C04_Attachment 6 Boiler 3 - Drawing Binder.pdf
PDF 10 MB Posted
- Attached to
- WRRC Boiler Upgrades Federal contract opportunity
- Solicitation number
- 1232SA26R0033
About this file
This document is a design package for boiler upgrades at the Western Regional Research Center (WRRC), an Agricultural Research Service facility located in Albany, California. The work encompasses mechanical and electrical design for replacement of existing boilers and associated heating water systems in the West Annex Building.
The project scope includes five sequential work sequences: (1) demolition and replacement of boilers B-9 and B-10 with new high-efficiency condensing boilers, with one boiler offline at a time to maintain operational status; (2) through (5) installation of electronic actuated heating water control valves with networked thermostat controllers on the first through fourth floors of the West Annex Building, with each floor's reheat coils requiring full operational balance before advancing to the next sequence. The contractor must provide 14 days advance notice before any outages and submit a detailed work sequencing plan for approval prior to commencing work. New equipment includes Lochinvar Crest high-efficiency condensing boilers (1500 MBH input, 1380 MBH output) and Bell & Gossett base-mounted and inline heating water pumps. Control systems utilize networked thermostats with stand-alone operation capability and future BACnet DDC system integration. All work must comply with ASME, ASHRAE, and IMC standards; the Buy American Act applies to all equipment. The project includes environmental work addressing lead-based paint disturbance with contractor-submitted design required prior to performance. Design documents include comprehensive mechanical details, equipment schedules, control sequences, piping legends, and electrical connections for both demolition and new work across all building floors.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_1232SA26R0033_Amd_0002.pdf | ||
| RFI-AE Responses.docx | DOCX document | |
| 33PLMs-1-20-26-4384058_R1257169.pdf | ||
| 8LEADs-1-20-26-4384048_R1257169.pdf | ||
| Sol_1232SA26R0033_Amd_0001.pdf | ||
| C04_Sol_1232SA26R0033.pdf | ||
| C04_Attachment 3 Boiler 2 - Specifications.pdf | ||
| C04_Attachment 5 Boiler 3 - Specifications.pdf | ||
| C04_Attachment 8 Schedule of Pricing.xlsx | XLSX spreadsheet | |
| C04_ Attachment 1 Boiler 1 - Specifications.pdf | ||
| C04_Attachment 7 Wage Determination CA20260018.pdf | ||
| C04_Attachment 2 Boiler 1 - Drawings Binder.pdf | ||
| C04_Attachment 4 Boiler 2 - Drawings Binder.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WESTERN REGIONAL RESEARCH CENTER (WRRC)
AGRICULTURAL RESEARCH SERVICE
U.S. DEPARTMENT OF AGRICULTURE
ALBANY, CALIFORNIA
USDA
BOILER UPGRADES DESIGN (CONTRACT 3)
U
D A
S
Dustin Caruso
WRRC C1 & C3
DRAWING NO.
INDEX OF DRAWINGS
SHEET NO. TITLE
LEGEND AND SYMBOLS
GENERAL
T-100
T-101
TITLE SHEET
DRAWING INDEX, GENERAL NOTES, AND LEGEND
M-001
MD101
MD102
MD103
MD104
MD401
M-101
M-102
M-103
M-104
M-401
M-501
M-601
M-701
GENERAL NOTES, ABBREVIATIONS, AND LEGEND
WEST ANNEX BUILDING 1ST FLOOR MECHANICAL DEMOLITION PLAN
WEST ANNEX BUILDING 2ND FLOOR MECHANICAL DEMOLITION PLAN
WEST ANNEX BUILDING 3RD FLOOR MECHANICAL DEMOLITION PLAN
WEST ANNEX BUILDING 4TH FLOOR MECHANICAL DEMOLITION PLAN
WEST ANNEX BUILDING ENLARGED MECHANICAL DEMOLITION PLAN
WEST ANNEX BUILDING 1ST FLOOR MECHANICAL NEW WORK PLAN
WEST ANNEX BUILDING 2ND FLOOR MECHANICAL NEW WORK PLAN
WEST ANNEX BUILDING 3RD FLOOR MECHANICAL NEW WORK PLAN
WEST ANNEX BUILDING 4TH FLOOR MECHANICAL NEW WORK PLAN
WEST ANNEX BUILDING ENLARGED MECHANICAL NEW WORK PLAN
MECHANICAL DETAILS
MECHANICAL SCHEDULES
MECHANICAL CONTROLS
MECHANICAL
ELECTRICAL
ED101
ED102
ED103
ED104
ED401
E-000
E-101
E-102
E-103
E-104
E-401
WEST ANNEX BUILDING 1ST FLOOR ELECTRICAL DEMOLITION PLAN
WEST ANNEX BUILDING 2ND FLOOR ELECTRICAL DEMOLITION PLAN
WEST ANNEX BUILDING 3RD FLOOR ELECTRICAL DEMOLITION PLAN
WEST ANNEX BUILDING 4TH FLOOR ELECTRICAL DEMOLITION PLAN
WEST ANNEX BUILDING ENLARGED ELECTRICAL DEMOLITION PLAN
ELECTRICAL LEGEND
WEST ANNEX BUILDING 1ST FLOOR ELECTRICAL NEW WORK PLAN
WEST ANNEX BUILDING 2ND FLOOR ELECTRICAL NEW WORK PLAN
WEST ANNEX BUILDING 3RD FLOOR ELECTRICAL NEW WORK PLAN
WEST ANNEX BUILDING 4TH FLOOR ELECTRICAL NEW WORK PLAN
WEST ANNEX BUILDING ENLARGED ELECTRICAL NEW WORK PLAN
DRAWING INDEX, GENERAL
NOTES, AND LEGEND
T-101
U
D A
S
SHEET SHOWN ON
PLAN, DETAIL OR SECTION NUMBER
PLAN, DETAIL OR SECTION TITLE
PLAN, DETAIL OR SECTION NUMBER
SHEET SHOWN ON
PLAN, DETAIL OR SECTION SCALE
ROOM MARK
ROOM NUMBER
DETAIL MARK
DRAWING TITLE
SCALE:
FLOOR PLAN
1/16" = 1'-0"
SHEET SHOWN ON
PLAN, DETAIL OR SECTION NUMBER
PLAN, DETAIL OR SECTION TITLE
PLAN, DETAIL OR SECTION NUMBER
SHEET SHOWN ON
PLAN, DETAIL OR SECTION SCALE
ROOM MARK
ROOM NUMBER
DETAIL MARK
DRAWING TITLE
SCALE:
FLOOR PLAN
1/16" = 1'-0"
WORK SEQUENCING NOTES
GENERAL WORK SEQUENCING NOTES:
THE CONTRACTOR MUST PROVIDE THE GOVERNMENT 14-DAYS NOTICE PRIOR TO ANY OUTAGE. A DETAILED WORK
SEQUENCING PLAN MUST BE SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL PRIOR TO THE
COMMENCEMENT OF ANY DEMOLITION OR NEW WORK.
WORK SEQUENCE #1:
DEMOLISH EXISTING B-9, B-10, AND ASSOCIATED PUMPS LOCATED IN THE FIRST FLOOR MECHANICAL ROOM. PROVIDE NEW B-9, B-10, AND ASSOCIATED PUMPS. CONNECT NEW BOILERS AND PUMPS TO EXISTING CONTROL SYSTEM. B-9 AND B-10 BOILER
PLANT MUST BE FULLY OPERATIONAL, BALANCED, AND ASSOCIATED WORK COMPLETED PRIOR TO MOVING ON TO WORK
SEQUENCE #2.
DURING THE BOILER REPLACEMENT UNDER THIS WORK SEQUENCE, ONLY ONE BOILER MUST BE TAKEN OFFLINE AND
REPLACED AT A TIME. BEFORE MOVING ONTO THE NEXT BOILER IN THIS SEQUENCE, THE PREVIOUS BOILER MUST BE FULLY
OPERATIONAL.
CONTRACTOR MUST CONDUCT THE BOILER REPLACEMENT WORK UNDER THIS SEQUENCE FIRST. EXISTING HWP-5, HWP-6, HWP-7, AND HWP-8 MUST REMAIN FULLY OPERATIONAL UNTIL THE BOILER REPLACEMENT IS COMPLETED.
WORK SEQUENCE #2:
PROVIDE CONTROL VALVES FOR FIRST FLOOR OF WEST ANNEX BUILDING. FIRST FLOOR REHEAT COILS MUST BE FULLY
OPERATIONAL, BALANCED, AND ASSOCIATED WORK COMPLETED PRIOR TO MOVING ON TO WORK SEQUENCE #3.
