Attch 2 Drawings 603-22-602 Renovate Pathology Lab 08-19-2022.pdf

PDF 14 MB Posted

Attached to
Z1DB--603-23-1-2311-0001 - 603-22-602 - Renovate Pathology (VA-23-00009816)
Solicitation number
36C24922R0104
Issued by

About this file

This solicitation package describes a federal contract opportunity for renovations to a pathology laboratory at the Louisville VA Medical Center. Key details include a 100% set-aside for service-disabled veteran-owned small businesses, a project budget between $250,000 to $500,000, a bid due date of November 21, 2022, and performance and payment bond requirements for awards over $35,000 and $150,000 respectively. The scope of work involves renovations and potential hazardous material abatement. Offerors must register in the System for Award Management and provide past safety records, current experience modification rates from their insurance carrier, and confirmation of E-Verify registration within 30 days of award.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E

H

C O

T

R A M

P

COMPACT

COMPACT

STORAGE

SHED

T1

T3

T20

T22 T27

PROJECT LOCATION

ROBLEY REX VA MEDICAL CENTER

PROJECT NUMBER: 603-22-602

DEPARTMENT OF VETERANS AFFAIRS

800 ZORN AVE, LOUISVILLE, KY 40206

RENOVATE PATHOLOGY LAB

D R A W I N G L I S T

G E N E R A L N O T E S

A. THE CONTRACT DRAWINGS AND SPECIFICATIONS (INDICATED BY THE SAME PROJECT NUMBER) ARE COMPLEMENTARY. THE CONTRACTOR SHALL NOTIFY THE C.O.R. OF ANY DISCREPANCIES FOUND DURING BIDDING AND THROUGH CONSTRUCTION.

B. DO NOT SCALE DRAWINGS; DIMENSIONS SHALL GOVERN.

C. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE GENERAL CONTRACTOR SHALL EXAMINE EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE CONTRACTING OFFICER

REPRESENTATIVE (COR).

D. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING ITEMS TO REMAIN DURING DEMOLITION AND

CONSTRUCTION.

E. THE CONTRACTOR SHALL MAINTAIN ACCESSIBLE EGRESS FOR THE DURATION OF THE PROJECT. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK AND THE ROUTES MUST

BE RETURNED TO THEIR ORIGINAL CONDITION AT THE END OF THE PROJECT.

F. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. FOR THE SCHEDULED TIME OF CONSTRUCTION ACTIVITIES. THE CONTRACTING OFFICER REPRESENTATIVE RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT ANY TIME. NO RADIOS SHALL BE PERMITTED AT ANY TIME IN WORK AREAS ADJACENT TO OCCUPIED

SPACES.

G. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED AND FIRE SAFE’D TO ACHIEVE

THE REQUIRED FIRE RATING BY THE END OF CONSTRUCTION OPERATIONS FOR EACH DAY.

H. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE CODES AND FEDERAL AUTHORITIES, RULES AND REGULATIONS.

I. THESE DOCUMENTS SHOW DESIGN INTENT WITH MINIMUM CONSTRUCTION REQUIREMENTS AND MINIMUM QUALITY OF WORK EXPECTED. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR CONSTRUCTION

AND EXPECTED QUALITY.

J. ALL MATERIALS UTILIZED ON THIS PROJECT SHALL BE NEW UNLESS OTHERWISE NOTED TO BE SALVAGED AND REFURBISHED.

MATERIAL QUALITY SHALL MEET OR EXCEED APPLICABLE INDUSTRY STANDARDS.

K. ALL CONCEALED WOOD SHALL BE FIRE RETARDANT TREATED.

L. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL EQUIPMENT INSTALLATION AND VERIFYING ALL REQUIRED ROUGH OPENINGS AND ROUGH-IN DIMENSIONS WITH THE EQUIPMENT MANUFACTURER AND CONTRACTING OFFICER

REPRESENTATIVE PRIOR TO CONSTRUCTION.

M. WHERE EXISTING SURFACES ARE TO BE RE-FINISHED OR ARE TO SERVE AS SUBSTRATE FOR THE ATTACHMENT OF NEW CONSTRUCTION, PREPARE EXISTING SURFACES AS NECESSARY TO RECEIVE THE NEW MATERIALS FOR A LEVEL AND SMOOTH

FINISH.

N. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES APPARATUSES IMPACTING NEW CONSTRUCTION. DETERMINE EXACT SIZE AND LOCATION OF PENETRATION WITHIN NEW CONSTRUCTION, TIGHTLY SEAL AND CAULK.

O. GENERAL CONTRACTOR SHALL HOST SUBMITTAL EXCHANGE SOFTWARE FOR THE DURATION OF THE PROJECT.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:0

P

M

GI000

COVER SHEET

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

NTS

VICINITY MAP

NTS

CAMPUS MAP

GENERAL

GI000 COVER SHEET

GI001 ABBREVIATIONS AND GENERAL DETAILS

GI002 THIRD FLOOR LIFE SAFETY PLAN

ARCHITECTURE

AD100 PARTIAL THIRD FLOOR DEMOLITION PLAN

AD101 PARTIAL DEMOLITON REFLECTED CEILING PLAN

AE100 PARTIAL THIRD FLOOR PLAN

AC141 PARTIAL THIRD FLOOR REFLECTED CEILING PLAN

AE601 CASEWORK DETAILS, DOOR AND FINISH SCHEDULES

FIRE PROTECTION

FX101 THIRD FLOOR FIRE SUPPRESSION PLAN

PLUMBING

PL101 THIRD FLOOR PLUMBING PLANS

MECHANICAL

M001 MECHANICAL LEGEND

MD101 THIRD FLOOR DEMOLITION MECHANICAL PLAN

MH101 THIRD FLOOR NEW WORK MECHANICAL PLAN

M500 MECHANICAL DETAILS

M600 MECHANICAL SCHEDULES AND CONTROLS

ELECTRICAL

E001 ELECTRICAL LEGEND

ED100 THIRD FLOOR ELECTRICAL DEMOLITION PLANS

EP100 THIRD FLOOR ELECTRICAL POWER AND TECHNOLOGY PLAN

EL100 THIRD FLOOR ELECTRICAL LIGHTING PLAN

N N

No. Revisions: Date:

BID DOCUMENTS FOR CONSTRUCTION 08/19/2022

P1

A101

SIM

A101

SIM

A101

SIM

A101

SIM

LEVEL NAME W/ ELEVATION

NEW GRID HEAD

CALL OUT HEAD W/ SHEET NUMBER

ROOM NAME W/ ROOM NUMBER, AREA

& OCCUPANCY

BUILDING SECTION NUMBER W/ SHEET

NUMBER

WALL SECTION NUMBER W/

SHEET NUMBER

DOOR NUMBER

WALL TAG

KEYNOTE

REVISION TAG

FINISH TAG

DETAIL SECTION NUMBER W/

SHEET NUMBER

NORTH ARROW

LEVEL

ELEVATION

150 SF

S Y M B O L S

N

WINDOW TAGA

0 EXISTING GRID HEAD

10'-0" CEILING HEIGHT TAG

ROOM NAME

A B B R E V I A T I O N S

A.B. ANCHOR BOLT

A.C.M. ASBESTOS CONTAINING MATERIALS

A.C.P. ASPHALT CONCRETE PAVING

A/C AIR CONDITIONING

ACOUS. ACOUSTIC

A.C.T. ACOUSTICAL CEILING TILE

A.D. AREA DRAIN

ADJ. ADJUSTABLE

AFF ABOVE FINISH FLOOR

AGG. AGGREGATE

AL. ALUMINUM

ALT. ALTERNATE

APPROX. APPROXIMATE

ARCH. ARCHITECT

ASPH. ASPHALT

BD. BOARD

BITUM. BITUMINOUS

BLDG. BUILDING

BLK. BLOCK

BLKG. BLOCKING

BM. BENCH MARK OR BEAM

BOT. BOTTOM

BRG. BEARING

BRK. BRICK

BRZ. BRONZE

BTWN. BETWEEN

B.U.R BUILT-UP ROOFING

CAB. CABINET

CARP. CARPET

C.B. CATCH BASIN

C.B.B. CEMENTITIOUS BACKER BOARD

CEM. CEMENT

CER. CERAMIC

CER.T. CERAMIC TILE

C.HK. COAT HOOK

C.I. CAST IRON

CIR. CIRCLE

C.J. CONSTRUCTION JOINT

CLG. CEILING

CLG.J. CEILING JOINT

CLKG. CAULKING

CLO. CLOSET

CLR. CLEAR

CLS. CLOSURE

CMU CONCRETE MASONRY UNIT

CNTR. COUNTER

C.O. CLEAN OUT

COL. COLUMN

COMB. COMBINATION

COMP. COMPOSITION

CONC. CONCRETE

CONN. CONNECTION

CONST. CONSTRUCTION

CONT. CONTINUOUS

CONV.O. CONVECTION OVEN

C.O.R. CONTRACTING OFFICER'S

REPRESENTATIVE

CTR. CENTER

C.W. COLD WATER

CW. CURTAINWALL

DET. DETAIL

DF. DOUGLAS FIR

D.F. DRINKING FOUNTAIN

DIA. DIAMETER

DIAG. DIAGONAL

DIM. DIMENSION

DISP. DISPOSAL

DIV. DIVISION

DN. DOWN

D.O. DOOR OPENING

DR. DOOR

D.S. DOWN SPOUT

D.T. DRAIN TILE

D.W. DISHWASHER

DWG(S). DRAWING(S)

