B08_-_Attachment_04_-_NPS_CASA_324271_Seawall_DD_CD_-_FInal_CDs_-_ELEC_-_stamped.pdf
PDF 1 MB Posted
- Solicitation number
- 140P2026R0016
About this file
These electrical drawings detail the electrical design for a new ticket booth building at the Castillo de San Marcos national monument. The documents include electrical, low voltage, and site plans for a small administrative building with key components including:
Electrical Systems: A 60-amp, 3-phase branch panel (P1) with multiple circuits for lighting, receptacles, IT equipment, access control, and fire alarm systems. The design includes underground conduit connections from the existing Castillo de San Marcos main electrical panel to the new ticket booth building. Lighting fixtures include LED recessed troffers, downlights, and exterior wall sconces. The electrical design also specifies device mounting heights, conduit routing, and installation requirements.
Low Voltage Systems: The plans outline comprehensive low voltage infrastructure, including a wall-mounted IT rack with fiber optic connectivity, network video recorder (NVR), access control system, and security cameras. Specific provisions include a 12-strand multi-mode fiber termination box, PoE switches, wireless access points, and a dedicated UPS for the video surveillance system. The design also includes detailed riser diagrams for telecom, access control, and intrusion detection systems, with careful attention to cable routing, device placement, and integration with existing infrastructure.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A AMPS, AMPERES
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING
JURISDICTION
AIC AMPERE INTERRUPTING
CAPACITY
ATS AUTOMATIC TRANSFER
SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT
TELEVISION
CL CENTER LINE
CLG CEILING
ELECTRICAL ABBREVIATIONS: (NOT ALL USED ON PLANS)
CLG CEILING
CT CURRENT
TRANSFORMER
CU COPPER
DC DIRECT CURRENT
DIA DIAMETER
EA EACH
ELEC ELECTRICAL
EMER EMERGENCY
EMT ELECTRICAL METALLIC
TUBING
ES EMERGENCY STOP
FA FIRE ALARM
FACP FIRE ALARM CONTROL
PANEL
FLA FULL LOAD AMPS
FU FUSE
GC GENERAL CONTRACTOR
GFCI GROUND FAULT
CIRCUIT INTERRUPTER
GND GROUND
H.M.I. HUMAN-MACHINE
INTERFACE
HP HORSEPOWER
HZ HERTZ
IMC INTERMEDIATE METAL
CONDUIT
JB JUNCTION BOX
KVA KILO-VOLT AMP(S)
KW KILO-WATT
KWH KILO-WATT HOUR(S)
MC METAL-CLAD CABLE
MCB MAIN CIRCUIT
BREAKER
MCC MOTOR CONTROL
CENTER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MTR METER
MTS MANUAL TRANSFER
SWITCH
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
OC OVERCURRENT
OCPD OVERCURRENT
PROTECTION DEVICE
OD OUTSIDE DIAMETER
P POLE
PB PUSHBUTTON
PH PHASE
PNL PANELBOARD
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RA REMOTE
ANNUNCIATOR
RMC RIGID METAL CONDUIT
SW SWITCH
SWB SWITCHBOARD
SWGR SWITCHGEAR
UC UNDER COUNTER
UL UNDERWRITERS
LABORATORY
UNO UNLESS NOTED
OTHERWISE
V VOLT(S)
VA VOLT-AMPERE(S)
VFD VARIABLE FREQUENCY
DRIVE
W WATT(S)
WP WATER PROOF
EQUIPMENT JUNCTION BOX, VOLTAGE AND WIRING PER
EQUIPMENT REQUIREMENTS
EQUIPMENT JUNCTION BOX, WALL MOUNTED.
J
120V DUPLEX RECEPTACLE, WALL MOUNTED, 18" AFF UNO.
USE "X" TO DESIGNATE DEVICE. TYPICAL OF MOST RECEPTACLES.
A = ARC FAULT CIRCUIT INTERRUPTER (AFCI)
G = GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
TR = TAMPER RESISTANT
U = COMBINATION USB RECEPTACLE (DUPLEX WITH (1) BUILT-IN
USB-A & (1) BUILT-IN USB-C TYPE CONNECTIONS) BASIS OF
DESIGN: LEGRAND WRR26USBAC6W
WP = WEATHERPROOF (IN-USE COVER)
WPG = WEATHERPROOF GFCI
72" = NON-STANDARD MOUNTING HEIGHT. NUMBER INDICATES
INCHES AFF
120V DUPLEX RECEPTACLE, CEILING MOUNTED.
120V QUAD RECEPTACLE, WALL MOUNTED, 18" AFF UNO.
SPECIAL PURPOSE OUTLET, WALL MOUNTED, 18" AFF
UNO.
120V DUPLEX RECEPTACLE, IN FLUSH FLOOR BOX.
120V QUAD RECEPTACLE, IN FLUSH FLOOR BOX.
ELECTRICAL SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.
J
FURNITURE POWER CONNECTION.P
LIGHTING, POWER, DISTRIBUTION PANEL.
INDICATES MOUNTING HEIGHT AFF OTHER THAN STANDARD
INDICATES PANEL AND/OR CIRCUIT NUMBER
48"
A-1
120V SPLIT-WIRED DUPLEX RECEPTACLE. (1) OUTLET CONTROLLED BY RELAY
PANEL, WALL MOUNTED, 18" AFF UNO.
120V SPLIT-WIRED QUAD RECEPTACLE. (2) OUTLETS CONTROLLED BY RELAY
PANEL, WALL MOUNTED, 18" AFF UNO.
120V SPLIT-WIRED DUPLEX RECEPTACLE, IN FLUSH FLOOR BOX. (1) OUTLET
CONTROLLED BY RELAY PANEL.
120V SPLIT-WIRED QUAD RECEPTACLE, IN FLUSH FLOOR BOX. (2) OUTLETS
CONTROLLED BY RELAY PANEL.