WORK SEQUENCE #3:
PROVIDE CONTROL VALVES FOR SECOND FLOOR OF WEST ANNEX BUILDING. SECOND FLOOR REHEAT COILS MUST BE FULLY
OPERATIONAL, BALANCED, AND ASSOCIATED WORK COMPLETED PRIOR TO MOVING ON TO WORK SEQUENCE #4.
WORK SEQUENCE #4:
PROVIDE CONTROL VALVES FOR THIRD FLOOR OF WEST ANNEX BUILDING. THIRD FLOOR REHEAT COILS MUST BE FULLY
OPERATIONAL, BALANCED, AND ASSOCIATED WORK COMPLETED PRIOR TO MOVING ON TO WORK SEQUENCE #5.
WORK SEQUENCE #5:
PROVIDE CONTROL VALVES FOR FOURTH FLOOR OF WEST ANNEX BUILDING. FOURTH FLOOR REHEAT COILS MUST BE FULLY
OPERATIONAL, BALANCED, AND ASSOCIATED WORK COMPLETED PRIOR PROJECT CLOSEOUT.
ENVIRONMENTAL NOTES
1. CONTRACTOR MUST ASSUME THAT ALL EXISTING PAINT COATINGS CONTAIN LEAD. IT IS NOT THE INTENT
OF THIS PROJECT TO PROVIDE A COMPREHENSIVE LEAD-BASED PAINT REMEDIATION, BUT
DISTURBANCE OF SOME PAINT-COATED SURFACES WILL BE REQUIRED TO PERFORM THE WORK.
WHERE EXISTING PAINTED SURFACES ARE DISTURBED (DRILLING, CUTTING, ETC.), THE
CONTRACTOR MUST PROVIDE WORKER PROTECTION IN ACCORDANCE WITH OSHA, AND ANY LOOSE
COATINGS AND COATING DUST MUST BE DISPOSED OF AS A HAZARDOUS LEAD WASTE. PAINTED
MATERIALS THAT ARE REMOVED AND DISPOSED OF MAY BE DISPOSED AS NORMAL CONSTRUCTION
WASTE PROVIDED THE COATINGS ARE INTACT ON THE MATERIAL BEING DISPOSED.
2. THE CONTRACTOR MUST PROVIDE A DESIGN FOR THE ENVIRONMENTAL WORK AS A SUBMITTAL FOR
APPROVAL PRIOR TO PERFORMING ANY ENVIRONMENTAL WORK.
GENERAL NOTES, ABBREVIATIONS,
AND LEGEND
M-001
U
D A
S
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY WORK IS PERFORMED. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE RELOCATED AS REQUIRED AT NO
ADDITIONAL COST TO THE OWNER.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, AND EQUIPMENT IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR
FOR REVIEW AND COORDINATION.
4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE AND INTERNATIONAL BUILDING CODE / INTERNATIONAL
MECHANICAL CODE.
5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL OR MODIFICATION
TO OTHER PIPING, WIRING, OR EQUIPMENT.
6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT
AND RELATED ACCESSORIES.
7. COORDINATE WALL, FLOOR, AND ROOF PENETRATIONS WITH THE CONTRACTOR OFFICER.
8. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT PIPING AND EQUIPMENT FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE HVAC
CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
9. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS. ACTUAL LOCATIONS SHALL BE
FIELD DETERMINED.
10. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.
11. FOR WALL, FLOOR, AND SLAB PENETRATIONS, SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING CONSTRUCTION/FINISH OR AS SHOWN ON MECHANICAL DETAILS SHEET. PROVIDE FIRE STOPPING FOR RATED WALLS AND FLOORS.
12. INSTALL CONTROL WIRING IN GREEN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.
13. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
14. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE
THE SPECIFICATION HAS OPTIONS.
15. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.
16. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE.
17. CONTROLS CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, CONDUIT AND PATHWAYS IN ACCORDANCE WITH THE
REQUIREMENTS OF 26 20 00.
18. NOT ALL ABBREVIATIONS AND LEGEND ITEMS WILL BE USED.
GENERAL MECHANICAL NOTES: ABBREVIATIONS:
@ AT
& AND
AHU AIR HANDLING UNIT
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING,
AND AIR CONDITIONING ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
BD BALANCING DAMPER
BDD BACKDRAFT DAMPER
BLDG BUILDING
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
COND STEAM CONDENSATE
CONN CONNECT, CONNECTING, CONNECTION
CON CONTINUED
COV STEAM CONVERTER
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DFCU DUCTLESS FAN COIL UNIT
DH DEHUMIDIFIER
DIA, Ø DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE,
PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
EMCS ENERGY MONITORING AND CONTROLS
SYSTEM
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXIST. EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
H HEIGHT
HPS HIGH PRESSURE STEAM
HR HOUR
HTG HEATING
HTR HEATER
HTW HEATING WATER
HWR HEATING WATER RETURN
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBD LINEAR BAR DIFFUSER
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFCR, MFG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP, MOP MAXIMUM OVER CURRENT PROTECTION
MTWR MEDIUM TEMPERATURE WATER RETURN
MTWS MEDIUM TEMPERATURE WATER SUPPLY
MXB MIXING BOX
N.C. NORMALLY CLOSED
NC NOISE CRITERIA
NG NATURAL GAS
NO. NUMBER
N.C. NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PCHWR PLANT CHILLED WATER RETURN
PCHWS PLANT CHILLED WATER SUPPLY
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PMTWR PLANT MEDIUM TEMPERATURE
WATER RETURN
PMTWS PLANT MEDIUM TEMPERATURE
WATER SUPPLY
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
SAG SUPPLY AIR GRILLE
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
STM STEAM
SS STAINLESS STEEL
TEMP TEMPERATURE
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL
SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME TERMINAL UNIT
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
VVS VARIABLE VOLUME SUPPLY TERMINAL
UNIT
VVLE VARIABLE VOLUME EXHAUST TERMINAL
UNIT
WB, Twb WET BULB (TEMPERATURE)
A
J
SD
SP
F
CO
T
VFD
T
H
TH
H
DP
C
AQ
PS
FS
X
MISCELLANEOUS LEGEND:
A
J
SD
SP
F
CO
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
CONTROL WIRING
STATIC PRESSURE SENSOR
ROUND OR DIAMETER
FIRESTAT
TEMPERATURE SENSORT
120 VOLT STAND BY POWER JUNCTION
BOX PROVIDED BY THE ELECTRICAL
CONTRACTOR. JUNCTION BOX IS
DEDICATED FOR USE BY THE
CONTROLS CONTRACTOR.
VARIABLE FREQUENCY DRIVEVFD
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
FLOW ARROWS INDICATE AIR PATTERN.
NO FLOW ARROWS SHOWN INDICATES
4-WAY PATTERN.
EXHAUST AIR GRILLE
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START/ STOP SWITCH
TH THERMOSTAT/ HUMIDISTAT
HUMIDITY SENSORH
DP DIFFERENTIAL PRESSURE SENSOR
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
POINT OF RECONNECTION OR
EXTENT OF DEMOLITION
PIPING LEGEND:
FLEXIBLE CONNECTION
THERMOMETER
PRESSURE REDUCING VALVE
MANUAL AIR VENT
PRESSURE/TEMPERATURE TAP WITH
BALL VALVE
PRESSURE SWITCH
PLUG VALVE
FLOW SWITCH
T&P RELIEF VALVE
AUTOMATIC AIR VENT
PRESSURE GAUGE WITH GAUGE COCK
PS
FS
BUTTERFLY VALVE
STRAINER WITH BLOWDOWN VALVE,
CAP, AND CHAIN
FLOW MEASURING/BALANCING/SHUT-
OFF VALVE
GATE VALVE
CHECK VALVE
BALL VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
PIPE FLANGE
PIPE CAP
PIPE GUIDE (PG)
PIPE ANCHOR (PA) X
UNION
TEE OUTLET UP
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
ELBOW UP
ELBOW DOWN
RISE OR DROP
TEE OUTLET DOWN
GLOBE VALVE
ELEC.
SKYLIGHT
PANEL 1E
FURR DN.
COMM.
SCALE:
WEST ANNEX FIRST FLOOR MECHANICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 1ST FLOOR
MECHANICAL DEMOLITION PLAN
MD101
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
CH-51
HC-6 1
CH-4 1
CH-31
CH-2 1
CH-9 1
CH-61
CH-101 CH-8 1
CH-71
HC-11 1
HC-12 1
RHC-1 1
CH-11
1. DEMOLISH EXISTING PNEUMATICALLY ACTUATED
HEATING VALVE, ZONE CONTROLLER, AND
ASSOCIATED THERMOSTAT. CAP EXISTING PNEUMATIC
LINES. DEMOLISH EXISTING HTWS AND HTWR PIPING
BACK TO COIL ISOLATION VALVES.
