This document provides details for a federal solicitation opportunity. The solicitation number is 140P2021R0111 for NACE 242190 - Carter G. Woodson Home & Adjacent Properties from the Department of the Interior National Park Service National Office. The opportunity type is listed as a solicitation for work related to the Carter G. Woodson Home and Adjacent Properties. No other details are provided on products or services required, response dates, pricing terms, set asides, or incumbent contractors. The attached file is listed as drawings but no other information is included.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
16268
DATE:
7/8/2021
UP
UP
UP
UP
DATE:
DN
DN
DATE:
DATE:DATE:
DATE:
HVAC GENERAL NOTES
HVAC DUCTWORK NOTES
HVAC PIPING NOTESHVAC DEMOLITION NOTES
MOTORIZED EQUIPMENT (EF, B)
DUCTWORK SPECIALTIES
MISCELLANEOUS
SD
EQP
MD
*E/R/N
RETURN/EXHAUST OUTLET
DIFFUSER WITH FLEX DUCT
12Ø
24/12
14 x 6
24/12
12Ø
DIFFUSER
MOTORIZED DAMPER
EXISTING DUCT TO BE REMOVED
EXISTING DUCT TO REMAIN
RECTANGULAR DUCT
SOUND ATTENUATOR
ACOUSTICAL DUCT LINING
RETURN/EXHAUST OUTLET
FLEXIBLE DUCT CONNECTION
DUCT RISE IN RESPECT TO AIR FLOW
SPLITTER DAMPER
VOLUME EXTRACTOR
DUCT TURNING DOWN
DUCT TURNING UP
FLAT OVAL DUCT WITH SIZE
ROUND DUCT WITH SIZE
DUCT SECTION - RETURN
DUCT SECTION - SUPPLY
ROUND DUCT
FLAT OVAL DUCT
DUCT DROP IN RESPECT TO AIR FLOW
LOWER - EQUIPMENT NUMBER
UPPER - EQUIPMENT DESIGNATION
CONNECT NEW TO EXISTING
SMOKE DETECTOR
LIMIT OF REMOVAL
THERMOSTAT (EXISTING/RELOCATED/NEW)
TRANSFER DUCT
NEW DUCTWORK
FUTURE DUCTWORK
UP
DN
HVAC LEGEND
VOLUME DAMPER
TAGS - EQUIPMENT, DRAWING
VD
T
ABBREVIATIONS
ETR
AD
ACD
AFF
AP
CFM
DB
DX
EP
EAT
ATC
EWT
FLA
EXH
FD
FPM
HP
LAT
LRA
CO
FSD
EXISTING TO REMAIN
LEAVING AIR TEMPERATURE
LOCK ROTOR AMPS
AUTOMATIC CONTROL DAMPER
EXHAUST
CUBIC FEET PER MINUTE
ACCESS DOOR
ABOVE FINISHED FLOOR
DRY BULB
FIRE DAMPER
ACCESS PANEL
AUTOMATIC TEMPERATURE CONTROL
DIRECT EXPANSION
ENTERING AIR TEMPERATURE
ELECTRIC PNEUMATIC RELAY
ENTERING WATER TEMPERATURE
FULL LOAD AMPS
HORSEPOWER
FEET PER MINUTE
CLEAN OUT
COMBINATION FIRE DAMPER/SMOKE DAMPER
NIC
MAX
MBH
MIN
MD
NO
OA
PD
OBD
RH
RA
RPM
SD
SMD
SP
SPD
WB
VD
NC
OED
WMS
NOT IN CONTRACT
MINIMUM
MOTORIZED DAMPER
MAXIMUM
THOUSAND BTU PER HOUR
SPLITTER DAMPER
REVOLUTIONS PER MINUTE
STATIC PRESSURE (INCHES OF WATER)
SMOKE DETECTOR
SMOKE DAMPER
RELATIVE HUMIDITY
WET BULB TEMPERATURE °F
VOLUME DAMPER
OUTSIDE AIR
RETURN AIR
NORMALLY OPEN
PRESSURE DROP
OPPOSED BLADE DAMPER
NORMALLY CLOSED
OPEN END DRAIN
1/2" x 1/2" GALVANIZED WIRE MESH SCREEN
CD
RL
RS REFRIGERANT SUCTION
REFRIGERANT LIQUID
CONDENSATION DRAIN
PIPING SYSTEMS
14 x 6
14 x 6
SA SUPPLY AIR
DUCT SECTION - EXHAUST14 x 6
EA EXHAUST AIR
FIRE SMOKE DAMPER (VERTICAL)
FIRE DAMPER (HORIZONTAL)
FIRE SMOKE DAMPER (HORIZONTAL)
FIRE DAMPER (VERTICAL)
FD
FD
FSD
FSD
SMOKE DAMPER (HORIZONTAL)
SMOKE DAMPER (VERTICAL)
SD
SD
EQP
NON-MOTORIZED EQUIPMENT (SD, B)
CFM VALUE
UPPER - EQUIPMENT DESIGNATION
1. MINIMUM SIZE OF CONDENSATE DRAIN PIPING SHALL BE 3/4" UNLESS OTHERWISE
NOTED.
2. ALL PIPING ABOVE GRADE SHALL BE SUPPORTED BY THE BUILDING STRUCTURE
AND SHALL NOT REST ON CEILING TILES OR CEILING STRUCTURE. PIPING HUNG
FROM JOISTS SHALL BE HUNG FROM THE TOP CHORDS OF THE JOISTS.
3. CONDENSATE FROM ALL COOLING COILS SHALL BE TRAPPED AND ROUTED TO
THE NEAREST HUB/FLOOR DRAIN, STORM OR EXTERIOR DRY WELLS. CONDENSATE
PIPING SHALL BE INSULATED COPPER. CONDENSATE SHALL BE PUMPED AS
REQUIRED.
4. REFRIGERANT PIPING SHALL BE TYPE L OR REFRIGERATION SERVICE COPPER
TUBING WITH BRAZED JOINTS. SUCTION PIPING SHALL BE INSULATED WITH 3/4"
MANVILLE AEROTUBE II PIPE INSULATION OVER TUBING WITHOUT CUTTING. ALL
JOINTS AND SEAMS SHALL BE SEALED WITH ADHESIVE.
1. ALL WORK SHALL CONFORM TO THE STATE BUILDING CODES AND ALL OTHER
APPLICABLE CODES AND REGULATIONS
2. THE DRAWINGS DEPICT ONLY GENERALLY THE EXISTING CONDITIONS THE
CONTRACTOR SHALL MAKE FIELD OBSERVATIONS AND CONFIRM WALL LOCATIONS,
DUCTWORK, PIPING AND OTHER UTILITIES ABOVE EXISTING CEILINGS.
3. ALL CONFLICTS AND ITEMS FOR CLARIFICATIONS SHALL BE BROUGHT TO THE
CONTRACTING OFFICER'S ATTENTION PRIOR TO WORK IN THE AREA.
4. THE CONTRACTOR IS RESPONSIBLE TO FOLLOW PROJECT CONSTRUCTION SITE
RULES WITH REGARDS TO TRASH, ELEVATORS, NOISE,SPRINKLERS AND FIRE
ALARM.
5. THE CONTRACTOR SHALL MAINTAIN IN OPERATION ALL EXISTING UTILITIES
DURING CONSTRUCTION.
6. ITEMS IDENTIFIED TO BE SALVAGED SHALL BE STOCKPILED IN AN AREA FOR
REMOVAL BY THE CONTRACTING OFFICER. ALL OTHER ITEMS BEING REMOVED
SHALL BE
DISPOSED OF LEGALLY OFF SITE. ALL ITEMS BEING REMOVED AND NOT REUSED
SHALL BE DISPOSED OF AS DIRECTED BY THE CONTRACTING OFFICER.
7. CAPPING OF ALL SERVICES SHALL BE PERFORMED TO LEAVE EXISTING SERVICES
TO OTHER AREAS INTACT AND FUNCTIONAL.
8. ALL DEMOLITION WORK WILL BE SCHEDULED WITH CONTRACTING OFFICER
AND PERFORMED ONLY FOLLOWING APPROVAL.
9. THE CONTRACTOR SHALL INFORM CONTRACTING OFFICER AND RECEIVE
SCHEDULE APPROVAL FOR ANY REQUIRED UTILITY SHUTDOWN.
10. WHERE EQUIPMENT IS SHOWN TO BE REMOVED, THE EQUIPMENT SHALL BE
DELIVERED TO CONTRACTING OFFICER FOR STORAGE OR PROPERLY DISPOSED OF
AS DIRECTED BY CONTRACTING OFFICER.
11. WHERE EQUIPMENT IS SHOWN OR NOTED AS BEING REMOVED & REPLACED
AFTER WALL/CEILING STRUCTURAL OR ARCHITECTURAL WORK IS PERFORMED.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER, SAFE STORAGE OF SUCH
EQUIPMENT.
12. ANY DUCTWORK SHOWN TO BE REMOVED SHALL INCLUDE REMOVE OF ALL
ASSOCIATED DUCTWORK, FLEXIBLE CONNECTIONS, DIFFUSERS, HANGERS,
INSULATION, ETC.
13. ANY PIPING SHOWN TO BE REMOVED WILL BE REMOVED TO THE POINT
INDICATED ON THE DRAWING OR TO THE ACTIVE MAIN AND VALVED AND CAPPED.
PIPING REMOVAL SHALL INCLUDE ALL HANGERS, VALVES, INSULATION, ETC.
14. EXISTING DUCTWORK SHALL BE CAPPED AND SEALED AIR TIGHT, EXCEPT
WHERE UTILIZED FOR NEW BRANCH DUCTWORK.
15. THERMOSTATS ARE TO BE RELOCATED AS SHOWN ON NEW WORK DRAWING.
16. REMOVE AND CLEAN ALL SUPPLY, RETURN & EXHAUST DIFFUSERS & GRILLES.
RE-INSTALL OR SAVE FOR RELOCATION AS SHOWN ON NEW WORK PLAN.
17. ALL DIFFUSERS TO BE TIED TO UNDERSIDE OF STRUCTURE TO FACILITATE
REMOVAL OF EXISTING CEILING AND MAINTAIN DIFFUSER CONNECTION TO
DUCTWORK WHERE APPLICABLE. DIFFUSERS SHALL BE REPLACED INTO NEW
CEILING GRID AS SHOWN ON THE NEW WORK DRAWING. ADDITIONAL LENGTH OF
FLEX MAY BE REQUIRED FOR DIFFUSERS.
18. CONTRACTOR SHOULD SURVEY EXISTING CONDITIONS AND INFORM
CONTRACTING OFFICER OF ANY DEVIATIONS PRIOR TO CONSTRUCTION.
1. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF SMACNA STANDARDS.
2. PROVIDE VOLUME DAMPERS AT ALL LOW PRESSURE SUPPLY, RETURN AND
EXHAUST DUCTWORK BRANCH TAKE-OFFS.
