This is a Limited Hazardous Materials Survey Report for Building 140 at JBSA – Chapman Training Annex in San Antonio, Texas, dated February 27, 2026, prepared by TTL, Inc. for the 802 CES/CENME Execution Support division.
The survey encompasses four primary assessments: asbestos-containing materials (ACM), lead-based paint (LBP), hazardous components, and mold. For the ACM survey, 84 bulk samples were collected and analyzed using Polarized Light Microscopy. Results identified asbestos at 1% or greater in ten material types, including steam boiler insulation (10% Amosite, 10% Chrysotile), domestic hot water tank insulation (65% Chrysotile), steam line pipe wrap (20% Amosite), door sealants (2% Chrysotile), drywall joint compound and texture (2% Chrysotile), vinyl composition tile and mastic (3-5% Chrysotile), ceramic tile thinset (2% Chrysotile), exterior CMU sealant (2% Chrysotile), and window glazing (2% Chrysotile). Roof materials were presumed ACM due to inaccessibility. For the LBP survey, 23 paint chip samples were analyzed; six samples exceeded the 0.5% lead threshold, including cream ceiling paint (0.650%), blue metal railing paint (18.560%), yellow metal pipe paint (1.961%), green CMU wall paint (0.553%), brown wood door paint (2.151%), and brown metal railing paint (2.481%). The hazardous components survey identified approximately 64 fluorescent light ballasts with mercury-containing bulbs, electronic thermostats, 6 illuminated exit signs with lead-acid batteries, 8 emergency lighting systems with lead-acid batteries, and 54 halogen light fixtures. The mold assessment documented visible growth in multiple areas with higher indoor spore concentrations (10,981 spores/m³ in the Main Gym and 7,313 spores/m³ in the Southwest Room) compared to outdoor levels (3,133 spores/m³), attributed to roof leaks and inadequate HVAC conditioning. Recommendations include removal of identified ACM under NESHAP protocols by licensed contractors, proper disposal of lead-contaminated materials, and remediation of moisture sources causing mold growth.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B7362 HazMat Report.pdf | ||
| PWS CTO MultiFacDemo JBSA_LAK_19May_FINAL.docx | DOCX document | |
| jbsanantonio7_UAR_20240920.pdf | ||
| B7561 HazMatRprt.pdf | ||
| B2988 HazMatRprt.pdf | ||
| Outage Request.pdf | ||
| B4395 HazMatRprt.pdf | ||
| B5584 HazMat Report.pdf | ||
| Solicitation Amendment - FA301626R00330001.pdf | ||
| Solicitation - FA301626R0033.pdf | ||
| B2989 HazMatRprt.pdf | ||
| WD-2015-5253 Rev 29.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Limited Hazardous Materials Survey
Building 140 1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
Prepared for:
802 CES/CENME, Execution Support
2250 Engineer Street - Building 4196
JBSA - Fort Sam Houston, Texas 78234
Prepared by:
TTL, Inc.
17215 Jones Maltsberger Road, Suite 101
San Antonio, Texas 78247
Project No. 26-09-00191.00
February 27, 2026
17215 Jones Maltsberger Rd., Ste. 101
San Antonio, TX 78247
210.888.6100 www. TTLUSA.com
Asbestos Consultant Agency No. 100550 ▪ Lead Firm No. 2110644 ▪ Mold Assessment Company No. ACO1228
February 27, 2026
Mr. Eraldo David Martinez
802 CES/CENME, Execution Support (JBSA - 802 CES/CENME, EXECUTION SUPPORT)
2250 Engineer Street, Building 4196
JBSA - Fort Sam Houston, Texas 78234
P: 210.295.4727
E: eraldo.martinez@us.af.mil
RE: Limited Hazardous Materials Survey Report
1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
TTL Project No. 26-09-00191.00
Dear Mr. Martinez, TTL, Inc. (TTL) is pleased to submit this Hazardous Materials Survey report for Building 140 located at
1117 Eagle Drive, JBSA – Chapman Training Annex, Texas, herein referred to as the “Site”. It should be noted that that JBSA – Chapman Training Annex is considered a National Standards for Hazardous
Air Pollutants (NESHAP) facility due to limited access to buildings and badging requirements.
Scope of Services
TTL was retained to conduct an asbestos-containing materials (ACM) survey, lead-based paint (LBP) inspection, a hazardous components survey, and a mold assessment.
The purpose of this survey was to determine the presence, quantity, and condition of suspect ACM, LBP, hazardous components, and mold growth located at the Site. The field work for the hazardous materials survey was conducted on January 22, 2026.
Report
Laboratory results, sample location maps, and photographs are included in the appendices following the report. This report is divided into four (4) sections, which include ACM Survey, LPB Survey, Hazardous Components Survey, and a Mold Assessment. A photo log is provided in Appendix C.
Applicable licenses or certifications are provided in Appendix D.
Limitations
Observations and sampling performed during this site assessment are likely to be reasonable assessment of the conditions in the areas assessed at the Site. Environmental measurements within a building can vary from day to day and represent a snapshot on the day and time of the assessment.
This assessment did not include destructive sampling to check behind wallpaper, wall cavities or concealed areas for hazardous materials.
Roof access was not available in the building. Roofing materials could not be safely sampled for ACM with traditional extension ladders. Roofing materials should be assumed ACM
This report is intended for the sole use and benefit of JBSA - 802 CES/CENME, Execution Support and may not be relied upon by any other party without express permission of TTL.
http://www/
JBSA – Chapman Training Annex – Building 140 – Hazardous Materials Survey February 27, 2026
TTL Project No. 26-09-00191.00 Page 2 of 24
© 2026, TTL, Inc. Passion | Purpose | Principles
TTL has no knowledge of any hidden or unapparent or adverse environmental conditions of the property, including the presence of hidden mold, hazardous wastes, toxic substances, etc. TTL makes no guarantees or warranties, express or implied, regarding the condition of the property. This report is not an environmental assessment of the property.
This report and associated conclusions are based on the visible conditions of the inspected areas and materials. TTL reserves the right to revise opinions and conclusions if necessary and warranted by the discovery of new or additional circumstances. This report is specific and limited in nature and shall not be relied on as a statement that all Hazardous Materials have been identified and that more exist beyond the visibly accessible areas.
Closing
TTL appreciates the opportunity to provide environmental consulting services to JBSA - 802
CES/CENME, EXECUTION SUPPORT on this phase of the project. Should you have any questions, or require additional information regarding the Hazardous Materials Survey, please call us at your convenience.