DWR. DRAWER

(E) EXISTING

EA. EACH

E.C. ELECTRICAL CONTRACTOR

E.E. EACH END

E.F. EXHAUST FAN

E.J. EXPANSION JOINT

ELEC. ELECTRICAL

ELEV. ELEVATION

E.N. EDGE NAIL

ENCL. ENCLOSURE

EQUIV. EQUIVALENT

E.S. EACH SIDE

E.W. EACH WAY

E.W.C. ELECTRICAL WATER CLOSET

EXP. EXPANSION

EXP.B. EXPANSION BOLT

EXPO. EXPOSURE

EXT. EXTERIOR

F. FACE

F.A. FIRE ALARM

F.B. FACE BRICK

F.BD. FIRE BOARD

F.BELL FIRE BELL

F.B.O. FURNISHED BY OTHERS

F.D. FLOOR DRAIN

FDN. FOUNDATION

F.E. FIRE EXTINGUISHER

F.E.C. FIRE EXTINGUISHER CABINET

F.F. FINISH FLOOR

F.G. FINISH GRADE

FGL. FIBERGLASS

F.H. FIRE HYDRANT

FH.M.S. FLAT HEAD MACHINE SCREW

FIN. FINISH

FIXT. FIXTURE

F.J. FLOOR JOIST

F.L. FLOOR LINE

FLASH FLASHING

FLOUR FLUORESCENT

FLR. FLOOR

F.N. FACE NAIL

F.O.B. FACE OF BUILDING

F.O.C. FACE OF CONCRETE

F.O.F. FACE OF FINISH

F.O.M. FACE OF MASONRY

F.O.S. FACE OF STUD

F.R.T.W. FIRE RETARDANT TREATED WOOD

F.S.C. FIRE SUPPRESSION CONTRACTOR

F.S.E.C. FOOD SERVICE EQUIPMENT

CONTRACTOR

FTG. FOOTING

FUT. FUTURE

F.V.C. FIRE VAULT CABINET

GA. GAUGE

GALV. GALVANIZED

G.C. GENERAL CONTRACTOR

G.B. GRAB BAR

G.D. GARBAGE DISPOSAL

G.E. GRATE ELEVATION

G.I. GALVANIZED IRON

GL. GLASS

GLB. GLUE LAMINATED BEAM

GND. GROUND

GR. GRADE

G.S.M. GALVANIZED SHEET METAL

GYP.BD. GYPSUM BOARD

H.B. HOSE BIB

HC. HANDICAPPED

HDR. HEADER

HDWD. HARDWOOD

HDWE. HARDWARE

HGT. HEIGHT

H.M. HOLLOW METAL

HORIZ. HORIZONTAL

H.P. HIGH POINT

HR. HOUR

H.S.S. HOLLOW STRUCTURAL STEEL

HTG. HEATING

H.V.A.C. HEATING, VENTILATION & AIR

CONDITIONING

H.W. HOT WATER

I.D. INSIDE DIAMETER

INSUL. INSULATION

INT. INTERIOR

INV. INVERT

JAN. JANITOR

J.H. JOIST HANGER

JST. JOIST HANGER

JT. JOINT

KIT. KINTCHEN

LAB LABORATORY

LAM. LAMINATE

LAV. LAVATORY

L.B. LAG BOLT

L.H. LEFT HAND

L.L. LIVE LOAD

L.P. LOW POINT

LT. LIGHT

MAT. MATERIAL

MAX. MAXIMUM

M.B. MACHINE BOLT

M.C. MEDICINE CABINET

MECH. MECHANICAL

MED. MEDIUM

MEMB. MEMBRANE

M.E.P. MECHANICAL, ELECTRICAL,

PLUMBING

MFG. MANUFACTURER

MH. MANHOLE

MIN. MINIMUM

MIR. MIRROR

MISC. MISCELLANEOUS

M.O. MASONRY OPENING

MOD. MODULAR

MP.H. MOP HOLDER

MR. FRAMED MIRROR

M.R. MOISTURE RESISTANT

M.T. METAL THRESHOLD

MTD. MOUNTED

MTL. METAL

(N) NEW

N. NORTH

NAT. NATURAL

N.I.C. NOT IN CONTRACT

(NOT PART OF OSA APPROVAL)

NO. NUMBER

NOM. NOMINAL

NON/COM NON-COMBUSTIBLE

N.T.S. NOT TO SCALE

O/ OVER

O.A. OVERALL

OBS. OBSCURE

O.C. ON CENTER

O.D. OUTSIDE DIAMETER

O.F. OVERFLOW

OFF. OFFICE

O.F.S. OUTSIDE FACE OF STUD

O.H.W.S. OVAL HEAD WOOD SCREW

OPP. OPPOSITE

P. PAINT

P.C. PLUMBING CONTRACTOR

P.C.F. POUNDS PER CUBIC FOOT

P.E.N. PANEL EDGE NAILING

PERF. PERFORATED

PL. PLATE

P.LAM PLASTIC LAMINATE

PLAS. PLASTER

P.L.F. POUNDS PER LINEAR FOOT

PLYWD. PLYWOOD

P.M.F. PRESSED METAL FRAME

PR. PAIR

PROP. PROPERTY

P.S.F. POUNDS PER SQUARE FOOT

P.S.I. POUNDS PER SQUARE INCH

P.STA. PULL STATION

PTD. PAINTED

P.T.D. PAPER TOWEL DISPENSER

PT. POINT

P.T.D.F. PRESSURE TREATED DOUGLAS

FIR

PTN. PARTITION

P.T.R. PAPER TOWEL RECEPTACLE

P.V.C. POLYVINYL-CHLORIDE

Q.T. QUARRY TILE

RAD. RADIUS

R.B. RUBBER BASE

R.C.P. REFLECTED CEILING PLAN

R.D. ROOF DRAIN

RDWD. REDWOOD

REF. REFERENCE

REFR. REFRIGERATOR

REINF. REINFORCING

REQD. REQUIRED

RESIL. RESILIENT

R.H. ROOF HATCH

R.HK. ROBE HOOK

R.H.M.S. ROUND HEAD METAL SCREW

R.H.W.S. ROUND HEAD WOOD SCREW

RM. ROOM

R.O. ROUGH OPENING

R.W.L. RAIN WATER LEADER

S. SOUTH

S.A.B. SOUND ATTENUATION BATT

S.A.D. SEE ARCHITECTURAL DRAWINGS

S.A.F.F. SELF ADHERED FLEXIBLE FLASHING

S.A.S.M. SELF ADHERED FLEXIBLE MEMBRANE

S.BLKG. SOLID BLOCKING

SCWD. SOLID CORE WOOD DOOR

S.C.D. SEE CIVIL DRAWINGS

S.D. STORM DRAIN

S.DISP. SOAP DISPENSER

SEAL. SEALANT

SECT. SECTION

S.E.D. SEE ELECTRICAL DRAWINGS

SHR. SHOWER

SHT. SHEET

SHTG. SHEATHING

SIM. SIMILAR

SL. SLIDING

S.L.D. SEE LANDSCAPE DRAWINGS

S.M.D. SEE MECHANICAL DRAWINGS

S.N.D. SANITARY NAPKIN DISPOSAL

S.N.V. SANITARY NAPKIN DISPENSER

S.P. SOUNDPROOF

SPEC. SPECIFICATION

SQ. SQUARE

SQ.FT. SQUARE FOOT (FEET)