3. SUPPLY AND RETURN DUCT MAINS FROM AIR HANDLING EQUIPMENT SHALL BE
INTERNALLY LINED WITH 1" ACOUSTICAL LINING A MINIMUM OF 10'-0" FROM THE UNIT
UNLESS OTHERWISE NOTED. ALL DUCTWORK DIMENSIONS INDICATED ARE CLEAR
INSIDE DIMENSIONS. ALL INTERNAL ACOUSTICAL DUCT LINING SHALL HAVE AIR
SURFACE COATED WITH ACRYLIC COATING FORMULATED WITH IMMOBILIZED EPA
REGISTERED ANTI-MICROBIAL AGENT PROVEN TO RESIST MICROBIAL GROWTH AS
DETERMINED BY ASTM G21 AND G22.
4. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATIONS OF
DIFFUSERS, REGISTERS AND GRILLES.
5. FIRE DAMPERS AND ACCESS PANELS SHALL BE INSTALLED AT ALL FIRE RATED
ASSEMBLIES AND FLOOR PENETRATIONS. REFER TO ARCHITECTURAL DRAWINGS
FOR ASSEMBLY LOCATIONS. WHERE DUCTS PENETRATE WALLS THAT CARRY BOTH
FIRE AND SMOKE RATINGS, THE DAMPER SHALL BE COMBINATION FIRE/ SMOKE
DAMPERS. COMBINATION FIRE/ SMOKE DAMPERS SHALL BE PROVIDED WITH POWER
IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS. THE MECHANICAL
SUBCONTRACTOR SHALL COORDINATE COMBINATION FIRE/ SMOKE DAMPER
POWER REQUIREMENTS WITH THE CONTRACTING OFFICER.
6. PROVIDE FIRE DAMPERS AT ALL TRANSFER DUCTS IN FIRE RATED PARTITIONS.
7. EACH SUPPLY DIFFUSER/REGISTER RUNOUT SHALL BE PROVIDED WITH A VOLUME
DAMPER. REFER TO CEILING DIFFUSER BRANCH TAKE-OFF DETAIL FOR ADDITIONAL
INFORMATION.
8. ALL VOLUME DAMPERS LOCATED ABOVE HARD NON-ACCESSIBLE CEILINGS SHALL
BE PROVIDED WITH A YOUNG REGULATOR VOLUME DAMPER FOR REMOTE
BALANCING.
9. RUNOUT SIZES TO DIFFUSERS/REGISTERS SHALL MATCH INLET SIZE NOTED IN
THE DIFFUSER REGISTER/ GRILLE SCHEDULE OR TAG UNLESS SHOWN OTHERWISE
ON THE FLOOR PLANS.
10. RUNOUT SIZES TO TERMINAL UNITS SHALL BE 2" LARGER THAN INLET SIZE
UNLESS OTHERWISE NOTED OR SHOWN ON THE FLOOR PLANS.
11. ALL FANS SUPPLYING MORE THAN 2,000 CFM OF AIR TO ANY SPACE SHALL BE
INSTALLED WITH A SMOKE DETECTOR IN THE [SUPPLY] [RETURN] DUCTWORK.
DUCT SMOKE DETECTORS SHALL BE INSTALLED IN THE [SUPPLY] [RETURN] AIR
PATH OF AIR DISTRIBUTION SYSTEMS UTILIZING A COMMON SUPPLY AND/OR
RETURN AIR PLENUM WITH A COMBINED DESIGN CAPACITY GREATER THAN 2,000
CFM. THE SMOKE DETECTOR SHALL BE WIRED TO STOP THE FAN UPON DETECTION
OF SMOKE, AND SIGNAL THE BUILDING FIRE ALARM CONTROL PANEL. THE SMOKE
DETECTOR SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, MOUNTED IN THE
DUCT BY MECHANICAL CONTRACTOR AND WIRED BY THE ELECTRICAL
CONTRACTOR.
12. LOCATIONS OF LOUVERS SHOWN ON THE PLANS ARE APPROXIMATE. REFER TO
ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION.
1. ALL HVAC WORK SHALL BE IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE
AND LOCAL CODES INCLUDING AMENDMENTS:
2018 INTERNATIONAL EXISTING BUILDING CODE
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
2. INDOOR DESIGN CONDITIONS:
SUMMER (COOLING): 75ºF, 50% RH, AT 95ºF DB/76ºF WB OUTDOOR.
WINTER (HEATING): 70ºF AT 17ºF OUTDOOR.
3. THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) CONTRACTOR SHALL
VISIT THE SITE TO DETERMINE ALL PRE-EXISTING CONDITIONS AND WORK
NECESSARY PRIOR TO SUBMISSION OF BID PRICE.
4. THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC) CONTRACTOR SHALL
BE FAMILIAR WITH ALL CONTRACT DOCUMENTS FOR ALL TRADES AND COORDINATE
WITH THE CONTRACTING OFFICER.
5. DRAWINGS ARE DIAGRAMMATIC ONLY: FINAL ROUTING OF DUCTWORK, PIPING
AND EQUIPMENT LOCATIONS SHALL BE DETERMINED IN THE FIELD ADDITIONAL
OFFSETS, ELBOWS, ETC., SHALL BE PROVIDED AND INSTALLED WITHOUT
ADDITIONAL COST TO THE CONTRACTING OFFICER.
6. THE HVAC CONTRACTOR SHALL COORDINATE ALL ELECTRICAL AND PLUMBING
REQUIREMENTS WITH THE CONTRACTING OFFICER.
7. THE AUTOMATIC TEMPERATURE CONTROL (ATC) CONTRACTOR SHALL
COORDINATE THERMOSTAT LOCATIONS WITH THE ARCHITECTURAL FURNITURE
PLANS. THERMOSTATS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR UNLESS
OTHERWISE NOTED.
8. THE HVAC CONTRACTOR SHALL FURNISH AND INSTALL ALL INCIDENTAL
ACCESSORIES NECESSARY TO MAKE THE HVAC WORK COMPLETE AND READY FOR
OPERATION.
9. ALL HVAC EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
10. DEMOLITION WORK SHALL BE DONE BY THE HVAC CONTRACTOR. THE HVAC
CONTRACTOR SHALL COORDINATE ALL WORK CONCERNING EXISTING EQUIPMENT
AND SYSTEMS REMAINING IN THE BUILDING. ALL UNUSED DUCTS AND PIPES AS A
RESULT OF THE DEMOLITION SHALL BE CAPPED, SEALED AND INSULATED.
11. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE
INTEGRITY, CONDITION AND LOCATION OF EXISTING DUCTWORK AND PIPING WHICH
IS TO BE REUSED. IF PIPING AND DUCTWORK CANNOT BE REUSED, THE
CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER TO DETERMINE THE
EXTENT OF REPLACEMENT.
12. FURNISH TO THE CONTRACTING OFFICER ALL INFORMATION REQUIRED FOR
SETTING OF WALL, ROOF AND PARTITION OPENINGS FOR HVAC WORK. THIS
INFORMATION SHALL BE FURNISHED IN A TIMELY MANNER SUCH THAT
CONSTRUCTION SCHEDULE IS NOT JEOPARDIZED.
13. INFORM AND COORDINATE WITH THE CONTRACTING OFFICER ALL NECESSARY
INTERRUPTIONS TO EXISTING BUILDING SYSTEMS AND SERVICE THAT MAY AFFECT
THE NORMAL OPERATION OF OCCUPIED PORTIONS OF THE BUILDING. THE
CONTRACTING OFFICER SHALL BE INFORMED OF ANY INTERRUPTIONS AT LEAST
TWO (2) WEEKS IN ADVANCE.
14. INFORM THE CONTRACTING OFFICER WELL IN ADVANCE OF ANY WORK TO BE
UNDERTAKEN IN OCCUPIED AREAS OF THE BUILDING ASSOCIATED WITH THIS
PROJECT. CONFORM NOISE LIMITS IN THE PORTIONS OF THE BUILDING WHICH
REMAIN OCCUPIED DURING CONSTRUCTION.
15. COORDINATE PHASING REQUIREMENTS FOR THE PROJECT WITH THE
CONTRACTING OFFICER.
16. FIELD MEASURE THE EXACT SIZES AND VERIFY ALL OPENINGS FOR SHAFTS AND
LOUVERS PRIOR TO SUBMISSION OF SHOP DRAWINGS AND INSTALLATION.
17. MINIMAL CONTROL POWER HAS BEEN IDENTIFIED ON THE DRAWINGS. IF ANY
ADDITIONAL POWER IS REQUIRED BASED ON SYSTEMS DESIGN BY THE CONTROLS
CONTRACTOR THE ATC/BAS CONTRACTOR SHALL BE RESPONSIBLE TO SUPPLY
THAT POWER.
18. THE HVAC CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL
MECHANICAL EQUIPMENT,DUCTWORK, PIPING, ETC. TO FIT WITHIN THE SPACE
ALLOWED BY THE ARCHITECTURAL AND STRUCTURAL CONDITIONS. CUTTING OR
OTHERWISE ALTERING ANY STRUCTURAL MEMBERS SHALL NOT BE PERMITTED
WITHOUT WRITTEN PERMISSION FROM THE CONTRACTING OFFICER.
19. ANY EXISTING WALL, FLOOR, OR CEILING SURFACE THAT IS DISTURBED DURING
THE COURSE OF THE HVAC WORK SHALL BE REPAIRED TO MATCH NEW AND/OR
EXISTING CONDITIONS.
20. PROVIDE ACCESS PANELS IN NON-ACCESSIBLE CEILINGS AND IN WALL
STRUCTURES OF ADEQUATE SIZE TO ALLOW FOR MAINTENANCE, BALANCING AND
COMPLETE REPLACEMENT OF EQUIPMENT WITHOUT DISTURBING PERMANENT
CONSTRUCTION. ACCESS PANELS IN CEILINGS AND WALLS SHALL BE PROVIDED
WHERE SHOWN ON THE PLANS OR NECESSARY TO ACCESS DAMPERS, VALVES,
ETC. COORDINATE EXACT LOCATION & SIZES OF ALL ACCESS PANELS WITH THE
ARCHITECT DURING THE SHOP DRAWING PROCESS.
21. PORTIONS OF DUCTWORK AND PIPE INSULATION VISIBLE THROUGH AIR
DISTRIBUTION DEVICES IN FINISHED AREAS SHALL BE PAINTED FLAT BLACK.
22. ALL PIPE AND DUCT PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES
SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE THE ASSEMBLY TO ITS
ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY
TREMCO, HILTI, 3M OR APPROVED EQUAL.
23. WHERE ABOVE CEILING VOLUMES OR MECHANICAL ROOM/CLOSETS ARE
UTILIZED AS A RETURN AIR PLENUM, ALL MATERIALS EXPOSED WITHIN THE
PLENUMS SHALL BE NON-COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 AS
DETERMINED IN ACCORDANCE WITH ASTM E84.
24. THE HVAC CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS
AND REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH ELECTRICAL DRAWINGS
PRIOR TO SUBMITTING SHOP DRAWINGS OR ORDERING EQUIPMENT. EQUIPMENT
SHALL BE FURNISHED WIRED FOR THE VOLTAGES SHOWN ON THE ELECTRICAL
PLANS.