Respectfully submitted, Nicolas Espino Osanna Carrasco
Project Professional Sr. Project Manager
TDSHS Lead Risk Assessor 2071258 TDSHS Lead Project Designer 2090091
TDLR Mold Assessment Consultant MAC1943 TDLR Mold Assessment Consultant MAC1587
TDSHS Asbestos Inspector 603646
TTL Project No. 26-09-00191.00 Page 3 of 16
TABLE OF CONTENTS
1.0 ASBESTOS-CONTAINING MATERIAL SURVEY
1.1 Sampling Methods
1.2 Laboratory Analysis
1.3 Findings
1.4 Asbestos Recommendations
2.0 LEAD BASED PAINT SURVEY
2.1 Sampling Methods
2.2 Paint Chip Sample Summary
2.4 Lead Recommendations
3.0 LIMITED HAZARDOUS COMPONENTS SURVEY
3.1 Purpose and Scope
3.2 Polychlorinated Biphenyls
3.3 Mercury
3.4 Additional Hazardous Components
4.0 LIMITED MOLD ASSESSMENT
4.1 LIMITED MOLD ASSESSMENT METHODS
4.1.1 Building Materials Moisture Assessment
4.1.2 Indoor Air Parameters
4.1.3 Bioaerosol Samples
4.1.4 Surface Samples
4.2 MOLD ASSESSMENT FINDINGS
4.2.1 Visual Observations and Building Materials Moisture Assessment
4.2.2 Indoor Air Parameters
4.2.2 Bioaerosol Sample Results
4.2.3 Surface Sample Results
4.3 MOLD ASSESSMENT CONCLUSIONS
APPENDIX A: SAMPLE LOCATION MAPS
APPENDIX B: LABORATORY RESULTS
APPENDIX C: SITE PHOTOGRAPHS
APPENDIX D: LICENSES AND CERTIFICATIONS
TTL Project No. 26-09-00191.00 Page 4 of 16
1.0 ASBESTOS-CONTAINING MATERIAL SURVEY
The limited asbestos survey was conducted on January 22, 2026, by Texas Department of State Health
Services (TDSHS)-licensed Asbestos inspectors Deborah Salahuddin (license number 603987), and
Nicolas Espino (license number 603646).
1.1 Sampling Methods
TTL performed the limited asbestos inspection survey in general accordance with TDSHS
Administrative Code Title 25, Part 1, Chapter 296, Texas Asbestos Health Protection Rules (TAHPR), as well as the United States Environmental Protection Agency (USEPA) National Standards for
Hazardous Air Pollutants (NESHAP). Approximate quantities of suspect materials were estimated by field measurements. The condition (e.g., good, damaged, significantly damaged) and friability (i.e., easily crumbled, pulverized, or reduced to powder by hand pressure) of suspect ACM was noted for each material. The friability of each sampled material was determined by hand-touch.
• Surfacing materials, including spray-applied or troweled on wall/ceiling coatings,
• Thermal system insulation (TSI), including pipe insulation, duct insulation, boiler lagging and
• Miscellaneous materials, including ceiling panels/tiles, floor tiles and mastic, gaskets (if accessible), and wallboard/joint compound.
Suspected ACMs were grouped into homogeneous areas (i.e., a material that is uniform in texture, color, date of application, use or system, and appears identical in every other aspect). Homogeneous areas were determined by the TDSHS licensed Asbestos Inspector(s) based upon date of installation and uniformity or color and texture. Fiberglass, foam glass, rubber or wood products, plastic products, glass and steel were not sampled since they are not considered suspect ACM.
1.2 Laboratory Analysis
A total of eighty-four (84) bulk samples were collected from the selected areas of the interior and exterior of the building. Samples were deposited in secure containers for transport to the analytical laboratory.
Bulk suspect asbestos samples were submitted under secure chain of custody and were analyzed utilizing Polarized Light Microscopy (PLM), following the USEPA PLM Method EPA-600/R-93/116. The bulk samples were analyzed by Moody Labs (Moody), in Farmers Branch, Texas. Moody is accredited by the National Institute of Standards and Technology National Voluntary Laboratory Accreditation
Program (NVLAP No. 102056-0) and licensed by TDSHS (license number 300084).
A summary of TTL’s asbestos sampling, including analytical results, sample number, material descriptions, sample locations, material condition, friability and estimated quantities is provided in
Table 1 below.
TTL Project No. 26-09-00191.00 Page 5 of 16
TABLE 1: Asbestos Sample Results Summary
Building 140
1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
Sample
No.
Suspect Material Sample Location Asbestos %
Estimated
Quantities
Friability
(F/NF)
Condition
1-01, 02,03
Steam Boiler
Insulation Boiler Room
10% Amosite
10% Chrysotile
50 SF F D
2-01, 02,03
Insulation on
Domestic Hot Water
Tank
Boiler Room 65% Chrysotile 50 SF F D
3-01, 02,03
Steam Line Pipe
Wrap / Insulation
Boiler Room, East
Restrooms 20% Amosite 250 LF F D
4-01, 02,03 Textured CMU
Boiler Room, Main
Gym, Southwest
Room
None Detected N/A F D
5-01, 02,03 Thin Door Sealant
Boiler Room &
Boiler Room Loft 2% Chrysotile 20 SF NF SD
6-01, 02,03 Thick Door Sealant Main Gym 2% Chrysotile 20 SF NF SD
7-01, 02,03 Drywall System
Southeast
Restrooms
JC: 2% Chrysotile
TX: 2% Chrysotile
900 SF NF SD
8-01, 02,03 12” x 12” Green VCT
South Hallway, East Entry None Detected N/A NF SD
9-01, 02,03
9” x 9” Dark Green
VCT & Black Mastic
East Entry, Southeast Room
FT: 5% Chrysotile
M: 3% Chrysotile
300 SF NF SD
10–01, 02, 03
Red Vinyl Flooring with Treads
South Hallway, East Entry None Detected N/A NF D
11-01, 02,03
Paper Backing and
Mastic
Beneath Wood
Flooring in Main
Gym
None Detected N/A NF D
12-01, 02,03
Black Cove Base /
Mastic Main Gym None Detected N/A NF D
13-01, 02,03
Brown 4” Cove Base
/ Mastic South Room None Detected N/A NF D
14-01, 02,03
Grey Cove Base /
Mastic East Entry None Detected N/A NF D
15-01, 02,03
2’ x 2’ Dot & Fissures
Ceiling Tile
South & Southwest
Rooms None Detected N/A F SD
16-01, 02,03
1’ x 1’ Pin Hole
Ceiling Tile
South & Southwest
Rooms None Detected N/A F SD
17-01, 02,03
Drywall Ceiling
System with Black
Paper Backing
South & Southwest
Rooms None Detected N/A F D
18-01, 02,03
Tan Mastic associated with
Mirror
Southwest Room None Detected N/A NF D
19-01, 02,03
1” Ceramic Floor tile, Grout, & Thin set
East and South
Restrooms None Detected N/A NF D
20–01, 02, 03
4” Ceramic Wall Tile, Grout, & Thin set South Restroom TS: 2% Chrysotile 1,000 SF NF D
21-01, 02,03
White Mastic on
HVAC
South Room None Detected N/A NF SD
22-01, 02,03 Carpet Mastic
Southeast Room, South Hallway None Detected N/A NF D
23-01, 02,03
Mastic below Rubber
Flooring South Room None Detected N/A NF D
TTL Project No. 26-09-00191.00 Page 6 of 16
TABLE 1: Asbestos Sample Results Summary
Building 140
1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
Sample
No.
