B5584 HazMat Report.pdf

PDF 7 MB Posted

Attached to
Demolition Services At JBSA LAK/ LAK Chapman Annex
Solicitation number
FA301626R0033
Issued by

About this file

This is a Limited Hazardous Materials Survey Report for Building 5584 at JBSA–Lackland Air Force Base in San Antonio, Texas, prepared by TTL, Inc. for the 802 CES/CENME, Execution Support on February 25, 2026.

The survey was conducted on January 23, 2026, and encompassed four primary assessments: asbestos-containing materials (ACM), lead-based paint (LBP), hazardous components, and mold assessment. For the asbestos survey, TTL collected 30 bulk samples and identified asbestos at concentrations of 1% or greater in three material types: spray-on insulation above ceiling tiles (5% Chrysotile, approximately 800 square feet), window glazing on interior windows (2% Chrysotile, approximately 10 square feet), and window caulking on exterior windows (3% Chrysotile, approximately 10 square feet). For the lead-based paint assessment, ten paint chip samples were analyzed, with one sample—gray paint on metal (sample L-03)—exceeding the 0.5% lead concentration threshold at 2.358% by weight, covering approximately 20 square feet. The hazardous components survey identified approximately four ceiling-mounted fluorescent lamp ballasts without "No PCBs" labeling that require further investigation, pad-mounted transformers along Walker Avenue requiring PCB determination, and mercury-containing fluorescent tube bulbs requiring disposal as Universal Waste. The mold assessment revealed water damage on the interior east side attributable to roof leakage, elevated relative humidity at 99.9% (significantly above recommended levels of less than 65%), and bioaerosol samples showing elevated levels of Cladosporium, Aspergillus/Penicillium, and other fungal spores compared to outdoor baseline samples. TTL recommends that ACMs impacted by renovation or demolition be removed and disposed of in accordance with federal, state, and local regulations by TDSHS-licensed asbestos abatement contractors, that contractors be informed of LBP presence and comply with OSHA regulations, that mercury-containing bulbs be disposed of as Universal Waste, and that water intrusion and humidity issues be addressed to prevent further mold growth.

View the file

Other files

File Type Posted
jbsanantonio7_UAR_20240920.pdf PDF
B140 HazMat Report.pdf PDF
B7561 HazMatRprt.pdf PDF
B2988 HazMatRprt.pdf PDF
B7362 HazMat Report.pdf PDF
PWS CTO MultiFacDemo JBSA_LAK_19May_FINAL.docx DOCX document
Outage Request.pdf PDF
B4395 HazMatRprt.pdf PDF
Solicitation Amendment - FA301626R00330001.pdf PDF
Solicitation - FA301626R0033.pdf PDF
B2989 HazMatRprt.pdf PDF
WD-2015-5253 Rev 29.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Limited Hazardous Materials Survey

Building 5584 Walker Avenue & Gott Street

29º22’32.0”N, 98º37’11.6”W

JBSA – Lackland Air Force Base, Texas 78236

Prepared for:

802 CES/CENME, Execution Support

2250 Engineer Street - Building 4196

JBSA - Fort Sam Houston, Texas 78234

Prepared by:

TTL, Inc.

17215 Jones Maltsberger Road, Suite 101

San Antonio, Texas 78247

Project No. 26-09-00191.00

February 25, 2026

17215 Jones Maltsberger Rd., Ste. 101

San Antonio, TX 78247

210.888.6100 www. TTLUSA.com

Asbestos Consultant Agency No. 100550 ▪ Lead Firm No. 2110644 ▪ Mold Assessment Company No. ACO1228

February 25, 2026

Mr. Eraldo David Martinez

802 CES/CENME, Execution Support (JBSA - 802 CES/CENME, EXECUTION SUPPORT)

2250 Engineer Street, Building 4196

JBSA - Fort Sam Houston, Texas 78234

P: 210.295.4727

E: eraldo.martinez@us.af.mil

RE: Limited Hazardous Materials Survey Report

Walker Avenue & Gott Street (29º22’32.0”N, 98º37’11.6”W)

JBSA – Lackland Air Force Base, Texas 78236

TTL Project No. 26-09-00191.00

Dear Mr. Martinez, TTL, Inc. (TTL) is pleased to submit this Hazardous Materials Survey report for Building 5584 located on Walker Avenue & Gott Street (29º22’32.0”N, 98º37’11.6”W), JBSA – Lackland Air Force Base, Texas, herein referred to as the “Site”. It should be noted that that JBSA – Lackland Air Force Base is considered a National Standards for Hazardous Air Pollutants (NESHAP) facility due to limited access to buildings and badging requirements.

Scope of Services

TTL was retained to conduct an asbestos-containing materials (ACM) survey, lead-based paint (LBP) inspection, a hazardous components survey, and a mold assessment.

The purpose of this survey was to determine the presence, quantity, and condition of suspect ACM, LBP, hazardous components, and mold growth located at the Site. The field work for the hazardous materials survey was conducted on January 23, 2026.

Report

Laboratory results, sample location maps, and photographs are included in the appendices following the report. This report is divided into four (4) sections, which include ACM Survey, LPB Survey, Hazardous Components Survey, and a Mold Assessment. A photo log is provided in Appendix C.

Applicable licenses or certifications are provided in Appendix D.

Limitations

Observations and sampling performed during this site assessment are likely to be reasonable assessment of the conditions in the areas assessed at the Site. Environmental measurements within a building can vary from day to day and represent a snapshot on the day and time of the assessment.

This assessment did not include destructive sampling to check behind wallpaper, wall cavities or concealed areas for hazardous materials.

This report is intended for the sole use and benefit of JBSA - 802 CES/CENME, Execution Support and may not be relied upon by any other party without express permission of TTL.

TTL has no knowledge of any hidden or unapparent or adverse environmental conditions of the property, including the presence of hidden mold, hazardous wastes, toxic substances, etc. TTL makes http://www/

JBSA Lackland Air Force Base – Building 5584 – Hazardous Materials Survey February 25, 2026

TTL Project No. 26-09-00191.00 Page 2 of 15

© 2026, TTL, Inc. Passion | Purpose | Principles no guarantees or warranties, express or implied, regarding the condition of the property. This report is not an environmental assessment of the property.

This report and associated conclusions are based on the visible conditions of the inspected areas and materials. TTL reserves the right to revise opinions and conclusions if necessary and warranted by the discovery of new or additional circumstances. This report is specific and limited in nature and shall not be relied on as a statement that all Hazardous Materials have been identified and that more exist beyond the visibly accessible areas.

Closing

TTL appreciates the opportunity to provide environmental consulting services to JBSA - 802

CES/CENME, EXECUTION SUPPORT on this phase of the project. Should you have any questions, or require additional information regarding the Hazardous Materials Survey, please call us at your convenience.

