B08_Attachment_5_1-_Construction_Zones__APE_and_Laydown_Areas.pdf
PDF 6 MB Posted
- Solicitation number
- 140P2022R0023
About this file
This document package includes construction drawings and schematics for rehabilitating the electrical system at Kalaupapa National Historical Park on Molokai Island in Hawaii. The project involves replacing overhead electrical cabling and poles throughout the park and burial of new underground lines along roads connecting park facilities. Work zones, areas of potential effect, and contractor laydown areas are delineated on the drawings. Improvements are needed to address unsafe and failing electrical infrastructure. Relevant details include the solicitation number for this opportunity, the scope of work involving electrical line and system upgrades, and the involved agency as the National Park Service National Office.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B09_Amendment_01_Q_A_0001.xlsx | XLSX spreadsheet | |
| Sol_140P2022R0023_Amd_0001.pdf | ||
| B08_NPS_Data___Materials_3.zip | ZIP file | |
| B08_Attachment_5_3-_HECO_General_Expectations_for_Design_Review_Stages.pdf | ||
| B08_Davis_Bacon_WD_HI20220001_07082022.pdf | ||
| B08_Attachment_5_2-_SubmittalList-ReviewEstimate_Template_1-27-21_v508.pdf | ||
| B08_Memo_Certification_of_Vaccination_Form.pdf | ||
| B08_SF24-16d_Bid_Bond.pdf | ||
| B08_Solit_PSP_Vol_I_PastPerf_REQD.docx | DOCX document | |
| B08_NPS_Data___Materials_2.zip | ZIP file | |
| B08_Solit_PSP_Vol_I_Exp_REQD.docx | DOCX document | |
| B08_LmtOnSubconRpt_REQD.xlsx | XLSX spreadsheet | |
| B08_Solit_PSP_Vol_II_PriceSched.xlsx | XLSX spreadsheet | |
| B08_NPS_Data___Materials_1.zip | ZIP file | |
| B08_SF330-21.pdf | ||
| B08_KALA_217676_DB_RFP_SOW_06212022.docx | DOCX document | |
| B08_Certification_of_Vaccination_Form.pdf | ||
| B08_Solit_PSP_Vol_II_GenRefs.doc | DOC document | |
| Sol_140P2022R0023.pdf |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lighthouse
Cemetery
Demolish existing overhead electrical.
Cabling to be removed and poles to be cut off at grade and removed.
Install new overhead electrical at traditional settlement spacing and pole height.
20 10
Detail 2 Detail 3
Detail 1
´0 210 420ft.
Scale 1:5,3001 inch = 442 ft.
Legend Existing System
Pole
Pad Mounted Transformer
Pole Mounted Transformer
Electrical Line Comm/Guy Line Notes:
1. Source: unknown date, NPS-provided CAD file named "KALA_utilities.dwg"
2. Source: 1983, Reconstruct Water System Dwg, Sheets 10 & 11
Additions & Upgrades - Electrical Line System New Pole
Replace Pole
Remove Pole
Replace Pole Mounted Transformer
Replace Pad Mounted Transformer
Replace Pole & Pole Mounted Transformer
New Above Ground Line
New Below Ground Line
Upgrade Existing Line
Remove Cabling
Existing Water Line1
Existing Water Line
FIGURE 1- Detail 1 Construction Zones, Areas of
Potential Effect and Laydown Areas
National Park Service U.S. Department of the Interior
Kalaupapa National Historic Park
L imits of Construction and Laydown Areas
3,633.8 ft
For Continuation, See Figure 2 - Detail 2
Construction Zones, Area of Potential Effects (APE) and Laydown Areas
Zone 2- See Section A on Figure 5
Zone 2- APE
Zone 1- APE
Zone 3- APE
Schematic Design-
Schematic Design-
Notes: APE boundary is not to scale. The area is based on completed surveys.
Zone 2
Cemetery
McVeigh Home
Paschoal Hall
Bishop Home for Girls
Bayview Home
MECO power line ends
New buried electrical under existing road.
Maintain 36-inch minimum horizontal clerance from waterline in accordance with RUS Electric standards.
Restore trench to match existing with gravel surfacing or grass.
18.4
Replace 3 Transformers
Replace 3 Transformers
Replace 3 Transformers
Replace 3 Transformers
Detail 1
Detail 3 Detail 2
´ 0 190 380ft.
Scale 1:4,7001 inch = 392 ft.
Legend Existing System
Pole
Pad Mounted Transformer
Pole Mounted Transformer
Electrical Line Comm/Guy Line Notes:
1. Source: unknown date, NPS-provided CAD file named "KALA_utilities.dwg"
2. Source: 1983, Reconstruct Water System Dwg, Sheets 10 & 11
Additions & Upgrades - Electrical Line System New Pole
Replace Pole
Remove Pole
Replace Pole Mounted Transformer
Replace Pad Mounted Transformer
Replace Pole & Pole Mounted Transformer
Hand Hole
New Above Ground Line
New Below Ground Line
Upgrade Existing Line
Remove Cabling
Existing Water Line1
Existing Water Line2
FIGURE 2 - Detail 2 Construction Zones, Areas of Potential Effect and Laydown Areas
National Park Service U.S. Department of the Interior
Kalaupapa National Historic Park
For Continuation, See Figure 3- Detail 3
For Continuation, See Figure 1 - Detail 1
9.
ft
Contractor Laydown Area
Contractor Laydown Area
Construction Zones, Area of Potential Effects and Laydown Areas
Zone 2- APE
Zone 1- APE
Zone 3- APE Contractor Laydown Areas
Schematic Design-
Notes: APE boundary is not to scale. The area is
Zone 1
New buried electrical.
