove box and equipment covers so splices are accessible to portable scanner. Correct deficiencies determined during the scan.

a. Instrument: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

b. Record of Infrared Scanning: Prepare a certified report that identifies switches checked and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

B. Cables will be considered defective if they do not pass tests and inspections.

C. Prepare test and inspection reports to record the following:

1. Procedures used.

2. Results that comply with requirements.

3. Results that do not comply with requirements, and corrective action taken to achieve compliance with requirements.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260519 - 6

END OF SECTION 260519

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

GROUNDING AND BONDING FOR ELECTRICAL

SYSTEMS

260526 - 1

SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

1.1 SUMMARY

A. Section Includes:

1. Grounding and bonding conductors.

2. Grounding and bonding clamps.

3. Grounding and bonding bushings.

4. Grounding and bonding connectors.

5. Grounding (earthing) electrodes.

B. Related Requirements:

1. Section 260553 "Identification for Electrical Systems" specifies electrical equipment labels and warning signs installed by this Section.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Product Listing: Include copy of unexpired approval letter, on letterhead of qualified electrical testing agency, certifying product's compliance with specified listing criteria.

a. If listed manufacturer differs from selling manufacturer, indicate relationship between entities on submittal. Clearly indicate which entity warrants product performance and fitness for purpose.

b. Listing criteria identified in approval letter must match specified listing criteria.

UL label indicating approval of equipment's enclosure is not considered approval of equipment for intended application.

c. Product identification in approval letter must match product branding and model numbers in submittal. Approval letters for discontinued or superseded products are unacceptable for submitted product.

B. Field quality-control reports.

1.3 INFORMATIONAL SUBMITTALS

A. Manufacturer's published instructions.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 2

1.4 SERVICE CONDITIONS FOR ELECTRICAL EQUIPMENT

A. Electrical and ICT Equipment Grounding (Earthing): Do not exceed 25 Ω resistance to ground

(earth).

1. Contact Architect for resolution if 25 Ω specified resistance to ground (earth) is not attained after complying with prescriptive requirements in Article 250 of NFPA 70.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Regulatory Requirements: Products or components listed and labeled in accordance with NFPA

70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.

2.2 GROUNDING AND BONDING CONDUCTORS

A. ASTM - Bare Copper Grounding and Bonding Conductor:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ERICO; brand of nVent Electrical plc

b. Harger Lightning & Grounding; business of Harger, Inc.

2. Standard Features: Complying with one or more of the following:

a. Soft or Annealed Copper Wire: ASTM B3.

b. Concentric-Lay Stranded Copper Conductor: ASTM B8.

c. Tin-Coated Soft or Annealed Copper Wire: ASTM B33.

d. 19-Wire Combination Unilay-Stranded Copper Conductor: ASTM B787/B787M.

2.3 GROUNDING AND BONDING CLAMPS

A. Description: Clamps suitable for attachment of grounding and bonding conductors to grounding electrodes, pipes, tubing, and rebar. Grounding and bonding clamps specified in this article are also suitable for use with communications applications.

B. UL KDER and KDSH - Hex-Fitting-Type Pipe and Rod Grounding and Bonding Clamp:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Crouse-Hinds; brand of Eaton, Electrical Sector

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 3

b. ERICO; brand of nVent Electrical plc

c. Harger Lightning & Grounding; business of Harger, Inc.

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.

b. Grounding and Bonding Equipment for Communications: UL CCN KDSH;

including UL 467.

4. Standard Features:

a. Two pieces with stainless steel bolts.

b. Clamp Material: Silicon bronze.

c. Listed for outdoor use.

C. UL KDER and KDSH - U-Bolt-Type Pipe and Rod Grounding and Bonding Clamp:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Crouse-Hinds; brand of Eaton, Electrical Sector

b. ERICO; brand of nVent Electrical plc

c. Harger Lightning & Grounding; business of Harger, Inc.

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.

b. Grounding and Bonding Equipment for Communications: UL CCN KDSH;

including UL 467.

4. Standard Features:

a. Clamp Material: Brass.

b. Listed for outdoor use.