U
D A
S
CORRIDOR
OFFICE AREA
RECEPTION
ELEV.
CORRIDOR
CORRIDOR
CORRIDOR
STAIR #1
SCALE:
WEST ANNEX SECOND FLOOR MECHANICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 2ND FLOOR
MECHANICAL DEMOLITION PLAN
MD102
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
CH-13
CH-16
CH-17
CH-15
CH-18
CH-36
CH-37
CH-32
CH-35
CH-38
CH-34
CH-33
CH-20
CH-21
CH-19
1. DEMOLISH EXISTING PNEUMATICALLY ACTUATED
HEATING VALVE, ZONE CONTROLLER, AND
ASSOCIATED THERMOSTAT. CAP EXISTING PNEUMATIC
LINES. DEMOLISH EXISTING HTWS AND HTWR PIPING
BACK TO COIL ISOLATION VALVES.
U
D A
S
UP DNCORRIDOR
CORRIDOR
ELEV.
CORRIDOR
SHOWER
CORRIDOR
STORAGE
STAIR #1
SCALE:
WEST ANNEX THIRD FLOOR MECHANICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 3RD FLOOR
MECHANICAL DEMOLITION PLAN
MD103
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
RHC-313
RHC-312B
RHC-312A
RHC-309
HC-24
RHC-310
RHC-308
RHC-307
RHC-306
RHC-305
HC-28
1. DEMOLISH EXISTING PNEUMATICALLY ACTUATED
HEATING VALVE, ZONE CONTROLLER, AND
ASSOCIATED THERMOSTAT. CAP EXISTING PNEUMATIC
LINES. DEMOLISH EXISTING HTWS AND HTWR PIPING
BACK TO COIL ISOLATION VALVES.
U
D A
S
U P
SHAFT
STAIR #1
ROOF
ROOF
ROOF
ROOFROOF
SCALE:
WEST ANNEX FOURTH FLOOR MECHANICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 4TH FLOOR
MECHANICAL DEMOLITION PLAN
MD104
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
RHC-406
RHC-406A RHC-406B RHC-405 RHC-404A
RHC-404 RHC-400
RHC-404B
1. DEMOLISH EXISTING PNEUMATICALLY ACTUATED
HEATING VALVE, ZONE CONTROLLER, AND
ASSOCIATED THERMOSTAT. CAP EXISTING PNEUMATIC
LINES. DEMOLISH EXISTING HTWS AND HTWR PIPING
BACK TO COIL ISOLATION VALVES.
U
D A
S
HWP-6
SCALE:
MAIN BUILDING BASEMENT MECHANICAL DEMOLITION PLAN
3/8" = 1'-0"
WEST ANNEX BUILDING ENLARGED
MECHANICAL DEMOLITION PLAN
MD401
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/8"=1'-0"
0 1' 2' 4' 8'
1. DEMOLISH EXISTING BOILER (B-9), COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP,
AND ALL OTHER APPURTENANCES. DEMOLISH
HEATING WATER SUPPLY AND RETURN PIPING UP TO
BOILER ISOLATION VALVES.
2. DEMOLISH EXISTING BOILER (B-10),COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP, ,
AND ALL OTHER APPURTENANCES. DEMOLISH
HEATING WATER SUPPLY AND RETURN PIPING UP TO
BOILER ISOLATION VALVES.
3. DEMOLISH EXISTING BASE MOUNTED HEATING WATER
PUMP AND INERTIA BASE. DEMOLISH EXISTING
HEATING WATER PIPING UP TO PUMP ISOLATION
VALVES. PUMP MUST BE TURNED OVER TO THE
GOVERNMENT AND DELIVERED TO A LOCATION ON
SITE DETERMINED BY THE CONTRACTING OFFICER.
4. DEMOLISH EXISTING INLINE HEATING WATER PUMP.
DEMOLISH EXISTING HEATING WATER PIPING UP TO
PUMP ISOLATION VALVES. PUMP MUST BE TURNED
OVER TO THE GOVERNMENT AND DELIVERED TO A
LOCATION ON SITE DETERMINED BY THE
CONTRACTING OFFICER.
5. DEMOLISH EXISTING NATURAL GAS PIPING UP TO
EXISTING ISOLATION VALVE. DEMOLISH EXISTING
BOILER ISOLATION VALVES AND REGULATORS.
HWP-7
HWP-5
HWP-8
4 4
U
D A
S
DEMOLISH EXIST. BOILER
EXIST. HOUSEKEEPING PAD
TO REMAIN
DEMOLISH
EXIST. ASME
PRESSURE
RELIEF VALVE
DEMOLISH EXIST. BOILER
PRIMARY PUMP
DEMOLISH EXIST.
PRESSURE GAUGE (TYP.)
DEMOLISH EXIST.
STRAINER
DEMOLISH EXIST.
THERMOMETER (TYP.)
DEMOLISH EXIST. BOILER
DRAIN AND VALVE
DEMOLISH EXIST. 4" HTWS
& 4" HTWR PIPING (TYP.)
EXIST. 4" HTWS TO REMAINEXIST. 4" HTWR TO REMAIN
DEMOLISH EXIST. NGEXIST.
BUTTERFLY ISOLATION
VALVE TO REMAIN (TYP. 2)
SCALE:
EXIST. B-9, & B-10 DEMOLITION DETAIL
NTS
DEMOLISH EXISTING
INERTIA BASE
DEMOLISH EXIST. PUMP
AND MOTOR
DEMOLISH EXIST. BRAIDED
FLEX CONNECTOR (TYP. 2)
DEMOLISH EXIST. SUCTION
DIFFUSER
EXIST. ISOLATION GATE
VALVE (TYP. 2) TO REMAIN
EXIST. HEATING WATER PIPING
P-5 (2-1/2")
P-6 (6") P-7 (6") P-8 (6")
EXIST. HEATING WATER PIPING
P-5 (2-1/2") P-6 (6") P-7 (6") P-8 (6")
SCALE:
EXIST. HWP-5, HWP-6, HWP-7, AND HWP-8 DEMOLITION DETAIL
NTS
DEMOLISH EXIST. CHECK
VALVE
NOTE:
SEVERAL CONDITIONS EXIST REGARDING THE VALVING AND PIPING BETWEEN THE
ISOLATION VALVES AND THE PUMPS IN THE WEST ANNEX MECHANICAL ROOM. THE
INTENT IS TO DEMOLISH ALL PIPING, VALVES, REDUCERS, ETC. BETWEEN THE
ISOLATION VALVES AND THE PUMPS.
DEMOLISH EXIST. PIPING
(TYP.)
PANEL 1E
FURR DN.
COMM.
SCALE:
WEST ANNEX FIRST FLOOR MECHANICAL NEW WORK PLAN
3/32" = 1'-0"
C.E.
MECH
ROOM
WEST ANNEX BUILDING 1ST FLOOR
MECHANICAL NEW WORK PLAN
M-101
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
CH-51
HC-6 1
CH-4 1
CH-3 1
CH-2 1
CH-91
CH-61
CH-101 CH-8 1
CH-71
HC-11 1
HC-12 1
RHC-1 1CH-11
1. PROVIDE ELECTRONIC ACTUATED HEATING WATER
CONTROL VALVE, STAND ALONE NETWORKED
THERMOSTAT CONTROLLER, AND COIL DISCHARGE
AIR TEMPERATURE SENSOR. PROVIDE CONTROL
POWER TRANSFORMER ABOVE CEILING TO POWER
NETWORKED THERMOSTAT CONTROLLER, SEE
ELECTRICAL FOR POWER SUPPLY TO CONTROL
POWER TRANSFORMER. THERMOSTAT MUST INCLUDE
ALL PROGRAMMING AND HARDWARE NECESSARY FOR
STAND ALONE CONTROL OF THE REHEAT COIL
CONTROL VALVE. INSTALL NEW DISCHARGE AIR
SENSOR IN DUCTWORK DOWNSTREAM OF REHEAT
COIL AND CONNECT TO NETWORKED THERMOSTAT.
NETWORKED THERMOSTAT MUST BE PROVIDED WITH
HARDWARE CAPABLE OF FUTURE INTEGRATION INTO
A BACNET DDC SYSTEM.
U
D A
S
RECEPTION
ELEV.
