B08_Section_J_Attachment_7__REVISED_FINAL_CD_SET_2024_10_9.pdf
PDF 11 MB Posted
- Attached to
- HOSP 318915 Rehabilitate Park Bathhouses
- Solicitation number
- 140P2025R0004
About this file
This is a complete set of mechanical, electrical and SCADA control system construction drawings for the HVAC rehabilitation of the Buckstaff Bathhouse at Hot Springs National Park in Arkansas. The 60-page drawing set includes detailed plans for installing new HVAC equipment including an air-cooled chiller, boilers, fan coil units, dedicated outside air system (DOAS), and associated piping, ductwork, and controls across the basement, ground floor, second floor and third floor of the historic bathhouse building.
The drawings provide comprehensive technical details including demolition plans, new equipment layouts, piping and duct routing, electrical power distribution, lighting plans, control system architecture, and building automation specifications. Key components include a new 60-ton air-cooled chiller, hot water heating system with redundant boilers, variable frequency drives for pumps and fans, digital controls integration with the park's SCADA system, and preservation considerations for the historic structure. The drawings are dated February 15, 2024 and were prepared by Kenneth Hahn Architects with Alvine Engineering as the mechanical/electrical subconsultant.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT
LOCATION
BUCKSTAFF
BATHHOUSE
PARK
ADMINISTRATION
BUILDING
BUCKSTAFF
ADMINISTRATION
BUILDING
HOT SPRINGS
A/E FIRM
PRIME/ARCH:
KENNETH HAHN ARCHITECTS
OMAHA, NE
MECHANICAL ENGINEER:
ALVINE ENGINEERING
OMAHA, NE
ELECTRICAL ENGINEER:
ALVINE ENGINEERING
OMAHA, NE
PROJECT LOCATION
BATHHOUSE ROW
REGIONAL MAP
AREA MAP
PROJECT
LOCATION
PROJECT
LOCATION
SCHEDULE OF DRAWINGS
GENERAL
1. G1 COVER SHEET
2. G2 GENERAL NOTES, LEGEND AND ABBREVIATIONS
STRUCTURAL
3. S-100 GENERAL NOTES, PLATFORM FRAMING PLAN & DETAILS
4. S-101 DETAILS & SECTIONS
ARCHITECTURAL
5. AD1 BASEMENT DEMOLITION PLAN
6. A1 BASEMENT PLAN
7. A2 GROUND FLOOR PLAN
8. A3 2ND FLOOR PLAN
9. A4 3RD FLOOR REFLECTED CEILING PLAN
10. A5 ROOF PLAN
11. A6 DETAILS, ELEVATIONS, SECTIONS
MECHANICAL
12. M0-0 MECHANICAL SYMBOL LEGEND AND ABBREVIATIONS
13. M0-1 MECHANICAL GENERAL NOTES
14. M1-1 BASEMENT FLOOR PLAN - MECHANICAL DEMOLITION
15. M1-2 GROUND FLOOR PLAN - MECHANICAL DEMOLITION
16. M1-3 SECOND FLOOR PLAN - MECHANICAL DEMOLITION
17. M1-4 THIRD FLOOR PLAN - MECHANICAL DEMOLITION
18. M1-5 ROOF PLAN - MECHANICAL DEMOLITION
19. M2-1 BASEMENT FLOOR PLAN - HVAC
20. M2-2 GROUND FLOOR PLAN - HVAC
21. M2-3 SECOND FLOOR PLAN - HVAC
22. M2-4 THIRD FLOOR PLAN - HVAC
23. M2-5 ROOF PLAN-HVAC
24. M3-1 BASEMENT FLOOR PLAN - HVAC PIPING
25. M3-2 GROUND FLOOR PLAN - HVAC PIPING
26. M3-3 SECOND FLOOR OPLAN - HVAC PIPIN
27. M3-4 THIRD FLOOR PLAN - HVAC PIPING
28. M4-1 ENLARGED MECHANICAL ROOM PLANS
29. M5-1 CHILLED WATER PIPING SCHEMATIC
30. M5-2 HEATING WATER PIPING SCHEMATIC
31. M6-1 MECHANICAL DETAI
32. M6-2 MECHANICAL SECTIONS AND DETAILS
33. M7-1 MECHANICAL SCHEDULES
34. M7-2 MECHANICAL SCHEDULES
35. M7-3 MECHANICAL SCHEDULES
ELECTRICAL
36. E0-0 ELECTRICAL SYMBOL LEGEND AND ABBREVIATIONS
37. E1-1 BASEMENT FLOOR PLAN - ELECTRICAL DEMOLITION
38. E1-2 GROUND FLOOR PLAN - ELECTRICAL DEMOLITION
39. E1-3 SECOND FLOOR PLAN - ELECTRICAL DEMOLITION
40. E1-4 THIRD FLOOR PLAN - ELECTRICAL DEMOLITION
41. E2-1 BASEMENT FLOOR PLAN - LIGHTING
42. E2-2 THIRD FLOOR PLAN-LIGHTING
43. E3-1 BASEMENT FLOOR PLAN - POWER
44. E3-2 GROUND FLOOR PLAN - POWER
45. E3-3 SECOND FLOOR OPLAN - POWER
46. E3-4 THIRD FLOOR PLAN - POWER
47. E4-1 ONE LINE DIAGRAM
48. E5-1 ELECTRICAL DETAILS
49. E6-1 ELECTRICAL SCHEDULES
50. E6-2 ELECTRICAL SCHEDULES
51. E6-3 ELECTRICAL SCHEDULES
SCADA
52. Y0-01 SCADA INSTUMENTATION LEGEND
53. Y4-01 SCADA CONTROL PANEL
54. Y4-02 TYPICAL POWER SCHEMATIC
55. Y4-03 TYPICAL DI WIRING
56. Y4-04 TYPICAL AI WIRING
57. Y4-05 TYPICAL DO WIRING
58. Y6-01 P&ID
59. Y6-02 HVAC - SCADA NETWORK
60. Y6-03 SCADA FIBER DIAGRAM
SCADA
ABBREVIATIONS REFERENCES
XX
DETAIL NUMBER
DETAIL SHEET NUMBER
SECTION NUMBER
SECTION SHEET NUMBER
ELEVATION NUMBER
ELEVATION SHEET NUMBER
COLUMN LINE
ROOM NAME AND NUMBER
DOOR NUMBER
WINDOW NUMBER
WALL TYPE
KEYNOTE
ELEVATION NUMBER
ELEVATION SHEET NUMBER
ELEVATION SYMBOL
ABOVE FINISHED FLOOR AFF
ACOUSTIC TILE CEILING ATC
ADJACENT ADJ
AIR CONDITIONING AC
ALTERNATE ALT
ALUMINUM ALUM
ANCHOR BOLT AB
ANGLE L
APPROXIMATELY APPROX
ARCHITECT ARCH
ARCHITECT / ENGINEER A/E
AT @
BASEMENT BSMT
BEAM BM
BEARING BRG
BLOCKING BLKG
BOARD BD
BOTTOM BOT
BOTTOM OF B.O.
BUILDING BLDG
CARPET CPT
CAST IRON CI
CEILING CLG
CENTERLINE CL
CERAMIC TILE CT
CHANNEL CH
CIRCUIT CKT
CLEANOUT CO
CLEAR CLR
CLOSET CLO
COMPACTED COMP
COMPRESSIBLE COMPR
CONCRETE CONC
CONCRETE MASONRY UNIT CMU
CONSTRUCTION CONST
CONTINUOUS CONT
CONTRACTOR CONTR
CONTROL JOINT CJ
CORRIDOR CORR
COUNTERSUNK CTSK
CURB C
DEAD LOAD DL
DETAIL DET
DIAMETER DIA
DIMENSION DIM
DISPENSER DISP
DISHWASHER DW
DOOR DR
DOUBLE DBL
DOWN DN
DOWNSPOUT DS
DRAWING DWG
DRINKING FOUNTAIN DF
EACH EA
ELECTRICAL ELEC
ELECTRIC WATER COOLER EWC
ELEVATION EL
ELEVATOR ELEV
ENGINEER ENGR
EQUAL EQ
EQUIPMENT EQUIP
EXHAUST FAN EF
EXISTING EXIST
EXPANSION EXP
EXPANSION JOINT EJ
EXTERIOR EXT
EXTERIOR INSULATION FINISH SYSTEM EIFS
FIELD VERIFY F.V.
FINISH FIN
FIRE ALARM FA
FIRE EXTINGUISHER FE
FIRE EXTINGUISHER CABINET FEC
FLATHEAD FH
FLEXIBLE FLEX
FLOOR FL
FLOORING FLRG
FLOOR DRAIN FD
FLUORESCENT FLUOR
FOOTING FTG
FOUNDATION FNDN
FRAME FR
FURRING FUR
GALVANIZED GALV
GAUGE GA
GLASS GL
GLASS FIBER REINFORCED PANEL GFRP
GLAZING GLZ
GRANULAR GRAN
GUTTER G
GYPSUM WALLBOARD GWB
HANDICAP HC
HARDWARE HDWE
HARDWOOD HDWD
HEIGHT HT
HIGH POINT HP
HOLLOW CORE HC
HOLLOW METAL HM
HORIZONTAL HORIZ
INSIDE DIAMETER ID
INSULATION INSUL
INTERIOR INT
JOINT JT
JOIST JST
KNEE SPACE KS
LAVATORY LAV
LIGHT LT
LIGHTWEIGHT LTWT
LIVE LOAD LL
LOW POINT LP
LUXURY VINYL TILE LVT
MARKERBOARD MB.
MANHOLE MH
MANUFACTURER MFR
MATERIAL MATL, MAT
MECHANICAL MECH
MEDICINE CABINET MC
METAL MET
METAL BUILDING PANEL MBP
METAL WALL PANEL MWP
MINIMUM MIN
MISCELLANEOUS MISC
MOUNT MT
NOT IN CONTRACT NIC
NOT TO SCALE NTS
NUMBER NO.
ON CENTER O.C.
