C04_Attachment 2 Boiler 1 - Drawings Binder.pdf
PDF 10 MB Posted
- Attached to
- WRRC Boiler Upgrades Federal contract opportunity
- Solicitation number
- 1232SA26R0033
About this file
This document is a design package for boiler upgrades at the Western Regional Research Center (WRRC) Agricultural Research Service facility in Albany, California. The project involves the replacement of six boilers and associated heating water pumps across three locations: the main building basement, main building attic, and service building. The work is organized into three sequential work sequences with mandatory 14-day advance notice required to the Contracting Officer's Representative before any outage commences.
Work Sequence #1 addresses replacement of boilers B-7 and B-8 with associated pumps HWP-1-1 and HWP-1-2 in the basement, with boilers replaced one at a time to maintain system operability. Work Sequence #2 covers boiler B-6 and pumps HWP-6-1 and HWP-6-2 in the attic, also requiring sequential replacement. Work Sequence #3 involves demolition and installation of boilers B-11, B-12, and B-13 with pumps HWP-5 and HWP-6 in the service building. All new equipment includes natural gas-fired high-efficiency condensing boilers manufactured by Lochinvar Crest with 1,500 MBH input capacity, condensate neutralizers, ASME pressure relief valves, and integration into existing control systems. The design specifications require compliance with the Buy American Act, field verification of existing conditions, worker protection for lead-based paint disturbance per OSHA standards, and submission of environmental work designs for approval prior to execution. Electrical connections utilize liquid-tight flexible metal conduit with flexible connections not exceeding three feet in length, and all existing control points and capabilities must be maintained post-installation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_1232SA26R0033_Amd_0002.pdf | ||
| RFI-AE Responses.docx | DOCX document | |
| 33PLMs-1-20-26-4384058_R1257169.pdf | ||
| 8LEADs-1-20-26-4384048_R1257169.pdf | ||
| Sol_1232SA26R0033_Amd_0001.pdf | ||
| C04_Sol_1232SA26R0033.pdf | ||
| C04_Attachment 3 Boiler 2 - Specifications.pdf | ||
| C04_Attachment 5 Boiler 3 - Specifications.pdf | ||
| C04_Attachment 8 Schedule of Pricing.xlsx | XLSX spreadsheet | |
| C04_ Attachment 1 Boiler 1 - Specifications.pdf | ||
| C04_Attachment 6 Boiler 3 - Drawing Binder.pdf | ||
| C04_Attachment 7 Wage Determination CA20260018.pdf | ||
| C04_Attachment 4 Boiler 2 - Drawings Binder.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WESTERN REGIONAL RESEARCH CENTER (WRRC)
AGRICULTURAL RESEARCH SERVICE
U.S. DEPARTMENT OF AGRICULTURE
ALBANY, CALIFORNIA
USDA
BOILER UPGRADES DESIGN (CONTRACT 1)
U
D A
S
Dustin Caruso
WRRC C1 & C3
DRAWING NO.
INDEX OF DRAWINGS
SHEET NO. TITLE
LEGEND AND SYMBOLS
SHEET SHOWN ON
PLAN, DETAIL OR SECTION NUMBER
PLAN, DETAIL OR SECTION TITLE
PLAN, DETAIL OR SECTION NUMBER
SHEET SHOWN ON
PLAN, DETAIL OR SECTION SCALE
ROOM MARK
ROOM NUMBER
DETAIL MARK
DRAWING TITLE
GENERAL
T-100
T-101
TITLE SHEET
DRAWING INDEX, NOTES, AND LEGEND
M-001
MD101
MD102
MD103
MD401
M-101
M-102
M-103
M-401
M-501
M-601
GENERAL NOTES, LEGEND, AND ABBREVIATIONS
MAIN BUILDING BASEMENT OVERALL MECHANICAL DEMOLITION PLAN
MAIN BUILDING ATTIC OVERALL MECHANICAL DEMOLITION PLAN
SERVICE BUILDING MECHANICAL DEMOLITION PLAN
ENLARGED MECHANICAL DEMOLITION PLANS
MAIN BUILDING BASEMENT OVERALL MECHANICAL NEW WORK PLAN
MAIN BUILDING ATTIC OVERALL MECHANICAL NEW WORK PLAN
SERVICE BUILDING MECHANICAL NEW WORK PLAN
ENLARGED MECHANICAL NEW WORK PLANS
MECHANICAL DETAILS
MECHANICAL SCHEDULES
MECHANICAL
ELECTRICAL
ED101
ED102
ED103
ED401
E-000
E-101
E-102
E-103
E-401
MAIN BUILDING BASEMENT OVERALL ELECTRICAL DEMOLITION PLAN
MAIN BUILDING ATTIC OVERALL ELECTRICAL DEMOLITION PLAN
SERVICE BUILDING ELECTRICAL DEMOLITION PLAN
ENLARGED ELECTRICAL DEMOLITION PLANS
ELECTRICAL LEGEND
MAIN BUILDING BASEMENT OVERALL ELECTRICAL NEW WORK PLAN
MAIN BUILDING ATTIC OVERALL ELECTRICAL NEW WORK PLAN
SERVICE BUILDING ELECTRICAL PLAN
ENLARGED ELECTRICAL PLANS
U
D A
S
DRAWING INDEX, NOTES, AND
LEGEND
T-101
WORK SEQUENCING NOTES
GENERAL WORK SEQUENCING NOTES:
THE CONTRACTOR MUST PROVIDE THE GOVERNMENT 14-DAYS NOTICE PRIOR TO ANY OUTAGE. A DETAILED WORK
SEQUENCING PLAN MUST BE SUBMITTED TO THE CONTRACTING OFFICER'S REPRESENTATIVE FOR REVIEW AND APPROVAL
PRIOR TO THE COMMENCEMENT OF ANY DEMOLITION OR NEW WORK.
WORK SEQUENCE #1:
DEMOLISH EXISTING B-7, B-8, AND ASSOCIATED PUMPS LOCATED IN THE BASEMENT. PROVIDE NEW B-7, B-8, AND ASSOCIATED
PUMPS. CONNECT NEW BOILERS AND PUMPS TO EXISTING CONTROL SYSTEM. B-7 AND B-8 BOILER PLANT MUST BE FULLY
OPERATIONAL, BALANCED, AND ASSOCIATED WORK COMPLETED PRIOR TO MOVING ON TO WORK SEQUENCE #2.
DURING THE BOILER REPLACEMENT UNDER THIS WORK SEQUENCE, ONLY ONE BOILER MUST BE TAKEN OFFLINE AND
REPLACED AT A TIME. BEFORE MOVING ONTO THE NEXT BOILER IN THIS SEQUENCE, THE PREVIOUS BOILER MUST BE FULLY
OPERATIONAL.
CONTRACTOR MUST CONDUCT THE BOILER REPLACEMENT WORK UNDER THIS SEQUENCE FIRST. EXISTING HWP-1-1 AND
HWP-1-2 MUST REMAIN FULLY OPERATIONAL UNTIL THE BOILER REPLACEMENT IS COMPLETED. WORK IS BEING SEQUENCED IN
THIS MANNER TO MINIMIZE DOWNTIME OF THE HEATING WATER SYSTEM DUE TO THE REROUTING OF THE EXISTING HEATING
WATER PIPING.
WORK SEQUENCE #2:
DEMOLISH EXISTING B-6 AND ASSOCIATED PUMPS LOCATED IN THE ATTIC. PROVIDE NEW B-6 AND ASSOCIATED PUMPS.
CONNECT NEW BOILER AND PUMPS TO EXISTING CONTROL SYSTEM. B-6 BOILER PLANT MUST BE FULLY OPERATIONAL, BALANCED, AND ASSOCIATED WORK COMPLETED PRIOR TO MOVING ON TO WORK SEQUENCE #3.
DURING THE REPLACEMENT OF HWP-6-1 AND HWP-6-2 UNDER THIS WORK SEQUENCE, ONLY ONE PUMP MUST BE TAKEN
OFFLINE AND REPLACED AT A TIME. BEFORE MOVING ONTO THE NEXT PUMP IN THIS SEQUENCE, THE PREVIOUS PUMP MUST BE
FULLY OPERATIONAL.
WORK SEQUENCE #3:
DEMOLISH EXISTING B-11, B-12, B-13, AND ASSOCIATED PUMPS LOCATED IN THE SERVICE BUILDING. PROVIDE NEW B-11, B-12, B-13, AND ASSOCIATED PUMPS. CONNECT NEW BOILER AND PUMPS TO EXISTING CONTROL SYSTEM. B-11, B-12, AND B-13
BOILER PLANT MUST BE FULLY OPERATIONAL AND ASSOCIATED WORK COMPLETED PRIOR TO PROJECT CLOSEOUT.
DURING THE BOILER REPLACEMENT UNDER THIS WORK SEQUENCE, ONLY ONE BOILER MUST BE TAKEN OFFLINE AND
REPLACED AT A TIME. BEFORE MOVING ONTO THE NEXT BOILER IN THIS SEQUENCE, THE PREVIOUS BOILER MUST BE FULLY
OPERATIONAL.
DURING THE REPLACEMENT OF HWP-5 AND HWP-6 UNDER THIS WORK SEQUENCE, ONLY ONE PUMP MUST BE TAKEN OFFLINE
AND REPLACED AT A TIME. BEFORE MOVING ONTO THE NEXT PUMP IN THIS SEQUENCE, THE PREVIOUS PUMP MUST BE FULLY
OPERATIONAL.
