B08_-_Attachment_04_-_NPS_CASA_324271_Seawall_DD_CD_-_FInal_CDs_-_ELEC_-_stamped.pdf

PDF 1 MB Posted

Attached to
CASA 324271, Castillo de San Marco National Monume
Solicitation number
140P2026R0016
Issued by

About this file

These electrical drawings detail the electrical design for a new ticket booth building at the Castillo de San Marcos national monument. The documents include electrical, low voltage, and site plans for a small administrative building with key components including:

Electrical Systems: A 60-amp, 3-phase branch panel (P1) with multiple circuits for lighting, receptacles, IT equipment, access control, and fire alarm systems. The design includes underground conduit connections from the existing Castillo de San Marcos main electrical panel to the new ticket booth building. Lighting fixtures include LED recessed troffers, downlights, and exterior wall sconces. The electrical design also specifies device mounting heights, conduit routing, and installation requirements.

Low Voltage Systems: The plans outline comprehensive low voltage infrastructure, including a wall-mounted IT rack with fiber optic connectivity, network video recorder (NVR), access control system, and security cameras. Specific provisions include a 12-strand multi-mode fiber termination box, PoE switches, wireless access points, and a dedicated UPS for the video surveillance system. The design also includes detailed riser diagrams for telecom, access control, and intrusion detection systems, with careful attention to cable routing, device placement, and integration with existing infrastructure.

View the file

Other files

File Type Posted
Sol_140P2026R0016_Amd_0005.pdf PDF
B09_-_CASA_324271_Updated__Consolidated_RFIs_as_of_1-21-26_0005.xlsx XLSX spreadsheet
B09_-_CASA_324271_-_Revision_1__2026-01-07_0004.pdf PDF
B09_-_10_45_00-RIB-Pedestrian_Control_Devices-Jan-8-2026_0004.pdf PDF
Sol_140P2026R0016_Amd_0004.pdf PDF
B09_-_CASA324271_Final_Construction_Drawings_-_Signed_C601_0004.pdf PDF
B09_-_CASA324271_Final_Construction_Drawings_-_Signed_GM001_0004.pdf PDF
B09_-_CASA_324271_-_Consolidated_RFIs_as_of_1-8-26_0004.xlsx XLSX spreadsheet
Sol_140P2026R0016_Amd_0003.pdf PDF
B09_-_Sign-in_Sheet_for_Site_visit_0003.pdf PDF
B09_-_CASA_324271_-_Drawings_-_Revision_1__2025-12-22_0003.pdf PDF
B09_-_RFIs_for_CASA_324271_-_With_Responses_12-22-2025_0003.pdf PDF
Sol_140P2026R0016_Amd_0002.pdf PDF
B08_-_Attachment_13_-_CASA_324271_STRUCT_drawings_0002.pdf PDF
Sol_140P2026R0016_Amd_0001.pdf PDF
B08_-_Attachment_02_-_NPS_CASA_324271_Seawall_DD_CD_-_Final_CDs_-_ARCH_-_stamped.pdf PDF
B08_-_Attachment_11_-_Vol_II_-_GenRefs_doc.pdf PDF
B08_-_Attachment_06_-_NPS_CASA_324271_Seawall_DD_CD_-_Final_CDs_-_MECH_-_stamped.pdf PDF
B08_-_Attachment_01_-_CASA_324271_Project_Specifications.pdf PDF
B08_-_Attachment_10_-_Vol_I_PastPerf.docx DOCX document
Sol_140P2026R0016.pdf PDF
B08_-_Attachment_07_-_NPS_CASA_324271_Seawall_DD_CD_-_Final_CDs_-_MARINE_-_stamped_pdf.pdf PDF
B08_-_Attachment_05_-_NPS_CASA_324271_Seawall_DD_CD_-_Final_CDs_-_LA_-_stamped.pdf PDF
B08_-_Attachment_09_-_Vol_I_Exp.docx DOCX document
B08_-_Attachment_12_-_SF-24_Bid_Bond.pdf PDF
B08_-_Attachment_08_-_Wage_Determination_WD_FL20250135.pdf PDF
B08_-_Attachment_03_-_NPS_CASA_324271_Seawall_DD_CD_-_Final_CDs_-_CIVIL_-_stamped.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A AMPS, AMPERES

AFCI ARC FAULT CIRCUIT

INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING

JURISDICTION

AIC AMPERE INTERRUPTING

CAPACITY

ATS AUTOMATIC TRANSFER

SWITCH

AWG AMERICAN WIRE GAUGE

C CONDUIT

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT

TELEVISION

CL CENTER LINE

CLG CEILING

ELECTRICAL ABBREVIATIONS: (NOT ALL USED ON PLANS)

CLG CEILING

CT CURRENT

TRANSFORMER

CU COPPER

DC DIRECT CURRENT

DIA DIAMETER

EA EACH

ELEC ELECTRICAL

EMER EMERGENCY

EMT ELECTRICAL METALLIC

TUBING

ES EMERGENCY STOP

FA FIRE ALARM

FACP FIRE ALARM CONTROL

PANEL

FLA FULL LOAD AMPS

FU FUSE

GC GENERAL CONTRACTOR

GFCI GROUND FAULT

CIRCUIT INTERRUPTER

GND GROUND

H.M.I. HUMAN-MACHINE

INTERFACE

HP HORSEPOWER

HZ HERTZ

IMC INTERMEDIATE METAL

CONDUIT

JB JUNCTION BOX

KVA KILO-VOLT AMP(S)

KW KILO-WATT

KWH KILO-WATT HOUR(S)

MC METAL-CLAD CABLE

MCB MAIN CIRCUIT

BREAKER

MCC MOTOR CONTROL

CENTER

MFR MANUFACTURER

MLO MAIN LUGS ONLY

MTR METER

MTS MANUAL TRANSFER

SWITCH

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NO NORMALLY OPEN

NTS NOT TO SCALE

OC OVERCURRENT

OCPD OVERCURRENT

PROTECTION DEVICE

OD OUTSIDE DIAMETER

P POLE

PB PUSHBUTTON

PH PHASE

PNL PANELBOARD

PVC POLYVINYL CHLORIDE

QTY QUANTITY

RA REMOTE

ANNUNCIATOR

RMC RIGID METAL CONDUIT

SW SWITCH

SWB SWITCHBOARD

SWGR SWITCHGEAR

UC UNDER COUNTER

UL UNDERWRITERS

LABORATORY

UNO UNLESS NOTED

OTHERWISE

V VOLT(S)

VA VOLT-AMPERE(S)

VFD VARIABLE FREQUENCY

DRIVE

W WATT(S)

WP WATER PROOF

EQUIPMENT JUNCTION BOX, VOLTAGE AND WIRING PER

EQUIPMENT REQUIREMENTS

EQUIPMENT JUNCTION BOX, WALL MOUNTED.

J

120V DUPLEX RECEPTACLE, WALL MOUNTED, 18" AFF UNO.

USE "X" TO DESIGNATE DEVICE. TYPICAL OF MOST RECEPTACLES.