Suspect Material Sample Location Asbestos %
Estimated
Quantities
Friability
(F/NF)
Condition
24-01, 02,03
Texture and Grout associated with Brick East Restrooms None Detected N/A NF D
25-01, 02,03
Exterior Tan Mastic on HVAC Exterior None Detected N/A NF SD
26-01, 02,03 Sealant on CMU Exterior 2% Chrysotile 50 SF NF D
27-01, 02,03
CMU Texture and
Grout Exterior None Detected N/A NF SD
28-01, 02,03 Window Glazing Exterior 2% Chrysotile 20 SF NF SD
LEGEND
SF – Square Feet
G – Good F – Friable FT – Floor Tile
D – Damaged NF – Non-Friable M - Mastic
SD – Significantly Damaged N/A – Not Applicable TX – Texture
PACM – Presumed Asbestos-Containing Materials * – Positive for Asbestos JC – Joint Compound
VCT – Vinyl Composition Tile
1.3 Findings
The laboratory analytical results identified asbestos at 1% or greater in the following materials:
▪ Steam boiler insulation found in boiler room.
▪ Dometic hot water pipe insulation found in boiler room.
▪ Steam line pipe wrap insulation found in boiler room and east restrooms.
▪ Thin sealant found on door in boiler room.
▪ Thick sealant found on door in main gym.
▪ Drywall system found in the southeast restrooms.
▪ 9” x 9” dark green VCT and black mastic found in east entry and southeast room.
▪ Thin set associated with 4” ceramic wall tile found in south restroom.
▪ Sealant on CMU found on the exterior of the building.
▪ Window glazing found on the exterior of the building.
Due to the lack of safe access to the roof, materials should be assumed to be ACM and removed under
NESHAP methods.
The site sample location map is provided in Appendix A. The laboratory report and chain of custody are provided in Appendix B.
1.4 Asbestos Recommendations
ACMs identified at the building that will be impacted by renovation or demolition should be removed and disposed of in accordance with federal, state, and local regulation, prior to disturbance. It is recommended that the asbestos abatement must be performed by a TDSHS licensed asbestos abatement contractor in accordance with a project design prepared by a TDSHS licensed asbestos consultant. In addition, third party air monitoring should be performed during the abatement. Prior to initiating an asbestos abatement project, written notification must be provided no later than 10 calendar days prior to starting abatement.
TTL Project No. 26-09-00191.00 Page 7 of 16
Contractors should use caution during construction related activities as concealed suspect ACM or other hazardous materials that were not previously analyzed may be encountered. If additional material, not previously sampled are later identified during construction related activities, then supplemental sample should be performed.
Materials that were noted as none-detected for asbestos may be disposed of as general construction debris.
TTL Project No. 26-09-00191.00 Page 8 of 16
2.0 LEAD BASED PAINT SURVEY
As part of the Hazardous Materials Survey, TTL representative Mr. Nicolas Espino, a Texas Department of State Health Services (TDSHS) certified Lead Risk Assessor (license number 2071258) conducted a lead-based paint (LBP) survey at the Site on January 22, 2026.
2.1 Sampling Methods
The LBP sampling was conducted in general accordance with sampling guidelines and methodologies documented in the U.S. Department of Housing and Urban Development (HUD) Guidelines for the
Evaluation and Control of Lead-Based Paint Hazards in Housing, Second Edition dated July 2012 and
EPA Lead: Requirements for Lead-Based Paint Activities in Target Housing and Child-Occupied
Facilities, dated August 1996. Paint chip sampling methods were utilized to complete this survey.
Lead-based paint (LBP) is defined as paint containing >1.0 milligrams per square centimeter (mg/cm2) as measured by >0.5% of lead by weight as analyzed by Atomic Absorption, for the purposes of renovation and/or demolition work. Occupational Safety and Health Administration (OSHA) defines
LBP as any paint containing detectable amounts of lead.
The scope of work required a visual inspection and sampling of all painted surfaces from the Site.
Paint chip samples were collected from painted areas throughout the Site.
2.2 Paint Chip Sample Summary
A total of twenty-three (23) paint chip samples were collected from painted areas at the Site. The samples were submitted to SanAir Technologies Laboratory, North Chesterfield, Virginia. The samples were analyzed for total lead utilizing EPA Method SW846/M3050B/7000B. A summary of the samples collected, and analytical results are presented in Table 2.
TTL Project No. 26-09-00191.00 Page 9 of 16
Table 2: Lead Based Paint Sample Results Building 140
1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
Sample ID Paint Color / Substrate Sample Location
Lead
Concentration % by Weight
Approximate
Quantity (SF)
L-01 Cream Paint on Metal
Ceiling Boiler Room Loft 0.650 1,000 SF
L-02 Blue Paint on Wood Door Boiler Room Loft 0.220 N/A
L-03 Blue Paint on Metal Railing Boiler Room Loft 18.560 20 SF
L-04 Yellow Paint on Metal Pipe Boiler Room 1.961 20 SF
L-05
Grey Paint on Domestic Hot
Water Tank Insulation
Cover
Boiler Room 0.165 N/A
L-06 Black Paint on Metal Boiler Boiler Room 0.262 N/A
L-07 Grey Paint on Metal
Domestic Hot Water Tank Boiler Room 0.153 N/A
L-08 Green Paint on CMU Wall Boiler Room 0.553 250 SF
L-09 Brown Paint on Concrete Exterior North Entrance 0.011 N/A
L-10 Brown Paint on Wood Door Exterior West Entrance 2.151 500 SF
L-11 White Paint on CMU Wall Exterior South <0.010 N/A
L-12 Brown Paint on Metal
Railing Exterior South Entrance 2.481 100 SF
L-13 Cream Paint on HVAC Duct
Insulation Exterior South <0.009 N/A
L-14 Cream Paint on Concrete
Wall Exterior South 0.057 N/A
L-15 White on Metal Downspout Exterior East 0.222 N/A
L-16 White Paint Layered Over
Brown on Concrete Wall Exterior <0.009 N/A
L-17 Red Paint on Metal Doors East Restroom 0.062 N/A
L-18 Black Paint on Metal Door
Frame West Restroom <0.009 N/A
L-19 Red Paint on CMU Wall Main Gym <0.009 N/A
L-20 Black Paint on CMU Wall Main Gym <0.009 N/A
L-21 Yellow Paint on CMU Wall Main Gym <0.009 N/A
L-22 White Paint on Drywall Southeast Restrooms <0.008 N/A
L-23 Green Paint on CMUE Wall Main Gym <0.009 N/A
Laboratory analysis indicated that six (6) of the twenty-three (23) samples collected from the Site indicated a concentration of lead of 0.5% concentration by weight or greater, as noted below:
• Cream Paint on Metal Ceiling (L-01)
• Blue Paint on Metal Railing (L-03)
• Yellow Paint on Metal Pipe (L-04)
• Green Paint on CMU wall (L-08)
• Brown Paint on Wood Door (L-10)
• Brown Paint on Metal Railing (L-12)
TTL Project No. 26-09-00191.00 Page 10 of 16
A sample location map depicting all sampling locations is included in Appendix A. The laboratory results can be found in Appendix B.
2.4 Lead Recommendations
Contractor(s) should be made aware of the results for LBP. LBP that is in poor or deteriorated condition or that is disturbed during renovation by dry sanding, scraping, brushing, or burning can produce dust with lead, which can be inhaled or enter the body from hand-to-mouth contact.