X
X
X
X
X
MAGNETIC DOOR HOLDER
CEILING MOUNTED SMOKE DETECTOR
FIRE ALARM TAMPER, FLOW AND PRESSURE SWITCH RESPECTIVELY
(COORDINATE EXACT QUANTITY AND LOCATION WITH SPRINKLER SHOP
DRAWINGS)
FIRE ALARM ADA APPROVED STROBE WALL DEVICE, 84"AFF
FIRE ALARM ADA APPROVED HORN WALL DEVICE, 84"AFF
FIRE ALARM ADA PULL STATION, 48"AFF
FIRE ALARM ADA APPROVED SPEAKER WALL DEVICE, 84"AFF
P
F
F
CEILING MOUNTED CO DETECTOR
SMOKE DUCT MOUNTED DETECTOR
HEAT DETECTOR
F co
P F
T
FIRE ALARM ADA APPROVED HORN/STROBE
WALL DEVICE, 84"AFF
C M
M
FIRE ALARM ADA APPROVED STROBE CEILING DEVICE
FIRE ALARM ADA APPROVED HORN/STROBE CEILING DEVICE
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FACP
FAA
FIRE ALARM ADA APPROVED SPEAKER CEILING DEVICE
FIRE ALARM ADA APPROVED SPEAKER/STROBE WALL DEVICE,
84"AFF
F
FIRE ALARM ADA APPROVED SPEAKER/STROBE CEILING DEVICE
FIRE ALARM SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.
ABORT SWITCH
CONTROL (C) MODULE, MONITOR (M) MODULE
FIRE ALARM REMOTE AMPLIFIERAMP
FIRE ALARM LOCAL OPERATOR CONSOLELOC
PHOTOCELL (EXTERIOR, INTERIOR)PC
LIGHT SWITCH, 48" UNO.
USE "X" TO DESIGNATE TYPE. TYPICAL OF MOST SWITCHES.
BLANK = SINGLE-POLE, SINGLE-THROW
3 = 3-WAY, SINGLE-POLE, DOUBLE-THROW
4 = 4-WAY, DOUBLE-POLE, DOUBLE-THROW
D = DIMMER SWITCH, 0-10V
DOS = COMBINATION DIMMER/WALL OCCUPANCY SENSOR, DUAL
TECHNOLOGY
F = FAN CONTROL
LV = LOW-VOLTAGE, MULTI-BUTTON WALL STATION
M = MOTOR-RATED
OS = WALL OCCUPANCY SENSOR-SINGLE OR 3-WAY, DUAL
TECHNOLOGY
S = PROJECTION SCREEN CONTROL
T = TIMER SWITCH
VOS = COMBINATION VACANCY/WALL OCCUPANCY SENSOR, DUAL
TECHNOLOGY
USE "x" TO DESIGNATE ZONE.
CEILING/WALL MOUNTED EXIT SIGN
WALL MOUNTED EMERGENCY LIGHTING FIXTURE
RECESSED DOWNLIGHT, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
EMERGENCY RECESSED DOWNLIGHT, REFER TO LIGHTING
FIXTURE SCHEDULE FOR DETAILS.
2X4 RECESSED TROFFER, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
2X2 RECESSED TROFFER, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
LINEAR STRIP FIXTURE, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
CEILING MOUNTED OCCUPANCY SENSOR, DUAL
TECHNOLOGY. WATTSTOPPER DT-300 OR EQUIVALENT.
OS
LIGHTING SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.
CEILING MOUNTED VACANCY SENSOR, DUAL
TECHNOLOGY. WATTSTOPPER DT-300 OR EQUIVALENT.
EMERGENCY 2X4 RECESSED TROFFER, REFER TO
LIGHTING FIXTURE SCHEDULE FOR DETAILS.
EMERGENCY 2X2 RECESSED TROFFER, REFER TO
LIGHTING FIXTURE SCHEDULE FOR DETAILS.
EXTERIOR WALL FIXTURE, REFER TO LIGHTING FIXTURE
SCHEDULE FOR DETAILS.
VS
AE a
A-1
INDICATES FIXTURE TYPE
INDICATES EMERGENCY FIXTURE
INDICATES SWITCHING
INDICATES PANEL AND/OR CIRCUIT NUMBER
Xx
DATA/PHONE OUTLET WALL MOUNTED 18" AFF UNO, WITH 3/4" CONDUIT &
PULLSTRING STUBBED TO 6" ABOVE ACCESSIBLE CEILING, TERMINATED WITH
BUSHING.
TV OUTLET, SINGLE GANG BOX, 18" AFF UNO, WITH 1" CONDUIT IN
WALL, STUBBED OUT 6" ABOVE CEILING W/PULL STRING.
TV
DATA/PHONE OUTLET FLOOR MOUNTED, WITH 1" CONDUIT &
PULLSTRING STUBBED TO 6" ABOVE ACCESSIBLE CEILING.
FURNITURE COMMUNICATION/DATA CONNECTION.
DOORBELL PUSH BUTTON, PROVIDE SINGLE GANG BOX WITH 3/4"C
& PULLSTRING TO PLENUM SPACE ABOVE CEILING LEVEL
PAGING SYSTEM CONTROL UNITPAG
SPEAKER, CEILING/PENDANT, WALLS
S
PB
WIRELESS ACCESS POINT, CEILING MOUNTED
LOW VOLTAGE SYMBOL LEGEND *NOT ALL SYMBOLS ARE USED ON PLANS.
**LISTED MOUNTING HEIGHTS ARE TO CENTER OF DEVICE.
C
DATA OUTLET, CEILING MOUNTED
ACCESS CONTROL CARD READER
ELECTRIC DOOR LOCK WITH INTEGRAL REQUEST-TO-EXIT SWITCHDL
CR
360 DEGREE WALL OR CEILING MOUNTED SECURITY CAMERA
DOOR MAGNETIC CONTACTDC
DB
DURESS PUSH BUTTON, PROVIDE SINGLE GANG BOX WITH 3/4"C &
PULLSTRING TO PLENUM SPACE ABOVE CEILING LEVEL
BACKBOARD: 3/4" 4FT X 8FT FIRE-RATED PLYWOOD
GROUND BAR
MOTION SENSOR
SECURITY KEY PAD
MS
KP
APPLICATION OF THE DRAWINGS:
1. THE DRAWINGS ARE AN ESSENTIAL PART OF THE
CONTRACT DOCUMENTS AND SHALL BE USED IN
CONJUNCTION WITH THE REQUIREMENTS OF THE
SPECIFICATIONS SECTION OF THE CONTRACT
DOCUMENTS. IN NO CASE ARE THE DRAWINGS TO
BE CONSTRUED TO REQUIRE LESS THAN WHAT IS
REQUIRED BY LOCAL CONDITIONS AND STATE AND
LOCAL BUILDING CODES AND OTHER APPLICABLE
LAWS.