OPENING OPNG
OPPOSITE OPP
ORIENTED STRAND BOARD OSB
OUTSIDE AIR OA
OUTSIDE DIAMETER OD
PAINT PT
PANEL PNL
PARTITION PART
PLASTER PLAS
PLASTIC LAMINATE PLAM
PLATE PL
PLYWOOD PLYWD
POLISHED POL
POUND LB
PROPERTY PROP
QUARRY TILE QT
RADIUS R
RECESSED REC
REFERENCE REF
REFRIGERATOR REFRIG, REF
REGARDING RE:
REINFORCE REINF
REQUIRED REQ
RESILIENT BASE RB
RETURN AIR RA
REVERSE REV
RISER R
ROOF DRAIN RD
ROOM RM
ROUGH OPENING RO
ROUND RND
SCHEDULE SCHED
SECTION SET
SHEET SHT
SHEET METAL SM
SHEET VINYL SV
SHEET VINYL BASE SVB
SIMILAR SIM
SLAB-ON-GRADE SOG
SPECIFICATIONS SPEC
SQUARE SQ
SQUARE FOOT SF
STEEL STL
STORAGE STOR
STRUCTURAL STRUCT
SUPPLY AIR SA
SUSPENDED SUSP
TACKBOARD TB.
TELEPHONE TELE
TEMPERATURE TEMP
TERRAZZO TERR
TOILET TLT
TONGUE & GROOVE T&G
TOP OF T.O.
TOP OF STEEL TOS
TREAD T
TYPICAL TYP
UNDERGROUND UG
UNLESS NOTED OTHERWISE UNO
URINAL UR
VERTICAL VERT
VESTIBULE VEST
VINYL COMPOSITION TILE VCT
VINYL WALLCOVERING VWC
WATER CLOSET WC
WATER HEATER WH
WEIGHT WT
WELDED WIRE FABRIC WWF
WHERE OCCURRING W.O.
WOOD WD
X A-X01
X A-X01
XX.XX
X
X
X
A-X01
X
ROOM
NAME
XXXX
XX
XX
ELEV. = 100'-0"
FINISH FLOOR
XX
GENERAL NOTES
XXX
1. THE CONTRACTOR SHALL PROTECT EXISTING BUILDING AND
SITE MATERIALS SCHEDULED TO REMAIN, AND SHALL BE
RESPONSIBLE FOR DAMAGE TO SAME RESULTING FROM WORK
UNDER THIS CONTRACT. THE CONTRACTOR SHALL RESTORE
DAMAGED EXISTING BUILDING AND SITE MATERIALS TO THEIR
ORIGINAL CONDITION.
2. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND
SHALL BE RESPONSIBLE FOR THE SAME. COORDINATE ALL
WORK AND SHOP DRAWINGS WITH OTHER TRADES.
3. INFORMATION PERTAINING TO THE EXISTING BUILDING HAS
BEEN OBTAINED THROUGH THE BUILDING'S ORIGINAL
DRAWINGS, WHERE AVAILABLE, AND LIMITED ON-SITE
VERIFICATION. REPORT DISCREPANCIES TO THE CONTRACTING
OFFICER PRIOR TO ANY DEMOLITION. CONTRACTOR SHALL
FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
COMMENCING WORK.
4. THE CONTRACTOR SHALL COORDINATE ALL TESTING AND
INSPECTIONS AS SPECIFIED, OR AS NECESSARY TO
DEMONSTRATE A COMPLETE AND SATISFACTORY
INSTALLATION.
5. THE CONTRACTOR SHALL COORDINATE ON-SITE STORAGE OF
BUILDING MATERIALS, EQUIPMENT, AND TRASH CONTAINERS
WITH THE PARK.
6. ALL WORK SHALL COMPLY WITH LOCAL CODES AND ALL OTHER
APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
7. ALL MATERIALS AND EQUIPMENT OF THE SAME TYPE SHALL BE
SUPPLIED BY THE SAME MANUFACTURER, AND SHALL BE NEW,
OF THE BEST QUALITY AND DESIGN, AND FREE FROM DEFECTS.
8. ALL ITEMS ARE NEW UNLESS SPECIFICALLY IDENTIFIED AS
EXISTING.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF
ALL WORK. CONTRACTOR SHALL ANTICIPATE AREAS WHERE
THE INSTALLATION OF MECHANICAL AND ELECTRICAL WORK
WILL BE RESTRICTED, CONGESTED, OR DIFFICULT TO INSTALL,
AND SHALL COORDINATE INSTALLATION BETWEEN THE
TRADES.
10. CONTRACTOR SHALL COORDINATE LOCATIONS FOR ALL
MECHANICAL AND ELECTRICAL ITEMS WITH EXISTING
CONDITIONS AND NEW WORK. CONTRACTOR SHALL NOTIFY
THE CONTRACTING OFFICER OF ANY DISCREPANCIES PRIOR
TO INSTALLATION AND/OR FABRICATION.
11. IT IS THE INTENT OF THIS CONTRACT THAT ALL AREAS
AFFECTED BY CONSTRUCTION SHALL PROVIDE A FINISHED
AND COMPLETE PROJECT, UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PATCH, REPAIR, AND ADJUST AS
REQUIRED TO ACHIEVE THIS FINISHED PROJECT.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING
ALL WORK AND PROVIDING ALL MATERIALS REQUIRED TO
ACHIEVE THE DESIGN INTENT SHOWN ON THESE DRAWINGS.
THE GOVERNMENT WILL NOT BE RESPONSIBLE FOR ANY
ADDITIONAL EXPENSE TO THE CONTRACTOR IF THE
CONDITIONS CAUSING THOSE EXPENSES COULD HAVE BEEN
DISCOVERED IN AN ON-SITE INSPECTION PRIOR TO BID
SUBMITTAL.
13. THE BUILDING, LANDSCAPE AND SURROUNDINGS ARE ON THE
NATIONAL REGISTER OF HISTORIC PLACES. THE ENTIRE SITE IS
A HISTORIC PROPERTY AND ALL REASONABLE PRECAUTIONS
SHALL BE TAKEN TO PREVENT COLLATERAL DAMAGE TO
HISTORIC MATERIALS SURROUNDING THE WORK AREA. IF
DAMAGE OCCURS, REPAIRS SHALL BE MADE AT NO
ADDITIONAL COST TO THE GOVERNMENT TO THE
SATISFACTION OF THE CONTRACTING OFFICER. EVERY
OPPORTUNITY SHOULD BE TAKEN TO PRESERVE, REPAIR AND
CONSERVE HISTORIC MATERIALS AND DESIGNS. COORDINATE
ALL NEW PENETRATIONS AND ANY ALTERATIONS TO THE
BUILDING WHICH MIGHT AFFECT THE HISTORIC INTEGRITY OF
THE BUILDING WITH THE CONTRACTING OFFICER PRIOR TO
BEGINNING WORK.
14. "REMOVE" MEANS TO DEMOLISH AND DISPOSE OF AN ITEM OFF
OF NPS PROPERTY.
GENERAL NOTES, LEGEND
AND ABBREVIATIONS
G2
F e b a m
C
U s e r s t o d d A p p D a t a L o c a l T e m p A c P u b l i s h
H
O S
P G d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
W14X53
W12X26
W12X26
W12X26
W12X26
W12X26
W14X53
W12X26
W
X
W
X
W
X
W
X
EXIST PILLAR
(NOTE 1)
EXIST PILLAR
(NOTE 1)
EXIST PILLAR
(NOTE 1)
4' -1
/2
3'
-8
3' -8
4'
-2
4' -2
19-W-4 (1 X 3/16)
METAL BAR GRATING
(TYP) (NOTE 2)
REMOVABLE
GUARDRAIL
STEEL LADDER
SEE 3 & 4/S-101
REMOVABLE
GAURDRAIL
S-100
3' -8
4'
-1
/2
'-1
(V
E R
IF
Y
15'-11"
21'-9"±
(VERIFY)
EXIST PILLAR
(NOTE 1)
OUTLINE OF GENERATOR
SITTING ON GRATING
EXIST WALL
EXIST BUILDING
EXIST BUILDING
S-101
S-101
W
X
7' -4
7'-10 5/16"4'-0 11/16" 4'-0"
FIXED
PIPE RAILING
GRATING EXTENDS
TO WITHIN 2" OF FACE
OF BLDG
W12X26
S-100
NORTH BEAM END
EXTENDS 4" BEYOND
C OF PILLAR SEE
DETAIL 3/S-100 FOR
ANCHORAGE TYP
L
4"
C PILLAR & BEAMSL
TERMINATE
OUT-TO-OUT DIMS.
OF CHILLER - VERIFY
CONN PER 1/S-101 (TYP)
C PILLAR & BEAMSL
6'-0" LONG HANDRAIL
FOR ELECTRICAL PANEL
MOUNTING - WELD (3)
POSTS ALL AROUND TO
TOP OF BEAM, NOTCH
GRATING AS REQ'D.
W14X53
W14X53
EXTENT OF GROUT
BELOW BEAM
ANCHOR RODS ON
5 1/2"x5 1/2" GA
S-100
W14X53
W14X53
SINGLE PLATE CONN. w/
(3) 34 Ø BOLTS
4" GROUT
(4) 12" Ø HILTI HAS-V-36 (HDG)
THREADED RODS w/ 8" MIN EMBED
INTO TOP OF PILLAR, UTILIZING HILTI
"HIT-HY200 A/R V3" ADHESIVE
ANCHORING SYSTEM
EXIST PILLAR
GRATING
W12X26
ANCHORS FOR MECH
UNIT PER SUPPLIER
NOTE:
DETAIL IS TYP @ (4) SIDES OF CHILLER
MECH UNIT
C BEAML
CONTRACTOR VERIFY
MIN 1 1/4" EDGE DISTANCE
N O
R
TH
1 PLATFORM FRAMING PLAN
SCALE: 3/8" = 1'-0"
BEAM ANCHORS
SCALE: 1 1/2" = 1'-0"
SECTION
SCALE: 1 1/2" = 1'-0"
STRUCTURAL GENERAL NOTES:
1. BUILDING CODE - 2018 INTERNATIONAL BUILDING CODE (IBC).
2. 100 PSF LIVE LOAD USED FOR DESIGN.
3. CONTRACTOR MUST VERIFY ALL EQUIPMENT SIZES AND
EXISTING CONDITIONS. STRUCTURAL ENGINEER WILL NEED
TO VERIFY BEAM SIZES, GRATING SPAN AND SIZE.