25. ALL MECHANICAL EQUIPMENT REQUIRING ELECTRICAL POWER SHALL BE
INSTALLED WITH DISCONNECT SWITCHES AT EACH PIECE OF EQUIPMENT.
COORDINATE SWITCH TYPE WITH EQUIPMENT CHARACTERISTICS,
MANUFACTURER'S RECOMMENDATIONS AND THE ELECTRICAL DRAWINGS.
26. ALL REQUIRED CONTROL WIRING (INCLUDING POWER WIRING REQUIRED FOR
CONTROL PANELS, DEVICES, ETC. ) NOT SHOWN ON THE ELECTRICAL DRAWINGS
SHALL BE INCLUDED AS PART OF THE MECHANICAL WORK.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:0
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-0.1
HVAC LEGEND & GENERAL
NOTES
NACE 242190
SELECTION BASED ON PRICE
REMARKS
1. ALUMINUM SHALL BE USED IN WET LOCATIONS SUCH AS SHOWER ROOMS, GLASSWASH ROOMS, ETC.
2. INDUCTION AIR DIFFUSER WITH 24"x24" LAY-IN BORDER. DIFFUSERS INSTALLED IN GYP. CEILING SHALL BE WITHOUT A LAY-IN BORDER.
3. DIFFUSER CONNECTIONS SHALL BE ON THE INSIDE NECK AND SEALED AIR TIGHT.
4. PROVIDE A DIFFUSER BOOT. REFER TO DETAILS FOR REQUIREMENTS.
5. INDUCTION AIR DIFFUSER WITHOUT INDUCTION VANES.
6. WITH ACOUSTICALLY LINED PLENUM.
24"x16"
24"x10"
18"x12"
12"x10"
12"x8"
14"x6"
10"x6"
6"x6"
SR-4
SR-8
SR-7
SR-6
SR-5
SR-3
SR-2
SR-1
SUPPLY STEEL
SUPPLY
SUPPLY
SUPPLY
SUPPLY
STEEL
STEEL
STEEL
STEEL
SUPPLY
SUPPLY
SUPPLY
STEEL
STEEL
STEEL
PER ARCH
PER ARCH
PER ARCH
PER ARCH
PER ARCH
EXP/CLG/WALL
PER ARCH
PER ARCH
PER ARCH
YES
YES
YES
YES
YES
YES
YES
YES520
201 - 275
891 - 1,250
591 - 890
366 - 590
276 - 365
141 - 200
91 - 140
0 - 90 30
300.041
0.034
0.029
0.042
0.041
0.029
0.030
0.038
281 - 400
401 - 550
551 - 665
666 - 800
801 - 955
161 - 280
0 - 160 8"x6"
14"x6"
14"x8"
18"x10"
20"x10"
20"x12"
24"x12"
THE ABOVE ALSO APPLIES TO TRAINING ROOMS, CLASSROOMS, CONFERENCE CENTERS AND
ALL SOUND CRITICAL SPACES THAT REQUIRE A MAXIMUM NC LEVEL OF 30.
161 - 225
226 - 280
281 - 400
401 - 530
531 - 665
101 - 160
0 - 100 6"Ø
8"Ø
9"Ø
10"Ø
12"Ø
14"Ø
16"Ø
ER-1 6"x6" EXHAUST STEEL CEIL./WALL PER ARCH530 200.054 0 - 70
ER-2 8"x8" EXHAUST STEEL CEIL./WALL PER ARCH530 200.054 71 - 150
ER-3 10"x10" EXHAUST STEEL CEIL./WALL PER ARCH530 200.054 151 - 240
ER-4 12"x12" EXHAUST STEEL CEIL./WALL PER ARCH530 200.054 241 - 350
ER-5 14"x14" EXHAUST STEEL CEIL./WALL PER ARCH530 200.054 351 - 470
ER-6 16"x16" EXHAUST STEEL CEIL./WALL PER ARCH530 200.054 471 - 600
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
DUCTWORK GENERAL NOTES:
1. EACH SUPPLY & RETURN/EXHAUST DIFFUSER RUNOUT SHALL BE PROVIDED WITH A VOLUME
DAMPER. REFER TO CEILING DIFFUSER BRANCH TAKE-OFF DETAIL FOR ADDITIONAL INFORMATION.
2. RUNOUT SIZES TO LINEAR DIFFUSERS SHALL MATCH INLET SIZE NOTED IN THE DIFFUSER
REGISTER AND GRILLE SCHEDULE.
3. RUNOUT SIZES TO TERMINAL UNITS (VV ,CV, FPT) SHALL MATCH INLET SIZE UNLESS NOTED
OTHERWISE ON THE FLOOR PLANS.
4. ALL VOLUME DAMPERS LOCATED ABOVE HARD NON-ACCESSABLE CEILINGS SHALL BE PROVIDED
WITH A YOUNG REGULATOR VOLUME DAMPER FOR REMOTE BALANCING.
FINISH
DIFFUSER, REGISTER & GRILLE SCHEDULE
SYMBOL SIZE MATERIALFUNCTION TYPE DAMPER REMARKSMODEL TP
CFM RANGE
ENCLOSED AREA
MAX NC
SUPPLY AIR DIFFUSER RUNOUT SIZE
SCHEDULE FOR ENCLOSED OFFICE OR
CONFERENCE ROOMS
EXHAUST REGISTER/GRILLE RUNOUT SIZE
SCHEDULE FOR ENCLOSED OFFICE OR
CONFERENCE ROOMS
ENCLOSED OFFICE
CFM RANGE
DUCT RUNOUT SIZE
TO DIFFUSER
ENCLOSED OFFICE
CFM RANGE
DUCT RUNOUT SIZE
TO REGISTER/GRILLE
24"x12"
18"x12"
12"x10"
12"x8"
14"x6"
10"x6"
6"x6"
RR-4
RR-7
RR-6
RR-5
RR-3
RR-2
RR-1
STEEL
STEEL
STEEL
STEEL
RETURN
STEEL
STEEL
STEEL
PER ARCH
PER ARCH
PER ARCH
PER ARCH
EXP/CLG/WALL
PER ARCH
PER ARCH
PER ARCH
YES
YES
YES
YES
YES
YES
YES530
277 - 360
671 - 900
501 - 670
205 - 276
127 - 204
0 - 126 30
300.034
0.029
0.042
0.041
0.029
0.030
0.038
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
EXP/CLG/WALL
RETURN
RETURN
RETURN
RETURN
RETURN
RETURN
24"x16"RR-8 STEEL PER ARCH YES 900 - 980 300.041530 EXP/CLG/WALLRETURN
400 - 500
2 3 4PER ARCH
SD-3
SD-6
SD-4
SD-5
SD-2
SD-1
9"x9"
9"x12"
12"x12"
15"x15"
6"x9"
6"x6"
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
CEILING
CEILING
CEILING
CEILING
CEILING
CEILING
NONE
NONE
NONE
NONE
NONE
NONE
PER ARCH
PER ARCH
PER ARCH
PER ARCH
PER ARCH
161 - 225
226 - 320
321 - 400
401 - 530
101 - 160
0 - 100SMX 30
SMX
SMX
SMX
SMX
SMX
6.
6.
6.
6.
6.
6.
0.105
0.106
0.068
0.106
0.060
0.068
RD-1
RD-3
RD-2
6"x6"
12"x12"
9"x9"
RETURN
RETURN
RETURN
STEEL
STEEL
STEEL
CEILING
CEILING
CEILING
NONE
NONE
NONE
PER ARCH
PER ARCH
PER ARCHSMD 0.066
0.086
0.092
SMD
SMD 161 - 400
0 - 100
101 - 160
2 3 4
2 3 4
2 3 4
2 3 4
2 3 4
4 5
4 5
4 5
LD-1 CEILING NONEPER ARCHSUPPLY ALUMINUM48"L x 3 SLOT 10"Ø INLET.0 - 2700.071TBD3100 32 6
RD-4 15"x15" RETURN STEEL CEILING NONEPER ARCH 0.092SMD 401 - 670 30 4 5
YES
YES
YES
YES
YES
YES
AC-1 BASEMENT
SELECTION BASED ON: MITSUBISHI
REMARKS
1. INDOOR UNIT POWERED BY OUTDOOR UNIT.
2. CONTRACTOR TO PROVIDE CONDENSATE DRAIN PIPING AS SHOWN ON PLANS.
3. PROVIDE SECONDARY DRAIN PAN WITH OVERFLOW SWITCH.
4. PROVIDE UNIT WITH MAXIBLUE PLENUM RATED CONDENSATE PUMP (208 V).
5. PROVIDE CONTROL WIRING FROM THERMOSTAT TO AC UNIT.
6. PROVIDE EACH UNIT WITH FREEZE STAT.
7. PROVIDE WITH MERV-13 FILTER BOX AS SCHEDULED ON M0.3.
SPLIT SYSTEM HEAT PUMP - INDOOR UNIT SCHEDULE
SYMBOL
AC
REMARKSLOCATION
AC-2
AC-3
AC-4
BASEMENT
BASEMENT
BASEMENT
CFM
OA CFM
ESP
(IN WC)
COOLING DATA
EAT
DB°F WB°F
ELECTRICAL DATA
V PH FLA MCA
2. 3. 5.
1. 2. 3. 5.208 1
208 1
AC-5 3RD FLOOR ATTIC
3.30 4.13
1480 200 208 1 2.80 3.50
TOTAL
HTG MBH
18.6
22.0
26.0
67.080.0
67.080.0
67.080.0
AC-6 BASEMENT
MODEL
NUMBER
0.8
0.8
0.8
PVA-A30AA7
PEAD-A42AA7
875 208 1 3.30 4.1315.067.080.00.8
SENSIBLE
CLG MBH
22.0
26.2
18.5
31.5
230 67.080.00.81400 208 1 4.50 5.6330.567.080.00.8 PVFY-P48NAMU-E131.2
PVA-A36AA7
PVA-A24AA7
2. 3. 4. 5.
1. 2. 3. 4. 5.
1. 2. 3. 4. 5.
1. 2. 3. 4. 5. 7.
1125 208 1 4.40 5.5022.067.080.00.8 26.2 PVA-A36AA7
4.40 5.50
1. 2. 3.
EERLOCATION REMARKS
CU
CONDENSER FAN DATA
RFS
SYMBOL
SPLIT SYSTEM HEAT PUMP- OUTDOOR UNIT
SELECTION BASED ON: MITSUBISHI
REMARKS
1. PROVIDE WIND BAFFLE FOR LOW AMBIENT HEATING.
2. REFRIGERANT TYPE: R-410A.
3. REFER TO DETAIL FOR MOUNTING.
CU-2
CU-3
CU-4
SEE PLAN
SEE PLAN
SEE PLAN
INDOOR UNIT
AC-2
AC-3
AC-4
COOLING DATA
NOMINAL
CAPACITY
AMBIENT
TEMP (°F)
VOLTS PHASE
ELECTRICAL DATA
2513.030.0 95 1208
3012.536.0 95 1208
13.024.0 95 1208
CU-5
HEATNG
AMBIENT
TEMP (°F)
MCA
MOCP
CU-6
MODEL
NUMBER
25 19 26
PUZ-A30NHA7
SEE PLAN AC-5 95 5 120812.542.0 95 120830 25 31
CU-1 SEE PLAN AC-1
SEE PLAN AC-6 3012.548.0 95 12085 29 44 PUMY-P48NKMU3
PUZ-A36NKA7
PUZ-A24NHA7
PUZ-A42NKA7
1. 2. 3.