2. THE OMISSION OF ANY PART OF THE CONTRACT
DOCUMENTS IS LIKELY TO RESULT IN CONFLICTS,
INCOMPLETE INSTALLATION, OR A FINISHED
PRODUCT THAT DOES NOT FUNCTION IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
ANY SUCH CIRCUMSTANCES IDENTIFIED BY THE
DESIGN PROFESSIONAL, THE OWNER, OR THE
AUTHORITIES HAVING JURISDICTION SHALL
REQUIRE THE CONTRACTOR TO REMEDY THE
IDENTIFIED DEFICIENT WORK AT NO ADDITIONAL
COST TO THE PROJECT.
3. DRAWINGS SHOULD NOT BE RELIED UPON TO
DETERMINE THE QUANTITY OF MATERIALS TO BE
SUPPLIED WITHOUT RECOURSE TO THE
SPECIFICATIONS.
4. DRAWINGS ARE DIAGRAMMATIC AND ARE NOT
REPRESENTATIVE OF ALL POTENTIAL CONDITIONS.
COORDINATE WITH ALL DISCIPLINES TO ENSURE
PROPER INSTALLATION OF ALL SYSTEMS AND
EQUIPMENT.
5. CONFLICTS: THE PROVISION, SPECIFICATION OR
DRAWING IN THE CONTRACT DOCUMENTS WHICH
PROVIDES FOR THE HIGHER QUALITY OR QUANTITY
SHALL TAKE PRECEDENCE OVER A CONFLICTING
OR INCONSISTENT PROVISION, SPECIFICATION OR
DRAWING IN THE CONTRACT DOCUMENTS. WHERE
SUCH A CONFLICT IS IDENTIFIED, THE
CONTRACTOR SHALL SUBMIT A REQUEST FOR
INFORMATION (RFI) FOLLOWING THE PROCEDURES
OUTLINED IN THE SPECIFICATIONS, SECTION 01
3000 ADMINISTRATIVE REQUIREMENTS.
6. REFER TO ARCHITECTURAL FLOOR PLANS,
REFLECTED CEILING PLANS, AND ELEVATIONS FOR
EXACT LOCATIONS OF ALL EQUIPMENT, LIGHTING,
AND DEVICES.
7. SEE SHEET G-00X FOR COMMON PROJECT
ABBREVIATIONS, DEFINITIONS, AND GENERAL
NOTES APPLICABLE TO THESE DRAWINGS.
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEETA/E FIRM
PRIME:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
STRUCTURAL
MH STRUCTURES
POWDER SPRINGS, GA
LANDSCAPE
CATALYST DESIGN
GROUP
WINTER PARK, FL
COASTAL
MOFFATT & NICHOL, INC
MIAMI, FL
/4
/2
:1
:3
A
M A u to d e s k D o c s /2
-4
A
C A
S A
F E
E S
T A
T
IO
N /2
-4
A
C A
S A
E
.r v t
ELECTRICAL GENERAL
E001
LRJ
KEJ
RER
74 119
324271
09/05/2025
189856
MC CABLE SHALL ONLY BE USED FROM THE LAST JUNCTION BOX TO THE DEVICE BEING
FED. MC CABLE SHALL NOT BE USED TO FEED PANELBOARDS, ROUTING FROM JUNCTION
BOX TO JUNCTION BOX OR IN AREAS WITH EXPOSED CEILINGS, CLOUD CEILINGS OR
EXPOSED WALLS.
MC CABLE INSTALLATION NOTE:
RESTRICTIONS OF SURFACE MOUNTED CONDUIT AND DEVICES FOR NEW CONSTRUCTION:
UNLESS OTHERWISE NOTED ON THE DRAWINGS OR SPECIFICATIONS, ALL CONDUIT
SHALL BE CONCEALED AND WALL MOUNTED DEVICES RECESSED FLUSH WITHIN
WALLS. SURFACE MOUNTED CONDUIT AND DEVICES ARE PROHIBITED.
RESTRICTIONS OF SURFACE MOUNTED CONDUIT AND DEVICES FOR RENOVATIONS:
UNLESS OTHERWISE NOTED ON THE DRAWINGS OR SPECIFICATIONS, ALL CONDUIT SHALL
BE CONCEALED AND WALL MOUNTED DEVICES RECESSED FLUSH WITHIN EXISTING WALLS.
CONTRACTORS PRICING TO INCLUDE CUTTING EXISTING WALLS TO INSTALL CONCEALED
CONDUIT AND FLUSH WALL MOUNTED DEVICES. PRICE TO ALSO INCLUDE PATCHING
EXISTING WALLS BACK TO ORIGINAL CONDITION. SURFACE MOUNTED CONDUIT AND
DEVICES ARE PROHIBITED.
MASTER KEY: ELECTRICAL NEW WORK SHEET NOTES
SEE INDIVIDUAL ELECTRICAL SHEETS FOR APPLICATION
TAG # TAG DESCRIPTION
1 NEW FEEDER RUN UNDERGROUND TO MAIN ELECTRICAL PANEL IN EXISTING
CASTILLO DE SAN MARCOS. SEE ES101 FOR MORE INFORMATION.
2 EXISTING INTRUSION PANEL TO BE RELOCATED FROM EXISTING TICKET BOOTH
BUILDING TO NEW TICKET BOOTH BUILDING.
3 UNDERGROUND CONDUIT RUN 24" BELOW FINISH GRADE FROM MAIN ELECTRICAL
PANEL IN EXISTING CASTILLO DE SAN MARCOS TO NEW PANEL BOARD LOCATED IN
THE NEW TICKET BOOTH BUILDING. SEE 3/E100 FOR MORE INFORMATION.
4 IT EQUIPMENT. REFER TO 5/E100 FOR ELEVATION.
5 REMOVE EXISTING MOAT LIGHT, AND REPLACE ONE FOR ONE (RAB LIGHTING:
FXLED78SFY W/ PROTECTIVE LENS GDFXLED78P & PROTECTIVE MESH SCREEN
GDFXLED78W & BSF MOUNT). REPLACE ALL WIRING, CONDUIT AND ANY
ASSOCIATED EQUIPMENT ONE FOR ONE.
6 PROVIDE AND INSTALL SECURITY CAMERA OVER DESK, POINTED AT THE DESK.
7 EXISTING CAMERA FROM EXISTING TICKET BOOTH TO BE REUSED AND INSTALLED
IN THIS LOCATION.