Maintain 36-inch minimum horizontal clerance from waterline in accordance with RUS Electric standards. Restore trench to match existing with gravel surfacing or grass.
Existing Water Tanks
Existing 6" Waterline
Existing Pump Station
Existing Water Valve Box
Existing 6" Waterline
Existing 6" Waterline
Detail 1
Detail 2 Detail 3
´ 0 210 420ft.
Scale 1:5,2001 inch = 433 ft.
Legend Existing System
Pole
Pad Mounted Transformer
Pole Mounted Transformer
Electrical Line Comm/Guy Line Notes:
1. Source: unknown date, NPS-provided CAD file named "KALA_utilities.dwg"
2. Source: 1983, Reconstruct Water System Dwg, Sheets 10 & 11
Additions & Upgrades - Electrical Line System New Pole
Replace Pole
Remove Pole
Replace Pole Mounted Transformer
Replace Pad Mounted Transformer
Replace Pole & Pole Mounted Transformer
Hand Hole
New Above Ground Line
New Below Ground Line
Upgrade Existing Line
Remove Cabling
Existing Water Line1
Existing Water Line i FIGURE 3 - Detail 3 Construction Zones, Areas of Potential Effect and Laydown Areas Potential Effect and Laydown Areas
National Park Service U.S. Department of the Interior
Kalaupapa National Historic Park
See Figure 4
For Continuation, See Figure 2 - Detail 2
7,858.9 ft
Contractor Laydown Area
Zone 2- APE
Zone 1- APE
Zone 3- APE Notes: APE boundary is not to scale. The area is based on completed surveys.
Zone 3- See Section B on Figure 5 Zone 3- See Section
C on Figure 5
Schematic Design-
Construction Zones, Area of Potential Effects and Laydown Areas
Contractor Laydown Areas
Zone 3
13001200
11001000
900800700600500
Detail 1
Detail 2 Detail 3
Zoom 3´ 0 60 120ft.
Scale 1:1,536
Legend
Existing System
Pole
Pad Mounted Transformer
Pole Mounted Transformer
Electrical Line
Comm/Guy Line
1 inch = 128 ft.
FIGURE 4 - Water Treatment Facility Construction Zones, Areas of Potential Effect and Laydown Areas
Kalaupapa National Historic Park
National Park Service U.S. Department of the Interior
Additions & Upgrades - Electrical Line System
New Pole
Replace Pole
Remove Pole
Replace Pole Mounted Transformer
Replace Pad Mounted Transformer
Replace Pole & Pole Mounted Transformer
New Above Ground Line
New Below Ground Line
Upgrade Existing Line
Remove Cabling
Existing Water Line 1
Existing Water Line 2
100' Contour
Protect Existing Well
Demolish Existing Small Fuel Storage Tank
Demolish Gable Wall
Existing 6" Waterline
Demolish Existing Generators
Remove existing trees in vicinity of the building and grade area to support new electrical enclosure and transformer pad
Install new power under existing road
Demolish Existing Large Fuel Storage Tank
Existing Water Tanks
Install new buried power under existing road
Notes:
1. Source: unknown date, NPS-provided CAD file named "KALA_utilities.dwg"
2. Source: 1983, Reconstruct Water System Dwg, Sheets 10 & 11
Demolish Existing Storage Shed
Zone 2- APE
Zone 1- APE Zone 3- APE
Notes: APE boundary is not to scale. The area is
Construction Zones, Area of Potential Effects and Laydown Areas
A
OVERHEAD ELECTRIC ALONG AIRPORT RD
NTS
PROPOSED POWERPOLE
DISTANCE TO TREES VARIES
EXST POWERPOLE DISTANCE FROM ROAD VARIES
SCHEMATICALLY
EXST GROUND SHOWN
APPROX 12' EXISTING ROADWAY
DISTANCE TO TREES VARIES, APPROX 10' TO 20'APPROX 12' EXISTING ROADWAYDISTANCE TO TREES VARIES, APPROX 10' TO 20'
B
NTS
BURIED ELECTRICAL ALONG ROAD FROM SETTLEMENT
WATERLINE
EXST 6" DIP
THRU HANDHOLE
(2) 3" ELEC CONDUIT
SCHEMATICALLY
EXST GROUND SHOWN
C
NTS
BURIED ELECTRICAL ALONG WATER PUMP STATION RD
SCHEMATICALLY
EXST GROUND SHOWN
WATERLINE
EXST 6" DIP
CONCRETE ENCASED
(2) 3" ELEC CONDUIT
3'
PROJ NO
ANSI_DR.dgnFILENAME: PLOT DATE:3/10/2020 PLOT TIME:11:46:29 AM
KALAUPAPA NATIONAL PARK, REHAB ELECTRICAL SYSTEM
SITE ELECTRICAL TYPICAL SECTIONS
SCHEMATIC DESIGN
APPROX 5' TO 10'
DISTANCE TO TREES VARIES,
APPROX 8' EXISTING ROADWAYAPPROX 5' TO 10'
DISTANCE TO TREES VARIES,
ELECTRICAL HANDHOLE
PROPOSED TRAFFIC RATED
BASED ON EXISTING FENCE
POWERPOLE OFFSET VARIES
(SCHEMATICALLY SHOWN)
EXST FENCE
(SCHEMATICALLY SHOWN)
TO BE REMOVED
EXST POWERPOLE
to
22' APE (5' EITHER SIDE OF ROADWAY)
25' APE for New Poles
Figure 5 -APE Sections
APE
18' APE (5' EITHER SIDE OF ROADWAY)
NPS TO VERIFY
THIS DIMENSION
NPS TO VERIFY
THIS DIMENSION
File details come from the government source that posted it. Updated .