A = ARC FAULT CIRCUIT INTERRUPTER (AFCI)

G = GROUND FAULT CIRCUIT INTERRUPTER (GFCI)

TR = TAMPER RESISTANT

U = COMBINATION USB RECEPTACLE (DUPLEX WITH (1) BUILT-IN

USB-A & (1) BUILT-IN USB-C TYPE CONNECTIONS) BASIS OF

DESIGN: LEGRAND WRR26USBAC6W

WP = WEATHERPROOF (IN-USE COVER)

WPG = WEATHERPROOF GFCI

72" = NON-STANDARD MOUNTING HEIGHT. NUMBER INDICATES

INCHES AFF

120V DUPLEX RECEPTACLE, CEILING MOUNTED.

120V QUAD RECEPTACLE, WALL MOUNTED, 18" AFF UNO.

SPECIAL PURPOSE OUTLET, WALL MOUNTED, 18" AFF

UNO.

120V DUPLEX RECEPTACLE, IN FLUSH FLOOR BOX.

120V QUAD RECEPTACLE, IN FLUSH FLOOR BOX.

ELECTRICAL SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.

**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.

J

FURNITURE POWER CONNECTION.P

LIGHTING, POWER, DISTRIBUTION PANEL.

INDICATES MOUNTING HEIGHT AFF OTHER THAN STANDARD

INDICATES PANEL AND/OR CIRCUIT NUMBER

48"

A-1

120V SPLIT-WIRED DUPLEX RECEPTACLE. (1) OUTLET CONTROLLED BY RELAY

PANEL, WALL MOUNTED, 18" AFF UNO.

120V SPLIT-WIRED QUAD RECEPTACLE. (2) OUTLETS CONTROLLED BY RELAY

PANEL, WALL MOUNTED, 18" AFF UNO.

120V SPLIT-WIRED DUPLEX RECEPTACLE, IN FLUSH FLOOR BOX. (1) OUTLET

CONTROLLED BY RELAY PANEL.

120V SPLIT-WIRED QUAD RECEPTACLE, IN FLUSH FLOOR BOX. (2) OUTLETS

CONTROLLED BY RELAY PANEL.

X

X

X

X

X

MAGNETIC DOOR HOLDER

CEILING MOUNTED SMOKE DETECTOR

FIRE ALARM TAMPER, FLOW AND PRESSURE SWITCH RESPECTIVELY

(COORDINATE EXACT QUANTITY AND LOCATION WITH SPRINKLER SHOP

DRAWINGS)

FIRE ALARM ADA APPROVED STROBE WALL DEVICE, 84"AFF

FIRE ALARM ADA APPROVED HORN WALL DEVICE, 84"AFF

FIRE ALARM ADA PULL STATION, 48"AFF

FIRE ALARM ADA APPROVED SPEAKER WALL DEVICE, 84"AFF

P

F

F

CEILING MOUNTED CO DETECTOR

SMOKE DUCT MOUNTED DETECTOR

HEAT DETECTOR

F co

P F

T

FIRE ALARM ADA APPROVED HORN/STROBE

WALL DEVICE, 84"AFF

C M

M

FIRE ALARM ADA APPROVED STROBE CEILING DEVICE

FIRE ALARM ADA APPROVED HORN/STROBE CEILING DEVICE

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

FACP

FAA

FIRE ALARM ADA APPROVED SPEAKER CEILING DEVICE

FIRE ALARM ADA APPROVED SPEAKER/STROBE WALL DEVICE,

84"AFF

F

FIRE ALARM ADA APPROVED SPEAKER/STROBE CEILING DEVICE

FIRE ALARM SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.

**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.

ABORT SWITCH

CONTROL (C) MODULE, MONITOR (M) MODULE

FIRE ALARM REMOTE AMPLIFIERAMP

FIRE ALARM LOCAL OPERATOR CONSOLELOC

PHOTOCELL (EXTERIOR, INTERIOR)PC

LIGHT SWITCH, 48" UNO.

USE "X" TO DESIGNATE TYPE. TYPICAL OF MOST SWITCHES.

BLANK = SINGLE-POLE, SINGLE-THROW

3 = 3-WAY, SINGLE-POLE, DOUBLE-THROW

4 = 4-WAY, DOUBLE-POLE, DOUBLE-THROW

D = DIMMER SWITCH, 0-10V

DOS = COMBINATION DIMMER/WALL OCCUPANCY SENSOR, DUAL

TECHNOLOGY

F = FAN CONTROL

LV = LOW-VOLTAGE, MULTI-BUTTON WALL STATION

M = MOTOR-RATED

OS = WALL OCCUPANCY SENSOR-SINGLE OR 3-WAY, DUAL

TECHNOLOGY

S = PROJECTION SCREEN CONTROL

T = TIMER SWITCH

VOS = COMBINATION VACANCY/WALL OCCUPANCY SENSOR, DUAL

TECHNOLOGY

USE "x" TO DESIGNATE ZONE.

CEILING/WALL MOUNTED EXIT SIGN

WALL MOUNTED EMERGENCY LIGHTING FIXTURE

RECESSED DOWNLIGHT, REFER TO LIGHTING FIXTURE

SCHEDULE FOR DETAILS.

EMERGENCY RECESSED DOWNLIGHT, REFER TO LIGHTING

FIXTURE SCHEDULE FOR DETAILS.

2X4 RECESSED TROFFER, REFER TO LIGHTING FIXTURE

SCHEDULE FOR DETAILS.

2X2 RECESSED TROFFER, REFER TO LIGHTING FIXTURE

SCHEDULE FOR DETAILS.

LINEAR STRIP FIXTURE, REFER TO LIGHTING FIXTURE

SCHEDULE FOR DETAILS.

CEILING MOUNTED OCCUPANCY SENSOR, DUAL

TECHNOLOGY. WATTSTOPPER DT-300 OR EQUIVALENT.

OS

LIGHTING SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.

**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.

CEILING MOUNTED VACANCY SENSOR, DUAL

TECHNOLOGY. WATTSTOPPER DT-300 OR EQUIVALENT.

EMERGENCY 2X4 RECESSED TROFFER, REFER TO

LIGHTING FIXTURE SCHEDULE FOR DETAILS.

EMERGENCY 2X2 RECESSED TROFFER, REFER TO

LIGHTING FIXTURE SCHEDULE FOR DETAILS.

EXTERIOR WALL FIXTURE, REFER TO LIGHTING FIXTURE

SCHEDULE FOR DETAILS.

VS

AE a

A-1

INDICATES FIXTURE TYPE

INDICATES EMERGENCY FIXTURE

INDICATES SWITCHING

INDICATES PANEL AND/OR CIRCUIT NUMBER

Xx

DATA/PHONE OUTLET WALL MOUNTED 18" AFF UNO, WITH 3/4" CONDUIT &

PULLSTRING STUBBED TO 6" ABOVE ACCESSIBLE CEILING, TERMINATED WITH

BUSHING.