CORRIDOR
CORRIDOR
CORRIDOR
STAIR #1
SCALE:
WEST ANNEX SECOND FLOOR MECHANICAL NEW WORK PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 2ND FLOOR
MECHANICAL NEW WORK PLAN
M-102
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
U
D A
S
1. PROVIDE ELECTRONIC ACTUATED HEATING WATER
CONTROL VALVE, STAND ALONE NETWORKED
THERMOSTAT CONTROLLER, AND COIL DISCHARGE
AIR TEMPERATURE SENSOR. PROVIDE CONTROL
POWER TRANSFORMER ABOVE CEILING TO POWER
NETWORKED THERMOSTAT CONTROLLER, SEE
ELECTRICAL FOR POWER SUPPLY TO CONTROL
POWER TRANSFORMER. THERMOSTAT MUST INCLUDE
ALL PROGRAMMING AND HARDWARE NECESSARY FOR
STAND ALONE CONTROL OF THE REHEAT COIL
CONTROL VALVE. INSTALL NEW DISCHARGE AIR
SENSOR IN DUCTWORK DOWNSTREAM OF REHEAT
COIL AND CONNECT TO NETWORKED THERMOSTAT.
NETWORKED THERMOSTAT MUST BE PROVIDED WITH
HARDWARE CAPABLE OF FUTURE INTEGRATION INTO
A BACNET DDC SYSTEM.
CH-13 CH-16
CH-17
CH-15
CH-18
CH-36
CH-37
CH-32
CH-35
CH-38
CH-34
CH-33
CH-20
CH-21
CH-19
CORRIDOR
ELEV.
CORRIDOR
SHOWER
CORRIDOR
STORAGE
STAIR #1
SCALE:
WEST ANNEX THIRD FLOOR MECHANICAL NEW WORK PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 3RD FLOOR
MECHANICAL NEW WORK PLAN
M-103
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
RHC-313
RHC-312B
RHC-312A
RHC-309
HC-24
RHC-310
RHC-308
RHC-307
RHC-306
RHC-305
HC-28
U
D A
S
1. PROVIDE ELECTRONIC ACTUATED HEATING WATER
CONTROL VALVE, STAND ALONE NETWORKED
THERMOSTAT CONTROLLER, AND COIL DISCHARGE
AIR TEMPERATURE SENSOR. PROVIDE CONTROL
POWER TRANSFORMER ABOVE CEILING TO POWER
NETWORKED THERMOSTAT CONTROLLER, SEE
ELECTRICAL FOR POWER SUPPLY TO CONTROL
POWER TRANSFORMER. THERMOSTAT MUST INCLUDE
ALL PROGRAMMING AND HARDWARE NECESSARY FOR
STAND ALONE CONTROL OF THE REHEAT COIL
CONTROL VALVE. INSTALL NEW DISCHARGE AIR
SENSOR IN DUCTWORK DOWNSTREAM OF REHEAT
COIL AND CONNECT TO NETWORKED THERMOSTAT.
NETWORKED THERMOSTAT MUST BE PROVIDED WITH
HARDWARE CAPABLE OF FUTURE INTEGRATION INTO
A BACNET DDC SYSTEM.
SHAFT
STAIR #1
ROOF
ROOF
ROOF
ROOFROOF
SCALE:
WEST ANNEX FOURTH FLOOR MECHANICAL NEW WORK PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 4TH FLOOR
MECHANICAL NEW WORK PLAN
M-104
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
RHC-406
RHC-406A RHC-406B
RHC-405
RHC-404A
RHC-404 RHC-400
RHC-404B
1 1
U
D A
S
1. PROVIDE ELECTRONIC ACTUATED HEATING WATER
CONTROL VALVE, STAND ALONE NETWORKED
THERMOSTAT CONTROLLER, AND COIL DISCHARGE
AIR TEMPERATURE SENSOR. PROVIDE CONTROL
POWER TRANSFORMER ABOVE CEILING TO POWER
NETWORKED THERMOSTAT CONTROLLER, SEE
ELECTRICAL FOR POWER SUPPLY TO CONTROL
POWER TRANSFORMER. THERMOSTAT MUST INCLUDE
ALL PROGRAMMING AND HARDWARE NECESSARY FOR
STAND ALONE CONTROL OF THE REHEAT COIL
CONTROL VALVE. INSTALL NEW DISCHARGE AIR
SENSOR IN DUCTWORK DOWNSTREAM OF REHEAT
COIL AND CONNECT TO NETWORKED THERMOSTAT.
NETWORKED THERMOSTAT MUST BE PROVIDED WITH
HARDWARE CAPABLE OF FUTURE INTEGRATION INTO
A BACNET DDC SYSTEM.
ENLARGED WEST ANNEX BUILDING BASEMENT MECHANICAL NEW WORK PLAN
3/8" = 1'-0"
WEST ANNEX BUILDING ENLARGED
MECHANICAL NEW WORK PLAN
M-401
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
SCALE: 3/8"=1'-0"
0 1' 2' 4' 8'
1. PROVIDE NATURAL GAS FIRED HIGH-EFFICIENCY
CONDENSING BOILER, CONDENSATE NEUTRALIZER,
AND ALL OTHER APPURTENANCES. INSTALL PER
MANUFACTURER'S REQUIREMENTS. RECONNECT TO
EXISTING HTW PIPING AS SHOWN IN DETAIL 2/M-401.
INTEGRATE BOILER INTO EXISTING CONTROL SYSTEM.
ALL EXISTING POINTS AND CONTROL CAPABILITIES
MUST BE MAINTAINED.
2. PROVIDE BASE MOUNTED HEATING WATER PUMP,
HOUSEKEEPING PAD, AND ALL OTHER
APPURTENANCES. INSTALL PER MANUFACTURER'S
REQUIREMENTS. RECONNECT TO EXISTING HTWS
PIPING AS SHOWN IN DETAIL 3/M-401. INTEGRATE
PUMP INTO EXISTING CONTROL SYSTEM. ALL EXISTING
POINTS AND CONTROL CAPABILITIES MUST BE
MAINTAINED.
3. PROVIDE INLINE HEATING WATER PUMP. INSTALL PER
MANUFACTURER'S REQUIREMENTS. INTEGRATE PUMP
INTO EXISTING CONTROL SYSTEM. ALL EXISTING
POINTS AND CONTROL CAPABILITIES MUST BE
MAINTAINED.
4. CONNECT BOILER TO EXISTING BOILER FLUE.
5. CONNECT BOILER TO EXISTING COMBUSTION INTAKE.
6. CONNECT NEW 1-1/2" NG PIPING TO BOILER. PROVIDE
ISOLATION VALVE, PRESSURE REGULATOR, AND DRIP
LEG. SEE DETAIL 1/M-501.
7. PROVIDE ASME CSD-1 COMPLIANT BOILER
EMERGENCY SHUTDOWN SWITCH. SWITCH SHALL BE
CONNECTED TO B-9 AND B-10. INSTALL PUSH BUTTON
IN A PROTECTIVE POLYCARBONATE ENCLOSURE
(SIMILAR TO STI UNIVERSAL STOPPER).
HWP-7
HWP-5
HWP-8
B-9 B-10
BP-9 BP-10
3 3
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
U
D A
S
BOILER
EXIST. HOUSEKEEPING PAD
ASME PRESSURE
RELIEF VALVE.
PIPE FULL SIZE
TO FLOOR DRAIN
BOILER PRIMARY PUMP
PRESSURE GAUGE (TYP.)
STRAINER W/BLOWDOWN
THERMOMETER (TYP.)
BOILER DRAIN AND VALVE
4" HTWS & 4" HTWR PIPING
(TYP.)
EXIST. 4" HTWSEXIST. 4" HTWR
1-1/2" NGEXIST. BUTTERFLY
ISOLATION VALVE (TYP. 2)
SCALE:
B-9 & B-10 INSTALLATION DETAIL
NTS
T AND P PLUG (TYP.)
DRAIN VALVE WITH HOSE
CONNECTION (TYP.)
NOTES:
1. MAKE FINAL CONNECTIONS TO EQUIPMENT.
COORDINATE INSTALLATION, CONNECTIONS, AND
LOCATIONS WITH ACTUAL EQUIPMENT SUPPLIED AND WITH
MANUFACTURER'S REQUIREMENTS.
2. CONTRACTOR MUST FIELD VERIFY EXISTING PIPING SIZES
PRIOR TO ORDERING ANY PIPING, VALVES, OR FITTINGS.
HOUSEKEEPING PAD
PUMP AND MOTOR
TRIPLE DUTY VALVE
HTWP-5 (2")
HTWP-6 (3")
HTWP-7 (3")
HTWP-8(3")
RUBBER FLEX
CONNECTOR (TYP. 2).
SUCTION DIFFUSER
W/PULL OUT STRAINER
EXIST.GATE ISOLATION
VALVE (TYP. 2)
EXIST.HTWS
P-5 (2-1/2")
P-6 (4") P-7 (6") P-8 (6")
EXIST.HTWS
P-5 (2-1/2") P-6 (4") P-7 (6") P-8 (6")
SCALE:
HWP-5, HWP-6, HWP-7 AND HWP-8 DETAIL
NTS
4 4
6 7
PIPING SPOOL
P-5 (2") P-6 (4") P-7 (4") P-8 (4")
NOTES:
CONTRACTOR MUST FIELD VERIFY EXISTING PIPING
SIZES PRIOR TO ORDERING ANY PIPING, VALVES,
OR FITTINGS.