Respectfully submitted, Nicolas Espino Osanna Carrasco

Project Professional Sr. Project Manager

TDSHS Lead Risk Assessor 2071258 TDSHS Lead Project Designer 2090091

TDLR Mold Assessment Consultant MAC1943 TDLR Mold Assessment Consultant MAC1587

TDSHS Asbestos Inspector 603646

TTL Project No. 26-09-00191.00 Page 3 of 14

TABLE OF CONTENTS

1.0 ASBESTOS-CONTAINING MATERIAL SURVEY

1.1 Sampling Methods

1.2 Laboratory Analysis

1.3 Findings

1.4 Asbestos Recommendations

2.0 LEAD BASED PAINT SURVEY

2.1 Sampling Methods

2.2 Paint Chip Sample Summary

2.4 Lead Recommendations

3.0 LIMITED HAZARDOUS COMPONENTS SURVEY

3.1 Purpose and Scope

3.2 Polychlorinated Biphenyls

3.3 Mercury

4.0 LIMITED MOLD ASSESSMENT

4.1 LIMITED MOLD ASSESSMENT METHODS

4.1.1 Building Materials Moisture Assessment

4.1.2 Indoor Air Parameters

4.1.3 Bioaerosol Samples

4.2 MOLD ASSESSMENT FINDINGS

4.2.1 Visual Observations and Building Materials Moisture Assessment

4.2.2 Indoor Air Parameters

4.2.2 Bioaerosol Sample Results

4.3 MOLD ASSESSMENT CONCLUSIONS

APPENDIX A: SAMPLE LOCATION MAPS

APPENDIX B: LABORATORY RESULTS

APPENDIX C: SITE PHOTOGRAPHS

APPENDIX D: LICENSES AND CERTIFICATIONS

TTL Project No. 26-09-00191.00 Page 4 of 14

1.0 ASBESTOS-CONTAINING MATERIAL SURVEY

The limited asbestos survey was conducted on January 23, 2026, by TDSHS-licensed Asbestos inspectors Deborah Salahuddin (license number 603987), and Nicolas Espino (license number

603646).

1.1 Sampling Methods

TTL performed the limited asbestos inspection survey in general accordance with Texas Department of State Health Services (TDSHS) Administrative Code Title 25, Part 1, Chapter 296, Texas Asbestos

Health Protection Rules (TAHPR), as well as the United States Environmental Protection Agency

(USEPA) National Standards for Hazardous Air Pollutants (NESHAP). Approximate quantities of suspect materials were estimated by field measurements. The condition (e.g., good, damaged, significantly damaged) and friability (i.e., easily crumbled, pulverized, or reduced to powder by hand pressure) of suspect ACM was noted for each material. The friability of each sampled material was determined by hand-touch.

• Surfacing materials, including spray-applied or troweled on wall/ceiling coatings,

• Thermal system insulation (TSI), including pipe insulation, duct insulation, boiler lagging and

• Miscellaneous materials, including ceiling panels/tiles, floor tiles and mastic, gaskets (if accessible), and wallboard/joint compound.

Suspected ACMs were grouped into homogeneous areas (i.e., a material that is uniform in texture, color, date of application, use or system, and appears identical in every other aspect). Homogeneous areas were determined by the TDSHS licensed Asbestos Inspector(s) based upon date of installation and uniformity or color and texture. Fiberglass, foam glass, rubber or wood products, plastic products, glass and steel were not sampled since they are not considered suspect ACM.

1.2 Laboratory Analysis

A total of thirty (30) bulk samples were collected from the selected areas of the interior and exterior of the building. Samples were deposited in secure containers for transport to the analytical laboratory.

Bulk suspect asbestos samples were submitted under secure chain of custody and were analyzed utilizing Polarized Light Microscopy (PLM), following the USEPA PLM Method EPA-600/R-93/116. The bulk samples were analyzed by Moody Labs (Moody), in Farmers Branch, Texas. Moody is accredited by the National Institute of Standards and Technology National Voluntary Laboratory Accreditation

Program (NVLAP No. 102056-0) and licensed by TDSHS (license number 300084).

A summary of TTL’s asbestos sampling, including analytical results, sample number, material descriptions, sample locations, material condition, friability and estimated quantities is provided in

Table 1 below.

TTL Project No. 26-09-00191.00 Page 5 of 14

TABLE 1: Asbestos Sample Results Summary

Building 5584

Walker Avenue & Gott Street

JBSA Lackland Air Force Base, Texas 78236

Sample

No.

Suspect Material Sample Location Asbestos %

Estimated

Quantities

Friability

(F/NF)

Condition

1-01, 02,03

1’ x 1’ Wall Tile with

Fissures

Interior – East

Wall, West Wall None Detected N/A F D

2-01, 02,03

1’ x 1’ Wall Tile with

Short Fissures Interior – East Wall None Detected N/A F D

3-01, 02,03

1’x1’ Wall Tile with

Deep Fissures

Interior – East

Wall, West Wall None Detected N/A F D

4-01, 02,03

2’ x 4’ Ceiling Tile with Dots and

Fissures

Interior – East, West, Center None Detected N/A F SD

5-01, 02,03 Spray on Insulation

Interior – East, Center 5% Chrysotile 800 SF F SD

6-01, 02,03

Black Paper

Insulation Backing Interior – West None Detected N/A NF SD

7-01, 02,03

CMU Grout and

Texture

Interior – East

Wall, West Wall None Detected N/A NF D

8-01, 02,03 Window Glazing

Interior – North

Window, South

Window

2% Chrysotile 10 SF NF SD

9-01, 02,03 Window Caulking

Exterior – North

Window, South

Window

3% Chrysotile 10 SF NF SD

10–01, 02, 03

Grout associated with

Brick

Exterior - North

Tunnel, South

Tunnel

None Detected N/A NF G

LEGEND

SF – Square Feet

G – Good F – Friable FT – Floor Tile

D – Damaged NF – Non-Friable M - Mastic

SD – Significantly Damaged N/A – Not Applicable TX – Texture

PACM – Presumed Asbestos-Containing Materials * – Positive for Asbestos JC – Joint Compound

VCT – Vinyl Composition Tile

1.3 Findings

The laboratory analytical results identified asbestos at 1% or greater in the following materials:

▪ Spray on insulation found above ceiling tile on walls and ceiling deck

▪ Window glazing found on interior windows

▪ Window caulking found on exterior windows

Site sample location map is provided in Appendix A. The laboratory report and chain of custody are provided in Appendix B.

1.4 Asbestos Recommendations

ACMs identified at the building that will be impacted by renovation or demolition should be removed and disposed of in accordance with federal, state, and local regulation, prior to disturbance. It is recommended that the asbestos abatement must be performed by a TDSHS licensed asbestos abatement contractor in accordance with a project design prepared by a TDSHS licensed asbestos consultant. In addition, third party air monitoring should be performed during the abatement. Prior to initiating an asbestos abatement project, written notification must be provided no later than 10 calendar days prior to starting abatement.

TTL Project No. 26-09-00191.00 Page 6 of 14

Contractors should use caution during construction related activities as concealed suspect ACM or other hazardous materials that were not previously analyzed may be encountered. If additional material, not previously sampled are later identified during construction related activities, then supplemental sample should be performed.

Materials that were noted as none-detected for asbestos may be disposed of as general construction debris.