S.S. SANITARY SEWER

S.S.D. SEE STRUCTURAL DRAWINGS

STA. STATION

STD. STANDARD

STL. STEEL

S.STL. STAINLESS STEEL

STO. STORAGE

STRUC. STRUCTRUAL

SUSP. SUSPENDED

T.B. TACKBOARD

T&B. TOP AND BOTTOM

TEL. TELEPHONE

TEMP. TEMPERED

TER. TERRAZZO

T&G. TOUNGE AND GROOVE

THK. THICK

T.J. TOOL JOINT

T.N. TOE NAIL

T.O.C. TOP OF CURB

T.O.P TOP OF PAVEMENT

T.O.PL. TOP OF PLATE

T.O.S. TOP OF SEAT

T.O.W. TOP OF WALL

T.P.D. TOILET PAPER DISPENSER

T.S. TUBE STEEL

T.V. TELEVISION

TYP. TYPICAL

UNF. UNFINISHED

U.N.O. UNLESS NOTED OTHERWISE

UR. URINAL

U/S. UNDERSIDE

V.C.T. VINYL COMPOSITION TILE

VERT. VERTICAL

VEST. VESTIBULE

V.G. VERTICAL GRAIN

V.I.F. VERIFY IN FIELD

V.T. VINYL TILE

V.T.R. VENT TO ROOF

V.W.C. VINYL WALL COVERING

(VC) V.A. FURNISHED / CONTRACTOR

INSTALLED

(VV) V.A. FURNISHED AND INSTALLED

W. WEST

W/ WITH

W/IN WITHIN

W.C. WATER CLOSET

WD. WOOD

WDW. WINDOW

W.F. WATER COOLER

W.H. WATER HEATER

W/O WITHOUT

W.P. WATER PROOF

W.R. WATER RESISTANT

WT. WEIGHT

W.W.F. WELDED WIRE FABRIC

YD. YARD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:0

P

M

GI001

ABBREVIATIONS AND GENERAL

DETAILS

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

N E

W W

A L L

MED SVC

MED SVC

M. HECKMAN

SATWANT SOOCH

BURKS/PETERS/RUSSELL/SMITH

PHYLLIS TAYLOR

DR MAYFIELD P/T

DR RUBEL

DR SHAHEEN

WHITTAKER/JOHNSON/STINE

HOUSE SUPERV MED SVC MED SVC MED MHBS

DR OMAR

MED SVC SURGERY

C. CHAMBERS

C. ARNOLD

SURGERY

NURSING

DR LEVINSON

HARRINGTON/SAMMONS

DR SCIORTINO

R. RANDOLPH

RESIDENTS

CANTELLI

STEPHANIE WALKER

CELSA THOMAS

SHAUGHNESSY

STAFF DENTISTS

DENTAL ASSISTANTS

SUE BASHAM

DN

A-324

ROOM

EXAM

OFFICES

A-329

A-328

OFFICE

A-327

OFFICE

A-326

ROOM

EXAM EXAM

ROOM

A-325

A-330

LOUNGE

STAFF

A-331

CLOSET

ELECTRIC

B-313c

RESTROOM

B-313a

OFFICE

NURSING

B-313b

ROOM

MULTIPURPOSE

B-315a

RESTROOM

B-316a

RESTROOM

B-315

ROOM

ON-CALL

B-316

ROOM

ON-CALL

B-317

#8

STAIRWELL

B-364

H.A.C.

SUPERVISOR

MICROBIOLOGY LAB

B-365

A-343

ROOM

H.V.A.C. EQUIPMENT

A-342

#1

STAIRWELL

A-336b

OFFICE

A-306

ROOM

MULTIPURPOSE

A-322

ROOM

TREATMENT

A-315a

RESTROOM

A-313

ROOM

EXAM

A-314

ROOM

EXAM

A-315

ROOM

EXAM

A-313a

RESTROOM

A-318a

RESTROOM

A-316

ROOM

EXAM

A-317

ROOM

EXAM

A-318

ROOM

EXAM

A-321

OFFICE

CLINIC

A-317a

RESTROOM

A-319

ROOM

MULTIPURPOSE

A-320

UTILITY

SOILED

A-335

#2

STAIRWELL

A-320a

STORAGE

A-336a

PHARMACY

F.A.C.

A-336

STATION

NURSE'S

A-309a

RESTROOM

A-311a

RESTROOM

A-312

ROOM

EXAM

A-311

ROOM

EXAM

A-310

ROOM

RESIDENTS'

SUPPLY

AND

ELECTRICAL

CLOSET

A-305

A-308a

RESTROOM

A-307

ROOM

EXAM

A-308

ROOM

EXAM

A-309

ROOM

EXAM

A-303a

RESTROOM

A-304

H.A.C.

A-302

PHLEBOTOMY

WAITING

ROOM

A-338

A-336c

RESTROOM

STAFF

A-337

OFFICE

MECHANICAL

EQUIPMENT

PENTHOUSE

M301-1

A-348

LAB

HISTOLOGY

A-348d

CHASE

PIPE

A-390

AREA

WAITING

A-301a

AREA

WAITING ANTICOAG

OFFICE

A-391

A-350

CLOSET

ELECTRIC

F.A.C.

A-340

CLOSET

ELECTRIC

A-341

CLOSET

COMM.

A-349

CLOSET

TELEPHONE

S-5

S-6

P-4

P-3

A-351

LOBBY

ELEVATOR

P-2

P-1

A-348a

EXAM ROOM

SPECIMEN

A-389

STORAGE

RECORD

A-382a

RESTROOM

A-380

PATIENT 5

A-380a

RESTROOM

A-381

PATIENT 4

A-382

PATIENT 3

A-385a

RESTROOM

A-388

H.A.C.

A-384a

RESTROOM

A-383

PATIENT 2

A-384

PATIENT 1

A-387

LINEN

CLEAN

A-385

LOUNGE

A-386

CENTER

NOURISHMENT

A-353

RESTROOM

STAFF

A-348e

OFFICE

A-352

RESTROOM

WOMEN'S

A-351a

H.A.C.

A-348c

OFFICE

LAB

A-354

OFFICE

DIS. PLAN

A-348b

CYTOLOGY

A-355

OFFICE

DIS. PLAN

B-302

TECHNOLOGIST

CHIEF MEDICAL

B-307

SERVICE

PATHOLOGY

NURSING

OFFICE

B-312a

B-313

OFFICE

NURSING

B-307b

PATHOLOGIST

STAFF

B-307d

PATHOLOGIST

STAFF

B-307c

PATHOLOGIST

STAFF

B-309

OFFICE

A&MM

B-328

CLOSET

TELEPHONE

B-312

OFFICE

NURSING

B-329

CLOSET

COMM

NURSING

OFFICE

B-312b

B-330

PROCEDURE ROOM

DEMONSTRATION

B-318

OFFICE

NURSING

PENTHOUSE

ELEVATOR

B-319

ROOM

ON-CALL

B-327

CLOSET

ELECTRIC

NURSE

OFFICE

B-311

B-331

CONFERENCE ROOM

NURSING

B-320

ROOM

ON-CALL

B-319a

RESTROOM

B-321

ROOM

ON-CALL

CHIEF,

LABORATORY

OFFICE

B-307a

MEN'S

LOCKER

ROOM

B-308

WOMEN'S

LOCKER

ROOM

B-306

B-332

ROOM

MULTIPURPOSE

B-310

OFFICE

A&MM

B-322

ROOM

ON-CALL

B-321a

RESTROOM

B-323

ROOM

ON-CALL

B-325a

RESTROOM

B-335

OFFICE

A&MM

B-334

H.A.C.

B-333

OFFICE

PATH & LAB

B-326

LINEN

CLEAN

B-324

ROOM

ON-CALL

B-323a

RESTROOM

D-302

PENTHOUSE

MECHANICAL

B-325

ROOM

STORAGE

D-303

EQUIPMENT

ELEVATOR

C-302a

REFRIGERATOR

P-7

B-353b

ROOM

EXAM

B-366a

STORAGE

LABORATORY

B-303

& BREAK ROOM

LAB CONFERENCE

B-340

CHUTE

LINEN

F.A.C.

B-366

STORAGE

B-352

CLOSET

ELECTRIC

B-351

#3

STAIRWELL

B-358

STAFF LOUNGE

B-355

RESTROOM

B-354

CLOSET

UNIFORM

LAB

B-353a

B-353c

RESTROOM

B-356

RESTROOM

C-302

LABORATORY

DEVELOPMENTAL

C-301

CLOSET

ELECTRIC

P-8 P-9

C-305

LABORATORY

DENTAL

D-301

#9

STAIRWELL

A-361

LOUNGE

A-374a

RESTROOM

SURGERY

STORAGE

A-370

A-377a

RESTROOM

A-378a

RESTROOM

A-379

PATIENT 6

A-377

PATIENT 8

A-378

PATIENT 7

A-375

MED ROOM

A-373

CLOSET

SUPPLY

A-376

STATION

NURSE

A-374

OFFICE

A-372

UTILITY

SOILED

A-369

OFFICE

A-356

OFFICE

DIS. PLAN

A-357

ROOM

MULTIPURPOSE

A-358

UTILITY

CLEAN

A-371

STORAGE

F.A.C.

A-359

#6

STAIRWELL

A-360

UTILITY

SOILED

A-368b

CONSTULT

A-362

RESTROOM

PATIENT

A-363

CLOSET

ELECTRIC

A-364

OFFICE

B-363c

REFRIGERATOR

B-363d

REFRIGERATOR

MOLECULAR

PATHOLOGY

LABORATORY

B-359

B-363

LABORATORY

MICROBIOLOGY

B-360

LABORATORY

BACTERIOLOGY

C-306

LABORATORY

HEMOTOLOGY

B-363b

LABORATORY

TUBERCULOSIS

MOLECULAR

MICROBIOLOGY

LABORATORY

B-361

B-363a

LABORATORY

PARASITOLGY

B-362

#5

STAIRWELL

C-306b

CLINICAL CHEMISTRY

CHIEF

C-306c

REFRIGERATOR

C-306e

CLOSET

COMPUTER

C-306d

CLOSET

ELECTRIC

C-306a

OFFICE

LABORATORY

A-365

ROOM

TREATMENT

CHIEF OF

MICROBIOLOGY &

ASSISTANT DIRECTOR OF

MOLECULAR PATHOLOGY

A-347

LABORATORY

COMPUTER

COORDINATOR

OFFICE

B-305

A-365a

PROCEDURE

PRE / POST

A-365b

ROOM

CONSULT

A-367a

OFFICE

A-344

RESTROOM

MEN'S

A-345

RESTROOM

WOMEN'S

A-346

ROOM

CONFERENCE

A&MM

OFFICE

B-314

B-353d

PHLEBOTOMY

SUPERVISOR

B-357

STORAGE

B-301

HISTOLOGY/CYTOLOGY LAB

SUPERVISOR

A-392

OFFICE

ANTICOAG

B-338f

OPERATORY #6

B-338e

OPERATORY #5

B-338d

OPERATORY #4

B-338c

OPERATORY #3

B-338b

OPERATORY #2

B-338g

OPERATORY #7

B-338a

OPERATORY #1

B-337d

BREAK ROOM

B-337c

OFFICE

CHIEF, DENTAL SVC

B-337b

OFFICE

DENTIST

CLOSET B-337

WORK RM.