TV OUTLET, SINGLE GANG BOX, 18" AFF UNO, WITH 1" CONDUIT IN

WALL, STUBBED OUT 6" ABOVE CEILING W/PULL STRING.

TV

DATA/PHONE OUTLET FLOOR MOUNTED, WITH 1" CONDUIT &

PULLSTRING STUBBED TO 6" ABOVE ACCESSIBLE CEILING.

FURNITURE COMMUNICATION/DATA CONNECTION.

DOORBELL PUSH BUTTON, PROVIDE SINGLE GANG BOX WITH 3/4"C

& PULLSTRING TO PLENUM SPACE ABOVE CEILING LEVEL

PAGING SYSTEM CONTROL UNITPAG

SPEAKER, CEILING/PENDANT, WALLS

S

PB

WIRELESS ACCESS POINT, CEILING MOUNTED

LOW VOLTAGE SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.

**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.

C

DATA OUTLET, CEILING MOUNTED

ACCESS CONTROL CARD READER

ELECTRIC DOOR LOCK WITH INTEGRAL REQUEST-TO-EXIT SWITCHDL

CR

360 DEGREE WALL OR CEILING MOUNTED SECURITY CAMERA

DOOR MAGNETIC CONTACTDC

DB

DURESS PUSH BUTTON, PROVIDE SINGLE GANG BOX WITH 3/4"C &

PULLSTRING TO PLENUM SPACE ABOVE CEILING LEVEL

BACKBOARD: 3/4" 4FT X 8FT FIRE-RATED PLYWOOD

GROUND BAR

MOTION SENSOR

SECURITY KEY PAD

MS

KP

APPLICATION OF THE DRAWINGS:

1. THE DRAWINGS ARE AN ESSENTIAL PART OF THE

CONTRACT DOCUMENTS AND SHALL BE USED IN

CONJUNCTION WITH THE REQUIREMENTS OF THE

SPECIFICATIONS SECTION OF THE CONTRACT

DOCUMENTS. IN NO CASE ARE THE DRAWINGS TO

BE CONSTRUED TO REQUIRE LESS THAN WHAT IS

REQUIRED BY LOCAL CONDITIONS AND STATE AND

LOCAL BUILDING CODES AND OTHER APPLICABLE

LAWS.

2. THE OMISSION OF ANY PART OF THE CONTRACT

DOCUMENTS IS LIKELY TO RESULT IN CONFLICTS,

INCOMPLETE INSTALLATION, OR A FINISHED

PRODUCT THAT DOES NOT FUNCTION IN

ACCORDANCE WITH THE CONTRACT DOCUMENTS.

ANY SUCH CIRCUMSTANCES IDENTIFIED BY THE

DESIGN PROFESSIONAL, THE OWNER, OR THE

AUTHORITIES HAVING JURISDICTION SHALL

REQUIRE THE CONTRACTOR TO REMEDY THE

IDENTIFIED DEFICIENT WORK AT NO ADDITIONAL

COST TO THE PROJECT.

3. DRAWINGS SHOULD NOT BE RELIED UPON TO

DETERMINE THE QUANTITY OF MATERIALS TO BE

SUPPLIED WITHOUT RECOURSE TO THE

SPECIFICATIONS.

4. DRAWINGS ARE DIAGRAMMATIC AND ARE NOT

REPRESENTATIVE OF ALL POTENTIAL CONDITIONS.

COORDINATE WITH ALL DISCIPLINES TO ENSURE

PROPER INSTALLATION OF ALL SYSTEMS AND

EQUIPMENT.

5. CONFLICTS: THE PROVISION, SPECIFICATION OR

DRAWING IN THE CONTRACT DOCUMENTS WHICH

PROVIDES FOR THE HIGHER QUALITY OR QUANTITY

SHALL TAKE PRECEDENCE OVER A CONFLICTING

OR INCONSISTENT PROVISION, SPECIFICATION OR

DRAWING IN THE CONTRACT DOCUMENTS. WHERE

SUCH A CONFLICT IS IDENTIFIED, THE

CONTRACTOR SHALL SUBMIT A REQUEST FOR

INFORMATION (RFI) FOLLOWING THE PROCEDURES

OUTLINED IN THE SPECIFICATIONS, SECTION 01

3000 ADMINISTRATIVE REQUIREMENTS.

6. REFER TO ARCHITECTURAL FLOOR PLANS,

REFLECTED CEILING PLANS, AND ELEVATIONS FOR

EXACT LOCATIONS OF ALL EQUIPMENT, LIGHTING,

AND DEVICES.

7. SEE SHEET G-00X FOR COMMON PROJECT

ABBREVIATIONS, DEFINITIONS, AND GENERAL

NOTES APPLICABLE TO THESE DRAWINGS.

DATE:

TECH REVIEW:

DESIGNED: SUB SHEET NO. DRAWING NO.

PMIS/PKG NO.

SHEET

OF

TITLE OF SHEETA/E FIRM

PRIME:

CROFT & ASSOCIATES

KENNESAW, GEORGIA

STRUCTURAL

MH STRUCTURES

POWDER SPRINGS, GA

LANDSCAPE

CATALYST DESIGN

GROUP

WINTER PARK, FL

COASTAL

MOFFATT & NICHOL, INC

MIAMI, FL

/4

/2

:1

:3

A

M A u to d e s k D o c s /2

-4

A

C A

S A

F E

E S

T A

T

IO

N /2

-4

A

C A

S A

E

.r v t

ELECTRICAL GENERAL

E001

LRJ

KEJ

RER

74 119

324271

09/05/2025

189856

MC CABLE SHALL ONLY BE USED FROM THE LAST JUNCTION BOX TO THE DEVICE BEING

FED. MC CABLE SHALL NOT BE USED TO FEED PANELBOARDS, ROUTING FROM JUNCTION

BOX TO JUNCTION BOX OR IN AREAS WITH EXPOSED CEILINGS, CLOUD CEILINGS OR

EXPOSED WALLS.

MC CABLE INSTALLATION NOTE:

RESTRICTIONS OF SURFACE MOUNTED CONDUIT AND DEVICES FOR NEW CONSTRUCTION:

UNLESS OTHERWISE NOTED ON THE DRAWINGS OR SPECIFICATIONS, ALL CONDUIT

SHALL BE CONCEALED AND WALL MOUNTED DEVICES RECESSED FLUSH WITHIN

WALLS. SURFACE MOUNTED CONDUIT AND DEVICES ARE PROHIBITED.

RESTRICTIONS OF SURFACE MOUNTED CONDUIT AND DEVICES FOR RENOVATIONS:

UNLESS OTHERWISE NOTED ON THE DRAWINGS OR SPECIFICATIONS, ALL CONDUIT SHALL

BE CONCEALED AND WALL MOUNTED DEVICES RECESSED FLUSH WITHIN EXISTING WALLS.