TTL Project No. 26-09-00191.00 Page 7 of 14

2.0 LEAD BASED PAINT SURVEY

As part of the Hazardous Materials Survey, TTL representative Mr. Nicolas Espino, a Texas Department of State Health Services (TDSHS) certified Lead Risk Assessor (license number 2071258) conducted a lead-based paint (LBP) survey at the Site on January 23, 2026.

2.1 Sampling Methods

The LBP sampling was conducted in general accordance with sampling guidelines and methodologies documented in the U.S. Department of Housing and Urban Development (HUD) Guidelines for the

Evaluation and Control of Lead-Based Paint Hazards in Housing, Second Edition dated July 2012 and

EPA Lead: Requirements for Lead-Based Paint Activities in Target Housing and Child-Occupied

Facilities, dated August 1996. Paint chip sampling methods were utilized to complete this survey.

Lead-based paint (LBP) is defined as paint containing >1.0 milligrams per square centimeter (mg/cm2) as measured by >0.5% of lead by weight as analyzed by Atomic Absorption, for the purposes of renovation and/or demolition work. Occupational Safety and Health Administration (OSHA) defines

LBP as any paint containing detectable amounts of lead.

The scope of work required a visual inspection and sampling of all painted surfaces from the Site.

Paint chip samples were collected from painted areas throughout the Site.

2.2 Paint Chip Sample Summary

A total of ten (10) paint chip samples were collected from painted areas at the Site. The samples were submitted to SanAir Technologies Laboratory, North Chesterfield, Virginia. The samples were analyzed for total lead utilizing EPA Method SW846/M3050B/7000B. A summary of the samples collected, and analytical results are presented in Table 2.

TTL Project No. 26-09-00191.00 Page 8 of 14

Table 2: Lead Based Paint Sample Results

Walker Avenue

JBSA Lackland Air Force Base, Texas 78236

Sample ID Paint Color / Substrate Sample Location

Lead

Concentration % by Weight

Approximate

Quantity (SF)

L-01 Red Paint on Concrete Interior 0.168 N/A

L-02 Red Paint on Wood Interior 0.055 N/A

L-03 Gray Paint on Metal Interior 2.358 20 SF

L-04 White Paint on CMU Wall Interior 0.491 N/A

L-05 Gray Paint on Wood Interior 0.033 N/A

L-06 White Paint on Metal Door Interior 0.213 N/A

L-07 Brown Paint on Metal Door

Frame Exterior 0.158 N/A

L-08 Cream Paint on CMU Wall Exterior 0.011 N/A

L-09 Cream Paint on Metal Wall Exterior <0.010 N/A

L-10 Cream Paint on Concrete Exterior – Tunnel Vent

Stack

0.022 N/A

Laboratory analysis indicated that one (1) of the ten (10) samples collected from the Site indicated a concentration of lead of 0.5% concentration by weight or greater, as noted below:

• Gray paint on metal (L-03)

A Sample location map depicting all sampling locations is included in Appendix A. The laboratory results can be found in Appendix B.

2.4 Lead Recommendations

Contractor(s) should be made aware of the results for LBP. LBP that is in poor or deteriorated condition or that is disturbed during renovation by dry sanding, scraping, brushing, or burning can produce dust with lead, which can be inhaled or enter the body from hand-to-mouth contact.

Prior to performing renovation or demolition activities, the contractor should be made aware of the presence of LBP or potential LBP particularly in the areas of observed damaged paint to satisfy the hazard communication requirements set forth by OSHA regulations. Specifically, the contractors should be required to comply with OSHA regulations including 29 CFR 1926.62, Lead Exposure in

Construction: Interim Final Rule and 29 CFR 1926.59, Hazardous Communication for the Construction

Industry.

If any renovation, repair or demolition activity will disturb the LBP, engineering controls such as barriers and water should be used to minimize dust levels. The public should be prevented from unauthorized access to the work area. Ambient air monitoring is recommended to document engineering controls are adequate and that the ambient airborne concentrations do not exceed the permissible exposure levels.

TTL Project No. 26-09-00191.00 Page 9 of 14

3.0 LIMITED HAZARDOUS COMPONENTS SURVEY

As part of this Hazardous Materials Survey, a Limited Hazardous Components Survey was conducted at the Site on January 23, 2026.

3.1 Purpose and Scope

The purpose of the Hazardous Component Survey was to visually identify suspect hazardous components at the Site. This survey included identifying equipment that may contain Polychlorinated

Biphenyls (PCBs) or Mercury that may be handled during renovation. These components may be subject to special handling for recycling or waste disposal prior to demolition activities. A hazardous component location map can be found in Appendix E.

3.2 Polychlorinated Biphenyls

PCBs are a class of man-made organic chemicals manufactured and used from the late 1920s until

1979 when the EPA banned its manufacture. PCBs are stable, resistant to acids and bases, have thermal stability, and fire resistance properties. These special properties led to widespread use of

PCBs in industrial and commercial applications including electrical, heat transfer, hydraulic, and lighting equipment, caulks, paint, coatings, etc. The EPA regulates PCBs through several statutes, the most comprehensive of which is the Toxic Substances Control Act of 1976 codified in 40 CFR Part

761. This regulation governs the use, marking, storage, recording, and disposal of PCBs and PCB wastes. In Texas, PCB waste is regulated by the Texas Commission on Environmental Quality (TCEQ) through 30 Texas Administrative Code (TAC) Chapter 335.

Fluorescent Lamp Ballasts

Fluorescent Lamp Ballasts (FLBs) manufactured prior to July 1, 1979 may contain PBCs. FLB manufactured between July 1. 1978 and July 1, 1998 that do not contain PCBs must be labeled “No

PCBs”. If an FLB is not labeled "No PCBs", it is best to assume it contains PCBs unless it is known to be manufactured after 1979. FLBs manufactured after 1998 are not required to be labeled.

To inspect a light fixture for the presence of PCBs, parts of the fixture were temporarily removed to expose the ballast (if present) and identify a “no PCBs” label. A photograph was taken for every newly encountered ballast before the fixture was reassembled. Details regarding the styles of fluorescent light fixtures identified are provided below.

Approximately four (4) individual ceiling mounted FLBs were observed inside the building.

Approximately 10% of these fixtures were disassembled. The “No PCBs” label was not observed on the

FLBs. Additional investigation is required to determine the presence of PCBs in the dielectric fluids therein.

Electric Transformers

Dielectric fluids in electrical transformers may contain PCBs. Pad mounted transformers were observed along Walker Avenue to the east of the building. The labels did not indicate the presence or absence of PCBs – additional investigation is required to determine the presence of PCBs in the dielectric fluids therein.

3.3 Mercury

Mercury is found in thermostats, switches, thermometers, compact fluorescent bulbs and fluorescent and high-intensity discharge lamps.

All four (4) ballasts at the Site were equipped with two (2) mercury containing fluorescent tube bulbs.

They should be disposed of in accordance with applicable rules and regulations. All fluorescent bulbs must be disposed of as a Universal Waste at an EPA approved recycling facility prior to any renovation

/ demolition activities.