1. 2. 3.
1. 2. 3.
1. 2. 3.
1. 2. 3.
3012.536.0 95 12085 25 31 PUZ-A36NKA7
ELECTRIC CABINET UNIT HEATERS
SYMBOL
ECUH-1
SERVES
STAIRWELL ST1-3
MOUNTING CFM
WALL 250
MODEL #
922U06000C
KW STAGES
5 2
V
ELECTRICAL
PH
EMERGENCY
POWER
REMARKS
208 1 NO 1.
SELECTION BASED ON: INDEECO CUI SERIES
REMARKS:
1. INTEGRAL THERMOSTAT, FACTORY DISCONNECT SWITCH, COLOR AND FINISH BY ARCHITECT.
ECUH
FSD-1 120 1 DUCT SMOKE DETECTOR -40 NOCOMBINATION FIRE DAMPER/SMOKE DAMPER
COMBINATION FIRE/SMOKE DAMPERS
SYMBOL TYPE
VOLT PHASE
FSD
REMARKS
CURRENT
MAX WATTS
SMOKE DAMPER
CONTROL METHOD
EMERGENCY
POWER
SELECTION BASED ON: RUSKIN
REMARKS
1. REFER TO FLOOR PLANS FOR SIZES AND LOCATIONS
HC-1 210 8 8 65 2084.0 17.0 1. 2.
LAT
AIR SIDE
HEATING COILS (ELECTRIC)
SYMBOL CFM
HEIGHTWIDTH EAT VOLTSKW PH
DUCT SIZE ELECTRICAL
HC
REMARKS
SELECTION BASED ON: INDEECO QUZ SERIES
REMARKS
1. PROVIDE WITH AIRFLOW SWITCH, CONTROL CIRCUIT TRANSFORMER, AND DOOR INTERLOCKING DISCONNECT SWITCH.
2. PROVIDE WITH SCR CONTROLS.
HC-2
HC-3
HC-4
90 6 6 657.0 1.5
200 657.0 4.0
170 657.0 3.0
208 1
208 1
208 1
HC-5
HC-6
8 8
10 8
8 8
8 8
7.0
7.0
4.0
4.5
MIN.
FPM APD
0.07
0.08
0.08
0.08
0.02
0.08
ACTUAL
FPM
1. 2.
1. 2.
1. 2.
1. 2.
1. 2.
EBB-1 4'-0" 0.85 250 COLOR AND FINISH BY ARCHITECT.1120 NO
ELECTRIC BASEBOARD (ELECTRIC)
SYMBOL LENGTH
EBB
REMARKS
OUTPUT (MBH)
PER LINEAR FOOT
WATTS PER
LINEAR FOOT
POWER
PHV POWER
EMERGENCY
SELECTION BASED ON: QMARK
MODEL
BF-1 SQ-120-VG
BOOSTER FAN SCHEDULE
SYMBOL MODEL
BF
REMARKSCFMTYPE SERVICE RPM HP VOLTS PH
FAN
BHP(IN.)
E.S.P.
SELECTION BASED ON: GREENHECK
1. PROVIDE ALL FANS WITH EC MOTORS (VARI-GREEN)
2. MOTORS SHALL BE PROVIDED WITH MOTOR MOUNTED SPEED CONTROLLER.
3. MOTOR SHALL BE PROVIDED WITH CONTANT CFM PRESSURE CONTROL.
4. FAN SHALL BE PROVIDED WITH OUTLET GUARD.
5. FAN HOUSING SHALL BE INSULATED.
BF-2 -
BF-3 -
FLADRIVE
DIRECT
DIRECT
DIRECT
BF-4
BF-5
1151125AC-1INLINE
INLINE
0.5 1302 0.20 1
208 1
AC-2
INLINE AC-3
INLINE AC-4
INLINE AC-6
SQ-100-VG 875 0.6 1476 0.15
SQ-120-VG 1125 0.6 1355 0.23
875 0.6 1476 0.15 DIRECT -SQ-100-VG
1400 0.7 1395 0.33SQ-130-VG DIRECT -
0.50 6.2
0.50 6.2 115
3.70.25
3.70.25
0.75 6.6
EF-1 G-090-D ROOF 375RESTROOMS 0.5 1550 1/15 120 10.08
EXHAUST FAN SCHEDULE
SYMBOL MODEL
EF
REMARKSCFMTYPE SERVICE RPM HP VOLTS PH
FAN
BHP(IN.)
E.S.P.
SELECTION BASED ON: GREENHECK
REMARKS:
1. TOILET EXHAUST FANS TO BE INTERLOCKED WITH BUILDING TIME CLOCK.
2. PROVIDE FAN WITH EC MOTORS.
3. PROVIDE WITH SPEED FOR BALANCING.
EF-2 G-060-D ROOF 753RD FLOOR RR 0.31 1550 120 10.02 -
EF-3 CSP-A290 INLINE MENS ROOM 003 225 0.5 1039 0.05 - 120 1 -
WATTS
DRIVE
DIRECT
DIRECT
DIRECT
1/60
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:0
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-0.2
HVAC SCHEDULES (1 OF 2)
AC-1 PARTICULATE PRECISION CELL III
HOUSED FILTER UNIT SCHEDULE
SYMBOL SERVICE
HFU
REMARKS
FILTER
MODEL
TYPE
HFU-2 AC-2 -
AC-3
SP2-10H10W
HOUSING
MODEL
SIDE
LOADING
CFM
MERV
DEPTH
(IN.)
FACE
AREA
(SF)
FACE
VELOCITY
(FPM)
0.10
APD
(IN. WC)
INITIAL FINAL
0.35HFU-1
HFU-3
SELECTION BASED ON: FLANDERS
REMARKS:
1. PROVIDE WITH 4" DEEP PRECISIONCELL III MERV 13 FILTER.
HFU-4
HFU-5
AC-4
AC-6
PARTICULATE
PARTICULATE
PARTICULATE
PARTICULATE
SP2-10H10W
SP2-10H10W
SP2-10H10W
SP2-10H10W
SIDE
SIDE
SIDE
SIDE
220 0.10 0.35
285 0.10 0.35
220 0.10 0.35
350 0.15 0.35
PRECISION CELL III
PRECISION CELL III
PRECISION CELL III
PRECISION CELL III
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:0
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
Author
Checker
7/8/2021
M-0.3
HVAC SCHEDULES (2 OF 2)
TAKE OFF FITTINGTAKE OFF FITTING
ALTERNATE RECTANGULAR BRANCH DUCT TAKE OFFS
BRANCHBRANCH
AIR FLOW
VDVD
45° RECTANGULAR
TAKE OFF
ALTERNATE ROUND BRANCH DUCT TAKE OFFS
ALTERNATEPREFERRED
VDVD
AIR FLOW
VDVDVD
ALTERNATE
TAKE OFF FITTINGTAKE OFF FITTING
PREFERRED ALTERNATE
TAKE OFF FITTING
ALTERNATE
TAKE OFF FITTING
ALTERNATE
TAKE OFF FITTING
RECTANGULAR BELL
MOUTH FITTING
MODEL RBMD
STANDAR 45º
REGULAR TO ROUND
BOOT CONNECTION
MODEL 33000
OVAL-
BELLMOUTH
CONNECTION
MODEL OVBMD
MINI-
BELLMOUTH
CONNECTION
MODEL MBMD
BELL MOUTH
MODEL BMD
W/END FLAPS
BENT OVER
BELL MOUTH
CONNECTION
MODEL BMD
NOTES:
ALL ROUND AND RECTANGULAR BELL MOUTH FITTINGS SHALL
BE INCLUDED WITH THE FOLLOWING STANDARD FEATURES:
1.NEOPRENE GASKET TO MINIMIZE AIR LEAKAGE.
2.PRE-DRILLED HOLES FOR QUICK MOUNTING.
3.CONSTRUCTED OF HEAVY DUTY GALVANIZED STEEL.
OPTIONAL FEATURES SHALL INCLUDE THE FOLLOWING:
1.26 GAUGE GALVANIZED QUADRANT VOLUME DAMPER WITH
TIGHT FITTING GASKETING TO MINIMIZE LEAKAGE AT DAMPER
PIVOT POINTS.
2.HEAVY DUTY HARDWARE IS AVAILABLE FOR APPLICATIONS
WITH INCREASED STATIC PRESSURE.
CONCRETE
SLAB
CEILING
CABINET INLINE FAN
FLEXIBLE DUCT CONNECTION
AIR FLOWAIR FLOW
EXHAUST FAN INLET
ACOUSTICALLY INSULATE
EXHAUST DUCT W/ 1" (TYP)
EXHAUST FAN OUTLET
TYPE "F" ISOLATOR (TYP)
HANGING RODS W/ VIBRATION ISOLATORS
SUSPENDED FROM STRUCTURE
S
FAN SPEED SWITCH FURNISHED BY HVAC.
INSTALLED ON FAN FOR BALANCING.
NOTE:
1.SEE DUCTWORK DRAWINGS AND SCHEDULES FOR
DUCT SIZE TO DIFFUSERS
PLENUM LINED W/1" SOUND LINING
THROUGHOUT
SEE DRAWINGS FOR DIRECTION OF BLOW
ARCH. SOFFIT OR CEILING
INLET CENTERED
48" MAX. LENGTH OF FLEXIBLE
CONNECTION (TYP., SEE SPEC.)
INSULATED FLEXIBLE DUCT FASTENED WITH
BAND CLAMPS, SCREWS ON BOTH SIDES
INSULATED LOW PRESSURE DUCT
SPIN-IN DUCT COLLAR
VOLUME DAMPER
TYP.
MOTOR HOUSING WITH
BIRD SCREEN BY FAN
MANUFACTURER
SOUND ATTENUATING ROOF CURB
FURNISHED BY HVAC
SUBCONTRACTOR. INSTALLED
AND FLASHED BY GENERAL
CONTRACTOR
DUCT SIZE TO MATCH FAN INLET
OPENING UNLESS OTHERWISE
NOTED
MOTORIZED DAMPER
(TYP) PROVIDED BY
FAN MANUFACTURER
AND INTERLOCKED
WITH FAN.
FOR ROOF
CONSTRUCTION SEE
ARCH. DRAWINGS
ROOF
14"
MIN
ROOF EXHAUST FAN. FOR
ACTUAL TYPE (V-BELT OR
DIRECT DRIVE AND
UPBLAST OR
DOWNBLAST). SEE
SCHEDULE ON THE
DRAWINGS
NOTE:
FOR HINGED FAN CURB REQUIREMENTS (WHERE REQUIRED),
REFER TO SCHEDULES ON THE DRAWINGS AND/ OR SPECIFICATION.