CONTRACTORS PRICING TO INCLUDE CUTTING EXISTING WALLS TO INSTALL CONCEALED

CONDUIT AND FLUSH WALL MOUNTED DEVICES. PRICE TO ALSO INCLUDE PATCHING

EXISTING WALLS BACK TO ORIGINAL CONDITION. SURFACE MOUNTED CONDUIT AND

DEVICES ARE PROHIBITED.

MASTER KEY: ELECTRICAL NEW WORK SHEET NOTES

SEE INDIVIDUAL ELECTRICAL SHEETS FOR APPLICATION

TAG # TAG DESCRIPTION

1 NEW FEEDER RUN UNDERGROUND TO MAIN ELECTRICAL PANEL IN EXISTING

CASTILLO DE SAN MARCOS. SEE ES101 FOR MORE INFORMATION.

2 EXISTING INTRUSION PANEL TO BE RELOCATED FROM EXISTING TICKET BOOTH

BUILDING TO NEW TICKET BOOTH BUILDING.

3 UNDERGROUND CONDUIT RUN 24" BELOW FINISH GRADE FROM MAIN ELECTRICAL

PANEL IN EXISTING CASTILLO DE SAN MARCOS TO NEW PANEL BOARD LOCATED IN

THE NEW TICKET BOOTH BUILDING. SEE 3/E100 FOR MORE INFORMATION.

4 IT EQUIPMENT. REFER TO 5/E100 FOR ELEVATION.

5 REMOVE EXISTING MOAT LIGHT, AND REPLACE ONE FOR ONE (RAB LIGHTING:

FXLED78SFY W/ PROTECTIVE LENS GDFXLED78P & PROTECTIVE MESH SCREEN

GDFXLED78W & BSF MOUNT). REPLACE ALL WIRING, CONDUIT AND ANY

ASSOCIATED EQUIPMENT ONE FOR ONE.

6 PROVIDE AND INSTALL SECURITY CAMERA OVER DESK, POINTED AT THE DESK.

7 EXISTING CAMERA FROM EXISTING TICKET BOOTH TO BE REUSED AND INSTALLED

IN THIS LOCATION.

8 PROVIDE AND INSTALL WALL-MOUNT IT RACK.

9 PROVIDE AND INSTALL 120V/1P 20A POWER CONNECTION FOR MICROPHONE.

Notes:

Continuous 0.50 kVA 125.00% 0.63 kVA

Lighting 0.34 kVA 125.00% 0.42 kVA

Power 1.30 kVA 100.00% 1.30 kVA Total Est. Demand: 26.41 A

Receptacle 4.14 kVA 100.00% 4.14 kVA Total Conn.: 25.49 A

Motor 0.50 kVA 125.00% 0.63 kVA Total Est. Demand: 9.52 kVA

HVAC 2.60 kVA 100.00% 2.60 kVA Total Conn. Load: 9.18 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 24.94 A 26.43 A 25.70 A

Total Load: 2.99 kVA 3.16 kVA 3.07 kVA

41 SPACE -- 1 -- -- 1 -- SPACE 42

39 SPACE -- 1 -- -- 1 -- SPACE 40

37 SPACE -- 1 -- -- 1 -- SPACE 38

35 SPACE -- 1 -- -- 1 -- SPACE 36

33 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 34

31 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 32

29 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 30

27 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 28

25 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 26

23 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 24

21 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 22

19 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 20

17 Power 20 A 1 0.80 kVA 0.00 kVA 1 20 A SPARE 18

15 ACCESS CONTROL PANEL 20 A 1 0.50 kVA 0.50 kVA 1 20 A INTRUSION PANEL 16

13 IT EQUIPMENT 20 A 1 0.36 kVA 0.50 kVA 1 30 A FACP 14

11 RECEPT. RM: 103 20 A 1 0.54 kVA 0.15 kVA 1 20 A LTG EXTERIOR 12

9 RECEPT. RM: 104,103, 101 20 A 1 0.72 kVA 0.54 kVA 1 20 A RECEPT. RM: 103 10

7 RECEPT. RM: 103 20 A 1 0.54 kVA 1.30 kVA 8

5 RECEPT. RM: 102 20 A 1 0.36 kVA 1.30 kVA

2 20 A VRHP-1

3 FRIDGE RECEPT. RM: 102 20 A 1 0.18 kVA 0.72 kVA 1 20 A RECEPT. RM: 104 4

1 LTG RM: 101,102,103,104 20 A 1 0.19 kVA 0.18 kVA 1 20 A EXTERNAL RECEPT. 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1 MCB Rating: 60 A

Mounting: Recessed Wires: 4 Mains Rating: 60 A

Supply From: MAIN BUILDING SERVICE Phases: 3 Mains Type: MCB

Location: OFFICE 104 Volts: 120/208 Wye A.I.C. Rating: TBD

Branch Panel: P1

RobbieRahn RR_Florida Seal

OS

D

D D

OS

P

CR

D L

F A

C P

DB

DB

DB

DB

MS

J

J

J J

1. ALL ELECTRICAL FEEDERS FOR CIRCUITS SHALL BE ONE RUN 2#12, 1#12G. IN 1/2"C.

UNLESS NOTED OTHERWISE ON DRAWINGS.

2. CONDUCTOR RUNS GREATER THAN 75 LINEAR FEET SHALL BE UPSIZED TO #10 WIRE

UNLESS NOTED OTHERWISE.

3. COORDINATE FINISHES AND MOUNTING HEIGHTS OF ALL DEVICES WITH

ARCHITECTURAL PLANS.

4. ALL CONDUIT AND OUTLET BOXES SHALL BE INSTALLED WITHIN WALL CAVITIES. NO

EXPOSED CONDUITS ARE ACCEPTABLE BELOW CEILING LEVEL.

5. ROUTE ALL EXTERIOR LIGHTING THROUGH PHOTOCELL AND LIGHTING CONTACTOR.

6. COORDINATE WITH THE PARK FOR ACCEPTABLE MANUFACTURERS FOR ALL NEW

SECURITY AND FIRE ALARM EQUIPMENT.

7. PROVIDE MACHINE PRINTED ADDRESS LABELS ON ADDRESSABLE DEVICES. PROVIDE

MACHINE PRINTED LABELS ON NOTIFICATION APPLIANCES WITH APPROPRIATE

CIRCUIT INFORMATION. LABELS TO BE VISIBLE FROM THE FLOOR WITHOUT

MAGNIFICATION.

GENERAL NOTES:

C

AE A AE

AE

XSE

b a b

SE

SE

SE

P1-1aP1-1a P1-1a

P1-1

P1-1b

P1-12

P1-12P1-12

P1-12

P1-1

TICKETS

OFFICE

ENTRY

BREAK

AREA

XP1-1

SE

SE

P1-12

P1-12

44"

OFFICE

TICKETS

BREAK

AREA

ENTRY

44"

P1

VRHP-1

VRFC-01

WPG

VRFC-02

44" 44"

44"

P1-4

P1-4

P1-9

P1-9

P1-9

P1-9

P1-11

P1-10

P1-7

P1-11 P1-10

P1-7

P1-3 P1-5

P1-5

P1-14

P1-13

E100

P1-16

P1-17

P1-17

P1-17

P1-17

60.4

PANEL "P1"

280/120V 3Ø, 4W

1#8

OFFICE 104

BATT/CHGR

FACP

DEDICATED 120V AC, 20A, 1P

BRANCH CIRCUIT

SLC CIRCUITS

CLASS B

NAC CIRCUITS

CLASS B

ACCESS

CONTROL

SYSTEM

(2) DEDICATED TELEPHONE LINES

P

OFFICE 104

DL

FIRE ALARM DEVICES: REFER TO FLOOR

PLANS FOR LOCATIONS AND QUANTITIES.