4. ALL W-SHAPE SECTIONS SHALL CONFORM TO ASTM A992 (Fy =
50 KSI).
5. BOLTS FOR STRUCTURAL CONNECTIONS SHALL BE 3/4-INCH
DIAMETER ASTM F3125 GRADE A325, TYPE 1 IN BEARING-TYPE
CONNECTIONS, TIGHTENED TO SNUG TIGHT, UNLESS
OTHERWISE NOTED.
6. ANCHOR RODS SHALL BE SPECIFIED IN DETAIL 3/S-100.
7. CONNECTIONS NOT SPECIFICALLY DETAILED SHALL BE PER
DETAIL 1/S-101.
8. HOT-DIP GALVANIZE ALL STEEL BEAM ANCHORS, GRATING,
LADDER, ETC. SEE ARCH DWGS FOR ANY PAINTING
REQUIREMENTS IN ADDITION TO GALVANIZING.
9. SPECIAL INSPECTIONS AS DEFINED AND REQUIRED BY THE
CODE SHALL BE PERFORMED BY AN INDEPENDENT
INSPECTION AGENCY APPROVED BY THE BUILDING OFFICIAL
TO PERFORM SUCH WORK. THE DESIGNATED INSPECTOR
SHALL ALSO BE APPROVED BY THE ARCHITECT AND
ENGINEER OF RECORD AND SHALL BE PAID FOR BY THE
TESTING ALLOWANCE.
10. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK HEREIN
AFTER ASSIGNED FOR CONFORMANCE WITH APPROVED
DESIGN DRAWINGS AND SPECIFICATIONS AND SHALL BRING
ALL DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE
CONTRACTOR FOR CORRECTION. UNCORRECTED
DISCREPANCIES SHALL BE REPORTED TO THE BUILDING
OFFICIAL AND ARCHITECT/ENGINEER OF RECORD.
11. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION
REPORTS TO THE BUILDING OFFICIAL AND THE
ARCHITECT/ENGINEER OF RECORD AT MONTHLY INTERVALS
AND SHALL SUBMIT A FINAL SIGNED REPORT AT THE PROJECT
COMPLETION STATING WHETHER THE WORK INSPECTED WAS,
TO THE BEST OF THEIR KNOWLEDGE, IN ACCORDANCE WITH
APPROVED DESIGN DRAWINGS AND SPECIFICATIONS.
12. ITEMS FABRICATED IN FABRICATOR'S SHOP SHALL BE
INSPECTED PER ALL APPLICABLE PORTIONS OF IBC SECTION
1704.2.5, EXCEPT WHEN FABRICATOR IS APPROVED IN
ACCORDANCE WITH SECTION 1704.2.5.1. THE CONTRACTOR
SHALL FURNISH CERTIFICATES OF COMPLIANCE TO THE
BUILDING OFFICIAL FOR ALL PREFABRICATED STRUCTURAL
STEEL MEMBERS AS REQUIRED BY SECTIONS 1704.2.5.1 &
1704.5.
13. STEEL ELEMENTS SHALL BE INSPECTED PER QUALITY
ASSURANCE INSPECTION REQUIREMENTS OF AISC 360.
14. STEEL GRATING SHALL BE ATTACHED TO STEEL BEAMS WITH
GALVANIZED "G" CLIPS INSTALLED FROM THE TOP SIDE. CLIPS
SHALL BE PLACED AT INTERMEDIATE SUPPORTS IN THE
MIDDLE OF THE GRATING PANELS AND AT THE FOUR
CORNERS OF EACH GRATING PANEL, 6" FROM EACH SIDE OF
PANEL.
FRAMING PLAN NOTES:
1. EXISTING CONCRETE PILLAR AT NORTHEAST, NORTHWEST, AND SOUTHEAST CORNERS ARE
APPROXIMATELY 3'-0"X3'-0" IN PLAN AT THE TOP, TAPERING TO A WIDER DIMENSION AT THE
BOTTOM. FIELD VERIFY PILLAR SIZE @ SOUTHWEST CORNER. PLAN DIMENSIONS BETWEEN
PILLAR CENTERLINES ARE APPROXIMATE, TO BE VERIFIED BY CONTRACTOR.
2. INDICATES GALVANIZED STEEL GRATING (19-W-4, w/ 1"X3/16" BEARING BARS).
SEE STRUCTURAL GENERAL NOTES FOR CONNECTION TO BEAMS.
SECTION
SCALE: 1 1/2" = 1'-0"
F eb
5,
- 1
2:
pm oa .a d.
oa co ns ult ing
.co m
\fn ts-ns 1\ pr oje cts -d ire ct\
\0
-0
\0
-0
\4
0- De sig n\
Re vit
\0 1-
S\
-P ro jec t C on te nt \ 1
-0
H
OS
P
Bu ck sta ff
XF
P0
_S
TR
C.
dw g
- U
SE
R m fu jan
SUB SHEET NO.
OF
DESIGNED:
NRJ
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
177425
DRAWN BY:
TECH. REVIEW:
DATE:
1/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
MF
NRJ
FINAL CONSTRUCTION DOCUMENTS
STRUCTURAL GENERAL NOTES,
PLATFORM FRAMING PLAN & DETAILS
S-100
S-100
2"
1" GRATING SPANNING EAST-WEST
3/8"X6" LONG PLATES FULL PEN
WELDED TO BEAM, IN LINE WITH
EACH NORTH-SOUTH BEAM FOR
GRATING BEARING
W12X26
W14X53
FACE OF EXIST BLDG
1'-1"± (FIELD
VERIFY)
2 1/2"X3/8" SIDE RAILS
-SEE DET 3/S-101 FOR
CONDITION @ GATE
ABOVE
3/4" RUNGS @
12" O.C. PLUG
WELD TO RAILS
3X3X1/4 w/ 5/8" Ø BOLTS
EACH END AT BOTH RAILS
CONNECTING TO W10X26
BEAM ABOVE
6" 6"
GRADE
1/4" SHOP WELDED GUSSET PL
TYP TOP & BOT
ABOVE THE PLATFORM TOE PLATES THE SIDE
RAILS SHALL FLARE OUT TO BE 2'-0" APART, AND
EXTEND TO TOP OF GUARDRAIL. SINCE THE
GUARDRAILS ON BOTH SIDES OF THE LADDER
ARE REMOVABLE, PROVIDE DEDICATED FIXED
GUARDRAIL POST BEHIND BOTH RAILS, WITH
TOP OF POST AND RAIL CONNECTED TOGETHER
AT THE TOP. PROVIDE "LSG LADDER SAFETY
GATE" BY PS DOORS (OR APPROVED EQUAL IN
CONFORMANCE WITH OSHA), ATTACHED TO THE
DEDICATED POSTS AND ALIGNED WITH THE TOP
OF THE GUARDRAIL.
W14X53
3/4" RUNGS
@ 12" O.C.
PLUG WELD
TO RAILS
BENT PL 3/8"X9"
2 1/2"X3/8" SIDE RAILS
(3) 3/4" Ø BOLTS
1'-4" TYP
7" M
IN
1/4
4" 1'-
8" 1'-
6"
3'- 6"
4" 1'-
6"
3'- 6"
1 1/2"Ø SCH. 40 PIPE
(CARBON STEEL)
WELD ALL JOINTS &
GRIND SMOOTH (TYP)
1 1/2"Ø SCH. 40 PIPE
@ 4'-0" MAX O.C.
(CARBON STEEL)
L7x4x3/8 L.L.O. W/
(2)-3/4"Ø A325 BOLTS
W14X53
6"
TYP
GUARDRAIL POST
@ 4'-0" O.C. MAX
1/4"x4" TOE PLATE
GUARDRAIL WELD
ALL JOINTS &
GRIND SMOOTH
(TYP)
TOP OF
GRATING
NOTES:
1. ALL RAILS AND POST = 1 1/2"Ø SCH. 40 PIPE, GALVANIZED.
2. TOUCH UP GALVANIZED SURFACES DAMAGED BY FIELD
WELDING WITH ZRC COLD GALVANIZING PAINT.
ELEVATION SECTION
NOTES:
1. ALL BOLTS SHALL BE F3125, GRADE A325 UNLESS NOTED OTHERWISE.
2. PROVIDE MINIMUM BOLT NUMBER BOLTS TYPICAL. WHERE BOLT ROWS
AND/OR BOLT DIAMETER AS INDICATED I.E. 4'-1"Ø AT CONNECTION,
INCREASE NUMBER OF ROWS AND/OR BOLT DIAMETER AS INDICATED.
3. MINIMUM DISTANCE FROM TOP BOLT TO A COPE SHALL BE 1 1/2".
INCREASE DISTANCE FROM TOP OF BEAM TO TOP OF BOLT, IF REQUIRED.
4. USE ONLY SHORT HORIZONTAL SLOTTED HOLES.
4'-0" 6"
4" 1'-
6"
3'- 6"
6"
1/4
L7x4x3/8 L.L.O. W/
(2)-3/4"Ø A325 BOLTS
W14X536
TYP
1 1/2"Ø SCH. 40 PIPE
(CARBON STEEL)
WELD ALL JOINTS &
GRIND SMOOTH
(TYP)
1 1/2"Ø SCH. 40 PIPE
@ 4'-0" MAX O.C.
(CARBON STEEL)
2"Ø SCH. 80
SLEEVE
WELDED TO
ANGLE
GUARDRAIL POST
1/4"x4" TOE PLATE
GUARDRAIL
(MAX) (MAX)
TOP OF
GRATING
2"Ø SCH. 80 SLEEVE
WELDED TO ANGLE
1/4"x2 1/2"Ø O.D.
PLATE WELDED
TO POST
T/BEAM
SEE PLAN
1/4"x4" TOE PLATE
TYP
ELEVATION SECTION
SCALE: 1" = 1'-0"
TYPICAL SINGLE PLATE SHEAR CONNECTION
(SHEAR TAB) W/ 3/4" Ø BOLTS1 SECTION
SCALE: 1 1/2" = 1'-0"
SECTION
SCALE: 1 1/2" = 1'-0"
TOP LADDER CONNECTION DETAIL
SCALE: 1 1/2" = 1'-0"
F eb
5,
- 1
2:
pm oa .a d.
oa co ns ult ing
.co m
\fn ts-ns 1\ pr oje cts -d ire ct\
\0
-0
\0
-0
\4
0- De sig n\
Re vit
\0 1-
S\
-P ro jec t C on te nt \ 1
-0
H
OS
P
Bu ck sta ff
XF
P0
_S
TR
C.
dw g
- U
SE
R m fu jan
SUB SHEET NO.