CONCENTRIC REDUCER
WHERE REQUIRED (TYP.)
DRAIN WITH BALL
VALVE
SUCTION DIFFUSER
SUPPORT
PUMP INERTIA BASE
CONCENTRIC REDUCER
PRESSURE GAUGE (TYP.)
THERMOMETER (TYP.)
PETES PLUG
PIPE SPOOL MATCH TRIPLE DUTY
VALVE INLET DIAMETER
1-1/2"
NG
1-1/2"
NG
NG REGULATOR (TYP. 2)
M-501
MECHANICAL DETAILS
U
D A
S
NG MAIN
SCALE:
BOILER NATURAL GAS CONNECTION DETAIL
NTS SCALE:
CONDENSATE ACID NEUTRALIZER DETAIL
NTS
ISOLATION
VALVE
ISOLATION
VALVE
DRIP
LEG (MINIMUM OF 3" IN LENGTH)
PRESSURE REGULATOR
PER MANUFACTURER'S
REQUIREMENTS.
REGULATOR MUST BE INSTALLED WITH
A MINIMUM OF 10 LINEAR FEED OF PIPE
BETWEEN THE REGULATOR OUTLET
AND BOILER FUEL TRAIN
PROVIDE 10 PIPE DIAMETERS EQUIVALENT TO
REGULATOR CONNECTION SIZE. THIS PIPE
MUST BE STRAIGHT, UNINTERRUPTED PIPE
BETWEEN REGULATOR OUTLET AND ANY
FITTINGS, VALVES, OR ELBOWS.
2" NG
2" NG
TO BOILER
CONNECTION
CONDENSING WATER
HEATER FLUE
UNION
FULL SIZE
BYPASS
PIPE TO APPROPRIATE DRAIN
IN SANITARY SYSTEM
CONDENSATE
TRAP
ACID NEUTRALIZER. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS
HTWS
SHUT-OFF VALVE (TYP.)
HTWR
BALANCING VALVE
3-WAY CONTROL VALVE
PNEUMATIC TUBING
PLUG VALVE,
TEST PLUG (TYP.)
DRAIN VALVE COIL
MANUAL AIR VENT
BALL VALE (TYP.)
AIR FLOWSTRAINER
SCALE:
3-WAY HEATING WATER COIL DETAIL - DEMOLITION
NTS
HTWS
SHUT-OFF VALVE (TYP.)
HTWR
BALANCING VALVE
3-WAY CONTROL VALVE
DIRECT ACTING SIGNAL
PLUG VALVE, ADJUST TO EQUAL
GPM THRU COIL AT DESIGN
FLOW
TEST PLUG (TYP.)
1/2" PLUGGED
DRAIN VALVE
COIL
MANUAL AIR VENT,
3/8"
BALL VALE (TYP.)
5AIR FLOW
KEYED NOTES
NC
NO
C
STRAINER
W/BLOWDOWN
SCALE:
3-WAY HEATING WATER COIL DETAIL - NEW WORK
NTS
NOTE:
SEE CONTROL VALVE SCHEDULE FOR PIPING
DIAMETER AND CONTROL VALVE SIZE.
INSTALL BALANCING VALVE WITH MINIMUM OF 3
STRAIGHT PIPE DIAMETERS UPSTREAM AND 1
STRAIGHT PIPE DIAMETER DOWNSTREAM.
MAINTAIN 6" MINIMUM CLEARANCE ABOVE TEST
PLUG TO ALLOW GAUGE TO BE INSERTED. DO
NOT COVER PLUG WITH INSULATION.
INSTALL SWING JOINTS AT COIL CONNECTIONS.
PROVIDE COILS WITH INLET STRAINERS AND
CAPPED HOSE CONNECTION BLOW DOWN
VALVES.
INSTALL MANUAL AIR VENTS IN SUPPLY AND
RETURN COIL BRANCH PIPING AS FOLLOWS:
A) IN PIPING HIGH POINT WHEN PIPING IS
ABOVE MAIN.
B) CLOSE TO COIL WHEN PIPING IS NOT
ABOVE MAIN (SIDE CONNECTION).
HOUSEKEEPING PADS MUST EXTEND A
MINIMUM OF 6" BEYOND ALL SIDES OF
SUPPORTED EQUIPMENT UNLESS
OTHERWISE INDICATED. PADS MUST BE
A MINIMUM OF 4" THICK
PROVIDE 3000 PSI CONCRETE
HOUSEKEEPING PADS FOR ALL
GROUND AND/OR FLOOR
MOUNTED EQUIPMENT
EDGE OF SUPPORTED
EQUIPMENT
CHAMFERED EDGED
ON ALL SIDES
FLOOR
ALL PADS INSTALLED ON CONCRETE FLOORS
ARE TO BE PROVIDED WITH #4 REBAR DOWEL
RODS PENETRATING A MINIMUM OF 2" INTO
BOTH THE PAD AND THE SUPPORTING FLOOR.
PROVIDE A MINIMUM OF FOUR (4) DOWEL RODS
PER PAD, WITH SPACING OF DOWEL RODS AT 18"
ON CENTER MAXIMUM BOTH WAYS.
#4 REINFORCEMENT MAX 4"
ON CENTER EACH WAY
SCALE:
HOUSEKEEPING PAD DETAIL
NTSSCALE:
CLEVIS HANGER DETAIL
NOT TO SCALE
HEAVY DUTY
CLEVIS HANGER:
MSS SP-69 AND
MSS SP-58
PIPE
RIGID INSULATION INSERT
(12" LONG, 180^ ARC)
CLEVIS HANGER
WITH INSULATION
SHIELD
INSULATION
BOLT & NUT
SUPPORT NUT
LOCKING NUT
HANGER ROD TO
STRUCTURE
M-601
MECHANICAL SCHEDULES
BASIS OF
DESIGN
IMPELLER SIZE
(IN)
FLOW
(GPM)
HEAD
(FT)
FLUID
TYPE
MIN. MOTOR
HP
MOTOR RPM VOLTS/ PHASE REMARKS
PUMP SCHEDULE
NOTES:
1. PROVIDE BASE MOUNTED PUMPS WITH SUCTION DIFFUSERS AND FLANGED RUBBER PUMP CONNECTIONS.
2. ALL MOTORS TO BE NON-OVERLOADING AT ANY POINT ON THE PUMP CURVE.
3. PROVIDE WITH VIBRATION ISOLATION/INERTIA PADS.
4. CONTRACTOR MUST VERIFY BP-9 AND BP-10 REQUIREMENTS WITH BOILER MANUFACTURER. PUMPS MUST BE PROVIDED BY THE BOILER MANUFACTURER AS PART OF THE BOILER PACKAGE.
5. TRIPLE DUTY VALVES PROVIDED ON BASE MOUNTED PUMP DISCHARGE MUST BE SELECTED TO HAVE A MAXIMUM PRESSURE DROP OF 5 FT. HD. AT THE SCHEDULED OPERATING CONDITIONS.
MARK TYPE SERVES
FLUID DATA ELECTRICAL DATA MIN.
DUTY POINT
EFFICIENCY
BASIS OF
DESIGN
INPUT
(MBH)
OUTPUT
(MBH)
TURN DOWN
RATIO
LOCHINVAR
CREST
HIGH EFFICIENCY
CONDENSING
HEATING
WATER
BOILER SCHEDULE
MARK TYPE SERVICE
HEATING DATA
1500 1380B-9
NATURAL
GAS
FUEL
TYPE
25:1
NOTES:
VOLTS/PH
ELECTRICAL DATA
120/1 SEE NOTES
GPM FLUID
TYPE
350 WATER
FLUE
OUTLET
MCA
(A)
6" 13
REMARKS
OPER.
WEIGHT
(LBS)
2307160° 200°F
EWT
(F)
LWT
(F)
WPD
FT. HD.
5.0
COMB.
INTAKE
8"
1. PROVIDE BOILER WITH CONDENSATE NEUTRALIZER KIT. ROUTE CONDENSATE TO FLOOR DRAIN.
2. PROVIDE WITH LCD DISPLAY SCREEN.
3. PROVE WITH 160 PSI MAXIMUM WORKING PRESSURE.
4. PROVIDE WITH FLUE DAMPER KIT.
5. BOILER MUST BE INTEGRATED INTO THE EXISTING CONTROL SYSTEM. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL HARDWARE, GATEWAYS, SOFTWARE, AND PROGRAMMING NECESSARY TO MAINTAIN
ALL EXISTING CONTROL FUNCTIONS AND INTERLOCKS.