TTL Project No. 26-09-00191.00 Page 10 of 14

The building is conditioned with a wall mounted unit with a built-in thermostat. The thermostat is electric and does not contain mercury. All thermostats must be disposed as a Universal Waste at an

EPA approved recycling facility prior to any renovation / demolition activities.

TTL Project No. 26-09-00191.00 Page 11 of 14

4.0 LIMITED MOLD ASSESSMENT

As part of the Hazardous Materials Survey, On January 23, 2026, TTL representative Mr. Nicolas

Espino, a Texas Department of Licensing and Regulation (TDLR) licensed Mold Assessment Consultant

(MAC) completed a limited mold assessment and sampling of the Site area, which included the following.

4.1 LIMITED MOLD ASSESSMENT METHODS

TTL conducted a limited mold assessment in accordance with TDLR Texas Mold Assessors and

Remediators Administrative Rules (TMARR) as well as applicable portions of the Institute of Inspection, Cleaning and Restoration Certifications (IICRC) Standard and Reference Guide for Professional Water

Damage Restoration, Fourth Addition and the American Society for Testing and Materials (ASTM)

D7338-14 Standard Guide for Assessment of Fungal Growth in Buildings. The assessment included the following:

4.1.1 Building Materials Moisture Assessment

The relative moisture content (MC) of building materials potentially affected by moisture/water intrusion were measured by a moisture meter and or an infrared (IR) camera to identify temperature differentials that may be associated with wet building materials.

4.1.2 Indoor Air Parameters

TTL collected measurements of indoor relative humidity and temperature concentrations, as well as outdoors for comparison purposes utilizing a hand-held direct read instrument.

4.1.3 Bioaerosol Samples

Samples were collected in accordance with the American Council of Government Industrial Hygienist

(ACGIH) protocol outlined in “Bioaerosols: Assessment and Control”. Samples were collected by drawing air across an adhesive material within a “spore trap” cassette. Ambient air is drawn over the spore trap using a high-volume vacuum pump, calibrated to draw 15 liters of air per minutes, for five minutes.

4.2 MOLD ASSESSMENT FINDINGS

4.2.1 Visual Observations and Building Materials Moisture Assessment

Areas of suspect water damage were observed on the east side interior of the building. Water intrusion appears to originate from roof leakage.

Moisture meter readings were taken from the building materials at the Site indicated the materials were dry at the time of the assessment.

4.2.2 Indoor Air Parameters

The American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) Standard

62.1-2016, Ventilation for Acceptable Indoor Mold recommends an indoor temperature of 680

Fahrenheit (F) to 740F in the winter and 720F to 800F in the summer, and an indoor relative humidity

(RH) level of <65% to reduce the likelihood of conditions that can lead to microbial growth. Table 3, found below, lists the conditions observed during the assessment.

TTL Project No. 26-09-00191.00 Page 12 of 14

Table 3: Indoor Air Parameters

Building 5584

Walker Avenue

JBSA Lackland Air Force Base, Texas 78236

Area / Location Temperature 0F Relative Humidity (RH) %

Pre-Assessment – Exterior 64.5 99.9

Interior 65.3 99.9

The RH reading taken at the Site showed RH was significantly above normal range, which could be attributed to faulty seals on doors and windows in the building. The temperature throughout the building was below industry standards.

4.2.2 Bioaerosol Sample Results

One (1) indoor spore trap sample was collected from the Site, and one (1) outdoor sample for comparison. Samples were submitted under chain of custody to Moody Labs (Moody) located in

Farmers Branch, Texas. Moody is a TDLR license Mold Lab (LAB0117) and accredited by the American

Industrial Hygiene Association (AIHA) (102577). Summary of sample results can be found on the table below:

TTL Project No. 26-09-00191.00 Page 13 of 14

Table 4: Air Spore Sample Results – Samples collected on January 23, 2026

Building 5584

Walker Avenue

JBSA Lackland Air Force Base, Texas 78236

Sample ID. OS-01 ST-01

Sample Location Pre-Assessment Outdoor Interior

Identification Spores/m3 Spores/m3

Alternaria 213

Ascospores 400 413

Aspergillus / Penicillium 533 920

Basidiospores 600 293

Cercospora / Pseudocercospora 13

Chaetomium

Cladosporium 1280 3200

Coprinus group 13

Curvularia 27

Dreschslera/Bipolaris /Helminthosporum /

Exserohilum group

Epicoccum 27

Fusarium 13

Ganoderma 13

Hyphal / Spore Fragments - Dematiaceous 27 240

Hyphal / Spore Fragments - Hyaline

Myxomycete / Periconia / Rust / Smut 53 320

Nigrospora 67

Pithomyces 133

Stachybotrys

Stemphylium 40

Torula 13

Spores/m3 Total 2906 6025

Laboratory results indicated significantly higher levels of Cladosporium, Aspergillus / Penicillium, and

Myxomycete / Periconia / Rust / Smut in the interior of the building compared to the outdoor control sample. Alternaria, Cercospora / Pseudocercospora, Coprinus group, Curvularia, Dreschslera /

Bipolaris / Helminthosporum / Exserohilum group, Epicoccum, Ganoderma, Nigrospora, Pithomyces, Stemphylium, and Torula were found in the interior sample that were not found in the outdoor control sample.

A sample location map is found in Appendix A. The laboratory analysis results can be found in Appendix

B.

4.3 MOLD ASSESSMENT CONCLUSIONS

• Water damage was observed on the east interior of the building; The source of water damage appeared to be from roof leakages.

• The indoor spore trap sample showed Aspergillus / Penicillium, Cladosporium, Hyphal / Spore

Fragments – Dematiacious and Myxomycete / Periconia / Rust / Smut were significantly elevated compared to the outdoor comparison sample.

TTL Project No. 26-09-00191.00 Page 14 of 14

• Alternaria, Cercospora / Pseudocercospora, Coprinus group, Curvularia, Dreschslera /

Bipolaris /Helminthosporum/Exserohilum group, Epicoccum, Ganoderma, Nigrospora, Pithomyces, Stemphylium, and Torula were observed on the inside spore trap sample that that noted in the exterior sample.

• The relative humidity was significantly above the recommended levels and could be attributed to faulty seals on doors and windows in the building. It should be noted that relative humidity levels within the building were equal to those outside the building.