P1

WALL-MOUNT

IT RACK

ACCESS

CONTROL

PANEL

2'X4' TELEPHONE

BACKBOARD

GROUND BAR

FIBER

TERMINATION

BOX (UTILITY

DEMARCATION)

25-PAIR COPPER PROTECTION BLOCKS

(UTILITY DEMARCATION)

"5

CONDUIT

P1-15

RECEPTACLE

FOR POWER

DATE:

TECH REVIEW:

DESIGNED: SUB SHEET NO. DRAWING NO.

PMIS/PKG NO.

SHEET

OF

TITLE OF SHEETA/E FIRM

PRIME:

CROFT & ASSOCIATES

KENNESAW, GEORGIA

STRUCTURAL

MH STRUCTURES

POWDER SPRINGS, GA

LANDSCAPE

CATALYST DESIGN

GROUP

WINTER PARK, FL

COASTAL

MOFFATT & NICHOL, INC

MIAMI, FL

/4

/2

:1

:5

A

M A u to d e s k D o c s /2

-4

A

C A

S A

F E

E S

T A

T

IO

N /2

-4

A

C A

S A

E

.r v t

ELECTRICAL PLAN - LIGHTING,

POWER AND SYSTEMS

E100

LRD

KEJ

RER

76 119

324271

09/05/2025

189856

SHEET NOTES: (APPLY THIS SHEET ONLY)

SEE MASTER KEY ON E-001 FOR COMPLETE SHEET NOTE LIST

TAG # TAG DESCRIPTION

1 NEW FEEDER RUN UNDERGROUND TO MAIN ELECTRICAL PANEL IN EXISTING CASTILLO DE

SAN MARCOS. SEE ES101 FOR MORE INFORMATION.

2 EXISTING INTRUSION PANEL TO BE RELOCATED FROM EXISTING TICKET BOOTH BUILDING TO

NEW TICKET BOOTH BUILDING.

4 IT EQUIPMENT. REFER TO 5/E100 FOR ELEVATION.

6 PROVIDE AND INSTALL SECURITY CAMERA OVER DESK, POINTED AT THE DESK.

7 EXISTING CAMERA FROM EXISTING TICKET BOOTH TO BE REUSED AND INSTALLED IN THIS

LOCATION.

8 PROVIDE AND INSTALL WALL-MOUNT IT RACK.

9 PROVIDE AND INSTALL 120V/1P 20A POWER CONNECTION FOR MICROPHONE.

SCALE AE100

1 FIRST FLOOR PLAN - LIGHTING

SCALE AE100

2 FIRST FLOOR PLAN - POWER & SYSTEMS

SCALE

SCALE OF FEET

A

B L D

G

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER MODEL LAMP LOAD COMMENTS

A 2'X2' RECESSED DIMMABLE LED FIXTURE LITHONIA OR EQUAL 2BLT 33L ADP EZ1 LP835 LED, 3500K 27 VA

AE 2'X2' RECESSED DIMMABLE LED EMERGENCY FIXTURE LITHONIA OR EQUAL 2BLT2 33L ADP EZ1 LP835 EL14L LED, 3500K 27 VA PROVIDE 90 MINUTE BACKUP BATTERY WITH ADDITIONAL UNSWITCHED HOT CONDUCTOR

C 6" RECESSED DIMMABLE DOWNLIGHT LITHONIA OR EQUAL LDN6 35/10 LO6 WR 277 EZ1 LED, 3500K 60 VA

SE EXTERIOR WALL SCONCE HAMPTON BAY OR

EQUAL

JBO1691A-4 LED, 3500K 25 VA PROVIDE 90 MINUTE BACKUP BATTERY WITH ADDITIONAL UNSWITCHED HOT CONDUCTOR. PROVIDE BODINE ELIS400CEC REMOVE BATTERY BACKUP FOR EMERGENCY LIGHT.

X LED EXIT SIGN ISOLITE OR EQUAL RL R U WH MTEB LED 5 VA PROVIDE 90 MINUTE BACKUP BATTERY WITH ADDITIONAL UNSWITCHED HOT CONDUCTOR

MECHANICAL EQUIPMENT CONNECTION SCHEDULE

EQUIPMENT TAG DESCRIPTION VOLTAGE PHASE FEEDER DISCONNECT WATTS HP FLA MCA MOCP CIRCUIT COMMENTS

VRHP-1 SPLIT SYSTEM 208 V 1 1 SET(S) OF 2#12 AWG, 1#12 AWG G. - 1/2"C. 30A/2P/NF/NEMA 3R 12.5 A 15.6 A 20 A P1-6,8 INDOOR UNITS VRFC-1-01 & VRFC-1-02 FED FROM

OUTDOOR UNIT.

E100

3 ELECTRICAL RISER

CONDUCTOR SCHEDULE

Mark Capacity Sets Phase Wire Equipment

Ground Conduit

60.4 60 AMP 1 3 PHASE/4 WIRE (4)#4 (1)#10 1-1/4"

E100

4 FIRE ALARM RISER

SCALE

SCALE OF FEET

2 0 2 4 B

SCALE AE100

5 ELEVATION - IT EQUIPMENT

THERMOSTAT, ZONE

TEMPERATURE SENSOR,

OR OTHER H.M.I. SEE

DETAIL M-XXX FOR

PLACEMENT OF J-BOX.

FIRE ALARM DEVICE

B

LIGHT SWITCH

FINISHED

FLOOR

A

LIGHT SENSOR /

MOTION DETECTOR

DEVICES NOT

ALIGNED

DEVICES ALIGNED

ALONG EDGE

INSTEAD OF ALONG

CENTERLINE

FINISHED DOOR FRAME. SEE

SHEET A-6XX FOR FRAME

WIDTH AND DOOR DETAILS

TYP.

1"

C D

GENERAL WALL-MOUNTED DEVICE NOTES:

1. PROVIDE J-BOXES FOR SWITCHES AND H.M.I. DEVICES SERVING EQUIPMENT

SPECIFIED UNDER DIVISIONS 22 AND 23. ENSURE ALL WALL-MOUNTED DEVICES ARE

ALIGNED TO CENTERLINE WITH ALL OTHER DEVICES IN THE IMMEDIATE PROXIMITY.

2. INSTALLATION HEIGHTS ARE AS FOLLOWS, UNLESS NOTED OTHERWISE:

A = SEE DETAIL X/G-XXX FOR SPACING FROM EDGE OF DOOR FRAME.