Prior to performing renovation or demolition activities, the contractor should be made aware of the presence of LBP or potential LBP particularly in the areas of observed damaged paint to satisfy the hazard communication requirements set forth by OSHA regulations. Specifically, the contractors should be required to comply with OSHA regulations including 29 CFR 1926.62, Lead Exposure in
Construction: Interim Final Rule and 29 CFR 1926.59, Hazardous Communication for the Construction
Industry.
If any renovation, repair or demolition activity will disturb the LBP, engineering controls such as barriers and water should be used to minimize dust levels. The public should be prevented from unauthorized access to the work area. Ambient air monitoring is recommended to document engineering controls are adequate and that the ambient airborne concentrations do not exceed the permissible exposure levels.
TTL Project No. 26-09-00191.00 Page 11 of 16
3.0 LIMITED HAZARDOUS COMPONENTS SURVEY
As part of this Hazardous Materials Survey, a Limited Hazardous Components Survey was conducted at the Site on January 22, 2026.
3.1 Purpose and Scope
The purpose of the Hazardous Component Survey was to visually identify suspect hazardous components at the Site. This survey included identifying equipment that may contain Polychlorinated
Biphenyls (PCBs) or Mercury that may be handled during renovation. These components may be subject to special handling for recycling or waste disposal prior to demolition activities. A hazardous component location map can be found in Appendix A.
3.2 Polychlorinated Biphenyls
PCBs are a class of man-made organic chemicals manufactured and used from the late 1920s until
1979 when the EPA banned its manufacture. PCBs are stable, resistant to acids and bases, have thermal stability, and fire resistance properties. These special properties led to widespread use of
PCBs in industrial and commercial applications including electrical, heat transfer, hydraulic, and lighting equipment, caulks, paint, coatings, etc. The EPA regulates PCBs through several statutes, the most comprehensive of which is the Toxic Substances Control Act of 1976 codified in 40 CFR Part
761. This regulation governs the use, marking, storage, recording, and disposal of PCBs and PCB waste. In Texas, PCB waste is regulated by the Texas Commission on Environmental Quality (TCEQ) through 30 Texas Administrative Code (TAC) Chapter 335.
Fluorescent Lamp Ballasts
Fluorescent Lamp Ballasts (FLBs) manufactured prior to July 1, 1979 may contain PBCs. FLB manufactured between July 1. 1978 and July 1, 1998 that do not contain PCBs must be labeled “No
PCBs”. If an FLB is not labeled "No PCBs", it is best to assume it contains PCBs unless it is known to be manufactured after 1979. FLBs manufactured after 1998 are not required to be labeled.
To inspect a light fixture for the presence of PCBs, parts of the fixture were temporarily removed to expose the ballast (if present) and identify a “no PCBs” label. A photograph was taken for every newly encountered ballast before the fixture was reassembled. Details regarding the styles of fluorescent light fixtures identified are provided below.
Approximately 64 individual ceiling mounted FLBs were observed throughout the building.
Approximately 10% of these fixtures were disassembled and the “No PCBs” label was observed.
Electric Transformers
Dielectric fluids in electrical transformers may contain PCBs. Pole mounted transformers were observed near the exterior on the east side of the building. The labels did not indicate the presence or absence of PCBs – additional investigation is required to determine the presence of PCBs in the dielectric fluids therein.
3.3 Mercury
Mercury is found in thermostats, switches, thermometers, compact fluorescent bulbs and fluorescent and high-intensity discharge lamps.
Approximately 64 of the ballasts at the Site were equipped with mercury containing fluorescent tube bulbs. 44 of these ballasts were equipped with “U” shaped mercury containing bulbs. 20 of the ballasts were equipped with two (2) mercury containing tube bulbs per ballast. They should be disposed of in accordance with applicable rules and regulations. All fluorescent bulbs must be disposed of as a
Universal Waste at an EPA approved recycling facility prior to any renovation / demolition activities.
TTL Project No. 26-09-00191.00 Page 12 of 16
All thermostats observed throughout the building were electric and do not contain mercury. All thermostats must be disposed as Universal Waste at an EPA approved recycling facility prior to any renovation / demolition activities.
3.4 Additional Hazardous Components
Approximately six (6) Illuminated exit signs and eight (8) emergency lighting systems were observed throughout the building. Approximately 10% of these fixtures were disassembled and they were found to contain Lead Acid back-up batteries. These batteries must be disposed of as Universal Waste at an
EPA approved recycling facility prior to any renovation / demolition activities.
Approximately fifty-four ceiling mounted lighting fixtures with Halogen bulbs were observed in the main gym and Squash Courts. These bulbs can be disposed of as regular waste.
TTL Project No. 26-09-00191.00 Page 13 of 16
4.0 LIMITED MOLD ASSESSMENT
As part of the Hazardous Materials Survey, On January 22, 2026, TTL representative Mr. Nicolas
Espino, a Texas Department of Licensing and Regulation (TDLR) licensed Mold Assessment Consultant
(MAC) completed a limited mold assessment and sampling of the Site area, which included the following.
4.1 LIMITED MOLD ASSESSMENT METHODS
TTL conducted a limited mold assessment in accordance with TDLR Texas Mold Assessors and
Remediators Administrative Rules (TMARR) as well as applicable portions of the Institute of Inspection, Cleaning and Restoration Certifications (IICRC) Standard and Reference Guide for Professional Water
Damage Restoration, Fourth Addition and the American Society for Testing and Materials (ASTM)
D7338-14 Standard Guide for Assessment of Fungal Growth in Buildings. The assessment included the following:
4.1.1 Building Materials Moisture Assessment
The relative moisture content (MC) of building materials potentially affected by moisture/water intrusion were measured by a moisture meter and or an infrared (IR) camera to identify temperature differentials that may be associated with wet building materials.
4.1.2 Indoor Air Parameters
TTL collected measurements of indoor relative humidity and temperature concentrations, as well as outdoors for comparison purposes utilizing a hand-held direct read instrument.
4.1.3 Bioaerosol Samples
Samples were collected in accordance with the American Council of Government Industrial Hygienist
(ACGIH) protocol outlined in “Bioaerosols: Assessment and Control”. Samples were collected by drawing air across an adhesive material within a “spore trap” cassette. Ambient air is drawn over the spore trap using a high-volume vacuum pump, calibrated to draw 15 liters of air per minute, for five minutes.
4.1.4 Surface Samples
Surface samples were collected via Tape Lift method from the surface of the select areas/materials with signs of suspect visible mold growth (SVMG) using clear adhesive tape. One side of the tape is pressed against an environmental surface to gather a representative sample of transient materials, such as mold spores
4.2 MOLD ASSESSMENT FINDINGS
4.2.1 Visual Observations and Building Materials Moisture Assessment
Visible mold growth was observed on the ceiling tiles in the south room, the wall and ceiling of the southwest room, in the southeast Men’s restroom, and the walls of the east restrooms. Water damage was observed in the locker room and on the wood in the southwest room and the east restrooms.
Moisture meter readings were taken from the building materials at the Site indicated the materials were dry at the time of the assessment.