Appendices

APPENDIX A

SAMPLE LOCATION MAPS

OVERALL VIEW

17215 Jones Maltsberger Road San Antonio, TX 78247

210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622

Checked By:

Date:

Drawn By:

Scale:

Proj. No.:

File Name:

NOT TO SCALE

DS

NE

EXHIBIT

A-1

01/26/2026

26-09-00191.00

JBSA-LAK-5584.dwg

BU

IL

DI

N

G

JB

SA

LA

CK

LA

N D

AI

R

FO

RC

E

BA

SE

SA

N A

N

TO

N

IO

, T

EX

AS

AS

BE

ST

O

S

CO

N

TA

IN

IN

G M

AT

ER

IA

LS

SA

M

PL

E

LO

CA

TI

O

N S

LEGEND

NEGATIVE ASBESTOS CONTAINING

MATERIALS SAMPLE LOCATION

POSITIVE ASBESTOS CONTAINING

MATERIALS SAMPLE LOCATION

8-03

9-03

3-01,02

1-03

7-01,02

8-01,02

9-01,02

2-01,02

4-03

3-03

1-01

6-01,02

6-03

4-02

4-01

2-03

1-02

10-01,02,03

5-01,02

5-03

7-03

17215 Jones Maltsberger Road San Antonio, TX 78247

210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622

Checked By:

Date:

Drawn By:

Scale:

Proj. No.:

File Name:

NOT TO SCALE

DS

NE

EXHIBIT

A-2

01/26/2026

26-09-00191.00

LE

AD

B

AS

ED

P

AI

N

T

SU

RV

EY

SA

M

PL

E

LO

CA

TI

O

N S

LEGEND

<10 ug REPORTING LIMIT

FOR LEAD PAINT CHIP

SAMPLE LOCATION

<0.5% CONCENTRATION

BY WEIGHT LBP SAMPLE

LOCATION

>0.5% CONCENTRATION

BY WEIGHT LBP SAMPLE

LOCATION

L-04

L-09

L-05

L-08

L-01

L-02

L-03

L-06

L-07

L-10

JBSA-LAK-5584.dwg

BU

IL

DI

N

G

JB

SA

LA

CK

LA

N D

AI

R

FO

RC

E

BA

SE

SA

N A

N

TO

N

IO

, T

EX

AS

17215 Jones Maltsberger Road San Antonio, TX 78247

210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622

Checked By:

Date:

Drawn By:

Scale:

Proj. No.:

File Name:

NOT TO SCALE

DS

NE

EXHIBIT

A-3

01/26/2026

26-09-00191.00

HA

ZA

RD

O

U S

CO

M

PO

N

EN

TS

S U

RV

EY

LEGEND

POTENTIAL PCB LIGHTING BALLAST

WITH MERCURY TUBE BULBS

JBSA-LAK-5584.dwg

BU

IL

DI

N

G

JB

SA

LA

CK

LA

N D

AI

R

FO

RC

E

BA

SE

SA

N A

N

TO

N

IO

, T

EX

AS

17215 Jones Maltsberger Road San Antonio, TX 78247

210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622

Checked By:

Date:

Drawn By:

Scale:

Proj. No.:

File Name:

NOT TO SCALE

DS

NE

EXHIBIT

A-4

01/26/2026

26-09-00191.00

M O

LD

A

SS

ES

M

EN

T

SA

M

PL

E

LO

CA

TI

O N

S

SPORE TRAP SAMPLE LOCATION

LEGEND

OBSERVED WATER DAMAGE

ST-01

JBSA-LAK-5584.dwg

BU

IL

DI

N

G

JB

SA

LA

CK

LA

N D

AI

R

FO

RC

E

BA

SE

SA

N A

N

TO

N

IO

, T

EX

AS

APPENDIX B

LABORATORY RESULTS

PLM Summary Report

Client :

Project :

Project # :

Identification :

Test Method :

TTL - San Antonio

Building 5584, JBSA, Lackland AFB

26-09-00191.00

Asbestos, Bulk Sample Analysis

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 1/30/2026, thirty (30) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

26B-00999

01/23/2026

02/06/2026

NVLAP Lab Code 102056-0

TDSHS License No. 300084

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

1-01 1' x 1' Wall Tile (Fissures), Interior, East Wall, West Wall None Detected - Acoustic Tile

1-02 1' x 1' Wall Tile (Fissures), Interior, East Wall, West Wall None Detected - Acoustic Tile

1-03 1' x 1' Wall Tile (Fissures), Interior, East Wall, West Wall None Detected - Acoustic Tile

2-01 1' x 1' Wall Tile (Dots and Short Fissures), Interior, East

Wall

None Detected - Acoustic Tile

2-02 1' x 1' Wall Tile (Dots and Short Fissures), Interior, East

Wall

None Detected - Acoustic Tile

2-03 1' x 1' Wall Tile (Dots and Short Fissures), Interior, East

Wall

None Detected - Acoustic Tile

3-01 1' x 1' Wall Tile (Deep Fissures), Interior, East Wall, West

Wall

None Detected - Acoustic Tile

3-02 1' x 1' Wall Tile (Deep Fissures), Interior, East Wall, West

Wall

None Detected - Acoustic Tile

3-03 1' x 1' Wall Tile (Deep Fissures), Interior, East Wall, West

Wall

None Detected - Acoustic Tile

4-01 2' x 4' Ceiling Tile (Dots and Short Fissures), Interior, East, West, Center

None Detected - Acoustic Tile

4-02 2' x 4' Ceiling Tile (Dots and Short Fissures), Interior, East, West, Center

None Detected - Acoustic Tile

4-03 2' x 4' Ceiling Tile (Dots and Short Fissures), Interior, East, West, Center

None Detected - Acoustic Tile

5-01 Spray-on Insulation, Interior, East, Center 5% Chrysotile - Insulation

5-02 Spray-on Insulation, Interior, East, Center Not Analyzed - Positive Stop

5-03 Spray-on Insulation, Interior, East, Center Not Analyzed - Positive Stop

6-01 Paper Insulation Backing (Black), Interior, West None Detected - Tar Paper

6-02 Paper Insulation Backing (Black), Interior, West None Detected - Tar Paper

PLM Summary Report

Project :

Project # :

Identification :

Test Method :

TTL - San Antonio

Building 5584, JBSA, Lackland AFB

26-09-00191.00

Asbestos, Bulk Sample Analysis

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 1/30/2026, thirty (30) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

26B-00999

01/23/2026

02/06/2026

NVLAP Lab Code 102056-0

TDSHS License No. 300084

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

6-03 Paper Insulation Backing (Black), Interior, West None Detected - Tar Paper

7-01 CMU Grout and Texture, Interior, East Wall, West Wall None Detected - Grout

None Detected - Paint / Texture

7-02 CMU Grout and Texture, Interior, East Wall, West Wall None Detected - Grout

None Detected - Paint / Texture

7-03 CMU Grout and Texture, Interior, East Wall, West Wall None Detected - Grout

None Detected - Paint / Texture

8-01 Window Glazing, Interior, North Window, South Window 2% Chrysotile - Window Glazing

8-02 Window Glazing, Interior, North Window, South Window Not Analyzed - Positive Stop

8-03 Window Glazing, Interior, North Window, South Window Not Analyzed - Positive Stop

9-01 Window Caulking, Exterior, North Window South Window 3% Chrysotile - Caulking

9-02 Window Caulking, Exterior, North Window South Window Not Analyzed - Positive Stop

9-03 Window Caulking, Exterior, North Window South Window Not Analyzed - Positive Stop

10-01 Brick Grout, North Tunnel, South Tunnel None Detected - Grout

10-02 Brick Grout, North Tunnel, South Tunnel None Detected - Grout

10-03 Brick Grout, North Tunnel, South Tunnel None Detected - Grout

Willie PruittAnalyst(s):

Lab Director : Bruce Crabb Approved Signatory :

Thank you for choosing Moody Labs

Lab Manager : Heather Lopez Approved Signatory :

These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. The test report shall not be reproduced except in full without written approval of the laboratory. The results relate only to the items tested. These test results do not imply endorsement by NVLAP or any agency of the U.S.