VIBRATING
HVAC EQUIPMENT
5/8" TREADED SUPPORT
ROD & LOCKNUTS
5/8" ROD SUPPORT CONNECTED
TO BUILDING STRUCTURE (TYP
2)
VIBRATION ISOLATOR (TYP)
5/8" THREADED LOWER ROD
5/8" THREADED UPPER ROD & LOCKNUTS
NEOPRENE SPRING CUP
DOUBLE DEFLECTION NEOPRENE ELEMENT
FASTEN SHEET METAL WITH GASKET,
SCREWS AND A CONTINUOUS ANGLE IRON
ALONG LOUVER BASE. KEEP DUCT SLIGHTLY
HIGHER TO PREVENT ACCUMULATION OF
WATER ON SHEET METAL.
DRILL 3/8" HOLES 12"
O.C. ALONG FRONT BASE
OF LOUVER FOR DRAINAGE.
(OUTSIDE)
PITCH MIN 1/4" PER FOOT
SEAL BOTTOM OF PLENUM AND
UP TO 6" ON EACH SIDE WITH
WATERTIGHT MASTIC SEALANT.
LOUVER WITH 1/2" MESH
MIN. 18"
GALVANIZED STEEL
BIRDSCREEN
ENCLOSE ENTIRE PLENUM WITH 2" RIGID
EXTERIOR INSULATION. SEE SPECIFICATION.
LOUVER PROVIDED
BY G.C.
WALL
RELIEF/OUTSIDE AIR
DUCTWORK (REFER TO DWG.)
THREADED ROD PER SMACNA
LOAD RATED FASTENER
BAND OF SAME SIZE AS HANGER
STRAP. HANGER SIZED PER
SMACNA STANDARDS. HANGER
MUST NOT DEFORM DUCT SHAPE
SUPPLY REGISTER AT INTERIOR
ZONES (TYPICAL)
SUPPLY REGISTER AT EXTERIOR
WALLS (TYPICAL)
VOLUME DAMPER
ALIGN SIDES OF DUCT
RUNOUT WITH EDGE OF
REGISTER FRAME
45°
SUPPLY REGISTER WITH
OPPOSED BLADE DAMPER
TURN DUCT EDGE INWARD TO
FORM LIP FOR ATTACHMENT
OF DIFFUSER MARGIN
DUCT RUNOUT SIZED FOR
REGISTER AND MARGIN
LOAD RATED FASTENER
THREADED ROD PER SMACNA
ROUND SPIRAL DUCT
BAND OF SAME SIZE AS
HANGER STRAP. HANGER
SIZED PER SMACNA
STANDARDS. HANGER
MUST NOT DEFORM DUCT
SHAPE
DUCT RUNOUT SIZED FOR
REGISTER AND FRAME
VOLUME DAMPER
TURN DUCT EDGE
INWARD TO FORM LIP
FOR ATTACHMENT OF
DIFFUSER MARGIN
SUPPLY REGISTER WITH
OPPOSED BLADE DAMPER
SUPPORT FROM UNDERSIDE OF
STRUCTURE (TYP)
DIFFUSER BOOT CONNECTION WITH
EXTERNAL INSULATION AND ALL
SEAMS SEALED AIR TIGHT
CEILING
LAY-IN CEILING DIFFUSER
FLRXIBLE DUCT (USE AS REQ'D
FOR DIFFUSER ALIGNMENT)
BELL MOUTH
TAKE OFF
W/DAMPER (TYP)
VOLUME DAMPER
SUPPLY AIR DUCT2' 2' 2'
5'-0"
MAX
NOTES :
1.MAXIMUM SAG 1/2" PER FOOT.
SLOPE
TYPICAL-THREADED HANGING ROD
SECURELY ANCHORED TO
STRUCTURE - REF MANF. INSTALL
AND DIV 23 SPECS.
ALTERNATE HIGH LEVEL
OVERFLOW DRAIN TO
APPROVED
LOCATION WHEN
SPECIFIED/REQUIRED BY CODE.
TYPICAL OF SUPPLY
AND RETURN,
FLEXIBLE CANVAS
DUCT
CONNECTORS WHEN
SPECIFIED,
REF DIV 23 SPECS
WHEN SCHEDULED/SPECIFIED,
MANUFACTURER FILTER BOX
ACCESSORY WITH ANGLE
PLEATED
MEDIA.
SOFT ACR COPPER TUBE LINES (LIQUID &
GAS) TO INDOOR UNIT, ALL LINES (LIQUID &
GAS) FULLY INSULATED AND PROPERLY
SUPPORTED - REF DIV 23 SPECS
1-1/4" PRIMARY GRAVITY DRAIN
CONNECTION
WHEN USED IN LIEU OF BUILT IN LIFT
PUMP-ROUTE TO APPROVED LOCATION.
CONNECT WITH MANF. PROVIDED FLEXIBLE
HOSE.
PROVIDE TRAP WITH
CLEAN-OUT, SIZE PER
CODE FOR POSITIVE
PRESSURE (BLOW
THROUGH) COIL
OPERATION.
BUILT IN LIFT PUMP DISCHARGE, WHEN
USED (IF PRESENT ON MODEL),
MAINTAIN FULL LINE SIZE (DO NOT
TRAP) UP TO RATED MAX LIFT, THEN
IMMEDIATELY INTO GRAVITY VENTED
MAIN DRAIN.
CONTROL/ELEC
PANEL-MAINTAIN
REQUIRED
CLEARANCE - REF MANF
INSTALL MANUAL.
VENT
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:1
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-0.4
HVAC DETAILS (1 OF 2)
NACE 242190
N.T.S.
BELL MOUTH CONNECTION DETAIL
N.T.S.
INLINE CABINET FAN MOUNTING DETAIL
N.T.S.
LINEAR SIDEWALL DIFFUSER DETAIL (TYPICAL)
N.T.S.
ROOF EXHAUST FAN DETAIL (MUSHROOM TYPE)
N.T.S.
VIBRATION ISOLATOR DETAIL
N.T.S.
TYPICAL LOUVER DETAIL
N.T.S.
SUPPLY REGISTER (STRAIGHT & 45⁰ THROW) DETAIL
N.T.S.
CEILING DIFFUSER BRANCH TAKE-OFF DETAIL (SQUARE)
N.T.S.
MITSUBISHI HORIZONTAL DUCTED INDOOR UNIT
FLEXIBLE CASING AND WIRE (50'-0" MAXIMUM)
RACK & PINION OPERATOR
FLEXIBLE CASING AND WIRE (50'-0" MAXIMUM)
RACK & PINION OPERATOR
DIE CAST MOUNTING CUP
NOTE:
1) COORDINATE EXACT LOCATION OF CEILING MOUNTED CONCEALED REGULATOR
WITH CONTRACTING OFFICER PRIOR TO INSTALLATION.
2) THE 270-301 BOWDEN CABLE CONTROL SYSTEM IS DESIGNED TO BE IMBEDDED IN
THE CEILING FLUSH WITH THE FINISHED SURFACE.
3) CABLE SHALL CONSIST OF BOWDEN CABLE 0.054" STAINLESS STEEL CONTROL
WIRE ENCAPSULATED IN 1/16" FLEXIBLE GALVANIZED SPIRAL WIRE SHEATH.
4) LOCKING RACK AND PINION GEAR DRIVE SHALL BE CONSTRUCTED OF 14 GAUGE
STEEL AND SHALL BE USED TO CONVERT ROTARY MOTION INTO PUSH-PULL
MOTION.
5) CONTROL SHAFT SHALL BE "D"-STYLE FLATTENED 1/4" DIAMETER WITH 265°
ROTATION PROVIDING 1-1/2" LINEAR TRAVEL CAPABILITY.
NOTE:
1) COORDINATE EXACT LOCATION OF CEILING MOUNTED CONCEALED
REGULATOR WITH CONTRACTING OFFICER PRIOR TO INSTALLATION.
2) THE 270-301EZ BOWDEN CABLE CONTROL SYSTEM IS DESIGNED TO BE
IMBEDDED IN THE CEILING FLUSH WITH THE FINISHED SURFACE. DAMPER
POSITION INDICATOR VISIBLE UNDER COVER PLATE. CABLE SHALL CONSIST
OF BOWDEN CABLE 0.054" STAINLESS STEEL CONTROL WIRE
3) ENCAPSULATED IN 1/16" FLEXIBLE GALVANIZED SPIRAL WIRE SHEATH.
4) LOCKING RACK AND PINION GEAR DRIVE SHALL BE CONSTRUCTED OF 14
GAUGE STEEL AND SHALL BE USED TO CONVERT ROTARY MOTION INTO
PUSH-PULL MOTION.
5) CONTROL SHAFT SHALL BE "D"-STYLE FLATTENED 1/4" DIAMETER WITH 265°
ROTATION PROVIDING 1-1/2" LINEAR TRAVEL CAPABILITY.
6-32 SCREWS, TAMPER
PROOF OPTIONAL
3"∅ COVER PLATE
3"∅ COVER PLATE
270-301EZ BOWDEN CABLE CONTROL
SYSTEM
270-301 BOWDEN CABLE CONTROL
SYSTEM
5020CC ROUND DAMPER OR 830ACC RECTANGULAR
OPPOSED BLADE DAMPER
5020CC ROUND DAMPER OR 830ACC RECTANGULAR
OPPOSED BLADE DAMPER
SOCKET WRENCH
CONCEALED REGULATOR KIT
CEILING DIFFUSER
SOCKET WRENCH
CONCEALED REGULATOR KIT
CEILING DIFFUSER
FLEXIBLE DUCTWORK
RIGID DUCTWORK
FLEXIBLE DUCTWORK
RIGID DUCTWORK
CONCEALED REGULATOR KIT
CEILING DIFFUSER
RIGID DUCTWORK
FLEXIBLE DUCTWORK
SOCKET WRENCH
RIGID DUCTWORK
FLEXIBLE DUCTWORK
5020CC ROUND DAMPER
OR 830ACC RECTANGULAR
OPPOSED BLADE DAMPER
FLEXIBLE
CASING AND
WIRE (50'-0"
MAXIMUM)
RACK &
PINION
OPERATOR
FLEXIBLE
CASING AND
WIRE (50'-0"
MAXIMUM)
NOTES:
1) THE 270-275 BOWDEN CABLE CONTROL SYSTEM IS DESIGNED FOR USE WITH
EXTERNALLY CONTROLLED ROUND OR RECTANGULAR DAMPERS, AND CAN BE
MOUNTED IN A WIDE VARIETY OF LOCATIONS INCLUDING CEILING JOISTS, LAY-IN
CEILINGS, BEHIND GRILLES, ON OR INSIDE OTHER VARIOUS TYPES OF DIFFUSERS,
ETC.
2) CABLE SHALL CONSIST OF BOWDEN CABLE 0.054" STAINLESS STEEL CONTROL WIRE
ENCAPSULATED IN 1/16" FLEXIBLE GALVANIZED SPIRAL WIRE SHEATH.