OF
DESIGNED:
NRJ
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
177425
DRAWN BY:
TECH. REVIEW:
DATE:
1/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
MF
NRJ
FINAL CONSTRUCTION DOCUMENTS
DETAILS & SECTIONS
FIXED GUARDRAIL DETAILS
SCALE: 1" = 1'-0"
5 REMOVABLE GUARDRAIL DETAILS
SCALE: 1" = 1'-0"
S-101
S-101
WST
DUMBWAITER
DW1
LAUNDRY
B109 STORAGE
B110
LINEN ROOM
B108
AIR
CHAMBER
B104A
WIND TUNNEL
B104
HALL
B104B
EQUIPMENT
ROOM
B103
AIR
DISTRIBUTION
CHAMBER
B106
STORAGE
B107
TOOL ROOM
B102
STORAGE
B101
BOILER ROOM
B100
HALL
B105
AD1
BASEMENT DEMOLITION
PLAN
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
BASEMENT DEMOLITION PLAN
N1 b
T o d d A
K
H A w o r k
H
O S
P
B u c k s t a f f
H
V A
C D
W G s
H
O S
P A
D d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
DEMOLITION PLAN KEYNOTES (KN)
1 REMOVE DOOR AND FRAME. PREP OPENING FOR NEW WORK.
2 REMOVE WINDOW AND FRAME. PREP OPENING FOR NEW WORK.
3 REMOVE DOOR AND FRAME. PATCH WALL TO MATCH ADJACENT.
4 SEE MECHANICAL DEMOLITION PLAN. PREP AREA FOR NEW WORK.
5 REMOVE WOOD DOOR FRAME. PATCH AREA AS NEEDED.
6. REMOVE DOOR AND FRAME. PREP OPENING FOR NEW WORK. CUT
PLENUM DECK BACK ONLY AS NEEDED TO ACCOMMODATE NEW
DOOR AND FRAME. INSTALL 2X SUPPORT UNDER EDGE OF PLENUM
DECK TO STABILIZE. SEE 2/AD-1.
5 1
NOT TO SCALE
EXISTING PLENUM DECK
INSTALL NEW 2X SUPPORT BEFORE
CUTTING DECK BACK. SEE KN 6.
EXISTING PLENUM DECK
WST
DUMBWAITER
DW1
LAUNDRY
B109 STORAGE
B110
LINEN ROOM
B108
AIR
CHAMBER
B104A
WIND TUNNEL
B104
HALL
B104B
EQUIPMENT
ROOM
B103
AIR
DISTRIBUTION
CHAMBER
B106
STORAGE
B107
TOOL ROOM
B102
STORAGE
B101
BOILER ROOM
B100
HALL
B105
A1
BASEMENT PLAN
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
BASEMENT PLAN
b
T o d d A
K r k
H
O S
P
B u c k s t a f f
H
V A
C D
W G s
H
O S
P A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
FLOOR PLAN KEYNOTES:
1 NEW DOOR AND FRAME-PAINT. SEE SHEET A1.
2 INFILL OPENING PER 7/A6. PROVIDE SEALANT AT PERIMETER-BOTH SIDES,
PRIME AND PAINT. USE 6" STUDS WHERE ABLE DUE TO WALL THICKNESS.
3 AS NEEDED-PATCH AND REPAIR WHERE FRAME WAS REMOVED. MATCH
ADJACENT AREA.
4 NEW CONCRETE HOUSEKEEPING PADS- SEE MECHANICAL.
5 PATCH AND REPAIR AIR DISTRIBUTION CHAMBER AS NEEDED TO BE
REASONABLY AIRTIGHT. COORDINATE WITH CO/COR.
6 INFILL OPENING WITH GALVANIZED SHEET METAL ON METAL STUD FRAMING.
SEE 9/A6.
7 NEW DOOR AND FRAME, 1-HOUR RATED -PAINT. SECURE FRAME AT JAMBS.
PROVIDE FIRE STOP BRICK AND FIRE PUTTY INFILL ABOVE FRAME AT CONDUITS
TO ACHIEVE 1-HR RATING. FOLLOW MANUFACTURER'S RECOMMENDATIONS.
PROVIDE FIRE SEALANT AND FIRE BARRIER FOAM AT DOOR HEAD AND JAMBS.
SEE 5/A1.
8 EXISTING PENETRATION, APPROX. 18" H X 18" W, OF MULTIPLE PIPES THROUGH
CONCRETE WALL. INFILL OPENING WITH FIRE STOP BRICKS AND FIRE PUTTY TO
ACHIEVE 1-HR RATING. FOLLOW MANUFACTURER'S RECOMMENDATIONS. SEE
2/A1.
9. NEW DOOR AND FRAME-PAINT. INSTALL 2X SUPPORT UNDER EDGE OF PLENUM
DECK TO STABILIZE. SEE AD-1.
6 9
3 3
B1
B1
B1
B102
B1
DETAIL
DOOR AND FRAME SCHEDULE
NO. SIZE TYPE MAT.
FRAME
TYPE MAT. DEPTH
FIRE
RATING
DOOR
HM GALVANIZED HOLLOW METAL
LEGEND
B100 2'-10" x 6'-4" x 1-3/4" A HM F01 HM 5-7/8" 45 MIN. 3, 5SIM /A1 B102 2'-2" x 6'-4" x 1-3/4" A HM F01 HM 5-7/8" 45 MIN. 3, 5/A1 B104 2'-6" x 6'-8" x 1-3/4" A HM F01 HM 5-7/8" NA 3, 4/A1 B105 2'-6" x 6'-8" x 1-3/4" A HM F01 HM 5-7/8" NA 3, 4/A1 B107 2'-6" x 6'-2" x 1-3/4" A HM F01 HM 5-7/8" NA 3, 4/A1
2"SEE
SCHEDULE
2"
SE
E
SC
HE
DU
LE
DOOR A FRAME 01
NOTES:
A. FEILD VERIFY ALL DOOR AND FRAME SIZES
AFTER DEMOLITION AND PATCHING.
B. FRAME AND DOOR TO FIT UNDER AIR DUCT.
SEE MECHANICAL.
C. PROVIDE SEALANT AT PERIMETER OF
FRAMES.
D. PROVIDE FIRE-RATED CAULK AT RATED
DOORS.
NOT TO SCALE
WALL PENETRATION
SCALE: 1-1/2" = 1'-0" 8"4"0 16"
DOOR JAMB/HEAD @ MASONRY
EXISTING MASONRY WALL
HM FRAME -SEE SCHEDULE
SEALANT-BOTH SIDES
SCALE: 1-1/2" = 1'-0" 8"4"0 16"
DOOR HEAD @ WOOD INFILL
SEALANT-BOTH SIDES
WOOD INFILL UNDER
BRICK ARCH-EXISTING
2X HEADER
SCALE: 1-1/2" = 1'-0" 8"4"0 16"
FRAME HEAD -1 HOUR-RATED
FIRE BARRIER FOAM AND
SEALANT AT PERIMETER
-BOTH SIDES
EXISTING CONDUIT (MULTIPLE)
DUCT- SEE MECHANICAL
HM FRAME-SEE SCHEDULE
CONCRETE DECK
HM FRAME, SECURE FRAME AT
JAMBS-SEE SCHEDULE
FIRE STOP BRICK AND FIRE
PUTTY AT CONDUITS TO
ACHIEVE 1-HR RATING.
SIM
NOTES
A, D
A, B, D A,C A,C A,C
1 HR. RATED
UP
UP
UP
UP
UP
LAMAR
TOILET
MASSAGE
MASSAGE
107A
VEST.
106B
DUMBWAITER
DW1
OFFICE
101ELEV.
E1
STAIR
S1
LOBBY
DRESSING
COOLING RM.
MASSAGE
103A
MASSAGE
103B
COOLING RM.
103DRESSING
VEST.
106A
STAIR
S2
MEN'S BATH
HALL
TOILET
MEN'S
LOCKER/
LOUNGE
OZARK
A2
GROUND FLOOR PLAN
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
GROUND FLOOR PLAN
b
T o d d A
K r k
H
O S
P
B u c k s t a f f
H
V A
C D
W G s
H
O S
P A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
FLOOR PLAN KEYNOTES:
1 VERTICAL PIPE CHASE-FULL HEIGHT WITH SOLID-SURFACE WAINSCOT- PRIME
AND PAINT EXPOSED GWB. SEE 2 & 5 /A6. SEE MECHANICAL. SEE 2/A2 FOR
RECOMMENDED SIZE.
2 PARTIAL HEIGHT VERTICAL PIPE CHASE- HEIGHT TO MATCH FCU. INSTALL
WAINSCOT AND CAP OF SOLID SURFACE MATERIAL. SEE 4 & 5 /A6. SEE
MECHANICAL. SEE 2/A2 FOR RECOMMENDED SIZE.
3 SOFFIT-HORIZONTAL PIPE CHASE- PRIME AND PAINT. SEE 3/A6 AND
MECHANICAL.
4 MECHANICAL EQUIPMENT PLATFORM WITH GALVANIZED STRUCTURAL STEEL
BEAMS-PAINT, GALVANIZED STEEL PIPE RAILINGS AND SPRING-LOADED GATE-
PAINT, AND GALVANIZED BAR STEEL LADDER WITH EXTENSIONS-PAINT. SEE
STRUCTURAL. NOTE PAINT IS HIGH-PERFORMANCE PRODUCTS.
5 EQUIPMENT- SEE ELECTRICAL AND MECHANICAL.
GENERAL NOTES
1. PATCH/REPAIR FLOOR AS REQUIRED TO MATCH ADJACENT AREA WHERE NEW
FCU DOES NOT COMPLETELY COVER OLD LOCATIONS.
2. PATCH AND REPAIR FLOOR AND WALL TO MATCH ADJACENT AREA WHERE
EQUIPMENT IS PERMANENTLY REMOVED.
