This document includes structural calculations and design criteria for the expansion and renovation of an existing 5,000 square foot building to serve as the Monacan Health Clinic. The building is constructed of CMU block on a cement slab and will be expanded/renovated to provide primary care, behavioral health, outpatient pharmacy, visiting optometry, preventive care services, patient registration, and facility management functions. Design loads include roof live loads of 50 psf for offices and 100 psf for lobbies/corridors, and wind loads of 115 mph basic wind speed and 89 mph wind speed with components and cladding. Foundation, framing, canopy, and lateral structural elements are addressed, along with structural steel specifications. The related federal contract opportunity is solicitation number 75H701-21-R-00049 for construction services issued by the Department of Health and Human Services Indian Health Service. The contractor will provide all labor, tools, equipment, and incidentals to complete the expansion/renovation of the Monacan Health Clinic building.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NCE Job #: 21-191
Date: 6/15/2021
102 S. 21 st Avenue West, Suite One, Duluth, Minnesota 55806, voice (218) 727-5995, fax (218) 727-7779
Location:
STRUCTURAL CALCULATIONS
Mid-Atlantic Tribes
Monacan Health Clinic
Madison Heights, Virginia
Northland Consulting Engineers L.L.P.
Structural, Civil and Forensic Engineering Services
Attachment J04
Table of Contents:
Canopy…………………….………………………..……………………500
Basis for Structural Design………..……………………………………100
Foundation.………………….………………..…………………………200
Framing…………………...……………………..………………………300
Lateral…………………….………………………..……………………400
102 S. 21 st Avenue West, Suite One, Duluth, Minnesota 55806, voice (218) 727-5995, fax (218) 727-7779
BASIS OF DESIGN
Northland Consulting Engineers L.L.P.
Project # 21-191 Date: 6/3/21 By: TDR
Location:
Offices: LL = 50 psf + 15 psf Partitions
Patient / Exam Rooms: LL = 40 psf
Lobbies / Corridors: LL = 100 psf
Storage / Mechanical: LL = 125 psf
Pg = 25.0 psf
Is = 1.0
Ce = 1.0
Ct = 1.1 (building)
1.2 (exterior, unheated sttuctures)
Pm = 19 psf (building)
21 psf (exterior, unheated sttuctures)
II
VUlt = 115 mph (3-second gust)
VASD = 89 mph (3-second gust)
C
**Plus and Minus signs signify pressures acting toward and away from the building surfaces.
Roof - Zone 3 = +17 PSF/ -68 PSF (Edge) / -95 psf (Overhang)
Wall - Zone 4 (Interior) = +27 PSF/ -29 PSF
Wall - Zone 5 (Corner) = +27 PSF / -36 PSF
*Design C&C wind pressures for tributary areas larger than 10 sq.ft. may be used, as applicable, if determined by calculation, and approved by Engineer of Record.
Roof - Zone 2 = +17 PSF/ -46 PSF (Edge) / -58 psf (Overhang)
Minimum Snow Load:
Unbalanced snow loads and drift loads are determined on a case-by-case basis and shown on the Load Map where they occur.
Wind Loads (ASCE 7, Chapter 26):
Risk Category:
Exposure:
Wind Directionality Factor Kd: 0.85
Wind Components & Cladding (ASCE 7, Chapter 30):
Roof - Zone 1 (Interior) = +17 PSF/ -27 PSF
Basic Wind Speed:
Thermal Coefficient:
American Concrete Institute (ACI), 318-14 - Concrete
American Concrete Institute (ACI), 530-13 - Masonry
Specification for Structural Steel Buildings (AISC), 360-10
Building Classification (ASCE 7, Chapter 1):
Risk Category: II
Live Loads (ASCE 7, Chapter 4):
Snow Loads (ASCE 7, Chapter 7):
Ground Snow Load:
Importance Factor:
Exposure Coefficient:
American Society of Civil Engineers (ASCE), 7-10
MAT - Monacan Health Clinic
Madison Heights, VA
BASIS FOR STRUCTURAL DESIGN
Building Codes:
International Building Code (IBC), 2015 Edition
Northland Consulting Engineers L.L.P.
����� *�����-���/����%#�-���0+� ���
123456789:;4<3=>;9
?@@42AAB "#)��+��,�*���� ��C�.
����� *�����C�/����%#�C
0+�
D;;4@>93=2AB "#��##$%�&C�(#$���#&)��
EF2G3=>;9B $�%�H�
I><2A=3<JB ����(��(�������������$�K
L3M34@7INJ2B +���
?1DE7OPQR
S����
T �
U�*������ �����*V�** V�,�,�*�*W
������H����������
�*X���*�� ����*(��*��H����
����W* W���
Y����
?1DE7OPQZ
S����
V�,�, *�*W ������H����������
��*����������*��*X���*��
��*��H����
����W*
W����Y����
?1DE7OPZ[
S����
V�,�,�*�*W
������H����������
�*X���*�� ����*(��*��H����
����W* W���
Y����
\]̂_̀̂abcda_efgehid̂g_]̂`̂_jk_lk\_̀̂mĉhd_ifn_adid̂_ò_cohic_ip̂ fgp̂ fda_do_d]̂_qicb̂a_ò_ifn_ĝcef̂ideof_cef̂a_piĝ_gb̀efr_d]̂_sbecgefr_hoĝ igotdeof_t̀oĥaau_vâ à_a]obcg_hofmèp_ifn_obdtbd_osdief̂g_m̀op_d]ea_dooc_wed]_d]̂_cohic_xbd]òedn_yiqefr_zb̀eagehdeof_ŝmò _̂t̀oĥ ĝefr_wed] ĝaerfu
{>A5F3><24
�H��,� ����W�
}���*���*���H��, ����������*����*�����*��*W* �����*�����*��C�����
�������H������� ������H��� �����*��H���
*V �W*��H�� ������H����� ��C����� ����H*�����
��*��H��������H��, �,*����H��������,�*�*������H*����� ��C�� W����*V�*��*��*� �*������*�H�*� ��H��� ����*C����
������������*�H�����*��� ��H�� �*��*X���* ��H���������H*����� ����������*��*�������H���*��*��������W�
0�*����H���*���H��, �����H��,�������*����*� �������H��,��������*��0�*��H���*���������H�������*����*� ����W
��*���W*���������� �*���*��������*�H������� ����W �����H�����*�����
Monacan Health Clinic
#REF!
Snow Loading - ASCE 7- 10
#REF!
25.00 psf Balanced & Unbalanced Snow Load for Hips and Gable Roofs
Flat Balanced Snow, ps = 20 psf
0.25 :12 Unbalanced, I*pg = 25 psf, W <= 20ft with roof rafter system
= 1.19 ° hd = 2.077
S = 48.00 Unbalanced, hd γ sqrt(S) = 5 psf w/ 8/3 hd sqrt(S) = 38.37 ft
40 ft Unbalanced, 0.3 ps = 6 psf
1.00
1.10
1.00
20 psf
1.00
Sloped Roof Snow Load, ps = 20.00 psf
Snow Drifts on Lower Roof From Higher Portions of the Same Structure
17.25 pcf but not greater than 30 pcf
Height of Balanced Snow Load, hb = 1.16 ft
Drift Truncated Drift
Case Level y hc hc/hb lu1 hd1 lu2 hd2 hd max w hd pd pd SMEAR w' pd' High side Low side Y/N pSLIDE
(ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (ft) (psf) (psf) (ft) (psf) (psf) (psf) (psf)
Adj. to Barrel Roof (sides) R 4.17 3.011 2.597 25.830 1.592 29.000 1.285 1.592 6.367 1.592 27 18 NA NA 47.46 20.00 Y 13.78
Adj. to Barrel Roof (F-B) R 15 13.841 11.938 75.000 2.911 25.000 1.169 2.911 11.643 2.911 50 33 NA NA 70.21 20.00 n NA
Adj. to Gable Roof R 13.17 12.011 10.359 68.000 2.769 24.670 1.169 2.769 11.076 2.769 48 32 NA NA 67.76 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
Canopy Drift C 12.83 11.671 10.066 81.000 3.025 3.340 1.169 3.025 12.101 3.025 52 35 3.340 38 72.19 57.78 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
-1.159 -1.000 1.558 1.169 1.558 NA NA NA 0 NA NA 20.00 20.00 n NA
Drift Truncated Drift Total Load = hb + hd Sliding LoadLeeward Windward
#REF!
Importance Factor, I =
Flat Roof Snow Load, pf =
Roof Slope Factor, Cs =
Snow Density, γ =
Ground Snow Load, pg =
Roof Type =
Roof Slope =
W =
Exposure Factor, Ce =
Thermal Factor, Ct = w lu2 y hc pd lu1 hb
Upper Roof lu2 w' pd h lu1 hc y pd'
Upper Roof
,14p13.0 g +=γ γ= sb ph gtef IpCC7.0p = fss pCp =
����� *�����-���/����%#�-���0+� ���
123456789:;4<3=>;9
?@@42AAB "#)��+��,�*���� ��C�.