D. UL KDER and KDSH - Strap-Type Pipe and Rod Grounding and Bonding Clamp:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Burndy; brand of Hubbell Electrical Solutions; Hubbell Incorporated

b. Crouse-Hinds; brand of Eaton, Electrical Sector

c. ERICO; brand of nVent Electrical plc

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 4

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.

b. Grounding and Bonding Equipment for Communications: UL CCN KDSH;

including UL 467.

4. Standard Features:

a. Clamp Material: Aluminum.

b. Listed for outdoor use.

E. UL KDER - Beam Grounding and Bonding Clamp:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ABB, Electrification Business

b. Anderson; brand of Hubbell Utility Solutions; Hubbell Incorporated

c. Panduit Corp

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.

b. Grounding and Bonding Equipment for Communications: UL CCN KDSH;

including UL 467.

4. Standard Features: Mechanical-type, terminal, ground wire access from four directions;

with dual, tin-plated or silicon bronze bolts.

F. UL KDER - Exothermically Welded Connection:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Crouse-Hinds; brand of Eaton, Electrical Sector

b. ERICO; brand of nVent Electrical plc

c. Harger Lightning & Grounding; business of Harger, Inc.

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 5

a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.

b. Grounding and Bonding Equipment for Communications: UL CCN KDSH;

including UL 467.

4. Standard Features: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.

2.4 GROUNDING AND BONDING BUSHINGS

A. Description: Bonding bushings connect conduit fittings, tubing fittings, threaded metal conduit, and unthreaded metal conduit to metal boxes and equipment enclosures, and have one or more bonding screws intended to provide electrical continuity between bushing and enclosure.

Grounding bushings have provision for connection of bonding or grounding conductor and may or may not also have bonding screws.

B. UL KDER - Bonding Bushing:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ABB, Electrification Business

b. Crouse-Hinds; brand of Eaton, Electrical Sector

c. Killark; brand of Hubbell Electrical Solutions; Hubbell Incorporated

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.

4. Standard Features: Threaded bushing with insulated throat.

C. UL KDER - Grounding Bushing:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ABB, Electrification Business

b. Crouse-Hinds; brand of Eaton, Electrical Sector

c. Killark; brand of Hubbell Electrical Solutions; Hubbell Incorporated

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 6

4. Standard Features: Threaded bushing with insulated throat and mechanical-type wire terminal.

2.5 GROUNDING AND BONDING CONNECTORS

A. UL KDER - Split-Bolt Pressure-Type Grounding and Bonding Cable Connector:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ABB, Electrification Business

b. ERICO; brand of nVent Electrical plc

c. Greaves Corp.; Essex Products Group, Inc.

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.

b. Grounding and Bonding Equipment for Communications: UL CCN KDSH;

including UL 467.

4. Standard Features: Bolts that surround cable and bond to cable under compression when nut is tightened.

a. Copper.

2.6 GROUNDING (EARTHING) ELECTRODES

A. UL KDER - Rod Electrode:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ABB, Electrification Business

b. ERICO; brand of nVent Electrical plc

c. Harger Lightning & Grounding; business of Harger, Inc.

2. Source Limitations: Obtain products from single manufacturer.

3. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

4. Standard Features: Copper-clad steel[, sectional type]; 3/4 inch by 10 ft.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 7

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine facility's grounding electrode system and equipment grounding for compliance with requirements for maximum ground-resistance level and other conditions affecting performance of grounding and bonding of electrical system.

B. Inspect test results of grounding system measured at point of electrical service equipment connection.

C. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.

D. Proceed with connection of electrical service equipment only after unsatisfactory conditions have been corrected.

3.2 SELECTION OF GROUNDING AND BONDING PRODUCTS

A. Grounding and Bonding Conductors:

1. Provide solid conductor for 8 AWG and smaller, and stranded conductors for 6 AWG and larger unless otherwise indicated.