B = 48 INCHES A.F.F. (STUD WALL) OR 44 INCHES A.F.F. (STUD WALL W/ 10"-25" DEEP

COUNTER)

C = 80 INCHES A.F.F.

D = 96 INCHES A.F.F. (OR 6 INCHES BELOW THE CEILING, WHICHEVER IS LOWER)

ACCESS CONTROL PANEL

DIMMER (IF SEPARATE

FROM LIGHT SWITCH)

NEUTRAL

HOT

WHT

BLK

-1

V

D R

IV

E

R

WHT

BLK

GRAY

PURPLE

GREEN

GROUND

GRAY

PURPLE

BLUE

LINE VOLTAGE

STEEL JOIST

PROVIDE APPROVED

MECHANICAL

FASTENERS AT ALL 4 CORNERS

OF

LIGHT FIXTURE TO SECURE

FIXTURE

TO CEILING GRID SYSTEM PER

NEC.

LED LAY-IN

LIGHT FIXTURE

#12 ZINC COATED

HANGER WIRE, PROVIDE

AT ALL 4 CORNERS OF

EACH FIXTURE.

ACOUSTICAL CEILING TILE

FLEXIBLE

CONDUIT

CONNECTION 6'

MAX

EMT CONDUIT SHALL BE SUPPORTED FROM

STEEL OR

FIXED STRUCTURE WITH APPROVED

HANGERS AND

FITTINGS. CONDUIT SHALL NOT BE

SUPPORTED BY

SUSPENDED CEILING SYSTEM OR LIGHT

FIXTURE

HANGERS.

CONCRETE OR

STEEL ROOF DECK

JUNCTION

BOX

SIZED

PER NEC

AS REQ'D

CEILING

NOTE 2

NOTE 3

48" AFF

96" AFF MAX

80" AFF

5' MAX

6"

3" MIN

A/C

SUPPLY OR

RETURN

DIFFUSER

CEILING

MOUNTED

SMOKE/HEAT

DETECTOR

24"

FIREFIRE

MAGNETIC DOOR HOLDER

MANUAL PULL STATION

FIRE

PHONE

JACK

4"

CEILING

MOUNTED

SMOKE/HEAT

DETECTOR;

NOTE 1

4"

12" MAX

80" AFF

FINISHED

FLOOR

NOTES:

1.

2.

3.

FINISHED

WALL

WALL MOUNTED

SMOKE/HEAT

DETECTOR;

NOTE 1

REFERENCES:

AUDIBLE/VISUAL OR

VISUAL ONLY

APPLIANCES

80" - ADA

80" MIN - NFPA

80" MIN/96" MAX - IBC

NFPA 72 2022 EDITION

SECTION 18.5.5.1

SECTION 18.5.5.7.2

NFPA 72 2019 EDITION

SECTION 18.5.5.1

SECTION 18.5.5.5.2

NFPA 72 2016 EDITION

SECTION 18.5.5.1

SECTION 18.5.5.4.2

MANUAL PULL

STATIONS

48" MAX - ADA

42" MIN/48" MAX - NFPA

NFPA 72 2022 EDITION

SECTION

17.15.4-17.15.6

NFPA 72 2019 EDITION

SECTION

17.15.4-17.15.6

NFPA 72 2016 EDITION

SECTION

17.14.3-17.14.5

REFER TO THE PROPER DEVICE INSTALLATION

INSTRUCTIONS FOR

BACKBOX MOUNTING HEIGHT.

SYNCHRONIZE MORE THAN 2 APPLIANCES IN ANY FIELD OF

VIEW.

MAGNETIC DOOR HOLDER - POSITION 3" LESS THAN WIDTH

OF DOOR.

1.

NOTES:

70" AFF.

FINISHED CEILING

LINE

FINISHED FLOOR

FIELD VERIFY BOX

REQUIREMENTS

FIELD CONDUIT

1" CONDUIT

J--BOX

LOGO

DIM: 12"W x 16"H x 3"D

120VAC

PAD-3

FIRE ALARM PANEL SHALL BE TERMINATED

TO A DEDICATED 120VAC PROTECTED POWER

SOURCE. THE DEDICATED POWER SOURCE

SHALL BE CLEARLY LABELED 'FIRE ALARM' IN

RED AT THE DISCONNECT. SUCH DISCONNECTS

SHALL BE ACCESSIBLE ONLY TO AUTHORIZED

PERSONNEL. ANY FIRE ALARM UNIT BEING

PROVIDED POWER SHALL BE LABELED AT THE

UNIT, IDENTIFYING THE LOCATION OF ITS

CORRESPONDING POWER DISCONNECT.

CONDUIT MUST NOT STUB INTO THE

BOTTOM OR THE LOWER SIDES OF

THE CABINET BY THE BATTERIES

OTHERWISE THE BATTERIES WILL

NOT FIT INSIDE OF THE

ENCLOSURE.

FIXTURE "G"

SURFACE MOUNT "SM"

6” DIAMETER CONCRETE

PEDESTAL WITH BUILT IN

CONDUIT FOR CIRCUIT ROUTING.

ENSURE CONDUIT IS

WATERTIGHT ONCE FIXTURE IS

INSTALLED. ENSURE CONCRETE

PEDESTAL IS MOUNTED 12”

MINIMUM BELOW GRADE AND

STANDS 4” ABOVE GRADE.

DATE:

TECH REVIEW:

DESIGNED: SUB SHEET NO. DRAWING NO.

PMIS/PKG NO.

SHEET

OF

TITLE OF SHEETA/E FIRM

PRIME:

CROFT & ASSOCIATES

KENNESAW, GEORGIA

STRUCTURAL

MH STRUCTURES

POWDER SPRINGS, GA

LANDSCAPE

CATALYST DESIGN

GROUP

WINTER PARK, FL

COASTAL

MOFFATT & NICHOL, INC

MIAMI, FL

/4

/2

:1

:0

A

M A u to d e s k D o c s /2

-4

A

C A

S A

F E

E S

T A

T

IO

N /2

-4

A

C A

S A

E

.r v t

ELECTRICAL DETAILS

E701

LRD

KEJ

RER

77 119

324271

09/05/2025

189856

NOT TO SCALEE701

3 WALL-MOUNTED ELECTRICAL DEVICE PLACEMENT DETAIL

NOT TO SCALEE701

4 TYPICAL 0-10V DIMMER SWITCH WIRING DIAGRAM

NOT TO SCALEE701

2 TYPICAL LAY-IN FIXTURE INSTALLATION DETAIL

NOT TO SCALEE701

5 FIRE ALARM DEVICES MOUNTING HEIGHTS (PER NFPA 72)

NOT TO SCALEE701

1 TYPICAL FIRE ALARM PANEL MOUNTING DETAIL

NOT TO SCALEE701

6 ABOVE GRADE LIGHTING FIXTURE MOUNT

FRONT VIEW

FCP

UPS

1. INSTALL A 2U FIBER CONNECTOR PANEL.

2. INSTALL (48) PORT PATCH PANEL.

3. INSTALL (24) PORT VOICE PATCH PANEL.

4. PROVIDE AND INSTALL NVR (NETWORK

VIDEO RECORDER) FOR VIDEO

SURVEILLANCE SYSTEM.