3. CLEAN FLOOR AND WALL AT FCUs AS NEEDED AS PART OF PREP FOR NEW FCUs.
A6
3 RECOMMENDED OUTSIDE DIMENSION.
COORDINATE VARIANCE W/ CO/COR
10" X 2'-0"
9" X 2'-0" -WIDTH AS NEEDED TO FIT
BEHIND DOOR
1'-0" X 2'-0"
10" X 1'-3"
A
A
A
A
A
A
A
B
C
D
B
C
C
D E
E
1'-2" X 2'-0"
A CHASE SIZE SCHEDULE
DN
DN
MASSAGE
213B
MASSAGE
213C
MASSAGE
213D
MASSAGE
210B
MASSAGE
210C
MASSAGE
210D
WOMENS
LOCKERS
STAIR
HALL
S2
TOILET
DRESSING
ROOM
COOLING
ROOM
DRESSING
ROOM
LOBBY
STAIR
S1
FOYER
ELEVA
E1
DRESSING
ROOM
COOLING
ROOM
FOYER
210A
PACK ROOM
G15
DUMBWAITER
DW1
WOMEN'S
BATH HALL
STORAGE
FOYER
213A
WOMEN'S
LOCKER LOUNGE
TOILET
MASSAGE
216A
MASSAGE
216B
MASSAGE
216C
MASSAGE
216D
A3
2ND FLOOR PLAN
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
2ND FLOOR PLAN
b
T o d d A
K r k
H
O S
P
B u c k s t a f f
H
V A
C D
W G s
H
O S
P A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
FLOOR PLAN KEYNOTES:
1 VERTICAL PIPE CHASE-FULL HEIGHT-PRIME AND PAINT GWB. PROVIDE BASE
MATERIAL TO MATCH EXISTING. SEE 2 & 5 /A6. SEE MECHANICAL. SEE 2/A2
CHASE SIZE SCHEDULE FOR RECOMMENDED SIZE.
2 PARTIAL HEIGHT VERTICAL PIPE CHASE- HEIGHT TO MATCH FCU. INSTALL
WAINSCOT AND CAP OF SOLID SURFACE MATERIAL. SEE 4 & 5 /A6. SEE
MECHANICAL. SEE 2/A2 CHASE SIZE SCHEDULE FOR RECOMMENDED SIZE.
ALIGN FACE OF CHASE WITH THE FACE OF THE FCU.
3 AT THE FCU INSTALLED IN FRONT OF THE WINDOW INSTALL SOLID-SURFACE
MATERIAL SPACER FLATWISE AGAINST THE WALL. THE TOP OF THE FCU WILL
BE AT THE SAME LEVEL AS THE LIP OF THE MARBLE SILL LEAVING A GAP
BETWEEN THE FCU AND THE WALL. SIZE THE SPACER 1/4" LARGER THAN THE
FCU AND NOTCH THE SPACER AT THE SILL.
GENERAL NOTES
1. PATCH/REPAIR FLOOR AS REQUIRED TO MATCH ADJACENT AREA WHERE
NEW FCU DOES NOT COMPLETELY COVER OLD LOCATIONS.
2. PATCH AND REPAIR FLOOR AND WALL TO MATCH ADJACENT AREA WHERE
EQUIPMENT IS PERMANENTLY REMOVED.
3. CLEAN FLOOR AND WALL AT FCUs AS NEEDED AS PART OF PREP FOR NEW FCUs.
A
3 3
CONFERENCE
ROOM
WAITING
ROOM
ELEVA
E1
MGR. OFFICE
STORAGE
STORAGE
300B
HALL
300A
MANI./PEDI.
ROOM
300CFACIAL RM
300D
FACIAL RM
300E
STAIR
S1STORAGE
EQ4'-0"EQEQ4'-0"EQ
A4
3RD FLOOR REFLECTED
CEILING PLAN
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
3RD FLOOR - REFLECTED CEILING PLAN
b
T o d d A
K r k
H
O S
P
B u c k s t a f f
H
V A
C D
W G s
H
O S
P A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
FLOOR PLAN KEYNOTES:
1 SOFFIT-HORIZONTAL DUCT CHASE- PRIME AND PAINT. SEE 8/A6.
2 2' X 2' ACOUSTICAL CEILING TILE IN 15/16" ALUMINUM GRID. INSTALL AT 8'-1"
A.F.F., INSTALL AS HIGH AS POSSIBLE UNDER DUCTWORK IN MGR. OFFICE
301.
3 EXTEND EXISTING WALL TO DECK. KEEP LOWER CROWN MOLDING IN PLACE,
REMOVE UPPER CROWN MOLDING-PATCH. ADD MATCHING CROWN MOLDING
AT DECK. PRIME NEW GWB AND PAINT FULL WALL-BOTH SIDES. SEE 6/A6.
4 LOWER EXISTING GRILL IN RM. 304. PROVIDE NEW THRU-WALL OPENING FOR
NEW DUCT AND DIFFUSER. SEE MECHANICAL.
5 NEW THRU-WALL OPENING FOR TRANSFER DUCT. SEE MECHANICAL.
PROVIDE SOFFIT TO ENCLOSE TRANSFER DUCT. CONSTRUCTION BOTH
SOFFITS IN A SIMILAR MANNER AT SIMILAR HEIGHTS. SEE 3/A6 SIM.
GENERAL NOTES
1. PATCH/REPAIR FLOOR AS REQUIRED TO MATCH ADJACENT AREA WHERE NEW
FCU DOES NOT COMPLETELY COVER OLD LOCATION.
2. PATCH AND REPAIR FLOOR AND WALL TO MATCH ADJACENT AREA WHERE
EQUIPMENT IS PERMANENTLY REMOVED.
3. CLEAN FLOOR AND WALL AT FCUs AS NEEDED AS PART OF PREP FOR NEW FCUs.
4. PATCH AND REPAIR AT NEW WORK TYING INTO ADJACENT AREAS.
A5
ROOF PLAN
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
ROOF PLAN
b
T o d d A
K r k
H
O S
P
B u c k s t a f f
H
V A
C D
W G s
H
O S
P A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
GENERAL NOTES
1. CAP ROOF VENTS AS DIRECTED. SEE MECHANICAL.
2. PATCH AND REPAIR ROOF AS NEEDED AS A RESULT OF INSTALLING
CONDENSING UNIT. SEE MECHANICAL.
CONDENSING UNIT
SEE MECHANICAL
ROOF VENTS-TYP.
ROOF VENTS-TYP.
SEE A4
DETAILS,ELEVATIONS,
SECTIONS
b
T o d d A
K r k
H
O S
P
B u c k s t a f f
H
V A
C D
W G s
H
O S
P A d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
ELEVATION- MECHANICAL PLATFORM
NOT TO SCALE
ELEVATION- PIPE CHASE (TYP.)
FLOOR PLAN KEYNOTES:
1 EXISTING CONCRETE COLUMN
2 WIDE-FLANGE BEAM- HP PAINT. SEE STRUCTURAL
3 2" STEEL OPEN GRATING- SEE STRUCTURAL
4 42"H PIPE RAILING W/ REMOVEABLE SECTIONS- HP PAINT. SEE STRUCTURAL
5 SPRING-LOADED GATE- HP PAINT (IF NOT PREVIOUSLY FINISHED). SEE
STRUCTURAL.
6 EQUIPMENT BEYOND. SEE MECHANICAL & ELECTRICAL.
7 BAR-STEEL LADDER W/ EXTENSIONS, BRACED- HP PAINT. SEE STRUCTURAL
8 EXISTING MARBLE WAINSCOT
9 3/4" SOLID-SURFACE MATERIAL WAINSCOT -MATCH HEIGHT (U.N.O.) AND
HORIZONTAL JOINTING OF EXISTING WAINSCOT. NOTCH AS NEEDED TO ABUT
EXISTING WAINSCOT.
10 NEW GWB PIPE CHASE. SEE 5/A6.
11 EXISTING PLASTER WALL BEYOND
12 PARTIAL HEIGHT PIPE CHASE- HEIGHT TO ALIGN WITH TOP OF FCU. CAP CHASE
W/ SOLID SURFACE MATERIAL. FLATWISE PIECE TO 'CAP' VERT. WALL PIECE.
SEE 5/A6.
13 FCU- SEE MECHANICAL
14 NOT USED
15 1/2" MR TYPE 'X' GYPSUM DRYWALL-BOTH SIDES
16 2-1/2" 25-GAUGE C-CHANNEL (TYP.)
17 17A 2-1/2" 25 -GAUGE METAL STUD @ 16" O.C. 17A -FLATWISE
18 ALIGN FACE OF CHASE WITH FACE OF FCU.
19 SIZE CHASE/SOFFIT TO ACCOMMODATE MECHANICAL PIPING- SEE 2/A2 CHASE
SIZE SCHEDULE. SEE MECHANICAL
20 3-5/8" 25-GAUGE C-CHANNEL (TYP.) INSTALL C-CHANNEL AROUND PERIMETER
AT INFILL AND AT 9/A6.
21 3-5/8" 25 -GAUGE METAL STUD @ 16" O.C.
22 WOOD CROWN MOLDING W/ FRIEZE BOARD- MATCH EXISTING. INSTALL
MOLDING ALONG CEILING ONLY.
23 INFILL OPENING WITH 16 GAUGE GALVANIZED SHEET METAL ON METAL STUD
FRAMING. USE FULL SHEETS. INSTALL SEALANT AT PERIMETER. OVERLAP THE
GALVANIZED STEEL SHEETS 3" WITH SEALANT BEAD BETWEEN SHEETS AND
SEALANT BEAD BETWEEN PERIMETER CHANNEL AND SHEET. MAKE AIRTIGHT.
NOT TO SCALE
ELEVATION- PARTIAL HEIGHT
PIPE CHASE (TYP.)
ALIGN W/ TOP OF FCU
TOP OF CHASE
NOT TO SCALE
SECTION - PIPE SOFFIT @ WALL (TYP.)
NOT TO SCALE
PLAN DETAIL-PIPE CHASE (TYP.)
SECTION-SIM.
A6
A6
FIN. FLOOR FIN. FLOOR
NOT TO SCALE
SECTION - PIPE SOFFIT @ 3RD FLR.
A.FIN.FLR.