2. Custom-Length Insulated Equipment Bonding Jumpers: 6 AWG, 19-strand, Type THHN.

3. Bonding Cable: 28 kcmil, 14 strands of 17 AWG conductor, 1/4 inch in diameter.

4. Bonding Conductor: 4 AWG or 6 AWG, stranded conductor.

5. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-

5/8 inch wide and 1/16 inch thick.

6. Tinned Bonding Jumper: Tinned-copper tape, braided conductors terminated with copper ferrules; 1-5/8 inch wide and 1/16 inch thick.

7. Underground Grounding Conductors: Install bare copper conductor, 2/0 AWG minimum.

B. Grounding and Bonding Connectors:

1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.

2. Underground Connections: Welded connectors exceptas otherwise indicated.

3. Connections to Structural Steel: Welded connectors.

3.3 INSTALLATION OF GROUNDING AND BONDING

A. Comply with manufacturer's published instructions.

B. Reference Standards:

1. Electrical Construction: ICC IBC, ICC IFC, NFPA 1, NFPA 70, and NECA NEIS 1.

2. Electrical Maintenance: NFPA 70B.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 8

3. Electrical Safety: NFPA 70E.

4. Grounding and Bonding: NECA NEIS 331 and Article 250 of NFPA 70.

5. Communications Work: BICSI N1.

6. Consult Architect for resolution of conflicting requirements.

C. Special Techniques:

1. Grounding and Bonding Conductors:

a. Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.

2. Grounding and Bonding Connectors: Make connections so possibility of galvanic action or electrolysis is minimized. Select connectors, connection hardware, conductors, and connection methods so metals in direct contact are galvanically compatible.

a. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer in order of galvanic series.

b. Make connections with clean, bare metal at points of contact.

c. Make aluminum-to-steel connections with stainless steel separators and mechanical clamps.

d. Make aluminum-to-galvanized-steel connections with tin-plated copper jumpers and mechanical clamps.

e. Coat and seal connections having dissimilar metals with inert material to prevent future penetration of moisture to contact surfaces.

f. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit.

1) Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate adjacent parts.

2) Bonding to Equipment Mounted on Vibration Isolation Hangers and

Supports: Install bonding so vibration is not transmitted to rigidly mounted equipment.

3) Use exothermic-welded connectors for outdoor locations; if disconnect-type connection is required, use bolted clamp.

g. Grounding and Bonding for Piping:

1) Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes; use bolted clamp connector or bolt lug-type connector to pipe flange by using one of lug bolts of flange. Where dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.

3. Electrodes:

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 9

a. Ground Rods: Drive rods until tops are 2 inch below finished floor or final grade unless otherwise indicated.

1) Use exothermic welds for below-grade connections.

4. Grounding at Service:

a. Equipment grounding conductors and grounding electrode conductors must be connected to ground busbar. Install main bonding jumper between neutral and ground buses.

5. Equipment Grounding and Bonding:

a. Install insulated equipment grounding conductors with feeders and branch circuits.

3.4 FIELD QUALITY CONTROL FOR GROUNDING AND BONDING

A. Administrant for Electrical Power Tests and Inspections:

1. Engage qualified electrical testing and inspecting agency to administer and perform tests and inspections.

B. Tests and Inspections:

1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.

2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with calibrated torque wrench in accordance with manufacturer's published instructions.

C. Nonconforming Work:

1. Grounding system will be considered defective if it does not pass tests and inspections.

2. Remove and replace defective components and retest.

D. Collect, assemble, and submit test and inspection reports.

1. Report measured ground resistances that exceed the following values:

a. Power and Lighting Equipment or System with Capacity of 500 kVA and Less: 10

Ω.

3.5 PROTECTION

A. After installation, protect grounding and bonding cables and equipment from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260526 - 10

END OF SECTION 260526

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

HANGERS AND SUPPORTS FOR ELECTRICAL

260529 - 1

SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

1.1 SUMMARY

A. Section Includes:

1. Support systems.

2. Mounting, anchoring, and attachment components.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for the following:

a. Slotted support systems, hardware, and accessories.

b. Clamps.

c. Hangers.

d. Sockets.

e. Eye nuts.

f. Fasteners.

g. Anchors.

h. Saddles.

i. Brackets.

