Attch-3-Drawings_and_Test_Results-TE-B.pdf.pdf

PDF 27 MB Posted

Attached to
W91QF4-26-B-A013 - Installation Lightning Protection (Insp-Test-Rpr)
Solicitation number
W91QF4-26-B-A013
Issued by

About this file

This is a technical test results and drawings document containing lightning protection system measurements and inspections conducted at Fort Leavenworth, Kansas during March and April 2022. The document presents detailed resistance measurements (in milli-ohms) for air terminals across 13 buildings, along with architectural drawings and test result tables. Inspections were performed on Buildings 52, 102, 132, 286, 314, 336, 399, 466, 467, 472, 474, 1156, and 1157 at various Fort Leavenworth addresses including Sherman Avenue, Meade Avenue, Chief Joseph Loop, Sedgwick Avenue, Thomas Avenue, Sheridan Drive, and Harrison Drive. The measurements document the condition of existing lightning protection systems, identifying issues such as loose air terminals, loose clamps, missing fasteners, open-circuited terminals (marked as "OPEN" in tables), and absent terminals (marked as "NO AT"). Notable findings include several terminals with high resistance values exceeding acceptable thresholds, such as Building 52 terminal 71 at 72.100 milli-ohms and Building 286 terminal 5 at 30.410 milli-ohms, indicating potential deficiencies in grounding continuity.

The inspection work was conducted across two site visits due to inclement weather during the initial March 28-April 1, 2022 trip, with follow-up measurements completed April 25-26, 2022. Each building section includes comprehensive drawings showing the locations of air terminals, ground rods, downs, thru-roof connections, and cable routing, supplemented by resistance measurement tables correlating terminal numbers to recorded values. This technical documentation serves as baseline data for the Army's lightning protection system installation, inspection, testing, and repair solicitation W91QF4-26-B-A013, with a scheduled site visit for perspective bidders on August 25, 2026, at 10:00 AM CST at Fort Leavenworth to review these systems and discuss required remediation work.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONTENTS

Contents

1 Introduction 4

2 Locations 6

2.1 Bldg 52 - 415 Sherman Ave

2.2 Bldg 102 - 101 Meade Ave

2.3 Bldg 132 - 1000 Chief Joseph Loop

2.4 Bldg 286 - 255 Sedgwick Ave

2.5 Bldg 314 - 245 Sedgwick Ave

2.6 Bldg 336 - 604 Thomas Ave

2.7 Bldg 399 - 1015 Sheridan Dr

2.8 Bldg 466 - 801 Harrison Dr

2.9 Bldg 467 - 803 Harrison Dr

2.10 Bldg 472 - 804 Harrison Dr

2.11 Bldg 474 - Harrison Dr

2.12 Bldg 1156 - 840 Sabalu Rd

CONTENTS

2.13 Bldg 1157 - 844 Sabalu Rd

INTRODUCTION

1 Introduction

• Many loose air terminals, loose clamps, and missing fasteners were observed. Some terminals provided resistance measurements and some were open circuited. Open circuited terminals are marked as such in the measurement tables.

• Every attempt was made at maintaining due diligence.

• Fort Leavenworth was visited to make measurements: from Monday, March 28th, 2022 through Friday, April 1, 2022, and on Monday, April 25 and Tuesday, April 26, 2022.

• We experienced inclement weather throughout most of the initial trip.

• On the second trip, our staff had to deploy tractor cones to keep cars from blocking the area(s) where the boom lift needed to operate.

INTRODUCTION

Nomenclature:

• Numeric value “0.343”, etc. = meter reading, in units of milli-ohms.

• “NO AT” = No air terminal present at the indicated location.

• “OPEN” = open circuit, no measured continuity.

LOCATIONS

2 Locations

2.1 Bldg 52 - 415 Sherman Ave

AT# Value AT# Value AT# Value AT# Value

1 0.340 31 4.491 61 NO AT 91 NO AT

2 1.956 32 15.700 62 NO AT 92 0.897

3 0.275 33 NO AT 63 0.974 93 0.638

4 0.429 34 3.766 64 NO AT 94 0.242

5 0.499 35 14.200 65 NO AT 95 0.519

6 0.371 36 0.658 66 0.698 96 1.174

7 0.449 37 0.714 67 NO AT 97 2.544

8 0.339 38 1.219 68 NO AT 98 0.897

9 0.639 39 NO AT 69 1.087 99 1.030

10 0.348 40 0.873 70 NO AT 100 2.276

11 0.578 41 0.873 71 72.100 101 0.401 12 0.379 42 2.475 72 4.800 102 1.897 13 0.328 43 0.319 73 3.600 103 4.234 14 0.315 44 0.319 74 4.259 104 2.924 15 0.452 45 3.370 75 2.824 105 0.592 16 0.284 46 0.383 76 0.706