SCALE:
FLOOR PLAN
1/16" = 1'-0"
ENVIRONMENTAL NOTES
1. CONTRACTOR MUST ASSUME THAT ALL EXISTING PAINT COATINGS CONTAIN LEAD. IT IS NOT THE INTENT
OF THIS PROJECT TO PROVIDE A COMPREHENSIVE LEAD-BASED PAINT REMEDIATION, BUT
DISTURBANCE OF SOME PAINT-COATED SURFACES WILL BE REQUIRED TO PERFORM THE WORK.
WHERE EXISTING PAINTED SURFACES ARE DISTURBED (DRILLING, CUTTING, ETC.), THE
CONTRACTOR MUST PROVIDE WORKER PROTECTION IN ACCORDANCE WITH OSHA, AND ANY LOOSE
COATINGS AND COATING DUST MUST BE DISPOSED OF AS A HAZARDOUS LEAD WASTE. PAINTED
MATERIALS THAT ARE REMOVED AND DISPOSED OF MAY BE DISPOSED AS NORMAL CONSTRUCTION
WASTE PROVIDED THE COATINGS ARE INTACT ON THE MATERIAL BEING DISPOSED.
2. THE CONTRACTOR MUST PROVIDE A DESIGN FOR THE ENVIRONMENTAL WORK AS A SUBMITTAL FOR
APPROVAL PRIOR TO PERFORMING ANY ENVIRONMENTAL WORK.
GENERAL NOTES, LEGEND, AND
ABBREVIATIONS
M-001
U
D A
S
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY WORK IS PERFORMED. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE RELOCATED AS REQUIRED AT NO
ADDITIONAL COST TO THE OWNER.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, AND EQUIPMENT IS NOT LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL
CONTRACTOR FOR REVIEW AND COORDINATION.
4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE AND INTERNATIONAL BUILDING CODE / INTERNATIONAL
MECHANICAL CODE.
5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL OR MODIFICATION
TO OTHER PIPING, WIRING, OR EQUIPMENT.
6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK ACCESS TO EQUIPMENT
AND RELATED ACCESSORIES.
7. COORDINATE WALL, FLOOR, AND ROOF PENETRATIONS WITH THE CONTRACTOR OFFICER.
8. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT PIPING AND EQUIPMENT FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE HVAC
CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
9. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS. ACTUAL LOCATIONS SHALL BE
FIELD DETERMINED.
10. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.
11. FOR WALL, FLOOR, AND SLAB PENETRATIONS, SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING CONSTRUCTION/FINISH OR AS SHOWN ON MECHANICAL DETAILS SHEET. PROVIDE FIRE STOPPING FOR RATED WALLS AND FLOORS.
12. INSTALL CONTROL WIRING IN GREEN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.
13. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
14. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE
THE SPECIFICATION HAS OPTIONS.
15. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.
16. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE.
17. CONTROLS CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, CONDUIT AND PATHWAYS IN ACCORDANCE WITH THE
REQUIREMENTS OF 26 20 00.
18. NOT ALL ABBREVIATIONS AND LEGEND ITEMS WILL BE USED.
GENERAL MECHANICAL NOTES: ABBREVIATIONS:
@ AT
& AND
AHU AIR HANDLING UNIT
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING,
AND AIR CONDITIONING ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
BD BALANCING DAMPER
BDD BACKDRAFT DAMPER
BLDG BUILDING
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
COND STEAM CONDENSATE
CONN CONNECT, CONNECTING, CONNECTION
CON CONTINUED
COV STEAM CONVERTER
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DFCU DUCTLESS FAN COIL UNIT
DH DEHUMIDIFIER
DIA, Ø DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE,
PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
EMCS ENERGY MONITORING AND CONTROLS
SYSTEM
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXIST. EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
H HEIGHT
HPS HIGH PRESSURE STEAM
HR HOUR
HTG HEATING
HTR HEATER
HTW HEATING WATER
HWR HEATING WATER RETURN
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBD LINEAR BAR DIFFUSER
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFCR, MFG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP, MOP MAXIMUM OVER CURRENT PROTECTION
MTWR MEDIUM TEMPERATURE WATER RETURN
MTWS MEDIUM TEMPERATURE WATER SUPPLY
MXB MIXING BOX
N.C. NORMALLY CLOSED
NC NOISE CRITERIA
NG NATURAL GAS
NO. NUMBER
N.C. NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PCHWR PLANT CHILLED WATER RETURN
PCHWS PLANT CHILLED WATER SUPPLY
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PMTWR PLANT MEDIUM TEMPERATURE
WATER RETURN
PMTWS PLANT MEDIUM TEMPERATURE
WATER SUPPLY
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
SAG SUPPLY AIR GRILLE
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
STM STEAM
SS STAINLESS STEEL
TEMP TEMPERATURE
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL
SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME TERMINAL UNIT
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
VVS VARIABLE VOLUME SUPPLY TERMINAL
UNIT
VVLE VARIABLE VOLUME EXHAUST TERMINAL
UNIT
WB, Twb WET BULB (TEMPERATURE)
A
J
SD
SP
F
CO
T
VFD
T
H
TH
H
DP
C
AQ
PS
FS
X
MISCELLANEOUS LEGEND:
A
J
SD
SP
F
CO
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
CONTROL WIRING
STATIC PRESSURE SENSOR
ROUND OR DIAMETER
FIRESTAT
TEMPERATURE SENSORT
120 VOLT STAND BY POWER JUNCTION
BOX PROVIDED BY THE ELECTRICAL
CONTRACTOR. JUNCTION BOX IS
DEDICATED FOR USE BY THE
CONTROLS CONTRACTOR.
VARIABLE FREQUENCY DRIVEVFD
RETURN AIR GRILLE
SUPPLY AIR DIFFUSER
FLOW ARROWS INDICATE AIR PATTERN.
NO FLOW ARROWS SHOWN INDICATES
4-WAY PATTERN.
EXHAUST AIR GRILLE
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START/ STOP SWITCH
TH THERMOSTAT/ HUMIDISTAT
HUMIDITY SENSORH
DP DIFFERENTIAL PRESSURE SENSOR
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
POINT OF RECONNECTION OR
EXTENT OF DEMOLITION
PIPING LEGEND:
FLEXIBLE CONNECTION
THERMOMETER
PRESSURE REDUCING VALVE
MANUAL AIR VENT
PRESSURE/TEMPERATURE TAP WITH
BALL VALVE
PRESSURE SWITCH
PLUG VALVE
FLOW SWITCH
T&P RELIEF VALVE
AUTOMATIC AIR VENT
PRESSURE GAUGE WITH GAUGE COCK
PS
FS
BUTTERFLY VALVE
STRAINER WITH BLOWDOWN VALVE,
CAP, AND CHAIN
FLOW MEASURING/BALANCING/SHUT-
OFF VALVE
GATE VALVE
CHECK VALVE
BALL VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
PIPE FLANGE
PIPE CAP
PIPE GUIDE (PG)
PIPE ANCHOR (PA) X
UNION
TEE OUTLET UP
BRANCH BOTTOM CONNECTION
BRANCH TOP CONNECTION
ELBOW UP
ELBOW DOWN
RISE OR DROP
TEE OUTLET DOWN
GLOBE VALVE
ME
N'
S
TO
ILE
T
EL
EC
CL
OS
ET
DARK ROOM
DOOR
LAT
GYP GYP
LAT
LAT
LAT
LAT LAT
LAT LAT
LATLAT
GYP
LAT
LATLAT
LAT LAT
LATLAT
LATLAT
LAT LAT
LAT
LAT
NO CLG
LAT
LAT LAT
LATLAT
LAT
LAT LAT LAT LAT
LAT
LAT
NO CLG
NO CLGNO CLGNO CLGNO CLG
FI
RE
E
. NO CLG
NO CLG
NO CLG
LAT
NO CLG
NO CLG NO CLG
NO CLG
NO CLG
EL
EC
CL
OS
ET
GYP
LAT
LAT
LAT
NO CLG
LAT
LAT
NO CLG
NO CLG
GYP
GYP
MI. SP.
LAT
SCALE:
MAIN BUILDING BASEMENT MECHANICAL DEMOLITION PLAN
1/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
MD101
MAIN BUILDING BASEMENT OVERALL
MECHANICAL DEMOLITION PLAN
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
U
D A
S
CORRIDORCORRIDORCORRIDORCORRIDORCORRIDORCORRIDOR
DN.
UP.
UP.
DN.
ELEVATOR
JANITOR'S CLOSET
CORRIDOR
STAIR A
STAIR B
DN
DN
UP
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF TOP OF ROOF TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
GREENHOUSE BAY #1
GREENHOUSE BAY #3
GREENHOUSE BAY #2
GREENHOUSE BAY #4
SCALE:
MAIN BUILDING ATTIC MECHANICAL DEMOLITION PLAN
1/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
MAIN BUILDING ATTIC OVERALL
MECHANICAL DEMOLITION PLAN
MD102
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
U
D A
S
GYP
SCALE:
SERVICE BUILDING MECHANICAL DEMOLITION PLAN
3/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
SERVICE BUILDING
MECHANICAL DEMOLITION PLAN
MD103
1. DEMOLISH EXISTING BOILER (B-11), COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP,
AND ALL OTHER APPURTENANCES. DEMOLISH
HEATING WATER SUPPLY AND RETURN PIPING UP TO
BOILER ISOLATION VALVES.
2. DEMOLISH EXISTING BOILER (B-12), COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP,
AND ALL OTHER APPURTENANCES. DEMOLISH
HEATING WATER SUPPLY AND RETURN PIPING UP TO
BOILER ISOLATION VALVES.