8 PROVIDE AND INSTALL WALL-MOUNT IT RACK.
9 PROVIDE AND INSTALL 120V/1P 20A POWER CONNECTION FOR MICROPHONE.
Notes:
Continuous 0.50 kVA 125.00% 0.63 kVA
Lighting 0.34 kVA 125.00% 0.42 kVA
Power 1.30 kVA 100.00% 1.30 kVA Total Est. Demand: 26.41 A
Receptacle 4.14 kVA 100.00% 4.14 kVA Total Conn.: 25.49 A
Motor 0.50 kVA 125.00% 0.63 kVA Total Est. Demand: 9.52 kVA
HVAC 2.60 kVA 100.00% 2.60 kVA Total Conn. Load: 9.18 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 24.94 A 26.43 A 25.70 A
Total Load: 2.99 kVA 3.16 kVA 3.07 kVA
41 SPACE -- 1 -- -- 1 -- SPACE 42
39 SPACE -- 1 -- -- 1 -- SPACE 40
37 SPACE -- 1 -- -- 1 -- SPACE 38
35 SPACE -- 1 -- -- 1 -- SPACE 36
33 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 34
31 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 32
29 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 30
27 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 28
25 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 26
23 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 24
21 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 22
19 SPARE 20 A 1 0.00 kVA 0.00 kVA 1 20 A SPARE 20
17 Power 20 A 1 0.80 kVA 0.00 kVA 1 20 A SPARE 18
15 ACCESS CONTROL PANEL 20 A 1 0.50 kVA 0.50 kVA 1 20 A INTRUSION PANEL 16
13 IT EQUIPMENT 20 A 1 0.36 kVA 0.50 kVA 1 30 A FACP 14
11 RECEPT. RM: 103 20 A 1 0.54 kVA 0.15 kVA 1 20 A LTG EXTERIOR 12
9 RECEPT. RM: 104,103, 101 20 A 1 0.72 kVA 0.54 kVA 1 20 A RECEPT. RM: 103 10
7 RECEPT. RM: 103 20 A 1 0.54 kVA 1.30 kVA 8
5 RECEPT. RM: 102 20 A 1 0.36 kVA 1.30 kVA
2 20 A VRHP-1
3 FRIDGE RECEPT. RM: 102 20 A 1 0.18 kVA 0.72 kVA 1 20 A RECEPT. RM: 104 4
1 LTG RM: 101,102,103,104 20 A 1 0.19 kVA 0.18 kVA 1 20 A EXTERNAL RECEPT. 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 MCB Rating: 60 A
Mounting: Recessed Wires: 4 Mains Rating: 60 A
Supply From: MAIN BUILDING SERVICE Phases: 3 Mains Type: MCB
Location: OFFICE 104 Volts: 120/208 Wye A.I.C. Rating: TBD
Branch Panel: P1
RobbieRahn RR_Florida Seal
OS
D
D D
OS
P
CR
D L
F A
C P
DB
DB
DB
DB
MS
J
J
J J
1. ALL ELECTRICAL FEEDERS FOR CIRCUITS SHALL BE ONE RUN 2#12, 1#12G. IN 1/2"C.
UNLESS NOTED OTHERWISE ON DRAWINGS.
2. CONDUCTOR RUNS GREATER THAN 75 LINEAR FEET SHALL BE UPSIZED TO #10 WIRE
UNLESS NOTED OTHERWISE.
3. COORDINATE FINISHES AND MOUNTING HEIGHTS OF ALL DEVICES WITH
ARCHITECTURAL PLANS.
4. ALL CONDUIT AND OUTLET BOXES SHALL BE INSTALLED WITHIN WALL CAVITIES. NO
EXPOSED CONDUITS ARE ACCEPTABLE BELOW CEILING LEVEL.
5. ROUTE ALL EXTERIOR LIGHTING THROUGH PHOTOCELL AND LIGHTING CONTACTOR.
6. COORDINATE WITH THE PARK FOR ACCEPTABLE MANUFACTURERS FOR ALL NEW
SECURITY AND FIRE ALARM EQUIPMENT.
7. PROVIDE MACHINE PRINTED ADDRESS LABELS ON ADDRESSABLE DEVICES. PROVIDE
MACHINE PRINTED LABELS ON NOTIFICATION APPLIANCES WITH APPROPRIATE
CIRCUIT INFORMATION. LABELS TO BE VISIBLE FROM THE FLOOR WITHOUT
MAGNIFICATION.
GENERAL NOTES:
C
AE A AE
AE
XSE
b a b
SE
SE
SE
P1-1aP1-1a P1-1a
P1-1
P1-1b
P1-12
P1-12P1-12
P1-12
P1-1
TICKETS
OFFICE
ENTRY
BREAK
AREA
XP1-1
SE
SE
P1-12
P1-12
44"
OFFICE
TICKETS
BREAK
AREA
ENTRY
44"
P1
VRHP-1
VRFC-01
WPG
VRFC-02
44" 44"
44"
P1-4
P1-4
P1-9
P1-9
P1-9
P1-9
P1-11
P1-10
P1-7
P1-11 P1-10
P1-7
P1-3 P1-5
P1-5
P1-14
P1-13
E100
P1-16
P1-17
P1-17
P1-17
P1-17
60.4
PANEL "P1"
280/120V 3Ø, 4W
1#8
OFFICE 104
BATT/CHGR
FACP
DEDICATED 120V AC, 20A, 1P
BRANCH CIRCUIT
SLC CIRCUITS
CLASS B
NAC CIRCUITS
CLASS B
ACCESS
CONTROL
SYSTEM
(2) DEDICATED TELEPHONE LINES
P
OFFICE 104
DL
FIRE ALARM DEVICES: REFER TO FLOOR
PLANS FOR LOCATIONS AND QUANTITIES.