5. PROVIDE AND INSTALL ACCESS CONTROL

SYSTEM RACK MOUNTED CONTROL UNIT.

6. PROVIDE AND INSTALL RACK MOUNTED

UPS UNIT, 3000VA, 120V, 30A. APC SMART-

UPS OR EQUIVALENT.

1. PROVIDE AND INSTALL (2) 4" PVC CONDUIT WITH MESH INNDERDUCTS AND

PULLSTRINGS FROM EXISTING MAIN IT SERVICE. SEE DETAIL 7/E702. PROVIDE

AND INSTALL NEW 12-STRAND MULTI-MODE FIBER TERMINATION BOX ON NEW

PLYWOOD BACKBOARD FOR TELECOM DEMARCATION. EXTEND EXISTING

TICKET BOOTH IT SERVICE TO NEW TICKET BOOTH TO FIBER CONNECTOR

PANEL. REFER TO C002 FOR EXISTING IT SERVICE LOCATION.

2. 2' BY 4' BY 3/4" FIRE RETARDANT PLYWOOD BACKBOARD FOR TELECOM

EQUIPMENT.

3. 2" BY 10" BY 1/4" THICK SOLID COPPER TELECOM GROUND BAR. CONNECT TO

BUILDING SERVICE GROUND WITH #4/0 INSULATED COPPER GROUND

CONDUCTOR IN 3/4" CONDUIT.

4. CONTRACTOR TO PROVIDE PROTECTION BLOCKS.

5. DATA OUTLET, LOCATED AS INDICATED ON FLOOR PLANS, WITH (2) CAT6A

CABLE PER OUTLET, TERMINATED TO JACKS PER EIA/TIA 568B STANDARDS.

CABLES SHALL BE IN 3/4" METAL CONDUIT ROUTED ABOVE CEILING TO CLOSEST

TELECOM/DATA BACKBOARD. (TYPICAL)

6. PROVIDE AND INSTALL "PoE" (POWER OVER ETHERNET) SWITCHES TO BE USED

FOR ACCESS CONTROL SYSTEM.

7. WIRELESS ACCESS POINT, LOCATED AS INDICATED ON FLOOR PLANS,

CONNECTED PER EIA/TIA STANDARDS. CABLES SHALL BE IN 3/4" METAL

CONDUIT ROUTED ABOVE CEILING TO CLOSEST TELECOM/DATA BACKBOARD.

(TYPICAL)

8. PROVIDE AND INSTALL 24" WIDE, 15U, ENCLOSED, LOCKABLE, WALL-MOUNTED

CABINET WITH COOLING FANS AND INTERNAL RAILS TO SUPPORT 19" RACK

EQUIPMENT. SWITCHES AND OTHER IT EQUIPMENT SHALL BE PROVIDED AND

INSTALLED BY GOVERNMENT. SEE ELEVATION 5/E702.

# TELECOM RISER KEY NOTES:

IT/SERVER ROOM 107 ADMINISTRATIVE BUILDING

EXTENSION FROM

EXISTING BUILDING

MAIN IT SERVICE

INTRUSION PANEL

(INSTALLED IN

OFFICE 104)

DL DL

KP KP

MAIN CALL OUT LINE: PROVIDE

TELEPHONE LINE TO VOICE BLOCK.

120V POWER

DOOR LOCKS, KEY PADS AND DURRESS

BUTTONS: REFER TO FLOOR PLANS FOR

LOCATIONS AND QUANTITIES.

DB DB

ACCESS

CONTROL

PANEL

CR CR

120V, 1P, 20A BRANCH CIRCUIT

POWER

(2) DEDICATED TELEPHONE

LINES

OFFICE 104

DL MS

DL MS 10

NETWORK VIDEO

RECORDER (NVR)

WORK

STATION

LOCAL

VIEWING

MONITOR

ROUTER

(1) CAT6A CABLE PER

CAMERA

(1) TVSS DEVICE

PER CAMERA

INTERIOR

CAMERA

INTERIOR

CAMERA

EXTERIOR

CAMERA

5 EXTERIOR

CAMERA

FINISH GRADE

18" MINIMUM

DUCTBANK

MARKING TAPE

(TYPICAL)

7-1/2"

12"

CONDUITS PER SITE PLAN

MESH FABRIC

INNERDUCTS

(TYPICAL)

TRACER WIRE

GENERAL NOTES (THIS DETAIL ONLY)

1. GROUND AND BOND TRACER WIRES.

2. PROVIDE PULL STRINGS/MULE TAPE IN EACH CONDUIT.

3. PROVIDE MESH FABRIC INNERDUCTS IN CONDUITS FOR SERVICE PROVIDER USE.

1. PROVIDE NETWORK VIDEO RECORDER: MOUNT IN IT/SERVER OFFICE 104. CONTRACTOR TO CONFIGURE VIDEO MANAGEMENT SYSTEM FOR ACTIVITY DETECTION RECORDING. ALL VIDEO TO MAINTAINED FOR

MINIMUM OF 30 DAYS.

2. PROVIDE WORK STATION: CONTRACTOR TO LOAD AND CONFIGURE VIDEO SURVEILLANCE SOFTWARE ON UP TO (2) GOVERNMENT PROVIDED WORKSTATIONS. ALL CAMERA SETTINGS TO BE PROGRAMMED BY

CONTRACTOR TO GOVERNMENT'S SATISFACTION.

3. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6A CABLE CONTINUOUS PER IP CAMERA. REFER TO PLANS FOR QUANTITY AND LOCATIONS. ALL ABOVE GROUND CABLING SHALL BE INSTALLED IN 1" METAL

CONDUIT. ALL UNDERGROUND CABLING SHALL BE INSTALLED IN 1" PVC CONDUIT.

4. CONTRACTOR TO PROVIDE AND INSTALL ALL CATEGORY 6A CABLE FOR DEVICE INTERCONNECTIONS. ALL CABLING SHALL BE INSTALLED IN 1" METAL CONDUIT. ALL UNDERGROUND CABLING SHALL BE INSTALLED IN

1" PVC CONDUIT.

5. CONTRACTOR TO PROVIDE AND INSTALL LOW LIGHT, WIDE DYNAMIC RANGE, COLOR, IP MEGAPIXEL

CAMERAS FOR EXTERIOR LOCATIONS. SEE FLOOR PLAN FOR LOCATIONS.

6. PROVIDE TRANSIENT VOLTAGE SURGE PROTECTION FOR ALL CAMERAS AT PATCH PANEL AND CAMERA

LOCATIONS.

7. PROVIDE 24" LOCAL VIEWING MONITOR AND CONNECT TO NETWORK VIDEO RECORDER DISPLAY OUTPUT.

COORDINATE WITH CONTRACTING OFFICER FOR CAMERA VIEW SETUP.