����� *�����C�/����%#�C
0+�
D;;4@>93=2AB "#��##$%�&C�(#$���#&)��
EF2G3=>;9B $�%�H�
I><2A=3<JB ����(��(���������%"���%K
L3M34@7INJ2B O��
?1DE7PQRS
.TU���(V*
.TU��%(V*
.TU�%�(V*
.TU����(V*
T��W�� �*�����U ���,��
T��W��
�*�����UU ��$,��
T��W��
�*�����UUU ��),��
T��W�� �*�����U/ ���,��
?1DE7PQRX
.TU���(V*
.TU��%(V*
.TU�%�(V*
.TU����(V*
T��W�� �*�����U ��%,��
T��W��
�*�����UU ��%,��
T��W��
�*�����UUU(U/ ���,��
?1DE7PQXY
�+�Z�#(�%�O��
[\]̂_]̀abc̀̂defdghc]f̂\]_]̂iĵkj[̂_]lb]gĉhem̂̀ chc]̂n_̂bnghb̂ho]efo]ec̀̂cn̂c\]̂phba]̀ n̂_̂hem̂f]bde]hcdnêbde]̀ ôhf]̂fa_deq̂c\]̂radbfdeq̂gnf] hfnscdnês_ng]̀ t̀̂ù]_̀̂ \̀nabf̂gneld_ôhem̂nacsaĉnrchde]f̂l_nôc\d̀̂cnnb̂vdc\̂c\]̂bnghb̂wac\n_dcm̂xhpdeq̂ya_d̀fdgcdnêr]ln_]̂s_ng]]fdeq̂vdc\ f]̀dqet z>A5F3><24
�H��,� �����+�Z�#� �*�������*����*�*���|*���+�Z�#C����
����������H���*��� �*�C�������*����*������*~��
���*�*H��*C����{� ������������������*������Z��������*��*���* ��*�C���*
HH*�����*��*��������������������
��C�����*�C���* �����,������*�C� �H��������
O���*���*���H��, �����*�����*��C�����
�������H������� ������H��� �����*��H���
�{*��H�� ������H����� ��C����� ����H*�����
��*��H��������H��, �,*����H��������,�*�*������H*����� ��C�� �W����* �*������*�H�*� ��H��� ����*C����
������������*�H�����*��� ��H�� ��H���������H*����� ����������*��*�������H���*��*��������{�
0�*����H���*���H��, �����H��,�������*����*� �������H��,��������*��0�*��H���*���������H�������*����*�
�*���*��������*�H������� �����H�����*�����
"ASCE710W.xls" Program
Version 2.2
WIND LOADING ANALYSIS - Main Wind-Force Resisting System Per ASCE 7-10 Code for Enclosed or Partially Enclosed Buildings
Using Method 2: Analytical Procedure (Section 27) for Buildings of Any Height
Job Name: Monacan Health Clinic Subject:
Job Number: 21-191 Originator: ZKS Checker:
Input Data:
Wind Direction = Normal (Normal or Parallel to building ridge)
Wind Speed, V = 115 mph (Wind Map, Figure 26.5-1A-C)
Bldg. Classification = II (Table 1.4-1 Risk Cat.)
Exposure Category = C (Sect. 26.7)
Ridge Height, hr = 24.67 ft. (hr >= he)
Eave Height, he = 12.00 ft. (he <= hr)
Building Width = 164.50 ft. (Normal to Building Ridge)
Building Length = 173.25 ft. (Parallel to Building Ridge)
Roof Type = Gable (Gable or Monoslope)
Topo. Factor, Kzt = 1.00 (Sect. 26.8 & Table 26.8-1)
Direct. Factor, Kd = 0.85 (Table 26.6-1)
Enclosed? (Y/N) Y (Sect. 6.2 & Figure 6-5)
Hurricane Region? N
Damping Ratio, β = 0.050 (Suggested Range = 0.010-0.070)
Period Coef., Ct = 0.0350 (Suggested Range = 0.020-0.035)
(Assume: T = Ct*h^(3/4) , and f = 1/T)
Resulting Parameters and Coefficients:
Roof Angle, θ = 8.76 deg.
Mean Roof Ht., h = 12.00 ft. (h = he, for roof angle <=10 deg.) L = 164.5 ft.
Windward Wall Cp = 0.80 (Fig. 27.4-1) B = 173.25 ft.
Leeward Wall Cp = -0.50 (Fig. 27.4-1)
Side Walls Cp = -0.70 (Fig. 27-4.1)
Roof Cp (zone #1) = -0.90 -0.18 (Fig. 27-4.1) (zone #1 for 0 to h/2)
Roof Cp (zone #2) = -0.90 -0.18 (Fig. 27-4.1) (zone #2 for h/2 to h)
Roof Cp (zone #3) = -0.50 -0.18 (Fig. 27-4.1) (zone #3 for h to 2*h)
Roof Cp (zone #4) = -0.30 -0.18 (Fig. 27-4.1) (zone #4 for > 2*h)
+GCpi Coef. = 0.18 (Table 26.11-1)(positive internal pressure)
-GCpi Coef. = -0.18 (Table 26.11-1)(negative internal pressure)
If z <= 15 then: Kz = 2.01*(15/zg)^(2/α) , If z > 15 then: Kz = 2.01*(z/zg)^(2/α) (Table 27.3-1) α = 9.50 zg = 900 (Table 26.9-1)
Kh = 0.85 (Kh = Kz evaluated at z = h)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Eq. 27.3-1) qh = 24.43 psf qh = 0.00256*Kh*Kzt*Kd*V^2 (qz evaluated at z = h)
Ratio h/L = 0.073 freq., f = 4.431 hz. (f >= 1, Rigid structure)
Gust Factor, G = 0.848 (Sect. 26.9)
Design Net External Wind Pressures (Sect. 27.4):
p = qz*G*Cp - qi*(+/-GCpi) for windward wall (psf), where: qi =qh (Eq. 27.4-1) p = qh*G*Cp - qi*(+/-GCpi) for leeward wall, sidewalls, and roof (psf), where: qi = qh (Eq. 27.4-1) θ o
L
B hr he h
Plan
Elevation
L
Wind
Normal to Ridge Wind Load Tabulation for MWFRS - Buildings of Any Height
Surface z Kz qz Cp p = Net Design Press. (psf)
(ft.) (psf) (w/ +GCpi) (w/ -GCpi)
Windward Wall 0 0.85 24.43 0.80 12.18 20.97
15.00 0.85 24.43 0.80 12.18 20.97
20.00 0.90 25.95 0.80 13.21 22.00
For z = hr: 24.67 0.94 27.13 0.80 14.01 22.80
For z = he: 12.00 0.85 24.43 0.80 12.18 20.97
For z = h: 12.00 0.85 24.43 0.80 12.18 20.97
Leeward Wall All - - -0.50 -14.76 -5.96
Side Walls All - - -0.70 -18.90 -10.10
Roof (zone #1) cond. 1 - - - -0.90 -23.04 -14.25
Roof (zone #1) cond. 2 - - - -0.18 -8.13 0.67
Roof (zone #2) cond. 1 - - - -0.90 -23.04 -14.25
Roof (zone #2) cond. 2 - - - -0.18 -8.13 0.67
Roof (zone #3) cond. 1 - - - -0.50 -14.76 -5.96
Roof (zone #3) cond. 2 - - - -0.18 -8.13 0.67
Roof (zone #4) cond. 1 - - - -0.30 -10.61 -1.82
Roof (zone #4) cond. 2 - - - -0.18 -8.13 0.67
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Per Code Section 27.4.7, the minimum wind load for MWFRS shall not be less than 16 psf.
4. Roof zone #1 is applied for horizontal distance of 0 to h/2 from windward edge.
5. Roof zone #2 is applied for horizontal distance of h/2 to h from windward edge.
6. Roof zone #3 is applied for horizontal distance of h to 2*h from windward edge.
7. Roof zone #4 is applied for horizontal distance of > 2*h from windward edge.
Determination of Gust Effect Factor, G:
Is Building Flexible? No f >=1 Hz.
1: Simplified Method for Rigid Building
G = 0.850
Parameters Used in Both Item #2 and Item #3 Calculations (from Table 26.9-1):
α^ = 0.105 b^ = 1.00 α(bar) = 0.154 b(bar) = 0.65 c = 0.20 l = 500 ft.
ε(bar) = 0.200 z(min) = 15 ft.
Calculated Parameters Used in Both Rigid and/or Flexible Building Calculations:
z(bar) = 15.00 = 0.6*h , but not < z(min) , ft. Table 26.9-1
Iz(bar) = 0.228 = c*(33/z(bar))^(1/6) , Eq. 26.9-7
Lz(bar) = 427.06 = l*(z(bar)/33)^(ε(bar)) , Eq. 26.9-9 gq = 3.4 (3.4, per Sect. 26.9.4) gv = 3.4 (3.4, per Sect. 26.9.4) gr = 4.531 = (2*(LN(3600*f)))^(1/2)+0.577/(2*LN(3600*f))^(1/2) , Eq. 26.9-11
Q = 0.854 = (1/(1+0.63*((B+h)/Lz(bar))^0.63))^(1/2) , Eq. 26.9-8
2: Calculation of G for Rigid Building
G = 0.848 = 0.925*((1+1.7*gq*Iz(bar)*Q)/(1+1.7*gv*Iz(bar))) , Eq. 26.9-6
3: Calculation of Gf for Flexible Building β = 0.050 Damping Ratio
Ct = 0.035 Period Coefficient
T = 0.226 = Ct*h^(3/4) , sec. (Approximate fundamental period) f = 4.431 = 1/T , Hz. (Natural Frequency)
V(fps) = N.A. = V(mph)*(88/60) , ft./sec.