P1
WALL-MOUNT
IT RACK
ACCESS
CONTROL
PANEL
2'X4' TELEPHONE
BACKBOARD
GROUND BAR
FIBER
TERMINATION
BOX (UTILITY
DEMARCATION)
25-PAIR COPPER PROTECTION BLOCKS
(UTILITY DEMARCATION)
"5
CONDUIT
P1-15
RECEPTACLE
FOR POWER
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEETA/E FIRM
PRIME:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
STRUCTURAL
MH STRUCTURES
POWDER SPRINGS, GA
LANDSCAPE
CATALYST DESIGN
GROUP
WINTER PARK, FL
COASTAL
MOFFATT & NICHOL, INC
MIAMI, FL
/4
/2
:1
:5
A
M A u to d e s k D o c s /2
-4
A
C A
S A
F E
E S
T A
T
IO
N /2
-4
A
C A
S A
E
.r v t
ELECTRICAL PLAN - LIGHTING,
POWER AND SYSTEMS
E100
LRD
KEJ
RER
76 119
324271
09/05/2025
189856
SHEET NOTES: (APPLY THIS SHEET ONLY)
SEE MASTER KEY ON E-001 FOR COMPLETE SHEET NOTE LIST
TAG # TAG DESCRIPTION
1 NEW FEEDER RUN UNDERGROUND TO MAIN ELECTRICAL PANEL IN EXISTING CASTILLO DE
SAN MARCOS. SEE ES101 FOR MORE INFORMATION.
2 EXISTING INTRUSION PANEL TO BE RELOCATED FROM EXISTING TICKET BOOTH BUILDING TO
NEW TICKET BOOTH BUILDING.
4 IT EQUIPMENT. REFER TO 5/E100 FOR ELEVATION.
6 PROVIDE AND INSTALL SECURITY CAMERA OVER DESK, POINTED AT THE DESK.
7 EXISTING CAMERA FROM EXISTING TICKET BOOTH TO BE REUSED AND INSTALLED IN THIS
LOCATION.
8 PROVIDE AND INSTALL WALL-MOUNT IT RACK.
9 PROVIDE AND INSTALL 120V/1P 20A POWER CONNECTION FOR MICROPHONE.
SCALE AE100
1 FIRST FLOOR PLAN - LIGHTING
SCALE AE100
2 FIRST FLOOR PLAN - POWER & SYSTEMS
SCALE
SCALE OF FEET
A
B L D
G
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL LAMP LOAD COMMENTS
A 2'X2' RECESSED DIMMABLE LED FIXTURE LITHONIA OR EQUAL 2BLT 33L ADP EZ1 LP835 LED, 3500K 27 VA
AE 2'X2' RECESSED DIMMABLE LED EMERGENCY FIXTURE LITHONIA OR EQUAL 2BLT2 33L ADP EZ1 LP835 EL14L LED, 3500K 27 VA PROVIDE 90 MINUTE BACKUP BATTERY WITH ADDITIONAL UNSWITCHED HOT CONDUCTOR
C 6" RECESSED DIMMABLE DOWNLIGHT LITHONIA OR EQUAL LDN6 35/10 LO6 WR 277 EZ1 LED, 3500K 60 VA
SE EXTERIOR WALL SCONCE HAMPTON BAY OR
EQUAL
JBO1691A-4 LED, 3500K 25 VA PROVIDE 90 MINUTE BACKUP BATTERY WITH ADDITIONAL UNSWITCHED HOT CONDUCTOR. PROVIDE BODINE ELIS400CEC REMOVE BATTERY BACKUP FOR EMERGENCY LIGHT.
X LED EXIT SIGN ISOLITE OR EQUAL RL R U WH MTEB LED 5 VA PROVIDE 90 MINUTE BACKUP BATTERY WITH ADDITIONAL UNSWITCHED HOT CONDUCTOR
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
EQUIPMENT TAG DESCRIPTION VOLTAGE PHASE FEEDER DISCONNECT WATTS HP FLA MCA MOCP CIRCUIT COMMENTS
VRHP-1 SPLIT SYSTEM 208 V 1 1 SET(S) OF 2#12 AWG, 1#12 AWG G. - 1/2"C. 30A/2P/NF/NEMA 3R 12.5 A 15.6 A 20 A P1-6,8 INDOOR UNITS VRFC-1-01 & VRFC-1-02 FED FROM
OUTDOOR UNIT.
E100
3 ELECTRICAL RISER
CONDUCTOR SCHEDULE
Mark Capacity Sets Phase Wire Equipment
Ground Conduit
60.4 60 AMP 1 3 PHASE/4 WIRE (4)#4 (1)#10 1-1/4"
E100
4 FIRE ALARM RISER
SCALE
SCALE OF FEET
2 0 2 4 B
SCALE AE100
5 ELEVATION - IT EQUIPMENT
THERMOSTAT, ZONE
TEMPERATURE SENSOR,
OR OTHER H.M.I. SEE
DETAIL M-XXX FOR
PLACEMENT OF J-BOX.
FIRE ALARM DEVICE
B
LIGHT SWITCH
FINISHED
FLOOR
A
LIGHT SENSOR /
MOTION DETECTOR
DEVICES NOT
ALIGNED
DEVICES ALIGNED
ALONG EDGE
INSTEAD OF ALONG
CENTERLINE
FINISHED DOOR FRAME. SEE
SHEET A-6XX FOR FRAME
WIDTH AND DOOR DETAILS
TYP.
1"
C D
GENERAL WALL-MOUNTED DEVICE NOTES:
1. PROVIDE J-BOXES FOR SWITCHES AND H.M.I. DEVICES SERVING EQUIPMENT
SPECIFIED UNDER DIVISIONS 22 AND 23. ENSURE ALL WALL-MOUNTED DEVICES ARE
ALIGNED TO CENTERLINE WITH ALL OTHER DEVICES IN THE IMMEDIATE PROXIMITY.
2. INSTALLATION HEIGHTS ARE AS FOLLOWS, UNLESS NOTED OTHERWISE:
A = SEE DETAIL X/G-XXX FOR SPACING FROM EDGE OF DOOR FRAME.
B = 48 INCHES A.F.F. (STUD WALL) OR 44 INCHES A.F.F. (STUD WALL W/ 10"-25" DEEP
COUNTER)
C = 80 INCHES A.F.F.
D = 96 INCHES A.F.F. (OR 6 INCHES BELOW THE CEILING, WHICHEVER IS LOWER)
ACCESS CONTROL PANEL
DIMMER (IF SEPARATE
FROM LIGHT SWITCH)
NEUTRAL
HOT
WHT
BLK
-1
V
D R
IV
E
R
WHT
BLK
GRAY
PURPLE
GREEN
GROUND
GRAY
PURPLE
BLUE
LINE VOLTAGE
STEEL JOIST
PROVIDE APPROVED
MECHANICAL
FASTENERS AT ALL 4 CORNERS
OF
LIGHT FIXTURE TO SECURE
FIXTURE
TO CEILING GRID SYSTEM PER
NEC.
