Section 27 10 00 specifies the furnishing, installation, and connection of a comprehensive telecommunications infrastructure cabling system. The specification requires control wiring with a minimum size of No. 14 AWG, sized to prevent voltage drop under inrush conditions that could adversely affect control operation. Communication and signal wiring must conform to manufacturer recommendations for the specific systems being furnished, with multi-conductor cables color-coded and pull in multiple together within single conduits. Wire lubricating compound must be suitable for the wire insulation and conduit without hardening or becoming adhesive, and shall not be used on isolated type electrical power systems. Fireproofing tape must be self-extinguishing, arc-proof, fireproof, resist water/gases/salt water/sewage/fungus/sunlight/ultraviolet light, and withstand a 200-ampere arc for at least 30 seconds. Installation requires all wiring in raceway systems with sealing of underground cable entries using nonhardening approved compound. Wire pulling must prevent insulation cutting or abrasion, using nonmetallic ropes and either woven basket grips or pulling eyes. System voltages shall be 120 volts or lower per NEC requirements. Permanent wire markers must be installed at each termination corresponding to wiring diagrams, with embossed brass tags in manholes and handholes identifying systems served. Submittals include manufacturer literature and data for each cable type, with certification delivered two weeks prior to final inspection to the Contracting Officer Representative in four copies. The specification references applicable standards from ASTM, Federal Specifications, NFPA, and UL regarding electrical materials and installations.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Overton Brooks VAMC July 03, 2014
Construct New Parking Garage Issued for 100% Construction Documents
Shreveport, LA 71101 Project No. 667-082
27 10 00 - 1
STRUCTURED CABLING
SECTION 27 10 00
STRUCTURED CABLING
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies the furnishing, installation, and connection of the structured cabling system to provide a comprehensive telecommunications infrastructure.
1.2 RELATED WORK
A. Excavation and backfill for cables that are installed in conduit:
Section 31 20 00, EARTH MOVING.
B. Sealing around penetrations to maintain the integrity of time rated construction: Section 07 84 00, FIRESTOPPING.
C. General electrical requirements that are common to more than one section in Division 27: Section 27 05 11, REQUIREMENTS FOR
COMMUNICATIONS INSTALLATIONS.
D. Conduits for cables and wiring: Section 27 05 33, RACEWAYS AND BOXES
FOR COMMUNICATIONS SYSTEMS.
E. Requirements for personnel safety and to provide a low impedance path for possible ground fault currents: Section 27 05 26, GROUNDING AND
BONDING FOR COMMUNICATIONS SYSTEMS.
1.3 SUBMITTALS
A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND
SAMPLES, furnish the following:
1. Manufacturer's Literature and Data: Showing each cable type and rating.
2. Certificates: Two weeks prior to final inspection, deliver to the
Contracting Officer Representative (COR) four copies of the certification that the material is in accordance with the drawings and specifications and has been properly installed.
1.4 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are reference in the text by the basic designation only.
27 10 00 - 2
B. American Society of Testing Material (ASTM):
D2301-04................Standard Specification for Vinyl Chloride
Plastic Pressure Sensitive Electrical
Insulating Tape
C. Federal Specifications (Fed. Spec.):
A-A-59544-00............Cable and Wire, Electrical (Power, Fixed
Installation)
D. National Fire Protection Association (NFPA):
70-05...................National Electrical Code (NEC)
E. Underwriters Laboratories, Inc. (UL):
44-02...................Thermoset-Insulated Wires and Cables
83-03...................Thermoplastic-Insulated Wires and Cables
467-01..................Electrical Grounding and Bonding Equipment
486A-01.................Wire Connectors and Soldering Lugs for Use with
Copper Conductors
486C-02.................Splicing Wire Connectors
486D-02.................Insulated Wire Connector Systems for
Underground Use or in Damp or Wet Locations
486E-00.................Equipment Wiring Terminals for Use with
Aluminum and/or Copper Conductors
493-01..................Thermoplastic-Insulated Underground Feeder and
Branch Circuit Cable
514B-02.................Fittings for Cable and Conduit
1479-03.................Fire Tests of Through-Penetration Fire Stops
PART 2 - PRODUCTS
2.1 CONTROL WIRING
A. Unless otherwise specified in other sections of these specifications, control wiring shall be as specified for power and lighting wiring, except the minimum size shall be not less than No. 14 AWG.
B. Control wiring shall be large enough so that the voltage drop under inrush conditions does not adversely affect operation of the controls.
2.2 COMMUNICATION AND SIGNAL WIRING
A. Shall conform to the recommendations of the manufacturers of the communication and signal systems; however, not less than what is shown.
B. Wiring shown is for typical systems. Provide wiring as required for the systems being furnished.
C. Multi-conductor cables shall have the conductors color coded.
27 10 00 - 3
2.3 WIRE LUBRICATING COMPOUND
A. Suitable for the wire insulation and conduit it is used with, and shall not harden or become adhesive.
B. Shall not be used on wire for isolated type electrical power systems.
2.4 FIREPROOFING TAPE
A. The tape shall consist of a flexible, conformable fabric of organic composition coated one side with flame-retardant elastomer.
B. The tape shall be self-extinguishing and shall not support combustion.
It shall be arc-proof and fireproof.
C. The tape shall not deteriorate when subjected to water, gases, salt water, sewage, or fungus and be resistant to sunlight and ultraviolet light.
D. The finished application shall withstand a 200-ampere arc for not less than 30 seconds.
E. Securing tape: Glass cloth electrical tape not less than 0.18 mm
(7 mils) thick, and 19 mm (3/4 inch) wide.
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Install all wiring in raceway systems.
B. Seal cable and wire entering a building from underground, between the wire and conduit where the cable exits the conduit, with a non-hardening approved compound.
C. Wire Pulling:
1. Provide installation equipment that shall prevent the cutting or abrasion of insulation during pulling of cables.
2. Use ropes made of nonmetallic material for pulling feeders.
3. Attach pulling lines for feeders by means of either woven basket grips or pulling eyes attached directly to the conductors, as approved by the COR.
4. Pull in multiple cables together in a single conduit.
3.2 CONTROL, COMMUNICATION AND SIGNAL WIRING INSTALLATION
A. Unless otherwise specified in other sections, install wiring and connect to equipment/devices to perform the required functions as shown and specified.
B. Except where otherwise required, install a separate power supply circuit for each system so that malfunctions in any system shall not affect other systems.
27 10 00 - 4
C. Where separate power supply circuits are not shown, connect the systems to the nearest panelboards of suitable voltages, which are intended to supply such systems and have suitable spare circuit breakers or space for installation.
D. Install a red warning indicator on the handle of the branch circuit breaker for the power supply circuit for each system to prevent accidental de-energizing of the systems.
E. System voltages shall be 120 volts or lower where shown on the drawings or as required by the NEC.
3.3 CONTROL, COMMUNICATION AND SIGNAL SYSTEM IDENTIFICATION
A. Install a permanent wire marker on each wire at each termination.
B. Identifying numbers and letters on the wire markers shall correspond to those on the wiring diagrams used for installing the systems.
C. Wire markers shall retain their markings after cleaning.
D. In each manhole and handhole, install embossed brass tags to identify the system served and function.
- - - E N D - - -