8'-8"
NOT TO SCALE
INFILL DETAIL
T.O. WAINSCOT
EXISTING WALL
EXISTING WALL W/
CROWN MOLDING
BEAM BEYOND
BTTM. OF
NOT TO SCALE
WALL EXTENSION DETAIL
SI
M
ALIGN
FIN. FLOOR
NOT TO SCALE
WALL EXTENSION DETAIL
EXISTING CONSTRUCTION
AIR
CHAMBER
B106
EQUIPMENT
RM
B103
17A
REMOVE UPPER CROWN
MOLDING. PATCH AND REPAIR
Fe br ua ry
, 2
7:3 6a m M
0- 0.d wg m gr eg or y
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2024
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239955
SUB SHEET NO.
OF
DESIGNED:
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE. 51
FINAL CONSTRUCTION DOCUMENTS
MRG
MRG
BAH
MECHANICAL SYMBOLS
AND ABBREVIATIONSM0-0
F
SM
FHC
FVC
PIV
FS
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
FIRE PROTECTION
FIRE LINE
CEILING CLEAN AGENT NOZZLE FLUSH FIRE PUMP TEST HEADERSPRINKLER MAIN
SUB-FLOOR CLEAN AGENT NOZZLE FREE-STANDING FIRE PUMP TEST HEADERCLEAN AGENT
CEILING DETECTOR FREE-STANDING FIRE DEPARTMENT CONNECTIONSPRINKLER BRANCH AND HEADS
SUB-FLOOR DETECTOR FLUSH FIRE DEPARTMENT CONNECTIONRECESSED PENDANT SPRINKLER
CLEAN AGENT ALARM BELL FIRE DEPARTMENT CONNECTIONCONCEALED PENDANT SPRINKLER
CLEAN AGENT HORN WITH STROBE FIRE HOSE CABINETUPRIGHT SPRINKLER
ELECTRIC PULL STATION FIRE HOSE VALVE CABINETDRY PENDANT SPRINKLER
ABORT PULL STATION POST INDICATOR VALVEHORIZONTAL SIDEWALL SPRINKLER
CLEAN AGENT PRESSURE SWITCH ISOLATION VALVE WITH TAMPER SWITCHDRY HORIZONTAL SIDEWALL SPRINKLER
WARNING LIGHT ALARM CHECK VALVEPRE-ACTION HEAT DETECTOR
CLEAN AGENT PANEL DRY PIPE VALVEPRE-ACTION PULL STATION
FIRE HYDRANT FLOW SWITCHPRE-ACTION ALARM BELL
ALARM BELL WATER FLOW SWITCHPRE-ACTION TROUBLE STROBE
ALARM STROBEDELUGE VALVE FOR PRE-ACTION SYSTEM
PRE-ACTION RELEASING PANEL FIRE DEPARTMENT HOSE VALVE
CA
PA
CAP
MECHANICAL SYMBOLS MECHANICAL SYMBOLS
SYMBOLS INDICATED HERE AND NOT USED IN THE
CONTRACT DOCUMENTS DO NOT APPLY TO THIS
PROJECT. ADDITIONAL SYMBOLS AND ABBREVIATIONS
MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
FINTUBE-TYPE (SHADED AREA INDICATES
CAPACITY MBH ELEMENT LOCATION)
VOLUME DAMPER
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
HEATING - VENTILATING - AIR-CONDITIONING
T RS
T
H
A
S
P T
FS
AD
L"
D"
FT-1
MBH
XØ
X/X
SD
M
CFM
SIZE TYPE
CFM
SIZE TYPE
FRD
FSD
M
MCO2
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE OR BOILER FEED PUMP DISCHARGE
CONDENSER WATER SUPPLY FROM TOWER
CONDENSER WATER RETURN TO TOWER
COIL OR EQUIPMENT DRAIN
THERMAL HOT WATER
THERMAL COLD WATER
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
NATURAL GAS
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HIGH PRESSURE CONDENSATE RETURN
HIGH PRESSURE STEAM
HOT WATER SUPPLY
HOT WATER RETURN
LOW PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE RETURN
MEDIUM PRESSURE STEAM
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS DISCHARGE
BACK-DRAFT DAMPER (COUNTER BALANCED)B.D.D.
LPS
MPS
HPS
LPR
MPR
HPR
HWS
HWR
THW
TCW
CWS
CWR
PC
FOS
FOR
FOV
G
RL
RS
RD
CS
CR
CD
#/HR
HPWS
HPWR
PIPE IN SLEEVE
VALVE IN VERTICAL PIPE
F AND T TRAP CAP LBS/HR
BUCKET TRAP CAP LBS/HR
AIR QUALITY SENSOR
C02 SENSOR
HUMIDISTAT
REMOTE SENSOR
THERMOSTAT
THERMOSTAT WITH REMOTE SENSOR
AQUASTAT
SOLENOID VALVE (REFRIGERANT)
THERMOSTATIC EXPANSION VALVE (REFRIGERANT)
SIGHT GLASS
MANUAL AIR VENT
PRESSURE OR TEMPERATURE MEASURING POINTS
FLOW SWITCH
HEATING RISER
ACCESS DOOR - SIZE AS SHOWN OR PER SPEC.
EXPANSION LOOP, LENGTH AND DEPTH
NEW TO EXISTING CONNECTION
#/HR
AQ
RECTANGULAR DUCTWORK
(FIRST NUMBER IS SIDE SHOWN)X/X
ROUND DUCT
FLAT OVAL (FIRST NUMBER IS THE SIDE SHOWN)
MOTORIZED DAMPER
FIRE DAMPER WITH ACCESS DOOR
COMBINATION FIRE AND SMOKE DAMPER
WITH ACCESS DOOR
SMOKE DAMPER WITH ACCESS DOOR
SOUND ATTENUATOR
FLEX CONNECTION
SUPPLY REGISTER OR GRILLE
RETURN REGISTER OR GRILLE
SA
TYP DIFFUSER NECK SIZE, MARK
CFM
X X X
X X X
SUPPLY, OUTDOOR, OR MIXED AIR DUCT
END OR RISER (SA) (OA) (MA)
RETURN EXHAUST OR RELIEF AIR DUCT
END OR RISER (RA) (EA) (RLFA)
TYP EXHAUST/RETURN GRILLE NECK SIZE, MARK
CFM
TURNING VANES
MECHANICAL/ELECTRICAL COORDINATION SCHEDULE
MECHANICAL EQUIPMENT WITH ELEC CONNECTION SEE
AUTOMATIC CONTROL VALVE, 2-WAY
AUTOMATIC CONTROL VALVE, 3-WAY
PRESSURE REGULATING VALVE (PRV)
X X
POINT OF DISCONNECT BREAK / CONTINUATION
T
OR
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
PIPING
R
PTT
TEE
ELBOW
UNION
STRAINER WITH DRAIN VALVE AND HOSE END
BALANCING VALVE
ISOLATION VALVE (BALL OR BUTTERFLY)
PRESSURE RELIEF VALVE
ELBOW UP
ELBOW DOWN
GLOBE VALVE
PRESS / TEMP TEST PORT
GATE VALVE
CHECK VALVE (ARROW INDICATES FLOW)
FLEXIBLE PIPING
AUTOMATIC AIR VENT
MANUAL AIR VENT WITH ISOLATION VALVE
CONCENTRIC REDUCER
ECCENTRIC REDUCER
PRESSURE GAUGE WITH GAUGE COCK
THERMOMETER, SIDE FEED
THERMOMETER, BOTTOM FEED
ARROW INDICATES FLOW DIRECTION
ARROW INDICATES DOWNWARD PIPE PITCH
WATER METERM
S
S
SS
AW
AW
S
S
OF
OF
SS
AW
AW
AV
V
140°
140°
SS
W
S
S
S
A
V
GCO
HB
WH
Y.H.
