This document provides details for a federal contract opportunity for solicitation number 140P2021R0111. The solicitation is for preservation and rehabilitation services at the Carter G. Woodson Home and adjacent properties located in Washington, D.C. The work includes structural repairs, HVAC upgrades, electrical work, and other facility improvements. The National Park Service is the contracting agency. The response due date is not specified, but the document includes design drawings that appear to be part of the solicitation requirements. Relevant services, response timing, and the involved federal locations and agency are outlined concisely for the preservation and rehabilitation project.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MATERIALS LEGEND

EARTH

CRUSHED STONE

CONCRETE

CONCRETE

MASONRY UNIT

BRICK

STONE

STEEL

WOOD SHIM

WOOD, FINISHED

GYPSUM BOARD

GLASS

BATT INSULATION

RIGID INSULATION

PLYWOOD

WOOD BLOCKING/ FRAMING

ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AP ACCESS PANEL

ACT ACOUSTICAL CEILING TILE

A/C AIR CONDITIONING

ALT ALTERNATE

ALUM ALUMINUM

AB ANCHOR BOLT

ARCH ARCHITECT(URAL)

ASPH ASPHALT

ASTM AMERICAN SOCIETY FOR TESTING

MATERIALS

AUX AUXILARY

BRG BEARING

BD BOARD

BOT BOTTOM

BLDG BUILDING

CAB CABINET

CARP CARPET

CLG CEILING

CTR CENTER

CENTERLINE

CT CERAMIC TILE

CLR CLEAR(ANCE)

CL CLOSET

COL COLUMN

CONC CONCRETE

CMU CONCRETE MASONRY UNIT

CONST CONSTRUCTION

CONT CONTINUE/CONTINOUS

CJ CONTROL JOINT

COORD COORDINATE

CORR CORRIDOR

DEMO DEMOLISH, DEMOLITION

DTL DETAIL

DIAG DIAGONAL

DIA DIAMETER

DIM DIMENSION

DN DOWN

DWR DRAWER

DWG DRAWING

D DRAIN

EA EACH

E EAST

ELEC ELECTRIC(AL)

EWC ELECTRIC WATER COOLER

EMER EMERGENCY

ENCL ENCLOSE (URE)

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

EJ EXPANSION JOINT

EXP EXPOSED

EXT EXTERIOR

FIN FINISH(ED)

FFL FINISH FLOOR LEVEL

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FLR FLOOR(ING)

FD FLOOR DRAIN

FM FLOOR MAT & FRAME

FT FEET

FTG FOOTING

FR FRAME(ED), (ING)

FBO FURNISHED BY OTHERS

FURR FURRED (ING)

GA GAGE, GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GL GLASS, GLAZING

GWB GYPSUM WALLBOARD

HC HANDICAPPED

HDR HEADER

HVAC HEATING/VENTILATION/

AIR-CONDITIONING

HT HEIGHT

HM HOLLOW METAL

HORIZ HORIZONTAL

HB HOSE BIB

HWH HOT WATER HEATER

IN INCH

INSUL INSULATE(D), (ING)

INT INTERIOR

JAN JANITOR

JT JOINT

JST JOIST

LAV LAVATORY

LT LIGHT

MB MARKER BOARD

MFR MANUFACTURE(R)

MO MASONRY OPENING

MAX MAXIMUM

MECH MECHANIC(AL)

MTL METAL

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

NOM NOMINAL

N NORTH

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NO NUMBER

OFF OFFICE

OC ON CENTER(S)

OPG OPENING

OPP OPPOSITE

PTD PAINTED

PVG PAVE(D), (ING)

PVMT PAVEMENT

PLAM PLASTIC LAMINATE

PLYWD PLYWOOD

PVC POLYVINYL CHLORIDE

PSI POUNDS PER SQUARE

INCH

PSF POUNDS PER SQUARE

FOOT

QTY QUANTITY

RAD RADIUS

REF REFERENCE

REFR REFRIGERATOR

REINF REINFORCING

REQ REQUIRE(D)

REV REVISION(S), REVISED

R RISER

RD ROOF DRAIN

RM ROOM

RO ROUGH OPENING

SEC SECTION

SHT SHEET

SIM SIMILAR

STC SOUND TRANSMISSION

S SOUTH

SPEC SPECIFICATION(S)

SQ SQUARE

SF SQUARE FEET

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STOR STORAGE

STR STRUCTURAL

SUSP SUPSPENDED

TB TACKBOARD

THK THICK(NESS)

T&G TONGUE AND GROOVE

TOS TOP OF SLAB

TO STL TOP OF STEEL

TOW TOP OF WALL

TYP TYPICAL

UL UNDERWRITERS

LABORATORY

UNO UNLESS OTHERWISE

NOTED

VERT VERTICAL

VIF VERIFY IN FIELD

VCT VINYL COMPOSITE TILE

WC WATER CLOSET

WWF WELDED WIRE FABRIC

W WEST

W WIDTH, WIDE

W/ WITH

W/O WITHOUT

WD WOOD

TYPICAL SYMBOLS

A1

A-1.0

SIM

SECTION

DETAIL

SHEET

INTERIOR ELEVATION

DWG #

SHEET

Room name

SECTION DETAIL

DWG #

SHEET

PLAN DETAIL

DWG #

SHEET

REVISION BUBBLE

REVISION TAG

ROOM TAG

NAME

NUMBER

X' - X"

REFERENCE SPOT/ELEVATION

NORTH ARROW

FLOOR MATERIAL CHANGE

A-1.0 A1

A-1.0 A1

A-1.0

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.1

SYMBOLS, & ABBREVIATIONS

NACE 242190

REFER TO SHEET G-0.2 FOR DRAWING INDEX

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.2

INDEX OF DRAWINGS

NACE 242190

DRAWING INDEX- VOLUME 1

SHEET # SUB SHEET NO. SHEET TITLE

125 ED-1.0 ELECTRICAL BASEMENT DEMO PLAN

126 ED-1.1 ELECTRICAL FIRST FLOOR DEMO PLAN

127 ED-1.2 ELECTRICAL SECOND FLOOR DEMO PLAN

128 ED-1.3 ELECTRICAL THIRD FLOOR DEMO PLAN

129 E-1.0 ELECTRICAL LIGHTING BASEMENT FLOOR PLAN

130 E-1.1 ELECTRICAL LIGHTING FIRST FLOOR PLAN

131 E-1.2 ELECTRICAL LIGHTING SECOND FLOOR PLAN

132 E-1.3 ELECTRICAL LIGHTING THIRD FLOOR PLAN

133 E-2.0 ELECTRICAL POWER BASEMENT FLOOR PLAN

134 E-2.1 ELECTRICAL POWER FIRST FLOOR PLAN

135 E-2.2 ELECTRICAL POWER SECOND FLOOR PLAN

136 E-2.3 ELECTRICAL POWER THIRD FLOOR PLAN

137 LV-0.1 LOW VOLTAGE LEGEND AND GENERAL NOTES

138 LV-0.2 LOW VOLTAGE AUDIO VISUAL CABLING LEGEND

139 LV-0.3 LOW VOLTAGE RISER DIAGRAM

140 LV-0.4 LOW VOLTAGE ENLARGED PART PLAN

141 LV-0.5 LOW VOLTAGE A/V PLAN

142 LV-1.0 LOW VOLTAGE BASEMENT FLOOR NEW PLAN

143 LV-1.1 LOW VOLTAGE FIRST FLOOR NEW PLAN

144 LV-1.2 LOW VOLTAGE SECOND FLOOR NEW PLAN

145 LV-1.3 LOW VOLTAGE THIRD FLOOR NEW PLAN

146 FA-0.1 FIRE ALARM NOTES

147 FA-1.0 FIRE ALARM BASEMENT FLOOR PLAN

148 FA-1.1 FIRE ALARM FIRST FLOOR PLAN

149 FA-1.2 FIRE ALARM SECOND FLOOR PLAN

150 FA-1.3 FIRE ALARM THIRD FLOOR PLAN

151 FP-0.1 FIRE PROTECTION NOTES

152 FP-1.0 FIRE PROTECTION BASEMENT FLOOR PLAN

153 FP-1.1 FIRE PROTECTION FIRST FLOOR PLAN

154 FP-1.2 FIRE PROTECTION SECOND FLOOR PLAN

155 FP-1.3 FIRE PROTECTION THIRD FLOOR PLAN

156 TY-0.1 SECURITY NOTES

157 TY-1.0 SECURITY BASEMENT FLOOR PLAN

158 TY-1.1 SECURITY FIRST FLOOR PLAN

159 TY-1.2 SECURITY SECOND FLOOR PLAN

160 TY-1.3 SECURITY THIRD FLOOR PLAN

161 TY-2.0 SECURITY DETAILS

162 TY-2.1 SECURITY RISER

DRAWING INDEX- VOLUME 1

SHEET # SUB SHEET NO. SHEET TITLE

63 A-5.3 ROOF DETAILS 2

64 A-6.0 DOOR & HARDWARE SCHEDULE

65 A-6.1 DOOR DETAILS

66 A-6.2 DOOR DETAILS

67 A-6.3 WINDOW SCHEDULE

68 A-6.4 WINDOW SCHEDULE 2

69 A-6.5 WINDOW DETAILS

70 A-6.6 WINDOW DETAILS 2

71 A-6.7 SIGNAGE SCHEDULE & DETAILS

72 A-6.8 FLOOR TRANSITION DETAILS

73 A-7.0 ELEVATOR SECTION AND PLANS

74 A-7.1 LIFT SECTION AND PLANS

75 A-8.0 MILLWORK FRONT DESK

76 A-8.1 MILLWORK FRONT DESK - ALTERNATIVES

77 A-8.2 MILLWORK KITCHENETTE, NURSING STATION

78 S-0.0 GENERAL NOTES

79 S-0.1 GENERAL NOTES

80 S-0.2 GENERAL NOTES

81 S-0.3 GENERAL NOTES

82 S-1.0 FOUNDATION AND BASEMENT FLOOR PLAN

83 S-1.1 FIRST FLOOR FRAMING PLAN

84 S-1.2 SECOND FLOOR FRAMING PLAN

85 S-1.3 THIRD FLOOR FRAMING PLAN

86 S-1.4 ROOF FRAMING PLAN

87 S-2.0 UNDERPINNING SECTIONS AND DETAILS

88 S-3.0 CONCRETE SECTIONS AND DETAILS

89 S-3.1 CONCRETE SECTIONS AND DETAILS

90 S-4.0 MASONRY AND WOOD SECTIONS AND DETAILS

91 S-5.0 STEEL SECTIONS AND DETAILS

92 S-6.0 BUILDING SECTIONS

93 M-0.1 HVAC LEGEND & GENERAL NOTES

94 M-0.2 HVAC SCHEDULES (1 OF 2)

95 M-0.3 HVAC SCHEDULES (2 OF 2)

96 M-0.4 HVAC DETAILS (1 OF 2)

97 M-0.5 HVAC DETAILS (2 OF 2)

98 M-D1.0 HVAC BASEMENT DEMOLITION PLAN

99 M-D1.1 HVAC FIRST FLOOR DEMOLITION PLAN

100 M-1.0 HVAC DUCTWORK BASEMENT FLOOR PLAN

101 M-1.1 HVAC DUCTWORK FIRST FLOOR PLAN

102 M-1.2 HVAC DUCTWORK SECOND FLOOR PLAN

103 M-1.3 HVAC DUCTWORK THIRD FLOOR PLAN

104 M-2.2 HVAC BUILDING SECTIONS

105 P-0.1 PLUMBING LEGEND & NOTES

106 P-0.2 PLUMBING SCHEDULES & DETAILS

107 PD-1.0 PLUMBING BASEMENT FLOOR DEMOLITION PLAN

108 PD-1.1 PLUMBING FIRST FLOOR DEMOLITION PLAN

109 PD-1.2 PLUMBING SECOND FLOOR DEMOLITION PLAN

110 PD-1.3 PLUMBING THIRD FLOOR DEMOLITION PLAN

111 P-1.0U PLUMBING BURIED PIPING PLAN

112 P-1.0 PLUMBING BASEMENT FLOOR PLAN

113 P-1.1 PLUMBING FIRST FLOOR PLAN

114 P-1.2 PLUMBING SECOND FLOOR PLAN

115 P-1.3 PLUMBING THIRD FLOOR PLAN

116 P-2.0 PLUMBING BUILDING SECTIONS

117 P-3.0 PLUMBING ISOMETRICS

118 E-0.1 ELECTRICAL LEGEND & GENERAL NOTES

119 E-0.1A ELECTRICAL GENERAL NOTES

120 E-0.2 ELECTRICAL SCHEDULES

121 E-0.2A ELECTRICAL ONE-LINE, SCHEDULES, & DETAIL

122 E-0.3 ELECTRICAL PANEL SCHEDULES

123 E-0.3A ELECTRICAL PANEL SCHEDULES

124 E-0.4 ELECTRICAL DETAILS

DRAWING INDEX- VOLUME 1

SHEET # SUB SHEET NO. SHEET TITLE

1 - COVER

2 G-0.1 SYMBOLS, & ABBREVIATIONS

3 G-0.2 INDEX OF DRAWINGS

4 G-0.3 ASBESTOS ABATEMENT DRAWING (FIRST FLOOR PLAN)

5 G-0.4 ASBESTOS ABATEMENT DRAWING (FIRST FLOOR PLAN)

6 G-0.5 ASBESTOS ABATEMENT DRAWING (SECOND FLOOR PLAN)

7 G-0.6 ASBESTOS ABATEMENT DRAWING (THIRD FLOOR PLAN)

8 G-0.7 ACCESSIBILITY

9 G-0.8 ACCESSIBILITY

10 G-0.9 EGRESS AND OCCUPANCY

11 G-0.10 CODE OUTLINE

12 G-0.11 CODE OUTLINE

13 G-0.12 CODE OUTLINE

14 G-0.13 FIRESTOPPING PENETRATION DETAILS

15 G-0.14 FIRESTOPPING PENETRATION DETAILS

16 G-1.0 NOTES

17 V-1.0 TOPOGRAPHIC SURVEY PLAN

18 C-1.0 DEMOLITION PLAN

19 C-2.0 SOIL EROSION & SEDIMENT CONTROL PLAN

20 C-3.0 SITE PLAN

21 C-4.0 GRADING PLAN

22 C-5.0 UTILITY PLAN

23 C-6.0 EROSION & SEDIMENT CONTROL DETAILS

24 C-7.0 SITE DETAILS

25 C-8.0 SITE DETAILS II

26 C-9.0 UTILITY DETAILS

27 C-10.0 WATER PROFILE

28 C-11.0 DC WATER FORMS

29 D-1.0 BASEMENT DEMOLITION PLAN

30 D-1.1 FIRST FLOOR DEMOLITION PLAN

31 D-1.2 SECOND FLOOR DEMOLITION PLAN

32 D-1.3 THIRD FLOOR DEMOLITION PLAN

33 D-1.4 ROOF DEMOLITION PLAN

34 A-1.0 BASEMENT FLOOR PLAN

35 A-1.1 FIRST FLOOR PLAN

36 A-1.2 SECOND FLOOR PLAN

37 A-1.3 THIRD FLOOR PLAN

38 A-1.4 ROOF PLAN

39 A-1.5 PARTITION TYPES

40 A-2.0 BASEMENT REFLECTED CEILING PLAN

41 A-2.1 FIRST FLOOR REFLECTED CEILING PLAN

42 A-2.2 SECOND FLOOR REFLECTED CEILING PLAN

43 A-2.3 THIRD FLOOR REFLECTED CEILING PLAN

44 A-2.4 ENLARGED CEILING PLAN

45 A-2.5 CEILING DETAIL

46 A-2.6 CEILING DETAIL

47 A-3.0 EAST ELEVATION

48 A-3.1 WEST ELEVATION

49 A-4.0 BUILDING SECTIONS

50 A-4.1 BATHROOM PLANS

51 A-4.2 BATHROOM ELEVATIONS

52 A-4.3 BATHROOM ELEVATIONS & DRINKING FOUNTAIN

53 A-4.4 BATHROOM DETAILS

54 A-4.5 STAIR PLANS & DETAILS

55 A-4.6 STAIR SECTIONS & DETAILS

56 A-4.7 RAMP PLANS AND DETAILS

57 A-4.8 BASEMENT STAIR DETAILS

58 A-4.9 MEETING ROOM STAIR DETAILS

59 A-4.10 FENCE DETAILS

60 A-5.0 PLAN DETAILS

61 A-5.1 SECTION DETAILS

62 A-5.2 ROOF DETAILS

UP

Material Location Survey Results Estimated Quantity of ACM Notes/Comments

1542 9th Street NW Building

ACM

Gypsum board

1st floor - Former Kitchen Ceiling and Small Portion of Wall on 2nd Floor near Bathroom

ACM Contaminated

300SF

Gypsum board joint compound ACM

12"x12" Green floor tile Scattered on 1st, 2nd and 3rd Floors ACM 625SF

Red floor materials Scattered on 1st, 2nd and 3rd Floors ACM 500SF of ACM Notes/Comments

1542 9th Street NW Building

ACM

Gypsum board

1st floor - Former Kitchen Ceiling and Small Portion of Wall on 2nd Floor near Bathroom

ACM Contaminated

300SF

Gypsum board joint compound ACM

DN

of ACM Notes/Comments

1542 9th Street NW Building

ACM

Gypsum board

1st floor - Former Kitchen Ceiling and Small Portion of Wall on 2nd Floor near Bathroom

ACM Contaminated

300SF

Gypsum board joint compound ACM of ACM Notes/Comments

1542 9th Street NW Building

ACM

Sink undercoating 3rd Floor - Kitchen ACM 3SF

Beige linoleum floor covering 3rd Floor - Bathroom ACM 25SF

12"x12" Green floor tile Scattered on 1st, 2nd and 3rd Floors ACM 625SF

Red floor materials Scattered on 1st, 2nd and 3rd Floors ACM 500SF

1540 9th Street NW Building

ACM

Mastic associated with 9"x9" wooden floor tiles 3rd Floor ACM 500SF

Gypsum board

3rd Floor NE Section

ACM Contaminated

600SF

Gypsum board joint compound ACM

ELEV

MEETING ROOM

EXISTING MECH

ELECTRIC ROOM

WOMENS RM

CLASSROOM

MENS RM

MECHANICAL

MECH

MECH

STAIR 1

ST1-0

T

E

T

ELEV

(ALTERNATE ENTRY

IF LIFT OUT OF ORDER)

EXHIBIT

EXHIBIT

EXHIBIT

STAIR 1

ST1-1

EXHIBIT

ENTRY EXHIBIT /

BOOK STORE

TOILET RM

STORAGE

122 ENTRY

MECH

RAMP FROM

REAR YARD

RAMP

MAIN

ENTRY

ACCESSIBLE

DROP-OFF POINT

N.I.C.

PLATFORM

LIFT

R

T

E

L W

NEW INTERCOM TO

RANGER STATION

FOR ACCESS

ACCESSIBILITY LEGEND

ACCESSIBLE ROUTE, 36" MIN, W/ 32" AT DOOR

ACCESSIBLE ENTRANCE W/ AUTOMATIC OPENER

ACCESSIBLE WORK AREA

ACCESSIBLE INTERPRETIVE OR EDUCATION ROOM

DOOR REMOVED & JAMB MODIFIED TO

PROVIDE FULL ACCESSIBLE CLEARANCE

5'-0" TURNING RADIUS

SIGNAGE - ELEVATORE

SIGNAGE - ADA TOILET ROOMT

SIGNAGE - ADA LIFT ENTRYL

SIGNAGE - ADA RAMP ENTRYR

SIGNAGE - WAY FINDINGW

NON-ACCESSIBLE PUBLIC SPACE

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.7

ACCESSIBILITY

NACE 242190

SCALE AG-0.7

1 ACCESSIBILITY PLAN - BASEMENT

SCALE AG-0.7

2 ACCESSIBILITY PLAN - FIRST FLOOR

SCALE A

0 8 168

SCALE OF FEET

UPUP

UP

ELEV

STAFF

STAFF

STAFF

EXHIBIT

EXHIBIT

ASALH OFFICE

STAIR 1

ST1-2

ASALH OFFICE

ASALH OFFICE

KITCHEN / MEETING

RM

TOILET RM

MOP CLOSET

NURSING STATION

CORRIDOR

MECH

T

E

ELEV

EXHIBIT

EXHIBIT

AV CLOSET /

STORAGE

EXHIBIT

STAIR 1

ST1-3

NPS OFFICE

TOILET RM

STORAGE

MECH.

T

E

ACCESSIBILITY LEGEND

ACCESSIBLE ROUTE, 36" MIN, W/ 32" AT DOOR

ACCESSIBLE ENTRANCE W/ AUTOMATIC OPENER

ACCESSIBLE WORK AREA

ACCESSIBLE INTERPRETIVE OR EDUCATION ROOM

DOOR REMOVED & JAMB MODIFIED TO

PROVIDE FULL ACCESSIBLE CLEARANCE

5'-0" TURNING RADIUS

SIGNAGE - ELEVATORE

SIGNAGE - ADA TOILET ROOMT

SIGNAGE - ADA LIFT ENTRYL

SIGNAGE - ADA RAMP ENTRYR

SIGNAGE - WAY FINDINGW

NON-ACCESSIBLE PUBLIC SPACE

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.8

ACCESSIBILITY

NACE 242190

SCALE AG-0.8

1 ACCESSIBILITY PLAN - SECOND FLOOR

SCALE AG-0.8

2 ACCESSIBILITY PLAN - THIRD FLOOR

SCALE A

0 8 168

CODE LEGEND

1 HOUR FIRE RESISTANT WALL #

2 HOUR FIRE RESISTANT WALL

DIAGONAL DISTANCE

OCCUPANCY TAG : USE/OCCUPANCY AREA (SF)

# OF OCCUPANTS

### SF

USE

EGRESS POINT

ROOM WITH COMMUNICATION FEATURES

(INTERNATIONAL SYMBOL OF ACCESS FOR

HEARING LOSS)

(CALCULATED) ACTUAL

OCCUPANCY MAY VARY,

SEE A - 0.2 A

PATH OF EGRESS

REMOTE SEPARATION OF EXIT

MAXIMUM EXIT ACCESS TRAVEL DISTANCE

EXISTING MASONRY WALLS MEET

FIRE RESISTANCE WITHOUT NEED

FOR ALTERATION

SEE SHEET G-0.2 FOR ACCESSIBILITY DRAWINGS

EXISTING STAIR & OPENINGS

OCCUPANCY BY FLOOR

BASEMENT

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

175BUILDING TOTAL

OCCUPANCY LOAD

COMPONENT CAPACITY

CALCULATED EGRESS

(ACTUAL LOAD MAY VARY)

S

D

OCCUPANCY LOAD

COMPONENT CAPACITY

CALCULATED EGRESS

(ACTUAL LOAD MAY VARY)

STAIR

EGRESS TAG:

DOOR

EGRESS TAG:

ELEV

383 SF

A:U

200 SF

S/M

70 SF

S/M

165 SF

S/M

194 SF

S/M

19 SF

S/M

LENGTH OF TRAVEL =

63' - 5"

S D

DS

375 SF

A:U

ELEV

23 SF

S/M

491 SF

A:E

141 SF

A:E

168 SF

A:E

205 SF

A:E

10 SF

S/M

160*

135*

155*

145*

LENGTH OF TRAVEL =

46' - 4"

A:E

357 SF

LENGTH OF TRAVEL = 70' - 8"

SECOND FLOOR

& BASEMENT

CONVERGENCE

EXISTING DOORS

EXIT STAIR

EXISTING LANDING

AND STAIRS

D

S

D D

S

D

S

D

DD

A:E

290 SF

ELEV

256 SF

A:E

275 SF

B

154 SF

B

30 SF

S/M

223 SF

A:U

147 SF

A:E

131 SF

B

117 SF

B

45 SF

B

14 SF

S/M

23 SF

S/M

85 SF

B

38 SF

B

93*

LENGTH OF TRAVEL =

58' - 5"

135*

135*

DIAGONAL LENGTH =

82' - 6 1/2"

EXISTING WINDER STAIR

RESTRICTED

OCCUPANCY PUBLIC

VIEW INTO ROOM ONLY

EXIT STAIR

D

S

D

S

D

HISTORIC STAIR

203 SF

B

ELEV

132 SF

A:E

159 SF

A:E

66 SF

S/M

480 SF

A:E

14 SF

S/M

29 SF

S/M

358 SF

B

140*

140*

103*

LENGTH OF TRAVEL =

50' - 8"

EXISTING STRAIGHT

RUN STAIR

RESTRICTED

OCCUPANCY PUBLIC

VIEW INTO ROOM ONLY

D

S

S

D

D

D

HISTORIC STAIR

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.9

EGRESS AND OCCUPANCY

NACE 242190

SCALE AG-0.9

1 EGRESS PLAN - BASEMENT

SCALE AG-0.9

2 EGRESS PLAN - FIRST FLOOR

SCALE AG-0.9

3 EGRESS PLAN - SECOND FLOOR

SCALE AG-0.9

4 EGRESS PLAN - THIRD FLOOR

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.10

CODE OUTLINE

NACE 242190

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.11

CODE OUTLINE

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.12

CODE OUTLINE

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.13

FIRESTOPPING PENETRATION

DETAILS

NACE 242190

System No. W-J-5044 F Rating – 2 Hr.

T rating – 1 ½ hr

1. Wall assembly – Min 6 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 9-1/2 in.

• See Concrete Block (CAZT) category in the Fire Resistance Directory for name of manufacturers.

2. Through Penetrant – one metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:

A. Steel Pipe – Nom 4 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe – Nom 4 in diam (or smaller) cast or ductile iron pipe.

C. Copper Tubing – Nom 4 in diam (or smaller) type L (or heavier) copper tubing.

D. Copper Pipe - Nom 4 in diam (or smaller) Regular (or heavier) copper pipe.

3. Pipe Coverings – One of the following types of pipe coverings shall be used:

A. Pipe and Equipment Covering Materials* – Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated through penetrant and the periphery of the opening shall be a min of 0 in. (point contact) to a max 1-3/8 in.

• See Pipe and Equipment Covering Materials (BRGU) category in the

Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.

B. Pipe Covering Materials* – Nom 2 in. thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (or heavier) and sized to the outside diam of pipe or tube. Pipe insulation secured with min 8 AWG steel wire spaced max 12

in. OC. The annular space between the insulated through penetrant and the periphery of the opening shall be a min of 0 in. (point contact) to a max 1-3/8in.

• OWENS CORNING HT INC, DIV OF OWENS CORNING – Paroc 1200, Paroc

BWT or Paroc Thermaloc 1200 C. Sheathing Material* – Used in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape.

• See Sheathing Materials (BVDV) category in the Building Materials

Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL classification Marking with Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.

4. Firestop System – the firestop system shall consist of the following:

A. Forms – Used to prevent leakage of fill material during installation. Forms to be rigid sheet or polyurethane backer rod, cut to fit the contour of the insulated penetrating item and friction fitted into opening on both sides of wall. Forms to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material.

B. Fill, Void, or Cavity Materials – Sealant – Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between insulated through penetrant and concrete, a min 3/8 in. diam bead of fill material shall be applied at the concrete/insulated through penetrant interface on both surfaces of wall.

• W R GRACE & CO –CONN CONSTRUCTION PRODUCTS DIV – FS1900.

FS1901, FS1905, AND FS1929 Sealant

System No. C-AJ-7008 F Rating — 1-1/2 Hr T Rating — 1/2 Hr

1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening is 364 sq in. with max dimensions of 26 in.

• See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Steel Duct — Nom 24 by 12 in. (or smaller) No. 24 gauge (or heavier) steel duct. One duct to be installed within the firestop system with a nom 1 in.

annular space. Steel duct to be rigidly supported on both sides of floor or wall assembly.

3. Firestop System — The firestop system shall consist of the following:

A. Packing Material — Min 2 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor and from both surfaces of wall as required to accommodate the required thickness of fill material.

B. Fill, Void or Cavity Material* — Sealant — Min 1 in. thickness of fill material applied within the annulus, flush with top surface of floor and both surfaces of wall.

• RECTORSEAL — FS 1900 Sealant

C. Steel Angle — Min 2 in. wide by 3 in. high by 0.108 in. thick steel angle cut to fit the contour of the duct with a 1 in. lap on the top surface of floor or both surfaces of wall. Horizontal leg of angle secured to top surface of floor or both surfaces of wall by means 1/4 in. diam by

1-3/4 in. long steel concrete fasteners spaced a max 6 in. OC. Vertical leg of angle secured to duct with min two No. 8 by 3/4 in. sheet metal screws per side, spaced a max 6 in. OC.

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

G-0.14

FIRESTOPPING PENETRATION

DETAILS

NACE 242190

System No. C-AJ-5116 F Rating — 2 Hr T Rating — 3/4 Hr

1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced normal weight (140-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 18 in.

• See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Metallic Sleeve — Optional — Nom 18 in. diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces.

3. Through Penetrants — One metallic pipe to be installed either concentrically or eccentrically within the firestop system. Pipe to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes may be used:

A. Steel Pipe — Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe — Nom 12 in. diam (or smaller) cast or ductile iron pipe.

4. Pipe Coverings — One of the following types of pipe coverings shall be used:

A. Pipe and Equipment Covering Materials* — Nom 1 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space within the firestop system shall be min 0 in. (point contact) to a max 2-3/4 in.

• See Pipe and Equipment Covering—Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used .

B. Pipe Covering Materials* — Nom 1 in. thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (or heavier) and sized to the outside diam of pipe or tube. Pipe insulation secured with min 8 AWG steel wire spaced max 12 in. OC. The annular space within the firestop system shall be min 0 in. (point contact) to a max 2-3/4 in.

• IIG MINWOOL L L C — High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High Temperature Pipe Insulation Thermaloc.

C. Sheathing Material* — Used in conjunction with Item 4B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 4B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape.

• See Sheathing Materials (BVDV) category in the Building Materials

Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.

5. Firestop System — The firestop system shall consist of the following:

A. Packing Material — Min 2 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. At the point contact location between through penetrant and concrete, packing material forced into interstices of through penetrant and concrete to max extent possible.

B. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. At the point contact location between through penetrant and concrete, fill material forced into interstices of through penetrant and concrete to max extent possible. Additional fill material to be installed such that a min 1/4

in. crown is formed around the through penetrants.

• RECTORSEAL — FS1900, FS1901, FS1905 and FS1929 Sealant

System No. C-AJ-1088 F Rating — 2 Hr T Rating — 0 Hr

1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced lightweight or normal weight concrete (100-150 pcf) floor or wall. Wall may also be constructed of any UL Classified Concrete Blocks*.

Max diam of opening is 15 in.

• See Concrete Block (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Through Penetrants — A max of four pipes, conduits or tubing to be installed within the opening. Of the four through-penetrants, only two of through-penetrants may have a nom diam greater than 2 in. The annular space between through-penetrants and between through-penetrants and periphery of opening shall be min 2 in. to max 3 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Nom 4 in. diam (or smaller) rigid galv steel conduit.

B. Nom 4 in. diam (or smaller) steel electrical metallic tubing.

C. Nom 4 in. diam (or smaller) trade size Type L (or heavier) copper tubing.

D. Nom 4 in. diam (or smaller) Schedule 5 (or heavier) steel pipe.

3. Firestop System — The firestop system shall consist of the following:

A. Wire Hangers — Three No. 9 AWG steel wires bent into a U-shaped hanger and placed in through-opening to support forming material.

B. Forming Material — Min 2 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material.

C. Fill, Void or Cavity Material* — Sealant — Min 1 in. thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. If cracking occurs after fill material cures, cracks shall be sealed with additional sealant.

• RECTORSEAL — Types FS900, FS901, FS903, FS903CG, FS905, FS905CG,FS929, FST901, FST903 and FST905

7/14/2020

UP

ADJACENT PROPERTY

ADJACENT PROPERTY

DEMO COLUMN

DEMO TOP OF WALL

TO ALLOW FOR NEW

LOBBY STAIRS

ETR SUMP PUMP

ETR SEDIMENT

INTERCEPTOR

ETR SEWAGE

EJECTOR

ETR WATER

HEATER

ELEVATOR PIT &

SUMP PUMP PIT

FLOOR DEMO

FOR SEWAGE &

STORM PIPING

ETR ELECTRIC

PANELS

ETR 3/4"

PLYWOOD

ETR SEWER

STORM

UNINHABITED

E-010

ELECTRICAL

E-022

UNINHABITED

E-020

UTILITY

E-021

MECHANICAL

E-011

UNINHABITED

E-012

MECHANICAL

E-004

UNINHABITED

E-001

DEMO STAIR TREADS, RISERS,

RAILING, AND LANDING

ETR STAIR,

RAILING &

LANDING

ETR COLUMNS

(TYP), U.O.N

ETR

LANDING

ETR CONC SHELF ETR CONC

SHELF

PARTIAL DEMOLITION OF WALL, SEE

DEMOLITION NOTES

DEMOLITION FLOOR PLAN LEGEND

EXISTING DOOR TO REMAIN

EXISTING WALL TO REMAIN

EXISTING WALL TO BE REMOVED

EXISTING DOOR TO BE REMOVED

GENERAL AREA OF DEMOLITION, SEE

DEMOLITION NOTES FOR MORE

INFORMATION

1. CONTRACTOR TO VERIFY ALL CONDITIONS IN FIELD PRIOR TO DEMOLITION AND TO

CORRDINATE ALL DEMOLITION ACTIVITIED WITH INTENDED CONSTRUCTION. REPORT

ALL DISCREPANCIES TO THE CONTRACTING OFFICER FOR RESOLUTION.

2. PROTECT ALL CONSTRUCTION TO REMAIN FROM DAMAGE DURING DEMOLITION OF

ADJACENT CONSTRUCTION. REPAIR/REPLACE CONSTRUCTION TO REMAIN

DAMAGED DURING DEMOLITION TO MATCH THE QUALITY OF THE NEW WORK.

3. WHERE WALLS, COUNTERS, DOORS, ETC ARE SHOWN TO BE REMOVED, ALL WIRING IN

DEMOLISHED AREAS SHALL BE REMOVED BACK TO PANEL EXCEPT WIRING THAT IS

NECESSARY TO FACILITATE NEW CONSTRUCTION. ALL PIPING BRANCHES, SOIL

LINES, ETC TO BE REMOVED BACK TO THE NEXT LARGEST SERVICE LINE EXCEPT

WHERE TO BE ALTERED TO FACILITATE NEW CONSTRUCTION.

4. REVIEW RELOCATION OF EXISTING ELECTRICAL SWITCHES, OUTLETS, FIXTURES (IF

ANY) WITH CO PRIOR TO DEMOLITION.

5. SALVAGE EXISTING STAIR NEWEL POST, BALUSTERS, AND RAILING (REFER TO

DEMOLITION KEYNOTE #2 FOR LOCATION). STORE IN A SAFE, SECURE AND DRY

LOCATION THAT DOES NOT INTERFERE WITH OCCUPANT EGRESS & ACTIVITIES OF

SPACE REQUIREMENTS. TO BE RETURNED TO THE NPS FOR USE IN THE LEGACY

PRESERVATION EXHIBIT OR FUTURE REPAIR OF THE STAIR IN BUILDING 1538.

6. CONTRACTOR TO DISPOSE OF DEMOLISHED MATERIALS OFF-SITE IN ACCORDANCE

WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL REQUIREMENTS.

7. CONTRACTOR TO MAINTAIN STRUCTURAL INTEGRITY OF FLOOR. WHERE EXISTING

SUB-FLOOR OF 7/8" T&G BOARDS ARE MISSING OR DAMAGED, NEW 3/4" PLYWOOD

w/ SHIMMING TO BE INSTALLED LEVEL w/ SURROUNDING EXISTING SUB-FLOOR.

8. REMOVE ALL EXISTING FLOOR FINISHES & UNDERLAYMENT DOWN TO LEVEL SUB-

FLOOR OR 7/8" T&G BOARDS OR PLYWOOD. REFER TO ABATEMENT DRAWINGS FOR

MATERIALS THAT REQUIRE SPECIAL REMOVAL ATTENTION.

9. COORDINATE THE EXTENT OF REMOVAL w/ INTENDED NEW WORK.

DEMOLITION GENERAL NOTES

DEMOLITION NOTES

REMOVE PLYWOOD INFILL

PANELS AND

ASSOCIATED BLOCKING

2 SALVAGE WOOD STAIR

COMPONENTS

REMOVE DOOR & MODIFY JAMB TO

ALLOW FULL ACCESSIBLE

CLEARANCE. SALVAGE DOOR AND

ANY REMOVED DOOR COMPONENTS

4 REMOVE BRICK TO

EXPOSED EXISTING CMU

5 ETR RADIATOR

6 ETR STOOP STAIRS, RAILINGS,

AND BALUSTERS

7 ETR DISPLAY STRUCTURE

8 DEMO AREA OF EXISTING

FLOOR FOR NEW DUCT CHASE

DEMO EXISTING

PLUMBING FIXTURES AND

TOILET ACCESSORIES

10 REFER TO DOOR DETAIL J6

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:2

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

D-1.0

BASEMENT DEMOLITION PLAN

NACE 242190

SCALE AD-1.0

1 DEMO PLAN - BASEMENT

SCALE A

0 4 84

ADJACENT PROPERTY

ADJACENT PROPERTY

1 1

ADJUST PATH OF EXISTING

DOWNSPOUT (REF: 2/ A-4.6)

DEMO AREA OF

EXISTING RAISED

FLOOR LEVEL

TEMPORARY

INFORMATION &

ORIENTATION

E-100

RESTROOM

E-111UNINHABITED

E-112

UNINHABITED

E-124

ENTRY

E-120

INTERPRETIVE

BOOK STORAGE

E-110

INTERPRETIVE

ORDER & SHIPPING

E-110

CLOSET

E-108

CLOSET

E-103A

CORRIDOR

E-103

INTERPRETIVE

CLERICAL SPACE

E-105

INTERPRETIVE

RECEPTION AREA

E-104

CORRIDOR

E-102

ENTRY

E-101

DEMO STAIR

TREADS, RISERS,

RAILING, AND

LANDING

DEMO EXISTING STEEL

RAMP, RAILINGS, AND

LANDING

DEMO EXISTING STAIRS,

RAILINGS, AND STEEL LANDING

5 5

ETR FIREPLACE

ETR STAIRCASE

AND RAILINGS

DEMO EXISTING AREA OF

FLOOR FOR NEW

STAIRCASE AND ELEVATOR

UP

UP

DN

UP

DEMO EXISTING MASONRY

WALLS AND PILASTERS

REMOVE ANY

EXISTING SHELVES

OR MILLWORK

WITHIN THIS SPACE

PARTIAL DEMOLITION OF WALL, SEE

DEMOLITION NOTES

DEMOLITION FLOOR PLAN LEGEND

EXISTING DOOR TO REMAIN

EXISTING WALL TO REMAIN

EXISTING WALL TO BE REMOVED

EXISTING DOOR TO BE REMOVED

GENERAL AREA OF DEMOLITION, SEE

DEMOLITION NOTES FOR MORE

INFORMATION

1. CONTRACTOR TO VERIFY ALL CONDITIONS IN FIELD PRIOR TO DEMOLITION AND TO

CORRDINATE ALL DEMOLITION ACTIVITIED WITH INTENDED CONSTRUCTION. REPORT

ALL DISCREPANCIES TO THE CONTRACTING OFFICER FOR RESOLUTION.

2. PROTECT ALL CONSTRUCTION TO REMAIN FROM DAMAGE DURING DEMOLITION OF

ADJACENT CONSTRUCTION. REPAIR/REPLACE CONSTRUCTION TO REMAIN

DAMAGED DURING DEMOLITION TO MATCH THE QUALITY OF THE NEW WORK.

3. WHERE WALLS, COUNTERS, DOORS, ETC ARE SHOWN TO BE REMOVED, ALL WIRING IN

DEMOLISHED AREAS SHALL BE REMOVED BACK TO PANEL EXCEPT WIRING THAT IS

NECESSARY TO FACILITATE NEW CONSTRUCTION. ALL PIPING BRANCHES, SOIL

LINES, ETC TO BE REMOVED BACK TO THE NEXT LARGEST SERVICE LINE EXCEPT

WHERE TO BE ALTERED TO FACILITATE NEW CONSTRUCTION.

4. REVIEW RELOCATION OF EXISTING ELECTRICAL SWITCHES, OUTLETS, FIXTURES (IF

ANY) WITH CO PRIOR TO DEMOLITION.

5. SALVAGE EXISTING STAIR NEWEL POST, BALUSTERS, AND RAILING (REFER TO

DEMOLITION KEYNOTE #2 FOR LOCATION). STORE IN A SAFE, SECURE AND DRY

LOCATION THAT DOES NOT INTERFERE WITH OCCUPANT EGRESS & ACTIVITIES OF

SPACE REQUIREMENTS. TO BE RETURNED TO THE NPS FOR USE IN THE LEGACY

PRESERVATION EXHIBIT OR FUTURE REPAIR OF THE STAIR IN BUILDING 1538.

6. CONTRACTOR TO DISPOSE OF DEMOLISHED MATERIALS OFF-SITE IN ACCORDANCE

WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL REQUIREMENTS.

7. CONTRACTOR TO MAINTAIN STRUCTURAL INTEGRITY OF FLOOR. WHERE EXISTING

SUB-FLOOR OF 7/8" T&G BOARDS ARE MISSING OR DAMAGED, NEW 3/4" PLYWOOD

w/ SHIMMING TO BE INSTALLED LEVEL w/ SURROUNDING EXISTING SUB-FLOOR.

8. REMOVE ALL EXISTING FLOOR FINISHES & UNDERLAYMENT DOWN TO LEVEL SUB-

FLOOR OR 7/8" T&G BOARDS OR PLYWOOD. REFER TO ABATEMENT DRAWINGS FOR

MATERIALS THAT REQUIRE SPECIAL REMOVAL ATTENTION.

9. COORDINATE THE EXTENT OF REMOVAL w/ INTENDED NEW WORK.

DEMOLITION GENERAL NOTES

DEMOLITION NOTES

REMOVE PLYWOOD INFILL

PANELS AND

ASSOCIATED BLOCKING

2 SALVAGE WOOD STAIR

COMPONENTS

REMOVE DOOR & MODIFY JAMB TO

ALLOW FULL ACCESSIBLE

CLEARANCE. SALVAGE DOOR AND

ANY REMOVED DOOR COMPONENTS

4 REMOVE BRICK TO

EXPOSED EXISTING CMU

5 ETR RADIATOR

6 ETR STOOP STAIRS, RAILINGS,

AND BALUSTERS

7 ETR DISPLAY STRUCTURE

8 DEMO AREA OF EXISTING

FLOOR FOR NEW DUCT CHASE

DEMO EXISTING

PLUMBING FIXTURES AND

TOILET ACCESSORIES

10 REFER TO DOOR DETAIL J6

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

D-1.1

FIRST FLOOR DEMOLITION

PLAN

NACE 242190

SCALE AD-1.1

1 DEMO PLAN - FIRST FLOOR

SCALE A

ADJACENT PROPERTY

ADJACENT PROPERTY

1 1

UNINHABITED

E-224

UNINHABITED

E-211UNINHABITED

E-212

INTERPRETIVE

STORAGE

E-210

CLOSET

E-209

INTERPRETIVE

KITCHEN

E-211

INTERPRETIVE

BATHROOM

E-207

CORRIDOR

E-201

CORRIDOR

E-202

INTERPRETIVE

LIBRARY

E-205

INTERPRETIVE

OFFICE

E-203

CLOSET

E-206

CLOSET

E-204

DEMO EXISTING

STAIR TREADS,

RISERS, & RAILINGS

ETR STAIRCASE

& RAILINGS

DEMO AREA OF

EXISTING FLOOR FOR

NEW ELEVATOR &

STAIT LANDING

DEMO EXISTING MASONRY WALLS

REMOVE ANY MILLWORK

OR SHELVING WITHIN

THIS SPACE

PARTIAL DEMOLITION OF WALL, SEE

DEMOLITION NOTES

DEMOLITION FLOOR PLAN LEGEND

EXISTING DOOR TO REMAIN

EXISTING WALL TO REMAIN

EXISTING WALL TO BE REMOVED

EXISTING DOOR TO BE REMOVED

GENERAL AREA OF DEMOLITION, SEE

DEMOLITION NOTES FOR MORE

INFORMATION

1. CONTRACTOR TO VERIFY ALL CONDITIONS IN FIELD PRIOR TO DEMOLITION AND TO

CORRDINATE ALL DEMOLITION ACTIVITIED WITH INTENDED CONSTRUCTION. REPORT

ALL DISCREPANCIES TO THE CONTRACTING OFFICER FOR RESOLUTION.

2. PROTECT ALL CONSTRUCTION TO REMAIN FROM DAMAGE DURING DEMOLITION OF

ADJACENT CONSTRUCTION. REPAIR/REPLACE CONSTRUCTION TO REMAIN

DAMAGED DURING DEMOLITION TO MATCH THE QUALITY OF THE NEW WORK.

3. WHERE WALLS, COUNTERS, DOORS, ETC ARE SHOWN TO BE REMOVED, ALL WIRING IN

DEMOLISHED AREAS SHALL BE REMOVED BACK TO PANEL EXCEPT WIRING THAT IS

NECESSARY TO FACILITATE NEW CONSTRUCTION. ALL PIPING BRANCHES, SOIL

LINES, ETC TO BE REMOVED BACK TO THE NEXT LARGEST SERVICE LINE EXCEPT

WHERE TO BE ALTERED TO FACILITATE NEW CONSTRUCTION.

4. REVIEW RELOCATION OF EXISTING ELECTRICAL SWITCHES, OUTLETS, FIXTURES (IF

ANY) WITH CO PRIOR TO DEMOLITION.

5. SALVAGE EXISTING STAIR NEWEL POST, BALUSTERS, AND RAILING (REFER TO

DEMOLITION KEYNOTE #2 FOR LOCATION). STORE IN A SAFE, SECURE AND DRY

LOCATION THAT DOES NOT INTERFERE WITH OCCUPANT EGRESS & ACTIVITIES OF

SPACE REQUIREMENTS. TO BE RETURNED TO THE NPS FOR USE IN THE LEGACY

PRESERVATION EXHIBIT OR FUTURE REPAIR OF THE STAIR IN BUILDING 1538.

6. CONTRACTOR TO DISPOSE OF DEMOLISHED MATERIALS OFF-SITE IN ACCORDANCE

WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL REQUIREMENTS.

7. CONTRACTOR TO MAINTAIN STRUCTURAL INTEGRITY OF FLOOR. WHERE EXISTING

SUB-FLOOR OF 7/8" T&G BOARDS ARE MISSING OR DAMAGED, NEW 3/4" PLYWOOD

w/ SHIMMING TO BE INSTALLED LEVEL w/ SURROUNDING EXISTING SUB-FLOOR.

8. REMOVE ALL EXISTING FLOOR FINISHES & UNDERLAYMENT DOWN TO LEVEL SUB-

FLOOR OR 7/8" T&G BOARDS OR PLYWOOD. REFER TO ABATEMENT DRAWINGS FOR

MATERIALS THAT REQUIRE SPECIAL REMOVAL ATTENTION.

9. COORDINATE THE EXTENT OF REMOVAL w/ INTENDED NEW WORK.

DEMOLITION GENERAL NOTES

DEMOLITION NOTES

REMOVE PLYWOOD INFILL

PANELS AND

ASSOCIATED BLOCKING

2 SALVAGE WOOD STAIR

COMPONENTS

REMOVE DOOR & MODIFY JAMB TO

ALLOW FULL ACCESSIBLE

CLEARANCE. SALVAGE DOOR AND

ANY REMOVED DOOR COMPONENTS

4 REMOVE BRICK TO

EXPOSED EXISTING CMU

5 ETR RADIATOR

6 ETR STOOP STAIRS, RAILINGS,

AND BALUSTERS

7 ETR DISPLAY STRUCTURE

8 DEMO AREA OF EXISTING

FLOOR FOR NEW DUCT CHASE

DEMO EXISTING

PLUMBING FIXTURES AND

TOILET ACCESSORIES

10 REFER TO DOOR DETAIL J6

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

D-1.2

SECOND FLOOR DEMOLITION

PLAN

NACE 242190

SCALE AD-1.2

1 DEMO PLAN - SECOND FLOOR

SCALE A

ADJACENT PROPERTY

ADJACENT PROPERTY

INTERPRETIVE

BEDROOM

E-305

INTERPRETIVE

LIVING ROOM

E-303

CLOSET

E-306

CLOSET

E-304

CORRIDOR

E-301

INTERPRETIVE

BOOK STORAGE

E-302

REFER TO 1/ D-1.4

FOR ROOF DEMOLITION

INFORMATION

REFER TO 1/ D-1.4

FOR ROOF DEMOLITION

INFORMATION

ETR CHIMNEY

DEMO AREA OF

EXISTING FLOOR FOR

NEW ELEVATOR &

STAIR LANDING

DEMO EXISTING STAIR

TREADS, RISERS,

LANDING, & RAILINGS

ETR STAIRCASE

& RAILINGS

5 5

DEMO EXISTING MASONRY WALLS

PARTIAL DEMOLITION OF WALL, SEE

DEMOLITION NOTES

DEMOLITION FLOOR PLAN LEGEND

EXISTING DOOR TO REMAIN

EXISTING WALL TO REMAIN

EXISTING WALL TO BE REMOVED

EXISTING DOOR TO BE REMOVED

GENERAL AREA OF DEMOLITION, SEE

DEMOLITION NOTES FOR MORE

INFORMATION

1. CONTRACTOR TO VERIFY ALL CONDITIONS IN FIELD PRIOR TO DEMOLITION AND TO

CORRDINATE ALL DEMOLITION ACTIVITIED WITH INTENDED CONSTRUCTION. REPORT

ALL DISCREPANCIES TO THE CONTRACTING OFFICER FOR RESOLUTION.

2. PROTECT ALL CONSTRUCTION TO REMAIN FROM DAMAGE DURING DEMOLITION OF

ADJACENT CONSTRUCTION. REPAIR/REPLACE CONSTRUCTION TO REMAIN

DAMAGED DURING DEMOLITION TO MATCH THE QUALITY OF THE NEW WORK.

3. WHERE WALLS, COUNTERS, DOORS, ETC ARE SHOWN TO BE REMOVED, ALL WIRING IN

DEMOLISHED AREAS SHALL BE REMOVED BACK TO PANEL EXCEPT WIRING THAT IS

NECESSARY TO FACILITATE NEW CONSTRUCTION. ALL PIPING BRANCHES, SOIL

LINES, ETC TO BE REMOVED BACK TO THE NEXT LARGEST SERVICE LINE EXCEPT

WHERE TO BE ALTERED TO FACILITATE NEW CONSTRUCTION.

4. REVIEW RELOCATION OF EXISTING ELECTRICAL SWITCHES, OUTLETS, FIXTURES (IF

ANY) WITH CO PRIOR TO DEMOLITION.

5. SALVAGE EXISTING STAIR NEWEL POST, BALUSTERS, AND RAILING (REFER TO

DEMOLITION KEYNOTE #2 FOR LOCATION). STORE IN A SAFE, SECURE AND DRY

LOCATION THAT DOES NOT INTERFERE WITH OCCUPANT EGRESS & ACTIVITIES OF

SPACE REQUIREMENTS. TO BE RETURNED TO THE NPS FOR USE IN THE LEGACY

PRESERVATION EXHIBIT OR FUTURE REPAIR OF THE STAIR IN BUILDING 1538.

6. CONTRACTOR TO DISPOSE OF DEMOLISHED MATERIALS OFF-SITE IN ACCORDANCE

WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL REQUIREMENTS.

7. CONTRACTOR TO MAINTAIN STRUCTURAL INTEGRITY OF FLOOR. WHERE EXISTING

SUB-FLOOR OF 7/8" T&G BOARDS ARE MISSING OR DAMAGED, NEW 3/4" PLYWOOD

w/ SHIMMING TO BE INSTALLED LEVEL w/ SURROUNDING EXISTING SUB-FLOOR.

8. REMOVE ALL EXISTING FLOOR FINISHES & UNDERLAYMENT DOWN TO LEVEL SUB-

FLOOR OR 7/8" T&G BOARDS OR PLYWOOD. REFER TO ABATEMENT DRAWINGS FOR

MATERIALS THAT REQUIRE SPECIAL REMOVAL ATTENTION.

9. COORDINATE THE EXTENT OF REMOVAL w/ INTENDED NEW WORK.

DEMOLITION GENERAL NOTES

DEMOLITION NOTES

REMOVE PLYWOOD INFILL

PANELS AND

ASSOCIATED BLOCKING

2 SALVAGE WOOD STAIR

COMPONENTS

REMOVE DOOR & MODIFY JAMB TO

ALLOW FULL ACCESSIBLE

CLEARANCE. SALVAGE DOOR AND

ANY REMOVED DOOR COMPONENTS

4 REMOVE BRICK TO

EXPOSED EXISTING CMU

5 ETR RADIATOR

6 ETR STOOP STAIRS, RAILINGS,

AND BALUSTERS

7 ETR DISPLAY STRUCTURE

8 DEMO AREA OF EXISTING

FLOOR FOR NEW DUCT CHASE

DEMO EXISTING

PLUMBING FIXTURES AND

TOILET ACCESSORIES

10 REFER TO DOOR DETAIL J6

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

D-1.3

THIRD FLOOR DEMOLITION

PLAN

NACE 242190

SCALE AD-1.3

1 DEMO PLAN - THIRD FLOOR

SCALE A

SLOPE DOWN

SLOPE DOWN

SLOPE DOWN

S L O

P E

D O

W N

S L O

P E

D O

W N

S L O

P E

D O

W N

S L O

P E

D O

W N

REMOVE ROOFING SHEATHING &

FRAMING IN PREPARATION FOR NEW

ELEVATOR SHAFT ROOF CONSTRUCTION

REMOVE ROOFING. PREPARE FOR

OVERFRAMING AND ROOFING

REMOVE ROOFING IN PREPARATION

FOR NEW ROOF CONNECTION

REMOVE ROOFING AND

VALLEY. PREPARE FOR

NEW VALLEY LOCATION

REMOVE ROOFING FOR NEW

ROOF HATCH

REMOVE ROOFING FOR NEW PENETRATIONS.

REFER TO PLUMBING DRAWINGS FOR

ADDITIONAL INFORMATION

DEMO HATCHED PORTION

OF EXISTING GUTTER FOR

NEW CONSTRUCTION1

9'-0 3/4"

--- ROOF DEMOLITION PLAN LEGEND

GENERAL AREA OF DEMOLITION, SEE

DEMOLITION NOTES FOR MORE

INFORMATION

1. CONTRACTOR TO VERIFY ALL CONDITIONS IN FIELD PRIOR TO DEMOLITION AND TO

CORRDINATE ALL DEMOLITION ACTIVITIED WITH INTENDED CONSTRUCTION. REPORT

ALL DISCREPANCIES TO ARCHITECT FOR RESOLUTION.

2. PROTECT ALL CONSTRUCTION TO REMAIN FROM DAMAGE DURING DEMOLITION OF

ADJACENT CONSTRUCTION. REPAIR/REPLACE CONSTRUCTION TO REMAIN

DAMAGED DURING DEMOLITION TO MATCH THE QUALITY OF THE NEW WORK.

3. WHERE WALLS, COUNTERS, DOORS, ETC ARE SHOWN TO BE REMOVED, ALL WIRING IN

DEMOLISHED AREAS SHALL BE REMOVED BACK TO PANEL EXCEPT WIRING THAT IS

NECESSARY TO FACILITATE NEW CONSTRUCTION. ALL PIPING BRANCHES, SOIL

LINES, ETC TO BE REMOVED BACK TO THE NEXT LARGEST SERVICE LINE EXCPET

WHERE TO BE ALTERED TO FACILITATE NEW CONSTRUCTION.

4. REVIEW RELOCATION OF EXISTING ELECTRICAL SWITCHES, OUTLETS, FIXTURES (IF

ANY) WITH ARCHITECT PRIOR TO DEMOLITION.

5. SALVAGED ITEMS TO BE REINSTALLED IN CONJUCTION WITH NEW WORK TO BE

STORED IN A SAFE, SECURE, AND DRY LOCATION AND TO NOT INTERFERE WITH

OCCUPANT EGRESS, ACTIVITIES, OR SPACE REQUIREMENTS.

6. CONTRACTOR TO DISPOSE OF DEMOLISHED MATERIALS OFF-SITE IN ACCORDANCE

WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL REQUIREMENTS.

7. EXISTING CHIMNEYS TO REMAIN. CONFIRM THE INSTALLATION OF SECURE CAPS.

8. EXISTING STANDING SEAM ROOF TO REMAIN, UNLESS REQUIRED TO ACCOMODATE

NEW WORK

ROOF DEMOLITION GENERAL NOTES

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:3

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

D-1.4

ROOF DEMOLITION PLAN

NACE 242190

SCALE AD-1.4

1 DEMO PLAN - ROOF

SCALE A

UP

UP

UP

A-4.0

A-4.0

A-4.0

A-4.0

A-4.0

MECH

E 1 E E

ELECTRIC ROOM

E E E E

EXISTING MECH

E E E E

MEETING ROOM

2 1 2 2

CLASSROOM

2 1 2 2

MECH

2 1 2 E

MECHANICAL

E E E E

CORRIDOR

2 1 2 2

CORRIDOR

2 1 2 2

CORRIDOR

2 1 2 2

ELEV.

ADJACENT PROPERTY

ADJACENT PROPERTY

ST1-0

001A

CORRIDOR

2 1 2 2

MENS RM

3 3 3 3

WOMENS RM

3 3 3 3

7a

7a

67 6

6a

EL-0

6'-6 1/2"

6'-2"

MW3

7a

7a

6a

11 11

STAIR 1

ST1-0

2 1 2 2

72' - 0"

A-4.1

A-7.0

A-4.9

A-4.1

A-4.5

74' - 6"

74' - 6"

74' - 6"

74' - 6"

74' - 0"

A-5.0

A-5.0

FD

FD

FD

A-5.1

FOUNTAIN

002A

2 3 2 2

A-6.6

TYP

A-4.8

A-4.3

2' - 0 3/4"

6a

6a

IT & SECURITY

BACKBOARD LOCATION

FE

FE

5'-0"

AV RACK

BY OTHERS

GC TO INSTALL (2) WALL MOUNTED

LOCKABLE CABINETS ABOVE

EXISTING CONCRETE SHELF.

REFER TO LOW VOLTAGE DRAWINGS

FOR ADDITIONAL INFORMATION

ADD BLOCKING IN WALL

FOR DIGITAL MONITOR

MOUNT

ADD BLOCKING IN WALL

FOR DIGITAL MONITOR

MOUNT

PARTITION TYPE

WINDOW TYPE

DOOR TYPE

& TAG

FLOOR PLAN LEGEND

EXISTING

DOOR & TAG

NEW WALL EXISTING WALL TO REMAIN

XXX

1. ALL DIMENSIONS TO FINISHED FACE OF CONSTRUCTION, UNLESS OTHERWISE NOTED.

2. ALL NEW DOORS ARE OFFSET 5" FROM ADJACENT WALL, U.O.N.

3. CONTRACTOR TO VERIFY ALL CONDITIONS AND DIMENSIONS IN THE FIELD. REPORT ALL

DISCREPANCIES IN THESE DRAWINGS AND RELATED SPECIFICATIONS TO THE

CONTRACTING OFFICER FOR RESOLUTION PRIOR TO START OF CONSTRUCTION.

FAILURE TO VERIFY ALL CONDITIONS AFFECTING THE WORK AND FAILURE TO REPORT

DISCREPANCIES WILL NOT RELIEVE THE CONTRACTOR OF COMPLETE COORDINATION

OF ALL ASPECTS OF THE WORK.

4. ALL MATERIAL TO REMAIN IS TO BE PROTECTED DURING CONSTRUCTION.

CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE.

5. REFER TO SPECIFICATIONS AND ALL TRADE DRAWINGS FOR ADDITIONAL INFORMATION.

6. CONTRACTOR IS RESPONSIBLE FOR ALL TEMPORARY SUPPORT AND SHORING.

7. THE CARTER WOODSON HOUSE CONSISTS OF THREE DOMESTIC STRUCTURES THAT

TOGETHER WILL SERVE AS A FULLY FUNCTIONAL MUSEUM. THE MEP/FP, AV, AND

LIGHTING SYSTEMS WHICH ARE REQUIRED FOR SAFETY, FUNCTION, AND COMFORT

WILL COMPETE FOR LIMITED SPACED BEHIND FINISHES WITHIN THE STRUCTURE.