V(bar,zbar) = N.A. = b(bar)*(z(bar)/33)^(α(bar))*V*(88/60) , ft./sec. , Eq. 26.9-16
N1 = N.A. = f*Lz(bar)/(V(bar,zbar)) , Eq. 26.9-14
Rn = N.A. = 7.47*N1/(1+10.3*N1)^(5/3) , Eq. 26.9-13 ηh = N.A. = 4.6*f*h/(V(bar,zbar))
Rh = N.A. = (1/ηh)-1/(2*ηh^2)*(1-e^(-2*ηh)) for ηh>0, or = 1 for ηh=0 ,Eq. 26.9-15a, b ηb = N.A. = 4.6*f*B/(V(bar,zbar))
RB = N.A. = (1/ηb)-1/(2*ηb^2)*(1-e^(-2*ηb)) for ηb>0, or = 1 for ηb=0,Eq. 26.9-15a, b ηd = N.A. = 15.4*f*L/(V(bar,zbar))
RL = N.A. = (1/ηd)-1/(2*ηd^2)*(1-e^(-2*ηd)) for ηd>0, or = 1 for ηd=0 ,Eq. 26.9-15a, b
R = N.A. = ((1/β)*Rn*Rh*RB*(0.53+0.47*RL))^(1/2) , Eq. 26.9-12
Gf = N.A. = 0.925*(1+1.7*Iz(bar)*(gq^2*Q^2+gr^2*R^2)^(1/2))/(1+1.7*gv*Iz(bar)) , Use: G = 0.848 Eq. 26.9-10
Figure 27.4-1 - Design Wind Load Cases of MWFRS for Buildings of All Heights
Case 1: Full design wind pressure acting on the projected area perpendicular to each principal axis of the structure, considered separately along each principal axis.
Case 2: Three quarters of the design wind pressure acting on the projected area perpendicular to each principal axis of the structure in conjunction with a torsional moment as shown, considered separately for each principal axis.
Case 3: Wind pressure as defined in Case 1, but considered to act simultaneously at 75% of the specified value.
Case 4: Wind pressure as defined in Case 2, but considered to act simultaneously at 75% of the specified value.
Notes: 1. Design wind pressures for windward (Pw) and leeward (PL) faces shall be determined in accordance with the provisions of Section 27.4.1 and 27.4.2 as applicable for buildings of all heights.
2. Above diagrams show plan views of building.
3. Notation:
Pwx, Pwy = Windward face pressure acting in the X, Y principal axis, respectively.
PLx, PLy = Leeward face pressure acting in the X, Y principal axis, respectively.
e (ex, ey) = Eccentricity for the X, Y principal axis of the structure, respectively.
MT = Torsional moment per unit height acting about a vertical axis of the building.
WIND LOADING ANALYSIS - Main Wind-Force Resisting System Per ASCE 7-10 Code for Enclosed or Partially Enclosed Buildings
Using Method 2: Analytical Procedure (Section 27) for Buildings of Any Height
Job Name: Monacan Health Clinic Subject:
Job Number: 21-191 Originator: ZKS Checker:
Input Data:
Wind Direction = Parallel (Normal or Parallel to building ridge)
Wind Speed, V = 115 mph (Wind Map, Figure 26.5-1A-C)
Bldg. Classification = II (Table 1.4-1 Risk Cat.)
Exposure Category = C (Sect. 26.7)
Ridge Height, hr = 24.67 ft. (hr >= he)
Eave Height, he = 12.00 ft. (he <= hr)
Building Width = 164.50 ft. (Normal to Building Ridge)
Building Length = 173.25 ft. (Parallel to Building Ridge)
Roof Type = Gable (Gable or Monoslope)
Topo. Factor, Kzt = 1.00 (Sect. 26.8 & Table 26.8-1)
Direct. Factor, Kd = 0.85 (Table 26.6-1)
Enclosed? (Y/N) Y (Sect. 6.2 & Figure 6-5)
Hurricane Region? N
Damping Ratio, β = 0.050 (Suggested Range = 0.010-0.070)
Period Coef., Ct = 0.0350 (Suggested Range = 0.020-0.035)
(Assume: T = Ct*h^(3/4) , and f = 1/T)
Resulting Parameters and Coefficients:
Roof Angle, θ = 8.76 deg.
Mean Roof Ht., h = 12.00 ft. (h = he, for roof angle <=10 deg.) L = 173.25 ft.
Windward Wall Cp = 0.80 (Fig. 27.4-1) B = 164.5 ft.
Leeward Wall Cp = -0.49 (Fig. 27.4-1)
Side Walls Cp = -0.70 (Fig. 27-4.1)
Roof Cp (zone #1) = -0.90 -0.18 (Fig. 27-4.1) (zone #1 for 0 to h/2)
Roof Cp (zone #2) = -0.90 -0.18 (Fig. 27-4.1) (zone #2 for h/2 to h)
Roof Cp (zone #3) = -0.50 -0.18 (Fig. 27-4.1) (zone #3 for h to 2*h)
Roof Cp (zone #4) = -0.30 -0.18 (Fig. 27-4.1) (zone #4 for > 2*h)
+GCpi Coef. = 0.18 (Table 26.11-1)(positive internal pressure)
-GCpi Coef. = -0.18 (Table 26.11-1)(negative internal pressure)
If z <= 15 then: Kz = 2.01*(15/zg)^(2/α) , If z > 15 then: Kz = 2.01*(z/zg)^(2/α) (Table 27.3-1) α = 9.50 zg = 900 (Table 26.9-1)
Kh = 0.85 (Kh = Kz evaluated at z = h)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Eq. 27.3-1) qh = 24.43 psf qh = 0.00256*Kh*Kzt*Kd*V^2 (qz evaluated at z = h)
Ratio h/L = 0.069 freq., f = 4.431 hz. (f >= 1, Rigid structure)
Gust Factor, G = 0.850 (Sect. 26.9)
Design Net External Wind Pressures (Sect. 27.4):
p = qz*G*Cp - qi*(+/-GCpi) for windward wall (psf), where: qi =qh (Eq. 27.4-1) p = qh*G*Cp - qi*(+/-GCpi) for leeward wall, sidewalls, and roof (psf), where: qi = qh (Eq. 27.4-1) θ o
L
B hr he h
Plan
Elevation
L
Wind
Parallel to Ridge Wind Load Tabulation for MWFRS - Buildings of Any Height
Surface z Kz qz Cp p = Net Design Press. (psf)
(ft.) (psf) (w/ +GCpi) (w/ -GCpi)
Windward Wall 0 0.85 24.43 0.80 12.21 21.01
15.00 0.85 24.43 0.80 12.21 21.01
20.00 0.90 25.95 0.80 13.25 22.04
For z = hr: 24.67 0.94 27.13 0.80 14.05 22.84
For z = he: 12.00 0.85 24.43 0.80 12.21 21.01
For z = h: 12.00 0.85 24.43 0.80 12.21 21.01
Leeward Wall All - - -0.49 -14.56 -5.76
Side Walls All - - -0.70 -18.93 -10.14
Roof (zone #1) cond. 1 - - - -0.90 -23.08 -14.29
Roof (zone #1) cond. 2 - - - -0.18 -8.13 0.66
Roof (zone #2) cond. 1 - - - -0.90 -23.08 -14.29
Roof (zone #2) cond. 2 - - - -0.18 -8.13 0.66
Roof (zone #3) cond. 1 - - - -0.50 -14.78 -5.98
Roof (zone #3) cond. 2 - - - -0.18 -8.13 0.66
Roof (zone #4) cond. 1 - - - -0.30 -10.63 -1.83
Roof (zone #4) cond. 2 - - - -0.18 -8.13 0.66
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Per Code Section 27.4.7, the minimum wind load for MWFRS shall not be less than 16 psf.
4. Roof zone #1 is applied for horizontal distance of 0 to h/2 from windward edge.
5. Roof zone #2 is applied for horizontal distance of h/2 to h from windward edge.
6. Roof zone #3 is applied for horizontal distance of h to 2*h from windward edge.
7. Roof zone #4 is applied for horizontal distance of > 2*h from windward edge.
Determination of Gust Effect Factor, G:
Is Building Flexible? No f >=1 Hz.
1: Simplified Method for Rigid Building
G = 0.850
Parameters Used in Both Item #2 and Item #3 Calculations (from Table 26.9-1):
α^ = 0.105 b^ = 1.00 α(bar) = 0.154 b(bar) = 0.65 c = 0.20 l = 500 ft.
ε(bar) = 0.200 z(min) = 15 ft.
Calculated Parameters Used in Both Rigid and/or Flexible Building Calculations:
z(bar) = 15.00 = 0.6*h , but not < z(min) , ft. Table 26.9-1
Iz(bar) = 0.228 = c*(33/z(bar))^(1/6) , Eq. 26.9-7
Lz(bar) = 427.06 = l*(z(bar)/33)^(ε(bar)) , Eq. 26.9-9 gq = 3.4 (3.4, per Sect. 26.9.4) gv = 3.4 (3.4, per Sect. 26.9.4) gr = 4.531 = (2*(LN(3600*f)))^(1/2)+0.577/(2*LN(3600*f))^(1/2) , Eq. 26.9-11
Q = 0.857 = (1/(1+0.63*((B+h)/Lz(bar))^0.63))^(1/2) , Eq. 26.9-8
2: Calculation of G for Rigid Building
G = 0.850 = 0.925*((1+1.7*gq*Iz(bar)*Q)/(1+1.7*gv*Iz(bar))) , Eq. 26.9-6
3: Calculation of Gf for Flexible Building β = 0.050 Damping Ratio
Ct = 0.035 Period Coefficient
T = 0.226 = Ct*h^(3/4) , sec. (Approximate fundamental period) f = 4.431 = 1/T , Hz. (Natural Frequency)
V(fps) = N.A. = V(mph)*(88/60) , ft./sec.