3. DEMOLISH EXISTING BOILER (B-13), COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP,
AND ALL OTHER APPURTENANCES. DEMOLISH
HEATING WATER SUPPLY AND RETURN PIPING UP TO
BOILER ISOLATION VALVES.
4. DEMOLISH EXISTING BASE MOUNTED HEATING WATER
PUMP (HWP-5). DEMOLISH EXISTING 6" HEATING
WATER PIPING UP TO ISOLATION VALVES. EXISTING
PUMP MUST BE TURNED OVER TO THE GOVERNMENT
AND DELIVER TO A LOCATION ON SITE DETERMINED
BY THE CONTRACTING OFFICER.
5. DEMOLISH EXISTING BASE MOUNTED HEATING WATER
PUMP (HWP-6). DEMOLISH EXISTING 6" HEATING
WATER PIPING UP TO ISOLATION VALVES. EXISTING
PUMP MUST BE TURNED OVER TO THE GOVERNMENT
AND DELIVER TO A LOCATION ON SITE DETERMINED
BY A CONTRACTING OFFICER.
6. DEMOLISH EXISTING NATURAL GAS PIPING UP TO
EXISTING MAIN ISOLATION VALVE. DEMOLISH EXISTING
BOILER ISOLATION VALVES, AND REGULATORS.
1 2 3
4 5
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
U
D A
S
EXIST. TO REMAIN
5" HTWR
EXIST. TO REMAIN
5" HTWS
EXIST. FLUE VENT PIPING
TO REMAIN (TYP.)
EXIST. FLUE TO VENT
PIPING TO REMAIN (TYP.)
EXIST. TO REMAIN
5" HTWR
EXIST. TO REMAIN
5" HTWS
DEMOLISH EXIST. 4" NG
DEMOLISH EXIST. 1-1/2" NG
(TYP. 3)
DEMOLISH EXIST. BOILER
EXIST. HOUSEKEEPING PAD
TO REMAIN
DEMOLISH
EXIST. ASME
PRESSURE
RELIEF VALVE
DEMOLISH EXIST. BOILER
PRIMARY PUMP
DEMOLISH EXIST.
PRESSURE GAUGE (TYP.)
DEMOLISH EXIST.
STRAINER
DEMOLISH EXIST.
THERMOMETER (TYP.)
DEMOLISH EXIST. BOILER
DRAIN AND VALVE
DEMOLISH EXIST. 4" HTWS
& 4" HTWR PIPING (TYP.)
EXIST. 4" HTWS TO REMAINEXIST. 4" HTWR TO REMAIN
DEMOLISH EXIST. NG TO
BOILER
EXIST. HOUSEKEEPING
PAD TO REMAIN
DEMOLISH EXIST. PUMP
AND MOTOR
DEMOLISH EXIST. TRIPLE
DUTY VALVE
DEMOLISH EXIST. BRAIDED
FLEX CONNECTOR (TYP. 2)
DEMOLISH EXIST. SUCTION
DIFFUSER
EXIST.
BUTTERFLY ISOLATION
VALVE TO REMAIN (TYP. 2)
EXIST. ISOLATION GATE
VALVE (TYP. 2) TO REMAIN
EXIST. 6" HTWS TO REMAIN
EXIST. 6" HTWS TO REMAIN
SCALE:
EXIST. B-11, B-12, & B-13 DEMOLITION DETAIL
NTS
SCALE:
EXIST. HWP-5 AND HWP-6 DEMOLITION DETAIL
NTS
DEMOLISH EXIST. CHECK
VALVE
SCALE:
MAIN BUILDING BASEMENT ENLARGED
MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
SCALE:
MAIN BUILDING ATTIC ENLARGED MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE APPROXIMATE. ITEMS TO BE REMOVED ARE
DESIGNATED BY HATCHING AND DASHED LINES.
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
UNLESS NOTED OTHERWISE.
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
ENLARGED
MECHANICAL DEMOLITION PLANS
MD401
1. DEMOLISH EXISTING BOILER (B-6), COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP,
AND ALL OTHER APPURTENANCES. DEMOLISH
EXISTING HEATING WATER PIPING UP TO BOILER
ISOLATION VALVES.
2. DEMOLISH EXISTING BOILER (B-7), COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP,
AND ALL OTHER APPURTENANCES. DEMOLISH
EXISTING HEATING WATER PIPING UP TO BOILER
ISOLATION VALVES.
3. DEMOLISH EXISTING BOILER (B-8), COMBUSTION AIR
INTAKE FILTER, BOILER PRIMARY CIRCULATION PUMP,
HOUSEKEEPING PAD, AND ALL OTHER
APPURTENANCES. DEMOLISH EXISTING HEATING
WATER PIPING UP TO BOILER ISOLATION VALVES.
4. DEMOLISH EXISTING BASE MOUNTED HEATING WATER
PUMP (HWP 1-1). DEMOLISH EXISTING HEATING WATER
PIPING UP TO PUMP SUCTION ISOLATION VALVE.
EXISTING PUMP MUST BE TURNED OVER TO THE
GOVERNMENT AND DELIVER TO A LOCATION ON SITE
DETERMINED BY THE CONTRACTING OFFICER.
5. DEMOLISH EXISTING BASE MOUNTED HEATING WATER
PUMP (HWP 1-2). DEMOLISH EXISTING HEATING WATER
PIPING UP TO PUMP SUCTION ISOLATION VALVE.
EXISTING PUMP MUST BE TURNED OVER TO THE
GOVERNMENT AND DELIVER TO A LOCATION ON SITE
DETERMINED BY THE CONTRACTING OFFICER.
6. DEMOLISH EXISTING INLINE HEATING WATER PUMP.
EXISTING PUMP MUST BE TURNED OVER TO THE
GOVERNMENT AND DELIVER TO A LOCATION ON SITE
DETERMINED BY THE CONTRACTING OFFICER.
7. DEMOLISH EXISTING 1-1/2" NATURAL GAS PIPING UP
TO EXISTING MAIN. DEMOLISH EXISTING BOILER
ISOLATION VALVES AND REGULATORS.
8. DEMOLISH EXISTING 1-1/2" NATURAL GAS PIPING UP
TO EXISTING ISOLATION VALVE. DEMOLISH EXISTING
BOILER ISOLATION VALVES AND REGULATORS.
9. DEMOLISH EXISTING 4" HTWS PIPING FROM
CONNECTION TO PUMPS UP TO CONENCTION TO TEE.
REMOVE AND PROTECT EXISTING SENSORS
INSTALLED IN PIPING RUN TO BE DEMOLISHED FOR
INSTALLATION IN NEW WORK.
U
D A
S
EXIST. HOUSEKEEPING PAD
TO REMAIN
DEMOLISH EXIST. PUMP
AND MOTOR
DEMOLISH EXIST. TRIPLE
DUTY VALVE
DEMOLISH EXIST. CHECK
VALVE
DEMOLISH EXIST. SUCTION
DIFFUSER
EXIST. ISOLATION VALVE
TO REMAIN
DEMOLISH EXIST. 4" HTWS
EXIST. 4" HTWS TO REMAIN
SCALE:
EXIST. HWP 1-1 AND HWP 1-2 DEMOLITION DETAIL
NTS
DEMOLISH EXIST. BOILER
EXIST. HOUSEKEEPING PAD
TO REMAIN FOR B-6 AND
B-7. EXIST. HOUSEKEEPING
PAD TO BE DEMOLISHED
FOR B-8.
DEMOLISH
EXIST. ASME
PRESSURE
RELIEF VALVE
DEMOLISH EXIST. BOILER
PRIMARY PUMP
DEMOLISH EXIST.
PRESSURE GAUGE (TYP.)
DEMOLISH EXIST.
STRAINER
DEMOLISH EXIST.
THERMOMETER (TYP.)
DEMOLISH EXIST. BOILER
DRAIN AND VALVE
DEMOLISH EXIST. 4" HTWS
& 4" HTWR PIPING (TYP.)
EXIST. 4" HTWS TO REMAINEXIST. 4" HTWR TO REMAIN
EXIST.
BUTTERFLY ISOLATION
VALVE (TYP. 2) TO REMAIN
DEMOLISH EXISTING NG TO
BOILER
SCALE:
EXIST. B-6, B-7, & B-8 DEMOLITION DETAIL
NTS
EXIST. FLUE VENT PIPING
TO REMAIN (TYP.)
EXIST. FLUE TO VENT
PIPING TO REMAIN (TYP.)
EXIST. EXPANSION
TANK TO REMAIN
EXIST. AIR SEPARATOR
TO REMAIN
DEMOLISH EXIST. PUMP
AND MOTOR (TYP.2)
EXIST. GATE ISOLATION
VALVE (TYP. 4) TO REMAIN
DEMOLISH EXIST.
DIFFERENTIAL PRESSURE
GAUGE, VALVES, AND
PIPING (TYP. 2)
EXIST. HTW
PIPING
EXIST. HTW
PIPING
SCALE:
EXIST. ATTIC BOILER INLINE PUMPS DEMOLITION DETAIL
NTS
DEMOLISH EXIST. PIPING
INSULATION BETWEEN MAIN
AND ISOLATION VALVE
DEMOLISH EXIST. PIPING
INSULATION BETWEEN MAIN
AND ISOLATION VALVE
DEMOLISH EXIST. PIPING
INSULATION BETWEEN MAIN
AND ISOLATION VALVE
DEMOLISH EXIST. PIPING
INSULATION BETWEEN MAIN
AND ISOLATION VALVE
EXIST. 1" NG
DEMOLISH EXIST. RUBBER
FLEX CONNECTOR
DEMOLISH EXIST.