4.2.2 Indoor Air Parameters
The American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) Standard
62.1-2016, Ventilation for Acceptable Indoor Mold recommends an indoor temperature of 680
Fahrenheit (F) to 740F in the winter and 720F to 800F in the summer, and an indoor relative humidity
(RH) level of <65% to reduce the likelihood of conditions that can lead to microbial growth. Table 3, found below, lists the conditions observed during the assessment.
TTL Project No. 26-09-00191.00 Page 14 of 16
Table 3: Indoor Air Parameters
1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
Area / Location Temperature 0F Relative Humidity (RH) %
Main Gym 66.5 51.7
Southwest Room 66.5 59.9
Pre-Assessment – Exterior 73.5 45.9
The RH readings taken throughout the Site showed RH were within normal range. The temperature throughout the building was slightly below industry standards.
4.2.2 Bioaerosol Sample Results
Two (2) indoor spore trap samples were collected from the Site, and one (1) outdoor sample for comparison. Samples were submitted under chain of custody to Moody Labs (Moody) located in
Farmers Branch, Texas. Moody is a TDLR license Mold Lab (LAB0117) and accredited by the American
Industrial Hygiene Association (AIHA) (102577). Summary of sample results can be found on the table below:
TTL Project No. 26-09-00191.00 Page 15 of 16
Table 4: Air Spore Sample Results
Building 140
1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
Sample ID. OS-01 ST-01 ST-02
Sample Location Pre-Assessment
Outdoor Main Gym
Southwest
Room
Identification Spores/m3 Spores/m3 Spores/m3
Alternaria 67 253 267
Arthrinium 13
Ascospores 360 347 480
Aspergillus / Penicillium 893 2675 1013
Basidiospores 240 840 307
Cercospora / Pseudocercospora 53
Cladosporium 893 4320 3633
Coprinus group 213 227
Curvularia 27 27
Diatrypaceae 107 107
Dreschslera/Bipolaris /Helminthosporum / Exserohilum group 253 80
Fusarium 13 27
Ganoderma 120 53
Hyphal / Spore Fragments - Dematiaceous 160 853 413
Hyphal / Spore Fragments - Hyaline 80 13
Myxomycete / Periconia / Rust / Smut 120 613 507
Nigrospora 93 160 133
Paecilomyces 187
Pithomyces 67 53
Stachybotrys 27
Stemphylium 13
Torula 27
Spores/m3 Total 3133 10981 7313
Laboratory results indicated higher levels of mold spores in the indoor samples of of the building compared to the outdoor control sample.
A sample location map is found in Appendix A. Laboratory analysis results can be found in Appendix
B.
4.2.3 Surface Sample Results
During the mold assessments, one (1) tape lift surface sample was collected from the drywall in
Men’s Southeast Restroom where suspect microbial growth was observed.
Clear tape was applied to the surface of suspect microbial growth. The sample was submitted under chain of custody to Moody Labs (Moody) located in Farmers Branch, Texas. Moody is a
TDLR license Mold Lab (LAB0117) and accredited by the American Industrial Hygiene
Association (AIHA) (102577).
TTL Project No. 26-09-00191.00 Page 16 of 16
Sample locations can be found in the sample location map in Appendix A. The laboratory analysis for surface tape sample collected during the mold assessment is presented in the table below and the analytical results are provided in Appendix B.
Table 5: Surface Tape Sample Results
Building 140
1117 Eagle Drive
JBSA – Chapman Training Annex, Texas 78245
Sample
No Location/Surface Spore Identification
Prevalence of Mold
T-01 Drywall Surface / Men’s Southeast
Restroom Cladosporium Moderate
Laboratory results indicated moderate levels of mold spores from the tape sample on the surface where the sample was collected.
4.3 MOLD ASSESSMENT CONCLUSIONS
• The indoor spore trap samples of the building indicated higher levels of total mold spores compared to the outdoor comparison sample.
• Tape sample results indicated moderate levels of mold spores from the tape samples which confirm the presence of mold growth on the drywall in the southeast Men’s restroom where the sample was collected.
• The mold growth is likely due to roof leaks coupled with the lack of HVAC conditioning in the building.
• The temperature of the building was slightly below industry standards.
Appendices
APPENDIX A
SAMPLE LOCATION MAPS
17215 Jones Maltsberger Road
210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622
Checked By:
Date:
Drawn By:
Scale:
Proj. No.:
File Name:
NOT TO SCALE
DS
NE
EXHIBIT
A-1
01/26/2026
26-09-00191.00
JBSA-Chapman-140.dwg
BU
IL
DI
N
G
E
AG
LE
D
RI
VE
JB
SA
CH
AP
M
AN
T
RA
IN
IN
G A
N N
EX
SA
N A
N
TO
N
IO
, T
EX
AS
AS
BE
ST
O
S
CO
N
TA
IN
IN
G M
AT
ER
IA
LS
SA
M
PL
E
LO
CA
TI
O
N S
LEGEND
NEGATIVE ASBESTOS CONTAINING
MATERIALS SAMPLE LOCATION
POSITIVE ASBESTOS CONTAINING
MATERIALS SAMPLE LOCATION
4-01
5-02,03
5-01 2-01
2-03
2-02
3-01,02,03
27-0328-03
27-02
28-02
11-01
11-02,03
12-01
14-01,02,03 8-01,02
9-01
4-02
10-01
22-01
7-03
7-017-02
10-02 8-03
12-03
13-01
17-01 17-02
16-02
15-02
13-02
12-0210-03
4-03
15-03 17-03
16-03
18-01,02,03 13-03
16-01
15-01 23-01,02,03
1-01,02,03 6-01,02,03
9-02,03
21-01,02,03
22-02, 03
19-01, 02
19-03
24-01,02,03
25-01,02,03 26-01,02
26-03
28-0127-01
20-01,02
20-03
17215 Jones Maltsberger Road
210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622
Checked By:
Date:
Drawn By:
Scale:
Proj. No.:
File Name:
NOT TO SCALE
DS
NE
EXHIBIT
A-2
01/26/2026
26-09-00191.00
LE
AD
B
AS
ED
P
AI
N
T
SU
RV
EY
SA
M
PL
E
LO
CA
TI
O
N S
LEGEND
<10 ug REPORTING LIMIT
FOR LEAD PAINT CHIP
SAMPLE LOCATION
<0.5% CONCENTRATION
BY WEIGHT LBP SAMPLE
LOCATION
>0.5% CONCENTRATION
BY WEIGHT LBP SAMPLE
LOCATION
L-08
L-06
L-05 L-07
L-04L-01
L-17
L-16
L-15 L-14
L-12L-13L-11
L-18 L-10
L-20 L-19
L-23 L-21
L-09
L-22
L-02 L-03
JBSA-Chapman-140.dwg
BU
IL
DI
N
G
E
AG
LE
D
RI
VE
JB
SA
CH
AP
M
AN
T
RA
IN
IN
G A
N N
EX
SA
N A
N
TO
N
IO
, T
EX
AS
Checked By:
Date:
Drawn By:
Scale:
Proj. No.:
File Name:
DS
NE
EXHIBIT
17215 Jones Maltsberger Road San Antonio, TX 78247
210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622
Checked By:
Date:
Drawn By:
Scale:
Proj. No.:
File Name:
NOT TO SCALE
EXHIBIT
1/30/2026
26-09-00191.00
A-3
HA
ZA
RD
O
U S
CO
M
PO
N
EN
TS
S U
RV
EY
LEGEND
JBSA-Chapman-140.dwg
BU
IL
DI
N
G
E
AG
LE
D
RI
VE
JB
SA
CH
AP
M
AN
T
RA
IN
IN
G A
N N
EX
SA
N A
N
TO
N
IO
, T
EX
AS
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
ET
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
LIGHTING WITH HALOGEN BULBSH
EMERGENCY FLOOD LIGHTS WITH LEAD
ACID BATTERYLF
L F
L F
LF
L F
L F
L F