V(bar,zbar) = N.A. = b(bar)*(z(bar)/33)^(α(bar))*V*(88/60) , ft./sec. , Eq. 26.9-16
N1 = N.A. = f*Lz(bar)/(V(bar,zbar)) , Eq. 26.9-14
Rn = N.A. = 7.47*N1/(1+10.3*N1)^(5/3) , Eq. 26.9-13 ηh = N.A. = 4.6*f*h/(V(bar,zbar))
Rh = N.A. = (1/ηh)-1/(2*ηh^2)*(1-e^(-2*ηh)) for ηh>0, or = 1 for ηh=0 ,Eq. 26.9-15a, b ηb = N.A. = 4.6*f*B/(V(bar,zbar))
RB = N.A. = (1/ηb)-1/(2*ηb^2)*(1-e^(-2*ηb)) for ηb>0, or = 1 for ηb=0,Eq. 26.9-15a, b ηd = N.A. = 15.4*f*L/(V(bar,zbar))
RL = N.A. = (1/ηd)-1/(2*ηd^2)*(1-e^(-2*ηd)) for ηd>0, or = 1 for ηd=0 ,Eq. 26.9-15a, b
R = N.A. = ((1/β)*Rn*Rh*RB*(0.53+0.47*RL))^(1/2) , Eq. 26.9-12
Gf = N.A. = 0.925*(1+1.7*Iz(bar)*(gq^2*Q^2+gr^2*R^2)^(1/2))/(1+1.7*gv*Iz(bar)) , Use: G = 0.850 Eq. 26.9-10
Figure 27.4-1 - Design Wind Load Cases of MWFRS for Buildings of All Heights
Case 1: Full design wind pressure acting on the projected area perpendicular to each principal axis of the structure, considered separately along each principal axis.
Case 2: Three quarters of the design wind pressure acting on the projected area perpendicular to each principal axis of the structure in conjunction with a torsional moment as shown, considered separately for each principal axis.
Case 3: Wind pressure as defined in Case 1, but considered to act simultaneously at 75% of the specified value.
Case 4: Wind pressure as defined in Case 2, but considered to act simultaneously at 75% of the specified value.
Notes: 1. Design wind pressures for windward (Pw) and leeward (PL) faces shall be determined in accordance with the provisions of Section 27.4.1 and 27.4.2 as applicable for buildings of all heights.
2. Above diagrams show plan views of building.
3. Notation:
Pwx, Pwy = Windward face pressure acting in the X, Y principal axis, respectively.
PLx, PLy = Leeward face pressure acting in the X, Y principal axis, respectively.
e (ex, ey) = Eccentricity for the X, Y principal axis of the structure, respectively.
MT = Torsional moment per unit height acting about a vertical axis of the building.
WIND LOADING ANALYSIS - Roof Components and Cladding Per ASCE 7-10 Code for Bldgs. of Any Height with Gable Roof θ <= 45 o or Monoslope Roof θ <= 3 o
Using Part 1 & 3: Analytical Procedure (Section 30.4 & 30.6)
Job Name: Monacan Health Clinic Subject:
Job Number: 21-191 Originator: ZKS Checker:
Input Data:
Wind Speed, V = 115 mph (Wind Map, Figure 26.5-1A-C)
Bldg. Classification = II (Table 1.5-1 Risk Category)
Exposure Category = C (Sect. 26.7)
Ridge Height, hr = 24.67 ft. (hr >= he)
Eave Height, he = 12.00 ft. (he <= hr)
Building Width = 164.50 ft. (Normal to Building Ridge)
Building Length = 173.25 ft. (Parallel to Building Ridge)
Roof Type = Gable (Gable or Monoslope)
Topo. Factor, Kzt = 1.00 (Sect. 26.8 & Figure 26.8-1)
Direct. Factor, Kd = 0.85 (Table 26.6)
Enclosed? (Y/N) Y (Sect. 28.6-1 & Figure 26.11-1)
Hurricane Region? N
Component Name = Joist (Purlin, Joist, Decking, or Fastener)
Effective Area, Ae = 10 ft.^2 (Area Tributary to C&C)
Overhangs? (Y/N) N (if used, overhangs on all sides)
Resulting Parameters and Coefficients:
Roof Angle, θ = 8.76 deg.
Mean Roof Ht., h = 12.00 ft. (h = he, for roof angle <=10 deg.)
Roof External Pressure Coefficients, GCp:
GCp Zone 1-3 Pos. = 0.50 (Fig. 30.4-2A, 30.4-2B, and 30.4-2C)
GCp Zone 1 Neg. = -0.90 (Fig. 30.4-2A, 30.4-2B, and 30.4-2C)
GCp Zone 2 Neg. = -1.70 (Fig. 30.4-2A, 30.4-2B, and 30.4-2C)
GCp Zone 3 Neg. = -2.60 (Fig. 30.4-2A, 30.4-2B, and 30.4-2C)
Positive & Negative Internal Pressure Coefficients, GCpi (Figure 26.11-1):
+GCpi Coef. = 0.18 (positive internal pressure)
-GCpi Coef. = -0.18 (negative internal pressure)
If z <= 15 then: Kz = 2.01*(15/zg)^(2/α) , If z > 15 then: Kz = 2.01*(z/zg)^(2/α) (Table 30.3-1) α = 9.50 (Table 26.9-1) zg = 900 (Table 26.9-1)
Kh = 0.85 (Kh = Kz evaluated at z = h)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2 (Sect. 30.3.2, Eq. 30.3-1) qh = 24.43 psf qh = 0.00256*Kh*Kzt*Kd*V^2 (qz evaluated at z = h)
Design Net External Wind Pressures (Sect. 30.4 & 30.6):
For h <= 60 ft.: p = qh*((GCp) - (+/-GCpi)) (psf)
For h > 60 ft.: p = q*(GCp) - qi*(+/-GCpi) (psf) where: q = qh for roof qi = qh for roof (conservatively assumed per Sect. 30.6) θ o
L
B hr he h
Plan
Elevation
L
Wind Load Tabulation for Roof Components & Cladding
Component z Kh qh p = Net Design Pressures (psf)
(ft.) (psf) Zone 1,2,3 (+) Zone 1 (-) Zone 2 (-) Zone 3 (-)
Joist 0 0.85 24.43 16.61 -26.38 -45.93 -67.91
15.00 0.85 24.43 16.61 -26.38 -45.93 -67.91
20.00 0.85 24.43 16.61 -26.38 -45.93 -67.91
For z = hr: 24.67 0.85 24.43 16.61 -26.38 -45.93 -67.91
For z = he: 12.00 0.85 24.43 16.61 -26.38 -45.93 -67.91
For z = h: 12.00 0.85 24.43 16.61 -26.38 -45.93 -67.91
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Width of Zone 2 (edge), 'a' = 6.58 ft.
3. Width of Zone 3 (corner), 'a' = 6.58 ft.
4. For monoslope roofs with θ <= 3 degrees, use Fig. 30.4-2A for 'GCp' values with 'qh'.
5. For buildings with h > 60' and θ > 10 degrees, use Fig. 30.6-1 for 'GCpi' values with 'qh'.
6. For all buildings with overhangs, use Fig. 30.4-2B for 'GCp' values per Sect. 30.10.
7. If a parapet >= 3' in height is provided around perimeter of roof with θ <= 10 degrees, Zone 3 shall be treated as Zone 2.
8. Per Code Section 30.2.2, the minimum wind load for C&C shall not be less than 16 psf.
9. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures".
b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" by: Kishor C. Mehta and James M. Delahay (2004).
Roof Components and Cladding:
θ <= 7 deg. 7 deg. < θ <= 27 deg. 27 deg. < θ <= 45 deg.
Roof Zones for Buildings with h <= 60 ft.
(for Gable Roofs <= 45 o and Monoslope Roofs <= 3 o
Roof Zones for Buildings with h > 60 ft.
(for Gable Roofs <= 10 o and Monoslope Roofs <= 3 o
WIND LOADING ANALYSIS - Wall Components and Cladding Per ASCE 7-10 Code for Buildings of Any Height
Using Part 1 & 3: Analytical Procedure (Section 30.4 & 30.6)
Job Name: Monacan Health Clinic Subject:
Job Number: 21-191 Originator: ZKS Checker:
Input Data:
Wind Speed, V = 115 mph (Wind Map, Figure 26.5-1A-C)
Bldg. Classification = II (Table 1.5-1 Risk Category)
Exposure Category = C (Sect. 26.7)
Ridge Height, hr = 24.67 ft. (hr >= he)
Eave Height, he = 12.00 ft. (he <= hr)
Building Width = 164.50 ft. (Normal to Building Ridge)
Building Length = 173.25 ft. (Parallel to Building Ridge)
Roof Type = Gable (Gable or Monoslope)
Topo. Factor, Kzt = 1.00 (Sect. 26.8 & Figure 26.8-1)
Direct. Factor, Kd = 0.85 (Table 26.6)
Enclosed? (Y/N) Y (Sect. 28.6-1 & Figure 26.11-1)
Hurricane Region? N
Component Name = Wall (Girt, Siding, Wall, or Fastener)
Effective Area, Ae = 10 ft.^2 (Area Tributary to C&C)
Resulting Parameters and Coefficients:
Roof Angle, θ = 8.76 deg.
Mean Roof Ht., h = 12.00 ft. (h = he, for roof angle <=10 deg.)