2" NG
DEMOLISH EXIST.
CHECK VALVE
(TYP. 2)
S
TO
ILE
T
EL
EC
CL
OS
ET
DARK ROOM
DOOR
LAT
GYP GYP
LAT
LAT
LAT
LAT LAT
LAT LAT
LATLAT
GYP
LAT
LATLAT
LAT LAT
LATLAT
LATLAT
LAT LAT
LAT
LAT
NO CLG
LAT
LAT LAT
LATLAT
LAT
LAT LAT LAT LAT
LAT
LAT
NO CLG
NO CLGNO CLGNO CLGNO CLG
FI
RE
E
. NO CLG
NO CLG
NO CLG
LAT
NO CLG
NO CLG NO CLG
NO CLG
NO CLG
EL
EC
CL
OS
ET
GYP
LAT
LAT
LAT
NO CLG
LAT
LAT
NO CLG
NO CLG
GYP
GYP
MI. SP.
LAT
SCALE:
MAIN BUILDING BASEMENT MECHANICAL NEW WORK PLAN
1/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
M-101
MAIN BUILDING BASEMENT OVERALL
MECHANICAL NEW WORK PLAN
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
U
D A
S
UP.
UP.
DN.
ELEVATOR
JANITOR'S CLOSET
CORRIDOR
STAIR A
STAIR B
DN
DN
UP
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF TOP OF ROOF TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
GREENHOUSE BAY #1
GREENHOUSE BAY #3
GREENHOUSE BAY #2
GREENHOUSE BAY #4
SCALE:
MAIN BUILDING ATTIC MECHANICAL NEW WORK PLAN
1/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
MAIN BUILDING ATTIC OVERALL
MECHANICAL NEW WORK PLAN
M-102
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
U
D A
S
SCALE:
SERVICE BUILDING MECHANICAL NEW WORK PLAN
3/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
SERVICE BUILDING
MECHANICAL NEW WORK PLAN
M-103
1. PROVIDE NATURAL GAS FIRED HIGH-EFFICIENCY
CONDENSING BOILER, CONDENSATE NEUTRALIZER,
AND ALL OTHER APPURTENANCES. INSTALL PER
MANUFACTURER'S REQUIREMENTS. RECONNECT TO
EXISTING FLUE VENT PIPING. RECONNECT TO
EXISTING HTW PIPING AS SHOWN IN DETAIL 2/M-103.
INTEGRATE BOILER INTO EXISTING CONTROL SYSTEM.
ALL EXISTING POINTS AND CONTROL CAPABILITIES
MUST BE MAINTAINED.
2. PROVIDE BASE MOUNTED HEATING WATER PUMP,
AND ALL OTHER APPURTENANCES. INSTALL PER
MANUFACTURER'S REQUIREMENTS. RECONNECT TO
EXISTING HTWS PIPING AS SHOWN IN DETAIL 3/M-103.
INTEGRATE PUMP INTO EXISTING CONTROL SYSTEM.
ALL EXISTING POINTS AND CONTROL CAPABILITIES
MUST BE MAINTAINED.
3. PROVIDE INLINE HEATING WATER PUMP, AND ALL
OTHER APPURTENANCES. INSTALL PER
MANUFACTURER'S REQUIREMENTS. INTEGRATE PUMP
INTO EXISTING CONTROL SYSTEM. ALL EXISTING
POINTS AND CONTROL CAPABILITIES MUST BE
MAINTAINED.
4. CONNECT NEW 1-1/2" NG PIPING TO BOILER. PROVIDE
ISOLATION VALVE, PRESSURE REGULATOR, AND DRIP
LEG. SEE DETAIL 1/M-501.
5. PROVIDE ASME CSD-1 COMPLIANT BOILER
EMERGENCY SHUTDOWN SWITCH. SWITCH SHALL BE
CONNECTED TO B-11, B-12, AND B-13. INSTALL PUSH
BUTTON IN A PROTECTIVE POLYCARBONATE
ENCLOSURE (SIMILAR TO STI UNIVERSAL STOPPER).
B-13 B-12
B-11
BP-113 BP-123 BP-13 3
HWP-52
HWP-62
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
U
D A
S
EXIST. 5" HTWS
EXIST. 5" HTWR
2" NG
BOILER
EXIST. HOUSEKEEPING
PAD.
ASME PRESSURE
RELIEF VALVE.
PIPE FULL SIZE
TO FLOOR DRAIN
BOILER PRIMARY PUMP
PRESSURE GAUGE (TYP.)
STRAINER W/BLOWDOWN
THERMOMETER (TYP.)
BOILER DRAIN AND VALVE
4" HTWS & 4" HTWR PIPING
(TYP.)
EXIST. 4" HTWSEXIST. 4" HTWR
1-1/2" NGEXIST.
BUTTERFLY ISOLATION
VALVE (TYP. 2)
SCALE:
B-11, B-12, & B-13 INSTALLATION DETAIL
NTS
T AND P PLUG (TYP.)
DRAIN VALVE WITH HOSE
CONNECTION (TYP.)
EXIST. HOUSEKEEPING
PAD.
PUMP AND MOTOR
6" TRIPLE DUTY VALVE
RUBBER FLEX CONNECTOR
(TYP. 2)
SUCTION DIFFUSER
W/PULL OUT STRAINER
EXIST. GATE ISOLATION
VALVE (TYP. 2)
EXIST. 6" HTWS
EXIST. 6" HTWS
SCALE:
HWP-5 AND HWP-6 DETAIL
NTS
1-1/2"
NG
6" HTWS
EXIST. PRESSURE GAUGE
(TYP.2)
1-1/2"
NG
1-1/2"
NG
CONCENTRIC
REDUCER
DRAIN WITH BALL
VALVE
PUMP INERTIA BASE
SUCTION DIFFUSER
SUPPORT
P
P
NG REGULATOR (TYP. 3)
ISOLATION VALVE (TYP. 3)
6" HTWS
NOTES:
1. MAKE FINAL CONNECTIONS TO EQUIPMENT.
COORDINATE INSTALLATION, CONNECTIONS, AND
LOCATIONS WITH ACTUAL EQUIPMENT SUPPLIED AND WITH
MANUFACTURER'S REQUIREMENTS.
2. CONTRACTOR MUST FIELD VERIFY EXISTING PIPING SIZES
PRIOR TO ORDERING ANY PIPING, VALVES, OR FITTINGS.
NOTES:
CONTRACTOR MUST FIELD VERIFY EXISTING PIPING
SIZES PRIOR TO ORDERING ANY PIPING, VALVES,
OR FITTINGS.
SCALE:
MAIN BUILDING BASEMENT ENLARGED MECHANICAL NEW WORK PLAN
1/4" = 1'-0"
SCALE:
MAIN BUILDING ATTIC ENLARGED MECHANICAL NEW WORK PLAN
1/4" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
ENLARGED
MECHANICAL NEW WORK PLANS
M-401
1. PROVIDE NATURAL GAS FIRED HIGH-EFFICIENCY
CONDENSING BOILER, CONDENSATE NEUTRALIZER,
AND ALL OTHER APPURTENANCES. INSTALL PER
MANUFACTURER'S REQUIREMENTS. RECONNECT TO
EXISTING FLUE VENT PIPING. RECONNECT TO
EXISTING HTW PIPING AS SHOWN IN DETAIL 3/M-401.
INTEGRATE BOILER INTO EXISTING CONTROL SYSTEM.
ALL EXISTING POINTS AND CONTROL CAPABILITIES
MUST BE MAINTAINED.
2. PROVIDE NATURAL GAS FIRED HIGH-EFFICIENCY
CONDENSING BOILER, CONDENSATE NEUTRALIZER,
AND ALL OTHER APPURTENANCES. INSTALL PER
MANUFACTURER'S REQUIREMENTS. RECONNECT TO
EXISTING FLUE VENT PIPING. RECONNECT TO
EXISTING HTW PIPING AS SHOWN IN DETAIL 3/M-401.
INTEGRATE BOILER INTO EXISTING CONTROL SYSTEM.
ALL EXISTING POINTS AND CONTROL CAPABILITIES
MUST BE MAINTAINED.
3. PROVIDE BASE MOUNTED HEATING WATER PUMP,
AND ALL OTHER APPURTENANCES. INSTALL PER
MANUFACTURER'S REQUIREMENTS. RECONNECT TO
EXISTING HTWS PIPING AS SHOWN IN DETAIL 4/M-401.
INTEGRATE PUMP INTO EXISTING CONTROL SYSTEM.
ALL EXISTING POINTS AND CONTROL CAPABILITIES
MUST BE MAINTAINED.
4. PROVIDE INLINE HEATING WATER PUMP. INSTALL PER
MANUFACTURER'S REQUIREMENTS. INTEGRATE PUMP
INTO EXISTING CONTROL SYSTEM. ALL EXISTING
POINTS AND CONTROL CAPABILITIES MUST BE
MAINTAINED.
5. PROVIDE INLINE HEATING WATER PUMP (TYP. 2). SEE
DETAIL 5/M-401.INTEGRATE PUMP INTO EXISTING
CONTROL SYSTEM. ALL EXISTING POINTS AND
CONTROL CAPABILITIES MUST BE MAINTAINED.
6. PROVIDE 6" UL-1738 CATEGORY IV LISTED AND
LABELED DOUBLE WALL STAINLESS STEEL BOILER
FLUE. CONNECT TO EXISTING FLUE ON THE EXTERIOR
PENETRATION. PROVIDE ELBOW TO EXTEND FLUE 3'
ABOVE ADJACENT ROOF GRAVITY INTAKE. INSTALL
PER BOILER MANUFACTURER'S INSTALLATION
INSTRUCTIONS. PROVIDE MANUFACTURER APPROVED
RAIN CAP AT POINT OF DISCHARGE.