U NON-PCB LIGHTING BALLAST AND "U"
SHAPED MERCURY CONTAINING BULB
U
U
U
U
U
U U
U
U
U
U
U
U
U
U
U
U
U
U U
U U
U U
U U
U
NON-PCB LIGHTING BALLAST WITH TWO (2)
MERCURY CONTAINING BULBS
LF
U
U
U
U
U
U
U
U
U
U
U
U
UU
U
L F
U U
ILLUMINATED EXIT SIGN WITH LEAD ACID
BATTERYEXIT
ET ELECTRONIC THERMOSTAT
Checked By:
Date:
Drawn By:
Scale:
Proj. No.:
File Name:
DS
NE
EXHIBIT
17215 Jones Maltsberger Road San Antonio, TX 78247
210.888.6100 | www.ttlusa.com TBPE Firm Registration F-12622
Checked By:
Date:
Drawn By:
Scale:
Proj. No.:
File Name:
NOT TO SCALE
EXHIBIT
1/30/2026
26-09-00191.00
A-4
M O
LD
A
SS
ES
M
EN
T
SA
M
PL
E
LO
CA
TI
O N
M
AP
SPORE TRAP SAMPLE LOCATION
LEGEND
SURFACE TAPE SAMPLE LOCATION
T-01
ST-01
ST-02
WATER DAMAGE LOCATIONS
VISIBLE MOLD GROWTH ON WALLS
JBSA-Chapman-140.dwg
BU
IL
DI
N
G
E
AG
LE
D
RI
VE
JB
SA
CH
AP
M
AN
T
RA
IN
IN
G A
N N
EX
SA
N A
N
TO
N
IO
, T
EX
AS
Appendices
APPENDIX B
LABORATORY RESULTS
PLM Summary Report
Client :
Project :
Project # :
Identification :
Test Method :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
26-09-00191.00
Asbestos, Bulk Sample Analysis
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/30/2026, eighty four (84) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The
PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Lab Job No. :
Report Date :
26B-00995
01/22/2026
02/09/2026
NVLAP Lab Code 102056-0
TDSHS License No. 300084
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
01-01 Steam Boiler Insulation, Boiler Room 10% Amosite - Thermal Insulation
10% Chrysotile - Thermal Insulation
01-02 Steam Boiler Insulation, Boiler Room Not Analyzed - Positive Stop
01-03 Steam Boiler Insulation, Boiler Room Not Analyzed - Positive Stop
02-01 Domestic Hot Water Tank Insulation, Boiler Room 65% Chrysotile - Thermal Insulation
02-02 Domestic Hot Water Tank Insulation, Boiler Room Not Analyzed - Positive Stop
02-03 Domestic Hot Water Tank Insulation, Boiler Room Not Analyzed - Positive Stop
03-01 Steam Line Pipe Wrap, Boiler Room, East Restrooms 20% Amosite - Thermal Insulation
03-02 Steam Line Pipe Wrap, Boiler Room, East Restrooms Not Analyzed - Positive Stop
03-03 Steam Line Pipe Wrap, Boiler Room, East Restrooms Not Analyzed - Positive Stop
04-01 CMU Texture, Boiler Room, Main Gym, Southwest Room None Detected - CMU
None Detected - Paint / Texture
04-02 CMU Texture, Boiler Room, Main Gym, Southwest Room None Detected - CMU
None Detected - Paint / Texture
04-03 CMU Texture, Boiler Room, Main Gym, Southwest Room None Detected - CMU
None Detected - Paint / Texture
05-01 Door Sealant Thin, Boiler Room and Boiler Room Loft 2% Chrysotile - Sealant
05-02 Door Sealant Thin, Boiler Room and Boiler Room Loft Not Analyzed - Positive Stop
05-03 Door Sealant Thin, Boiler Room and Boiler Room Loft Not Analyzed - Positive Stop
06-01 Door Sealant Thick, Main Gym 2% Chrysotile - Sealant
06-02 Door Sealant Thick, Main Gym Not Analyzed - Positive Stop
06-03 Door Sealant Thick, Main Gym Not Analyzed - Positive Stop
Project :
Project # :
Identification :
Test Method :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
26-09-00191.00
Asbestos, Bulk Sample Analysis
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/30/2026, eighty four (84) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The
PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Lab Job No. :
Report Date :
26B-00995
01/22/2026
02/09/2026
NVLAP Lab Code 102056-0
TDSHS License No. 300084
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
07-01 Drywall System, Southeast Restrooms None Detected - Drywall Material
2% Chrysotile - Joint Compound
2% Chrysotile - Texture
07-02 Drywall System, Southeast Restrooms Not Analyzed - Positive Stop
07-03 Drywall System, Southeast Restrooms Not Analyzed - Positive Stop
08-01 12" x 12" Vinyl Composition Tile (Green), South Hallway, East Entry
None Detected - Yellow Mastic
None Detected - Floor Tile
None Detected - Yellow Mastic
08-02 12" x 12" Vinyl Composition Tile (Green), South Hallway, East Entry
None Detected - Yellow Mastic
None Detected - Floor Tile
None Detected - Yellow Mastic
08-03 12" x 12" Vinyl Composition Tile (Green), South Hallway, East Entry
None Detected - Yellow Mastic
None Detected - Floor Tile
None Detected - Yellow Mastic
09-01 9" x 9" Vinyl Composition Tile (Dark Green), East Entry, Southeast Room
5% Chrysotile - Floor Tile
3% Chrysotile - Black Mastic
09-02 9" x 9" Vinyl Composition Tile (Dark Green), East Entry, Southeast Room
Not Analyzed - Positive Stop
09-03 9" x 9" Vinyl Composition Tile (Dark Green), East Entry, Southeast Room
Not Analyzed - Positive Stop
10-01 Vinyl Flooring (Red) with Treads, South Hallway, East
Entry
None Detected - Flooring
None Detected - Brown Mastic
10-02 Vinyl Flooring (Red) with Treads, South Hallway, East
Entry
None Detected - Flooring
None Detected - Brown Mastic
10-03 Vinyl Flooring (Red) with Treads, South Hallway, East
Entry
None Detected - Flooring
None Detected - Brown Mastic
11-01 Paper Backing and Mastic, Beneath Wood Flooring in Main
Gym
None Detected - Tar Paper
Project :
Project # :
Identification :
Test Method :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
26-09-00191.00
Asbestos, Bulk Sample Analysis
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/30/2026, eighty four (84) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The
PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Lab Job No. :
Report Date :
26B-00995
01/22/2026
02/09/2026
NVLAP Lab Code 102056-0
TDSHS License No. 300084
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
11-02 Paper Backing and Mastic, Beneath Wood Flooring in Main
Gym
None Detected - Tar Paper
11-03 Paper Backing and Mastic, Beneath Wood Flooring in Main
Gym
None Detected - Tar Paper
12-01 Cove Base (Black), Main Gym None Detected - Cove Base
None Detected - Yellow Mastic
12-02 Cove Base (Black), Main Gym None Detected - Cove Base
None Detected - Yellow Mastic
12-03 Cove Base (Black), Main Gym None Detected - Cove Base
None Detected - Yellow Mastic
13-01 4" Cove Base (Brown), South Room None Detected - Cove Base
None Detected - Yellow Mastic
13-02 4" Cove Base (Brown), South Room None Detected - Cove Base
None Detected - Yellow Mastic
13-03 4" Cove Base (Brown), South Room None Detected - Cove Base
None Detected - Yellow Mastic
14-01 Cove Base (Grey), East Entry None Detected - Cove Base
None Detected - Yellow Mastic
14-02 Cove Base (Grey), East Entry None Detected - Cove Base