Government. Accredited by the National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056-0.

PLM Detail Report

Project # : 26-09-00191.00

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report

Client :

Project :

TTL - San Antonio

Building 5584, JBSA, Lackland AFB

Lab Job No. :

Report Date :

26B-00999

02/06/2026

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Moody Labs NVLAP Lab Code 102056-0

TDSHS License No. 300084

Cellulose Fibers1-01 Acoustic Tile (Light Grey) 100% 02/0630% WP

Mineral Wool Fibers1-01 Acoustic Tile (Light Grey) 100% 02/0670% WP

Cellulose Fibers1-02 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers1-02 Acoustic Tile (Light Grey) 100% 02/0680% WP

Cellulose Fibers1-03 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers1-03 Acoustic Tile (Light Grey) 100% 02/0680% WP

Mineral Wool Fibers2-01 Acoustic Tile (Light Grey) 100% 02/0660% WP

Cellulose Fibers2-01 Acoustic Tile (Light Grey) 100% 02/0620% WP

Perlite2-01 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers2-02 Acoustic Tile (Light Grey) 100% 02/0650% WP

Cellulose Fibers2-02 Acoustic Tile (Light Grey) 100% 02/0630% WP

Perlite2-02 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers2-03 Acoustic Tile (Light Grey) 100% 02/0645% WP

Cellulose Fibers2-03 Acoustic Tile (Light Grey) 100% 02/0635% WP

Perlite2-03 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers3-01 Acoustic Tile (Light Grey) 100% 02/0650% WP

Cellulose Fibers3-01 Acoustic Tile (Light Grey) 100% 02/0630% WP

Perlite3-01 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers3-02 Acoustic Tile (Light Grey) 100% 02/0650% WP

Cellulose Fibers3-02 Acoustic Tile (Light Grey) 100% 02/0630% WP

Perlite3-02 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers3-03 Acoustic Tile (Light Grey) 100% 02/0650% WP

Cellulose Fibers3-03 Acoustic Tile (Light Grey) 100% 02/0630% WP

Perlite3-03 Acoustic Tile (Light Grey) 100% 02/0620% WP

Cellulose Fibers4-01 Acoustic Tile (Light Grey) 100% 02/0650% WP

Mineral Wool Fibers4-01 Acoustic Tile (Light Grey) 100% 02/0630% WP

Perlite4-01 Acoustic Tile (Light Grey) 100% 02/0620% WP

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report

Client :

Project :

TTL - San Antonio

Building 5584, JBSA, Lackland AFB

Lab Job No. :

Report Date :

26B-00999

02/06/2026

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Moody Labs NVLAP Lab Code 102056-0

TDSHS License No. 300084

Cellulose Fibers4-02 Acoustic Tile (Light Grey) 100% 02/0650% WP

Mineral Wool Fibers4-02 Acoustic Tile (Light Grey) 100% 02/0630% WP

Perlite4-02 Acoustic Tile (Light Grey) 100% 02/0620% WP

Mineral Wool Fibers4-03 Acoustic Tile (Light Grey) 100% 02/0645% WP

Cellulose Fibers4-03 Acoustic Tile (Light Grey) 100% 02/0635% WP

Perlite4-03 Acoustic Tile (Light Grey) 100% 02/0620% WP

Chrysotile5-01 Insulation (Light Tan) 100% 02/065% WP

Vermiculite5-01 Insulation (Light Tan) 100% 02/0640% WP

Binders / Fillers5-01 Insulation (Light Tan) 100% 02/0655% WP

5-02 Not Analyzed - Positive Stop 100% 02/06 WP

5-03 Not Analyzed - Positive Stop 100% 02/06 WP

Cellulose Fibers6-01 Tar Paper (Black) 100% 02/0690% WP

Tar Binders6-01 Tar Paper (Black) 100% 02/0610% WP

Cellulose Fibers6-02 Tar Paper (Black) 100% 02/0690% WP

Tar Binders6-02 Tar Paper (Black) 100% 02/0610% WP

Cellulose Fibers6-03 Tar Paper (Black) 100% 02/0690% WP

Tar Binders6-03 Tar Paper (Black) 100% 02/0610% WP

Aggregate7-01 Grout (Grey) 98% 02/0665% WP

Cement Binders7-01 Grout (Grey) 98% 02/0635% WP

Calcite7-01 Paint / Texture (Off White / Green) 2% 02/065% WP

Pigment / Binders7-01 Paint / Texture (Off White / Green) 2% 02/0695% WP

Aggregate7-02 Grout (Grey) 98% 02/0665% WP

Cement Binders7-02 Grout (Grey) 98% 02/0635% WP

Calcite7-02 Paint / Texture (Off White) 2% 02/065% WP

Pigment / Binders7-02 Paint / Texture (Off White) 2% 02/0695% WP

Aggregate7-03 Grout (Grey) 98% 02/0665% WP

Cement Binders7-03 Grout (Grey) 98% 02/0635% WP

Calcite7-03 Paint / Texture (Off White) 2% 02/065% WP

Pigment / Binders7-03 Paint / Texture (Off White) 2% 02/0695% WP

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report

Client :

Project :

TTL - San Antonio

Building 5584, JBSA, Lackland AFB

Lab Job No. :

Report Date :

26B-00999

02/06/2026

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Moody Labs NVLAP Lab Code 102056-0

TDSHS License No. 300084

Chrysotile8-01 Window Glazing (Off-White) 100% 02/062% WP

Calcite8-01 Window Glazing (Off-White) 100% 02/0658% WP

Binders / Fillers8-01 Window Glazing (Off-White) 100% 02/0640% WP

8-02 Not Analyzed - Positive Stop 100% 02/06 WP

8-03 Not Analyzed - Positive Stop 100% 02/06 WP

Chrysotile9-01 Caulking (Grey) 100% 02/063% WP

Calcite / Binders9-01 Caulking (Grey) 100% 02/0697% WP

9-02 Not Analyzed - Positive Stop 100% 02/06 WP

9-03 Not Analyzed - Positive Stop 100% 02/06 WP

Aggregate10-01 Grout (Grey) 100% 02/0660% WP

Cement Binders10-01 Grout (Grey) 100% 02/0635% WP

Calcite10-01 Grout (Grey) 100% 02/065% WP

Aggregate10-02 Grout (Grey) 100% 02/0660% WP

Cement Binders10-02 Grout (Grey) 100% 02/0635% WP

Calcite10-02 Grout (Grey) 100% 02/065% WP

Aggregate10-03 Grout (Grey) 100% 02/0660% WP

Cement Binders10-03 Grout (Grey) 100% 02/0635% WP

Calcite10-03 Grout (Grey) 100% 02/065% WP

SanAir ID#: 26005239

Project #: 26-09-00191.00 Project Name: JBSA-Lackland AFB-Building 5584 Report Date: 2/6/2026

Analysis Report prepared for

Dear Nicolas Espino, We at SanAir would like to thank you for the work you recently submitted. The 10 sample(s) were received on Friday, January 30, 2026 via FedEx. The final report(s) is enclosed for the following sample(s): L-01, L-02, L-03, L-04, L-05, L-06, L-07, L-08, L-09, L-10.