2. Include rated capacities and furnished specialties and accessories.

PART 2 - PRODUCTS

2.1 SUPPORT SYSTEMS

A. Steel Slotted Support Systems:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Atkore Unistrut

b. Cooper B-line; brand of Eaton, Electrical Sector

c. Flex-Strut Inc.

2. Standard Features: Preformed steel channels and angles with minimum 13/32 inch

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260529 - 2 diameter holes at a maximum of 8 inch on center in at least one surface.

a. Referenced Standard: MFMA-4 factory-fabricated components for field assembly.

b. Material for Channel, Fittings, and Accessories: Stainless steel, Type 316.

c. Channel Width: 1-5/8 inch.

B. Conduit and Cable Support Devices:

1. Standard Features: Stainless steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.

2.2 MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS

A. Mechanical-Expansion Anchors:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Cooper B-line; brand of Eaton, Electrical Sector

b. Hilti, Inc.

c. MKT Fastening, LLC

2. Standard Features: Insert-wedge-type, stainless steel, for use in hardened portland cement concrete, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.

B. Concrete Inserts:

1. Standard Features: Steel or malleable-iron, slotted support system units are similar to

MSS Type 18 units and comply with MFMA-4 or MSS SP-58.

C. Clamps for Attachment to Steel Structural Elements:

1. Standard Features: MSS SP-58 units are suitable for attached structural element.

D. Through Bolts:

1. Standard Features: Structural type, hex head, and high strength. Comply with ASTM

F3125/F3125M, Grade A325.

E. Toggle Bolts:

1. Standard Features: Stainless steel springhead type.

F. Hanger Rods:

1. Standard Features: Threaded steel.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260529 - 3

PART 3 - EXECUTION

3.1 SELECTION OF HANGERS AND SUPPORTS

A. Maximum Support Spacing and Minimum Hanger Rod Size for Raceways: Space supports for

EMT, IMC, and ERMC as NFPA 70. Minimum rod size must be 1/4 inch in diameter.

B. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

1. Secure raceways and cables to these supports with two-bolt conduit clamps.

C. Spring-steel clamps designed for supporting single conduits without bolts may be used for 1-

1/2 inch and smaller raceways serving branch circuits and communication systems above suspended ceilings, and for fastening raceways to trapeze supports.

3.2 INSTALLATION OF HANGERS AND SUPPORTS

A. Comply with manufacturer's published instructions.

B. Reference Standards for Installation: Unless more stringent installation requirements are specified in the Contract Documents or manufacturer's published instructions, comply with the following:

1. Electrical Construction: ICC IBC, ICC IFC, NFPA 1, NFPA 70, and NECA NEIS 1.

2. Work in Confined Spaces: NFPA 350.

3. Consult Architect for resolution of conflicting requirements.

C. Special Installation Techniques:

1. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination must be weight of supported components plus 200 lb.

2. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:

a. To Masonry: Approvedexpansion anchor fasteners on solid masonry units.

b. To Steel: Beam clamps (MSS SP-58, Type 19, 21, 23, 25, or 27), complying with

MSS SP-69.

3. Drill holes for expansion anchors in concrete at locations and to depths that avoid the need for reinforcing bars.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

260529 - 4

END OF SECTION 260529

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 1

SECTION 260533.13 - CONDUITS FOR ELECTRICAL SYSTEMS

1.1 SUMMARY

A. Section Includes:

1. Type PVC duct raceways and fittings.

B. Related Requirements:

1. Section 260519 "Low-Voltage for Electrical Power Conductors and Cables" specifies nonmetallic underground conduit with conductors (Type NUCC).

2. Section 260529 "Hangers and Supports for Electrical Systems" specifies conduit hangers and supports referenced by this Section.

3. Section 260553 "Identification for Electrical Systems" specifies electrical equipment labels.

1.2 REFERENCES

A. Abbreviations and Acronyms for Electrical Raceway Types:

1. PVC-40: Schedule 40 rigid PVC conduit.

2. PVC-80: Schedule 80 rigid PVC Conduit.

B. Definitions:

1. Conduit: A structure containing one or more duct raceways.

2. Direct Buried: Installed underground without encasement in concrete or other protective material.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Field quality-control reports.