3) LOCKING RACK AND PINION GEAR DRIVE SHALL BE CONSTRUCTED OF 14 GAUGE
STEEL AND SHALL BE USED TO CONVERT ROTARY MOTION INTO PUSH-PULL MOTION.
4) CONTROL SHAFT SHALL BE "D"-STYLE FLATTENED 1/4" DIAMETER WITH 265°
ROTATION PROVIDING 1-1/2" LINEAR TRAVEL CAPABILITY.
NOTE:
1) COORDINATE EXACT LOCATION OF CEILING MOUNTED CONCEALED REGULATOR
WITH CONTRACTING OFFICER PRIOR TO INSTALLATION.
2) THE 270-896 BOWDEN CABLE CONTROL SYSTEM IS DESIGNED TO BE IMBEDDED IN
THE CEILING FLUSH WITH THE FINISHED SURFACE.
3) CABLE SHALL CONSIST OF BOWDEN CABLE 0.054" STAINLESS STEEL CONTROL
WIRE ENCAPSULATED IN 1/16" FLEXIBLE GALVANIZED SPIRAL WIRE SHEATH.
4) LOCKING RACK AND PINION GEAR DRIVE SHALL BE CONSTRUCTED OF 14 GAUGE
STEEL AND SHALL BE USED TO CONVERT ROTARY MOTION INTO PUSH-PULL
MOTION.
5) CONTROL SHAFT SHALL BE "D"-STYLE FLATTENED 1/4" DIAMETER WITH 265°
ROTATION PROVIDING 1-1/2" LINEAR TRAVEL CAPABILITY.
270-896 BOWDEN CABLE CONTROL SYSTEM 270-275 BOWDEN CABLE CONTROL SYSTEM
7/8" THREADED CAP,
TAMPER PROOF OPTIONAL
LINEAR SLOT
DIFFUSER WITH
PLENUM BOX
SOCKET
WRENCH
MOUNTING BRACKET
LOCKING
RACK &
PINION
OPERATOR
MOUNTING BRACKET
NOTE:
DIFFUSER BOOT CONSTRUCTION
AND AIR LEAKAGE SHALL BE
SIMILAR OR EQUAL TO DONCO.
E F
D
G A
B
C
A 6" 6" 9" 9" 9" 9" 12" 12" 12" 15"
B 6" 9" 9" 9" 12" 12" 12" 12" 15" 15"
MAX
CFM
120 185 265 280 325 375 470 500 62
C 6" 8" 9" 10" 10" 12" 12" 14" 14" 16"
D 8" 10" 12" 12" 12" 14" 14" 16" 16" 18"
E
F
G
10" 10" 14" 14" 14" 14" 16" 16" 16" 20"
10" 14" 14" 14" 16" 16" 16" 16" 20" 20"
6" 6" 6" 6" 6"6" 6" 6" 6" 6"
4" TYP
EXTERIOR WALL
CAULK WITH ACOUSTICAL SEALANT
TIGHTLY PACK
ANNULAR SPACE WITH
A FIRE SAFING
MATERIAL
PIPE
PIPE INSULATION. REFER TO
SPECIFICATION FOR INSULATION
REQUIREMENTS
PIPE SLEEVE
JACKETED PIPE INSULATION.
REFER TO INSULATION
SPECIFICATION
1/2"Ø MIS
SPOT WELD ANGLE TO STRUCTURAL STEEL
STRUCTURAL STEEL OR
BUILDING STRUCTURE
STRAP HANGER
STRAPS
HANGERC-CLAMP
(TYPICAL)
TRAPEZE HANGER
ANGLES
NOTES:
1.REFER TO OTHER DETAILS ON THIS DRAWING FOR HIGH VELOCITY DUCTWORK
DETAILS AS REQUIRED.
2.FOR STRAP AND TRAPEZE HANGER SIZE, REFER TO SMACNA DUCT STANDARDS.
3.NO POP RIVETS ALLOWED, USE SELF-TAPPING SHEET METAL SCREWS ONLY.
4. DUCTWORK HANGER SUPPORT SHALL BE ON OUTSIDE OF DUCT INSULATION.
DUCT/SLEEVE CONNECTION
OVER-CENTER LINK
AUX. OPERATION JACKSHAFT
DAMPER
FIRESTAT (SP-100)
16" MAX 6" MAX
NOTE:
1. FIRE DAMPER INSTALLATION TO MEET "UL555S LEAK CLASS 1, NFPA AND WASHINGTON, DC CODE REQUIREMENTS.
2. CONTRACTOR TO PROVIDE A MOCK-UP ISNTALLATION OF ONE DAMPER PRIOR TO THE COMPELTE INSTALLATION OF ALL
DAMPERS FOR CONTRACTING OFFICER APPROVAL.
3. DETAIL BASED ON RUSKIN FSD-60 VERTICAL WALL INSTALLATION WITH TWO ANGLES.
FASTEN DAMPER TO
SLEEVE BY WELDING 6"
O.C.
MOUNTING ANGLES
(PFMA OR FAST OR CONVENTIONAL)
FLOOR OR WALL
BUILDING CONSTRUCTION
ACCESS DOOR SHALL
BE MIN. 8" x 8"
FOR DUCT UP TO 12"
WIDE &
12" x 12" FOR WIDER
DUCTWORK
ACTUATOR
(LOCATION CAN VARY)
1" TYPICAL MIN. OVERLAP
ON ALL SIDES OF
PARTITION WALL
STAINLESS STEEL
NEGATOR CLOSURE
SPRING
FASTEN DAMPER TO
SLEEVE BY
WELDING 6" ON CENTER
FLOOR OR WALL
BUILDING
CONSTRUCTION
BLADE LOCK
ALTERNATE LOCATION
FOR ACCESS DOOR
"S" JOINT COLLAR TO DUCT
BOTH
SIDES OF FIRE DAMPER (TYP.)
ONE PIECE ROLL FORMED
GALVANIZED STEEL FRAME
FUSIBLE LINK
(REPLACEABLE SNAP LINK)
9/32" DIAMETER GALVANIZED
STEEL PIVOT ROD OR RIVET
ACCESS DOOR (MINIMUM 8"x8" FOR
DUCT UP TO 12" WIDE; MINIMUM
12"x12" FOR WIDER DUCTWORK)
NOTE:
FIRE DAMPER INSTALLATION TO MEET UL REQUIREMENTS.
12" HIGH ROOF SUPPORT CURBS
SECURELY
ANCHORED TO ROOF DECK, FLASH AND
SEAL-COORDINATE WITH ROOFING
CONTRACTOR
HOLDING ROOF WARRANTY.
P SERIES OUTDOOR UNIT SECURELY
MOUNTED/BOLTED ON QUICK SLING
STAND -
WIND BAFFLES REQUIRED (NOT SHOWN).
12" HIGH MIN. (OR HIGHER TO
ENSURE 12" ABOVE
MAX SNOW FALL HEIGHT)
QUICK SLING STAND
SECURELY ANCHORED INTO
ROOF SUPPORT
CURBS BELOW
BLOW
ER SECTIO
N
FIELD PROVIDED MERV-13 FILTER BANK.
REFER TO HFU SCHEDULE FOR SIZES.
PROVIDE TURNING VANES
ON DISCHARGE DUCT OF
UNIT AT ELBOW FITTING.
ELECTRICAL SECTION
SUPPLY DUCTWORK TO
BE INSULATED AND LINED
PER SPECIFICATIONS.
SOUND LINING SHALL BE
1" THICK AND INSTALLED
10 FT FROM UNIT
DISCHARGE.
SOFT ACR COPPER TUBE LINES
(LIQUID & GAS) TO INDOOR UNIT,
ALL LINES (LIQUID & GAS) FULLY
INSULATED AND PROPERLY
SUPPORTED
COIL SECTION
PROVIDE ALL UNITS WITH
DRAIN PAN LEVEL SENSOR TO
SHUT DOWN INDOOR UNIT AND
PREVENT DRAIN PAN
OVERFLOW.
BLOWER SECTION
FILTER RACK SECTION.
WASHABLE MANUFACTUER
PROVIDED BUILT IN FILTER.
3/4" CONDENSATE DRAIN CONNECTION -
CONNECT WITH FULL LINE SIZE AND
PROVIDE TRAP WITH CLEANOUT AND ANTI-
SIPHON. REFER TO MANUFACTURER'S
INSTALLATION MANUAL FOR ADDITIONAL
INFORMATION. REFER TO DRAWINGS FOR
ROUTING AND DISCHARGE LOCATION.
ANTI-SIPHON
20"x20" RETURN AIR OPENING. PROVIDE
WITH 1/4" GLAVINIZED FRAME WIRE MESH
SCREEN OVER OPENING.
FIELD PROVIDED 24"X24" RETURN PLENUM BASE
WITH INTERNAL RE-REINFORCEMENTS TO
SUPPORT 200 LBS AND NEGATIVE 2" PRESSURE
CLASSIFICATION. PLENUM CONNECTION TO FAN
COIL UNIT SHALL MATCH THE RETURN AIR
OPENING OF VERTICAL FAN COIL UNIT AND
SHOULD BE SEALED AIRTIGHT. INTERNAL
REINFORCEMENTS SHALL BE LOCATED BELOW
FAN COIL UNIT BASE FOR SUPPORT. PLENUM TO
HAVE FLANGES FOR FAN FILTER HOUSING
INSTALLATION.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:1
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
Author
Checker
7/8/2021
M-0.5
HVAC DETAILS (2 OF 2)
NACE 242190
N.T.S.
DIFFUSER CONNECTION DETAIL
N.T.S.
EXTERIOR WALL PIPE PENETRATION DETAIL
N.T.S.
DUCT HANGER DETAIL (LOW VELOCITY)
N.T.S.
YOUNG REGULATOR DAMPER DETAIL
N.T.S.
FIRE/SMOKE COMBINATION DAMPER DETAIL - 2
N.T.S.
FIRE DAMPER WITH BLADE OUTSIDE OF AIRSTREAM
N.T.S.
YOUNG REGULATOR DAMPER DETAIL
N.T.S.
P-SERIES CONDENSING UNIT MOUNTING DETAIL
N.T.S.
MITSUBISHI VERTICAL DUCTED INDOOR UNIT
KEYED NOTES
8"x8"
8"x6" 12"x10"
12"x12"
"x
"x
"ø
"ø
EUH
X
EXISTING
EUH
X
EXISTING
EUH
X
EXISTING
AC
2X
EXISTING
AC
1X
EXISTING
"x
10"x10"
8"ø
REMOVE 18x8 OA
FROM 3RD FLOOR EUH
X
REMOVE
8"x8"
10"x10"
AC
3X
REMOVE
20"x12"
18"x12" 16"x10" 14"x10"
14"x10"
FLOOR MOUNTED
"x
6"x6"
6"x6"
EXISTING
10x10 UP
EXISTING
10x8 UP
12"x10"
EUH
X
EXISTING
M-2.2
M-2.2
M-2.2
M-2.2
M-2.2
EUH
X
REMOVE
UP TO EXISTING
CU-1X
REMOVE EXISTING
REFRIGERANT PIPING
ASSOCIATED WITH AC-3X AND
CU-3X IN ITS ENTIRETY.