These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.

Sincerely, Abisola Kasali Metals Laboratory Director SanAir Technologies Laboratory

Final Report Includes:

- Cover Letter

- Chemistry Analysis

- Disclaimers and Additional Information

Sample conditions:

- 10 samples in Good condition.

10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com

26-09-00191.00Project Number:

P.O. Number:

Project Name: JBSA-Lackland AFB-Building 5584

1/23/2026Collected Date:

1/30/2026 11:30:00 AMReceived Date:

2/6/2026 9:44:36 AM

26005239 SanAir ID Number

FINAL REPORT

TTL, Inc.Name:

Address: 17215 Jones Maltsberger

San Antonio, TX 78247

210-888-6100Phone:

Analyst: Baird, Marti

Test Method: SW846/M3050B/7000B

Lead Paint Analysis PAINT µg Pb Sample Size Calculated Sample Sample

Sample Description In Sample (grams) RL Results Results

26005239 - 1 L-01 193 0.1148 87.1 1684 0.168 % Red Paint On Concrete / Interior µg/g (ppm) By Weight

26005239 - 2 L-02 63 0.1156 86.5 546.2 0.055 % Red Paint On Wood / Interior µg/g (ppm) By Weight

26005239 - 3 L-03 2829 0.12 83.3 23580 2.358 % Grey Paint On Metal / Interior µg/g (ppm) By Weight

26005239 - 4 L-04 526 0.1072 93.3 4905 0.491 % White Paint On CMU Wall / Interior µg/g (ppm) By Weight

26005239 - 5 L-05 36 0.1092 91.6 331.3 0.033 % Grey Paint On Wood / Interior µg/g (ppm) By Weight

26005239 - 6 L-06 254 0.119 84 2132 0.213 % White Paint On Metal Door / Interior µg/g (ppm) By Weight

26005239 - 7 L-07 173 0.1098 91.1 1576 0.158 % Brown Paint On Metal Door Frame / Exterior µg/g (ppm) By Weight

26005239 - 8 L-08 12 0.1128 88.7 105.4 0.011 % Cream Paint On CMU Wall / Exterior µg/g (ppm) By Weight

26005239 - 9 L-09 < 10.0 0.105 95.2 <95.2 <0.010 % Cream Paint On Metal / Exterior µg/g (ppm) By Weight

26005239 - 10 L-10 23 0.1056 94.7 222.2 0.022 % Cream Paint On Concrete / Tunnel Vent Stack µg/g (ppm) By Weight

Method Reporting Limit <10 µg/0.1 g paint

Signature:

Date: 2/4/2026 Date: 2/5/2026

Reviewed:

10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | LabReports@SanAir.com

26-09-00191.00Project Number:

P.O. Number:

Project Name: JBSA-Lackland AFB-Building 5584

1/23/2026Collected Date:

1/30/2026 11:30:00 AMReceived Date:

2/6/2026 9:44:36 AM

26005239 SanAir ID Number

FINAL REPORT

TTL, Inc.Name:

Address: 17215 Jones Maltsberger

San Antonio, TX 78247

210-888-6100Phone:

Disclaimer

This report is the sole property of the client account named on the chain-of-custody (COC) submitted to SanAir Technologies Laboratory, Inc. (SanAir). Results in the report are confidential information intended only for the use by the customer listed on the chain of custody. Neither results nor reports will be discussed with or released to any third party without our client’s written permission. Final reports cannot be reproduced, except in full, without written approval from SanAir to assure that parts of the report are not taken out of context. This report and any information contained within shall not be edited, altered, or modified in any way by any persons or agencies receiving, viewing, distributing, or otherwise possessing a copy of this final report. The laboratory reserves the right to perform amendments to any finalized report, of which shall supersede and make obsolete any previous editions. Such changes, modifications, additions, or deletions shall be effective immediately upon notice thereof, which may be given by means including but not limited to posting on the SanAir client portal website, electronic or conventional mail, or by any other means.

The information provided in this report applies only to the samples submitted and is relevant only for the date, time, and location of sampling. The accuracy of the results of the analysis is dependent upon the method of sample procurement and information provided by the client on the COC. SanAir is not responsible for the method of sample procurement. SanAir assumes no responsibility for information provided by the client on the COC such as project number, project name, collection dates, po number, special instructions, samples collected by, sample numbers, sample identifications, sample type, selected analysis type, flow rate, total volume or area, and start stop times that may affect the validity of the results in this report.

SanAir only assures the precision and accuracy of the data it generates and assumes no responsibility for errors or biasing that occur during collection prior to SanAir’s receipt of the sample(s). Evaluation reports are based solely on the sample(s) in the condition in which they are received at the laboratory and on the information provided by the client on the COC. Sample(s) were received in good condition unless otherwise noted on the report. All quality control results are acceptable unless otherwise noted. SanAir does not make contamination corrections to reports based upon analysis of laboratory and/or field blanks. When the client requires samples to be tested that deviate from a specific method or condition, all reported results may be affected by the deviation. SanAir assumes no responsibility or liability for the manner in which the results are used or interpreted. SanAir’s Method Detection Limits (MDL) and Reporting Limits (RL) have been derived using various materials meeting each accrediting agencies’ standards. All samples are disposed of after 60 days unless otherwise requested by the client. For Lead Exposure Limits, refer to HUD Guidelines for the Evaluation and Control of Lead-Based Paint Hazards and State and Federal Regulations, where applicable.

SanAir Technologies Laboratory, Inc. participates in the Environmental Lead Accreditation Program (ELAP) administered by AIHA LAP, LLC (Laboratory ID LAP-162952), and has met the EPA's NLLAP program standards. SanAir also participates in the State of New York’s DOH-ELAP program (NY Lab Id No. 11983) for lead in paint. This report does not constitute nor shall be used by the client to claim product, process, system, or person certification, approval, or endorsement by AIHA LAP, LLC, NELAC, NIST, and/or any other U.S. governmental agencies. All or some test results contained in this report may not be accredited by every local, state or federal regulatory agency. Refer to the SanAir website at www.sanair.com for copies of current certificates and scopes of various accreditations, certifications, and licenses or contact the laboratory for inquiries regarding the status or scope of an accreditation or certification.

AIHA LAP, LLC Lab ID: LAP-162952 New York State Department of Health Laboratory ID No: 11983 State of Connecticut Department of Public Health Environmental Laboratory Registration Number: PH-0105 Ohio Department of Health Environmental Lead Laboratory Approval Number E10049 State of Rhode Island Department of Health Environmental Lead Laboratory No LAO00371

Revision Date 3/24/2025

IAQ Mold Report

Project :

Project # :

TTL - San Antonio

JBSA, Lackland AFB, Building 5584

26-09-00191.00

Sample Number Sample Description Identification

Summary

Volume

(liters)

On 1/30/2026, two (2) samples were submitted by a representative of TTL - San Antonio (located at 17215 Jones Maltsberger, Suite 101, San Antonio, TX 78247) for Spore Trap, Non-cultured mold analysis. This report consists of three sections; a summary section, a data detail section, and an analytical notes section.