COPY/

B-337a

ADMINISTRATION

B-338p

CLOSET

B-338m

X-RAY B-338n

OMFS-1

B-338o

OMFS-2

B-338m1

ROOM

DARK

B-338l

OPERATORY #8

B-338k

PERIO

B-338j

HYGIENE

B-338i

STORAGE

B-338h

DECONTAM

A-303

PHLEBOTOMY

B-353

ROOM

WAITING

B-338q

STORAGE

B-338

DENTAL SUITE

A-330a

KITCHEN

STAFF

B-353e

OFFICE

A-323

ROOM

EXAM

A-368a

WAITING

CHECK IN/OUT

A-367b

OFFICE

A-332

LAB

A-333c

ROOM

CLEAN

A-333b

ROOM

ANTI

A-333a

STORAGE

A-333

PHARMACY A-334

ROOM

MULTIPURPOSE

A-369a

OFFICE

A-301

AREA

WAITING

B-359a

P A

T H

O F

T R

A V

E L

PROJECT LOCATION

L I F E S A F E T Y L E G E N D

1 HOUR FIRE BARRIER

HORIZONTAL EXIT PASSAGEWAYHE

EX EXIT

EP EXIT PASSAGEWAY

HAZARDOUS ROOM

PROJECT SCOPE

DIRECTIONAL EXIT SIGN

FIRE EXTINGUISHER

PATH OF TRAVEL

2 HOUR FIRE BARRIER

FAC FIRE ALARM CONTROL

1 HOUR SMOKE BARRIER

WALL MOUNTED

DIRECTIONAL EXIT SIGN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:1

P

M

GI002

THIRD FLOOR LIFE SAFETY PLAN

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

1/16" = 1'-0"

THIRD FLOOR LIFE SAFETY PLAN

N

CODE REVIEW:

Project: Renovate Pathology

Location: Robley Rex VA Medical Center

Project Number: 603-22-602

PROJECT SUMMARY:

LOCATED IN LOUISVILLE KY ROBLEY REX VAMC, THIS PROJECT CONSISTS OF THE RENOVATION OF AN EXISTING PATHOLOGY LAB ON THE THIRD FLOOR OF BUILDING 1. THE PROJECT IS ANTICIPATED TO RENOVATE APPROXIMATELY 1,500 DGSF AND INCLUDES IMPROVED SPACE LAYOUT, ARCHITECTURAL, FINISH UPGRADES AND MODERNIZATION OF THE MECHANICAL DEVICES, ELECTRICAL LIGHTING FIXTURES, PLUMBING. THE AREA IS TO REMAIN OPERATIONAL THROUGH CONSTRUCTION AND MULTI PHASED

DURING CONSTRUCTION AS NEEDED TO REMAIN OPERATIONAL.

BUILDING 1 IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA AND REMAINS UNCHANGED.

ASCE7-2016 SEISMIC DESIGN CATEGORY – C (RISK CATEGORY IV, SITE CLASS D)

2021 NFPA 5000

TABLE 7.2.1.1 CONSTRUCTION TYPE II (222):

EXTERIOR BEARING WALLS: 2-HOUR

INTERIOR BEARING WALLS: 2-HOUR

COLUMNS: 2-HOUR

BEAMS, GIRDERS, TRUSSES, AND ARCHES: 2-HOUR

FLOOR-CEILING ASSEMBLIES: 2-HOUR

ROOF-CEILING ASSEMBLIES: 1-HOUR

INTERIOR NONBEARING WALLS: 0-HOUR

EXTERIOR NONBEARING WALLS: 0-HOUR

NOTE: ACCEPTABLE CONSTRUCTION TYPES BASED ON OBSERVATIONS OF CONSTRUCTION MATERIALS INCLUDE TYPE I (443), I (332) AND II (222). THIS REPORT WILL USE THE LEAST RESTRICTIVE TYPE II (222).

2021 NFPA 101 LIFE SAFETY CODE REVIEW

AREA OF WORK:

BUILDING 1 – THIRD FLOOR (AREA OF WORK ONLY): 1,500 DGSF

CHAPTER 3 DEFINITIONS

3.3.32.2 SMOKE BARRIER. A CONTINUOUS MEMBRANE, OR A MEMBRANE WITH DISCONTINUITIES CREATED BY PROTECTED OPENINGS, WHERE SUCH MEMBRANE IS DESIGNED AND CONSTRUCTED TO RESTRICT THE

MOVEMENT OF SMOKE.

CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD OF CONTENT

6.1.11 EXISTING BUSINESS OCCUPANCY (CHAPTER 39)

6.2.2 HAZARD CLASSIFICATION: ORDINARY - NO CHANGE

CHAPTER 7 - MEANS OF EGRESS:

7.1.3.1 EXIT ACCESS CORRIDORS: CORRIDORS USED AS EXIT ACCESS AND SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 SHALL BE SEPARATED FROM OTHER PARTS OF THE BUILDING BY WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: (1) THIS REQUIREMENT SHALL NOT APPLY TO EXISTING BUILDINGS, PROVIDED THAT THE OCCUPANCY CLASSIFICATION DOES NOT CHANGE. (2) THIS

REQUIREMENT SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 11 THROUGH 43.

7.2.4.1.1 WHERE HORIZONTAL EXISTS ARE USED IN THE MEANS OF EGRESS, THEY SHALL CONFORM TO THE

GENERAL REQUIREMENTS OF SECTION 7.1 AND SPECIAL REQUIREMENTS OF 7.2.4.

7.2.6.3 STAIR DISCHARGE – AN EXIT PASSAGEWAY THAT SERVES AS A DISCHARGE FROM A STAIR

ENCLOSURE SHALL HAVE NOT LESS THAN THE SAME FIRE RESISTANCE RATING AND OPENING

PROTECTIVE RATING AS THOSE REQUIRED FOR THE STAIR ENCLOSURE.

7.2.6.4.1 THE WIDTH OF AN EXIT PASSAGEWAY SHALL BE SIZED TO ACCOMMODATE THE AGGREGATE REQUIRED CAPACITY OF ALL EXITS THAT DISCHARGE THROUGHT IT, UNLESS ONE OF THE FOLLOWING

CONDITIONS APPLIES:

WHERE AN EXIT PASSAGEWAY SERVES OCCUPANTS OF THE LEVEL OF EXIT DISCHARGE AS WELL AS

OTHER STORIES THE CAPACITY SHALL NOT BE REQUIRED TO BE AGGREGATED.

7.3.1.2 OCCUPANT LOAD OF SPACE (PROJECT AREA ONLY):

BUILDING 1 –LEVEL 3: 1,500 SF AT 150 SF / OCCUPANT = 10 OCCUPANTS

CHAPTER 8 - FEATURES OF FIRE PROTECTION: NO CHANGE

8.4. SMOKE PARTITIONS

8.4.2. SMOKE PARTITIONS SHALL EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR ROOF

DECK ABOVE

8.5.3. FIRE BARRIERS AS SMOKE BARRIERS

A FIRE BARRIER SHALL BE PERMITTED TO BE USED AS A SMOKE BARRIER, PROVIDED THAT IT MEETS THE

REQUIREMENTS OF SECTION 8.5.

8.7. SPECIAL HAZARD PROTECTIONS

8.7.1.1 PROTECTION FROM ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE

FOLLOWING MEANS:

(1) SEPARATING THE AREA FROM OTHER PARTS OF THE BUILDING WITH A FIRE BARRIER HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR IN ACCORDANCE WITH SECTION 8.3 AND WITHOUT

WINDOWS.

(2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYSTEMS IN ACCORDANCE WITH SECTION 9.7.

(3) APPLYING BOTH 8.7.1.1(1) AND 8.7.1.1.(2) WHERE THE HAZARD IS SEVERE OR WHERE OTHERWISE

SPECIFIED IN CHAPTERS 11 THROUGH 43.

CHAPTER 9 - BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT: NO CHANGE

CHAPTER 10 - INTERIOR FINISH, CONTENTS, AND FURNISHES

10.2.3.1

INTERIOR WALL AND CEILING FINISH MATERIALS TESTED IN ACCORDANCE WITH NFPA 286.

10.2.3.1.1

INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE CLASSIFIED IN ACCORDANCE WITH NFPA 286

AND COMPLY WITH 10.2.3.2.

10.2.3.1.2

MATERIALS TESTED IN ACCORDANCE WITH 10.2.3.1.1 AND COMPLYING WITH 10.2.3.2 SHALL BE CONSIDERED ALSO TO COMPLY WITH THE REQUIREMENTS OF CLASS A, CLASS B, OR CLASS C IN ACCORDANCE WITH 10.2.3.3

10.2.3.2.

(1) DURING THE 40 KW EXPOSURE, FLAMES SHALL NOT SPREAD TO THE CEILING.

(2) THE FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF THE SAMPLE ON ANY WALL OR CEILING.