6. PROVIDE WITH COMBUSTION AIR INTAKE FILTER.
7. PROVIDE REGULATOR AND BOILER NATURAL GAS ISOLATION VALVE. INSTALL PER MANUFACTURER'S INSTALLATION MANUAL AND ALL APPLICABLE CODES AND STANDARDS.
8. PROVIDE ASME CSD-1 COMPLIANT BOILER EMERGENCY SHUTDOWN SWITCH.
SEE NOTESHWP-5
BASE MOUNTED
END SUCTION
BASE MOUNTED
END SUCTIONHWP-6
7.0
SEE NOTES
B-9, B-10
B-10
SEE NOTESHWP-7
BASE MOUNTED
END SUCTION
BASE MOUNTED
END SUCTIONHWP-8 SEE NOTES
SEE NOTESBP-9
BELL &
GOSSETT
INLINE BOILER
PUMP
INLINE BOILER
PUMPBP-10
BELL &
GOSSETT
5.625
5.625
1.5
1.5
208/3
208/3
71.8%
71.8% SEE NOTES
B-9, B-10
B-9, B-10
B-9, B-10
B-9
B-10
CONTROL VALVE SCHEDULE
SERVES
CH-16
CH-17
CH-18
CH-19
CH-20
CH-21
CH-32
CH-33
CH-34
CH-35
CH-36
CH-37
CH-38
HC-6
HC-11
HC-12
CH-15
CH-13
CH-10
CH-9
CH-8
CH-7
CH-6
CH-5
CH-4
CH-3
CH-2
CH-1
ROOM
101, 103, 133
110, 111, 112, 113
114A
114A
118, 119, 120
114A, 114B
114B
114B
114B
114B-5
216, 217
222-E
207, 208
228-W
228-N
114A
VALVE
CONFIGURATION
FLOW
(GPM)
FLOW
COEFFICIENT
(CV)
3-WAY 2.14
2.78
1.10
2.03
0.49
1.13
3.89
2.73
0.17
0.49
1.12
0.98
1.45
1.88
0.50
1.10
3.51
0.68
5.01
1.60
0.98
2.76
1.45
0.58
0.58
1.17
1.09
2.86
CONTROL VALVE SCHEDULE (CONT.)
MARK
HC-24
HC-28
RHC-305
RHC-306
RHC-307
RHC-308
RHC-309
RHC-400
RHC-404
RHC-404A
RHC-404B
RHC-405
RHC-406
RHC-406A
RHC-406B
ROOM
3F
CORRIDOR
306A, 306B
404A
404B
406A
406B
VALVE
CONFIGURATION
FLOW
(GPM)
0.5
0.5
3F
CORRIDOR
1.1
1.1
1.7
0.7
0.8
0.5
0.8
1.6
1.0
0.5
0.5
3-WAY
RHC-1 103 1.0
WATER
WATER
U
D A
S
LOCHINVAR
CREST
HIGH EFFICIENCY
CONDENSING
HEATING
WATER 1500 1380NATURAL
GAS 25:1 120/1 SEE NOTESWATER 6" 13 2307160° 200°F 8"
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
FLOW
COEFFICIENT
(CV)
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
3-WAY
350 5.0
7.0
7.75
7.75
32 1-1/2 1750 60%
105 2 1750 78.7%
206 5 1750
206 5 1750WATER
WATER
WATER
WATER50
1. REBALANCE ALL REHEAT COILS TO THE GPM INDICATED.
2. CLEAN ALL STRAINERS.
NOTES:
1. REBALANCE ALL REHEAT COILS TO THE GPM INDICATED.
2. CLEAN ALL STRAINERS.
3. FOR REHEAT COILS WITH VALUES INDICATED AS "-" CONTRACTOR MUST MEASURE FLOW
WITH EXISTING VALVE IN THE FULL OPEN POSITION AND UTILIZE THE MEASURED FLOW (GPM)
FOR REBALANCING THE SYSTEM. CONTRACTOR MUST SELECT VALVE SIZE AND FLOW
COEFFICIENT BASED ON THE MEASURED GPM AND SUBMIT FOR APPROVAL IN ACCORDANCE
WITH THE SPECIFICATIONS.
NOTES:
VALVE
SIZE
(IN)
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
VALVE
SIZE
(IN)
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1.2
0.8
0.3
0.8
0.3
0.3
0.8
0.46
0.8
0.3
0.8
0.3
0.8
0.46
0.8
0.3
0.3
0.8
0.46
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
4.7
0.3
0.3
0.8
0.8
0.8
0.46
0.46
0.3
0.46
0.8
0.46
0.3
0.3
0.46
PIPE
DIAM.
(IN)
3/4"
3/4"
1/2"
1/2"
1/2"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
PIPE
DIAM.
(IN)
3/4"
3/4"
1/2"
3/4"
1/2"
1/2"
1"
3/4"
1/2"
1/2"
1/2"
3/4"
3/4"
3/4"
1/2"
1/2"
1"
1/2"
1"
3/4"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
3/4"
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
208/3
208/3
208/3
208/3
73.3%
73.3%
RHC-313 313 -3-WAY - -1"
RHC-312B 312B -3-WAY - -3/4"
RHC-312A 312A -3-WAY - -3/4"
RHC-310 310 -3-WAY - -3/4"
M-701
MECHANICAL CONTROLS
U
D A
S
ALARMING
FUNCTION POINT NAME DESCRIPTION SETTING
(WITH UNITS)
RANGE
(WITH UNITS)
IO
TYPE
ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
ZONE TEMPERATURE
CONTROL
ZN-T ZONE TEMPERATURE 40 - 85°F ZONE TEMPERATURE BELOW 60°F OR
ABOVE 80°F INFO
ZN-T-SP ZONE TEMPERATURE SETPOINT OCCUPANCY
ADJUSTABLE 68 - 78°F
ZN-T-SP-UNOCC ZONE TEMPERATURE SETPOINT FOR UNOCCUPIED MODE 55 - 80°F BO
HTG-V-C VAV REHEAT VALVE COMMAND 0-100% OPEN
NOTES:
1. THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THIS DRAWING.
2. "TBD" = TO BE DETERMINED DURING COMMISSIONING.
NETWORKEDHTG-V-C
DA-T
RETURN ZN-T
TO
H ZONE
SUPPLY
SCALE:
NETWORKED THERMOSTAT W/REHEAT CONTROLS
NTS
SEQUENCE OF OPERATION
NETWORKED THERMOSTAT W/REHEAT CONTROLS
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
· OCCUPIED MODE: THE UNIT SHALL MAINTAIN
· A 75°F (ADJ.) COOLING SETPOINT
· A 70°F (ADJ.) HEATING SETPOINT.
· UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
· A 85°F (ADJ.) COOLING SETPOINT.
· A 60°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
· LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE ZONE SENSOR.
ZONE UNOCCUPIED OVERRIDE:
A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO
THE SCHEDULE.
SPACE OCCUPIED MODE:
· SPACE THERMOSTAT SHALL MODULATE THE REHEAT COIL TO MAINTAIN SPACE TEMPERATURE SETPOINT.
· UPON CALL FOR HEAT THE REHEAT CONTROL VALVE SHALL OPEN AND MODULATE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE
SET POINT.
· UPON CALL FOR COOLING, THE REHEAT VALVE SHALL MODULATE CLOSED.
· ONCE SPACE SET POINT IS REACHED THE REHEAT VALVE SHALL MODULATE TO PROVIDE NEUTRAL SUPPLY AIR TO THE SPACE.
HEATING WATER REHEATING:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE 3-WAY HEATING WATER VALVES TO MAINTAIN THE SPACE
SETPOINT.
THE REHEATING SHALL BE ENABLED WHENEVER:
· THE SPACE THERMOSTAT IS IN THE HEATING MODE.
· THE THERMOSTAT IS IN THE COOLING MODE AND SPACE SETPOINT TEMPERATURE IS MET.
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE. DISCHARGE AIR TEMPERATURE SENSOR SHALL BE UTILIZED IN MODULATING THE REHEAT COIL TO PROVIDE NEUTRAL AIR TO THE SPACE ONCE SPACE TEMPERATURE IS MET.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
· LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).