8. CONTRACTOR TO PROVIDE DEDICATED UPS BACKUP FOR NETWORK VIDEO RECORDER AND ASSOCIATED

CAMERAS SIZED TO ALLOW 45 MINUTES OF RUN TIME.

9. PROVIDE ACCESS CONTROL PANEL IN OFFICE 104. ACCESS CONTROL SYSTEM AND DEVICES SHALL ALLOW FOR UNIHIBITED EGRESS IN THE EVENT OF FIRE OR OTHER EMERGENCY. ALL EQUIPMENT SHALL

FAIL OPEN.

10. REFER TO FLOOR PLAN ON SHEET E100 FOR QUANTITY AND LOCATION OF DEVICES. ALL DEVICES SHALL

FAIL OPEN.

# ACCESS CONTROL/CCTV KEY NOTES:

DATE:

TECH REVIEW:

DESIGNED: SUB SHEET NO. DRAWING NO.

PMIS/PKG NO.

SHEET

OF

TITLE OF SHEETA/E FIRM

PRIME:

CROFT & ASSOCIATES

KENNESAW, GEORGIA

STRUCTURAL

MH STRUCTURES

POWDER SPRINGS, GA

LANDSCAPE

CATALYST DESIGN

GROUP

WINTER PARK, FL

COASTAL

MOFFATT & NICHOL, INC

MIAMI, FL

/4

/2

:1

:0

A

M A u to d e s k D o c s /2

-4

A

C A

S A

F E

E S

T A

T

IO

N /2

-4

A

C A

S A

E

.r v t

LOW VOLTAGE DETAILS

E702

LRD

LRD

RER

78 119

324271

09/05/2025

189856

NOT TO SCALEE702

1 WALL-MOUNT RACK EQUIPMENT ELEVATION

NOT TO SCALEE702

3 TELECOM RISER

NOT TO SCALEE702

4 INTRUSION DETECTION RISER

NOT TO SCALEE702

5 ACCESS CONTROL RISER DIAGRAM

NOT TO SCALEE702

7 TELECOM UNDERGROUND SERVICE DUCT BANK

EXISTING CASTILLO DE SAN MARCOS

EXISTING CASTILLO

DE SAN MARCOS

DATE:

TECH REVIEW:

DESIGNED: SUB SHEET NO. DRAWING NO.

PMIS/PKG NO.

SHEET

OF

TITLE OF SHEETA/E FIRM

PRIME:

CROFT & ASSOCIATES

KENNESAW, GEORGIA

STRUCTURAL

MH STRUCTURES

POWDER SPRINGS, GA

LANDSCAPE

CATALYST DESIGN

GROUP

WINTER PARK, FL

COASTAL

MOFFATT & NICHOL, INC

MIAMI, FL

/5

/2

:5

:2

A

M A u to d e s k D o c s /2

-4

A

C A

S A

F E

E S

T A

T

IO

N /2

-4

A

C A

S A

E

.r v t

ELECTRICAL SITE

ES101

LRD

KEJ

RER

75 119

324271

09/05/2025

189856

1. ALL EXISTING UNDERGROUND UTILITIES SHALL BE PHYSICALLY LOCATED PRIOR TO

ANY CONSTRUCTION IN THE VICINITY OF THE UTILITIES.

2. CONTRACTOR SHALL MAINTAIN A SAFE WORK SITE AND COMPLY WITH ALL LOCAL,

STATE, AND FEDERAL SAFETY REGULATIONS.

3. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ELECTRICAL PERMIT, PROVIDING ALL

SECONDARY UTILITY CONNECTIONS, AND COORDINATING AND OBTAINING

ELECTRICAL INSPECTION.

4. DAMAGE TO EXISTING FACILITIES AS A RESULT OF CONTRACTOR ACTIVITIES SHALL

BE REPAIRED OR REPLACED TO PRE-CONSTRUCTION CONDITIONS BY THE

CONTRACTOR AT NO COST TO THE OWNER.

5. CONTRACTOR SHALL RESTORE ALL DISTURBED AREAS TO PRE-CONSTRUCTION

CONDITIONS AND MATCH SURROUNDING AREA.

6. WHERE PROPOSED UNDERGROUND UTILITIES CROSS EXISTING UNDERGROUND

UTILITIES, CONTRACTOR SHALL EXCAVATE TEST PITS TO LOCATE EXISTING UTILITIES

PRIOR TO EXCAVATING FOR PROPOSED UTILITIES.

7. INTENT TO REUSE EXISTING DATA CABLING AND CONDUIT FOR LOW VOLTAGE

UTILITY. INTERCEPT THE EXISTING LOW VOLTAGE CONDUIT AND CABLING AND

EXTEND TO THE NEW TICKET BOOTH BUILDING. MATCH THE EXISTING CONDUIT AND

CABLING TO EXTEND TO THE NEW TICKET BOOTH BUILDING.

GENERAL NOTES:

SHEET NOTES: (APPLY THIS SHEET ONLY)

SEE MASTER KEY ON E-001 FOR COMPLETE SHEET NOTE LIST

TAG # TAG DESCRIPTION

3 UNDERGROUND CONDUIT RUN 24" BELOW FINISH GRADE FROM MAIN ELECTRICAL PANEL IN

EXISTING CASTILLO DE SAN MARCOS TO NEW PANEL BOARD LOCATED IN THE NEW TICKET

BOOTH BUILDING. SEE 3/E100 FOR MORE INFORMATION.

5 REMOVE EXISTING MOAT LIGHT, AND REPLACE ONE FOR ONE (RAB LIGHTING: FXLED78SFY W/

PROTECTIVE LENS GDFXLED78P & PROTECTIVE MESH SCREEN GDFXLED78W & BSF MOUNT).

REPLACE ALL WIRING, CONDUIT AND ANY ASSOCIATED EQUIPMENT ONE FOR ONE.

ES101

1 ELECTRICAL SITE

20 0 20 40

SCALE OF FEET

20 0 20 40

SCALE OF FEET

B L D

G

E001 - ELECTRICAL GENERAL
2023-416A CASA_E25
E001 - ELECTRICAL GENERAL
E100 - ELECTRICAL PLAN - LIGHTING, POWER AND SYSTEMS
2023-416A CASA_E25
E100 - ELECTRICAL PLAN - LIGHTING, POWER AND SYSTEMS
E701 - ELECTRICAL DETAILS
2023-416A CASA_E25
E701 - ELECTRICAL DETAILS
E702 - LOW VOLTAGE DETAILS
2023-416A CASA_E25
E702 - LOW VOLTAGE DETAILS
ES101 - ELECTRICAL SITE
2023-416A CASA_E25
ES101 - ELECTRICAL SITE
2025-09-05T13:59:50-0400
Robert Rahn
2025-09-05T14:00:24-0400
Robert Rahn
2025-09-05T14:00:41-0400
Robert Rahn
2025-09-05T14:00:57-0400
Robert Rahn
2025-09-05T14:01:13-0400
Robert Rahn

File details come from the government source that posted it. Updated .