Wall External Pressure Coefficients, GCp:
GCp Zone 4 Pos. = 0.90 (Fig. 30.4-1, GCp is reduced by 10% for roof angle <=10 deg. )
GCp Zone 5 Pos. = 0.90 (Fig. 30.4-1, GCp is reduced by 10% for roof angle <=10 deg. )
GCp Zone 4 Neg. = -0.99 (Fig. 30.4-1, GCp is reduced by 10% for roof angle <=10 deg. )
GCp Zone 5 Neg. = -1.26 (Fig. 30.4-1, GCp is reduced by 10% for roof angle <=10 deg. )
Positive & Negative Internal Pressure Coefficients, GCpi (Figure 26.11-1):
+GCpi Coef. = 0.18 (positive internal pressure)
-GCpi Coef. = -0.18 (negative internal pressure)
If z <= 15 then: Kz = 2.01*(15/zg)^(2/α) , If z > 15 then: Kz = 2.01*(z/zg)^(2/α) (Table 30.3-1) α = 9.50 (Table 26.9-1) zg = 900 (Table 26.9-1)
Kh = 0.85 (Kh = Kz evaluated at z = h)
Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2 (Sect. 30.3.2, Eq. 30.3-1) qh = 24.43 psf qh = 0.00256*Kh*Kzt*Kd*V^2 (qz evaluated at z = h)
Design Net External Wind Pressures (Sect. 30.4 & 30.6):
For h <= 60 ft.: p = qh*((GCp) - (+/-GCpi)) (psf)
For h > 60 ft.: p = q*(GCp) - qi*(+/-GCpi) (psf) where: q = qz for windward walls, q = qh for leeward walls and side walls qi = qh for all walls (conservatively assumed per Sect. 30.6) θ o
L
B hr he h
Plan
Elevation
L
Wind Load Tabulation for Wall Components & Cladding
Component z Kh qh p = Net Design Pressures (psf)
(ft.) (psf) Zone 4 (+) Zone 4 (-) Zone 5 (+) Zone 5 (-)
Wall 0 0.85 24.43 26.38 -28.58 26.38 -35.18
15.00 0.85 24.43 26.38 -28.58 26.38 -35.18
20.00 0.85 24.43 26.38 -28.58 26.38 -35.18
For z = hr: 24.67 0.85 24.43 26.38 -28.58 26.38 -35.18
For z = he: 12.00 0.85 24.43 26.38 -28.58 26.38 -35.18
For z = h: 12.00 0.85 24.43 26.38 -28.58 26.38 -35.18
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Width of Zone 5 (end zones), 'a' = 6.58 ft.
3. Per Code Section 30.2.2, the minimum wind load for C&C shall not be less than 16 psf.
4. References : a. ASCE 7-10, "Minimum Design Loads for Buildings and Other Structures".
b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" by: Kishor C. Mehta and James M. Delahay (2004).
Wall Components and Cladding:
Wall Zones for Buildings with h <= 60 ft.
Wall Zones for Buildings with h > 60 ft.
Siesmic Loads (ASCE 7, Chapter 11):
Lat:
Long:
Site Class: D (default)
II
Importance Factor: IE = 1.00
Mapped Spectral Acceleration Perameters: SS = 0.157g
S1 = 0.057g
SDS=
SD1=
Seismic Design Category: B
Geotechnical Information:
Minimum Frost Depth: hfrost = 3'-0" Heated
Geotechnical Consultant:
Report Number:
Report Date:
ECS Mid-Atlantic, LLC
12:19292
10-Jun-21
79.118° W
Spectral Response Coefficients: 0.167g
0.091g
Allowable Soil Bearing Pressure: Psoil = 2,000 psf
Risk Category:
Site Coordinates: 37.478° N
����� ������-���/����&$�-���01 ���
23456789:;<5=4>?<:
@AA53BBC #$*��+�� ������ ,�D�.
����� ������D�/����&$�D
0+�
E<<5A?:4>3BC #$��$$%&�'D�)$%���$'*��
FG3H4>?<:C %�&�I�
J?=3B>4=KC ����)��)������������*�$L
M4N45A8JOK3C +��� ��
P3;353:63
Q<6R=3:>C
�+�S$)�*
P?BT8E4>3U<5OC VV
2?>38EG4BBC W
XEFP8M<5?N<:>4G8P3BK<:B382K36>5R= Q3B?U:8M<5?N<:>4G8P3BK<:B382K36>5R=
Y4B?68Z454=3>35B
[4=3 \4GR3 Q3B65?K>?<:
++ ���&$ .�S]������
+� ���&$ .�S]������
�I��
�I��
+W+ ���*$ a� ��������� ���
+W� ���%� a� ��������� ��� b@AA?>?<:4G89:;<5=4>?<:
[4=3 \4GR3 Q3B65?K>?<:
+W� c +��� ��� d ���I�� �����I d̀ ��� +���� ���I�� �����I efghij klmnopqrqsrmqloonotrmqurprqvwxwyqznn{|l
� � � * ' �� �� Z35?<A8}B~
24}U~
� � � * ' �� �� Z35?<A8}B~
24}U~
����� ������-���/����&$�-���01 ���
�2+ ��%#* ���33��������3����4�5����6
�2� ��%�� ���33��������3����4�5����6
78� ���'# .�98��� 4������
:78� ��* +���� ���3�� �����3 ��78�
78�. ���## +���� � �3�� 4������
�5�6
+�2� ���&$ 7��� ������������4)� � ������5����6
+�0 ���*' :
����3�� )� �����5�-����� ��������3
��6
����5����6
+�2� ���&$ 7��� ������������4)� � ������5����6
+�0 ���*� :
����3�� )� �����5�-����� ��������3
��6
����5����6
78� ����578�6
>?@AB@CDEFCAGHIGJKF@IA?@B@ALMANM>AB@OE@JFAKHPACFKF@AQBAEQJKEAKR@HIR@HFCAFQAF?@ASKED@CAQBAKHPAI@EGH@KFGQHAEGH@CARKI@AIDBGHTAF?@AUDGEIGHTAJQI@
KIQVFGQHAVBQJ@CCWAXC@BCAC?QDEIAJQHOGBRAKHPAQDFVDFAQUFKGH@IAOBQRAF?GCAFQQEAYGF?AF?@AEQJKEAZDF?QBGFPA[KSGHTA\DBGCIGJFGQHAU@OQB@AVBQJ@@IGHTAYGF?
I@CGTHW
]̂_̀ab̂cde
��������0�+��8������� ��+��=���+��� ���<������f���+��=����� f�����������3�� ��������������g�����
�������3������� ������3��� ��������3���
�=���3�� ������3����� ��g����� ����3������
�����3��������3�� �h� � �����3�������� ����������3������ ��g�� �4��,�� ����������3��� ��3��� �����g����
��������������3��������� ��3�� �����i���� ��3���������3������ ���������������������3���������������=�
0������3�������3�� �����3�� ������,������� �������3�� �����������0����3�������������3������,�������
����������������3������� �����3�����������
FOUNDATION
st Avenue West, Suite One, Duluth, Minnesota 55806, voice (218) 727-5995, fax (218) 727-7779
Northland
NCE
ZKS
21-191
Monacan Health Clinic
SK - 2
June 15, 2021 at 1:44 PM
Barrel Roof Structure - MOD. ROO...
X
Z
Results for LC 1, D+S (w/ Drift)
Company : NCE June 15, 2021 1:47 PMDes igner : ZKS
Job Number : 21-191 Checked By: TDR Model Name : Monacan Health Clinic
Concrete Properties Label E [ksi] G [ksi] Nu Therm (/1E ...Density[k/ft... f'c[ksi] Lambda Flex Steel[... Shear S tee...
1 Conc4000NW 3644 1584 0.15 0.6 0.145 4 1 60 60
Masonry Properties Label E [ksi] G [ksi] Nu Therm (/1E5...Self Weight[... f'm[ks i] Flex Steel[ksi]Shear S teel[...
1 Concrete Matl 1350 540 0.25 0.6 Custom 1.5 60 60 2 C lay Matl 1050 420 0.25 0.6 Custom 1.5 60 60 3 G en Masonry 1050 420 0.25 0.6 0.08 1.5 60 60
Wall Footing Code Check Label Top Flex...Top Flex...Bot Flex ...Bot Flex ...Heel She... Heel She... Toe She...Toe She...Phi * Mn...Phi * Vn...Phi * Mn...Phi * Vn...