PROVIDE ZONE NETWORKED
THERMOSTAT(S)
AS INDICATED ON THE PLANS
THERMOSTAT
ZN-T-SP
ZN-T-SP-UNOCC
GENERAL CONTROLS NOTES:
1. ALL CONTROL WIRING SHALL BE INSTALLED IN CONDUIT IN ACCORDANCE WITH DIVISION 26 SPECIFICATIONS.
2. NETWORKED THERMOSTAT MUST BE CAPABLE OF STAND ALONE OPERATION OF ALL INPUT AND OUTPUT FUNCTIONS LISTED IN THE SEQUENCE OF OPERATIONS AND SHOWN ON THE CONTROLS DIAGRAM/POINTS LIST. THERMOSTAT MUST ALSO BE PROVIDED WITH THE
CAPABILITY OF INTEGRATION INTO A BACNET DDC SYSTEM.
3. CONTRACTOR MUST PROVIDE ALL SOFTWARE, HARDWARE, GATEWAYS, AND APPURTENANCES NECESSARY FOR A COMPLETE AND
OPERATIONAL SYSTEM.
AO
AI
AI
PANEL 1E
FURR DN.
COMM.
SCALE:
WEST ANNEX FIRST FLOOR ELECTRICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 1ST FLOOR
ELECTRICAL DEMOLITION PLAN
ED101
GENERAL NOTES
GRAPHIC SCALE
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
U
D A
S
THE CONTROLS CONTRACTOR IS RESPONSIBLE FOR
DEMOLITION OF THERMOSTATS AND RELATED CIRCUITRY.
RECEPTION
ELEV.
CORRIDOR
CORRIDOR
CORRIDOR
STAIR #1
SCALE:
WEST ANNEX SECOND FLOOR ELECTRICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 2ND FLOOR
ELECTRICAL DEMOLITION PLAN
ED102
GENERAL NOTES
GRAPHIC SCALE
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
U
D A
S
CORRIDOR
ELEV.
CORRIDOR
SHOWER
CORRIDOR
STORAGE
STAIR #1
SCALE:
WEST ANNEX THIRD FLOOR ELECTRICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 3RD FLOOR
ELECTRICAL DEMOLITION PLAN
ED103
GENERAL NOTES
GRAPHIC SCALE
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
U
D A
S
SHAFT
STAIR #1
ROOF
ROOF
ROOF
ROOFROOF
SCALE:
WEST ANNEX FOURTH FLOOR ELECTRICAL DEMOLITION PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 4TH FLOOR
ELECTRICAL DEMOLITION PLAN
ED104
GENERAL NOTES
GRAPHIC SCALE
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
U
D A
S
MAIN BUILDING BASEMENT ELECTRICAL DEMOLITION PLAN
3/8" = 1'-0"
WEST ANNEX BUILDING ENLARGED
ELECTRICAL DEMOLITION PLAN
ED401
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE BASED ON THE BEST INFORMATION AT THE TIME
OF DESIGN AND MUST BE FIELD VERIFIED. EQUIPMENT
AND CIRCUITRY NOT EXPRESSLY LISTED FOR
DEMOLITION SHALL BE EXISTING-TO-REMAIN.
SCALE: 3/8"=1'-0"
0 1' 2' 4' 8'
1. DISCONNECT AND DEMOLISH ELECTRICAL
CONNECTION TO EXISTING BOILER (B-9). BOILER IS
FED FROM PANEL 1E-27. RETAIN AND REUSE EXISTING
RACEWAYS AND CIRCUITRY TO EXTENT PRACTICAL.
2. DISCONNECT AND RETAIN ELECTRICAL CONNECTION
TO EXISTING BOILER (B-10). BOILER IS FED FROM
PANEL 1E-29. RETAIN AND REUSE EXISTING
RACEWAYS AND CIRCUITRY TO EXTENT PRACTICAL.
3. DISCONNECT CIRCUITRY TO EXISTING BP-9. EXISTING
DISCONNECT AND EXISTING MOTOR STARTER TO
REMAIN ARE FED FROM PANEL 1E AT CIRCUITS 2,4,6.
RETAIN AND REUSE RACEWAYS AND CIRCUITRY TO
EXTENT PRACTICAL.
4. DISCONNECT CIRCUITRY TO EXISTING BP-10.
EXISTING DISCONNECT AND EXISTING MOTOR
STARTER TO REMAIN ARE FED FROM PANEL 1E AT
CIRCUITS 2,4,6. RETAIN AND REUSE RACEWAYS AND
CIRCUITRY TO EXTENT PRACTICAL.
5. DISCONNECT CIRCUITRY TO EXISTING HWP-5. HWP-5
IS FED FROM BUCKET 1C IN MCCC. RETAIN AND
REUSE FLEXIBLE CONNECTION.
6. DISCONNECT CIRCUITRY TO EXISTING HWP-6. HWP-6
IS FED FROM BUCKET 1D IN MCCC. RETAIN AND
REUSE FLEXIBLE CONNECTION.
7. DISCONNECT CIRCUITRY TO EXISTING HWP-7. HWP-7
IS FED FROM BUCKET 1E IN MCCC. RETAIN AND
REUSE FLEXIBLE CONNECTION.
8. DISCONNECT CIRCUITRY TO EXISTING HWP-8. HWP-8
IS FED FROM BUCKET 1F IN MCCC. RETAIN AND
REUSE FLEXIBLE CONNECTION.
HWP-7
HWP-5
HWP-8
3 4
U
D A
S
MOTOR CONTROL CENTER C (MCCC)
E-000
ELECTRICAL LEGEND
ELECTRICAL LEGEND
1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" SHALL BE GROUND FAULT CIRCUIT INTERRUPTING
DEVICES.
3. DEVICES NOTED AS "WP" SHALL BE WEATHERPROOF WHILE-IN-USE.
4. DEVICES NOTED AS "DL" SHALL BE RATED FOR DAMP LOCATION.
5. DEVICES NOTED AS "NL" SHALL BE NIGHT LIGHTS. PROVIDE UNSWITCHED
POWER TO FIXTURE.
6. DEVICES NOTED AS "WG" SHALL BE PROVIDED AND INSTALLED WITH A WIRE
GUARD.
7. DEVICES NOTED AS "TR" SHALL BE TAMPER RESISTANT.
8. PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY PACKS.
9. "W/E" INDICATES DEVICE/DISCONNECT PROVIDED WITH THE EQUIPMENT BY
OTHERS.
LA-1
FUSED DISCONNECT SWITCH. TEXT INDICATES AMPACITY/NUMBER OF
POLES/ENCLOSURE TYPE; F-(RATING OF FUSES).
NON-FUSED DISCONNECT SWITCH. TEXT INDICATES AMPACITY/NUMBER
OF POLES/ENCLOSURE TYPE.
PANELBOARD.
FLEXIBLE CONNECTION TO EQUIPMENT.
MAGNETIC MOTOR STARTER.
COMBINATION FUSED DISCONNECT AND MAGNETIC MOTOR
STARTER.
COMBINATION CIRCUIT BREAKER AND MAGNETIC MOTOR STARTER.
GEAR
CONDUIT AND WIRINGGENERAL NOTES
MISCELLANEOUS
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING.
TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE
PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND
THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS
SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT
GROUNDING CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE,
THE MARKINGS TO THE LEFT SIGNIFY THAT THREE CONDUCTORS
PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE
PROVIDED.
CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR FLOOR.
TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE
PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND
THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS
SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT
GROUNDING CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS
TO THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN
EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED.
THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF THE
CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT. THE
ABSENCE OF TEXT SIGNIFIES THAT THE CONDUCTORS SHOULD BE
#12 AWG.
HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH CIRCUIT
NUMBER. DEVICES HAVING CIRCUIT NUMBERS LOCATED BESIDE
THEM MAY NOT SHOW THE CIRCUIT NUMBERS AT THE HOMERUN
ARROWS.
ENCLOSED CIRCUIT BREAKER.
U
D A
S
VOLTAGE DROP CHART FOR 20A, 1Ø CIRCUITS
Voltage Circuit Length Conductor Size (AWG)
120 < 50' #12
120 > 50' #10
120 > 90' #8
120 > 140' #6
277 < 130' #12
277 > 130' #10
277 > 200' #8
277 > 330' #6
VOLTAGE DROP CHART NOTES:
1) CIRCUIT SIZES INDICATED ON THE DRAWINGS ARE MINIMUM
REQUIREMENTS. REFER TO THIS CHART FOR UPSIZING CONDUCTORS AS
NEEDED.
2) DO NOT CONNECT CONDUCTORS LARGER THAN #10 DIRECTLY TO A
RECEPTACLE OR A SWITCH. PROVIDE A JUNCTION BOX TO DOWNSIZE THE
CONDUCTOR TO #12 AT THE DEVICE.
3) FOR CIRCUITS LONGER THAN THOSE LISTED ABOVE, CONSULT WITH THE
ENGINEER FOR CONDUCTOR SIZES.
PANEL 1E
FURR DN.
COMM.
SCALE:
WEST ANNEX FIRST FLOOR ELECTRICAL NEW WORK PLAN
3/32" = 1'-0"
C.E.