7. CONNECT BOILER TO EXISTING BOILER FLUE.
8. CONNECT NEW 1-1/2" NG PIPING TO BOILER. PROVIDE
ISOLATION VALVE, PRESSURE REGULATOR, AND DRIP
LEG. SEE DETAIL 1/M-501.
9. PROVIDE ASME CSD-1 COMPLIANT BOILER
EMERGENCY SHUTDOWN SWITCH. SWITCH SHALL BE
CONNECTED TO B-7 AND B-8. INSTALL PUSH BUTTON IN
A PROTECTIVE POLYCARBONATE ENCLOSURE
(SIMILAR TO STI UNIVERSAL STOPPER).
10. PROVIDE ASME CSD-1 COMPLIANT BOILER
EMERGENCY SHUTDOWN SWITCH. SWITCH SHALL BE
CONNECTED TO B-6. INSTALL PUSH BUTTON IN A
PROTECTIVE POLYCARBONATE ENCLOSURE (SIMILAR
TO STI UNIVERSAL STOPPER).
11. CONNECT 4" HTWS TO EXISTING TEE AND ROUTE TO
DISCHARGE SIDE OF PUMPS. INSTALL EXISTING
SENSORS IN NEW PIPING.
B-6
B-7
B-8
HWP-1-1
HWP-1-2
ET-1
HWP-6-15
BP-74 BP-8 4
BP-6 4
HWP-6-25
1. MECHANICAL SYSTEMS AND EQUIPMENT SHOWN ON
THIS DRAWING ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
U
D A
S
BOILER
EXIST. HOUSEKEEPING
PAD. MOUNT B-8 DIRECTLY
TO EXISTING BUILDING
SLAB
ASME PRESSURE
RELIEF VALVE.
PIPE FULL SIZE
TO FLOOR DRAIN
BOILER PRIMARY PUMP
PRESSURE GAUGE (TYP.)
STRAINER W/BLOWDOWN
THERMOMETER (TYP.)
BOILER DRAIN AND VALVE
4" HTWS & 4" HTWR PIPING
(TYP.)
EXIST. 4" HTWSEXIST. 4" HTWR
1-1/2" NGEXIST.
ISOLATION BUTTERFLY
VALVE (TYP. 2)
SCALE:
B-6, B-7 & B-8 INSTALLATION DETAIL
NTS
T AND P PLUG (TYP.)
DRAIN VALVE WITH HOSE
CONNECTION (TYP.)
EXIST. HOUSEKEEPING
PAD.
PUMP AND MOTOR
4" TRIPLE DUTY VALVE
RUBBER FLEX
CONNECTOR (TYP. 2)
SUCTION DIFFUSER
W/PULL OUT STRAINER
EXIST. BUTTERFLY
ISOLATION VALVE
4" HTWS
EXIST. 4" HTWS
SCALE:
HWP 1-1 AND HWP 1-2 DETAIL
NTS
1-1/2"
NG1" NG
HWP 6-1
EXIST. GATE ISOLATION
VALVE (TYP. 4)
DIFFERENTIAL PRESSURE
GAUGE, VALVES, AND
PIPING (TYP. 2)
EXIST. HTW
PIPING
EXIST. HTW
PIPING
SCALE:
ATTIC BOILER INLINE PUMPS DETAIL
NTS
PROVIDE NEW PIPING INSULATION BETWEEN
MAIN AND ISOLATION VALVE. THIS NOTE DOES
NOT OMIT REQUIREMENT FOR INSULATION ON
ALL OTHER PIPING. THIS NOTE IS INDICATING THE
REQUIREMENT FOR THE INSULATION OF
EXISTING PIPING TO REMAIN.
HWP 6-2
FULL PORT BALL
VALVE (TYP. 4)
1-1/2"
NG
4" HTWS 10
4" HTWS11
4" HTWS
BUTTERFLY ISOLATION
VALVE
PRESSURE GAUGE
(TYP.2)
THERMOMETER
CONCENTRIC REDUCER
PUMP INERTIA BASE
SUCTION DIFFUSER
SUPPORT
DRAIN WITH BALL
VALVE
PETES PLUG (TYP.)
CHECK VALVE
(TYP 2.)
NG ISOLATION VALVE (TYP. 2)
NG REGULATOR (TYP. 2)
NATURAL GAS REGULATOR
EXIST. NATURAL GAS ISOLATION VALVE
EXIST. 1" NG 1" NG
1-1/2" NG
NOTES:
CONTRACTOR MUST FIELD VERIFY EXISTING PIPING
SIZES PRIOR TO ORDERING ANY PIPING, VALVES,
OR FITTINGS.
4" HTWS
NOTES:
CONTRACTOR MUST FIELD VERIFY EXISTING PIPING
SIZES PRIOR TO ORDERING ANY PIPING, VALVES,
OR FITTINGS.
NOTES:
CONTRACTOR MUST FIELD VERIFY EXISTING PIPING
SIZES PRIOR TO ORDERING ANY PIPING, VALVES,
OR FITTINGS.
NOTES:
1. MAKE FINAL CONNECTIONS TO EQUIPMENT.
COORDINATE INSTALLATION, CONNECTIONS, AND
LOCATIONS WITH ACTUAL EQUIPMENT SUPPLIED AND WITH
MANUFACTURER'S REQUIREMENTS.
2. CONTRACTOR MUST FIELD VERIFY EXISTING PIPING SIZES
PRIOR TO ORDERING ANY PIPING, VALVES, OR FITTINGS.
M-501
MECHANICAL DETAILS
U
D A
S
NG MAIN
SCALE:
BOILER NATURAL GAS CONNECTION DETAIL
NTS SCALE:
CONDENSATE ACID NEUTRALIZER DETAIL
NTS
ISOLATION
VALVE
ISOLATION
VALVE
DRIP
LEG (MINIMUM OF 3" IN LENGTH)
PRESSURE REGULATOR
PER MANUFACTURER'S
REQUIREMENTS.
REGULATOR MUST BE INSTALLED WITH
A MINIMUM OF 10 LINEAR FEET OF PIPE
BETWEEN THE REGULATOR OUTLET
AND BOILER FUEL TRAIN
PROVIDE 10 PIPE DIAMETERS EQUIVALENT TO
REGULATOR CONNECTION SIZE. THIS PIPE
MUST BE STRAIGHT, UNINTERRUPTED PIPE
BETWEEN REGULATOR OUTLET AND ANY
FITTINGS, VALVES, OR ELBOWS.
1-1/2" NG UNLESS NOTED OTHERWISE
1-1/2" NG
TO BOILER
CONNECTION
CONDENSING WATER
HEATER FLUE
UNION
FULL SIZE
BYPASS
PIPE TO APPROPRIATE DRAIN
IN SANITARY SYSTEM
CONDENSATE
TRAP
ACID NEUTRALIZER. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS
SCALE:
CLEVIS HANGER DETAIL
NOT TO SCALE
HEAVY DUTY
CLEVIS HANGER:
MSS SP-69 AND
MSS SP-58
PIPE
RIGID INSULATION INSERT
(12" LONG, 180^ ARC)
CLEVIS HANGER
WITH INSULATION
SHIELD
INSULATION
BOLT & NUT
SUPPORT NUT
LOCKING NUT
HANGER ROD TO
STRUCTURE ABOVE
M-601
MECHANICAL SCHEDULES
BASIS OF
DESIGN
IMPELLER SIZE
(IN)
FLOW
(GPM)
HEAD
(FT)
FLUID
TYPE
MIN. MOTOR
HP
MOTOR RPM VOLTS/ PHASE REMARKS
PUMP SCHEDULE
NOTES:
1. PROVIDE BASE MOUNTED PUMPS WITH SUCTION DIFFUSERS AND FLANGED RUBBER FLEX CONNECTIONS.
2. ALL MOTORS TO BE NON-OVERLOADING AT ANY POINT ON THE PUMP CURVE.
3. PROVIDE WITH VIBRATION ISOLATION/INERTIA PADS.
4. CONTRACTOR MUST VERIFY BP-6 THROUGH BP-13 REQUIREMENTS WITH BOILER MANUFACTURER. PUMPS MUST BE PROVIDED BY THE BOILER MANUFACTURER AS PART OF THE BOILER PACKAGE.
5. TRIPLE DUTY VALVES PROVIDED ON BASE MOUNTED PUMP DISCHARGE MUST BE SELECTED TO HAVE A MAXIMUM PRESSURE DROP OF 5 FT. HD. AT THE SCHEDULED OPERATING CONDITIONS.
MARK TYPE SERVES
FLUID DATA ELECTRICAL DATA
HWP-6-1
HWP-6-2
MIN.
DUTY POINT
EFFICIENCY
BASIS OF
DESIGN
INPUT
(MBH)
OUTPUT
(MBH)
TURN DOWN
RATIO
LOCHINVAR
CREST HEATING WATER
HIGH EFFICIENCY CONDENSING BOILER SCHEDULE
MARK SERVICE
HEATING DATA
1,500
B-6 NATURAL GAS
FUEL TYPE
25:1
NOTES:
VOLTS/PH
ELECTRICAL DATA
120/1 SEE NOTES
GPM FLUID
TYPE
350 WATER
FLUE
OUTLET MCA
8" 13A
REMARKS
OPER.
WEIGHT
(LBS)
2307160
EWT
(F)
LWT
(F)
WPD
FT. HD
5.0
COMB.