1 WF1 0(Toe) NC 0.005(T... 3 0.032 4 0 3 3.691 9.89 10.052 9.89 2 WF2 0(Toe) NC 0.014(H... 4 0.031 3 0 4 3.691 9.89 10.052 9.89 3 WF3 0(Toe) NC 0.023(T... 3 0.03 4 0.002 3 3.691 9.89 10.052 9.89 4 WF4 0(Toe) NC 0.007(T... 3 0.032 4 0 3 3.691 9.89 10.052 9.89 5 WF5 0(Toe) NC 0.008(T... 3 0.032 4 0 3 3.691 9.89 10.052 9.89 6 WF6 0(Toe) NC 0.033(H... 3 0.029 4 0.003 3 3.691 9.89 10.052 9.89 7 WF7 0(Toe) NC 0.033(H... 4 0.029 3 0.002 4 3.691 9.89 10.052 9.89 8 WF8 0(Toe) NC 0.003(T... 3 0.032 4 0 3 3.691 9.89 10.052 9.89 9 WF11 0(Toe) NC 0.007(H... 3 0.032 4 0 3 3.691 9.89 10.052 9.89 10 WF12 0(Toe) NC 0.011(H... 3 0.031 4 0 3 3.691 9.89 10.052 9.89 11 WF13 0(Toe) NC 0.007(T... 3 0.032 4 0 3 3.691 9.89 10.052 9.89 12 WF14 0(Toe) NC 0.052(H... 3 0.028 4 0.005 3 3.691 9.89 10.052 9.89 13 WF15 0(Toe) NC 0.017(T... 4 0.031 3 0.002 4 3.691 9.89 10.052 9.89 14 WF16 0(Toe) NC 0.016(T... 4 0.031 3 0.002 4 3.691 9.89 10.052 9.89
Wall Footing Steel Label Int Wall Verts Ext Wall Verts Wall Horz Bars Foot Top Bars Foot Bot Bars Foot Long Bars Dowel Bars
1 WF1 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 2 WF2 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 3 WF3 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 4 WF4 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 5 WF5 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 6 WF6 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 7 WF7 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 8 WF8 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 9 WF11 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 10 WF12 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 11 WF13 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 12 WF14 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 13 WF15 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in 14 WF16 #5@ 32"in #5@ 14in #5@ 12in #5@ 32in
Masonry Wall Code C heck (TMS 402-16: ASD) Wall Panel Combined ... LC Shear UC LC UC Max Dowel Fa[ks i] Fb[ksi] Fv[ksi]
1 WF1 0.04 2 0.003 2 0.004 0.366 0.675 0.044
2 WF2 0.175 1 0.011 1 0.016 0.366 0.675 0.044
3 WF3 0.068 1 0.001 1 0.001 0.366 0.675 0.044
4 WF4 0.075 1 0.005 1 0.008 0.366 0.675 0.044
5 WF5 0.129 1 0.008 1 0.014 0.366 0.675 0.044
6 WF6 0.102 2 0.005 2 0.006 0.366 0.675 0.044
RISAFoundation Version 13.0.1 Page 1 [S:\...\...\...\...\...\Barrel Roof Structure - MOD. ROOF HEIGHTS.rfl]
1:47 PMDes igner : ZKS
Job Number : 21-191 Checked By: TDR Model Name : Monacan Health Clinic
Masonry Wall Code C heck (TMS 402-16: ASD) (C ontinued) Wall Panel Combined ... LC Shear UC LC UC Max Dowel Fa[ks i] Fb[ksi] Fv[ksi]
7 WF7 0.385 1 0.028 1 0.034 0.366 0.675 0.044
8 WF8 0.043 2 0.003 2 0.005 0.366 0.675 0.044
9 WF11 0.034 1 0.002 1 0.003 0.366 0.675 0.044
10 WF12 0.068 1 0.004 1 0.006 0.366 0.675 0.044
11 WF13 0.033 1 0.001 1 0.002 0.366 0.675 0.044
12 WF14 0.126 1 0 1 0 0.366 0.675 0.044
13 WF15 0.048 2 0 N/A 0 0.366 0.675 0.039
14 WF16 0.044 2 0 1 0.001 0.366 0.675 0.044
Designer : ZKS
Footing 1 - R3D_N54Job Number : 21-191 Checked By:_____
Sketch
4 ft f t
1.333 ft
.3 f t
16 in i n
A B
CD
x z i n i n
CD
Details x z
A B
CD
#6@15 in
4 ft f t
#6@15 in x Dir. Steel: 1.77 in
(4 #6) z Dir. Steel: 1.77 in
(4 #6)
Bottom Rebar Plan i n i n
.5 i n
#4@12 in
CD
Footing Elevation
.5 i n
16 in i n
4#6
Pedestal Rebar Plan
RISAFoundation Version 12.0.2 [S:\...\...\...\...\...\Barrel Roof Structure - MOD. ROOF HEIGHTS.rfl] Page 1
Footing 1 - R3D_N54Job Number : 21-191 Checked By:_____
Geometry, Materials and Criteria
Length : eX : Net Allowable Bearing : Steel fy :
Width : eZ : Concrete Weight : Minimum Steel :
Thickness : pX : Concrete f'c : Maximum Steel :
Height : pZ : Design Code :
Rot. Angle :
Footing Top Bar Cover : Overturning / Sliding SF : Phi for Flexure :
Footing Bottom Bar Cover : Coefficient of Friction : Phi for Shear :
Pedestal Longitudinal Bar Cover : Passive Resistance of Soil :
4 ft 0 in 2 ksf (net) 60 ksi
4 ft 0 in 0.145 k/ft^3 .0018 12 in 16 in 4 ksi .0075 36 in 16 in ACI 318-14 45 deg
1.5 in 1 0.9
1.5 in 0.3 0.75
1.5 in 0 k 0.65
Loads
P (k) Vx (k) Vz (k) Mx (k-ft) Mz (k-ft) Overburden (ksf)
DL
SL
SLN
OL1
0.110.591 7.985 1.131 1.165
+P +Vx
A D
+Vz
D C
+Mx
D C
+Mz
A D
+Over
Soil Bearing
Description Categories and Factors Gross Allow.(ksf) Max Bearing (ksf) Max/Allowable Ratio
D+S (w/ Drift.. 1DL+1SL+1OL1+1HL 2.282 1.516 (A) 0.664
D+S (w/ Slidi.. 1DL+1SL+1SLN+1HL 2.282 1.514 (A) 0.663
A B
CD
1DL+1SL+1OL1+..
QA:
QB:
QC:
QD:
NAZ:
NAX:
1.516 ksf
1.516 ksf
1.516 ksf
1.516 ksf -1 in -1 in
A B
CD
1DL+1SL+1SLN+..
QA:
QB:
QC:
QD:
NAZ:
NAX:
1.514 ksf
1.514 ksf
1.514 ksf
1.514 ksf -1 in -1 in
Footing Flexure Design (Bottom Bars)
As-min x-dir (Top Flexure): 0 in^2 As-min z-dir (Top Flexure): 0 in^2
As-min x-dir (T & S) : 1.037 in^2 As-min z-dir (T & S) : 1.037 in^2
As-min x-dir (Bot Flexure) : 1.037 in^2 As-min z-dir (Bot Flexure) : 1.037 in^2 z-Dir As z-Dir As x-Dir As x-Dir As Mu-xx Mu-xx Required Provided Mu-zz Mu-zz Required Provided
Description Categories and Factors UC Max (k-ft) (in^2) (in^2) UC Max (k-ft) (in^2) (in^2)
1.2D+1.6S (.. 1.2DL+1.6SL+1.6O.. 0.08321 6.24 0.143 1.767 0.08321 6.24 0.143 1.767 1.2D+1.6S (.. 1.2DL+1.6SL+1.6S.. 0.08305 6.22 0.142 1.767 0.08305 6.22 0.142 1.767
RISAFoundation Version 12.0.2 [S:\...\...\...\...\...\Barrel Roof Structure - MOD. ROOF HEIGHTS.rfl] Page 2
Footing 1 - R3D_N54Job Number : 21-191 Checked By:_____
Footing Shear Check
Two Way (Punching) Vc: One Way (x Dir. Cut) Vc One Way (z Dir. Cut) Vc:254.057 k 59.198 k 59.198 k
Punching x Dir. Cut z Dir. Cut Description Categories and Factors Vu(k) Vu/ Vc Vu(k) Vu/ Vc Vu(k) Vu/ Vc
1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6OL1+1.6HL 19.987 0.105 3.654 0.082 3.654 0.082 1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6SLN+1.6HL 19.949 0.105 3.647 0.082 3.647 0.082
Pedestal Design
Shear Check Results (Envelope):
Vc (k) Vs (k) Vu (k) Vu/phi*Vn phi Gov LC
Shear Along x Direction: 27.575 26.753 0 0 0.75 NC Shear Along z Direction: 27.575 26.753 0 0 0.75 NC Pedestal Ties : #4 @ 12 in
Bending Check Results (Envelope): PCA Load Contour Method (for biaxial) Unity Check : 0.056 Pu : 28.277 k Pn : 776.336 k Governing LC : 3 Pedestal Bars : 4 #6
Phi : 0.65 Mux : 0 k-ft Mnx : NC Mnox : NC % Steel : 0.6903
Parme Beta : 0.65 Muz : 0 k-ft Mnz : NC Mnoz : NC
Concrete Bearing Check (Vertical Loads Only)
Bearing Bc : 1740.8 k
Description Categories and Factors Bearing Bu (k) Bearing Bu/ Bc
1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6OL1+1.6HL 28.277 0.025
1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6SLN+1.6HL 28.223 0.025
Overturning Check (Service)
Description Categories and Factors Mo-xx (k-ft) Ms-xx (k-ft) Mo-zz (k-ft) Ms-zz (k-ft) OSF-xx OSF-zz
D+S (w/ Drift.. 1DL+1SL+1OL1+1HL 0 48.512 0 48.512 NA NA D+S (w/ Slidi.. 1DL+1SL+1SLN+1HL 0 48.446 0 48.446 NA NA
Mo-xx: Governing Overturning Moment about AD or BC
Ms-xx: Governing Stablizing Moment about AD or BC
OSF-xx: Ratio of Ms-xx to Mo-xx
Sliding Check (Service)
Description Categories and Factors Va-xx (k) Vr-xx (k) Va-zz (k) Vr-zz (k) SR-xx SR-zz
D+S (w/ Drift.. 1DL+1SL+1OL1+1HL 0 7.277 0 7.277 NA NA
D+S (w/ Slidi.. 1DL+1SL+1SLN+1HL 0 7.267 0 7.267 NA NA
Va-xx: Applied Lateral Force to Cause Sliding Along xx Axis
Vr-xx: Resisting Lateral Force Against Sliding Along xx Axis
SR-xx: Ratio of Vr-xx to Va-xx
RISAFoundation Version 12.0.2 [S:\...\...\...\...\...\Barrel Roof Structure - MOD. ROOF HEIGHTS.rfl] Page 3
Footing 2 - FLR_1_N324Job Number : 21-191 Checked By:_____
Sketch
5 ft f t
1.833 ft
.8 f t
16 in i n
A B
CD
x z i n i n
CD
Details x z
A B
CD
#6@14 in
5 ft f t
#6@14 in x Dir. Steel: 2.21 in
(5 #6) z Dir. Steel: 2.21 in
(5 #6)
Bottom Rebar Plan i n i n
.5 i n
#4@12 in
CD
Footing Elevation
.5 i n
16 in i n
4#6
Pedestal Rebar Plan
RISAFoundation Version 12.0.2 [S:\...\...\...\...\...\Barrel Roof Structure - MOD. ROOF HEIGHTS.rfl] Page 1
Footing 2 - FLR_1_N324Job Number : 21-191 Checked By:_____
Geometry, Materials and Criteria
Length : eX : Net Allowable Bearing : Steel fy :
Width : eZ : Concrete Weight : Minimum Steel :
Thickness : pX : Concrete f'c : Maximum Steel :
Height : pZ : Design Code :
Rot. Angle :
Footing Top Bar Cover : Overturning / Sliding SF : Phi for Flexure :
Footing Bottom Bar Cover : Coefficient of Friction : Phi for Shear :
Pedestal Longitudinal Bar Cover : Passive Resistance of Soil :
5 ft 0 in 2 ksf (net) 60 ksi
5 ft 0 in 0.145 k/ft^3 .0018 12 in 16 in 4 ksi .0075 36 in 16 in ACI 318-14 45 deg
1.5 in 1 0.9
1.5 in 0.3 0.75
1.5 in 0 k 0.65
Loads
P (k) Vx (k) Vz (k) Mx (k-ft) Mz (k-ft) Overburden (ksf)
DL
SL
SLN
OL1
0.115.094 11.364 1.445 1.805
+P +Vx
A D
+Vz
D C
+Mx
D C
+Mz
A D
+Over
Soil Bearing
Description Categories and Factors Gross Allow.(ksf) Max Bearing (ksf) Max/Allowable Ratio
D+S (w/ Drift.. 1DL+1SL+1OL1+1HL 2.269 1.399 (A) 0.617
D+S (w/ Slidi.. 1DL+1SL+1SLN+1HL 2.269 1.385 (A) 0.61
A B
CD
1DL+1SL+1OL1+..