LED LAY-IN
LIGHT FIXTURE
#12 ZINC COATED
HANGER WIRE, PROVIDE
AT ALL 4 CORNERS OF
EACH FIXTURE.
ACOUSTICAL CEILING TILE
FLEXIBLE
CONDUIT
CONNECTION 6'
MAX
EMT CONDUIT SHALL BE SUPPORTED FROM
STEEL OR
FIXED STRUCTURE WITH APPROVED
HANGERS AND
FITTINGS. CONDUIT SHALL NOT BE
SUPPORTED BY
SUSPENDED CEILING SYSTEM OR LIGHT
FIXTURE
HANGERS.
CONCRETE OR
STEEL ROOF DECK
JUNCTION
BOX
SIZED
PER NEC
AS REQ'D
CEILING
NOTE 2
NOTE 3
48" AFF
96" AFF MAX
80" AFF
5' MAX
6"
3" MIN
A/C
SUPPLY OR
RETURN
DIFFUSER
CEILING
MOUNTED
SMOKE/HEAT
DETECTOR
24"
FIREFIRE
MAGNETIC DOOR HOLDER
MANUAL PULL STATION
FIRE
PHONE
JACK
4"
CEILING
MOUNTED
SMOKE/HEAT
DETECTOR;
NOTE 1
4"
12" MAX
80" AFF
FINISHED
FLOOR
NOTES:
1.
2.
3.
FINISHED
WALL
WALL MOUNTED
SMOKE/HEAT
DETECTOR;
NOTE 1
REFERENCES:
AUDIBLE/VISUAL OR
VISUAL ONLY
APPLIANCES
80" - ADA
80" MIN - NFPA
80" MIN/96" MAX - IBC
NFPA 72 2022 EDITION
SECTION 18.5.5.1
SECTION 18.5.5.7.2
NFPA 72 2019 EDITION
SECTION 18.5.5.1
SECTION 18.5.5.5.2
NFPA 72 2016 EDITION
SECTION 18.5.5.1
SECTION 18.5.5.4.2
MANUAL PULL
STATIONS
48" MAX - ADA
42" MIN/48" MAX - NFPA
NFPA 72 2022 EDITION
SECTION
17.15.4-17.15.6
NFPA 72 2019 EDITION
SECTION
17.15.4-17.15.6
NFPA 72 2016 EDITION
SECTION
17.14.3-17.14.5
REFER TO THE PROPER DEVICE INSTALLATION
INSTRUCTIONS FOR
BACKBOX MOUNTING HEIGHT.
SYNCHRONIZE MORE THAN 2 APPLIANCES IN ANY FIELD OF
VIEW.
MAGNETIC DOOR HOLDER - POSITION 3" LESS THAN WIDTH
OF DOOR.
1.
NOTES:
70" AFF.
FINISHED CEILING
LINE
FINISHED FLOOR
FIELD VERIFY BOX
REQUIREMENTS
FIELD CONDUIT
1" CONDUIT
J--BOX
LOGO
DIM: 12"W x 16"H x 3"D
120VAC
PAD-3
FIRE ALARM PANEL SHALL BE TERMINATED
TO A DEDICATED 120VAC PROTECTED POWER
SOURCE. THE DEDICATED POWER SOURCE
SHALL BE CLEARLY LABELED 'FIRE ALARM' IN
RED AT THE DISCONNECT. SUCH DISCONNECTS
SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
PERSONNEL. ANY FIRE ALARM UNIT BEING
PROVIDED POWER SHALL BE LABELED AT THE
UNIT, IDENTIFYING THE LOCATION OF ITS
CORRESPONDING POWER DISCONNECT.
CONDUIT MUST NOT STUB INTO THE
BOTTOM OR THE LOWER SIDES OF
THE CABINET BY THE BATTERIES
OTHERWISE THE BATTERIES WILL
NOT FIT INSIDE OF THE
ENCLOSURE.
FIXTURE "G"
SURFACE MOUNT "SM"
6” DIAMETER CONCRETE
PEDESTAL WITH BUILT IN
CONDUIT FOR CIRCUIT ROUTING.
ENSURE CONDUIT IS
WATERTIGHT ONCE FIXTURE IS
INSTALLED. ENSURE CONCRETE
PEDESTAL IS MOUNTED 12”
MINIMUM BELOW GRADE AND
STANDS 4” ABOVE GRADE.
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEETA/E FIRM
PRIME:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
STRUCTURAL
MH STRUCTURES
POWDER SPRINGS, GA
LANDSCAPE
CATALYST DESIGN
GROUP
WINTER PARK, FL
COASTAL
MOFFATT & NICHOL, INC
MIAMI, FL
/4
/2
:1
:0
A
M A u to d e s k D o c s /2
-4
A
C A
S A
F E
E S
T A
T
IO
N /2
-4
A
C A
S A
E
.r v t
ELECTRICAL DETAILS
E701
LRD
KEJ
RER
77 119
324271
09/05/2025
189856
NOT TO SCALEE701
3 WALL-MOUNTED ELECTRICAL DEVICE PLACEMENT DETAIL
NOT TO SCALEE701
4 TYPICAL 0-10V DIMMER SWITCH WIRING DIAGRAM
NOT TO SCALEE701
2 TYPICAL LAY-IN FIXTURE INSTALLATION DETAIL
NOT TO SCALEE701
5 FIRE ALARM DEVICES MOUNTING HEIGHTS (PER NFPA 72)
NOT TO SCALEE701
1 TYPICAL FIRE ALARM PANEL MOUNTING DETAIL
NOT TO SCALEE701
6 ABOVE GRADE LIGHTING FIXTURE MOUNT
FRONT VIEW
FCP
UPS
1. INSTALL A 2U FIBER CONNECTOR PANEL.
2. INSTALL (48) PORT PATCH PANEL.
3. INSTALL (24) PORT VOICE PATCH PANEL.
4. PROVIDE AND INSTALL NVR (NETWORK
VIDEO RECORDER) FOR VIDEO
SURVEILLANCE SYSTEM.
5. PROVIDE AND INSTALL ACCESS CONTROL
SYSTEM RACK MOUNTED CONTROL UNIT.
6. PROVIDE AND INSTALL RACK MOUNTED
UPS UNIT, 3000VA, 120V, 30A. APC SMART-
UPS OR EQUIVALENT.