(3) FLASHOVER, AS DESCRIBED IN NFPA 286, SHALL NOT OCCUR.

(4) THE PEAK HEAT RELEASE RATE THROUGHOUT THE TEST SHALL NOT EXCEED 800 KW.

(5) FOR NEW INSTALLATIONS, THE TOTAL SMOKE RELEASED THROUGH-OUT THE TEST SHALL NOT EXCEED 1000 M2.

10.2.3.3

WALL AND CEILING- CLASSIFICATIONS CHARACTERISTICS.

(1) CLASS A: FLAME SPREAD: 0-25; SMOKE DEV. : 0-450.

(2) CLASS B: FLAME SPREAD: 26-75; SMOKE DEV. : 0-450

(3) CLASS C: FLAME SPREAD: 76-200; SMOKE DEV. : 0-450

10.2.8.1

WALL AND CEILING FINISHES, WHERE SPRINKLED:

CLASS C PERMITTED IN ANY LOCATION WHERE CLASS B IS REQ’D.

CLASS B PERMITTED IN ANY LOCATION WHERE CLASS A IS REQ’D.

-MAINTAIN ACCESSIBILITY TO EXISTING FIRE EXTINGUISHERS DURING CONSTRUCTION

39.1.5 CLASSIFICATION OF HAZARDS OF CONTENTS – THE CONTENTS OF BUSINESS OCCUPANCIES SHALL

BE CLASSIFIED AS ORDINARY HAZARD IN ACCORDANCE WITH SECTION 6.2.

39.2.2.2.2 DOOR LOCKING TO PREVENT UNWANTED ENTRY – WHERE APPROVED DOORS OTHER THAN THOSE COMPLYING WITH 39.2.11.2 SHALL BE PERMITTED TO BE LOCKED TO PREVENT UNWANTED ENTRY

PROVIDED THAT ALL THE FOLLOWING CONDITIONS ARE MET:

THE LOCKING MEANS SHALL BE CAPABLE OF BEING ENGAGED WITHOUT OPENING THE DOOR.

THE UNLOCKING AND UNLATCHING OPERATION FROM THE EGRESS SIDE OF THE DOOR SHALL BE

ACCOMPLISHED WITHOUT THE USE OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR EFFORT.

EGRESS SHALL REQUIRE NOT MORE THAN ONE RELEASING OPERATION.

THE RELEASING MECHANISM FOR UNLOCKING AND UNLATCHING SHALL BE LOCATED AT A HEIGHT OF NOT

LESS THAN 34” AND NOT EXCEEDING 48” ABOVE THE FINISHED FLOOR.

LOCKS, IF REMOTELY ENGAGED, SHALL BE UNLOCKABLE FROM THE EGRESS SIDE OF THE DOOR WITHOUT

THE USE OF A KEY, TOOL OR SPECIAL KNOWLEDGE OR EFFORT.

THE DOOR SHALL BE CAPABLE OF BEING UNLOCKED AND OPENEDED FROM OUTSIDE THE ROOM WITH THE

NECESSARY KEY OR OTHER CREDENTIAL.

THE LOCKING MEANS SHALL NOT MODIFY THE DOOR CLOSER, PANIC HARDWARE OR FIRE EXIT

HARDWARE.

MODIFICATIONS TO REQUIRED FIRE DOOR ASSEMBLIES, INCLUDING DOOR HARDWARE, SHALL BE IN

ACCORDANCE WITH NFPA 80.

39.2.5. ARRANGEMENT OF MEANS OF EGRESS

39.2.2.5 HORIZONTAL EXITS COMPLYING WITH 7.2.4 SHALL BE PERMITTED.

39.2.5.2 DEAD END CORRIDORS SHALL NOT EXCEED 50 FT.

39.2.5.2.1 COMMON PATH OF TRAVEL SHALL NOT EXCEED 100 FT ON A STORY PROTECTED THROUGHOUT

BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.(1).

39.2.6. TRAVEL DISTANCE TO EXITS

39.2.6.3. TRAVEL DISTANCE TO AN EXIT SHALL NOT EXCEED 300 FT IN BUSINESS OCCUPANCIES

PROTECTED THOUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN

ACCORDANCE WITH SECTION 9.7.

39.2.11.3 HAZARDOUS MATERIALS – WHERE HAZARDOUS MATERIALS ARE PRESENT THE PROVISIONS OF

7.12.2 SHALL APPLY.

39.3.2. PROTECTION FROM HAZARDS

39.3.2.1 GENERAL HAZARDOUS AREAS INCLUDING, BUT NOT LIMITED TO, AREAS USED FOR GENERAL STORAGE, BOILER OR FURNACE ROOMS, AND MAINTENANCE SHOPS THAT INCLUDE WOODWORKING AND

PAINTING AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7.

39.3.2.2 HIGH HAZARD CONTENTS AREAS – HIGH HAZARDOUS CONTENT AREAS AS CLASSIFIED IN SECTION

6.2 SHALL MEET ALL OF THE FOLLOWING CRITERIA:

THE AREA SHALL BE SEPARATED FROM OTHER PARTS OF THE BUILDING BY FIRE BARRIERS HAVING A MINIMUM 1 HOUR FIRE RESISTANCE RATING, WITH ALL OPENINGS THEREHEIN PROTECTED BY SELF

CLOSING FIRE DOOR ASSEMBLIES HAVING A MIN. ¾ HOUR FIRE PROTECTION RATING.

THE AREA SHALL BE PROTECTED BY AN AUTOMATIC EXTINGUISHING SYSTEM IN ACCORDANCE WITH

9.7.1.1(1) OR 9.7.1.2.

39.3.2.3 HAZARDOUS MATERIALS. WHERE HAZARDOUS MATERIALS ARE STORED OR HANDLED, THE

PROVISIONS OF 8.7.3.1 SHALL APPLY.

39.3.2.5 MEDICAL GAS. MEDICAL GAS STORAGE AREAS AND THE OPERATION, MANAGEMENT AND

MAINTENANCE OF MEDICAL GASES SHALL BE IN ACCORDANCE WITH NFPA 99.

39.3.3 INTERIOR FINISHES.

39.3.3.1. GENERAL. INTERIOR FINISHES SHALL BE IN ACCORDANCE WITH SECTION 10.2.

39.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASS A, CLASS B, OR CLASS C IN AREAS

OTHER THAN EXITS AND EXIT ACCESS CORRIDORS.

39.3.3.3 INTERIOR FLOOR FINISH – NO REQUIREMENTS.

39.3.5 EXTINGUISHMENT REQUIREMENTS – PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED IN EVERY

BUSINESS OCCUPANCY IN ACCORDANCE WITH SECTION 9.9.

39.3.6 CORRIDORS (NO REQUIREMENTS)

E

E

EE

VENTANA

HE 600

U P

S

S-5

P-4

P-3

P-2

P-1

STORAGE

A-366

SPECIMEN EXAM

A-348a

CYTOLOGY

A-348b

LAB OFFICE

A-348c

OFFICE

A-348e

ELEVATOR LOBBY

A-351

TELE.

A-349

CORRIDOR

H.A.C

A-351c

DIS. PLAN OFFICE

A-354

CORRIDOR

HISTOLOGY

A-348

PIPE CHASE

A-348d

CORRIDOR

OFFICE

A-347

MLK

16' - 2" 19' - 10"

VENTANA

HE 600

U P

S

V.I.F

± 4' - 2"

V.I.F

± 2' - 6"

7 8 9

G E N E R A L C E I L I N G D E M O L I T I O N N O T E S

A. REFER TO SHEET GI000 FOR GENERAL NOTES.

B. FOR ALL REMOVALS, THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES.

C. DASHED LINES INDICATE FINISHES, MATERIALS, AND ASSOCIATED FIXTURES TO BE REMOVED. KEYNOTES SHALL

GOVERN OVER LINETYPES.

D. ALL WALLS BEING DEMOLISHED ARE GYPSUM BOARD AND COLD-FORMED STEEL FRAMING UNLESS NOTED

OTHERWISE.

E. HALF-TONED ITEMS INDICATE EXISTING CONSTRUCTION SHALL BE PROTECTED & REMAIN. KEYNOTES SHALL

GOVERN OVER LINEWEIGHTS.

F. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS

REQUIRED UNTIL PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.

G. UTILITIES THAT REMAIN, WITHIN WALLS BEING DEMOLISHED, SHALL BE REROUTED AS REQUIRED TO FACILITATE

THE NEW PLAN CONFIGURATION.

H. AT PENETRATIONS, ALL UTILITY SYSTEM AND OTHER COMPONENTS THAT ARE SCHEDULED FOR DISCONNECTION SHALL BE REMOVED IN THEIR ENTIRETY. ANY FIRE RESISTIVE MEMBER OR THROUGH PENETRATIONS RESULTING FROM SUCH DEMOLITION WORK SHALL BE FIRESTOPPED OR SEALED IN ACCORDANCE WITH NFPA FOR THE

NECESSARY RATING PROTECTIONS.