17 0.613 47 3.257 77 4.440

18 NO AT 48 2.656 78 NO AT

19 1.684 49 2.475 79 6.400

20 1.289 50 NO AT 80 5.400

21 NO AT 51 0.210 81 4.400

22 0.364 52 NO AT 82 2.500

23 2.659 53 0.799 83 3.300

24 NO AT 54 0.799 84 3.300

25 1.330 55 NO AT 85 1.382

26 1.322 56 2.443 86 0.821

27 NO AT 57 NO AT 87 1.379

28 0.636 58 NO AT 88 0.562

29 14.700 59 0.673 89 1.452

30 NO AT 60 0.577 90 NO AT

Table 1: Measurements: Bldg 52 - 415 Sherman Ave

2.2 Bldg 102 - 101 Meade Ave

NO TERMINAL

31 27 22 20 16 8

36 34 28 24 17 12 4 1

32 13 9

29 26 37 35 18

3 2

33 30 23 21 19

NO TERMINAL

38 6

LightningMastCeorrporation

BLDG 102 - 101 MEADE AVE

5' 10' 8 00

LEGEND

A R TERM NAL:

GROUND RODS & DOWNS:

THRU-ROOF:

CABLE:

Figure 2: Bldg 102 - 101 Meade Ave

Terminal # Value Terminal # Value 1 0.240 31 0.310 2 0.441 32 0.280 3 0.206 33 0.238 4 0.387 34 0.341 5 0.239 35 0.350 6 0.229 36 0.350 7 0.235 37 0.344 8 0.297 38 0.239 9 0.272 39 0.234 10 0.259

12 0.877

13 1.888

14 1.690

16 0.344

17 0.844

18 29.192

19 0.314

20 0.277

21 0.349 22 0.217

23 0.304

24 1.236

25 1.444

26 1.804

27 0.329

28 2.088

29 3.443

30 0.279

Table 2: Measurements: Bldg 102 - 101 Meade Ave

2.3 Bldg 132 - 1000 Chief Joseph Loop

4 1

3 2

LightningMastCeorrporation

BLDG 132 - 1000 CHIEF JOSEPH LOOP

32' 16' 00

LEGEND

A R TERM NAL:

GROUND RODS & DOWNS:

Figure 3: Bldg 132 - 1000 Chief Joseph Loop

AT# Value

1 0.559 2 0.554 3 0.548 4 0.591

Table 3: Measurements: Bldg 132 - 1000 Chief Joseph Loop

2.4 Bldg 286 - 255 Sedgwick Ave

18 11 10 8

12 2

13 3

14 4

16 15 5 6 LightningMastCeorrporation

BLDG 286 - 255 SEDGWICK AVE

5' 10' 8 00

LEGEND

A R TERM NAL:

GROUND RODS & DOWNS:

Figure 4: Bldg 286 - 255 Sedgwick Ave

1 OPEN

2 NO AT

3 OPEN

4 OPEN

5 30.410 6 6.520

7 OPEN

8 0.410

9 OPEN

10 0.895 11 5.847

12 NO AT

13 OPEN

14 OPEN

15 0.531 16 1.608

17 OPEN

18 OPEN

Table 4: Measurements: Bldg 286 - 255 Sedgwick Ave

2.5 Bldg 314 - 245 Sedgwick Ave

LEGEND

AIR TERMINAL:

GROUND RODS & DOWNS:

THRU-ROOF:

CABLE:

12 1

11 10 9 8

13 3

14 5

15 16 7 6

LightningMastCeorrporation

00 8' 16'

BLDG 314 - 245 SEDGWICK AVE

Figure 5: Bldg 314 - 245 Sedgwick Ave

1 NO AT

2 OPEN

3 OPEN

4 OPEN

5 OPEN

6 24.475 7 0.592 8 5.680

9 OPEN

10 OPEN

11 1.179 12 23.154

13 OPEN

14 OPEN

15 6.450 16 28.000

Table 5: Measurements: Bldg 314 - 245 Sedgwick Ave

2.6 Bldg 336 - 604 Thomas Ave

BLDG 336 - 604 THOMAS AVE

LightningMastCeorrporation

8' ' 00

LEGEND

A R TERM NAL:

GROUND RODS & DOWNS:

Figure 6: Bldg 336 - 604 Thomas Ave

1 1.410 2 9.310 3 47.300

Table 6: Measurements: Bldg 336 - 604 Thomas Ave

2.7 Bldg 399 - 1015 Sheridan Dr

GROUND RODS & DOWNS:

THRU-ROOF:

CABLE:

2 1

LightningMastCeorrporation

00 ' 8'

BLDG 399 - 1015 SHERIDAN DR

Figure 7: Bldg 399 - 1015 Sheridan Dr

Terminal # Value

1 11.613 2 26.455 3 12.342

Table 7: Measurements: Bldg 399 - 1015 Sheridan Dr

2.8 Bldg 466 - 801 Harrison Dr

AIR TERM NAL:

GROUND RODS & DOWNS:

CABLE:

4 5

BLDG 466 - 801 HARRISON DR

Figure 8: Bldg 466 - 801 Harrison Dr

LightningMastCeorrporation

32' 16' 00

1 5.0235 2 2.2052 3 7.580 4 35.530 5 5.380 6 6.630 7 7.260 8 6.770

Table 8: Measurements: Bldg 466 - 801 Harrison Dr

2.9 Bldg 467 - 803 Harrison Dr

15 11 6 3

17 1 16 13 9 8 5 2

14 12 7 4

BLDG 467 - 803 HARRISON DR

LightningMastCeorrporation

16' 8' 00

LEGEND

AIR TERM NAL:

GROUND RODS & DOWNS:

Figure 9: Bldg 467 - 803 Harrison Dr

1 6.136 2 7.906 3 10.813 4 14.828 5 0.073 6 16.765 7 14.362 8 9.158 9 10.259 10 5.110 11 9.842 12 20.356 13 9.804 14 32.280 15 7.636 16 13.570 17 1.762

Table 9: Measurements: Bldg 467 - 803 Harrison Dr

2.10 Bldg 472 - 804 Harrison Dr

AIR TERM NAL:

GROUND RODS & DOWNS:

THRU-ROOF:

CABLE:

BLDG 472- 804 HARRISON DR

LightningMastCeorproration

16' 8' 00

Figure 10: Bldg 472 - 804 Harrison Dr

1 9.306 2 10.395 3 8.821 4 56.42 5 8.98 6 88.08 7 11.128 8 8.185

Table 10: Measurements: Bldg 472 - 804 Harrison Dr

2.11 Bldg 474 - Harrison Dr

2 1

BLDG 474 - HARRISON DR

Figure 11: Bldg 474 - Harrison Dr

1 13.089 2 15.131 3 21.228

Table 11: Measurements: Bldg 474 - Harrison Dr

2.12 Bldg 1156 - 840 Sabalu Rd

ANTENNA EXPOSED

12 9 6 1

18 17 16 15 13 10 7 19 3

14 11 8 5

BLDG 1156 - 840 SABALU RD

LightningMastCeorrporation

16' 8' 00

LEGEND

A R TERM NAL:

GROUND RODS & DOWNS:

Figure 12: Bldg 1156 - 840 Sabalu Rd

1 0.408 2 0.447 3 0.397 4 0.405 5 0.273 6 2.015 7 0.546 8 0.216 9 0.381 10 1.131 11 17.924 12 0.298 13 0.390 14 3.006 15 0.726 16 0.511 17 0.562 18 3.261 19 22.641

Table 12: Measurements: Bldg 1156 - 840 Sabalu Rd

2.13 Bldg 1157 - 844 Sabalu Rd

7 1

13 12 11 10 9 6 4

16 5

15 2

BLDG 1157- 844 SABALU RD

Figure 13: Bldg 1157 - 844 Sabalu Rd

1 22.320 2 2.460 3 0.714 4 0.3822 5 5.839 6 0.450 7 5.914 8 N/A 9 0.2382 10 0.956 11 0.334 12 0.614 13 0.441 14 0.670 15 11.649 16 4.2832

Table 13: Measurements: Bldg 1157 - 844 Sabalu Rd

File details come from the government source that posted it. Updated .