Sample Type:

Test Method: Page 1 of 2

Spore Trap, Non-cultured

Concentration spores/cubic meter

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

TDLR License No.: LAB0117

AIHA EMPAT ID: 102577

Mold: MLQ - 0112 - Standard Profile

Lab Job No. :

Report Date :

26F-00983

02/04/2026

Spore Trap Type: Zefon - Air-O-Cell

Sample Date: 01/23/2026

OS-01 75 Outdoor Pre-Assessment Cladosporium 44%1280

Basidiospores 21%600

Aspergillus / Penicillium 18%533

Ascospores 14%400

Myxomycete / Periconia / Rust / Smut 2%53

Hyphal / Spore Fragments -

Dematiaceous

<1%27

Fusarium <1%13

Total: 100%2906

ST-01 75 Interior

* See Analytical Notes report for further details

Cladosporium 53%3200

Aspergillus / Penicillium 15%920

Ascospores 7%413

Myxomycete / Periconia / Rust / Smut 5%320

Basidiospores 5%293

Hyphal / Spore Fragments -

Dematiaceous

4%240

Alternaria 4%213

Pithomyces 2%133

Drechslera / Bipolaris /

Helminthosporum / Exserohilum group

1%80

Nigrospora 1%67

Stemphylium <1%40

Curvularia <1%27

Epicoccum <1%27

Coprinus group <1%13

Ganoderma <1%13

Cercospora / Pseudocercospora <1%13

Torula <1%13

Total: 100%6025

Project :

Project # :

TTL - San Antonio

JBSA, Lackland AFB, Building 5584

26-09-00191.00

Sample Number Sample Description Identification

Summary

Volume

(liters)

On 1/30/2026, two (2) samples were submitted by a representative of TTL - San Antonio (located at 17215 Jones Maltsberger, Suite 101, San Antonio, TX 78247) for Spore Trap, Non-cultured mold analysis. This report consists of three sections; a summary section, a data detail section, and an analytical notes section.

Sample Type:

Test Method: Page 2 of 2

Spore Trap, Non-cultured

Concentration spores/cubic meter

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

TDLR License No.: LAB0117

AIHA EMPAT ID: 102577

Mold: MLQ - 0112 - Standard Profile

Lab Job No. :

Report Date :

26F-00983

02/04/2026

Spore Trap Type: Zefon - Air-O-Cell

Sample Date: 01/23/2026

Analyst(s): Julia Krause

Lab Director : Bruce Crabb Approved Signatory :

Thank you for choosing Moody Labs

Lab Director : Heather Lopez Approved Signatory :

SMLMS v14.06

This report shall not be reproduced except in full, without approval of the laboratory. Data contained in this test report relates only to the samples tested. This report does not express or imply interpretation of the results contained herein. Interpretation should be made by a qualified professional. Moody Labs assumes no responsibility for the manner in which these samples were collected or handled prior to being received at this laboratory. Volume, area, and/or weight is provided by the customer. Moody Labs assumes no responsibility for the qualifications of personnel performing sampling and/or interpretations of this data.

End of Summary section (26F-00983)

Project :

Project # :

TTL - San Antonio

JBSA, Lackland AFB, Building 5584

26-09-00191.00

Data Detail

Sample Type:

Test Method:

Spore Trap, Non-cultured

This report consists of three sections; a summary section, a data detail section, and an analytical notes section. Results may not be reported except in full.

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

TDLR License No.: LAB0117

AIHA EMPAT ID: 102577

Mold: MLQ - 0112 - Standard Profile

Lab Job No. :

Report Date :

26F-00983

02/04/2026

Spore Trap Type: Zefon - Air-O-Cell

Sample Date: 01/23/2026 Page 1 of 1

OS-01 ST-01Sample ID:

Outdoor Pre-Assessment InteriorLocation:

Oct 2026 Oct 2026Media Expires On:

See Analytical NotesNotes Included:

75 75Volume:

- - spores/m³ SF - - RL* - Raw Ct RL* Raw Ct %Total spores/m³ %Total spores/m³ SF spores/m³

- - - - - 13 - 16 Alternaria - - - - 4% 210 213

- - 400 - - 13 - 31 Ascospores 13 30 14% 400 7% 410 413

- - 530 - - 13 - 69 Aspergillus / Penicillium 13 40 18% 533 15% 920 920

- - 600 - - 13 - 22 Basidiospores 13 45 21% 600 5% 290 293

- - - - - 13 - 1 Cercospora / Pseudocercospora - - - - <1% 13 13

- - - - - - - - Chaetomium - - - - - - -

- - 1300 - - 27 - 120 Cladosporium 13 96 44% 1280 53% 3200 3200

- - - - - 13 - 1 Coprinus group - - - - <1% 13 13

- - - - - 13 - 2 Curvularia - - - - <1% 27 27

- - - - - 13 - 6 Drechslera / Bipolaris / Helminthosporum / - - - - 1% 80 80

- - - - - 13 - 2 Epicoccum - - - - <1% 27 27

- - 13 - - - - - Fusarium 13 1 <1% 13 - - -

- - - - - 13 - 1 Ganoderma - - - - <1% 13 13

- - 27 - - 13 - 18 Hyphal / Spore Fragments - Dematiaceous 13 2 <1% 27 4% 240 240

- - - - - - - - Hyphal / Spore Fragments - Hyaline - - - - - - -

- - 53 - - 13 - 24 Myxomycete / Periconia / Rust / Smut 13 4 2% 53 5% 320 320

- - - - - 13 - 5 Nigrospora - - - - 1% 67 67

- - - - - 13 - 10 Pithomyces - - - - 2% 130 133

- - - - - - - - Stachybotrys - - - - - - -

- - - - - 13 - 3 Stemphylium - - - - <1% 40 40

- - - - - 13 - 1 Torula - - - - <1% 13 13

- - 2900 - - - - 332 TOTALS - 218 100% 2906 100% 6000 6025

Julia Krause Julia KrauseAnalyst

2/4/2026 2/4/2026Analysis Date

1 3Debris Rating

Debris Composition

0/5 1/5 Fibers

1/5 3/5 Inorganic/Other

1/5 1/5 Insect Parts

0/5 1/5 Pollen

0/5 2/5 Skin/Dander

End of Data Detail section

26F-00983 SMLMS v14.06

Project :

Project # :

TTL - San Antonio

JBSA, Lackland AFB, Building 5584

26-09-00191.00

Analytical Notes

Sample Type:

Test Method: Mold: MLQ - 0112 - Standard Profile

Sample Date :

Spore Trap, Non-cultured

Lab Job No. :

Report Date :

26F-00983

02/04/2026

Spore Trap Type: Zefon - Air-O-Cell

This report consists of three sections; a summary section, a data detail section, and an analytical notes section. Results may not be reported except in full.

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

TDLR License No.: LAB0117

AIHA EMPAT ID: 102577

01/23/2026

NOTE: All remaining samples suitable for analysis.

Samples Analyzed

Please note: the minimum reporting limit for…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .