B08_140P1424R0004_Attachment_2_100_Final_CD_s_Energy_Model_Compairson.pdf

PDF 181 KB Posted

Attached to
BICA - ADMINISTRATIVE BUILDING REMODEL Federal contract opportunity
Solicitation number
140P1424R0004
Issued by
Department of the Interior National Park Service Intermountain Region

About this file

This energy analysis compares the energy and cost impacts of proposed renovations to an administrative building at Bighorn Canyon National Recreation Area against an ASHRAE 90.1-2013 baseline. The analysis was conducted using Trace 700 energy modeling software and found that the preferred alternative of additional envelope insulation and upgraded windows with lower U-values would reduce annual energy costs by 40.4% compared to the baseline, from $25,164 to $14,986. Electric consumption would decrease by 65.8%, propane consumption by 32.9%, and total building energy use by 38.9%. The energy usage intensity would also fall by 38.9%, and equivalent carbon dioxide emissions by 65.8%. The analysis demonstrates that the proposed renovations would exceed the 20% improvement requirement over the ASHRAE baseline for major federal renovation projects.

View the file

Other files for this federal contract opportunity

Other files attached to BICA - ADMINISTRATIVE BUILDING REMODEL, newest first.
File Type Posted
B08_140P1424R0004_Attachment_6_DOL_WD_20240056_01052024_0002.pdf PDF
B08_140P1424R0004_Attachment_15_Specifications_SECTION_113013_-_RESIDENTIAL_APPLIANCES_0002.pdf PDF
B08_140P1424R0004_Attachment_13_Request_for_Proposal_140P1424R0004_Question_and_Answers_01162024_0002.pdf PDF
Sol_140P1424R0004_Amd_0002.pdf PDF
B08_140P1424R0004_Attachment_13_Request_for_Proposal_140P1424R0004_Questions_and_Answers_01022024_0001.pdf PDF
Sol_140P1424R0004_Amd_0001.pdf PDF
B08_140P1424R0004_Attachment_14_Request_for_Proposal_140P1424R0004_Organized_Site_Visit_Sign_In_Sheet_0001.pdf PDF
B08_140P1424R0004_Attachment_10_General_References.pdf PDF
B08_140P1424R0004_Attachment_9_Contract_Admin.docx DOCX document
Sol_140P1424R0004.pdf PDF
B08_140P1424R0004_Attachment_12_Schedule_of_Values.docx DOCX document
B08_140P1424R0004_Attachment_11_Subcontracting_Percentage_Worksheet.xlsx XLSX spreadsheet
B08_140P1424R0004_Attachment_3_Fort_Smith_Admin_Building_Geotechnical_Report_Final.pdf PDF
B08_140P1424R0004_Attachment_7_Past_Performance_Questionnaire.docx DOCX document
B08_140P1424R0004_Attachment_8_Project_Experience_Form.docx DOCX document
B08_140P1424R0004_Attachment_6_DOL_WD_20230056_Rev_6_10062023.pdf PDF
B08_140P1424R0004_Attachment_5_7112_24_Design_Calculations_Final_CD_3-14-23.pdf PDF
B08_140P1424R0004_Attachment_1_Specifications_Final_CD_3-23-23_Clean_with_Addendum.pdf PDF
B08_140P1424R0004_Attachment_4_Final_CD_Drawing_Full_Set_3-23-23_Revised.pdf PDF
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

360 Engineering, Inc. | 751 Pine Ridge Rd, Suite 360, Golden, CO 80403 | (303) 940-2050 | www.360eng.com

March 15, 2023

Rehabilitate Fort Smith Administrative Building

Bighorn Canyon National Recreation Area, MT

Energy Model Results The purpose of this energy analysis is to quantify the benefits of the improvements to the envelope and glass of the current building compared to the ASHRAE 90.1-2013 baseline. Federal Guiding Principles for a major renovation require that the building systems improve upon the ASHRAE 90.1 baseline system by at least 20%. Based on the assumptions of utility pricing, the proposed building envelope and glass selections outperform the baseline building by approximately 40%.

These pricing assumptions are an electricity cost of $0.1074/kWh, sourced from local commercial energy bill and a propane cost of $2.34/therm, sourced from a local propane distributor. Referring to Table 1, below, the proposed alternative improves upon the ASHRAE 90.1 baseline energy cost by 40.4%, bringing down the annual utility cost of $25,164 to $14,986. With regards to the environmental impact, the anticipated energy usage intensity and equivalent tons of CO2 are also included in the table to show the reduction from the ASHRAE baseline for the alternative.

The energy model was conducted using Trace 700 Energy Modeling Software. The model compared the preferred alternative to the ASHRAE 90.1 baseline. The preferred alternative model assumes additional insulation to the envelope of the building as well as upgraded windows with lower U-Values. These values are based on the Architectural CD drawings provided. The model was then compared to ASHRAE 90.1-2013 standard systems for the building baseline.

Table 1. Energy Analysis Summary

Preferred

Alternative

ASHRAE 90.1

Percent

Improvement on Baseline

Electric

Consumption 18,338 kWh 53,595 kWh 65.8%

Propane

Consumption 556,279 kBTU 829,382 kBTU 32.9%

Total Building

Energy 618,866 kBTU/yr

1,012,303 kBTU/yr 38.9%

Energy Usage

Intensity

84.8 kBTU/ft2/yr 138.7 kBTU/ft2/yr 38.9%

Equivalent CO2 14.8 Tons/year CO2

43.26 Tons/year

CO2

65.8%

Estimated Yearly

Energy Costs $14,986 $25,164 40.4%

The designed system beats the baseline Energy Usage Intensity by 38.9%