INTAKE
8"
1. PROVIDE BOILER WITH CONDENSATE NEUTRALIZER KIT. ROUTE CONDENSATE TO FLOOR DRAIN.
2. PROVIDE WITH LCD DISPLAY SCREEN.
3. PROVE WITH 160 PSI MAXIMUM WORKING PRESSURE.
4. PROVIDE WITH FLUE DAMPER KIT.
5. BOILER MUST BE INTEGRATED INTO THE EXISTING CONTROL SYSTEM. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL HARDWARE, GATEWAYS, SOFTWARE, AND PROGRAMMING NECESSARY TO MAINTAIN
ALL EXISTING CONTROL FUNCTIONS AND INTERLOCKS.
6. PROVIDE WITH COMBUSTION AIR INTAKE FILTER.
7. PROVIDE REGULATOR AND BOILER NATURAL GAS ISOLATION VALVE. REGULATOR MUST BE SIZED TO PROVIDE NATURAL GAS SUPPLY PRESSURE TO BOILER AS SCHEDULED. INSTALL PER MANUFACTURER'S
INSTALLATION MANUAL AND ALL APPLICABLE CODES AND STANDARDS.
8. PROVIDE ASME CSD-1 COMPLIANT BOILER EMERGENCY SHUTDOWN SWITCH.
SEE NOTESHWP-1-1
BELL &
GOSSETT
BASE MOUNTED
END SUCTION
BASE MOUNTED
END SUCTION
INLINE SUCTION
INLINE SUCTION
HWP-1-2
HWP-6
BP-6
BASE MOUNTED
END SUCTION
INLINE BOILER
PUMP
BASE MOUNTED
END SUCTION
HWP-5
BP-7
BP-8
BP-11
BP-12
BP-13
9.375
9.375
12.625
12.625
5.625
WATER
WATER
WATER
WATER
WATER
1.5
208/3
208/3
460/3
460/3
208/3
68.6%
68.6%
61.1%
61.1%
75.1%
75.1%
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
INLINE BOILER
PUMP
INLINE BOILER
PUMP
INLINE BOILER
PUMP
INLINE BOILER
PUMP
INLINE BOILER
PUMP
B-7, B-8
B-6
B-6
B-7
B-8
B-11
B-12
B-13
B-7, B-8
B-6
B-11, B-12, B-13
B-11, B-12, B-13
B-7
B-8
1,380B-11
B-12
B-13
U
D A
S
HEATING WATER
HEATING WATER
HEATING WATER
HEATING WATER
HEATING WATER
NATURAL GAS
NATURAL GAS
NATURAL GAS
NATURAL GAS
NATURAL GAS
1,500
1,500
1,380
1,380
1,3801,500
1,3801,500
1,3801,500
WATER
WATER
WATER
WATER
WATER
8"
8"
8"
8"
8"
120/1
120/1
120/1
120/1
120/1
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
WATER
WATER
WATER
WATER
WATER
208/3
208/3
208/3
208/3
208/3
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
BELL &
GOSSETT
WATER
WATER
5.0
5.0
5.0
5.0
5.0
208/3
208/3
1.5
1.5
1.5
1.5
1.5
5.625
5.625
5.625
5.625
5.625
71.8%
71.8%
71.8%
71.8%
71.8%
71.8%
LOCHINVAR
CREST
LOCHINVAR
CREST
LOCHINVAR
CREST
LOCHINVAR
CREST
LOCHINVAR
CREST
25:1
25:1
25:1
25:1
25:1
8"
8"
8"
8"
8"
13A
13A
13A
13A
13A
NATURAL GAS
SUPPLY PRESSURE
7-14 IN. WC.
7-14 IN. WC.
7-14 IN. WC.
7-14 IN. WC.
7-14 IN. WC.
7-14 IN. WC.
S
TO
ILE
T
EL
EC
CL
OS
ET
DARK ROOM
DOOR
LAT
GYP GYP
LAT
LAT
LAT
LAT LAT
LAT LAT
LATLAT
GYP
LAT
LATLAT
LAT LAT
LATLAT
LATLAT
LAT LAT
LAT
LAT
NO CLG
LAT
LAT LAT
LATLAT
LAT
LAT LAT LAT LAT
LAT
LAT
NO CLG
NO CLGNO CLGNO CLGNO CLG
FI
RE
E
. NO CLG
NO CLG
NO CLG
LAT
NO CLG
NO CLG NO CLG
NO CLG
NO CLG
EL
EC
CL
OS
ET
GYP
LAT
LAT
LAT
NO CLG
LAT
LAT
NO CLG
NO CLG
GYP
GYP
MI. SP.
LAT
SCALE:
MAIN BUILDING BASEMENT OVERALL ELECTRICAL DEMOLITION PLAN
1/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
ED101
MAIN BUILDING BASEMENT OVERALL
ELECTRICAL DEMOLITION PLAN
A. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE BASED ON THE BEST INFORMATION AT THE TIME
OF DESIGN AND MUST BE FIELD VERIFIED. EQUIPMENT
AND CIRCUITRY NOT EXPRESSLY LISTED FOR
DEMOLITION SHALL BE EXISTING-TO-REMAIN.
U
D A
S
UP.
UP.
DN.
ELEVATOR
JANITOR'S CLOSET
CORRIDOR
STAIR A
STAIR B
DN
DN
UP
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF TOP OF ROOF TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
GREENHOUSE BAY #1
GREENHOUSE BAY #3
GREENHOUSE BAY #2
GREENHOUSE BAY #4
SCALE:
MAIN BUILDING ATTIC OVERALL ELECTRICAL DEMOLITION PLAN
1/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
MAIN BUILDING ATTIC OVERALL
ELECTRICAL DEMOLITION PLAN
ED102
A. THE DEMOLITION PLAN AND EXISTING CONDITIONS
ARE BASED ON THE BEST INFORMATION AT THE TIME
OF DESIGN AND MUST BE FIELD VERIFIED. EQUIPMENT
AND CIRCUITRY NOT EXPRESSLY LISTED FOR
DEMOLITION SHALL BE EXISTING-TO-REMAIN.
U
D
VFD FOR HWP-5 (ETR)
VFD FOR HWP-6 (ETR)
PUMP
BP-11
(1.5 HP)
PUMP
BP-12
(1.5 HP)
PUMP
BP-13
(1.5 HP)
P2 L2
SBE-MCC
HWP-6 (25 HP)
HWP-5 (25 HP)
EQUIPMENT RACK
SCALE:
SERVICE BUILDING ELECTRICAL DEMOLITION PLAN
3/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
SERVICE BUILDING ELECTRICAL
DEMOLITION PLAN
ED103
1. DEMOLISH ELECTRICAL CONNECTION TO EXISTING
BOILER (B-11) FED THROUGH CONDUIT FROM
EQUIPMENT RACK. BOILER (B-11) IS FED FROM A 20/1
BREAKER IN PANEL L2 AT CIRCUIT #18. RETAIN
EXISTING RACEWAYS AND CIRCUITRY TO THE EXTENT
PRACTICAL.
2. DEMOLISH ELECTRICAL CONNECTION TO EXISTING
BOILER (B-12) FED THROUGH CONDUIT FROM
EQUIPMENT RACK. BOILER (B-12) IS FED FROM A 20/1
BREAKER IN PANEL L2 AT CIRCUIT #24. RETAIN
EXISTING RACEWAYS AND CIRCUITRY TO THE EXTENT
PRACTICAL.
3. DEMOLISH ELECTRICAL CONNECTION TO EXISTING
BOILER (B-13). BOILER (B-13) IS FED FROM A 20/1
BREAKER IN PANEL L2 AT CIRCUIT #16. RETAIN
EXISTING RACEWAYS AND CIRCUITRY TO THE EXTENT
PRACTICAL.
4. DEMOLISH ELECTRICAL CONNECTION FROM VFD TO
EXISTING PUMP (HWP-5). VFD IS FED FROM
SBE-MCC-18. CONDUIT SHALL BE RETAINED AND
REUSED. REPLACE FLEXIBLE CONNECTION
(APPROXIMATELY 18", FIELD VERIFY PRIOR TO
CONSTRUCTION).
5. DEMOLISH ELECTRICAL CONNECTION FROM VFD TO
EXISTING PUMP (HWP-6). VFD IS FED FROM
SBE-MCC-17. CONDUIT SHALL BE RETAINED AND
REUSED. REPLACE FLEXIBLE CONNECTION
(APPROXIMATELY 18", FIELD VERIFY PRIOR TO
CONSTRUCTION).
6. DEMOLISH CONNECTIONS FROM MOTOR STARTERS
TO THE THREE PUMPS (PUMP BP-11, PUMP BP-12, AND
PUMP BP-13). RETAIN DISCONNECTS AND MOTOR
STARTERS. NOTE: PROVIDE NEW LABELS IN PANEL P2
FOR ALL THREE PUMPS WITH APPROPRIATE NAMES.
A. THE DEMOLITION PLAN AND EXISTING CONDITIONS ARE
BASED ON THE BEST INFORMATION AT THE TIME OF
DESIGN AND MUST BE FIELD VERIFIED. EQUIPMENT AND
CIRCUITRY NOT EXPRESSLY LISTED FOR DEMOLITION
SHALL BE EXISTING-TO-REMAIN.
B. LOCK OFF ALL UNUSED BREAKERS AND LABEL "SPARE".
C. SEAL UNUSED CONDUIT OPENINGS WITH PLATES
EQUIVALENT TO ENCLOSURE MATERIAL AND
THICKNESS.