1. PROVIDE AND INSTALL (2) 4" PVC CONDUIT WITH MESH INNDERDUCTS AND
PULLSTRINGS FROM EXISTING MAIN IT SERVICE. SEE DETAIL 7/E702. PROVIDE
AND INSTALL NEW 12-STRAND MULTI-MODE FIBER TERMINATION BOX ON NEW
PLYWOOD BACKBOARD FOR TELECOM DEMARCATION. EXTEND EXISTING
TICKET BOOTH IT SERVICE TO NEW TICKET BOOTH TO FIBER CONNECTOR
PANEL. REFER TO C002 FOR EXISTING IT SERVICE LOCATION.
2. 2' BY 4' BY 3/4" FIRE RETARDANT PLYWOOD BACKBOARD FOR TELECOM
EQUIPMENT.
3. 2" BY 10" BY 1/4" THICK SOLID COPPER TELECOM GROUND BAR. CONNECT TO
BUILDING SERVICE GROUND WITH #4/0 INSULATED COPPER GROUND
CONDUCTOR IN 3/4" CONDUIT.
4. CONTRACTOR TO PROVIDE PROTECTION BLOCKS.
5. DATA OUTLET, LOCATED AS INDICATED ON FLOOR PLANS, WITH (2) CAT6A
CABLE PER OUTLET, TERMINATED TO JACKS PER EIA/TIA 568B STANDARDS.
CABLES SHALL BE IN 3/4" METAL CONDUIT ROUTED ABOVE CEILING TO CLOSEST
TELECOM/DATA BACKBOARD. (TYPICAL)
6. PROVIDE AND INSTALL "PoE" (POWER OVER ETHERNET) SWITCHES TO BE USED
FOR ACCESS CONTROL SYSTEM.
7. WIRELESS ACCESS POINT, LOCATED AS INDICATED ON FLOOR PLANS,
CONNECTED PER EIA/TIA STANDARDS. CABLES SHALL BE IN 3/4" METAL
CONDUIT ROUTED ABOVE CEILING TO CLOSEST TELECOM/DATA BACKBOARD.
(TYPICAL)
8. PROVIDE AND INSTALL 24" WIDE, 15U, ENCLOSED, LOCKABLE, WALL-MOUNTED
CABINET WITH COOLING FANS AND INTERNAL RAILS TO SUPPORT 19" RACK
EQUIPMENT. SWITCHES AND OTHER IT EQUIPMENT SHALL BE PROVIDED AND
INSTALLED BY GOVERNMENT. SEE ELEVATION 5/E702.
# TELECOM RISER KEY NOTES:
IT/SERVER ROOM 107 ADMINISTRATIVE BUILDING
EXTENSION FROM
EXISTING BUILDING
MAIN IT SERVICE
INTRUSION PANEL
(INSTALLED IN
OFFICE 104)
DL DL
KP KP
MAIN CALL OUT LINE: PROVIDE
TELEPHONE LINE TO VOICE BLOCK.
120V POWER
DOOR LOCKS, KEY PADS AND DURRESS
BUTTONS: REFER TO FLOOR PLANS FOR
LOCATIONS AND QUANTITIES.
DB DB
ACCESS
CONTROL
PANEL
CR CR
120V, 1P, 20A BRANCH CIRCUIT
POWER
(2) DEDICATED TELEPHONE
LINES
OFFICE 104
DL MS
DL MS 10
NETWORK VIDEO
RECORDER (NVR)
WORK
STATION
LOCAL
VIEWING
MONITOR
ROUTER
(1) CAT6A CABLE PER
CAMERA
(1) TVSS DEVICE
PER CAMERA
INTERIOR
CAMERA
INTERIOR
CAMERA
EXTERIOR
CAMERA
5 EXTERIOR
CAMERA
FINISH GRADE
18" MINIMUM
DUCTBANK
MARKING TAPE
(TYPICAL)
7-1/2"
12"
CONDUITS PER SITE PLAN
MESH FABRIC
INNERDUCTS
(TYPICAL)
TRACER WIRE
GENERAL NOTES (THIS DETAIL ONLY)
1. GROUND AND BOND TRACER WIRES.
2. PROVIDE PULL STRINGS/MULE TAPE IN EACH CONDUIT.
3. PROVIDE MESH FABRIC INNERDUCTS IN CONDUITS FOR SERVICE PROVIDER USE.
1. PROVIDE NETWORK VIDEO RECORDER: MOUNT IN IT/SERVER OFFICE 104. CONTRACTOR TO CONFIGURE VIDEO MANAGEMENT SYSTEM FOR ACTIVITY DETECTION RECORDING. ALL VIDEO TO MAINTAINED FOR
MINIMUM OF 30 DAYS.
2. PROVIDE WORK STATION: CONTRACTOR TO LOAD AND CONFIGURE VIDEO SURVEILLANCE SOFTWARE ON UP TO (2) GOVERNMENT PROVIDED WORKSTATIONS. ALL CAMERA SETTINGS TO BE PROGRAMMED BY
CONTRACTOR TO GOVERNMENT'S SATISFACTION.
3. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6A CABLE CONTINUOUS PER IP CAMERA. REFER TO PLANS FOR QUANTITY AND LOCATIONS. ALL ABOVE GROUND CABLING SHALL BE INSTALLED IN 1" METAL
CONDUIT. ALL UNDERGROUND CABLING SHALL BE INSTALLED IN 1" PVC CONDUIT.
4. CONTRACTOR TO PROVIDE AND INSTALL ALL CATEGORY 6A CABLE FOR DEVICE INTERCONNECTIONS. ALL CABLING SHALL BE INSTALLED IN 1" METAL CONDUIT. ALL UNDERGROUND CABLING SHALL BE INSTALLED IN
1" PVC CONDUIT.
5. CONTRACTOR TO PROVIDE AND INSTALL LOW LIGHT, WIDE DYNAMIC RANGE, COLOR, IP MEGAPIXEL
CAMERAS FOR EXTERIOR LOCATIONS. SEE FLOOR PLAN FOR LOCATIONS.
6. PROVIDE TRANSIENT VOLTAGE SURGE PROTECTION FOR ALL CAMERAS AT PATCH PANEL AND CAMERA
LOCATIONS.
7. PROVIDE 24" LOCAL VIEWING MONITOR AND CONNECT TO NETWORK VIDEO RECORDER DISPLAY OUTPUT.
COORDINATE WITH CONTRACTING OFFICER FOR CAMERA VIEW SETUP.