QA:
QB:
QC:
QD:
NAZ:
NAX:
1.399 ksf
1.399 ksf
1.399 ksf
1.399 ksf -1 in -1 in
A B
CD
1DL+1SL+1SLN+..
QA:
QB:
QC:
QD:
NAZ:
NAX:
1.385 ksf
1.385 ksf
1.385 ksf
1.385 ksf -1 in -1 in
Footing Flexure Design (Bottom Bars)
As-min x-dir (Top Flexure): 0 in^2 As-min z-dir (Top Flexure): 0 in^2
As-min x-dir (T & S) : 1.296 in^2 As-min z-dir (T & S) : 1.296 in^2
As-min x-dir (Bot Flexure) : 1.296 in^2 As-min z-dir (Bot Flexure) : 1.296 in^2 z-Dir As z-Dir As x-Dir As x-Dir As Mu-xx Mu-xx Required Provided Mu-zz Mu-zz Required Provided
Description Categories and Factors UC Max (k-ft) (in^2) (in^2) UC Max (k-ft) (in^2) (in^2)
1.2D+1.6S (.. 1.2DL+1.6SL+1.6O.. 0.14313 13.41 0.307 2.209 0.14313 13.41 0.307 2.209 1.2D+1.6S (.. 1.2DL+1.6SL+1.6S.. 0.14107 13.22 0.303 2.209 0.14107 13.22 0.303 2.209
RISAFoundation Version 12.0.2 [S:\...\...\...\...\...\Barrel Roof Structure - MOD. ROOF HEIGHTS.rfl] Page 2
Footing 2 - FLR_1_N324Job Number : 21-191 Checked By:_____
Footing Shear Check
Two Way (Punching) Vc: One Way (x Dir. Cut) Vc One Way (z Dir. Cut) Vc:254.057 k 73.997 k 73.997 k
Punching x Dir. Cut z Dir. Cut Description Categories and Factors Vu(k) Vu/ Vc Vu(k) Vu/ Vc Vu(k) Vu/ Vc
1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6OL1+1.6HL 32.548 0.171 8.145 0.147 8.145 0.147 1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6SLN+1.6HL 32.079 0.168 8.028 0.145 8.028 0.145
Pedestal Design
Shear Check Results (Envelope):
Vc (k) Vs (k) Vu (k) Vu/phi*Vn phi Gov LC
Shear Along x Direction: 27.575 26.753 0 0 0.75 NC Shear Along z Direction: 27.575 26.753 0 0 0.75 NC Pedestal Ties : #4 @ 12 in
Bending Check Results (Envelope): PCA Load Contour Method (for biaxial) Unity Check : 0.079 Pu : 40.109 k Pn : 776.336 k Governing LC : 3 Pedestal Bars : 4 #6
Phi : 0.65 Mux : 0 k-ft Mnx : NC Mnox : NC % Steel : 0.6903
Parme Beta : 0.65 Muz : 0 k-ft Mnz : NC Mnoz : NC
Concrete Bearing Check (Vertical Loads Only)
Bearing Bc : 1740.8 k
Description Categories and Factors Bearing Bu (k) Bearing Bu/ Bc
1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6OL1+1.6HL 40.109 0.035
1.2D+1.6S (w/.. 1.2DL+1.6SL+1.6SLN+1.6HL 39.534 0.035
Overturning Check (Service)
Description Categories and Factors Mo-xx (k-ft) Ms-xx (k-ft) Mo-zz (k-ft) Ms-zz (k-ft) OSF-xx OSF-zz
D+S (w/ Drift.. 1DL+1SL+1OL1+1HL 0 87.456 0 87.456 NA NA D+S (w/ Slidi.. 1DL+1SL+1SLN+1HL 0 86.557 0 86.557 NA NA
Mo-xx: Governing Overturning Moment about AD or BC
Ms-xx: Governing Stablizing Moment about AD or BC
OSF-xx: Ratio of Ms-xx to Mo-xx
Sliding Check (Service)
Description Categories and Factors Va-xx (k) Vr-xx (k) Va-zz (k) Vr-zz (k) SR-xx SR-zz
D+S (w/ Drift.. 1DL+1SL+1OL1+1HL 0 10.495 0 10.495 NA NA
D+S (w/ Slidi.. 1DL+1SL+1SLN+1HL 0 10.387 0 10.387 NA NA
Va-xx: Applied Lateral Force to Cause Sliding Along xx Axis
Vr-xx: Resisting Lateral Force Against Sliding Along xx Axis
SR-xx: Ratio of Vr-xx to Va-xx
RISAFoundation Version 12.0.2 [S:\...\...\...\...\...\Barrel Roof Structure - MOD. ROOF HEIGHTS.rfl] Page 3
Company : June 15, 2021 Designer :
Wall Footing : WF1Job Number : Checked By:_____
Sketch
6 in i n
.3 f t
.3 f t
1.3 ft
1.3 ft
.3 f t
3 in
2.69 in
#5 @ 12in oc
#5 @ 12in oc
#5 @ 24" oc
RISAFoundation Version 13.0.1 Page 1 [S:\...\...\Monacan Clinic\Eng\retaining wall.fnd]
Loading Diagram
0.4 k/ft
0.68 ksf
0.26 ksf
0.44 ksf
1.04 ksf
0.01 ksf
0.2 ksf
0.24 ksf0.46 ksf
RISAFoundation Version 13.0.1 Page 2 [S:\...\...\Monacan Clinic\Eng\retaining wall.fnd]
Geometry, Materials and Criteria
General/Geometry
Start Point : N1 End Point : N2
Wall Length : 22 ft Wall Height : 5.34 ft Wall Propped ? : NO
Footing Criteria
Concrete Code : ACI 318-14 Foot Toe Len. : 1.25 ft Foot Heel Len. : 1.25 ft Foot Thickness : 12 in Foot Top Cover : 3 in Foot Bot Cover : 3 in
Foot Bot Bar : #5@12 in Foot Long Bar : #5@12 in Foot bar Location : Single Layer
Shear Key ? : NO
Wall Materials & Criteria
Design Code : ACI 530-13: ASD Material : Masonry Reinforced : Yes
Blk Nom Width : 6" Blk Grouting : Fully Grouted Wall Vert Bar : #5 Wall Bar Location : Center Wall Grt/Bar Spacing: 24" Cover : 2.5 in Eq Sld Thickness: 5.625 in An c/c of reinf : 135 in2
Masonry f'm : 1.5 ksi Masonry Em : 1350 ksi Steel fy : 60 ksi Steel E : 29000 ksi
Blk Material : Conc 115 pcf Grt Weight : 140 pcf Wall Dead Wt : 0.058 ksf Mortar Type : Type M or S Cement Type : Portland, Lime/Mortar Wall Area : NCMA
Soil Criteria
Heel Soil Height : 5.34 ft Toe Soil Height : 2.34 ft θBackfill Angle( ): 0 deg Water Height : 0 ft Heel Surcharge : 0.04 ksf γ Heel : 0.12 k/ft^3
Φ ' Heel : 30 deg
Lat HeelK : 0.3 (Active)
Wall Design
LC 1 DIAGRAMS
Max: 0.71 at 0 ft
Min: 0.4 at 5.34 ft
P k/ft
Max: 0.267 at 1.068 ft
Min: 0 at 5.34 ft
V k/ft
Max: 0 at 5.073 ft
Min: -0.79 at 0 ft
M k-ft/ft
ACI 530-13: ASD Code Check
COMBINED CHECKS
(fa + fb) / Fb : 0.961 fa/Fa : 0.03 fs/Fs : 0.778
AXIAL SUMMARY
fa : 0.011 ksi
Fa : 0.345 ksi
BENDING SUMMARY
fb : 0.638 ksi
Fb : 0.675 ksi fs : 24.907 ksi
Fs : 32 ksi
SHEAR CHECKS
fv/Fv : 0.091
SHEAR SUMMARY
fv : 0.004 ksi
Fv : 0.044 ksi
Fv max : 0.077 ksi
RISAFoundation Version 13.0.1 Page 3 [S:\...\...\Monacan Clinic\Eng\retaining wall.fnd]
Company : June 15, 2021 3:39 PMDesigner :
Job Number : Checked By:_____ Model Name :
DESIGN DETAILS