U
D A
S
1 2 3B-11 B-12 B-13
LAT
LC2
SCALE:
MAIN BUILDING BASEMENT ENLARGED ELECTRICAL DEMOLITION PLAN
1/4" = 1'-0"
SCALE:
MAIN BUILDING ATTIC ENLARGED ELECTRICAL DEMOLITION PLAN
1/4" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE DEMOLITION PLAN AND EXISTING CONDITIONS ARE
BASED ON THE BEST INFORMATION AT THE TIME OF
DESIGN AND MUST BE FIELD VERIFIED. EQUIPMENT AND
CIRCUITRY NOT EXPRESSLY LISTED FOR DEMOLITION
SHALL BE EXISTING-TO-REMAIN.
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
ENLARGED
ELECTRICAL DEMOLITION PLANS
ED401
1. DEMOLISH EXISTING CONNECTION TO BOILER (B-6).
THE BOILER IS FED FROM A 20/1 BREAKER IN LC2 AT
CIRCUIT #27. RETAIN AND REUSE RACEWAYS AND
CIRCUITRY TO EXTENT PRACTICAL.
2. DEMOLISH EXISTING CONNECTION TO BOILER (B-7).
THE BOILER IS FED FROM A BREAKER IN G-208N-PP3
AT CIRCUIT #11. RETAIN AND REUSE RACEWAYS AND
CIRCUITRY TO EXTENT PRACTICAL.
3. DEMOLISH EXISTING CONNECTION TO BOILER (B-8).
THE BOILER IS FED FROM A BREAKER IN G-208N-PP3
AT CIRCUIT #9. RETAIN AND REUSE RACEWAYS AND
CIRCUITRY TO EXTENT PRACTICAL.
4. DEMOLISH EXISTING CONNECTION TO PUMP (HWP 1-1).
RETAIN DISCONNECT. THE PUMP IS FED FROM BUCKET
1C IN G-208N-MCC1. RETAIN AND REUSE RACEWAYS
AND CIRCUITRY TO EXTENT PRACTICAL.
5. DEMOLISH EXISTING CONNECTION TO PUMP (HWP 1-2).
RETAIN DISCONNECT. THE PUMP IS FED FROM BUCKET
2B IN G-208N-MCC1. RETAIN AND REUSE RACEWAYS
AND CIRCUITRY TO EXTENT PRACTICAL.
6. DEMOLISH EXISTING CONNECTION TO INLINE HEATING
WATER PUMP 6-1. RETAIN DISCONNECT. PUMP 6-1 IS
FED FROM BUCKET 4B OF MSE-MCC-11. RETAIN AND
REUSE RACEWAYS AND CIRCUITRY TO EXTENT
PRACTICAL.
7. DEMOLISH EXISTING CONNECTION TO INLINE HEATING
WATER PUMP 6-2. RETAIN DISCONNECT. PUMP 6-2 IS
FED FROM BUCKET 4C OF MSE-MCC-11. RETAIN AND
REUSE RACEWAYS AND CIRCUITRY TO EXTENT
PRACTICAL.
8. DEMOLISH EXISTING CONNECTION TO BOILER PUMP
BP-6. BOILER PUMP BP-6 IS FED FROM A 30/3 BREAKER
IN PANEL LC2 AT CIRCUIT #26,28,30. RETAIN AND
REUSE RACEWAYS AND CIRCUITRY TO EXTENT
PRACTICAL.
9. DEMOLISH EXISTING CONNECTION TO BOILER PUMP
BP-7. RETAIN AND REUSE RACEWAYS AND CIRCUITRY
TO EXTENT PRACTICAL.
10. DEMOLISH EXISTING CONNECTION TO BOILER PUMP
BP-8. RETAIN AND REUSE RACEWAYS AND CIRCUITRY
TO EXTENT PRACTICAL.
MSE-MCC-11 (ETR)
U
D A
S
G-208N-MCC1 (ETR)
G-208N-PP3 (ETR)
HWP1-1 (15 HP)
5 HWP1-2 (15 HP)
RETAIN DISCONNECT AND MOTOR
STARTER FOR BP-6.
7HWP 6-1 (5 HP) & HWP 6-2 (5 HP)6 18BP-6 (1.5 HP) B-6
BP-7 (1.5 HP)
BP-8 (1.5 HP)
3B-8
B-7
E-000
ELECTRICAL LEGEND
ELECTRICAL LEGEND
1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" SHALL BE GROUND FAULT CIRCUIT INTERRUPTING
DEVICES.
3. DEVICES NOTED AS "WP" SHALL BE WEATHERPROOF WHILE-IN-USE.
4. DEVICES NOTED AS "DL" SHALL BE RATED FOR DAMP LOCATION.
5. DEVICES NOTED AS "NL" SHALL BE NIGHT LIGHTS. PROVIDE UNSWITCHED
POWER TO FIXTURE.
6. DEVICES NOTED AS "WG" SHALL BE PROVIDED AND INSTALLED WITH A WIRE
GUARD.
7. DEVICES NOTED AS "TR" SHALL BE TAMPER RESISTANT.
8. PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY PACKS.
9. "W/E" INDICATES DEVICE/DISCONNECT PROVIDED WITH THE EQUIPMENT BY
OTHERS.
LA-1
VOLTAGE DROP CHART FOR 20A, 1Ø CIRCUITS
FUSED DISCONNECT SWITCH.
NON-FUSED DISCONNECT SWITCH.
PANELBOARD.
FLEXIBLE CONNECTION TO EQUIPMENT.
MAGNETIC MOTOR STARTER.
COMBINATION FUSED DISCONNECT AND MAGNETIC MOTOR
STARTER.
COMBINATION CIRCUIT BREAKER AND MAGNETIC MOTOR STARTER.
GEAR
CONDUIT AND WIRINGGENERAL NOTES
MISCELLANEOUS
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING.
TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE
PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND
THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS
SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT
GROUNDING CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE,
THE MARKINGS TO THE LEFT SIGNIFY THAT THREE CONDUCTORS
PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE
PROVIDED.
CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR FLOOR.
TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE
PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND
THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS
SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT
GROUNDING CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS
TO THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN
EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED.
THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF THE
CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT. THE
ABSENCE OF TEXT SIGNIFIES THAT THE CONDUCTORS SHOULD BE
#12 AWG.
HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH CIRCUIT
NUMBER. DEVICES HAVING CIRCUIT NUMBERS LOCATED BESIDE
THEM MAY NOT SHOW THE CIRCUIT NUMBERS AT THE HOMERUN
ARROWS.
Voltage Circuit Length Conductor Size (AWG)
120 < 50' #12
120 > 50' #10
120 > 90' #8
120 > 140' #6
277 < 130' #12
277 > 130' #10
277 > 200' #8
277 > 330' #6
VOLTAGE DROP CHART NOTES:
1) CIRCUIT SIZES INDICATED ON THE DRAWINGS ARE MINIMUM
REQUIREMENTS. REFER TO THIS CHART FOR UPSIZING CONDUCTORS AS
NEEDED.
2) DO NOT CONNECT CONDUCTORS LARGER THAN #10 DIRECTLY TO A
RECEPTACLE OR A SWITCH. PROVIDE A JUNCTION BOX TO DOWNSIZE THE
CONDUCTOR TO #12 AT THE DEVICE.
3) FOR CIRCUITS LONGER THAN THOSE LISTED ABOVE, CONSULT WITH THE
ENGINEER FOR CONDUCTOR SIZES.
ENCLOSED CIRCUIT BREAKER.
U
D
S
TO
ILE
T
EL
EC
CL
OS
ET
DARK ROOM
DOOR
LAT
GYP GYP
LAT
LAT
LAT
LAT LAT
LAT LAT
LATLAT
GYP
LAT
LATLAT
LAT LAT
LATLAT
LATLAT
LAT LAT
LAT
LAT
NO CLG
LAT
LAT LAT
LATLAT
LAT
LAT LAT LAT LAT
LAT
LAT
NO CLG
NO CLGNO CLGNO CLGNO CLG
FI
RE
E
. NO CLG
NO CLG
NO CLG
LAT
NO CLG
NO CLG NO CLG
NO CLG
NO CLG
EL
EC
CL
OS
ET
GYP
LAT
LAT
LAT
NO CLG
LAT
LAT
NO CLG
NO CLG
GYP
GYP
MI. SP.
LAT
SCALE:
MAIN BUILDING BASEMENT OVERALL ELECTRICAL NEW WORK PLAN
1/16" = 1'-0"
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
E-101
MAIN BUILDING BASEMENT OVERALL
ELECTRICAL NEW WORK PLAN
U
D A
S
GENERAL NOTES
1. THE NEW ELECTRICAL PLAN IS BASED ON THE BEST
INFORMATION AVAILABLE AT THE TIME OF DESIGN. ALL
EXISTING-TO-REMAIN PIECES OF EQUIPMENT ARE
INTENDED TO BE FULLY FUNCTIONAL UPON
COMPLETION OF CONSTRUCTION WORK.
UP.
UP.
DN.
ELEVATOR
JANITOR'S CLOSET
CORRIDOR
STAIR A
STAIR B
DN
DN
UP
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF TOP OF ROOF TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
TOP OF ROOF
GREENHOUSE BAY #1
GREENHOUSE BAY #3
GREENHOUSE BAY #2
GREENHOUSE BAY #4
SCALE:
MAIN BUILDING ATTIC OVERALL ELECTRICAL NEW WORK PLAN
1/16" = 1'-0"
GRAPHIC SCALE
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
MAIN BUILDING ATTIC OVERALL
ELECTRICAL NEW WORK PLAN
E-102
U
D A
S
GENERAL NOTES
1. THE NEW ELECTRICAL PLAN IS BASED ON THE BEST
INFORMATION AVAILABLE AT THE TIME OF DESIGN. ALL
EXISTING-TO-REMAIN PIECES OF EQUIPMENT ARE
INTENDED TO BE FULLY FUNCTIONAL UPON
COMPLETION OF CONSTRUCTION WORK.