1.4 INFORMATIONAL SUBMITTALS

A. Manufacturer's published instructions.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 2

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Regulatory Requirements: Products or components listed and labeled in accordance with NFPA

70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.

2.2 TYPE PVC DUCT RACEWAYS AND FITTINGS

A. UL DZYR - Schedule 40 Rigid PVC Conduit (PVC-40) and Fittings:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ABB, Electrification Business

b. Calconduit; Atkore International

c. JM Eagle

2. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. UL CCN DZYR; including UL 651.

3. Standard Features:

a. Dimensional Specifications: Schedule 40.

b. Markings: For use with maximum 90 deg C wire.

B. UL DZYR - Schedule 80 Rigid PVC Conduit (PVC-80) and Fittings:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. ABB, Electrification Business

b. Calconduit; Atkore International

c. JM Eagle

2. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following

UL product categories:

a. UL CCN DZYR; including UL 651.

3. Standard Features:

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 3

a. Dimensional Specifications: Schedule 80.

b. Markings: For use with maximum 90 deg C wire.

PART 3 - EXECUTION

3.1 INSTALLATION OF CONDUITS FOR ELECTRICAL SYSTEMS

A. Comply with manufacturer's published instructions.

B. Reference Standards for Installation: Unless more stringent installation requirements are specified in the Contract Documents or manufacturer's published instructions, comply with the following:

1. Electrical Construction: ICC IBC, ICC IFC, NFPA 1, NFPA 70, and NECA NEIS 1.

2. Grounding and Bonding: NECA NEIS 331 and Article 250 of NFPA 70.

3. Communications Work: BICSI N1.

4. Emergency and Standby Power Work: NFPA 110, NFPA 111, and NECA NEIS 416.

5. Work in Basements and Other Developed Subterranean Spaces: NFPA 520.

6. Type EMT-SS: Article 358 of NFPA 70 and NECA NEIS 101.

7. Type ERMC-SS: Article 344 of NFPA 70 and NECA NEIS 101.

8. Type ERMC-S: Article 344 of NFPA 70 and NECA NEIS 101.

9. Type LFMC: Article 350 of NFPA 70 and NECA NEIS 101.

10. Type PVC: Article 356 of NFPA 70 and NECA NEIS 111.

C. Special Installation Techniques:

1. General Requirements for Installation of Duct Raceways:

a. Complete duct raceway installation before starting conductor installation.

b. Make bends in duct raceway using large-radius preformed ells except for parallel bends. Field bending must be in accordance with NFPA 70 minimum radii requirements. Provide only equipment specifically designed for material and size involved.

c. Support conduit within 12 inch of enclosures to which attached.

d. Cut conduit perpendicular to the length. For conduits metric designator 53 (trade size 2) and larger, use roll cutter or a guide to make cut straight and perpendicular to the length. Ream inside of conduit to remove burrs.

e. Install pull wires in empty duct raceways. Provide polypropylene or monofilament plastic line with not less than 200 lb tensile strength. Leave at least 12 inch of slack at both ends of pull wire. Cap underground duct raceways designated as spare above grade alongside duct raceways in use.

f. Install duct raceways square to the enclosure and terminate at enclosures without hubs with locknuts on both sides of enclosure wall. Install locknuts hand tight, plus one-quarter turn more.

1) Termination fittings with shoulders do not require two locknuts.

Task Order 12445221D0017/12445123F0023

JLA#3094.2302

Fifty-Six, Arkansas

CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 4

g. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to metric designator

35 (trade size 1-1/4) and insulated throat metal bushings on metric designator 41

(trade size 1-1/2) and larger conduits terminated with locknuts. Install insulated throat metal grounding bushings on service conduits.

2. Types ERMC and IMC:

a. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor

Conditions: Apply listed compound that maintains electrical…

This is the start of the file's text. The full file is on GovTribe.