8. CONTRACTOR TO PROVIDE DEDICATED UPS BACKUP FOR NETWORK VIDEO RECORDER AND ASSOCIATED
CAMERAS SIZED TO ALLOW 45 MINUTES OF RUN TIME.
9. PROVIDE ACCESS CONTROL PANEL IN OFFICE 104. ACCESS CONTROL SYSTEM AND DEVICES SHALL ALLOW FOR UNIHIBITED EGRESS IN THE EVENT OF FIRE OR OTHER EMERGENCY. ALL EQUIPMENT SHALL
FAIL OPEN.
10. REFER TO FLOOR PLAN ON SHEET E100 FOR QUANTITY AND LOCATION OF DEVICES. ALL DEVICES SHALL
FAIL OPEN.
# ACCESS CONTROL/CCTV KEY NOTES:
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEETA/E FIRM
PRIME:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
STRUCTURAL
MH STRUCTURES
POWDER SPRINGS, GA
LANDSCAPE
CATALYST DESIGN
GROUP
WINTER PARK, FL
COASTAL
MOFFATT & NICHOL, INC
MIAMI, FL
/4
/2
:1
:0
A
M A u to d e s k D o c s /2
-4
A
C A
S A
F E
E S
T A
T
IO
N /2
-4
A
C A
S A
E
.r v t
LOW VOLTAGE DETAILS
E702
LRD
LRD
RER
78 119
324271
09/05/2025
189856
NOT TO SCALEE702
1 WALL-MOUNT RACK EQUIPMENT ELEVATION
NOT TO SCALEE702
3 TELECOM RISER
NOT TO SCALEE702
4 INTRUSION DETECTION RISER
NOT TO SCALEE702
5 ACCESS CONTROL RISER DIAGRAM
NOT TO SCALEE702
7 TELECOM UNDERGROUND SERVICE DUCT BANK
EXISTING CASTILLO DE SAN MARCOS
EXISTING CASTILLO
DE SAN MARCOS
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEETA/E FIRM
PRIME:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
STRUCTURAL
MH STRUCTURES
POWDER SPRINGS, GA
LANDSCAPE
CATALYST DESIGN
GROUP
WINTER PARK, FL
COASTAL
MOFFATT & NICHOL, INC
MIAMI, FL
/5
/2
:5
:2
A
M A u to d e s k D o c s /2
-4
A
C A
S A
F E
E S
T A
T
IO
N /2
-4
A
C A
S A
E
.r v t
ELECTRICAL SITE
ES101
LRD
KEJ
RER
75 119
324271
09/05/2025
189856
1. ALL EXISTING UNDERGROUND UTILITIES SHALL BE PHYSICALLY LOCATED PRIOR TO
ANY CONSTRUCTION IN THE VICINITY OF THE UTILITIES.
2. CONTRACTOR SHALL MAINTAIN A SAFE WORK SITE AND COMPLY WITH ALL LOCAL,
STATE, AND FEDERAL SAFETY REGULATIONS.
3. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ELECTRICAL PERMIT, PROVIDING ALL
SECONDARY UTILITY CONNECTIONS, AND COORDINATING AND OBTAINING
ELECTRICAL INSPECTION.
4. DAMAGE TO EXISTING FACILITIES AS A RESULT OF CONTRACTOR ACTIVITIES SHALL
BE REPAIRED OR REPLACED TO PRE-CONSTRUCTION CONDITIONS BY THE
CONTRACTOR AT NO COST TO THE OWNER.
5. CONTRACTOR SHALL RESTORE ALL DISTURBED AREAS TO PRE-CONSTRUCTION
CONDITIONS AND MATCH SURROUNDING AREA.
6. WHERE PROPOSED UNDERGROUND UTILITIES CROSS EXISTING UNDERGROUND
UTILITIES, CONTRACTOR SHALL EXCAVATE TEST PITS TO LOCATE EXISTING UTILITIES
PRIOR TO EXCAVATING FOR PROPOSED UTILITIES.
7. INTENT TO REUSE EXISTING DATA CABLING AND CONDUIT FOR LOW VOLTAGE
UTILITY. INTERCEPT THE EXISTING LOW VOLTAGE CONDUIT AND CABLING AND
EXTEND TO THE NEW TICKET BOOTH BUILDING. MATCH THE EXISTING CONDUIT AND
CABLING TO EXTEND TO THE NEW TICKET BOOTH BUILDING.
GENERAL NOTES:
SHEET NOTES: (APPLY THIS SHEET ONLY)
SEE MASTER KEY ON E-001 FOR COMPLETE SHEET NOTE LIST
TAG # TAG DESCRIPTION
3 UNDERGROUND CONDUIT RUN 24" BELOW FINISH GRADE FROM MAIN ELECTRICAL PANEL IN
EXISTING CASTILLO DE SAN MARCOS TO NEW PANEL BOARD LOCATED IN THE NEW TICKET
BOOTH BUILDING. SEE 3/E100 FOR MORE INFORMATION.
5 REMOVE EXISTING MOAT LIGHT, AND REPLACE ONE FOR ONE (RAB LIGHTING: FXLED78SFY W/
PROTECTIVE LENS GDFXLED78P & PROTECTIVE MESH SCREEN GDFXLED78W & BSF MOUNT).
REPLACE ALL WIRING, CONDUIT AND ANY ASSOCIATED EQUIPMENT ONE FOR ONE.
ES101
1 ELECTRICAL SITE
20 0 20 40
SCALE OF FEET
20 0 20 40
SCALE OF FEET
B L D
G
| E001 - ELECTRICAL GENERAL |
| 2023-416A CASA_E25 |
| E001 - ELECTRICAL GENERAL |
| E100 - ELECTRICAL PLAN - LIGHTING, POWER AND SYSTEMS |
| 2023-416A CASA_E25 |
| E100 - ELECTRICAL PLAN - LIGHTING, POWER AND SYSTEMS |
| E701 - ELECTRICAL DETAILS |
| 2023-416A CASA_E25 |
| E701 - ELECTRICAL DETAILS |
| E702 - LOW VOLTAGE DETAILS |
| 2023-416A CASA_E25 |
| E702 - LOW VOLTAGE DETAILS |
| ES101 - ELECTRICAL SITE |
| 2023-416A CASA_E25 |
| ES101 - ELECTRICAL SITE |