UP TO EXISTING
CU-2X
EXISTING CD TO
STORM.
DEMOLISH EXISTING DUCTWORK BACK TO POINT SHOWN. SEAL AND
CAP AIRTIGHT.
DEMOLISH EXISTING DUCTWORK BACK TO POINT SHOWN AND MAKE
READY FOR NEW CONNECTION.
REMOVE EXISTING UNIT AND STORE AS DIRECTED BY CONTRACTING
OFFICER.
DEMOLISH EXISTING 3/4" CD PIPING BACK TO POINT SHOWN AND UPSIZE
TO SIZE SHOWN ON NEW WORK PLANS. MAKE READY FOR NEW
CONNECTION.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:2
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-D1.0
HVAC BASEMENT DEMOLITION
PLAN
ENTRY
EXHIBIT
110ELEV.
STAIR 1
ST1-1
SR-X
REMOVE
RR-X
RELOCATE
SR-X
RELOCATE
RR-X
RELOCATE
SR-X
REBALANCE
EXISTING
RR-X
REBALANCE
EXISTING
CU
1X
RELOCATE
CU
2X
RELOCATE
CU
3X
REMOVE
M-2.2
M-2.2
M-2.2
M-2.2
M-2.2
AC
X
REMOVE
EF
X
REMOVE
EXISTING
REFRIGERANT
PIPING DN TO AC-2X.
EXISTING
REFRIGERANT
PIPING DN TO AC-1X.
REMOVE EXISTING
REFRIGERANT PIPING
ASSOCIATED WITH AC-3X AND
CU-3X IN ITS ENTIRETY.
EXISTING TO REMAIN
RELOCATE EXISTING CONDENSING UNIT TO LOCATION SHOWN ON NEW
WORK PLAN.
DEMOLISH EXISTING DUCTWORK BACK TO POINT SHOWN. CAP AND
SEAL AIRTIGHT.
DEMOLISH EXISTING REFRIGERANT LINES BACK TO POINT SHOWN AND
MAKE READY FOR NEW CONNECTION.
DEMOLISH DUCTWORK BACK TO POINT SHOWN AND MAKE READY FOR
NEW CONNECTION.
REMOVE EXISTING CONDENSING UNIT AND STORE AS DIRECTED BY
CONTRACTING OFFICER.
EXISTING OA DUCTWORK
TO BE REMOVED.
EXISTING OA LOUVER,
ASSOCIATED CONTROLS, AND
DUCTWORK TO BE REMOVED.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:2
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-D1.1
HVAC FIRST FLOOR
DEMOLITION PLAN
NACE 242190
1/4" = 1'-0"
HVAC DUCTWORK SECOND FLOOR DEMOLITION PART PLAN
1/4" = 1'-0"
HVAC DUCTWORK THIRD FLOOR DEMOLITION PART PLAN
SHEET NOTES
20x10 LINED SA &
RA DUCTS UP.
10x10 SA DUCT
UP.
10x8 EA UP TO
EF-1 ON ROOF.
8"x8"
8"x6" 12"x10"
"x
"x
"ø
"ø
EUH
X
EXISTING
EUH
X
EXISTING
EUH
X
EXISTING
AC
2X
EXISTING
AC
1X
EXISTING
16x10 LINED SA & RA DUCTS UP.
24x14 LINED SA & RA DN TO AC-3.
28x10 SA & RA
DUCTS UP.
SR-5
(TYP. 2)
NEW705
RR-6
NEW
18"x10"
M-2.2
M-2.2
M-2.2
M-2.2
M-2.2
12x6 EA UP TO
THIRD FLOOR.
UP TO NEW
CU-2
UP TO NEW
CU-1
UP TO NEW
CU-3
UP TO NEW
CU-4
UP TO RELOCATED
CU-1X.
SR-7
NEW
RR-6
NEW
12"x12"
12"x12"
20"x16"
18"x14"
30x14 OA DUCT
FROM ABOVE.
20"x10"
18"x10" "x
ECUH
NEW
10x10 OA UP TO
FIRST FLOOR.
14x14 RA DN
TO PLENUM.
UP TO NEW
CU-6
8"x8"
SD-1
NEW
RR-3
NEW
FSD
FD
FD
FD
UP TO RELOCATED
CU-2X.
AC
NEW
AC
NEW
AC
NEW
22"x10"
LINED
18"x10"
LINED
20"x16"
18"x14"
LINED
LINED
1" COND DN TO OED.
3/4" COND TO
NEAREST OED.
VD
VD
HC
4.0 kW
NEW
HC
4.0 kW
NEW
HC
4.5 kW
NEW
HC
1.5 kW
NEW
BF
NEW
8"ø
"ø
"ø
HC
3.0 kW
NEW
FD
FD
SD
SD
18"x10"
20x10 SA
DUCT UP.
18x10 RA
DUCT UP.
FSD
ER-3
NEW
BF
NEW
T N
TO AC-4
VD
MD
MD
AC
NEW
MD
CO
AC
NEW
BF
NEW
VD
210 CFM8"x8"
3/4" COND DN TO OED.
CO
VD
90 CFM
6"ø
230 CFM
200 CFM
160 CFM
BF
NEW
CO
1 1/4" CON
1 1/4" COND
1" COND
L
L
MD
MD
1" CD FROM AC-5 ON 3RD FLOOR.
CO
CO
1 1/4" COND
3/4" COND
1" COND
1" COND
1" COND
1 1/4" COND
AP
AP
BF
NEW
LINED
8"x8"
AP
AP
AP
AP
1. REFRIGERANT PIPING SIZED PER MANUFACTURER'S
RECOMMENDATIONS.
PROVIDE ACOUSTICALLY LINED SHEET METAL PLENUM BOX
BELOW AC UNITS FOR RETURN AIR DUCT TO TIE INTO.
PROVIDE 10' OF ACOUSTICALLY LINED SUPPLY DUCTWORK
FROM DISCHARGE OF AC UNITS.
PROVIDE 10' OF ACOUSTICALLY LINED RETURN DUCTWORK TO
INLET OF AC UNITS.
ALL SUPPLY AND RETURN ELBOWS MUST HAVE TURNING
VANES.
FIRE AND COMBINATION FIRE/SMOKE DAMPERS SHOWN ON
BASEMENT PLAN ARE TO BE INSTALLED AT LEVEL 1 SLAB.
EACH OUTSIDE AIR TAKE OFF TO AC UNITS SHALL BE
PROVIDED WITH A MOTORIZED DAMPER, HEATING COIL, AND A
VOLUME DAMPER. VOLUME DAMPER TO BE BALANCED TO
OUTSIDE AIR VALUE NOTED ON AC SCHEDULES AND FLOOR
PLANS.
OUTSIDE AIR DUCTWORK SHALL BE INSULATED IN ITS
ENTIRETY.
MOTORIZED DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS,
AND HEATING COILS LOCATED ABOVE GYPSUM BOARD CEILING
WILL NEED ACCESS PANELS FOR SERVICE.
2.
3.
4.
5.
6.
7.
8.
9.
PROVIDE YOUNG REGULATOR VOLUME DAMPER.
FIRE DAMPER TO BE ACCESSED FROM LEVEL ABOVE DUE TO SPACE
CONSTRAINTS AND LIMITED ACCESSIBILITY.
RETURN AIR TO BE SUPPLIED INTO MECHANICAL ROOM. MECHANICAL
ROOM TO BE UTILIZED AS AIR PLENUM. ASSOCIATED AC UNIT TO
PULL AIR IN FROM MECHANICAL ROOM.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:1
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-1.0
HVAC DUCTWORK BASEMENT
FLOOR PLAN
NACE 242190
SCALE: 1/4" = 1'-0"M-1.0
1 HVAC DUCTWORK BASEMENT FLOOR PLAN
KEYED NOTESENTRY
ELEV.
STAIR 1
ST1-1
CORRIDOR
SR-6
NEW
SR-1
NEW
RR-4
NEW
RR-5
NEW
CU
2X
RELOCATED
CU
1X
RELOCATED
"x
12"x8"
28x10 SA & RA DUCTS DN.
26x8 SA & RA DUCTS UP.
(AC-1)
16x10 SA & RA
DUCTS UP & DN.
(AC-3)
14x10 SA & RA DUCT UP.
20x10 SA DUCT DN.
18x12 RA DUCT DN.
(AC-2)
6x8 SA DUCT UP.
8x8 SA DUCT DN.
(AC-4)
LD-1
(TYP. 2)
NEW
6"x18"
REFRIGERANT PIPING
UP TO AC-5 IN 3RD
FLOOR ATTIC.
SD-3
(TYP. 2)
NEW
SD-3
(TYP. 2)
NEW
RR-X
REBALANCE
RELOCATED
RR-X
REBALANCE
RELOCATED
SR-X
REBALANCE
EXISTING
RR-X
REBALANCE
EXISTING
10x10 OA DUCT DN
TO BASEMENT
LEVEL.
30x14 OA DUCT DN TO
BASEMENT LEVEL.
T N
TO AC-6
T N
TO AC-1
T N
TO AC-2
DN TO NEW
AC-6
DN TO NEW
AC-4
DN TO NEW
AC-2
DN TO NEW
AC-1
DN TO AC-1X
DN TO AC-2X
PROVIDE A 5.0 SF FREE AREA
INTAKE LOUVER WITH 18" DEEP
INSULATED PLENUM. ASSUMING
50% FREE AREA.LOUVER TO BE
AT LEAST 36" ABOVE GRADE.
LOUVER BY OTHERS.
12x6 EA UP
AND DN.
ER-3
NEW
SD-1
NEW
U
FD FD FDFD
FSD
FSD
FSD
FSD
FSD
6.0 SF FREE AREA INTAKE
LOUVER (LOUVER BY OTHERS),
LOUVER SIZE ASSUMES 50%
FREE AREA. PROVIDE 18" DEEP
INSULATED PLENUM BEHIND
LOUVER. LOUVER TO BE A
MINIMUM OF 36" ABOVE GRADE.
LOUVER BY OTHERS.
EXTEND NEW REFRIGERANT
PIPING BELOW GRADE TO
EXISTING CU-1X AND CU-2X.
NEW REFRIGERANT PIPING
BELOW GRADE .
CU
NEW
CU
NEW
CU
NEW
CU
NEW
CU
NEW
CU
NEW
3/4" CD DN TO OED
IN BASEMENT.
10x8 EA DN TO BASEMENT LEVEL & 10x10 EA UP TO EF-1
ON ROOF.
FSD
SD
SD SD
SD SD
SD
SD
SD
TRANSITION
20x10 SA RISER
INTO EXISTING
12x10 SA RISER.
TRANSITION
18x10 RA RISER
INTO EXISTING
14x10 RA RISER.
EXISTING TO REMAIN
U
EBB-1
1.0 kW
NEW
4'-0"
FD
FSD
VD
VD VD
VD VD
1 1
10"Ø
(TYP. 4)
VD
AP
AP
AP
AP
AP
AP
AP
AP
AP
1. REFRIGERANT PIPING SIZED PER MANUFACTURER'S
RECOMMENDATIONS.