N

K E Y P L A N

NTS

F I R E / S M O K E R A T I N G L E G E N D

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:5

P

M

AD100

PARTIAL THIRD FLOOR

DEMOLITION PLAN

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

N 1/4" = 1'-0"

PARTIAL THIRD FLOOR DEMOLITION PLAN

D R A W I N G N O T E S

1 THIS AREA NOT IN CONTRACT. (NIC)

2 REMOVE INFILL WALL, DOOR FRAME, AND ALL RELATED SUPPORTS.

3 REMOVE EPOXY RESIN COUNTERTOP, BASE CABINETS, WALL CABINETS AND ALL RELATED SUPPORTS.

4 INSTALL 6 MIL PLASTIC SHEET BARRIER IN THIS LOCATION. SEAL TO BE AIR TIGHT AT TOP AND BOTTOM OF WALL. LAB MUST BE KEPT OPERATIONAL DURING CONSTRUCTION. SEE SPECIFICATIONS FOR ADDITIONAL ICRA REQUIREMENTS

FOR THIS SPACE.

5 REMOVE CARPET FLOORING FINISH AND MASTICS. CLEAN AND PREPARE SURFACE TO RECEIVE NEW FINISHES.

6 REMOVE PORTION OF EXISTING WALL (SHOWN AS DASHED) AND DOOR FRAME. PREPARE OPENING TO RECEIVE WALL

INFILL, NEW DOOR FRAME AND DOOR. SEE AE100.

7 EXISTING FINISHES TO REMAIN.

8 EXISTING EQUIPMENT IN THIS AREA TO REMAIN AND BE PROTECTED DURING CONSTRUCTED.

9 EXISTING FLOORING IS TO REMAIN IN THIS AREA.

10 NO ARCHITECTURAL SCOPE IN THIS ROOM

N

K E Y P L A N

NTS

G E N E R A L C E I L I N G D E M O L I T I O N N O T E S

A. REFER TO SHEET GI000 FOR GENERAL NOTES.

B. FOR ALL REMOVALS, THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES.

C. DASHED LINES INDICATE FINISHES, MATERIALS, AND ASSOCIATED FIXTURES TO BE REMOVED. KEYNOTES SHALL

GOVERN OVER LINETYPES.

D. ALL WALLS BEING DEMOLISHED ARE GYPSUM BOARD AND COLD-FORMED STEEL FRAMING UNLESS NOTED

OTHERWISE.

E. HALF-TONED ITEMS INDICATE EXISTING CONSTRUCTION SHALL BE PROTECTED & REMAIN. KEYNOTES SHALL

GOVERN OVER LINEWEIGHTS.

F. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS

REQUIRED UNTIL PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.

G. UTILITIES THAT REMAIN, WITHIN WALLS BEING DEMOLISHED, SHALL BE REROUTED AS REQUIRED TO FACILITATE

THE NEW PLAN CONFIGURATION.

H. AT PENETRATIONS, ALL UTILITY SYSTEM AND OTHER COMPONENTS THAT ARE SCHEDULED FOR DISCONNECTION SHALL BE REMOVED IN THEIR ENTIRETY. ANY FIRE RESISTIVE MEMBER OR THROUGH PENETRATIONS RESULTING FROM SUCH DEMOLITION WORK SHALL BE FIRESTOPPED OR SEALED IN ACCORDANCE WITH NFPA FOR THE

NECESSARY RATING PROTECTIONS.

S-5

S-6

P-4

P-3

P-2

P-1

CORRIDOR

STORAGE

A-366

CORRIDOR

SPECIMEN EXAM

A-348a

CYTOLOGY

A-348b

HISTOLOGY

A-348

LAB OFFICE

A-348c

OFFICE

A-348e

DIS. PLAN OFFICE

A-354

H.A.C

A-351c

ELEVATOR LOBBY

A-351

TELE.

A-349

PIPE CHASE

A-348d

C E

IL

IN

G H

T . C

H A

N G

E

CORRIDOR

OFFICE

A-347

MLK

16' - 2" 19' - 10"

R E F L E C T E D C E I L I N G P L A N L E G E N D

1' x 4' FIXTURE.

2' x 4' FIXTURE.

EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED

2' x 2' FIXTURE.

DEMO LIGHT FIXTURE.

EXISTING EXHAUST DUCT (UP & DOWN)

EXISTING RETURN DUCT (UP & DOWN)

EXISTING SUPPLY DUCT (UP & DOWN)

LINEAR SLOT DIFFUSER

(REFER TO MEP DRAWINGS)

NEW SUPPLY DUCT (UP & DOWN)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:5

P

M

AD101

PARTIAL DEMOLITON REFLECTED

CEILING PLAN

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

D R A W I N G N O T E S

1 THIS AREA NOT IN CONTRACT. (NIC)

2 REMOVE CEILING TILE, CEILING DEVICES AND CEILING GRID.

3 EXISTING GRID AND CEILING TILES TO REMAIN.

4 EXISTING EMERGENCY SHOWER TO REMAIN.

5 REMOVE 24" X 48" CEILING TILES, CEILING GRID TO REMAIN. CEILING WORK TO BE PERFORMED IN PHASES IN THIS AREA

TO ALLOW FOR LAB TO REMAIN OPERATIONAL DURING CONSTRUCTION.

6 REMOVE LINEAR DIFFUSERS WHERE INDICATED. REFER TO MECHANICAL DRAWINGS.

7 MECHANICAL DEVICES TO REMAIN. REFER TO MECHANICAL DRAWINGS.

N 1/4" = 1'-0"

REFLECTED CEILING PLAN - DEMOLITION

BSL II

S-5

P-4

P-3

P-2

P-1

AE601

AE6012

HISTOLOGY

A-348

BIOSAFETY LAB

A-347

MLK

STORAGE

A-366

SPECIMEN EXAM

A-348a

CYTOLOGY

A-348b

LAB OFFICE

A-348c

OFFICE

A-348e

ELEVATOR LOBBY

A-351

TELE.

A-349 H.A.C

A-351c

DIS. PLAN OFFICE

A-354

PIPE CHASE

A-348d

CORRIDOR

CORRIDOR

4 5

16' - 2" 19' - 10"

5"

V.I.F

± 2' - 6"

10 V.I.F

± 4' - 2"

N

K E Y P L A N

NTS

G E N E R A L N O T E S

A. REFER TO SHEET GI000 FOR GENERAL NEW WORK NOTES.

B. REFER TO DEMOLITION DRAWINGS FOR WORK REQUIRED IN ADVANCE OF CONSTRUCTION AND COORDINATE

ACCORDINGLY.

C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, CONFIRM ALIGNMENT WITH

PLANS.

D. ALL WALL HUNG CASEWORK MUST BE ANCHORED IN ACCORDANCE WITH VA STANDARD 05 500-02.

E. NEW CONSTRUCTION TO ALIGN WITH ADJACENT EXISTING CONSTRUCTION WHERE APPLICABLE. PREPARE

ALIGNED SURFACES TO RECEIVE NEW FINISHES.

F. SOUND ATTENUATION BATTS (SAB) ARE TO BE PLACED IN ALL PARTITIONS WHICH ENCLOSE A ROOM UNLESS

NOTED OTHERWISE.

F I R E / S M O K E R A T I N G L E G E N D

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:0

P

M

AE100

PARTIAL THIRD FLOOR PLAN

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

N 1/4" = 1'-0"

PARTIAL THIRD FLOOR PLAN - NEW WORK

D R A W I N G N O T E S

1 EQUIPMENT (VC) OWNER FURNISHED CONTRACTOR INSTALLED - SEE EQUIPMENT/FINISH PLAN ON AE601

2 INSTALL NEW DOOR - SEE DOOR SCHEDULE ON AE601

3 THIS AREA NOT IN CONTRACT. (NIC)

4 EXISTING FLOORING FINISH TO REMAIN IN THIS ROOM.

5 EXISTING WALL FINISH TO REMAIN IN THIS ROOM.

6 INSTALL METAL BASE AND WALL CABINETS AND ALL RELATED SUPPORTS AND FIRE RATED BLOCKING. REFER TO

SECTIONS AND ELEVATIONS.

7 PROVIDE AND INSTALL CHEMICAL RESISTANT EPOXY RESIN COUNTERTOP WITH BACKSPLASH AND INTEGRAL SINK. 1"

OVERHANG BEYOND FRONT AND SIDE FACES OF CABINET PRODUCT .

8 INSTALL NEW SHEET VINYL FLOORING WITH VINYL BASE.

9 NEW DOUBLE STUD JAMB WITH 5/8" TYPE X GYPSUM BOARD ON BOTH SIDES OF WALL. ALIGN WITH ADJACENT

CONSTRUCTION.

10 WALL AND BASE CABINET FILLER SHALL COVER EXISTING UTILITY CHASE; COUNTERTOP SHALL BE CUT TO FIT AROUND

CHASE. BACKSPLASH TO WRAP CHASE.

R E F L E C T E D C E I L I N G P L A N L E G E N D

1' x 4' FIXTURE.

2' x 4' FIXTURE.

EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED

2' x 2' FIXTURE.

DEMO LIGHT FIXTURE.

EXISTING EXHAUST DUCT (UP & DOWN)

EXISTING RETURN DUCT (UP & DOWN)

EXISTING SUPPLY DUCT (UP & DOWN)

LINEAR SLOT DIFFUSER

(REFER TO MEP DRAWINGS)

NEW SUPPLY DUCT (UP & DOWN)

N

K E Y P L A N

NTS

L

S-5

P-4

P-3

P-2

P-1

STORAGE

A-366

BIOSAFETY LAB

A-347

SPECIMEN EXAM

A-348a

LAB OFFICE

A-348c

OFFICE

A-348e

ELEVATOR LOBBY

A-351

TELE.