CONTRACTOR IS REQUIRED TO SUBMIT FULL COORDINATION DRAWINGS OF ALL

SYSTEMS TO RESOLVE ANY POTENTIAL CONFLICTS AND ASSURE SMOOTH

INSTALLATION OF THE SYSTEMS.

GENERAL FLOOR PLAN NOTES

1i xx

NEW WOOD

SUBFLOOR INFILL

XXX

EXISTING DOWNSPOUT

VENT TO ROOF

MW# MILLWORK TAG

X'-X" SPOT ELEVATION

FURRED OUT WALL

DRINKING

FOUNTAIN

FLOOR DRAIN (REFER TO

PLUMBING DRAWINGS)

FD

FIRE EXTINGUISHER

(SEMI-RECESSED CABINET)

FEFE

FIRE EXTINGUISHER

(SURFACE MOUNTED,

NO CABINET)

FINISH LEGEND

FLOOR

1 TEXTILE COMPOSITE

2 LVT

3 TILE

4 RUBBER TILE

E EXISTING TO REMAIN

- UNFINISHED

BASE

1 RUBBER

2 STAINED WOOD

3 TILE

E EXISTING TO REMAIN

- NO BASE

WALL

1 PAINT EXISTING

2 PTD GWB

3 TILE

4 RFP WALL PANEL

E EXISTING TO REMAIN

- UNFINISHED

CEILING

1 PAINT EXISTING

2 ACT

3 PTD 1/2" GWB

4 ACOUSTIC PLASTER

E EXISTING TO REMAIN

- UNFINISHED

Room Name

Room#

F B W C

F L O

O R

B A

S E

W A

L L

C E

IL

IN

G

CHANGE IN

MATERIAL

FINISH NOTES

1. FINISH MATERIALS USED IN EXIT ENCLOSURES, EXIT PASSAGEWAYS, AND CORRIDORS

SHALL BE CLASS A. FINISH MATERIALS IN ROOMS AND ENCLOSED SPACES SHALL BE

CLASS C.

2. WHEN TWO OR MORE MATERIALS ARE INDICATED, SEE PLANS OR INTERIOR ELEVATIONS

FOR EXTENT.

3. ALL EXISTING DAMAGE TO EXISTING WALLS SHALL BE PATCHED/REPAIRED PRIOR TO

PAINTING. DAMAGE INCLUDES, BUT IS NOT LIMITED TO, NICKS IN GWB/PLASTER;

REMOVAL OF MISC NAILS, SCREWS, & HANGERS; AND REMOVAL OF MISC ADHESIVES.

4. PATCH ALL REMAINING SURFACES AS REQUIRED TO MATCH ADJACENT

CONSTRUCTION.

5. PAINT ALL SURFACES IN AREAS OF WORK.

6. RFP WALL PANEL INSTALLED TO HEIGHT OF 48" @ WALLS OF MOP CLOSET, ROOM 227

7. FURNITURE BY OTHERS - SHOWN FOR REFERENCE ONLY

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

137898

CARTER G. WOODSON HOUSE

NATIONAL CAPITAL PARKS EAST

FINAL CONSTRUCTION DOCUMENTS

/8

/2

:2

:5

A

M C

U s e rs

\s c o tt s \D o c u m e n ts

\1

C a rt e r

W o o d s o n u p d a te s c o tt s

J W

W F

.r v t

AM/CC

SS/TC

MJM

7/8/2021

A-1.0

BASEMENT FLOOR PLAN

NACE 242190

SCALE A

0 4 84

SCALE OF FEET

SCALE AA-1.0

1 BASEMENT FLOOR PLAN

UP

A-4.0

A-4.0

A-4.0

A-4.0

A-4.0

ENTRY

2 2 2 4

ENTRY EXHIBIT /

BOOK STORE

2 2 2 2

STORAGE

2 1 2 3

TOILET RM

3 3 3 3

EXHIBIT

2 2 2 4

ELEV.

EXHIBIT

E E E E

EXHIBIT

E E E E

EXHIBIT

E E E E

STAIR 1

ST1-1

2 1 2 2

CORRIDOR

2 2 2 2

CLOSET

E E E E

ADJACENT PROPERTY

ADJACENT PROPERTY

ST1-1

ST1-1A

100B

100A

D N

D N

103ADN

100C

110A

105 104

126 125

A-4.8

EL-1

NEW FENCE AROUND CU UNITS.

(REFER SHEET A-4.10 FOR

ADDITIONAL INFORMATION).

REFER TO

SHEET A-4.7

FOR RAMP

DRAWINGS

EXHIBIT BUILD

OUT BY OTHERS

EXHIBIT BUILD

OUT & FASCIA

ABOVE BY

OTHERS

13 13

3'-0"

17'-7"4'-4 1/4"7'-3 3/4"6'-0"5'-11 1/4"

2'-1 3/4"

3'-1"

1'-9 3/4"

12'-6 3/4"4'-11"5'-1 1/4"

6'-0 1/2"

8'-6"2'-5"

1'-4 3/4"

9 9

MECH

2 1 2 E

9 9

A-7.1

A-8.0

A-4.5

A-7.0

NEW LIFT

A-4.1

84' - 7"

88' - 8"

84'- 7"

74'- 6" 84'- 7"

82'- 5 1/4" 83'- 0 1/2"

83'- 6 1/2"

82'- 6"

UP

UP

UP

DN

A-5.1

1'-0" 2'-6 3/4" 5'-9 1/4" 2'-0" 2'-11"

2'-6 1/4"

4'-5 3/4"

84' - 7"

FE

FE

10'-8"

A-8.1

A-8.1

A-8.1 5A-8.1 6

PARTITION TYPE

WINDOW TYPE

DOOR TYPE

& TAG

FLOOR PLAN LEGEND

EXISTING

DOOR & TAG

NEW WALL EXISTING WALL TO REMAIN

XXX

1. ALL DIMENSIONS TO FINISHED FACE OF CONSTRUCTION, UNLESS OTHERWISE NOTED.

2. ALL NEW DOORS ARE OFFSET 5" FROM ADJACENT WALL, U.O.N.

3. CONTRACTOR TO VERIFY ALL CONDITIONS AND DIMENSIONS IN THE FIELD. REPORT ALL

DISCREPANCIES IN THESE DRAWINGS AND RELATED SPECIFICATIONS TO THE

CONTRACTING OFFICER FOR RESOLUTION PRIOR TO START OF CONSTRUCTION.

FAILURE TO VERIFY ALL CONDITIONS AFFECTING THE WORK AND FAILURE TO REPORT

DISCREPANCIES WILL NOT RELIEVE THE CONTRACTOR OF COMPLETE COORDINATION

OF ALL ASPECTS OF THE WORK.

4. ALL MATERIAL TO REMAIN IS TO BE PROTECTED DURING CONSTRUCTION.

CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE.

5. REFER TO SPECIFICATIONS AND ALL TRADE DRAWINGS FOR ADDITIONAL INFORMATION.

6. CONTRACTOR IS RESPONSIBLE FOR ALL TEMPORARY SUPPORT AND SHORING.

7. THE CARTER WOODSON HOUSE CONSISTS OF THREE DOMESTIC STRUCTURES THAT

TOGETHER WILL SERVE AS A FULLY FUNCTIONAL MUSEUM. THE MEP/FP, AV, AND

LIGHTING SYSTEMS WHICH ARE REQUIRED FOR SAFETY, FUNCTION, AND COMFORT

WILL COMPETE FOR LIMITED SPACED BEHIND FINISHES WITHIN THE STRUCTURE.

CONTRACTOR IS REQUIRED TO SUBMIT FULL COORDINATION DRAWINGS OF ALL

SYSTEMS TO RESOLVE ANY POTENTIAL CONFLICTS AND ASSURE SMOOTH

INSTALLATION OF THE SYSTEMS.

GENERAL FLOOR PLAN NOTES

1i xx

NEW WOOD

SUBFLOOR INFILL

XXX

EXISTING DOWNSPOUT

VENT TO ROOF

MW# MILLWORK TAG

X'-X" SPOT ELEVATION

FURRED OUT WALL

DRINKING

FOUNTAIN

FLOOR DRAIN (REFER TO

PLUMBING DRAWINGS)

FD

FIRE EXTINGUISHER

(SEMI-RECESSED CABINET)

FEFE

FIRE EXTINGUISHER

(SURFACE MOUNTED,

NO CABINET)

FINISH LEGEND

FLOOR

1 TEXTILE COMPOSITE

2 LVT

3 TILE

4 RUBBER TILE

E EXISTING TO REMAIN

- UNFINISHED

BASE

1 RUBBER

2 STAINED WOOD

3 TILE

E EXISTING TO REMAIN

- NO BASE

WALL

1 PAINT EXISTING

2 PTD GWB

3 TILE

4 RFP WALL PANEL

E…