CONDENSING UNITS MUST HAVE A MINIMUM OF 24" BETWEEN
EACHOTHER.
CONDENSING UNITS MUST HAVE A MINIMUM OF 24" CLEAR TO
ARCHITECTURAL FENCE.
CONTRACTOR TO ENSURE THAT CONDENSING UNIT CLEARANCE
REQUIREMENTS ARE MET.
ALL SUPPLY AND RETURN ELBOWS MUST HAVE TURNING VANES.
MOTORIZED DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, AND
HEATING COILS LOCATED ABOVE GYPSUM BOARD CEILING WILL
REQUIRE ACCESS PANELS FOR SERVICE.
2.
3.
4.
5.
6.
PROVIDE YOUNG REGULATOR VOLUME DAMPER.1
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:1
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-1.1
HVAC DUCTWORK FIRST
FLOOR PLAN
NACE 242190
SCALE: 1/4" = 1'-0"M-1.1
1 HVAC DUCTWORK FIRST FLOOR PLAN
10x10 UP TO EF-1
ON ROOF.
SR-5
NEW
RR-7
NEW
RR-5
NEW
RR-5
NEW
16x10 SA & RA DN.
(AC-3)
14x10 SA & RA
DUCT DN.
(AC-2)
6x8 SA
DUCT DN.
(AC-4)
26x8 SA & RA
DUCTS DN.
(AC-1)
SR-7
NEW
"x
10"x14"
REFRIGERANT PIPING
UP TO AC-5 IN 3RD
FLOOR ATTIC. 400
SR-6
NEW
16"x10"
T N
TO AC-3
RR-X
REBALANCE
EXISTING
SR-X
REBALANCE
EXISTING
SR-X
REBALANCE
EXISTING
RR-X
REBALANCE
EXISTING
12x6 EA UP
AND DN.
U
3/4" CD DN TO OED
IN BASEMENT.
MD
10x10 DN TO
LEVEL 1.
SD
SD-1
NEW
RD-1
NEW
SD-1
NEW
FD
FD
FD
FD FDFD
12"x10"
EXISTING TO REMAIN
U
FD VD
VD
VD
EBB-1
1.0 kW
NEW
4'-0"
SD
SR-1
(TYP. 2)
NEW
6"x8" 6"x6"
FSD
VD
FSD
ER-2
NEW
AP AP
1. REFRIGERANT PIPING SIZED PER MANUFACTURER'S
RECOMMENDATIONS.
ALL SUPPLY AND RETURN ELBOWS MUST HAVE TURNING
VANES.
MOTORIZED DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS,
AND HEATING COILS LOCATED ABOVE GYPSUM BOARD CEILING
WILL REQUIRE ACCESS PANELS FOR SERVICE.
2.
3.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:1
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-1.2
HVAC DUCTWORK SECOND
FLOOR PLAN
NACE 242190
SCALE: 1/4" = 1'-0"M-1.2
1 HVAC DUCTWORK SECOND FLOOR PLAN
SD-5
(TYP. 2)
NEW
SD-6
(TYP. 2)
NEW
SD-2
NEW
ER-2
NEW
EF
NEW
RD-4
NEW
REFRIGERANT
PIPING FROM CU-5.
RR-7
NEW
PROVIDE A 1.0 SF FREE AREA
OUTSIDE AIR LOUVER WITH 18"
DEEP INSULATED PLENUM.
ASSUMING 50% FREE AREA.
LOUVER BY OTHERS.
12x6 EA DN TO
MENS ROOM 003.
RETURN GRILLE TO BE
INSTALLED 10" AFF.
T N
SR-X
REBALANCE
EXISTING
RR-X
REBALANCE
EXISTING
SR-X
REBALANCE
EXISTING
RR-X
REBALANCE
EXISTING
EF
NEW
PROVIDE A 1.0 SF FREE AREA
EXHAUST LOUVER WITH 18" DEEP
INSULATED PLENUM. ASSUMING 50%
FREE AREA. LOUVER BY OTHERS.
SD-1
NEW
MD
FD
U
HC
4.0 kW
NEW
LINED
VD
1" COND
1" CD DN TO OED IN
BASEMENT.
MD
8"x8" UP TO EF-2
ON ROOF.
VD
"x
30"x14"
VDVD
"x
L
IN
E D
8"ø
EXISTING TO REMAIN
EBB-1
1.0 kW
NEW
4'-0"
U
MD
VDVD
200 CFM
VD
VD
1 1
AP
AP
1. REFRIGERANT PIPING SIZED PER MANUFACTURER'S
RECOMMENDATIONS.
PROVIDE 10' OF ACOUSTICALLY LINED SUPPLY DUCTWORK
FROM DISCHARGE OF AC-5.
PROVIDE ACOUSTICALLY LINED RETURN DUCTWORK TO AC-5.
OUTSIDE AIR TO AC-5 SHALL BE BALANCED TO OUTSIDE AIR
VALUE NOTED ON AC SCHEDULES.
ALL SUPPLY AND RETURN ELBOWS MUST HAVE TURNING
VANES.
MOTORIZED DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS,
AND HEATING COILS LOCATED ABOVE GYPSUM BOARD CEILING
WILL REQUIRE ACCESS PANELS FOR SERVICE.
2.
3.
4.
5.
6.
PROVIDE YOUNG REGULATOR VOLUME DAMPER.1
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION DOCUMENTS
/8
/2
:0
:1
P M
D R e v it D o c u m e n ts
\M
-0
.0
C a rt e r
W o o d s o n
M
E C
H v
T o m a s ia n A
-A H
A .r v t
Designer
AT
JS
7/8/2021
M-1.3
HVAC DUCTWORK THIRD
FLOOR PLAN
NACE 242190
SCALE: 1/4" = 1'-0"M-1.3
1 HVAC DUCTWORK THIRD FLOOR PLAN
FINISHED FIRST
FLOOR
84' - 7"
FINISHED SECOND
FLOOR
95' - 8"
FINISHED THIRD
FLOOR
105' - 8"
BASEMENT FLOOR
74' - 6"
EF
NEW
10"x16"
ECUH
NEW
EF
NEW
6"x12"
AHA FINISHED FIRST
FLOOR
84' - 7"
AHA FINISHED
SECOND FLOOR
95' - 8"
AHA FINISHED THIRD
FLOOR
105' - 8"
AHA ROOF
118' - 9"
AHA BASEMENT
FLOOR PLAN
74' - 6"
FINISHED FIRST
FLOOR
84' - 7"
AHA FINISHED
SECOND FLOOR
95' - 8"
AHA FINISHED THIRD
FLOOR
105' - 8"
AHA ROOF
118' - 9"
AHA BASEMENT
FLOOR PLAN
74' - 6"
GRADE
81' - 0"
FINISHED FIRST
FLOOR
84' - 7"
FINISHED SECOND
FLOOR
95' - 8"
FINISHED THIRD
FLOOR
105' - 8"
BASEMENT FLOOR
74' - 6"
SD-1
(TYP. 2)
SD-6
(TYP. 2)
NEW
SD-5
(TYP. 2)
NEW
AHA FINISHED FIRST
FLOOR
84' - 7"
AHA FINISHED
SECOND FLOOR
95' - 8"
AHA FINISHED THIRD
FLOOR
105' - 8"
AHA ROOF
118' - 9"
AHA BASEMENT
FLOOR PLAN
74' - 6"
FINISHED FIRST
FLOOR
84' - 7"
AHA FINISHED
SECOND FLOOR
95' - 8"
AHA FINISHED THIRD
FLOOR
105' - 8"
AHA ROOF
118' - 9"
AHA BASEMENT
FLOOR PLAN
74' - 6"
GRADE
81' - 0"
FINISHED FIRST
FLOOR
84' - 7"
FINISHED SECOND
FLOOR
95' - 8"
FINISHED THIRD
FLOOR
105' - 8"
BASEMENT FLOOR
74' - 6"
EF
NEW
16"x10"
20"x10"
16"x10"
18"x6"
12"x6"
28"x10" 28"x8"
12"x6"
PROVIDE A 1.0 SF FREE AREA EXHAUST
LOUVER WITH 18" DEEP INSULATED
PLENUM. ASSUMING 50% FREE AREA.
PROVIDE A 1.0 SF FREE AREA
OUTSIDE AIR LOUVER WITH 18" DEEP
INSULATED PLENUM. ASSUMING 50%
FREE AREA.
GRADE
81' - 0"
FINISHED FIRST
FLOOR
84' - 7"
FINISHED SECOND
FLOOR
95' - 8"
FINISHED THIRD
FLOOR
105' - 8"
BASEMENT FLOOR
74' - 6"
AHA FINISHED THIRD
FLOOR
105' - 8"
16"x10"
10"x18" 14"x20"
8"x8"
12"x6" 10"x12"
RR-X
REBALANCE
RELOCATED
RR-X
REBALANCE
EXISTING
SD-3
(TYP. 2)
NEW
RR-5
NEW
SD-6
(TYP. 2)
NEW
PROVIDE A 1.0 SF FREE AREA
EXHAUST LOUVER WITH 18" DEEP
INSULATED PLENUM. ASSUMING 50%
FREE AREA.
PROVIDE A 1.0 SF FREE AREA
OUTSIDE AIR LOUVER WITH 18" DEEP
INSULATED PLENUM. ASSUMING 50%
FREE AREA.
24"x8"
10"x16"
AHA FINISHED FIRST
FLOOR
84' - 7"
AHA FINISHED
SECOND FLOOR
95' - 8"
AHA FINISHED THIRD
FLOOR
105' - 8"
AHA ROOF
118' - 9"
AHA BASEMENT
FLOOR PLAN
74' - 6"
FINISHED FIRST
FLOOR
84' - 7"
AHA FINISHED
SECOND FLOOR
95' - 8"
AHA FINISHED THIRD
FLOOR
105' - 8"
AHA ROOF
118' - 9"
AHA BASEMENT
FLOOR PLAN
74' - 6"
GRADE
81' - 0"
FINISHED FIRST
FLOOR
84' - 7"
FINISHED SECOND
FLOOR
95' - 8"
FINISHED THIRD
FLOOR
105' - 8"
BASEMENT FLOOR
74' - 6"
EF
NEW
28"x8"28"x10"
20"x10"
18"x6"
LD-1
(TYP. 2)
NEW
RR-4
NEW 365
SR-5
NEW
SD-1
NEW
PROVIDE A 1.0 SF FREE AREA EXHAUST
LOUVER WITH 18" DEEP INSULATED
PLENUM. ASSUMING 50% FREE AREA.
PROVIDE A 3.5 SF FREE AREA
INTAKE LOUVER WITH 18" DEEP
INSULATED PLENUM. ASSUMING
50% FREE AREA.LOUVER TO BE
AT LEAST 36" ABOVE GRADE.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
137898
CARTER G. WOODSON HOUSE
NATIONAL CAPITAL PARKS EAST
FINAL CONSTRUCTION…