BFP
_ FD-X
_ FS-X
_ RD-X
DS
MH
VTR
SH
EXISTING SANITARY DRAIN (ABOVE FLOOR)
VENT
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
PLUMBING
EXISTING SANITARY SEWER (BELOW FLOOR)
HOT WATER CIRCULATING 140°
GRADE CLEAN OUT
EXISTING STORM DRAIN (ABOVE FLOOR)
OVERFLOW STORM DRAIN (ABOVE FLOOR)
DOUBLE GRADE CLEAN-OUT
EXISTING STORM DRAIN (BELOW FLOOR)
OVERFLOW STORM DRAIN (BELOW FLOOR)
HOSE BIBB
EXISTING SUB SOIL DRAIN
SANITARY DRAIN (ABOVE FLOOR)
WALL HYDRANT (NON-FREEZE TYPE)
EXISTING ACID WASTE (ABOVE FLOOR)
SANITARY SEWER (BELOW FLOOR)
YARD HYDRANT
EXISTING ACID WASTE (BELOW FLOOR)
BACK FLOW PREVENTER
SITE STORM SEWER
FLOOR DRAIN SIZE-TYPE
SITE WATER PIPING
FLOOR SINK SIZE-TYPE
STORM DRAIN (BELOW FLOOR)
ROOF DRAIN SIZE-TYPE
SUB SOIL DRAIN
DOWN SPOUT
MANHOLE
ACID WASTE (ABOVE FLOOR)
VACUUM BREAKER
ACID WASTE (BELOW FLOOR)
GAS COCK
ACID VENT
RUNNING TRAP
VENT THROUGH ROOF ON RISER
PLUMBING RISER NUMBER
SHOWER
COLD WATER (CW)
COLD SOFT WATER
COMPRESSED AIR
HOT WATER (HW)
HOT WATER CIRCULATING (HWC)
HOT SOFT WATER
HOT SOFT WATER RECIRCULATING
STORM DRAIN (ABOVE FLOOR)
HOT WATER 140°
CLEAN OUT
NATURAL GASG
ORCO CO
BLDG BUILDING
BTUH BRITISH THERMAL UNIT PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CLG CEILING
CLR CLEAR
CRAC
CV CONSTANT VOLUME
DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EL ELEVATION
EHC ELECTRIC HEATING COIL
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
FA FIRE ALARM
FL FLOOR
FT FEET
PWR POWER
PVC POLYVINYL CHLORIDE
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
PNL PANEL
PLBG PLUMBING
PIV POST INDICATOR VALVE
RM ROOM
RH RELATIVE HUMIDITY
REQD REQUIRED
RLFA RELIEF AIR
RA RETURN AIR
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UL UNDERWRITERS LABORATORY
UG UNDERGROUND
TYP TYPICAL
TEMP TEMPERATURE
STD STANDARD
SS STAINLESS STEEL
SPECS SPECIFICATIONS
SIM SIMILAR
SCHD SCHEDULE
SAN SANITARY
SA SUPPLY AIR
NC NORMALLY CLOSED
MTD MOUNTED
MISC MISCELLANEOUS
MIN MINIMUM
MECH MECHANICAL
MAX MAXIMUM
LBS POUNDS
KW KILOWATT
OC ON CENTER
OA OUTDOOR AIR
NTS NOT TO SCALE
NOM NOMINAL
NO NORMALLY OPEN
NIC NOT IN CONTRACT
GA GAUGE
HVAC HEATING, VENTILATING
HTG HEATING
HP HORSEPOWER
HGT HEIGHT
GPM GALLONS PER MINUTE
GEN GENERATOR
GALV GALVANIZED
AND AIR CONDITIONING
ELEC ELECTRICAL
DIA
CPVC
DX DIRECT EXPANSION
EPO EMERGENCY POWER OFF
F FIRE WATER
FCO FLOOR CLEAN OUT
FDC FIRE DEPARTMENT CONNECTION
FHC FIRE HOSE CABINET
FW FILTERED WATER
GC GENERAL CONTRACTOR
MBH 1000 BTU/HOUR
NPW NON-POTABLE WATER
PS PLASTER SINK
RO REVERSE OSMOSIS WATER
SCW SOFT COLD WATER
SM SPRINKLER MAIN
SMACNA SHEET METAL AND AIR
CONDITIONING CONTRACTORS'
BTU BRITISH THERMAL UNIT
PERP PERPENDICULAR
RGS RIGID GALVANIZED STEEL
HZ HERTZ, HIGH ZONE WET STANDPIPE
CFH CUBIC FEET PER HOUR
SHW SOFT HOT WATER
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MOA MINIMUM OUTDOOR AIR
EOA ECONOMIZER OUTDOOR AIR
IE INVERT ELEVATION
NATIONAL ASSOCIATION
AHJ
ASHRAE
AUX
AV
AW
AWG
BFP
AUTHORITY HAVING JURISDICTION
AMERICAN SOCIETY OF HEATING,
REFRIGERATING AND
AIR-CONDITIONING ENGINEERS
AUXILIARY
ACID VENT
ACID WASTE
AMERICAN WIRE GAUGE
DOUBLE CHECK BACKFLOW
VOLT-AMPS
VERTICAL
VARIABLE FREQUENCY CONTROL
VENT THROUGH ROOF
WATT
WEATHERPROOF
TRANSFORMER
VA
VERT
VFC
VTR
W
WP
XFMR
AFF ABOVE FINISHED FLOOR
AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
STANDARD SPECIFICATIONS OF
THE AMERICAN SOCIETY FOR
ASME
ASTM
TESTING MATERIALS
AVG AVERAGE
BMCS BUILDING MANAGEMENT
EMS ENERGY MANAGEMENT SYSTEM
IP INTERNET PROTOCOL
NATIONAL FIRE PROTECTION
ASSOCIATION
NFPA
WATER GAUGEWG
CHLORINATED POLYVINYL CHLORIDE
COMPUTER ROOM AIR CONDITIONER
MA MIXED AIR
CONTROL SYSTEM
ABBREVIATIONS
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
PREVENTER RPZ REDUCED PRESSURE ZONE
BACKFLOW PREVENTER
LZ LOW ZONE WET STANDPIPE
GW GARAGE WASTE
FHV FIRE HOSE VALVE
DDCV DOUBLE DETECTOR CHECK VALVE
ASSEMBLY BACKFLOW PREVENTER
DPAC DRY PIPE AIR COMPRESSOR
DPV DRY PIPE VALVE
12 60
Fe br ua ry
, 2
7:3 6a m M
0- 1.d wg m gr eg or y
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2024
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239955
SUB SHEET NO.
OF
DESIGNED:
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE. 51
FINAL CONSTRUCTION DOCUMENTS
MECHANICAL
GENERAL NOTESM0-1
DEMOLITION NOTES:
1. THE OWNER SHALL HAVE THE FIRST RIGHT OF SALVAGE FOR ALL MECHANICAL,
ELECTRICAL, AND PLUMBING ITEMS BEING REMOVED. IF OWNER DECLINES, THE
CONTRACTOR SHALL REMOVE FROM THE PREMISES AND DISPOSE OF PROPERLY.
VERIFY OWNER'S INTENT PRIOR TO REMOVAL OR DEMOLITION.
2. INFORMATION PERTAINING TO THE EXISTING BUILDING HAS BEEN OBTAINED THROUGH
ON-SITE FIELD VERIFICATION. REPORT DISCREPANCIES TO THE ARCHITECT/ENGINEER
PRIOR TO ANY DEMOLITION. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS PRIOR TO COMMENCING WORK.
3. COORDINATE SHUT DOWN OF ALL UTILITIES FOR DEMOLITION WORK WITH THE OWNER.
4. DISCONNECT AND REMOVE MECHANICAL SYSTEMS, EQUIPMENT, AND COMPONENTS AS
INDICATED TO BE REMOVED.
PIPING TO BE REMOVED: REMOVE PORTION OF PIPING INDICATED TO BE REMOVED AND
CAP REMAINING PIPING WITH THE SAME OR COMPATIBLE PIPING MATERIAL.
PIPING TO BE ABANDONED IN PLACE: DRAIN PIPING AND CAP WITH THE SAME OR
COMPATIBLE PIPING MATERIAL.
DUCTS TO BE REMOVED: REMOVE PORTIONS OF DUCT AND CAP REMAINING DUCTS
WITH THE SAME OR COMPATIBLE DUCTWORK MATERIAL.
DUCTS TO BE ABANDONED IN PLACE: CAP DUCTS WITH THE SAME OR COMPATIBLE
DUCTWORK MATERIAL.
EQUIPMENT TO BE REMOVED: DISCONNECT AND CAP SERVICES AND REMOVE
EQUIPMENT.
EQUIPMENT TO BE REMOVED AND REINSTALLED: DISCONNECT AND CAP SERVICES AND
REMOVE, CLEAN, AND STORE EQUIPMENT. WHEN APPROPRIATE, REINSTALL,
RECONNECT, AND MAKE EQUIPMENT FULLY OPERATIONAL.
EQUIPMENT TO BE REMOVED AND SALVAGED: DISCONNECT AND CAP SERVICES AND
REMOVE EQUIPMENT AND DELIVER TO OWNER.
5. IF PIPE OR EQUIPMENT INSULATION TO REMAIN IS DAMAGED IN APPEARANCE OR IS
UNSERVICEABLE, REMOVE DAMAGED OR UNSERVICEABLE PORTIONS AND REPLACE
WITH NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY.
6. CONTRACTOR IS REQUIRED TO VISIT SITE AND FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO BIDDING PROJECT.
7. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY
UTILITIES AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
8. DUCTWORK, PIPING, PLUMBING, AND EQUIPMENT SHOWN BOLD SHALL BE REMOVED TO
THE EXTENTS INDICATED.
HVAC GENERAL NOTES:
1. DO NOT RUN DUCTWORK , PIPING, AND PLUMBING ABOVE ELECTRICAL
PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL
ROUTING WORK WITH ALL OTHER TRADES.
2. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL
LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,
INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION
CHANGES TO DUCTWORK, PIPING, AND PLUMBING AS REQUIRED TO
COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET
ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.
3. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR DIFFUSER,
REGISTER, GRILLE, AND CEILING MOUNTED DEVICE LOCATIONS.
4. CONTRACTOR SHALL COORDINATE LOCATION OF DUCTWORK IN CEILING
SPACE WITH ALL TRADES PRIOR TO FABRICATION AND INSTALLATION OF
DUCTWORK.
5. FOR GENERAL DUCTWORK CONSTRUCTION, SEE DUCT FITTING DETAILS.
6. DUCTWORK AND EQUIPMENT SHOWN WITH THIN LINES INDICATES EXISTING
TO REMAIN. DUCTWORK AND EQUIPMENT SHOWN WITH BOLD LINES
INDICATES NEW.
7. PROVIDE VOLUME DAMPER IN ALL BRANCH TAKEOFFS CONNECTING TO
DIFFUSERS, REGISTERS, OR GRILLES AND IN LOCATIONS INDICATED.
8. PROVIDE REMOTE VOLUME DAMPER BALANCING POSITION CONTROL FOR
ALL VOLUME DAMPERS MOUNTED ABOVE NON-ACCESSIBLE CEILINGS.
9. PROVIDE CLEARANCES TO ALL EQUIPMENT AS REQUIRED BY
MANUFACTURERS' INSTALLATION AND OPERATION REQUIREMENTS AND/OR
BY CODE.
10. INSTALL ALL DUCT AND PIPING IN MECHANICAL ROOMS AS HIGH AS
POSSIBLE. PROVIDE 7'-6" MINIMUM HIGH ACCESS PATHWAYS TO ALL
EQUIPMENT WHERE POSSIBLE.
11. COORDINATE LOCATIONS OF ALL EQUIPMENT HOUSEKEEPING PADS WITH
GENERAL CONTRACTOR. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR
INSTALLATION OF EQUIPMENT HOUSEKEEPING PADS.
12. CAP ENDS OF ALL INSTALLED DUCTWORK DURING CONSTRUCTION TO
MINIMIZE DIRT, DEBRIS, AND FOREIGN OBJECTS FROM ENTERING THE DUCT
SYSTEM.
13. COORDINATE SCHEDULE OF SHUTDOWN FOR EXISTING HVAC SYSTEMS,
FOR INSTALLATION OF NEW HVAC SYSTEMS, WITH THE OWNER'S
REPRESENTATIVE PRIOR TO SHUTDOWN.
14. ALL INSULATION SHALL MEET THE ENERGY CODE'S INSTALLED R VALUE
REQUIREMENTS.
15. PERFORM FUNCTIONAL PERFORMANCE TESTING FOR HVAC SYSTEM AND
SUBMIT DOCUMENTATION REQUIRED BY 2018 IECC SECTION C408.2 TO THE
BUILDING OWNER OR OWNER'S AUTHORIZED AGENT WITHIN 90 DAYS OF
THE RECEIPT OF CERTIFICATE OF OCCUPANCY.