AXIAL DETAILS
Max Axial : 0.71 k/ft
Location : 0 ft
Load Comb : 1
Rad gyration r : 1.62 in h'/r : 39.556
BENDING DETAILS
Max Moment : 0.79 k-ft/ft
Location : 0 ft
Load Comb : 1 k : 0.355 d : 2.813 in j : 0.882
SHEAR DETAILS
Max Shear : 0.268 k/ft
Location : 1.068 ft
Load Comb : 1
Width for Shear : 24 in
Corresponding M: 0.53 k-ft/ft
Corresponding P : 0.648 k/ft
M / (V*d) : 1
Gammag : 1
UC Max Dowel : 0.039 µ : 1 vfA : 0.153 in^2/ft
Dowel Bars : #5@24in
ENVELOPED WALL FORCES (NOT USED FOR DESIGN)
M in Plane : 0 k-ft (LC : 1) V in Plane : 0 k (LC : 1)
Footing Design
As-min z-dir (Top Flexure): 0.259 in^2/ft As-min z-dir (Bot Flexure) : 0.259 in^2/ft z-dir (T & S) : 0.259 in^2/ft x-dir Long. (T & S) : 0.778 in^2
Bottom Bar Design (Toe) : Shear (Toe) Mu UC Gov Mu Max Mu Phi*Mn As Req'd As Prov'd Vu UC Gov Vu Vu Phi*Vn
Max LC (k-ft/ft) (k-ft/ft) (in^2/ft) (in^2/ft) Max LC (k/ft) (k/ft)
0.056 2 0.655 11.682 0.017 0.307 0.048 2 0.473 9.89
Top Bar Design (Heel) : Shear (Heel) Mu UC Gov Mu Max Mu Phi*Mn As Req'd As Prov'd Vu UC Gov Vu Vu Phi*Vn
Max LC (k-ft/ft) (k-ft/ft) (in^2/ft) (in^2/ft) Max LC (k/ft) (k/ft)
0.099 2 0.421 4.262 0.028 0.307 0.151 2 0.57 3.771
Overturning Check (Service)
Moverturn Mresist Description Categories and Factors (k-ft/ft) (k-ft/ft) SF SF Min SF Min/SF
Service 1DL+1LL+1HL 1.77 4.655 2.629 1.5 0.57
Sliding Check (Service)
Vsliding Vresist Description Categories and Factors (k/ft) (k/ft) SF SF Min SF Min/SF
Service 1DL+1LL+1HL 0.8 1.883 2.354 1.5 0.637
Soil Bearing Check (Service)
Max Bearing Bearing Allowed Bearing Description Categories and Factors (ksf) (ksf) UC
Service 1DL+1LL+1HL 1.041 3 0.347
RISAFoundation Version 13.0.1 Page 4 [S:\...\...\Monacan Clinic\Eng\retaining wall.fnd]
FRAMING
st Avenue West, Suite One, Duluth, Minnesota 55806, voice (218) 727-5995, fax (218) 727-7779
Northland
NCE
ZKS
21-191
Monacan Health Clinic
Floor Plan 1 SK - 1
June 15, 2021 at 1:15 PM
Barrel Roof Structure - MOD. ROO...
k k
3- 1.
X
FS
8k
8k
3- 1.
X
FS
9k k
3- 1.
X
FS
7k6k 3-1.75X14FS
1k 1k
3- 1.
X
FS
6k
7k
3-1.75X
14FS
1k
1k
3-1.75X
14FS
7k
5k
3-1.75X
14FS
1k
1k
3- 1.
X
FS
4k
5k
3- 1.
X
FS
4k
5k
3- 1.
X
FS
4k
7k
3-1.75X
14FS
3k
3k
3-1.75X
14FS
8k
4k
3-1.75X
14FS
1k1k TJI 110_14
1k1kTJI 110_14
1k 1kTJI 110_14
1k1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 210_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14 k k
T J I k1 k T
J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
-1
.7 X
F
S k k
-1
.7 X
F
S k k
-1
.7 X
F
S k k
3- 1.
X
FS
k k
3- 1.
X
FS
8k
9k
3- 1.
X
FS
5k 7k3-1.75X14FS 4k 4k3-1.75X14FS 3k 3k3-1.75X14FS1 k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
T J I k k
-1
.7 X
F
S
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
1k 1kTJI 110_14
2k 1kTJI 110_14
2k 1kTJI 210_14
2k 2kTJI 230_14
2k 2kTJI 360_14
2k 2kTJI 560_14
2k 2kTJI 560_14
2k 2kTJI 560_14
2k 2kTJI 560_14
2k 2kTJI 560_14
2k 2kTJI 560_14
2k 2kTJI 560_14
2k 1kTJI 360_14
2k 1kTJI 360_14
2k 1kTJI 360_14
2k 1kTJI 360_14
1k1 k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k 1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
2k
1k
TJ
I 1
_1
2k
1k
TJ
I 2
_1
2k
1k
TJ
I 3
_1
2k
1k
TJ
I 3
_1
2k
1k
TJ
I 2
_1
2k
1k
TJ
I 2
_1
2k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k 1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 2
_1
1k
1k
TJ
I 2
_1
1k
1k
TJ
I 3
_1
1k
1k
TJ
I 3
_1
1k
1k
TJ
I 2
_1
1k
1k
TJ
I 2
_1
2k
1k
TJ
I 3
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
2k
TJ
I 1
_1
1k
2k
TJ
I 2
_1
1k
2k
TJ
I 2
_1
1k
2k
TJ
I 2
_1
1k
2k
TJ
I 2
_1
1k
2k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
1k
TJ
I 1
_1
1k
2k
TJ
I 3
_1
2k
2k
TJ
I 3
_1
2k
2k
TJ
I 5
_1
1k
2k
TJ
I 3
_1
2k
2k
TJ
I 3
_1
2k
2k
TJ
I 5
_1
1k1k3-1.75X14FS
Y
X
Z
Lateral Gravity
Member Camber and Reactions
1:26 PMDes igner : ZKS
Job Number : 21-191 Checked By: TDR Model Name : Monacan Health Clinic
Deck Loads Label Two W ay Self Wt [ksf] Super DL [ksf] Const DL [ksf] Const LL [ksf]
1 Wood 0.003 0 0 0.02
Uniform Area Loads Label Additive P reDL[ksf] PostDL[ksf] LL[ksf] LL Type VL[ksf] Dyn Load[ksf]
1 Roof 0.02 0.02 SL 0.011 0.01 2 Mech #1 Yes 0.05 LL-Non 0.011 3 SLIDING SNOW Yes 0.014 SLN 0.011
Line Loads : Floor Plan 1 S tart P oint End Point S tart P re... End PreD...S tart P ost...End Pos t... S tart LL[k...End LL[k/ft] LL Type S t Dyn Load[k/...End Dyn Load[...
1 N32 N2 0.048 0.048 LL-Non 2 N33 N25 0.048 0.048 LL-Non 3 N5 N12 0.024 0.024 LL-Non 4 N10 N7 0.036 0.036 LL-Non 5 N9 N8 0.036 0.036 LL-Non 6 N19 N20 0.024 0.024 LL-Non 7 N6 N21 0.04 0.04 LL-Non 8 N11 N27 0.04 0.04 LL-Non
9 N11 N27 0.05 0.05 SL
10 N6 N21 0.05 0.05 SL
Line Loads : Floor Plan 2 S tart P oint End Point S tart P re... End PreD...S tart P ost...End Pos t... S tart LL[k...End LL[k/ft] LL Type S t Dyn Load[k/...End Dyn Load[...
No Data to Print ...
Tapered Area Loads : Floor Plan 1 A Point B Point C Point D Point Base Mag[ksf] Peak Mag[ksf] Category Direction
1 N35 N36 N25 N33 0 0.027 OL1 Y
2 N37 N38 N2 N32 0 0.027 OL1 Y
3 N39 N40 N20 N19 0 0.05 OL1 Y
4 N41 N42 N43 N8 0 0.05 OL1 Y
5 N42 N33 N12 N43 0 0.05 OL1 Y
6 N44 N45 N46 N7 0 0.05 OL1 Y
7 N45 N32 N5 N46 0 0.05 OL1 Y
8 N37 N47 N21 N32 0 0.048 OL1 Y
9 N35 N48 N27 N33 0 0.048 OL1 Y
10 N41 N44 N7 N8 0 0.05 OL1 Y
Tapered Area Loads : Floor…