A-349

CORRIDOR

H.A.C

A-351c

DIS. PLAN OFFICE

A-354

CORRIDOR

HISTOLOGY

A-348

PIPE CHASE

A-348d

CYTOLOGY

A-348b

CORRIDOR

MLK

16' - 2" 19' - 10"

8' - 1"

8' - 1"

8' - 1"

G E N E R A L C E I L I N G N O T E S

A. REFER TO CEILING PLAN AND FINISH LEGEND FOR CEILING FINISH INFORMATION

B. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND

EXHAUST GRILLES. SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.

C. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER

OUTLETS, ETC.

D. VERIFY CEILING HEIGHTS WITH STRUCTURE AND DUCTWORK.

E. REFER TO FINISH LEGEND FOR CEILING TYPES.

F. ALL LAY-IN CEILING GRID MUST BE CENTERED IN ROOM UNLESS OTHERWISE NOTED. AVOID CUT SIZES SMALLER

THAN 6". SCRIBE CEILING MATERIALS FOR A TIGHT FIT.

G. CENTER SPRINKLER HEADS WITHIN CEILING TILES. COORDINATE WITH OTHER CEILING MOUNTED ACCESSORIES.

H. ALL VERTICAL FACES OF SOFFITS OR BULKHEADS SHALL BE FINISHED TO MATCH ADJACENT SURFACES.

F I R E / S M O K E R A T I N G L E G E N D

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:5

P

M

AC141

PARTIAL THIRD FLOOR

REFLECTED CEILING PLAN

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

D R A W I N G N O T E S

1 24" X 24" SOIL-RESISTANT FILM FACED CEILING TILE PRODUCT WITH GASKETED CEILING GRID.

2 REPLACE EXISTING CEILING TILES WITH 24" X 24" SOIL-RESISTANT FILM FACED CEILING TILE, SEE SPECS FOR BASIS OF DESIGN. EXISTING GRID TO REMAIN. PROVIDE INTERMEDIATE METAL GRID PIECES TO EXISTING 2’-0” X 4’-0” METAL GRID TO ACCOMMODATE 2’-0” X 2’-0” ACOUSTICAL TILES AND CEILING DEVICES. CLEAN AND/OR PAINT EXISTING METAL GRID TO MATCH NEW INTERMEDIATE GRID PIECES. CEILING WORK TO BE PERFORMED IN PHASES IN THIS AREA TO ALLOW

FOR LAB TO REMAIN OPERATIONAL DURING CONSTRUCTION.

3 THIS AREA NOT IN CONTRACT. (NIC)

4 EXISTING GRID AND CEILING TILES TO REMAIN.

5 COORDINATE TILE PENETRATION WITH EXISTING EMERGENCY SHOWER PIPING AND EXISTING EMERGENCY EXIT

SIGNAGE/LIGHTING.

N 1/4" = 1'-0"

PARTIAL THIRD FLOOR REFLECTED CEILING PLAN

P-1

ER-1

SLOPING METAL TOP

METAL CABINETS

TOP, BACK & ENDS

EXISTING UTILITY CHASE

METAL CABINETS

TOP, BACK & ENDS

2' - 6" 2' - 6" 3' - 0"

2' - 6" 2' - 6" 3' - 0"

FILLER PANEL

FILLER PANEL

" 1' - 1"

V .I .F

5'

0"

T O

F

IN

IS

H

E D

F

LO

O R

SLOPING METAL TOP

METAL CABINETS

(TOP, BACK & ENDS)

ANCHORAGE PER VA

STD. DETAIL 05 50 00-02

SEE DETAIL 6/AE601

EPOXY RESIN COUNTERTOP

AND BACKSPLASH WITH

INTEGRAL EPOXY RESIN

SINK AND SPILL

CONTAINMENT LIP.

ER-1

METAL CABINETS

(TOP, BACK & ENDS)

4"

AE601

AE6012

VENTANA

HE 600

VENTANA

HE 600

U P

S U

P S

NO WORK

NO WORK

BSL II

NO WORK

S-5

P-4

P-3

P-2

P-1

MLK

HISTOLOGY

A-348

CYTOLOGY

A-348b

SPECIMEN EXAM

A-348a

BIOSAFETY LAB

A-347

LAB OFFICE

A-348c

OFFICE

A-348e

PIPE CHASE

A-348d

16' - 2" 19' - 10"

WSF-1

ER-1

P-2

P-1

P-1

P-2

P-1

P-1

P-1

P-1

N

K E Y P L A N

NTS

F I R E / S M O K E R A T I N G L E G E N D

1 HOUR FIRE BARRIER

2 HOUR FIRE BARRIER

1 HOUR SMOKE BARRIER

G E N E R A L N O T E S

A. REFER TO SHEET GI000 FOR GENERAL NEW WORK NOTES.

B. REFER TO DEMOLITION DRAWINGS FOR WORK REQUIRED IN ADVANCE OF CONSTRUCTION AND COORDINATE

ACCORDINGLY.

C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, CONFIRM ALIGNMENT WITH

PLANS.

D. ALL WALL HUNG CASEWORK MUST BE ANCHORED IN ACCORDANCE WITH VA STANDARD 05 500-02.

E. NEW CONSTRUCTION TO ALIGN WITH ADJACENT EXISTING CONSTRUCTION WHERE APPLICABLE. PREPARE

ALIGNED SURFACES TO RECEIVE NEW FINISHES.

F. SOUND ATTENUATION BATTS (SAB) ARE TO BE PLACED IN ALL PARTITIONS WHICH ENCLOSE A ROOM UNLESS

NOTED OTHERWISE.

F

S E

E S

C H

E D

U L E

SEE SCHEDULE

9"

100 IN² MAX.,

TAMPERED GLAZING

TYPE 1

SEE SCHEDULE

S E

E S

C H

E D

U L E

2" 2"

F I N I S H L E G E N D

MARK DESCRIPTION BASIS OF DESIGN STYLE/ COLOR COMMENTS

ACT-1 2X2 ACOUSTICAL CEILING TILE

ARMSTRONG,

CLEAN ROOM FL

WHITE, SQUARE LAY-IN, 2'x2'x3/4"

GWB GYPSUM WALL BOARD TYPE X - -

P-1 PAINT GLIDDEN 9300-0110 / MANUSCRIPT FINISH: EGG SHELL

WSF-1 WELDED SHEET VINYL FLOORING ARMSTRONG MEDINTECH/ COLOR TBD

DIAMOND 10 TECHNOLOGY;

INTEGRAL BASE - 6"

ER-1 EPOXY RESIN TRESPA BLACK COUNTER TOP

-P-2 PAINT GLIDDEN 9200-0300 / CAMEL TAN

FINISH: FLAT

HOLLOW METAL FRAMES; CAULK AT PERIMETER

1 15/16" VARIES VARIES

5/8" DRYWALL

DOUBLE STUDS

BACK TO BACK

CONTINUOUS

SEALANT BOTH SIDES

STANDARD FRAME FOR

DRYWALL

JAMB ANCHORS

/4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\d u n n t\ D o c u m e n ts

\R e v it \2

\F F

E

L o u is v ill e

P a th o lo g y L a b

B tj .d u n n

.r v t

/1

/2

:3

:0

P

M

AE601

CASEWORK DETAILS, DOOR AND

FINISH SCHEDULES

08/19/2022 ET JF

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

1/2" = 1'-0"

CASEWORK ELEVATION

1/2" = 1'-0"

CASEWORK SECTION

N 1/4" = 1'-0"

PARTIAL THIRD FLOOR EQUIPMENT AND FINISH PLAN

D R A W I N G N O T E S

1 BIO-SAFETY CABINET, CLASS II - (VC) OWNER FURNISHED CONTRACTOR INSTALLED

2 ME-200 GROSSING STATION - (VC) OWNER FURNISHED CONTRACTOR INSTALLED

3 EXISTING EQUIPMENT TO REMAIN - PROTECT DURING ALL PHASES OF CONSTRUCTION.

4 TRANSITION STRIP BETWEEN DIFFERENT FLOORING FINISHES

GROUND FLOOR ROOM FINISH SCHEDULE

ROOM NAME ROOM NUMBER FLOOR FINISH BASE FINISH

WALL FINISH

Ceiling FinishN S E W

BIOSAFETY LAB A-347 WSF-1 INTEGRAL TO

WSF-1

P-1/P-2 P-1/P-2 P-1/P-2 P-1/P-2 ACT-1

HISTOLOGY A-348 - - - - - - ACT-1

SPECIMEN EXAM A-348a -- - P-1/P-2 (AREA OF

NEW WORK)

- - P-1 (AREA OF

NEW WORK)

DOOR SCHEDULE

DOOR #

PANEL FRAME DETAILS

HARDWARE# DOOR TYPE MATERIAL

DIMENSION

TYPE MATERIAL HEAD JAMBW H T

03-Third Floor

347 F HW 0' - 1 3/4" 1 HM 4/AE601 4/AE601 HW-1A

DOOR ELEVATIONS FRAME ELEVATIONS

1 3' - 6" 7' - 0"

3" = 1'-0"

HEAD/JAMB DETAIL - HM FRAME

NTS

VA STANDARD 05 50 00-02 - ANCHORAGE FOR CABINETS

MLK

SPECIMEN EXAM

A-348a

BIOSAFETY LAB

A-347

CORRIDOR

HISTOLOGY

A-348

CYTOLOGY

A-348b

HISTOLOGY

A-348

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

S1

LAB OFFICE

A-348c

OFFICE

A-348e

ELEVATOR LOBBY

A-351

F I R E H A Z A R D C L A S S I F I C A T I O N :

ORDINARY HAZARD I

ML

FIRE SPRINKLER HAZARD SCHEDULE

CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES

ORDINARY HAZARD

GROUP I

0.15 GPM/SF OVER 1500

SF

250 GPM 60 MIN QR; K = 5.6 OR K = 8.0 BASE AREA

SPRINKLER DENSITY

1 SPRINKLER PER 130 SF

A. PROVIDE COMPLETE AUTOMATIC FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH NFPA 13 AND VA FIRE

PROTECTION MANUAL. THE AREA RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE

SPRINKLERS. REWORK SPRINKLER HEADS AND PIPING AS NECESSARY TO ACCOMMODATE NEW FLOOR PLAN.

B. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND BRING TO THE ATTENTION OF THE COR IN

WRITING ANY DISCREPANCIES THAT MAY IMPACT THE PROGRESS OF WORK.

C. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN SUCH EQUIPMENT

CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE PATTERN AND COVERAGE.

D. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO PROVIDE A

COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER CONSTRUCTION.

E. PIPE SIZES SHALL BE DETERMINED BY HYDRAULIC CALCULATION.

F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO CONVEY DESIGN INTENT AND DOES NOT DICTATE

THE MEANS AND METHODS OF IMPLEMETATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.

G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE RATED WALLS, SMOKE PARTITIONS, AND

FIRE EXTINGUISHER CABINETS.

H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND SPRINKLER DESIGN.

G E N E R A L N O T E S :

GPM GALLONS PER MINUTE

MIN MINUTES

QR QUICK RESPONSE

SF SQUARE FEET

A B B R E V I A T I O N S :

N KEY PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\g jp e a \D o c u m e n ts

\F F

E

L o u is v ill e

P a th o lo g y L a b

B

M

E P g re g

.p e a rs o n ff e -s e rv

.c o m

.r v t

/1

/2

:1

:1

P

M

FX101

THIRD FLOOR FIRE SUPPRESSION

PLAN

08/19/2022 PP GP

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

1/8" = 1'-0"

FIRE SUPPRESSION THIRD FLOOR PLAN

No. Revisions: Date:

08/19/2022

MLK

SPECIMEN EXAM

A-348a

BIOSAFETY LAB

A-347

CORRIDOR

HISTOLOGY

A-348

CYTOLOGY

A-348b

HISTOLOGY

A-348

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

S1

LAB OFFICE

A-348c

OFFICE

A-348e

ELEVATOR LOBBY

A-351

(E) P-530

(E) P-530

(E) P-414

(E) P-708

ML

(E) P-528

(E) P-501

PL101

MLK

SPECIMEN EXAM

A-348a

BIOSAFETY LAB

A-347

CORRIDOR

HISTOLOGY

A-348

CYTOLOGY

A-348b

HISTOLOGY

A-348

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

S1

LAB OFFICE

A-348c

OFFICE

A-348e

ELEVATOR LOBBY

A-351

1(E) P-530

(E) P-414

(E) P-530

(E) P-708

ML

(E) P-528

(E) P-501

PL101

A. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND BRING TO THE ATTENTION OF THE COR IN

WRITING ANY DISCREPANCIES THAT MAY IMPACT THE PROGRESS OF WORK.

G E N E R A L N O T E S :

(E) EXISTING TO REMAIN

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

LA LABORATORY AIR

LV LABORATORY VACUUM

SAN SANITARY

V VENT

A B B R E V I A T I O N S :

N KEY PLAN

K

(E) 1/2" LA (E) 1/2" LV

(E) 1 1/2" SAN DN

SPECIMEN EXAM

A-348a

K

(E) 1 1/2" SAN DN

SPECIMEN EXAM

A-348a

1/2" LA

1/2" LV (E) 1/2" LA

(E) 1/2" LV

(E) 1 1/2" SAN

(E) 1 1/2" V

THIRD

FLOOR 1 1/2" SAN ROUGH-IN FOR

NEW GROSSING STATION

1 1/2" V

1 1/2" SAN

NEW SINK

1/2" DCW

1/2" DHW

(E) 1/2" DCW

(E) 1/2" DHW

NEW SINK

1/2" BALL VALVE

1/2" DCW & 1/2" DHW ROUGH-INS

FOR NEW GROSSING STATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\g jp e a \D o c u m e n ts

\F F

E

L o u is v ill e

P a th o lo g y L a b

B

M

E P g re g

.p e a rs o n ff e -s e rv

.c o m

.r v t

/1

/2

:1

:1

P

M

PL101

THIRD FLOOR PLUMBING PLANS

08/19/2022 PP GP

RENOVATE PATHOLOGY LAB 603-22-602

LOUISVILLE, KY

BID DOCUMENTS FOR

CONSTRUCTION 1

ROBLEY REX VA

MEDICAL

CENTER Approved: Owner

1/8" = 1'-0"

PLUMBING THIRD FLOOR NEW WORK PLAN

1/8" = 1'-0"

PLUMBING THIRD FLOOR DEMOLITION PLAN

D R A W I N G N O T E S :

1 PLUMBING FIXTURE TO REMAIN.

2 REMOVE LAB GAS OUTLET AND ASSOCIATED PIPING. CAP LAB AIR AND LAB VACUUM PIPING AT POINTS SHOWN ABOVE

CEILING. POINTS OF REMOVAL TO BE POINTS OF CONNECTION FOR NEW LAB GAS OUTLETS.

3 REMOVE SINK AND ASSOCIATED PIPING. CAP SANITARY PIPING ABOVE FLOOR AND VENT AND DOMESTIC HOT AND COLD WATER PIPING IN WALL. POINTS OF REMOVAL TO BE POINTS OF CONNECTION FOR NEW PIPING.

4 CONNECT DCW, DHW, SANITARY, AND VENT PIPING TO EXISTING AT POINTS SHOWN.

5 CONNECT LABORATORY VACUUM AND AIR PIPING TO EXISTING AT POINTS SHOWN.

6 NEW SINK. BOWL INTEGRAL TO COUNTERTOP. REFER TO SPECIFICATION 12 36 00 COUNTERTOPS FOR INFORMATION ON SINK BOWL, FAUCET, DRAIN, AND TRAP. INSTALL POINT OF USE THERMOSTATIC MIXING VALVE TO LIMIT HOT WATER

OUTLET TEMPERATURE TO 110 DEGREES F.

7 NEW LAB GAS OUTLET. CONNECT LAB AIR AND LAB VACUUM PIPING TO EXISTING AT POINTS OF REMOVAL. REFER TO

SPECIFICATION 12 36 00 COUNTERTOPS FOR INFORMATION ON LAB GAS OUTLETS.

8 NEW GROSSING STATION PROVIDED BY VA. PROVIDE 1/2" DCW, 1/2" DHW, AND 1 1/2" SANITARY PIPING ROUGH-IN

CONNECTIONS. INSTALL BALL VALVES FOR DOMESTIC WATER PIPING.

1/4" = 1'-0"

PLUMBING THIRD FLOOR DEMOLITION ENLARGED PLAN

1/4" = 1'-0"

PLUMBING THIRD FLOOR NEW WORK ENLARGED PLAN

NTS

SANITARY & VENT ISOMETRIC

NTS

DOMESTIC WATER ISOMETRIC

No. Revisions: Date:

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AAV AUTOMATIC AIR VENT

ACD AUTOMATIC CONTROL DAMPER, MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMS AIR FLOW MEASURING STATION

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AIR CONDITIONING ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BIW BACKWARD INCLINED WHEEL (FAN)

BSC BIOLOGICAL SAFETY CABINETS

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C CENTIGRADE (CELSIUS)

CAV CONSTANT AIR VOLUME

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION1)

CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION2)

CENT CENTRIFICAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CG CEILING GRILLE

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CLEAN OUT

CO2 CARBON DIOXODE

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

D DAMPER - AUTOMATIC

Db DRY-BULB TEMPERATURE

DB DECIBELS

DCW DOMESTIC COLD WATER

DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)

DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DIFFUSER

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DIA DIAMETER

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ECC ENGINEERING CONTROL CENTER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EWT ENTERING WATER TEMPERATURE

EX EXISTING

ABBREVIATIONS

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

FA FREE AREA

FC FLEXIBLE CONNECTION

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FM FLOW METER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT WC FEET OF WATER COLUMN

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GS GALVANIZED STEEL

H HUMIDIFER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

J INTENTIALLY LEFT BLANK

KG KILOGRAM

KG/HR KILOGRAM PER HOUR

kPa KILOPASCAL

KW KILOWATT

KWH KILOWATT HOUR

L LITER

L/h LITERS PER HOUR (or LITERS/HOUR) L/m LITERS PER MINUTE (or LITERS/MINUTE) L/s LITERS PER SECOND (or LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LH LATENT HEAT

LPR LOW…