1. THIN LINE ITEMS INDICATE EXISTING TO REMAIN. BOLD LINE ITEMS INDICATE
NEW WORK.
2. CONTRACTOR IS RESPONSIBLE FOR ANY CUTTING AND PATCHING NEEDED
FOR MECHANICAL INSTALLATION. PATCHING MUST MATCH EXISTING.
GENERAL NOTES:PIPING GENERAL NOTES:
1. DO NOT RUN PIPING, PLUMBING, AND DUCTWORK ABOVE ELECTRICAL
PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL
ROUTING WORK WITH ALL OTHER TRADES.
2. DRAWINGS, PLANS, SCHEMATICS, AND DIAGRAMS INDICATE THE GENERAL
LOCATIONS AND THE ARRANGEMENT OF SYSTEMS. WHEREVER PRACTICAL,
INSTALL SYSTEMS AS INDICATED. PROVIDE OFFSETS AND ELEVATION
CHANGES TO PIPING, PLUMBING, AND DUCTWORK AS REQUIRED TO
COMPLETE THE LAYOUT AND COORDINATION PROCESS AS WELL AS MEET
ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS.
3. SIZE AND ROUTE REFRIGERANT PIPING PER MANUFACTURERS'
RECOMMENDATIONS.
4. ROUTE ALL HORIZONTAL HVAC PIPING IN MECHANICAL ROOMS AT A
MINIMUM OF 7'-6" ABOVE FINISHED FLOOR WHERE POSSIBLE.
5. PIPING AND EQUIPMENT SHOWN WITH THIN LINES INDICATES EXISTING TO
REMAIN. PIPING AND EQUIPMENT SHOWN WITH BOLD LINES INDICATES NEW.
6. SEE SCHEDULES FOR SIZES OF BRANCH RUNOUTS TO EQUIPMENT.
7. ALL PIPING INSULATION SHALL MEET THE ENERGY CODE'S INSTALLED R
VALUE REQUIREMENTS.
8. DIELECTRIC NIPPLES OR FLANGE INSULATION KITS SHALL BE UTILIZED FOR
ALL DISSIMILAR PIPE CONNECTIONS. DIELECTRIC UNIONS WILL NOT BE
ACCEPTED.
MRG
MRG
BAH
THW TCW
6 6
14 14
DUMBWAITER
DW1
LAUNDRY
B109
STORAGE
B110
LINEN ROOM
B108
AIR
CHAMBER
B104A
WIND TUNNEL
B104
HALL
B104B
EQUIPMENT
ROOM
B103
AIR
DISTRIBUTION
CHAMBER
B106
STORAGE
B107
TOOL ROOM
B102
STORAGE
B101
BOILER ROOM
B100
HALL
B105
TCW
EXISTING TO CREEK ARCH
G
G
G
G
G G
G
EXISTING
1 1/2"
NAT GAS
EXISTING
GAS
DRYERS
EXIST.
WASHER
EXISTING LAUNDRY
WATER HEATER
Fe br ua ry
, 2
7:3 6a m M
1- 1.d wg m gr eg or y
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS
and clearances from ARCHITECTURAL, STRUCTURAL, shop and other appropriate drawing or at site. lay out and coordinate all work prior to installation to provide clearances required for operation, maintenance, and codes and verify non-interference with other work. DO NOT FABRICATE
PRIOR TO VERIFICATION OF CLEARANCE FOR ALL
TRADES. READ SPECIFICATIONS.
COPYRIGHT 2024
Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Alvine Engineering is prohibited by copyright law.
AE# 20239955
SUB SHEET NO.
OF
DESIGNED:
BUCKSTAFF BATHHOUSE HVAC
HOT SPRINGS NATIONAL PARK
HOT SPRINGS, AK
XXX/XXXX
177425
DRAWN BY:
TECH. REVIEW:
DATE:
2/15/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE. 51
FINAL CONSTRUCTION DOCUMENTSBASEMENT FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/8" = 1'-0"
8 16 24 32 4042
BASEMENT FLOOR PLAN -
MECHANICAL DEMOLITIONM1-1
FLAG NOTES
REMOVE EXISTING BOILER COMPLETE INCLUDING ALL ASSOCIATED ABANDONED
STEAM AND CONDENSATE RETURN PIPING COMPLETE SHOWN BOLD. VERIFY
PIPING IN FIELD.
REMOVE EXISTING BOILER BREACHING SHOWN BOLD COMPLETE.
COORDINATE WITH GENERAL CONTRACTOR INFILL OF EXISTING REMAINING
OPENING IN CHIMNEY WALL ONCE BREACHING IS REMOVED.
REMOVE ABANDONED TANK ABOVE NORTH BOILER SHOWN BOLD COMPLETE
INCLUDING ASSOCIATED PIPING. PIPING NOT SHOWN FOR CLARITY.
EXISTING VENTILATION DUCTWORK SHOWN TO REMAIN AND BE REUSED.
REMOVE EXISTING 3" THERMAL HOT WATER PIPING SHOWN BOLD COMPLETE.
REMOVE EXISTING VENTILATION FAN SHOWN BOLD. COMPLETE INCLUDING BELT &
GUARD AND FAN MOTOR.
REMOVE EXISTING HEAT COIL INCLUDING COIL BASE AND ASSOCIATED
VENTILATION DUCTWORK SHOWN BOLD COMPLETE.
REMOVE EXISTING 3" THERMAL HOT WATER PIPING SHOWN BOLD. CAP REMAINING
PIPING WHERE SHOWN.
REMOVE EXISTING DAMPER ASSEMBLIES IN WALL BELOW COIL SHOWN BOLD
COMPLETE. REMOVE DAMPER ACTUATOR AND TEMPERATURE CONTROL AIR LINES
AND DEVICE WIRING SERVING DAMPER ACTUATOR.
REMOVE EXISTING DAMPER ASSEMBLIES IN EXTERIOR WALL SHOWN BOLD
COMPLETE. REMOVE DAMPER ACTUATOR AND TEMPERATURE CONTROL AIR LINES
AND DEVICE WIRING SERVING DAMPER ACTUATOR.
EXISTING THERMAL HOT AND THERMAL COLD WATER PIPING SHALL REMAIN.
REMOVE EXISTING CONDENSING UNIT SHOWN BOLD SERVING GROUND FLOOR
FURNACE. TURN OVER REMOVED EQUIPMENT TO GOVERNMENT'S
REPRESENTATIVE.
REMOVE EXISTING THERMAL HOT WATER SUPPLY AND RETURN PIPING IN
CRAWLSPACE SHOWN DARK WHICH SERVES EXISTING FAN COIL UNIT SYSTEM.
PIPING INDICATED ON PLAN IS DIAGRAMMATIC. CONTRACTOR SHALL VERIFY PIPE
SIZES AND EXTENT OF EXISTING ROUTING IN FIELD.
REMOVE ABANDONED 6" STEAM PIPING INCLUDING VALVES AND FITTINGS SHOWN
DARK COMPLETE.
REMOVE ABANDONED 2" WATER PIPING SHOWN BOLD BACK TO MAIN AND CAP.
FIELD VERIFY EXISTING CONDITIONS.
REMOVE EXISTING 2" NATURAL GAS PIPING SHOWN BOLD. REMOVE OUT TO
EXISTING GAS METER LOCATED AT WEST SIDE OF BUILDING.
EXISTING 2" GAS PIPING TO REMAIN AND BE REUSED. CONTRACTOR TO VERIFY
PIPE SIZE FOR RECONNECTION TO NEW GAS UTILITY PIPING.
EXISTING 3" THERMAL HOT WATER RETURN TO CREEK OUTSIDE OF BUILDING TO
REMAIN AND BE REUSED.
REMOVE EXTERIOR HOSE BIBB AND WATER LINE SERVING HOSE BIBB BACK TO
MAIN AND CAP. FIELD VERIFY EXISTING CONDITIONS.
EXISTING COLD WATER LINE SHALL BE REMOVED AND RELOCATED WITH NEW
LOCATION TO BE DETERMINED IN THE FIELD. COORDINATE RELOCATING THIS LINE
BASED ON FINAL DUCTWORK AND PIPING TO BE INSTALLED THROUGH EXISTING
BOILER ROOM. FINAL LOCATION OF RELOCATED WATER LINE SHALL BE MADE ONCE
DUCTWORK AND PIPING IS INSTALLED IN SPACE.
REMOVE EXISTING PNEUMATIC TEMPERATURE CONTROL AIR COMPRESSOR,
CONTROL AIR REFRIGERATED AIR DRYER AND EXISTING PNEUMATIC
TEMPERATURE CONTROL PANEL COMPLETE INCLUDING CONTROL WIRING AND
CONTROL AIR LINES SHOWN BOLD.
REMOVE PORTION OF EXISTING 2" THERMAL HOT WATER PIPING SHOWN BOLD TO
MAKE ROOM FOR NEW HVAC DUCTWORK AT EXISTING WALL OPENING AT WEST END
OF ROOM.
REMOVE PORTION OF EXISTING 3/4" COLD WATER PIPING SHOWN BOLD.
MRG
MRG
UP UP
UPUP
COUNTER
1 1
1 1
6 6 6 7 7 7
T
T
EXISTING
GRILLE
EX
IS
TI
NG
GR
ILL
E
EXISTING
GRILLE
EXISTING
GRILLE
EXISTING
GRILLE
EX
IS
TI
NG
GR
ILL
E
EXISTING
GRILLE
EX
IS
TI
NG
GR
ILL
E
EX
IS
TI
NG
GR
ILL
E
EX
IS
TI
NG
GR
ILL
E
EXISTING
GRILLE
EX
IS
TI
NG
GR
ILL
E
EX
IS
TI
NG
GR
ILL
E
EX
IS
TI
NG
GR
ILL
E
EXISTING
GRILLE
EXISTING
GRILLE
EX
IS
TI
NG
GR
ILL
E
EX
IS
TI
NG
GR
ILL
E
EXISTING
GRILLE
EX
IS
TI
NG
GR
ILL
E
EXISTING
GRILL
E
EX
IS
TI
NG
GR
ILL
E
EXISTING
GRILLE
TOILET
MASSAGE
MASSAGE
107A
VEST.
106B
This is the start of the file's text. The full file is on GovTribe.