MECH
ROOM
WEST ANNEX BUILDING 1ST FLOOR
ELECTRICAL NEW WORK PLAN
E-101
GENERAL NOTES
GRAPHIC SCALE
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. EQUIPMENT SHOWN ON THIS DRAWING IS
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY ALL
EXISTING CONDITIONS.
U
D A
S
KEYED NOTESX
1. PROVIDE 120V CONNECTION FOR NEW CONTROL
POWER TRANSFORMER (MOUNTED ABOVE THE
CEILING) FROM NEAREST 20A, 120V CIRCUIT WITH
AVAILABLE CAPACITY. ALLOW UP TO 30' OF 2#12,
#12(G), 3/4"C. PER ACTUATOR. NOTIFY CONTRACTING
OFFICER'S REPRESENTATIVE IF TOTAL DISTANCE OF
ALL TAKEN TOGETHER EXCEEDS THIS ALLOWANCE.
CH-51
HC-6 1
CH-4 1
CH-3 1
CH-2 1
CH-91
CH-61
CH-101 CH-8 1
CH-71
HC-11 1
HC-12 1
RHC-1 1CH-11
RECEPTION
ELEV.
CORRIDOR
CORRIDOR
CORRIDOR
STAIR #1
SCALE:
WEST ANNEX SECOND FLOOR ELECTRICAL NEW WORK PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 2ND FLOOR
ELECTRICAL NEW WORK PLAN
E-102
GENERAL NOTES
GRAPHIC SCALE
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. EQUIPMENT SHOWN ON THIS DRAWING IS
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY ALL
EXISTING CONDITIONS.
U
D A
S
KEYED NOTESX
1. PROVIDE 120V CONNECTION FOR NEW CONTROL
POWER TRANSFORMER (MOUNTED ABOVE THE
CEILING) FROM NEAREST 20A, 120V CIRCUIT WITH
AVAILABLE CAPACITY. ALLOW UP TO 30' OF 2#12,
#12(G), 3/4"C. PER ACTUATOR. NOTIFY CONTRACTING
OFFICER'S REPRESENTATIVE IF TOTAL DISTANCE OF
ALL TAKEN TOGETHER EXCEEDS THIS ALLOWANCE.
CH-13 CH-16
CH-17
CH-15
CH-18
CH-36
CH-37
CH-32
CH-35
CH-38
CH-34
CH-33
CH-20
CH-21
CH-19
CORRIDOR
ELEV.
CORRIDOR
SHOWER
CORRIDOR
STORAGE
STAIR #1
SCALE:
WEST ANNEX THIRD FLOOR ELECTRICAL NEW WORK PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 3RD FLOOR
ELECTRICAL NEW WORK PLAN
E-103
GENERAL NOTES
GRAPHIC SCALE
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. EQUIPMENT SHOWN ON THIS DRAWING IS
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY ALL
EXISTING CONDITIONS.
U
D A
S
KEYED NOTESX
1. PROVIDE 120V CONNECTION FOR NEW CONTROL
POWER TRANSFORMER (MOUNTED ABOVE THE
CEILING) FROM NEAREST 20A, 120V CIRCUIT WITH
AVAILABLE CAPACITY. ALLOW UP TO 30' OF 2#12,
#12(G), 3/4"C. PER ACTUATOR. NOTIFY CONTRACTING
OFFICER'S REPRESENTATIVE IF TOTAL DISTANCE OF
ALL TAKEN TOGETHER EXCEEDS THIS ALLOWANCE.
RHC-313
RHC-312B
RHC-312A
RHC-309
HC-24
RHC-310
RHC-308
RHC-307
RHC-306
RHC-305
HC-28
SHAFT
STAIR #1
ROOF
ROOF
ROOF
ROOFROOF
SCALE:
WEST ANNEX FOURTH FLOOR ELECTRICAL NEW WORK PLAN
3/32" = 1'-0"
WEST ANNEX BUILDING 4TH FLOOR
ELECTRICAL NEW WORK PLAN
E-104
GENERAL NOTES
GRAPHIC SCALE
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
U
D A
S
KEYED NOTESX
1. PROVIDE 120V CONNECTION FOR NEW CONTROL
POWER TRANSFORMER (MOUNTED ABOVE THE
CEILING) FROM NEAREST 20A, 120V CIRCUIT WITH
AVAILABLE CAPACITY. ALLOW UP TO 30' OF 2#12,
#12(G), 3/4"C. PER ACTUATOR. NOTIFY CONTRACTING
OFFICER'S REPRESENTATIVE IF TOTAL DISTANCE OF
ALL TAKEN TOGETHER EXCEEDS THIS ALLOWANCE.
RHC-406
RHC-406A RHC-406B
RHC-405
RHC-404A
RHC-404 RHC-400
RHC-404B
1 1
ENLARGED WEST ANNEX BUILDING BASEMENT ELECTRICAL NEW WORK PLAN
3/8" = 1'-0"
WEST ANNEX BUILDING ENLARGED
ELECTRICAL NEW WORK PLAN
E-401
GENERAL NOTES
GRAPHIC SCALE
SCALE: 3/8"=1'-0"
0 1' 2' 4' 8'
HWP-7
HWP-5
HWP-8
B-9 B-10
BP-9
BP-10
1. THE NEW WORK PLAN AND EXISTING CONDITIONS ARE
BASED ON THE BEST INFORMATION AT THE TIME OF
DESIGN AND MUST BE FIELD VERIFIED.
U
D A
S
KEYED NOTESX
1. RECONNECT EXISTING ELECTRICAL CONNECTION TO
BOILER (B-9). BOILER IS FED FROM PANEL 1E-23A.
EXTEND CIRCUITRY AS REQUIRED USING 2#12, #12(G),
3/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT
2. RECONNECT EXISTING ELECTRICAL CONNECTION TO
BOILER (B-10). BOILER IS FED FROM PANEL 1E-23B.
EXTEND CIRCUITRY AS REQUIRED USING 2#12, #12(G),
3/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
3. RECONNECT EXISTING ELECTRICAL CONNECTION TO
BP-9. EXISTING DISCONNECT AND EXISTING MOTOR
STARTER ARE FED FROM PANEL 1E AT CIRCUITS 2,4,6.
EXTEND CIRCUITRY AS REQUIRED USING 3#10, #10(G),
3/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
4. RECONNECT EXISTING ELECTRICAL CONNECTION TO
EXISTING BP-10. EXISTING DISCONNECT AND
EXISTING MOTOR STARTER ARE FED FROM PANEL 1E
AT CIRCUITS 2,4,6.EXTEND CIRCUITRY AS REQUIRED
USING 3#10, #10(G), 3/4"C. FINAL CONNECTION SHALL
BE FLEXIBLE METALLIC CONDUIT.
5. RECONNECT EXISTING ELECTRICAL CONNECTION TO
HWP-5. HWP-5 IS FED FROM BUCKET 1C IN MCCC.
EXTEND CIRCUITRY AS REQUIRED USING 3#12, #12(G),
3/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
6. RECONNECT EXISTING ELECTRICAL CONNECTION TO
HWP-6. HWP-6 IS FED FROM BUCKET 1D IN
MCCC.EXTEND CIRCUITRY AS REQUIRED USING 3#12,
#12(G), 3/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
7. RECONNECT EXISTING ELECTRICAL CONNECTION TO
HWP-7. HWP-7 IS FED FROM BUCKET 1E IN MCCC.
EXTEND CIRCUITRY AS REQUIRED USING 3#12, #12(G),
3/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
8. RECONNECT EXISTING ELECTRICAL CONNECTION TO
HWP-8. HWP-8 IS FED FROM BUCKET 1F IN MCCC.
EXTEND CIRCUITRY AS REQUIRED USING 3#12, #12(G),
3/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
EXISTING MOTOR CONTROL CENTER C (MCCC)
| Contract #3 General Binder |
| Sheets and Views |
| T-100-T100 |
| T-101-T101 |
| Contract #3 Mechanical Binder |
| Sheets and Views |
| M-001-M-001 |
| MD101-MD101 |
| MD102-MD102 |
| MD103-MD103 |
| MD104-MD104 |
| MD401-MD101 |
| M-101-M-101 |
| M-102-M-102 |
| M-103-M-103 |
| M-104-M-104 |
| M-401-M-401 |
| M-501-M-601 |
| M-601-M-601 |
| M-701-M-701 |
| 2026-2-19 Contract 3 Sealed Electrical Drawings |
| Sheets and Views |
| ED101 |
| ED102 |
| ED103 |
| ED104 |
| ED401 |
| E-000 |
| E-101 |
| E-102 |
| E-103 |
| E-104 |
| E-401 |