VFD FOR HWP-5 (ETR)
VFD FOR HWP-6 (ETR)
PUMP
BP-11
(1.5 HP)
PUMP
BP-12
(1.5 HP)
PUMP
BP-13
(1.5 HP)
P2 L2
SBE-MCC (ETR)
EQUIPMENT RACK (ETR)
ETRETR
5HWP-6 (25 HP)
HWP-5 (25 HP)
SCALE:
SERVICE BUILDING ELECTRICAL PLAN
3/16" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
SERVICE BUILDING ELECTRICAL
PLAN
E-103
1. PROVIDE NEW CONNECTION TO NEW BOILER B-11.
NEW BOILER (B-11) SHALL BE FED FROM A 20/1
BREAKER IN PANEL L2 AT CIRCUIT #18. EXTEND
CIRCUITRY AS REQUIRED USING 2#12, #12(G), 3/4" C.
FINAL CONNECTION SHALL BE FLEXIBLE METALLIC
CONDUIT.
2. PROVIDE NEW CONNECTION TO NEW BOILER (B-12).
NEW BOILER (B-12) SHALL BE FED FROM A 20/1
BREAKER IN PANEL L2 AT CIRCUIT #24. EXTEND
CIRCUITRY AS REQUIRED USING 2#12, #12(G), 3/4" C.
FINAL CONNECTION SHALL BE FLEXIBLE METALLIC
CONDUIT.
3. PROVIDE NEW CONNECTION TO NEW BOILER (B-13).
NEW BOILER (B-13) SHALL BE FED FROM A 20/1
BREAKER IN PANEL L2 AT CIRCUIT #16. EXTEND
CIRCUITRY AS REQUIRED USING 2#12, #12(G), 3/4" C.
FINAL CONNECTION SHALL BE FLEXIBLE METALLIC
CONDUIT.
4. PROVIDE A NEW FLEXIBLE CONNECTION FROM VFD TO
PUMP (HWP-5) WITH 3#6, #10(G), 1"C. VFD IS FED FROM
SBE-MCC-18.
5. PROVIDE A NEW FLEXIBLE CONNECTION FROM VFD TO
PUMP (HWP-6) WITH 3#6, #10(G), 1"C. VFD IS FED FROM
SBE-MCC-17.
6. PROVIDE ELECTRICAL CONNECTION FROM MOTOR
STARTERS TO THE THREE PUMPS (PUMP BP-11, PUMP
BP-12, AND PUMP BP-13). FINAL CONNECTION SHALL BE
FLEXIBLE METALLIC CONDUIT. NOTE: PROVIDE NEW
LABELS IN PANEL P2 FOR ALL THREE PUMPS WITH
APPROPRIATE NAMES.
1. THE NEW ELECTRICAL PLAN IS BASED ON THE BEST
INFORMATION AVAILABLE AT THE TIME OF DESIGN. ALL
EXISTING-TO-REMAIN PIECES OF EQUIPMENT ARE
INTENDED TO BE FULLY FUNCTIONAL UPON
COMPLETION OF CONSTRUCTION WORK.
2. USE LIQUID TIGHT FLEXIBLE METAL CONDUIT FOR FINAL
CONNECTIONS TO EQUIPMENT. FLEXIBLE CONNECTIONS
SHALL NOT EXCEED 3 FEET IN LENGTH.
U
D A
S
1 2 3B-11 B-12 B-13
LC2
LAT
SCALE:
MAIN BUILDING BASEMENT ENLARGED ELECTRICAL PLAN
1/4" = 1'-0"
SCALE:
MAIN BUILDING ATTIC ENLARGED ELECTRICAL PLAN
1/4" = 1'-0"
GENERAL NOTES
GRAPHIC SCALE
KEYED NOTESX
1. THE NEW ELECTRICAL PLAN IS BASED ON THE BEST
INFORMATION AVAILABLE AT THE TIME OF DESIGN. ALL
EXISTING-TO-REMAIN PIECES OF EQUIPMENT ARE
INTENDED TO BE FULLY FUNCTIONAL UPON
COMPLETION OF CONSTRUCTION WORK.
2. USE LIQUID TIGHT FLEXIBLE METAL CONDUIT FOR FINAL
CONNECTIONS TO EQUIPMENT. FLEXIBLE CONNECTIONS
SHALL NOT EXCEED 3 FEET IN LENGTH.
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
ENLARGED
ELECTRICAL PLANS
E-401
1. PROVIDE NEW ELECTRICAL CONNECTION TO NEW
BOILER B-6. B-6 SHALL BE FED FROM A 20/1 BREAKER
IN LC2 AT CIRCUIT #27. EXTEND CIRCUITRY AS
REQUIRED USING 2#12, #12(G), 3/4"C. FINAL
CONNECTION SHALL BE FLEXIBLE METALLIC CONDUIT.
2. PROVIDE NEW ELECTRICAL CONNECTION TO NEW
BOILER B-7. B-7 SHALL BE FED FROM A BREAKER IN
G-208N-PP3 AT CIRCUIT #11. EXTEND CIRCUITRY AS
REQUIRED USING 2#12, #12(G), 3/4"C. FINAL
CONNECTION SHALL BE FLEXIBLE METALLIC CONDUIT.
3. PROVIDE NEW ELECTRICAL CONNECTION TO NEW
BOILER B-8. B-8 SHALL BE FED FROM A BREAKER IN
G-208N-PP3 AT CIRCUIT #9. EXTEND CIRCUITRY AS
REQUIRED USING 2#12, #12(G), 3/4"C. FINAL
CONNECTION SHALL BE FLEXIBLE METALLIC CONDUIT.
4. PROVIDE ELECTRICAL CONNECTION FROM
DISCONNECT TO PUMP (HWP 1-1). HWP 1-1 SHALL BE
FED FROM BUCKET 1C IN G-208N-MCC1. USE 3#4, #8(G),
1-1/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
5. PROVIDE ELECTRICAL CONNECTION FROM
DISCONNECT TO PUMP (HWP 1-2). HWP 1-2 SHALL BE
FED FROM BUCKET 2B IN G-208N-MCC1. USE 3#4, #8(G),
1-1/4"C. FINAL CONNECTION SHALL BE FLEXIBLE
METALLIC CONDUIT.
6. PROVIDE ELECTRICAL CONNECTION FROM
DISCONNECT TO INLINE HEATING WATER PUMP #6-1.
PUMP #6-1 SHALL BE FED FROM BUCKET 4B OF
MSE-MCC-11. USE 3#10, #10(G), 3/4"C. FINAL
CONNECTION SHALL BE FLEXIBLE METALLIC CONDUIT.
7. PROVIDE ELECTRICAL CONNECTION FROM
DISCONNECT TO INLINE HEATING WATER PUMP #6-2.
PUMP #6-2 SHALL BE FED FROM BUCKET 4C OF
MSE-MCC-11. USE 3#10, #10(G), 3/4"C. FINAL
CONNECTION SHALL BE FLEXIBLE METALLIC CONDUIT.
8. PROVIDE ELECTRICAL CONNECTION TO BP-6. BOILER
PUMP BP-6 SHALL BE FED FROM A 30/3 BREAKER IN
PANEL LC2 AT CIRCUIT #26,28,30. EXTEND CIRCUITRY
AS REQUIRED USING 3#10, #10(G), 3/4"C. FINAL
CONNECTION SHALL BE FLEXIBLE METALLIC CONDUIT.
9. PROVIDE ELECTRICAL CONNECTION TO BP-7. EXTEND
CIRCUITRY AS REQUIRED USING 3#12, #12(G), 3/4"C.
FINAL CONNECTION SHALL BE FLEXIBLE METALLIC
CONDUIT.
10. PROVIDE ELECTRICAL CONNECTION TO BP-8. EXTEND
CIRCUITRY AS REQUIRED USING 3#12, #12(G), 3/4"C.
FINAL CONNECTION SHALL BE FLEXIBLE METALLIC
CONDUIT.
U
D A
S
4 HWP1-1 (15 HP)
5 HWP1-2 (15 HP)
G-208N-MCC1 (ETR)
G-208N-PP3 (ETR)
MSE-MCC-11 (ETR)
EXISTING DISCONNECT AND MOTOR
STARTER FOR BP-6.
HWP 6-1 (5 HP) & HWP 6-2 (5 HP)6
BP-7 (1.5 HP)
BP-8 (1.5 HP)
3B-8
B-7
BP-6 (1.5 HP) B-6
| WRRC Contract 1 General Binder |
| Sheets and Views |
| T-100-T100 |
| T-101-T101 |
| WRRC Contract 1 Mechanical Binder |
| Sheets and Views |
| M-001-M-001 |
| MD101-MD101 |
| MD102-MD102 |
| MD103-MD103 |
| MD401-MD401 |
| M-101-M-101 |
| M-102-M-102 |
| M-103-M-103 |
| M-401-M-401 |
| M-501-M-601 |
| M-601-M-601 |
| WRRC Contract 1 Electrical Binder |
| Sheets and Views |
| ED101 |
| ED102 |
| ED103 |
| ED401 |
| E-000 |
| E-101 |
| E-102 |
| E-103 |
| E-401 |
File details come from the government source that posted it. Updated .