None Detected - Yellow Mastic
14-03 Cove Base (Grey), East Entry None Detected - Cove Base
None Detected - Yellow Mastic
15-01 2' x 2' Ceiling Tile (Dot and Fissure), South and Southwest
Rooms
None Detected - Acoustic Tile
15-02 2' x 2' Ceiling Tile (Dot and Fissure), South and Southwest
Rooms
None Detected - Acoustic Tile
15-03 2' x 2' Ceiling Tile (Dot and Fissure), South and Southwest
Rooms
None Detected - Acoustic Tile
Project :
Project # :
Identification :
Test Method :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
26-09-00191.00
Asbestos, Bulk Sample Analysis
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/30/2026, eighty four (84) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The
PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Lab Job No. :
Report Date :
26B-00995
01/22/2026
02/09/2026
NVLAP Lab Code 102056-0
TDSHS License No. 300084
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
16-01 1' x 1' Ceiling Tile (Pinhole), South and Southwest Rooms None Detected - Acoustic Tile
16-02 1' x 1' Ceiling Tile (Pinhole), South and Southwest Rooms None Detected - Acoustic Tile
16-03 1' x 1' Ceiling Tile (Pinhole), South and Southwest Rooms None Detected - Acoustic Tile
17-01 Drywall Ceiling System with Paper Backing (Black), South and Southwest Rooms
None Detected - Drywall Material
17-02 Drywall Ceiling System with Paper Backing (Black), South and Southwest Rooms
None Detected - Drywall Material
17-03 Drywall Ceiling System with Paper Backing (Black), South and Southwest Rooms
None Detected - Drywall Material
18-01 Mirror Mastic (Tan), Southwest Room None Detected - Tan Mastic
18-02 Mirror Mastic (Tan), Southwest Room None Detected - Tan Mastic
18-03 Mirror Mastic (Tan), Southwest Room None Detected - Tan Mastic
19-01 1" Ceramic Floor Tile, Grout and Thinset, East and South
Restrooms
None Detected - Ceramic Tile
None Detected - Grout
None Detected - Thinset
19-02 1" Ceramic Floor Tile, Grout and Thinset, East and South
Restrooms
None Detected - Ceramic Tile
None Detected - Grout
None Detected - Thinset
19-03 1" Ceramic Floor Tile, Grout and Thinset, East and South
Restrooms
None Detected - Ceramic Tile
None Detected - Grout
None Detected - Thinset
20-01 4" Ceramic Wall Tile, Grout and Thinset, South Restroom None Detected - Ceramic Tile
None Detected - Grout
2% Chrysotile - Thinset
20-02 4" Ceramic Wall Tile, Grout and Thinset, South Restroom Not Analyzed - Positive Stop
20-03 4" Ceramic Wall Tile, Grout and Thinset, South Restroom Not Analyzed - Positive Stop
Project :
Project # :
Identification :
Test Method :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
26-09-00191.00
Asbestos, Bulk Sample Analysis
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/30/2026, eighty four (84) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The
PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Lab Job No. :
Report Date :
26B-00995
01/22/2026
02/09/2026
NVLAP Lab Code 102056-0
TDSHS License No. 300084
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
21-01 HVAC Mastic (White), South Room None Detected - Thermal Insulation
None Detected - Duct Tape
None Detected - Vinyl Wrap
None Detected - White Mastic
21-02 HVAC Mastic (White), South Room None Detected - Paper / Foil Wrap
None Detected - Duct Tapes
None Detected - Vinyl Wrap
None Detected - White Mastic
21-03 HVAC Mastic (White), South Room None Detected - Duct Tape
None Detected - Vinyl Wrap
None Detected - White Mastic
22-01 Carpet Mastic, Southeast Room, South Hallway None Detected - Yellow Mastic
22-02 Carpet Mastic, Southeast Room, South Hallway None Detected - Yellow Mastic
22-03 Carpet Mastic, Southeast Room, South Hallway None Detected - Yellow Mastic
23-01 Rubber Flooring Mastic, South Room None Detected - Yellow Mastic
23-02 Rubber Flooring Mastic, South Room None Detected - Yellow Mastic
23-03 Rubber Flooring Mastic, South Room None Detected - Yellow Mastic
24-01 Brick Texture and Grout, East Restrooms None Detected - Grout
None Detected - Paint
24-02 Brick Texture and Grout, East Restrooms None Detected - Grout
None Detected - Paint
24-03 Brick Texture and Grout, East Restrooms None Detected - Grout
None Detected - Paint
25-01 Exterior HVAC Mastic (Tan), Exterior None Detected - Insulation
None Detected - Glass Fiber Mesh
None Detected - White Mastic
Project :
Project # :
Identification :
Test Method :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
26-09-00191.00
Asbestos, Bulk Sample Analysis
Sample Number Client Sample Description / Location Asbestos Content
Sample Date :
On 1/30/2026, eighty four (84) bulk material samples were submitted by a representative of TTL - San Antonio for asbestos analysis by PLM/DS. The
PLM Detail Report is attached; additional information may be found therein. The results are summarized below:
Lab Job No. :
Report Date :
26B-00995
01/22/2026
02/09/2026
NVLAP Lab Code 102056-0
TDSHS License No. 300084
Polarized Light Microscopy / Dispersion Staining (PLM/DS)
EPA Method 600 / R-93 / 116
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
25-02 Exterior HVAC Mastic (Tan), Exterior None Detected - Insulation
None Detected - Cotton Wrap
None Detected - White Mastic
25-03 Exterior HVAC Mastic (Tan), Exterior None Detected - Thermal Insulation
None Detected - Paper / Foil Wrap
None Detected - White Mastic
26-01 CMU Sealant, Exterior 2% Chrysotile - Sealant
26-02 CMU Sealant, Exterior Not Analyzed - Positive Stop
26-03 CMU Sealant, Exterior Not Analyzed - Positive Stop
27-01 Exterior CMU Texture and Grout, Exterior None Detected - Grout
None Detected - Paint
27-02 Exterior CMU Texture and Grout, Exterior None Detected - Grout
None Detected - Paint
27-03 Exterior CMU Texture and Grout, Exterior None Detected - Grout
None Detected - Paint
28-01 Exterior Window Glazing, Exterior 2% Chrysotile - Window Glazing
28-02 Exterior Window Glazing, Exterior Not Analyzed - Positive Stop
28-03 Exterior Window Glazing, Exterior Not Analyzed - Positive Stop
Isaac Rubio, Tommie SmithAnalyst(s):
Lab Director : Bruce Crabb Approved Signatory :
Thank you for choosing Moody Labs
Lab Manager : Heather Lopez Approved Signatory :
These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. The test report shall not be reproduced except in full without written approval of the laboratory. The results relate only to the items tested. These test results do not imply endorsement by NVLAP or any agency of the U.S.
Government. Accredited by the National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056-0.
PLM Detail Report
Project # : 26-09-00191.00
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report
Client :
Project :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
Lab Job No. :
Report Date :
26B-00995
02/09/2026
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
Moody Labs NVLAP Lab Code 102056-0
TDSHS License No. 300084
Amosite01-01 Thermal Insulation (Off-White) 100% 02/0810% TS
Chrysotile01-01 Thermal Insulation (Off-White) 100% 02/0810% TS
Binders / Fillers01-01 Thermal Insulation (Off-White) 100% 02/0880% TS
01-02 Not Analyzed - Positive Stop 100% 02/08 TS
01-03 Not Analyzed - Positive Stop 100% 02/08 TS
Chrysotile02-01 Thermal Insulation (Grey) 100% 02/0865% TS
Binders / Fillers02-01 Thermal Insulation (Grey) 100% 02/0835% TS
02-02 Not Analyzed - Positive Stop 100% 02/08 TS
02-03 Not Analyzed - Positive Stop 100% 02/08 TS
Amosite03-01 Thermal Insulation (White) 100% 02/0820% TS
Binders / Fillers03-01 Thermal Insulation (White) 100% 02/0880% TS
03-02 Not Analyzed - Positive Stop 100% 02/08 TS
03-03 Not Analyzed - Positive Stop 100% 02/08 TS
Aggregate04-01 CMU (Light Grey) 90% 02/0865% TS
Cement Binders04-01 CMU (Light Grey) 90% 02/0835% TS
Calcite04-01 Paint / Texture (White) 10% 02/0825% TS
Pigment / Binders04-01 Paint / Texture (White) 10% 02/0875% TS
Aggregate04-02 CMU (Light Grey) 90% 02/0865% TS
Cement Binders04-02 CMU (Light Grey) 90% 02/0835% TS
Calcite04-02 Paint / Texture (White) 10% 02/0825% TS
Pigment / Binders04-02 Paint / Texture (White) 10% 02/0875% TS
Aggregate04-03 CMU (Light Grey) 60% 02/0865% TS
Cement Binders04-03 CMU (Light Grey) 60% 02/0835% TS
Calcite04-03 Paint / Texture (White) 40% 02/0825% TS
Pigment / Binders04-03 Paint / Texture (White) 40% 02/0875% TS
Chrysotile05-01 Sealant (Light Grey) 100% 02/082% TS
Binders / Fillers05-01 Sealant (Light Grey) 100% 02/0898% TS
05-02 Not Analyzed - Positive Stop 100% 02/08 TS
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report
Client :
Project :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
Lab Job No. :
Report Date :
26B-00995
02/09/2026
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
Moody Labs NVLAP Lab Code 102056-0
TDSHS License No. 300084
05-03 Not Analyzed - Positive Stop 100% 02/08 TS
Chrysotile06-01 Sealant (Light Grey) 100% 02/082% TS
Binders / Fillers06-01 Sealant (Light Grey) 100% 02/0898% TS
06-02 Not Analyzed - Positive Stop 100% 02/08 TS
06-03 Not Analyzed - Positive Stop 100% 02/08 TS
Cellulose Fibers07-01 Drywall Material (White) 35% 02/085% TS
Gypsum / Binders07-01 Drywall Material (White) 35% 02/0895% TS
Cellulose Fibers07-01 DW Paper / Tape (Tan / White) 30% 02/08100% TS
Chrysotile07-01 Joint Compound (Off-White) 15% 02/082% TS
Calcite / Talc / Binders07-01 Joint Compound (Off-White) 15% 02/0898% TS
Chrysotile07-01 Texture (Off-White) 20% 02/082% TS
Calcite / Talc / Binders07-01 Texture (Off-White) 20% 02/0898% TS
07-02 Not Analyzed - Positive Stop 100% 02/08 TS
07-03 Not Analyzed - Positive Stop 100% 02/08 TS
Glue Binders08-01 Yellow Mastic (Yellow) 1% 02/08100% TS
Calcite / Vinyl Binders08-01 Floor Tile (Green) 97% 02/08100% TS
Glue Binders08-01 Yellow Mastic (Yellow) 2% 02/08100% TS
Glue Binders08-02 Yellow Mastic (Yellow) 1% 02/08100% TS
Calcite / Vinyl Binders08-02 Floor Tile (Green) 97% 02/08100% TS
Glue Binders08-02 Yellow Mastic (Yellow) 2% 02/08100% TS
Glue Binders08-03 Yellow Mastic (Yellow) 1% 02/08100% TS
Calcite / Vinyl Binders08-03 Floor Tile (Green) 97% 02/08100% TS
Glue Binders08-03 Yellow Mastic (Yellow) 2% 02/08100% TS
Chrysotile09-01 Floor Tile (Green) 98% 02/085% TS
Calcite / Vinyl Binders09-01 Floor Tile (Green) 98% 02/0895% TS
Chrysotile09-01 Black Mastic (Black) 2% 02/083% TS
Tar Binders09-01 Black Mastic (Black) 2% 02/0897% TS
09-02 Not Analyzed - Positive Stop 100% 02/08 TS
Sample Number Layer Components % Of
Sample
Analysis
Date
% of
Layer Analyst
Supplement to PLM Summary Report
Client :
Project :
TTL - San Antonio
Bldg 140, JBSA Chapman Training Annex
Lab Job No. :
Report Date :
26B-00995
02/09/2026
2051 Valley View Lane
Farmers Branch, TX 75234 Phone: (972) 241-8460
Moody Labs NVLAP Lab Code 102056-0
TDSHS License No. 300084
09-03 Not Analyzed - Positive Stop 100% 02/08 TS
Rubber Binders10-01 Flooring (Brown) 99% 02/08100% TS
Glue Binders10-01 Brown Mastic (Brown) 1% 02/08100% TS
Rubber Binders10-02 Flooring (Brown) 99% 02/08100% TS
Glue Binders10-02 Brown Mastic (Brown) 1% 02/08100% TS
Rubber Binders10-03 Flooring (Brown) 99% 02/08100% TS
Glue Binders10-03 Brown Mastic (Brown) 1% 02/08100% TS
Cellulose Fibers11-01 Tar Paper (Black) 100% 02/0890% TS
Tar Binders11-01 Tar Paper (Black) 100% 02/0810% TS
Cellulose Fibers11-02 Tar Paper (Black) 100% 02/0890% TS
Tar Binders11-02 Tar Paper (Black) 100% 02/0810% TS
Ce…